Complementary
technical information
General Contents
Use of LV switches
Protection of LV/LV
transformers and capacitors
Coordination with electrical
busbar trunking
Livre 1.indb 1
04/11/2009 15:54:48
Livre 1.indb 2
04/11/2009 15:54:50
Complementary
technical information
Contents
Protection discrimination
Protection discrimination / DC
64
70
Discrimination tables
75
Cascading
85
88
92
96
98
99
105
112
115
138
144
146
147
150
155
160
161
163
171
172
173
175
177
179
181
183
185
Use of LV switches
187
190
Switch-disconnectors protection
Protection of switch-disconnectors
195
204
210
214
216
218
221
225
226
230
233
558E4000TDM.indd 3
20/11/2009 13:41:31
Livre 1.indb 4
04/11/2009 15:54:53
Protection discrimination
Complementary
technical information
Contents
Upstream device
Downstream device
What is discrimination
Table
page
6
iDPN
B, C, D curves
iDPN
8 to 10
C60
B, C, K curves
iDPN, C60
11 to 13
C120N/H
B, C, D curves
iDPN
14
C60
14
C120N/H
15
iDPN
21
C120N/H
21
C60
23
NG125, C120
29
31
31
C60L
32
iDPN,
33
33
NSX100 to 250
iDPN
34 and 35
C60, C120
34 and 35
NG125-160, NSC100N
34 and 35
NSX100 to 630
iDPN
37
Micrologic
C60, C120
37
37
iDPN
38
C60, C120
38
38
NS630b-1600
39
iDPN
40 and 41
C60, C120
40 and 41
NG125N/H/L
NG125, C120
C60
C60L
B, C, D curves
B, C, D curves
D, K curves
B, C, K, Z curves
NG160N/E/H, NSC100N,
NS630b to 1600N/H
Micrologic
NS1600b to 3200N/H
iDPN
42
C60, C120
42
42
NS630b-1000
43
iDPN
44 and 49
C60, C120
44 and 49
44 and 49
NS630b-1600
45 and 47
Masterpact
46 and 48
NS630b-1000, Masterpact
49
iDPN
50 and 58, 61
C60, C120
50 and 58, 61
50 and 58, 61
NS630b-1600
51 and 55,
Masterpact
NS100 to 630 DC
NS100 to 630 DC
64
67
Masterpact NT
Masterpact NW
558E4300TDM.indd 5
20/11/2009 13:44:31
Complementary
technical information
Protection discrimination
What is discrimination?
Discrimination, also called selectivity, is the coordination of automatic protection
devices in such a manner that a fault appearing at a given point in a network is
cleared by the protection device installed immediately upstream of the fault, and by
that device alone.
b total discrimination
Discrimination is said to be total if, for all fault current values, from overloads up to
the non-resistive short-circuit current, circuit breaker D2 opens and D1 remains
closed.
b partial discrimination
Discrimination is partial if the above condition is not respected up to the full shortcircuit current, but only to a lesser value termed the selectivity limit current (Is).
b no discrimination
In the event of a fault, both circuit breakers D1 and D2 open.
DB115814
Due to the Roto-active breaking technique employed by the Compact NSX, the
combined use of Schneider Electric circuit breakers provides an exceptional level of
protection discrimination.
This is the result of the implementation and optimisation of three different
techniques:
b current discrimination
b time discrimination
b energy discrimination.
Tripping of the upstream device is slightly delayed to ensure that the downstream device
trips first.
Discrimination is ensured if the ratio between the short-circuit thresholds is greater than 1.5.
High short-circuit protection: time discrimination.
This protection system combines the exceptional current limiting capacity of the Compact
NS and the advantages of reflex tripping, sensitive to the energy dissipated in the device by the
short-circuit. In the event of a high short-circuit detected by two circuit breakers, the downstream
device limits it sharply. The energy dissipated in the upstream device is not sufficient to trip it, i.e.
discrimination is total for all short-circuit currents.
Discrimination is ensured if the ratio between the circuit breaker ratings is greater than 2.
(1) Except for the L1 performance level on Masterpact NT and subject to the discrimination rules
on page 558E4300/7.
Livre 1.indb 6
04/11/2009 15:54:57
Complementary
technical information
Protection discrimination
DB120590
Requisite conditions
The values indicated in the tables are valid for operational rated voltages
of 220, 380, 415 and 440V:
Discrimination between two distribution circuit breakers.
Upstream
TM
Micrologic
Downstream
TM or Multi 9
Micrologic
TM or Multi 9
Micrologic
u 2.5
u 2.5
u 2.5
u 2.5
Thermal protection
Ir up/Ir down
u 1.6
u 1.6
u 1.6
u 1.3
Magnetic protection
Im up/Im down
u2
u 1.5
u 1.5
u 1.5
These conditions ensure that curves dont overlap. Curves could also be checked with Curve Direct software tools
DB125679
DB117227
b I2t Off / On
Tables indicate selectivity limits assuming I2t Function is Off. If I2t function is ON
user shall check curves.
b Ground Fault protection (Ig, Tg)
When upstream and downstream breaker are equipped with Micrologic 6.x, user
should implement current and time discrimination:
v current sensing discrimination
Threshold setting of upstream GFP device tripping is greater than that of the
downstream GFP device. Because of tolerances on the settings, a 30 % difference
between the upstream and downstream thresholds is sufficient.
v time graded discrimination
The intentional time delay setting of the upstream GFP device is greater than the
opening time of the downstream device. Furthermore, the intentional time delay
given to the upstream device must respect the maximum time for the elimination of
insulation faults defined by the NEC 230.95 (i.e. 1s for 3000 A).
DB125678
Ig D1 >= 1,3 Ig D2
D1
RCD
D2
RCD
b Compact NSX Trip units dedicated to motor protection ("M" type) can not be used
to ensure discrimination with downstream circuit breaker.
b Furthermore Compact NSX trip unit dedicated to distribution should not be used to
protect motors, even motors wit soft starter or speed drive.
558E4300.indd 7
09/11/2009 15:00:40
Protection discrimination
Complementary
technical information
Upstream
In (A)
iDPN
B curve
1
Downstream
Rating
Discrimination limit (A)
iDPN
1
B curve
2
3
4
6
10
16
20
25
32
40
Discrimination limit (A)
iDPN
1
C curve
2
3
4
6
10
16
20
25
32
40
Discrimination limit (A)
iDPN
1
D curve
2
3
4
6
10
16
20
25
32
40
400
10
16
20
25
32
40
12
12
16
16
25
25
25
25
40
40
40
40
40
63
63
63
63
63
63
80
80
80
80
80
80
100
100
100
100
100
100
100
125
125
125
125
125
125
125
125
160
160
160
160
160
160
160
160
160
12
16
16
25
25
25
40
40
40
40
63
63
63
63
63
80
80
80
80
80
80
100
100
100
100
100
100
125
125
125
125
125
125
125
160
160
160
160
160
160
160
160
16
25
25
40
40
40
63
63
63
63
80
80
80
80
80
100
100
100
100
100
125
125
125
125
125
125
160
160
160
160
160
160
160
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
Livre 1.indb 8
04/11/2009 15:55:04
Protection discrimination
Complementary
technical information
Upstream
In (A)
iDPN
C curve
1
Downstream
Rating
Discrimination limit (A)
iDPN
1
B curve
2
3
4
6
10
16
20
25
32
40
Discrimination limit (A)
iDPN
1
C curve
2
3
4
6
10
16
20
25
32
40
Discrimination limit (A)
iDPN
1
D curve
2
3
4
6
10
16
20
25
32
40
400
10
16
20
25
32
40
16
25
25
32
32
32
50
50
50
50
80
80
80
80
80
125
125
125
125
125
125
160
160
160
160
160
160
160
200
200
200
200
200
200
200
250
250
250
250
250
250
250
250
320
320
320
320
320
320
320
320
320
16
25
25
32
32
32
50
50
50
50
80
80
80
80
80
125
125
125
125
125
125
160
160
160
160
160
160
160
200
200
200
200
200
200
200
250
250
250
250
250
250
250
250
320
320
320
320
320
320
320
320
320
16
25
32
32
50
50
50
80
80
80
80
125
125
125
125
125
160
160
160
160
160
160
200
200
200
200
200
200
200
250
250
250
250
250
250
250
320
320
320
320
320
320
320
320
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
Livre 1.indb 9
04/11/2009 15:55:05
Protection discrimination
Complementary
technical information
Upstream
In (A)
Downstream
Rating
Discrimination limit (A)
iDPN
1
B curve
2
3
4
6
10
16
20
25
32
40
Discrimination limit (A)
iDPN
1
C curve
2
3
4
6
10
16
20
25
32
40
Discrimination limit (A)
iDPN
1
D curve
2
3
4
6
10
16
20
25
32
40
400
iDPN
D curve
1
10
16
20
25
32
40
12
24
40
40
50
50
72
72
72
72
125
125
125
125
125
200
200
200
200
200
200
250
250
250
250
250
250
300
300
300
300
300
300
300
400
400
400
400
400
400
400
400
500
500
500
500
500
500
500
500
500
12
24
40
40
50
50
72
72
72
72
125
125
125
125
125
200
200
200
200
200
200
250
250
250
250
250
250
300
300
300
300
300
300
300
400
400
400
400
400
400
400
400
500
500
500
500
500
500
500
500
500
12
24
40
40
50
50
72
72
72
72
125
125
125
125
125
200
200
200
200
200
200
250
250
250
250
250
250
300
300
300
300
300
300
300
400
400
400
400
400
400
400
400
500
500
500
500
500
500
500
500
500
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
10
Livre 1.indb 10
04/11/2009 15:55:05
Protection discrimination
Complementary
technical information
Upstream
In (A)
C60N/H/L
B curve
2
3
Downstream
Rating
Discrimination limit (A)
iDPN, C60
1
B curve
2
3
4
6
10
16
20
25
32
40
50/63
Discrimination limit (A)
iDPN, C60
1
C curve
2
3
4
6
10
16
20
25
32
40
50/63
Discrimination limit (A)
iDPN, C60
1
D curve
2
3
4
6
10
16
20
25
32
40
50/63
400
10
16
20
25
32
40
50
63
16
16
25
25
25
25
40
40
40
40
40
63
63
63
63
63
63
80
80
80
80
80
80
100
100
100
100
100
100
100
125
125
125
125
125
125
125
125
160
160
160
160
160
160
160
160
160
200
200
200
200
200
200
200
200
200
200
250
250
250
250
250
250
250
250
250
250
250
16
16
25
25
25
40
40
40
40
63
63
63
63
63
80
80
80
80
80
80
100
100
100
100
100
100
125
125
125
125
125
125
125
160
160
160
160
160
160
160
160
200
200
200
200
200
200
200
200
200
250
250
250
250
250
250
250
250
250
250
16
25
25
40
40
40
63
63
63
63
80
80
80
80
80
100
100
100
100
100
125
125
125
125
125
125
160
160
160
160
160
160
160
200
200
200
200
200
200
200
200
250
250
250
250
250
250
250
250
250
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
11
Livre 1.indb 11
04/11/2009 15:55:06
Protection discrimination
Complementary
technical information
Upstream
In (A)
C60N/H/L
C curve
2
3
Downstream
Rating
Discrimination limit (A)
iDPN, C60
1
B curve
2
3
4
6
10
16
20
25
32
40
50/63
Discrimination limit (A)
iDPN, C60
1
C curve
2
3
4
6
10
16
20
25
32
40
50/63
Discrimination limit (A)
iDPN, C60
1
D curve
2
3
4
6
10
16
20
25
32
40
50/63
400
10
16
20
25
32
40
50
63
32
32
50
50
50
50
80
80
80
80
80
125
125
125
125
125
125
160
160
160
160
160
160
200
200
200
200
200
200
200
250
250
250
250
250
250
250
250
320
320
320
320
320
320
320
320
320
400
400
400
400
400
400
400
400
400
400
500
500
500
500
500
500
500
500
500
500
500
32
32
50
50
50
50
80
80
80
80
80
125
125
125
125
125
125
160
160
160
160
160
160
200
200
200
200
200
200
200
250
250
250
250
250
250
250
250
320
320
320
320
320
320
320
320
320
400
400
400
400
400
400
400
400
400
400
500
500
500
500
500
500
500
500
500
500
500
32
32
50
50
50
80
80
80
80
125
125
125
125
125
160
160
160
160
160
160
200
200
200
200
200
200
200
250
250
250
250
250
250
250
320
320
320
320
320
320
320
320
400
400
400
400
400
400
400
400
400
500
500
500
500
500
500
500
500
500
500
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
12
Livre 1.indb 12
04/11/2009 15:55:07
Protection discrimination
Complementary
technical information
Upstream
In (A)
C60N/H D curve
C60L K curve
2
3
Downstream
Rating
Discrimination limit (A)
iDPN, C60
1
B curve
2
3
4
6
10
16
20
25
32
40
50/63
Discrimination limit (A)
iDPN, C60
1
C curve
2
3
4
6
10
16
20
25
32
40
50/63
Discrimination limit (A)
iDPN, C60
1
D curve
2
3
4
6
10
16
20
25
32
40
50/63
400
10
16
20
25
32
40
50
63
50
50
72
72
72
72
125
125
125
125
125
200
200
200
200
200
200
250
250
250
250
250
250
300
300
300
300
300
300
300
400
400
400
400
400
400
400
400
500
500
500
500
500
500
500
500
500
630
630
630
630
630
630
630
630
630
630
800
800
800
800
800
800
800
800
800
800
800
50
50
72
72
72
72
125
125
125
125
125
200
200
200
200
200
200
250
250
250
250
250
250
300
300
300
300
300
300
300
400
400
400
400
400
400
400
400
500
500
500
500
500
500
500
500
500
630
630
630
630
630
630
630
630
630
630
800
800
800
800
800
800
800
800
800
800
800
50
50
72
72
72
72
125
125
125
125
125
200
200
200
200
200
200
250
250
250
250
250
250
300
300
300
300
300
300
300
400
400
400
400
400
400
400
400
500
500
500
500
500
500
500
500
500
630
630
630
630
630
630
630
630
630
630
800
800
800
800
800
800
800
800
800
800
800
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
13
558E4305.indd 13
23/11/2009 10:51:09
Protection discrimination
Complementary
technical information
Upstream
In (A)
Downstream
Rating
Discrimination limit (A)
iDPN
6
B curve
10
16
20
25
32
40
Discrimination limit (A)
iDPN
1
C curve
2
3
6
10
16
20
25
32
40
Discrimination limit (A)
iDPN, C60
1
D curve
2
3
6
10
16
20
25
32
40
400
C120N/H
B curve
10
16
20
25
32
40
50
63
80
100
125
63
80
80
400
100
100
500
100
125
125
700
500
160
160
160
800
600
200
200
200
200
3000
1800
1000
1000
800
600
250
T
3000
2000
1600
1300
1000
320
T
T
3300
2500
2100
1800
1600
T
T
3750
3700
3700
2700
2400
300
150
40
500
300
63
63
700
500
300
80
1000
700
500
400
100
1500
1000
700
500
350
125
2000
1500
1000
700
500
340
160
2500
2000
1500
800
600
450
200
200
T
T
T
3000
1800
1000
1000
800
600
T
T
T
T
3000
2000
1600
1300
1000
320
T
T
T
T
4000
3300
2500
2100
1800
1600
T
T
T
T
T
3700
3700
3700
2700
2400
300
150
40
500
300
63
63
700
500
300
80
1000
700
500
400
100
1500
1000
700
500
350
2000
1500
1000
700
500
340
2500
2000
1500
800
600
450
200
T
T
T
3000
1800
1000
1000
800
T
T
T
T
3000
2000
1600
1300
1000
T
T
T
T
4000
3300
2500
2100
1800
1600
T
T
T
T
T
3700
3700
3700
2700
2400
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
14
Livre 1.indb 14
04/11/2009 15:55:08
Protection discrimination
Complementary
technical information
Upstream
In (A)
C120N/H
B curve
10
Downstream
Rating
Discrimination limit (A)
C120N/H
10
B curve
16
20
25
32
40
50
63
80
100
125
Discrimination limit (A)
C120N/H
10
C curve
16
20
25
32
40
50
63
80
100
125
Discrimination limit (A)
C120N/H
10
D curve
16
20
25
32
40
50
63
80
100
125
400
16
20
25
32
40
50
63
80
100
125
80
100
125
125
160
160
160
200
200
200
200
250
250
250
250
250
320
320
320
320
320
320
400
400
400
400
400
400
400
500
500
500
500
500
500
500
500
125
160
200
250
250
250
320
320
320
400
400
400
400
500
500
500
500
500
200
250
320
320
400
400
400
500
500
500
500
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
15
Livre 1.indb 15
04/11/2009 15:55:09
Protection discrimination
Complementary
technical information
Upstream
In (A)
Downstream
Rating
Discrimination limit (A)
iDPN
6
B curve
10
16
20
25
32
40
Discrimination limit (A)
iDPN
1
C curve
2
3
6
10
16
20
25
32
40
Discrimination limit (A)
iDPN
1
D curve
2
3
6
10
16
20
25
32
40
400
C120N/H
C curve
10
16
20
25
32
40
50
63
80
100
125
125
170
160
400
200
200
500
350
270
250
700
500
340
320
320
800
600
450
400
400
400
3000
1800
1250
1000
800
600
500
T
3000
2000
1600
1300
1000
700
T
T
3300
2500
2100
1800
1600
T
T
3700
3700
3700
2700
2400
300
150
120
120
500
300
200
200
200
700
500
300
240
240
1000
700
500
400
300
300
1500
1000
700
500
400
400
2000
1500
1000
700
500
500
500
2500
2000
1500
800
600
600
600
600
4500
4500
4500
3000
1800
1000
1000
800
800
800
4500
4500
4500
4500
3000
2000
1600
1300
1000
1000
4500
4500
4500
4500
4500
3300
2500
2100
1800
1600
4500
4500
4500
4500
4500
3700
3700
3700
2700
2400
300
150
120
500
300
200
700
500
300
1000
700
500
400
1500
1000
700
500
2000
1500
1000
700
500
2500
2000
1500
800
600
4500
4500
4500
3000
1800
1000
1000
4500
4500
4500
4500
3000
2000
1600
1300
4500
4500
4500
4500
4500
3300
2500
2100
1800
4500
4500
4500
4500
4500
3700
3700
3700
2700
2400
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
16
Livre 1.indb 16
04/11/2009 15:55:09
Protection discrimination
Complementary
technical information
Upstream
In (A)
C120N/H
C curve
10
Downstream
Rating
Discrimination limit (A)
C120N/H
10
B curve
16
20
25
32
40
50
63
80
100
125
Discrimination limit (A)
C120N/H
10
C curve
16
20
25
32
40
50
63
80
100
125
Discrimination limit (A)
C120N/H
10
D curve
16
20
25
32
40
50
63
80
100
125
400
16
20
25
32
40
50
63
80
100
125
160
200
200
250
250
250
320
320
320
400
400
400
400
500
500
500
500
500
500
630
630
630
630
630
630
630
800
800
800
800
800
800
800
1000
1000
1000
1000
1000
1000
1000
1000
200
250
250
320
320
320
400
400
400
400
500
500
500
500
500
630
630
630
630
630
630
800
800
800
800
800
800
800
1000
1000
1000
1000
1000
1000
1000
1000
250
320
400
400
500
500
500
630
630
630
630
800
800
800
800
800
1000
1000
1000
1000
1000
1000
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
17
Livre 1.indb 17
04/11/2009 15:55:10
Protection discrimination
Complementary
technical information
Upstream
In (A)
Downstream
Rating
Discrimination limit (A)
iDPN
6
B curve
10
16
20
25
32
40
Discrimination limit (A)
iDPN
1
C curve
2
3
6
10
16
20
25
32
40
Discrimination limit (A)
iDPN
1
D curve
2
3
6
10
16
20
25
32
40
400
C120N/H
D curve
10
16
20
25
32
40
50
63
80
100
125
125
250
250
250
250
250
400
200
400
400
500
500
500
500
500
630
630
630
630
630
630
800
800
800
800
800
800
3000
1800
1250
1000
1000
1000
1000
T
3000
2000
1600
1250
1250
1250
T
T
3300
2500
2100
1800
1600
T
T
3700
3700
3700
2700
2400
300
150
125
125
500
300
200
250
250
700
500
250
250
250
250
1000
700
400
400
200
400
400
1500
1000
500
500
500
500
500
500
2000
1500
700
630
630
630
630
630
630
2500
2000
800
800
800
800
800
800
800
4500
4500
3000
3000
1800
1250
1000
1000
1000
1000
4500
4500
4500
4500
3000
2000
1600
1250
1250
1250
4500
4500
4500
4500
4500
3300
2500
2100
1800
1600
4500
4500
4500
4500
4500
3700
3700
3700
2700
2400
300
150
120
500
300
200
250
700
500
300
240
240
1000
700
500
400
200
400
1500
1000
700
500
500
500
500
2000
1500
1000
630
630
630
630
630
2500
2000
1500
800
800
800
800
800
800
4500
4500
4500
3000
1800
1250
1000
1000
1000
1000
4500
4500
4500
4500
3000
2000
1600
1250
1250
1250
4500
4500
4500
4500
4500
3300
2500
2100
1800
1600
4500
4500
4500
4500
4500
3700
3700
3700
2700
2400
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
18
Livre 1.indb 18
04/11/2009 15:55:10
Protection discrimination
Complementary
technical information
Upstream
In (A)
C120N/H
D curve
10
Downstream
Rating
Discrimination limit (A)
C120N/H
10
B curve
16
20
25
32
40
50
63
80
100
125
Discrimination limit (A)
C120N/H
10
C curve
16
20
25
32
40
50
63
80
100
125
Discrimination limit (A)
C120N/H
10
D curve
16
20
25
32
40
50
63
80
100
125
400
16
20
25
32
40
50
63
80
100
125
192
240
300
300
384
384
384
480
480
480
600
600
600
600
756
756
756
756
756
960
960
960
960
960
960
960
1200
1200
1200
1200
1200
1200
1200
1200
1500
1500
1500
1500
1500
1500
1500
1500
1500
300
384
384
480
480
480
600
600
600
600
756
756
756
756
756
960
960
960
960
960
960
960
1200
1200
1200
1200
1200
1200
1200
1500
1500
1500
1500
1500
1500
1500
1500
1500
300
384
480
600
600
600
756
756
756
756
756
756
960
960
960
960
960
960
960
1200
1200
1200
1200
1200
1200
1200
1500
1500
1500
1500
1500
1500
1500
1500
1500
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
19
Livre 1.indb 19
04/11/2009 15:55:11
Protection discrimination
Complementary
technical information
Upstream
In (A)
Downstream
Rating
Discrimination limit (A)
iDPN
6
B curve
10
16
20
25
32
40
Discrimination limit (A)
iDPN
1
C curve
2
3
6
10
16
20
25
32
40
Discrimination limit (A)
C120N/H
10
B curve
16
20
25
32
40
50
63
80
100
125
Discrimination limit (A)
C120N/H
10
C curve
16
20
25
32
40
50
63
80
100
125
Discrimination limit (A)
C120N/H
10
D curve
16
20
25
32
40
50
63
80
100
125
400
NG125N/H/L
B curve
10
16
300
150
40
25
32
40
50
63
80
100
125
63
80
80
400
100
100
500
100
125
125
700
500
160
160
160
800
600
200
200
200
200
3000
1800
1000
1000
800
600
T
3000
2000
1600
1300
1000
320
T
T
3300
2500
2100
1800
1600
T
T
3750
3700
3700
2700
2400
500
300
63
63
700
500
300
80
1000
700
500
400
100
1500
1000
700
500
350
125
2000
1500
1000
700
500
340
160
2500
2000
1500
800
600
450
200
200
T
T
T
3000
1800
1000
1000
800
600
T
T
T
T
3000
2000
1600
1300
1000
320
T
T
T
T
4000
3300
2500
2100
1800
1600
T
T
T
T
T
3700
3700
3700
2700
2400
80
100
100
125
125
125
160
160
160
200
200
200
200
250
250
250
250
250
250
320
320
320
320
320
320
320
400
400
400
400
400
400
400
500
500
500
500
500
500
500
500
500
125
160
200
200
250
250
250
320
320
320
320
400
400
400
400
400
500
500
500
500
500
200
250
320
320
400
400
400
500
500
500
500
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
20
558E4305.indd 20
20/11/2009 13:49:37
Protection discrimination
Complementary
technical information
Upstream
In (A)
Downstream
Rating
Discrimination limit (A)
iDPN
6
B curve
10
16
20
25
32
40
Discrimination limit (A)
iDPN
1
C curve
2
3
6
10
16
20
25
32
40
Discrimination limit (A)
iDPN
1
D curve
2
3
6
10
16
20
25
32
40
Discrimination limit (A)
C120N/H
10
B curve
16
20
25
32
40
50
63
80
100
125
Discrimination limit (A)
C120N/H
10
C curve
16
20
25
32
40
50
63
80
100
125
Discrimination limit (A)
C120N/H
10
D curve
16
20
25
32
40
50
63
80
100
125
400
NG125N/H/L
C curve
10
16
25
32
40
50
63
80
100
125
170
400
200
500
350
270
700
500
340
320
800
600
450
400
400
3000
1800
1250
1000
800
600
T
3000
2000
1600
1300
1000
700
T
T
3300
2500
2100
1800
1600
T
T
3700
3700
3700
2700
2400
300
150
120
120
500
300
200
200
200
700
500
300
240
240
1000
700
500
400
300
300
1500
1000
700
500
400
400
2000
1500
1000
700
500
500
500
2500
2000
1500
800
600
600
600
600
4500
4500
4500
3000
1800
1000
1000
800
800
800
4500
4500
4500
4500
3000
2000
1600
1300
1000
1000
4500
4500
4500
4500
4500
3300
2500
2100
1800
1600
4500
4500
4500
4500
4500
3700
3700
3700
2700
2400
300
150
120
500
300
200
700
500
300
1000
700
500
400
1500
1000
700
500
2000
1500
1000
700
500
2500
2000
1500
800
600
4500
4500
4500
3000
1800
1000
1000
4500
4500
4500
4500
3000
2000
1600
1300
4500
4500
4500
4500
4500
3300
2500
2100
1800
4500
4500
4500
4500
4500
3700
3700
3700
2700
2400
170
212
212
272
272
272
340
340
340
425
425
425
425
535
535
535
535
535
535
680
680
680
680
680
680
680
850
850
850
850
850
850
850
850
1062
1062
1062
1062
1062
1062
1062
1062
1062
212
212
272
272
272
340
340
340
425
425
425
425
535
535
535
535
535
535
680
680
680
680
680
680
680
850
850
850
850
850
850
850
850
1062
1062
1062
1062
1062
1062
1062
1062
1062
272
340
340
425
425
425
535
535
535
535
680
680
680
680
680
850
850
850
850
850
850
1062
1062
1062
1062
1062
1062
1062
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
21
558E4305.indd 21
20/11/2009 13:49:37
Protection discrimination
Complementary
technical information
Upstream
In (A)
Downstream
Rating
Discrimination limit (A)
iDPN
6
B curve
10
16
20
25
32
40
Discrimination limit (A)
iDPN
1
C curve
2
3
6
10
16
20
25
32
40
Discrimination limit (A)
iDPN
1
D curve
2
3
6
10
16
20
25
32
40
Discrimination limit (A)
C120N/H
10
B curve
16
20
25
32
40
50
63
80
100
125
Discrimination limit (A)
C120N/H
10
C curve
16
20
25
32
40
50
63
80
100
125
Discrimination limit (A)
C120N/H
10
D curve
16
20
25
32
40
50
63
80
100
125
400
NG125N/H/L
D curve
10
16
20
25
32
40
50
63
80
100
125
125
250
250
250
250
250
400
200
400
400
500
500
500
500
500
630
630
630
630
630
630
800
800
800
800
800
800
3000
1800
1250
1000
1000
1000
1000
T
3000
2000
1600
1250
1250
1250
T
T
3300
2500
2100
1800
1600
T
T
3700
3700
3700
2700
2400
300
150
125
125
500
300
200
250
250
700
500
250
250
250
250
1000
700
400
400
200
400
400
1500
1000
500
500
500
500
500
500
2000
1500
700
630
630
630
630
630
630
2500
2000
800
800
800
800
800
800
800
4500
4500
3000
3000
1800
1250
1000
1000
1000
1000
4500
4500
4500
4500
3000
2000
1600
1250
1250
1250
4500
4500
4500
4500
4500
3300
2500
2100
1800
1600
4500
4500
4500
4500
4500
3700
3700
3700
2700
2400
300
150
120
500
300
200
250
700
500
300
240
240
1000
700
500
400
200
400
1500
1000
700
500
500
500
2000
1500
1000
630
630
630
630
2500
2000
1500
800
800
800
800
800
800
4500
4500
4500
3000
1800
1250
1000
1000
1000
1000
4500
4500
4500
4500
3000
2000
1600
1250
1250
1250
4500
4500
4500
4500
4500
3300
2500
2100
1800
1600
4500
4500
4500
4500
4500
3700
3700
3700
2700
2400
240
300
300
384
384
480
480
480
600
600
600
600
756
756
756
756
756
756
960
960
960
960
960
960
960
1200
1200
1200
1200
1200
1200
1200
1500
1500
1500
1500
1500
1500
1500
1500
300
384
384
480
480
480
600
600
600
600
756
756
756
756
756
756
960
960
960
960
960
960
960
1200
1200
1200
1200
1200
1200
1200
1500
1500
1500
1500
1500
1500
1500
1500
300
384
384
480
480
480
600
600
600
600
756
756
756
756
756
756
960
960
960
960
960
960
1200
1200
1200
1200
1200
1200
1200
1500
1500
1500
1500
1500
1500
1500
1500
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
22
Livre 1.indb 22
04/11/2009 15:55:13
Complementary
technical information
Upstream
In (A)
NG125N/H/L, C120N/H
B curve
10
16
20
Protection discrimination
25
32
40
50
63
80
Downstream
Rating
Discrimination limit (A)
C60N
0.5
T
T
T
T
T
T
T
T
T
B, C curves
0.75
T
T
T
T
T
T
T
T
T
1
550
700
1500
2200
3100
3500
4000
T
T
2
300
450
700
1500
2100
2500
2800
4500
T
3
150
300
300
950
1500
1600
1800
4000
T
4
150
200
600
1200
1300
1400
3400
T
6
150
400
950
1000
1000
2800
5000
10
600
600
750
2500
4000
16
600
2100
3500
20
2500
25
1600
32
40
50
63
Discrimination limit (A)
C60H/L
0.5
10000
10000
10000
10000
10000
10000
10000
10000
10000
B, C, Z curves 0.75
10000
10000
10000
10000
10000
10000
10000
10000
10000
1
550
700
1500
2200
3100
3500
4000
6000
7000
2
300
450
700
1500
2100
2500
2800
4500
6000
3
150
300
300
950
1500
1600
1800
4000
6000
4
150
200
600
1200
1300
1400
3400
6000
6
150
400
950
1000
1000
2800
5000
10
600
600
750
2500
4000
16
600
2100
3500
20
2500
25
1600
32
40
50
63
Discrimination limit (A)
C60N
0.5
T
T
T
T
T
T
T
T
T
D curve
0.75
T
T
T
T
T
T
T
T
T
1
550
700
1500
2200
3100
3500
4000
T
T
2
450
700
1500
2100
2500
2800
4500
T
3
300
950
1500
1600
1800
4000
T
4
1200
1300
1400
3400
T
6
1000
2800
5000
10
4000
16
3500
20
25
32
40
50
63
Discrimination limit (A)
C60H/L
1
550
700
1500
2200
3100
3500
4000
6000
7000
D, K, MA curves 2
450
700
1500
2100
2500
2800
4500
6000
3
300
950
1500
1600
1800
4000
6000
4
1200
1300
1400
3400
6000
6
1000
2800
5000
10
4000
16
3500
20
25
32
40
50
63
The above tables indicate the discrimination limits in the following cases:
- phase-to-neutral short-circuit on a 230 V single-phase distribution network, downstream of a 3 Ph + N or single-phase network.
- short-circuit between two phases on a three-phase distribution network with a nominal voltage of 230 V.
T
400
100
125
T
T
T
T
T
T
T
5500
4500
3500
2500
T
T
T
T
T
T
T
T
5500
4500
3500
2800
2500
10000
10000
10000
8000
7000
6000
6000
5500
4500
3500
2500
10000
10000
10000
10000
10000
8000
6500
6000
5500
4500
3500
2800
2500
T
T
T
T
T
T
T
5500
4500
T
T
T
T
T
T
T
T
5500
4500
3500
10000
8000
7000
6000
6000
5500
4500
10000
10000
10000
8000
6500
6000
5500
4500
3500
No discrimination.
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
23
558E4305.indd 23
20/11/2009 13:50:57
Complementary
technical information
Upstream
In (A)
NG125N/H/L, C120N/H
C curve
10
16
20
Protection discrimination
25
32
40
50
63
80
Downstream
Rating
Discrimination limit (A)
C60N
0.5
T
T
T
T
T
T
T
T
T
B, C curves
0.75
T
T
T
T
T
T
T
T
T
1
800
1000
2000
3000
4500
T
T
T
T
2
400
600
1000
2000
3000
3500
4000
T
T
3
200
400
400
1300
2100
2300
2500
T
T
4
200
300
900
1600
1800
2000
T
T
6
200
500
1300
1400
1500
4000
T
10
300
800
900
1000
3500
T
16
500
650
800
3000
5000
20
400
700
2000
3600
25
500
1000
2200
32
700
1500
40
1300
50
63
Discrimination limit (A)
C60H/L
0.5
10000
10000
10000
10000
10000
10000
10000
10000
10000
B, C, Z curves 0.75
10000
10000
10000
10000
10000
10000
10000
10000
10000
1
800
1000
2000
3000
4500
5500
7000
10000
10000
2
400
600
1000
2000
3000
3500
4000
6000
10000
3
200
400
400
1300
2100
2300
2500
6000
10000
4
200
300
900
1600
1800
2000
5000
8000
6
200
500
1300
1400
1500
4000
6500
10
300
800
900
1000
3500
6000
16
500
650
800
3000
5000
20
400
700
2000
3600
25
500
1000
2200
32
700
1500
40
1300
50
63
Discrimination limit (A)
C60N
0.5
T
T
T
T
T
T
T
T
T
D curve
0.75
T
T
T
T
T
T
T
T
T
1
800
1000
2000
3000
4500
T
T
T
T
2
600
1000
2000
3000
3500
4000
T
T
3
400
1300
2100
2300
2500
T
T
4
900
1600
1800
2000
T
T
6
1300
1400
1500
4000
T
10
900
1000
3500
T
16
800
3000
5000
20
2000
3600
25
2200
32
40
50
63
Discrimination limit (A)
C60H/L
1
800
1000
2000
3000
4500
5500
7000
10000
10000
D, K, MA curves 2
600
1000
2000
3000
3500
4000
8000
10000
3
400
1300
2100
2300
2500
7000
10000
4
900
1600
1800
2000
5000
8000
6
1300
1400
1500
4000
6500
10
900
1000
3500
5500
16
800
3000
5000
20
2000
3600
25
2200
32
40
50
63
The above tables indicate the discrimination limits in the following cases:
- phase-to-neutral short-circuit on a 230 V single-phase distribution network, downstream of a 3 Ph + N or single-phase network.
- short-circuit between two phases on a three-phase distribution network with a nominal voltage of 230 V.
T
400
100
125
T
T
T
T
T
T
T
T
T
5500
3500
2500
1800
1500
T
T
T
T
T
T
T
T
T
T
5000
4000
3600
2500
2100
10000
10000
10000
10000
10000
10000
8500
6500
6000
5500
3500
2500
1800
1500
10000
10000
10000
10000
10000
10000
10000
8000
7000
6000
5000
4000
3600
2500
2100
T
T
T
T
T
T
T
T
T
5500
3500
2500
T
T
T
T
T
T
T
T
T
T
5000
4000
3600
10000
10000
10000
10000
8500
6500
6000
5500
3500
2500
10000
10000
10000
10000
10000
8000
7000
6000
5000
4000
3600
No discrimination.
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
24
558E4305.indd 24
20/11/2009 14:01:23
Complementary
technical information
Upstream
In (A)
NG125N/H/L, C120N/H
D curve
10
16
20
Protection discrimination
25
32
40
50
63
80
Downstream
Rating
Discrimination limit (A)
C60N
0.5
T
T
T
T
T
T
T
T
T
B, C curves
0.75
T
T
T
T
T
T
T
T
T
1
900
1100
2300
3400
5000
6000
T
T
T
2
450
700
1100
2300
3400
4000
4500
6000
T
3
250
450
450
1500
2400
2600
2800
6000
T
4
200
350
1000
1800
2000
2300
6000
T
6
250
600
1500
1600
1700
4500
6000
10
350
900
1000
1200
4000
6000
16
600
750
900
3400
5600
20
500
800
2300
4000
25
600
1200
2500
32
800
1700
40
600
1500
50
63
Discrimination limit (A)
C60H/L
0.5
10000
10000
10000
10000
10000
10000
10000
10000
10000
B, C, Z curves 0.75
10000
10000
10000
10000
10000
10000
10000
10000
10000
1
900
1100
2300
3400
5000
6000
7000
10000
10000
2
450
700
1100
2300
3400
4000
4500
8000
10000
3
250
450
450
1500
2400
2600
2800
7000
8000
4
200
350
1000
1800
2000
2300
6000
6500
6
250
600
1500
1600
1700
4500
6000
10
350
900
1000
1200
4000
6000
16
600
750
900
3400
5600
20
500
800
2300
4000
25
600
1200
2500
32
800
1700
40
600
1500
50
63
Discrimination limit (A)
C60N
0.5
T
T
T
T
T
T
T
T
T
D curve
0.75
T
T
T
T
T
T
T
T
T
1
900
1100
2300
3400
5000
6000
T
T
T
2
700
1100
2300
3400
4000
4500
6000
T
3
450
1500
2400
2600
2800
6000
T
4
1000
1800
2000
2300
6000
T
6
1500
1600
1700
4500
6000
10
1000
1200
4000
6000
16
900
3400
5600
20
2300
4000
25
1200
2500
32
40
50
63
Discrimination limit (A)
C60H/L
1
900
1100
2300
3400
5000
6000
10000
10000
10000
D, K, MA curves 2
700
1100
2300
3400
4000
4500
8000
10000
3
450
1500
2400
2600
2800
7000
8000
4
1000
1800
2000
2300
6000
6500
6
1500
1600
1700
4500
6000
10
1000
1200
4000
6000
16
900
3400
5600
20
2300
4000
25
1200
2500
32
40
50
63
The above tables indicate the discrimination limits in the following cases:
- phase-to-neutral short-circuit on a 230 V single-phase distribution network, downstream of a 3 Ph + N or single-phase network.
- short-circuit between two phases on a three-phase distribution network with a nominal voltage of 230 V.
