Preface, Contents

Product Overview 1
Structure and Components of
Instructions and Statements 2
SIMATIC S7 3
Adressing
Accumulator Operations and
Address Register Instructions 4
Statement List (STL)
for S7-300 and S7-400 Bit Logic Instructions 5
Programming
Timer Instructions 6
Reference manual Counter Instructions 7

Load and Transfer Instructions 8


This reference manual is part of the documentation
package with the order number
Integer Math Instructions 9
6ES7810-4CA04-8BR0
Floating-Point Math Instructions 10

Comparison Instructions 11

Conversion Instructions 12

Word Logic Instructions 13

Shift and Rotate Instructions 14

Data Block Instructions 15

Jump Instructions 16

Program Control Instructions 17

10/98 Appendix
C79000-G7076-C565
Glossary, Index
Release 01
Safety Guidelines This manual contains notices which you should observe to ensure your own personal safety, as well as to
protect the product and connected equipment. These notices are highlighted in the manual by a warning
triangle and are marked as follows according to the level of danger:

Danger
! indicates that death, severe personal injury or substantial property damage will result if proper precautions are
not taken.

Warning
! indicates that death, severe personal injury or substantial property damage can result if proper precautions are
not taken.

Caution
! indicates that minor personal injury or property damage can result if proper precautions are not taken.

Note
draws your attention to particularly important information on the product, handling the product, or to a particular
part of the documentation.

Correct Usage Note the following:

Warning
! This device and its components may only be used for the applications described in the catalog or the technical
description, and only in connection with devices or components from other manufacturers which have been
approved or recommended by Siemens.
This product can only function correctly and safely if it is transported, stored, set up, and installed correctly, and
operated and maintained as recommended.

Trademarks SIMATIC, SIMATIC HMI and SIMATIC NET are registered trademarks of SIEMENS AG.
Third parties using for their own purposes any other names in this document which refer to trademarks might
infringe upon the rights of the trademark owners.

Copyright  Siemens AG 1998 All rights reserved Disclaimer of Liability


The reproduction, transmission or use of this document or its contents is We have checked the contents of this manual for agreement with the
not permitted without express written authority. Offenders will be liable for hardware and software described. Since deviations cannot be precluded
damages. All rights, including rights created by patent grant or registration entirely, we cannot guarantee full agreement. However, the data in this
of a utility model or design, are reserved. manual are reviewed regularly and any necessary corrections included in
subsequent editions. Suggestions for improvement are welcomed.
Siemens AG
Bereich Automatisierungs- und Antriebstechnik
Geschaeftsgebiet Industrie-Automatisierungssysteme
 Siemens AG 1998
Postfach 4848, D-90327 Nuernberg
Technical data subject to change.
Siemens Aktiengesellschaft C79000-G7076-C565

Statement List (STL) for S7-300/S7-400


Preface

Purpose This manual is your guide to creating user programs in the Statement List
programming language STL.
The manual also includes a reference section that describes the syntax and
functions of the language elements of STL.

Audience This manual is intended for S7 programmers, operators, and


maintenance/service personnel. A working knowledge of automation
procedures is essential.

Scope of the This manual is valid for release 5.0 of the STEP 7 programming software
Manual package.

Compliance with STL corresponds to the “Instruction List” language defined in the
Standards International Electrotechnical Commission’s standard IEC 1131-3, although
there are substantial differences with regard to the operations. For further
details, refer to the table of standards in the STEP 7 file NORM_TBL.WRI.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 iii
Preface

Requirements To use this Statement List manual effectively, you should already be familiar
with the theory behind S7 programs which is documented in the online help
for STEP 7. The language packages also use the STEP 7 standard software,
so you should be familiar with handling this software and have read the
accompanying documentation.

Documentation Purpose Order Number


STEP 7 Basic Information with Basic information for technical per- 6ES7810-4CA04-8BA0
 Working with STEP 7 V5.0, Getting Started sonnel describing the methods of im-
Manual plementing control tasks with
STEP 7 and the S7-300/400 pro-
 Programming with STEP 7 V5.0
grammable controllers.
 Configuring Hardware and Communication
Connections, STEP 7 V5.0
 From S5 to S7, Converter Manual
STEP 7 Reference with Provides reference information and 6ES7810-4CA04-8BR0
 Ladder Logic (LAD)/Function Block Dia- describes the programming langua-
gram (FBD)/Statement List (STL) for ges LAD, FBD and STL and stan-
S7-300/400 manuals dard and system functions extending
the scope of the STEP 7 basic infor-
 Standard and System Functions for mation.
S7-300/400

Online Helps Purpose Order Number


Help on STEP 7 Basic information on programming Part of the STEP 7 Stan-
and configuraing hardware with dard software.
STEP 7 in the form of an online
help.
Reference helps on STL/LAD/FBD Context-sensitive reference informa- Part of the STEP 7 Stan-
Reference help on SFBs/SFCs tion. dard software.
Reference help on Organization Blocks

Accessing the You can display the online help in the following ways:
Online Help
 Context-sensitive help about the selected object with the menu command
Help > Context-Sensitive Help, with the F1 function key, or by clicking
the question mark symbol in the toolbar.
 Help on STEP 7 via the menu command Help > Contents.

References References to other documentation are indicated by reference numbers in


slashes /.../. Using these numbers, you can check the exact title in the
References section at the end of the manual.

Statement List (STL) for S7-300/S7-400


iv C79000-G7076-C565-01
Preface

SIMATIC Customer The SIMATIC Customer Support team offers you substantial additional
Support Online information about SIMATIC products via its online services:
Services
 General current information can be obtained:
– on the Internet under
http://www.ad.siemens.de/simatic/html_00/simatic
– via the Fax-Polling number 08765-93 02 77 95 00
 Current product information leaflets and downloads which you may find
useful are available:
– on the Internet under http://www.ad.siemens.de/support/html_00/
– via the Bulletin Board System (BBS) in Nuremberg (SIMATIC
Customer Support Mailbox) under the number +49 (911) 895-7100.
To dial the mailbox, use a modem with up to V.34 (28.8 Kbps) with
the following parameter settings: 8, N, 1, ANSI; or dial via ISDN
(x.75, 64 Kbps).

Additional If you have other questions, please contact the Siemens representative in your
Assistance area. The addresses are listed, for example, in catalogs and in Compuserve
(go autforum).
Our SIMATIC Basic Hotline is also ready to help:
 in Nuremberg, Germany
– Monday to Friday 07:00 to 17:00 (local time): telephone:
+49 (911) 895–7000
– or E-mail: simatic.support@nbgm.siemens.de
 in Johnson City (TN), USA
– Monday to Friday 08:00 to 17:00 (local time): telephone:
+1 423 461–2522
– or E-mail: simatic.hotline@sea.siemens.com
 in Singapore
– Monday to Friday 08:30 to 17:30 (local time): telephone:
+65 740–7000
– or E-mail: simatic@singet.com.sg
The SIMATIC Premium Hotline is available round the clock worldwide
with the SIMATIC card (telephone: +49 (911) 895-7777).

Courses for Siemens offers a number of training courses to introduce you to the SIMATIC
SIMATIC Products S7 automation system. Please contact your regional training center or the
central training center in Nuremberg, Germany for details:
Telephone: +49 (911) 895-3154.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 v
Preface

Questionnaires on To help us to provide the best possible documentation for you and future
the Manual and STEP 7 users, we need your support. If you have any comments or
Online Help suggestions relating to this manual or the online help, please complete the
questionnaire at the end of the manual and send it to the address shown.
Please include your own personal rating of the documentation.

Statement List (STL) for S7-300/S7-400


vi C79000-G7076-C565-01
Contents

Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii
1 Product Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
2 Structure and Components of Instructions and Statements . . . . . . . . . . . . . . . . 2-1
2.1 Structure of a Statement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2.2 Meaning of the CPU Register in Statements . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
3 Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
3.1 Immediate Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.2 Direct Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3.3 Memory Indirect Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
3.4 Address Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
3.5 Area-Internal Register Indirect Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
3.6 Area-Crossing Register Indirect Addressing . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
4 Accumulator Operations and Address Register Instructions . . . . . . . . . . . . . . . . 4-1
4.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
4.2 ENT and LEAVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
4.3 Incrementing and Decrementing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
4.4 +AR1 und +AR2: Adding a Constant to Address Register 1
or Address Register 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
5 Bit Logic Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
5.1 Boolean Bit Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
5.2 Bit Logic Instructions and Relay Coil Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6
5.3 Evaluating Conditions Using And, Or, and Exclusive Or . . . . . . . . . . . . . . . 5-10
5.4 Nesting Expressions and And before Or . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-14
5.5 Instructions for Transitional Contacts: FP, FN . . . . . . . . . . . . . . . . . . . . . . . . 5-16
5.6 Output of Boolean Logic String . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-20
5.7 Set and Reset Instructions: S and R . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21
5.8 Assign Instruction (=) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-24
5.9 Negating, Setting, Clearing, and Saving the RLO . . . . . . . . . . . . . . . . . . . . . 5-26

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 vii
Contents

6 Timer Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1


6.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
6.2 Location of a Timer in Memory and Components of a Timer . . . . . . . . . . . 6-3
6.3 Loading, Starting, Resetting, and Enabling a Timer . . . . . . . . . . . . . . . . . . . 6-5
6.4 Timer Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
6.5 Address Locations and Ranges for Timer Instructions . . . . . . . . . . . . . . . . . 6-17
6.6 Choosing the Right Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-18
7 Counter Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
7.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
7.2 Setting, Resetting, and Enabling a Counter . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
7.3 Couting Up and Counting Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-5
7.4 Loading a Count Value as Integer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-6
7.5 Loading a Count Value in Binary Coded Decimal Format . . . . . . . . . . . . . . 7-7
7.6 Counter Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-8
7.7 Address Locations and Ranges for Counter Instructions . . . . . . . . . . . . . . . 7-10
8 Load and Transfer Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
8.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
8.2 Loading and Transferring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-3
8.3 Reading the Status Word or Transferring to the Status Word . . . . . . . . . . . 8-6
8.4 Loading Times and Counts as Integers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-7
8.5 Loading Times and Counts in Binary Coded Decimal Format . . . . . . . . . . 8-9
8.6 Loading and Transferring between Address Registers . . . . . . . . . . . . . . . . 8-11
8.7 Loading Data Block Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-12
9 Integer Math Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
9.1 Four-Function Math . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
9.2 Adding an Integer to Accumulator 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-6
10 Floating-Point Math Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-1
10.1 Four-Function Math . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-2
10.2 Forming the Absolute Value of a Floating-Point Number . . . . . . . . . . . . . . . 10-6
10.3 Extended Math Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-7
10.4 Forming the Square / Square Root of a Floating-Point Number . . . . . . . . . 10-9
10.5 Forming the Natural Logarithm of a Floating-Point Number . . . . . . . . . . . . 10-11
10.6 Forming the Exponential Value of a Floating-Point Number . . . . . . . . . . . . 10-12
10.7 Forming Trigonometric Functions on Angles Acting as
Floating-Point Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-13

Statement List (STL) for S7-300/S7-400


viii C79000-G7076-C565-01
Contents

11 Comparison Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-1


11.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-2
11.2 Comparing Two Integers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-3
11.3 Comparing Two Floating-Point Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-5
12 Conversion Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-1
12.1 Converting Binary Coded Decimal Numbers and Integers . . . . . . . . . . . . . 12-2
12.2 Converting 32-Bit Floating-Point Numbers to 32-Bit Integers . . . . . . . . . . . 12-8
12.3 Reversing the Order of Bytes within Accumulator 1 . . . . . . . . . . . . . . . . . . . 12-13
12.4 Forming Complements and Negating Floating-Point Numbers . . . . . . . . . 12-14
13 Word Logic Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1
13.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-2
13.2 16-Bit Word Logic Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-3
13.3 32-Bit Word Logic Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-6
14 Shift and Rotate Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-1
14.1 Shift Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-2
14.2 Rotate Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-6
15 Data Block Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-1
15.1 Opening Data Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-2
15.2 Swapping Data Block Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-2
15.3 Loading Data Block Lengths and Numbers . . . . . . . . . . . . . . . . . . . . . . . . . . 15-3
16 Jump Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-1
16.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-2
16.2 Unconditional Jump Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-3
16.3 Conditional Jump Instructions Founded on Result of Logic Operation . . . 16-4
16.4 Conditional Jump Instructions Founded on BR, OV, or OS Bits
of the Status Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-5
16.5 Conditional Jump Instructions Based on Result in the CC 1 and
CC 0 Bits of the Status Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-6
16.6 Loop Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-8
17 Program Control Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-1
17.1 Parameter Assignment when Calling FCs and FBs . . . . . . . . . . . . . . . . . . . 17-2
17.2 Calling Functions and Function Blocks with CALL . . . . . . . . . . . . . . . . . . . . 17-3
17.3 Calling Functions and Function Blocks with CC and UC . . . . . . . . . . . . . . . 17-7
17.4 Working with Master Control Relay Functions . . . . . . . . . . . . . . . . . . . . . . . . 17-10
17.5 Master Control Relay Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-11
17.6 Ending Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-16

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 ix
Contents

A Alphabetical Listing of Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1


A.1 Listing with (German) SIMATIC and International Mnemonics . . . . . . . . . . A-2
A.2 Alphabetical Listing with International Names . . . . . . . . . . . . . . . . . . . . . . . . A-12
B Programming Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
B.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
B.2 Bit Logic Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3
B.3 Timer Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-7
B.4 Counter and Comparison Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-10
B.5 Integer Math Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-12
B.6 Word Logic Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-14
C Source Files - Examples and Reserved Keywords . . . . . . . . . . . . . . . . . . . . . . . . . C-1
D References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Glossary-1
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Index-1

Statement List (STL) for S7-300/S7-400


x C79000-G7076-C565-01
Product Overview 1
What is Statement Statement List (STL) is a textual programming language that can be used to
List? create the code section of logic blocks. Its syntax for statements is similar to
assembler language and consists of instructions followed by addresses on
which the instructions act.

The Programming Of all the programming languages with which you can program S7
Language STL controllers, STL is the closest to the machine code MC7 of the S7 CPU. This
means that by using it to program S7 controllers, you can optimize the run
time and the use of memory.
The programming language STL has all the necessary elements for creating a
complete user program. It contains a comprehensive range of instructions. A
total of over 130 different basic instructions and a wide range of addresses
are available. Functions and function blocks allow you to structure your STL
program clearly.

The Programming The STL programming package is an integral part of the STEP 7 Standard
Package Software. This means that following the installation of your STEP 7
software, all the editor functions, compiler functions and test/debug functions
for STL are available to you.
Using STL, you can create your own user program as follows:
 With the Incremental Editor. The input of the local data structure is made
easier with the help of table editors.
 With a source file in the Text Editor. Text input is made easier with the
help of block templates.
There are three programming languages in the standard software, STL, FBD,
and LAD. You can switch from one language to the other almost without
restriction and choose the most suitable language for the particular block you
are programming.
If you write programs in LAD or FBD, you can always switch over to the
STL representation. If you convert LAD programs into FBD programs and
vice versa, program elements that cannot be represented in the destination
language are displayed in STL.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 1-1
Statement List (STL) for S7-300/S7-400
1-2 C79000-G7076-C565-01
Structure and Components of
Instructions and Statements 2
Chapter Overview Section Description Page
2.1 Structure of a Statement 2-2
2.2 Meaning of the CPU Register in Statements 2-10

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 2-1
Structure and Components of Instructions and Statements

2.1 Structure of a Statement

Components of a With reference to structure, an instruction statement belongs to either one of


Statement the following two basic groups (see also Figure 2-1):
 A statement made up of an instruction alone (for example, NOT, see
Section 5.9)
 A statement made up of an instruction and an address (see Tables 2-1
through 2-5, and Table 2-9)

Statement group 1 Statement group 2

Instruction alone Instruction + address

Figure 2-1 Basic Groups of Statements

Address of an The address of an instruction indicates a constant or the location where the
Instruction instruction finds a value (data object) on which to perform an operation. The
address can have a symbolic name or an absolute designation. The address
can point to any of the following items (see also Tables 2-1 through 2-9):
 A constant, the value of a timer or counter, or an ASCII character string
to be loaded into accumulator 1 (for example, L +27, see Table 2-1)
 A bit in the status word of the programmable logic controller (for
example, A UO, see Table 2-2)
 A symbolic name (for example, A Motor.On, see Table 2-3)
 A data block and a location within the data block area (for example,
L DB4.DBD10, see Table 2-4)
 A function (FC), function block (FB), integrated system function (SFC),
or integrated system function block (SFB) and the number of the function
or block (see Table 2-5)
 An address identifier and a location within the memory area that is
indicated by the address identifier (for example, A I 1.0, or
A I [AR1,P#4.3], see Table 2-9)
Tables 2-1 through 2-9 show various statements that each include an
instruction with an address.

Statement List (STL) for S7-300/S7-400


2-2 C79000-G7076-C565-01
Structure and Components of Instructions and Statements

Constant Values Table 2-1 shows how you can use a constant value as the address of an
instruction.

Table 2-1 Addresses That Point to a Value or Character String

Statement
D
Description
i i
Instruction Address
Constant
L +27 Load the integer 27 into accumulator 1.
L ’END’ Load the ASCII characters ’END’ into accumulator 1.

Locations in the The address of a statement list instruction can refer to one or more bits in the
Status Word status word of the programmable logic controller (see Section 2.2). The
instruction checks and reacts to the signal state of a single bit in the status
word (for example, A BR) or interprets the bit combination in two of the bits
(for example, A UO).

Table 2-2 Addresses That Refer to a Bit in the Status Word

Statement
Instruction Address Description
Bit in the Status
Word
A BR The 1 or 0 in bit 8 of the status word is included in a
Boolean logic combination.
A UO The instruction interprets the bit combination that it
finds in bits CC 1 and CC 0 of the status word to
see if a certain condition has been fulfilled. For
example, a combination of 1 and 1 indicates
“unordered,” that is, one of the values in a
floating-point operation was not a valid
floating-point number.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 2-3
Structure and Components of Instructions and Statements

Symbolic Name Table 2-3 shows how you use a symbolic name as the address of an
instruction. You can only use symbolic names in STL statements once you
have declared them: shared symbolic names should be entered in the symbol
table and local names in a block.

Table 2-3 Addresses That Point to a Symbolic Name

Statement
D
Description
i i
Instruction Address
Symbol
A Motor.On Perform an And logic operation on the bit whose
symbolic name is “Motor.On”. In this case, the
symbolic name “Motor.On” can only represent a bit
in the data block (D) area of memory or element of a
structure “MOTOR” .
L SPEED Load the byte, word, or double word value, whose
symbolic name is SPEED, into accumulator 1 .

A Data Block and a Table 2-4 shows how you use a data block and a location within the data
Location within block as the address of an instruction.
the Data Block
Table 2-4 Addresses That Point to a Data Block and a Location within the Data
Block

Statement
Instruction Address
Description
Descr pt on
Data Block and
Location
L DB4.DBD10 Load data double word DBD10 from data block
DB4 into accumulator 1.
A DB10.DBX4.3 Perform an And logic operation on data bit DBX4.3
from data block DB10.

Statement List (STL) for S7-300/S7-400


2-4 C79000-G7076-C565-01
Structure and Components of Instructions and Statements

FCs, FBs, SFCs, Table 2-5 shows how you use a function (FC), function block (FB),
and SFBs integrated system function (SFC), or integrated system function block (SFB)
and the number of the function or block as the address of an instruction.

Table 2-5 Addresses That Point to a Function, Function Block, System Function,
or System Function Block

Statement
Instruction Address
D
Description
i ti
FC, FB,
SFC, SFB and
Number
CALL FB10, DB10 Call function block FB10 with instance data block
DB10.
CALL SFC43 Call integrated system function SFC43.

Address Identifiers Some addresses include an address identifier and a location within the
memory area indicated by the address identifier. An address identifier can be
one of the following three basic types (see Tables 2-6 through 2-8):
 An address identifier that indicates the memory area and the size of a data
object in that area as follows (see Table 2-6):
– The memory area in which an instruction finds a value (data object)
on which to perform an operation (for example, “I” for the process
image input area of memory)
– The size of the value (data object) on which the instruction is to
perform its operation (for example, B for “byte,” W for “word,” and D
for “double word”)
 An address identifier that indicates a memory area but no size of a data
object in that area (for example, an identifier that indicates the area T for
“timer,” C for “counter,” or DB or DI for “data block,” plus the number
of that timer, counter, or data block, see Table 2-7)
 An address identifier that indicates the size of a data object but no
memory area. The memory area is encoded in the memory location that
follows the address identifier (see Table 2-8).

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 2-5
Structure and Components of Instructions and Statements

Table 2-6 Address Identifier That Indicates Memory Area and Size of Data Object

Type of Addressing Instruction Address Identifier Memory Location


Memory Area Size of Data Object (If no
size is indicated, a bit is
implied.)
Direct A I 0.0
Direct L I B 10
Memory indirect A I [MD2]
Memory indirect L I B [DID4]
Area-internal register A I [AR1, P#4.3]
indirect
Area-internal register T L D [AR2, P#53.0]
indirect

Table 2-7 Address Identifier That Indicates Memory Area, but No Size of Data Object

Type of Addressing Instruction Address Identifier: Memory Number or


Area Location of
Number
Direct OPN DB 5
Direct SP T 7
Memory indirect OPN DB [LW2]
Memory Indirect S C [MW44]

Table 2-8 Address Identifier That Indicates Size of Data Object, but No Memory Area

Type of Addressing Instruction Size of Data Object Memory Location


(If no size is indicated, a bit is
implied.)
Area-crossing register A [AR1, P#4.3]
indirect
Area-crossing register L B [AR1, P#100.0]
indirect

Table 2-9 Addresses That Include Address Identifier and Location

Statement
Instruction Address
D
Description
i ti
Address Location in
Identifier Memory Area
or Register
A I 1.0 Perform an And logic operation on input bit 1.0.
A I [MD2] Perform an And logic operation on the input bit whose exact
location is in memory double word MD2.
L C 1 Load the count value of counter 1 into accumulator 1.

Statement List (STL) for S7-300/S7-400


2-6 C79000-G7076-C565-01
Structure and Components of Instructions and Statements

Working with Word If you are working with an instruction whose address identifier indicates a
or Double Word as memory area of your programmable logic controller and a data object that is
Data Object either a word or a double word in size (see Table 2-6), you need to be aware
of the fact that the memory location is always referenced as a byte location.
This byte location is the number of the most significant byte within the word
or double word. For example, the address in the statement shown in
Figure 2-2 references four successive bytes in memory area M, starting at
byte 10 (MB10) and going through byte 13 (MB13).

Statement: L MD10

Address identifier Byte location

Figure 2-2 Example of Memory Location Referenced as Byte Location

Figure 2-3 illustrates data objects of the following sizes:


 Double word: memory double word MD10
 Word: memory words MW10, MW11, and MW13
 Byte: memory bytes MB10, MB11, MB12, and MB13
When you use absolute addresses that are a word or a double word in width,
make sure that you do not create any byte assignments that overlap.

15 015 0
MW10 MW12

MB10 MB11 MB12 MB13

MSB LSB
MW11
31 1615 0
MD10

Figure 2-3 Referencing a Memory Location as a Byte Location

Memory Areas and Most addresses in STL refer to memory areas. The following table lists the
their Functions memory areas and describes the function of each area.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 2-7
Structure and Components of Instructions and Statements

Table 2-10 Memory Areas and Their Functions

Access to Area
Name of Area Function
Funct on of Area
via Units of the Following Size: Abbrev.
Process image At the beginning of the scan cycle, the operating Input bit I
input system reads the inputs from the process and Input byte IB
records the values in this area. The program can Input word IW
use these values in its cyclic processing. Input double word ID
Process image During the scan cycle, the program calculates Output bit Q
output output values and places them in this area. At the Output byte QB
end of the scan cycle, the operating system reads Output word QW
the calculated output values from this area and Output double word QD
sends them to the process outputs.
Bit memory This area provides storage for interim results Memory bit M
calculated in the program. Memory byte MB
Memory word MW
Memory double word MD
I/O: This area enables your program to have direct Peripheral input byte PIB
external input access to input and output modules (that is, Peripheral input word PIW
peripheral inputs and outputs). Peripheral input double word PID
I/O: Peripheral output byte PQB
external output Peripheral output word PQW
Peripheral output double word PQD
Timer Timers are function elements of STL Timer (T) T
programming. This area provides storage for
timer cells. In this area, clock timing accesses
time cells to update them by decrementing the
time value and timer instructions access time
cells.
Counter Counters are function elements of STL Counter (C) C
programming. This area provides storage for
counters. Counter instructions access them here.
Data block This area contains data that can be accessed from Data block opened with the statement
any block. If you need to have two different data “OPN DB”:
blocks open at the same time, you can open one
with the statement “OPN DB” and one with the Data bit DBX
statement “OPN DI”. In this way, the CPU can Data byte DBB
distinguish which of the two data blocks your Data word DBW
program wants to access while both data blocks Data double word DBD
are open.
While you can use the “OPN DI” statement to Data block opened with the statement
open any data block, the principal use of this “OPN DI”:
statement is to open instance data blocks that are
associated with function blocks (FBs) and system Data bit DIX
function blocks (SFBs). For more information on Data byte DIB
FBs, SFBs, and instance data blocks, see the Data word DIW
STEP 7 Online Help. Data double word DID

Local data This area contains temporary data that is used Temporary local data bit L
within a logic block (OB, FB, or FC). These data Temporary local data byte LB
are also called dynamic local data. They serve as Temporary local data word LW
an intermediate buffer. When the logic block is Temporary local data double word LD
finished, these data are lost. The data are
contained in the local data stack (L stack).

Statement List (STL) for S7-300/S7-400


2-8 C79000-G7076-C565-01
Structure and Components of Instructions and Statements

Table 2-11 lists the maximum address ranges for various memory areas. For
the address range possible with your CPU, refer to the technical data of the
CPU. For an explanation of the functions of the memory areas, see
Table 2-10.

Table 2-11 Memory Areas and Their Address Ranges

Access to Area
Name of Area M i
Maximum Address
Add Range
R
via Units of the Following Size: Abbrev.
Process image input Input bit I 0.0 to 65,535.7
Input byte IB 0 to 65,535
Input word IW 0 to 65,534
Input double word ID 0 to 65,532
Process image Output bit Q 0.0 to 65,535.7
output Output byte QB 0 to 65,535
Output word QW 0 to 65,534
Output double word QD 0 to 65,532
Bit memory Memory bit M 0.0 to 255.7
Memory byte MB 0 to 255
Memory word MW 0 to 254
Memory double Word MD 0 to 252
I/O: Peripheral input byte PIB 0 to 65,535
external input Peripheral input word PIW 0 to 65,534
Peripheral input double word PID 0 to 65,532
I/O: Peripheral output byte PQB 0 to 65,535
external output Peripheral output word PQW 0 to 65,534
Peripheral output double word PQD 0 to 65,532
Timer Timer (T) T 0 to 255
Counter Counter (C) C 0 to 255
Data block Data block opened with the statement “OPN DB”:

Data bit
Data byte DBX 0.0 to 65,535.7
Data word DBB 0 to 65,535
Data double word DBW 0 to 65, 534
DBD 0 to 65,532
Data block opened with the statement “OPN DI”:

Data bit
Data byte DIX 0.0 to 65,535.7
Data word DIB 0 to 65,535
Data double word DIW 0 to 65, 534
DID 0 to 65,532
Local data Temporary local data bit L 0.0 to 65,535.7
Temporary local data byte LB 0 to 65,535
Temporary local data word LW 0 to 65, 534
Temporary local data double word LD 0 to 65,532

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 2-9
Structure and Components of Instructions and Statements

2.2 Meaning of the CPU Register in Statements

Accumulators The two 32-bit accumulators are general purpose registers that you use to
process bytes, words, and double words. You can load constants or values
from the memory as addresses into the accumulator and perform logic
operations on them. You can also transfer the result of an operation from
accumulator 1 to a memory location. Figure 2-4 identifies the areas of an
accumulator.
The stack mechanism for accumulator administration is as follows:
 A load instruction always acts on accumulator 1 and saves the old
contents to accumulator 2.
 A transfer instruction does not change the accumulators (with the
exception of instructions TAR1 and TAR2).
 The TAK instruction swaps the contents of accumulators 1 and 2.
For information on accumulator administration for math instructions, see
Section 9.1.

31 24 23 16 15 8 7 0

High byte Low byte High byte Low byte

High word Low word


Accumulator (1 or 2)

Figure 2-4 Areas of an Accumulator

Nesting Stack The nesting stack is a storage area that is one byte wide. This storage area is
used by the nesting instructions A(, O(, X(, AN(, ON(, XN(. These
instructions save the current result of logic operation (RLO) to the nesting
stack and start a new logic string.
The nesting stack can accommodate seven entries. A nesting stack entry
consists of the RLO, BR, and OR bits of the status word, and a function code
to indicate which of the Boolean logic operations is to be used (A, AN, O,
ON, X, or XN).
The “)” instruction closes a nesting expression by performing the following
functions:
 Fetches an entry from the nesting stack
 Restores the OR and BR bits
 Defines the new RLO by logically combining the current RLO (that is,
the RLO from the expression nested in parentheses) with the RLO of the
stack entry according to the function code (see Section 5.4)

Statement List (STL) for S7-300/S7-400


2-10 C79000-G7076-C565-01
Structure and Components of Instructions and Statements

Figure 2-5 shows the structure of an entry in the nesting stack. Below
Figure 2-5 you can see an explanation of the bits in the nesting stack byte.

27 26 25 24 23 22 21 20

0 0 BR RLO OR Function code

Figure 2-5 Structure of an Entry in the Nesting Stack

The nesting stack byte contains the following bits (see Figure 2-5):
 Non-assigned bits (bits 7 and 6 with signal state “0”)
 The stored binary result (BR)
 The stored result of logic operation (RLO)
 The stored OR bit in the functions A( and AN(
Zero is stored in all other functions
 The function code (in bits 2, 1 and 0)

Function code
With the help of the function code, the instruction “)” defines the function
which is to be used for the combination of the current RLO (that is the RLO
from the expression nested in parentheses) with the RLO of the nesting stack
entry. Table 2-12 shows the bit combinations of the function code for each
function type:

Table 2-12 Function Codes of Nesting Stack Byte

Instruction Function Code 2 Function Code 1 Function Code 0


A( 0 0 0
AN( 0 0 1
O( 0 1 0
ON( 0 1 1
X( 1 0 0
XN( 1 0 1

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 2-11
Structure and Components of Instructions and Statements

Nesting Stack with Entries and Pointer


The nesting stack and the nesting stack pointer must be stored either in the
interrupt stack or they must be fetched from it, when the batches change. The
number in the nesting stack pointer indicates the number of entries available
in the nesting stack (see Figure 2-6).

15 7 0
Nesting stack entry 7 Nesting stack entry 6

Nesting stack entry 5 Nesting stack entry 4

Nesting stack entry 3 Nesting stack entry 2

Nesting stack entry 1 Nesting stack pointer Rising


addresses

Figure 2-6 Structure of a Nesting Stack with Entries and Pointer

Status Word The status word contains bits that you can reference in the address of bit
logic and word logic instructions. Figure 2-7 shows the structure of the status
word. The sections that follow the figure explain the significance of bits
0 through 8.

215... ...29 28 27 26 25 24 23 22 21 20
BR CC 1 CC 0 OV OS OR STA RLO FC

Figure 2-7 Structure of the Status Word

First Check Bit 0 of the status word is called the first-check bit (FC bit, see Figure 2-8).
The signal state of 0 in the FC bit indicates that, following this point in your
program, the next logic instruction begins a new logic string. (The bar over
the FC indicates that it is negated.)
Each logic instruction checks the signal state of the FC bit as well as the
signal state of the location it addresses. If the FC bit is 0, the instruction
stores the result of the signal state check in the result of logic operation bit of
the status word (RLO bit, see next section) and sets the FC bit to 1. This
process is called a first check (see Figure 2-8 and Section 5.6).
If the signal state of the FC bit is equal to 1, an instruction combines the
result of its signal state check on the contact it addresses with the value
stored in the previous RLO bit (see Figure 2-8).
A string of logic instructions always ends with an output instruction (S, R, or
=, see Sections 5.7 and 5.8), a jump instruction related to the result of logic
operation (JC, see Section 16), or one of the nesting instructions A(, O(, X(,
AN(, ON(, or XN( (see Section 5.4). Such an output, jump instruction, or
nesting instruction resets the FC bit to 0 (see Figure 2-8).

Statement List (STL) for S7-300/S7-400


2-12 C79000-G7076-C565-01
Structure and Components of Instructions and Statements

Result of Logic Bit 1 of the status word is called the RLO bit (RLO stands for “result of logic
Operation operation,” see Figure 2-7). This bit stores the result of a bit logic instruction
or math comparison.
For example, the second instruction in a string of bit logic instructions checks
the signal state of a contact and produces a result of 1 or 0. Then the
instruction combines this result with the value stored in the RLO bit of the
status word according to the principles of Boolean logic (see First Check
above and Chapter 5). The result of this logic operation is stored in the RLO
bit of the status word, replacing the former value in the RLO bit. Each
subsequent instruction in the string performs a logic operation on two values:
the result produced when the instruction checks the contact, and the current
RLO.
You can set the RLO to 1 unconditionally by using the SET instruction; you
can reset the RLO to 0 unconditionally by using the CLR instruction. You
can use a Boolean bit logic instruction on a first check to assign the state of
the contents of a Boolean bit memory location to the RLO. You can use the
RLO to trigger jump instructions.

Statement Signal State Result of RLO FC Explanation


List Program of Input (I) Check Bit Bit
or Output (Q)
0 FC bit = 0 indicates that next
instruction begins logic string
A I 1.0 1 1 1 1 Result of first check is stored in
RLO bit. FC bit is set to 1.

AN I 1.1 0 1 1 1 Result of check is combined with


previous RLO according to AND
truth table. FC bit remains 1.

= Q 4.0 1 0 RLO is assigned to output


coil. FC bit is reset to 0.

Figure 2-8 Effect of Signal State of FC Bit on Logic Instructions

Status Bit The status bit (STA bit) stores the value of a bit that is referenced. The status
of a bit instruction that has read access to the memory (A, AN, O, ON, X,
XN) is always the same as the value of the bit that this instruction checks (the
bit on which it performs its logic operation). The status of a bit instruction
that has write access to the memory (S, R, =) is the same as the value of the
bit to which the instruction writes or, if no writing takes place, the same as
the value of the bit that the instruction references. The status bit has no
significance for bit instructions that do not access the memory. Such
instructions set the status bit to 1 (STA=1). The status bit is not checked by
an instruction. It is interpreted during program test (program status) only.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 2-13
Structure and Components of Instructions and Statements

OR Bit The OR bit is needed if you use the O instruction to perform a logical AND
before OR operation. An AND function may contain the following
instructions: A, AN A(, AN(, ), and NOT. The OR bit shows these
instructions that a previously executed AND function has supplied the
value 1, thus forestalling the result of the logical OR operation. Any other
bit-processing command resets the OR bit (see Section 5.4).

Overflow Bit The overflow bit (OV bit) indicates a fault. It is set by a math instruction or a
floating-point comparison instruction after a fault occurs (overflow, illegal
operation, illegal floating-point number). This bit is set according to the
result of the next math instruction or comparison instruction.

Stored Overflow The stored overflow bit (OS bit) is set together with the OV bit when a fault
Bit occurs. Because the OS bit remains set after the fault has been eliminated, it
stores the OV bit status and indicates whether or not a fault occurred in one
of the previously executed instructions. The following commands reset the
OS bit: JOS (jump after stored overflow), the block call commands, and the
block end commands.

Condition Code 1 The CC 1 and CC 0 bits (condition codes) provide information on the
and Condition following results or bits:
Code 0
 Result of a math operation
 Result of a comparison
 Result of a digital operation
 Bits that have been shifted out by a shift or rotate command
Tables 2-13 through 2-18 list the significance of CC 1 and CC 0 after your
program executes certain instructions.

Table 2-13 CC 1 and CC 0 after Math Instructions, without Overflow

CC 1 CC 0 Explanation
0 0 Result = 0
0 1 Result < 0
1 0 Result > 0

Table 2-14 CC 1 and CC 0 after Integer Math Instructions, with Overflow

CC 1 CC 0 Explanation
0 0 Negative range overflow in +I and +D
0 1 Negative range overflow in I and D
Positive range overflow in +I, –I, +D, –D, NEGI, and NEGD
1 0 Positive range overflow in I, D, /I, and /D
Negative range overflow in +I, –I, +D, and –D
1 1 Division by 0 in /I, /D, and MOD

Statement List (STL) for S7-300/S7-400


2-14 C79000-G7076-C565-01
Structure and Components of Instructions and Statements

Table 2-15 CC 1 and CC 0 after Floating-Point Math Instructions, with Overflow

CC 1 CC 0 Explanation
0 0 Gradual underflow
0 1 Negative range overflow
1 0 Positive range overflow
1 1 Invalid floating-point number

Table 2-16 CC 1 and CC 0 after Comparison Instructions

CC 1 CC 0 Explanation
0 0 Accumulator 2 = accumulator 1
0 1 Accumulator 2 < accumulator 1
1 0 Accumulator 2 > accumulator 1
1 1 Accumulator 1 or accumulator 2 is an invalid floating-point
number

Table 2-17 CC 1 and CC 0 after Shift and Rotate Instructions

CC 1 CC 0 Explanation
0 0 Last bit shifted out = 0
1 0 Last bit shifted out = 1

Table 2-18 CC 1 and CC 0 after Word Logic Instructions

CC 1 CC 0 Explanation
0 0 Result = 0
1 0 Result <> 0

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 2-15
Structure and Components of Instructions and Statements

Binary Result Bit The binary result bit (BR bit) forms a link between the processing of bits and
words. It is an efficient means of interpreting the result of a word operation
as a binary result and integrates this result in a binary logic string. Viewed in
this way, the BR bit represents a machine-internal memory bit to which the
RLO is saved prior to a word operation that changes the RLO, so that the
RLO will be available again after the operation to continue the interrupted bit
string.
For example, the BR bit makes it possible for you to write a function block
(FB) or a function (FC) in statement list (STL) and then call the FB or FC
from ladder logic (LAD, see the Reference Manual /233/).
When writing a function block or function that you want to call from LAD,
no matter whether you write the FB or FC in STL or LAD, you are
responsible for managing the BR bit. The BR bit corresponds to the enable
output (ENO) of a LAD box. You should use the SAVE instruction (in STL,
see Section 5.9) or the –––(SAVE) coil (in LAD) to store an RLO in the BR
bit according to the following criteria:
 Store an RLO of 1 in the BR bit for a case where the FB or FC is
executed without error.
 Store an RLO of 0 in the BR bit for a case where the FB or FC is
executed with error
You should program these instructions at the end of the FB or FC so that
these are the last instructions that are executed in the block.
When you call a system function block (SFB) or a system function (SFC) in
your program, the SFB or SFC indicates whether the CPU was able to
execute the function with or without errors by providing the following
information in the binary result bit:
 If an error occurred during execution, the BR bit is 0.
 If the function was executed with no error, the BR bit is 1.

Statement List (STL) for S7-300/S7-400


2-16 C79000-G7076-C565-01
Addressing 3
Chapter Overview Section Description Page
3.1 Immediate Addressing 3-2
3.2 Direct Addressing 3-2
3.3 Memory Indirect Addressing 3-3
3.4 Address Registers 3-6
3.5 Area-Internal Register Indirect Addressing 3-7
3.6 Area-Crossing Register Indirect Addressing 3-11

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 3-1
Addressing

3.1 Immediate Addressing

Description With immediate addressing, the address is coded directly in the instruction;
that is, it directly follows the value with which the instruction is to work (for
example, Load). An instruction can also provide its own value (for example,
SET, see Table 3-1).

Table 3-1 Immediate Addressing

Examples Example Description


SET Set the RLO to 1.
OW W#16#A320 Or Word.
L 27 Load the integer value 27 into accumulator 1.
L ’ABCD’ Load the ASCII characters ABCD into accumulator 1.
L B#(100,12) Load the two bytes 100 and 12 into accumulator 1.
L C#0100 Load the BCD value 0000 into accumulator 1.

3.2 Direct Addressing

Description An instruction that uses direct addressing has the following two-part address
that indicates the location of the value that the instruction is going to process:
 An address identifier (for example, “IB” for “input byte”)
 An exact location within the memory area that is indicated by the address
identifier
The address points directly to the location of the value.

Table 3-2 Direct Addressing

Examples Example Description


A I 0.0 Perform an AND logic operation on input bit I 0.0.
S L 20.0 Set the local data bit L 20.0.
= M 115.4 Assign the RLO to memory bit M 115.4
L IB0 Load input byte IB0 into accumulator 1.
L MW64 Load memory word MW64 into accumulator 1.
T DBD12 Transfer the contents from accumulator 1 into data
double word DBD12.

Statement List (STL) for S7-300/S7-400


3-2 C79000-G7076-C565-01
Addressing

3.3 Memory Indirect Addressing

Description An instruction that uses memory indirect addressing has the following
two-part address that indicates the location of the value that the instruction is
going to process:
 An address identifier (for example, “IB” for “input byte”)
 One of the following pointers:
– A word that contains the number of a timer (T), counter (C), data
block (DB), function (FC), or function block (FB)
– A double word that contains the exact location of a value within the
memory area that is indicated by the address identifier
The address indicates the location of the value or number indirectly via the
pointer. This word or double word can be in one of the following areas:
 Bit memory (M)
 Data block (DB)
 Instance data block (DI)
 Local data (L)
The advantage of memory indirect addressing is that you can modify the
statement address dynamically during program execution.

Using the Right When working with a memory indirect address that is stored in the data block
Syntax area of memory, first you must open the data block by using the Open a Data
Block (OPN) instruction. Then you can use the data word or data double
word as an indirect address, as shown in the following example:
OPN DB10
L IB [DBD20]

Examples

Table 3-3 Memory Indirect Addressing

Example Description
A I [MD2] Perform an And logic operation on the input bit whose exact location is in memory
or double word MD2 or in the location designated by “anna” in the symbol table, as a
A I [anna] reference to MD2.
= DIX [DBD2] Assign the RLO bit to the instance data bit whose exact location is in data double
word DBD2.
OPN DB [LW2] Open the data block whose data block number is located in local word LW2.
O Q [LD3] Perform an Or logic operation on the output bit that is located in a local data
or double word LD3 or in a local TEMP variable designated as “boxcar.”
O Q [boxcar]

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 3-3
Addressing

Pointer Format There are two possible pointer formats: word and double word. The
abbreviation for a pointer in word format ends in W (for example, DBW).
Figure 3-1 shows the pointer format for a word. The abbreviation for a
double word format ends in D (for example, DBD). Figure 3-2 shows the
pointer format for a double word.

15.. ..8 7.. ..0


nnnn nnnn nnnn nnnn

Bits 0 to 15 (nnnn nnnn nnnn nnnn): number (range 0 to 65,535) of a


timer (T), counter (C), data block (DB), function (FC), or function block (FB)

Figure 3-1 Word Pointer Format for Memory Indirect Addressing

The following two examples show how to work with the word pointer
format:

STL Explanation
L +5 Load the value 5 as an integer into accumulator 1.
T MW2 Transfer the contents of accumulator 1 to memory word MW2.
OPN DB[MW2] Open data block 5.

STL Explanation
OPN DB10 Open data block DB10.
L +20 Load the value 20 as an integer into accumulator 1.
T DBW10 Transfer the contents of accumulator 1 to data word DBW10
A T[DBW10] Check the signal state of timer T 20.

Statement List (STL) for S7-300/S7-400


3-4 C79000-G7076-C565-01
Addressing

31.. ..24 23.. ..16 15.. ..8 7.. ..0


0000 0000 0000 0 bbb bbbb bbbb bbbb b xxx

Bits 3 to 18 (bbbb bbbb bbbb bbbb): byte number (range 0 to 65,535) of the
addressed byte

Bits 0 to 2 (xxx): bit number (range 0 to 7) of the addressed bit

Figure 3-2 Double Word Pointer Format for Memory Indirect Addressing

Note
If you access a byte, word, or double word, be sure that the bit number of
your pointer is 0.

The following two examples show you how to work with the double word
pointer format:

STL Explanation
L P#8.7 Load 2#0000 0000 0000 0000 0000 0000 0100 0111 (binary value)
into accumulator 1.
T MD2 Store the exact location 8.7 in memory double word MD2.

A I [MD2] The controller checks input bit I 8.7 and assigns its signal
= Q [MD2] state to output bit Q 8.7.

STL Explanation
L P#8.0 Load 2#0000 0000 0000 0000 0000 0000 0100 0000 (binary value)
into accumulator 1.
T MD2 Store the exact location 8 in memory double word MD2.

L IB [MD2] The controller loads input byte IB8 and transfers the contents
T MW [MD2] to memory word MW8. The exact location 8 comes from memory
double word MD2.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 3-5
Addressing

3.4 Address Registers

Explanation Some types of indirect addressing in statement list programming require the
use of certain registers in the CPU. These registers are described below.

Address Registers Address registers 1 and 2 (AR1 and AR2) are 32-bit registers that accept an
1 and 2 area-internal or area-crossing pointer for commands that use register-indirect
addressing (see Sections 3.5 and 3.6).

Pointers Pointers are used in register-indirect addressing (see Sections 3.5 and 3.6).
The following two types are available:
 Area-internal: used for area-internal access to bits, bytes, words, and
double words in memory areas P, I, Q, M, DBX, DIX, and L
 Area-crossing: used for area-crossing access to bits, bytes, words, and
double words in memory areas P, I, Q, M, DBX, DIX, and L

Statement List (STL) for S7-300/S7-400


3-6 C79000-G7076-C565-01
Addressing

3.5 Area-Internal Register Indirect Addressing

Description An instruction that uses area-internal register indirect addressing has the
following two-part address that indicates the memory location of the value
that the instruction is going to process:
 An address identifier (for example, “LD” for “local data double word,”
see Table 2-6)
 An address register and a pointer to specify byte and bit. The byte and bit
indicate an offset, which, when added to the contents of the register,
indicate the memory location of the value that the instruction is to
process.
The address points to the memory location of the value indirectly via the
address register plus offset.
A statement that uses area-internal register indirect addressing does not
change the value in the address register.

Calculating the The address of an instruction points to the value that the instruction is going
Memory Location to process. Where area-internal register indirect addressing is concerned, the
of the Address address points to the memory location of the value indirectly via the address
register plus offset. Figure 3-3 shows how you calculate the memory location
for the address of the Assign (=) instruction in the following statement:
= Q [AR1, P#1.1]

Byte Bit

Contents of address register AR1: 8.7 byte 8, bit 7

Offset P#: 1.1 byte 1, bit 1


+
Memory location: output byte Q 10.0 bytes: 9, bits: 8 (= 1 byte)

(9 bytes + 1 byte = 10 bytes)

Figure 3-3 Calculating the Memory Location of Output Q [AR1, P#1.1]

You calculate the memory location of the address by adding the byte portion
of the contents of the address register to the byte portion of the offset pointer
and by adding the bit portion of the contents of the address register to the bit
portion of the offset pointer. You calculate the byte portion of the memory
location using decimal math and the bit portion using octal math (8 bits =
1 byte). There can be a carry between the bit and byte portions.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 3-7
Addressing

Table 3-4 Area-Internal Register Indirect Addressing

Examples Example Description


A I [AR1, P#4.3] Perform an And logic operation on the input bit whose
memory location is calculated by the contents of
address register AR1 plus 4 bytes, plus 3 bits.
= DIX [AR2, P#0.0] Assign the RLO bit to the instance data bit whose
memory location is in address register AR2.
L IB [AR1, P#100.0] Load the input byte whose memory location is
calculated by the contents of address register AR1 plus
100 bytes into accumulator 1.
T LD [AR2, P#56.0] Transfer the contents of accumulator 1 into local data
double word LD whose memory location is calculated
by the contents of address register AR2 plus 56 bytes.

With reference to addressing local data, please read the


Warning below.

Warning
! Possible overwriting of the data that is used by the compiler.

When you use absolute addressing to access temporary local data, there is no
guarantee that there will be no conflict between the data used by the
compiler and the local data that you are attempting to access by means of
absolute addressing. It is possible that you overwrite some of the data that
the compiler uses. (For example, the compiler uses local data for transferring
formal parameters.) Local data that the compiler needs are attached to the
symbolic data that are defined by the person doing the programming.

When accessing temporary local data, you are advised to choose symbolic
addressing over absolute addressing.

Statement List (STL) for S7-300/S7-400


3-8 C79000-G7076-C565-01
Addressing

Pointer Format Area-internal register indirect addressing has only one possible pointer
format: double word. This double word contains an address encoded as a bit
address. The abbreviation for a double word format ends in D (for example,
DBD). Figure 3-4 shows the pointer format for a double word.

