You are on page 1of 2

PRE COMMISSIONING TEST PROTOCOL

25 MW TG SET EQUIPMENT LIGHTNING ARRESTOR LOCATION CUSTOMER SITE


LA, SC, & PT PANEL 4X25MW,TG#4

Page

Dept : I24

DOC NO FILE NO REPORT NO DATE 05-08-2011

M/s. PRAKASH INDUSTRIES LIMITED. CHAMPA,CHHATISGRAH

1. NAME PLATE DETAILS: MAKE

MODEL NO RATING FREQ COV PR CLASS YEAR OF MFRG


SERIAL NO

: ELPRO INTERNATIONAL LTD. : 94413NH012 : 12KV : 50HZ :3 : 40KA RMS : 12/2006


:

2. IR VALUE TEST LA:

MEGGER VOLTS: 5000V MEASURED VALUES IN G R-E LA WITH SURGE LA WITHOUT SURGE 100M 1.32 G Y-E 900M 4.15 G B-E 1.20 5.72G

REF

3. REMARKS: RESULTS FOUND SATISFACTORY.

Name Testing Engineer Site Engineer Mr. B. PARTHASARATHI Mr. ANKIT SINGH BAIS

Signature

Date

Remarks OK OK

Customer

Mr. AJAY SINGH THAKUR

OK