VENDOR PRINT
APPROVED WITH NO COMMENT APPROVED AS NOTED REJECTED REVIEWED WITH NO COMMENT REVIEWED AS NOTED This approval does not relieve the vendor / subcontractor of his responsibilities to meet all vendor / subcontractor shall not proceed until the requirements of the contract. In case of rejection, submitted documents are returned to them by Company. APPROVED BY PVC : DATE : APPROVED BY PEN : DATE : PVC PEN
Issued for Construction Issued for Approval Issued for Approval Issued for Approval DESCRIPTION PREPARATION REVIEW
N.V.HAU L.Q.DUNG N.V.HAU L.Q.DUNG N.V.HAU L.Q.DUNG N.V.HAU L.Q.DUNG PREP'N REVIEW QA CHECK APPROVAL APPROVAL
QA CHECK
0 N.V.HAU L.Q.DUNG
This DOCUMENT is the property of PetroVietnam Gas Joint Stock Corporation. Therefore, it shall not be released to any third party without permission of an authorized personnel of the PetroVietnam Gas Joint Stock Corporation.
Data sheet
Project Name
ITEM NO. MODEL TYPE USE LOCATION HEAT LOAD CRT No. of Cells CONDITOIN WATER FLOW INLET TEMP. OUTLET TEMP. WEB BULB TEMP. TYPE F A N AIR VOLUME MATERIAL 2,370,000 CT-1 NCG-500-1 Induced Draft Counter Flow Cooing tower PH Kcal/hr
500 RT 1 CELL(S) 3,950 LPM (237 /h) 43 33 28.0 (WB) AXIAL FLOW FAN 2,700 CMM / CELL AL ALLOY
POWER SOURCE 18.5kw /4P * 1 set(s) * 3Ph / 50Hz / 400V PRESS. DROP CONNECTION WATER INLET WATER OUTLET OVER FLOW DRAIN MAKE-UP DIMENSION NET WEIGHT OPER. WEIGHT QUANTITY REMARK 5.0 mAq 200 A x 1 200 A x 1 4,850 L X 3,350 W X 5,316 H 3,552 kg 7,625 kg 2 set(s)