31.. ..24 23.. ..16 15.. ..8 7.. ..0


0000 0000 0000 0 bbb bbbb bbbb bbbb b xxx

Bit 31 = 0 to indicate area-internal register indirect addressing

Bits 3 to 18 (bbbb bbbb bbbb bbbb): byte number (range 0 to 65,535) of the
addressed bit

Bits 0 to 2 (xxx): bit number (range 0 to 7) of the addressed bit

Figure 3-4 Double Word Pointer Format for Area-Internal Register Indirect
Addressing

Note
If you access a byte, word, or double word, be sure that the bit number of
your pointer is 0.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 3-9
Addressing

The following two examples show you how to work with the double word
pointer format:

STL Explanation
L P#8.7 Load a double word pointer to bit address location 8.7 into
accumulator 1.

LAR1 Store a double word pointer to bit address location 8.7 in


address register AR1.

A I [AR1, P#0.0] The CPU adds the offset (P#0.0) to the contents of address
register AR1 (8.7) and uses this address as the location of an
And bit logic instruction. The contents of AR1 remain
unchanged.

= Q [AR1, P#1.1] The CPU assigns the result of the And bit logic operation (RLO)
to an address (Q 10.0). The CPU calculates this address by
adding the contents of address register AR1 (8.7) and the
offset (P#1.1).

STL Explanation
L P#8.0 Load a double word pointer to bit address location 8.0 into
accumulator 1.

LAR2 Store a double word pointer to bit address location 8.0 in


address register AR2.

L IB [AR2, P#2.0] The CPU loads input byte IB10 into accumulator 1.

T MW [AR2, P#200.0] The CPU transfers the contents of accumulator 1 to memory word
MW208.

The location 208 comes from 8 (AR2) plus 200 (offset), which is
208.

Statement List (STL) for S7-300/S7-400


3-10 C79000-G7076-C565-01
Addressing

3.6 Area-Crossing Register Indirect Addressing

Description An instruction that uses area-crossing register indirect addressing has the
following two-part address that indicates the memory location of the value
that the instruction is going to process:
 An address identifier that indicates the size of a data object (for example,
“B” for “byte,” see Table 2-8). The memory area is indicated in bits 24,
25, and 26 of the address register.
 An address register and a pointer that indicate an offset which, when
added to the contents of the address register, indicates the memory
location of the value that is to be processed by the instruction. The pointer
is indicated by P#byte.bit.
The address points to the memory location of the value indirectly via the
address register plus offset.
A statement that uses area-crossing register indirect addressing does not
change the value in the address register.

Calculating the The address of an instruction points to the value that the instruction is going
Memory Location to process. Where area-crossing register indirect addressing is concerned, the
of the Address address points to the memory location of the value indirectly via the address
register plus offset. Figure 3-5 shows how you calculate the memory location
for the address of the Assign (=) instruction in the following statement:
= [AR1, P#1.1]

Byte Bit

Contents of address register AR1: 8.7 byte 8, bit 7

Offset P#: 1.1 byte 1, bit 1


+
Memory location: byte 10.0 bytes: 9, bits: 8 (= 1 byte)

(9 bytes + 1 byte = 10 bytes)

Figure 3-5 Calculating the Address [AR1, P#1.1]

You calculate the memory location of the address by adding the byte portion
of the contents of the address register to the byte portion of the offset pointer
and by adding the bit portion of the contents of the address register to the bit
portion of the offset pointer. You calculate the byte portion of the memory
location using decimal math and the bit portion using octal math (8 bits =
1 byte). There can be a carry between the bit and byte portions.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 3-11
Addressing

Example Table 3-5 provides examples of area-crossing register indirect addressing.


The address must contain an additional area identification in bits 24, 25, and
26 of the pointer. The addressed information is in the address register.

Table 3-5 Area-Crossing Register Indirect Addressing

Example Description
A [AR1, P#4.3] Perform an And logic operation on the bit whose
memory location is calculated by the contents of
address register AR1, plus 4 bytes plus 3 bits. The
memory area of the bit is indicated in bits 24, 25, and
26 of address register AR1.
= [AR2, P#0.0] Assign the RLO bit to the bit whose memory
location is in address register AR2. The memory area
of the bit is indicated in bits 24, 25, and 26 of address
register AR2.
L B [AR1, P#100.0] Load into accumulator 1 the byte whose memory
location is calculated in address register AR1 plus
100 bytes. The memory area of the byte is indicated
in bits 24, 25, and 26 of address register AR1.
T D [AR2, P#56.0] Transfer the contents of accumulator 1 into the
double word whose memory location is calculated by
the contents of address register AR2 plus 56 bytes.
The memory area of the double word is indicated in
bits 24, 25, and 26 of address register AR2.

Table 3-6 lists the binary code in bits 24, 25, and 26 of the pointer that
identifies the area.

Table 3-6 Area Identification for Area-Crossing Register Indirect Addressing

Area Identification (Memory Area) Binary Contents of Bits 26, 25, and 24
P (I/O, external inputs and outputs) 000
I (process-image input) 001
Q (process-image output) 010
M (bit memory) 011
DBX (data block) 100
DIX (data block) 101
(previous local data, that is, the local
data of the previous incompleted 111
block)

Statement List (STL) for S7-300/S7-400


3-12 C79000-G7076-C565-01
Addressing

Pointer Format Area-crossing register indirect addressing has only one possible pointer
format: double word. The abbreviation for a double word format ends in D
(for example, DBD). Figure 3-6 shows the pointer format for a double word.

31.. ..24 23.. ..16 15.. ..8 7.. 3.. ..0


1000 0rrr 0000 0 bbb bbbb bbbb bbbb b xxx

Bit 31 = 1 to indicate area-crossing register indirect addressing

Bits 24, 25, and 26 (rrr): area identification (memory area, see Table 3-6)

Bits 3 to 18 (bbbb bbbb bbbb bbbb): byte number (range 0 to 65,535) of the
addressed bit

Bits 0 to 2 (xxx): bit number (range 0 to 7) of the addressed bit

Figure 3-6 Double Word Pointer Format for Area-Crossing Register Indirect
Addressing

Note
If you access a byte, word, or double word, be sure that the bit number of
your pointer is 0.
You cannot access local data using area-crossing register indirect addressing!

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 3-13
Addressing

The following two examples show you how to work with the double word
pointer format:

STL Explanation
L P#I 8.7 Load a double word pointer to bit address location I 8.7 into
accumulator 1.

LAR1 Store a double word pointer to bit address location I 8.7 in


address register AR1.

L P#Q 8.7 Load a double word pointer to bit address location Q 8.7 into
accumulator 1.

LAR2 Store a double word pointer to bit address location Q 8.7 in


address register AR2.

A [AR1, P#0.0] The CPU adds the contents of address register AR1 (P#I 8.7) and
the offset (P#0.0) and uses the address pointed to by the
result (I 8.7) as the address of an And bit logic instruction.
The contents of AR1 remain unchanged.

The CPU assigns the result of the And bit logic operation (RLO)
= [AR2, P#1.1] to an address (Q 10.0). The CPU calculates this address by
adding the contents of address register AR2 (P#Q 8.7) and the
offset (P#1.1) and dereferencing the pointer. The contents of
AR2 remain unchanged.

STL Explanation
L P#I 8.0 Load a double word pointer to bit address location I 8.0 into
accumulator 1.

LAR2 Store a double word pointer to bit address location I 8.0 in


address register AR2.

L P#M 8.0 Load a double word pointer to bit address location M 8.0 into
accumulator 1.

LAR1 Store a double word pointer to bit address location M 8.0 in


address register AR1.

L B [AR2, P#2.0] The CPU loads input byte IB10.

T W [AR1, P#200.0] The CPU transfers the contents to memory word MW208.

Input byte 10 comes from 8 (AR2) plus 2 (offset).


Memory word 208 comes from 8 (AR1) plus 200 (offset), which is
208.

Statement List (STL) for S7-300/S7-400


3-14 C79000-G7076-C565-01
Accumulator Operations and Address
Register Instructions 4
Chapter Overview Section Description Page
4.1 Overview 4-2
4.2 ENT and LEAVE 4-3
4.3 Incrementing and Decrementing 4-6
4.4 +AR1 und +AR2: Adding a Constant to Address Register 1 4-7
or Address Register 2

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 4-1
Accumulator Operations

4.1 Overview
The following instructions are available to you for handling the contents of
one or both accumulators:

Mnemonic Instruction Explanation


TAK Toggle Accumulator 1 with This instruction exchanges the contents of accumulator 1
Accumulator 2 with the contents of accumulator 2.
PUSH Accumulator 1 to Accumulator 2 This instruction copies the contents of accumulator 1 to
with 2 ACCUs accumulator 2.
POP Accumulator 2 to Accumulator 1 This instruction copies the contents of accumulator 2 to
with 2 ACCUs accumulator 1.
PUSH Copy ACCU 3 to ACCU 4, This instruction copies the contents of accumulator 3 to
with 4 ACCUs ACCU 2 to ACCU 3, ACCU 1 accumulator 4, the contents of accumulator 2 to accumula-
to ACCU 2 tor 3 and the contents of accumulator 1 to accumulator 2.
POP Copy ACCU 2 to ACCU 1, This instruction copies the contents of accumulator 2 to
with 4 ACCUs ACCU 3 to ACCU 2, ACCU 4 accumulator 1, the contents of accumulator 3 to accumula-
to ACCU 3 tor 2 and the contents of accumulator 4 to accumulator 3.
ENT Enter accumulator stack This instruction copies the contents of accumulator 3 to
accumulator 4 and the contents of accumulator 2 to accu-
mulator 3.
LEAVE Leave accumulator stack This instruction copies the contents of accumulator 3 to
accumulator 2 and the contents of accumulator 4 to accu-
mulator 3.
INC Increment Accumulator 1 This instruction increases the contents of the low byte of
the low word of accumulator 1 by the 8-bit constant that is
indicated in the instruction statement. The constant can be
in the range of 0 to 255.
DEC Decrement Accumulator 1 This instruction decreases the contents of the low byte of
the low word of accumulator 1 by the 8-bit constant that is
indicated in the instruction statement. The constant can be
in the range of 0 to 255.
+AR1, +AR2 Add Accumulator 1 to Address This instruction adds the contents of the low word of ac-
Register cumulator 1 to address register 1 or 2.
+AR1 P#Byte.Bit, Add Constant to Address This instruction adds a constant to the contents of address
+AR2 P#Byte.Bit Register register 1 or 2.
BLD Program Display Instruction ”This instruction does not carry out any function and does
not influence the status bits. The instruction is only rele-
vant to the programming device (PG) when a program is
displayed. The address <number> is the ID of the instruc-
tion BLD and is generated by the programming device.”
NOP 0 Null Instruction 0 ”These instructions do not carry out any function, nor do
they influence the contents of the status word. The
NOP 1 Null Instruction 1
instructions NOP 1 and NOP 0 are required for decompil-
ing. The instruction code contains a bit pattern with either
16 zeroes or 16 ones.”

For information on reversing the order of bytes in accumulator 1, see


Section 12.3.

Statement List (STL) for S7-300/S7-400


4-2 C79000-G7076-C565-01
Accumulator Operations

4.2 ENT and LEAVE

Description With the instructions ENT (Enter Accumulator Stack) and LEAVE (Leave
Accumulator Stack) you can carry out the following functions:
 The instruction ENT copies the contents of Accumulator 3 to Accumulator
4 and the contents of Accumulator 2 to Accumulator 3. If you program
the ENT instruction directly before a load instruction, it SHIFTS
Accumulator 2 and Accumulator 3 further in the stack.
 The instruction LEAVE copies the contents of Accumulator 3 to
Accumulator 2 and the contents of Accumulator 4 to Accumulator 3. If
you program the LEAVE instruction directly before a shift and rotate
instruction, which combines accumulators, then the LEAVE instruction
will function like a math operation.

ENT Figure 4-1 shows how the ENT instruction works.

ACCU 4 ENT ACCU 4


31 0 31 0
I II III IV V VI VII VIII

ACCU 3 ACCU 3
31 0 31 0
V VI VII VIII IX X XI XII

ACCU 2 ACCU 2
31 0 31 0
IX X XI XII IX X XI XII

ACCU 1 ACCU 1
31 0 31 0
XIII XIV XV XVI XIII XIV XV XVI

Figure 4-1 Copying the contents of Accumulator 3 to Accumulator 4 and the contents of Accumulator 2 to
Accumulator 3 in the ENT instruction ENT

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 4-3
Accumulator Operations

LEAVE Figure 4-2 shows how the LEAVE instruction works.

ACCU 4 LEAVE ACCU 4


31 0 31 0
I II III IV I II III IV

ACCU 3 ACCU 3
31 0 31 0
V VI VII VIII I II III IV

ACCU 2 ACCU 2
31 0 31 0
IX X XI XII V VI VII VIII

ACCU 1 ACCU 1
31 0 31 0
XIII XIV XV XVI XIII XIV XV XVI

Figure 4-2 Copying the contents of Accumulator 3 to Accumulator 2 and the contents of Accumulator 4 to
Accumulator 3 in the LEAVE instruction

Example The following program extract shows the use of the ENT instruction.
The floating points in the data double words DBD0 and DBD4 should be
added together. The sum should then be divided by the difference of the
floating points of the data double words DBD8 and DBD12.

DBD0 + DBD4
DBD16 =
DBD8 – DBD12

The quotient of the above division should be stored in DBD16.


In this example, the purpose of the ENT instruction is to take the interim
result (DBD0+DBD4), which is located in Accumulator 2 and save it in
Accumulator 3. The subtraction command (-R) copies the interim result back
to Accumulator 2 following the subtraction.

Statement List (STL) for S7-300/S7-400


4-4 C79000-G7076-C565-01
Accumulator Operations

STL Explanation

L DBD0 Load the value from data double word DBD0 in ACCU1 (the value
must be in floating-point format).
L DBD4 Copy the value from ACCU1 to ACCU2.Load the value from data
double word DBD4 in ACCU1 (the value must be in floating-point
+R format).
Add the contents of ACCU1 and ACCU2 as floating-point numbers
(32 bits, IEEE-FP) and store the result in ACCU1.
L DBD8 Copy the value from ACCU1 to ACCU2.
Load the value from data double word DBD8 to ACCU1.
ENT Copy the contents of ACCU3 to ACCU4.
Copy the contents of ACCU2 (interim result) to ACCU3.
L DBD12 Copy the contents of ACCU1 to ACCU2.
Load the contents from data double word DBD12 to ACCU1.
–R Subtract the contents of ACCU1 from the contents of ACCU2.
Store the result in ACCU1.
Copy the contents of ACCU3 to ACCU2.
/R Divide the contents of ACCU 2 by the contents of ACCU1.
Save the quotient in ACCU1.
T DBD16 Transfer the result (ACCU1) to the data double word DBD16.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 4-5
Accumulator Operations

4.3 Incrementing and Decrementing

Description You can use the Increment Accumulator 1 (INC) and Decrement
Accumulator 1 (DEC) instructions to perform the following functions:
 INC increases the contents of the low byte of the low word of
accumulator 1 by the 8-bit constant that is indicated in the instruction
statement. The constant can be in the range of 0 to 255.
 DEC decreases the contents of the low byte of the low word of
accumulator 1 by the 8-bit constant that is indicated in the instruction
statement. The constant can be in the range of 0 to 255.
The CPU always executes the INC and DEC instructions, regardless of the
result of logic operation. These instructions do not affect the RLO nor do
they change any of the bits in the status word.

Note
These instructions are not suitable for 16-bit or 32-bit math because no carry
is made from the low byte of the low word of accumulator 1 to the high byte
of the low word of accumulator 1. For 16-bit or 32-bit math, use the +I or
+D instruction, respectively.

Example The following sample program provides an example of how the INC
instruction works within a loop triggered by a conditional jump.

STL Explanation
Body of a loop operation

L 1 Set the loop counter to 1.


T MB10
M1: L MB10 Load the contents of memory byte MB10 into accumulator 1.
INC 1 Increment the loop counter by 1.
T MB10 Transfer the contents of accumulator 1 to memory byte
. MB10.
. Instruction section which is processed five times.
L B#16#5
<= I
SPB M1 If the program has not run through the loop five times,
then return to LOOP.

Statement List (STL) for S7-300/S7-400


4-6 C79000-G7076-C565-01
Accumulator Operations

4.4 +AR1 und +AR2: Adding a Constant to Address Register 1 or


Address Register 2

Description Using the instructions +AR1 and +AR2 you can add a constant to the
contents of address registers 1 and 2:

Table 4-1 Adding to the Contents of Address Registers

Instruction Address Function


+AR1 – Adds the contents of the low word of
accumulator 1 to the contents of address
register 1.
+AR2 – Adds the contents of the low word of
accumulator 1 to the contents of address
register 2.
+AR1 P#Byte.Bit: Adds a pointer constant to the contents
(range 0.0 to 4095.7)1 of address register 1.
+AR2 P#Byte.Bit: Adds a pointer constant to the contents
(range 0.0 to 4095.7)1 of address register 2.

1 The bits 24, 25, and 26 of the address register remain unchanged. These bits indicate
the memory area.

Note
The address register 2 is used when multiple instances are being processed.
Therefore, before programming the command “+AR2”, you must “save” the
contents of AR2 and load them again later.

Examples Below are sample statements that use the +AR1 and +AR2 instructions.
Loading the pointer format into accumulator 1 and then using the +AR1 or
+AR2 instruction, as shown in the first two statements below, enables you to
select from a range of 0.0 to 8191.7.

STL Explanation
L P#250.7 Load a pointer constant (250.7) into accumulator 1.
+AR1 Add the contents of accumulator 1 (250.7) to the contents of
address register 1.
TAR2 #SAVE_AR2 Because multiple instances are using AR2 as base.

+AR2 P#126.7 Add a pointer constant (126.7) to the contents of address


. register 2.
.
L AR2 #SAVE_AR2 Restore AR2.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 4-7
Accumulator Operations

Statement List (STL) for S7-300/S7-400


4-8 C79000-G7076-C565-01
Bit Logic Instructions 5
Chapter Overview Section Description Page
5.1 Boolean Bit Logic 5-2
5.2 Bit Logic Instructions and Relay Coil Circuit 5-6
5.3 Evaluating Conditions Using And, Or, and Exclusive Or 5-10
5.4 Nesting Expressions and And before Or 5-14
5.5 Instructions for Transitional Contacts: FP, FN 5-16
5.6 Output of Boolean Logic String 5-20
5.7 Set and Reset Instructions: S and R 5-21
5.8 Assign Instruction (=) 5-24
5.9 Negating, Setting, Clearing, and Saving the RLO 5-26

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 5-1
Bit Logic Instructions

5.1 Boolean Bit Logic

Explanation Boolean bit logic applies to the following basic instructions:


 And (A) and its negated form, And Not (AN)
 Or (O) and its negated form, Or Not (ON)
 Exclusive Or (X) and its negated form, Exclusive Or Not (XN)
These instructions perform the following basic functions:
 They check the signal state of an address to establish whether an address
is activated “1”, or not activated “0”.
 They check the signal state of a timer or a counter to establish whether it
is set at “0” (value = 0) or “1” (value > 0).
The FC bit determines the result of logic operation (RLO):
 If FC is 0, the result of the state check will remain unchanged and will be
stored in the RLO (start of a logic string).
 If FC is 1, the result of the state check will be combined with the logic
instruction (A, O, X) according to the truth table and will be stored in the
RLO.

Truth Table at the The result of logic operation can be determined with the help of the
Start of a Boolean following truth table:
Logic String

Mnemonic Instruction Status of Result in RLO


Address
A And 0 0
1 1
AN And Not 0 1
1 0
O Or 0 0
1 1
ON Or Not 0 1
1 0
X Exclusive Or 0 0
1 1
XN Exclusive Or Not 0 1
1 0

Statement List (STL) for S7-300/S7-400


5-2 C79000-G7076-C565-01
Bit Logic Instructions

Truth Table within After the second Boolean bit operation the RLO can be established with the
the Boolean Logic help of the following table:
String

Mnemonic Instruction RLO Before Status of Result in


Instruction Address RLO
A And 0 0 0
0 1 0
1 0 0
1 1 1
AN And Not 0 0 0
0 1 0
1 0 1
1 1 0
O Or 0 0 0
0 1 1
1 0 1
1 1 1
ON Or Not 0 0 1
0 1 0
1 0 1
1 1 1
X Exclusive Or 0 0 0
0 1 1
1 0 1
1 1 0
XN Exclusive Or Not 0 0 1
0 1 0
1 0 0
1 1 1

Addresses of The address of an instruction can be a bit, a timer or a counter. The


Basic Functions instruction accesses the contact with one of these addressing types:
(A, AN, O, ON, X,  The address identifier and the address within the memory area defined by
XN) the address identifier (see Tables 5-1 and 5-3).
 Bit, timer or counter transferred as parameter (see Table 5-4).
 Conditions, expressed in bits of the status word (see Table 5-8).

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 5-3
Bit Logic Instructions

Table 5-1 Addresses: Direct and Indirect Addressing

Address Maximum Address Range According to Addressing Type


ID Direct Memory Indirect Register Indirect, Area-Internal
[DBD]
[AR1, P#byte.bit]
I 0.0 to [DID]
0 to 65,532 0.0 to 8,191.7
Q 65,535.7 [LD]
[AR2, P#byte.bit]
[MD]
[DBD]
[AR1, P#byte.bit]
0.0 to [DID]
M 0 to 65,532 0.0 to 8,191.7
65,535.7 [LD]
[AR2, P#byte.bit]
[MD]
[DBD]
DBX [AR1, P#byte.bit]
0.0 to [DID]
DIX 0 to 65,532 0.0 to 8,191.7
65,535.7 [LD]
L [AR2, P#byte.bit]
[MD]

Table 5-2 Addresses: Area-Crossing Register Indirect Addressing

Address Identifier1 Maximum Address Range


[AR1, P#byte.bit]
I, Q, M, DBX, DIX, or L 0.0 to 8,191.7
[AR2, P#byte.bit]
1 The memory area is encoded in pointer bits 24, 25, and 26 (see Section 3.6).

Table 5-3 Addresses: Timers and Counters

Maximum Address Range According to Addressing Type


Address Ident
Identifier
f er
Direct Memory Indirect
[DBW]
T [DIW]
0 to 65,535 0 to 65,534
C [LW]
[MW]

Table 5-4 Address: Bit, Timer, or Counter Transferred as Parameter

Address Address Parameter Format


Symbolic name A bit, timer, or counter transferred as parameter

Table 5-5 Addresses of Boolean Bit Logic Instructions: Bits of the Status Word

Memory Area or Reference to a Bits of the Status Word


Location
>0, <0, <>0, >=0, <=0, ==0 7 and 6: condition codes 1 and 0 (memory area)
UO 7 and 6: condition codes 1 and 0 (memory area)
BR 8: binary result (location)
OV 5: overflow (location)
OS 4: overflow, stored (location)

Statement List (STL) for S7-300/S7-400


5-4 C79000-G7076-C565-01
Bit Logic Instructions

Change of Bits in Instruction OR STA RLO FC


the Status Word
A x x x 1
AN x x x 1
A( 0 1 – 0
AN( 0 1 – 0
O 0 x x 1
ON 0 x x 1
O( 0 1 – 0
ON( 0 1 – 0
X 0 x x 1
XN 0 x x 1
X( 0 1 – 0
XN( 0 1 – 0
= 0 x – 0
CLR 0 0 0 0
FN 0 x x 1
FP 0 x x 1
NOT – 1 x –
R 0 x – 0
S 0 x – 0
SAVE – – – –
SET 0 1 1 0

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 5-5
Bit Logic Instructions

5.2 Bit Logic Instructions and Relay Coil Circuit

Introduction Bit logic instructions are also named relay logic instructions as they can
execute commands which can replace the function of a relay logic circuit.
The following explains how a relay logic circuit can be reproduced with STL
commands.

Normally Open Figure 5-1 shows a relay logic circuit with normally open control relay
Contact contact between a power rail and a coil. The normal state of this contact is
open. If the contact is not activated, it remains open. The signal state of the
open contact is 0 (not activated). If the contact remains open, the power from
the power rail cannot energize the coil at the end of the circuit. If the contact
is activated (signal state of the contact is 1), power will flow to the coil.

Power Rail

Normally Open
Contact I 1.1

Coil Q 4.0

Figure 5-1 Relay Logic Circuit with Normally Open Control Relay Contact

You can use an And (A) or an Or (O) instruction to check the signal state of a
normally open control relay contact. If the normally open contact (I1.1 = 0)
is open the check result is “0”, if it is closed the result is “1”.

Statement List (STL) for S7-300/S7-400


5-6 C79000-G7076-C565-01
Bit Logic Instructions

Normally Closed Figure 5-2 shows the representation of a relay logic circuit with normally
Contact closed control relay contact between a power rail and a coil. The normal state
of this contact is closed. If the contact is not activated, it remains closed. The
signal state of the closed contact is 0 (not activated). If the contact remains
closed, power from the power rail can cross the contact to energize the coil at
the end of the circuit. Activating the contact (signal state of the contact is 1)
opens the contact, interrupting the flow of power to the coil.

Power Rail

Normally Closed
I 1.1
Contact

Coil Q 4.0

Figure 5-2 Relay Logic Circuit with Normally Closed Control Relay Contact

You can use an And Not (AN) or an Or Not (ON) instruction to check the
signal state of a normally closed control relay contact. If the normally closed
contact is closed (I1.1 = 0) the check result is “1”, if it is open the result is
“0”.

Power Flow in a Figure 5-3 shows an example with a statement list that uses an AND
Series Circuit instruction (A) to program two normally open contacts in series. Only when
the signal state of both the normally open contacts is “1”, can the state of
output Q4.0 be set to “1” and the coil be energized.

Statement List Relay Logic Diagram


Program

A I 1.0 I 1.0

A I 1.1 I 1.1

= Q 4.0 Q 4.0

Figure 5-3 Using the And Instruction to Program Contacts in Series

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 5-7
Bit Logic Instructions

Power Flow in a Figure 5-4 shows a statement list that uses an Or instruction (O) to program
Parallel Circuit each of two normally open contacts connected in parallel to a coil.
Only when the signal state of one of the normally open contacts is “1”, can
the state of output Q4.0 be set to “1” and the coil be energized.

Statement List
Program Relay Logic Diagram

Power
Rail
I 1.0 I 1.1
O I 1.0
O I 1.1
= Q 4.0
Q 4.0

Figure 5-4 Using the Or Instruction to Program Contacts in Parallel

Exclusive Or The Exclusive Or (X) instruction in STL corresponds to a relay logic circuit,
as in Figure 5-5, in which a normally closed contact and a normally open
contact are connected. Q4.0 is “1” when I1.0 and I1.0 have different values.

Statement List
Relay Logic Diagram
Program

Power
Rail

Contact
I 1.0
X I 1.0
X I 1.1
Contact
= Q 4.0 I 1.1

Coil
Q 4.0

Figure 5-5 Using the Exclusive Or instruction to Program Contacts in Parallel

Statement List (STL) for S7-300/S7-400


5-8 C79000-G7076-C565-01
Bit Logic Instructions

AN, ON, XN Similarly the following instructions can affect other actions:

AN: Affects the series


connection of a Statement Relay Logic
normally closed List Program Diagram
contact..
Power Rail

A I 1.0 I 1.0
Normally
Open Contact
AN I 1.1 I 1.1
Normally
Closed Contact

= Q 4.0 Q 4.0
Coil

ON: Affects the parallel


connection of a Statement Relay Logic
normally closed List Program Diagram
contact.
Power Rail

O I 1.0 I 1.0
Normally
Open Contact
ON I 1.1 I 1.1
Normally
Closed Contact
= Q 4.0 Q 4.0
Coil

XN: Affects the


interconnected series Statement Relay Logic
connection of List Program Diagram
a normally closed
contact and a Power Rail
normally open
contact. X I 1.0 I 1.0
Normally
Open Contact

XN I 1.1 I 1.1
Normally
Closed Contact

= Q 4.0 Q 4.0
Coil

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 5-9
Bit Logic Instructions

5.3 Evaluating Conditions Using And, Or, and Exclusive Or

Description With the bit logic instructions you can check the bits of the status word CC 0,
CC 1, BR, OV and OS. These can be influenced by the following instructions
(Table 5-6).

Table 5-6 Instructions That Affect the CC, BR, OV, and OS Bits of the Status
Word
Type of Instruction Instruction Section in
This Manual
Integer Four-Function Math I, I, /I,I, D, D, 9.1
/D,D, MOD
Integer Comparisons ==I, <>I, <I, <=I, >I, >=I, ==D, 11.2
(Integer Math Instructions) <>D, <D, <=D,>D, >=D
Floating-Point Math R, R,R , /R, SQRT, SQR, 10.1
LN, EXP, SIN, COS, TAN,
ASIN, ACOS, ATAN
Floating-Point Comparisons ==R, <>R, <R, <=R, >R, >=R 11.3
Conversion BTI, BTD, RND, RND, 12.1, 12.2,
RND, TRUNC, NEGI, NEGD and 12.4
Shift and Rotate Functions SLW, SRW, SLD, SRD, SSI, 14.1 and 14.2
SSD, RLD, RRD, RLDA, RRDA
Word Logic AW, OW, XOW, AD, OD, XOD 13.2
Nesting ) 5.4
Saving the RLO to BR Register SAVE 5.9
Logic Control JCB, JNB, SPS 16.1
Program Control BEB, BE, BEA, CC, UC 17.6
Transfer T STW 8.3

Statement List (STL) for S7-300/S7-400


5-10 C79000-G7076-C565-01
Bit Logic Instructions

Relationship of a The combination of bits CC 1 and CC 0 in the status word can easily be
Result to 0 checked using “replacement addresses” (for example, >0, ==0, <0, etc.).
Table 5-7 shows the connection between different bit combinations and
simple checking. For example, you can check the combination CC 1 = 0 and
CC 0 = 1 in an And instruction with A <0.
Table 5-7 Combination States of CC 0 and CC 1 and Relevant Check Option

If the following signal combination is in the status ... the check can be
word ... carried out using
Signal State of CC 1 Signal State of CC 0
1 0 >0
0 1 <0
0 1
or or <>0
1 0
1 0
or or >=0
0 0
0 1
or or <=0
0 0
0 0 ==0
1 1 UO

STL Explanation
L +10 //LOWER LIMIT Load the integer 10 into accumulator 1 low as a lower limit.

L MW30 Load the value in memory word MW30 into accumulator 1 low,
transferring the integer value 10 to accumulator 2 low.

<=I Is 10 less than or equal to the value in MW30? If yes, then set
the RLO to 1; otherwise reset the RLO to 0.

L +100 //UPPER LIMIT Load the integer 100 into accumulator 1 low as an upper limit,
transferring the value from MW30 stored in accumulator 1 low to
accumulator 2 low.

–I Subtract 100 from the value in MW30. The result sets CC 1 and
CC 0 with a bit combination that shows how the result compares
to 0 (see Table 5-7). The RLO is not changed.

U <=0 According to the bit combination in CC 1 and CC 0, is the


condition <= 0 fulfilled? Yes produces a 1; no produces a 0
(see Table 5-7). Combine this 1 or 0 with the RLO according to
the And truth table, Store the result in the RLO bit.

= Q 4.0 Write the value of the RLO to the signal state of output Q 4.0.
The coil at output Q 4.0 is energized (has a signal state of 1)
if the value in MW30 is greater than or equal to 10 and less
than or equal to 100.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 5-11
Bit Logic Instructions

The Boolean bit logic instructions can also enable your program to react if
the result of a floating-point math operation is illegal because one of the
numbers is not a valid floating-point number (unordered, UO). The
instruction checks the signal state of bits CC1 and CC0 of the status word
(see Table 5-7).

Overflow and Some of the instructions listed in Table 5-6 can set the binary result bit (BR)
Binary Result or the overflow bits (OV and OS) of the status word to 1. You can use the A,
AN, O, ON, X, and XN bit logic instructions together with the following
memory areas to enable your program to react to an overflow or to a binary
result bit that is set to 1.

STL Explanation
L MW10 Load the integer in MW10 into accumulator 1 low.

L MW20 Load the integer in MW20 into accumulator 1 low, transferring


the value from MW10 to accumulator 2.

+I Add the two integer values in the accumulators.

T MW30 Transfer the result from accumulator 1 low to MW30.

A I 0.0 Check the signal state at input I 0.0 for 1 or 0.

A OV Check the OV bit of the status word for 1 or 0.

= Q 4.0 If the signal state of I 0.0 is 1 and there is a 1 in the OV


bit of the status word (i.e., an overflow occurred during the
last math operation), set the signal state of output Q 4.0 to
1; otherwise set it to 0.

STL Explanation
A BR Check the BR bit of the status word for 1 or 0.

= Q 4.0 If there is a 1 in the BR bit of the status word, set the


signal state of output Q 4.0 to 1; otherwise set it to 0.

Statement List (STL) for S7-300/S7-400


5-12 C79000-G7076-C565-01
Bit Logic Instructions

Addressing the The Boolean bit logic instructions evaluate conditions by using the addresses
Bits of the Status shown in Table 5-8.
Word
Table 5-8 Addresses of Boolean Bit Logic Instructions: Bits of the Status Word

Memory Area or Reference to a Bit(s) of Status Word


Location
>0, <0, <>0, >=0, <=0, ==0 7 and 6: condition codes 1 and 0 (memory area)
UO 7 and 6: condition codes 1 and 0 (memory area)
BR 8: binary result (location)
OV 5: overflow (location)
OS 4: overflow, stored (location)

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 5-13
Bit Logic Instructions

5.4 Nesting Expressions and And before Or

Description You can use the And (A), Or (O), and Exclusive Or (X) instructions and their
negated forms AN, ON, XN to perform Boolean logic operations on portions
of a logic string that are enclosed in parentheses (nesting expressions).
Parentheses around a portion of a logic string indicate that your program will
perform the operations inside the parentheses before performing the logic
operation indicated by the instruction that precedes the nesting expression.
You can also combine And and Or statements in a Boolean logic string
without using parentheses. By convention, the And statements are evaluated
first and the results are then combined according to the Or truth table.

Result of Logic The instruction that opens a nesting expression stores the RLO from the
Operation preceding operation in the nesting stack. Later, the program will combine this
stored RLO with the result produced by the logic combinations performed
inside the parentheses.

STL Description
A( The statements between A( and ) make up a normal Or combina-
O I 0.0 tion. The result of the first check is stored in the RLO bit.

O M 10.0 According to the Or truth table, the result of check is com-


) bined with the RLO formed by the previous statement. This com-
bination forms a new result that replaces the value in the RLO
bit.

A( A( copies the value currently in the RLO bit, stores it in the


nesting stack, and ends the previous logic string. Therefore
the next logic statement begins a new logic string, making a
“first check.”

O I 0.2 The statements between A( and ) make up a normal Or combina-


tion. The result of the first check is stored in the RLO bit.

O M 10.3 According to the Or truth table, the result of check is com-


bined with the RLO formed by the previous statement. This com-
bination forms a new result that replaces the value in the RLO
bit.

) The ) statement combines the RLO that is stored in the nesting


stack (see the A( instruction above) with the current RLO ac-
cording to the And truth table. This statement uses the And
truth table because the ) ends a nesting expression that began
with A. This logic combination forms a new RLO.

A M 10.1 This normal And statement combines the new RLO formed in the )
instruction above with the result of its check according to the
And truth table.

= Q 4.0 The Assign instruction (=, see Section 5.8) assigns the value
of the RLO to the output coil.

Statement List (STL) for S7-300/S7-400


5-14 C79000-G7076-C565-01
Bit Logic Instructions

And before Or The following statement list uses the principle of And before Or to program a
circuit. By convention, the program evaluates the And statements first. Then
the program combines the results of the And operation according to the Or
truth table. No parentheses are needed. The principle at work here is called
“And before Or.”

STL Description
A I 0.0 The result of the first check is stored in the RLO bit.

A M 10.0 According to the And truth table, the result of check is com-
bined with the RLO formed by the previous statement. This com-
bination forms a new result that replaces the value in the RLO
bit.

O The statement O copies the value currently in the RLO bit,


stores it in the Or bit and ends the previous logic string. The
statement “O” secures the RLO as one of the two values that it
will use to carry out an Or operation, according to the princi-
ple “And before Or”.

A I 0.2 The result of the first check is stored in the RLO bit. In each
And operation which follows an Or operation the newly formed
RLO is combined with the Or bit.

A M 0.3 According to the And truth table, the result of check is com-
bined with the RLO formed by the previous statement. This com-
bination forms a new result that replaces the value in the RLO
bit. In each And operation the newly formed RLO is combined
with the Or bit.

The first “O” operation fetches the stored RLO from the nesting
stack and combines it with the current RLO. This operation re-
sults to a new value which is stored in the RLO bit as the re-
sult of an “And before Or” operation. (There is no special op-
eration to end an “And before Or” operation. A special bit pro-
cessor in the programmable controller finds the last A opera-
tion in an “And before Or” operation. The operation that fol-
lows the last A operation (e.g. =, S, R or O) ends the “And
before Or” operation automatically with the estimation of the
RLO.)

O M 10.1 The next “O” operation combines the result of the ”And before
Or” operation with the check result of the second “O” opera-
tion.

= Q 4.0 The Assign instruction (=, see Section 5.8) assigns the value
of the RLO to the output coil.

Output Q 4.0 is energized (its signal state is 1) if the result of either one or
the other pair of And operations is 1 or if the result of the normal Or
operation on M 10.1 is 1.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 5-15
Bit Logic Instructions

5.5 Instructions for Transitional Contacts: FP, FN

Description You can use the Edge Positive (FP) and Edge Negative (FN) instructions like
transition-sensing contacts in a relay circuit. These instructions detect and
react to transitions in the result of logic operation. A transition from 0 to 1 is
called a “positive edge.” A transition from 1 to 0 is called a “negative edge”
(see Figure 5-6).

Positive Edge
RLO Negative Edge
1

0 Time

Figure 5-6 Representation of Positive and Negative Edges

Reacting to a Figure 5-7 shows a statement list that enables your program to react to a
Positive Edge positive edge transition. An explanation follows the figure.

Statement List Signal State Diagram


A I1.0 I 1.0 1
0
FP M 1.0 M 1.0 1
0
= Q 4.0 Q 4.0 1
0

OB1 Scan Cycle No.: 1 2 3 4 5 6 7 8 9

Figure 5-7 Programming a Reaction to a Positive Edge Transition

If the programmable logic controller detects a positive edge at contact I 1.0,


it energizes the coil at Q 4.0 for one OB1 scan cycle. The programmable
logic controller stores the result of the logic operation performed by the A
instruction in edge memory bit M 1.0 and compares it to the RLO from the
previous scan cycle. (In the example in Figure 5-7, the RLO of the statement
“A I 1.0” just happens to be the same as the signal state of input I 1.0. This
will not be the case for every program.) If the current RLO is 1 and the RLO
from the previous scan cycle stored in memory bit M 1.0 is 0, then the FP
statement sets the RLO to 1. The FP statement detects a positive edge at the
contact (that is, the signal state of the RLO changed from 0 to 1). If there is
no change in the RLO (current RLO and previous RLO stored in the edge
memory bit are both equal to 0 or 1), then the FP statement resets the RLO
to 0.

Statement List (STL) for S7-300/S7-400


5-16 C79000-G7076-C565-01
Bit Logic Instructions

Table 5-9 Checking for Positive Edge Transition at Input I 1.0

OB1 Scan Signal State at Signal State at Did the signal Is the coil at
Cycle No. Input in Input in state change Q 4.0
Previous Cycle Current Cycle from 0 to 1? energized?
1 0 0 No No
(default value)
2 0 1 Yes Yes
3 1 1 No No
4 1 0 No No
5 0 0 No No
6 0 1 Yes Yes
7 1 0 No No
8 0 1 Yes Yes
9 1 1 No No

Table 5-9 applies specifically to the statement list program shown in


Figure 5-7. In general, you should consider the transitions detected by FP and
FN to be transitions reflected in the RLO, not in the signal states of contacts.
For example, a logic string can form an RLO that is not directly related to the
signal state of a contact.

Reacting to a Figure 5-8 shows a statement list that enables your program to react to a
Negative Edge negative edge transition. An explanation follows the figure.

Statement List Signal State Diagram


1
A I1.0 I 1.0 0
FN M 1.0 M 1.0 1
0
= Q 4.0 Q 4.0 1
0

OB1 Scan Cycle No.: 1 2 3 4 5 6 7 8 9

Figure 5-8 Programming a Reaction to a Negative Edge Transition

If the programmable logic controller detects a negative edge at contact I 1.0,


it energizes the coil at Q 4.0 for one OB1 scan cycle.
The programmable logic controller stores the result of the logic operation
performed by the A instruction in edge memory bit M 1.0 and compares it to
the RLO from the previous scan cycle (see Table 5-10). (In the example in
Figure 5-8, the RLO of the statement “A I 1.0” just happens to be the same
as the signal state of input I 1.0. This will not be the case for every program.)
If the current RLO is 0 and the RLO from the previous scan cycle stored in
memory bit M 1.0 is 1, then the FN statement sets the RLO to 1.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 5-17
Bit Logic Instructions

The FN statement detects a negative edge at the contact (that is, the signal
state of the RLO changed from 1 to 0). If there is no change in the RLO
(current RLO and previous RLO stored in the edge memory bit are both
equal to 0 or 1), then the FN statement resets the RLO to 0.

Table 5-10 Checking for Negative Edge Transition at Input I 1.0

OB1 Scan Signal State at Signal State at Did the signal Is the coil at
Cycle No. Input in Input in state change Q 4.0
Previous Cycle Current Cycle from 1 to 0? energized?
1 0 0 No No
(default value)
2 0 1 No No
3 1 0 Yes Yes
4 0 0 No No
5 0 1 No No
6 1 1 No No
7 1 1 No No
8 1 0 Yes Yes
9 0 0 No No

Table 5-10 applies specifically to the statement list program shown in


Figure 5-8. In general, you should consider the transitions detected by FP and
FN to be transitions reflected in the RLO, not in the signal states of contacts.
For example, a logic string can form an RLO that is not directly related to the
signal state of a contact.

Addressed Bit The location that the FP or FN instruction addresses is a bit. The instruction
accesses the output through one of the following types of addresses:
 Address identifier (ID) and location within the memory area that is
indicated by the address identifier (see Tables 5-11 and 5-12)
 Bit transferred as a parameter (see Table 5-13)

Statement List (STL) for S7-300/S7-400


5-18 C79000-G7076-C565-01
Bit Logic Instructions

Table 5-11 Addresses of FP and FN: Direct and Indirect Addressing

Address Maximum Address Range According to Addressing Type


ID1 Direct Memory Indirect Area-Internal Register Indirect
I2
[DBD]
Q3 [AR1, P#byte.bit]
0.0 to [DID]
M 0 to 65,532 0.0 to 8,191.7
65,535.7 [LD]
DBX [AR2, P#byte.bit]
[MD]
DIX

1 See the Caution that follows this table.


2 Because the operating system overwrites the process-image input table at the
beginning of every scan cycle, the RLO stored by an FP or FN instruction that uses
an input bit as its address is corrupted. See the Caution that follows this table.
3 Using an output bit as the address of an FP or FN instruction is not recommended. If
you want to influence an output, use the S, R, or = instruction.

Caution
! Corruption of stored result of logic operation.

Can cause minor property damage.

If you use an FP or FN instruction in your program, the memory bit that is


the address of this instruction is used by FP or FN exclusively for its own
storage purposes. Therefore you should not use any instruction that would
change this bit. Otherwise you will corrupt the stored RLO. This caution
applies to all the memory areas indicated in the address identifiers listed in
Table 5-11.

Table 5-12 Addresses of FP and FN: Area-Crossing Register Indirect Addressing

Address Identifier1 Address Range


[AR1, P#byte.bit]
I, Q, M, DBX, or DIX 0.0 to 8,191.7
[AR2, P#byte.bit]

1 The memory area is encoded in AR1 or AR2, respectively (see Section 3.6).

Table 5-13 Addresses of FP and FN: Bit Transferred as Parameter

Address Address Parameter Format


Symbolic name A bit transferred as parameter

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 5-19
Bit Logic Instructions

5.6 Output of Boolean Logic String

Description You can terminate a Boolean bit logic string by using one of the following
three statement list instructions. Each of these instructions can influence a bit
that represents the end of that string.
 Set (S): if the RLO was set to 1 in the previous command, S sets the
signal state of the contact or coil that the instruction addresses to 1;
 Reset (R): if the RLO was set to 1 in the previous command, R resets the
signal state of the contact or coil that the instruction addresses to 0;
 Assign (=): independently of the state of the RLO, the value of the RLO
is assigned to the location that the instruction addresses.

Terminating a A logic string is terminated when the first-check bit (FC bit) is reset. When
Logic String the value in the FC bit is 0, this indicates that the next instruction in the
program is the first instruction of a new logic string (see Section 2.2, First
Check). A Set (S), Reset (R), or Assign (=) instruction terminates a logic
string by resetting the first-check bit (FC bit) to 0. (Conditional jump
instructions also reset the FC bit to 0, see Sections 16.3 through 16.5.)
Logic strings that are started with the instructions A(, AN(, O( etc. must be
terminated with the ) instruction. Because these commands can also be used
in the middle of a logic string, they represent an interruption in the string.
That means that a new logic string is started before the old one is terminated.
To continue the old logic string in the correct order after closing the
commands to be carried out in brackets, the old FC bit (saved by opening the
brackets) is restored again. You can therefore imagine program sections
within brackets as a sort of intermediate calculation which, once completed,
pick up the old thread again.

Statement List (STL) for S7-300/S7-400


5-20 C79000-G7076-C565-01
Bit Logic Instructions

5.7 Set and Reset Instructions: S and R

Description You can use the Set (S) instruction to set the signal state of an addressed bit
to 1. (For information on the S instruction for setting an addressed counter to
a specific value, see Section 7.2).
You can use the Reset (R) instruction to reset the signal state of an addressed
bit to 0. R can also reset an addressed timer or counter to 0 (see Sections 6.3
and 7.2). S and R terminate a logic string (see Section 5.6).

Setting a Bit The S instruction sets the bit that it addresses to 1 if the result of logic
operation from the previous statement is 1 and the master control relay
(MCR) is energized (that is, its signal state is 1). If the MCR is not energized
(its signal state is 0), the addressed bit is not changed. The S instruction
terminates a logic string.
Figure 5-9 illustrates how the S instruction holds the signal state of its
addressed coil Q 4.0 at 1 until the R instruction changes the signal state to 0.
The fact that the signal state of the addressed coil remains at 1 until an
R instruction resets it to 0 indicates the static nature of the S instruction.
In the relay logic diagram, if the normally open contact at input I 1.0 is
activated (its signal state becomes 1), the contact closes. Power flows across
the contact at I 1.0 and across the normally closed contact beneath it,
energizing the coil at output Q 4.0 (the signal state of Q 4.0 becomes 1).
When the coil is energized, the normally open contact at output Q 4.0 across
from I 1.0 is closed. After that, regardless whether the contact at input I 1.0 is
opened or closed, the coil at output Q4.0 remains energized (at signal
state1). The coil keeps itself energized.

Statement List Relay Logic Diagram


A I 1.0
S Q 4.0 Power Rail
A I 1.1
Q 4.0 I 1.1
R Q 4.0 I 1.0
Normally
Open Contact
Signal State Diagrams
1 Normally
I 1.0 0 Closed Contact
1
I 1.1 Q 4.0
0 Coil
1
Q 4.0 0

Figure 5-9 Setting and Resetting a Bit Statically

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 5-21
Bit Logic Instructions

Resetting a Bit The R instruction resets the bit that it addresses to 0 if the result of logic
operation from the previous statement is 1 and the master control relay
(MCR) is energized (that is, its signal state is 1). If the MCR is not energized
(its signal state is 0), the addressed bit is not changed. The R instruction
terminates a logic string.
Figure 5-9 illustrates how the R instruction holds the signal state of its
addressed coil Q 4.0 at 0 regardless of a change in signal state at the contact
that triggered the reset (I 1.1). The fact that the signal state of the addressed
coil remains at 0 until an S instruction resets it to 1 indicates the static nature
of the R instruction.
In the relay logic diagram, the coil at output Q 4.0 that was energized by the
S instruction is de-energized (its signal state becomes 0) by closing the
normally open contact at input I 1.1. Closing contact I 1.1 allows power to
flow to the coil beneath it. This coil opens the normally closed contact above
the coil at Q 4.0, interrupting the flow of power to the coil. Closing contact
I 1.1 triggers the R instruction.