T
400
100
125
T
T
T
T
T
T
T
T
6000
6000
4000
2800
2200
1700
T
T
T
T
T
T
T
T
T
T
5500
4500
4000
2800
2300
10000
10000
10000
10000
10000
10000
8500
6500
6000
6000
4000
2800
2200
1700
10000
10000
10000
10000
10000
10000
10000
10000
8000
7000
5500
4500
4000
2800
2300
T
T
T
T
T
T
T
T
6000
6000
4000
2800
T
T
T
T
T
T
T
T
T
T
5500
4500
4000
10000
10000
10000
10000
8500
6500
6000
6000
4000
2800
10000
10000
10000
10000
10000
10000
8000
7000
5500
4500
4000
No discrimination.
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
25
Livre 1.indb 25
04/11/2009 15:55:16
Complementary
technical information
Upstream
In (A)
NG125N/H/L, C120N/H
B curve
10
16
20
Protection discrimination
25
32
Downstream
Rating
Discrimination limit (A)
C60N
0.5
T
T
T
T
T
B, C curves
0.75
T
T
T
T
T
1
200
300
450
700
1000
2
100
220
300
450
550
3
60
150
220
350
450
4
100
150
250
400
6
120
200
300
10
200
16
20
25
32
40
50
63
Discrimination limit (A)
C60H/L
0.5
6000
6000
6000
6000
6000
B, C, Z curves 0.75
6000
6000
6000
6000
6000
1
200
300
450
700
1000
2
100
220
300
450
550
3
60
150
220
350
450
4
100
150
250
400
6
120
200
300
10
200
16
20
25
32
40
50
63
Discrimination limit (A)
C60N
0.5
T
T
T
T
T
D curve
0.75
T
T
T
T
T
1
200
300
450
700
1000
2
220
300
450
550
3
220
350
450
4
400
6
10
16
20
25
32
40
50
63
Discrimination limit (A)
C60H/L
1
200
300
450
700
1000
D, K, MA curves 2
220
300
450
550
3
220
350
450
4
400
6
10
16
20
25
32
40
50
63
The above tables indicate the discrimination limits in the following cases:
- short-circuit between two phases on a three-phase 230/400 V distribution network.
40
50
63
80
100
125
T
T
1300
900
700
650
500
300
T
T
1600
1260
1150
1000
700
600
450
T
T
2800
2500
2300
2000
1750
1100
700
T
T
3500
3000
2600
2300
2000
1500
1000
800
700
T
T
5000
4500
4000
3300
3000
2600
2300
1900
1700
T
T
T
T
4500
4000
3500
3300
2900
2500
2200
1550
1100
6000
6000
1300
900
700
650
500
300
6000
6000
1600
1260
1150
1000
700
600
450
6000
6000
2800
2500
2300
2000
1750
1100
700
6000
6000
3500
3000
2600
2300
2000
1500
1000
800
700
6000
6000
5000
4500
4000
3300
3000
2600
2300
1900
1700
6000
6000
6000
6000
4500
4000
3500
3300
2900
2500
2200
1550
1100
T
T
1300
900
700
650
T
T
1600
1260
1150
1000
700
T
T
2800
2500
2300
2000
1750
T
T
3500
3000
2600
2300
2000
1500
1000
T
T
5000
4500
4000
3300
3000
2600
2300
T
T
T
T
4500
4000
3500
3300
2900
2500
2200
1300
900
700
650
1600
1260
1150
1000
700
2800
2500
2300
2000
1750
3500
3000
2600
2300
2000
1500
1000
5000
4500
4000
3300
3000
2600
2300
6000
6000
4500
4000
3500
3300
2900
2500
2200
400
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
26
Livre 1.indb 26
04/11/2009 15:55:17
Complementary
technical information
Upstream
In (A)
NG125N/H/L, C120N/H
C curve
10
16
20
Protection discrimination
25
32
Downstream
Rating
Discrimination limit (A)
C60N
0.5
T
T
T
T
T
B, C curves
0.75
T
T
T
T
T
1
300
450
600
1000
1600
2
150
300
450
600
800
3
80
200
300
450
600
4
160
250
350
500
6
170
300
400
10
210
270
16
270
20
25
32
40
50
63
Discrimination limit (A)
C60H/L
0.5
6000
6000
6000
6000
6000
B, C, Z curves 0.75
6000
6000
6000
6000
6000
1
300
450
600
1000
1600
2
150
300
450
600
800
3
80
200
300
450
600
4
160
250
350
500
6
170
300
400
10
210
270
16
270
20
25
32
40
50
63
Discrimination limit (A)
C60N
0.5
T
T
T
T
T
D curve
0.75
T
T
T
T
T
1
300
450
600
1000
1600
2
300
450
600
800
3
300
450
600
4
350
500
6
400
10
16
20
25
32
40
50
63
Discrimination limit (A)
C60H/L
1
300
450
600
1000
1600
D, K, MA curves 2
300
450
600
800
3
300
450
600
4
350
500
6
400
10
16
20
25
32
40
50
63
The above tables indicate the discrimination limits in the following cases:
- short-circuit between two phases on a three-phase 230/400 V distribution network.
40
50
63
80
100
125
T
T
2000
1300
1000
1000
800
500
400
340
T
T
2500
2000
1600
1600
1200
800
600
500
420
T
T
T
T
5000
4000
2500
1000
1000
800
600
530
T
T
T
T
T
5000
4000
3200
1600
1200
1000
1000
680
T
T
T
T
T
T
T
5000
3600
3000
2500
1600
1000
850
T
T
T
T
T
T
T
T
5500
4000
3200
2500
1600
1300
1200
6000
6000
2000
1300
1000
1000
800
500
400
340
6000
6000
2500
2000
1600
1600
1200
800
600
500
420
6000
6000
6000
6000
5000
4000
2500
1000
1000
800
600
530
6000
6000
6000
6000
6000
5000
4000
3200
1600
1200
1000
1000
680
6000
6000
6000
6000
6000
6000
6000
5000
3600
3000
2500
1600
1000
850
6000
6000
6000
6000
6000
6000
6000
6000
5500
4000
3200
2500
1600
1300
1200
T
T
2000
1300
1000
1000
800
500
T
T
2500
2000
1600
1600
1200
800
600
T
T
T
T
5000
4000
2500
1000
1000
800
T
T
T
T
T
5000
4000
3200
1600
1200
1000
T
T
T
T
T
T
T
5000
3600
3000
2500
1600
T
T
T
T
T
T
T
T
5500
4000
3200
2500
1600
2000
1300
1000
1000
800
500
2500
2000
1600
1600
1200
800
600
6000
6000
5000
4000
2500
1000
1000
800
6000
6000
6000
5000
4000
3200
1600
1200
1000
6000
6000
6000
6000
6000
5000
3600
3000
2500
1600
6000
6000
6000
6000
6000
6000
5500
4000
3200
2500
1600
400
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
27
Livre 1.indb 27
04/11/2009 15:55:18
Complementary
technical information
Upstream
In (A)
NG125N/H/L, C120N/H
D curve
10
16
20
Protection discrimination
25
32
Downstream
Rating
Discrimination limit (A)
C60N
0.5
T
T
T
T
T
B, C curves
0.75
T
T
T
T
T
1
400
550
900
1400
1900
2
200
400
550
900
1200
3
130
250
350
650
900
4
140
270
450
700
6
220
400
600
10
260
500
16
370
20
25
32
40
50
63
Discrimination limit (A)
C60H/L
0.5
6000
6000
6000
6000
6000
B, C, Z curves 0.75
6000
6000
6000
6000
6000
1
400
550
900
1400
1900
2
200
400
550
900
1200
3
130
250
350
650
900
4
140
270
450
700
6
220
400
600
10
260
500
16
370
20
25
32
40
50
63
Discrimination limit (A)
C60N
0.5
T
T
T
T
T
D curve
0.75
T
T
T
T
T
1
400
550
900
1400
1900
2
200
400
550
900
1200
3
250
350
650
900
4
270
450
700
6
400
600
10
500
16
20
25
32
40
50
63
Discrimination limit (A)
C60H/L
1
400
550
900
1400
1900
D, K, MA curves 2
200
400
550
900
1200
3
250
350
650
900
4
270
450
700
6
400
600
10
500
16
20
25
32
40
50
63
The above tables indicate the discrimination limits in the following cases:
- short-circuit between two phases on a three-phase 230/400 V distribution network.
40
50
63
80
100
125
T
T
2400
1600
1300
1100
900
600
500
450
T
T
3000
2100
1900
1700
1300
900
700
600
500
T
T
T
T
T
4000
3000
2000
1400
1100
1000
800
500
T
T
T
T
T
T
4300
3300
2000
1800
1300
1300
1000
T
T
T
T
T
T
T
T
4300
3500
3000
1800
1300
1100
T
T
T
T
T
T
T
T
T
4500
3600
2600
2200
1800
1500
6000
6000
2400
1600
1300
1100
900
600
500
450
6000
6000
3000
2100
1900
1700
1300
900
700
600
500
6000
6000
6000
6000
6000
4000
3000
2000
1400
1100
1000
800
500
6000
6000
6000
6000
6000
6000
4300
3300
2000
1800
1300
1300
1000
6000
6000
6000
6000
6000
6000
6000
6000
4300
3500
3000
1800
1300
1100
6000
6000
6000
6000
6000
6000
6000
6000
6000
4500
3600
2600
2200
1800
1500
T
T
2400
1600
1300
1100
900
600
500
T
T
3000
2100
1900
1700
1300
900
700
T
T
T
T
4000
3000
2000
1400
1100
1000
T
T
T
T
T
4300
3300
2000
1800
1300
1300
T
T
T
T
T
T
T
4300
3500
3000
1800
1300
T
T
T
T
T
T
T
T
4500
3600
2600
2200
1800
2400
1600
1300
1100
900
600
500
3000
2100
1900
1700
1300
900
700
6000
6000
6000
4000
3000
2000
1400
1100
1000
6000
6000
6000
6000
4300
3300
2000
1800
1300
1300
6000
6000
6000
6000
6000
6000
4300
3500
3000
1800
1300
6000
6000
6000
6000
6000
6000
6000
4500
3600
2600
2200
1800
400
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
28
Livre 1.indb 28
04/11/2009 15:55:19
Protection discrimination
Complementary
technical information
Upstream
In (A)
Downstream
Rating
Discrimination limit (A)
NG125
10
B curve
16
20
25
32
40
50
63
80
100
Discrimination limit (A)
NG125
10
C curve
16
20
25
32
40
50
63
Discrimination limit (A)
NG125
10
D curve
16
20
25
32
40
50
63
Upstream
In (A)
Downstream
Rating
Discrimination limit (A)
NG125
10
B curve
16
20
25
32
40
50
63
80
100
Discrimination limit (A)
NG125
10
C curve
16
20
25
32
40
50
63
80
100
Discrimination limit (A)
NG125
10
D curve
16
20
25
32
40
50
63
80
100
T
NG125N/H/L
B curve
10
16
20
25
32
40
50
63
80
100
125
40
80
100
100
128
128
128
160
160
160
160
200
200
200
200
200
252
252
252
252
252
252
320
320
320
320
320
320
320
400
400
400
400
400
400
400
400
500
500
500
500
500
500
500
500
500
128
160
200
200
252
252
252
320
320
320
320
400
400
400
400
400
500
500
500
500
500
500
200
252
320
320
400
400
400
500
500
500
500
64
NG125N/H/L
C curve
10
16
20
25
32
40
50
63
80
100
125
128
160
200
200
256
256
256
320
320
320
320
400
400
400
400
400
504
504
504
504
504
504
640
640
640
640
640
640
640
800
800
800
800
800
800
800
1000
1000
1000
1000
1000
1000
1000
1000
128
160
200
200
256
256
256
320
320
320
320
400
400
400
400
400
504
504
504
504
504
504
640
640
640
640
640
640
640
800
800
800
800
800
800
800
800
1000
1000
1000
1000
1000
1000
1000
1000
1000
256
320
320
400
400
504
504
504
640
640
640
640
800
800
800
800
800
1000
1000
1000
1000
1000
1000
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
29
Livre 1.indb 29
04/11/2009 15:55:20
Protection discrimination
Complementary
technical information
Upstream
In (A)
Downstream
Rating
Discrimination limit (A)
NG125
10
B curve
16
20
25
32
40
50
63
80
100
Discrimination limit (A)
NG125
10
C curve
16
20
25
32
40
50
63
80
100
Discrimination limit (A)
NG125
10
D curve
16
20
25
32
40
50
63
80
100
T
NG125N/H/L
D curve
10
16
20
25
32
40
50
63
80
100
125
192
240
300
300
384
384
384
480
480
480
480
600
600
600
600
600
756
756
756
756
756
756
960
960
960
960
960
960
960
1200
1200
1200
1200
1200
1200
1200
1200
1500
1500
1500
1500
1500
1500
1500
1500
1500
192
240
300
300
384
384
384
480
480
480
480
600
600
600
600
600
756
756
756
756
756
756
960
960
960
960
960
960
960
1200
1200
1200
1200
1200
1200
1200
1200
1500
1500
1500
1500
1500
1500
1500
1500
1500
192
240
300
300
384
384
384
480
480
480
480
600
600
600
600
600
756
756
756
756
756
756
960
960
960
960
960
960
960
1200
1200
1200
1200
1200
1200
1200
1200
1500
1500
1500
1500
1500
1500
1500
1500
1500
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
30
Livre 1.indb 30
04/11/2009 15:55:21
Protection discrimination
Complementary
technical information
Upstream
Downstream In (A)
Discrimination limit (A)
C60N/H
0.5/0.75
D curve
1
C60L
1.6
K curve
2
3
4
6
10
16
20
25
32
40
Upstream
Downstream In (A)
Discrimination limit (A)
iDPN
6/10
B curve
16
20
25
32
40
Discrimination limit (A)
iDPN/
1
iDPN Vigi
2
C curve
3
4
5
6
10
16
20
25
32
400
C60L
K curve
2
10
16
20
25
32
40
50
63
24
24
36
36
48
48
48
48
72
72
72
72
72
120
120
120
120
120
120
192
192
192
192
192
192
240
240
240
240
240
240
240
300
300
300
300
300
300
300
300
384
384
384
384
384
384
384
384
384
480
480
480
480
480
480
480
480
480
480
600
600
600
600
600
600
600
600
600
600
600
756
756
756
756
756
756
756
756
756
756
756
756
10
16
20
25
32
40
50
63
192
240
300
384
384
480
480
480
480
600
600
600
600
756
756
756
756
756
192
192
192
192
192
192
240
240
240
240
240
240
240
300
300
300
300
300
300
300
384
384
384
384
384
384
384
384
480
480
480
480
480
480
480
480
480
600
600
600
600
600
600
600
600
600
600
756
756
756
756
756
756
756
756
756
756
756
C60
Curves D or K
2
24
36
48
48
72
72
72
72
120
120
120
120
120
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
31
Livre 1.indb 31
04/11/2009 15:55:21
Protection discrimination
Complementary
technical information
Upstream
C60L
B curve
2
3
Downstream In (A)
Discrimination limit (A)
C60L
1
8
Z curve
1.6
2
3
4
6
8
10
16
20
25
32
40
50
Upstream
C60L
C curve
Downstream In (A)
2
Discrimination limit (A)
C60L
1
15
Z curve
1.6
2
3
4
6
8
10
16
20
25
32
40
50
Upstream
C60L
K curve
Downstream In (A)
2
Discrimination limit (A)
C60L
1
24
Z curve
1.6
2
3
4
6
8
10
16
20
25
32
40
50
Upstream
C60L
Z curve
Downstream In (A)
1.6
Discrimination limit (A)
C60L
1
4
Z curve
1.6
2
3
4
6
8
10
16
20
25
32
40/5
400
10
16
20
25
32
40
50
63
12
12
16
16
16
24
24
24
24
24
40
40
40
40
40
40
64
64
64
64
64
64
64
64
80
80
80
80
80
80
80
80
100
100
100
100
100
100
100
100
100
128
128
128
128
128
128
128
128
128
128
160
160
160
160
160
160
160
160
160
160
160
200
200
200
200
200
200
200
200
200
200
200
200
240
240
240
240
240
240
240
240
240
240
240
240
240
10
16
20
25
32
40
50
63
23
23
30
30
30
45
45
45
45
45
75
75
75
75
75
75
120
120
120
120
120
120
120
120
150
150
150
150
150
150
150
150
188
188
188
188
188
188
188
188
188
240
240
240
240
240
240
240
240
240
240
300
300
300
300
300
300
300
300
300
300
300
375
375
375
375
375
375
375
375
375
375
375
375
450
450
450
450
450
450
450
450
450
450
450
450
450
10
16
20
25
32
40
50
63
36
36
48
48
48
72
72
72
72
72
120
120
120
120
120
120
192
192
192
192
192
192
192
192
240
240
240
240
240
240
240
240
300
300
300
300
300
300
300
300
300
384
384
384
384
384
384
384
384
384
384
480
480
480
480
480
480
480
480
480
480
480
600
600
600
600
600
600
600
600
600
600
600
600
720
720
720
720
720
720
720
720
720
720
720
720
720
10
16
20
25
32
40
50
63
8.6
8.6
9
9
12
12
18
18
18
18
18
24
24
24
24
24
24
30
30
30
30
30
30
30
48
48
48
48
48
48
48
60
60
60
60
60
60
60
60
75
75
75
75
75
75
75
75
75
96
96
96
96
96
96
96
96
96
96
120
120
120
120
120
120
120
120
120
120
120
150
150
150
150
150
150
150
150
150
150
150
150
189
189
189
189
189
189
189
189
189
189
189
189
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
32
Livre 1.indb 32
04/11/2009 15:55:22
Protection discrimination
Complementary
technical information
Upstream
Downstream
Rating (A)
Discrimination limit (kA)
iDPN
y 10
B, C curves
16
20
25
32
40
iDPNN
y 10
C, D curves
16
20
25
32
40
C60N/H
y 10
B, C, D curves
16
20
25
32
40
50
63
C60L
y 10
B-C-D-K-Z
16
curves
20
25
32
40
50
63
C120N/H
10 (H)
B, C, D curves
16 (H)
20 (H)
25 (H)
32 (H)
40 (H)
50 (H)
63
80
100
125
NG125N/H/L
10
B, C, D curves
16
20
25
32
40
50
63
80
100 (N)
125 (N)
NG160E/N/H
NSC100N
16
25
32
40
50
63
80
100
125
160
16
25
32
40
50
63
80
100
5
3
5
3
3
5
3
3
3
T
T
T
T
4
5
3
3
5
3
3
3
T
T
T
T
4
5
3
3
5
3
3
3
T
T
T
6
4
5
3
5
3
3
5
3
3
3
T
T
T
6
4
5
3
5
3
3
5
3
3
3
10
10
10
6
4
5
3
5
3
3
5
3
3
3
10
10
10
6
4
T
T
T
T
4
4
T
T
T
6
4
4
T
T
T
6
4
4
T
T
T
T
T
T
T
T
T
T
7
7
T
T
T
T
7
7
5
5
3
5
3
3
5
3
3
3
10
10
10
6
4
15
15
15
6
4
4
T
T
T
T
7
7
5
5
3
5
3
3
5
3
3
3
10
10
10
6
4
15
15
15
6
4
4
T
T
T
T
7
7
5
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
1
1
1
1
1
1
1
T
T
T
T
T
T
T
T
T
T
T
8
T
T
T
T
T
8
8
6
T
T
T
T
T
8
8
6
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
5
3
5
3
T
T
T
T
T
T
T
T
T
T
T
8
T
T
T
T
T
8
8
6
T
T
T
T
T
8
8
6
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
T
T
T
T
T
T
T
T
T
T
7
7
T
T
T
T
7
7
5
T
T
T
T
4
4
T
T
T
6
4
4
T
T
T
6
4
4
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
1
1
1
1
1
1
1
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
1
1
1
1
1
1
1
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
1
1
1
1
1
1
1
Note: respect the basic rules of discrimination for overload and short-circuit, see page6, or check curves with Curve Direct software. Particularly for D curves
downstream.
33
Livre 1.indb 33
04/11/2009 15:55:25
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Downstream
Rating (A)
Discrimination limit (kA)
iDPN
y 10
B,C curves
16
20
25
32
40
iDPNN
y 10
C,D curves
16
20
25
32
40
C60N/H
y 10
B-C-D Curves
16
20
C60L
25
B-C-D-K-Z curves 32
40
50
63
C120N/H
10 (H)
B-C-D curves
16 (H)
20 (H)
25 (H)
32 (H)
40 (H)
50 (H)
63
80
100
125
NG125N/H/L
10
B-C-D curves
16
20
25
32
40
50
63
80
100 (N)
125 (N)
NG160E/N/H
16
NSC100N
25
32
40
50
63
80
100
125
160
Compact
NSX100B/F/N/H/S/L
TM-D
Compact
NSX160B/F/N/H/S/L
TM-D
Compact
NSX250B/F/N/H/S/L
TM-D
16
25
32
40
50
63
80
100
80
100
125
160
160
200
250
0.19
0.3
0.3
0.4
0.4
0.4
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.19
0.3
0.3
0.4
0.4
0.4
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.19
0.3
0.3
0.4
0.4
0.4
0.9
0.5
0.5
0.5
0.9
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.9
0.5
0.5
0.5
0.5
0.5
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
1.3
1
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.63
1.3
1
0.63
0.63
0.63
0.63
0.63
0.19
0.3
0.3
0.4
0.4
0.4
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
3
2
1.5
1.5
1
1
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
3
2
1.5
1.5
1
1
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2.4
2.4
2.4
2.4
2.4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2.4
2.4
2.4
2.4
2.4
2.4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2.4
2.4
2.4
2.4
2.4
2.4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
0.19
0.3
0.3
0.4
0.4
0.4
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
T
T
T
2.4
2.4
2.4
2.4
2.4
T
T
T
2.4
2.4
2.4
2.4
2.4
2.4
T
T
T
2.4
2.4
2.4
2.4
2.4
2.4
T
T
T
T
T
T
T
T
T
T
0.4
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.63
0.63
0.63
0.63
0.63
0.8
0.8
0.8
0.8
0.8
0.8
0.63
0.63
0.63
0.63
0.63
0.8
0.8
0.8
0.8
0.8
0.8
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
0.63
0.63
0.63
0.63
0.63
0.63
0.63
No discrimination.
Note: respect the basic rules of discrimination for overload and short-circuit, see page6, or check curves with Curve Direct software. Particularly for D curves
downstream.
34
Livre 1.indb 34
04/11/2009 15:55:27
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Downstream Rating (A)
Setting
Discrimination limit (kA)
iDPN
y 10
B,C curves
16
20
25
32
40
iDPNN
y 10
C,D curves
16
20
25
32
40
C60N/H
y 10
B-C-D curves 16
20
C60L
25
B-C-D-K-Z
32
curves
40
50
63
C120N/H
10 (H)
B-C-D curves 16 (H)
20 (H)
25 (H)
32 (H)
40 (H)
50 (H)
63
80
100
125
NG125N/H/L
10
B-C-D curves 16
20
25
32
40
50
63
80
100 (N)
125 (N)
NG160E/N/H 16
NSC100N
25
32
40
50
63
80
100
125
160
Compact
NSX100B/F/N/H/S/L
Micrologic
40
16
Compact
NSX160B/F/N/H/S/L
Micrologic
25
32
40
100
40
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
63
80
100
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
6
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
6
6
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
0.6
0.6
0.6
0.6
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
0.6
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
160
80
Compact
NSX250B/F/N/H/S/L
Micrologic
100
125
160
250
160
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2.4
2.4
2.4
2.4
2.4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2.4
2.4
2.4
2.4
2.4
2.4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2.4
2.4
2.4
2.4
2.4
2.4
2.4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2.4
2.4
2.4
2.4
T
T
T
2.4
2.4
2.4
2.4
2.4
T
T
T
2.4
2.4
2.4
2.4
2.4
2.4
T
T
T
2.4
2.4
2.4
2.4
2.4
2.4
2.4
T
T
T
T
T
T
T
T
T
T
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2.4
2.4
2.4
2.4
200
250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
No discrimination.
Note: respect the basic rules of discrimination for overload and short-circuit, see page6, or check curves with Curve Direct software. Particularly for D curves
downstream.
35
Livre 1.indb 35
04/11/2009 15:55:28
Protection discrimination
Complementary
technical information
Upstream
Compact
NSX100B/F/N/H/S/L
TM-D
Trip unit
Downstream
Rating (A) 16
Discrimination limit (kA)
16
Compact NSX100
B/F
25
TM-D
32
40
50
63
80
100
16
Compact NSX100
N/H/S/L
25
TM-D
32
40
50
63
80
100
y 63
Compact NSX160
B/F/N/H/S/L
80
TM-D
100
160
y 100
Compact NSX250
B/F/N/H/S/L
125
TM-D
160
200
40
Compact NSX100
B/F/N/H/S/L Micrologic 100
40
Compact NSX160
B/F/N/H/S/L
100
Micrologic
160
y 100
Compact NSX250
B/F/N/H/S/L
160
Micrologic
250
Upstream
25
32
Compact
NSX160B/F/N/H/S/L
TM-D
40
50
63
80
100
80
100
0.5
0.5
0.5
0.5
0.5
0.5
0.63
0.63
0.63
0.63
0.63
0.8
0.8
0.8
0.8
0.8
0.8
0.63
0.63
0.63
0.63
0.63
0.8
0.8
0.8
0.8
0.8
0.8
0.5
0.5
0.5
0.5
0.5
0.63
0.63
0.63
0.63
0.63
0.8
0.8
0.8
0.8
0.8
0.8
0.63
0.63
0.63
0.63
0.63
0.8
0.8
0.8
0.8
0.8
0.8
0.5
Downstream
Rating (A) 40
Setting
16
Discrimination limit (kA)
16
Compact NSX100
B/F
25
TM-D
32
40
50
63
80
100
16
Compact NSX100
N/H/S/L
25
TM-D
32
40
50
63
80
100
y 63
Compact NSX160
B/F/N/H/S/L
80
TM-D
100
160
y 100
Compact NSX250
B/F/N/H/S/L
125
TM-D
160
200
40
Compact NSX100
B/F/N/H/S/L Micrologic 100
40
Compact NSX160
B/F/N/H/S/L
100
Micrologic
160
y 100
Compact NSX250
B/F/N/H/S/L
160
Micrologic
250
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
0.5
0.63
0.8
0.63
0.8
1.25
0.5
0.63
0.8
0.63
0.8
1.25
Compact
NSX100B/F/N/H/S/L
Micrologic
Trip unit
125
25
32
Compact
NSX250B/F/N/H/S/L
TM-D
160
160
200
250
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
36
4
4
4
1.25
2
2
T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
36
5
5
5
5
2.5
2.5
2.5
1.25
1.25
1.25
1.25
2
2
2
2
1.25
1.25
1.25
1.25
1.25
Compact
NSX160B/F/N/H/S/L
Micrologic
40
100
40
63
80
100
160
80
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
Compact
NSX250B/F/N/H/S/L
Micrologic
100
125
160
250
160
200
250
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
36
3
3
3
T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
36
3
3
3
3
3
T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
36
3
3
3
3
3
3
3
36
36
3
3
36
36
3
3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
36
36
3
3
3
3
3
No discrimination.
Note: respect the basic rules of discrimination for overload and short-circuit, see page6, or check curves with Curve Direct software. Particularly for D curves
downstream.
36
Livre 1.indb 36
04/11/2009 15:55:29
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Compact NSX400F/N/H/S/L
Micrologic
Downstream
400
160
Rating (A)
Setting
Discrimination limit (kA)
iDPN
iDPNN
C60N/H/L
C120N/H
y 80
100
125
NG125N/H/L
y 80
100
125
NG160E/N/H
y 80
NSC100N
100
125
160
Compact NSX100 y 80
B/F/N/H/S/L TM-D 100
Compact NSX160 y 100
B/F/N/H/S/L
125
TM-D
160
Compact NSX250 y 100
B/F/N/H/S/L
125
TM-D
160
200
250
Compact NSX100 40
B/F/N/H/S/L
100
Micrologic
Compact NSX160 40
B/F/N/H/S/L
100
Micrologic
160
Compact NSX250 y 100
B/F/N/H/S/L
160
Micrologic
250
Compact NSX400 160
F/N/H/S/L
200
Micrologic
250
320
400
Compact NSX630F/N/H/S/L
Micrologic
200
250
320
400
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
4.8
4.8
4.8
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
4.8
4.8
4.8
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
4.8
4.8
4.8
4.8
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
4.8
4.8
4.8
4.8
4.8
T
T
T
T
T
T
4.8
4.8
T
T
T
4.8
4.8
T
T
T
4.8
4.8
T
T
T
4.8
4.8
4.8
630
250
320
400
500
630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
6.9
6.9
6.9
T
T
T
T
T
T
6.9
6.9
6.9
T
T
T
T
T
T
6.9
6.9
6.9
6.9
T
T
T
T
T
T
6.9
6.9
6.9
6.9
6.9
No discrimination.
Note: respect the basic rules of discrimination for overload and short-circuit, see page6, or check curves with Curve Direct software. Particularly for D curves
downstream.
