You are on page 1of 1

motor 30 kW Date : Thursday, Mar.

03, 2011 Description Quantity Phase Efficiency Factor Power Factor Amp (rated) kW (rated) HP (rated) kVA (rated) VA (rated) Amp (act) kW (act) HP (act) kVA (act) VA (act) Volts (rated) Volts (act) Voltage Drop % Voltage Drop Current Type Conductor Qty Parallel Conductor Qty Conductor Size Include Gnd Ground Size Conductor Max(A) Ground Max(A) Neutral Qty Neutral Size Conductor Type % Conductor Capacity Conductor Mat. Insulation Type R/Z Conductor Raceway Type % Fill Limit % Fill (act) Ambient Temp. Terminal Temp. Distance NEC Table Circuit Breaker Device Category Z Device Device #1 1 3 0.88 0.9 105.14 30 40.21 33.33 33,333.33 92.7 30.06 40.29 33.4 33,397.72 208 92.7 4.8 2.31% AC 3 0 3 ga. yes 6 ga. 145 100 0 Single Conductor 125%, Copper THHN 0.045622779 Cable Tray

30 C 75 C 43 Meters 310-17 150A Light 2.19810642