Referenced The address that the S instruction references can be a bit. The address that
Address the R instruction references can be a bit, a timer number, or a counter
number. The addresses can be specified as follows:
 Address identifier (ID) and location within the memory area that is
indicated by the address identifier (see Tables 5-14 through 5-16)
 Bit, timer, or counter transferred as a parameter (see Table 5-17)

Table 5-14 Addresses of S and R: Direct and Indirect Addressing

Address Maximum Address Range According to Addressing Type


ID Direct Memory Indirect Area-Internal Register Indirect
[DBD]
[AR1, P#byte.bit]
I 0.0 to [DID]
0 to 65,532 0.0 to 8,191.7
Q 65,535.7 [LD]
[AR2, P#byte.bit]
[MD]
[DBD]
[AR1, P#byte.bit]
[DID]
M 0.0 to 255.7 0 to 65,532 0.0 to 8,191.7
[LD]
[AR2, P#byte.bit]
[MD]
[DBD]
DBX [AR1, P#byte.bit]
0.0 to [DID]
DIX 0 to 65,532 0.0 to 8,191.7
65,535.7 [LD]
L [AR2, P#byte.bit]
[MD]

Statement List (STL) for S7-300/S7-400


5-22 C79000-G7076-C565-01
Bit Logic Instructions

Table 5-15 Addresses of S and R: Area-Crossing Register Indirect Addressing

Address Identifier1 Maximum Address Range


[AR1, P#byte.bit]
I, Q, M, D, DBX, DIX, or L 0.0 to 8,191.7
[AR2, P#byte.bit]

1 The memory area is encoded in pointer bits 24, 25, and 26 (see Section 3.6).

Table 5-16 Addresses of R: Timers and Counters

Maximum Address Range According to Addressing Type


Address Ident
Identifier
f er
Direct Memory Indirect
[DW]
T1 [DXW]
0 to 65,535 0 to 65,534
C [LW]
[MW]

1 The S instruction that sets an addressed bit to 1 does not apply to timers or counters.
An S instruction used with a counter sets that counter to a specific value. Timers are
started with instructions for specific types of timers (see Sections 6.2, 6.3 and 7.2).

Table 5-17 Address of S and R: Bit, Timer, or Counter Transferred as Parameter

Address Address Parameter Format


Symbolic name A bit, timer,1 or counter transferred as parameter

1 The S instruction does not apply to timers. Timers are started with instructions for
specific types of timers (see Sections 6.2 and 6.3).

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 5-23
Bit Logic Instructions

5.8 Assign Instruction (=)

Description Each Boolean logic operation produces a result known as the “result of logic
operation” (RLO). This RLO is either 1 or 0. In reference to contacts and
coils, a 1 indicates power flow; a 0 indicates no power flow.
You can use the Assign (=) instruction to copy the RLO from the previous
statement in a logic string and assign the RLO as the signal state of the coil
that the = instruction addresses. The = instruction terminates a logic string
(see Section 5.6).

Setting or The value that the = instruction assigns to the coil that it addresses can be 1
Resetting a Bit or 0, depending on the RLO of the statement that preceded the = statement.
Unlike the instructions S and R, the nature of the = instruction is dynamic. It
assigns the RLO as the signal state of the coil that the = instruction addresses.
Figure 5-10 shows how this value changes as the RLO of the statement
“A I 1.0” changes.
In Figure 5-10, the = instruction enables the input signal at the contact I 1.0
to energize or de-energize the coil represented by output Q 4.0 (that is, = sets
or resets the bit represented by Q 4.0 by assigning the RLO of the previous
statement).

Statement List Relay Logic Diagram


A I 1.0 Power
= Q 4.0 Rail

I 1.1
Signal State Diagrams
1
I 1.0 0
Q 4.0
1 Coil
Q 4.0
0

Figure 5-10 Setting and Resetting a Bit Dynamically

Statement List (STL) for S7-300/S7-400


5-24 C79000-G7076-C565-01
Bit Logic Instructions

Addresses The address that the = instruction addresses can be a bit. The instruction
accesses the coil through one of the following addresses:
 Address identifier (ID) and location within the memory area that is
indicated by the address identifier (see Tables 5-18 and 5-19)
 Bit transferred as a parameter (see Table 5-20)

Table 5-18 Addresses of =: Direct and Indirect Addressing

Address Maximum Address Range According to Addressing Type


ID Direct Memory Indirect Area-Internal Register Indirect
[DBD]
[AR1, P#byte.bit]
I 0.0 to [DID]
0 to 65,532 0.0 to 8,191.7
Q 65,535.7 [LD]
[AR2, P#byte.bit]
[MD]
[DBD]
[AR1, P#byte.bit]
0.0 to [DID]
M 0 to 65,532 0.0 to 8,191.7
65,535 [LD]
[AR2, P#byte.bit]
[MD]
[DBD]
DBX [AR1, P#byte.bit]
0.0 to [DID]
DIX 0 to 65,532 0.0 to 8,191.7
65,535.7 [LD]
L [AR2, P#byte.bit]
[MD]

Table 5-19 Addresses of =: Area-Crossing Register Indirect Addressing

Address Identifier1 Maximum Range of Address Parameters


[AR1, P#byte.bit]
I, Q, M, DBX, DIX, or L 0.0 to 8,191.7
[AR2, P#byte.bit]

1 The memory area is encoded in the uppermost 8 bits of AR1 or AR2, respectively.

Table 5-20 Addresses of =: Bit Transferred as Parameter

Address Address Parameter Format


Symbolic name A bit transferred as parameter

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 5-25
Bit Logic Instructions

5.9 Negating, Setting, Clearing, and Saving the RLO

Description You can use one of the following instructions to change the result of logic
operation (RLO) stored in the RLO bit in the status word of the
programmable logic controller (see Section 5.8):

Mnemonic Instruction Meaning


NOT Negate RLO Negating (inverting) the current RLO
SET Set RLO Setting the current RLO to 1
CLR Clear RLO Resetting the current RLO to 0
SAVE Save RLO in BR Register Saving the current RLO to the bit of the
status word

Because these instructions affect the RLO directly, they have no addresses.

Negating the RLO You can use the Negate RLO (NOT) instruction in your program to negate
(invert) the current RLO. If the current RLO is 0, NOT changes it to 1; if the
current RLO is 1, NOT changes it to 0, provided the OR bit is not set. This
instruction is useful for shortening your program, for example by changing
from positive logic to negative logic (see the timer example in Section B.3).

Setting the RLO You can use the Set RLO (SET) instruction in your program if you need to
to 1 set the RLO bit to 1 unconditionally. Figure 5-11 shows how the SET
instruction works in a program.

Clearing the RLO You can use the Clear RLO (CLR) instruction in your program if you need to
to 0 reset the RLO bit to 0 unconditionally. CLR also resets the FC, OR, and STA
bits to 0. As a result, the logic string is ended. Figure 5-11 shows how the
CLR instruction works in a program.

Saving the RLO You can use the Save RLO in BR Register (SAVE) instruction in your
program if you need to save the RLO for future use or if you want to
influence the BR bit of the status word in the programmable logic controller,
for example when you are programming function blocks (FBs) and functions
(FCs) for ladder logic programming boxes.

Instruction Influence on the Bits of the Status Word


BR A1 A0 OV OS OR STA RLO FC
NOT – 1 x –
SET 0 1 1 0
CLR 0 0 0 0
SAVE x

Statement List (STL) for S7-300/S7-400


5-26 C79000-G7076-C565-01
Bit Logic Instructions

Applying SET and The program shown in Figure 5-11 illustrates an application of the SET and
CLR CLR instructions that set and reset a bit unconditionally.

Statement List Signal State Result of Logic Operation (RLO)


SET 1
= M 10.0 1
= M 15.1 1
= M 16.0 1
CLR 0
= M 10.1 0
= M 10.2 0

Figure 5-11 Setting and Resetting a Bit Unconditionally Using SET and CLR

You could use the statements in the program shown in Figure 5-11 in a
start-up organization block (OB). After you power up your programmable
logic controller, it processes the start-up OB with all the instructions that it
contains. After the programmable logic controller has executed all the
instructions, the following memory bits have a specific signal state regardless
of any conditions:
 The signal state of memory bits M 10.0, M 15.1, and M 16.0 is 1.
 The signal state of memory bits M 10.1 and M 10.2 is 0.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 5-27
Bit Logic Instructions

Statement List (STL) for S7-300/S7-400


5-28 C79000-G7076-C565-01
Timer Instructions 6
Chapter Overview Section Description Page
6.1 Overview 6-2
6.2 Location of a Timer in Memory and Components of a Timer 6-3
6.3 Loading, Starting, Resetting, and Enabling a Timer 6-5
6.4 Timer Examples 6-7
6.5 Address Locations and Ranges for Timer Instructions 6-17
6.6 Choosing the Right Timer 6-18

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 6-1
Timer Instructions

6.1 Overview

Definition A timer is a function element of the STEP 7 programming language that


implements and monitors timed sequences. The timer instructions enable
your program to perform the following functions:
 Provide waiting times. For example, after an injection molding procedure,
the mold must remain closed for two seconds. Your program ensures that
two seconds elapse before the part is released from the mold.
 Provide monitoring times. For example, the program monitors the speed
of a motor for 30 seconds after you press the start button.
 Generate pulses. For example, the program provides pulses that cause a
light to flash.
 Measure time. For example, the program can determine how long it takes
for a container to be filled.

Available The statement list representation of the STEP 7 programming language


Instructions provides the following timer instructions:
 Start timer as one of the following types:
– Pulse (SP)
– Extended pulse (SE)
– On-delay (SD)
– Retentive on-delay (SS)
– Off-delay (SF)
 Reset timer (R)
 Enable a timer to start (FR)
 Load timer in one of the following formats:
– Binary (L)
– Binary coded decimal (LC)
 Check the signal state of a timer and combine the result in a Boolean
logic operation (A, AN, O, ON, X, XN) (see Chapter 11).
Figure 6-1 summarizes the instructions that use a timer word as address.

Start timer (SP, SE, SD, SS, SF)

Enable timer (FR) Timer word Reset timer (R)

Check signal state of timer (A, O, X, AN, ON, XN) Load timer (L, LC)

Figure 6-1 Instructions That Can Use a Timer Word as an Address

Statement List (STL) for S7-300/S7-400


6-2 C79000-G7076-C565-01
Timer Instructions

6.2 Location of a Timer in Memory and Components of a Timer

Area in Memory Timers have an area reserved for them in the memory of your CPU. This
memory area reserves one 16-bit word for each timer address. The statement
list instruction set supports 256 timers. To find out how many timer words are
available in your CPU, please refer to the CPU technical data.
The following functions have access to the timer memory area:
 Timer instructions
 Updating of timer words via clock timing. This function decrements a
given time value by one unit at the interval designated by the time base
until the time value is equal to zero.

Time Value Bits 0 through 9 of the timer word contain the time value in binary code. The
time value specifies a number of units. Time updating decrements the time
value by one unit at an interval designated by the time base. Decrementing
continues until the time value is equal to zero. You can load a time value into
the low word of accumulator 1 in binary, hexadecimal, or binary coded
decimal (BCD) format. The time range is from 0 to 9,990 seconds.
You can pre-load a time value using either of the following syntax formats:
 L W#16#wxyz
– Where w = the time base (that is, the time interval or resolution)
– Where xyz = the time value in binary coded decimal format
 L S5T# aH_bbM_ccS_ddMS
– Where a = hours, bb = minutes, cc = seconds, and dd = milliseconds
– The time base is selected automatically and the value is rounded to the
next lower number with that time base.
The maximum time value that you can enter is 9,990 seconds, or
2H_46M_30S.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 6-3
Timer Instructions

Time Base Bits 12 and 13 of the timer word contain the time base in binary code. The
time base defines the interval at which the time value is decremented by one
unit. The smallest time base is 10 ms; the largest is 10 s.

Table 6-1 Time Base and Its Binary Code

Time Base Binary Code for the Time Base


10 ms 00
100 ms 01
1s 10
10 s 11

Because time values are stored with only one time interval, values that are
not exact multiples of a time interval are truncated. Values that have too
much resolution for the desired range are rounded down to achieve the
desired range but not the desired resolution. Table 6-2 shows the possible
resolutions and their corresponding ranges.

Table 6-2 Time Base Resolutions and Ranges

Resolution Range
0.01 second 10MS to 9S_990MS
0.1 second 100MS to 1M_39S_900MS
1 second 1S to 16M_39S
10 seconds 10S to 2HR_46M_30S

Bit Configuration When a timer is started, the contents of accumulator 1 are used as the time
in Accumulator 1 value. Bits 0 through 11 of accumulator 1 low hold the time value in binary
coded decimal format (BCD format: each set of four bits contains the binary
code for one decimal value). Bits 12 and 13 hold the time base in binary code
(see Table 6-1). Figure 6-2 shows the contents of accumulator 1 low loaded
with timer value 127 and a time base of 1 second. (See also Section 8.5.)

15... ...8 7... ...0


x x 1 0 0 0 0 1 0 0 1 0 0 1 1 1

1 2 7

Time base Time value in BCD (0 to 999)


1 second
Irrelevant: These bits are ignored when the timer is started.

Figure 6-2 Contents of Accumulator 1 Low: Timer Value 127, Time Base 1 Second

Statement List (STL) for S7-300/S7-400


6-4 C79000-G7076-C565-01
Timer Instructions

6.3 Loading, Starting, Resetting, and Enabling a Timer

Description To start a timer in your statement list program, include three statements to
trigger the following operations:
 Check a signal state for 0 or 1 (for example, A I 2.1)
 Load a time value and an accompanying time base (for example, L IW0)
 Start a timer as one of the following types:
– Pulse timer (SP, for example, SP T 1)
– Extended pulse timer (SE)
– On-delay timer (SD)
– Retentive on-delay (SS)
– Off-delay (SF)
In your statement list program, a change in the result of logic operation
(RLO) prior to a Start instruction statement starts a timer. A change in the
RLO from 1 to 0 starts an off–delay timer (SF); a change from 0 to 1 starts
any of the other timers. The programmed time and the Start timer statements
must follow the logic operation directly that provides the condition for
starting the timer. Section 6.4 provides examples of the five types of Start
instructions for timers.

Loading Loading a time value as an integer or as a BCD number is described in


Sections 8.4 and 8.5.

The Starting Time Because a timer runs down to zero from a set time, you must provide the
timer with a starting time. When you start a timer in your program, the CPU
looks in accumulator 1 for the starting time. The time range is from 0 to
9,990 seconds.

Example of Figure 6-3 provides an example for starting a pulse timer. A change in signal
Starting a Timer state from 0 to 1 at input I 2.1 starts the timer. Figure 6-3 refers to the
following STL program:

STL Explanation
A I 2.1 Check the signal state of input I 2.1.
L S5T#00H02M23S00MS Load the starting time into accumulator 1.
SP T 1 Start timer T1 as a pulse timer.

Signal state diagram:


1
I 2.1 0
Check I 2.1 for transition 1
from 0 to 1. 0

Timer is started with the starting time given in accumulator 1.

Figure 6-3 Starting a Pulse Timer

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 6-5
Timer Instructions

Resetting a Timer You reset a timer by using the Reset (R) instruction. The CPU resets a timer
when the result of logic operation is 1 immediately before the R instruction
in your program. As long as the RLO that comes before an R instruction
statement is 1, an A, O, or X instruction that checks the signal state of a timer
produces a result of 0 and an AN, ON, or XN instruction that checks the
signal state of a timer produces a result of 1.
Resetting a timer stops the current timing function and resets the time value
to 0.

Enabling a Timer A change in the result of logic operation from 0 to 1 in front of an Enable
for Restart instruction (FR) enables a timer. This change in signal state is always
necessary to enable a timer. The CPU executes the FR instruction only on a
positive signal edge.
Timer enable is not required to start a timer, nor is it required for normal
timer operation. An enable is used only to retrigger a running timer, that is, to
restart the timer. This restarting is possible only when the start operation
continues to be processed with an RLO of 1.

Statement List (STL) for S7-300/S7-400


6-6 C79000-G7076-C565-01
Timer Instructions

6.4 Timer Examples

Introduction Statement list programming offers five types of timers to meet your
automation needs. An example for each type is provided below.

Pulse Timer: SP Figures 6-4 and 6-5 provide examples of a pulse timer. The numbers in
squares in the figures are keyed to explanations that follow Figure 6-4. The
figures refer to the following STL program:

STL Explanation
A I 2.0
FR T 1 Enable timer T 1.
A I 2.1
L S5T#0H2M23S0MS
SP T 1 Start timer T 1 as a pulse timer.
A I 2.2
R T 1 Reset timer T 1.
A T 1
= Q 4.0 Check the signal state of timer T 1.
L T 1
T MW10
LC T 1
T MW12 Load timer T 1.

RLO at Enable input I 2.0


 
RLO at Start input I 2.1
   
RLO at Reset input I 2.2

Timer response
t
Check signal state
of timer output. Q 4.0 

Load timer: L, LC

t = programmed start time

Figure 6-4 Pulse Timer Example, Part 1

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 6-7
Timer Instructions

The following list describes the elements of Figures 6-4 and 6-5:
 A change in the RLO from 0 to 1 at the Start input starts the timer.
The programmed time t then elapses.
 When an RLO of 0 is applied to the Start input, the timer is reset.
 Checking the signal state of output Q 4.0 of the timer results in a
signal state of 1 for the entire duration of the timer operation.
 If an RLO of 1 is applied to the Reset input, the timer is reset. As
long as a signal state of 1 remains at the Start input, a change in the
RLO from 1 to 0 at the Reset input has no influence on the timer.
 A change in the RLO from 0 to 1 at the Start input with the Reset
signal applied causes the timer to start momentarily but to reset
immediately because of the Reset statement that follows directly in
the program (shown as a pulse line in the timing diagram in
Figure 6-4). No checking result is obtained for this pulse, provided
that the sequence of writing the statements as they appear above is
observed.
 A change in the RLO from 0 to 1 at the Enable input while the timer
is running restarts the timer. The time that is programmed is used as
the current time for the restart. A change in the RLO from 1 to 0 at
the Enable input has no effect.

If the RLO changes from 0 to 1 at the Enable input while the timer
is not running and there is still an RLO of 1 at the Start input, the
timer will also be started as a pulse with the time programmed.
A change in the RLO from 0 to 1 at the Enable input while there is
still an RLO of 0 at the Start input has no effect on the timer.



RLO at Enable input I 2.0

RLO at Start input I 2.1

RLO at Reset input I 2.2

Timer response
t t
Check signal state
of timer output. Q 4.0

Load timer: L, LC

t = programmed start time

Figure 6-5 Pulse Timer Example, Part 2

Statement List (STL) for S7-300/S7-400


6-8 C79000-G7076-C565-01
Timer Instructions

Extended Pulse Figures 6-6 and 6-7 provide examples of an extended pulse timer. The
Timer: SE numbers in squares in the figures are keyed to explanations that follow
Figure 6-6. The figures refer to the following STL program:

STL Explanation
A I 2.0
FR T 1 Enable timer T 1.
A I 2.1
L S5T#0H2M23S0MS
SE T 1 Start timer T 1 as an extended pulse timer.
A I 2.2
R T 1 Reset timer T 1.
A T 1
= Q 4.0 Check the signal state of timer T 1.
L T 1 Load timer T 1 (binary coded).
T MW10
LC T 1
T MW12 Load timer T 1 (BCD coded).

RLO at
Enable input I 2.0
     
RLO at
Start input I 2.1
 
RLO at
Reset input I 2.2

Timer
response
t
Check signal state
of timer output Q 4.0 

Load timer: L, LC

t = programmed start time

Figure 6-6 Extended Pulse Timer Example, Part 1

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 6-9
Timer Instructions

The following list describes the elements of Figures 6-6 and 6-7:
 A change in the RLO from 0 to 1 at the Start input starts the timer.
The programmed time t then elapses, regardless of a change in the
RLO from 1 to 0 at the Start input.
 If the RLO changes from 0 to 1 before the time has elapsed, the
timer is retriggered with the time that was programmed originally.
 Checking the signal state of the timer output produces a result of 1
for the entire duration of the timer operation.
 If an RLO of 1 is applied to the Reset input, the timer is reset. As
long as a signal state of 1 remains at the Start input, a change in the
RLO from 1 to 0 at the Reset input has no effect on the timer.
 A change in the RLO from 0 to 1 at the Start input with the Reset
signal applied causes the timer to start momentarily but to reset
immediately because of the Reset statement that follows directly in
the program (shown as a pulse line in the timing diagram in
Figure 6-6). No checking result is obtained for this pulse, provided
that the sequence of writing the statements as they appear above is
observed.
 A change in the RLO from 0 to 1 at the Enable input while the timer
is running restarts the timer. The time that is programmed is used as
the current time for the restart. A change in the RLO from 1 to 0 at
the Enable input has no effect.

If the RLO changes from 0 to 1 at the Enable input while the timer
is not running and there is still an RLO of 1 at the Start input, the
timer will also be started as a pulse with the time programmed.
A change in the RLO from 0 to 1 at the Enable input while there is
still an RLO of 0 at the Start input has no effect on the timer.



RLO at
Enable input I 2.0

RLO at
Start input I 2.1

RLO at
Reset input I 2.2

Timer
response
t t t
Check signal state
of timer output. Q 4.0

Load timer: L, LC

t = programmed start time

Figure 6-7 Extended Pulse Timer Example, Part 2

Statement List (STL) for S7-300/S7-400


6-10 C79000-G7076-C565-01
Timer Instructions

On-Delay Timer: Figures 6-8 and 6-9 provide examples of an on-delay timer. The numbers in
SD squares in the figures are keyed to explanations that follow Figure 6-8. The
figures refer to the following STL program:

STL Explanation
A I 2.0
FR T 1 Enable timer T 1.
A I 2.1
L S5T#0H2M23S0MS
SD T 1 Start timer T 1 as an on-delay timer.
A I 2.2
R T 1 Reset timer T 1.
A T 1
= Q 4.0 Check the signal state of timer T 1.
L T 1
T MW10
LC T 1
T MW12 Load timer T 1.

RLO at
Enable input I 2.0
  
RLO at  
Start input I 2.1
 
RLO at
Reset input I 2.2

Timer 
response
t t
Check signal state
of timer output Q 4.0

Load Timer: L, LC

t = programmed start time

Figure 6-8 On-Delay Timer Example, Part 1

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 6-11
Timer Instructions

The following list describes the elements of Figures 6-8 and 6-9:
 A change in the RLO from 0 to 1 at the Start input starts the timer.
The programmed time t then elapses.
 When an RLO of 0 is applied to the Start input, the timer is reset.
 Checking the signal state of output Q 4.0 of the timer results in a
signal state of 1 when the time has elapsed and the Start input is 1.
 If an RLO of 1 is applied to the Reset input, the timer is reset. As
long as a signal state of 1 remains at the Start input, a change in the
RLO from 1 to 0 at the Reset input has no effect on the timer.
 A change in the RLO from 0 to 1 at the Start input with the Reset
signal applied causes the timer to start momentarily but to reset
immediately because of the Reset statement that follows directly in
the program (shown as a pulse line in the timing diagram in
Figure 6-8). No checking result is obtained for this pulse, provided
that the sequence of writing the statements as they appear above is
observed.
 A change in the RLO from 0 to 1 at the Enable input while the timer
is running restarts the timer. The time that is programmed is used as
the current time for the restart. A change in the RLO from 1 to 0 at
the Enable input has no effect.

If the RLO changes from 0 to 1 at the Enable input following
normal operation of the timer, the timer is not affected
A change in the RLO from 0 to 1 at the Enable input after the timer
was reset and while there is still an RLO of 1 at the Start input starts
the timer. The time that is programmed is used as the current time.



RLO at
Enable input I 2.0

RLO at

Start input I 2.1

RLO at
Reset input I 2.2

Timer
response
t
Check signal state
of timer output. Q 4.0

Load timer: L, LC

t = programmed start time

Figure 6-9 On-Delay Timer Example, Part 2

Statement List (STL) for S7-300/S7-400


6-12 C79000-G7076-C565-01
Timer Instructions

Retentive On-Delay Figures 6-10 and 6-11 provide examples of a retentive on-delay timer. The
Timer: SS numbers in squares in the figures are keyed to explanations that follow
Figure 6-10. The figures refer to the following STL program:

STL Explanation
A I 2.0
FR T 1 Enable timer T 1.
A I 2.1
L S5T#0H2M23S0MS
SS T 1 Start timer T 1 as a retentive on-delay timer.
A I 2.2
R T 1 Reset timer T 1.
A T 1
= Q 4.0 Check the signal state of timer T 1.
L T 1
T MW10
LC T 1
T MW12 Load timer T 1.

RLO at
Enable input I 2.0
  
RLO at
Start input I 2.1
  
RLO at
Reset input I 2.2

Timer
response
t
Check signal state
of timer output Q 4.0 

Load timer: L, LC

t = programmed start time

Figure 6-10 Retentive On-Delay Timer Example, Part 1

The following list describes the elements of Figures 6-10 and 6-11:
 A change in the RLO from 0 to 1 at the Start input starts the timer.
The programmed time t then elapses regardless of a change in the
RLO from 1 to 0 at the Start input.
 Checking the signal state of the timer output results in 1 if the time
has elapsed.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 6-13
Timer Instructions

 The result of checking the signal state of output Q 4.0 changes to 0


only when the RLO at the Reset input is 1.
 If an RLO of 1 is applied to the Reset input, the timer is reset. As
long as a signal state of 1 remains at the Start input, a change in the
RLO from 1 to 0 at the Reset input has no influence on the timer.
 A change in the RLO from 0 to 1 at the Start input with the Reset
signal applied causes the timer to start momentarily but to reset
immediately because of the Reset statement that follows directly in
the program (shown as a pulse line in the timing diagram in
Figure 6-10). No checking result is obtained for this pulse, provided
that the sequence of writing the statements as they appear above is
observed.
 When the RLO at the Enable input changes from 0 to 1 while the
timer is running and the RLO at the Start input of the timer is 1, the
timer is restarted. The time that is programmed is used as the
current time for the restart. A change in the RLO from 1 to 0 at the
Enable input has no effect on the timer.

The timer is not affected when the RLO at the Enable input changes
from 0 to 1 following normal operation of the timer.
When the RLO at the Enable input changes from 0 to 1 while the
timer is running and the RLO at the Start input of the timer is 0, the
timer is not affected.
If the RLO at the Enable input changes from 0 to 1 when the timer
is reset and the RLO at the Start input is still 1, the timer is
restarted. The time that is programmed is used as the current time
for the restart.



RLO at
Enable input I 2.0

RLO at
Start input I 2.1
 
RLO at
Reset input I 2.2

Timer
response
t t t
Check signal state
of timer output. Q 4.0

Load timer: L, LC

t = programmed start time

Figure 6-11 Retentive On-Delay Timer Example, Part 2

Statement List (STL) for S7-300/S7-400


6-14 C79000-G7076-C565-01
Timer Instructions

Off-Delay Timer: Figures 6-12 and 6-13 provide examples of an off-delay timer. The numbers
SF in squares in the figures are keyed to explanations that follow Figure 6-12.
The figures refer to the following STL program:

STL Explanation
A I 2.0
FR T 1 Enable timer T 1.
A I 2.1
L S5T#0H2M23S0MS
SF T 1 Start timer T 1 as an off-delay timer.
A I 2.2
R T 1 Reset timer T 1.
A T 1 Check the signal state of timer T 1.
= Q 4.0
L T 1
T MW10
LC T 1 Load timer T 1.
T MW12

RLO at
Enable input I 2.0
      
RLO at
Start input I 2.1
  
RLO at
Reset input I 2.2

Timer 
response
t  t
Check signal state
of timer output. Q 4.0

Load timer: L, LC

t = programmed start time

Figure 6-12 Off-Delay Timer Example, Part 1

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 6-15
Timer Instructions

The following list describes the elements of Figures 6-12 and 6-13:
 A change in the RLO from 0 to 1 at the Start input causes a change
from 0 to 1 at output Q 4.0 of the timer. A change in the RLO from
1 to 0 at the Start input starts the timer. The programmed time t then
elapses.
 If an RLO of 1 reappears at the Start input, the timer is reset.
 Checking the signal state of output Q 4.0 of the timer results in a
signal state of 1 if the RLO at the Start input is 1 and if the time has
not yet elapsed.
 If an RLO of 1 is applied to the Reset input, the timer is reset.
Checking the signal state of the timer then results in 0. A change in
RLO from 1 to 0 at the Reset input has no influence on the timer.
 A 1 applied to the Reset input while the timer is not running has no
effect on the timer.
 A change in the RLO from 1 to 0 at the Start input while the Reset
signal is applied causes the timer to start momentarily but to reset
immediately because of the Reset statement that follows directly in
the program (shown as a pulse line in the timing diagram in
Figure 6-12). Checking the signal state of the timer then results in 0.

The timer is not affected if the RLO at the Enable input changes
from 0 to 1 while the timer is not running. A change in the RLO
from 1 to 0 also has no effect on the timer.
If the RLO at the Enable input changes from 0 to 1 while the timer
is running, the timer is restarted. The time that is programmed is
used as the current time for the restart.

RLO at Enable input I 2.0

RLO at Start input I 2.1

RLO at Reset input I 2.2

Timer response
t
Check signal state
of timer output. Q 4.0

Load timer: L, LC

t = programmed start time

Figure 6-13 Off-Delay Timer Example, Part 2

Statement List (STL) for S7-300/S7-400


6-16 C79000-G7076-C565-01
Timer Instructions

6.5 Address Locations and Ranges for Timer Instructions

Tables 6-3 and 6-4 show the address types, address locations, and address
ranges for the timer instructions.

Table 6-3 Address Locations, Ranges, and Types for Timer Instructions

Address Range According to Addressing Type


Direct Memory Indirect
[DBW]
[DIW]
0 to 255 0 to 65,534
[LW]
[MW]

Table 6-4 Timer Address transferred as Parameter

Address Address Parameter Format


Symbolic Time transferred as parameter
name

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 6-17
Timer Instructions

6.6 Choosing the Right Timer

Figure 6-14 provides an overview of the five types of timers described in


Section 6.4. This overview is intended to help you choose the right timer for
your timing job.

Input signal I 2.1

Output signal Q 4.0 SP:


(Pulse timer) t
The maximum time that the output signal remains at 1 is the
same as the programmed time value t. The output signal
stays at 1 for a shorter period if the input signal changes to 0.

Output signal Q 4.0 SE:


(Extended pulse t
timer)
The output signal remains at 1 for the programmed length of
time, regardless of how long the input signal stays at 1.

Output signal Q 4.0 SD:


(On-delay timer) t

The output signal changes from 0 to 1 only when the


programmed time has elapsed and the input signal is still 1.

Output signal Q 4.0 SS:


(Retentive t
on-delay timer)
The output signal changes from 0 to 1 only when the
programmed time has elapsed, regardless of how long the
input signal stays at 1.

Output signal Q 4.0 SF:


(Off-delay timer) t
The output signal changes from 0 to 1 when the input signal
changes from 0 to 1. The output signal remains at 1 for the
programmed length of time. The time is started when the input
signal changes from 1 to 0.

Figure 6-14 Choosing the Right Timer

Statement List (STL) for S7-300/S7-400


6-18 C79000-G7076-C565-01
Counter Instructions 7
Chapter Overview Section Description Page
7.1 Overview 7-2
7.2 Setting, Resetting, and Enabling a Counter 7-3
7.3 Couting Up and Counting Down 7-5
7.4 Loading a Count Value as Integer 7-6
7.5 Loading a Count Value in Binary Coded Decimal Format 7-7
7.6 Counter Example 7-8
7.7 Address Locations and Ranges for Counter Instructions 7-10

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 7-1
Counter Instructions

7.1 Overview

Definition A counter is a function element of the STEP 7 programming language that


counts.
Counters have an area reserved for them in the memory of your CPU. This
memory area reserves one 16-bit word for each counter. The statement list
instruction set supports 256 counters. To find out how many counters are
available in your CPU, please refer to the CPU technical data.
Counter instructions are the only functions with access to the memory area
reserved for the counter.

Available The statement list representation of the STEP 7 programming language


Instructions provides the following counter instructions:
 Set (S)
 Reset (R)
 Count up (CU)
 Count down (CD)
 Enable counter (FR)
 Load counter in one of the following formats:
– Binary (L)
– Binary coded decimal (LC)
 Check the signal state of a counter and combine the result in a Boolean
logic operation (A, AN, O, ON, X, XN).
A signal state check with an A, O or X instruction will have the result
“1”, when the value of a counter is greater than “0”.
A signal state check with an A, O or X instruction will have the result
“0”, when the value of the counter is equal to “0”.
Figure 7-1 summarizes the instructions that use a counter word as their
address.

Count Up (CU) Reset a counter (R) Set a counter (S)

Count Down (CD) Counter word Enable a counter (FR)

Check the signal state of a counter Load a count value (L, LC)
(A, AN, O, ON, X, XN)

Figure 7-1 Instructions That Can Use a Counter Word as an Address

Statement List (STL) for S7-300/S7-400


7-2 C79000-G7076-C565-01
Counter Instructions

7.2 Setting, Resetting, and Enabling a Counter

Description To set a counter in your statement list program, include three statements to
trigger the following operations:
 Check a signal state for 0 or 1 (for example, A I 2.3)
 Load a count value (for example, L C# 3) into the low word of
accumulator 1
 Set a counter with the count value you loaded (for example, S C 1). This
operation moves the count value from accumulator 1 to the counter word.
In your statement list program, a change in the result of logic operation
(RLO) from 0 to 1 prior to a Set (S) instruction statement sets a counter to
the programmed count value. The programmed count value and the Set
statements must follow the logic operation directly that provides the
condition for setting the counter.

The Starting Count You set a counter to a specific value by loading that value into the low word
of accumulator 1 and, immediately thereafter, setting that counter. When you
set a counter in your program, the CPU looks in accumulator 1 for the count
value. Then the CPU transfers the count value from the accumulator to the
counter word that you specified in your set statement (for example, S C 1).
The range of the count value is 0 to 999.

Example of Setting Figure 7-2 provides an example for setting a counter. A change in signal state
a Counter from 0 to 1 at input I 2.3 sets the counter. The figure refers to the following
program:

STL Explanation
A I 2.3 Check signal state of input I 2.3.
L C# 3 If the signal state is 1, load count value 3 into
accumulator 1.
S C 1 Set counter C 1 to a count value of 3. This operation
moves the count value of 3 from the accumulator into
counter word 1.

Signal state diagram:


1
I 2.3 0
Check I 2.3 for transition 1
from 0 to 1. 0

Counter is set to the value given in the load instruction.

Figure 7-2 Setting a Counter

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 7-3
Counter Instructions

Resetting a You reset a counter by using the Reset (R) instruction. The CPU resets a
Counter counter when the result of logic operation is 1 immediately before the R
instruction in your program. As long as the RLO that comes before an R
instruction statement is 1, an A, O, or X instruction that checks the signal
state of a counter produces a result of 0 and an AN, ON, or XN instruction
that checks the signal state of a counter produces a result of 1.
When your program resets a counter, it clears the counter, that is, it resets it
to a value of 0.
If a counter is to be reset by a static signal at the Reset (R) and independently
of the RLO of the other counter instructions, you need to write the Reset
statement immediately after the Set, Count Up, or Count Down statement
(see Section 7.3) and before the signal check or load operation.
Programming for counters should adhere to the following sequence (see also
the programming example in Section 7.6):
1. Count up
2. Count down
3. Set counter
4. Reset counter
5. Check signal state of counter
6. Load count value (Read count value)

Enabling a A change in the result of logic operation of the Enable instruction (FR) from
Counter for Restart 0 to 1 enables a counter. The CPU executes the FR instruction only on a
positive signal edge.
A counter enable is not required to set a counter, nor is it required for normal
counting. An enable is only used to set a counter, or to count up or down, if a
positive edge (transition from 0 to 1) in front of the corresponding count
statement is needed, and if the RLO bit in front of the corresponding
statement has a signal state of 1.

Statement List (STL) for S7-300/S7-400


7-4 C79000-G7076-C565-01
Counter Instructions

7.3 Couting Up and Counting Down

Description of In your statement list program, a change in the result of logic operation from
Counting Up 0 to 1 prior to a Count Up (CU) instruction statement increments the counter.
Each time a positive edge change occurs in the RLO directly before a Count
Up instruction, the count is incremented by one unit.
When the count reaches its upper limit of 999, incrementing stops and any
further change in the signal state at the Count Up input have no effect. No
provisions are made for overflow (OV).

STL Explanation
A I 0.1 If there is a positive edge change at input I 0.1,
CU C1 counter C 1 is incremented by 1.

Description of In your statement list program, a change in the result of logic operation from
Counting Down 0 to 1 prior to a Count Down (CD) instruction statement decrements the
counter. Each time a positive edge change occurs in the RLO directly before
a Count Down instruction, the count is decremented by one unit.
When the count reaches its lower limit of 0, decrementing stops and any
further change in the signal state at the Count Down input have no effect.
The counter does not count with negative values.

STL Explanation
A I 0.2 If there is a positive edge change at input I 0.2,
CD C1 counter C 1 is decremented by 1.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 7-5
Counter Instructions

7.4 Loading a Count Value as Integer

Description A count value is stored in a counter word in binary code. You can use the
following instruction to read the binary count value out of a counter word
and load it into the low word of accumulator 1:
L <counter word>
This type of loading is referred to as loading a counter value directly.

STL Explanation
L C 1 Load accumulator 1 low directly with the count value of
counter C 1 in binary format.

Count Value
15 10 9 0
Counter word
XXXXXX
for C 1
15 10 0
Accumulator 1
000000
low

Figure 7-3 Loading a Count Value into Accumulator 1 Using the L Instruction

You can use the value contained in the accumulator as a result of the L
operation for further processing. You cannot transfer a value from the
accumulator to the counter word. If you want to start a counter with a
specific count value, you need to use the appropriate Set counter statement.

Statement List (STL) for S7-300/S7-400


7-6 C79000-G7076-C565-01
Counter Instructions

7.5 Loading a Count Value in Binary Coded Decimal Format

Description A count value is stored in a counter word in binary code. You can use the
following instruction to read the count value in binary coded decimal (BCD)
format out of a counter word and load it into the low word of accumulator 1:
LC <counter word>
This type of loading is referred to as loading a count value in BCD format.
The value contained in the low word of accumulator 1 as a result of the LC
operation has the same format as is needed to set a counter.

STL Explanation
LC C 1 Load accumulator 1 low directly with the count value of
counter C 1 in binary coded decimal format.

Counter word for C 1


15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Count value

Accumulator 1 Binary to BCD


low
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 0 0 0

102 101 100


(Hundreds) (Tens) (Ones)

Count in BCD format

Figure 7-4 Loading a Count Value into Accumulator 1 Using the LC Instruction

The value contained in the accumulator as a result of the LC operation can be


used for further processing, such as transferring the value to the outputs for a
display.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 7-7
Counter Instructions

7.6 Counter Example

Figure 7-5 provides an example of counting up, counting down, setting and
resetting a counter, checking the signal state of a counter, and loading a count
value. The example follows the programming sequence recommended in
Section 7.2. The numbers in squares in the figure are keyed to explanations
that follow the figure. Figure 7-5 refers to the statement list program that
follows the explanatory list.

I 2.0 Enable
  
I 2.1 Count Up
  
I 2.2 Count Down

I 2.3 Set

I 2.4 Reset
3

ÎÎÎ
2 2
1 1 1 1

ÎÎÎ 0
Counter
Response

ÎÎÎ
Check signal 
state of counter
output Q 4.0
ÎÎÎ 3
2 2
MW10 Load
ÎÎÎ 1 1 1 1

ÎÎÎ
0
MW12

Figure 7-5 Example of Counter Instructions

Statement List (STL) for S7-300/S7-400


7-8 C79000-G7076-C565-01
Counter Instructions

The following list describes the elements of Figure 7-5:


 A change in the RLO from 0 to 1 at the Set input sets the counter to
a count value of 3. A transition from 1 to 0 at the Set input has no
effect on the counter.
 A change in the RLO from 0 to 1 at the Count Down input decreases
the counter by one. A transition from 1 to 0 at the Count Down
input has no effect on the counter.
 The result of the signal state check statement A C 1 is 0 when the
count value is 0.
 A change in the RLO from 0 to 1 at the Count Up input increases
the counter by one. A transition from 1 to 0 at the Count Up input
has no effect on the counter.
 If an RLO of 1 is applied at the Reset input, the counter is reset.
Checking the signal state produces a result of 0. A change in the
RLO from 1 to 0 at the Reset input has no effect on the counter.
 A change in the RLO from 0 to 1 at the Count Up input while the
Reset signal is applied causes the counter to increase momentarily
but to reset immediately because of the Reset statement that follows
directly in the program. (The momentary increase is indicated by a
pulse line in the timing diagram in Figure 7-5). Checking the signal
state then produces a result of 0.

A change in the RLO from 0 to 1 at the Enable input with Count Up
and Count Down applied causes the counter to increase momentarily
but then decrease immediately because of the Count Down
statement that follows directly in the program. (The momentary
increase is indicated by a pulse line in the timing diagram in
Figure 7-5). A transition from 1 to 0 at the Enable input has no
effect on the counter.

STL Explanation
A I 2.0
FR C 1 Enable counter C 1.
A I 2.1
CU C 1 Count up (increment by 1).
A I 2.2
CD C 1 Count down (decrement by 1).
A I 2.3
L C# 3
S C 1 Set counter C 1.
A I 2.4
R C 1 Reset counter C.
A C 1
= Q 4.0 Check the signal state of counter C 1.
L C 1 Load counter C 1 (binary coded)
T MW10
LC C 1
T MW12 Load counter C 1 (BCD coded).

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 7-9
Counter Instructions

7.7 Address Locations and Ranges for Counter Instructions

Table 7-1 shows the address types, address locations, and address ranges for
the counter instructions.

Table 7-1 Address Locations, Ranges, and Types for Counter Instructions

Address Range according to Addressing Type


Direct Memory Indirect
[DBW]
[DIW]
0 to 65,535 0 to 65,534
[LW]
[MW]

Statement List (STL) for S7-300/S7-400


7-10 C79000-G7076-C565-01
Load and Transfer Instructions 8
Chapter Overview Section Description Page
8.1 Overview 8-2
8.2 Loading and Transferring 8-3
8.3 Reading the Status Word or Transferring to the Status Word 8-6
8.4 Loading Times and Counts as Integers 8-7
8.5 Loading Times and Counts in Binary Coded Decimal 8-9
Format
8.6 Loading and Transferring between Address Registers 8-11
8.7 Loading Data Block Information 8-12

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 8-1
Load and Transfer Instructions

8.1 Overview

Definition The Load (L) and Transfer (T) instructions enable you to program an
interchange of information between input or output modules and memory
areas, or between memory areas. The CPU executes these instructions in
each scan cycle as unconditional instructions, that is, they are not affected by
the result of logic operation of a statement.

Information The L and T instructions enable an interchange of information between the


Interchange following modules or memory areas:
 Input and output modules and the following areas of memory:
– Process-image input and output tables
– Bit memory
– Timers and counters
– Data areas
 Process-image input and output tables and the following areas of
memory:
– Bit memory
– Timers and counters
– Data areas
 Timers and counters and the following areas of memory:
– Process-image input and output tables
– Bit memory
– Data areas

Method of The L and T instructions provide information exchange via the accumulator.
Interchange An L instruction statement writes (loads) the contents of its addressed source
location into accumulator 1, shifting any information already contained there
to accumulator 2. The old contents of accumulator 2 is overwritten. A
T instruction statement copies the contents of accumulator 1 and writes them
into the memory of its addressed destination. Because the T instruction only
copies the information that is in accumulator 1, this information is still
available to other instructions.
The L and T instructions can handle information in bytes (8 bits), words
(16 bits), and double words (32 bits).
The accumulator has a total of 32 bits. Data with fewer than 32 bits is right
justified in the accumulator. The remaining bits of the accumulator are
padded with zeros.
31 16 15 0
LOAD TRANSFER
Source Destination
Accumulator 1

Statement List (STL) for S7-300/S7-400


8-2 C79000-G7076-C565-01
Load and Transfer Instructions

8.2 Loading and Transferring

Description You can use the Load (L) or Transfer (T) instruction to transfer information
to or from accumulator 1 in chunks of the following sizes:
 Byte (B, 8 bits)
 Word (W, 16 bits)
 Double word (D, 32 bits)
A byte is loaded into the low byte of the low word of accumulator 1. A word
is loaded into the low word of accumulator 1. Unused bytes are reset to 0
when loading into the accumulator.

Immediate The L instruction can address constants of 8, 16, and 32 bits as well as ASCII
Addressing characters. This type of addressing is called immediate addressing (see
Section 3.1 and Table 8-1).

Table 8-1 Addresses of L Instructions: Immediate Addressing

Address Example Explanation


.. L +5 Loads a 16-bit integer constant into accumulator 1.
B#(..,..) L B#(1,10) Loads a contact as 2 bytes into accumulator 1.
(In this example, the 10 goes into the low byte of the low
word of accumulator 1; the 1 goes into the high byte of the
low word of accumulator 1, see Figure 2-4.)
L B#(1,10,5,4) Loads a contact as 4 bytes into accumulator 1.
(In this example, the 4 and the 5 go into the low and high
byte of the low word of accumulator 1, respectively; the 10
and the 1 go into the low and high byte of the high word of
accumulator 1, respectively, see Figure 2-4.)
L#.. L L#+5 Loads a 32-bit integer constant into accumulator 1.
16#.. L B#16#EF Loads an 8-bit hexadecimal constant into accumulator 1.
L W#16#FAFB Loads a 16-bit hexadecimal constant into accumulator 1.
L DW#16#1FFE_1ABC Loads a 32-bit hexadecimal constant into accumulator 1.
2#.. L 2#1111_0000_1111_0000 Loads a 16-bit binary constant into accumulator 1.
L 2#1111_0000_1111_0000_ Loads a 32-bit binary constant into accumulator 1.
1111_0000_1111_0000
’..’ L ’AB’ Loads 2 characters into accumulator 1.
L ’ABCD’ Loads 4 characters into accumulator 1.
C#.. L C#1000 Loads a 16-bit count constant into accumulator 1.
S5TIME#.. L S5TIME#2S Loads a 16-bit S5TIME constant into accumulator 1.
.. L 1.0E+5 Loads a 32-bit IEEE floating point into accumulator 1.
P#.. L P#I1.0 Loads a 32-bit pointer into accumulator 1.
L P##Start Loads a 32-bit pointer to a local variable (Start) into
accumulator 1
L P#ANNA Loads a pointer to a specified parameter in accumulator 1.
(This instruction loads the relative address offset of the
specified parameter. In order to determine the absolute offset
in the instance data block of a function block with multiple
instances, the contents of the AR2 register must be added to
this value.)

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 8-3
Load and Transfer Instructions

Table 8-1 , continuedAddresses of L Instructions: Immediate Addressing, continued

Address Example Explanation


D#.. L D#1994-3-15 Loads a 16-bit date into accumulator 1.
T#.. L T#0D_1H_1M_0S_0MS Loads a 32-bit time value into accumulator 1.
TOD#.. L TOD#1:10:3.3 Loads a 32-bit time-of-day value into accumulator 1.

Direct and Indirect The L and T instructions can address a byte (B), word (W), or double word
Addressing (D) in the following memory areas using direct and indirect addressing (see
also Sections 3.2, 3.3, and 3.5):
 Process-image input and output (address identifiers IB, IW, I, QB, QW,
QD)
 External inputs and outputs (address identifiers PIB, PIW, PID, PQB,
PQW, PQD). External inputs can be addresses of L instructions only;
external outputs can be addresses of T instructions only.
 Bit memory (address identifiers MB, MW, MD)
 Data block (address identifiers DBB, DBW, DBD, DIB, DIW, DID)
 Local data (temporary local data, address identifiers LB, LW, LD)
Table 8-2 lists the addresses for L and T instructions that use direct and
indirect addressing.

Table 8-2 Addresses of L and T Instructions: Direct and Indirect Addressing

Address Maximum Address Range according to Addressing Type


ID Direct Memory Indirect Area-Internal Register Indirect
IB 0 to 65,535
IW 0 to 65,534
ID 0 to 65,532 [DBD]
[AR1, P#byte.bit]
[DID]
0 to 65,532 0 to 8,191
[LD]
[AR2, P#byte.bit]
QB 0 to 65,535 [MD]
QW 0 to 65,534
QD 0 to 65,532
PIB 0 to 65,535
PIW 0 to 65,534
PID 0 to 65,532
[DBD]
(L only) [AR1, P#byte.bit]
[DID]
0 to 65,532 0 to 8,191
[LD]
PQB 0 to 65,535 [AR2, P#byte.bit]
[MD]
PQW 0 to 65,534
PQD 0 to 65,532
(T only)

Statement List (STL) for S7-300/S7-400


8-4 C79000-G7076-C565-01
Load and Transfer Instructions

Table 8-2 Addresses of L and T Instructions: Direct and Indirect Addressing


Address
ID Direct Memory Indirect Area-Internal Register Indirect
[DBD]
MB 0 to 255 [AR1, P#byte.bit]
[DID]
MW 0 to 254 0 to 65,532 0 to 8,191
[LD]
MD 0 to 252 [AR2, P#byte.bit]
[MD]
DBB 0 to 65,535
DBW 0 to 65,534
DBD 0 to 65,532
[DBD]
DIB 0 to 65,535 [AR1, P#byte.bit]
[DID]
DIW 0 to 65,534 0 to 65,532 0 to 8,191
[LD]
DID 0 to 65,532 [AR2, P#byte.bit]
[MD]
LB 0 to 65,535
LW 0 to 65,534
LD 0 to 65,532

Area-Crossing The L and T instructions can address a byte (B), word (W), or double word
Indirect (D) using area-crossing register indirect addressing (see Section 3.6).
Addressing
Table 8-3 Addresses of L and T Instructions: Area-Crossing Register Indirect
Addressing

Address Identifier1 Address Range


[AR1, P#byte.bit]
B (byte), W (word), D (double word) 0 to 8,191
[AR2, P#byte.bit]

1 The memory area is encoded in bits 24 through 31 of AR1 or AR2 (see Section 3.6).

Byte, Word, or For their address, the L and T instructions can also use a byte, word, or
Double Word as double word that is transferred as parameter.
Parameter
Table 8-4 Address of L and T Instructions: Byte, Word, or Double Word
Transferred as Parameter

Address Address Parameter Format


Symbolic name A byte, word, or double word transferred as parameter

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 8-5
Load and Transfer Instructions

8.3 Reading the Status Word or Transferring to the Status Word

Loading the Status You can use the Load (L) instruction to load bits 0 through 8 of the status
Word word (see Figure 8-1) into accumulator 1. Bits 9 through 31 of accumulator
1 are reset to 0. The instruction statement is shown in the example that
follows Figure 8-1.