37
Livre 1.indb 37
04/11/2009 15:55:29
Protection discrimination
Complementary
technical information
Upstream
Compact NS630b/800/1000/1250/1600N/H
Trip Unit
Micrologic 2.0
Rating (A)
Downstream
Setting Ir
Discrimination limit (kA)
iDPN, iDPNN
C60
C120N/H
NG125N/H
NG125L
NG160E/N/H
NSC100N
Compact NSX100
B/F/N/H/S/L TM-D
Compact NSX160
B/F/N/H/S/L TM-D
Compact NSX250 y 125
B/F/N/H/S/L
160
TM-D
200
250
Compact NSX100 40
B/F/N/H/S/L
100
Micrologic
Compact NSX160 40
B/F/N/H/S/L
100
Micrologic
160
Compact NSX250 y 100
B/F/N/H/S/L
160
Micrologic
250
Compact NSX400 160
F/N/H
200
Micrologic
250
320
400
Compact NSX400 160
S/L
200
Micrologic
250
320
400
Compact NSX630 250
F/N
320
Micrologic
400
500
630
Compact NSX630 250
H/S/L
320
Micrologic
400
500
630
630
250
400
630
800
800
400
630
800
800
400
630
800
800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
90
90
90
90
90
T
T
T
T
T
T
T
T
T
T
T
T
T
T
90
90
90
90
90
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
90
90
90
90
90
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
90
90
90
90
90
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
T
90
90
90
90
90
T
T
T
T
65
65
65
65
T
T
T
T
T
T
T
T
T
T
T
90
90
90
90
90
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
T
90
90
90
90
90
T
T
T
65
65
65
T
T
T
T
T
T
T
T
T
T
T
90
90
90
90
90
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
90
90
90
T
T
T
T
T
T
T
T
T
T
T
90
90
90
90
90
T
T
T
T
T
T
T
T
T
90
T
T
T
T
T
T
T
T
T
T
T
90
90
90
90
90
T
T
T
65
65
65
65
T
T
T
T
T
T
T
T
T
T
T
90
90
90
90
90
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
65
65
65
T
T
T
T
T
T
T
T
T
T
T
90
90
90
90
90
T
T
T
T
T
65
65
65
65
65
65
65
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
T
90
90
90
90
90
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
T
90
90
90
90
90
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
T
90
90
90
90
90
T
T
T
T
T
65
65
65
65
65
T
T
T
T
T
T
T
T
90
90
90
90
T
65
T
T
65
T
T
90
90
90
90
T
65
No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
38
558E4320.indd 38
20/11/2009 14:03:18
Protection discrimination
Complementary
technical information
Upstream
Trip Unit
Rating (A)
Downstream
Setting Ir
Discrimination limit (kA)
Compact NS630b 250
N/H
320
Micrologic
400
500
630
Compact NS800 320
N/H
400
Micrologic
500
630
800
Compact NS1000 400
N/H
500
Micrologic
630
800
1000
Compact NS1250 500
N/H
630
Micrologic
800
1000
1250
Compact NS1600 630
N/H
800
Micrologic
960
1250
1600
Compact NS630b 250
L/LB
320
Micrologic
400
500
630
Compact NS800 320
L/LB
400
Micrologic
500
630
800
Compact NS1000 400
L
500
Micrologic
630
800
1000
4
Compact NS630b/800/1000/1250/1600N/H
Micrologic 2.0
Micrologic 5.0 - 6.0 - 7.0
Inst 15 In
630
400
4
800
800
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
10
10
10
10
10
10
10
10
10
6.3
8
8
10
10
10
10
10
12.5
12.5
12.5
10
12.5
12.5
16
16
16
10
10
10
10
10
10
10
10
10
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
630
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
6.3
8
8
10
10
10
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
9.4
9.4
800
800
9.4
9.4
9.4
12
12
12
12
9.4
9.4
12
12
12
15
15
15
15
15
15
15
15
15
9.4
12
12
15
15
15
12
15
15
18
18
18
15
18
18
18
18
18
15
15
15
15
15
15
15
15
15
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
630
9.4
9.4
9.4
12
12
12
12
9.4
9.4
12
12
12
9.4
12
12
15
15
15
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
800
800
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
630
18
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
18
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
39
Livre 1.indb 39
04/11/2009 15:55:33
Protection discrimination
Complementary
technical information
Upstream
Compact NS1600b/2000/2500/3200N
Trip Unit
Micrologic 2.0
Downstream
Rating (A)
Discrimination limit (kA)
iDPN, iDPNN
C60N/H/L
C120N/H
NG125N/H
NG125L
NG160E/N/H
NSC100N
Compact NSX
NSX100
B/F/N/H/S/L
NSX160
TM-D
NSX250
Compact NSX
NSX100
B/F/N/H/S/L
NSX160
Micrologic
NSX250
Compact NSX
NSX400
F/N/H/S/L
NSX630
Compact NS
NS630b
N
NS800
NS1000
NS1250
NS1600
Compact NS
NS630b
H
NS800
NS1000
NS1250
NS1600
Compact NS
NS1600b
N/H
NS2000
NS2500
NS3200
Compact NS
NS630bL/LB
L/LB
NS800L/LB
NS1000L
1600
2000
2500
3200
1600
2000
2500
3200
1600
2000
2500
3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
16
16
16
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
20
20
20
20
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
30
30
30
30
30
30
30
30
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
48
48
48
48
48
48
48
48
48
48
48
48
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
24
24
24
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
20
20
20
20
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
32
32
32
32
32
32
32
32
32
32
32
32
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
24
24
24
16
16
16
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
25
25
25
25
25
25
25
25
25
25
25
60
60
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
40
Livre 1.indb 40
04/11/2009 15:55:34
Protection discrimination
Complementary
technical information
Upstream
Compact NS1600b/2000/2500/3200H
Trip Unit
Micrologic 2.0
Downstream
Rating (A)
Discrimination limit (kA)
iDPN, iDPNN
C60N/H/L
C120N/H
NG125N/H
NG125L
NG160E/N/H
NSC100N
Compact NSX
NSX100
B/F
NSX160
TM-D
NSX250
Compact NSX
NSX100
B/F
NSX160
Micrologic
NSX250
Compact NSX
NSX400
F
NSX630
Compact NSX
NSX100
N/H/S/L
NSX160
TM-D
NSX250
Compact NSX
NSX100
N/H/S/L
NSX160
Micrologic
NSX250
Compact NSX
NSX400
N/H/S/L
NSX630
Compact NS
NS630b
N
NS800
NS1000
NS1250
NS1600
Compact NS
NS630b
H
NS800
NS1000
NS1250
NS1600
Compact NS
NS1600b
N/H
NS2000
NS2500
NS3200
Compact NS
NS630bL/LB
L/LB
NS800L/LB
NS1000L
1600
2000
2500
3200
1600
2000
2500
3200
1600
2000
2500
3200
T
T
T
T
40
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
16
16
16
T
T
T
T
40
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
20
20
20
20
T
T
T
T
40
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
30
30
30
30
30
30
30
30
T
T
T
T
40
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
T
T
T
T
40
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
40
40
24
24
24
T
T
T
T
40
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
T
T
T
T
40
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
40
20
20
20
20
T
T
T
T
40
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
32
32
32
32
32
32
32
32
32
32
32
32
T
T
T
T
40
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
24
24
24
16
16
16
T
T
T
T
40
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
25
25
25
25
25
25
25
25
25
25
25
40
40
40
40
40
40
40
T
T
T
T
40
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
T
T
T
T
40
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
41
Livre 1.indb 41
04/11/2009 15:55:35
Protection discrimination
Complementary
technical information
Upstream
Trip Unit
Rating (A)
Downstream
Setting Ir
Discrimination limit (kA)
iDPN, iDPNN
C60
C120N/H
NG125N/H
NG125L
NG160
NSC100N
Compact NSX100
B/F/N/H/S/L TM-D
Compact NSX160
B/F TM-D
Compact NSX160
N/H/S/L TM-D
Compact NSX250 y 125
B/F/N/H/S/L
160
TM-D
200
250
Compact NSX100 40
B/F/N/H/S/L
100
Micrologic
Compact NSX160 40
B/F
100
Micrologic
160
Compact NSX160 40
N/H/S/L
100
Micrologic
160
Compact NSX250 y 100
B/F/N/H/S/L
160
Micrologic
250
Compact NSX400 160
F/N/H/S/L
200
Micrologic
250
320
400
Compact NSX630 250
F/N/H/S/L
320
Micrologic
400
500
630
Compact NS630b/800/1000L
Compact NS630b/800LB
Micrologic 2.0
630
250
400
630
800
800
1000
1000
630
250
400
630
800
800
1000
1000
630
250
400
630
800
800
1000
1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
36
36
36
36
20
20
20
20
20
20
T
T
20
20
20
20
T
T
T
T
T
T
T
T
T
T
T
T
T
T
20
20
20
20
20
20
T
T
20
20
20
20
T
T
T
T
T
T
T
T
T
T
T
T
T
T
20
20
20
20
20
20
T
T
20
20
20
20
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
36
36
36
20
20
20
6.3
6.3
6.3
6.3
T
T
T
36
36
36
20
20
20
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
T
T
T
T
T
T
T
T
T
10
10
10
10
10
8
8
8
8
T
T
T
T
T
T
T
T
T
15
15
15
15
15
10
10
10
10
10
T
T
T
36
36
36
20
T
T
T
36
36
36
20
20
20
6.3
6.3
6.3
T
T
T
36
36
36
20
20
20
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
T
T
T
T
T
T
T
T
T
10
10
10
10
10
8
8
8
8
T
T
T
T
T
T
T
T
T
15
15
15
15
15
10
10
10
10
10
T
T
T
T
T
36
36
36
20
20
20
6.3
6.3
6.3
T
T
T
36
36
36
20
20
20
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
T
T
T
T
T
T
T
T
T
10
10
10
10
10
8
8
8
8
T
T
T
T
T
T
T
T
T
15
15
15
15
15
10
10
10
10
10
T
T
T
T
T
36
36
36
20
6.3
6.3
T
T
6.3
6.3
T
T
36
36
36
20
6.3
6.3
No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
42
Livre 1.indb 42
04/11/2009 15:55:35
Protection discrimination
Complementary
technical information
Upstream
Trip Unit
Compact NS630b/800/1000L
Compact NS630b/800LB
Micrologic 2.0
800
800
1000
1000
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
10
10
10
10
10
10
10
10
10
6.3
8
8
10
10
10
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
10
10
10
10
10
10
10
10
10
6.3
8
8
400
630
6.3
6.3
10
10
10
630
250
800
800
1000
1000
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
10
10
10
10
10
10
10
10
10
6.3
8
8
10
10
10
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
10
10
10
10
10
10
10
10
10
6.3
8
8
400
630
6.3
6.3
800
800
1000
1000
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
10
10
10
10
10
10
10
10
10
6.3
8
8
10
10
10
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
10
10
10
10
10
10
10
10
10
6.3
8
8
400
630
6.3
6.3
10
10
10
10
10
10
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
43
Livre 1.indb 43
04/11/2009 15:55:36
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Downstream
630
250
400
630
800
800
400
630
800
800
400
630
800
800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Rating (A)
Setting Ir
Discrimination limit (kA)
iDPN, iDPNN
C60
C120N/H
NG125N/H
NG125L
NG160E/N/H
NSC100N
Compact NSX100
B/F/N/H/S/L TM-D
Compact NSX160
B/F/N/H/S/L TM-D
Compact NSX250 y 125
B/F/N/H/S/L
160
TM-D
200
250
Compact NSX100 40
B/F/N/H/S/L
100
Micrologic
Compact NSX160 40
B/F/N/H/S/L
100
Micrologic
160
Compact NSX250 y 100
B/F/N/H/S/L
160
Micrologic
250
Compact NSX400 160
F/N/H/S/L
200
Micrologic
250
320
400
Compact NSX630 250
F/N/H/S/L
320
Micrologic
400
500
630
T
T
T
T
T
T
T
T
T
T
T
T
T
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
44
Livre 1.indb 44
04/11/2009 15:55:37
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Masterpact NT06/08/12/16 H1
Micrologic 2.0
Downstream
630
400
Rating (A)
Setting Ir
Discrimination limit (kA)
Compact NS630b 250
N/H
320
Micrologic
400
500
630
Compact NS800 320
N/H
400
Micrologic
500
630
800
Compact NS1000 400
N/H
500
Micrologic
630
800
1000
Compact NS1250 500
N/H
630
Micrologic
800
1000
1250
Compact NS1600 630
N/H
800
Micrologic
960
1250
1600
Compact NS630b 250
L/LB
320
Micrologic
400
500
630
Compact NS800 320
L/LB
400
Micrologic
500
630
800
Compact NS1000 400
L
500
Micrologic
630
800
1000
800
800
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
10
10
10
10
10
10
10
10
10
6.3
8
8
10
10
10
10
10
12.5
12.5
12.5
10
12.5
12.5
16
16
16
T
T
T
T
T
10
10
10
10
T
T
T
T
T
T
T
T
T
12.5
12.5
12.5
12.5
12.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
630
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
6.3
8
8
10
10
10
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
9.4
800
800
9.4
9.4
9.4
12
12
12
12
9.4
9.4
12
12
12
15
15
15
15
15
15
15
15
15
9.4
12
12
15
15
15
12
15
15
18.7
18.7
18.7
15
18.7
18.7
24
24
24
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
630
T
T
T
T
T
T
T
9.4
9.4
T
T
T
9.4
12
12
T
T
T
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
800
800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
45
Livre 1.indb 45
04/11/2009 15:55:39
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Downstream Rating (A)
Setting Ir
Discrimination limit (kA)
Masterpact
250
NT06 H1/H2
320
Micrologic
400
500
630
Masterpact
320
NT08 H1/H2
400
Micrologic
500
630
800
Masterpact
400
NT10 H1/H2
500
Micrologic
630
800
1000
Masterpact
500
NT12 H1/H2
630
Micrologic
800
1000
1250
Masterpact
630
NT16 H1/H2
800
Micrologic
960
1250
1600
Masterpact
250
NT06 L1
320
Micrologic
400
500
630
Masterpact
320
NT08 L1
400
Micrologic
500
630
800
Masterpact
400
NT10 L1
500
Micrologic
630
800
1000
Masterpact NT06/08/12/16 H1
Micrologic 2.0
630
400
4
800
800
1000
1000
1250
1250
1600
1600
630
400
6.3
6.3
6.3
8
8
8
8
8
8
8
6.3
8
8
10
10
10
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
10
10
12.5
12.5
12.5
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
9.4
6.3
6.3
10
10
10
10
10
10
10
10
10
10
12.5
12.5
16
16
16
T
T
T
T
T
10
10
10
10
T
T
T
T
T
T
T
T
T
T
12.5
12.5
12.5
12.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
630
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
6.3
8
8
10
10
10
800
800
1000
1000
1250
1250
1600
1600
630
400
9.4
9.4
9.4
12
12
12
12
12
12
12
9.4
12
12
15
15
15
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
12
15
15
18.7
18.7
18.7
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
9.4
9.4
15
15
15
15
15
15
15
15
15
15
18.7
18.7
24
24
24
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
630
T
T
T
T
T
T
T
9.4
9.4
T
T
T
9.4
12
12
T
T
T
800
800
1000
1000
1250
1250
1600
1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
46
Livre 1.indb 46
04/11/2009 15:55:40
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Downstream Rating (A)
Setting Ir
Discrimination limit (kA)
Compact
250
NS630bN/H
320
Micrologic
400
500
630
Compact
320
NS800N/H
400
Micrologic
500
630
800
Compact
400
NS1000N/H
500
Micrologic
630
800
1000
Compact
500
NS1250N/H
630
Micrologic
800
1000
1250
Compact
630
NS1600N/H
800
Micrologic
960
1250
1600
Compact
250
NS630bL/LB 320
Micrologic
400
500
630
Compact
320
NS800L/LB
400
Micrologic
500
630
800
Compact
400
NS1000L
500
Micrologic
630
800
1000
Masterpact NT06/08/12/16 H2
Micrologic 2.0
630
400
4
800
800
1000
1000
1250
1250
1600
1600
630
400
6.3
6.3
6.3
8
8
8
8
8
8
8
6.3
8
8
10
10
10
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
10
10
12.5
12.5
12.5
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
9.4
6.3
6.3
10
10
10
10
10
10
10
10
10
10
12.5
12.5
16
16
16
T
T
T
T
T
10
10
10
10
T
T
T
T
T
T
T
T
T
T
12.5
12.5
12.5
12.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
630
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
6.3
8
8
10
10
10
800
800
1000
1000
1250
1250
1600
1600
630
400
9.4
9.4
9.4
12
12
12
12
12
12
12
9.4
12
12
15
15
15
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
12
15
15
18.7
18.7
18.7
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
42
9.4
9.4
15
15
15
15
15
15
15
15
15
15
18.7
18.7
24
24
24
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
630
T
T
T
T
T
T
T
9.4
9.4
T
T
T
9.4
12
12
T
T
T
800
800
1000
1000
1250
1250
1600
1600
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
630
42
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
47
Livre 1.indb 47
04/11/2009 15:55:41
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Downstream Rating (A)
Setting Ir
Discrimination limit (kA)
Masterpact
250
NT06 H1/H2
320
Micrologic
400
500
630
Masterpact
320
NT08 H1/H2
400
Micrologic
500
630
800
Masterpact
400
NT10 H1/H2
500
Micrologic
630
800
1000
Masterpact
500
NT12 H1/H2
630
Micrologic
800
1000
1250
Masterpact
630
NT16 H1/H2
800
Micrologic
960
1250
1600
Masterpact
250
NT06 L1
320
Micrologic
400
500
630
Masterpact
320
NT08 L1
400
Micrologic
500
630
800
Masterpact
400
NT10 L1
500
Micrologic
630
800
1000
Masterpact NT06/08/12/16 H2
Micrologic 2.0
630
400
4
800
800
1000
1000
1250
1250
1600
1600
630
400
6.3
6.3
6.3
8
8
8
8
8
8
8
6.3
8
8
10
10
10
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
10
10
12.5
12.5
12.5
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
9.4
6.3
6.3
10
10
10
10
10
10
10
10
10
10
12.5
12.5
16
16
16
T
T
T
T
T
10
10
10
10
T
T
T
T
T
T
T
T
T
T
12.5
12.5
12.5
12.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
630
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
6.3
8
8
10
10
10
800
800
1000
1000
1250
1250
1600
1600
630
400
9.4
9.4
9.4
12
12
12
12
12
12
12
9.4
12
12
15
15
15
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
18.7
12
15
15
18.7
18.7
18.7
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
42
9.4
9.4
15
15
15
15
15
15
15
15
15
15
18.7
18.7
24
24
24
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
630
T
T
T
T
T
T
T
9.4
9.4
T
T
T
9.4
12
12
T
T
T
800
800
1000
1000
1250
1250
1600
1600
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
42
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
630
42
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
48
Livre 1.indb 48
04/11/2009 15:55:41
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Masterpact NT06/08/10 L1
Micrologic 2.0
Downstream
630
250
400
630
800
800
1000
1000
630
250
400
630
800
800
1000
1000
630
250
400
630
800
800
1000
1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
36
36
36
36
20
20
20
20
20
20
T
T
20
20
20
20
T
T
T
T
T
T
T
T
T
T
T
T
T
T
20
20
20
20
20
20
T
T
20
20
20
20
T
T
T
T
T
T
T
T
T
T
T
T
T
T
20
20
20
20
20
20
T
T
20
20
20
20
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
36
36
36
20
20
20
6.3
6.3
6.3
6.3
T
T
T
36
36
36
20
20
20
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
T
T
T
T
T
T
T
T
T
10
10
10
10
10
8
8
8
8
T
T
T
T
T
T
T
T
T
15
15
15
15
15
10
10
10
10
10
T
T
T
36
36
36
20
T
T
T
36
36
36
20
20
20
6.3
6.3
6.3
T
T
T
36
36
36
20
20
20
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
T
T
T
T
T
T
T
T
T
10
10
10
10
10
8
8
8
8
T
T
T
T
T
T
T
T
T
15
15
15
15
15
10
10
10
10
10
T
T
T
T
T
36
36
36
20
20
20
6.3
6.3
6.3
T
T
T
36
36
36
20
20
20
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
T
T
T
T
T
T
T
T
T
10
10
10
10
10
8
8
8
8
T
T
T
T
T
T
T
T
T
15
15
15
15
15
10
10
10
10
10
Rating (A)
Setting Ir
Discrimination limit (kA)
iDPN, iDPNN
C60
C120N/H
NG125N/H
NG125L
NG160
NSC100N
Compact NSX100
B/FN/H/S/L TM-D
Compact NSX160
B/F
TM-D
Compact NSX160
N/H/S/L
TM-D
Compact NSX250 y 125
B/F/N//H/S/L
160
TM-D
200
250
Compact NSX100 40
B/F/N/H/S/L
100
Micrologic
Compact NSX160 40
B/F
100
Micrologic
160
Compact NSX160 40
N/H/S/L
100
Micrologic
160
Compact NSX250 y 100
B/F/N/H/S/L
160
Micrologic
250
Compact NSX400 160
F/N/H/S/L
200
Micrologic
250
320
400
Compact NSX630 250
F/N/H/S/L
320
Micrologic
400
500
630
T
T
T
T
T
36
36
36
20
6.3
6.3
T
T
6.3
6.3
T
T
36
36
36
20
6.3
6.3
No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
49
Livre 1.indb 49
04/11/2009 15:55:42
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Masterpact NT06/08/10 L1
Micrologic 2.0
Downstream
800
800
1000
1000
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
10
10
10
10
10
10
10
10
10
400
630
6.3
630
250
1000
1000
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
10
10
10
10
10
10
10
10
10
400
630
6.3
10
10
10
6.3
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
10
10
10
10
10
10
10
10
10
10
10
10
630
250
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
10
10
10
10
10
10
10
10
10
1000
1000
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
10
10
10
10
10
10
10
10
10
6.3
10
10
10
10
10
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
10
10
10
10
10
10
10
10
10
6.3
10
10
630
6.3
10
10
10
6.3
800
800
400
6.3
10
10
10
10
10
10
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
50
Livre 1.indb 50
04/11/2009 15:55:43
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Downstream
800
1000 1250 1600 2000 800
1000 1250 1600 2000 800
1000 1250 1600 2000
320 630 800 1000 1250 1600 2000 320 630 800 1000 1250 1600 2000 320 630 800 1000 1250 1600 2000
Rating (A)
Setting Ir
Discrimination limit (kA)
iDPN, iDPNN
C60
C120N/H
NG125N/H
NG125L
NG160E/N/H
NSC100N
Compact NSX100
B/F/N/H/S/L TM-D
Compact NSX160
B/F/N/H/S/L TM-D
Compact NSX250 y 125
B/F/N/H/S/L
160
TM-D
200
250
Compact NSX100 40
B/F/N/H/S/L
100
Micrologic
Compact NSX160 40
B/F/N/H/S/L
100
Micrologic
160
Compact NSX250 y 100
B/F/N/H/S/L
160
Micrologic
250
Compact NSX400 160
F/N/H/S/L
200
Micrologic
250
320
400
Compact NSX630 250
F/N/H/S/L
320
Micrologic
400
500
630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
51
Livre 1.indb 51
04/11/2009 15:55:44
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Downstream
800
630
Rating (A)
Setting Ir
Discrimination limit (kA)
Compact NS630b 250
N/H
320
Micrologic
400
500
630
Compact NS800 320
N/H
400
Micrologic
500
630
800
Compact NS1000 400
N/H
500
Micrologic
630
800
1000
Compact NS1250 500
N/H
630
Micrologic
800
1000
1250
Compact NS1600 630
N/H
800
Micrologic
960
1250
1600
Compact NS630b 250
L/LB
320
Micrologic
400
500
630
Compact NS800 320
L/LB
400
Micrologic
500
630
800
Compact NS1000 400
L
500
Micrologic
630
800
1000
800
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
6.3
8
8
10
10
10
10
10
12.5
12.5
12.5
10
12.5
12.5
16
16
16
T
T
T
T
T
10
10
10
10
T
T
T
T
T
T
T
T
T
T
12.5
12.5
12.5
12.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
6.3
8
8
10
10
10
10
10
10
10
10
10
10
10
10
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
800
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
12
12
12
12
12
12
12
15
15
15
15
15
15
15
15
15
12
12
12
12
12
12
12
12
15
15
15
12
15
15
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
12
12
12
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
18.75 24
18.75 24
18.75 24
24
15
18.75 24
18.75 24
24
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
800
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
52
Livre 1.indb 52
04/11/2009 15:55:44
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Downstream Rating (A)
Setting Ir
Discrimination limit (kA)
Masterpact
250
NT06 H1/H2
320
Micrologic
400
500
630
Masterpact
320
NT08 H1/H2
400
Micrologic
500
630
800
Masterpact
400
NT10 H1/H2
500
Micrologic
630
800
1000
Masterpact
500
NT12 H1/H2
630
Micrologic
800
1000
1250
Masterpact
630
NT16 H1/H2
800
Micrologic
960
1250
1600
Masterpact
250
NT06L
320
Micrologic
400
500
630
Masterpact
320
NT08L
400
Micrologic
500
630
800
Masterpact
400
NT10L
500
Micrologic
630
800
1000
800
1000
1000
1250
1250
1600
1600
2000
2000
800
630
10
10
10
10
10
10
10
10
10
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
15
15
15
12
15
15
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
12
12
12
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
6.3
8
8
10
10
10
10
10
12.5
12.5
12.5
10
12.5
12.5
16
16
16
T
T
T
T
T
10
10
10
10
T
T
T
T
T
T
T
T
T
T
12.5
12.5
12.5
12.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
6.3
8
8
10
10
10
800
1000
1000
1250
1250
15
15
15
15
15
15
15
15
15
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
18.75 24
18.75 24
18.75 24
24
15
18.75 24
18.75 24
24
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2000
2000
800
630
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
800
1000
1000
1250
1250
1600
1600
2000
2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
53
Livre 1.indb 53
04/11/2009 15:55:45
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Downstream
800
630
Rating (A)
Setting Ir
Discrimination limit (kA)
Masterpact
320
NW08 N1/H1/L1 400
Micrologic
500
630
800
Masterpact
400
NW10 N1/H1/L1 500
Micrologic
630
800
1000
Masterpact
500
NW12 N1/H1/L1 630
Micrologic
800
1000
1250
Masterpact
630
NW16 N1/H1/L1 800
Micrologic
960
1250
1600
Masterpact
800
NW20 N1/H1/L1 1000
Micrologic
1250
1600
Masterpact
320
NW08 H2
400
Micrologic
500
630
800
Masterpact
400
NW10 H2
500
Micrologic
630
800
1000
Masterpact
500
NW12 H2
630
Micrologic
800
1000
1250
Masterpact
630
NW16 H2
800
Micrologic
960
1250
1600
Masterpact
800
NW20 H2
1000
Micrologic
1250
1600
800
6.3
6.3
8
8
8
10
10
10
10
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
16
16
16
16
16
16
16
16
16
16
16
16
16
16
6.3
8
8
10
10
10
10
10
12.5
12.5
12.5
10
12.5
12.5
16
16
16
12.5
16
16
20
20
20
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
16
16
16
16
16
16
16
16
16
16
16
16
16
16
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
6.3
6.3
8
8
8
10
10
10
10
6.3
8
8
10
10
10
10
10
12.5
12.5
12.5
10
12.5
12.5
16
16
16
12.5
16
16
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
800
12
12
12
12
12
15
15
15
15
12
12
12
15
15
15
12
15
15
15
12
12
12
12
12
15
15
15
15
12
12
12
15
15
15
12
15
15
15
20
20
20
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
24
24
24
24
24
24
24
24
24
24
18.75 24
18.75 24
18.75 24
24
18.75 24
18.75 24
24
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
18.75 24
24
30
30
30
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
24
24
24
24
24
24
24
24
24
24
18.75 24
18.75 24
18.75 24
24
18.75 24
18.75 24
24
18.75 24
24
800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
30
30
30
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
54
Livre 1.indb 54
04/11/2009 15:55:46
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Masterpact NW08/12/16/20 H2
Micrologic 2.0
Downstream
800
630
Rating (A)
Setting Ir
Discrimination limit (kA)
Masterpact
320
NW08 N1/H1/L1 400
Micrologic
500
630
800
Masterpact
400
NW10 N1/H1/L1 500
Micrologic
630
800
1000
Masterpact
500
NW12 N1/H1/L1 630
Micrologic
800
1000
1250
Masterpact
630
NW16 N1/H1/L1 800
Micrologic
960
1250
1600
Masterpact
800
NW20 N1/H1/L1 1000
Micrologic
1250
1600
Masterpact
320
NW08 H2
400
Micrologic
500
630
800
Masterpact
400
NW10 H2
500
Micrologic
630
800
1000
Masterpact
500
NW12 H2
630
Micrologic
800
1000
1250
Masterpact
630
NW16 H2
800
Micrologic
960
1250
1600
Masterpact
800
NW20 H2
1000
Micrologic
1250
1600
800
6.3
6.3
8
8
8
10
10
10
10
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
16
16
16
16
16
16
16
16
16
16
16
16
16
16
6.3
8
8
10
10
10
10
10
12.5
12.5
12.5
10
12.5
12.5
16
16
16
12.5
16
16
20
20
20
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
16
16
16
16
16
16
16
16
16
16
16
16
16
16
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
6.3
6.3
8
8
8
10
10
10
10
6.3
8
8
10
10
10
10
10
12.5
12.5
12.5
10
12.5
12.5
16
16
16
12.5
16
16
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
800
12
12
12
12
12
15
15
15
15
12
12
12
15
15
15
12
15
15
15
12
12
12
12
12
15
15
15
15
12
12
12
15
15
15
12
15
15
15
20
20
20
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
24
24
24
24
24
24
24
24
24
24
18.75 24
18.75 24
18.75 24
24
18.75 24
18.75 24
24
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
18.75 24
24
30
30
30
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
24
24
24
24
24
24
24
24
24
24
18.75 24
18.75 24
18.75 24
24
18.75 24
18.75 24
24
18.75 24
24
800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
30
30
30
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
82
82
82
No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
55
Livre 1.indb 55
04/11/2009 15:55:47
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Masterpact NW08/12/16/20 L1
Micrologic 2.0
Downstream
800
630
Rating (A)
Setting Ir
Discrimination limit (kA)
Compact NS630b 250
N/H
320
Micrologic
400
500
630
Compact NS800 320
N/H
400
Micrologic
500
630
800
Compact NS1000 400
N/H
500
Micrologic
630
800
1000
Compact NS1250 500
N/H
630
Micrologic
800
1000
1250
Compact NS1600 630
N/H
800
Micrologic
960
1250
1600
Compact NS630b 250
L/LB
320
Micrologic
400
500
630
Compact NS800 320
L/LB
400
Micrologic
500
630
800
Compact NS1000 400
L
500
Micrologic
630
800
1000
800
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
6.3
8
8
10
10
10
10
10
12.5
12.5
12.5
10
12.5
12.5
16
16
16
10
10
10
10
10
10
10
10
10
T
T
T
T
T
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
6.3
8
8
10
10
10
10
10
10
10
10
10
10
10
10
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
800
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
15
15
15
12
15
15
T
T
T
T
T
T
T
12
12
12
12
12
12
12
12
15
15
15
15
15
15
15
15
15
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
18.75 24
18.75 24
18.75 24
24
15
18.75 24
18.75 24
24
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
800
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
37
37
37
37
37
37
37
37
37
T
T
T
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
56
Livre 1.indb 56
04/11/2009 15:55:48
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Downstream Rating (A)
Setting Ir
Discrimination limit (kA)
Masterpact
250
NT06 H1/H2
320
Micrologic
400
500
630
Masterpact
320
NT08 H1/H2
400
Micrologic
500
630
800
Masterpact
400
NT10 H1/H2
500
Micrologic
630
800
1000
Masterpact
500
NT12 H1/H2
630
Micrologic
800
1000
1250
Masterpact
630
NT16 H1/H2
800
Micrologic
960
1250
1600
Masterpact
250
NT06 L1
320
Micrologic
400
500
630
Masterpact
320
NT08 L1
400
Micrologic
500
630
800
Masterpact
400
NT10 L1
500
Micrologic
630
800
1000
Masterpact NW08/12/16/20 L1
Micrologic 2.0
800
630
800
1000
1000
1250
1250
1600
1600
2000
2000
800
630
10
10
10
10
10
10
10
10
10
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
15
15
15
12
15
15
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
12
12
12
12
12
12
12
12
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
6.3
8
8
10
10
10
10
10
12.5
12.5
12.5
10
12.5
12.5
16
16
16
10
10
10
10
10
10
10
10
10
T
T
T
T
T
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
6.3
6.3
6.3
8
8
8
8
6.3
6.3
8
8
8
6.3
8
8
10
10
10
800
1000
1000
1250
1250
15
15
15
15
15
15
15
15
15
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
24
24
24
24
24
24
24
24
24
24
24
24
24
24
24
18.75 24
18.75 24
18.75 24
24
15
18.75 24
18.75 24
24
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2000
2000
800
630
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
800
1000
1000
1250
1250
1600
1600
2000
2000
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
57
Livre 1.indb 57
04/11/2009 15:55:49
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Masterpact NW08/12/16/20 L1
Micrologic 2.0
Downstream
800
630
Rating (A)
Setting Ir
Discrimination limit (kA)
Masterpact
320
NW08 N1/H1/H2 400
Micrologic
500
630
800
Masterpact
400
NW10 N1/H1/H2 500
Micrologic
630
800
1000
Masterpact
500
NW12 N1/H1/H2 630
Micrologic
800
1000
1250
Masterpact
630
NW16 N1/H1/H2 800
Micrologic
960
1250
1600
Masterpact
800
NW20 N1/H1/H2 1000
Micrologic
1250
1600
Masterpact
320
NW08 L1
400
Micrologic
500
630
800
Masterpact
400
NW10 L1
500
Micrologic
630
800
1000
Masterpact
500
NW12 L1
630
Micrologic
800
1000
1250
Masterpact
630
NW16 L1
800
Micrologic
960
1250
1600
Masterpact
800
NW20 L1
1000
Micrologic
1250
1600
4
800
6.3
6.3
8
8
8
10
10
10
10
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
16
16
16
16
16
16
16
16
16
16
16
16
16
16
6.3
8
8
10
10
10
10
10
12.5
12.5
12.5
10
12.5
12.5
16
16
16
12.5
16
16
20
20
20
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
16
16
16
16
16
16
16
16
16
16
16
16
16
16
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
6.3
6.3
8
8
8
10
10
10
10
6.3
8
8
10
10
10
10
10
12.5
12.5
12.5
10
12.5
12.5
16
16
16
12.5
16
16
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
800
12
12
12
12
12
15
15
15
15
12
12
12
15
15
15
12
15
15
15
12
12
12
12
12
15
15
15
15
12
12
12
15
15
15
12
15
15
15
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
24
24
24
24
24
24
24
24
24
24
18.75 24
18.75 24
18.75 24
24
18.75 24
18.75 24
24
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
18.75 24
24
30
30
30
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
18.75
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
24
24
24
24
24
24
24
24
24
24
18.75 24
18.75 24
18.75 24
24
18.75 24
18.75 24
24
18.75 24
24
800
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
30
30
30
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
37
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
58
Livre 1.indb 58
04/11/2009 15:55:50
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Downstream
Rating (A)
Discrimination limit (kA)
iDPN, iDPNN
C60
C120N/H
NG125N/H/L
NG160E/N/H
NSC100N
Compact NSX
NSX100
B/F/H/N/S/L
NSX160
TM-D
NSX250
Compact NSX
NSX100
B/F/H/N/S/L
NSX160
Micrologic
NSX250
Compact NSX
NSX400
F/H/N/S/L
NSX630
Micrologic
Compact NS
NS630b
N
NS800
Micrologic
NS1000
NS1250
NS1600
Compact NS
NS630b
H
NS800
Micrologic
NS1000
NS1250
NS1600
Compact NS
NS1600b
N
NS2000
Micrologic
NS2500
NS3200
Compact NS
NS1600b
H
NS2000
Micrologic
NS2500
NS3200
Compact NS
NS630b
L
NS800
Micrologic
NS1000
Compact NS
NS630b
LB
NS800
Micrologic
Masterpact
NW25/32/40 H1/H2
Micrologic 2.0
Masterpact
NW40b 50/63 H1
Masterpact
Masterpact
NW25/32/40 H1/H2 NW40b 50/63 H1
Micrologic 5.0 - 6.0 - 7.0
Inst : 15 In
Masterpact
Masterpact
NW25/32/40 H1/H2 NW40b 50/63 H1
Micrologic 5.0 - 6.0 - 7.0
Inst : OFF
2500
3200
4000
4000
5000
6300
2500
3200
4000
4000
5000
6300
2500
3200
4000
4000
5000
6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
25
25
25
25
25
25
25
25
25
25
25
25
32
32
32
32
32
32
32
32
32
32
32
32
32
37.5
37.5
48
48
48
T
T
T
T
T
T
T
T
T
T
T
T
T
T
75
75
75
75
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
60
60
60
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
60
60
60
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
63
63
63
63
63
63
63
63
63
63
63
63
63
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
50
50
50
50
50
50
50
50
T
T
T
T
T
48
48
48
48
48
48
48
48
48
48
48
48
48
32
32
32
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
25
25
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
59
Livre 1.indb 59
04/11/2009 15:55:51
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Downstream
Rating (A)
Discrimination limit (kA)
Masterpact NT
NT06
H1
NT08
Micrologic
NT10
NT12
NT16
Masterpact NT
NT06
H2
NT08
Micrologic 2.0
NT10
NT12
NT16
Masterpact NW
NW08
N1
NW10
Micrologic
NW12
NW16
Masterpact NW
NW08
H1
NW10
Micrologic
NW12
NW16
NW20
NW25
NW32
Masterpact NW
NW08
H2
NW10
Micrologic
NW12
NW16
NW20
NW25
NW32
Masterpact NW
NW20
H3
NW25
Micrologic
NW32
Masterpact NT
NT06
L1
NT08
Micrologic
NT10
Masterpact NW
NW08
L1
NW10
Micrologic
NW12
NW16
NW20
Masterpact NW25/32/40 H1
Micrologic 2.0
2500
3200
4000
2500
3200
4000
2500
3200
4000
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
T
T
T
T
T
48
48
48
48
48
T
T
T
T
48
48
48
48
48
48
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
32
32
32
32
32
32
37.5
37.5
37.5
37.5
37.5
48
48
48
48
48
48
T
T
T
T
T
T
T
T
T
T
T
25
32
32
37.5
48
48
T
T
T
T
T
25
25
25
25
25
T
T
T
32
32
32
32
32
T
T
T
37.5
37.5
37.5
37.5
37.5
T
T
T
48
48
48
48
48
T
T
T
T
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
T
T
T
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
25
25
25
25
25
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
T
T
T
40
40
40
40
40
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
60
Livre 1.indb 60
04/11/2009 15:55:52
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Downstream
Rating (A)
Discrimination limit (kA)
Masterpact NT NT06
H1
NT08
Micrologic
NT10
NT12
NT16
Masterpact NT NT06
H2
NT08
Micrologic
NT10
NT12
NT16
Masterpact NW NW08
N1
NW10
Micrologic
NW12
NW16
Masterpact NW NW08
H1
NW10
Micrologic
NW12
NW16
NW20
NW25
NW32
NW40
Masterpact NW NW08
H2
NW10
Micrologic
NW12
NW16
NW20
NW25
NW32
NW40
Masterpact NW NW40b
H1
NW50
Masterpact NW NW20
H3
NW25
Micrologic
NW32
NW40
Masterpact NW NW40b
H2
NW50
Masterpact NT NT06
L1
NT08
Micrologic
NT10
Masterpact NW NW08
L1
NW10
Micrologic
NW12
NW16
NW20
Masterpact
NW25/32/40 H2
Micrologic 2.0
Masterpact
NW40b 50/63 H1
Masterpact
Masterpact
NW25/32/40 H2
NW40b 50/63 H1
Micrologic 5.0 - 6.0 - 7.0
Inst : 15 In
Masterpact
Masterpact
NW25/32/40 H2
NW40b 50/63 H1
Micrologic 5.0 - 6.0 - 7.0
Inst : OFF
2500
3200
4000
4000
5000
6300
2500
3200
4000
4000
5000
6300
2500
3200
4000
4000
5000
6300
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
48
48
48
48
48
T
T
T
T
48
48
48
48
48
48
T
T
T
T
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
37.5
37.5
37.5
37.5
37.5
48
48
48
48
48
48
60
60
60
60
60
60
60
60
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
82
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
25
32
32
40
40
40
40
40
40
50
50
50
50
50
37.5
48
48
60
60
60
60
60
60
75
75
75
75
75
82
82
82
82
82
82
T
T
T
T
T
T
T
T
T
T
T
25
25
25
25
25
T
T
T
32
32
32
32
32
T
T
T
40
40
40
40
40
T
T
T
40
40
40
40
40
T
T
T
50
50
50
50
50
T
T
T
37.5
37.5
37.5
37.5
37.5
T
T
T
48
48
48
48
48
T
T
T
60
60
60
60
60
T
T
T
60
60
60
60
60
T
T
T
75
75
75
75
75
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
94
94
94
94
94
94
94
94
94
94
94
94
94
94
94
94
T
T
T
94
94
94
94
94
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
75
75
75
75
75
75
75
75
75
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
T
T
T
T
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
32
32
32
32
32
32
T
T
T
T
T
T
T
T
T
T
T
T
T
T
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
T
T
T
63
63
63
63
63
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
25
25
25
25
25
T
T
T
T
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
61
Livre 1.indb 61
04/11/2009 15:55:53
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Masterpact
NW20/25/32/40H3
Micrologic 2.0
Masterpact
Masterpact
Masterpact
NW40b 50/63 H2 NW20/25/32/40 H3
NW40b 50/63 H2
Micrologic 5.0 - 6.0 - 7.0
Inst : 15 In
Masterpact
Masterpact
NW20/25/32/40 H3
NW40b 50/63 H2
Micrologic 5.0 - 6.0 - 7.0
Inst : OFF
2500 3200 4000 4000 5000 6300 2000 2500 3200 4000 4000 5000 6300 2000 2500 3200 4000 4000 5000 6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
25
25
25
25
25
25
25
25
25
25
25
25
T
T
T
T
T
T
T
T
T
T
T
T
T
T
32
32
32
32
32
32
32
32
32
32
32
32
32
25
25
32
32
32
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
50
50
50
50
50
50
50
50
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
63
63
63
63
63
63
63
63
63
63
63
63
63
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
30
30
30
30
30
30
30
30
30
30
30
T
T
T
T
T
T
T
T
T
T
T
T
T
T
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
48
48
48
48
48
48
48
48
48
48
48
48
48
30
37.5 48
37.5 48
48
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
60
60
60
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
60
60
60
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
75
75
75
75
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
65
65
65
65
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
65
65
65
65
65
65
65
65
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
62
Livre 1.indb 62
04/11/2009 15:55:54
Protection discrimination
Complementary
technical information
Upstream
Trip unit
Downstream Rating (A)
Discrimination limit (kA)
Masterpact NT NT06
H1
NT08
Micrologic
NT10
NT12
NT16
Masterpact NT NT06
H2
NT08
Micrologic
NT10
NT12
NT16
Masterpact NW NW08
N1
NW10
Micrologic
NW12
NW16
Masterpact NW NW08
H1
NW10
Micrologic
NW12
NW16
NW20
NW25
NW32
NW40
Masterpact NW NW08
H2
NW10
Micrologic
NW12
NW16
NW20
NW25
NW32
NW40
Masterpact NW NW40b
H1
NW50
Masterpact NW NW20
H3
NW25
Micrologic
NW32
NW40
Masterpact NW NW40b
H2
NW50
Masterpact NT NT06
L1
NT08
Micrologic
NT10
Masterpact NW NW08
L1
NW10
Micrologic
NW12
NW16
NW20
Masterpact
NW20/25/32/40 H3
Micrologic 2.0
Masterpact
Masterpact
Masterpact
NW40b 50/63 H2 NW20/25/32/40 H3
NW40b 50/63 H2
Micrologic 5.0 - 6.0 - 7.0
Inst : 15 In
Masterpact
Masterpact
NW20/25/32/40 H3
NW40b 50/63 H2
Micrologic 5.0 - 6.0 - 7.0
Inst : OFF
2000 2500 3200 4000 4000 5000 6300 2000 2500 3200 4000 4000 5000 6300 2000 2500 3200 4000 4000 5000 6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
32
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
20
20
20
20
25
25
25
25
25
32
32
32
32
32
32
40
40
40
40
40
40
40
40
40
40
40
40
40
40
20
25
32
32
40
40
40
40
40
40
50
50
50
50
50
T
T
T
20
20
20
20
20
T
T
T
25
25
25
25
25
T
T
T
32
32
32
32
32
T
T
T
40
40
40
40
40
T
T
T
40
40
40
40
40
T
T
T
50
50
50
50
50
T
T
T
T
T
T
T
T
T
T
T
T
T
T
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
T
T
T
63
63
63
63
63
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
30
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
37.5
T
T
T
T
T
48
48
48
48
48
T
T
T
T
48
48
48
48
48
48
T
T
T
T
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
60
60
30
30
30
30
37.5
37.5
37.5
37.5
37.5
48
48
48
48
48
48
T
T
T
30
30
30
30
60
60
60
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
T
T
T
T
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
75
75
75
75
75
75
75
75
75
37.5 48
48
60
60
60
60
60
60
75
75
75
75
75
T
T
T
37.5
37.5
37.5
37.5
37.5
T
T
T
60
60
60
60
60
T
T
T
60
60
60
60
60
T
T
T
75
75
75
75
75
T
T
T
48
48
48
48
48
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
94
94
94
94
94
94
94
94
94
94
94
94
94
94
94
94
T
T
T
94
94
94
94
94
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
65
T
T
T
T
T
T
T
T
65
65
65
65
65
65
120
120
120
120
120
120
120
120
T
T
T
100
100
100
100
100
T
T
T
100
100
100
100
100
T
T
T
100
100
100
100
100
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
100
100
100
100
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
120
120
120
120
120
120
T
T
T
T
T
T
T
T
No discrimination.
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
63
Livre 1.indb 63
04/11/2009 15:55:57
Protection discrimination / DC
Complementary
technical information
Upstream
Type of trip unit
Fixed or adjustable
Im (A)
Downstream
Compact NS100 DC
TMD trip units
Rating In (A)
16
25
32
40
50
63
80
100
Upstream
Type of trip unit
Fixed or adjustable
Im (A)
Downstream
Rating In (A)
Compact NS100 DC 16
TMD trip units
25
32
40
50
63
TMDC trip units
80
100
Compact NS160 DC 16
TMD trip units
25
32
40
50
63
TMDC trip units
80
100
125
160
550
700
700
700
700
TM63D
Fixed
700
TM80DC
Fixed
640
TM100DC
Fixed
800
700
700
700
640
640
640
640
640
800
800
800
800
800
800
TM63D
Fixed
700
TM80DC
Fixed
640
550
700
700
700
700
700
700
700
640
640
640
640
640
800
800
800
800
800
800
1250
1250
1250
1250
1250
1250
550
700
700
700
700
700
700
700
640
640
640
640
640
800
800
800
800
800
800
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
64
Livre 1.indb 64
04/11/2009 15:56:15
Complementary
technical information
Upstream
Type of trip unit
Fixed or adjustable
Im (A)
Downstream
Compact NS100 DC
TMD trip units
Compact NS250 DC
TMDC trip units
Rating In (A)
16
25
32
40
50
63
80
100
16
25
32
40
50
63
80
100
125
160
80
100
125
160
200 Irm min.
200 Irm max.
250 Irm min.
250 Irm max.
Protection discrimination / DC
Upstream: Compact NS250 DC
Downstream: Compact NS100 and
NS250 DC
Compact NS250 DC - Thermal magnetic protection
TM80DC TM100DC TM125DC TM160DC TM200DC
Fixed
Fixed
Fixed
Fixed
Adjustable
Min.
Max.
640
800
1250
1250
1000
2000
640
640
640
640
640
800
800
800
800
800
800
1250
1250
1250
1250
1250
1250
1250
640
640
640
640
640
800
800
800
800
800
800
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1000
1000
1000
1000
1000
1000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
TM250DC
Adjustable
Min.
Max.
1250
2500
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
65
Livre 1.indb 65
04/11/2009 15:56:18
Complementary
technical information
Upstream
Magnetic trip unit
Adjustable
Im (A)
Downstream
Compact NS100 DC
TMD trip units
Compact NS250 DC
TMDC trip units
Compact
NS400 DC-NS630 DC
NS630 DC
Rating In (A)
16
25
32
40
50
63
80
100
16
25
32
40
50
63
80
100
125
160
80
100
125
160
200 Irm min.
200 Irm max.
250 Irm min.
250 Irm max.
MP1 Irm min.
MP1 Irm max.
MP2 Irm min.
MP2 Irm max.
MP3 Irm min.
