Professional Documents
Culture Documents
TCN4170
Nomenclature: Subject:
Problems Corrected:
This revision corrects the following problems, which were found in all previous revisions: The MFP serial ports stop functioning when the primary enters the "Hot Backup" state during an on-line configuration sequence. The backup module of a pair of redundant MFP's may fail to come on-line (LEDs 7 & 8 are off ) when using configurations that have large amounts of NVRAM set aside for the file system. The communications on the 40k/5k SAC/DCS link may be momentarily interrupted during the failover of a primary MFP to its backup when the MFP configuration takes more than 1/2 second to execute. Typical configurations that meet this criteria are those that contain C, Batch 90, UDF, or BASIC programs that take over 1/2 second to execute.
September 1995
Reference:
(N/A)