FIELD TEST REPORT
Vibration Measurement Test
Project : :
Date of Test :
Unit Designation :
Unit Location :
Sty & Area Served :
Unit Make :
Unit Model :
Serial No. :
FIELD MEASUREMENT
Selected or
No. Description Specified
Field Measurement Remarks
Electrical Characteristics
1 Volt/ Phase/ Freq. (V/ ø/ Hz)
2 Motor Rated Power (kW)
3 Motor Full Load Amp (A)
4 Motor Type/ RPM
5 Starting Current (A)
6 Running Current (A)
7 Thermal Overload Range (A)
8 Thermal Overload Setting (A)
Mechanical Characteristics
9 Water Flow Rate (l/s)
10 Discharge Pressure (PSI)
11 Suction Pressure (PSI)
12 Water IN Temp. (oC)
o
13 Water OUT Temp. ( C)
REMARKS / COMMENTS
Tested By :
Shinsung (Name & Signature) (Date & Time)
Witnessed By :
Hyundai E&C Co Ltd (Name & Signature) (Date & Time)
Page 2 Vib
FIELD TEST REPORT
Pump
Project : :
Date of Test :
Unit Designation :
Unit Location :
Sty & Area Served :
Unit Make :
Unit Model :
Serial No. :
Control Panel Designation :
FIELD MEASUREMENT
Selected or
No. Description Specified
Field Measurement Remarks
Electrical Characteristics
1 Volt/ Phase/ Freq. (V/ ø/ Hz)
2 Motor Rated Power (kW)
3 Motor Full Load Amp (A)
4 Motor Type/ RPM
5 Starting Current (A)
6 Running Current (A)
7 Thermal Overload Range (A)
8 Thermal Overload Setting (A)
Mechanical Characteristics
9 Water Flow Rate (l/s)
10 Discharge Pressure (PSI)
11 Suction Pressure (PSI)
12 Water IN Temp. (oC)
o
13 Water OUT Temp. ( C)
REMARKS / COMMENTS
Page 3 PUMP
FIELD TEST REPORT
Fan Coil Unit
Project : :
Date of Test :
Unit Designation :
Unit Location :
Sty & Area Served :
Unit Make :
Unit Model :
Serial No. :
Control Panel Designation :
FIELD MEASUREMENT
Selected or
No. Description Specified
Field Measurement Remarks
Electrical Characteristics
1 Volt/ Phase/ Freq. (V/ ø/ Hz)
2 Motor Rated Power (kW)
3 Motor Full Load Amp (A)
4 Motor Type/ RPM
5 Starting Current (A)
6 Running Current (A)
7 Thermal Overload Range (A)
8 Thermal Overload Setting (A)
Mechanical Characteristics
9 Supply Air Qty (CMH)
10 Fresh Air Qty (CMH)
12 Off Coil (S/A) Temp. DB/ WB (oC)
13 On Coil (R/A) Temp. DB/ WB (oC)
14 Outside Air Temp. DB/ WB (oC)
15 Water IN/ OUT Temp. (oC)
16 Water Flow Rate (l/s)
17 Static Pressure (kPa)
18 Coil Pressure Drop (kPa)
Miscellaneous
19 Sound Pressure Level (dBA) -
ACCEPTED RE-INSPECTION REQUIRED
Page 4 FCU
FIELD TEST REPORT
Mechanical Ventilation Fan
Project : :
Date of Test :
Unit Designation :
Unit Location :
Sty & Area Served :
Unit Make :
Unit Model :
Serial No. :
Control Panel Designation :
FIELD MEASUREMENT
Selected or
No. Description Specified
Field Measurement Remarks
Electrical Characteristics
1 Volt/ Phase/ Freq. (V/ ø/ Hz)
2 Motor Rated Power (kW)
3 Motor Full Load Amp (A)
4 Fan Type/ RPM
5 Starting Current (A)
6 Running Current (A)
7 Thermal Overload Range (A)
8 Thermal Overload Setting (A)
9 VSD (Hz)
Mechanical Characteristics
1 Static Pressure (kPa)
2 Air Qty (CMH)
REMARKS / COMMENTS
Tested By :
Shinsung (Name & Signature) (Date & Time)
Witnessed By :
Hyundai E&C Co Ltd (Name & Signature) (Date & Time)
Page 5 FAN
FIELD TEST REPORT
DX Split Unit / VRV Unit
Project : :
Date of Test :
FAN COIL UNIT
Unit Designation :
Unit Location :
Sty & Area Served :
Unit Make :
Unit Model :
Serial No. :