Note
For the S7-300 series CPUs, the statement L STW does not load the FC,
STA, and OR bits of the status word. Only bits 1, 4, 5, 6, 7, and 8 are loaded
into the corresponding bit positions of the low word of accumulator 1.

215... ...29 28 27 26 25 24 23 22 21 20
BR CC 1 CC 0 OV OS OR STA RLO FC

Figure 8-1 Structure of the Status Word

STL Explanation
L STW Loads bits 0 to 8 of the status word into the low word of
accumulator 1.

Transferring to the You can use the Transfer (T) instruction to transfer the contents of
Status Word accumulator 1 to the status word (see Figure 8-1). The instruction statement
is shown in the following program excerpt.

STL Explanation
T STW Transfers the contents of accumulator 1 to the status
word.

Statement List (STL) for S7-300/S7-400


8-6 C79000-G7076-C565-01
Load and Transfer Instructions

8.4 Loading Times and Counts as Integers

Loading a Time A time value is stored in a timer word in binary code. You can use the
following Load (L) instruction to read the binary time value out of a timer
word and load it into the low word of accumulator 1:
L <timer word>
This type of loading is referred to as loading of a time value directly.
The time value in the timer word is decremented from its starting value to 0
during the processing of the user program in the CPU. When you use the L
instruction with a timer word as address, you get a value that lies between the
starting time of the timer word and 0. The time that elapses from the moment
a timer starts is calculated from the difference of the start time and the time
being read currently.

STL Explanation
L T 1 Load accumulator 1 low directly with the time of timer
T 1 in binary code.

Time
15 10 9 0

Timer word

15 10 9 0
Accumulator 1 low 0000 00

Figure 8-2 Loading a Time Value into Accumulator 1 Using the L Instruction

You can use the value contained in the accumulator as a result of the L
operation for further processing. You cannot transfer a value from the
accumulator to the timer word.

Note
When you use the L instruction to read out a timer word, you get a value
between 0 and 999. You do not get the time base that was loaded with the
time value.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 8-7
Load and Transfer Instructions

Loading a Count A count value is stored in a counter word in binary code. You can use the
following Load (L) instruction to read the binary count value out of a counter
word and load it into the low word of accumulator 1:
L <counter word>
This type of loading is referred to as loading a counter value directly.

STL Explanation
L C 1 Load accumulator 1 low directly with the count value of
counter C 1 in binary format.

Count Value
15 10 9 0
Counter word
XXXXXX
for C 1
15 10 0
Accumulator 1
000000
low

Figure 8-3 Loading a Count Value into Accumulator 1 Using the L Instruction

You can use the value contained in the accumulator as a result of the L
operation for further processing. You cannot transfer a value from the
accumulator to the counter word. If you want to start a counter with a
specific count value, you need to use the appropriate Set counter statement
(see Section 7.2).

Statement List (STL) for S7-300/S7-400


8-8 C79000-G7076-C565-01
Load and Transfer Instructions

8.5 Loading Times and Counts in Binary Coded Decimal Format

Loading a Time in A time value is stored in a timer word in binary code. You can use the
BCD Format following Load (L) instruction to read the time value in binary coded decimal
(BCD) format out of a timer word and load it into the low word of
accumulator 1:
LC <timer word>
In addition to the time value, the time base is also loaded. The value which
appears in the low word of Accumulator 1 as the result the LC instruction,
has the format which is required to start a time. This type of loading is
referred to as loading a time in BCD format.
The time value in the timer word is decremented from its start value to 0.
When you use the LC instruction with a timer word as address, you get a
value that lies between the starting time of the timer word and 0. The time
that elapses from the moment a timer starts is calculated from the difference
of the start time and the time currentlybeing read.

STL Explanation
LC T 1 Load accumulator 1 low with the time and time base of
timer T 1 in BCD format.

Time
15 14 13 12 11 10 9 0

Timer word

Time base Binary to BCD

15 14 13 12 11 0
Accumulator 1 low 0 0

Time 102 101 100


base (Hundreds) (Tens) (Ones)

Figure 8-4 Loading a Count Value into Accumulator 1 Using the L Instruction

The value contained in the accumulator as a result of the LC operation can be


used for further processing, such as transferring the value to the outputs for a
display. You cannot transfer a value from the accumulator to the timer word.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 8-9
Load and Transfer Instructions

Loading a Count in A count value is stored in a counter word in binary code. You can use the
BCD Format following Load (L) instruction to read the count value in binary coded
decimal (BCD) format out of a counter word and load it into the low word of
accumulator 1:
LC <counter word>
This type of loading is referred to as loading a count value in BCD format.
The value contained in the low word of accumulator 1 as a result of the LC
operation has the same format as is needed to set a counter.
A count value is stored in a counter word in binary code. You can load the
time value into the low word of accumulator 1 in binary coded decimal
format (BCD format, see Figure 8-5). You can use the LC instruction to read
out a count value in BCD format.

STL Explanation
LC C 1 Load accumulator 1 low directly with the count value of
counter C 1 in binary coded decimal format.

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Counter word for C 1 X X X X X X

Count value

Binary to BCD

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Accumulator 1 low 0 0 0 0

102 101 100


(Hundreds) (Tens) (Ones)

Count in BCD format

Figure 8-5 Loading a Count Value into Accumulator 1 Using the LC Innstruction

The value contained in the accumulator as a result of the LC operation can be


used for further processing, such as transferring the value to the outputs for a
display. You cannot transfer a value from the accumulator to the counter
word.

Statement List (STL) for S7-300/S7-400


8-10 C79000-G7076-C565-01
Load and Transfer Instructions

8.6 Loading and Transferring between Address Registers

Description Your program can use the following instructions to enable the CPU to
exchange information between address registers or exchange the contents of
the two registers:

Instruction Explanation
LAR1 Loads address register 1 with the contents of the area that the instruc-
tion addresses. If no address is indicated, LAR1 loads address register
1 with the contents of accumulator 1. LAR1 can also use AR2 as an
address, that is LAR1 can load AR1 with the contents of AR2.
LAR2 Loads address register 2 with the contents of the area that the instruc-
tion addresses. If no address is indicated, LAR2 loads address register
2 with the contents of accumulator 1.
TAR1 Transfers the contents of address register 1 into the destination that the
instruction addresses. If no address is indicated, TAR1 transfers the
contents of address register 1 to accumulator 1. TAR1 can also use
AR2 as an address, that is, TAR1 can transfer the contents of AR1 into
AR2.
TAR2 Transfers the contents of address register 2 into the destination that the
instruction addresses. If no address is indicated, TAR2 transfers the
contents of address register 2 to accumulator 1.
TAR Exchanges the contents of AR1 and AR2.

Immediate The LAR1 and LAR2 instructions can address constants of 32 bits. This type
Addressing of addressing is called immediate addressing (see Section 3.1). The
immediate address is used to load a 32-bit pointer immediately into the
address register (see Table 8-5).
LAR1 P#{area,} Byte{.Bit}
with {area} = {I, Q, M, D, DX, L}
Byte = 0 to 65,535
{.Bit} = 0 to 7

Table 8-5 LAR1 and LAR2: Immediate Addressing

Example Description
LAR1 P#I0.0 Loads the area-crossing pointer P#I0.0 into address
register 1
LAR2 P#0.0 Loads the area-internal pointer with the location 0 into
address register 2
LAR1 P##Start Loads an area-crossing pointer to the local variable
(Start) into address register 1

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 8-11
Load and Transfer Instructions

Direct Addressing You can use direct addressing with LAR1, LAR2, TAR1, and TAR2.

Table 8-6 LAR1, LAR2, TAR1, TAR2: Direct Addressing

Instruction Register As Address Address Identifier and Range


LAR1 {BLANK}1) or AR2 DBD
DID
0 to 65 532
65,532
LAR2 {BLANK}1 LD
MD
TAR1 {BLANK}2) or AR2 DBD
DID
LD 0 to 65,532
TAR2 {BLANK}2) MD

1 {BLANK} If no address is indicated, LAR1/LAR2 loads the address register with


the contents of accumulator 1.
2 {BLANK} If no address is indicated, TAR1/TAR2 transfers the contents of the
address register to accumulator 1.

8.7 Loading Data Block Information

You can use the Load (L) instruction to load the length or number of a data
block into accumulator 1. Table 8-7 summarizes the addresses for this type of
loading. For more information on on loading the length or number of a data
block into accumulator 1 see Section 15.3.

Table 8-7 Loading the Length or Number of a Data Block into Accumulator 1

Address Explanation
DBLG Loads the length in bytes of a shared data block into accumulator 1
DILG Loads the length in bytes of an instance data block into accumulator 1
DBNO Loads the number of a shared data block into accumulator 1
DINO Loads the number of an instance data block into accumulator 1

Statement List (STL) for S7-300/S7-400


8-12 C79000-G7076-C565-01
Integer Math Instructions 9
Chapter Overview Section Description Page
9.1 Four-Function Math 9-2
9.2 Adding an Integer to Accumulator 1 9-6

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 9-1
Integer Math Instructions

9.1 Four-Function Math

Description Table 9-1 lists the statement list instructions that you can use to add, subtract,
multiply, and divide integers (16 bits) and double integers (32 bits).

Table 9-1 Four-Function Math Instructions for Integers and Double Integers

Size in Function
Instruction
Bits
Adds the contents of the low words of accumulators 1 and 2
+I 16
and stores the result in the low word of accumulator 1.
Subtracts the contents of the low word of accumulator 1
–I 16 from the contents of the low word of accumulator 2 and
stores the result in the low word of accumulator 1.
Multiplies the contents of the low words of accumulators 1
I 16
and 2 and stores the result (32 bits) in accumulator 1.
Divides the contents of the low word of accumulator 2 by
the contents of the low word of accumulator 1. The result is
/I 16
stored in the low word of accumulator 1. Any whole
remainder is stored in the high word of accumulator 1.
Adds the contents of accumulators 1 and 2 and stores the
+D 32
result in accumulator 1.
Subtracts the contents of accumulator 1 from the contents
–D 32
of accumulator 2 and stores the result in accumulator 1.
Multiplies accumulator 1 by the contents of accumulator 2
D 32
and stores the result in accumulator 1.
Divides the contents of accumulator 2 by the contents of
/D 32
accumulator 1. The result is stored in accumulator 1.
Divides the contents of accumulator 2 by the contents of
MOD 32 accumulator 1 and stores the remainder as a result in
accumulator 1.

Relationship of The function descriptions in Table 9-1 point out that the math operations
Math Operators to combine the contents of accumulators 1 and 2. The result is stored in
Accumulators accumulator 1. The old contents of accumulator 1 is shifted to accumulator 2.
The contents of accumulator 2 remains unchanged.
In the case of CPUs with four accumulators, the contents of accumulator 3 is
then copied into accumulator 2 and the contents of accumulator 4 into
accumulator 3. The old contents of accumulator 4 remains unchanged.

Statement List (STL) for S7-300/S7-400


9-2 C79000-G7076-C565-01
Integer Math Instructions

Combining two The Add Accumulators 1 and 2 As Integer instruction (+I) tells the CPU to
Integers (16 bits) add the contents of the low word of accumulator 1 and the low word of
in CPUs with two accumulator 2 and store the result in the low word of accumulator 1. This
Accumulators operation overwrites the old contents of the low word of accumulator 1. The
old contents of accumulator 2 and the high word of accumulator 1 remain
unchanged (see Figure 9-1). A sample program follows the figure.

Accumulator contents Accumulator contents


before math operation after math operation
Accumulator 2 Accumulator 2
31 16 15 0
IV III IV III

Accumulator 1 +I Accumulator 1
31 16 15 0
II I II III + I

Figure 9-1 Adding Two Integers

Combining two The Add Accumulators 1 and 2 As Integer instruction (+I) tells the CPU to
Integers (16 bits) add the contents of the low word of accumulator 1 and the low word of
in CPUs with four accumulator 2 and store the result in the low word of accumulator 1. This
Accumulators operation overwrites the old contents of the low word of accumulator 1. It
then copies the contents of accumulator 3 to accumulator 2 and the contents
of accumulator 4 to accumulator 3. Accumulator 4 and the high word of
accumulator 1 remain unchanged (see Figure 9-2).

Accumulator contents Accumulator contents


before math operation after math operation

Accumulator 4 Accumulator 4
31 16 15 0
VIII VII VIII VII

Accumulator 3 Accumulator 3
31 16 15 0
VI V VIII VII

Accumulator 2 Accumulator 2
31 16 15 0
IV III VI V

Accumulator 1 +I Accumulator 1
31 16 15 0
II I II III + I

Figure 9-2 Adding two Integers in CPUs with four Accumulators

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 9-3
Integer Math Instructions

STL Explanation
L MW10 Load the value of memory word MW10 into accumulator 1.
Load the value of data word DBW12 into accumulator 1. The
L DBW12 old contents of accumulator 1 are shifted to
accumulator 2.
The CPU interprets the contents of the low words of
+I accumulators 1 and 2 as 16-bit integers, adds them, and
stores the result in the low word of accumulator 1.
Transfer the contents of the low word of accumulator 1
T DBW14 (the result) to data word DBW14.

Evaluating the Bits The math instructions affect the following bits of the status word:
in the Status Word
 CC 1 and CC 0
 OV
 OS

Valid Result A hyphen (–) entered in a bit column of the table means that the bit in
question is not affected by the result of the integer math operation. You can
use the instructions in Table 9-5 to evaluate these bits of the status word

Table 9-2 Signal State of Bits in the Status Word for Integer Math Result
in Valid Range

Valid Rangeg for an Integer


g (16 Bits) and Double Bits of Status Word
Integer (32 Bits) Result CC 1 CC 0 OV OS
0 (zero) 0 0 0 –
I: -32,768 v Result t 0 (negative number)
0 1 0 –
D: -2,147,483,648 v Result t 0 (negative number)
I: 32,767 w Result u0 (positive number)
1 0 0 –
D 2,147,483,647 w Result u0 (positive number)

Table 9-3 Signal State of Bits in the Status Word for Integer Math Result
That Is Not in Valid Range
Invalid Result Range
g Not Valid for a Double Integer
g Result Bits of Status Word
(32 Bits) CC 1 CC 0 OV OS
I: Result u 32,767 (positive number)
1 0 1 1
D: Result u 2,147,483,647 (positive number)
I: t –32,768 (negative number)
0 1 1 1
D: Result t -2,147,483,648 (negative number)

Statement List (STL) for S7-300/S7-400


9-4 C79000-G7076-C565-01
Integer Math Instructions

Table 9-4 Signal State of Bits in the Status Word for Double Integer Math
Instructions +D, /D, and MOD

Bits of Status Word


Instruction
Instruct on
CC 1 CC 0 OV OS
+D: Result = -4,294,967,296 0 0 1 1
/D or MOD: Division by 0 has occurred. 1 1 1 1

Table 9-5 Instructions That Evaluate the CC 1, CC 0, OV, and OS Bits

Instruction Reference to Bit of Bits in Status Word Section in


the Status Word or That Are Evaluated This Manual
Jump Label (indicated by an X)
A,O,X,AN,ON,XN >0, <0, <>0, >=0, <=0, CC 1, CC 0, OV, OS 5.3
==0, UO, OV, OS
JO <jump label> OV 16.4
JOS <jump label> OS 16.4
JUO <jump label> CC 1 and CC 0 16.5
JZ <jump label> CC 1 and CC 0 16.5
JN <jump label> CC 1 and CC 0 16.5
JP <jump label> CC 1 and CC 0 16.5
JM <jump label> CC 1 and CC 0 16.5
JMZ <jump label> CC 1 and CC 0 16.5
JPZ <jump label> CC 1 and CC 0 16.5

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 9-5
Integer Math Instructions

9.2 Adding an Integer to Accumulator 1

Add 16 and 32-Bit You can use the Add Integer Constant instruction to add an integer constant
Integer Constants to the contents of the low word of accumulator 1. Table 9-6 lists the
possibilities. These instructions do not affect the status word bits.

Table 9-6 Adding an Integer to Accumulator 1

Instruction Address Function


+ + integer Adds a 16-bit integer constant to the contents of the low word
of accumulator 1. The result is stored in accumulator 1. The
old contents of the low word of this accumulator are
overwritten. Accumulator 2 and the high word of
accumulator 1 remain unchanged.
+ + L#double integer Adds a 32-bit integer constant to the contents of
accumulator 1. The result is stored in accumulator 1. The old
contents of this accumulator are overwritten. Accumulator 2
remains unchanged.

Examples Below are two programs with Add Integer Constant instructions.

STL Explanation
L MW10 Load the value in MW10 into accumulator 1.
L MW20 Load the value in MW20 into accumulator 1.
+I Add the 16-bit values in accumulator 1 and 2.
+ –5 Add a minus 5 to the result of the +I statement.
T MW14 Transfer the new result to MW14.

STL Explanation
L MD10 Load the value in MD10 into accumulator 1.
L MD16 Load the value in MD16 into accumulator 1.
+D Add the 32-bit values in accumulator 1 and 2.
+ L#–1 Add a minus 1 to the result of the +D statement.
T MD24 Transfer the new result to MD24.

Statement List (STL) for S7-300/S7-400


9-6 C79000-G7076-C565-01
Floating-Point Math Instructions 10
Chapter Overview Section Description Page
10.1 Four-Function Math 10-2
10.2 Forming the Absolute Value of a Floating-Point Number 10-6
10.3 Extended Math Instructions 10-7
10.4 Forming the Square / Square Root of a Floating-Point 10-9
Number
10.5 Forming the Natural Logarithm of a Floating-Point Number 10-11
10.6 Forming the Exponential Value of a Floating-Point Number 10-12
10.7 Forming Trigonometric Functions on Angles Acting as 10-13
Floating-Point Numbers

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 10-1
Floating-Point Math Instructions

10.1 Four-Function Math

Description Table 10-1 lists the statement list instructions that you can use to add,
subtract, multiply, and divide 32-bit IEEE floating-point numbers. Because
IEE 32-bit floating-point numbers belong to the data type called “REAL”,
the mnemonic abbreviation for these instructions is R.

Table 10-1 Four-Function Math Instructions for IEEE 32-Bit Floating-Point


Numbers

Instruction Function
+R Adds the IEEE 32-bit floating-point numbers in accumulators 1 and 2
and stores the 32-bit result in accumulator 1.
-R Subtracts the IEEE 32-bit floating-point number in accumulator 1 from
the IEEE 32-bit floating-point number in accumulator 2 and stores the
32-bit result in accumulator 1.
R Multiplies the IEEE 32-bit floating-point number in accumulator 1 by
the IEEE 32-bit floating-point number in accumulator 2 and stores the
32-bit result in accumulator 1.
/R Divides the IEEE 32-bit floating-point number in accumulator 2 by the
IEEE 32-bit floating-point number in accumulator 1. The 32-bit result is
stored in accumulator 1.

Relationship of The function descriptions in Table 10-1 point out that the math instructions
Math Instructions combine the contents of accumulators 1 and 2. The result is stored in
to Accumulators accumulator 1. The old contents of accumulator 1 is shifted to accumulator 2.
The contents of accumulator 2 remains unchanged.
In the case of CPUs with four accumulators, the contents of accumulator 3 is
copied into accumulator 2 and the contents of accumulator 4 into
accumulator 3. The old contents of accumulator 4 remains unchanged.

Statement List (STL) for S7-300/S7-400


10-2 C79000-G7076-C565-01
Floating-Point Math Instructions

Result of The Add Accumulators 1 and 2 As Real instruction (+R) tells the CPU to add
Combining Two the contents of accumulator 1 and accumulator 2 and store the result in
Integers in CPUs accumulator 1. This operation overwrites the old contents of accumulator 1.
with Two The old contents of accumulator 2 remain unchanged (see Figure 10-1).
Accumulators A sample program follows Figure 10-2.

Accumulator contents Accumulator contents


before math operation after math operation
Accumulator 2 Accumulator 2
31 16 15 0
II II

Accumulator 1 +R Accumulator 1
31 16 15 0
I II + I

Figure 10-1 Adding Two IEEE Floating-Point Numbers

The same pattern applies to the remaining floating-point math instructions.

Table 10-2 Result of Instructions with Denormalized Numbers in CPUs with Two
Accumulators

Instruction Input Value Result


Accumulator 1 Accumulator 2 Accumulator 1 Accumulator 2
+R a b a b
-R a b -a b
*R a b 0 b
+R a b FFFF b

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 10-3
Floating-Point Math Instructions

Result of The Add Accumulators 1 and 2 As Real instruction (+R) tells the CPU to add
Combining Two the contents of accumulator 1 and accumulator 2 and store the result in
Integers in CPUs accumulator 1. This instruction overwrites the old contents of accumulator 1.
with Two Next the contents of accumulator 3 is copied into accumulator 2 and the
Accumulators contents of accumulator 4 is copied into accumulator 3 (see Figure 10-2).

Accumulator contents Accumulator contents


before math instruction after math instruction
Accumulator 4 Accumulator 4
31 16 15 0
IV IV

Accumulator 3 Accumulator 3
31 16 15 0
III IV

Accumulator 2 Accumulator 2
31 16 15 0
II II

Accumulator 1 +R Accumulator 1
31 16 15 0
I II + I

Figure 10-2 Adding Two IEEE Floating-Point Numbers in CPUs with four
Accumulators

The same pattern applies to the remaining floating-point math instructions.

Example
STL Explanation
L MD100 Load the value in memory double word MD100 into accumulator 1.
L DBD4 Load the value in data double word DBD4 into accumulator 1.
The old contents of accumulator 1 are shifted to
accumulator 2. (The values in these double words must be in
floating-point format.)
+R The CPU interprets the contents of accumulators 1 and 2 as
32-bit IEEE floating-point numbers, adds them, and stores the
result in accumulator 1.
T DBD16 Transfer the contents of accumulator 1 (the result) to data
double word DBD16. (DBD16 = MD100 + DBD4)

Bits Affected by The math instructions do affect the following bits of the status word:
the Math  CC 1 and CC 0
Instructions
 OV
 OS
You can use the instructions in Table 10-5 to evaluate these bits of the status
word. Table 10-3 shows the signal states of the status word bits for
floating-point math results that fall within the valid range. A hyphen (–)
entered in a bit column of the table means that the bit in question is not
affected by the result of the floating-point math instruction.

Statement List (STL) for S7-300/S7-400


10-4 C79000-G7076-C565-01
Floating-Point Math Instructions

Table 10-3 Signal State of Bits in the Status Word for Floating-Point
Math Result in Valid Range

Bits of Status Word


Valid
Val d Range for a Float
Floating
ng-Po
Point
nt Result (32 B
Bits)
ts)
CC 1 CC 0 OV OS
+0, -0 (zero) 0 0 0 –
-3.402823E+38 t Result t -1.175494E–38 0 1 0 –
(negative number)
+1.175494E–38 t Result t 3.402823E+38 1 0 0 –
(positive number)

Table 10-4 Signal State of Bits in the Status Word for Floating-Point Math Result
That Is Not in Valid Range

g Not Valid for a Floating-Point


Range g Result Bits of Status Word
(32 Bits) CC 1 CC 0 OV OS
-1.175494E–38 t Result t -1.401298E–45 0 0 1 1
(negative number) Underflow
+1.401298E–45 t Result t +1.175494E–38 0 0 1 1
(positive number) Underflow
Result t -3.402823E+38 0 1 1 1
(negative number) Overflow
Result u -3.402823E+38 1 0 1 1
(positive number) Overflow

Table 10-5 Instructions That Evaluate the CC 1, CC 0, OV, and OS Bits of the
Status Word

Instruction Reference to Bit of Bits in Status Word Section in


Status Word or Jump That Are Evaluated This Manual
Label (indicate d by an X)
A,O,X,AN,ON,XN >0, <0, <>0, >=0, <=0, CC 1, CC 0, OV, OS 5.3
==0, UO, OV, OS
JO <jump label> OV 16.4
JOS <jump label> OS 16.4
JUO <jump label> CC 1 and CC 0 16.4
JZ <jump label> CC 1 and CC 0 16.5
JN <jump label> CC 1 and CC 0 16.5
JP <jump label> CC 1 and CC 0 16.5
JM <jump label> CC 1 and CC 0 16.5
JMZ <jump label> CC 1 and CC 0 16.5
JPZ <jump label> CC 1 and CC 0 16.5

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 10-5
Floating-Point Math Instructions

10.2 Forming the Absolute Value of a Floating-Point Number

Description You can use the Absolute Value of a Real instruction (ABS) to form the
absolute value of an IEEE 32-bit floating-point number in accumulator 1. An
absolute value is a non-negative number equal in numerical value to a given
real number. For an absolute value, a sign (+ or -) is not relevant. For
example, 5 is the absolute value of +5 or -5.

Example The following program provides an example of the ABS instruction:

STL Explanation
L DBD0 Load the value in data double word DBD0 into
accumulator 1.
L +12.3E+00 Load the value +12.3E+00 into accumulator 1. The old
contents of accumulator 1 are shifted to accumulator 2.
/R The CPU divides the contents of accumulator 2 by the
contents of accumulator 1 and stores the result in
accumulator 1.
T MD20 Transfer the contents of accumulator 1 (the result) to
memory double word MD20. (MD20 = DBD0 / 12.3)
NEGR Negate the IEEE floating-point number in accumulator 1
(see Section 12.4).
T MD24 Transfer the result from accumulator 1 to memory double
word MD24. (MD24 = [–1]  MD20)
ABS The CPU forms the absolute value of the IEEE
floating-point number in accumulator 1.
T MD28 Transfer the absolute value from accumulator 1 to memory
double word MD28. (MD28 = ABS[MD20])

Statement List (STL) for S7-300/S7-400


10-6 C79000-G7076-C565-01
Floating-Point Math Instructions

10.3 Extended Math Instructions

Description Table 10-6 lists the STL instructions which can be used for extended math
instructions on floating-point numbers.

ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Table 10-6

ÁÁÁÁÁ
Extended Math Instructions for IEEE 32-Bit Floating-Point Numbers

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Instruction Function

ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
SQRT Calculates the square root of the 32 bit IEEE floating-point number in
ACCU1 and stores the 32 bit result in ACCU1.

ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
SQR Calculates the square of the 32 bit IEEE floating-point number in

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ACCU1 and stores the 32-bit result in ACCU1.

ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
LN Calculates the natural logarithm of the 32 bit IEEE floating-point num-

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ber in ACCU1 and stores the 32-bit result in ACCU1.

ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
EXP Calculates the exponential value of the 32 bit IEEE floating-point num-

ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ber to base E and stores the 32-bit result in ACCU1.

ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
SIN Calculates the sine of the 32 bit IEEE floating-point number in ACCU1
and stores the 32-bit result in ACCU1.

ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
COS Calculates the cosine of the 32 bit IEEE floating-point number in

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ACCU1 and stores the 32-bit result in ACCU1.

ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
TAN Calculates the tangent of the 32 bit IEEE floating-point number in

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ACCU1 and stores the 32-bit result in ACCU1.

ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ASIN Calculates the arc sine of the 32 bit IEEE floating-point number in

ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ACCU1 and stores the 32-bit result in ACCU1.

ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ACOS Calculates the arc cosine of the 32 bit IEEE floating-point number in
ACCU1 and stores the 32-bit result in ACCU1.

ÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁ
ATAN Calculates the arc tangent of the 32 bit IEEE floating-point number in

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ACCU1 and stores the 32-bit result in ACCU1.

Relationship of The extended math instructions only work in conjunction with


Extended Math accumulator 1. The value to which the operation is applied is expected in
Instructions to accumulator 1. The result is stored in accumulator 1; the old contents of
Accumulators accumulator 1 is overwritten. The contents of accumulator 2, accumulator 3
and accumulator 4 remain unchanged.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 10-7
Floating-Point Math Instructions

Effect of Extended The CPU executes the four-function math instructions listed in Table 10-1,
Math Instructions without regard to, and without affecting the result of logic operation. The
on the Bits in the extended math instructions do affect the following bits of the status word:
Status Word
 CC 1 and CC 0
 OV
 OS
To evaluate these bits, you can use the instructions in Table 10-7 (Section
10.1) and see Section 5.3.

Table 10-7 Extended Math Instructions for 32-Bit IEEE Floating-Point

ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
Numbers

ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ ÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ ÁÁÁÁÁ
Instruction

ÁÁÁÁÁÁ
ÁÁÁÁÁ
Reference to Bit of Bits in Status Word
Status Word or Jump That Are Evaluated
Section in
This

ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
Label (indicated by an X) Manual

ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
A, O, X, AN, ON, XN >0, <0, <>0, >=0, <=0, CC 1, CC 0, OV, OS 5.3

ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
==0, UO, OV, OS

ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
JO <jump label> OV 16.4

ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
JOS <jump label> OS 16.4

ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
JUO <jump label> CC 1 and CC 0 16.4

ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
JZ <jump label> CC 1 and CC 0 16.5

ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
JN <jump label> CC 1 and CC 0 16.5

ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
ÁÁÁÁÁ
JP <jump label> CC 1 and CC 0 16.5

ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ ÁÁÁÁÁÁ
JM

ÁÁÁÁÁÁÁ ÁÁÁÁÁ
ÁÁÁÁÁÁ
JMZ
ÁÁÁÁÁ
<jump label>
<jump label>
CC 1 and CC 0
CC 1 and CC 0
16.5
16.5

ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁ
ÁÁÁÁÁÁ
JPZ
ÁÁÁÁÁ <jump label> CC 1 and CC 0 16.5

Statement List (STL) for S7-300/S7-400


10-8 C79000-G7076-C565-01
Floating-Point Math Instructions

10.4 Forming the Square / Square Root of a Floating-Point Number

Description The instruction SQR (square) calculates the square of the 32 bit IEEE
floating-point number in accumulator 1 and stores the 32-bit result in
accumulator 1. The operation SQR overwrites the old contents of
accumulator 1; the contents of accumulator 2, accumulator 3, and
accumulator 4 remain unchanged.
The instruction SQRT (square root) calculates the square root of the 32 bit
IEEE floating-point number in accumulator 1 and stores the 32-bit result in
accumulator 1. The input value must be greater or equal to zero. The
instruction SQRT overwrites the old contents of accumulator 1; the contents
of accumulator 2, accumulator 3, and accumulator 4 remain unchanged.
This instruction gives a positive result when all the addresses are greater than
zero (“0”). The only exception: the Square Root of -0 is -0.

Table 10-8 Effects of Instruction SQR on Bits CC 1, CC 0, OV and OS

Effects on Bits Result in Accumulator 1 CC 1 CC 0 OV OS


CC 1, CC 0, OV + qNaN 1 1 1 1
and OS of the
Status Word + Infinite (Overflow) 1 0 1 1
+ Valid 1 0 0 –
+ Not valid (Underflow) 0 0 1 1
+ Null 0 0 0 –
- qNaN 1 1 1 1

Example The following program extract is an example of how the instruction SQR is
used.

ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
STL Explanation

ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
OPN DB17 Open data block DB17. (It is assumed that it contains the input
value and will store the result).

ÁÁÁÁÁÁÁÁÁ
L DBD0
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Load the value in data double word DBD0 into accumulator 1.
(The value in this double word must be in floating-point for-

ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
mat.)

ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
SQR Calculate the square of the 32 bit IEEE floating-point number.
Store the result in accumulator 1.

ÁÁÁÁÁÁÁÁÁ
AN OV
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁ
JC OK
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Check that the status bit OV is 0.
If operation SQR has no errors, jump tothe label OK

ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
... (In the event of an error an appropriate reaction takes place

ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
at this point.)
OK: T DBD4 Transfer the result of accumulator 1 to data double word DBD4.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 10-9
Floating-Point Math Instructions

Table 10-9 Effects of Instruction SQRT on Bits CC 1, CC 0, OV and OS

Result in Accumulator 1 CC 1 CC 0 OV OS
+ qNaN 1 1 1 1
+ Infinite (Overflow) 1 0 1 1
+ Valid 1 0 0 –
+ Not valid (Underflow) 0 0 1 1
+ Zero 0 0 0 –
-Zero 0 0 0 –
- qNaN 1 1 1 1

Example The following program extract is an example of how the instruction SQRT is
used.

STL Explanation
L MD10 Load the value in memory double word MD10 into accumulator 1.
(The value must be in floating-point format.)
SQRT Form the square root of the 32 bit IEEE floating-point number
in accumulator 1. Store the result in accumulator 1.
AN OV Check that the status bit OV is 0.
JC OK If operation SQR has no errors, jump to the label OK.
(In the event of an error an appropriate reaction takes place
... at this point.)
OK: T MD20 Transfer the result (accumulator 1) in the memory double word
MD20.

Statement List (STL) for S7-300/S7-400


10-10 C79000-G7076-C565-01
Floating-Point Math Instructions

10.5 Forming the Natural Logarithm of a Floating-Point Number

Description The instruction LN (natural logarithm) calculates the natural logarithm of the
floating-point number in accumulator 1 and stores the 32-bit result in
accumulator 1. The input value must be greater than zero (0). The instruction
LN overwrites the old contents of accumulator 1; the contents of
accumulator 2, accumulator 3, and accumulator 4 remain unchanged.

Effects on Bits Table 10-10 shows the effects that the instruction LN has on the signal state
CC 1, CC 0, OV of bits CC 1, CC 0, OV and OS of the status word. A hyphen (-) entered in a
and OS of the bit column of the table means that the bit in question is not affected by the
Status Word result of the floating-point math instruction.

Table 10-10 Effects of Instruction LN on Bits CC 1, CC 0, OV and OS

Result in Accumulator 1 CC 1 CC 0 OV OS
+ qNaN 1 1 1 1
+ Infinite (Overflow) 1 0 1 1
+ Valid 1 0 0 –
+ Not valid (Underflow) 0 0 1 1
+ Zero 0 0 0 –
-Zero 0 0 0 –
- Not valid (Underflow) 0 0 1 1
- Valid 0 1 0 –
- Infinite (Overflow) 0 1 1 1
- qNaN 1 1 1 1

Example The following program extract is an example of how the instruction LN is


used.

ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
STL Explanation

ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L MD10 Load the value from memory double word MD10 into accumulator 1.

ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(The value must be in floating-point format.)
LN Form the natural logarithm of the 32 bit IEEE floating-point

ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
number in accumulator 1. Store the result in accumulator 1.

ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
AN OV Check that the status bit OV is 0.

ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
JC OK If operation SQR has no errors, jump to the label OK.

ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
... (In the event of an error an appropriate reaction takes place

ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
at this point.)
OK: T MD20 Transfer the result from accumulator 1 to memory double word

ÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
MD20.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 10-11
Floating-Point Math Instructions

10.6 Forming the Exponential Value of a Floating-Point Number

Description The instruction EXP (exponential value to base E) calculates the exponential
value of the 32 bit IEEE floating-point number in accumulator 1 to base E
(=2.71828) and stores the 32-bit result in accumulator 1. The input value
must be greater than zero (0). The operation EXP overwrites the old contents
of accumulator 1; the contents of accumulator 2, accumulator 3, and
accumulator 4 remain unchanged.

Effects on Bits Table 10-11 shows the effects that the instruction EXP has on the signal state
CC 1, CC 0, OV of bits CC 1, CC 0, OV and OS of the status word. A hyphen (-) entered in a
and OS of the bit column means that the bit in question is not affected by the result of the
Status Word floating-point math instruction.

Table 10-11 Effects of Instruction EXP on Bits CC 1, CC 0, OV and OS of the Status


Word

Result in Accumulator 1 CC 1 CC 0 OV OS
+ qNaN 1 1 1 1
+ Infinite (Overflow) 1 0 1 1
+ Valid 1 0 0 –
+ Not Valid (Underflow) 0 0 1 1
+ Zero 0 0 0 –
- qNaN 1 1 1 1

Example The following program extract is an example of how the instruction EXP is
used.

ÁÁÁÁÁÁÁÁ
STL
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Explanation

ÁÁÁÁÁÁÁÁ
L MD10
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
Load the value from memory double word MD10 into accumulator 1.

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(The value must be in floating-point format.)

ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
EXP Form the exponential value on basis E of the 32 bit IEEE float-
ing-point number in accumulator 1. Store the result in accumu-

ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
lator 1.

ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
AN OV Check that the status bit OV is 0.

ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
JC OK If operation EXP has no errors, jump to the label OK.

ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
... (In the event of an error an appropriate reaction takes place
at this point.)

ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
OK: T MD20

ÁÁÁÁÁÁÁÁ
Transfer the result from accumulator 1 to memory double word

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
MD20.

Statement List (STL) for S7-300/S7-400


10-12 C79000-G7076-C565-01
Floating-Point Math Instructions

10.7 Forming Trigonometric Functions on Angles Acting as


Floating-Point Numbers

Description Using the following instructions you can form trigonometric functions on
angles acting as 32 bit IEEE floating-point numbers. The 32-bit result is
stored in accumulator 1; the contents of accumulator 2, accumulator 3 and
accumulator 4 remain unchanged.

Instr. Function
SIN Form the sine of the floating-point number of an angle expressed in radians.
Store the angle as a floating-point number in ACCU1.
ASIN Form the arc sine of a floating-point number in ACCU1. The result is an
angle expressed in radians. The value will be in the following range:
/ 2  cosecant (ACCU 1)  +  / 2,when  = 3.14...
COS Form the cosine of the floating-point number of an angle expressed in
radians. Store the angle as a floating-point number in ACCU1.
ACOS Form the arc cosine of a floating-point number in ACCU1. The result is an
angle expressed in radians. The value will be in the following range:
0  secant (ACCU 1)  + , when  = 3.14...
TAN Form the tangent of the floating-point number of an angle expressed in
radians. Save the angle as a floating-point number in ACCU1.
ATAN Form the arc tangent of a floating-point number in ACCU1. The result is an
angle expressed in radians. The value will be in the following range:
/ 2  cotangent (ACCU 1)  +  / 2, when  = 3.14...

Effects on Bits Table 10-12 shows the effect that the instructions SIN, ASIN, COS, ACOS
CC 1, CC 0, OV and ATAN have on the signal state of bits CC 1, CC 0, OV and OS in the
and OS of the status word. Table 10-13 shows how TAN affects these bits. A hyphen (–)
Status Word means that the bit in question is not affected by the instruction.

Table 10-12 Effects of Instructions SIN, ASIN, COS, ACOS and ATAN

Result in Accumulator 1 CC 1 CC 0 OV OS
+ qNaN 1 1 1 1
+ Valid 1 0 0 –
+ Infinite (Overflow) 0 0 1 1
+ Zero 0 0 0 –
-Zero 0 0 0 –
- Not valid (Underflow) 0 0 1 1
- Valid 0 1 0 –
- qNaN 1 1 1 1

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 10-13
Floating-Point Math Instructions

Table 10-13 Effects of Instruction TAN on Bits CC 1, CC 0, OV and OS

Result in Accumulator 1 CC 1 CC 0 OV OS
+ qNaN 1 1 1 1
+ Infinite (Overflow) 1 0 1 1
+ Valid 1 0 0 –
+ Not valid (Underflow) 0 0 1 1
+ Zero 0 0 0 –
-Zero 0 0 0 –
–-Not valid (Underflow) 0 0 1 1
-Valid 0 1 0 –
- Infinite (Overflow) 0 1 1 1
- qNaN 1 1 1 1

Example The following program extract is an example of how the instruction SIN is
used.

ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
STL Explanation

ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
L MD10 Load the value from memory double word MD10 into accumulator 1.

ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(The value must be in floating-point format.)

ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
SIN Form the sine of the 32 bit IEEE floating-point number into
accumulator 1. Store the result in accumulator 1.

ÁÁÁÁÁÁÁÁ
T MD20
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
Transfer the result from accumulator 1 into memory double word

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
MD20.

Example The following program extract is an example of how the instruction ASIN is
used.

ÁÁÁÁÁÁÁÁ
STL
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Explanation

ÁÁÁÁÁÁÁÁ
L MD10
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
Load the value from memory double word MD10 into accumulator 1.

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
(The value must be in floating-point format.)

ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ASIN Form the cosecant of the 32 bit IEEE floating-point number in

ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
accumulator 1. Store the result in accumulator 1.

ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
AN OV Check that the status bit OV is 0.
JC OK If operation ASIN has no errors, jump to the label OK.

ÁÁÁÁÁÁÁÁ
...
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
(In the event of an error an appropriate reaction takes place

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
at this point.)

ÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
OK: T MD20 Transfer the result from accumulator 1 into memory double word
MD20.

Statement List (STL) for S7-300/S7-400


10-14 C79000-G7076-C565-01
Floating-Point Math Instructions

Evaluating the Bits The extended math instructions affect the following bits in the status word:
in the Status Word
 CC 1 and CC 0
 OV
 OS

Valid Result A hyphen (–) entered in a bit column of the table means that the bit in
question is not affected by the result of the floating-point math instruction.

Table 10-14 Inverse Functions for 32 Bit IEEE Floating-Point Numbers and Valid

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
Ranges for the Value Input

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁ
Valid Range for a Floating-Point Result (32 Bits) Bits of Status Word

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ +0, -0 (zero)
CC 1 CC 0
0 0
OV
0
OS

-3.402823E+38 t Result t -1.175494E–38 0 1 0 –
(negative number)
+1.175494E–38 t Result t 3.402823E+38 1 0 0 –
(positive number)

Table 10-15 Signal States of the Bits in the Status Word: Calculation Result with

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁ
Floating-Point Numbers outside the Valid Range

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁ
Valid Range for a Floating-Point Result (32 Bits) Bits of Status Word

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
-1.175494E–38 t Result t -1.401298E–45
(negative number) Underflow
CC 1 CC 0
0 0
OV
1
OS
1

+1.401298E–45 t Result t +1.175494E–38 0 0 1 1


(positive number) Underflow
Result t -3.402823E+38 0 1 1 1
(negative number) Overflow
Result u -3.402823E+38 1 0 1 1
(positive number) Overflow

Table 10-16 Signal States of the Bits in the Status Word: The Input Value Represents

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁ
ÁÁÁ
an Invalid Number or is outside the Valid Range

ÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
Valid Range for a Floating-Point Result (32 Bits)

ÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ
Bits of Status Word
CC 1 CC 0 OV OS

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁÁ ÁÁÁ
ÁÁÁ
ÁÁÁ
ÁÁ
There is no valid 32-bit IEEE floating-point number 1 1 1 1
in ACCU 1.

ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ
ÁÁÁ
ÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁÁ ÁÁÁ
ÁÁÁ ÁÁÁ
Instruction not permitted: the input value in ACCU 1

ÁÁÁ
ÁÁÁ
is outside the valid range.
1 1 1 1

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 10-15
Floating-Point Math Instructions

Statement List (STL) for S7-300/S7-400


10-16 C79000-G7076-C565-01
Comparison Instructions 11
Chapter Overview Section Description Page
11.1 Overview 11-2
11.2 Comparing Two Integers 11-3
11.3 Comparing Two Floating-Point Numbers 11-5

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 11-1
Comparison Instructions

11.1 Overview

You can use the Compare instructions to compare the following pairs of
numeric values:
 Two integers (16 bits)
 Two double integers (32 bits)
 Two real numbers (IEEE floating-point, 32 bits)
You load the numeric values into accumulators 1 and 2. A Compare
instruction compares the value in accumulator 2 to the value in
accumulator 1 according to the criteria listed in Table 11-1.
The result of the comparison is a binary digit, that is, either a 1 or a 0. A 1
indicates that the result of the comparison is true; a 0 indicates that the result
of the comparison is false (see Table 11-2). This result is stored in the result
of logic operation bit (RLO bit, see Section 3.4). You can use this result in
your program for further processing.
When the CPU executes a Compare instruction, it also sets bits in the status
word. Other statement list instructions can evaluate the bits of the status
word. The CPU executes Compare instructions without regard to the result of
logic operation.

Table 11-1 Criteria for Comparisons

Type of Numeric Value in Comparison Criterion Symbol(s) for Instruction Type of Numeric Value
Accumulator 2 in Accumulator 1
is equal to ==I
==D
==R
is not equal to <>I
<>D
<>R

Integer (16 bits) is greater than >I Integer (16 bits)


>D
g ((32 bits))
Double integer >R g ((32 bits))
Double integer
is less than <I
Real number <D Real number
(floating-point, 32 bits) <R (floating-point, 32 bits)

is greater than or equal to >=I


>=D
>=R
is less than or equal to <=I
<=D
<=R

Statement List (STL) for S7-300/S7-400


11-2 C79000-G7076-C565-01
Comparison Instructions

11.2 Comparing Two Integers

Description The Compare Integer instructions compare two single integers (16 bits each)
and the Compare Double Integer instructions compare two double integers
(32 bits each) according to the criteria listed in Table 11-2. A sample
program follows Table 11-3.

Table 11-2 Compare Integer and Compare Double Integer Instructions

Instruction
Instruct on Explanation
Explanat on
==I The integer in the low word of accumulator 2 is equal to the integer in the low word of
accumulator 1.
==D The double integer in accumulator 2 is equal to the double integer in accumulator 1.
<>I The integer in the low word of accumulator 2 is not equal to the integer in the low word of
accumulator 1.
<>D The double integer in accumulator 2 is not equal to the double integer in accumulator 1.
>I The integer in the low word of accumulator 2 is greater than the integer in the low word of
accumulator 1.
>D The double integer in accumulator 2 is greater than the double integer in accumulator 1.
<I The integer in the low word of accumulator 2 is less than the integer in the low word of
accumulator 1.
<D The double integer in accumulator 2 is less than the double integer in accumulator 1.
>=I The integer in the low word of accumulator 2 is greater than or equal to the integer in the
low word of accumulator 1.
>=D The double integer in accumulator 2 is greater than or equal to the double integer in accumulator 1.
<=I The integer in the low word of accumulator 2 is less than or equal to the integer in the
low word of accumulator 1.
<=D The double integer in accumulator 2 is less than or equal to the double integer in accumulator 1.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 11-3
Comparison Instructions

Setting Bits CC 1 A Compare Integer or Compare Double Integer instruction sets certain
and CC 0 of the combinations in the CC 1 and CC 0 bits to indicate what condition has been
Status Word fulfilled (see Table 11-3).

Table 11-3 Settings of Bits CC 1 and CC 0 after a Compare Instruction

Possible check
Condition Signal states of CC 1 and CC 0:
with the instructions
CC 1 CC 0 A, O, X, AN, ON, XN
ACCU 2 > ACCU 1 1 0 >0
ACCU 2 < ACCU 1 0 1 <0
ACCU 2 = ACCU 1 0 0 ==0
0 1
ACCU 2 <> ACCU 1 or or <>0
1 0
1 0
ACCU 2 >= ACCU 1 or or >=0
0 0
0 1
ACCU 2 <= ACCU 1 or or <=0
0 0

Example The following sample program shows how the Compare instructions for
integers (16 bits) work.

STL Explanation
L MW10 Load the contents of memory word MW10 into accumulator 1.

L IW0 Load the contents of input word IW0 into accumulator 1. The
old contents of accumulator 1 are shifted to accumulator 2.

==I Compare the value in the low word of accumulator 2 to the


value in the low word of accumulator 1 to see if they are
equal.

= Q 4.0 Output Q 4.0 will be energized if MW10 and IW0 are equal.

>I Compare the value in the low word of accumulator 2 to see


if it is greater than the value in the low word of
accumulator 1.

= Q 4.1 Output Q 4.1 will be energized if MW10 is greater than IW0.

<I Compare the value in the low word of accumulator 2 to see


if it is less than the value in the low word of
accumulator 1.
= Q 4.2
Output Q 4.2 will be energized if MW10 is less than IW0.

Statement List (STL) for S7-300/S7-400


11-4 C79000-G7076-C565-01
Comparison Instructions

11.3 Comparing Two Floating-Point Numbers

Description The Compare Floating-Point Number instructions compare two 32-bit IEEE
floating-point numbers according to the criteria listed in Table 11-4. Because
IEE 32-bit floating-point numbers belong to the data type called “REAL,”
the mnemonic abbreviation for these instructions is R.

Table 11-4 Compare Real Instructions (IEEE 32-bit Floating-Point Numbers)

Instruction
Instruct on Explanation
Explanat on
==R The IEEE 32-bit floating-point number in accumulator 2 is equal to the
IEEE 32-bit floating-point number in accumulator 1.
<>R The IEEE 32-bit floating-point number in accumulator 2 is not equal to
the IEEE 32-bit floating-point number in accumulator 1.
>R The IEEE 32-bit floating-point number in accumulator 2 is greater than
the IEEE 32-bit floating-point number in accumulator 1.
<R The IEEE 32-bit floating-point number in accumulator 2 is less than the
IEEE 32-bit floating-point number in accumulator 1.
>=R The IEEE 32-bit floating-point number in accumulator 2 is greater than
or equal to the IEEE 32-bit floating-point number in accumulator 1.
<=R The IEEE 32-bit floating-point number in accumulator 2 is less than or
equal to the IEEE 32-bit floating-point number in accumulator 1.