MP3 Irm max.
Protection discrimination / DC
800
800
800
800
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
MP3
Min.
2000
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2500
2000
2500
2500
Max.
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
66
Livre 1.indb 66
04/11/2009 15:56:20
Complementary
technical information
Upstream
Magnetic trip unit
Adjustable
li (A)
Downstream
Compact NS100 DC
TMD trip units
Compact NS250 DC
TMDC trip units
Compact
NS400 DC - NS630 DC
Compact NS630 DC
Masterpact NW10
li = 1250/2500 A
Masterpact NW10
li = 2500/5400 A
Rating In (A)
16
25
32
40
50
63
80
100
16
25
32
40
50
63
80
100
125
160
80
100
125
160
200 Irm min.
200 Irm max.
250 Irm min.
250 Irm max.
MP1 Irm min.
MP1 Irm max.
MP2 Irm min.
MP2 Irm max.
MP3 Irm min.
MP3 Irm max.
Setting
A
B
C
D
E
Setting
A
B
C
D
E
Protection discrimination / DC
Upstream: Masterpact NW10
Downstream: Compact NS100
to NS630 DC, Masterpact NW10
Masterpact NW10 magnetic protection only
1250 A to 2500 A
Setting
A
B
C
D
E
1250
1500
1600
2000
2500
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1250
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1500
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1250
1250
1500
1500
1600
1600
1500
1600
1250
1500
1600
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2000
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2000
2500
2500
2000
2500
2500
2500
2500
2500
2500
2000
1600
2500 A to 5400 A
Setting
A
B
2500
3300
2000
2000
2000
2500
2500
2500
2500
2500
2500
2500
2500
C
4000
D
5000
E
5400
3300
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
3300
3300
3300
3300
3300
3300
4000
4000
4000
4000
4000
4000
5000
5000
5000
5000
5000
5000
5000
5000
5400
5400
5400
5400
5400
5400
5400
5400
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
67
Livre 1.indb 67
04/11/2009 15:56:22
Complementary
technical information
Upstream
Magnetic trip unit
Adjustable
li (A)
Downstream
Compact NS100 DC
TMD trip units
Compact NS250 DC
TMDC trip units
Compact
NS400 DC-NS630 DC
NS630 DC
Masterpact NW10
li = 1250/2500 A
Masterpact NW10
li = 2500/5400 A
Masterpact NW10
li = 5000/11000 A
Masterpact NW20
li = 2500/5400 A
Rating In (A)
16
25
32
40
50
63
80
100
16
25
32
40
50
63
80
100
125
160
80
100
125
160
200 Irm min.
200 Irm max.
250 Irm min.
250 Irm max.
MP1 Irm min.
MP1 Irm max.
MP2 Irm min.
MP2 Irm max.
MP3 Irm min.
MP3 Irm max.
Setting
A
B
C
D
E
Setting
A
B
C
D
E
Setting
A
B
C
D
E
Setting
A
B
C
D
E
Protection discrimination / DC
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
2500 A to 5400 A
Setting
A
B
2500
3300
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
C
4000
D
5000
E
5400
3300
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
4000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
5400
3300
3300
3300
3300
3300
3300
4000
4000
4000
4000
4000
4000
5000
5000
5000
5000
5000
5000
5000
5000
5400
5400
5400
5400
5400
5400
5400
5400
3300
4000
5000
5000
5000
5400
5400
5400
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
68
Livre 1.indb 68
04/11/2009 15:56:23
Complementary
technical information
Upstream
Magnetic trip unit
Adjustable
li (A)
Downstream
Compact NS100 DC
TMD trip units
Compact NS250 DC
TMDC trip units
Compact
NS400 DC-NS630 DC
NS630 DC
Masterpact NW10
li = 1250/2500 A
Masterpact NW10
li = 2500/5400 A
Masterpact NW10
li = 5000/11000 A
Masterpact NW20
li = 2500/5400 A
Masterpact NW20
li = 5000/11000 A
Masterpact NW40
li = 5000/11000 A
Rating In (A)
16
25
32
40
50
63
80
100
16
25
32
40
50
63
80
100
125
160
80
100
125
160
200 Irm min.
200 Irm max.
250 Irm min.
250 Irm max.
MP1 Irm min.
MP1 Irm max.
MP2 Irm min.
MP2 Irm max.
MP3 Irm min.
MP3 Irm max.
Setting
A
B
C
D
E
Setting
A
B
C
D
E
Setting
A
B
C
D
E
Setting
A
B
C
D
E
Setting
A
B
C
D
E
Setting
A
B
C
D
E
Protection discrimination / DC
5000 A to 11000 A
Setting
A
B
C
5000
8000
10000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
8000
8000
8000
8000
8000
8000
10000
10000
10000
10000
10000
10000
10000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
D
11000
E
11000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
5000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
8000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
10000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
5000
5000
5000
5000
5000
5000
5000
8000
8000
8000
8000
8000
8000
8000
10000
10000
10000
10000
10000
10000
10000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
11000
5000
5000
8000
8000
10000
10000
11000
11000
11000
11000
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
69
Livre 1.indb 69
04/11/2009 15:56:24
Complementary
technical information
Protection discrimination
with fuses
DB125649
Principle
Schneider Electric offers a coordinated protection system
In an electrical installation, protection fuses are never used alone and must always
be integrated in a system comprising circuit breakers.
Coordination is required between:
b upstream and downstream fuses
b upstream circuit breakers and downstream fuses
b upstream fuses and downstream circuit breakers.
I ON
O
OFF
test
Total energy of downstream fuse (Etav) < Pre-arcing energy of upstream fuse
(Epam)
I ON
O
OFF
DB115746
test
Note: If Etav is higher than 80 % of Epam, the upstream fuse may be derated.
DB114881
Curves E = f ( I) superimposed.
16
20
25
32
40
50
63
80
100
125
160
200
250
315
400
500
630
800
1 000
1 250
0.27
0.40
0.55
0.79
1.00
1.20
1.50
1.85
2.30
3.00
4.00
5.10
6.80
8.70
11.80
15.00
20.00
26.00
37.00
50.00
0.55
0.79
1.00
1.20
1.50
1.85
2.30
3.00
4.00
5.10
6.80
8.70
11.80
15.00
20.00
26.00
37.00
50.00
66.00
90.00
291
640
1 210
2 500
4 000
5 750
9 000
13 700
21 200
36 000
64 000
104 000
185 000
302 000
557 000
900 000
1 600 000
2 700 000
5 470 000
10 000 000
1 210
2 500
4 000
5 750
9 000
13 700
21 200
36 000
64 000
104 000
185 000
302 000
557 000
900 000
1 600 000
2 700 000
5 470 000
10 000 000
17 400 000
33 100 000
l = f(t) curves.
70
558E4340.indd 70
20/11/2009 15:43:56
Protection discrimination
with fuses
Complementary
technical information
DB125650
HA10 12kV
Ui 1000V
Uimp
Ue (V)
690
50kA/1s
50/60Hz
AS NBMA
947-2
UNE
IEC
BS CEI
EN 60947-2
VDE
UTE
Rule
Examination of discrimination at the critical points on the LT (long time) and ST
(short time) curves results in a discrimination table.
Analysis of the LT critical point indicates whether discrimination between the
protection devices is possible or not.
Analysis of the ST (or Icw) critical point indicates whether the discrimination limit is
greater than or equal to the ST (or Icw) value.
Note:
b the LT critical point is the most restrictive
b for circuit breakers with a Icw value that is high and/or equal to Icu, the ST critical point is
almost never a problem, i.e. discrimination is total.
I ON
O
OFF
DB125651
test
DB125652
DB125653
I ON
O
OFF
test
71
Livre 1.indb 71
04/11/2009 15:56:40
Protection discrimination
with fuses
Complementary
technical information
DB125650
HA10 12kV
Ui 1000V
Uimp
Ue (V)
690
50kA/1s
50/60Hz
AS NBMA
947-2
UNE
IEC
BS CEI
EN 60947-2
VDE
UTE
DB125655
I ON
DB125654
The new Micrologic control unit has a special LT delay setting for HVF very inverse
time applications.
This curve is ideal for discrimination when fuse-based protection devices are
installed downstream (LV distribution) or upstream (HV).
O
OFF
test
IDMTL curve.
Increase in discrimination.
The new Micrologic 5.0 - 6.0 - 7.0 P / H control units are equipped as standard with
four settings for LT inverse-time curves with adjustable slopes.
SIT: standard inverse time.
VIT: very inverse time.
EIT: extremely inverse time (traditional LT curve).
HVF: high-voltage fuse, inverse-time curve that follows the fuse thermal curve.
72
Livre 1.indb 72
04/11/2009 15:56:41
Protection discrimination
with fuses
Complementary
technical information
The upstream protection circuit breaker must be coordinated with the thermal relay
and the short-circuit protection aM fuse-link.
l2t ON setting
DB115190
DB115820
l2t ON curve.
Increase in the discrimination limit.
73
Livre 1.indb 73
04/11/2009 15:56:43
Protection discrimination
with fuses
Complementary
technical information
DB125652
DB125656
I ON
O
OFF
test
I ON
O
OFF
DB125658
test
74
Livre 1.indb 74
04/11/2009 15:56:45
DB125659
Complementary
technical information
I ON
O
OFF
test
Discrimination tables
I ON
O
OFF
test
Rating (A)
16
20
25
32
40
50
63
80
100
125
160
200
250
315
400
500
630
800
1000
1250
Downstream fuse-link
gG (In) / gM (Ich)
aM (In)
6
10
16
20
25
32
40
50
63
80
100
125
160
200
250
315
400
500
630
8000
4
6
8
10
12
16
20
25
32
40
63
80
125
125
160
200
250
315
400
500
Examples:
b an upstream 125 A gG fuse-link ensures total discrimination with an 80 A gG
fuse-link and/or a 40 A aM fuse-link situated downstream
b an upstream 125 A gG fuse-link ensures total discrimination with a 63 A gG 63M80
fuse-link (with an 80 A characteristic) situated downstream.
75
Livre 1.indb 75
04/11/2009 15:56:46
DB125650
Complementary
technical information
NX 08
HA10 12kV
Ui 1000V
Discrimination tables
Uimp
Ue (V)
690
50kA/1s
50/60Hz
AS NBMA
947-2
UNE
IEC
BS CEI
EN 60947-2
VDE
UTE
I ON
O
OFF
test
Upstream
NT08
H1
NW08
N1
H1/H2
NT08
H1
NW08
N1
H1/H2
NT08
H1
NW08
N1
H1/H2
NT10
H1
NW10
N1
H1/H2
Table key
T
16
Total discrimination
Discrimination limit in kA
No discrimination
NT12
H1
NW12
N1
H1/H2
NT16
H1
NW16 NW20 NW25 NW32 NW40 NW50 NW63
N1
H1/H2 H1/H2 H1/H2 H1/H2 H1/H2 H1/H2 H1/H2
H3
H3
H3
H3
1200
1200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
12
1600
1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
16
2000
2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
20
2500
2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
3200
3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
4000
4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
5000
5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
6300
6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NW08 to NW16
N1 / Icu = Icw = 42 kA
H1 / Icu = Icw = 65 kA
H2 / Icu = 100 Icw = 85 kA
NW08 to NW20
L1 / Icu = 150 kA Icw = 30 kA
NW20 to NW40
H1 / Icu = Icw = 65 kA
H2 / Icu = 100 Icw = 85 kA
H3 / Icu = 150 Icw = 65 kA
NW40b to NW63
H1 / Icu = Icw = 100 kA
H2 / Icu = 150 Icw = 100 kA
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
76
Livre 1.indb 76
04/11/2009 15:56:47
Discrimination tables
Complementary
technical information
DB125650
NX 08
The Masterpact circuit breaker is equipped with a Micrologic 5.0 - 6.0 - 7.0 P / H
control unit with the following settings:
b LT setting: HVF curve with Tld = 24 seconds
b ST setting: instantaneous OFF / Tsd = 0.4 seconds.
HA10 12kV
Ui 1000V
Uimp
Ue (V)
690
50kA/1s
50/60Hz
AS NBMA
947-2
UNE
IEC
BS CEI
EN 60947-2
VDE
UTE
Upstream
I ON
O
OFF
test
Upstream
Downstream
gG/aM
Fuselink
Masterpact NT L1
Micrologic 5.0-6.0-7.0 P/H
NT08 NT08 NT08 NT08
400
160
T
T
T
T
T
T
400
200
T
T
T
T
T
T
T
400
240
T
T
T
T
T
T
T
16
630
315
T
T
T
T
T
T
T
16
10
NT08
NT08
NT08
NT08
NT10
630
400
T
T
T
T
T
T
T
16
10
10
630
480
T
T
T
T
T
T
T
16
10
10
5
630
630
T
T
T
T
T
T
T
16
10
10
10
10
6
800
800
T
T
T
T
T
T
T
16
10
10
10
10
10
8
1000
1000
T
T
T
T
T
T
T
16
10
10
10
10
10
10
10
Masterpact NW L1
Micrologic 5.0-6.0-7.0 P/H
Rating (A)
Ir setting
32
40
50
63
80
100
125
160
200
250
315
355
400
500
630
800
1000
1250
NW08
NW08
NW08
NW08
NW08
NW08
NW08
NW08
NW10
NW12
NW16
NW20
400
160
T
T
T
T
T
T
400
200
T
T
T
T
T
T
T
400
240
T
T
T
T
T
T
T
T
630
315
T
T
T
T
T
T
T
T
T
630
400
T
T
T
T
T
T
T
T
T
T
630
480
T
T
T
T
T
T
T
T
T
T
5
630
630
T
T
T
T
T
T
T
T
T
T
T
100
6
800
800
T
T
T
T
T
T
T
T
T
T
T
100
83
8
1000
1000
T
T
T
T
T
T
T
T
T
T
T
100
83
43
1200
1200
T
T
T
T
T
T
T
T
T
T
T
100
83
43
30
12
1600
1600
T
T
T
T
T
T
T
T
T
T
T
100
83
43
30
30
16
2000
2000
T
T
T
T
T
T
T
T
T
T
T
100
83
43
30
30
30
20
Table key
T
16
Total discrimination
Discrimination limit in kA
No discrimination
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
77
Livre 1.indb 77
04/11/2009 15:56:48
Discrimination tables
Complementary
technical information
DB125650
NX 08
The Masterpact circuit breaker is equipped with a Micrologic 5.0 - 6.0 - 7.0 A / P / H
control unit with the following settings:
b LT setting: Tr = 24 seconds
b ST setting: instantaneous OFF / Tsd = 0.4 seconds.
HA10 12kV
Ui 1000V
Uimp
Ue (V)
690
50kA/1s
50/60Hz
AS NBMA
947-2
UNE
IEC
BS CEI
EN 60947-2
VDE
UTE
I ON
O
OFF
test
Upstream
Masterpact NT H1 / NW H1/H2/H3
Micrologic 5.0-6.0-7.0 A/P/H
NT08 NT08 NT08 NT08 NT08
H1
H1
H1
H1
H1
NW08 NW08 NW08 NW08 NW08
N1
N1
N1
N1
N1
H1/H2 H1/H2 H1/H2 H1/H2 H1/H2
400
160
T
T
T
T
Table key
T
16
Total discrimination
Discrimination limit in kA
No discrimination
400
200
T
T
T
T
T
400
240
T
T
T
T
T
T
630
315
T
T
T
T
T
T
T
800
400
T
T
T
T
T
T
T
T
NT08
H1
NW08
N1
H1/H2
NT08
H1
NW08
N1
H1/H2
NT08
H1
NW08
N1
H1/H2
NT10
H1
NW10
N1
H1/H2
NT12
H1
NW12
N1
H1/H2
NT16
H1
NW16 NW20 NW25 NW32 NW40 NW50 NW63
N1
H1/H2 H1/H2 H1/H2 H1/H2 H1/H2 H1/H2 H1/H2
H3
H3
H3
H3
800
480
T
T
T
T
T
T
T
T
T
800
630
T
T
T
T
T
T
T
T
T
T
800
800
T
T
T
T
T
T
T
T
T
T
T
1000
1000
T
T
T
T
T
T
T
T
T
T
T
T
T
1200
1200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
1600
1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2000
2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2500
2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
3200
3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
4000
4000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
5000
5000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
6300
6300
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NW20 to NW40
H1 / Icu = Icw = 65 kA
H2 / Icu = 100 Icw = 85 kA
H3 / Icu = 150 Icw = 65 kA
NW40b to NW63
H1 / Icu = Icw = 100 kA
H2 / Icu = 150 Icw = 100 kA
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
78
Livre 1.indb 78
04/11/2009 15:56:49
Protection discrimination
Complementary
technical information
DB125650
NX 08
The Masterpact circuit breaker is equipped with a Micrologic 5.0 - 6.0 - 7.0 P / H
control unit with the following settings:
b LT setting: HVF curve with Tld = 24 seconds
b ST setting: instantaneous OFF / Tsd = 0.4 seconds.
HA10 12kV
Ui 1000V
Uimp
Ue (V)
690
50kA/1s
50/60Hz
AS NBMA
947-2
UNE
IEC
BS CEI
EN 60947-2
VDE
UTE
Upstream
I ON
O
OFF
test
Upstream
Downstream
gG/aM
Fuselink
Masterpact NT L1
Micrologic 5.0-6.0-7.0 P/H
NT08 NT08 NT08 NT08
400
160
T
T
T
T
T
T
400
200
T
T
T
T
T
T
T
400
240
T
T
T
T
T
T
T
16
630
315
T
T
T
T
T
T
T
16
10
NT08
NT08
NT08
NT08
NT10
630
400
T
T
T
T
T
T
T
16
10
10
630
480
T
T
T
T
T
T
T
16
10
10
5
630
630
T
T
T
T
T
T
T
16
10
10
10
10
6
800
800
T
T
T
T
T
T
T
16
10
10
10
10
10
8
1000
1000
T
T
T
T
T
T
T
16
10
10
10
10
10
10
10
Masterpact NW L1
Micrologic 5.0-6.0-7.0 P/H
Rating (A)
Ir setting
32
40
50
63
80
100
125
160
200
250
315
355
400
500
630
800
1000
1250
NW08
NW08
NW08
NW08
NW08
NW08
NW08
NW08
NW10
NW12
NW16
NW20
400
160
T
T
T
T
T
T
400
200
T
T
T
T
T
T
T
400
240
T
T
T
T
T
T
T
T
630
315
T
T
T
T
T
T
T
T
T
630
400
T
T
T
T
T
T
T
T
T
T
630
480
T
T
T
T
T
T
T
T
T
T
5
630
630
T
T
T
T
T
T
T
T
T
T
T
100
6
800
800
T
T
T
T
T
T
T
T
T
T
T
100
83
8
1000
1000
T
T
T
T
T
T
T
T
T
T
T
100
83
43
1200
1200
T
T
T
T
T
T
T
T
T
T
T
100
83
43
30
12
1600
1600
T
T
T
T
T
T
T
T
T
T
T
100
83
43
30
30
16
2000
2000
T
T
T
T
T
T
T
T
T
T
T
100
83
43
30
30
30
20
Table key
T
16
Total discrimination
Discrimination limit in kA
No discrimination
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6,, or check curves with curve direct software.
79
Livre 1.indb 79
04/11/2009 15:56:50
Discrimination tables
Complementary
technical information
DB125660
The Compact NS630b to 3200 circuit breaker is equipped with a Micrologic 5.0-6.07.0 A control unit with the following settings:
b LT setting: Tr = 24 seconds
b ST setting: instantaneous OFF / Tsd = 0.4 seconds.
I ON
O
OFF
test
Upstream
Downstream
gG
fuse-link
Compact NS L
Micrologic 5.0-6.0-7.0 A
NS630b NS630b NS630b
Rating (A)
Ir setting
32
40
50
63
80
100
125
160
200
250
315
355
400
500
630
800
1000
1250
Upstream
Downstream
gG
fuse-link
Rat. (A)
Ir setting
32
40
50
63
80
100
125
160
200
250
315
355
400
500
630
800
1000
1250
400
160
T
T
T
T
T
400
240
T
T
T
T
T
74
41
NS630b
NS630b
NS630b
NS800
NS1000
630
315
T
T
T
T
T
74
41
16
630
400
T
T
T
T
T
74
41
16
10
630
500
T
T
T
T
T
74
41
16
10
10
630
630
T
T
T
T
T
74
41
16
10
10
800
800
T
T
T
T
T
74
41
16
10
10
10
10
1000
1000
T
T
T
T
T
74
41
16
10
10
10
10
10
Compact NS N/H
Micrologic 5.0-6.0-7.0 A
NS630b NS630b NS630b NS630b NS630b NS630b NS630b NS800
400
160
T
T
T
T
T
400
200
T
T
T
T
T
T
Table key
T
41
400
200
T
T
T
T
T
74
NS630b
400
240
T
T
T
T
T
T
T
630
315
T
T
T
T
T
T
T
T
630
400
T
T
T
T
T
T
T
T
T
630
500
T
T
T
T
T
T
T
T
T
T
630
630
T
T
T
T
T
T
T
T
T
T
800
800
T
T
T
T
T
T
T
T
T
T
T
44
1200
1200
T
T
T
T
T
T
T
T
T
T
T
44
35
25
1600
1600
T
T
T
T
T
T
T
T
T
T
T
44
35
25
25
1600
1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
40
2000
2000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
40
40
2500
2500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
40
40
40
3200
3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
40
40
40
40
NS630b/400 to 1000
L / Icu = 150 kA Icw = 10 kA / 0.5
NS630b to NS1600
N / Icu = 50 kA, lcw = 25 kA
H / Icu = 70 kA, Icw = 25 kA
NS1600b to NS3200
N / Icu = 70 kA, lcw = 40 kA
H / Icu = 85 kA, lcw = 40 kA
H3 / Icu = 150 Icw = 65 kA
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
80
Livre 1.indb 80
04/11/2009 15:56:51
Discrimination tables
Complementary
technical information
DB125652
I ON
O
OFF
test
Downstream
gG
fuse-link
NS100N/H/L
NS160N/H/L
NS250/N/H/L
Trip unit
TM-D
TM-D
TM-D
Rating (A)
Im (kA)
2
4
6
10
16
20
25
32
35
40
50
63
80
100
125
160
200
250
315
355
16
0.19
T
T
T
T
25
0.3
T
T
T
T
40
0.5
T
T
T
T
T
T
T
63
0.5
T
T
T
T
T
T
T
80
0.63
T
T
T
T
T
T
T
T
100
0.8
T
T
T
T
T
T
T
T
80
1
T
T
T
T
T
T
T
T
T
T
100
1.25
T
T
T
T
T
T
T
T
T
T
T
125
1.25
T
T
T
T
T
T
T
T
T
T
T
T
160
1.25
T
T
T
T
T
T
T
T
T
T
T
T
160
1.25
T
T
T
T
T
T
T
T
T
T
T
T
T
NS400/630/N/
H/L
STR23/53
STR22
200
2
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
250
2.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
160
1.6
T
T
T
T
T
T
T
T
T
T
T
T
250
2.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
400
4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
630
6.3
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Downstream
aM
fuse-link
NS100N/H/L
NS160N/H/L
NS250/N/H/L
Trip unit
TM-D
TM-D
TM-D
Rating (A)
Im (kA)
2
4
6
10
16
20
32
40
50
63
80
100
125
160
200
16
0.19
T
T
T
25
0.3
T
T
T
40
0.5
T
T
T
T
63
0.5
T
T
T
T
T
80
0.63
T
T
T
T
T
T
100
0.8
T
T
T
T
T
T
80
1
T
T
T
T
T
T
100
1.25
T
T
T
T
T
T
125
1.25
T
T
T
T
T
T
T
160
1.25
T
T
T
T
T
T
T
160
1.25
T
T
T
T
T
T
T
NS400/630/N/
H/L
STR23/53
STR22
200
2
T
T
T
T
T
T
T
T
T
T
250
2.5
T
T
T
T
T
T
T
T
T
T
160
1.6
T
T
T
T
T
T
T
250
2.5
T
T
T
T
T
T
T
T
T
T
400
4
T
T
T
T
T
T
T
T
T
T
T
T
630
6.3
T
T
T
T
T
T
T
T
T
T
T
T
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
81
Livre 1.indb 81
04/11/2009 15:56:52
Discrimination tables
Complementary
technical information
DB125661
I ON
O
OFF
test
Trip unit
Trip unit
Upstream
Im (kA)
2
4
6
10
16
20
32
35
40
50
63
Trip unit
Im (kA)
2
4
6
10
16
20
32
35
40
50
63
80
100
NSX100B/F/N/H/S/L
TM-D
16
0.19
T
T
T
25
0.3
T
T
T
32
0.4
T
T
T
NSX160B/F/N/H/S/L
TM-D
40
0.5
T
T
T
T
50
0.5
T
T
T
T
63
0.5
T
T
T
T
T
NSX100B/F/N/H/S/L
Micrologic
40
18
T
T
25
0.25
T
T
T
40
0.4
T
T
T
T
80
0.63
T
T
T
T
T
T
200
2
T
T
T
T
T
T
T
T
T
T
80
1
T
T
T
T
T
T
100
1
T
T
T
T
T
T
125
1
T
T
T
T
T
T
T
NSX160B/F/N/H/S/L
Micrologic
100
40
0.4
T
T
T
T
63
0.63
T
T
T
T
T
80
0.8
T
T
T
T
T
T
100
1
T
T
T
T
T
T
160
63
0.63
T
T
T
T
T
NSX400F/N/H/S/L
Micrologic
400
160
1.6
T
T
T
T
T
T
T
T
T
100
0.8
T
T
T
T
T
T
80
0.8
T
T
T
T
T
T
100
1
T
T
T
T
T
T
NSX250B/F/N/H/S/L
TM-D
160
1
T
T
T
T
T
T
T
160
1
T
T
T
T
T
T
T
200
2
T
T
T
T
T
T
T
T
T
T
T
250
2.5
T
T
T
T
T
T
T
T
T
T
T
NSX250B/F/N/H/S/L
Micrologic
125
1.25
T
T
T
T
T
T
T
160
1.6
T
T
T
T
T
T
T
250
100
1
T
T
T
T
T
T
125
1.25
T
T
T
T
T
T
T
160
1.6
T
T
T
T
T
T
T
T
T
200
2
T
T
T
T
T
T
T
T
T
T
250
2.5
T
T
T
T
T
T
T
T
T
T
T
NSX630F/N/H/S/L
Micrologic
250
2.5
T
T
T
T
T
T
T
T
T
T
T
320
3.2
T
T
T
T
T
T
T
T
T
T
T
T
400
4
T
T
T
T
T
T
T
T
T
T
T
T
T
630
250
2.5
T
T
T
T
T
T
T
T
T
T
T
320
3.2
T
T
T
T
T
T
T
T
T
T
T
T
400
4
T
T
T
T
T
T
T
T
T
T
T
T
T
500
5
T
T
T
T
T
T
T
T
T
T
T
T
T
630
6.3
T
T
T
T
T
T
T
T
T
T
T
T
T
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
82
Livre 1.indb 82
04/11/2009 15:56:54
Discrimination tables
Complementary
technical information
DB125662
I ON
O
OFF
test
gG
Downstream
NSX100
TM-D
Rating (A)
16
25
32
40
50
63
80
100
y 63
80
100
125
160
y 100
125
160
200
250
40
100
40
100
160
100
160
250
160
200
250
320
400
400
630
NSX160
TM-D
NSX250
TM-D
NSX100
Micrologic
NSX160
Micrologic
NSX250
Micrologic
NSX400
Micrologic
NSX630
Micrologic
160
2.5
2.5
2.5
2.5
2.5
2.5
200
4
4
4
4
4
4
4
250
7
7
7
7
7
7
7
7
7
7
315
15
15
15
15
15
15
15
15
15
15
355
T
T
T
T
T
T
T
T
T
T
T
400
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
4
4
10
10
7
7
7
T
T
8
8
8
T
T
T
T
T
10
10
450
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
500
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
6
6
6
6
6
560
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
7
7
7
7
7
630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
9
9
9
9
9
670
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
10
10
10
10
10
710
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
12
12
750
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
15
15
800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
30
30
1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Table key
T
Total discrimination
16
Discrimination limit in kA
No discrimination
DB125663
O
OFF
test
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
83
Livre 1.indb 83
04/11/2009 15:56:56
84
Livre 1.indb 84
04/11/2009 15:56:57
Complementary
technical information
Cascading
What is cascading?
Cascading is the use of the current limiting capacity of circuit breakers at a given
point to permit installation of lower-rated and therefore lower-cost circuit breakers
downstream.
The upstream Compact circuit breakers acts as a barrier against short-circuit
currents. In this way, downstream circuit breakers with lower breaking capacities
than the prospective short-circuit (at their point of installation) operate under their
normal breaking conditions.
Since the current is limited throughout the circuit controlled by the limiting circuit
breaker, cascading applies to all switchgear downstream. It is not restricted to two
consecutive devices.
Cascading tables
Schneider Electric cascading tables are:
b drawn up on the basis of calculations (comparison between the energy limited by
the upstream device and the maximum permissible thermal stress for the
downstream device)
b verified experimentally in accordance with IEC standard 60947-2.
For distribution systems with 220/240 V, 400/415 V and 440 V between phases,
the tables of the following pages indicate cascading possibilities between upstream
Compact and downstream Multi 9 and Compact circuit breakers as well as between
upstream Masterpact and downstream Compact circuit breakers.