CONDENSING UNIT
Unit Designation :
Unit Location :
Unit Make :
Unit Model :
Serial No. :
Control Panel Designation :
FIELD MEASUREMENT
Selected or
No. Description Specified
Field Measurement Remarks
Electrical Characteristics
1 Volt/ Phase/ Freq. (V/ ø/ Hz)
2 Compressor Rated Power (kW)
3 Compressor Full Load Amp (A)
5 Starting Current (A)
6 Running Current (A)
Mechanical Characteristics
7 Supply Air Qty (CMH) H/L
8 Outside Air Qty (CMH)
9 FCU Off Coil (S/A) Temp. DB/ WB (oC)
10 FCU On Coil (R/A) Temp. DB/ WB (oC)
11 Outside Air Temp. DB/ WB (oC)
12 Static pressure (Pa)
13 Suction Pressure (PSI)
14 Discharge Pressure (PSI)
ACCEPTED RE-INSPECTION REQUIRED
ACCEPTED WITH COMMENTS NOT ACCEPTED
REMARKS / COMMENTS
Tested By :
Shinsung (Name & Signature) (Date & Time)
Witnessed By :
Hyundai E&C Co Ltd (Name & Signature) (Date & Time)
Miscellaneous
13 Motorized Valve Operation Check -
Tested By :
Shinsung (Name & Signature) (Date & Time)
Witnessed By :
Hyundai E&C Co Ltd (Name & Signature) (Date & Time)
Page 7 HX
Air Flow Measurement Report
Project : :
Date of Test :
Equipment Designation :
Unit Location :
Sty & Area Served :
FIELD MEASUREMENT
Grille Neck Size (mm) Air Velocity (m/s) / Air volume (CMH) Measured Design
Grille
Grille Type Area (m²) Air Qty
No. Air Qty Air Velocity
H (mm) W (mm) 1 2 3 4 5 6 7 8 AVE (cmh)
(cmh (m/s)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Total 0
Tested By :
ACCEPTED RE-INSPECTION Shinsung (Name & Signature) (Date & Time)
REQUIRED
Witnessed By :
Hyundai E&C Co Ltd (Name & Signature) (Date & Time)
ACCEPTED WITH COMMENTS NOT ACCEPTED
Verified & Accepted By :
RTO / PowerQ (Name & Signature) (Date & Time)
H=
Project :
70
:
0
Date of Test :
Equipment Designation :
Unit Location :
Sty & Area Served :
FIELD MEASUREMENT
Tested By :
ACCEPTED RE-INSPECTION Shinsung (Name & Signature) (Date & Time)
REQUIRED
Witnessed By :
Hyundai E&C Co Ltd (Name & Signature) (Date & Time)
ACCEPTED WITH COMMENTS NOT ACCEPTED
Verified & Accepted By :
RTO / PowerQ (Name & Signature) (Date & Time)
Page 9 Duct Tr
FIELD TEST REPORT
Air Handling Unit / Pre-Cool Air Handling Unit
Project : :
Date of Test :
Unit Designation :
Unit Location :
Sty & Area Served :
Unit Make :
Unit Model :
Serial No. :
Control Panel Designation :
Belt size/ qty :
FIELD MEASUREMENT
Field
No. Description Selected or Specified
Measurement
Remarks
Electrical Characteristics
1 Volt/ Phase/ Freq. (V/ ø/ Hz)
2 Motor Rated Power (kW)
3 Motor Full Load Amp (A)
4 Motor Type/ RPM
5 Starting Current (A)
6 Running Current (A)
7 Thermal Overload Range (A)
8 Thermal Overload Setting (A)
9 VSD (HZ)
Mechanical Characteristics
9 Supply Air Qty (CMH)
10 Outside Air Qty (CMH)
11 Outside Air Temp. DB/ WB (oC)
12 Off Coil (S/A) Temp. DB/ WB (oC)
13 On Coil (R/A) Temp. DB/ WB (oC)
14 Outside Air Temp. DB/ WB (oC)
15 Water IN/ OUT Temp. (oC)
16 Water Flow Rate (l/s)
17 Static Pressure (kPa)
18 Coil Pressure Drop (kPa)
Miscellaneous
19 Smoke Detector Activation Test -
20 Sound Pressure Level (dBA)
ACCEPTED RE-INSPECTION REQUIRED
Tested By :
Shinsung (Name & Signature) (Date & Time)
Witnessed By :
Hyundai E&C Co Ltd (Name & Signature) (Date & Time)
Page 10 AHU,PAU
Project:
STAIRCASE PRESSURIZATION TEST REPORT