Setting Bits of the A Compare Real number instruction sets certain combinations in the CC 1,
Status Word CC 0, OV, and OS bits of the status word to indicate what condition has been
fulfilled.

Table 11-5 Settings of Bits of the Status Word after a Compare Real Instruction
(IEEE 32-bit Floating-Point Numbers)

Condition CC 1 CC 0 OV OS
== 0 0 0 not applicable
0 1
<> or or 0 not applicable
1 0
> 1 0 0 not applicable
< 0 1 0 not applicable
1 0
>= or or 0 not applicable
0 0
0 1
<= or or 0 not applicable
0 0
UO 1 1 1 1

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 11-5
Comparison Instructions

Evaluating the Bits Other statement list instructions can evaluate the bits of the status word (see
of the Status Word Section 5.3 and Table 11-6).

Table 11-6 Instructions That Evaluate the CC 1, CC 0, OV, and OS Bits


of the Status Word

Instruction Reference to Bits of the Status Word or Jump Section in


Label this Manual
A,O,X,AN,ON,XN >0, <0, <>0, >=0, <=0, ==0, UO, OV, OS 5.3
JUO <jump label> 16.4
JZ <jump label> 16.5
JN <jump label> 16.5
JP <jump label> 16.5
JM <jump label> 16.5
JMZ <jump label> 16.5
JPZ <jump label> 16.5

Example The following sample program shows how the Compare Real number
instructions work.

STL Explanation
L MD24 Load the contents of memory double word MD24 into
accumulator 1.
L +1.00E+00 Load the value 1 as a 32-bit floating-point number into
accumulator 1.
The old contents of accumulator 1 are shifted to
accumulator 2.
>R Compare the value in accumulator 2 to see if it is
greater than the value in accumulator 1.
= Q 4.1 Output Q 4.1 will be energized if MD24 is greater than 1.
<R Compare the value in accumulator 2 to see if it is less
than the value in accumulator 1.
= Q 4.2 Output Q 4.2 will be energized if MD24 is less than 1.

Statement List (STL) for S7-300/S7-400


11-6 C79000-G7076-C565-01
Conversion Instructions 12
Chapter Overview Section Description Page
12.1 Converting Binary Coded Decimal Numbers and Integers 12-2
12.2 Converting 32-Bit Floating-Point Numbers to 32-Bit 12-8
Integers
12.3 Reversing the Order of Bytes within Accumulator 1 12-13
12.4 Forming Complements and Negating Floating-Point 12-14
Numbers

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 12-1
Conversion Instructions

12.1 Converting Binary Coded Decimal Numbers and Integers

Description You can use the following instructions to convert binary coded decimal
numbers and integers to other types of numbers:

Mne- Instruction Function


monic
BTI BCD to Integer This instruction converts a binary coded
decimal value in the low word of
accumulator 1 to a 16-bit integer.
BTD BCD to Double This instruction converts a binary coded
Integer decimal value in accumulator 1 to a 32-bit
integer.
ITB Integer to BCD This instruction converts a 16-bit integer in
the low word of accumulator 1 to a binary
coded decimal value.
ITD Integer to Double This instruction converts a 16-bit integer in
Integer the low word of accumulator 1 to a 32-bit
integer.
DTB Double Integer to This instruction converts a 32-bit integer in
BCD accumulator 1 to a binary coded decimal
value.
DTR Double Integer to This instruction converts a 32-bit integer in
Real accumulator 1 to a 32-bit IEEE floating-point
number (real number).

Statement List (STL) for S7-300/S7-400


12-2 C79000-G7076-C565-01
Conversion Instructions

BCD to Integer: The BCD to Integer (BTI) instruction converts a three-place binary coded
BTI decimal number (BCD number, see Figure 12-1) in the low word of
accumulator 1 to a 16-bit integer. The BCD number can be in the range of
-999 to +999. The result of the conversion is stored in the low word of
accumulator 1.

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
S S S S

102 101 100


Hundreds Tens Ones

Value of the BCD number

These bits are not used during the transfer.

Sign: 0000 stands for positive, 1111 stands for negative.

Figure 12-1 Structure of a Binary Coded Decimal Number to Be Converted to


Integer

If a place of a BCD number is in the invalid range of 10 to 15, a BCDF error


occurs during an attempted conversion. In this case, one of the following
occurrences takes place:
 The CPU goes into the STOP mode. “BCD Conversion Error” is entered
in the diagnostic buffer with event ID number 2521.
 If OB121 is programmed, it is called.
The following sample program includes a BTI instruction. Figure 12-2 shows
how this instruction works.

STL Explanation
L MW10 Load the BCD value in memory word MW10 into accumulator 1.
BTI Convert the BCD value to a 16-bit integer and store the
result in accumulator 1.
T MW20 Transfer the result to memory word MW20.

“+” “9” “1” “5”

15... ...8 7... ...0


L MW10 MW10 0 0 0 0 1 0 0 1 0 0 0 1 0 1 0 1 “+915” BCD

BTI BCD to integer

T MW20 MW20 0 0 0 0 0 0 1 1 1 0 0 1 0 0 1 1 “+915” integer

Figure 12-2 Using the BTI Instruction to Convert a BCD Number to a 16-Bit Integer

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 12-3
Conversion Instructions

BCD to Double The BCD to Double Integer (BTD) instruction converts a seven-place binary
Integer: BTD coded decimal number (BCD number, see Figure 12-3) in accumulator 1 to a
32-bit integer. The BCD number can be in the range of -9,999,999 to
+9,999,999. The result of the conversion is stored in accumulator 1.
If a place of a BCD number is in the invalid range of 10 to 15, a BCDF error
occurs during an attempted conversion. In this case, either one of the
following occurrences takes place:
 The CPU goes into the STOP mode. “BCD Conversion Error” is entered
in the diagnostic buffer with event ID number 2521.
 If OB121 is programmed, it is called.

31... ...16 15... ...0


SSSS

106 105 104 103 102 101 100

Value of the BCD number

These bits are not used during the transfer.

Sign: 0000 stands for positive, 1111 stands for negative.

Figure 12-3 Structure of a 32-Bit BCD Number to Be Converted to Double Integer

The following sample program includes a BTD instruction. Figure 12-4


shows how this instruction works.

STL Explanation
L MD10 Load the BCD value in memory double word MD10 into
accumulator 1.
BTD Convert the BCD value to a 32-bit integer and store the
result in accumulator 1.
T MD20 Transfer the result to memory double word MD20.

“+” “0” “1” “5” “7” “8” “2” “1”

31... ...16 15... ...0


L MD10 MD10 0000 0000 0001 0101 0111 1000 0010 0001 “157821”

BTD BCD to integer

T MD20 MD20 0000 0000 0000 0010 0110 1000 0111 1101 “+157821”

Figure 12-4 Using the BTD Instruction to Convert a BCD Number to a 32-Bit Integer

Statement List (STL) for S7-300/S7-400


12-4 C79000-G7076-C565-01
Conversion Instructions

Integer to BCD: The Integer to BCD (ITB) instruction converts a 16-bit integer in the low
ITB word of accumulator 1 to a three-place binary coded decimal number. The
BCD number can be in the range of -999 to +999. The result of the
conversion is stored in the low word of accumulator 1.
If the integer is too large to be represented in BCD format, no conversion
takes place and the overflow (OV) and stored overflow (OS) bits of the status
word (see Section 3.4) are set to a signal state of 1.
The following sample program includes an ITB instruction. Figure 12-5
shows how this instruction works.

STL Explanation
L MW10 Load the 16-bit integer value in memory word MW10 into
accumulator 1.
ITB Convert the 16-bit integer to a BCD value and store the
result in accumulator 1.
T MW20 Transfer the result to memory word MW20.

15... ...8 7... ...0


L MW10 MW10 1 1 1 1 1 1 1 0 0 1 1 0 0 0 1 1 “-413” integer

ITB Integer to BCD

T MW20 MW20 1 1 1 1 0 1 0 0 0 0 0 1 0 0 1 1 “-413” BCD

“–” “4” “1” “3”

Figure 12-5 Using the ITB Instruction to Convert a 16-Bit Integer to a BCD Number

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 12-5
Conversion Instructions

Integer to Double The Integer to Double Integer (ITD) instruction converts a 16-bit integer in
Integer: ITD the low word of accumulator 1 to a 32-bit integer. The result of the
conversion is stored in accumulator 1. The following sample program
includes an ITD instruction. Figure 12-6 shows how this instruction works.
STL Explanation
L MW10 Load the 16-bit integer value in memory word MW10 into
accumulator 1.
ITD Convert the 16-bit integer value to a 32-bit integer and
store the result in accumulator 1.
T MD20 Transfer the result to memory double word MD20.

15... ...0
L MW10 MW10 1111 1111 1111 0110 “-10”
integer

ITD Integer (16-bit) to integer (32-bit)


31... ...16 15... ...0
T MD20 MD20 1111 1111 1111 1111 1111 1111 1111 0110 “-10”
integer

Figure 12-6 Using the ITD Instruction to Convert a 16-Bit Integer to a 32-Bit Integer

Double Integer to The Double Integer to BCD (DTB) instruction converts a 32-bit integer in
BCD: DTB accumulator 1 to a seven-place binary coded decimal value. The BCD
number can be in the range of -9,999,999 to +9,999,999. The result of the
conversion is stored in accumulator 1.
If the double integer is too large to be represented in BCD format, no
conversion takes place and the overflow (OV) and stored overflow (OS) bits
of the status word (see Section 3.4) are set to a signal state of 1.
The following sample program includes a DTB instruction. Figure 12-7
shows how this instruction works.
STL Explanation
L MD10 Load the 32-bit integer in memory double word MD10 into
accumulator 1.
DTB Convert the 32-bit integer to a BCD value and store the
result in accumulator 1.
T MD20 Transfer the result to memory double word MD20.

31... ...16 15... ...0


L MD10 MD10 1111 1111 1111 1111 1111 1101 0100 0011 “-701”
integer

DTB Integer to BCD

T MD20 MD20 1111 0000 0000 0000 0000 0111 0000 0001 “-701”
BCD

“–” “0” “0” “0” “0” “7” “0” “1”

Figure 12-7 Using the DTB Instruction to Convert a 32-Bit Integer to a BCD Number

Statement List (STL) for S7-300/S7-400


12-6 C79000-G7076-C565-01
Conversion Instructions

Double Integer to The Double Integer to Real (DTR) instruction converts a 32-bit integer in
Real: DTR accumulator 1 to a 32-bit IEEE floating-point number (real number). If
necessary, the instruction rounds the result. The result of the conversion is
stored in accumulator 1. The following sample program includes an DTR
instruction. Figure 12-8 shows how this instruction works.

STL Explanation
L MD10 Load the 32-bit integer in memory double word MD10 into
accumulator 1.
DTR Convert the 32-bit integer to a 32-bit IEEE
floating-point value and store the result in
accumulator 1.
T MD20 Transfer the result to memory double word MD20.

L MD10 MD10 0000 0000 0000 0000 0000 0001 1111 0100 “+500”
integer

DTR Integer (32-bit) to IEEE floating-point


31 30... 22... ...0
T MD20 MD20 0 100 0011 1 111 1010 0000 0000 0000 0000 “+500”
IEEE

8-bit exponent
23-bit mantissa
1 bit
Sign of the mantissa

Figure 12-8 Using the DTR Instruction to Convert a 32-Bit Integer to an IEEE 32-Bit Floating-Point Number

For a summary of the number conversions, see Figure 12-13 at the end of
Section 12.2.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 12-7
Conversion Instructions

12.2 Converting 32-Bit Floating-Point Numbers to 32-Bit Integers

Description You can use any of the following instructions to convert a 32-bit IEEE
floating-point number in accumulator 1 to a 32-bit integer (double integer).
The individual instructions differ in their method of rounding.

Mne- Instruction Function


monic
RND Round This instruction rounds the converted num-
ber to the nearest whole number. If the frac-
tional part of the converted number is mid-
way between an even and an odd result, the
instruction chooses the even result.
RND+ Round to Upper This instruction rounds the converted num-
Double Integer ber to the smallest whole number greater
than or equal to the floating-point number
that is converted.
RND- Round to Lower This instruction rounds the converted num-
Double Integer ber to the largest whole number less than or
equal to the floating-point number that is
converted.
TRUNC Truncate This instruction converts the whole number
part of the floating-point number.

The result of the conversion is stored in accumulator 1. If the number to be


converted is not a floating-point number or is a floating-point number that
cannot be represented as a 32-bit integer, no conversion takes place and an
overflow is indicated.

Statement List (STL) for S7-300/S7-400


12-8 C79000-G7076-C565-01
Conversion Instructions

Round: RND The Round (RND) instruction converts a 32-bit IEEE floating-point number
in accumulator 1 to a 32-bit integer (double integer) and rounds it to the
nearest whole number. If the fractional part of the converted number is
midway between an even and an odd result, the instruction chooses the even
result. The following sample program includes an RND instrruction.
Figure 18-9 shows how this instruction works.

STL Explanation
L MD10 Load the 32-bit IEEE floating-point value in memory
double word MD10 into accumulator 1.
RND Convert the 32-bit floating-point number to a 32-bit
integer, round to the nearest whole number, and store the
result in accumulator 1.
T MD20 Transfer the result to memory double word MD20.

31 30... 22... ...0


L MD10 MD10 0 100 0010 1 100 1001 0000 0000 0000 0000 “+100.5”
IEEE

RND IEEE to integer (32-bit)

“+100”
T MD20 MD20 0000 0000 0000 0000 0000 0000 0110 0100
integer

31 30... 22... ...0


L MD10 MD10 1 100 0010 1 100 1001 0000 0000 0000 0000 “-100.5”
IEEE

RND IEEE to integer (32-bit)

“-100”
T MD20 MD20 1111 1111 1111 1111 1111 1111 1001 1100
integer

Figure 12-9 Using the RND Instruction to Convert an IEEE 32-Bit Floating-Point Number to a 32-Bit Integer

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 12-9
Conversion Instructions

Round to Upper The Round to Upper Double Integer (RND+) instruction converts a 32-bit
Double Integer: IEEE floating-point number in accumulator 1 to a 32-bit integer (double
RND+ integer). The instruction rounds the converted number to the smallest whole
number greater than or equal to the floating-point number that is converted.
The following sample program includes an RND+ instruction. Figure 12-10
shows how this instruction works.

STL Explanation
L MD10 Load the 32-bit IEEE floating-point value in memory
double word MD10 into accumulator 1.
RND+ Convert the 32-bit floating-point number to a 32-bit
integer. Round to the smallest whole number greater than
or equal to the floating-point number that is converted
and store the result in accumulator 1.
T MD20 Transfer the result to memory double word MD20.

31 30... 22... ...0


L MD10 MD10 0 100 0010 1 100 1001 0000 0000 0000 0000 “+100.5”
IEEE

RND+ IEEE to integer (32-bit)

“+101”
T MD20 MD20 0000 0000 0000 0000 0000 0000 0110 0101
integer

31 30... 22... ...0


L MD10 MD10 1 100 0010 1 100 1001 0000 0000 0000 0000 “-100.5”
IEEE

RND+ IEEE to integer (32-bit)

“-100”
T MD20 MD20 1111 1111 1111 1111 1111 1111 1001 1100
integer

Figure 12-10 Using the RND+ Instruction to Convert an IEEE 32-Bit Floating-Point Number to a 32-Bit Integer

Statement List (STL) for S7-300/S7-400


12-10 C79000-G7076-C565-01
Conversion Instructions

Round to Lower The Round to Lower Double Integer (RND-) instruction converts a 32-bit
Double Integer: IEEE floating-point number in accumulator 1 to a 32-bit integer (double
RND- integer). The instruction rounds the converted number to the largest whole
number less than or equal to the floating-point number that is converted. The
following sample program includes an RND- instruction. Figure 12-11 shows
how this instruction works.

STL Explanation
L MD10 Load the 32-bit IEEE floating-point value in memory
double word MD10 into accumulator 1.
RND– Convert the 32-bit floating-point number to a 32-bit
integer. Round to the largest whole number less than or
equal to the floating-point number that is converted and
store the result in accumulator 1.
T MD20 Transfer the result to memory double word MD20.

31 30... 22... ...0


L MD10 MD10 0 100 0010 1 100 1001 0000 0000 0000 0000 “+100.5”
IEEE

RND– IEEE to integer (32-bit)

“+100”
T MD20 MD20 0000 0000 0000 0000 0000 0000 0110 0100
integer

31 30... 22... ...0


L MD10 MD10 1 100 0010 1 100 1001 0000 0000 0000 0000 “-100.5”
IEEE

RND– IEEE to integer (32-bit)

“-101”
T MD20 MD20 1111 1111 1111 1111 1111 1111 1001 1011
integer

Figure 12-11 Using the RND– Instruction to Convert an IEEE 32-Bit Floating-Point Number to a 32-Bit Integer

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 12-11
Conversion Instructions

Truncate: TRUNC The Truncate (TRUNC) instruction converts a 32-bit IEEE floating-point
number in accumulator 1 to a 32-bit integer (double integer). The instruction
converts the whole number part of the floating-point number. The following
sample program includes a TRUNC instruction. Figure 12-12 shows how this
instruction works.

STL Explanation
L MD10 Load the 32-bit IEEE floating-point value in memory double word MD10
into accumulator 1.
TRUNC Convert the 32-bit floating-point number to a 32-bit integer. Round
to the largest whole number less than or equal to the floating-point
number that is converted and store the result in accumulator 1.
T MD20 Transfer the result to memory double word MD20.

31 30... 22... ...0


L MD10 MD10 0 100 0010 1 100 1001 0000 0000 0000 0000 “+100.5”
IEEE
TRUNC IEEE to integer (32-bit)
“+100”
T MD20 MD20 0000 0000 0000 0000 0000 0000 0110 0100
integer

31 30... 22... ...0


L MD10 MD10 1 100 0010 1 100 1001 0000 0000 0000 0000 “-100.5”
IEEE
TRUNC IEEE to integer (32-bit)
“-100”
T MD20 MD20 1111 1111 1111 1111 1111 1111 1001 1100
integer

Figure 12-12 Using the TRUNC Instruction to Convert an IEEE 32-Bit Floating-Point Number to a 32-Bit Integer

Summary of Figure 12-13 summarizes number conversions and rounding (see also
Number Sections 12.1 and 12.2).
Conversions

BCD BTI Integer Floating


ITB ITD
3-place 16-bit 32-bit
7-place 32-bit DTR IEEE
BTD
DTB RND, RND+, RND–,
TRUNC

Figure 12-13 Overview of Number Conversions and Rounding

Statement List (STL) for S7-300/S7-400


12-12 C79000-G7076-C565-01
Conversion Instructions

12.3 Reversing the Order of Bytes within Accumulator 1

Description You can use the following Change Bit Sequence in Accumulator 1
instructions to reverse the order of bytes in the low word of accumulator 1 or
in the entire accumulator:
 Change Byte Sequence in Accumulator 1, 16 bits (CAW)
 Change Byte Sequence in Accumulator 1, 32 bits (CAD)

CAW CAW inverts the order of bytes in the low word of accumulator 1 (see
Figure 12-14).

31... ...16 15... ...0

L MD10 MD10 0101 1111 1010 0000 1111 1010 0101 0000

CAW

T MD20 MD20 0101 1111 1010 0000 0101 0000 1111 1010

Figure 12-14 Using CAW to Reverse Byte Order in the Low Word of Accumulator 1

CAD CAD inverts the byte order in all of accumulator 1 (see Figure 12-15).

31... ...16 15... ...0

L MD10 MD10 0101 1111 1010 0000 1111 1010 0101 0000

CAD

T MD20 MD20 0101 0000 1111 1010 1010 0000 0101 1111

Figure 12-15 Using CAD to Reverse Byte Order in Accumulator 1

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 12-13
Conversion Instructions

12.4 Forming Complements and Negating Floating-Point Numbers

Description Forming the ones complement of a number in the accumulator inverts the
number bit by bit, that is, zeros are replaced by ones and ones are replaced by
zeros.
Forming the twos complement of an integer in the accumulator also inverts
the number bit by bit, that is, zeros are replaced by ones and ones are
replaced by zeros. Then a +1 is added to the contents of the accumulator.
Forming the twos complement of an integer is the same as multiplying the
number by a -1. Negating a real number inverts the sign bit.
You can use one of the following instructions to form the complement of an
integer or to invert the sign of a floating-point number:

Mne- Instruction Function


monic
INVI Ones Complement This instruction forms the ones complement of the
Integer 16-bit value in the low word of accumulator 1. The
result is stored in the low word of accumulator 1
(see Figure 12-16).
INVD Ones Complement This instruction forms the ones complement of the
Double Integer 32-bit value in accumulator 1. The result is stored in
accumulator 1.
NEGI Twos Complement This instruction forms the twos complement of the
Integer 16-bit value in the low word of accumulator 1, that
is, it multiplies it by -1. The result is stored in the
low word of accumulator 1 (see Figure 12-17). In
the status word (see Section 3.4), NEGI sets the
CC 1, CC 0, OV and OS bits.
NEGD Twos Complement This instruction forms the twos complement of the
Double Integer 32-bit value in accumulator 1, that is, it multiplies it
by -1. The result is stored in accumulator 1. In the
status word (see Section 3.4), NEGI sets the CC 1,
CC 0, OV and OS bits.
NEGR Negate Floating- This instruction inverts the sign bit of the 32-bit
Point Number IEEE floating-point value in accumulator 1 (see Fig-
ure 12-18).

Statement List (STL) for S7-300/S7-400


12-14 C79000-G7076-C565-01
Conversion Instructions

Statement List Program

L DBW30 Load the value of data word DBW30 into the low word of accumulator 1.
INVI Form the ones complement of the value in the low word of accumulator 1.
T DBW32 Transfer the contents of the low word of accumulator 1 to data word DBW32.
Bit Patterns

L DBW30 0 1 0 1 1 1 0 1 0 0 1 1 1 0 0 0

INVI Ones Complement Integer

T DBW32 1 0 1 0 0 0 1 0 1 1 0 0 0 1 1 1

Figure 12-16 Forming the Ones Complement of a 16-Bit Integer

Statement List Program

L DBW40 Load the value of data word DBW40 into the low word of accumulator 1.
NEGI Form the twos complement of the value in the low word of accumulator 1.
T DBW42 Transfer the contents of the low word of accumulator 1 to data word DBW42.

Bit Patterns
“23,864”
L DBW40 0 1 0 1 1 1 0 1 0 0 1 1 1 0 0 0 integer

NEGI Twos Complement Integer


“-23,864”
T DBW42 1 0 1 0 0 0 1 0 1 1 0 0 1 0 0 0
integer

Figure 12-17 Forming the Twos Complement of a 16-Bit Integer

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 12-15
Conversion Instructions

Decimal value 10.0


Hexadecimal
value 4 1 2 0 0 0 0 0
Bits 31 28 27 24 23 20 19 16 15 12 11 8 7 4 3 0

0 1 0 0 0 0 0 1 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Sign of Exponent: e Mantissa or fraction: f


Mantissa: s (8 bits) (23 bits)
(1 bit)
e = 27 + 21 = 130 f = 2–2 = 0.25
1.f  2e–bias = 1.25  23 = 10.0
[1.25  2(130–127) = 1.25  23 = 10.0]

Statement List Program

L DBD62 Load the value of data double word DBD62 into accumulator 1.
NEGR Invert the sign of the value in accumulator 1.
T DBD66 Transfer the contents of accumulator 1 to data double word DBD66.

L DBD62 0 1 0 0 0 0 0 1 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

NEGR Negate Floating-Point Number

T DBD66 1 1 0 0 0 0 0 1 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Sign of Mantissa (0 = positive, 1 = negative)

Figure 12-18 Inverting the Sign of a Floating-Point Number

Statement List (STL) for S7-300/S7-400


12-16 C79000-G7076-C565-01
Word Logic Instructions 13
Chapter Overview Section Description Page
13.1 Overview 13-2
13.2 16-Bit Word Logic Instructions 13-3
13.3 32-Bit Word Logic Instructions 13-6

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 13-1
Word Logic Instructions

13.1 Overview

Description Word logic instructions combine pairs of words (16 bits) or double words
(32 bits) bit by bit according to Boolean logic. Each word or double word
must be in one of the two accumulators.

Accumulator For words, the contents of the low word of accumulator 2 is combined with
Administration the contents of the low word of accumulator 1. The result of the combination
is stored in the low word of accumulator 1, overwriting the old contents.
For double words, the contents of accumulator 2 is combined with the
contents of accumulator 1. The result of the combination is stored in
accumulator 1, overwriting the old contents.

Influence on Bits If the result of the logic combination is 0, the CC 1 bit of the status word is
of the Status Word reset to 0. If the result of the logic combination is not 0, CC 1 is set to 1. In
any case, the CC 0 and OV bits of the status word are reset to 0.

Available The following instructions are available for performing word logic
Instructions operations:

Mnemonic Instruction Function


AW And Word Combines two words bit by bit
according to the And truth table
OW Or Word Combines two words bit by bit
according to the Or truth table
XOW Exclusive Or Word Combines two words bit by bit
according to the Exclusive Or
truth table
AD And Double Word Combines two double words bit
by bit according to the And truth
table
OD Or Double Word Combines two double words bit
by bit according to the Or truth
table
XOD Exclusive Or Double Combines two double words bit
Word by bit according to the Exclusive
Or truth table

Constants as An AW, OW, or XOW instruction can use a 16-bit constant as its address.
Addresses The instruction combines the contents of the low word of accumulator 1 with
the 16-bit constant.
An AD, OD, or XOD instruction can use a 32-bit constant as its address.

Statement List (STL) for S7-300/S7-400


13-2 C79000-G7076-C565-01
Word Logic Instructions

13.2 16-Bit Word Logic Instructions

Description The And Word, Or Word, and Exclusive Or Word instructions (AW, OW,
XOW) combine pairs of words (16 bits) bit by bit according to Boolean
logic.

Mnemonic Instruction RLO Before Address Result in


Logic Operation RLO
AW And Word 0 0 0
0 1 0
1 0 0
1 1 1
OW Or Word 0 0 0
0 1 1
1 0 1
1 1 1
XOW Exclusive Or 0 0 0
Word 0 1 1
1 0 1
1 1 0

Relationship to For the instructions that combine 16-bit words, the contents of the low word
Accumulators of accumulator 2 is combined with the contents of the low word of
accumulator 1. The result of the logic combination is stored in the low word
of accumulator 1, overwriting the old contents. The contents of the high word
of accumulator 1 and both words of accumulator 2 remain unchanged (see
Figure 13-1).

Accumulator contents Accumulator contents


before word logic operation after word logic operation
Accumulator 2 Accumulator 2
31 16 15 0
Combination
IV III IV III

Accumulator 1 AW, OW, XOW Accumulator 1


31 16 15 0
II I II III c. I
c = combined with

Figure 13-1 Combining the Contents of the Low Words of Accumulators 2 and 1

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 13-3
Word Logic Instructions

Example of an AW The following sample program includes an AW instruction. Figure 13-2


Instruction shows how this instruction works.

STL Explanation
L MW10 Load the contents of memory word MW10 into accumulator 1.

L MW20 Load the contents of memory word mW20 into accumulator 1.


The old contents of accumulator 1 are shifted to
accumulator 2.
AW The contents of the low word of accumulator 2 are
combined bit by bit with the contents of the low word of
accumulator 1 according to the AND truth table. The
result is stored in the low word of accumulator 1.
T MW24 Transfer the contents of accumulator 1 to memory word
MW24.

15... ...8 7... ...0


MW10 0 1 1 0 0 1 0 1 1 1 1 0 1 0 1 0

MW20 1 0 1 0 1 0 1 0 0 1 0 1 0 1 1 1

AND bit by bit

MW24 0 0 1 0 0 0 0 0 0 1 0 0 0 0 1 0

Figure 13-2 Combining Two Words Using the AW Instruction

Combining An AW, OW, or XOW instruction can use a 16-bit constant as its address.
Accumulator and The instruction combines the contents of the low word of accumulator 1 with
Constant the 16-bit constant that is indicated in the instruction statement. The result of
the combination is stored in the low word of accumulator 1. Accumulator 2
and the high word of accumulator 1 remain unchanged (see Figure 13-3).

Accumulator contents Accumulator contents


before word logic operation after word logic operation
Accumulator 2 Accumulator 2
31 16 15 0
Combination
IV III IV III

Accumulator 1 AW2#, OW2#, Accumulator 1


31 16 15 0 XOW2#
II I II I c. 2#
c = combined with

Figure 13-3 Combining the Low Word of Accumulator 1 with a 16-Bit Constant

Statement List (STL) for S7-300/S7-400


13-4 C79000-G7076-C565-01
Word Logic Instructions

Example of an AW The following sample program includes an AW instruction that makes a logic
Instruction with combination with a 16-bit constant that is indicated in the instruction
Constant statement. Figure 13-4 shows how this instruction works.

STL Explanation
L MW10 Load the contents of memory word MW10 into
accumulator 1.
AW 2#1010_1010_0101_0101 The contents of the low word of accumulator 1 are
combined bit by bit with 1010_1010_0101_0101
according to the AND truth table. The result is
stored in the low word of accumulator 1.
T MW24 Transfer the contents of accumulator 1 to memory
word MW24.

15... ...8 7... ...0


MW10 0 1 1 0 0 1 0 1 1 1 1 0 1 0 1 0

Value of AW statement 1 0 1 0 1 0 1 0 0 1 0 1 0 1 0 1

AND Bit by Bit

MW24 1 0 1 0 0 0 0 0 0 1 0 0 0 0 0 0

Figure 13-4 Using an AW Instruction with a 16-Bit Constant

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 13-5
Word Logic Instructions

13.3 32-Bit Word Logic Instructions

Description The And Double Word, Or Double Word, and Exclusive Or Double Word
instructions (AD, OD, XOD) combine pairs of words (32 bits) bit by bit
according to Boolean logic.

Mnemonic Instruction RLO Before Address Result


Logic Operation in RLO
AD And Double 0 0 0
Word 0 1 0
1 0 0
1 1 1
OD Or Double Word 0 0 0
0 1 1
1 0 1
1 1 1
XOD Exclusive Or 0 0 0
Double Word 0 1 1
1 0 1
1 1 0

Relationship to For the instructions that combine double words, the contents of
Accumulators accumulator 2 is combined with the contents of accumulator 1. The result of
the logic combination is stored in accumulator 1, overwriting the old
contents. The contents of accumulator 2 remains unchanged (see
Figure 13-5).

Accumulator contents Accumulator contents


before word logic operation after word logic operation
Accumulator 2 Accumulator 2
31 16 15 0
Combination
IV III IV III

Accumulator 1 AD, OD, XOD Accumulator 1


31 16 15 0
II I IV c. II III c. I
c = combined with

Figure 13-5 Combining the Contents of Accumulators 2 and 1

Statement List (STL) for S7-300/S7-400


13-6 C79000-G7076-C565-01
Word Logic Instructions

Example of an AD The following sample program includes an AD instruction. Figure 13-6


Instruction shows how this instruction works.

STL Explanation
L MD10 Load the contents of memory double word MD10 into
accumulator 1.
L MD20 Load the contents of memory double word mD20 into
accumulator 1. The old contents of accumulator 1 are
shifted to accumulator 2.
AD The contents of accumulator 2 are combined bit by bit
with the contents of accumulator 1 according to the AND
truth table. The result is stored in accumulator 1.
T MD24 Transfer the contents of accumulator 1 to memory double
word MD24.

31... ...16 15... ...0


MD10 0110 1001 1000 0001 1000 0000 1010 0111

MD20 1010 1010 1010 1010 0101 0101 0101 0101

AND bit by bit

MD24 0010 1000 1000 0000 0000 0000 0000 0101

Figure 13-6 Using an AD Instruction

Combining An AD, OD, or XOD instruction can use a 32-bit constant as its address. The
Accumulator and instruction combines the contents of accumulator 1 with the 32-bit constant
Constant that is indicated in the instruction statement. The result of the combination is
stored in accumulator 1. Accumulator 2 remains unchanged (see
Figure 13-7).

Accumulator contents Accumulator contents after


before word logic operation word logic operation
Accumulator 2 Accumulator 2
31 16 15 0
IV III Combination IV III
Accumulator 1 AD, OD, XOD Accumulator 1
31 16 15 0 DW#16#
II I IIc.DW#16#Ic.DW#16#
c=combined with

Figure 13-7 Combining Accumulator 1 with a 32-Bit Constant

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 13-7
Word Logic Instructions

Example of an AD The following sample program includes an AD instruction that makes a logic
Instruction with combination with a 32-bit constant that is indicated in the instruction
Constant statement. Figure 13-8 shows how this instruction works.

STL Explanation
L MD10 Load the contents of memory double word MD10 into
accumulator 1.
AD DW#16#AAAA_5555 The contents of accumulator 1 are combined bit by bit
with DW#16#AAAA_5555 according to the AND truth table.
The result is stored in accumulator 1.
T MD24 Transfer the contents of accumulator 1 to memory double
word MD24.

31... ...16 15... ...0


MD10 0110 1001 1000 0001 1000 0000 1010 0111

Value of AD statement 1010 1010 1010 1010 0101 0101 0101 0101

AND bit by bit

MD24 0010 1000 1000 0000 0000 0000 0000 0101

Figure 13-8 Using an AD Instruction with a 32-Bit Constant

Statement List (STL) for S7-300/S7-400


13-8 C79000-G7076-C565-01
Shift and Rotate Instructions 14
Chapter Overview Section Description Page
14.1 Shift Instructions 14-2
14.2 Rotate Instructions 14-6

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 14-1
Shift and Rotate Instructions

14.1 Shift Instructions

Shift Instructions You can use the Shift instructions to move the contents of the low word of
accumulator 1 or the contents of the whole accumulator bit by bit to the left
or the right. Shifting by n bits to the left multiplies the contents of the
accumulator by “2n”; shifting by n bits to the right divides the contents of the
accumulator by “2n”. For example, if you shift the binary equivalent of the
decimal value 3 to the left by 3 bits, you end up with the binary equivalent of
the decimal value 24 in the accumulator. If you shift the binary equivalent of
the decimal value 16 to the right by 2 bits, you end up with the binary
equivalent of the decimal value 4 in the accumulator.
The number that follows the shift instruction or a value in the low byte of the
low word of accumulator 2 indicates the number of bits by which to shift.
The bit places that are vacated by the shift instruction are either filled with
zeros or with the signal state of the sign bit (a 0 stands for positive and a 1
stands for negative). The bit that is shifted last is loaded into the CC 1 bit of
the status word (see Figure 2-7). The CC 0 and OV bits of the status word are
reset to 0. You can use jump instructions to evaluate the CC 1 bit.
The shift operations are unconditional, that is, their execution does not
depend on any special conditions. They do not affect the result of logic
operation.

Shift Functions: The following instruction shift the contents of the low word of accumulator 1
Unsigned bit by bit to the left or right:
Numbers
 Shift Left Word (SLW, 16 bits)
 Shift Right Word (SRW, 16 bits)
The following instructions shift the entire contents of accumulator 1 bit by
bit to the left or right:
 Shift Left Double Word (SLD, 32 bits)
 Shift Right Double Word (SRD, 32 bits)
In all cases, the free bit positions are filled with a 0,

Shift Left Word: The following sample program and Figure 14-1 provide an example of how
SLW the SLW instruction works. Table 14-1 provides a summary of all the Shift
instructions.

STL Explanation
L MW10 Load the contents of memory word MW10 into the low word of
accumulator 1.
SLW 6 Shift the bits of the low word in accumulator 1 six places
to the left.
T MW20 Transfer the contents of the low word of accumulator 1 to
memory word MW20.

Statement List (STL) for S7-300/S7-400


14-2 C79000-G7076-C565-01
Shift and Rotate Instructions

15... ...8 7... ...0


0 0 0 0 1 1 1 1 0 1 0 1 0 1 0 1

6 places

0 0 0 0 1 1 1 1 0 1 0 1 0 1 0 1 0 0 0 0 0 0

These five bits


are lost. The vacated places
are filled with zeros.
The bit that is shifted out last is stored
in the CC 1 bit of the status word.

Figure 14-1 Shifting Bits of the Low Word of Accumulator 1 Six Bits to the Left

Shift Right Double The following sample program and Figure 14-2 provide an example of how
Word (32 Bits): the SRW instruction works. Table 14-1 provides a summary of all the Shift
SRD instructions.

STL Explanation
L +3 Load the value +3 into accumulator 1.
L MD10 Load the contents of memory double word MD10 into
accumulator 1. The old contents of accumulator 1 (+3) is
moved to accumulator 2.
SRD Shift the bits in accumulator 1 three places to the right.
T MD20 Transfer the contents of accumulator 1 to memory double
word MD20.

31... ...16 15... ...0


1111 1111 0101 0101 1010 1010 1111 1111

3 places

0001 1111 1110 1010 1011 0101 0101 1111 111

The vacated places


are filled with zeros. The bit that is shifted out These two
last is stored in the CC 1 bits are lost.
bit of the status word.

Figure 14-2 Shifting Bits of Accumulator 1 Three Bits to the Right

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 14-3
Shift and Rotate Instructions

Shift Functions: The Shift Sign Integer (SSI, 16 bits) instruction shifts the contents of the low
Signed Numbers word of accumulator 1 bit by bit to the right, including sign, as described in
the overview of this chapter:
The Shift Sign Double Integer (SSD, 32 bits) instruction shifts the entire
contents of accumulator 1 bit by bit to the right, including sign.
The shift bit is copied into the free bit positions.

Shift Sign Integer: The following sample program and Figure 14-3 provide an example of how
SSI the SSI instruction works. Table 14-1 provides a summary of all the Shift
instructions.

STL Explanation
L MW10 Load the contents of memory word MW10 into the low word
of accumulator 1.
SSI 4 Shift the bits in the low word of accumulator 1,
including sign, four places to the right.
T MW20 Transfer the contents of the low word of accumulator 1 to
memory word MW20.

15... ...8 7... ...0


1 0 1 0 1 1 1 1 0 0 0 0 1 0 1 0

Sign bit 4 places

1 1 1 1 1 0 1 0 1 1 1 1 0 0 0 0 1 0 1 0

The vacated places are


filled with the signal The bit that is shifted out last is stored These three
state of the sign bit. in the CC 1 bit of the status word. bits are lost.

Figure 14-3 Shifting Bits of the Low Word of Accumulator 1 Four Bits to the Right with Sign

Statement List (STL) for S7-300/S7-400


14-4 C79000-G7076-C565-01
Shift and Rotate Instructions

Table 14-1 Overview of Shift Instructions

Instruction Area Affected Direction Indication of Number of Filler for Shift


Places to Shift Vacated Range1
Places
SLW n Low word of Left In the instruction 0 n=0 to 15
accumulator 1 statement
SLW Low word of Left In the low byte of the low 0 0 to 2552
accumulator 1 word of accumulator 2
SLD n Accumulator 1 Left In the instruction 0 n=0 to 32
statement
SLD Accumulator 1 Left In the low byte of the low 0 0 to 2553
word of accumulator 2
SRW n Low word of Right In the instruction 0 n=0 to 15
accumulator 1 statement
SRW Low word of Right In the low byte of the low 0 0 to 2552
accumulator 1 word of accumulator 2
SRD n Accumulator 1 Right In the instruction 0 n=0 to 32
statement
SRD Accumulator 1 Right In the low byte of the low 0 0 to 2553
word of accumulator 2
SSI n Low word of Right In the instruction Sign bit n=0 to 15
accumulator 1 statement
SSI Low word of Right In the low byte of the low Sign bit 0 to 2554
accumulator 1 word of accumulator 2
SSD n Accumulator 1 Right In the instruction Sign bit n=0 to 32
statement
SSD Accumulator 1 Right In the low byte of the low Sign bit 0 to 2555
word of accumulator 2

1 If the number of bits by which to shift or rotate is 0, the instruction is executed like a NOP.
2 For shift numbers greater than 16, the result of the shift function is W#16#0000 and CC 1 = 0.
3 For shift numbers greater than 32, the result of the shift function is DW#16#0000_0000 and CC 1 = 0.
4 For shift numbers greater than 15, the result of the shift function is W#16#0000 and CC 1 = 0 or W#16#FFFF and
CC 1 = 1 depending on the sign (0 or 1).
5 For shift numbers greater than 31, the result of the shift function is DW#16#0000_0000 (CC 1 = 0) or
DW#16#FFFF_FFFF (CC 1 = 1) depending on the sign of the number of bits to be shifted.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 14-5
Shift and Rotate Instructions

14.2 Rotate Instructions

Description You can use the Rotate instructions to rotate the entire contents of
accumulator 1 bit by bit to the left or to the right. The Rotate instructions
trigger functions that are similar to the shift functions described in
Section 14.1. However, the vacated bit places are filled with the signal states
of the bits that are shifted out of the accumulator.
The number that follows the rotate instruction or a value in the low byte of
the low word of accumulator 2 indicates the number of bits by which to
rotate.
Depending on the instruction, rotation takes place via the CC 1 bit of the
status word (see Section 2.2). The CC 0 bit of the status word is reset to 0.
The following Rotate instructions are available:
 Rotate Left Double Word (RLD)
 Rotate Right Double Word (RRD)
 Rotate Accumulator 1 Left via CC 1 (RLDA)
 Rotate Accumulator 1 Right via CC 1 (RRDA)
If the number of bits that are rotated is 0, then the instruction is carried out as
a Null Operation (NOP).

Table 14-2 Overview of the Rotate Instructions

Instruction Rotate via CC 1? Direction Indication of Number of Places to Shift Shift Range
RLD n No Left In the instruction statement n=0 to 32
RLD No Left In the low byte of the low word of 0 to 255
accumulator 2
RRD No Right In the instruction statement 0 to 32
RRD No Right In the low byte of the low word of 0 to 255
accumulator 2
RLDA Yes Left 1 (fixed)
RRDA Yes Right 1 (fixed)

Statement List (STL) for S7-300/S7-400


14-6 C79000-G7076-C565-01
Shift and Rotate Instructions

Rotate Left Double Table 14-2 provides a summary of all the Rotate instructions. The following
Word: RLD sample program and Figure 14-4 provide an example of how the RLD
instruction works.

STL Explanation
L MD10 Load the contents of memory double word MD10 into
accumulator 1.
RLD 3 Rotate the bits in accumulator 1 three places to the left.
T MD20 Transfer the contents of accumulator 1 to memory double
word MD20.

31... ...16 15... ...0


1111 0000 1010 1010 0000 1111 0000 1111

3 places

111 1000 0101 0101 0000 0111 1000 0111 1111

The three bits that are shifted


out are inserted in the vacated The last bit shifted is
places. also stored in CC 1.

Figure 14-4 Rotating Bits of Accumulator 1 Three Bits to the Left

Rotate Right The following sample program and Figure 14-5 provide an example of how
Double Word: RRD the RRD instruction works.

STL Explanation
L +3 Load the value +3 into accumulator 1.
L MD10 Load the contents of memory double word MD10 into
accumulator 1. The old contents of accumulator 1 (+3) is
moved to accumulator 2.
RRD Rotate the bits in accumulator 1 three places to the right.
T MD20 Transfer the contents of accumulator 1 to memory double
word MD20.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 14-7
Shift and Rotate Instructions

31... ...16 15... ...0


1010 1010 0000 1111 0000 1111 0101 0101

3 places

1011 0101 0100 0001 1110 0001 1110 1010 101

The three bits that are


The last bit shifted is shifted out are inserted
also stored in CC 1. in the vacated places.

Figure 14-5 Rotating Bits of Accumulator 1 Three Bits to the Right

Rotate Figure 14-6 shows an example of how the RLDA instruction works.
Accumulator 1 Left
via CC 1: RLDA

CC1 31... ...16 15... ...0

X 1010 1010 0000 1111 0000 1111 0101 0101

1 place

1 1010 0100 0001 1110 0001 1110 1010 101X

The last bit shifted is The signal state of the


also stored in CC 1. CC 1 bit is loaded into
the vacated bit place.

Figure 14-6 Rotating Accumulator 1 One Bit to the Left via the CC 1 Bit of the Status Word

Rotate The RRDA instruction works in a manner similar to the RLDA instruction.
Accumulator 1 The only difference is in the direction of the rotation.
Right via CC 1:
RRDA

Statement List (STL) for S7-300/S7-400


14-8 C79000-G7076-C565-01
Data Block Instructions 15
Chapter Overview Section Description Page
15.1 Opening Data Blocks 15-2
15.2 Swapping Data Block Registers 15-2
15.3 Loading Data Block Lengths and Numbers 15-3

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 15-1
Data Block Instructions

15.1 Opening Data Blocks

Description You can use the Open a Data Block (OPN) instruction to open a data block as
a shared data block or as an instance data block. The program itself can
accomodate one open shared data block and one open instance data block at
the same time.

Addressing Tables 15-1 and 15-2 lists the addresses and their ranges for the OPN
Format instruction.

Table 15-1 Addresses of the Open a Data Block Instruction OPN

Data Block Maximum Address Range according to Addressing Type


A
Area
Direct Memory Indirect
[DBW]
DB [DIW]
1 to 65,535 1 to 65,534
DI [LW]
[MW]

Table 15-2 Addresses of the Open a Data Block Instruction OPN Transferred as
Parameter

Type of DB Opened Address Parameter Format


DBpara BLOCK_DB
DIpara

15.2 Swapping Data Block Registers

Description You can use the Exchange Shared DB and Instance DB (CDB) instruction to
exchange data block registers. A shared data block becomes an instance data
block and vice versa.

Statement List (STL) for S7-300/S7-400


15-2 C79000-G7076-C565-01
Data Block Instructions

15.3 Loading Data Block Lengths and Numbers

Description You can use the following instructions to load the length (in bytes) or the
number of a shared data block or an instance data block into accumulator 1:
 Load Length of Shared DB in Accumulator 1 (L DBLG)
 Load Number of Shared DB in Accumulator 1 (L DBNO)
 Load Length of Instance DB in Accumulator 1 (L DILG)
 Load Number of Instance DB in Accumulator 1 (L DINO)

Examples The following sample program illustrates how you can use the L DBLG
instruction to jump to the label ERR if the length of a data block is 50 bytes
or more. The statement at the label ERR calls FC10, which you have
programmed as an appropriate reaction if the length of the data block in
question is 50 bytes or more.

STL Explanation
OPN DB40 Open shared data block DB40.

L DBLG Load the length of the open data block into accumulator 1.

L +50 Load the integer +50 into accumulator 1. The old contents of
accumulator 1 (the length of the open data block) are moved
to accumulator 2.

>=I Compare the contents of accumulator 2 (the length of the


open data block) to the contents of accumulator 1 (+50).

JC ERR If the length of the data block is greater than or equal to


+50, jump to the label ERR. If the length of the data block
is less than +50, continue to the next instruction
statement.
A I 0.0
= M 1.0 The program continues with an And instruction.

BEU
End the current block, regardless of the result of logic
operation.
ERR: CALL FC10
FC10 contains an appropriate reaction in the event that the
length of DB40 is 50 bytes or more.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 15-3
Data Block Instructions

The following sample program illustrates how you can use the L DBNO
instruction to check the data block that is presently open in your program to
see if it falls into a particular range of data blocks, for example, data block
DB190 to data block DB250.

STL Explanation
L DBNO Load into accumulator 1 the number of the data block that is
presently open.

L +190 Load the integer +190 as lower limit into accumulator 1. The
old contents of accumulator 1 (the number of the open data
block) are moved to accumulator 2.

<I Compare the contents of accumulator 2 (the number of the


open data block) to the contents of accumulator 1 (+190).

JC ERR If the number of the data block is less than +190, jump to
the label ERR. If the number of the data block is not less
than +190, continue to the next instruction statement.

L DBNO Load into accumulator 1 the number of the data block that is
presently open.

L +250 Load the integer +250 as upper limit into accumulator 1. The
old contents of accumulator 1 (the number of the open data
block) are moved to accumulator 2.

>I Compare the contents of accumulator 2 (the number of the


open data block) to the contents of accumulator 1 (+250).

JC ERR If the number of the data block is greater than +250, jump
to the label ERR. If the number of the data block is not
greater than +250, continue to the next instruction
statement.
SET
= M 1.0 Set the RLO to 1.
Assign the RLO to memory bit M 1.0.
BEU
End the current block, regardless of the result of logic
operation.
ERR: CALL FC10
FC10 contains an appropriate reaction in the event that the
number of the data block that is currently open does not
fall into the range of DB190 to DB250.