85
Livre 1.indb 85
04/11/2009 15:56:58
Cascading
Complementary
technical information
Contents
Application
Distribution cascading
Network
220/240 V
380/415 V
440 V
Cascading and enhanced discrimination
220/240 V
Upstream device
Multi 9
Compact
Compact and Masterpact
Multi 9
Compact
Compact and Masterpact
Compact
Compact and Masterpact
Compact
380/415 V
NSC100N, NG160E/N
Compact
440 V
Compact
Downstream device
Multi 9
Compact and Multi 9
Compact
Multi 9
Compact and Multi 9
Compact
Compact and Multi 9
Compact
Multi 9
NG160N, NSC100N
Compact
Multi 9
Multi 9
NG160N, NSC100N
Compact
Compact
Table page
88
89
91
92
93
95
96
97
99
103
105
106
110
112
86
Livre 1.indb 86
04/11/2009 15:56:58
Cascading
DB120605
DB120606
DB120607
Complementary
technical information
DB120608
Livre 1.indb 87
04/11/2009 15:56:59
Complementary
technical information
Upstream
iDPNN
C60N
C60H
10
20
30
Downstream
Breaking capacity (kA rms)
iDPN
10
15
20
(130 V between phase and neutral)
iDPNN
20
30
(130 V between phase and neutral)
C60N
30
C60H
C60L y 25 A
C60L 32 A and 40 A
C60L 50 A and 63 A
C120N
30
C120H
NG125N
NG125H
C60L
y 25 A
50
32/40 A
40
50/63 A
30
30
25
50
50
50
50
50
C120N
C120H
NG125N
NG125H
NG125L
20
30
50
70
100
20
15
20
20
40
50
40
30
20
30
30
40
50
40
40
30
30
50
50
50
70
70
70
70
50
70
100
100
70
70
70
70
100
40
30
50
50
50
50
88
Livre 1.indb 88
04/11/2009 15:57:00
Cascading 220/240 V
Complementary
technical information
Upstream
Breaking capacity (kA rms)
NG160E
25
NG160H
50
NSC100N NSX100B
42
40
Downstream
Reinforced breaking capacity (kA rms)
iDPN
(130 V between phase and neutral)
iDPNN
(130 V between phase and neutral)
C60N
25
40
50
40
C60H
40
50
42
C60L y 25 A
40
50
C60L 32 A and 40 A
40
50
42
C60L 50 A and 63 A
40
50
42
C120N
40
40
42
C120H
40
40
42
NG125N
NG125H
NG125L
NG160E
50
NG160N
NG160H
NSC100N
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
Upstream
Breaking capacity ( rms)
Downstream
iDPN
(130 V between phase and neutral)
iDPNN
(130 V between phase and neutral)
C60N
C60H
C60L y 25 A
C60L 32 A and 40 A
C60L 50 A and 63 A
C120N
C120H
NG125N
NG125H
NG125L
NG160E
NG160N
NG160H
NSC100N
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
NSX160B
NSX160F
NSX160N
NSX160H
NSX160S
NSX160B
40
NSX100N
90
NSX100H
100
NSX100S
120
NSX100L
150
20
20
20
20
20
20
30
30
30
30
30
30
40
40
40
50
65
65
65
40
40
60
85
60
80
80
80
80
50
50
70
85
60
80
80
80
80
50
50
70
85
60
80
80
80
80
70
70
85
100
120
60
80
80
80
80
70
70
85
100
150
85
85
90
90
90
100
90
100
100
100
100
120
120
120
100
100
150
150
150
150
40
40
40
NSX160H
100
NSX160S
120
NSX160L
150
20
20
20
30
30
30
30
30
30
40
40
40
50
65
65
65
40
40
60
85
60
80
80
80
80
50
50
70
85
60
80
80
80
80
50
50
70
85
50
85
85
85
85
50
90
90
90
90
90
50
100
100
100
90
100
100
60
80
80
80
80
70
70
85
100
120
60
100
100
100
100
120
120
120
85
90
90
90
100
100
60
80
80
80
80
70
70
85
100
150
60
100
100
100
100
150
150
150
150
100
150
150
150
150
40
40
40
40
NSX160F
85
NSX100F
85
NSX160N
90
100
120
120
120
89
Livre 1.indb 89
04/11/2009 15:57:01
Cascading 220/240 V
Complementary
technical information
Upstream
Breaking capacity (kA rms)
Downstream
iDPN
(130 V between phase and neutral)
iDPNN
(130 V between phase and neutral)
C60N
C60H
C60L y 25 A
C60L 32 A and 40 A
C60L 50 A and 63 A
C120N
C120H
NG125N
NG125H
NG125L
NG160E
NG160N
NG160H
NSC100N
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
NSX160B
NSX160F
NSX160N
NSX160H
NSX160S
NSX250B
NSX250F
NSX250N
NSX250H
NSX250S
NSX250B
40
NSX250S
120
NSX250L
150
20
20
20
30
30
30
30
30
30
40
40
40
50
65
65
50
40
40
60
85
60
65
80
80
65
50
50
70
85
60
65
80
80
65
50
50
70
85
50
85
85
85
85
50
90
90
90
90
90
50
100
100
100
90
100
100
60
65
80
80
65
70
70
85
100
120
60
100
100
100
100
120
120
120
85
90
90
90
100
100
100
120
120
120
85
90
90
90
100
100
100
120
120
120
60
65
80
80
65
70
70
85
100
150
60
100
100
100
100
150
150
150
150
100
150
150
150
150
100
150
150
150
150
40
40
40
40
NSX250F
85
NSX250N
90
90
Livre 1.indb 90
04/11/2009 15:57:01
Cascading 220/240 V
Complementary
technical information
Upstream
NSX400F
Breaking capacity 40
(kA rms)
Downstream
NG160E
NG160N
NG160H
NSC100N
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
NSX160B
NSX160F
NSX160N
NSX160H
NSX160S
NSX250B
NSX250F
NSX250N
NSX250H
NSX250S
NSX400F
NSX400N
NSX400H
NSX400S
NSX630F
NSX630N
NSX630H
NSX630S
Upstream
NSX400H
100
NS630bL
NSX400N
85
NSX400L
150
NSX630F
40
NSX630N
85
NSX630H
100
NSX630S
120
NSX630L
150
60
100
100
100
100
120
120
120
60
100
100
100
100
150
150
150
150
100
150
150
150
150
100
150
150
150
150
150
150
150
150
40
40
40
40
50
85
85
85
85
50
90
90
90
90
100
100
60
100
100
100
100
120
120
120
85
90
100
100
100
120
120
120
85
90
100
100
100
120
120
120
85
100
100
100
85
100
100
100
120
120
120
120
120
120
120
120
60
100
100
100
100
150
150
150
150
100
150
150
150
150
100
150
150
150
150
150
150
150
150
150
150
150
150
85
90
100
100
100
120
120
120
85
90
100
100
100
120
120
120
85
100
100
120
120
120
NS630LB
NS800L
NS800LB
NS1000L
200
150
200
150
Masterpact Masterpact
NT L1
NW L1
150
150
50
150
150
150
200
200
50
150
150
150
200
200
50
150
150
150
200
200
150
150
150
200
200
150
150
150
200
200
50
150
150
150
150
50
150
150
150
150
50
150
150
150
150
50
150
150
150
150
50
150
150
150
150
50
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
100
100
91
Livre 1.indb 91
04/11/2009 15:57:02
Complementary
technical information
Upstream
C60N
iDPNN
10
C60L
y 25 A
25
Downstream
Breaking capacity (kA rms)
iDPN
10 kA
10 kA
20 kA
(230 V between phase and neutral)
iDPNN
15
25
(230 V between phase and neutral)
C60N
15
25
C60H
25
C60L y 25 A
C60L 32 A and 40 A
C60L 50 A and 63 A
C120N
C120H
NG125N
NG125H
C120N
C120H
NG125N
NG125H
NG125L
10
15
25
36
50
10 kA
10 kA
10 kA
15 kA
20 kA
15
15
15
20
25
15
15
25
25
25
36
36
36
36
25
25
36
25
36
50
50
36
36
36
36
50
32/40 A
20
50/63 A
15
15 kA
10 kA
20
20
15
15
25
25
25
25
92
Livre 1.indb 92
04/11/2009 15:57:02
Complementary
technical information
Upstream
Breaking capacity (kA rms)
Downstream
iDPN
(230 V between phase and neutral)
iDPNN
(230 V between phase and neutral)
C60N
C60H
C60L y 25 A
C60L 32 A and 40 A
C60L 50 A and 63 A
C120N
C120H
NG125N
NG125H
NG125L
NSC100N
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
Upstream
Breaking capacity (kA rms)
Downstream
iDPN
(230 V between phase and neutral)
iDPNN
(230 V between phase and neutral)
C60N
C60H y 40 A
C60H 50 A and 63 A
C60L y 25 A
C60L 32 A and 40 A
C60L 50 A and 63 A
C120N
C120H
NG125N
NG125H
NG125L
NG160E
NG160N
NG160H
NSC100N
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
NSX160B
NSX160F
NSX160N
NSX160H
NSX160S
NG160E
16
NSX100B
25
NSX100F
36
NSX100N
50
NSX100H
70
NSX100S
100
NSX100L
150
10
10
10
10
10
10
15
15
15
15
15
15
15
15
15
15
15
15
20
25
25
25
25
25
25
25
25
18
18
20
25
18
18
18
25
25
25
25
25
36
36
36
36
25
25
36
30
40
40
40
40
25
25
36
40
36
36
50
36
50
30
40
40
40
40
25
25
36
50
70
50
50
70
70
30
40
40
40
40
25
25
50
70
100
50
50
100
100
100
30
40
40
40
40
25
25
70
100
150
50
50
150
150
150
150
25
25
25
25
NG160H
36
NSC100N
18
25
NSX160B
25
NSX160F
36
NSX160N
50
NSX160H
70
NSX160S
100
NSX160L
150
10
10
10
10
10
10
15
15
15
15
15
15
20
25
25
25
36
30
36
36
30
25
25
36
30
40
30
40
40
30
25
25
36
40
50
30
36
50
50
36
50
30
40
30
40
40
30
25
25
36
50
70
30
50
50
50
50
70
70
30
40
30
40
40
30
25
25
50
70
100
30
50
50
50
50
100
100
100
36
50
50
70
70
50
100
100
100
30
40
30
40
40
30
25
25
70
100
150
30
50
50
50
50
150
150
150
150
50
150
150
150
150
25
25
25
25
25
25
36
25
36
36
36
93
Livre 1.indb 93
04/11/2009 15:57:02
Complementary
technical information
Upstream
Breaking capacity (kA rms)
Downstream
iDPN
(230 V between phase and neutral)
iDPNN
(230 V between phase and neutral)
C60N y 40 A
C60N 50 A and 63 A
C60H y 40 A
C60H 50 A and 63 A
C60L y 25 A
C60L 32 A and 40 A
C60L 50 A and 63 A
C120N
C120H
NG125N
NG125H
NG125L
NG160E
NG160N
NG160H
NSC100N
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
NSX160B
NSX160F
NSX160N
NSX160H
NSX160S
NSX250B
NSX250F
NSX250N
NSX250H
NSX250S
Upstream
NSX400F
Breaking capacity 36
(kA rms)
Downstream
NG160E
NG160N
NG160H
NSC100N
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
NSX160B
NSX160F
NSX160N
NSX160H
NSX160S
NSX250B
NSX250F
NSX250N
NSX250H
NSX250S
NSX400F
NSX400N
NSX400H
NSX400S
NSX630F
NSX630N
NSX630H
NSX630S
NSX250B
25
NSX250H
70
NSX250S
100
NSX250L
150
10
10
10
15
15
15
15
15
15
20
20
25
25
25
25
25
25
25
25
25
30
25
30
30
25
25
25
36
25
25
36
25
36
36
30
25
30
25
30
30
25
25
25
36
40
50
30
36
50
50
36
50
30
25
30
25
30
30
25
25
25
36
50
70
30
50
50
50
50
70
70
30
25
30
25
30
30
25
25
25
50
70
100
30
50
50
50
50
100
100
100
36
36
50
50
70
70
50
100
100
100
36
36
50
50
70
70
50
100
100
100
30
25
30
25
30
30
25
25
25
70
100
150
30
50
50
50
50
150
150
150
150
50
150
150
150
150
50
150
150
150
150
NSX400N
50
NSX250F
36
NSX400H
70
NSX250N
50
NSX400S
100
NSX400L
150
NSX630F
36
NSX630N
50
NSX630H
70
NSX630S
100
NSX630L
150
30
50
50
50
50
100
100
100
30
50
50
50
50
150
150
150
150
50
150
150
150
150
50
150
150
150
150
150
150
150
150
25
25
36
50
50
36
50
30
50
50
50
50
70
70
30
50
50
50
50
100
100
100
36
36
50
50
70
70
50
100
100
100
36
36
50
50
70
70
50
100
100
100
50
70
70
100
100
100
50
70
70
100
100
100
30
50
50
50
50
150
150
150
150
50
150
150
150
150
50
150
150
150
150
150
150
150
150
150
150
150
150
36
36
50
50
70
70
50
100
100
100
36
36
50
50
70
70
50
100
100
100
50
70
70
100
100
100
36
94
558E4200.indd 94
20/11/2009 14:11:40
Complementary
technical information
Upstream
NS630bN
NS630b NS630b NS630b NS800 NS800 NS800 NS1000 NS1000 NS1250H NS2000N Masterpact Masterpact
to NS1600N H
L
LB
H
L
LB
H
L
NS1600H NS2500N NT L1
NW L1
NS3200N
Breaking capacity 50
70
150
200
70
150
70
150
70
70
150
150
(kA rms)
Downstream
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
NSX100L
NSX160B
NSX160F
NSX160N
NSX160H
NSX160S
NSX160L
NSX250B
NSX250F
NSX250N
NSX250H
NSX250S
NSX250L
NSX400F
NSX400N
NSX400H
NSX400S
NSX400L
NSX630F
NSX630N
NSX630H
NSX630S
NSX630L
NS630bN
NS630bH
NS800N
NS800H
NS1000N
NS1000H
NS1250N
NS1600N
50
70
70
50
150
150
150
150
50
70
70
50
150
150
150
150
50
70
70
50
150
150
150
150
70
70
150
150
150
150
70
70
150
150
150
150
70
150
150
150
150
70
50
150
150
150
200
200
50
150
150
150
200
200
50
150
150
150
200
200
150
150
150
200
200
150
150
150
200
200
200
200
200
200
200
200
50
70
70
50
150
150
150
150
50
70
70
50
150
150
150
150
50
70
70
50
150
150
150
150
50
70
70
50
150
150
150
150
50
70
70
50
150
150
150
150
50
70
70
50
150
150
150
150
70
70
150
150
150
150
70
70
150
150
150
150
70
70
150
150
150
150
70
70
150
150
150
150
70
150
150
150
150
150
150
70
70
70
70
70
70
70
70
70
70
70
150
150
150
150
150
150
65
65
65
65
65
95
Livre 1.indb 95
04/11/2009 15:57:04
Complementary
technical information
Upstream
NSX100B NSX100F NSX100N NSX100H NSX100S NSX100L NSX160B NSX160F NSX160N NSX160H NSX160S NSX160L
Breaking capacity 20
35
50
65
90
130
20
35
50
65
90
130
(kA rms)
Downstream
C60N
C60H
C60L y 25 A
C60L 32 A and 40 A
NG160E
NG160N
NG160H
NSC100N
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
NSX160B
NSX160F
NSX160N
NSX160H
NSX160S
20
50
35
50
50
50
65
65
20
25
25
25
50
50
90
90
90
50
50
130
130
130
130
15
20
15
20
20
20
20
20
35
20
35
35
35
Upstream
NSX250B
Breaking capacity 20
( rms)
Downstream
NG160E
NG160N
NG160H
NSC100N
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
NSX160B
NSX160F
NSX160N
NSX160H
NSX160S
NSX250B
NSX250F
NSX250N
NSX250H
NSX250S
35
35
20
25
25
25
NSX250F
35
20
25
25
25
30
50
50
50
50
65
65
20
25
25
25
30
50
50
50
50
90
90
90
35
50
50
65
65
50
90
90
90
NSX250N
50
NSX250H
65
NSX250S
90
NSX250L
130
30
35
50
50
35
50
30
50
50
50
50
65
65
30
50
50
50
50
90
90
90
35
35
50
50
65
65
50
90
90
90
35
35
50
50
65
65
50
90
90
90
30
50
50
50
50
130
130
130
130
50
130
130
130
130
50
130
130
130
130
20
25
25
25
30
35
50
50
35
50
35
35
20
25
25
25
30
50
50
50
50
130
130
130
130
50
130
130
130
130
96
Livre 1.indb 96
04/11/2009 15:57:04
Complementary
technical information
Upstream
NSX400F
Breaking capacity 30
( rms)
Downstream
NG160E
NG160N
NG160H
NSC100N
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
NSX160B
NSX160F
NSX160N
NSX160H
NSX160S
NSX250B
NSX250F
NSX250N
NSX250H
NSX250S
NSX400F
NSX400N
NSX400H
NSX400S
NSX630F
NSX630N
NSX630H
NSX630S
NSX400N
42
NSX400S
90
NSX400L
130
NSX630F
30
NSX630N
42
NSX630H
65
NSX630S
90
NSX630L
130
30
50
50
50
50
90
90
90
30
50
50
50
50
130
130
130
130
50
130
130
130
130
50
130
130
130
130
130
130
130
130
20
30
30
30
42
42
30
42
30
50
50
50
50
65
65
30
50
50
50
50
90
90
90
35
30
42
50
65
65
50
90
90
90
35
30
42
50
65
65
50
90
90
90
42
65
65
90
90
90
42
65
65
90
90
90
30
50
50
50
50
130
130
130
130
50
130
130
130
130
50
130
130
130
130
130
130
130
130
130
130
130
130
30
30
42
50
65
65
50
90
90
90
30
30
42
50
65
65
50
90
90
90
42
65
65
90
90
90
30
30
Upstream
NS630bN
NS630b NS630b NS630b NS800 NS800 NS800 NS1000 NS1000 NS1250H NS2000N Masterpact Masterpact
to NS1600N H
L
LB
H
L
LB
H
L
NS1600H NS2500N NT L1
NW L1
NS3200N
Breaking capacity 50
65
130
200
65
130
200
65
130
65
65
130
150
( rms)
Downstream
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
NSX100L
NSX160B
NSX160F
NSX160N
NSX160H
NSX160S
NSX160L
NSX250B
NSX250F
NSX250N
NSX250H
NSX250S
NSX250L
NSX400F
NSX400N
NSX400H
NSX400S
NSX400L
NSX630F
NSX630N
NSX630H
NSX630S
NSX630L
NS630bN
NS630bH
NS800N
NS800H
NS1000N
NS1000H
NS1250N
NS1600N
50
65
65
50
130
130
130
130
50
65
65
50
130
130
130
130
50
65
65
50
130
130
130
130
65
65
130
130
130
130
65
65
130
130
130
130
65
130
130
130
130
65
50
130
130
130
200
200
50
130
130
130
200
200
50
130
130
130
200
200
130
130
130
200
200
130
130
130
200
200
200
200
200
200
50
65
65
50
130
130
130
130
50
65
65
50
130
130
130
130
50
65
65
50
130
130
130
130
50
65
65
50
130
130
130
130
50
65
65
50
130
130
130
130
50
65
65
50
130
130
130
130
65
65
130
130
130
130
65
65
130
130
130
130
65
65
130
130
130
130
65
65
130
130
130
130
65
130
130
130
130
130
130
65
65
65
65
65
65
65
65
65
65
130
130
130
130
130
130
65
65
65
65
65
97
Livre 1.indb 97
04/11/2009 15:58:54
Complementary
technical information
With traditional circuit breakers, cascading between two devices generally results in
the look of discrimination.
With Compact circuit breakers, the discrimination characteristics in the tables remain
applicable and are in some cases even enhanced. Protection discrimination is
ensured for short-circuit currents greater than the rated breaking capacity of the
circuit breaker and even, in some cases, for its enhanced breaking capacity. In the
later case, protection discrimination is total, i.e. only the downstream device trips
for any and all possible faults at its point in the installation.
Example
Consider a combination between:
b a Compact NSX250H with trip unit TM250D
b a Compact NSX100F with trip unit TM25D.
The discrimination tables indicate total discrimination. Protection discrimination is
therefore ensured up to the breaking capacity of the NSX100F, i.e. 36 kA.
The cascading tables indicate an enhanced breaking capacity of 70 kA.
The enhanced discrimination tables indicate that in a cascading configuration,
discrimination is ensured up to 70 kA, i.e. for any and all possible faults at that point
in the installation.
15 / 25
In a table, a box containing two equal values indicates that discrimination is provided
up to the reinforced breaking capacity of the downstream device.
These tables apply only to cases with combined discrimination and cascading
between two devices. For all other cases, refer to the normal cascading and
discrimination tables.
Technical principle
DB125677
NSX160F
TM160D
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
98
Livre 1.indb 98
04/11/2009 15:59:00
Complementary
technical information
C60H
30 kA
C60L
50 kA
40 kA
30 kA
C120N/H
20/30 kA
NG125N
50 kA
NG125H
70 kA
NSX160B
40 kA
TM-D
Rating
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63
y 16
20 - 25
32 - 40
50 - 63
80
100
125
y 16
20 - 25
32 - 40
50 - 63
80
100
125
y 16
20 - 25
32 - 40
50 - 63
80
80-100
NSX160F
85 kA
TM-D
125-160 80-100
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
NSX160N
90 kA
TM-D
NSX160H
100 kA
TM-D
NSX160S
120 kA
TM-D
NSX160L
150 kA
TM-D
125-160 80-100
40/40
40/40
40/40
40/40
40/40
40/40
40/40
50/50
50/50
50/50
50/50
50/50
50/50
50/50
65/65
65/65
65/65
65/65
65/65
65/65
65/65
40/40
40/40
40/40
125-160 80-100
60/60
60/60
60/60
60/60
60/60
60/60
60/60
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
50/50
50/50
50/50
125-160 80-100
60/60
60/60
60/60
60/60
60/60
60/60
60/60
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
50/50
50/50
50/50
125-160 80-100
60/60
60/60
60/60
60/60
60/60
60/60
60/60
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
70/70
70/70
70/70
125-160
60/60
60/60
60/60
60/60
60/60
60/60
60/60
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
70/70
70/70
70/70
60/60
60/60
60/60
70/70
70/70
70/70
70/70
70/70
70/70
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
100/100
100/100
100/100
100/100
100/100
100/100
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
99
Livre 1.indb 99
04/11/2009 15:59:02
Complementary
technical information
20 kA
C60H
30 kA
C60L
50 kA
40 kA
30 kA
C120N/H
20/30 kA
NG125N
50 kA
NG125H
70 kA
NSX250B
40 kA
TM-D
NSX250F
85 kA
TM-D
NSX250N
90 kA
TM-D
NSX250H
100 kA
TM-D
NSX250S
120 kA
TM-D
NSX250L
150 kA
TM-D
Rating
160/200/250
160/200/250
160/200/250
160/200/250
160/200/250
160/200/250
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63
y 16
20 - 25
32 - 40
50 - 63
80
100
125
y 16
20 - 25
32 - 40
50 - 63
80
100
125
y 16
20 - 25
32 - 40
50 - 63
80
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
50/50
50/50
50/50
50/50
50/50
50/50
50/50
65/65
65/65
65/65
65/65
65/65
50/50
50/50
40/40
40/40
40/40
40/40
40/40
40/40
60/60
60/60
60/60
60/60
60/60
60/60
60/60
65/65
65/65
65/65
65/65
65/65
65/65
65/65
80/80
80/80
80/80
80/80
80/80
65/65
65/65
50/50
50/50
50/50
50/50
50/50
50/50
60/60
60/60
60/60
60/60
60/60
60/60
60/60
65/65
65/65
65/65
65/65
65/65
65/65
65/65
80/80
80/80
80/80
80/80
80/80
65/65
65/65
50/50
50/50
50/50
50/50
50/50
50/50
60/60
60/60
60/60
60/60
60/60
60/60
60/60
65/65
65/65
65/65
65/65
65/65
65/65
65/65
80/80
80/80
80/80
80/80
80/80
65/65
65/65
70/70
70/70
70/70
70/70
70/70
70/70
60/60
60/60
60/60
60/60
60/60
60/60
60/60
65/65
65/65
65/65
65/65
65/65
65/65
65/65
80/80
80/80
80/80
80/80
80/80
65/65
65/65
70/70
70/70
70/70
70/70
70/70
70/70
60/60
60/60
60/60
60/60
60/60
60/60
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
85/85
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
100
04/11/2009 15:59:03
Complementary
technical information
C60H
30 kA
C60L
50 kA
40 kA
30 kA
Rating
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63
Upstream
Breaking capacity
Trip unit
Downstream
C60N
20 kA
C60H
30 kA
C60L
50 kA
40 kA
30 kA
Rating
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63
NSX100B
40 kA
Micrologic
NSX100F
85 kA
Micrologic
NSX100N
90 kA
Micrologic
NSX100H
100 kA
Micrologic
NSX100S
120 kA
Micrologic
NSX100L
150 kA
Micrologic
40
40/40
40/40
40/40
100
40/40
40/40
40/40
40/40
40/40
40
40/40
40/40
40/40
100
40/40
40/40
40/40
40/40
40/40
40
60/60
60/60
60/60
100
60/60
60/60
60/60
60/60
60/60
40
60/60
60/60
60/60
100
60/60
60/60
60/60
60/60
60/60
40
60/60
60/60
60/60
100
60/60
60/60
60/60
60/60
60/60
40
60/60
60/60
60/60
100
60/60
60/60
60/60
60/60
60/60
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
65/65
65/65
65/65
65/65
65/65
65/65
65/65
65/65
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
NSX160B
40 kA
Micrologic
NSX160F
85 kA
Micrologic
NSX160N
90 kA
Micrologic
NSX160H
100 kA
Micrologic
NSX160S
120 kA
Micrologic
NSX160L
150 kA
Micrologic
80
40/40
40/40
40/40
40/40
40/40
40/40
80
40/40
40/40
40/40
40/40
40/40
40/40
80
60/60
60/60
60/60
60/60
60/60
60/60
80
60/60
60/60
60/60
60/60
60/60
60/60
80
60/60
60/60
60/60
60/60
60/60
60/60
80
60/60
60/60
60/60
60/60
60/60
60/60
40/40
40/40
40/40
40/40
40/40
40/40
40/40
160
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
50/50
50/50
50/50
50/50
50/50
50/50
65/65
65/65
65/65
65/65
65/65
65/65
160
40/40
40/40
40/40
40/40
40/40
40/40
40/40
50/50
50/50
50/50
50/50
50/50
50/50
50/50
65/65
65/65
65/65
65/65
65/65
65/65
65/65
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
160
60/60
60/60
60/60
60/60
60/60
60/60
60/60
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
160
60/60
60/60
60/60
60/60
60/60
60/60
60/60
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
160
60/60
60/60
60/60
60/60
60/60
60/60
60/60
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
160
60/60
60/60
60/60
60/60
60/60
60/60
60/60
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
80/80
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
101
558E4200.indd 101
20/11/2009 14:18:40
Complementary
technical information
Upstream
Breaking capacity
Trip unit
Downstream
C60N
20 kA
C60H
30 kA
C60L
50 kA
40 kA
30 kA
C120N/H
20/30 kA
NG125N
50 kA
NG125H
70 kA
Rating
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63
y 16
20 - 25
32 - 40
50 - 63
80
100
125
y 16
20 - 25
32 - 40
50 - 63
80
100
125
y 16
20 - 25
32 - 40
50 - 63
80
NSX250B
40 kA
Micrologic
NSX250F
85 kA
Micrologic
NSX250N
90 kA
Micrologic
NSX250H
100 kA
Micrologic
NSX250S
150 kA
Micrologic
NSX250L
150 kA
Micrologic
250
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
250
40/40
40/40
40/40
40/40
40/40
40/40
40/40
50/50
50/50
50/50
50/50
50/50
50/50
50/50
65/65
65/65
65/65
65/65
65/65
65/65
65/65
40/40
40/40
40/40
40/40
40/40
40/40
40/40
60/60
60/60
60/60
60/60
60/60
60/60
60/60
85/85
85/85
85/85
85/85
85/85
250
60/60
60/60
60/60
60/60
60/60
60/60
60/60
65/65
65/65
65/65
65/65
65/65
65/65
65/65
80/80
80/80
80/80
80/80
80/80
65/65
65/65
50/50
50/50
50/50
50/50
50/50
50/50
50/50
70/70
70/70
70/70
70/70
70/70
70/70
70/70
85/85
85/85
85/85
85/85
85/85
250
60/60
60/60
60/60
60/60
60/60
60/60
60/60
65/65
65/65
65/65
65/65
65/65
65/65
65/65
80/80
80/80
80/80
80/80
80/80
65/65
65/65
50/50
50/50
50/50
50/50
50/50
50/50
50/50
70/70
70/70
70/70
70/70
70/70
70/70
70/70
85/85
85/85
85/85
85/85
85/85
250
60/60
60/60
60/60
60/60
60/60
60/60
60/60
65/65
65/65
65/65
65/65
65/65
65/65
65/65
80/80
80/80
80/80
80/80
80/80
65/65
65/65
70/70
70/70
70/70
70/70
70/70
70/70
70/70
85/85
85/85
85/85
85/85
85/85
85/85
85/85
100/100
100/100
100/100
100/100
100/100
250
60/60
60/60
60/60
60/60
60/60
60/60
60/60
65/65
65/65
65/65
65/65
65/65
65/65
65/65
80/80
80/80
80/80
80/80
80/80
65/65
65/65
70/70
70/70
70/70
70/70
70/70
70/70
70/70
85/85
85/85
85/85
85/85
85/85
85/85
85/85
100/100
100/100
100/100
100/100
100/100
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
102
04/11/2009 15:59:04
Complementary
technical information
25 kA
50 kA
42 kA
40 kA
NSX100F
85 kA
NSX100N
90 kA
NSX100H
100 kA
NSX100S
120 kA
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
40 kA
85 kA
90 kA
100 kA
120 kA
NSX250F
85 kA
TM-D
Rating
TM-D y 25
TM-D 40 - 100
TM-D y 25
TM-D 40 - 100
TM-D y 25
TM-D 40 - 100
TM-D y 25
TM-D 40 - 100
TM-D y 25
TM-D 40 - 100
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Upstream
Breaking capacity
Trip unit
Downstream
NG160E
50 kA
NG160N/H
NSC100N
42 kA
NSX100B
40 kA
NSX100F
85 kA
NSX100N
90 kA
NSX100H
100 kA
NSX100S
120 kA
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
40 kA
85 kA
90 kA
100 kA
120 kA
160
NSX250N
90 kA
TM-D
200-250
40/40
85/85
85/85
85/85
36/85
36/85
NSX250F
85 kA
Micrologic
Rating
TM-D y 25
TM-D 40 - 100
TM-D y 25
TM-D 40 - 100
TM-D y 25
TM-D 40 - 100
TM-D y 25
TM-D 40 - 100
TM-D y 25
TM-D 40 - 100
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
160
NS250H
100 kA
TM-D
200-250
50/50
90/90
90/90
90/90
36/90
90/90
36/90
160
36/90
36/90
NSX250N
90 kA
Micrologic
NSX250S
120 kA
TM-D
200-250
50/50
100/100
100/100
100/100
36/100
100/100
36/100
100/100
36/100
160
36/100
36/100
36/100
NS250H
100 kA
Micrologic
NSX250L
150 kA
TM-D
200-250
60/60
100/100
100/100
100/100
36/120
120/120
36/120
120/120
36/120
120/120
36/120
160
36/120
36/120
36/120
36/120
NSX250S
120 kA
Micrologic
200-250
60/60
100/100
100/100
100/100
36/150
150/150
36/150
150/150
36/150
150/150
36/150
150/150
36/150
36/100
36/150
36/150
36/150
36/150
NSX250L
150 kA
Micrologic
160
40/40
85/85
85/85
85/85
36/85
200-250
40/40
85/85
85/85
85/85
36/85
160
50/50
90/90
90/90
90/90
36/90
90/90
36/90
200-250
50/50
90/90
90/90
90/90
36/90
90/90
36/90
160
50/50
100/100
100/100
100/100
36/100
100/100
36/100
100/100
36/100
200-250
50/50
100/100
100/100
100/100
36/100
100/100
36/100
100/100
36/100
160
60/60
100/100
100/100
100/100
36/120
120/120
36/120
120/120
36/120
120/120
36/120
200-250
60/60
100/100
100/100
100/100
36/120
120/120
36/120
120/120
36/120
120/120
36/120
36/85
36/85
36/90
36/90
36/90
36/90
36/100
36/100
36/100
36/100
36/100
36/100
36/100
36/120
36/120
36/120
36/100
36/120
36/120
36/120
160
60/60
100/100
100/100
100/100
36/150
150/150
36/150
150/150
36/150
150/150
36/150
150/150
36/150
36/100
36/150
36/150
36/150
36/150
200-250
60/60
100/100
100/100
100/100
36/150
150/150
36/150
150/150
36/150
150/150
36/150
150/150
36/150
36/100
36/150
36/150
36/150
36/150
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
103
04/11/2009 15:59:05
Complementary
technical information
NSX400N NSX400H NSX400S NSX400L NSX630N NSX630H NSX630S NSX630L NS800L NS800LB NS1000L
85 kA
100 kA
120 kA
150 kA
85 kA
100 kA
120 kA
150 kA
150 kA
200 kA
150 kA
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
400
50/50
85/85
85/85
85/85
400
50/50
90/90
90/90
90/90
90/90
100/100
400
60/60
100/100
100/100
100/100
120/120
120/120
120/120
400
60/60
100/100
100/100
100/100
150/150
150/150
150/150
150/150
400
50/50
85/85
85/85
85/85
400
50/50
90/90
90/90
90/90
90/90
100/100
400
60/60
100/100
100/100
100/100
120/120
120/120
120/120
400
60/60
100/100
100/100
100/100
150/150
150/150
150/150
150/150
800
50/50
150/150
150/150
150/150
150/150
85/85
90/90
90/90
100/100
100/100
120/120
120/120
120/120
100/100
150/150
150/150
150/150
150/150
85/85
90/90
90/90
100/100
100/100
120/120
120/120
120/120
100/100
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
85/85
90/90
90/90
100/100
100/100
120/120
120/120
120/120
100/100
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
85/85
90/90
90/90
100/100
100/100
120/120
120/120
120/120
100/100
150/150
150/150
150/150
150/150
85/85
90/90
90/90
100/100
100/100
120/120
120/120
120/120
100/100
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
85/85
90/90
90/90
100/100
100/100
120/120
120/120
120/120
100/100
150/150
150/150
150/150
150/150
85/85
90/90
90/90
100/100
100/100
120/120
120/120
120/120
100/100
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
85/85
90/90
90/90
100/100
100/100
120/120
120/120
120/120
100/100
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
10/150
10/150
10/150
10/150
1000
50/50
150/150
150/150
150/150
200/200
200/200
50/50
150/150
150/150
150/150
200/200
200/200
50/50
150/150
150/150
150/150
200/200
200/200
50/50
150/150
150/150
150/150
200/200
200/200
50/50
150/150
150/150
150/150
200/200
200/200
50/50
150/150
150/150
150/150
200/200
200/200
10/150
10/150
10/150
10/200
10/200
50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
15/150
15/150
15/150
15/150
10/150
10/150
10/150
10/150
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
104
04/11/2009 15:59:06
Complementary
technical information
NSC100N
18 kA
TM-D
Rating
y 16
20
25
32
40
50
63
Upstream
Breaking capacity
Trip unit
Downstream
C60N
10 kA
C60H
15 kA
C60L
25 kA
20 kA
15 kA
63
18/18
18/18
18/18
6/18
70
18/18
18/18
18/18
6/18
6/18
80
18/18
18/18
18/18
6/18
6/18
6/18
100
18/18
18/18
18/18
8/18
8/18
6/18
6/18
NG160E
16 kA
TM-D
Rating
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63
63
15/15
15/15
15/15
6/15
NG160N
25 kA
TM-D
80
15/15
15/15
15/15
6/15
6/15
6/15
100
15/15
15/15
15/15
8/15
8/15
6/15
6/15
125
15/15
15/15
15/15
8/15
8/15
6/15
6/15
160
15/15
15/15
15/15
8/15
8/15
6/15
6/15
63
15/25
15/25
15/25
6/25
80
15/25
15/25
15/25
6/25
6/25
6/25
15/25
15/25
15/25
6/25
15/25
15/25
15/25
6/25
6/25
6/25
15/25
15/25
15/25
6/25
15/25
15/25
15/25
6/25
6/25
6/25
100
15/25
15/25
15/25
8/25
8/25
6/25
6/25
25/25
25/25
25/25
8/25
8/25
6/25
6/25
25/25
25/25
25/25
8/25
8/25
6/25
6/25
125
15/25
15/25
15/25
8/25
8/25
6/25
6/25
25/25
25/25
25/25
8/25
8/25
6/25
6/25
25/25
25/25
25/25
8/25
8/25
6/25
6/25
160
15/25
15/25
15/25
8/25
8/25
6/25
6/25
25/25
25/25
25/25
8/25
8/25
6/25
6/25
25/25
25/25
25/25
8/25
8/25
6/25
6/25
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
105
04/11/2009 15:59:07
Complementary
technical information
C60H
C60L
C120N/H
NG125N
NG125H
NG125L
Rating
y 16
20
25
32
40
50
63
15 kA
y 16
20
25
32
40
50
63
25 kA
y 16
20
25
20 kA
32
40
15 kA
50
63
10/15 kA y 16
20 - 25
32 - 40
50 - 63
80
100
125
25 kA
y 16
20 - 25
32 - 40
50 - 63
80
100
125
36 kA
y 16
20 - 25
32 - 40
50 - 63
80
50 kA
y 16
20 - 25
32 - 40
50 - 63
80
NSX160B
25 kA
TM-D
80-100
NSX160F
36 kA
TM-D
125- 160 80-100
20/20
20/20
20/20
20/20
20/20
20/20
20/20
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
NSX160N
50 kA
TM-D
NSX160H
70 kA
TM-D
NSX160S
100 kA
TM-D
NSX160L
150 kA
TM-D
125- 160
30/30
30/30
30/30
30/30
30/30
30/30
30/30
40/40
40/40
40/40
40/40
40/40
30/30
30/30
40/40
40/40
40/40
40/40
40/40
40/40
40/40
25/25
25/25
25/25
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
70/70
70/70
70/70
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
100/100
100/100
100/100
70/70
70/70
70/70
100/100
100/100
100/100
150/150
150/150
150/150
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
106
04/11/2009 15:59:08
Complementary
technical information
10 kA
C60H
15 kA
C60L
25 kA
20 kA
15 kA
C120N/H
10/15 kA
NG125N
25 kA
NG125H
36 kA
NG125L
50 kA
NSX250B
25 kA
TM-D
NSX250F
36 kA
TM-D
NSX250N
50 kA
TM-D
NSX250H
70 kA
TM-D
NSX250S
100 kA
TM-D
NSX250L
150 kA
TM-D
Rating
200/250
200/250
200/250
200/250
200/250
200/250
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63
y 16
20 - 25
32 - 40
50 - 63
80
100
125
y 16
20 - 25
32 - 40
50 - 63
80
100
125
y 16
20 - 25
32 - 40
50 - 63
80
y 16
20 - 25
32 - 40
50 - 63
80
20/20
20/20
20/20
20/20
20/20
20/20
20/20
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
30/30
30/30
30/30
30/30
30/30
25/25
25/25
30/30
30/30
30/30
30/30
30/30
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
36/36
36/36
36/36
36/36
36/36
36/36
36/36
30/30
30/30
30/30
30/30
30/30
25/25
25/25
30/30
30/30
30/30
30/30
30/30
25/25
25/25
30/30
30/30
30/30
30/30
30/30
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
36/36
36/36
36/36
36/36
36/36
36/36
36/36
50/50
50/50
50/50
50/50
50/50
30/30
30/30
30/30
30/30
30/30
25/25
25/25
30/30
30/30
30/30
30/30
30/30
25/25
25/25
30/30
30/30
30/30
30/30
30/30
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
36/36
36/36
36/36
36/36
36/36
36/36
36/36
50/50
50/50
50/50
50/50
50/50
70/70
70/70
70/70
70/70
70/70
30/30
30/30
30/30
30/30
30/30
25/25
25/25
30/30
30/30
30/30
30/30
30/30
25/25
25/25
30/30
30/30
30/30
30/30
30/30
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
36/36
36/36
36/36
36/36
36/36
36/36
36/36
50/50
50/50
50/50
50/50
50/50
100/100
100/100
100/100
100/100
100/100
30/30
30/30
30/30
30/30
30/30
25/25
25/25
30/30
30/30
30/30
30/30
30/30
25/25
25/25
30/30
30/30
30/30
30/30
30/30
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