Staircase No. : Fan Designation :
Air Velocity Across Door (m/s) (Criteria : › 1.0 m/s) When All Doors Are Closed
Test
FLOOR Force Required to Open Door (N) Pressure Differentiate Across REMARKS
No. 1 2 3 4 5 6 Average
(Criteria : ‹ 110 N) Door (Pa) (Criteria : › 50 Pa)
Tested By :
ACCEPTED RE-INSPECTION Shinsung (Name & Signature) (Date & Time)
REQUIRED Witnessed By :
ACCEPTED NOT ACCEPTED Hyundai E&C Co Ltd (Name & Signature) (Date & Time)
Page 11 Stair P
Room Temperature Report
Project : :
Date of Test :
Floor :
Unit No. :
Unit Location :
Equipment Designation
Drawing No. :
Time : AM/PM
Design Temperature : WB / DB (Deg C)
: RH (%)
FIELD MEASUREMENT
Measured Temperature
(Deg C) Relativity Humidity
Points No. Remarks
(%)
WB DB
Point 1
Point 2
Point 3
Point 4
Point 5
Point 6
Point 7
Point 8
Point 9
Point 10
REMARKS / COMMENTS
Tested By :
Shinsung (Name & Signature) (Date & Time)
Witnessed By :
Hyundai E&C Co Ltd (Name & Signature) (Date & Time)
Page 12 Rm Temp
Water Flow Balancing Test Report
Project :
Date of Test :
Floor :
Unit No. :
Unit Location :
Drawing No. :
FIELD MEASUREMENT
Equipment Valve Model Setting Diffential Flow (l/s) Design Flow
Valve Index Designation Turns Pressure Flow (l/s) Deviation
(kPa) (%)
REMARKS / COMMENTS
Tested By :
Shinsung (Name & Signature) (Date & Time)
Witnessed By :
Hyundai E&C Co Ltd (Name & Signature) (Date & Time)
Date of Test :
Floor :
Unit No. :
Unit Location :
Equipment Designation
Drawing No. :
Time : AM/PM
FIELD MEASUREMENT
REMARKS / COMMENTS
Tested By :
Shinsung (Name & Signature) (Date & Time)
Witnessed By :
Hyundai E&C Co Ltd (Name & Signature) (Date & Time)
Page 14 NC Pg 1
FIELD TEST REPORT
Noise Criteria Measurement
90
85
NC65
80
NC60
75
NC65 NC55
70 NC50
NC60
65 NC45
NC55 NC40
60
NC35
NC50
55 NC30
50 NC45 NC25
45 NC40 NC20
NC15
40 NC35
Measured Point : P
35 NC30 #REF!
30 NC25
25
NC20
20
15 NC15
10
63 125 250 500 1000 2000 4000 8000
Frequency (Hz)
-12
Sound Power Level, dB re10 W Octave Band Centre Frequency
Record (Hz)
Equipment /Area :
no.
63 125 250 500 1000 2000 4000 8000
Measured Point : P 1
Project :
STATUS INDICATION AT
ACTUAL FAN STATUS
ITEM FAN DESIGNATION LOCATION LMCP Supervisory Panel REMARKS
RUN STOP RUN STOP RUN STOP
Tested By :
ACCEPTED RE-INSPECTION Shinsung (Name & (Date & Time)
REQUIRED
Witnessed By :
ACCEPTED NOT ACCEPTED Hyundai E&C Co Ltd (Name & (Date & Time)
WITH COMMENTS Verified & Accepted By :
RTO / PowerQ (Name & (Date & Time)
Main Incoming
1 Main incoming circuit breaker CB0 function properly
AHU operation
1 Earth leakage protection relay
2 Ammeter if applicable
Manual mode
1 Put the selector switch to ‘Manual’ mode
2 Press start pushbutton to start the motor, the run light will lights on.
Press the stop pushbutton, motor will be stop, the stop light will
lights on.
3 Simulate the overload trip, the trip light will lights on, the AHU will
cut off.
Auto mode
1 Put the selector switch to ‘Auto’ mode
Fire alarm
1 Simulate the fire alarm occur, the AHU will cut off.
Panel others
1 Put back the panel drawing inside the drawing pocket.
Tested By :
Shinsung (Name & Signature) (Date & Time)
Witnessed By :
Hyundai E&C Co Ltd (Name & Signature) (Date & Time)
Verified & Accepted By :
RTO / PowerQ (Name & Signature) (Date & Time)