Statement List (STL) for S7-300/S7-400


15-4 C79000-G7076-C565-01
Jump Instructions 16
Chapter Overview Section Description Page
16.1 Overview 16-2
16.2 Unconditional Jump Instructions 16-3
16.3 Conditional Jump Instructions Based on Result of Logic 16-4
Operation
16.4 Conditional Jump Instructions Based on BR, OV, or OS Bits 16-5
of the Status Word
16.5 Conditional Jump Instructions Based on Result in the CC 1 16-6
and CC 0 Bits of the Status Word
16.6 Loop Control 16-8

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 16-1
Logic Control Instructions

16.1 Overview

Instructions You can use the following Jump and Loop instructions to control the flow of
logic, enabling your program to interrupt its linear flow to resume scanning
at a different point. The address of a Jump or Loop instruction is a label.

Instruction Explanation
Unconditional jump instructions
JU Jump Unconditional
JL Jump to List
Conditional jump instructions, condition based on RLO
JC Jump if RLO = 1
JCN Jump if RLO = 0
JCB Jump if RLO = 1 WITH BR
JNB Jump if RLO = 0 WITH BR
Conditional jump instructions, condition based on result in CC 1 and CC 0
JBI Jump If BR = 1
JNBI Jump If BR = 0
JO Jump If OV = 1
JOS Jump If OS = 1
Conditional jump instructions, condition based on result in CC 1 and CC 0
JZ Jump If Zero
JN Jump If Not Zero
JP Jump If Plus
JM Jump If Minus
JMZ Jump If Minus or Zero
JPZ Jump If Plus or Zero
JUO Jump If Unordered
Loop control
LOOP Jump if the contents of Accumulator 1 > 0

Although the Master Control Relay instructions also control the flow of logic
in a program, they are not included in this chapter. For information on MCR
instructions, see Sections 17.4 and 17.5.

Jump Label A jump label can be the address of a jump instruction or serve as a marker
for the destination of a jump instruction. It consists of a maximum of four
characters. The first character must be a letter of the alphabet; the other
characters can be letters or numbers (for example, SEG3:). When used as a
destination marker, the jump label must be closed with a colon. In this case, a
statement must follow the jump label (for example, SEG3: NOP 0).

Statement List (STL) for S7-300/S7-400


16-2 C79000-G7076-C565-01
Logic Control Instructions

16.2 Unconditional Jump Instructions

Description You can use the following jump instructions to interrupt the normal flow of
your program unconditionally:
 Jump Unconditional (JU)
 Jump to List (JL)

Jump A Jump Unconditional (JU) instruction in your program interrupts the normal
Unconditional: JU flow of logic control and causes the program to jump to a label (the address
of the JU instruction). The label marks the point at which the program should
continue. The jump is made regardless of any condition.

Jump to List: JL The Jump to List (JL) instruction is a jump distributor. It is followed by a
series of unconditional jumps to labels (see Figure 16-1). Access to the list is
in accumulator 1.

Start
Load destination:
0 = Jump to SEG0
1 = Jump to SEG1
Selection according to L MB100 2 = Jump to GEM
Segment Number 3 = Jump to SEG3
(jump distributor) JL LIST >3 = Jump to LIST
=0 =1 =2 =3 >3
JU SEG0
JU SEG1 Jump distributor
with length of
Seg. 0 Seg. 1 Seg. 3 JU COMM four

JU SEG3
LIST: JU COMM
SEG0:
Program
Segment 0
JU COMM
Common SEG1:
Program
Program
Segment 1
JU COMM
End
SEG3:
Program
Segment 3
COMM:
Common
Program

Figure 16-1 Controlling the Flow of Logic Control Using the Jump to List Instruction JL

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 16-3
Logic Control Instructions

16.3 Conditional Jump Instructions Founded on Result of Logic


Operation

Description The following jump instructions interrupt the flow of logic in your program
based on the result of logic operation (RLO) produced by the previous
instruction statement:
 Jump If RLO = 1 (JC)
 Jump If RLO = 0 (JCN)
 Jump If RLO = 1 with BR (JCB): The RLO is saved in the BR bit of the
status word.
 Jump If RLO = 0 with BR (JNB): The RLO is saved in the BR bit of the
status word.
Irrespectively of the jump, the following status word bits are described:
OR :=0
STA :=1
RLO :=1
FC :=0

Start

I 1.0 = 1 No RLO=1
and I 1.1 = 1?
A I1.0
Program Section B A I1.1
Yes RLO=0 IF
Erase MB10 RLO=0 JCN COMM
L 0
Section B
T MB10
COMM:
Common
Program
Common
Program

End

Figure 16-2 Controlling the Flow of Logic Control Using the Jump If RLO = 0 Instruction JCN

Statement List (STL) for S7-300/S7-400


16-4 C79000-G7076-C565-01
Logic Control Instructions

16.4 Conditional Jump Instructions Founded on BR, OV, or OS Bits of


the Status Word

Description The following jump instructions interrupt the flow of logic in your program
based on the signal state of a bit in the status word (see Section 2.2).
 Jump If BR = 1 with BR (JBI) or Jump If BR = 0 (JNBI)
 Jump If OV = 1 ( JO) or Jump If OS = 1 (JOS)
The JBI and JNBI instructions reset the OR and FC bits of the status word to
0 and set the STA bit to 1. The JOS instruction resets the OS bit to 0.

Start

Reset
OS Bit JOS ODEL Reset OS Bit
ODEL: L MW12

Calculate L MW14
<MW10>=<MW12>+<MW14>–<MW16>
+ I
Calculate
L MW16
– I
Overflow Yes
stored? T MW10

Section C JOS SECC*


No
JPZ SECB
Erase
<MB10> L +10
Section A
Result Yes T MW20
<MW10>  0
JU COMM

No SECB: L +17
Section B
T MW30
Section A Section B
JU COMM
<MW20> = 10 <MW30> = 17 SECC: L 0
Section C
T MW10
COMM:
Common
Program
Common
Program * In this case, do not use the JO instruction.
The JO instruction would check only the
previous – I instruction if an overflow
occurred.
End

Figure 16-3 Controlling the Flow of Logic Control Using the Jump If OS = 1 Instruction JOS, JP

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 16-5
Logic Control Instructions

16.5 Conditional Jump Instructions Based on Result in the CC 1 and


CC 0 Bits of the Status Word

Description The following jump instructions interrupt the flow of logic in your program
based on the result of a calculation:
 Jump If Zero (JZ)
 Jump If Not Zero (JN)
 Jump If Plus (JP, that is, greater than zero)
 Jump If Minus (JM, that is, less than zero)
 Jump If Minus or Zero (JMZ, that is, less than or equal to zero)
 Jump If Plus or Zero (JPZ, that is, greater than or equal to zero, see
Figure 16-4)
 Jump If Unordered (JUO, that is, if one of the numbers in a floating-point
math operation is not a valid floating-point number)

CC 1 and CC 0 in The status word bits CC 1 and CC 0 are described, irrespectively of the result
the Status Word of the previous operation. The signal states of the CC 1 and CC 0 bits of the
status word indicate the conditions shown in Table 16-1.

Table 16-1 Relationship of CC 1 and CC 0 to Conditional Jump Instructions

Signal State
Result of Calculat
Calculation
on Jump Instruct
Instruction
on Tr
Triggered
ggered
CC 1 CC 0
0 0 =0 JZ
1 0
or or <>0 JN
0 1
1 0 >0 JP
0 1 <0 JM
0 0
or or >=0 JPZ
1 0
0 0
or or <=0 JMZ
0 1
1 1 UO (unordered) JUO

Statement List (STL) for S7-300/S7-400


16-6 C79000-G7076-C565-01
Logic Control Instructions

Start

Reset
OS–Bit JOS ODEL Reset OS–Bit
ODEL: L MW12
Calculate L MW14
<MW10>=<MW12>+<MW14>–<MW16>
+ I
Calculate
L MW16

Yes – I
Overflow
stored? T MW10

Section C JOS SECC*


No
Erase <MB10> JPZ SECB
L +10
Section A
Result Yes
T MW20
<MW10> >=0?
JU COMM

No SECB: L +17
Section B
T MW30
Section A Section B
JU COMM
<MW20> = 10 <MW30> = 17
SECC: L 0
Section C
T MW10
COMM:
Common
Program
Common
Program * In this case, do not use the JO instruction.
The JO instruction would check only the
previous – I instruction if an overflow
happened.
End

Figure 16-4 Controlling the Flow of Logic Control Using the Jump If Plus or Zero Instruction JPZ

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 16-7
Logic Control Instructions

16.6 Loop Control

Description You can use the Loop (LOOP) instruction to call a program segment multiple
times (see Figure 16-5). The Loop instruction decrements the low word of
accumulator 1 by 1. Then the value in the low word of accumulator 1 is
tested. If it is not 0, a jump is executed to the label indicated in the address of
the Loop instruction; otherwise the next instruction is executed.

Providing a Label You provide the Loop instruction with a label so it knows the point to which
as Address it should return in the program. For example, the Loop instruction in the
program shown in Figure 22-5 has the label NEXT as its address. This label
tells the instruction to return to the statement T MB10 in th program. At this
point, the program processes Section A. The Loop instruction returns to the
label as many times as you tell it to. You provide this information in the low
word of accumulator 1. One way to do this is to set up a loop counter and
load it into the accumulator.

Start

Initialize Loop
Counter

Initialize
L +5 Loop
Program Section A Counter
NEXT: T MB10

Section A
Decrement Loop
Counter by 1
L MB10
LOOP NEXT
Yes Loop Counter
<> 0?

No

End

Figure 16-5 Using the Loop Instruction to Call a Program Segment Multiple Times

Statement List (STL) for S7-300/S7-400


16-8 C79000-G7076-C565-01
Logic Control Instructions

Setting Up a Loop You provide the Loop instruction with a value that indicates how many times
Counter you want LOOP to call a particular program segment.
The Loop instruction interprets the loop counter as a WORD data type.
Table 16-2 provides information about the two possible formats for a loop
counter.

Table 16-2 Possible Format for a Loop Counter

Value Type Value Range Data Type Memory Area


1 to 65,535
Integer WORD I, Q, M, D, L
(positive value only)
W#16#0001 to
Word WORD I, Q, M, D, L
W#16#FFFF

Using the Loop In order to avoid running a loop more times than is necessary, you need to be
Instruction aware of the following characteristics of the Loop instruction:
Efficiently
 If you initialize the loop counter with a 0, the loop is executed 65,535
times.
 You should avoid initializing the loop counter with a negative number.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 16-9
Logic Control Instructions

Statement List (STL) for S7-300/S7-400


16-10 C79000-G7076-C565-01
Program Control Instructions 17
Chapter Overview Section Description Page
17.1 Parameter Assignment when Calling FCs and FBs 17-2
17.2 Calling Functions and Function Blocks with CALL 17-3
17.3 Calling Functions and Function Blocks with CC and UC 17-7
17.4 Working with Master Control Relay Functions 17-10
17.5 Master Control Relay Instructions 17-11
17.6 Ending Blocks 17-16

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 17-1
Program Control Instructions

17.1 Parameter Assignment when Calling FCs and FBs

Terms When calling blocks that require parameters the terms formal parameters
and actual parameters play an important role.
A formal parameter is a parameter whose name and data type are assigned
and declared (for example, as INPUT, OUTPUT parameters) when the block is
created. When a block is called in the Incremental Editor (for example CALL
SFC31), STEP 7 automatically displays a list of all the formal parameters.
The next step is to assign actual parameters to the formal parameters. An
actual parameter is a parameter which functions and function blocks use
during the actual run time of the user program.
The following diagram shows the call of SFC31 “QRY_TINT” (Query
Time-of-Day Interrupt) in STL.

STL Representation

CALL SFC 31
OB_NO := 10
RET_VAL:= MW 22
STATUS := MW 100

Actual parameters

Formal parameters

Statement List (STL) for S7-300/S7-400


17-2 C79000-G7076-C565-01
Program Control Instructions

17.2 Calling Functions and Function Blocks with CALL

Description You can use the Call (CALL) instruction to call functions (FCs) and function
blocks (FBs) that you have created for your program or that you have
received as standard functions and standard function blocks from Siemens.
The Call instruction calls the FC or FB that you indicate as an address
regardless of the result of logic operation or any other condition.
When you use the Call instruction to call a function block, you must supply
the function block with an instance data block (instance DB) or declare it as a
local instance. The instance data block stores all the static variables and
actual parameters of the function block.
If you need information on how to program a function or a function block, or
how to work with their parameters, see the STEP 7 Online Help.

Formal Parameters When calling a function (FC) or a function block (FB), you must assign
and Actual corresponding actual parameters to the declared formal parameters.
Parameters
The actual parameter that is specified when a function block is called must
have the same data type as the formal parameter.

Specifying the The actual parameters used when a function (FC) or function block (FB) is
Actual Parameters called are generally specified symbolically. Absolute addressing of actual
parameters is possible only for an address whose maximum size is a double
word (for example, I 1.0, MB2, QW4, ID0).
When you call a function, all formal parameters must be supplied with actual
parameters. You only need to declare the actual parameters when these are
different to the parameters of the previous call (actual parameters remain
stored in the instance data block after the processing of the function block
has been completed).
When you call a function block, the Call instruction copies one of the
following items into the instance data block of the function block, depending
on the data type of the actual parameter and on the declaration of the formal
parameter (IN, OUT, IN_OUT):
 The value of the actual parameter
 A pointer to the address of the actual parameter
 A pointer to the L stack of the calling block where the value of the actual
parameter has been buffered

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 17-3
Program Control Instructions

Calling an FB with The call can take place once the following details are entered:
Instance DB and
 The name of the function block
Block Parameters
 The name of the instance data block and
 The parameters (if the actual parameter is a data block, the complete
absolute address must always be specified, for example DB1.DBW2).
The call uses either with an absolute or a symbolic address.

Absolute Call:
CALL FBx,DBy (pass parameters);
x = block number
y = data block number

Symbolic Call:
CALL fbname,datablockname (pass parameters);
fbname = symbolic block name
datablockname = symbolic data block name

Examples The following example shows the call of function block FB40 with instance
data block DB41. In this example, the formal parameters have the following
data types:
IN1: BOOL
IN2: WORD
OUT1: DWORD

STL Explanation
CALL FB40,DB41 Call of FB40 with instance data block DB41.
IN1:= I1.0 IN1 (formal parameter) is supplied with I 1.0 (actual
parameter).
IN2:= MW2 IN2 (formal parameter) is supplied with MW2 (actual
parameter).
OUT1:= MD20 OUT1 (formal parameter) is supplied with MD20 (actual
parameter).
L MD20 With this instruction, the program accesses the formal
parameter OUT1.

The following example shows the call of function block FB50 with instance
data block DB51. In this example, the formal parameters have the following
data types:
IN10: BOOL
OUT11: STRUCT
V1: BOOL
V2: INT
END_STRUCT

Statement List (STL) for S7-300/S7-400


17-4 C79000-G7076-C565-01
Program Control Instructions

STL Explanation
CALL FB50,DB51 Call of FB50 with instance data block DB51.
IN10:= I1.0 IN10 (formal parameter) is supplied with I 1.0 (actual
parameter).
OUT11:= ACTPA11 Here it is not possible to specify an absolute actual
parameter (for example, MW10) because the formal
parameter OUT11 was defined as a structure. Instead, the
symbolic actual parameter ACTPA11 is specified. Please
note that ACTPA11 has the same structure as the formal
parameter OUT11.

Access to the values of the structure OUT11 in FB50 would be made as


follows:

STL Explanation
A OUT11.V1 Perform an AND logic operation on the bit OUT11.V1.
L OUT11.V2 Load word OUT11.V2 into accumulator 1.

Calling Multiple The call can take place once the following details are entered:
Instances
 The instance name (= name of a static variable of the type FB z) and
 The Parameters
The call always has a symbolic designation.
CALL Instance Name (pass parameters);

STL Explanation
FUNCTION_BLOCK FB 11 Source file
VAR
loc_inst : FB 10; Declaration of a multiple instance with data type FB10
END_VAR
BEGIN
NETWORK
CALL #loc_inst ( Call of the multiple instance with syntax
in_bool := M Parameter pass
0.0); (in_bool in this case is a variable declared in FB10)

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 17-5
Program Control Instructions

Calling an FC with The call can take place once the following details are entered:
Block Parameters
 The name of the fucntion block and
 The parameters
The call is addressed either with an absolute or a symbolic name.

Absolute Call:
CALL FCx (pass parameters);
x = block number

Symbolic Call:
CALL fcname (pass parameters);
fcname = symbolic block name

Example The following example shows the call of function FC80 with block
parameters. In this example, the formal parameters have the following data
types:
INC1: BOOL
INC2: INT
OUT: WORD

STL Explanation
CALL FC80 Call FC80.
INC1:= M 1.0 INC1 (formal parameter) is supplied with M 1.0 (actual
parameter).
INC2:= IW2 INC2 (formal parameter) is supplied with IW2 (actual
parameter).
OUT:= QW4 OUT (formal parameter) is supplied with QW4 (actual
parameter).

Calling an FC That You can create a function (FC) that delivers a return value (RET_VAL). For
Delivers a Return example, if you want to create a floating-point math function, you can use
Value this return value as an output for the result of your function. When you call
this function in your program, you provide the output “RET_VAL” with a
double word location to accommodate the 32-bit result of your floating-point
math function.

Statement List (STL) for S7-300/S7-400


17-6 C79000-G7076-C565-01
Program Control Instructions

17.3 Calling Functions and Function Blocks with CC and UC

Description You can use the following instructions to call functions (FCs) and function
blocks (FBs) that you have created for your program in the same way as
using the Call instruction. Using these instructions, you cannot transfer
parameters.
 Conditional Call (CC): Calls the function or function block that you
indicate as an address if the result of logic operation is 1.
 Unconditional Call (UC): Calls the function or function block that you
indicate as an address regardless of the result of logic operation or any
other condition.
It is not possible for function blocks which are called with either a CC or a
UC instruction to have associated data blocks.

Addressing A CC or UC instruction can call a function (FC) or a function block (FB)


Format using direct or memory indirect addressing or via an FC or FB transferred as
a parameter (see Tables 17-1 and 17-2). The address is FC plus the number of
the FC.

Table 17-1 Addresses of CC and UC Instructions: Direct and Indirect Addressing

FC or FB Maximum Range of Address Number according to Addressing Type


Part of
Address Direct Memory Indirect

[DBW]
FC [DIW]
0 to 65,535 0 to 65,534
FB [LW]
[MW]

Table 17-2 Addresses of CC and UC Instructions: FC Transferred as Parameter

Address Parameter Data Types


Name of the formal parameter or a BLOCK_FC 1
symbolic name BLOCK_FB 1

1 Parameters of type BLOCK_FC or BLOCK_FB cannot be used with the CC


command in FCs and FBs.

Example To call an FC that you had created and given the number 12, you would use
one of the following instructions, depending on whether you want the call to
be conditional or not:
CC FC12 (Call FC12 if the RLO is 1.)
UC FC12 (Call FC12 no matter what the RLO is.)

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 17-7
Program Control Instructions

Assigning Actual Depending on the data type there are various ways to assign actual
Parameters parameters to the formal parameters when you call a function or a function
block. The following table is compiled according to the length of the data
type.

Table 17-3 Assigning Actual Parameters

Data Type of Example of Assigning an Actual Parameter


Formall Parameter
F P t
Direct Input (Value) Input of a Shared Symbolic Input1
Data Element
BOOL (Bit) TRUE M 100.0 #OK_BIT
I 0.0
Q 0.0
DBX 3.0
BYTE (Byte) B#16#1F MB 100 #TYP_BYTE
IB 0
QB 0
CHAR ’K’ DBB 1 #TYP_CHAR
WORD (Word) W#16#1F12 MW 100 #TYP_WORD
2#0001_1111_0001_0010 IW 0
C#32 QW 0
B#(5,25) DBW 2
INT (Integer) 27 #TYP_INT
–25
S5TIME (S5 Time) S5T#10MS #TYP_S5_TIME
DATE (IEC Date) D#1995–12–24 #TYP_DATE
DWORD (Double DW#16#FFFF_0F02 MD 100 #TYP_DWORD
Word)
2#0001_1111_0001_0010_0001 ID 0
_1111_0001_0010
QD 0
B#(5,4,59,8)
DBD 4
DINT (Double L#170 #TYP_DINT
Integer)
L#-350
REAL (Floating- 1.23 #TYP_REAL
Point Number)
TIME (IEC Time) T#20MS #TYP_TIME
TIME_OF_DAY TOD#23:59:12.3 #TYP_TOD
(IEC Time-of-Day)

Statement List (STL) for S7-300/S7-400


17-8 C79000-G7076-C565-01
Program Control Instructions

Table 17-3 Assigning Actual Parameters, continued

Data Type of Example of Assigning an Actual Parameter


Formal Parameter
Direct Input (Value) Input of a Shared Symbolic Input1
Data Element
DATE_AND_TIME Not possible #TYP_8_BYTE
(IEC Date and Time)
(Variable must be declared, for example, temporary
variable)
ANY (Data type of P#M0.0 BYTE20 E 0.0 #TYP_ANYTYP
any type and size)
MB 5 (Declaration of
20 bytes 2 ...
... from bit memory 0.0 3 arrays and struc-
AW 2
tures)
Prefix for ANY pointer
(Use of any STEP 7
shared addresses
P#DB58.DBX16.0 BYTE14 possible)

14 bytes 2 ...
... in DB58 from data bit 16.0 3
Prefix for ANY pointer

1 Prerequisite: In the case of shared data, the name (= symbol) must be declared in the symbol table before it can be used
as an actual parameter. In the case of local data, the name (= symbol) must be declared in the declaration table of the
block before it can be used as an actual parameter. Local data symbols must be preceded by a hash #.
2 Length specification can include elementary data types, for example BOOL, BYTE, WORD or DWORD or complex
types, for example DATE_AND_TIME.
3 Always enter a bit address; in length specifications enter 0 as the bit address (exception: BOOL).

Conditional Call in In order to call an SFC conditionally, you can follow a sequence similar to
STL the following:

STL Explanation
A #OK_BIT_MEMORY Condition for the call
JCNB m001 If the condition is not fulfilled
CALL SFC 28 (RLO=0), the call of the SFC is
OB_NO := 10 jumped and the RLO in the status bit
SDT := #OUT_TIME_DATE is saved.
PERIOD := W#16#1201
RET_VAL := MW 200
m001: A BR Check status bit BR
= M 202.3

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 17-9
Program Control Instructions

17.4 Working with Master Control Relay Functions

Description The Master Control Relay (MCR) is an American relay ladder logic master
switch for energizing and de-energizing power flow (current path). A
de-energized current path corresponds to an instruction sequence that writes a
zero value instead of the calculated value, or, to an instruction sequence that
leaves the existing memory value unchanged. Operations triggered by the
following bit logic and transfer instructions are dependent on the MCR:
 =
 S
 R
 T (used with byte, word, or double word)
The T instruction used with byte, word, or double word, and the = instruction
write a 0 to the memory if the MCR is 0. The S and R instructions leave the
existing value unchanged.

Table 17-4 Operations Dependent on MCR and How They React to Its Signal State

Signal State = S or R T
of MCR
0 Writes 0 Does not write Writes 0

(Imitates a relay that (Imitates a latching (Imitates a component


falls to its quiet state relay that remains in that, on loss of
when voltage is its current state when voltage, produces a
removed) voltage is removed) value of 0)
1 Normal execution Normal execution Normal execution

Statement List (STL) for S7-300/S7-400


17-10 C79000-G7076-C565-01
Program Control Instructions

17.5 Master Control Relay Instructions

Overview You can use the following statements to implement a master control relay:
 MCRA Activate MCR Area
 MCRD Deactivate MCR Area
 MCR( Save RLO in MCR Stack, Begin MCR Area
 )MCR End MCR Area

Description: The following instructions activate or deactivate an MCR area, that is, they
MCRA, MCRD specify which instructions in your program depend on the MCR (see also
Figure 17-1):
 Activate MCR Area: MCRA
 Deactivate MCR Area: MCRD
The instructions that are programmed between the MCRA and the MCRD
statements depend on the signal state of the MCR bit. The instructions that
are programmed outside an MCRA-MCRD sequence do not depend on the
signal state of the MCR bit. If an MCRD instruction is missing, the
instructions programmed between an MCRA instruction and a BEU
instruction depend on the MCR bit (see Figure 17-1).
You must program the MCR dependency of functions (FCs) and function
blocks (FBs) in the blocks themselves, that is, if such a function or function
block is called from an MCRA-MCRD sequence, all the commands within
that sequence are not automatically dependent on the MCR bit. To make the
instructions in a called block dependent on the MCR bit, you must use the
MCRA instruction in the block that is called.

Danger
! Never use the MCR instruction as an emergency off or personnel safety
device.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 17-11
Program Control Instructions

ÀÀÀÀÀÀ OB1

ÀÀÀÀÀÀ ÀÀÀÀÀÀ ÀÀÀÀÀÀÀ


ÀÀÀÀÀÀ ÀÀÀÀÀÀ
FBx

ÀÀÀÀÀÀÀ
FCy

ÀÀÀÀÀÀ ÀÀÀÀÀÀ ÀÀÀÀÀÀÀ


ÀÀÀÀÀÀ ÀÀÀÀÀÀ ÀÀÀÀÀÀÀ
ÀÀÀÀÀÀ MCRA
ÀÀÀÀÀÀ ÀÀÀÀÀÀÀ
ÀÀÀÀÀÀ MCRA

MCRA

ÀÀÀÀÀÀ
MCRD CALL FCy

ÀÀÀÀÀÀ ÀÀÀÀÀÀ
ÀÀÀÀÀÀ CALL FBx

ÀÀÀÀÀÀ
ÀÀÀÀÀÀ
MCRD

ÀÀÀÀÀÀ MCRA
ÀÀÀÀÀÀ BEU

BEU

Instructions do not depend on the MCR bit

Instructions depend on the MCR bit

Figure 17-1 Activating and Deactivating a Master Control Relay Area

Statement List (STL) for S7-300/S7-400


17-12 C79000-G7076-C565-01
Program Control Instructions

Description: MCR(, The following instructions turn the Master Control Relay function on and off:
)MCR
 Save RLO in MCR Stack, Begin MCR: MCR(
 End MCR: )MCR
You can nest MCR( and )MCR instructions. The maximum nesting depth is
eight, that is, you can have a maximum of eight MCR( instructions in
sequence before you insert an )MCR instruction. You must program an equal
number of MCR( and )MCR instructions (see Figure 17-3).
When MCR( instructions are nested, the MCR bit of the deeper nesting levels
is formed. To form this MCR bit, the MCR( instruction combines the current
RLO with the current MCR bit according to the And truth table.
The )MCR instruction terminates a nesting level by restoring the MCR bit
from the higher level. The )MCR instruction of the highest level sets the
MCR bit to 1.
If you use MCR( and )MCR in your program, you must always use them in
pairs.

Example Figure 17-2 shows how to implement a Master Control Relay.


If the MCR bit is 1, then the MCR contact is closed. The signal states of
outputs Q 4.0 and Q 4.1 are calculated according to the signal state of inputs
I 1.0 to I 1.3 and their logic combinations.
If the MCR bit is 0, then the MCR contact is opened. The outputs Q 4.0 and
Q 4.1 are reset to 0, regardless of the signal states of inputs I 1.0 to I 1.3.

STL Relay Logic Diagram

MCR
contact
MCRA Power rail
A I 2.0
MCR(
O I 1.0 I 2.0 I 1.0 I 1.1 I 1.2
O I 1.1
= Q 4.0
A I 1.2 I 1.3
A I 1.3
= Q 4.1
)MCR Q 4.0 Q 4.1
MCRD
MCR coil

Master Control Relay Area which is controlled by the MCR


implemented with the MCR( (Master Control Relay), implemented with
and )MCR instructions MCRA and MCRD instructions

Figure 17-2 Implementation of a Master Control Relay

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 17-13
Program Control Instructions

Figure 17-3 shows the nesting application of the instructions.

Signal Result of RLO MCR Bit of Level


STL
State Check 1 2 3

MCRA
A I 1.1 1 1 1
MCR ( 1
A I 1.2 1 1 1 1
MCR ( * 1
A I 1.3 0 0 0 1
MCR (
0
0
This bit (M 1.0) remains unchanged 0
regardless of any previous logic 0
S M 1.0 string because the MCR bit = 0. 0
)MCR
1 **
This bit (M 1.1) is changed due to 1
the previous logic string and the 1
S M 1.1 function of the S instruction because 1
)MCR the MCR = 1.
1
1
1
1
)MCR
MCRD

* The MCR bit of the deeper nesting level is formed. To form this MCR bit, the MCR(
instruction combines the current RLO with the MCR bit of the current
nesting level according to the And truth table.
** When the )MCR instruction ends a nesting level, the instruction restores the MCR bit of the
next higher level.

Figure 17-3 Nesting Application of MCR Instructions

Statement List (STL) for S7-300/S7-400


17-14 C79000-G7076-C565-01
Program Control Instructions

Important Notes on Using MCR Functions

Take care with blocks in which the Master Control Relay was activated with
MCRA:
 If the MCR is deactivated, the value 0 is written by all assignments in
program segments between (MCR<) and (MCR>).
 The MCR is deactivated if the RLO was =0 before an (MCR<) instruc-
tion.

Danger
! PLC in STOP or undefined runtime characteristics!
The compiler also uses write access to local data behind the temporary varia-
bles defined in VAR_TEMP for calculating addresses.
Formal parameter access
 Access to components of complex FC parameters of the type STRUCT,
UDT, ARRAY, STRING
 Access to components of complex FB parameters of the type STRUCT,
UDT, ARRAY, STRING from the IN_OUT area in a version 2 block.
 Access to parameters of a version 2 function block if its address is
greater than 8180.0.
 Access in a version 2 function block to a parameter of the type
BLOCK_DB opens DB0. Any subsequent data access sets the CPU to
STOP. T 0, C 0, FC0 or FB0 are always used for TIMER, COUNTER,
BLOCK_FC, and BLOCK_FB.
Parameter passing
 Calls in which parameters are transferred.
KOP/FUP
 T branches and midline outputs in Ladder or FBD starting with RLO=0.

Remedy:
Free the above commands from their dependence on the MCR:
1. Deactivate the Master Control Relay using the Master Control Relay De-
activate instruction before the statement or network in question.
2. Activate the Master Control Relay again mit Master Control Relay Acti-
vate instruction after the statement or network in question.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 17-15
Program Control Instructions

17.6 Ending Blocks

Description A Block End instruction is by itself a programming statement that terminates


the scanning of a block. You can use either of the following types of
Block End instructions to end a block:
 Block End Unconditional (BEU): This instruction ends scanning in the
current block and returns control to the block that called the one that has
been terminated. When the program encounters a BEU instruction, it
terminates the current block, regardless of the result of logic operation.
 Block End Conditional (BEC): This instruction ends scanning in the
current block and returns control to the block that called the one that has
been terminated. When the program encounters a BEC instruction, it
terminates the current block only if the result of logic operation is 1
(RLO = 1). If the RLO is 0, the program does not execute the Block End
Conditional (BEC) statement. The RLO is set to 1 and program scanning
continues within the current block.

Statement List (STL) for S7-300/S7-400


17-16 C79000-G7076-C565-01
Alphabetical Listing of
Instructions A
Appendix
Programming Examples B
Source Files – Examples and
Reserved Key Words C

References D
Statement List (STL) for S7-300/S7-400
Q-2 C79000-G7076-C565-01
Alphabetical Listing of Instructions A
Chapter Overview Section Description Page
A.1 Listing with (German) SIMATIC and International A-2
Mnemonics
A.2 Alphabetical Listing with International Names A-12

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 A-1
Alphabetical Listing of Instructions

A.1 Listing with (German) SIMATIC and International Mnemonics

Table A-1 provides an alphabetical listing of the mnemonic abbreviations of


the statement list instructions. Next to each German abbreviation are the
equivalent international abbreviation, the full international name and the
page on which the instruction is explained.

Table A-1 Alphabetical Listing with the SIMATIC and the International Mnemonic Abbreviations

SIMATIC International Name Page


Abbreviation Abbreviation No.
+ + Add Integer Constant (8, 16, 32-Bit) 9-6
= = Assign 5-24
) ) Nesting Closed 5-14
+AR1 +AR1 Add Accumulator 1 to Address Register 1 4-7
+AR2 +AR2 Add Accumulator 1 to Address Register 2 4-7
+D +D Add Accumulator 1 and Accumulator 2 as Double Integer (32-Bit) 9-2
-D -D Subtract Accumulator 1 and Accumulator 2 as Double Integer (32-Bit) 9-2
*D *D Multiply Accumulator 1 by Accumulator 2 as Double Integer (32-Bit) 9-2
/D /D Divide Accumulator 2 by Accumulator 1 as Doubel Integer (32-Bit) 9-2
==D ==D Compare Double Integer (32-Bit) >, <, >=, <=, ==, <> 17-3
+I +I Add Accumulator 1 and Accumulator 2 as Integer (16-Bit) 9-2
-I -I Subtract Accumulator 1 from Accumulator 2 as Integer (16-Bit) 9-2
*I *I Multiply Accumulator 1 by Accumulator 2 as Integer (16-Bit) 9-2
/I /I Divide Accumulator 2 by Accumulator 1 as Integer (16-Bit) 9-2
==I ==I Compare Integer (16-Bit) >, <, >=, <=, ==, <> 17-3
+R +R Add Accumulator 1 and Accumulator 2 as Real (32-Bit IEEE FP) 10-2
-R -R Subtract Accumulator 1 from Accumulator 2 as Real (32-Bit IEEE FP) 10-2
*R *R Multiply Accumulator 1 by Accumulator 2 as Real (32 Bit IEEE FP) 10-2
/R /R Divide Accumulator 2 by Accumulator 1 as Real (32-Bit IEEE FP) 10-2
==R ==R Compare Real >, <, >=, <=, ==, <> 17-5
ABS ABS Absolute Value of a Real (32-Bit IEEE FP) 10-6
ACOS ACOS Arc Cosine of a Floating-Point Number (32-Bit IEEE FP) 10-7
ASIN ASIN Arc Sine of a Floating-Point Number (32-Bit IEEE FP) 10-7
ATAN ATAN Arc Tangent of a Floating-Point Number (32-Bit IEEE FP) 10-7
AUF OPN Call a Data Block 21-2
BEA BEU Block End Unconditional 17-16
BEB BEC Block End Conditional 17-16
BLD BLD Program Display Instruction 4-2
BTD BTD BCD to Double Integer (32-Bit) 18-4
BTI BTI BCD to Integer (16-Bit) 18-2
CALL CALL Call 17-3

Statement List (STL) for S7-300/S7-400


A-2 C79000-G7076-C565-01
Alphabetical Listing of Instructions

Table A-1 Alphabetical Listing with the SIMATIC and the International Mnemonic Abbreviations, cont.

SIMATIC International Name Page


Abbreviation Abbreviation No.
CC CC Conditional Call 17-7
CLR CLR Clear RLO (= 0) 5-26
COS COS Cosine of a Floating-Point Number (32-Bit IEEE FP) 10-7
DEC DEC Decrement Accumulator 1 4-6
DTB DTB Double Integer (32-Bit) to BCD 12-6
DTR DTR Double Integer (32-Bit) to Real (32-Bit IEEE FP) 12-7
ENT ENT Accumulator 3 ---> Accumulator 4, Accumulator 2 ---> Accumulator 3 4-3
EXP EXP Exponential Value of a Floating-Point Number (32-Bit IEEE FP) to 10-12
Base E
FN FN Edge Negative 5-17
FP FP Edge Positive 5-16
FR FR Enable Counter (Free, FR C 0 to C 255) 6-5
FR FR Enable Timer (Free, FR T 0 to T 255) 7-3
INC INC Increment Accumulator 1 4-6
INVD INVD Ones Complement Double Integer (32-Bit) 12-14
INVI INVI Ones Complement Integer (16-Bit) 12-14
ITB ITB Integer (16-Bit) to BCD 12-5
ITD ITD Integer (16-Bit) to Double Integer (32-Bit) 12-6
L L Load 8-3
L L Load Length of Shared Data Block into Accumulator 1 (L DBLG) 8-12
15-2
L L Load Number of Shared Data Block into Accumulator 1 (L DBNO) 8-12
L L Load Length of Instance Data Block into Accumulator 1 (L DILG) 8-12
15-2
L L Load Number of Instance Data Block into Accumulator 1 (L DINO) 8-12
15-2
L L Load Status Word into Accumulator 1 (L STW) 8-6
L L Load Current Timer Value into Accumulator 1 as Integer (where the 8-7
number of the current timer can be in the range of 0 to 255, for example:
L T 32)
L L Load Current Counter Value into Accumulator 1 as Integer (where the 7-6
number of the current counter can be in the range of 0 to 255, for exam- 8-8
ple: L C 15)
LAR1 LAR1 Load Address Register 1 from Accumulator 1 8-11
(if no address is indicated)
LAR1 LAR1 Load Address Register 1 from ... (from address indicated) 8-11
LAR1 LAR1 Load Address Register 1 from Address Register 2 (LAR1 AR2) 8-11
LAR1 LAR1 Load Address Register 1 with Double Integer (32-Bit, LAR1 P#area 8-11
byte.bit)
LAR2 LAR2 Load Address Register 2 from Accumulator 1 (if no address is indi- 8-11
cated)

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 A-3
Alphabetical Listing of Instructions

Table A-1 Alphabetical Listing with the SIMATIC and the International Mnemonic Abbreviations, cont.

SIMATIC International Name Page


Abbreviation Abbreviation No.
LAR2 LAR2 Load Address Register 2 from ... (from address indicated) 8-11
LAR2 LAR2 Load Address Register 2 with Double Integer (32-Bit, LAR2 P#area 8-11
byte.bit)
LC LC Load Current Counter Value into Accumulator 1 as BCD (where the 8-9
number of the current counter can be in the range of 0 to 255, for
example: LC C 15)
LC LC Load Current Timer Value into Accumulator 1 as BCD (where the 7-7
number of the current timer can be in the range of 0 to 255, for example: 8-9
LC T 32)
LEAVE LEAVE Accumulator 3 ---> Accumulator 2, Accumulator 4 ---> Accumulator 3 4-3
LN LN Natural Logarithm of a Floating-Point Number (32-Bit IEEE FP) 10-11
LOOP LOOP Loop 16-8
MCR( MCR( Save RLO in MCR Stack, Begin MCR 17-11
)MCR MCR) Restore RLO, End MCR 17-11
MCRA MCRA Activate MCR Area 17-11
MCRD MCRD Deactivate MCR Area 17-11
MOD MOD Division Remainder Double Integer (32-Bit) 9-5
NEGD NEGD Twos Complement Double Integer (32-Bit) 12-14
NEGI NEGI Twos Complement Integer (16-Bit) 12-14
NEGR NEGR Negate Real Number 12-14
NOP 0 NOP 0 Null Operation 0 4-2
NOP 1 NOP 1 Null Operation 1 4-2
NOT NOT Negate RLO 5-26
O O Or 5-10
O( O( Or with Nesting Open 5-14
OD OD Or Double Word (32-Bit) 13-6
ON ON Or Not 5-8
ON( ON( Or Not with Nesting Open 5-14
OW OW Or Word (16-Bit) 13-3
POP POP Accumulator 1 <--- Accumulator 2, Accumulator 2 <--- Accumulator 3, 4-2
Accumulator 3 <--- Accumulator 4
PUSH PUSH Accumulator 3 ---> Accumulator 4, Accumulator 2 ---> Accumulator 3, 4-2
Accumulator 1 ---> Accumulator 2
R R Reset 5-22
R R Reset Counter (where the current counter can have a number in the 6-5
range of 0 to 255, for example: R C 15)
R R Reset Timer (where the current timer can have a number in the range of 7-4
0 to 255, for example: R T 32)
RLD RLD Rotate Left Double Word (32-Bit) 14-8
RLDA RLDA Rotate Accumulator 1 Left via CC 1 (32-Bit) 14-6

Statement List (STL) for S7-300/S7-400


A-4 C79000-G7076-C565-01
Alphabetical Listing of Instructions

Table A-1 Alphabetical Listing with the SIMATIC and the International Mnemonic Abbreviations, cont.

SIMATIC International Name Page


Abbreviation Abbreviation No.
RND RND Round 12-9
RND+ RND+ Round to Upper Double Integer 12-10
RND- RND- Round to Lower Double Integer 12-11
RRD RRD Rotate Right Double Word (32-Bit) 14-8
RRDA RRDA Rotate Accumulator 1 Right via CC 1 (32-Bit) 14-6
S S Set 5-21
S S Set Counter Preset Value (where the current counter can have a number 7-3
in the range of 0 to 255, for example: S C 15)
SA SF Off-Delay Timer 6-15
SAVE SAVE Save RLO in BR Register 5-26
SE SD On-Delay Timer 6-11
SET SET Set RLO (= 1) 5-26
SI SP Pulse Timer 6-7
SIN SIN Sine of a Floating-Point Number (32-Bit IEEE FP) 10-7
SLD SLD Shift Left Double Word (32-Bit) 14-2
SLW SLW Shift Left Word (16-Bit) 14-2
SPA JU Jump Unconditional 16-3
SPB JC Jump if RLO = 1 16-4
SPBB JCB Jump if RLO = 1 with BR 16-4
SPBI JBI Jump if BR = 1 16-4
SPBIN JNBI Jump if BR = 0 16-4
SPBN JCN Jump if RLO = 0 16-4
SPBNB JNB Jump if RLO = 0 with BR 16-4
SPL JL Jump to Labels 16-3
SPM JM Jump if Minus 16-6
SPMZ JMZ Jump if Minus or 0 16-6
SPN JN Jump if Not 0 16-6
SPO JO Jump if OV = 1 16-5
SPP JP Jump if Plus 16-6
SPPZ JPZ Jump if Plus or 0 16-6
SPS JOS Jump if OS = 1 16-5
SPU JUO Jump if Unordered 16-6
SPZ JZ Jump if 0 16-6
SQR SQR Square of a Floating-Point Number (32-Bit IEEE PF) 10-9
SQRT SQRT Square Root of a Floating-Point Number (32-Bit IEEE PF) 10-9
SRD SRD Shift Right Double Word (32-Bit) 14-3
SRW SRW Shift Right Word (16-Bit) 14-2

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 A-5
Alphabetical Listing of Instructions

Table A-1 Alphabetical Listing with the SIMATIC and the International Mnemonic Abbreviations, cont.

SIMATIC International Name Page


Abbreviation Abbreviation No.
SS SS Retentive On-Delay Timer 6-13
SSD SSD Shift Sign Double Integer (32-Bit) 14-4
SSI SSI Shift Sign Integer (16-Bit) 14-4
SV SE Extended Pulse Timer 6-9
T T Transfer 8-3
T T Transfer Accumulator 1 to Status Word (T STW) 8-6
TAD CAD Change Byte Sequence in Accumulator 1 (32-Bit) 12-13
TAK TAK Toggle Accumulator 1 with Accumulator 2 4-2
TAN TAN Tangent of a Floating-Point Number (32-Bit IEEE FP) 10-7
TAR CAR Exchange Address Register 1 with Address Register 2 8-11
TAR1 TAR1 Transfer Address Register 1 to Accumulator 1 (if no address is 8-11
indicated)
TAR1 TAR1 Transfer Address Register 1 to ... (to address indicated) 8-11
TAR1 TAR1 Transfer Address Register 1 to Address Register 2 (T AR1 AR2) 8-11
TAR2 TAR2 Transfer Address Register 2 to Accumulator 1 (if no address is 8-11
indicated)
TAR2 TAR2 Transfer Address Register 2 to ... (to address indicated) 8-11
TAW CAW Change Byte Sequence in Accumulator 1 (16-Bit) 12-13
TDB CDB Exchange Shared Data Block and Instance Data Block 15-2
TRUNC TRUNC Truncate 12-12
U A And 5-10
U( A( And with Nesting Open 5-14
UC UC Unconditional Call 17-7
UD AD And Double Word (32-Bit) 13-6
UN AN And Not 5-8
UN( AN( And Not with Nesting Open 5-14
UW AW And Word (16-Bit) 13-3
X X Exclusive Or 5-10
X( X( Exclusive Or with Nesting Open 5-14
XN XN Exclusive Or Not 5-8
XN( XN( Exclusive Or Not with Nesting Open 5-14
XOD XOD Exclusive Or Double Word (32-Bit) 13-6
XOW XOW Exclusive Or Word (16-Bit) 13-3
ZR CD Counter Down 7-5
ZV CU Counter Up 7-5

Statement List (STL) for S7-300/S7-400


A-6 C79000-G7076-C565-01
Alphabetical Listing of Instructions

Table A-2 provides an alphabetical listing of the mnemonic abbreviations of


the statement list instructions. Next to each international abbreviation are the
equivalent (German) SIMATIC abbreviation, the full international name and
the page on which the instruction is explained.

Table A-2 Alphabetical Listing with the International and the SIMATIC Mnemonic Abbreviations

International SIMATIC Name Page


Abbreviation Abbreviation No.
+ + Add Integer Constant (8, 16, 32-Bit) 15-6
= = Assign 11-24
) ) Nesting Closed 11-14
+AR1 +AR1 Add Accumulator 1 to Address Register 1 10-7
+AR2 +AR2 Add Accumulator 1 to Address Register 2 10-7
+D +D Add Accumulator 1 and Accumulator 2 as Double Integer (32-Bit) 15-2
-D -D Subtract Accumulator 1 from Accumulator 2 as Double Integer 15-2
(32-Bit)
*D *D Multiply Accumulator 1 by Accumulator 2 as Double Integer (32-Bit) 15-2
/D /D Divide Accumulator 2 by Accumulator 1 as Double Integer (32-Bit) 15-2
==D ==D Compare Double Integer (32-Bit) >, <, >=, <=, ==, <> 17-3
+I +I Add Accumulator 1 and Accumulator 2 as Integer (16-Bit) 15-2
-I -I Subtract Accumulator 1 from Accumulator 2 as Integer (16-Bit) 15-2
*I *I Multiply Accumulator 1 by Accumulator 2 as Integer (16-Bit) 15-2
/I /I Divide Accumulator 2 by Accumulator 1 as Integer (16-Bit) 15-2
==I ==I Compare Integer (16-Bit) >, <, >=, <=, ==, <> 17-3
+R +R Add Accumulator 1 and Accumulator 2 as Real (32-Bit IEEE FP) 16-2
-R -R Subtract Accumulator 1 from Accumulator 2 as Real (32-Bit IEEE FP) 16-2
*R *R Multiply Accumulator 1 by Accumulator 2 as Real (32-Bit IEEE FP) 16-2
/R /R Divide Accumulator 2 by Accumulator 1 as Real (32-Bit IEEE FP) 16-2
==R ==R Compare Real >, <, >=, <=, ==, <> 17-5
A U And 11-10
A( U( And with Nesting Open 11-14
ABS ABS Absolute Value of a Real (32-Bit IEEE FP) 16-6
ACOS ACOS Arc Cosine of a Floating-Point Number (32-Bit IEEE FP) 16-7
AD UD And Double Word (32-Bit) 19-6
AN UN And Not 11-9
AN( UN( And Not with Nesting Open 11-14
ASIN ASIN Arc Sine of a Floating-Point Number (32-Bit IEEE FP) 16-7
ATAN ATAN Arc Tangent of a Floating-Point Number (32-Bit IEEE FP) 16-7
AW UW And Word (16-Bit) 19-3
BEC BEB Block End Conditional 23-15
BEU BEA Block End Unconditional 23-15

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 A-7
Alphabetical Listing of Instructions

Table A-2 Alphabetical Listing with the International and the SIMATIC Mnemonic Abbreviations, cont.

International SIMATIC Name Page


Abbreviation Abbreviation No.
BLD BLD Program Display Instruction 10-2
BTD BTD BCD to Double Integer (32-Bit) 18-4
BTI BTI BCD to Integer (16-Bit) 18-2
CAD TAD Change Byte Sequence in Accumulator 1 (32-Bit) 18-13
CALL CALL Call 23-3
CAR TAR Exchange Address Register 1 with Address Register 2 14-11
CAW TAW Change Byte Sequence in Accumulator 1 (16-Bit) 18-13
CC CC Conditional Call 23-7
CD ZR Counter Down 13-5
CDB TDB Exchange Shared Data Block and Instance Data Block 21-2
CLR CLR Clear RLO (= 0) 11-26
COS COS Cosine of a Floating-Point Number (32-Bit IEEE FP) 16-7
CU ZV Counter Up 13-5
DEC DEC Decrement Accumulator 1 10-6
DTB DTB Double Integer (32-Bit) to BCD 18-6
DTR DTR Double Integer (32-Bit) to Real (32-Bit IEEE FP) 18-7
ENT ENT Accumulator 3 ---> Accumulator 4, Accumulator 2 ---> Accumulator 3 10-3
EXP EXP Exponential Value of a Floating-Point Number (32-Bit IEEE FP) to 16-12
base E
FN FN Edge Negative 11-17
FP FP Edge Positive 11-16
FR FR Enable Counter (Free, FR C 0 to C 255) 12-5
FR FR Enable Timer (Free, FR T 0 to T 255) 13-3
INC INC Increment Accumulator 1 10-6
INVD INVD Ones Complement Double Integer (32-Bit) 18-14
INVI INVI Ones Complement Integer (16-Bit) 18-14
ITB ITB Integer (16-Bit) to BCD 18-5
ITD ITD Integer (16-Bit) to Double Integer 18-6
JBI SPBI Jump if BR = 1 22-4
JC SPB Jump if RLO = 1 22-4
JCB SPBB Jump if RLO = 1 with BR 22-4
JCN SPBN Jump if RLO = 0 22-4
JL SPL Jump to Labels 22-3
JM SPM Jump if Minus 22-6
JMZ SPMZ Jump if Minus or 0 22-6
JN SPN Jump if Not 0 22-6
JNB SPBNB Jump if RLO = 0 with BR 22-4

Statement List (STL) for S7-300/S7-400


A-8 C79000-G7076-C565-01
Alphabetical Listing of Instructions

Table A-2 Alphabetical Listing with the International and the SIMATIC Mnemonic Abbreviations, cont.