70/70
70/70
70/70
70/70
70/70
70/70
70/70
100/100
100/100
100/100
100/100
100/100
150/150
150/150
150/150
150/150
150/150
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
107
04/11/2009 15:59:08
Complementary
technical information
C60H
15 kA
C60L
25 kA
20 kA
15 kA
Rating
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63
Upstream
Breaking capacity
Trip unit
Downstream
C60N
10 kA
C60H
15 kA
C60L
25 kA
20 kA
15 kA
Rating
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63
NSX100B
25 kA
Micrologic
NSX100F
36 kA
Micrologic
NSX100N
50 kA
Micrologic
NSX100H
70 kA
Micrologic
NSX100S
100 kA
Micrologic
NSX100L
150 kA
Micrologic
40
20/20
20/20
20/20
100
20/20
20/20
20/20
20/20
20/20
40
25/25
25/25
25/25
100
25/25
25/25
25/25
25/25
25/25
40
30/30
30/30
30/30
100
30/30
30/30
30/30
30/30
30/30
40
30/30
30/30
30/30
100
30/30
30/30
30/30
30/30
30/30
40
30/30
30/30
30/30
100
30/30
30/30
30/30
30/30
30/30
40
30/30
30/30
30/30
100
30/30
30/30
30/30
30/30
30/30
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
40/40
25/25
25/25
NSX160B
25 kA
Micrologic
NSX160F
36 kA
Micrologic
NSX160N
50 kA
Micrologic
NSX160H
70 kA
Micrologic
NSX160S
100 kA
Micrologic
NSX160L
150 kA
Micrologic
80
20/20
20/20
20/20
20/20
20/20
20/20
80
25/25
25/25
25/25
25/25
25/25
25/25
80
25/25
25/25
25/25
25/25
25/25
25/25
80
25/25
25/25
25/25
25/25
25/25
25/25
80
25/25
25/25
25/25
25/25
25/25
25/25
80
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
160
20/20
20/20
20/20
20/20
20/20
20/20
20/20
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
36/36
36/36
36/36
36/36
36/36
30/30
36/36
36/36
36/36
36/36
36/36
30/30
160
25/25
25/25
25/25
25/25
25/25
25/25
25/25
36/36
36/36
36/36
36/36
36/36
30/30
30/30
36/36
36/36
36/36
36/36
36/36
30/30
30/30
40/40
40/40
40/40
40/40
40/40
30/30
40/40
40/40
40/40
40/40
40/40
30/30
160
25/25
25/25
25/25
25/25
25/25
25/25
25/25
40/40
40/40
40/40
40/40
40/40
30/30
30/30
40/40
40/40
40/40
40/40
40/40
30/30
30/30
40/40
40/40
40/40
40/40
40/40
30/30
40/40
40/40
40/40
40/40
40/40
30/30
160
25/25
25/25
25/25
25/25
25/25
25/25
25/25
40/40
40/40
40/40
40/40
40/40
30/30
30/30
40/40
40/40
40/40
40/40
40/40
30/30
30/30
40/40
40/40
40/40
40/40
40/40
30/30
40/40
40/40
40/40
40/40
40/40
30/30
160
25/25
25/25
25/25
25/25
25/25
25/25
25/25
40/40
40/40
40/40
40/40
40/40
30/30
30/30
40/40
40/40
40/40
40/40
40/40
30/30
30/30
40/40
40/40
40/40
40/40
40/40
30/30
40/40
40/40
40/40
40/40
40/40
30/30
160
25/25
25/25
25/25
25/25
25/25
25/25
25/25
40/40
40/40
40/40
40/40
40/40
30/30
30/30
40/40
40/40
40/40
40/40
40/40
30/30
30/30
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
108
04/11/2009 15:59:10
Complementary
technical information
C60H
15 kA
C60L
25 kA
20 kA
15 kA
C120N/H
10/15 kA
NG125N
25 kA
NG125H
36 kA
NG125L
NG125LMA
50 kA
Rating
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63
y 16
20
25
32
40
50
63
y 16
20 - 25
32 - 40
50 - 63
80
100
125
y 16
20 - 25
32 - 40
50 - 63
80
100
125
y 16
20 - 25
32 - 40
50 - 63
80
y 16
20 - 25
32 - 40
50 - 63
80
NSX250B
25 kA
Micrologic
NSX250F
36 kA
Micrologic
NSX250N
50 kA
Micrologic
NSX250H
70 kA
Micrologic
NSX250S
100 kA
Micrologic
NSX250L
150 kA
Micrologic
250
20/20
20/20
20/20
20/20
20/20
20/20
20/20
25/25
25/25
25/25
25/25
25/25
25/25
25/25
250
25/25
25/25
25/25
25/25
25/25
25/25
25/25
30/30
30/30
30/30
30/30
30/30
25/25
25/25
30/30
30/30
30/30
30/30
30/30
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
36/36
36/36
36/36
36/36
36/36
36/36
36/36
250
30/30
30/30
30/30
30/30
30/30
25/25
25/25
30/30
30/30
30/30
30/30
30/30
25/25
25/25
30/30
30/30
30/30
30/30
30/30
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
36/36
36/36
36/36
36/36
36/36
36/36
36/36
50/50
50/50
50/50
50/50
50/50
250
30/30
30/30
30/30
30/30
30/30
25/25
25/25
30/30
30/30
30/30
30/30
30/30
25/25
25/25
30/30
30/30
30/30
30/30
30/30
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
36/36
36/36
36/36
36/36
36/36
36/36
36/36
50/50
50/50
50/50
50/50
50/50
70/70
70/70
70/70
70/70
70/70
250
30/30
30/30
30/30
30/30
30/30
25/25
25/25
30/30
30/30
30/30
30/30
30/30
25/25
25/25
30/30
30/30
30/30
30/30
30/30
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
36/36
36/36
36/36
36/36
36/36
36/36
36/36
50/50
50/50
50/50
50/50
50/50
100/100
100/100
100/100
100/100
100/100
250
30/30
30/30
30/30
30/30
30/30
25/25
25/25
30/30
30/30
30/30
30/30
30/30
25/25
25/25
30/30
30/30
30/30
30/30
30/30
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
70/70
70/70
70/70
70/70
70/70
70/70
70/70
100/100
100/100
100/100
100/100
100/100
150/150
150/150
150/150
150/150
150/150
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
109
558E4200.indd 109
20/11/2009 14:20:21
Complementary
technical information
16 kA
25 kA
36 kA
18 kA
25 kA
NSX250F
36 kA
TM-D
Rating
200-250
25/25
36/36
16 - 100
TM-D y 25
TM-D 40 - 100
36 kA TM-D y 25
TM-D 40 - 100
50 kA TM-D y 25
TM-D 40 - 100
70 kA TM-D y 25
TM-D 40 - 100
100 kA TM-D y 25
TM-D 40 - 100
25 kA Micrologic
36 kA Micrologic
50 kA Micrologic
70 kA Micrologic
100 kA Micrologic
Upstream
Breaking capacity
Trip unit
Downstream
NG160E
NG160N
NG160H
NSC100N
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
NSX160B
NSX160F
NSX160N
NSX160H
NSX160S
NSX250B
NSX250F
NSX250N
NSX250H
NSX250S
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
NSX160B
NSX160F
NSX160N
NSX160H
NSX160S
NSX250B
NSX250F
NSX250N
NSX250H
NSX250S
NSX400F
NSX400N
NSX400H
NSX400S
NSX630F
NSX630N
NSX630H
NSX630S
160
16 kA
25 kA
36 kA
18 kA
25 kA
36 kA
50 kA
70 kA
100 kA
25 kA
36 kA
50 kA
70 kA
100 kA
25 kA
36 kA
50 kA
70 kA
100 kA
25 kA
36 kA
50 kA
70 kA
100 kA
25 kA
36 kA
50 kA
70 kA
100 kA
25 kA
36 kA
50 kA
70 kA
100 kA
36 kA
50 kA
70 kA
100 kA
36 kA
50 kA
70 kA
100 kA
NSX250N
50 kA
TM-D
160
36/36
36/36
36/36
36/36
NSX250H
70 kA
TM-D
200-250
30/30
36/36
50/50
50/50
36/36
36/36
50/50
36/50
160
36/36
36/50
NSX250S
100 kA
TM-D
200-250
30/30
50/50
50/50
50/50
50/50
36/50
70/70
36/70
70/70
36/70
160
36/50
36/70
36/70
NSX250L
150 kA
TM-D
200-250
30/30
50/50
50/50
50/50
50/50
36/50
100/100
36/100
100/100
36/100
100/100
36/100
160
36/50
36/100
36/100
36/100
200-250
30/30
50/50
50/50
50/50
50/50
36/50
150/150
36/150
150/150
36/150
150/150
36/150
150/150
36/150
36/50
36/150
36/150
36/150
36/150
NSX400F NSX400N NSX400H NSX400S NSX400L NSX630F NSX630N NSX630H NSX630S NSX630L
36 kA
50 kA
70 kA
100 kA
150 kA
36 kA
50 kA
70 kA
100 kA
150 kA
Micrologic
Rating
400
25/25
36/36
16 - 100
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
TM-D
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
36/36
36/36
36/36
400
30/30
36/36
50/50
36/36
36/36
50/50
400
30/30
50/50
50/50
50/50
50/50
70/70
70/70
400
30/30
50/50
50/50
50/50
50/50
100/100
100/100
100/100
36/36
50/50
50/50
70/70
70/70
50/50
100/100
100/100
100/100
36/36
50/50
50/50
50/50
70/70
70/70
50/50
100/100
100/100
100/100
36/36
50/50
50/50
50/50
70/70
70/70
50/50
100/100
100/100
100/100
400
30/30
50/50
50/50
50/50
50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
630
25/25
36/36
630
30/30
36/36
50/50
36/36
36/36
50/50
630
30/30
50/50
50/50
50/50
50/50
70/70
70/70
630
30/30
50/50
50/50
50/50
50/50
100/100
100/100
100/100
36/36
36/36
50/50
50/50
70/70
70/70
50/50
100/100
100/100
100/100
36/36
36/36
50/50
50/50
70/70
70/70
50/50
100/100
100/100
100/100
36/36
50/50
50/50
50/50
70/70
70/70
50/50
100/100
100/100
100/100
36/36
50/50
50/50
50/50
70/70
70/70
50/50
100/100
100/100
100/100
36/36
50/50
50/50
50/50
70/70
70/70
50/50
100/100
100/100
100/100
36/36
36/36
630
30/30
50/50
50/50
50/50
50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
50/50
150/150
150/150
150/150
150/150
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
110
04/11/2009 15:59:12
Complementary
technical information
16 kA
25 kA
36 kA
18 kA
25 kA
NSX100F
36 kA
NSX100N
50 kA
NSX100H
70 kA
NSX100S
100 kA
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
25 kA
36 kA
50 kA
70 kA
100 kA
NSX250F
36 kA
Micrologic
NSX250N
50 kA
NSX250H
70 kA
NSX250S
100 kA
NSX250L
150 kA
Rating
250
25/25
36/36
16 - 100
TM-D y 25
TM-D 40 - 100
TM-D y 25
TM-D 40 - 100
TM-D y 25
TM-D 40 - 100
TM-D y 25
TM-D 40 - 100
TM-D y 25
TM-D 40 - 100
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
36/36
36/36
36/36
250
30/30
36/36
50/50
50/50
50/50
36/50
50/50
36/50
250
30/30
50/50
50/50
50/50
50/50
36/50
70/70
36/70
70/70
36/70
250
30/30
50/50
50/50
50/50
50/50
36/50
100/100
36/100
100/100
36/100
100/100
36/100
36/50
36/50
36/50
36/70
36/70
36/50
36/100
36/100
36/100
250
30/30
50/50
50/50
50/50
50/50
36/50
150/150
36/150
150/150
36/150
150/150
36/150
150/150
36/150
36/50
36/150
36/150
36/150
36/150
Upstream
Breaking capacity
Trip unit
Downstream
NSX100B
25 kA
NSX100F
36 kA
NSX100N
50 kA
NSX100H
70 kA
NSX100S
100 kA
NSX100L
150 kA
NSX160B
25 kA
NSX160F
36 kA
NSX160N
50 kA
NSX160H
70 kA
NSX160S
100 kA
NSX160L
150 kA
NSX250B
25 kA
NSX250F
36 kA
NSX250N
50 kA
NSX250H
70 kA
NSX250S
100 kA
NSX250L
150 kA
NSX400F
36 kA
NSX400N
50 kA
NSX400H
70 kA
NSX400S
100 kA
NSX400L
150 kA
NSX630F
36 kA
NSX630N
50 kA
NSX630H
70 kA
NSX630S
100 kA
36/36
NS800N NS800H NS800L NS800LB NS1000N NS1000H NS1000L NS1250N NS1250H NS1600N NS1600H
50 kA
70 kA
150 kA 200 kA
50 kA
70 kA
150 kA
50 kA
70 kA
50 kA
70 kA
Micrologic
Rating
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
800
50/50
50/50
800
50/50
70/70
70/70
800
50/50
150/150
150/150
150/150
150/150
50/50
50/50
50/50
70/70
70/70
50/50
150/150
150/150
150/150
150/150
50/50
50/50
50/50
70/70
70/70
50/50
150/150
150/150
150/150
150/150
50/50
70/70
70/70
10/150
10/150
10/150
10/150
50/50
150/150
150/150
150/150
200/200
200/200
50/50
150/150
150/150
150/150
200/200
200/200
50/50
150/150
150/150
150/150
200/200
200/200
10/150
10/150
10/150
10/200
10/200
1000
50/50
50/50
1000
50/50
70/70
70/70
1000
50/50
150/150
150/150
150/150
150/150
1250
50/50
50/50
1250
50/50
70/70
70/70
1600
50/50
50/50
1600
50/50
70/70
70/70
50/50
50/50
50/50
70/70
70/70
50/50
150/150
150/150
150/150
150/150
50/50
50/50
50/50
70/70
70/70
50/50
50/50
50/50
70/70
70/70
50/50
50/50
50/50
70/70
70/70
50/50
150/150
150/150
150/150
150/150
50/50
50/50
50/50
70/70
70/70
50/50
50/50
50/50
70/70
70/70
50/50
70/70
70/70
15/150
15/150
15/150
15/150
50/50
70/70
70/70
50/50
70/70
70/70
50/50
65/70
65/70
10/150
10/150
10/150
10/150
50/50
65/70
65/70
50/50
65/70
65/70
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
111
04/11/2009 15:59:13
Complementary
technical information
35 kA
NSX100N
50 kA
NSX100H
65 kA
NSX100S
90 kA
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
20 kA
35 kA
50 kA
65 kA
90 kA
NSX250F
35 kA
TM-D
Rating
TM-D y 25
4 TM-D 0 - 100
TM-D y 25
TM-D 40 - 100
TM-D y 25
TM-D 40 - 100
TM-D y 25
TM-D 40 - 100
TM-D y 25
TM-D 40 - 100
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Upstream
Breaking capacity
Trip unit
Downstream
NSX100B
20 kA
NSX100F
35 kA
NSX100N
50 kA
NSX100H
65 kA
NSX100S
90 kA
NSX100B
NSX100F
NSX100N
NSX100H
NSX100S
20 kA
35 kA
50 kA
65 kA
90 kA
Rating
TM-D y 25
4 TM-D 0 - 100
TM-D y 25
TM-D 40 - 100
TM-D y 25
TM-D 40 - 100
TM-D y 25
TM-D 40 - 100
TM-D y 25
TM-D 40 - 100
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
NSX250N
50 kA
TM-D
NSX250H
65 kA
TM-D
NSX250S
90 kA
TM-D
NSX250L
130 kA
TM-D
200
35/35
35/35
250
35/35
35/35
200
35/35
35/35
35/35
35/35
250
35/35
35/35
35/35
35/35
200
50/50
35/50
65/65
35/65
65/65
35/65
250
50/50
35/50
65/65
35/65
65/65
35/65
200
50/50
35/50
90/90
35/90
90/90
35/90
90/90
35/90
250
50/50
35/50
90/90
35/90
90/90
35/90
90/90
35/90
35/35
35/35
35/35
35/50
35/35
35/50
35/50
35/50
35/65
35/50
35/50
35/65
35/50
35/50
35/90
35/90
35/50
35/50
35/90
35/90
200
50/50
35/50
130/130
35/130
130/130
35/130
130/130
35/130
130/130
35/130
35/50
35/50
35/130
35/130
35/130
NSX250N
35 kA
Micrologic
NSX250S
50 kA
Micrologic
NSX250H
65 kA
Micrologic
NSX250S
90 kA
Micrologic
NSX250L
130 kA
Micrologic
250
35/35
35/35
250
50/50
35/50
50/50
35/50
50/50
35/50
250
50/50
35/50
65/65
35/65
65/65
35/65
250
50/50
35/50
90/90
35/90
90/90
35/90
90/90
35/90
35/35
35/35
35/35
35/50
35/50
35/65
35/50
35/50
35/90
35/90
250
50/50
35/50
130/130
35/130
130/130
35/130
130/130
35/130
130/130
35/130
35/50
35/50
35/130
35/130
35/130
250
50/50
35/50
130/130
35/130
130/130
35/130
130/130
35/130
130/130
35/130
35/50
35/50
35/130
35/130
35/130
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
112
04/11/2009 15:59:13
Complementary
technical information
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
Upstream
Breaking capacity
Trip unit
Downstream
NSX100B 25 kA
NSX100F 35 kA
NSX100N 50 kA
NSX100H 65 kA
NSX100S 90 kA
NSX100L 130 kA
NSX160B 25 kA
NSX160F 35 kA
NSX160N 50 kA
NSX160H 65 kA
NSX160S 90 kA
NSX160L 130 kA
NSX250B 25 kA
NSX250F 35 kA
NSX250N 50 kA
NSX250H 65 kA
NSX250S 90 kA
NSX250L 130 kA
NSX400F 35 kA
NSX400N 50 kA
NSX400H 65 kA
NSX400S 90 kA
NSX400L 130 kA
NSX630F 35 kA
NSX630N 50 kA
NSX630H 65 kA
NSX630S 90 kA
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
TM-D / Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
Micrologic
NSX630F
30 Ka
400
30/30
400
30/30
42/42
400
50/50
65/65
65/65
400
50/50
90/90
90/90
90/90
630
30/30
630
30/30
42/42
630
50/50
65/65
65/65
30/30
30/30
42/42
50/50
65/65
65/65
50/50
90/90
90/90
90/90
30/30
30/30
42/42
50/50
65/65
65/65
50/50
90/90
90/90
90/90
35/35
30/30
42/42
50/50
65/65
65/65
50/50
90/90
90/90
90/90
400
50/50
130/130
130/130
130/130
130/130
50/50
130/130
130/130
130/130
130/130
50/50
90/90
90/90
90/90
630
50/50
130/130
130/130
130/130
130/130
50/50
130/130
130/130
130/130
130/130
50/50
130/130
130/130
130/130
130/130
NS800N NS800H NS800L NS800LB NS1000N NS1000H NS1000L NS1250N NS1250H NS1600N NS1600H
50 kA
65 kA
130 kA 200 kA
50 kA
65 kA
130 kA
50 kA
65 kA
50 kA
65 kA
Micrologic
800
50/50
50/50
800
50/50
65/65
65/65
800
50/50
130/130
130/130
130/130
130/130
50/50
50/50
50/50
65/65
65/65
50/50
130/130
130/130
130/130
130/130
50/50
50/50
50/50
65/65
65/65
50/50
130/130
130/130
130/130
130/130
50/50
65/65
65/65
10/130
10/130
10/130
10/130
50/50
130/130
130/130
130/130
200/200
200/200
50/50
130/130
130/130
130/130
200/200
200/200
50/50
130/130
130/130
130/130
200/200
200/200
10/200
10/200
10/200
10/200
10/200
1000
50/50
50/50
1000
50/50
65/65
65/65
1000
50/50
130/130
130/130
130/130
130/130
1250
50/50
50/50
1250
50/50
65/65
65/65
1600
50/50
50/50
1600
50/50
65/65
65/65
50/50
50/50
50/50
65/65
65/65
50/50
130/130
130/130
130/130
130/130
50/50
50/50
50/50
65/65
65/65
50/50
50/50
50/50
65/65
65/65
50/50
50/50
50/50
65/65
65/65
50/50
130/130
130/130
130/130
130/130
50/50
50/50
50/50
65/65
65/65
50/50
50/50
50/50
65/65
65/65
50/50
65/65
65/65
15/130
15/130
15/130
15/130
50/50
65/65
65/65
50/50
65/65
65/65
50/50
65/65
65/65
10/130
10/130
10/130
10/130
50/50
65/65
65/65
50/50
65/65
65/65
Note: respect the basic rules of discrimination, in terms of overload, short-circuit, see page6, or check curves with Curve Direct software.
113
04/11/2009 15:59:14
114
04/11/2009 15:59:14
Complementary
technical information
Contents
Using the tables
Two circuit breakers offer total discrimination when the corresponding box in the
discrimination table is shaded or contains the letter T.
When discrimination is partial for the combination, the corresponding box indicates
the maximum value of the fault current for which discrimination is provided.
For fault currents above this value, the two circuit breakers trip simultaneously.
Application
Motor protection discrimination
Upstream device
Downstream device
Cascading
Cascading and enhanced
discrimination 380/415 V
Cascading and enhanced
discrimination 440 V
Protection of motor circuits
Table
page
116
117
120
118
121
123
124
130
131
133
134
135
136
137
138
143
147
149
DB118571
CB1
CB2
Requisite conditions
The values indicated in the tables (for 220, 380, 415 and 440 V) are guaranteed
if the following conditions are respected:
Upstream
TM
Micrologic
Downstream
Thermal protection
Ir up/Ir down
Magnetic protection
Im up/Im down
u3
u3
u3
u3
u2
u2
u 1.5
u 1.5
115
558E4350.indd 115
09/11/2009 14:38:33
Complementary
technical information
Upstream
Breaking capacity
Trip unit
Downstream Thermal
relay
Discrimination limit (kA)
GV2 M01
integrated
GV2 M02
integrated
GV2 M03
integrated
GV2 M04
integrated
GV2 M05
integrated
GV2 M06
integrated
GV2 M07
integrated
GV2 M08
integrated
GV2 M10
integrated
GV2 M14
integrated
GV2 M16
integrated
GV2 M20
integrated
GV2 M21
integrated
GV2 M22
integrated
GV2 M32
integrated
GW2 P01
integrated
GV2 P02
integrated
GV2 P03
integrated
GV2 P04
integrated
GV2 P05
integrated
GV2 P06
integrated
GV2 P07
integrated
GV2 P08
integrated
GV2 P10
integrated
GV2 P14
integrated
GV2 P16
integrated
GV2 P20
integrated
GV2 P21
integrated
GV2 P22
integrated
GV2 L03
LR2 D13 03
GV2 L04
LR2 D13 04
GV2 L05
LR2 D13 05
GV2 L06
LR2 D13 06
GV2 L07
LR2 D13 07
GV2 L08
LR2 D13 08
GV2 L10
LR2 D13 10
GV2 L14
LR2 D13 14
GV2 L16
LR2 D13 16
GV2 L20
LR2 D13 21
GV2 L22
LR2 D13 22
LUB12
LUC*X6
LUC*1X
LUC*05
LUC*12
LUB32
LUC*X6
LUC*1X
LUC*05
LUC*12
LUC*18
LUC*32
Rating (A)
Setting Ir
16
20
25
32
40
50
63
70
80
100
0.1/0.16
0.16/0.25
0.25/0.40
0.40/0.63
0.63/1
1/1.6
1.6/2.5
2.5/4
4/6.3
6/10
9/14
13/18
17/23
20/25
24/32
0.1/0.16
0.16/0.25
0.25/0.40
0.40/0.63
0.63/1
1/1.6
1.6/2.5
2.5/4
4/6.3
6/10
9/14
13/18
17/23
20/25
0.25/0.40
0.40/0.63
0.63/1
1/1.6
1.6/2.5
2.5/4
4/6.3
7/10
9/13
12/18
17/25
0.15/0.6
0.35/1.4
1.25/5
3/12
0.150.6
0.351.4
1.255
312
4.518
832
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
0.6
T
T
T
T
T
T
T
T
0.6
T
T
T
T
T
T
T
T
0.6
0.6
T
T
T
T
T
T
T
T
0.6
0.6
T
T
T
T
T
T
T
T
1
1
1
T
T
T
T
T
T
T
T
1
1
1
1
T
T
T
T
T
T
T
T
1
1
1
1
1
T
T
T
T
T
T
T
T
1
1
1
1
1
1
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
0.6
T
T
T
T
T
T
T
T
0.6
T
T
T
T
T
T
T
T
0.6
0.6
T
T
T
T
T
T
T
T
0.6
0.6
T
T
T
T
T
T
T
T
1
1
1
T
T
T
T
T
T
T
T
1
1
1
1
T
T
T
T
T
T
T
T
1
1
1
1
1
T
T
T
T
T
T
T
T
T
T
T
T
0.6
T
T
T
T
T
T
0.6
T
T
T
T
T
T
0.6
0.6
T
T
T
T
T
T
0.6
0.6
T
T
T
T
T
T
1
1
1
T
T
T
T
T
T
1
1
1
1
T
T
T
T
T
T
1
1
1
1
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
T
T
T
T
T
T
T
T
1
1
1
1
1
1
T
T
T
T
T
T
1
1
1
1
1
1
1
1
1
1
1
1
1
1
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.25
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
116
558E4350.indd 116
09/11/2009 14:38:34
Complementary
technical information
Upstream
NSX100B/F/N/H/S/L
NSX160B/F/N/H/S/L
NSX250B/F/N/H/S/L
Trip unit
TM-D
TM-D
TM-D
16
25
32
40
50
63
80
100
80
100
125
160
160
200
250
T
T
T
T
T
0.19
0.19
0.19
T
T
T
T
T
T
0.25
0.25
0.25
T
T
T
T
T
T
0.4
0.4
0.4
0.4
T
T
T
T
T
T
T
0.5
0.5
0.5
T
T
T
T
T
T
T
0.5
0.5
0.5
0.5
T
T
T
T
T
T
T
0.5
0.5
0.5
0.5
T
T
T
T
T
T
T
0.63
0.63
0.63
0.63
0.63
0.63
0.63
T
T
T
T
T
T
T
0.63
0.63
0.63
0.63
0.63
0.63
0.63
T
T
T
T
T
0.19
0.19
0.19
T
T
T
T
T
T
0.25
0.25
0.25
T
T
T
T
T
T
0.4
0.4
0.4
0.4
T
T
T
T
T
T
T
0.5
0.5
0.5
T
T
T
T
T
T
T
0.5
0.5
0.5
0.5
T
T
T
T
T
T
T
0.5
0.5
0.5
0.5
T
T
T
T
T
T
T
0.63
0.63
0.63
0.63
0.63
0.63
0.63
T
T
T
0.19
0.19
0.19
T
T
T
T
0.25
0.25
0.25
T
T
T
T
0.4
0.4
0.4
0.4
T
T
T
T
T
0.5
0.5
0.5
T
T
T
T
T
0.5
0.5
0.5
0.5
T
T
T
T
T
0.5
0.5
0.5
0.5
T
T
T
T
T
0.63
0.63
0.63
0.63
0.63
0.63
T
T
T
T
T
T
T
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
T
T
T
T
T
T
T
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
T
T
T
T
T
0.8
0.8
0.8
0.8
0.8
0.8
0.8
T
T
T
T
T
T
T
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
T
T
T
T
T
T
T
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
T
T
T
T
T
0.8
0.8
0.8
0.8
0.8
0.8
0.8
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
0.63
0.63
0.63
0.63
0.63
0.63
0.63
T
T
T
T
T
0.63
0.63
0.63
0.63
0.63
0.63
T
T
T
T
0.19
0.19
0.19
0.3
0.3
0.3
0.4
0.4
0.4
0.19
0.19
0.19
0.3
0.3
0.3
0.4
0.4
0.4
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.5
0.5
0.5
0.5
0.63
0.63
0.63
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.7
0.63
0.63
0.63
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
T
T
T
T
5
5
5
5
5
5
1
1
1
1
1
T
T
T
T
5
5
5
5
5
5
1
1
1
1
1
1
T
T
T
T
5
5
5
5
5
5
1
1
1
1
1
1
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
No discrimination.
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
117
558E4350.indd 117
09/11/2009 14:38:35
Complementary
technical information
Upstream
Trip unit
Downstream Trip unit
or th. relay
Discrimination limit (kA)
GV2 M01
Integrated
GV2 M02
Integrated
GV2 M03
Integrated
GV2 M04
Integrated
GV2 M05
Integrated
GV2 M06
Integrated
GV2 M07
Integrated
GV2 M08
Integrated
GV2 M10
Integrated
GV2 M14
Integrated
GV2 M16
Integrated
GV2 M20
Integrated
GV2 M21
Integrated
GV2 M22
Integrated
GV2 M32
Integrated
GV2 P01
Integrated
GV2 P02
Integrated
GV2 P03
Integrated
GV2 P04
Integrated
GV2 P05
Integrated
GV2 P06
Integrated
GV2 P07
Integrated
GV2 P08
Integrated
GV2 P10
Integrated
GV2 P14
Integrated
GV2 P16
Integrated
GV2 P20
Integrated
GV2 P21
Integrated
GV2 P22
Integrated
GV2 P32
Integrated
GV2 L03
LRD 03
GV2 L04
LRD 04
GV2 L05
LRD 05
GV2 L06
LRD 06
GV2 L07
LRD 07
GV2 L08
LRD 08
GV2 L10
LRD 10
GV2 L14
LRD 14
GV2 L16
LRD 16
GV2 L20
LRD 21
GV2 L22
LRD 22
GV2 L32
LRD 32
GV3 P13
Integrated
GV3 P18
Integrated
GV3 P25
Integrated
GV3 P32
Integrated
GV3 P40
Integrated
GV3 P50
Integrated
GV3 P65
Integrated
GV3 L25
LRD 22
GV3 L32
LRD 32
GV3 L40
LRD 33 55
GV3 L50
LRD 33 57
GV3 L65
LRD 33 59
LUB12
LUC*X6
LUC*1X
LUC*05
LUC*12
LUB32
LUC*X6
LUC*1X
LUC*05
LUC*12
LUC*18
LUC*32
Integral 63
LB1-LD03M16
LB1-LD03M21
LB1-LD03M22
LB1-LD03M53
LB1-LD03M55
LB1-LD03M57
LB1-LD03M61
NSX160B/F/N/H/S/L
Micrologic
Rating (A)
Setting Ir
40
16
40
25
40
40
100
40
100
63
100
80
100
100
160
63
160
80
160
100
160
125
160
160
0.1/0.16
0.16/0.25
0.25/0.40
0.40/0.63
0.63/1
1/1.6
1.6/2.5
2.5/4
4/6.3
6 /10
9/14
13/18
17/23
20/25
24/32
0.1/0.16
0.16/0.25
0.25/0.40
0.40/0.63
0.63/1
1/1.6
1.6/2.5
2.5/4
4/6.3
6 /10
9/14
13/18
17/23
20/25
24/32
0.25/0.40
0.40/0.63
0.63/1
1/1.6
1.6/2.5
2.5/4
4/6.3
7 /10
9/13
12/18
17/25
23/32
9/13
12/18
17/25
23/32
30/40
37/50
48/65
20/25
23/32
30/40
37/50
48/65
0.150.6
0.351.4
1.255
312
0.150.6
0.351.4
1.255
312
4.518
832
10/13
13/18
18/25
23/32
28/40
35/50
45/63
T
T
T
T
T
0.6
0.6
0.6
T
T
T
T
T
0.6
0.6
0.6
0.6
T
T
T
T
T
0.6
0.6
0.6
0.6
0.6
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
0.6
0.6
0.6
T
T
T
T
T
0.6
0.6
0.6
0.6
T
T
T
T
T
0.6
0.6
0.6
0.6
0.6
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
0.6
0.6
0.6
T
T
T
0.6
0.6
0.6
0.6
T
T
T
0.6
0.6
0.6
0.6
0.6
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
0.6
1.5
1.5
1.5
1.5
1.5
1.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
1.5
1.5
1.5
1.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2.4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2.4
2.4
T
T
T
T
2.4
T
T
2.4
2.4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2.4
2.4
2.4
2.4
2.4
T
T
T
T
T
T
T
T
T
T
2.4
2.4
2.4
2.4
T
T
T
T
T
T
T
T
T
T
2.4
2.4
2.4
2.4
2.4
T
T
T
T
T
T
T
T
T
T
2.4
2.4
2.4
2.4
2.4
2.4
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
0.6
1.5
1.5
1.5
1.5
1.5
1.5
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
118
558E4350.indd 118
09/11/2009 14:38:36
Complementary
technical information
Upstream
Trip unit
Downstream Trip unit
or th. relay
Discrimination limit (kA)
GV2 M01
Integrated
GV2 M02
Integrated
GV2 M03
Integrated
GV2 M04
Integrated
GV2 M05
Integrated
GV2 M06
Integrated
GV2 M07
Integrated
GV2 M08
Integrated
GV2 M10
Integrated
GV2 M14
Integrated
GV2 M16
Integrated
GV2 M20
Integrated
GV2 M21
Integrated
GV2 M22
Integrated
GV2 M32
Integrated
GV2 P01
Integrated
GV2 P02
Integrated
GV2 P03
Integrated
GV2 P04
Integrated
GV2 P05
Integrated
GV2 P06
Integrated
GV2 P07
Integrated
GV2 P08
Integrated
GV2 P10
Integrated
GV2 P14
Integrated
GV2 P16
Integrated
GV2 P20
Integrated
GV2 P21
Integrated
GV2 P22
Integrated
GV2 P32
Integrated
GV2 L03
LRD 03
GV2 L04
LRD 04
GV2 L05
LRD 05
GV2 L06
LRD 06
GV2 L07
LRD 07
GV2 L08
LRD 08
GV2 L10
LRD 10
GV2 L14
LRD 14
GV2 L16
LRD 16
GV2 L20
LRD 21
GV2 L22
LRD 22
GV2 L32
LRD 32
GV3 P13
Integrated
GV3 P18
Integrated
GV3 P25
Integrated
GV3 P32
Integrated
GV3 P40
Integrated
GV3 P50
Integrated
GV3 P65
Integrated
GV3 L25
LRD 22
GV3 L32
LRD 32
GV3 L40
LRD 33 55
GV3 L50
LRD 33 57
GV3 L65
LRD 33 59
LUB12
LUC*X6
LUC*1X
LUC*05
LUC*12
LUB32
LUC*X6
LUC*1X
LUC*05
LUC*12
LUC*18
LUC*32
Integral 63
LB1-LD03M16
LB1-LD03M21
LB1-LD03M22
LB1-LD03M53
LB1-LD03M55
LB1-LD03M57
LB1-LD03M61
Rating (A)
Setting Ir
250
100
0.1/0.16
0.16/0.25
0.25/0.40
0.40/0.63
0.63/1
1/1.6
1.6/2.5
2.5/4
4/6.3
6 /10
9/14
13/18
17/23
20/25
24/32
0.1/0.16
0.16/0.25
0.25/0.40
0.40/0.63
0.63/1
1/1.6
1.6/2.5
2.5/4
4/6.3
6 /10
9/14
13/18
17/23
20/25
24/32
0.25/0.40
0.40/0.63
0.63/1
1/1.6
1.6/2.5
2.5/4
4/6.3
7 /10
9/13
12/18
17/25
23/32
9/13
12/18
17/25
23/32
30/40
37/50
48/65
20/25
23/32
30/40
37/50
48/65
0.150.6
0.351.4
1.255
312
0.150.6
0.351.4
1.255
312
4.518
832
10/13
13/18
18/25
23/32
28/40
35/50
45/63
NSX400F/N/H/S/L
Micrologic
NSX630F/N/H/S/L
Micrologic
125
160
200
250
400
160
200
250
320
400
630
250
320
400
500
630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
119
558E4350.indd 119
09/11/2009 14:38:37
Complementary
technical information
Upstream
Trip unit
Downstream
Discrimination limit (kA)
C60L MA 1.6
C60L MA 2.5
C60L MA 4
C60L MA 6.3
C60L MA 10
C60L MA 10
C60L MA 12.5
C60L MA 16
C60L MA 25
C60L MA 40
C60L MA 40
NG125L MA 1.6
NG125L MA 2.5
NG125L MA 4
NG125L MA 6.3
NG125L MA 10
NG125L MA 10
NG125L MA 12.5
NG125L MA 16
NG125L MA 25
NG125L MA 40
NG125L MA 40
NG125L MA 63
NG125L MA 63
NS80H-MA 2.5
NS80H-MA 2.5
NS80H-MA 6.3
NS80H-MA 6.3
NS80H-MA 12.5
NS80H-MA 12.5
NS80H-MA 12.5
NS80H-MA 25
NS80H-MA 25
NS80H-MA 50
NS80H-MA 50
NS80H-MA 50
NS80H-MA 80
NSX100 B/F/N/H/S/L MA 2.5
NSX100 B/F/N/H/S/L MA 2.5
NSX100 B/F/N/H/S/L MA 6.3
NSX100 B/F/N/H/S/L MA 6.3
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 25
NSX100 B/F/N/H/S/L MA 25
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 100
NSX100 B/F/N/H/S/L MA 100
NSX100B/F
NSX100N/H/S/L
NSX160B/F
NSX160N/H/S/L
NSX250B/F
NSX250N/H/S/L
NSX100B/F/N/H/S/L
TM-D
NSX160B/F/N/H/S/L
TM-D
NSX250B/F/N/H/S/L
TM-D
Trip unit
or th. relay
Rating (A)
Setting Ir
16
25
32
40
50
63
80
100
80
100
125
160
160
200
250
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 33 63
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
63/80
25/50
100
25/50
100
y 100
150
y 100
150
y 150
220
y 150
220
0.19 T
0.19 0.3
0.19 0.3
0.3
0.3
T
0.4
0.4
0.4
0.4
0.4
T
T
0.5
0.5
0.5
0.5
0.5
T
T
0.5
0.5
0.5
0.5
0.5
T
T
0.5
0.5
0.5
0.5
0.5
0.5
T
T
0.63
0.63
0.63
0.63
0.63
0.63
0.63
T
T
0.63
0.63
0.63
0.63
0.63
0.63
0.63
0.19 T
0.19 0.3
0.19 0.3
0.3
0.3
T
0.4
0.4
0.4
0.4
0.4
T
T
0.5
0.5
0.5
0.5
0.5
T
T
0.5
0.5
0.5
0.5
0.5
T
T
0.5
0.5
0.5
0.5
0.5
0.5
T
T
0.63
0.63
0.63
0.63
0.63
0.63
0.63
T
T
T
5
2
0.8
0.8
0.8
0.8
0.8
0.8
T
T
T
5
2
0.8
0.8
0.8
0.8
0.8
0.8
T
T
T
5
2
0.8
0.8
0.8
0.8
0.8
0.8
T
T
T
5
2
0.8
0.8
0.8
0.8
0.8
0.8
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
0.19 T
0.19 0.3
0.19 0.3
0.3
0.3
T
0.4
0.4
0.4
0.4
0.4
T
T
0.5
0.5
0.5
0.5
0.5
T
T
0.5
0.5
0.5
0.5
0.5
T
T
0.5
0.5
0.5
0.5
0.5
0.5
T
T
0.63
0.63
0.63
0.63
0.63
0.63
0.63
T
T
T
5
2
0.8
0.8
0.8
0.8
0.8
0.8
T
T
0.63
0.63
0.63
0.63
0.63
0.63
0.63
T
T
T
5
2
0.8
0.8
0.8
0.8
0.8
0.8
T
T
T
T
T
T
T
T
T
1
1
1
0.19 0.3
0.19 0.3
0.19 0.3
0.3
0.3
T
0.4
0.4
0.4
0.4
0.4
T
0.5
0.5
0.5
0.5
0.5
0.5
T
0.5
0.5
0.5
0.5
0.5
0.5
T
0.5
0.5
0.5
0.5
0.5
0.5
0.5
T
T
0.63
0.63
0.63
0.63
0.63
0.63
0.63
T
T
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
T
T
0.63
0.63
0.63
0.63
0.63
0.63
0.63
T
T
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
T
T
T
T
1
1
1
1
1
1
1
T
T
T
T
T
T
T
T
T
1
1
1
1
T
T
T
T
1
1
1
1
1
1
1
1
T
T
T
T
T
T
T
T
T
1
1
1
1
T
T
T
T
1
1
1
1
1
1
1
1
0.8
0.8
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
T
0.8
0.8
36
1
1
1
1
1
1
1
1
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
T
T
36
36
2.5
2.5
2.5
2.5
2.5
T
T
0.63
0.63
0.63
0.63
0.63
0.63
0.63
2.5
No discrimination.
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
120
558E4350.indd 120
09/11/2009 14:38:38
Complementary
technical information
Upstream
Trip unit
Downstream
NSX100B/F/N/H/S/L
Micrologic
Trip unit
or th. relay
Rat. (A) 40
Setting Ir 16
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
63/80
100
25/50
100
25/50
100
y 100
150
y 100
150
y 150
220
y 150
220
NSX160B/F/N/H/S/L
Micrologic
25
32
40
100
40 63
T
1
0.6
0.6
T
1
0.6
0.6
0.6
T
1
0.6
0.6
0.6
0.6
T
1
0.6
0.6
0.6
0.6
0.6
T
T
T
5
2
1.5
1.5
T
T
T
5
2
1.5
1.5
1.5
T
1
0.6
0.6
T
1
0.6
0.6
0.6
T
1
0.6
0.6
0.6
0.6
T
1
0.6
0.6
0.6
0.6
0.6
T
T
T
5
2
1.5
1.5
T
1
0.6
0.6
T
1
0.6
0.6
0.6
T
1
0.6
0.6
0.6
0.6
T
1
0.6
0.6
0.6
0.6
0.6
T
1
0.6
0.6
T
1
0.6
0.6
0.6
T
1
0.6
0.6
0.6
0.6
T
1
0.6
0.6
0.6
0.6
0.6
NSX250B/F/N/H/S/L
Micrologic
160
100 63 80
250
100 125 160 100 125 160 200 250
T
T
T
5
2
1.5
1.5
1.5
1.5
T
T
T
5
2
1.5
1.5
1.5
1.5
1.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
5
2
1.5
1.5
1.5
T
T
T
5
2
1.5
1.5
1.5
1.5
T
T
T
5
2
1.5
1.5
1.5
1.5
1.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
5
2
1.5
1.5
T
T
T
5
2
1.5
1.5
1.5
T
T
T
5
2
1.5
1.5
1.5
1.5
T
T
T
5
2
1.5
1.5
1.5
1.5
1.5
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
1.5
1.5
1.5
1.5
1.5
T
T
1.5
1.5
1.5
1.5
1.5
1.5
T
T
1.5
1.5
1.5
1.5
1.5
1.5
1.5
T
T
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
T
T
T
T
2.4
2.4
2.4
2.4
T
T
T
T
2.4
2.4
2.4
2.4
2.4
T
T
T
T
2.4
2.4
2.4
2.4
2.4
2.4
T
T
T
T
2.4
2.4
2.4
2.4
2.4
2.4
2.4
1.5
2.4
1.5
80
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
36
36
36
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
36
36
36
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
36
36
2.4
2.4
2.4
2.4
2.4
36
36
36
36
2.4
2.4
2.4
2.4
2.4
2.4
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
36
36
36
36
36
36
T
T
36
36
3
3
3
3
3
3
No discrimination.
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
121
558E4350.indd 121
09/11/2009 14:38:39
Complementary
technical information
Upstream
Trip unit
Downstream
Discrimination limit (kA)
C60L MA 1.6
C60L MA 2.5
C60L MA 4
C60L MA 6.3
C60L MA 10
C60L MA 10
C60L MA 12.5
C60L MA 16
C60L MA 25
C60L MA 40
C60L MA 40
NG125L MA 1.6
NG125L MA 2.5
NG125L MA 4
NG125L MA 6.3
NG125L MA 10
NG125L MA 10
NG125L MA 12.5
NG125L MA 16
NG125L MA 25
NG125L MA 40
NG125L MA 40
NG125L MA 63
NG125L MA 63
NS80H-MA 2.5
NS80H-MA 2.5
NS80H-MA 6.3
NS80H-MA 6.3
NS80H-MA 12.5
NS80H-MA 12.5
NS80H-MA 12.5
NS80H-MA 25
NS80H-MA 25
NS80H-MA 50
NS80H-MA 50
NS80H-MA 50
NS80H-MA 80
NSX100 B/F/N/H/S/L MA 2.5
NSX100 B/F/N/H/S/L MA 2.5
NSX100 B/F/N/H/S/L MA 6.3
NSX100 B/F/N/H/S/L MA 6.3
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 25
NSX100 B/F/N/H/S/L MA 25
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 100
NSX100 B/F/N/H/S/L MA 100
NSX100 B/F/N/H/S/L
NSX160 B/F/N/H/S/L
NSX250 B/F/N/H/S/L
NSX100B/F
NSX100N/H/S/L
NSX160B/F
NSX160N/H/S/L
NSX250B/F
NSX250N/H/S/L
NSX400F/N/H/S/L
NSX400F/N/H/S/L
Micrologic
Trip unit
or th. relay
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 33 63
MA
MA
MA
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.3 M
or 6.3 E-M
NSX630F/N/H/S/L
Micrologic
630
250
320
400
500
630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
4.8
T
T
T
T
T
T
T
T
4.8
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
4.8
4.8
6.9
6.9
6.9
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
6.9
6.9
200
250
320
400
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
4.8
4.8
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
4.8
No discrimination.
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
122
558E4350.indd 122
09/11/2009 14:38:39
Complementary
technical information
Upstream
Trip unit
Downstream
Discrimination limit (kA)
C60L MA 1.6
C60L MA 2.5
C60L MA 4
C60L MA 6.3
C60L MA 10
C60L MA 10
C60L MA 12.5
C60L MA 16
C60L MA 25
C60L MA 40
C60L MA 40
NG125L MA 1.6
NG125L MA 2.5
NG125L MA 4
NG125L MA 6.3
NG125L MA 10
NG125L MA 10
NG125L MA 12.5
NG125L MA 16
NG125L MA 25
NG125L MA 40
NG125L MA 40
NG125L MA 63
NG125L MA 63
NS80H-MA 2.5
NS80H-MA 2.5
NS80H-MA 6.3
NS80H-MA 6.3
NS80H-MA 12.5
NS80H-MA 12.5
NS80H-MA 12.5
NS80H-MA 25
NS80H-MA 25
NS80H-MA 50
NS80H-MA 50
NS80H-MA 50
NS80H-MA 80
NSX100 B/F/N/H/S/L MA 2.5
NSX100 B/F/N/H/S/L MA 2.5
NSX100 B/F/N/H/S/L MA 6.3
NSX100 B/F/N/H/S/L MA 6.3
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 25
NSX100 B/F/N/H/S/L MA 25
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 100
NSX100 B/F/N/H/S/L MA 100
NSX100 B/F/N/H/S/L
NSX160 B/F/N/H/S/L
NSX250 B/F/N/H/S/L
NSX400 F/N/H/S/L
NSX630 F/N/H/S/L
NSX100B/F
NSX100N/H/S/L
NSX160B/F
NSX160N/H/S/L
NSX250B/F
NSX250N/H/S/L
NSX400F/N/H/S/L
NSX630F/N/H/S/L
NS630b/800/1000/1250/1600N/H
Micrologic 2.0
Trip unit
or th. relay
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 33 63
MA
MA
MA
Micrologic 1.3 M
Micrologic 1.3 M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
63/80
100
150
220
320
500
25/50
100
25/50
100
y 100
150
y 100
150
y 150
220
y 100
160
220
Micrologic 2.3 M 160
200
or 6.3 E-M
250
320
Micrologic 2.3 M 250
320
or 6.3 E-M
400
500
800
800
1000
1000
1250
1250
1600
1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
320
400
500
630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
123
558E4350.indd 123
09/11/2009 14:38:40
Complementary
technical information
Upstream
Trip unit
Downstream
Discrimination limit (kA)
C60L MA 1.6
C60L MA 2.5
C60L MA 4
C60L MA 6.3
C60L MA 10
C60L MA 10
C60L MA 12.5
C60L MA 16
C60L MA 25
C60L MA 40
C60L MA 40
NG125L MA 1.6
NG125L MA 2.5
NG125L MA 4
NG125L MA 6.3
NG125L MA 10
NG125L MA 10
NG125L MA 12.5
NG125L MA 16
NG125L MA 25
NG125L MA 40
NG125L MA 40
NG125L MA 63
NG125L MA 63
NS80H-MA 2.5
NS80H-MA 2.5
NS80H-MA 6.3
NS80H-MA 6.3
NS80H-MA 12.5
NS80H-MA 12.5
NS80H-MA 12.5
NS80H-MA 25
NS80H-MA 25
NS80H-MA 50
NS80H-MA 50
NS80H-MA 50
NS80H-MA 80
NSX100 B/F/N/H/S/L MA 2.5
NSX100 B/F/N/H/S/L MA 2.5
NSX100 B/F/N/H/S/L MA 6.3
NSX100 B/F/N/H/S/L MA 6.3
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 25
NSX100 B/F/N/H/S/L MA 25
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 100
NSX100 B/F/N/H/S/L MA 100
NSX100 B/F/N/H/S/L
NSX160 B/F/N/H/S/L
NSX250 B/F/N/H/S/L
NSX400 F/N/H/S/L
NSX630 F/N/H/S/L
NSX100B/F
NSX100N/H/S/L
NSX160B/F
NSX160N/H/S/L
NSX250B/F
NSX250N/H/S/L
NSX400F/N/H/S/L
NSX630F/N/H/S/L
NS630b/800/1000/1250/1600N/H
Micrologic 5.0/6.0/7.0
Inst position OFF
Trip unit
or th. relay
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 33 63
MA
MA
MA
Micrologic 1.3 M
Micrologic 1.3 M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.3 M
or 6.3 E-M
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
63/80
100
150
220
320
500
25/50
100
25/50
100
y 100
150
y 100
150
y 150
220
y 150
220
160
200
250
320
Micrologic 2.3 M 250
320
or 6.3 E-M
400
500
800
800
1000
1000
1250
1250
1600
1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
320
400
500
630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
124
558E4350.indd 124
09/11/2009 14:38:41
Complementary
technical information
Upstream
Trip unit
Downstream
Discrimination limit (kA)
C60L MA 1.6
C60L MA 2.5
C60L MA 4
C60L MA 6.3
C60L MA 10
C60L MA 10
C60L MA 12.5
C60L MA 16
C60L MA 25
C60L MA 40
C60L MA 40
NG125L MA 1.6
NG125L MA 2.5
NG125L MA 4
NG125L MA 6.3
NG125L MA 10
NG125L MA 10
NG125L MA 12.5
NG125L MA 16
NG125L MA 25
NG125L MA 40
NG125L MA 40
NG125L MA 63
NG125L MA 63
NS80H-MA 2.5
NS80H-MA 2.5
NS80H-MA 6.3
NS80H-MA 6.3
NS80H-MA 12.5
NS80H-MA 12.5
NS80H-MA 12.5
NS80H-MA 25
NS80H-MA 25
NS80H-MA 50
NS80H-MA 50
NS80H-MA 50
NS80H-MA 80
NSX100 B/F/N/H/S/L MA 2.5
NSX100 B/F/N/H/S/L MA 2.5
NSX100 B/F/N/H/S/L MA 6.3
NSX100 B/F/N/H/S/L MA 6.3
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 25
NSX100 B/F/N/H/S/L MA 25
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 100
NSX100 B/F/N/H/S/L MA 100
NSX100 B/F/N/H/S/L
NSX160 B/F/N/H/S/L
NSX250 B/F/N/H/S/L
NSX400 F/N/H/S/L
NSX100B/F
NSX100N/H/S/L
NSX160B/F
NSX160N/H/S/L
NSX250B/F
NSX250N/H/S/L
NSX400F/N/H/S/L
NSX630F/N/H/S/L
NS630bN/H
Micrologic 5.0 - 6.0 - 7.0
Trip unit
or th. relay
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 33 63
MA
MA
MA
Micrologic 1.3 M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.3 M
or 6.3 E-M
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
63/80
100
150
220
320
25/50
100
25/50
100
y 100
150
y 100
150
y 150
220
y 150
220
160
200
250
320
Micrologic 2.3 M 250
320
or 6.3 E-M
Inst 15 In
NS800N/H
Micrologic 5.0 - 6.0 - 7.0
Inst 15 In
320
400
500
630
320
400
500
630
800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
No discrimination.
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
125
558E4350.indd 125
09/11/2009 14:38:42
Complementary
technical information
Upstream
Trip unit
Downstream
Discrimination limit (kA)
C60L MA 1.6
C60L MA 2.5
C60L MA 4
C60L MA 6.3
C60L MA 10
C60L MA 10
C60L MA 12.5
C60L MA 16
C60L MA 25
C60L MA 40
C60L MA 40
NG125L MA 1.6
NG125L MA 2.5
NG125L MA 4
NG125L MA 6.3
NG125L MA 10
NG125L MA 10
NG125L MA 12.5
NG125L MA 16
NG125L MA 25
NG125L MA 40
NG125L MA 40
NG125L MA 63
NG125L MA 63
NS80H MA 2.5
NS80H MA 2.5
NS80H MA 6.3
NS80H MA 6.3
NS80H MA 12.5
NS80H MA 12.5
NS80H MA 12.5
NS80H MA 25
NS80H MA 25
NS80H MA 50
NS80H MA 50
NS80H MA 50
NS80H MA 80
NSX100 B/F/N/H/S/L MA 2.5
NSX100 B/F/N/H/S/L MA 2.5
NSX100 B/F/N/H/S/L MA 6.3
NSX100 B/F/N/H/S/L MA 6.3
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 25
NSX100 B/F/N/H/S/L MA 25
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 100
NSX100 B/F/N/H/S/L MA 100
NSX100 B/F/N/H/S/L
NSX160 B/F/N/H/S/L
NSX250 B/F/N/H/S/L
NSX400 F/N/H/S/L
NSX100B/F
NSX100N/H/S/L
NSX160B/F
NSX160N/H/S/L
NSX250B/F
NSX250N/H/S/L
NSX400F/N/H/S/L
NSX630F/N/H/S/L
NS630b/800L
Micrologic 2.0
Trip unit
or th. relay
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 33 63
MA
MA
MA
Micrologic 1.3 M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.3 M
or 6.3 E-M
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
63/80
100
150
220
320
25/50
100
25/50
100
y 100
160
y 100
160
y 150
220
y 150
220
160
200
250
320
Micrologic 2.3 M 250
320
or 6.3 E-M
Micrologic 5.0/6.0/7.0
Inst 15 In
320
400
500
630
800
250
320
400
500
630
800
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
18
18
18
T
T
T
T
T
T
T
T
T
T
T
T
18
18
18
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
18
18
18
18
12
12
18
18
18
T
T
T
T
T
T
T
T
T
T
T
T
18
18
18
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
18
18
18
18
12
12
12
12
No discrimination.
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
126
558E4350.indd 126
09/11/2009 14:38:43
Complementary
technical information
Upstream: NS1000
Downstream: C60LMA, NG125LMA,
NS80H-MA, NSX100 to 630
Upstream
Trip unit
Downstream
Discrimination limit (kA)
C60L MA 1.6
C60L MA 2.5
C60L MA 4
C60L MA 6.3
C60L MA 10
C60L MA 10
C60L MA 12.5
C60L MA 16
C60L MA 25
C60L MA 40
C60L MA 40
NG125L MA 1.6
NG125L MA 2.5
NG125L MA 4
NG125L MA 6.3
NG125L MA 10
NG125L MA 10
NG125L MA 12.5
NG125L MA 16
NG125L MA 25
NG125L MA 40
NG125L MA 40
NG125L MA 63
NG125L MA 63
NS80H-MA 2.5
NS80H-MA 2.5
NS80H-MA 6.3
NS80H-MA 6.3
NS80H-MA 12.5
NS80H-MA 12.5
NS80H-MA 12.5
NS80H-MA 25
NS80H-MA 25
NS80H-MA 50
NS80H-MA 50
NS80H-MA 50
NS80H-MA 80
NSX100 B/F/N/H/S/L MA 2.5
NSX100 B/F/N/H/S/L MA 2.5
NSX100 B/F/N/H/S/L MA 6.3
NSX100 B/F/N/H/S/L MA 6.3
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 25
NSX100 B/F/N/H/S/L MA 25
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 100
NSX100 B/F/N/H/S/L MA 100
NSX100 B/F/N/H/S/L
NSX160 B/F/N/H/S/L
NSX250 B/F/N/H/S/L
NSX400 F/N/H/S/L
NSX100B/F
NSX100N/H/S/L
NSX160B/F
NSX160N/H/S/L
NSX250B/F
NSX250N/H/S/L
NSX400F/N/H/S/L
NSX630F/N/H/S/L
NS1000N/H
Micrologic 5.0/6.0/7.0
Trip unit
or th. relay
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 33 63
MA
MA
MA
Micrologic 1.3 M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.3 M
or 6.3 E-M
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
63/80
100
150
220
320
25/50
100
25/50
100
y 100
150
y 100
150
y 150
220
y 150
220
160
200
250
320
Micrologic 2.3 M 250
320
or 6.3 E-M
400
Inst 15 In
500
630
800
1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NS1000L
Micrologic 5.0/6.0/7.0
Inst 15 In
1000
400
500
630
800
1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
18
18
T
T
T
T
T
T
T
T
T
T
T
T
18
18
18
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
18
18
18
18
12
12
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
18
18
18
18
12
12
12
12
No discrimination.
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
127
558E4350.indd 127
09/11/2009 14:38:43
Complementary
technical information
Upstream
Trip unit
Downstream
Discrimination limit (kA)
C60L MA 1.6
C60L MA 2.5
C60L MA 4
C60L MA 6.3
C60L MA 10
C60L MA 10
C60L MA 12.5
C60L MA 16
C60L MA 25
C60L MA 40
C60L MA 40
NG125L MA 1.6
NG125L MA 2.5
NG125L MA 4
NG125L MA 6.3
NG125L MA 10
NG125L MA 10
NG125L MA 12.5
NG125L MA 16
NG125L MA 25
NG125L MA 40
NG125L MA 40
NG125L MA 63
NG125L MA 63
NS80H-MA 2.5
NS80H-MA 2.5
NS80H-MA 6.3
NS80H-MA 6.3
NS80H-MA 12.5
NS80H-MA 12.5
NS80H-MA 12.5
NS80H-MA 25
NS80H-MA 25
NS80H-MA 50
NS80H-MA 50
NS80H-MA 50
NS80H-MA 80
NSX100 B/F/N/H/S/L MA 2.5
NSX100 B/F/N/H/S/L MA 2.5
NSX100 B/F/N/H/S/L MA 6.3
NSX100 B/F/N/H/S/L MA 6.3
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 25
NSX100 B/F/N/H/S/L MA 25
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 100
NSX100 B/F/N/H/S/L MA 100
NSX100 B/F/N/H/S/L
NSX160 B/F/N/H/S/L
NSX250 B/F/N/H/S/L
NSX400 F/N/H/S/L
NSX630 F/N/H/S/L
NSX100B/F
NSX100N/H/S/L
NSX160B/F
NSX160N/H/S/L
NSX250B/F
NSX250N/H/S/L
NSX400F/N/H/S/L
NSX630F/N/H/S/L
NS1200N/H
Micrologic 5.0/ 6.0/7.0
Trip unit
or th. relay
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 33 63
MA
MA
MA
Micrologic 1.3 M
Micrologic 1.3 M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.3 M
or 6.3 E-M
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
63/80
100
150
220
320
500
25/50
100
25/50
100
y 100
150
y 100
150
y 150
220
y 150
220
160
200
250
320
Micrologic 2.3 M 250
320
or 6.3 E-M
400
500
Inst 15 In
630
800
1000
1250
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
NS1600N/H
Micrologic 5.0/ 6.0/7.0
Inst 15 In
1600
630
800
1000
1250
1600
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
128
558E4350.indd 128
09/11/2009 14:38:44
Complementary
technical information
Upstream
Trip unit
Downstream
Discrimination limit (kA)
C60L MA 1.6
C60L MA 2.5
C60L MA 4
C60L MA 6.3
C60L MA 10
C60L MA 10
C60L MA 12.5
C60L MA 16
C60L MA 25
C60L MA 40
C60L MA 40
NG125L MA 1.6
NG125L MA 2.5
NG125L MA 4
NG125L MA 6.3
NG125L MA 10
NG125L MA 10
NG125L MA 12.5
NG125L MA 16
NG125L MA 25
NG125L MA 40
NG125L MA 40
NG125L MA 63
NG125L MA 63
NS80H-MA 2.5
NS80H-MA 2.5
NS80H-MA 6.3
NS80H-MA 6.3
NS80H-MA 12.5
NS80H-MA 12.5
NS80H-MA 12.5
NS80H-MA 25
NS80H-MA 25
NS80H-MA 50
NS80H-MA 50
NS80H-MA 50
NS80H-MA 80
NSX100 B/F/N/H/S/L MA 2.5
NSX100 B/F/N/H/S/L MA 2.5
NSX100 B/F/N/H/S/L MA 6.3
NSX100 B/F/N/H/S/L MA 6.3
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 25
NSX100 B/F/N/H/S/L MA 25
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 100
NSX100 B/F/N/H/S/L MA 100
NSX100 B/F/N/H/S/L
NSX160 B/F/N/H/S/L
NSX250 B/F/N/H/S/L
NSX400 F/N/H/S/L
NSX100B/F
NSX100N/H/S/L
NSX160B/F
NSX160N/H/S/L
NSX250B/F
NSX250N/H/S/L
NSX400F/N/H/S/L
NSX630F/N/H/S/L
NS630b/800/1000L
Micrologic 5.0/6.0/7.0
Trip unit
or th. relay
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 33 63
MA
MA
MA
Micrologic 1.3 M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.3 M
or 6.3 E-M
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
1/1.6
1.6/2.5
2.5/4
4/6.3
5.5/8
7 /10
9/13
12/18
17/25
23/32
30/40
37/50
48/65
63/80
100
150
220
320
25/50
100
25/50
100
y 100
150
y 100
150
y 150
220
y 150
220
160
200
250
320
Micrologic 2.3 M 250
320
or 6.3 E-M
400
Inst OFF
320
400
500
630
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
18
18
18
18
18
T
T
T
T
T
T
T
T
T
T
T
T
18
18
18
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
12
800
800
1000
1000
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
18
18
18
18
12
12
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
18
18
18
18
12
12
12
No discrimination.
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
129
558E4350.indd 129
09/11/2009 14:38:45
Complementary
technical information
Upstream
Trip unit
Downstream
Discrimination limit (kA)
C60L MA 1.6
C60L MA 2.5
C60L MA 4
C60L MA 6.3
C60L MA 10
C60L MA 10
C60L MA 12.5
C60L MA 16
C60L MA 25
C60L MA 40
C60L MA 40
NG125L MA 1.6
NG125L MA 2.5
NG125L MA 4
NG125L MA 6.3
NG125L MA 10
NG125L MA 10
NG125L MA 12.5
NG125L MA 16
NG125L MA 25
NG125L MA 40
NG125L MA 40
NG125L MA 63
NG125L MA 63
NS80H-MA 2.5
NS80H-MA 2.5
NS80H-MA 6.3
NS80H-MA 6.3
NS80H-MA 12.5
NS80H-MA 12.5
NS80H-MA 12.5
NS80H-MA 25
NS80H-MA 25
NS80H-MA 50
NS80H-MA 50
NS80H-MA 50
NS80H-MA 80
NSX100 B/F/N/H/S/L MA 2.5
NSX100 B/F/N/H/S/L MA 2.5
NSX100 B/F/N/H/S/L MA 6.3
NSX100 B/F/N/H/S/L MA 6.3
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 12.5
NSX100 B/F/N/H/S/L MA 25
NSX100 B/F/N/H/S/L MA 25
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 50
NSX100 B/F/N/H/S/L MA 100
NSX100 B/F/N/H/S/L MA 100
NSX100 B/F/N/H/S/L
NSX160 B/F/N/H/S/L
NSX250 B/F/N/H/S/L
NSX400 F/N/H/S/L
NSX630 F/N/H/S/L
NSX100B/F
Trip unit
or th. relay
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 06
LRD 07
LRD 08
LRD 10
LRD 12
LRD 14
LRD 16
LRD 21
LRD 22
LRD 32
LRD 33 55
LRD 33 57
LRD 33 59
LRD 33 63
MA
MA
MA
Micrologic 1.3 M
Micrologic 1.3 M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.2 M
or 6.2 E-M
Micrologic 2.3 M
or 6.3 E-M
2000
2000
2500
2500
1600
1600
2000
2000
1/1.6
T
T
T
T
T
T
1.6/2.5
T
T
T
T
T
T
2.5/4
T
T
T
T
T
T
4/6.3
T
T
T
T
T
T
5.5/8
T
T
T
T
T
T
7 /10
T
T
T
T
T
T
9/13
T
T
T
T
T
T
12/18
T
T
T
T
T
T
17/25
T
T
T
T
T
T
23/32
T
T
T
T
T
T
30/40
T
T
T
T
T
T
1/1.6
T
T
T
T
T
T
1.6/2.5
T
T
T
T
T
T
2.5/4
T
T
T
T
T
T
4/6.3
T
T
T
T
T
T
5.5/8
T
T
T
T
T
T
7 /10
T
T
T
T
T
T
9/13
T
T
T
T
T
T
12/18
T
T
T
T
T
T
17/25
T
T
T
T
T
T
23/32
T
T
T
T
T
T
30/40
T
T
T
T
T
T
37/50
T
T
T
T
T
T
48/65
T
T
T
T
T
T
1/1.6
T
T
T
T
T
T
1.6/2.5
T
T
T
T
T
T
2.5/4
T
T
T
T
T
T
4/6.3
T
T
T
T
T
T
5.5/8
T
T
T
T
T
T
7 /10
T
T
T
T
T
T
9/13
T
T
T
T
T
T
12/18
T
T
T
T
T
T
17/25
T
T
T
T
T
T
23/32
T
T
T
T
T
T
30/40
T
T
T
T
T
T
37/50
T
T
T
T
T
T
48/65
T
T
T
T
T
T
1/1.6
T
T
T
T
T
T
1.6/2.5
T
T
T
T
T
T
2.5/4
T
T
T
T
T
T
4/6.3
T
T
T
T
T
T
5.5/8
T
T
T
T
T
T
7 /10
T
T
T
T
T
T
9/13
T
T
T
T
T
T
12/18
T
T
T
T
T
T
17/25
T
T
T
T
T
T
23/32
T
T
T
T
T
T
30/40
T
T
T
T
T
T
37/50
T
T
T
T
T
T
48/65
T
T
T
T
T
T
63/80
T
T
T
T
T
T
100
T
T
T
T
T
T
150
T
T
T
T
T
T
220
T
T
T
T
T
T
320
T
T
T
T
T
T
500
T
T
T
T
T
T
25/50
T
T
T
T
T
T
100
T
T
T
T
T
T
NSX100N/H/S/L
25/50
T
T
T
T
T
T
100
T
T
T
T
T
T
NSX160B/F
y 100
T
T
T
T
T
T
150
T
T
T
T
T
T
NSX160N/H/S/L
y 100
T
T
T
T
T
T
150
T
T
T
T
T
T
NSX250B/F
y 150
T
T
T
T
T
T
220
T
T
T
T
T
T
NSX250N/H/S/L
y 150
T
T
T
T
T
T
220
T
T
T
T
T
T
NSX400F/N/H/S/L
160
T
T
T
T
T
T
200
T
T
T
T
T
T
250
T
T
T
T
T
T
320
T
T
T
T
T
T
NSX630F/N/H/S/L
Micrologic 2.3 M 250
T
T
T
T
T
T
or 6.3 E-M
320
T
T
T
T
T
T
400
T
T
T
T
T
T
500
T
T
T
T
T
T
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
2500
2500
3200
3200
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
130
558E4350.indd 130
09/11/2009 14:38:45
Complementary
technical information
Network 220/240 V
Upstream
NSX100B
NSX160B
NSX250B
Breaking capacity 40
(kA rms)
Downstream
NS80H-MA
LUB12
LUB22
GV2M u 23 A
Integral 63 u 32 A
Upstream
NSX100S
NSX100L
NSX160L
NSX160F
NSX160N
NSX160H
NSX160S
NSX160L
85
90
100
120
150
85
90
100
120
150
120
120
120
120
150
150
150
100
150
85
90
85
100
100
100
90
120
120
120
100
100
150
150
150
100
150
NSX400F
NSX630F
40
NSX400N
NSX630N
85
NSX400H
NSX630H
100
NSX400S
NSX400L
NSX630S
NSX630L
120
150
120
150
120
150
90
90
NSX250H
NSX250S
NSX250L
100
120
150
150
150
150
100
150
NSX250N
NSX100B
NSX160B
NSX250B
Breaking capacity 25
(kA rms)
NSX100F
NSX160F
NSX250F
36
NSX100N
NSX160N
NSX250N
50
NSX100H
NSX160H
NSX250H
70
25
36
40
50
NSX400N
NSX630N
50
NSX400H
70
150
150
NSX100S
NSX160S
NSX250S
100
NSX100L
NSX160L
NSX250L
150
100
100
100
50
100
100
150
150
150
50
150
150
150
150
NSX400S
NSX630S
100
NSX400L
NSX630F
NSX630N
NSX630H
NSX630S
NSX630L
150
36
50
70
100
150
100
150
150
100
150
NSX400F
NSX630F
Breaking capacity 36
(kA rms)
Downstream
NS80H-MA
Integral 63 u 32 A
NSX100H
85
85
Upstream
Upstream
NSX100N
100
100
100
100
Network 380/415 V
Downstream
NS80H-MA
LUB12
LUB22
GV2M u 14 A
GV2L u 18 A
GV2P u 18 A
GV3M
Integral 63 u 32 A
NSX100F
NSX250F
Breaking capacity 90
(kA rms)
Downstream
NS80H-MA
LUB12
LUB22
GV2M u 23 A
Integral 63 u 32 A
70
70
50
70
70
70
70
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
131
558E4350.indd 131
09/11/2009 14:38:46
Complementary
technical information
Network 440 V
Upstream
Breaking capacity
(kA rms)
Downstream
NS80H-MA
LUB12
LUB32
Integral 63 u 25 A
Upstream
Breaking capacity
(kA rms)
Downstream
NS80H-MA
Integral 63 u 25 A
NSX100B
NSX160B
NSX250B
20
NSX100F
NSX160F
NSX250F
35
NSX100N
NSX160N
NSX250N
50
NSX100H
NSX160H
NSX250H
65
NSX100S
NSX160S
NSX250S
90
NSX100L
NSX160L
NSX250L
130
50
65
65
65
90
90
90
130
130
130
130
NSX400H
NSX630H
65
NSX400S
NSX630S
90
NSX400L
NSX630L
130
130
90
90
130
90
NSX400F
NSX630F
35
NSX400N
NSX630N
50
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
132
558E4350.indd 132
09/11/2009 14:38:46
Complementary
technical information
Thermal
relay
Tesys U
LUC*X6
LUB12
LUC*1X
LUC*05
LUC*12
Tesys U
LUC*X6
LUB32
LUC*1X
LUC*05
LUC*12
LUC*18
LUC*32
Integral 63 LB1-LD03M16
LD1-LD030 LB1-LD03M21
LD4-LD130 LB1-LD03M22
LD4-LD030 LB1-LD03M53
LB1-LD03M55
LB1-LD03M57
LB1-LD03M61
NSX160H
70 kA
TM-D
Thermal
relay
Tesys U
LUC*X6
LUB12
LUC*1X
LUC*05
LUC*12
Tesys U
LUC*X6
LUB32
LUC*1X
LUC*05
LUC*12
LUC*18
LUC*32
Integral 63 LB1-LD03M16
LD1-LD030 LB1-LD03M21
LD4-LD130 LB1-LD03M22
LD4-LD030 LB1-LD03M53
LB1-LD03M55
LB1-LD03M57
LB1-LD03M61
NSX160L
150 kA
TM-D
NSX250H
70 kA
TM-D
NSX250S
100 kA
TM-D
NSX250L
150 kA
TM-D
125/160 80/100
125/160 80/100
125/160 160
200/250 160
200/250 160
200/250
0.15/0.6
0.35/1.4
1.25/5
3/12
0.15/0.6
0.35/1.4
1.25/5
3/12
4.5/18
8/32
10/13
11/18
18/25
23/32
28/40
35/ 50
45/63
70/70
70/70
70/70
70/70
5/70
5/70
5/70
5/70
5/70
5/70
100/100
100/100
100/100
100/100
5/100
5/100
5/100
5/100
5/100
5/100
150/150
150/150
150/150
150/150
5/150
5/150
5/150
5/150
5/150
5/150
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
150/150
150/150
150/150
150/150
150/150
150/150
150/150
Upstream
Breaking capacity
Trip unit
Downst.
NSX160S
100 kA
TM-D
NSX160H NSX160L
70 kA
100 kA
Micrologic
70/70
70/70
70/70
70/70
5/70
5/70
5/70
5/70
5/70
5/70
100/100
100/100
100/100
100/100
5/100
5/100
5/100
5/100
5/100
5/100
100/100
100/100
100/100
100/100
5/100
5/100
5/100
5/100
5/100
5/100
NSX160L
150 kA
NSX250H
70 kA
NSX250S
100 kA
NSX250L
150 kA
NSX400H
70 kA
NSX400S
100 kA
NSX400L
150 kA
160
160
250
250
250
400
400
400
0.15/0.6
0.35/1.4
1.25/5
3/12
0.15/0.6
0.35/1.4
1.25/5
3/12
4.5/18
8/32
10/13
11/18
18/25
23/32
28/40
35/50
45/63
100/100
100/100
100/100
100/100
5/100
5/100
5/100
5/100
5/100
5/100
100/100
150/150
150/150
150/150
150/150
5/150
5/150
5/150
5/150
5/150
5/150
150/150
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
150/150
150/150
150/150
150/150
150/150
150/150
150/150
70/70
70/70
70/70
70/70
70/70
70/70
70/70
100/100
100/100
100/100
100/100
100/100
100/100
100/100
150/150
150/150
150/150
150/150
150/150
150/150
150/150
70/70
70/70
70/70
70/70
5/70
5/70
5/70
5/70
5/70
5/70
70/70
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
133
558E4350.indd 133
09/11/2009 14:38:46
Complementary
technical information
Upstream: NSX160
Downstream: GV2 M
Upstream
Breaking capacity
Trip unit
Downst.
GV2 M01
GV2 M02
GV2 M03
GV2 M04
GV2 M05
GV2 M06
GV2 M07
GV2 M08
GV2 M10
GV2 M14
GV2 M16
GV2 M20
GV2 M21
GV2 M22
GV2 M32
Thermal
relay
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
NSX160B
25 kA
TM-D
Rating (A) 16
25
40
63
80
100
125
160
16
25
32
40/50 63
80
100
125
160
0.1/0.16
0.16/0.25
0.25/0.40
0.40/0.63
0.63/1
1/1.6
1.6/2.5
2.5/4
4/6.3
6/10
9/14
13/18
17/23
20/25
24/32
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
25/25
25/25
25/25
25/25
25/25
Upstream
Breaking capacity
Trip unit
Downst.
GV2 M01
GV2 M02
GV2 M03
GV2 M04
GV2 M05
GV2 M06
GV2 M07
GV2 M08
GV2 M10
GV2 M14
GV2 M16
GV2 M20
GV2 M21
GV2 M22
GV2 M32
Thermal
relay
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
GV2 M01
GV2 M02
GV2 M03
GV2 M04
GV2 M05
GV2 M06
GV2 M07
GV2 M08
GV2 M10
GV2 M14
GV2 M16
GV2 M20
GV2 M21
GV2 M22
GV2 M32
Thermal
relay
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
36/36
36/36
36/36
36/36
36/36
36/36
36/36
NSX160N/H/S/L
50/70/100/150 kA
TM-D
Rating (A)
16
25
32
40
50
63
80
100
125
160
0.1/0.16
0.16/0.25
0.25/0.40
0.40/0.63
0.63/1
1/1.6
1.6/2.5
2.5/4
4/6.3
6/10
9/14
13/18
17/23
20/25
24/32
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
Upstream
Breaking capacity
Trip unit
Downst.
NSX160F
36 kA
TM-D
NSX160B
25 kA
Micrologic
NSX160F
36 kA
Micrologic
NSX160F
50/70/100/150 kA
Micrologic
Rating (A)
160
160
160
0.1/0.16
0.16/0.25
0.25/0.40
0.40/0.63
0.63/1
1/1.6
1.6/2.5
2.5/4
4/6.3
6/10
9/14
13/18
17/23
20/25
24/32
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
50/50
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
134
558E4350.indd 134
09/11/2009 14:38:47
Complementary
technical information
Upstream: NSX160
Downstream: GV2 P
Upstream
Breaking capacity
Trip unit
Downst.
GV2 P01
GV2 P02
GV2 P03
GV2 P04
GV2 P05
GV2 P06
GV2 P07
GV2 P08
GV2 P10
GV2 P14
GV2 P16
GV2 P20
GV2 P21
GV2 P22
Thermal
relay
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
NSX160H
70 kA
TM-D
Rating (A)
80
100
125
160
80
100
125
160
0.1/0.16
0.16/0.25
0.25/0.40
0.40/0.63
0.63/1
1/1.6
1.6/2.5
2.5/4
4/6.3
6/10
9/ 14
13/18
17/23
20/25
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
Upstream
Breaking capacity
Trip unit
Downst.
GV2 P01
GV2 P02
GV2 P03
GV2 P04
GV2 P05
GV2 P06
GV2 P07
GV2 P08
GV2 P10
GV2 P14
GV2 P16
GV2 P20
GV2 P21
GV2 P22
Thermal
relay
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
NSX160S
100 kA
TM-D
NSX160L
150 kA
TM-D
NSX160H
70 kA
Micrologic
NSX160S
100 kA
Micrologic
NSX160L
150 kA
Micrologic
Rating (A)
80
100
125
160
160
160
160
0.1/0.16
0.16/0.25
0.25/0.40
0.40/0.63
0.63/1
1/1.6
1.6/2.5
2.5/4
4/6.3
6/10
9/14
13/18
17/23
20/25
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
135
558E4350.indd 135
09/11/2009 14:38:47
Complementary
technical information
Upstream: NSX160
Downstream: GV2 L
Upstream
Breaking capacity
Trip unit
Downst.
GV2 L03
GV2 L04
GV2 L05
GV2 L06
GV2 L07
GV2 L08
GV2 L10
GV2 L14
GV2 L16
GV2 L20
GV2 L22
Thermal
relay
LR2 D13 03
LR2 D13 04
LR2 D13 05
LR2 D13 06
LR2 D13 07
LR2 D13 08
LR2 D13 10
LR2 D13 14
LR2 D13 16
LR2 D13 21
LR2 D13 22
NSX160H
70 kA
TM-D
Rating (A)
80
100
125
160
80
100
125
160
0.25/0.40
0.40/0.63
0.63/1
1/1.6
1.6/2.5
2.5/4
4/6.3
7/10
9/13
12/18
17/25
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
Upstream
Breaking capacity
Trip unit
Downst.
GV2 L03
GV2 L04
GV2 L05
GV2 L06
GV2 L07
GV2 L08
GV2 L10
GV2 L14
GV2 L16
GV2 L20
GV2 L22
Thermal
relay
LR2 D13 03
LR2 D13 04
LR2 D13 05
LR2 D13 06
LR2 D13 07
LR2 D13 08
LR2 D13 10
LR2 D13 14
LR2 D13 16
LR2 D13 21
LR2 D13 22
NSX160S
100 kA
TM-D
NSX160L
150 kA
TM-D
NSX160H
70 kA
Micrologic
NSX160S
100 kA
Micrologic
NSX160L
150 kA
Micrologic
Rating (A)
80
100
125
160
160
160
160
0.25/0.40
0.40/0.63
0.63/1
1/1.6
1.6/2.5
2.5/4
4/6.3
7/10
9/13
12/18
17/25
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
70/70
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
150/150
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
136
558E4350.indd 136
09/11/2009 14:38:48
Complementary
technical information
Thermal
relay
LUC*X6
LUC*1X
LUC*05
LUC*12
LUC*X6
LUC*1X
LUC*05
LUC*12
LUC*18
LUC*32
NSX160H
65 kA
TM-D
Tesys U
LUB12
Tesys U
LUB32
Thermal
relay
LUC*X6
LUC*1X
LUC*05
LUC*12
LUC*X6
LUC*1X
LUC*05
LUC*12
LUC*18
LUC*32
NSX160L
130 kA
TM-D
NSX250H
65 kA
TM-D
NSX250S
90 kA
TM-D
NSX250L
130 kA
TM-D
125/160 80/100
125/160 80/100
125/160 160
200/250 160
200/250 160
200/250
0.15/0.6
0.35/1.4
1.25/5
3/12
0.15/0.6
0.35/1.4
1.25/5
3/12
4.5/18
8/32
65/65
65/65
65/65
65/65
5/65
5/65
5/65
5/65
5/65
5/65
90/90
90/90
90/90
90/90
5/90
5/90
5/90
5/90
5/90
5/90
130/130
130/130
130/130
130/130
5/130
5/130
5/130
5/130
5/130
5/130
65/65
65/65
65/65
65/65
65/65
65/65
65/65
65/65
65/65
65/65
90/90
90/90
90/90
90/90
90/90
90/90
90/90
90/90
90/90
90/90
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
Upstream
Breaking capacity
Trip unit
Downst.
NSX160S
90 kA
TM-D
NSX160H
65 kA
Micrologic
65/65
65/65
65/65
65/65
5/65
5/65
5/65
5/65
5/65
5/65
90/90
90/90
90/90
90/90
5/90
5/90
5/90
5/90
5/90
5/90
100/100
100/100
100/100
100/100
5/100
5/100
5/100
5/100
5/100
5/100
NSX160S
90 kA
Micrologic
NSX160L
130 kA
Micrologic
NSX250H
65 kA
Micrologic
NSX250S
90 kA
Micrologic
NSX250L
130 kA
Micrologic
NSX400H
65 kA
Micrologic
NSX400L
90 kA
Micrologic
160
160
250
250
250
400
400
0.15/0.6
0.35/1.4
1.25/5
3/12
0.15/0.6
0.35/1.4
1.25/5
3/12
4.5/18
8/32
90/90
90/90
90/90
90/90
5/90
5/90
5/90
5/90
5/90
5/90
130/130
130/130
130/130
130/130
5/130
5/130
5/130
5/130
5/130
5/130
65/65
65/65
65/65
65/65
65/65
65/65
65/65
65/65
65/65
65/65
90/90
90/90
90/90
90/90
90/90
90/90
90/90
90/90
90/90
90/90
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
100/100
65/65
65/65
65/65
65/65
5/65
5/65
5/65
5/65
5/65
5/65
Note: respect the basic rules of discrimination, in terms of overcurrent, short-circuit, see page6, or check curves with curve direct software.
137
558E4350.indd 137
09/11/2009 14:38:48
Complementary
technical information
A circuit supplying a motor may include one, two, three or four switchgear or
controlgear devices fulfilling one or more functions.
When a number of devices are used, they must be coordinated to ensure
optimum operation of the motor.
Protection of a motor circuit involves a number of parameters that depend on:
b the application (type of machine driven, operating safety, starting frequency, etc.)
b the level of service continuity imposed by the load or the application
b the applicable standards to ensure protection of life and property.
The necessary electrical functions are of very different natures:
b protection (motor-dedicated for overloads)
b control (generally with high endurance levels)
b isolation.
DB115198
Protection functions
Disconnection functions:
b Isolate a motor circuit prior to maintenance operations.
Short-circuit protection:
Protect the starter and the cables against major overcurrents (> 10 In).
Control:
Start and stop the motor, and, if applicable:
b gradual acceleration
b speed control.
Overload protection:
Protect the starter and the cables against minor overcurrents (< 10 In).
Additional specific protection:
b limitative fault protection (while the motor is running)
b preventive fault protection (monitoring of motor insulation with motor off).
Overloads (I < 10 In).
An overload may be caused by:
b an electrical problem, for instance on the mains (loss of a phase, voltage outside
tolerances, etc.)
b a mechanical problem, for instance excessive torque due to abnormally high
demands by the process or motor damage (bearing vibrations, etc.)
A further consequence of these two origins is excessively long starting.
Impedant short-circuit (10 < I < 50 In)
Deterioration of motor-winding insulation is the primary cause.
Short-circuit (I > 50 In)
This type of fault is relatively rare. A possible cause may be a connection error during
maintenance.
Overload protection
Thermal relays provide protection against this type of fault. They may be:
b integrated in the short-circuit protective device
b separate.
Short-circuit protection
This type of protection is provided by a circuit breaker.
Protection against insulation faults
This type of protection may be provided by:
b a residual current device (RCD)
b an insulation monitoring device (IMD).
138
04/11/2009 15:59:55
Complementary
technical information
Applicable standards
A circuit supplying a motor must comply with the general rules set out in IEC
standard 60947-4-1 and in particular with those concerning contactors, motor
starters and their protection as stipulated in IEC 60947-4-1, notably:
b coordination of the components of the motor circuit
b trip class for thermal relays
b contactor utilisation categories
b coordination of insulation.
139
04/11/2009 15:59:55
Complementary
technical information
DB115199
Iq current
(short-circuit I > 50 In)
This type of fault is relatively rare. A possible cause may be a connection error during
maintenance.