International SIMATIC Name Page


Abbreviation Abbreviation No.
JNBI SPBIN Jump if BR = 0 22-4
JO SPO Jump if OV = 1 22-5
JOS SPS Jump if OS = 1 22-5
JP SPP Jump if Plus 22-5
JPZ SPPZ Jump if Plus or 0 22-6
JU SPA Jump Unconditional 22-3
JUO SPU Jump if Unordered 22-6
JZ SPZ Jump if 0 22-6
L L Load 14-3
L L Load Length of Shared Data Block into Accumulator 1 (L DBLG) 14-12
21-2
L L Load Number of Shared Data Block into Accumulator 1 (L DBNO) 14-12
L L Load Length of Instance Data Block into Accumulator 1 (L DILG) 14-12
21-2
L L Load Number of Instance Data Block into Accumulator 1 (L DINO) 14-12
21-2
L L Load Status Word into Accumulator 1 (L STW) 14-6
L L Load Current Timer Value into Accumulator 1 as Integer (where the 14-7
number of the current timer can be in the range of 0 to 255, for
example: L T 32)
L L Load Current Counter Value into Accumulator 1 as Integer (where the 13-6
number of the current counter can be in the range of 0 to 255, for 14-8
example: L C 15)
LAR1 LAR1 Load Address Register 1 from Accumulator 1 (if no address is 14-11
indicated)
LAR1 LAR1 Load Address Register 1 from ... (from address indicated) 14-11
LAR1 LAR1 Load Address Register 1 from Address Register 2 (LAR1 AR2) 14-11
LAR1 LAR1 Load Address Register 1 with Double Integer 14-11
(32-Bit, LAR1 P#area byte.bit)
LAR2 LAR2 Load Address Register 2 from Accumulator 1 (if no address is 14-11
indicated)
LAR2 LAR2 Load Address Register 2 from ... (from address indicated) 14-11
LAR2 LAR2 Load Address Register 2 with Double Integer (32-Bit, LAR2 P#area 14-11
byte.bit)
LC LC Load Current Counter Value into Accumulator 1 as BCD (where the 14-9
number of the current counter can be in the range of 0 to 255, for
example: LC C 15)
LC LC Load Current Timer Value into Accumulator 1 as BCD (where the 13-7
number of the current timer can be in the range of 0 to 255, for 14-10
example: LC T 32)
LEAVE LEAVE Accumulator 3 ---> Accumulator 2, Accumulator 4 ---> Accumulator 3 10-3
LN LN Natural Logarithm of a Floating-Point Number (32-Bit IEEE FP) 16-11

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 A-9
Alphabetical Listing of Instructions

Table A-2 Alphabetical Listing with the International and the SIMATIC Mnemonic Abbreviations, cont.

International SIMATIC Name Page


Abbreviation Abbreviation No.
LOOP LOOP Loop 22-8
MCR( MCR( Save RLO in MCR Stack, Begin MCR 23-11
MCR) )MCR Restore RLO, End MCR 23-11
MCRA MCRA Activate MCR Area 23-11
MCRD MCRD Deactivate MCR Area 23-11
MOD MOD Division Remainder Double Integer (32-Bit) 15-5
NEGD NEGD Twos Complement Double Integer (32-Bit) 18-14
NEGI NEGI Twos Complement Integer (16-Bit) 18-14
NEGR NEGR Negate Real Number (32-Bit IEEE FP) 18-14
NOP 0 NOP 0 Null Operation 0 10-2
NOP 1 NOP 1 Null Operation 1 10-2
NOT NOT Negate RLO 11-26
O O Or 11-10
O( O( Or with Nesting Open 11-14
OD OD Or Double Word (32-Bit) 19-6
ON ON Or Not 11-9
ON( ON( Or Not with Nesting Open 11-14
OPN AUF Open a Data Block 21-2
OW OW Or Word (16-Bit) 19-3
POP POP Accumulator 1 <--- Accumulator 2, Accumulator 2 <--- Accumulator 3, 10-2
Accumulator 3 <--- Accumulator 4
PUSH PUSH Accumulator 3 ---> Accumulator 4, Accumulator 2 ---> Accumulator 3, 10-2
Accumulator 1 ---> Accumulator 2
R R Reset 11-22
R R Reset Counter (where the current counter can have a number in the 12-5
range of 0 to 255, for example: R C 15)
R R Reset Timer (where the current timer can have a number in the range of 13-4
0 to 255, for example: R T 32)
RLD RLD Rotate Left Double Word (32-Bit) 20-6
RLDA RLDA Rotate Accumulator 1 Left via CC 1 (32-Bit) 20-6
RND RND Round 18-9
RND+ RND+ Round to Upper Double Integer 18-10
RND- RND- Round to Lower Double Integer 18-11
RRD RRD Rotate Right Double Word (32-Bit) 20-8
RRDA RRDA Rotate Accumulator 1 Right via CC 1 (32-Bit) 20-6
S S Set 11-21
S S Set Counter Preset Value (where the current counter can have a number 13-3
in the range of 0 to 255, for example: S C 15)
SAVE SAVE Save RLO in BR Register 11-26

Statement List (STL) for S7-300/S7-400


A-10 C79000-G7076-C565-01
Alphabetical Listing of Instructions

Table A-2 Alphabetical Listing with the International and the SIMATIC Mnemonic Abbreviations, cont.

International SIMATIC Name Page


Abbreviation Abbreviation No.
SD SE On-Delay Timer 12-11
SE SV Extended Pulse Timer 12-9
SET SET Set RLO (= 1) 11-26
SF SA Off-Delay Timer 12-15
SIN SIN Sine of a Floating-Point Number (32-Bit IEEE FP) 16-7
SLD SLD Shift Left Double Word (32-Bit) 20-2
SLW SLW Shift Left Word (16-Bit) 20-2
SP SI Pulse Timer 12-7
SQR SQR Square of a Floating-Point Number (32-Bit IEEE PF) 16-9
SQRT SQRT Square Root of a Floating-Point Number (32-Bit IEEE PF) 16-9
SRD SRD Shift Right Double Word (32-Bit) 20-3
SRW SRW Shift Right Word (16-Bit) 20-2
SS SS Retentive On-Delay Timer 12-13
SSD SSD Shift Sign Double Integer (32-Bit) 20-4
SSI SSI Shift Sign Integer (16-Bit) 20-4
T T Transfer 14-3
T T Transfer Accumulator 1 to Status Word (T STW) 14-6
TAK TAK Toggle Accumulator 1 with Accumulator 2 10-2
TAN TAN Tangent of a Floating-Point Number (32-Bit IEEE FP) 16-7
TAR1 TAR1 Transfer Address Register 1 to Accumulator 1 14-11
(if no address is indicated)
TAR1 TAR1 Transfer Address Register 1 to ... (to address indicated) 14-11
TAR1 TAR1 Transfer Address Register 1 to Address Register 2 (T AR1 AR2) 14-11
TAR2 TAR2 Transfer Address Register 2 to Accumulator 1 14-11
(if no address is indicated)
TAR2 TAR2 Transfer Address Register 2 to ... (to address indicated) 14-11
TRUNC TRUNC Truncate 18-12
UC UC Unconditional Call 23-7
X X Exclusive Or 11-10
X( X( Exclusive Or with Nesting Open 11-14
XN XN Exclusive Or Not 11-9
XN( XN( Exclusive Or Not with Nesting Open 11-14
XOD XOD Exclusive Or Double Word (32-Bit) 19-6
XOW XOW Exclusive Or Word (16-Bit) 19-3

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 A-11
Alphabetical Listing of Instructions

A.2 Alphabetical Listing with International Names

Table A-3 provides an alphabetical listing of the full international names of


the statement list instructions. Next to each name is its international
mnemonic abbreviation and the page on which the instruction is explained.

Table A-3 Statement List Instructions Arranged Alphabetically by International Full Name

Name Mnemonic Page No.


Abbreviation
Absolute Value of a Real (32-Bit IEEE FP) ABS 16-6
Accumulator 1 ---> Accumulator 2 PUSH 10-2
Accumulator 1 <--- Accumulator 2 POP 10-2
Accumulator 1 <--- Accumulator 2, Accumulator 2 <--- Accumulator 3, POP 10-2
Accumulator 3 <--- Accumulator 4
Accumulator 3 ---> Accumulator 2, Accumulator 4 ---> Accumulator 3 LEAVE 10-3
Accumulator 3 ---> Accumulator 4, Accumulator 2 ---> Accumulator 3 ENT 10-3
Accumulator 3 ---> Accumulator 4, Accumulator 2 ---> Accumulator 3, PUSH 10-2
Accumulator 1 ---> Accumulator 2
Activate MCR Area MCRA 23-11
Add Accumulator 1 and Accumulator 2 as Double Integer (32-Bit) +D 15-2
Add Accumulator 1 and Accumulator 2 as Integer (16-Bit) +I 15-2
Add Accumulator 1 and Accumulator 2 as Real (32-Bit IEEE FP) +R 16-2
Add Accumulator 1 to Address Register 1 +AR1 10-7
Add Accumulator 1 to Address Register 2 +AR2 10-7
Add Integer Constant (8, 16, 32-Bit) + 15-6
And A 11-10
And Double Word (32-Bit) AD 19-6
And Not AN 11-9
And Not with Nesting Open AN( 11-14
And with Nesting Open A( 11-14
And Word (16-Bit) AW 19-3
Arc Cosine of a Floating-Point Number (32-Bit IEEE FP) ACOS 16-7
Arc Sine of a Floating-Point Number (32-Bit IEEE FP) ASIN 16-7
Arc Tangent of a Floating-Point Number (32-Bit IEEE FP) ATAN 16-7
Assign = 11-24
BCD to Double Integer (32-Bit) BTD 18-4
BCD to Integer (16-Bit) BTI 18-2
Block End Conditional BEC 23-15
Block End Unconditional BEU 23-15
Call CALL 23-3
Change Byte Sequence in Accumulator 1 (16-Bit) CAW 18-13
Change Byte Sequence in Accumulator 1 (32-Bit) CAD 18-13

Statement List (STL) for S7-300/S7-400


A-12 C79000-G7076-C565-01
Alphabetical Listing of Instructions

Table A-3 Statement List Instructions Arranged Alphabetically by International Full Name, continued

Name Mnemonic Page No.


Abbreviation
Clear RLO (= 0) CLR 11-26
Compare Double Integer (32-Bit) >, <, >=, <=, ==, <> ==D 17-3
Compare Integer (16-Bit) >, <, >=, <=, ==, <> ==I 17-3
Compare Real >, <, >=, <=, ==, <> ==R 17-3
Conditional Call CC 23-7
Cosine of a Floating-Point Number (32-Bit IEEE FP) COS 16-7
Counter Down CD 13-5
Counter Up CU 13-5
Deactivate MCR Area MCRD 23-11
Decrement Accumulator 1 DEC 10-6
Divide Accumulator 2 by Accumulator 1 as Double Integer (32-Bit) /D 15-2
Divide Accumulator 2 by Accumulator 1 as Integer (16-Bit) /I 15-2
Divide Accumulator 2 by Accumulator 1 as Real (32-Bit IEEE FP) /R 16-2
Division Remainder Double Integer (32-Bit) MOD 15-5
Double Integer (32-Bit) to BCD DTB 18-6
Double Integer (32-Bit) to Real (32-Bit IEEE FP) DTR 18-7
Edge Negative FN 11-17
Edge Positive FP 11-16
Enable Counter (Free, FR C 0 to C 255) FR 12-5
Enable Timer (Free, FR T 0 to T 255) FR 13-3
Exchange Address Register 1 with Address Register 2 CAR 14-11
Exchange Shared Data Block and Instance Data Block CDB 21-2
Exclusive Or X 11-10
Exclusive Or Double Word (32-Bit) XOD 19-6
Exclusive Or Not XN 11-9
Exclusive Or Not with Nesting Open XN( 11-14
Exclusive Or with Nesting Open X( 11-14
Exclusive Or Word (16-Bit) XOW 19-3
Exponential Value of a Floating-Point Number (32-Bit IEEE FP) to base E EXP 16-12
Extended Pulse Timer SE 12-9
Increment Accumulator 1 INC 10-6
Integer (16-Bit) to BCD ITB 18-5
Integer (16-Bit) to Double Integer ITD 18-6
Jump if 0 JZ 22-6
Jump if BR = 0 JNBI 22-4
Jump if BR = 1 JBI 22-4
Jump if Minus JM 22-6

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 A-13
Alphabetical Listing of Instructions

Table A-3 Statement List Instructions Arranged Alphabetically by International Full Name, continued

Name Mnemonic Page No.


Abbreviation
Jump if Minus or 0 JMZ 22-6
Jump if Not 0 JN 22-6
Jump if OS = 1 JOS 22-5
Jump if OV = 1 JO 22-5
Jump if Plus JP 22-6
Jump if Plus or 0 JPZ 22-6
Jump if RLO = 0 JCN 22-4
Jump if RLO = 0 with BR JNB 22-4
Jump if RLO = 1 JC 22-4
Jump if RLO = 1 with BR JCB 22-4
Jump if Unordered JUO 22-6
Jump to Labels JL 22-3
Jump Unconditional JU 22-3
Load L 14-3
Load Address Register 1 from ... (from address indicated) LAR1 14-11
Load Address Register 1 from Accumulator 1 (if no address is indicated) LAR1 14-11
Load Address Register 1 from Address Register 2 (LAR1 AR2) LAR1 14-11
Load Address Register 1 with Double Integer (32-Bit, LAR1 P#area byte.bit) LAR1 14-11
Load Address Register 2 from ... (from address indicated) LAR2 14-11
Load Address Register 2 from Accumulator 1 (if no address is indicated) LAR2 14-11
Load Address Register 2 with Double Integer (32-Bit, LAR2 P#area byte.bit) LAR2 14-11
Load Current Counter Value into Accumulator 1 as Integer (where the number of the L 13-6
current counter can be in the range of 0 to 255, for example: L C 15) 14-8
Load Current Counter Value into Accumulator 1 as BCD (where the number of the LC 14-9
current counter can be in the range of 0 to 255, for example: LC C 15)
Load Current Timer Value into Accumulator 1 as BCD (where the number of the LC 13-7
current timer can be in the range of 0 to 255, for example: LC T 32) 14-10
Load Current Timer Value into Accumulator 1 as Integer (where the number of the L 14-7
current timer can be in the range of 0 to 255, for example: L T 32)
Load Length of Instance Data Block into Accumulator 1 (L DILG) L 14-12
21-2
Load Length of Shared Data Block into Accumulator 1 (L DBLG) L 14-12
21-2
Load Number of Instance Data Block into Accumulator 1 (L DINO) L 14-12
21-2
Load Number of Shared Data Block into Accumulator 1 (L DBNO) L 14-12
21-2
Load Status Word into Accumulator 1 (L STW) L 14-6
Loop LOOP 22-8
Multiply Accumulator 1 by Accumulator 2 as Double Integer (32-Bit) *D 15-2

Statement List (STL) for S7-300/S7-400


A-14 C79000-G7076-C565-01
Alphabetical Listing of Instructions

Table A-3 Statement List Instructions Arranged Alphabetically by International Full Name, continued

Name Mnemonic Page No.


Abbreviation
Multiply Accumulator 1 by Accumulator 2 as Integer (16-Bit) *I 15-2
Multiply Accumulator 1 by Accumulator 2 as Real (32-Bit IEEE FP) *R 16-2
Natural Logarithm of a Floating-Point Number (32-Bit IEEE FP) LN 16-11
Negate Real Number (32-Bit IEEE FP) NEGR 18-14
Negate RLO NOT 11-26
Nesting Closed ) 11-14
Null Operation 0 NOP 0 10-2
Null Operation 1 NOP 1 10-2
Off-Delay Timer SF 12-15
On-Delay Timer SD 12-11
Ones Complement Double Integer (32-Bit) INVD 18-14
Ones Complement Integer (16-Bit) INVI 18-14
Open a Data Block OPN 21-2
Or O 11-10
Or Double Word (32-Bit) OD 19-6
Or Not ON 11-9
Or Not with Nesting Open ON( 11-14
Or with Nesting Open O( 11-14
OR Word (16-Bit) OW 19-3
Program Display Instruction BLD 10-2
Pulse Timer SP 12-7
Reset R 11-22
Reset Counter (where the current counter can have a number in the range of 0 to 255, R 12-5
for example: R C 15)
Reset Timer (where the current timer can have a number in the range of 0 to 255, for R 13-4
example: R T 32)
Restore RLO, End MCR )MCR 23-11
Retentive On-Delay Timer SS 12-13
Rotate Accumulator 1 Left via CC 1 (32-Bit) RLDA 20-8
Rotate Accumulator 1 Right via CC 1 (32-Bit) RRDA 20-6
Rotate Left Double Word (32-Bit) RLD 20-6
Rotate Right Double Word (32-Bit) RRD 20-8
Round RND 18-9
Round to Lower Double Integer RND- 18-11
Round to Upper Double Integer RND+ 18-10
Save RLO in BR Register SAVE 11-26
Save RLO in MCR Stack, Begin MCR MCR( 23-11
Set S 11-21

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 A-15
Alphabetical Listing of Instructions

Table A-3 Statement List Instructions Arranged Alphabetically by International Full Name, continued

Name Mnemonic Page No.


Abbreviation
Set Counter Preset Value (where the current counter can have a number in the range of S 13-3
0 to 255, for example: S C 15)
Set RLO (= 1) SET 11-26
Shift Left Double Word (32-Bit) SLD 20-2
Shift Left Word (16-Bit) SLW 20-2
Shift Right Double Word (32-Bit) SRD 20-3
Shift Right Word (16-Bit) SRW 20-2
Shift Sign Double Integer (32-Bit) SSD 20-4
Shift Sign Integer (16-Bit) SSI 20-4
Sine of a Floating-Point Number (32-Bit IEEE FP) SIN 16-7
Square of a Floating-Point Number (32-Bit IEEE PF) SQR 16-9
Square Root of a Floating-Point Number (32-Bit IEEE PF) SQRT 16-9
Subtract Accumulator 1 from Accumulator 2 as Double Integer (32-Bit) -D 15-2
Subtract Accumulator 1 from Accumulator 2 as Integer (16-Bit) -I 15-2
Subtract Accumulator 1 from Accumulator 2 as Real (32-Bit IEEE FP) -R 16-2
Tangent of a Floating-Point Number (32-Bit IEEE FP) TAN 16-7
Toggle Accumulator 1 with Accumulator 2 TAK 10-2
Transfer T 14-3
Transfer Accumulator 1 to Status Word (T STW) T 14-6
Transfer Address Register 1 to ... (to address indicated) TAR1 14-11
Transfer Address Register 1 to Accumulator 1 (if no address is indicated) TAR1 14-11
Transfer Address Register 1 to Address Register 2 (T AR1 AR2) TAR1 14-11
Transfer Address Register 2 to ... (to address indicated) TAR2 14-11
Transfer Address Register 2 to Accumulator 1 (if no address is indicated) TAR2 14-11
Truncate TRUNC 18-12
Twos Complement Double Integer (32-Bit) NEGD 18-14
Twos Complement Integer (16-Bit) NEGI 18-14
Unconditional Call UC 23-7

Statement List (STL) for S7-300/S7-400


A-16 C79000-G7076-C565-01
Programming Examples B
Chapter Overview Section Description Page
B.1 Overview B-2
B.2 Bit Logic Instructions B-3
B.3 Timer Instructions B-7
B.4 Counter and Comparison Instructions B-10
B.5 Integer Math Instructions B-12
B.6 Word Logic Instructions B-14

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 B-1
Programming Examples

B.1 Overview

Practical Each statement list instruction described in this manual triggers a specific
Applications operation. When you combine these instructions into a program, you can
accomplish a wide variety of automation tasks. This chapter provides the
following examples of practical applications of the statement list instructions:
 Controlling a conveyor belt using bit logic instructions
 Detecting direction of movement on a conveyor belt using bit logic
instructions
 Generating a clock pulse using timer instructions
 Keeping track of storage space using counter and comparison instructions
 Solving a problem using integer math instructions
 Setting the length of time for heating an oven
When you create an ASCII file that will be imported into the STL editor, you
must follow the conventions outlined in Appendix C.

Instructions Used The examples in this chapter use the following instructions:
 And (A) and And Not (AN)
 Assign (=)
 Block End (BE) and Block End Conditional (BEC)
 Compare Integer (16-bit, <=, >=)
 Counter Down (CD) and Counter Up (CU)
 Edge Positive (FP)
 Extended Pulse Timer (SE)
 Increment Accumulator 1 (INC)
 Integer Four-function Math (16 BITS)
– Add Accumulators 1 and 2 As Integer (+I)
– Divide Accumulator 2 by Accumulator 1 As Integer (/I)
– Multiply Accumulators 1 and 2 As Integers (I)
 Load (L) and Transfer (T)
 Negate RLO (NOT)
 Or (O) and Or Not (ON)
 Set (S) and Reset (R)
 Word Logic (And Word, Or Word)

Statement List (STL) for S7-300/S7-400


B-2 C79000-G7076-C565-01
Programming Examples

B.2 Bit Logic Instructions

Controlling a Figure B-1 shows a conveyor belt that can be activated electrically. There are
Conveyor Belt two push button switches at the beginning of the belt: S1 for START and S2
for STOP. There are also two push button switches at the end of the belt: S3
for START and S4 for STOP. It it possible to start or stop the belt from either
end. Also, sensor S5 stops the belt when an item on the belt reaches the end.

Symbolic You can write a program to control the conveyor belt shown in Figure B-1
Programming using symbols that represent the various components of the conveyor system.
If you choose this method, you need to make a symbol table to correlate the
symbols you choose with absolute values (see Table B-1). Table B-3
compares a statement list program that uses symbols as addresses to a
program that uses absolute values as addresses. You define the symbols in the
symbol table (see STEP 7 Online Help).

Table B-1 Elements of Symbolic Programming for Conveyor Belt System

Absolute
System Component Symbol Symbol Table
Address
Push Button Start Switch I 1.1 S1 I 1.1 S1
Push Button Stop Switch I 1.2 S2 I 1.2 S2
Push Button Start Switch I 1.3 S3 I 1.3 S3
Push Button Stop Switch I 1.4 S4 I 1.4 S4
Sensor I 1.5 S5 I 1.5 S5
Motor Q 4.0 MOTOR_ON Q 4.0 MOTOR_ON

Sensor S5

S1  Start S3  Start
S2  Stop S4  Stop
MOTOR_ON

Figure B-1 Conveyor Belt System

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 B-3
Programming Examples

Absolute You can write a program to control the conveyor belt shown in Figure B-1
Programming using absolute values that represent the different components of the conveyor
system (see Table B-2). Table B-3 compares a statement list program that
uses absolute values as addresses to a program that uses symbols as
addresses. An explanation of the program follows the tables.

Table B-2 Elements of Absolute Programming for Conveyor Belt System

System Component Absolute Address


Push Button Start Switch I 1.1
Push Button Stop Switch I 1.2
Push Button Start Switch I 1.3
Push Button Stop Switch I 1.4
Sensor I 1.5
Motor Q 4.0

Table B-3 Symbolic and Absolute Programs to Control a Conveyor Belt

Symbolic Program Absolute Program


O S1 O I 1.1
O S3 O I 1.3
S MOTOR_ON S Q 4.0
O S2 O I 1.2
O S4 O I 1.4
ON S5 ON I 1.5
R MOTOR_ON R Q 4.0

STL Explanation
O I 1.1 Pressing either start switch turns the motor on.
O I 1.3
S Q 4.0
O I 1.2 Pressing either stop switch or opening the normally closed
O I 1.4 contact at the end of the belt turns the motor off.
ON I 1.5
R Q 4.0

Statement List (STL) for S7-300/S7-400


B-4 C79000-G7076-C565-01
Programming Examples

Detecting the Figure B-2 shows a conveyor belt that is equipped with two photoelectric
Direction of a barriers (PEB1 and PEB2) that are designed to detect the direction in which a
Conveyor Belt package is moving on the belt. Each photoelectric light barrier functions like
a normally open contact (see Section 5.1).

Symbolic You can write a program to activate a direction display for the conveyor belt
Programming system shown in Figure B-2 using symbols that represent the various
components of the conveyor system, including the photoelectric barriers that
detect direction. If you choose this method, you need to make a symbol table
to correlate the symbols you choose with absolute values (see Table B-4).
Table B-6 compares a statement list program that uses symbols as addresses
to a program that uses absolute values as addresses. You define the symbols
in the symbol table (see the STEP 7 Online Help).

Table B-4 Elements of Symbolic Programming for Detecting Direction

Absolute
System Component Symbol Symbol Table
Address
Photo electric barrier 1 I 0.0 PEB1 I 0.0 PEB1
Photo electric barrier 2 I 0.1 PEB2 I 0.1 PEB2
Display for movement to right Q 4.0 RIGHT Q 4.0 RIGHT
Display for movement to left Q 4.1 LEFT Q 4.1 LEFT
Pulse memory bit 1 M 0.0 PMB1 M 0.0 PMB1
Pulse memory bit 2 M 0.1 PMB2 M 0.1 PMB2

Q 4.0 PEB2 PEB1 Q 4.1

Figure B-2 Conveyor Belt System with Photoelectric Light Barriers for Detecting Direction

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 B-5
Programming Examples

Absolute You can write a program to control the direction display for the conveyor belt
Programming shown in Figure B-2 using absolute values that represent the photoelectric
barriers that detect direction (see Table B-5). Table B-6 compares a statement
list program that uses absolute values as addresses to a program that uses
symbols as addresses. An explanation of the program follows the figure.

Table B-5 Elements of Absolute Programming for Detecting Direction

System Component Absolute Address


Photo electric barrier 1 I 0.0
Photo electric barrier 2 I 0.1
Display for movement to right Q 4.0
Display for movement to left Q 4.1
Pulse memory bit 1 M 0.0
Pulse memory bit 2 M 0.1

Table B-6 Symbolic and Absolute Programs to Detect Direction

Symbolic Program Absolute Program


A I PEB1 A I 0.0
FP PMB1 FP M 0.0
AN PEB2 AN I 0.1
S LEFT S Q 4.1
A PEB2 A I 0.1
FP PMB2 FP M 0.1
AN PEB1 AN I 0.0
S RIGHT S Q 4.0
AN PEB1 AN I 0.0
AN PEB2 AN I 0.1
R RIGHT R Q 4.0
R LEFT R Q 4.1

STL Explanation
A I 0.0 If there is a transition in signal state from 0 to 1
FP M 0.0 (positive edge) at input I 0.0 and, at the same time, the
AN I 0.1 signal state at input I 0.1 is 0, then the package on
S Q 4.1 the belt is moving to the left.

A I 0.1 If there is a transition in signal state from 0 to 1


FP M 0.1 (positive edge) at input I 0.1 and, at the same time, the
AN I 0.0 signal state at input I 0.0 is 0, then the package on
S Q 4.0 the belt is moving to the right. If one of the
photoelectric light barriers is broken, this means
AN I 0.0 that there is a package between the barriers.
AN I 0.1
R Q 4.0 If neither photoelectric barrier is broken, then there
R Q 4.1 is no package between the barriers. The direction pointer
shuts off.

Statement List (STL) for S7-300/S7-400


B-6 C79000-G7076-C565-01
Programming Examples

B.3 Timer Instructions

Clock Pulse You can use a clock pulse generator or flasher relay when you need to
Generator produce a signal that repeats periodically. A clock pulse generator is common
in a signalling system that controls the flashing of indicator lamps.
When you use the S7-300, you can implement the clock pulse generator
function by using time-driven processing in special organization blocks. The
example shown in the following statement list program, however, illustrates
the use of timer functions to generate a clock pulse.
The following example shows how to implement a freewheeling clock pulse
generator by using a timer (pulse duty factor 1:1). The frequency is divided
into the values listed in Table B-7.

STL Explanation
AN T 1 If timer T 1 has expired, load the time value 250 ms into
L S5T#250ms T 1 and start T 1 as an extended-pulse timer.
SE T 1 Negate (invert) the result of logic operation.
NOT If the timer is running, end the current block. If the
BEC timer has expired, load the contents of memory byte MB100,
L MB100 increment the contents by 1, and transfer the result to
INC 1 memory byte MB100.
T MB100

A signal check of timer T 1 produces the result of logic operation.

1
0
250 ms

Figure B-3 RLO for AN T 1 Statement in the Clock Pulse Timer Example

As soon as the time runs out, the timer is restarted. Therefore, the signal
check made by the statement AN T 1 produces a signal state of 1 only
briefly.

1
0
250 ms

Figure B-4 Negated RLO Bit of Timer T 1 in the Clock Pulse Timer Example

Every 250 ms the RLO bit is 0. Figure B-4 shows what the negated (inverted)
RLO bit looks like. Then the BEC statement does not end the processing of
the block. Instead, the contents of memory byte MB100 is incremented by 1.
The contents of memory byte MB100 changes every 250 ms as follows:
0 !1!2!3! ... !254!255!0!1 ...

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 B-7
Programming Examples

Achieving a Table B-7 lists the frequencies that you can achieve from the individual bits
Specific of memory byte MB100. The statement list program that follows the table
Frequency shows how you can use the frequencies that are generated.

Table B-7 Frequencies for Clock Pulse Timer Example

Bits of Frequency in Hertz Duration


MB100
M 100.0 2.0 0.5 s (250 ms on/250 ms off)
M 100.1 1.0 1 s (0.5 s on/0.5 s off)
M 100.2 0.5 2 s (1 s on/1 s off
M 100.3 0.25 4 s (2 s on/2 s off)
M 100.4 0.125 8 s (4 s on/4 s off)
M 100.5 0.0625 16 s (8 s on/8 s off)
M 100.6 0.03125 32 s (16 s on/16 s off)
M 100.7 0.015625 64 s (32 s on/32 s off)

STL Explanation
A M 10.0 M 10.0 = 1 when a fault occurs.
A M 100.1
= Q 4.0 The fault lamp blinks at a frequency of 1 Hz when a
fault occurs.

Statement List (STL) for S7-300/S7-400


B-8 C79000-G7076-C565-01
Programming Examples

Table B-8 lists the signal states of the bits of memory byte MB100.
Figure B-5 shows the RLO of memory bit M100.1.

Table B-8 Signal States of the Bits of Memory Byte MB100

Signal State of Bits of Memory Byte MB100 Time


Scan
Value
Cycle
7 6 5 4 3 2 1 0 in ms
0 0 0 0 0 0 0 0 0 250
1 0 0 0 0 0 0 0 1 250
2 0 0 0 0 0 0 1 0 250
3 0 0 0 0 0 0 1 1 250
4 0 0 0 0 0 1 0 0 250
5 0 0 0 0 0 1 0 1 250
6 0 0 0 0 0 1 1 0 250
7 0 0 0 0 0 1 1 1 250
8 0 0 0 0 1 0 0 0 250
9 0 0 0 0 1 0 0 1 250
10 0 0 0 0 1 0 1 0 250
11 0 0 0 0 1 0 1 1 250
12 0 0 0 0 1 1 0 0 250

T
1
M 100.1 0
Time
0 250 ms 0.5 s 0.75 s 1 s 1.25 s 1.5 s

Frequency  1  1  1Hz
T 1 s

Figure B-5 Signal State of Bit 1 MB100 (M 100.1)

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 B-9
Programming Examples

B.4 Counter and Comparison Instructions

Storage Area with Figure B-6 shows a system with two conveyor belts and a temporary storage
Counter and area in between them. Conveyor belt 1 delivers packages to the storage area.
Comparator A photoelectric barrier at the end of conveyor belt 1 near the storage area
determines how many packages are delivered to the storage area. Conveyor
belt 2 transports packages from the temporary storage area to a loading dock
where trucks take the packages away for delivery to customers. A
photoelectric barrier at the end of conveyor belt 2 near the storage area
determines how many packages leave the storage area to go to the loading
dock.
A display panel with five lamps indicates the fill level of the temporary
storage area. The sample program that follows Figure B-6 is the program that
activates the indicator lamps on the display panel.

Display Panel

Storage area Storage area Storage area Storage area Storage area
empty not empty 50% full 90% full filled to capacity
(Q 4.0) (Q 4.1) (Q 4.2) (Q 4.3) (Q 4.4)

I 0.0 I 0.1
Temporary
Packages in storage for 100 Packages out
packages

Conveyor belt 1 Conveyor belt 2


Photoelectric barrier 1 Photoelectric barrier 2

Figure B-6 Storage Area with Counter and Comparator

Statement List (STL) for S7-300/S7-400


B-10 C79000-G7076-C565-01
Programming Examples

STL Explanation
A I 0.0 Each pulse generated by photoelectric barrier 1 increases
CU C 1 the count value of counter C 1 by one, thereby counting
the number of packages going into the storage area.
A I 0.1 Each pulse generated by photoelectric barrier 2 decreases
CD C 1 the count value of counter C 1 by one, thereby counting
the packages that leave the storage area.
AN C 1 If the count value is 0, the indicator lamp for “Storage
= Q 4.0 area empty” comes on.
A C 1 If the count value is not 0, the indicator lamp for
= Q 4.1 “Storage area not empty” comes on.
L +50 If 50 is less than or equal to the count value, the
L C 1 indicator lamp for “Storage area 50% full” comes on.
<=I
= Q 4.2 If the count value is greater than or equal to 90, the
L +90 indicator lamp for “Storage area 90% full” comes on.
>=I
= Q 4.3 If the count value is greater than or equal to 100, the
L C 1 indicator lamp for “Storage area filled to capacity”
L 100 comes on. (You could also use output Q 4.4 to lock
>=I conveyor belt 1.)
= Q 4.4

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 B-11
Programming Examples

B.5 Integer Math Instructions

Solving a Math The following sample program (applicable for the S7-300 only) shows you
Problem how to use three integer math instructions, along with Load and Transfer, to
produce the same result as the following equation:

(IW0 ) DBW3) 15
MD4 +
MW2

STL Explanation
L IW0 Load the value from input word IW0 into accumulator 1.
L DB5.DBW3 Load the value from shared data word DBW3 of DB5 into
accumulator 1. The old contents of accumulator 1 are
shifted to accumulator 2.
+I Add the contents of the low words of accumulators 1 and
2. The result is stored in the low word of accumulator
1. The contents of accumulator 2 and the high word of
accumulator 1 remain unchanged.
L +15 Load the constant value +15 into accumulator 1. The old
contents of accumulator 1 are shifted to accumulator 2.
I Multiply the contents of the low word of accumulator 2
by the contents of the low word of accumulator 1. The
result is stored in accumulator 1. The contents of
accumulator 2 remain unchanged.
L MW2 Load the value from memory word MW2 into accumulator 1.
The old contents of accumulator 1 are shifted to
accumulator 2.
/I Divide the contents of the low word of accumulator 2 by
the contents of the low word of accumulator 1. The
result is stored in accumulator 1. The contents of
accumulator 2 remain unchanged.
T MD4 Transfer the final result to memory double word MD4. The
contents of both accumulators remain unchanged.

Statement List (STL) for S7-300/S7-400


B-12 C79000-G7076-C565-01
Programming Examples

Figure B-7 shows the relationship of the program to the equation.

Accumulator 1 Accumulator 2
L IW0 (IW0) ³ (Old contents)

L DBW3 (DBW3) ³ (IW0)


+
±
+I (IW0) + (DBW3) (IW0)

L +15 15 ³ (IW0) + (DBW3)



±
I [(IW0) + (DBW3)] 15 (IW0) + (DBW3)

L MW2 MW2 ³ [(IW0) + (DBW3)] 15


/
±
/I (IW0 ) DBW3) 15 (IW0 ) DBW3) 15
MW2

T MD4 (IW0 ) DBW3) 15 (IW0 ) DBW3) 15


MW2

(IW0 ) DBW5) 15
MD4 +
MW2

Figure B-7 Relationship of Integer Math Statements to an Equation (S7-300)

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 B-13
Programming Examples

B.6 Word Logic Instructions

Heating an Oven The operator of the oven shown in Figure B-8 starts the oven heating by
pushing the start push button. The operator can set the length of time for
heating by using the thumbwheel switches shown in the figure. The value
that the operator sets indicates seconds in binary coded decimal (BCD)
format. Table B-9 lists the components of the heating system and their
corresponding absolute addresses used in the sample program that follows
Figure B-8.

Table B-9 Heating System Components and Corresponding Absolute Addresses

System Component Absolute Address in STL Program


Start push button I 0.7
Thumbwheel for ones I 1.0 to I 1.3
Thumbwheel for tens I 1.4 to I 1.7
Thumbwheel for hundreds I 0.0 to I 0.3
Heating starts Q 4.0

Thumbwheels for setting BCD digits

ÎÎÎÎÎ
Oven ÎÎÎÎÎ
4 4 4

Heat 7.... ...0 7... ...0 Bits


Q 4.0
XXXX 0001 1001 0001 IW0

IB0 IB1 Bytes


Start push button I 0.7

Figure B-8 Using the Inputs and Outputs for the Time-Limited Heating Process

STL Explanation
A T 1 If the timer is running, then turn on the heat.
= Q 4.0
BEC If the timer is running, then end processing here. This prevents
timer T 1 from being restarted if the push button is pressed.
L IW0 Mask input bits I 0.4 through I 0.7 (that is, reset them to 0).
AW W#16#0FFF The time value in seconds is in the low word of accumulator 1 in
binary coded decimal format.
OW W#16#2000 Assign the time base as seconds in bits 12 and 13 of the low word
of accumulator 1.
A I 0.7 Start timer T 1 as an extended pulse timer if the push button is
SE T 1 pressed.
BE End the program network.

Statement List (STL) for S7-300/S7-400


B-14 C79000-G7076-C565-01
Source Files - Examples and
Reserved Keywords C
Definition A keyword is a reserved identifier which cannot be used as a general
identifier.
To use a keyword as a global symbol it must be marked as scan cycle
checkpoint (SCC).
To use a keyword as a local symbol it must be marked with #.

Overview Table C-1 lists all keywords reserved for STEP 7.

Table C-1 Keywords

Keywords
A B
AB BEGIN
AD BIE
ANY BLOCK_DB
AO BLOCK_FB
AR1 BLOCK_FC
AR2 BLOCK_SDB
ARRAY BOOL
AUTHOR BYTE
AW

C DATA_BLOCK
CALL DATE
CHAR DATE_AND_TIME
COUNTER DB
DBB
DBD
DBLG
DBNO
DBW
DBX

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 C-1
Source Files – Examples and Reserved Keywords

Table C-1 Keywords, continued

Keywords
DI
DIB
DID
DILG
DINO
DINT
DIW
DIX
DT
DWORD

E FALSE
EB FAMILY
ED FB
END_Data_Block FC
END_Function FUNCTION
END_Function_Block FUNCTION_BLOCK
END_Organization_Block
END_Struct I
END_System_Function IB
END_System_Function_Block ID
END_Type INT
END_VAR IW
EW

KA L
KNOW_HOW_PROTECT LB
KP LD
LW

M NAME
MB NETWORK
MD NI
MW NO

OB PA
OF PAB
ORGANIZATION_BLOCK PAD

Statement List (STL) for S7-300/S7-400


C-2 C79000-G7076-C565-01
Source Files – Examples and Reserved Keywords

Table C-1 Keywords, continued

Keywords
OS PAW
OV PE
PEB
PED
PEW
PI
PIB
PID
PIW
PQ
PQB
PQD
PQW
POINTER

Q READ_ONLY
QB REAL
QD RET_VAL
QW

S5T T
S5TIME TIME
SDB TIME_OF_DAY
SFB TIMER
SFC TITLE
STANDARD TOD
STRING TRUE
STRUCT TYPE
STW
SYSTEM_FUNCTION
SYSTEM_FUNCTION_BLOCK

UDT VAR
UNLINKED VAR_IN_OUT
UO VAR_INPUT
VAR_OUTPUT
VAR_TEMP
VERSION

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 C-3
Source Files – Examples and Reserved Keywords

Table C-1 Keywords, continued

Keywords
VOID

WORD Z

Statement List (STL) for S7-300/S7-400


C-4 C79000-G7076-C565-01
References D
/30/ Getting Started: Working with STEP 7 V5.0
/70/ Manual: S7-300 Programmable Controller,
Hardware and Installation
/71/ Reference Manual: S7-300, M7-300 Programmable Controllers
Module Specifications
/72/ Instruction List: S7-300 Programmable Controller
/100/ Manual: S7-400/M7-400 Programmable Controllers,
Hardware and Installation
/101/ Reference Manual: S7-400/M7-400 Programmable Controllers
Module Specifications
/102/ Instruction List: S7-400 Programmable Controller
/231/ Manual:
Configuring Hardware and Communication Connections, STEP 7 V5.0
/233/ Reference Manual: Ladder Logic (LAD) for S7-300 and S7-400
Programming
/234/ Manual: Programming with STEP 7 V5.0
/235/ Reference Manual: System Software for S7-300 and S7-400
System and Standard Functions
/236/ Reference Manual: Function Block Diagram (FBD) for S7-300 and 400,
Programming
/250/ Manual: Structured Control Language (SCL) for S7-300/S7-400,
Programming
/251/ Manual: S7-GRAPH for S7-300 and S7-400,
Programming Sequential Control Systems
/252/ Manual: S7-HiGraph for S7-300 and S7-400,
Programming State Graphs
/253/ Manual: C Programming for S7-300 and S7-400,
Writing C Programs
/254/ Manual: Continuous Function Charts (CFC) for S7 and M7,
Programming Continuous Function Charts
/270/ Manual: S7-PDIAG for S7-300 and S7-400
“Configuring Process Diagnostics for LAD, STL, and FBD”
/271/ Manual: NETPRO,
“Configuring Networks”

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 D-1
References

/800/ DOCPRO
Creating Wiring Diagrams (CD only)
/801/ TeleService for S7, C7 and M7
Remote Maintenance for Automation Systems (CD only)
/802/ PLC Simulation for S7-300 and S7-400 (CD only)
/803/ Reference Manual: Standard Software for S7-300 and S7-400,
STEP 7 Standard Functions, Part 2

Statement List (STL) for S7-300/S7-400


D-2 C79000-G7076-C565-01
Glossary

Absolute In absolute addressing, the memory location of the address to be processed is


Addressing given.

Accumulator Accumulators are registers in the CPU which act as intermediate buffers for
load, transfer, comparison, math, and conversion operations.

Actual Parameter Actual parameters replace the formal parameters when function blocks (FBs)
and functions (FCs) are called.
Example: The formal parameter “Start” is replaced by the actual parameter
“I3.6”.

Address An address is part of a STEP 7 statement and specifies what the processor
should execute the instruction on. Addresses can be absolute or symbolic.

Address Identifier An address identifier is the part of the address which contains various data.
The data can include elements such as a value itself (data object) or the size
of a value with which the instruction can, for example, perform a logic
operation. In the instruction statement “L IB10” IB is the address identifier
(“I” indicates the memory input area and “B” indicates a byte in that area).

Address Register The address register is part of the registers in the communication part of the
CPU. They act as pointers for register indirect addressing (possible in STL).

Array An array is a complex data type which consists of data elements of the same
type. These data elements can be elementary or complex.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 Glossary-1
Glossary

Bit Result (BR) The bit result is the link between bit and word-oriented processing. This is an
efficient method to allow the binary interpretation of the result of a word
instruction and to include it in a series of logic operations.

Call Hierarchy All blocks must be called first before they can be processed. The sequence
and nesting of these calls within an organized block is called the call
hierarchy.

Condition Codes The CC 1 and CC 0 bits (condition codes) provide information on the
CC 1 and CC 0 following results or bits:
 Result of a math operation
 Result of a comparison
 Result of a digital operation
 Bits that have been shifted out by a shift or rotate command

CPU A CPU (central processing unit) is the central module in a programmable


controller in which the user program is stored and processed. It consists of an
operating system, processing unit, and communication interfaces.

Current Path Characteristic of the Ladder Logic programming language. Current paths
contain contacts and coils. Complex elements (for example, math functions)
can also be inserted into current paths in the form of “boxes.” Current paths
are connected to power rails.

Data Block (DB) Data blocks (DBs) are areas in a user program which store user data. There
are shared data blocks which can be accessed by all logic blocks and there
are instance data blocks which are associated with a certain function block
(FB) call. In contrast to all other blocks, data blocks do not contain
instructions.

Statement List (STL) for S7-300/S7-400


Glossary-2 C79000-G7076-C565-01
Glossary

Data, Static Static data are local data of a function block which are stored in the instance
data block and, therefore, remain intact until the function block is processed
again.

Data Type A data type defines how the value of a variable or a constant should be used
in the user program.
In SIMATIC STEP 7 two data types are available to the user (IEC 1131–3):
 Elementary data types
 Complex data types

Data Type, Complex data types are created by the user with the data type declaration.
Complex They do not have their own name and cannot, therefore, be used again. They
can either be arrays or structures. The data types STRING and DATE AND
TIME are classed as complex data types.

Data Type, Elementary data types are preset data types according to IEC 1131–3.
Elementary
Examples:
 Data type “BOOL” defines a binary variable (“Bit”)
 Data type “INT” defines a 16-bit fixed-point variable.

Declaration The declaration section is used for the declaration of the local data of a logic
block when programming in the Text Editor.

Direct Addressing In direct addressing, the address contains the memory location of a value
which is to be used by the instruction.
Example:
The location Q4.0 defines bit 0 in byte 4 of the process-image output table.

First Check Bit First check of the result of logic operation.

Folder Directory of the user interface of the SIMATIC Manager which can be
opened and can hold other directories or objects.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 Glossary-3
Glossary

Formal Parameter A formal parameter is a placeholder for the actual parameter in logic blocks.
In function blocks (FBs) and functions (FCs) the formal parameters are
declared by the user, in system function blocks (SFBs) and system functions
(SFCs) they are already available. When a block is called, formal parameters
are assigned actual parameters, so the called block works with the current
values.
The formal parameters are classed as local data. They can be input, output, or
in/out parameters.

Function (FC) According to the International Electrotechnical Commission’s IEC 1131–3


standard, functions are logic blocks without a ‘memory’ (meaning they do
not have static data). A function allows you to transfer parameters in the user
program, which means they are suitable for programming frequently
recurring, complex functions, such as calculations. Important: As a function
has no memory, you must continue processing the calculated values directly
after the function has been called.

Function Block According to the International Electrotechnical Commission’s IEC 1131–3


(FB) standard, function blocks are logic blocks with a ‘memory’ (meaning they
have static data). A function block allows you to transfer parameters in the
user program, which means they are suitable for programming frequently
recurring, complex functions, such as closed-loop control and operating
mode selection. As a function block has a memory (instance data block), you
can access its parameters (for example, outputs) at any time and at any point
in the user program.

Function Block Function Block Diagram (FBD) is one of the programming languages in
Diagram (FBD) STEP 5 and STEP 7. FBD represents logic in the boxes familiar from
Boolean algebra. In addition, complex functions (for example, math
functions) can be represented in direct connection with the logic box.
Programs created with FBD can also be translated into other programming
languages (for example, Ladder Logic).

Immediate In immediate addressing, the address contains the value with which the
Addressing instruction works.
Example: L.27 means load constant 27 into accumulator.

Input, Incremental When a block is input incrementally, each line or element is checked
immediately for errors (for example, syntax errors). If an error is detected, it
is marked and must be corrected before programming is completed.
Incremental input is possible in STL (Statement List), LAD (Ladder Logic),
and FBD (Function Block Diagram).

Statement List (STL) for S7-300/S7-400


Glossary-4 C79000-G7076-C565-01
Glossary

Instance An “instance” is the call of a function block. An instance data block is


assigned to each call.

Instance Data An instance data block stores the formal parameters and the static data of
Block (DB) function blocks. An instance data block can be assigned to one function
block call or a call hierarchy of function blocks.

Instruction An instruction is part of a STEP 7 statement; it specifies what the processor


should do.

Keyword Keywords are used when programming with source files to identify the start
and end of a block and to select sections in the declaration section of blocks,
the start of block comments and the start of titles.

Ladder Logic Ladder Logic is a graphic programming language in STEP 5 and STEP 7. Its
(LAD) representation is standardized in compliance with DIN 19239 (international
standard IEC 1131-1). Ladder Logic representation corresponds to the
representation of relay ladder logic diagrams. In contrast to Statement List
(STL), LAD has a restricted set of instructions.

Logic Block Logic blocks are blocks within SIMATIC S7 that contain a part of the
STEP 7 user program. In contrast, data blocks (DBs) only contain data. There
are the following types of logic blocks: organization blocks (OBs), function
blocks (FBs), functions (FCs), system function blocks (SFBs), and system
functions (SFCs). Blocks are stored in the “Blocks” folder under the “S7
Program” folder.

Logic String A logic string is that portion of a user program which begins with an FC bit
that has a signal state of 0 and which ends when an instruction or event resets
the FC bit to 0. When the CPU executes the first instruction in a logic string,
the FC bit is set to 1. Certain instructions such as output instructions (for
example, Set, Reset, or Assign) reset the FC bit to 0. See First Check Bit
above.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 Glossary-5
Glossary

Master Control The Master Control Relay (MCR) is an American relay ladder logic master
Relay switch for energizing and de-energizing power flow (current path). A
de-energized current path corresponds to an instruction sequence that writes a
zero value instead of the calculated value, or, to an instruction sequence that
leaves the existing memory value unchanged.

Memory Area In SIMATIC S7 a CPU has three memory areas:


 Load memory
 Work memory
 System memory

Memory Indirect A type of addressing in which the address of an instruction indicates the
Addressing location of the value with which the instruction is to work.

Mnemonic Mnemonic representation is an abbreviated form for displaying the names of


Representation addresses and programming instructions in the program (for example, “I”
stands for “input”). STEP 7 supports the international representation (based
on the English language), and the SIMATIC representation (based on the
German abbreviations of the instruction set and the SIMATIC addressing
conventions).

Nesting Stack The nesting stack is a storage byte used by the nesting instructions A(, O(,
X(, AN(, ON(, XN(. A total of eight bit logic instructions can be stacked.

Network Networks subdivide LAD and FBD blocks into complete current paths and
Statement List (STL) blocks into clear units.

OR Bit The OR bit is needed if you perform a logical AND before OR operation.
The OR bit shows these instructions that a previously executed AND function
has supplied the value 1, thus forestalling the result of the logical OR
operation. Any other bit-processing command resets the OR bit (see
Section 5.4).

Statement List (STL) for S7-300/S7-400


Glossary-6 C79000-G7076-C565-01
Glossary

Overflow Bit The status bit OV stands for overflow. An overflow can occur, for example,
after a math operation.

Pointer You can use a pointer to identify the address of a variable. A pointer contains
an identifier instead of a value. If you allocate an actual parameter type, you
provide the memory address. With STEP 7 you can either enter the pointer in
pointer format or simply as an identifier (for example, M 50.0). In the
following example, the pointer format is shown with which data from M 50.0
is accessed:
P#M50.0

Project A project is a folder for all objects in an automation task, irrespective of the
number of stations, modules, and how they are connected in networks.

Reference Data Reference data are used to check your S7 program and include the
cross-reference list, the assignment lists, the program structure, the list of
unused addresses, and the list of addresses without symbols.

Register Indirect A type of addressing in which the address of an instruction indicates


Addressing indirectly via an address register and an offset the memory location of the
value with which the instruction is to work.

Result of Logic The result of logic operation (RLO) is the result of the logic string which is
Operation (RLO) used to process other binary signals. The execution of certain instructions
depends entirely on their preceding RLO.

S7 Program A folder for blocks, source files, and charts for S7 programmable controllers.
The S7 program also includes the symbol table.

Shared Data Block A shared data block is a DB whose address is loaded in the DB address
(DB) register when it is opened. It provides storage and data for all logic blocks
(FCs, FBs, or OBs) that are being executed.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 Glossary-7
Glossary

In contrast, an instance DB is designed to be used as specific storage and data


for the FB with which it has been associated.

SIMATIC Manager The SIMATIC Manager is the graphical user interface for SIMATIC users
under Windows 95.

Source File A source file (text file) is part of a program created either with a graphic or a
text-oriented editor and is compiled into an executable S7 user program or
the machine code for M7.
An S7 source file is stored in the “Sources” folder under the “S7 program”
folder.

Statement A statement is the smallest independent part of a user program created in a


textual language. The statement represents a command for the processor.

Statement List Statement List (STL) is a textual representation of the STEP 7 programming
(STL) language, similar to machine code. STL is the assembler language of STEP 5
and STEP 7. If you program in STL, the individual statements represent the
actual steps in which the CPU executes the program.

Station A station is a device which can be connected to one or more subnets; for
example, the programmable controller, programming device, and operator
station.

Status Bit The status bit stores the value of a bit that is referenced. The status of a bit
instruction that has read access to the memory (A, AN, O, ON, X, XN) is
always the same as the value of the bit that this instruction checks (the bit on
which it performs its logic operation). The status of a bit instruction that has
write access to the memory (S, R, =) is the same as the value of the bit to
which the instruction writes or, if no writing takes place, the same as the
value of the bit that the instruction references. The status bit has no
significance for bit instructions that do not access the memory. Such
instructions set the status bit to 1 (STA=1). The status bit is not checked by
an instruction. It is interpreted during program test (program status) only.

Status Word The status word is part of the register of the CPU. It contains status
information and error information which is displayed when specific STEP 7
commands are executed. The status bits can be read and written on by the
user, the error bits can only be read.

STL Source File A source file programmed in Statement List; corresponds to a source or text
file.

Statement List (STL) for S7-300/S7-400


Glossary-8 C79000-G7076-C565-01
Glossary

Stored Overflow The status bit OS stands for “stored overflow bit of the status word”. An
Bit overflow can take place, for example, after a math operation.

Symbol A symbol is a name which can be defined by the user subject to syntax
guidelines. After it has been declared (for example, as a variable, data type,
jump label, block etc) the symbol can be used for programming and for
operator interface functions. Example: Address: I 5.0, data type: BOOL,
Symbol: momentary contact switch / emergency stop.

Symbol Table A table in which the symbols of addresses for shared data and blocks are
allocated. Examples: Emergency Stop (symbol) -I 1.7 (address) or
closed-loop control (symbol) - SFB24 (block).

Symbolic In symbolic addressing, the address being processed is designated with a


Addressing symbol (as opposed to an absolute address).

System Function A system function is a function (without a memory) that is integrated in the
(SFC) S7 operating system and can, if necessary, be called from the STEP 7 user
program like a function (FC).

System Function A system function block (SFB) is a function (with a memory) that is
Block (SFB) integrated in the S7 operating system and can, if necessary, be called from
the STEP 7 user program like a function block (FB).

User Data Types User data types are special data structures which you can create yourself and
(UDTs) use in the entire user program after they have been defined. They can be used
like elementary or complex data types in the variable declaration of logic
blocks (FCs, FBs, OBs) or as a template for creating data blocks with the
same data structure.

User Program The user program contains all the statements and declarations and all the data
for signal processing which can be used to control a device or a process. It is
part of a programmable module (CPU, FM) and can be structured with
smaller units (blocks).

User Program The user program structure describes the call hierarchy of the blocks within
Structure an S7 program and provides an overview of the blocks used and their
dependency.

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 Glossary-9
Glossary

Variable The variable declaration includes a symbolic name, a data type and,
Declaration optionally, an initial value, an address and a comment.

Variable The variable declaration table is used for declaring the local data of a logic
Declaration Table block, when programming takes place in the Incremental Editor.

Variable Table The variable table is used to collect together the variables that you want to
(VAT) monitor and modify and set their relevant formats.

Statement List (STL) for S7-300/S7-400


Glossary-10 C79000-G7076-C565-01
Index
Symbols Accumulators
adding a constant to an address register, 4-7
)MCR. See Restore RLO, End MCR instruction
adding an integer to accumulator 1, 9-6
+. See Instructions, integer math, adding an in-
description of, 2-10
teger to accumulator 1
functions
+I. See Four-function math, Adding two 16-bit
Accumulator 2 to Accumulator 1 (POP),
integers; Instructions, integer math, adding
4-2
two 16-bit integers
Decrement Accumulator 1 (DEC), 4-6
+R. See Floating-point math, Adding two float-
Increment Accumulator 1 (INC), 4-6
ing-point numbers
handling the contents of, 4-2–4-6
=. See Assign (=) instruction
information interchange using Load and
Transfer instructions, 8-2
loading the status word into, 8-6
A operation of, 2-10
ABS. See Absolute value, forming the absolute with comparison instructions, 11-2
value of a real (floating–point ) number with floating-point math instructions,
Absolute addressing, practical application, B-4 10-2–10-3
Absolute value with integer math instructions, 9-2–9-3
definition of, 10-6 with Load and Transfer instructions, 8-2
forming the absolute value of a real (float- with word logic instructions, 13-2, 13-3,
ing-point) number, 10-6 13-6
Accumulator 1 to Accumulator 2 (PUSH), 4-2 operations
Accumulator 2 to Accumulator 1 (POP), 4-2 Accumulator 1 to Accumulator 2
Accumulator operations and address register (PUSH), 4-2
instructions, 4-2–4-6 Decrement Accumulator 1 (DEC), 4-6
Accumulator 1 to Accumulator 2 (PUSH), Increment Accumulator 1 (INC), 4-6
4-2 reversing the order of bytes within accumu-
Accumulator 2 to Accumulator 1 (POP), 4-2 lator 1
Decrement Accumulator 1 (DEC), 4-6 Change Byte Sequence in Accumulator
Decrement Accumulator 1 (DEC), 4-6 1, 16 bits (CAW) instruction, 12-13
Increment Accumulator 1 (INC), 4-6 Change Byte Sequence in Accumulator
Increment Accumulator 1 (INC), 4-6 1, 32 bits (CAD) instruction, 12-13
Toggle ACCU 1 with ACCU 2, 4-2 time value in, 6-4
Toggle ACCU 1 with ACCU 2, 4-2
Toggle the contents of, 4-2
transferring the contents of to the status
word, 8-6

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 Index-1
Index

ACOS. See Secant Addressing


Activate MCR Area (MCRA) instruction, absolute, 17-3, B-4
17-11–17-12 area-crossing register indirect, 3-11–3-14
Actual parameter, 17-2, 17-3 area-internal register indirect, 3-7–3-9
Actual parameters, assignment, 17-8 constants, 2-3
AD. See And Double Word instruction direct, 3-2
Address immediate, 3-2
assigning addresses to a Call (CALL) in- memory indirect, 3-3–3-5
struction, 17-3 pointer format
bits of the status word as, 5-13 area-crossing register indirect, 3-13–3-14
constants as, 13-2 area-internal register indirect, 3-8
description of, 2-2 area–internal register indirect, 3-9–3-10
label for a jump instruction, 16-2 memory indirect, 3-4–3-5
label for a loop instruction, 16-2 ranges, 2-9
of instructions symbolic, 2-4, 17-3, B-3
Assign (=), 5-25 And (A), using counters as bit operands, 7-2
Conditional Call (CC), 17-7 And (A) instruction, 5-3
counter, 7-10 And before Or, 5-15–5-16
Edge Negative (FN), 5-19 And Double Word (AD) instruction, 13-7–13-8
Edge Positive (FP), 5-19 And Not (AN), using counters as bit operands,
Load (L) and Transfer (T), 8-3–8-5 7-2
Open a Data Block (OPN), 15-2 And Not (AN) instruction, 5-3
Reset (R), 5-23 And Word (AW) instruction, 13-4–13-5
Set (S), 5-23 combining accumulator and constant,
Timer, 6-17 13-4–13-5
Unconditional Call (UC), 17-7 ANY, 17-9
symbolic, 17-3 Arc cosine (ACOS), 10-13–10-15
types Arc sine (ASIN), 10-13–10-14
address identifier and location, 2-5–2-6 Arc tangent (ATAN), 10-13
constants, 2-3, 13-2 Area-crossing register indirect addressing,
data block, 2-4 3-11–3-15
function (FC), 2-5 Area-internal register indirect addressing,
function block (FB), 2-5 3-7–3-9
location in status word, 2-3 Areas of memory
symbolic, 2-4 address ranges, 2-9
system function (SFC), 2-5 bit memory, 2-8
system function block (SFB), 2-5 counter, 2-8
Address register, adding a real number to an ad- data block, 2-8
dress register, 4-7 I/O (external I/O), 2-8
Address registers, 3-6 local data, 2-8
loading and transferring between, 8-11–8-12 peripheral I/O. See Areas of memory, I/O
(external I/O)
process image input, 2-8
process image output, 2-8
timer, 2-8
ASIN. See Cosecant
Assign (=) instruction, 5-20, 5-24–5-25
Assigning addresses to a Call (CALL) instruc-
tion, 17-3
ATAN. See Cotangent
AW. See And Word instruction

Statement List (STL) for S7-300/S7-400


Index-2 C79000-G7076-C565-01
Index

B Bit logic instructions, 5-2–5-5


And Not (AN), using counters as Boolean
BCD to Double Integer (BTD) conversion in-
operands, 7-2
struction, 12-4
Assign (=), 5-20, 5-24–5-25
BCD to Integer (BTI) conversion instruction,
Clear RLO (CLR), 5-26–5-27
12-3–12-4
Edge Negative (FN), 5-16–5-19
BCDF. See Errors, binary coded decimal con-
Edge Positive (FP), 5-16–5-19
version
Exclusive Or (X), using counters as Boolean
BEC. See Blocks, ending: Block End Condi-
operands, 7-2
tional instruction
Exclusive Or Not (XN), using counters as
Beginning a logic string, 2-12–2-13
Boolean operands, 7-2
BEU. See Blocks, ending: Block End Uncondi-
Negate RLO (NOT), 5-26
tional instruction
Or (O), using counters as Boolean operands,
Binary coded decimal (BCD) format
7-2
loading a count in, 8-10
Or Not (ON), using counters as Boolean op-
loading a time in, 8-9
erands, 7-2
Binary coded decimal (BCD) numbers
practical applications, B-3–B-6
converting, 12-2–12-9
Reset (R), 5-20, 5-21–5-23, 7-8–7-9
structure of a BCD number converted from a
counter, 7-4
32-bit integer, 12-6
timer, 6-6
structure of a BCD number to be converted
Save RLO in BR Register (SAVE), 5-26
from integer, 12-5
Set (S), 5-20, 5-21–5-23
structure of a BCD number to be converted
counter, 7-3, 7-8–7-9
to integer, 12-3
Set RLO (SET), 5-26, 5-27
structure of a32-bit BCD number to be con-
using counters as bit operands, 7-2
verted to double integer, 12-4
Bit memory area of memory, 2-8
Binary result (BR), bit of status word, 2-16
address ranges, 2-9
Bit logic instructions, And (A), using counters
Blocks, ending
as Boolean operands, 7-2
Block End Conditional (BEC) instruction,
Bit logic
17-16
Boolean, 5-2–5-12
Block End Unconditional (BEU) instruction,
practical applications, B-3–B-6
17-16
Boolean bit logic, 5-2–5-12
And (A) instruction, 5-3
And Not (AN) instruction, 5-3
checking condition codes (CC 1 and CC 0),
2-14–2-15
checking for overflow, 5-12–5-13
nesting expressions, 5-14–5-15
output of logic string, 5-20
BR. See Binary result
BTD. See BCD to Double Integer conversion
instruction
BTI. See BCD to Integer conversion instruction

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 Index-3
Index

C Condition codes (CC 1 and CC 0)


as affected by Compare instructions, 11-4,
CAD. See Change Byte Sequence in Accumula-
11-5
tor 1 conversion instruction, 32 bits
as affected by floating-point math instruc-
CALL. See Call instruction
tions, 10-4
Call instruction, 17-3–17-5
as affected by integer math instructions, 9-4
Calling a function that delivers a return value,
as affected by the shift and rotate instruc-
17-6
tions, 14-2
Calling a program segment multiple times, 16-8
as affected by word logic instructions, 13-2
CAW. See Change Byte Sequence in Accumula-
bits of status word, 2-14–2-15
tor 1 conversion instruction, 16 bits
instructions that evaluate CC 1 and CC 0,
CC. See Conditional Call instruction
11-6
CC 1 and CC 0. See Condition codes
relationship to conditional jump instructions,
CD. See Count Down instruction
16-6
CDB. See Exchange Shared DB and Instance
Conditional Call (CC) instruction, 17-7
DB instruction
Conditional jump instructions
Change Byte Sequence in Accumulator 1 con-
Jump If BR = 0 (JNBI), 16-5
version instruction
Jump If BR = 1 (JBI), 16-5
16 bits (CAW), 12-13
Jump If Minus (JM), 16-6
32 bits (CAD), 12-13
Jump If Minus or Zero (JMZ), 16-6
Checking condition codes (CC 1 and CC 0),
Jump If Not Zero (JN), 16-6
2-14–2-15
Jump If OS = 1 (JOS), 16-5
Clearing
Jump If OV = 1 (JO), 16-5
RLO (CRL) instruction, 5-26–5-27
Jump If Plus (JP), 16-6
the result of logic operation, 5-26–5-27
Jump If Plus or Zero (JPZ), 16-6, 16-7
CLR. See Clear RLO instruction
Jump If RLO = 0 (JCN), 16-4
Comparing
Jump If RLO = 0 with BR (JNB), 16-4
two integers, 11-3–11-5
Jump If RLO = 1 (JC), 16-4
two real numbers, 11-5–11-6
Jump If RLO = 1 with BR (JCB), 16-4
Comparison instructions, 11-2–11-3
Jump If Unordered (JUO), 16-6
Compare Double Integer, 11-3–11-5
Jump If Zero (JZ), 16-6
Compare Integer, 11-3–11-5
relationship of condition codes CC 1 and CC
Compare Real Number, 11-5
0, 16-6
criteria for comparisons, 11-2
operation of accumulators, 11-2
practical applications, B-10–B-11
Complements, forming, 12-14

Statement List (STL) for S7-300/S7-400


Index-4 C79000-G7076-C565-01
Index

Constants Counters
adding an integer constant to accumulator 1, area of memory, 2-8
9-6 address ranges, 2-9
as addresses of word logic instructions, 13-2, components, 7-2
13-4–13-7 count instructions, bit logic instructions, 7-2
Decrement Accumulator 1 by an 8-bit count value, format, 7-6–7-7
constant, 4-6 definition of, 7-2
Decrementing Accumulator 1 by an 8-bit enabling, 7-4, 7-8–7-9
constant, 4-6 instructions used with counters, 7-2–7-9
Incrementing Accumulator 1 by an 8-bit bit logic, 5-22–5-23, 7-2
constant, 4-6 Count Down (CD), 7-2, 7-5
used as address, 2-3 Count Up (CU), 7-2, 7-5
Conversion instructions Enable (FR), 7-2, 7-4
BCD to Double Integer (BTD), 12-4 Load Current Counter Value into Accu-
BCD to Integer (BTI), 12-3–12-4 mulator 1 as Binary Coded Decimal
Change Byte Sequence in Accumulator 1 (LC), 7-2, 8-10
16 bits (CAW), 12-13 Load Current Counter Value into Accu-
32 bits (CAD), 12-13 mulator 1 as Integer, 7-2
Double Integer to BCD (DTB), 12-6 practical applications, B-10–B-11
Double Integer to Real (DTR), 12-7 Reset (R), 7-2, 7-4, 7-8–7-9
Integer to BCD (ITB), 12-5 Set (S), 7-2, 7-3, 7-8–7-9
Integer to Double Integer (ITD), 12-6 resetting, 7-2, 7-4, 7-8–7-9
Negate Real Number (NEGR), 12-14–12-15 setting, 7-2, 7-3, 7-8–7-9
Ones Complement Double Integer (INVD), types
12-14 Count Down (CD), 7-2, 7-8–7-9
Ones Complement Integer (INVI), 12-14 Count Up (CU), 7-2, 7-8–7-9
overview of number conversion and round- CPU, registers, 3-6–3-11
ing, 12-12 nesting stack, 2-10
Round (RND), 12-9 operation of accumulators, 2-10
Round to Lower Double Integer (RND–), pointers, 3-6
12-11 status word, 2-12–2-16
Round to Upper Double Integer (RND+), time value in accumulator 1, 6-4
12-10 CU. See Count Up instruction
Truncate (TRUNC), 12-12
Twos Complement Double Integer (NEGD),
12-14
Twos Complement Integer (NEGI),
12-14–12-15
Converting
32-bit floating-point numbers to 32-bit inte-
gers, 12-8–12-12
binary coded decimal numbers and integers,
12-2–12-9
numbers, 12-12
COS. See Cosine
Cosine (COS), 10-13
Count Down (CD) instruction, 7-5
Count Up (CU) instruction, 7-5
Count value, format, 7-6–7-7

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 Index-5
Index

D DTR. See Double Integer to Real conversion


instruction
Data block (DB)
area of memory, 2-8
address ranges, 2-9
instance, 17-3 E
lengths and numbers, loading, 15-3–15-4 Edge Negative (FN) instruction, 5-16–5-19
loading the length of a shared data block Edge Positive (FP) instruction, 5-16–5-19
into accumulator 1 (L DBLG), 8-12, 15-3 Enable (FR) instruction
loading the length of an instance data block counters, 7-4, 7-8–7-9
into accumulator 1 (L DILG), 8-12, 15-3 timers, 6-6
loading the number of a shared data block Enable output (ENO). See Binary result
into accumulator 1 (L DBNO), 8-12, Ending blocks
15-3–15-4 Block End Conditional (BEC) instruction,
loading the number of an instance data block 17-16
into accumulator 1 (L DINO), 8-12, 15-3 Block End Unconditional (BEU) instruction,
registers, exchanging, 15-2 17-16
Data block (DB) instructions Errors, binary coded decimal conversion
Exchange Shared DB and Instance DB (BCDF), 12-3, 12-4
(CDB), 15-2 Examples, practical applications of instructions,
Load Length of Instance Data Block in Ac- B-2–B-14
cumulator 1 (DILG), 15-3 Exchange Shared DB and Instance DB (CDB)
Load Length of Shared Data Block in Accu- instruction, 15-2
mulator 1 (DBLG), 15-3 Exchange the contents of accumulators, 4-2
Load Number of Instance Data Block in Ac- Exclusive Or (X), using counters as Boolean
cumulator 1 (DINO), 15-3 operands, 7-2
Load Number of Shared Data Block in Ac- Exclusive Or Not (XN), using counters as Bool-
cumulator 1 (DBNO), 15-3–15-4 ean operands, 7-2
Open a Data Block (OPN), 15-2 Exclusive Or Word (XOW) instruction, 13-3,
Data types 13-4–13-5
ANY, 17-9 combining accumulator and constant,
for actual and formal parameters, 17-3 13-4–13-5
DBLG. See Load Length of Shared DB in Accu- EXP. See Exponential value to base E
mulator 1 instruction Exponential value to base E, EXP, 10-12
DBNO. See Load Number of Shared DB in Ac- Extended Pulse Timer (SE), 6-5, 6-9–6-10
cumulator 1 instruction
Deactivate MCR Area (MCRD) instruction,
17-11–17-12 F
DEC. See Decrement Accumulator 1
FBs. See Function blocks
Decrement Accumulator 1 (DEC), 4-6
FCs. See Functions
DILG. See Load Length of Instance DB in Ac-
First check (FC)
cumulator 1 instruction
bit of status word, 2-12–2-13
DINO. See Load Number of Instance DB in Ac-
result of, 2-12
cumulator 1 instruction
Direct addressing, 3-2
Double Integer to BCD (DTB) conversion in-
struction, 12-6
Double Integer to Real (DTR) conversion in-
struction, 12-7
Double integers, comparing two, 11-3–11-5
DTB. See Double Integer to BCD conversion
instruction

Statement List (STL) for S7-300/S7-400


Index-6 C79000-G7076-C565-01
Index

Floating-point math I
Adding two floating-point numbers (+R),
I/O (external I/O) area of memory, 2-8
10-3, 10-4
address ranges, 2-9
instructions
Image registers. See Process-image
forming the absolute value of a real num-
Immediate addessing, 3-2
ber (ABS), 10-6
INC. See Increment Accumulator 1
overview of four-function math, 10-2
Increment Accumulator 1 (INC), 4-6
relationship to accumulators, 10-2–10-3
Instruction statement
valid ranges of result, 10-4
addressing
Floating-point math, extended operations
constants, 2-3
arc cosine (ACOS), 10-13–10-15
symbolic, 2-4
arc tangent (ATAN), 10-13
structure of, 2-2–2-7
Floating-point math, extended math operations,
Instructions
arc sine (ASIN), 10-13–10-14
accumulator operation and address register,
FN. See Edge Negative instruction
4-2–4-6
Formal parameter, 17-2
alphabetical listing, international names,
Formal parameters, 17-3
A-12–A-16
Format
bit logic, practical applications, B-3–B-6
count value, 7-6–7-7
comparison, 11-2–11-8
time value, 6-4
criteria for comparison, 11-2
Forming complements, 12-14
operation of accumulators, 11-2
Four-function math, Adding two 16-bit integers
practical applications, B-10–B-11
(+I), 9-3
conversion, overview of number conversion
FP. See Edge Positive instruction
and rounding, 12-12
FR. See Enable instruction
counter, 7-2–7-13
Function (FC)
practical applications, B-10–B-11
as address of an instruction, 2-5
dependent on the Master Control Relay
calling FCs with the Call (CALL) instruc-
(MCR), 17-11
tion, 17-3–17-5
dependent on the Master control Relay
calling FCs with the Conditional Call (CC)
(MCR), 17-10
instruction, 17-7
floating-point math
calling FCs with the Unconditional Call
overview of four-function math, 10-2
(UC) instruction, 17-7
relationship to accumulators, 10-2–10-3
dependency on Master Control Relay
valid ranges of results, 10-4
(MCR), 17-11
integer math
Function block (FB)
overview of four-function math instruc-
as address of an instruction, 2-5
tions, 9-2
calling FBs with the Call (CALL) instruc-
practical applications, B-12–B-13
tion, 17-3–17-5
relationship to accumulators, 9-2–9-3
calling FBs with the Conditional Call (CC)
valid ranges of results, 9-4
instruction, 17-7
jump, unconditional, 16-3–16-4
calling FBs with the Unconditional Call
Load (L) and Transfer (T), 8-2–8-12
(UC) instruction, 17-7
area-crossing indirect addressing, 8-5
dependency on Master Control Relay
(MCR), 17-11

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 Index-7
Index

byte, word, or double word as address, Integer math instructions


8-5 adding an integer constant to accumulator 1,
definition of, 8-2 9-6
direct addressing, 8-4 adding two 16-bit integers (+I), 9-3
immediate addressing, 8-3 overview of four-function math instructions,
indirect addressing, 8-4 9-2
information interchange, 8-2 practical applications, B-12–B-13
loading and transferring between address relationship to accumulators, 9-2–9-3
registers (LAR and TAR), 8-11–8-12 valid ranges of results, 9-4
loading bits of the status word into accu- Integer to BCD (ITB) conversion instruction,
mulator 1, 8-6 12-5
loading the status word into accumulator Integer to Double Integer (ITD) conversion in-
1, 8-6 struction, 12-6
transferring the contents of accumulator Integers
1 to the status word, 8-6 adding to accumulator 1, 9-6
loading and transferring between address comparing two, 11-3–11-5
registers (LAR and TAR), 8-11–8-12 converting, 12-2–12-9
logic control, 16-2–16-11 International names for instructions, alphabeti-
See also Jump instructions cal listing, A-12–A-16
Loop (LOOP), 16-8 International names of the statement list (STL)
providing a label as address, 16-8 instructions, A-12
using efficiently, 16-9 INVD. See Ones Complement Double Integer
practical applications, B-2–B-14 conversion instruction
program control, assigning addresses to a Inverting numbers bit by bit, 12-14
call, 17-3 INVI. See Ones Complement Integer conversion
rotate, 14-6–14-8 instruction
shift, 14-2–14-6 ITB. See Integer to BCD conversion instruction
signed numbers, 14-4 ITD. See Integer to Double Integer conversion
unsigned numbers, 14-2–14-3 instruction
shift and rotate, 14-2–14-6
that evaluate the condition codes (CC 1 and
CC 0), 9-4, 10-4 J
that evaluate the overflow bit (OV) of the
JBI. See Jump If BR = 1 instruction
status word, 9-4, 10-4
JC. See Jump If RLO = 1 instruction
that evaluate the stored overflow bit (OS) of
JCB. See Jump If RLO = 1 with BR instruction
the status word, 9-4, 10-4
JCN. See Jump If RLO = 0 instruction
timer, 6-2–6-17
JL. See Jump to List instruction
practical applications, B-7–B-10
JM. See Jump If Minus instruction
Transfer (T). See Load (L) and Transfer (T)
JMZ. See Jump If Minus or Zero instruction
instructions
JN. See Jump If Not Zero instruction
word logic, 13-2–13-8
JNB. See Jump If RLO = 0 with BR instruction
16-bit, 13-3–13-8
JNBI. See Jump If BR = 0 instruction
32-bit, 13-6–13-8
JO. See Jump If OV = 1 instruction
accumulator administration, 13-2, 13-3,
JOS. See Jump If OS = 1 instruction
13-6
JP. See Jump If Plus instruction
constants as addresses, 13-2
JPZ. See Jump If Plus or Zero instruction
influence on status word bits, 13-2
JU. See Jump Unconditional instruction
practical applications, B-14
Jump If BR = 0 (JNBI) instruction, 16-5
Instructions that affect the status word, 5-10
Jump If BR = 1 (JBI) instruction, 16-5
Integer math, adding a real to an address regis-
Jump If Minus (JM) instruction, 16-6
ter, 4-7

Statement List (STL) for S7-300/S7-400


Index-8 C79000-G7076-C565-01
Index

Jump If Minus or Zero (JMZ) instruction, 16-6 K


Jump If Not Zero (JN) instruction, 16-6
Keywords, definition, C-1
Jump If OS = 1 (JOS) instruction, 16-5
Jump If OV = 1 (JO) instruction, 16-5
Jump If Plus (JP) instruction, 16-6
Jump If Plus or Zero (JPZ) instruction, 16-6, L
16-7 L. See Load and Transfer instructions
Jump If RLO = 0 (JCN) instruction, 16-4 Label, as address of a jump or loop instruction,
Jump If RLO = 0 with BR (JNB) instruction, 16-2
16-4 LAR. See Loading and transferring between ad-
Jump If RLO = 1 (JC) instruction, 16-4 dress registers
Jump If RLO = 1 with BR (JCB) instruction, LC. See Load Current Value into Accumulator 1
16-4 as Binary Coded Decimal
Jump If Unordered (JUO) instruction, 16-6 LN. See Natural Logarithm
Jump If Zero (JZ) instruction, 16-6 Load (L) and Transfer (T) instructions, 8-2–8-12
Jump instructions, 16-3–16-10 See also Instructions, Load (L) and Transfer
condition based on BR, OV, or OS bit of sta- (T)
tus word, 16-5 area-crossing indirect addressing, 8-5
condition based on result in condition code byte, word, or double word as address, 8-5
bits (CC 1 and CC 0) of status word, definition of, 8-2
16-6–16-7 direct addressing, 8-4
condition based on result of logic operation immediate addressing, 8-3
(RLO), 16-4–16-5 indirect addressing, 8-4
conditional information interchange, 8-2
Jump If BR = 0 (JNBI), 16-5 between modules and memory areas, 8-2
Jump If BR = 1 (JBI), 16-5 by way of the accumulator, 8-2
Jump If Minus (JM), 16-6 Load Current Counter Value into Accumula-
Jump If Minus or Zero (JMZ), 16-6 tor 1 as Binary Coded Decimal (LC),
Jump If Not Zero (JN), 16-6 8-10
Jump If OS = 1 (JOS), 16-5 loading and transferring between address
Jump If OV = 1 (JO), 16-5 registers (LAR and TAR), 8-11–8-12
Jump If Plus (JP), 16-6 loading bits of the status word into accumu-
Jump If Plus or Zero (JPZ), 16-6, 16-7 lator 1, 8-6
Jump If RLO = 0 (JCN), 16-4 loading the length of a shared data block
Jump If RLO = 0 with BR (JNB), 16-4 into accumulator 1 (L DBLG), 8-12
Jump If RLO = 1 (JC), 16-4 loading the length of an instance data block
Jump If RLO = 1 with BR (JCB), 16-4 into accumulator 1 (L DILG), 8-12
Jump If Unordered (JUO), 16-6 loading the number of a shared data block
Jump If Zero (JZ), 16-6 into accumulator 1 (L DBNO), 8-12
label as address, 16-2 loading the number of an instance data block
overview of, 16-2 into accumulator 1 (L DINO), 8-12
unconditional, 16-3–16-4 loading the status into accumulator 1, 8-6
Jump to List (JL), 16-3 transferring the contents of accumulator 1 to
Jump Unconditional (JU), 16-3 the status word, 8-6
Jump to List (JL) instruction, 16-3 Load Current Value into Accumulator 1 as
Jump Unconditional (JU) instruction, 16-3 Binary Coded Decimal
JUO. See Jump If Unordered instruction counter, 7-2
JZ. See Jump If Zero instruction timer, 6-2

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 Index-9
Index

Load Length of Instance DB in Accumulator 1 Master Control Relay (MCR) instructions,


(DILG) instruction, 15-3 17-10–17-15
Load Length of Shared DB in Accumulator 1 See also Program control instructions
(DBLG) instruction, 15-3 nesting, 17-13–17-15
Load Number of Instance DB in Accumulator 1 MCR functions, Important notes, 17-15
(DINO) instruction, 15-3 MCR(. See Save RLO in MCR Stack, Begin
Load Number of Shared DB in Accumulator 1 MCR instruction
(DBNO) instruction, 15-3–15-4 MCRA. See Activate MCR Area instruction
Loading a count value MCRD. See Deactivate MCR Area instruction
format, 7-6 Memory areas
in binary coded decimal (BCD) format (LC address ranges, 2-9
counter word), 8-10 bit memory, 2-8
in binary form (L counter word), 8-8 counter, 2-8
Loading a time value data block, 2-8
format, 6-3 I/O (external I/O), 2-8
in binary coded decimal (BCD) format (LC local data, 2-8
timer word), 8-9 process image input, 2-8
in binary form (L timer word), 8-7 process image output, 2-8
range, 6-5 timer, 2-8
Loading and transferring between address regis- Memory indirect addressing, 3-3–3-5
ters, 8-11–8-12 Multiplying a number by –1, 12-14
Loading data block lengths and numbers,
15-3–15-4
Loading the length of a data block into accumu- N
lator 1
Natural Logarithm (LN), 10-11
instance data block (L DILG), 8-12
Negate Real Number (NEGR) conversion in-
shared data block (L DBLG), 8-12
struction, 12-14–12-15
Loading the number of a data block into accu-
Negate RLO (NOT) instruction, 5-26
mulator 1
Negating numbers, 12-14
instance data block (L DINO), 8-12
Negating the result of logic operation, 5-26
shared data block (L DBNO), 8-12
Negative edge transitions, 5-16–5-19
Local data, area of memory, 2-8
NEGD. See Twos Complement Double Integer
address ranges, 2-9
conversion instruction
Logic control instructions, 16-2–16-11
NEGI. See Twos Complement Integer conver-
See also Jump and Loop instructions
sion instruction
Logic string
NEGR. See Negate Real Number conversion
beginning of, 2-12–2-13
instruction
definition of, 2-12–2-13
Nesting expressions, 5-14–5-17
output of, 5-20
And before Or, 5-15–5-16
terminating, 5-20
Nesting stack, 2-10, 5-14
Loop (LOOP) instruction, 16-8
Normally closed contact, 5-7
label as address, 16-2, 16-8
Normally open contact, 5-6
using efficiently, 16-9
NOT. See Negate RLO instruction

M
Master Control Relay (MCR)
dependency on, 17-10, 17-11
effect on Set (S) and Reset (R) instructions,
5-21–5-22, 17-10
implementation of, 17-13
Important notes, 17-15

Statement List (STL) for S7-300/S7-400


Index-10 C79000-G7076-C565-01
Index

O Process image input area of memory, 2-8


Process image output area of memory, 2-8
Off-Delay Timer (SF), 6-5, 6-15–6-16
Process-image input area of memory, address
On-Delay Timer (SD), 6-5, 6-11–6-12
ranges, 2-9
Ones Complement Double Integer (INVD) con-
Process-image output area of memory, address
version instruction, 12-14
ranges, 2-9
Ones Complement Integer (INVI) conversion
Processing order for And with Or instructions,
instruction, 12-14
5-15–5-16
Open a Data Block (OPN) instruction, 15-2
Program control instructions
Operand. See Address
Activate MCR Area, 17-11–17-12
OPN. See Open a Data Block instruction
assigning addresses to a Call (CALL) in-
OR, bit of status word, 2-14
struction, 17-3
Or (O), using counters as bit operands, 7-2
Block End Conditional (BEC), 17-16
Or branch, nesting expressions, 5-14–5-17
Block End Unconditional (BEU), 17-16
Or Not (ON), using counters as bit operands,
Call (CALL), 17-3–17-5
7-2
Conditional Call (CC), 17-7
Or Word (OW) instruction, 13-3, 13-4–13-5
Deactivate MCR Area, 17-11–17-12
combining accumulator and constant,
Master Control Relay (MCR) functions,
13-4–13-5
17-10–17-15
Order of processing And with Or instructions,
Restore RLO, End MCR: )MCR,
5-15–5-16
17-11–17-12, 17-13–17-14
OS. See Stored overflow
Save RLO in MCR Stack, Begin MCR:
Output of a logic string, 5-20
MCR(, 17-11–17-12, 17-13–17-14
OV. See Overflow
Unconditional Call (UC), 17-7
Overflow (OV)
Programming, practical applications, B-2–B-14
as affected by comparing two real numbers,
Pulse Timer (SP), 6-5–6-6, 6-7–6-8
11-5
PUSH. See Accumulator 1 to Accumulator 2
as affected by floating-point math instruc-
tions, 10-4
as affected by integer math instructions, 9-4
as affected by the shift and rotate instruc- R
tions, 14-2 R. See Reset instruction
as affected by word logic instructions, 13-2 Real number
bit of status word, 2-14 comparing two real numbers, 11-5
forming the absolute value, 10-6
Registers
P address, 3-6
CPU, 3-6–3-11
Parallel branch, nesting expressions, 5-14–5-17
Exchange Shared DB and Instance DB
Parameters
(CDB) instruction, 15-2
actual, 17-3
exchanging data block registers, 15-2
formal, 17-3
image. See Process-image
Pointer format
Reset (R) instruction, 5-20, 5-21–5-23
area-crossing register indirect addressing,
counters, 7-4, 7-8–7-9
3-13–3-14
timers, 6-6
area–internal register indirect addressing,
Resetting
3-9
a counter, 7-4
memory indirect addressing, 3-4–3-5
a timer, 6-6
POP. See Accumulator 2 to Accumulator 1
Positive edge transitions, 5-16–5-19

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 Index-11
Index

Restore RLO, End MCR instruction: )MCR, S


17-11–17-12, 17-13–17-14
S. See Set instruction
Result of logic operation (RLO)
S5 TIME
bit of status word, 2-13
time base, 6-4–6-5
clearing, 5-26–5-27
time value, 6-3
instructions that do not affect the RLO, 4-6
SAVE. See Save RLO in BR Register instruc-
negating, 5-26
tion
relationship to Block End instructions, 17-16
Save RLO in BR Register (SAVE) instruction,
saving, 5-26
5-26
setting, 5-26, 5-27
Save RLO in MCR Stack, Begin MCR instruc-
stored in nesting stack, 5-14
tion: MCR(, 17-11–17-12, 17-13–17-14
transitions of, 5-16–5-19
Saving, the result of logic operation, 5-26
with Assign (=) instruction, 5-24–5-25
SD. See On–Delay Timer
Retentive On-Delay Timer (SS), 6-5, 6-13–6-14
SE. See Extended Pulse Timer
Return value, calling a function that delivers a
SET. See Set RLO instruction
return value, 17-6
Set (S) instruction, 5-20, 5-21–5-23
Reversing the order of bytes within accumulator
counters, 7-3
1, 12-13
Set RLO (SET) instruction, 5-26, 5-27
RLD. See Rotate instructions, Rotate Left
Setting
Double Word
a counter, 7-3, 7-8–7-9
RLDA. See Rotate instructions, Rotate Accumu-
the result of logic operation, 5-26, 5-27
lator 1 Left via CC 1
SF. See Off–Delay Timer
RLO. See Result of Logic Operation
SFBs. See System function blocks
RND. See Round conversion instruction
SFCs. See System functions
RND+. See Round to Upper Double Integer
Shift and rotate instructions, 14-2–14-8
conversion instruction
Shift instructions, 14-2–14-6
RND–. See Round to Lower Double Integer
effect on condition codes CC 1 and CC 0
conversion instruction
and on the Overflow bit(OV) of the sta-
Rotate instructions, 14-6–14-8
tus word, 14-2
Rotate Accumulator 1 Left via CC 1
method of operation, 14-2
(RLDA), 14-8
Shift Left Double Word (SLD, 32 bits), 14-2
Rotate Accumulator 1 Right via CC 1
Shift Left Word (SLW, 16 bits), 14-2
(RRDA), 14-8
Shift Right Double Word (SRD, 32 bits),
Rotate Left Double Word (RLD), 14-7–14-8
14-2, 14-3
Rotate Right Double Word (RRD), 14-7
Shift Right Word (SRW, 16 bits), 14-2
Round (RND) conversion instruction, 12-9
Shift Sign Double Integer (SSD, 32 bits),
Round to Lower Double Integer (RND–) con-
14-4
version instruction, 12-11
Shift Sign Integer (SSI, 16 bits), 14-4
Round to Upper Double Integer (RND+) con-
signed numbers, 14-4
version instruction, 12-10
unsigned numbers, 14-2–14-3
Rounding
SIMATIC and International mnemonic abbrevi-
32-bit floating-point numbers to double inte-
ations of the statement list (STL) instruc-
gers, 12-8–12-11
tions, A-2, A-7
numbers, overview, 12-12
SIN. See Sine
real numbers to double integers, 12-8–12-11
Sine (SIN), 10-13
RRD. See Rotate instructions, Rotate Right
SLD. See Shift instructions, Shift Left Double
Double Word
Word
RRDA. See Rotate instructions, Rotate Accu-
SLW. See Shift instructions, Shift Left Word
mulator 1 Right via CC 1

Statement List (STL) for S7-300/S7-400


Index-12 C79000-G7076-C565-01
Index

SP. See Pulse Timer result of logic operation (RLO) bit, 2-13
SQR. See Square status (STA) bit, 2-13
SQRT. See Square root stored overflow (OS) bit, 2-14
Square (SQR), 10-9 stored overflow bit (OS) after a Compare
Square root (SQRT), 10-9 Real number instruction, 11-5
SRD. See Shift instructions, Shift Right Double transferring the contents of accumulator 1 to
Word it, 8-6
SRW. See Shift instructions, Shift Right Word STL instructions, alphabetical listing
SS. See Retentive On–Delay Timer arranged by International full name,
SSD. See Shift instructions, Shift Sign Double A-12–A-16
Integer arranged by the International mnemonic ab-
SSI. See Shift instructions, Shift Sign Integer breviations, A-7–A-11
STA. See Status, bit of status word arranged by the SIMATIC mnemonic abbre-
Starting a logic string, 2-12–2-13 viations, A-2–A-11
Starting a timer, 6-5 Stored overflow (OS)
Statement. See Instruction statement as affected by floating-point math instruc-
Statement list (STL), 1-1 tions, 10-4
definition of, 1-1 as affected by integer math instructions, 9-4
Status (STA), bit of status word, 2-13 bit of status word, 2-14
Status word Stored overflow (OV), as affected by comparing
binary result (BR) bit, 2-16 two real numbers, 11-5
bits affected by floating-point math instruc- Structure of an instruction statement, 2-2–2-7
tions, 10-4 STW. See Status word
bits affected by integer math instructions, Swapping, data block registers, 15-2
9-4 Symbolic addresses, 17-3
bits affected by the shift and rotate instruc- Symbolic addressing, 2-4, 17-3
tions, 14-2 practical example, B-3
condition code bits (CC 1 and CC 0), over- System function blocks (SFBs), as address of an
flow bit (OV) as affected by word logic instruction, 2-5
instructions, 13-2 System functions (SFCs), as address of an in-
condition code bits CC 1 and CC 0, relation- struction, 2-5
ship to conditional jump instructions,
16-6
condition codes (CC 1 and CC 0), 2-14–2-15 T
condition codes CC 1 and CC 0 after a
T. See Load and Transfer instructions
Compare instruction, 11-4, 11-5
TAK. See Toggle Accumulator 1 with Accumu-
description of, 2-12–2-16
lator 2
evaluation of 32-bit integer math result, 9-4
TAN. See Tangent
first check (FC) bit, 2-12–2-13
Tangent (TAN), 10-13
indication of valid range for integer math
TAR. See Loading and transferring between ad-
result, 9-4
dress registers
instructions that affect the status word, 5-10
Terminating a logic string, 5-20
instructions that evaluate the bits of the sta-
Terminating the scanning of a block, 17-16
tus word, 11-6
Time base for S5 TIME, 6-4–6-5
OR bit, 2-14
Time resolution. See Time base for S5 TIME
overflow (OV) bit, 2-14
overflow bit (OV) after a Compare Real
number instruction, 11-5
reading using the Load (L) instruction, 8-6

Statement List (STL) for S7-300/S7-400


C79000-G7076-C565-01 Index-13
Index

Time value Toggle the contents of Accumulator 1 with Ac-


format in accumulator 1, 6-4 cumulator 2, 4-2
range, 6-3–6-4 Transfer (T) instruction. See Load (L) and
syntax, 6-3 Transfer (T) instructions
Timers Transferring the contents of accumulator 1 to
area of memory, 2-8 the status word, 8-6
address ranges, 2-9 Transitional contacts, 5-16–5-19
components, 6-3–6-4 TRUNC. See Truncate conversion instruction
definition of, 6-2 Truncate (TRUNC) conversion instruction,
enabling, 6-6 12-12
instructions used with, 6-2–6-17 Twos Complement Double Integer (NEGD)
instructions used with timers conversion instruction, 12-14
bit logic, 5-22–5-23 Twos Complement Integer (NEGI) conversion
Enable (FR), 6-6 instruction, 12-14–12-15
Extended Pulse Timer (SE), 6-5,
6-9–6-10
Off-Delay Timer (SF), 6-5, 6-15–6-16 U
On-Delay Timer (SD), 6-5, 6-11–6-12
UC. See Unconditional Call instruction
practical applications, B-7–B-10
Unconditional Call (UC) instruction, 17-7
Pulse Timer (SP), 6-5–6-6, 6-7–6-8
Unconditional jump instructions
Reset (R), 6-6
Jump to List (JL), 16-3
Retentive On-Delay Timer (SS), 6-5,
Jump Unconditional (JU), 16-3
6-13–6-14
location in memory, 6-3
number supported, 6-3
resetting, 6-6 W
resolution. See Time base for S5 TIME Word logic instructions, 13-2–13-8
starting, 6-5 16-bit, 13-3–13-8
time base for S5 TIME, 6-4–6-5 32-bit, 13-6–13-8
time value, 6-3 accumulator administration, 13-2, 13-3, 13-6
range, 6-3–6-4 And Double Word (AD), 13-7–13-8
syntax, 6-3 And Word (AW), 13-4, 13-5
types, 6-2 Exclusive Or Word (XOW), 13-3
Extended Pulse (SE), 6-2, 6-5, 6-9–6-10 Or Word (OW), 13-3, 13-4
Off-Delay (SF), 6-2, 6-5, 6-15–6-16 practical applications, B-14
On-Delay (SD), 6-2, 6-5, 6-11–6-12
overview, 6-18
Pulse (SP), 6-2, 6-5–6-6, 6-7–6-8 X
Retentive On-Delay (SS), 6-2, 6-5,
X. See Exclusive Or instruction
6-13–6-14
XN. See Exclusive Or Not instruction
Toggle Accumulator 1 with Accumulator 2. See
TAK

Statement List (STL) for S7-300/S7-400


Index-14 C79000-G7076-C565-01
Siemens AG
A&D AS E81

Oestliche Rheinbrueckenstr. 50
D-76181 Karlsruhe
Federal Republic of Germany

From:
Your Name: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Your Title: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Company Name: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Street: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
City, Zip Code_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Country: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Phone: _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Please check any industry that applies to you:

r Automotive r Pharmaceutical
r Chemical r Plastic
r Electrical Machinery r Pulp and Paper
r Food r Textiles
r Instrument and Control r Transportation
r Nonelectrical Machinery r Other _ _ _ _ _ _ _ _ _ _ _
r Petrochemical

Statement List (STL) for S7-300/S7-400


$

C79000-G7076-C565-01 1
Remarks Form
Your comments and recommendations will help us to improve the quality and usefulness
of our publications. Please take the first available opportunity to fill out this questionnaire
and return it to Siemens.

Please give each of the following questions your own personal mark within the range
from 1 (very good) to 5 (poor).
1. Do the contents meet your requirements?
2. Is the information you need easy to find?
3. Is the text easy to understand?
4. Does the level of technical detail meet your requirements?
5. Please rate the quality of the graphics/tables:

Additional comments:
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Statement List (STL) for S7-300/S7-400


2 C79000-G7076-C565-01