Short-circuit protection is provided by devices that open quickly.
IEC standard 60947-4-1 defines the Iq current as generally u 50 kA.
The Iq current is used to check the coordination of the switchgear and controlgear
installed on a motor supply circuit.
Following this test under extreme conditions, all the coordinated switchgear
and controlgear must remain operational.
140
04/11/2009 15:59:56
DB115200
Complementary
technical information
Class
10 A
10
20
30
1.05 Ir
1.2 Ir
1.5 Ir
7.2 Ir
t>2h
t>2h
t>2h
t>2h
t<2h
t<2h
t<2h
t<2h
t < 2 min.
t < 4 min.
t < 8 min.
t < 12 min.
2 y t y 10 s
4 y t y 10 s
6 y t y 20 s
9 y t y 30 s
141
04/11/2009 15:59:57
Complementary
technical information
Contactor usage
Typical applications
AC1
AC2
Category
heating, distribution
wire drawing machines
AC3
squirrel-cage motors
(cos j 0.45 for le y 100A)
(cos j 0.35 for le > 100A)
squirrel-cage motors
(cos j 0.45 for le y 100A)
(cos j 0.35 for le > 100A)
energisation
starting
switching off during running
regenerative braking
inching
starting
switching off during running
AC4
starting
switching off during running
regenerative braking
plugging
inching
DB115201
DB115202
142
04/11/2009 15:59:58
Complementary
technical information
DB115203
d
(in A rms)
5.8 to 8.6 In motor
Id
(in A peak)
Ordinary motor
Id = 2 Id = 11.5 In (A peak)
to Id = 2.1 Id = 18 In (A peak)
High-efficiency motor
5.8 to 8.6 In motor
Id = 2.2 Id = 12.5 In (A peak)
to Id = 2.5 Id = 21.5 In (A
peak)
Example: Upon energisation, a high-efficiency motor with an Id of 7.5 In produces a subtransient
current with a value between (depending on its characteritics):
v minimum = 16.5 In (in A peak)
v maximum = 18.8 In (in A peak).
143
04/11/2009 15:59:59
Complementary
technical information
b ordinary motor:
The starter components can be selected directly from the coordination tables,
whatever the values of the starting current (Id from 5.8 to 8.6 In) and the
subtransient current
b high-efficiency motors with Id y 7.5 In:
The starter components can be selected directly from the coordination tables,
whatever the values of the starting current and the subtransient current
b high-efficiency motors with Id > 7.5 In:
When circuit breakers are used for motor currents in the neighbourhood of their
rated current, they are set to provide minimum short-circuit protection at 19 In
motor (A peak).
There are two possibilities:
b the subtransient starting current is known (indicated by the motor manufacturer)
and is less than 19 In motor (A peak).
In this case, the starter components can be selected directly from the coordination
tables, whatever the value of the starting current (for Id > 7.5 In).
Example: for a 110 kW 380/415 V 3-phase motor, the selected components are:
NSX250-MA220/LC1-F225/LR9-F5371.
b the subtransient starting current is unknown or greater than 19 In motor
(A peak).
In this case, the value used for the motor power in the coordination tables should
be increased by 20 % to satisfy optimum starting and coordination conditions.
Example: for a 110 kW 380/415 V 3-phase motor, the selected components are
those for a motor power of 110 + 20 % = 132 kW:
NSX400 Micrologic 4.3M/LC1-F265/LR9-F5371
The starter components can be selected using the tables for direct-on-line starting.
Replace contactors LC1 by LC2.
b the components should be sized according to the current flowing in the motor
windings
b the mounting locations and connections of the various components of star-delta
starters should be selected according to the type of coordination required and the
protective devices implemented.
144
558E4500.indd 144
20/11/2009 14:26:36
Complementary
technical information
DB103905
Contactors KM2 and KM3 are sized for the line current divided by e KM1 can be
sized for the line current divided by 3, however, for the sake of homogeneity, it is
often identical to contactors KM2 and KM3.
DB103906
The starter components are selected from the special star-delta type 1
coordination tables.
Example: consider the following case:
b 45 kW motor supplied at 380 V
b star-delta starting
b separate thermal relay
b short-circuit current of 20 kA at the starter
b type 1 coordination.
The starter components are selected using the table on page167:
b circuit breaker: NSX100N-MA 100
b contactor: LC3-D50
b thermal relay: LR2-D3357.
DB103905
Contactors KM1, KM2 and KM3 are sized for the line current.
The starter components are selected from the direct-on-line type 2
coordination tables.
Example: consider the following case:
b 55 kW motor supplied at 415 V
b star-delta starting
b thermal protection built into the circuit breaker providing short-circuit protection
b short-circuit current of 45 kA at the starter
b type 2 coordination.
The starter components are selected using the table on page150:
b circuit breaker: NSX160H with Micrologic 6.2
b starter: LC1-F115 to be replaced by LC3-F115.
DB103907
145
04/11/2009 16:00:00
Complementary
technical information
Rating
Direct
b
b
b
0.2 to 1 A
1 to 5 A
5 to 25 A
Connecting
Using current trans.
b
b
v the characteristics of the current transformers are the following (as defined by
IEC44-1/44-3):
10
Multiple of the saturation current
146
04/11/2009 16:00:01
Type 2 coordination
(IEC 60947-4-1) 220/240 V
Complementary
technical information
DB115204
Motors
P (kW)
3
Circuit breakers
NS100/160/250 Micrologic 2.2M/6.2M
NSX400/630 Micrologic 2.3M/6.3M
NS800L/NS1000L Micrologic 5.0
B
40 kA
40 kA
-
F
85 kA
85 kA
-
N
90 kA
90 kA
-
H
100 kA
100 kA
-
Starting
Micrologic
Normal (class)
Long (class)
S
120 kA
120 kA
-
L
150 kA
150 kA
150 kA
5.0
10
20
Circuit breakers
Contactors
Type
Trip unit
Irth (A)
Irm (A)
Type
NSX100
Micrologic
12/25
13 Irth
LC1-D80
2.2 or 6.2
4
15
14
25
NSX100
Micrologic
12/25
13 Irth
LC1-D80
2.2 or 6.2
5.5
21
19
25
NSX100
Micrologic
12/25
13 Irth
LC1-D80
2.2 or 6.2
6.3
24
22
25
NSX100
Micrologic
12/25
13 Irth
LC1-D80
2.2 or 6.2
7.5
28
25
50
NSX100
Micrologic
25/50
13 Irth
LC1-D80
2.2 or 6.2
10
36
33
50
NSX100
Micrologic
25/50
13 Irth
LC1-D80
2.2 or 6.2
11
39
36
50
NSX100
Micrologic
25/50
13 Irth
LC1-D80
2.2 or 6.2
15
52
48
80
NSX100
Micrologic
50/100
13 Irth
LC1-D80
2.2 or 6.2
18.5
63
59
80
NSX100
Micrologic
50/100
13 Irth
LC1-D80
2.2 or 6.2
22
75
70
100
NSX100
Micrologic
50/100
13 Irth
LC1-D115 or LC1-F115
2.2 or 6.2
30
100
95
100
NSX100
Micrologic
50/100
13 Irth
LC1-D115 or LC1-F115
2.2 or 6.2
37
125
115
150
NSX160
Micrologic
70/150
13 Irth
LC1-D150 or LC1-F150
2.2 or 6.2
45
150
140
150
NSX160
Micrologic
70/150
13 Irth
LC1-D150 or LC1-F150
2.2 or 6.2
55
180
170
185
NSX250
Micrologic
100/220
13 Irth
LC1-F185
2.2 or 6.2
NSX400
Micrologic
160/320
13 Irth
LC1-F185
2.3 or 6.3
75
250
235
265
NSX400
Micrologic
160/320
13 Irth
LC1-F265
2.3 or 6.3
90
300
280
320
NSX400
Micrologic
160/320
13 Irth
LC1-F330
2.3 or 6.3
110
360
330
400
NSX630
Micrologic
250/500
13 Irth
LC1-F400
2.3 or 6.3
132
430
400
500
NSX630
Micrologic
250/500
13 Irth
LC1-F500
2.3 or 6.3
150
460
450
500
NSX630
Micrologic
250/500
13 Irth
LC1-F500
2.3 or 6.3
160
520
480
630
NS800L
Micrologic 5.0 320/800
8000
LC1-F630
200
630
580
630
NS800L
Micrologic 5.0 320/800
8000
LC1-F630
220
700
640
700
NS800L
Micrologic 5.0 320/800
9600
LC1-F780
250
800
730
800
NS1000L
Micrologic 5.0 400/1000
10000
LC1-F780
Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.
I (A) 220 V
12
I (A) 240 V
11
Ie max (A)
25
147
04/11/2009 16:00:01
Complementary
technical information
Type 2 coordination
(IEC 60947-4-1) 220/240 V
DB115205
Circuit breakers
NS80-MA
Starting (2): normal
Motors
N
-
Circuit breakers
P (kW)
I (A) 220 V
I (A) 240 V
Ie max (A)
Type
0.09
0.7
0.6
1
NS80H-MA
0.12
0.9
0.8
1
NS80H-MA
0.18
1.2
1.1
1.6
NS80H-MA
0.25
1.5
1.4
2.5
NS80H-MA
0.37
2
1.8
2.5
NS80H-MA
0.55
2.8
2.6
4
NS80H-MA
0.75
3.5
3.2
4
NS80H-MA
1.1
5
4.5
6
NS80H-MA
1.5
6.5
6
8
NS80H-MA
2.2
9
8
10
NS80H-MA
3
12
11
12.5
NS80H-MA
4
15
14
18
NS80H-MA
5.5
21
19
25
NS80H-MA
6.3
24
22
25
NS80H-MA
7.5
28
25
32
NS80H-MA
10
36
33
40
NS80H-MA
11
39
36
50
NS80H-MA
15
52
48
65
NS80H-MA
18.5
63
59
65
NS80H-MA
22
75
70
80
NS80H-MA
(1) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.
(2) For long starting (class 20), see the correspondence table for thermal relay.
Rating (A)
1.5
1.5
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
12.5
25
25
25
50
50
50
80
80
80
H
100 kA
LRD class 10 A
Contactors (1)
Irm (A)
13.5
13.5
22.5
32.5
32.5
57
57
82
113
138
163
250
325
325
450
550
650
880
880
1040
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D32
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D50
LC1-D50
LC1-D65
LC1-D65
LC1-D80
Thermal
relays
Type
LRD-05
LRD-05
LRD-06
LRD-07
LRD-07
LRD-08
LRD-08
LRD-10
LRD-33 12
LRD-33 14
LRD-33 16
LRD-33 21
LRD-33 22
LRD-33 22
LRD-33 53
LRD-33 55
LRD-33 57
LRD-33 59
LRD-33 59
LRD-33 63
L
-
148
04/11/2009 16:00:03
Type 2 coordination
(IEC 60947-4-1) 220/240 V
DB115205
Complementary
technical information
Circuit breakers
NSX100/160/250-MA
NSX400/630 Micrologic 1.3M
NS800L/NS1000L Micrologic 5.0
Starting (2): normal
Motors
B
F
N
H
40 kA
85 kA
90 kA
100 kA
40 kA
85 kA
90 kA
100 kA
LRD class 10 A, LR9 class 10
Circuit breakers
Contactors
Thermal relays
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D32
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D115
LC1-F115
LC1-D150
LC1-F150
LC1-D150
LC1-F150
LC1-F185
LC1-F265
LC1-F265
LC1-F330
LC1-F400
LC1-F500
LC1-F500
LC1-F630
Type
LRD-06
LRD-07
LRD-07
LRD-08
LRD-08
LRD-10
LRD-33 12
LRD-33 14
LRD-33 16
LRD-33 21
LRD-33 22
LRD-33 22
LRD-33 53
LRD-33 55
LRD-33 55
LRD-33 59
LRD-33 59
LRD-33 63
LRD-53 67
LR9-F53 67
LR9-D53 69
LR9-F53 69
LR9-D53 69
LR9-F53 69
LR9-F53 71
(1)
P (kW)
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
6.3
7.5
10
11
15
18.5
22
30
I (A) 220 V
1.2
1.5
2
2.8
3.5
5
6.5
9
12
15
21
24
28
36
39
52
63
75
100
I (A) 240 V
1.1
1.4
1.8
2.6
3.2
4.5
6
8
11
14
19
22
25
33
36
48
59
70
95
Ie max (A)
1.6
2.5
2.5
4
4
6
8
10
12.5
18
25
25
32
40
40
63
63
80
100
Type
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
Rating (A)
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
12.5
25
25
25
50
50
50
100
100
100
100
Irm (A)
23.5
32.5
32.5
57
57
82
113
138
163
250
325
325
450
550
550
700
900
1100
1300
37
125
115
150
NSX160-MA
150
1950
45
150
140
150
NSX160-MA
150
1950
55
180
170
185
220
265
320
400
500
500
630
S
120 kA
120 kA
-
L
150 kA
150 kA
150 kA
NSX250-MA
220
2420
132/220
NSX400-MA
320
2880
75
250
235
NSX400-MA
320
3500
LR9-F73 75
200/330
90
300
270
NSX400-MA
320
4160
LR9-F73 75
200/330
110
360
330
NSX630-MA
500
5700
LR9-F73 79
300/500
132
430
400
NSX630-MA
500
6500
LR9-F73 79
300/500
150
460
450
NSX630-MA
500
6500
LR9-F73 79
300/500
160
520
480
NS800L
800
8000
LR9-F73 81
380/630
Micrologic 5.0- LR off
200
630
580
630
NS800L
800
8000
LC1-F630
LR9-F73 81
380/630
Micrologic 5.0-LR off
220
700
640
700
NS800L
800
9600
LC1-F780
TC800/5 + LRD-10 630/1000
Micrologic 5.0-LR off
250
800
730
800
NS1000L
1000
10000
LC1-F780
TC800/5 + LRD-10 630/1000
Micrologic 5.0-LR off
(1) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.
(2) For long starting (class 20), see the correspondence table for thermal relay.
Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.
149
04/11/2009 16:00:04
Type 2 coordination
(IEC 60947-4-1) 380/415 V
Complementary
technical information
DB115204
Motors
P (kW)
7.5
10
11
15
18.5
22
30
37
45
55
75
90
Performance: U = 380/415 V
Circuit breakers
NS100/160/250 Micrologic 2.2M/6.2M
NSX400/630 Micrologic 2.3M/6.3M
NS800L/NS1000L Micrologic 5.0
B
25 kA
25 kA
-
F
36 kA
36 kA
-
N
50 kA
50 kA
-
H
70 kA
70 kA
-
Starting
Micrologic
Normal (class)
Long (class)
S
100 kA
100 kA
-
L
130 kA
130 kA
130 kA
5.0
10
20
Circuit breakers
Contactors (1)
Type
Trip unit/t.u.
Irth(A)
Irm(A) (2)
Type
NSX100
Micrologic 2.2 or 6.2
12/25
13 Irth
LC1-D80
NSX100
Micrologic 2.2 or 6.2
12/25
13 Irth
LC1-D80
NSX100
Micrologic 2.2 or 6.2
12/25
13 Irth
LC1-D80
NSX100
Micrologic 2.2 or 6.2
25/50
13 Irth
LC1-D80
NSX100
Micrologic 2.2 or 6.2
25/50
13 Irth
LC1-D80
NSX100
Micrologic 2.2 or 6.2
25/50
13 Irth
LC1-D80
NSX100
Micrologic 2.2 or 6.2
50/100
13 Irth
LC1-D80
NSX100
Micrologic 2.2 or 6.2
50/100
13 Irth
LC1-D80
NSX100
Micrologic 2.2 or 6.2
50/100
13 Irth
LC1-D115 or LC1-F115
NSX160
Micrologic 2.2 or 6.2
70/150
13 Irth
LC1-D115 or LC1-F115
NSX160
Micrologic 2.2 or 6.2
70/150
13 Irth
LC1-D150 or LC1-F150
NSX250
Micrologic 2.2 or 6.2
100/220
13 Irth
LC1-F185
NSX400
Micrologic 2.3 or 6.3
160/320
13 Irth
LC1-F225
110
205
200
NSX250
Micrologic 2.2 or 6.2
100/220
13 Irth
LC1-F225
NSX400
Micrologic 2.3 or 6.3
160/320
13 Irth
LC1-F225
132
250
240
265
NSX400
Micrologic 2.3 or 6.3
160/320
13 Irth
LC1-F265
160
300
280
320
NSX400
Micrologic 2.3 or 6.3
160/320
13 Irth
LC1-F330
200
370
340
400
NSX630
Micrologic 2.3 or 6.3
250/500
13 Irth
LC1-F400
220
408
385
500
NSX630
Micrologic 2.3 or 6.3
250/500
13 Irth
LC1-F500
250
460
425
500
NSX630
Micrologic 2.3 or 6.3
250/500
13 Irth
LC1-F500
630
NS800L
Micrologic 5.0
320/800
8000
LC1-F630
300
565
500
630
NS800L
Micrologic 5.0
320/800
8000
LC1-F630
335
620
560
630
NS800L
Micrologic 5.0
320/800
8000
LC1-F630
375
670
620
710
NS800L
Micrologic 5.0
320/800
9600
LC1-F780
400
710
660
710
NS800L
Micrologic 5.0
320/800
9600
LC1-F780
450
800
750
800
NS1000L
Micrologic 5.0
400/1000
10000
LC1-F780
(1) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.
(2) Ii for Micrologic 5.0 control unit.
Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.
I (A) 380 V
16
21
23
30
37
44
60
72
85
105
138
170
I (A) 415 V
14
19
21
28
35
40
55
66
80
100
135
165
Ie max (A)
20
25
25
50
50
50
80
80
100
115
150
185
225
220
150
04/11/2009 16:00:05
DB115205
Complementary
technical information
Type 2 coordination
(IEC 60947-4-1) 380/415 V
Circuit breakers, contactors and thermal relays
Performance: U = 380/415 V
Circuit breakers
NS80-MA
Starting (2): normal
Motors
Circuit breakers
P (kW)
I (A) 380 V
I (A) 415 V
Ie max (A)
Type
Rating (A)
0.18
0.7
0.6
1
NS80H-MA
1.5
0.25
0.9
0.8
1
NS80H-MA
1.5
0.37
1.2
1.1
1.6
NS80H-MA
2.5
0.55
1.6
1.5
2.5
NS80H-MA
2.5
0.75
2
1.8
2.5
NS80H-MA
2.5
1.1
2.8
2.6
4
NS80H-MA
6.3
1.5
3.7
3.4
4
NS80H-MA
6.3
2.2
5.3
4.8
6
NS80H-MA
6.3
3
7
6.5
8
NS80H-MA
12.5
4
9
8.2
10
NS80H-MA
12.5
5.5
12
11
12.5
NS80H-MA
12.5
7.5
16
14
16
NS80H-MA
25
10
21
19
25
NS80H-MA
25
11
23
21
25
NS80H-MA
25
15
30
28
32
NS80H-MA
50
18.5
37
34
40
NS80H-MA
50
22
43
40
50
NS80H-MA
50
30
59
55
63
NS80H-MA
80
37
72
66
80
NS80H-MA
80
(1) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.
(2) For long starting (class 20), see the correspondence table for thermal relay.
N
-
Irm (A)
13.5
13.5
22.5
32.5
32.5
57
57
82
113
138
163
250
325
325
450
550
650
880
1040
H
70 kA
LRD class 10 A
Contactors (1)
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D32
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D50
LC1-D50
LC1-D65
LC1-D80
L
-
Thermal relays
Type
Irth (2)
LRD-05
0.63/1
LRD-05
0.63/1
LRD-06
1/1.6
LRD-07
1.6/2.5
LRD-07
1.6/2.5
LRD-08
2.5/4
LRD-08
2.5/4
LRD-10
4/6
LRD-33 12
5.5/8
LRD-33 14
7/10
LRD-33 16
9/13
LRD-33 21
12/18
LRD-33 22
17/25
LRD-33 22
17/25
LRD-33 53
23/32
LRD-33 55
30/40
LRD-33 57
37/50
LRD-33 59
48/65
LRD-33 63
63/80
151
04/11/2009 16:00:05
DB115206
Complementary
technical information
Type 2 coordination
(IEC 60947-4-1) 380/415 V
Circuit breakers, contactors and thermal relays
Performance: U = 380/415 V
Circuit breakers
NSX100/160/250-MA
NSX400/630 Micrologic 1.3M
NS800L/NS1000L Micrologic 5.0
Starting (2): normal
Motors
P (kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
I (A) 380 V
1.2
1.6
2
2.8
3.7
5.3
7
9
12
16
21
23
30
37
43
59
72
85
I (A) 415 V
1.1
1.5
1.8
2.6
3.4
4.8
6.5
8.2
11
14
19
21
28
34
40
55
66
80
Ie max (A)
1.6
2.5
2.5
4
4
6
8
10
12.5
18
25
25
32
40
50
63
80
100
Circuit breakers
Type
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
Rating (A)
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
12.5
25
25
25
50
50
50
100
100
100
55
105
100
115
NSX160-MA
150
1500
75
140
135
150
NSX160-MA
150
1950
90
110
170
210
160
200
185
220
B
F
N
H
25 kA
36 kA
50 kA
70 kA
25 kA
36 kA
50 kA
70 kA
LRD class 10 A, other classes 10
Contactors (1)
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D32
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D115
LC1-F115
LC1-D115
LC1-F115
LC1-D150
LC1-F150
LC1-F185
LC1-F225
LC1-F265
Thermal relays
Type
LRD-06
LRD-07
LRD-07
LRD-08
LRD-08
LRD-10
LRD-33 12
LRD-33 14
LRD-33 16
LRD-33 21
LRD-33 22
LRD-33 22
LRD-33 53
LRD-33 55
LRD-33 57
LRD-33 59
LRD-33 63
LR9-D53 67
LR9-F53 67
LR9-D53 69
LR9-F53 69
LR9-D53 69
LR9-F53 69
LR9-F53 71
LR9-F53 71
S
100 kA
100 kA
-
L
130 kA
130 kA
130 kA
Irth (2)
1/1.6
1.6/2.5
1.6/2.5
2.5/4
2.5/4
4/6
5.5/8
7 /10
9/13
12/18
17/25
17/25
23/32
30/40
37/50
48/65
63/80
60/100
90/150
90/150
NSX250-MA
220
2420
132/220
NSX250-MA
220
2860
132/220
NSX400
320
2880
Micrologic 1.3M
132
250
230
265
NSX400
320
3500
LC1-F265
LR9-F73 75
200/330
Micrologic 1.3M
160
300
270
320
NSX400
320
4160
LC1-F330
LR9-F73 75
200/330
Micrologic 1.3M
200
380
361
400
NSX630
500
5700
LC1-F400
LR9-F73 79
300/500
Micrologic 1.3M
220
420
380
500
NSX630
500
6500
LC1-F500
LR9-F73 79
300/500
Micrologic 1.3M
250
460
430
500
NSX630
500
6500
LC1-F500
LR9-F73 79
300/500
Micrologic 1.3M
630
NS800L
800
8000
LC1-F630
LR9-F73 81
380/630
Micrologic 5.0 - LR off
300
565
500
630
NS800L
800
8000
LC1-F630
LR9-F73 81
380/630
Micrologic 5.0 - LR off
335
620
560
630
NS800L
800
8000
LC1-F630
LR9-F73 81
380/630
Micrologic 5.0 - LR off
375
670
620
710
NS800L
800
9600
LC1-F780
TC800/5 + LRD-10 630/1000
Micrologic 5.0 - LR off
400
710
660
710
NS800L
800
9600
LC1-F780
TC800/5 + LRD-10 630/1000
Micrologic 5.0 - LR off
450
800
750
800
NS1000L
1000
10000
LC1-F780
TC800/5 + LRD-10 630/1000
Micrologic 5.0 - LR off
(1) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.
(2) For long starting (class 20), see the correspondence table for thermal relay.
(3) Ii for Micrologic 5.0 control unit.
Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.
152
04/11/2009 16:00:08
DB119496
Complementary
technical information
Type 2 coordination
(IEC 60947-4-1) 380/415 V
Circuit breakers, contactors and thermal relays
Performance: U = 380/415 V
Circuit breakers
NS80H-MA
Starting (1): adjustable class 10 A to 30.
Motors
Circuit breakers
P (kW)
I (A) 380 V
I (A) 415 V
Ie max (A)
Type
Rating (A)
0.18
0.7
0.6
1
NS80H-MA
1.5
0.25
0.9
0.8
1
NS80H-MA
1.5
0.37
1.2
1.1
2.5
NS80H-MA
2.5
0.55
1.6
1.5
2.5
NS80H-MA
2.5
0.75
2
1.8
2.5
NS80H-MA
2.5
1.1
2.8
2.6
5
NS80H-MA
6.3
1.5
3.7
3.4
5
NS80H-MA
6.3
2.2
5.3
4.8
6.3
NS80H-MA
6.3
3
7
6.5
12.5
NS80H-MA
12.5
4
9
8.2
12.5
NS80H-MA
12.5
5.5
12
11
12.5
NS80H-MA
12.5
7.5
16
14
25
NS80H-MA
25
10
21
19
25
NS80H-MA
25
11
23
21
25
NS80H-MA
25
15
30
28
50
NS80H-MA
50
18.5
37
34
50
NS80H-MA
50
22
43
40
50
NS80H-MA
50
30
59
55
80
NS80H-MA
80
37
72
66
80
NS80H-MA
80
(1) For installation with a class 30 relay, a derating of 20 % must be apply on circuit breakers.
(2) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.
Irm (A)
13.5
13.5
32.5
32.5
32.5
70
70
82
163
163
163
325
325
325
650
650
650
1040
1040
N
-
H
70 kA
Contactors (2)
Type
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
L
-
Thermal relays
Type
Irth (A) (1)
LT6-P0M
0.2/1
LT6-P0M
0.2/1
LT6-P0M
1/5
LT6-P0M
1/5
LT6-P0M
1/5
LT6-P0M
1/5
LT6-P0M
1/5
LT6-P0M
5/25
LT6-P0M
5/25
LT6-P0M
5/25
LT6-P0M
5/25
LT6-P0M
5/25
LT6-P0M
5/25
LT6-P0M
5/25
LT6-P0M
on CT
LT6-P0M
on CT
LT6-P0M
on CT
LT6-P0M
on CT
LT6-P0M
on CT
153
04/11/2009 16:00:09
Type 2 coordination
(IEC 60947-4-1) 380/415 V
DB119497
Complementary
technical information
Motors
P (kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
I (A) 380 V
1.2
1.6
2
2.8
3.7
5.3
7
9
12
16
21
23
30
37
43
59
72
85
I (A) 415 V
1.1
1.5
1.8
2.6
3.4
4.8
6.5
8.2
11
14
19
21
28
34
40
55
66
80
Ie max (A)
1.6
2.5
2.5
4
4
6
8
10
12.5
18
25
25
32
40
50
63
80
100
Circuit breakers
Type
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
Rating (A)
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
12.5
25
25
25
50
50
50
100
100
100
55
105
100
115
NSX160-MA
150
1500
75
140
135
150
NSX160-MA
150
1950
90
110
170
210
160
200
185
220
F
36
36
-
N
50
50
-
Contactors (2)
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D32
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D115
LC1-F115
LC1-D115
LC1-F115
LC1-D150
LC1-F150
LC1-F185
LC1-F225
LC1-F265
LC1-F265
LC1-F330
LC1-F400
LC1-F500
LC1-F500
LC1-F630
H
70
70
-
Thermal relays
Type
LRD-06
LRD-07
LRD-07
LRD-08
LRD-08
LRD-10
LRD-33 12
LRD-33 14
LRD-33 16
LRD-33 21
LRD-33 22
LRD-33 22
LRD-33 53
LRD-33 55
LRD-33 57
LRD-33 59
LRD-33 63
LR9-D53 67
LR9-F53 67
LR9-D53 69
LR9-F53 69
LR9-D53 69
LR9-F53 69
LR9-F53 71
LR9-F53 71
S
100
100
-
L
130
130
130
NSX250-MA
220
2420
132/220
NSX250-MA
220
2860
132/220
NSX400-Micrologic 1.3 M 320
2880
132
250
230
265
NSX400-Micrologic 1.3 M 320
3500
LR9-F73 75
200/330
160
300
270
320
NSX400-Micrologic 1.3 M 320
4160
LR9-F73 75
200/330
200
380
361
400
NSX630-Micrologic 1.3 M 500
5700
LR9-F73 79
300/500
220
420
380
500
NSX630-Micrologic 1.3 M 500
6500
LR9-F73 79
300/500
250
460
430
500
NSX630-Micrologic 1.3 M 500
6500
LR9-F73 79
300/500
630
NS800L
800
8000
LR9-F73 81
380/630
Micrologic 5.0 - LR off
300
565
500
630
NS800L
800
8000
LC1-F630
LR9-F73 81
380/630
Micrologic 5.0 - LR off
335
620
560
630
NS800L
800
8000
LC1-F630
LR9-F73 81
380/630
Micrologic 5.0 - LR off
375
670
620
710
NS800L
800
9600
LC1-F780
TC800/5 + LRD-10 630/1000
Micrologic 5.0 - LR off
400
710
660
710
NS800L
800
9600
LC1-F780
TC800/5 + LRD-10 630/1000
Micrologic 5.0 - LR off
1000
10000
LC1-F780
TC800/5 + LRD-10 630/1000
450
800
750
800
NS1000L
Micrologic 5.0 - LR off
375
670
620
710
NS800L
800
9600
LC1-F800/780 LT6-P0M
on CT
Micrologic 5.0 - LR off
400
710
660
710
NS800L
800
9600
LC1-F800/780 LT6-P0M
on CT
Micrologic 5.0 - LR off
450
800
750
800
NS1000L
1000
10000
LC1-F800/780 LT6-P0M
on CT
Micrologic 5.0 - LR off
(1) For installation with a class 30 relay. a derating of 20 % must be apply on circuit breakers.
(2) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.
(3) Ii for Micrologic 5.0 control unit.
Note: where more than one association is possible for a rated power. if the motor starting current is high or unknown. the highest association shoud be applied.
154
04/11/2009 16:00:17
Complementary
technical information
Type 2 coordination
(IEC 60947-4-1) 440 V
DB115222
Motors
P (kW)
7.5
10
11
15
18.5
22
30
37
45
55
75
90
110
I (A) 440 V
13.7
19
20
26.5
33
39
51
64
76
90
125
146
178
Ie max (A)
25
25
25
50
50
50
80
80
80
100
150
150
185
132
215
220
160
200
220
250
300
256
320
353
400
460
265
320
400
400
500
630
630
630
720
720
800
Circuit breakers
NSX100/160/250 Micrologic 2.2 M/6.2 M
NSX400/630 Micrologic 2.3 M/6.3 M
NS630b/800/1000L
Micrologic 5.0
B
20 kA
-
Starting
Micrologic
Normal (class)
Long (class)
Circuit breakers
Type
NSX100
NSX100
NSX100
NSX100
NSX100
NSX100
NSX100
NSX100
NSX100
NSX100
NSX160
NSX160
NSX250
NSX400
NSX250
NSX400
NSX400
NSX400
NSX630
NSX630
NSX630
NS630bL
NS800L
NS800L
NS800L
NS800L
NS1000L
Trip unit/t.u.
Micrologic 2.2 or 6.2
Micrologic 2.2 or 6.2
Micrologic 2.2 or 6.2
Micrologic 2.2 or 6.2
Micrologic 2.2 or 6.2
Micrologic 2.2 or 6.2
Micrologic 2.2 or 6.2
Micrologic 2.2 or 6.2
Micrologic 2.2 or 6.2
Micrologic 2.2 or 6.2
Micrologic 2.2 or 6.2
Micrologic 2.2 or 6.2
Micrologic 2.2 or 6.2
Micrologic 2.3 or 6.3
Micrologic 2.3 or 6.3
Micrologic 2.3 or 6.3
Micrologic 2.3 or 6.3
Micrologic 2.3 or 6.3
Micrologic 2.3 or 6.3
Micrologic 2.3 or 6.3
Micrologic 2.3 or 6.3
Micrologic 5.0
Micrologic 5.0
Micrologic 5.0
Micrologic 5.0
Micrologic 5.0
Micrologic 5.0
Irth (A)
12/25
15/25
15/25
25/50
25/50
25/50
50/100
50/100
50/100
50/100
70/150
70/150
100/220
160/320
131/220
160/320
160/320
160/320
250/500
250/500
250/500
320/800
320/800
320/800
320/800
320/800
400/1000
F
35 kA
30 kA
-
N
50 kA
42 kA
-
H
65 kA
65 kA
-
S
90 kA
90 kA
-
L
130 kA
130 kA
130 kA
5.0
10
20
Contactors (2)
Type
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D115 or LC1-F115
LC1-D150 or LC1-F150
LC1-D150 or LC1-F150
LC1-F185
LC1-F185
LC1-F225
LC1-F225
LC1-F265
LC1-F330
LC1-F400
LC1-F400
LC1-F500
LC1-F630
LC1-F630
LC1-F630
LC1-F780
LC1-F780
LC1-F780
335
540
375
575
400
611
450
720
500
800
(1) Valid for 480 V NEMA.
(2) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.
(3) Ii for Micrologic 5.0 control unit.
Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.
155
04/11/2009 16:00:18
DB115219
Complementary
technical information
Type 2 coordination
(IEC 60947-4-1) 440 V
Circuit breakers, contactors and thermal relays
Performance (1): U = 440 V
Circuit breakers
NS80H-MA
Starting (3): normal
Motors
Circuit breakers
P (kW)
I (A) 440 V
Ie max (A)
Type
Rating (A)
0.25
0.7
1
NS80H-MA
1.5
0.37
1
1.6
NS80H-MA
2.5
0.55
1.4
1.6
NS80H-MA
2.5
0.75
1.7
2.5
NS80H-MA
2.5
1.1
2.4
2.5
NS80H-MA
2.5
1.5
3.1
4
NS80H-MA
6.3
2.2
4.5
6
NS80H-MA
6.3
3
5.8
6
NS80H-MA
6.3
4
8
8
NS80H-MA
12.5
5.5
10.5
12.5
NS80H-MA
12.5
7.5
13.7
16
NS80H-MA
25
10
19
25
NS80H-MA
25
11
20
25
NS80H-MA
25
15
26.5
32
NS80H-MA
50
18.5
33
40
NS80H-MA
50
22
39
40
NS80H-MA
50
30
52
63
NS80H-MA
80
37
63
63
NS80H-MA
80
45
76
80
NS80H-MA
80
(1) Valid for 480 V NEMA.
(2) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.
(3) For long starting (class 20), see the correspondence table for thermal relay.
N
-
Irm (A)
13.5
22.5
22.5
32.5
32.5
57
82
82
113
163
250
325
325
450
550
550
880
880
1040
H
65 kA
LRD class 10 A
Contactors (2)
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D32
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D50
LC1-D50
LC1-D65
LC1-D65
LC1-D80
Thermal relays
Type
LRD-05
LRD-06
LRD-06
LRD-07
LRD-07
LRD-08
LRD-10
LRD-10
LRD-33 12
LRD-33 16
LRD-33 21
LRD-33 22
LRD-33 22
LRD-33 53
LRD-33 55
LRD-33 55
LRD-33 59
LRD-33 59
LRD-33 63
L
-
156
04/11/2009 16:00:19
Type 2 coordination
(IEC 60947-4-1) 440 V
DB115220
Complementary
technical information
Motors
P (kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
55
I (A) 440 V
1
1.4
1.7
2.4
3.1
4.5
5.8
8
10.5
13.7
19
20
26.5
33
39
52
63
76
90
Ie max (A)
1.6
1.6
2.5
2.5
4
6
6
8
12.5
18
25
25
32
40
40
63
63
80
100
Circuit breakers
Type
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
Rating (A)
2.5
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
25
25
25
50
50
50
100
100
100
100
75
125
150
NSX160-MA
150
1950
90
140
150
NSX160-MA
150
1950
110
132
178
210
160
200
220
250
300
256
310
353
400
460
185
220
265
265
320
400
500
500
630
630
630
720
720
800
NSX250-MA
NSX250-MA
NSX400 Micrologic 1.3M
NSX400 Micrologic 1.3M
NSX400 Micrologic 1.3M
NSX630 Micrologic 1.3M
NSX630 Micrologic 1.3M
NSX630 Micrologic 1.3M
NS630bL Micrologic 5.0 - LR off
NS800L Micrologic 5.0 - LR off
NS800L Micrologic 5.0 - LR off
NS800L Micrologic 5.0 - LR off
NS800L Micrologic 5.0 - LR off
NS1000L Micrologic 5.0 - LR off
220
220
320
320
320
500
500
500
800
800
800
800
800
1000
2420
2860
3500
3500
4160
5500
6500
6500
8000
8000
8000
9600
9600
10000
F
N
H
S
35 kA
50 kA
65 kA
90 kA
30 kA
42 kA
65 kA
90 kA
LRD class 10 A, LR9 class 10.
Contactors (2)
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D32
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D115
LC1-F115
LC1-D150
LC1-F150
LC1-D150
LC1-F150
LC1-F185
LC1-F225
LC1-F265
LC1-F265
LC1-F330
LC1-F400
LC1-F500
LC1-F500
LC1-F630
LC1-F630
LC1-F630
LC1-F780
LC1-F780
LC1-F780
Thermal relays
Type
LRD-06
LRD-06
LRD-07
LRD-07
LRD-08
LRD-10
LRD-10
LRD-33 12
LRD-33 16
LRD-33 21
LRD-33 22
LRD-33 22
LRD-33 53
LRD-33 55
LRD-33 55
LRD-33 59
LRD-33 59
LRD-33 63
LR9-D53 67
LR9-F53 67
LR9-D53 69
LR9-F53 69
LR9-D53 69
LR9-F53 69
LR9-F53 71
LR9-F53 71
LR9-F73 75
LR9-F73 75
LR9-F73 79
LR9-F73 79
LR9-F73 79
LR9-F73 81
LR9-F73 81
LR9-F73 81
TC800/5 + LRD-10
TC800/5 + LRD-10
TC800/5 + LRD-10
L
130 kA
130 kA
130 kA
335
540
375
575
400
611
450
720
500
800
(1) Valid for 480 V NEMA.
(2) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.
(3) Ii for Micrologic 5.0 control unit.
(4) For long starting (class 20), see the correspondence table for thermal relay.
Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.
157
04/11/2009 16:00:20
DB119496
Complementary
technical information
Type 2 coordination
(IEC 60947-4-1) 440 V
Circuit breakers, contactors and thermal relays
Performance (1): U = 440 V
Circuit breakers
N
NS80H-MA
Starting (3): adjustable class 10 A to 30.
Motors
Circuit breakers
P (kW)
I (A) 440 V
Ie max (A)
Type
Rating (A)
Irm (A)
0.25
0.7
1
NS80H-MA
1.5
13.5
0.37
1
2.5
NS80H-MA
2.5
32.5
0.55
1.4
2.5
NS80H-MA
2.5
32.5
0.75
1.7
2.5
NS80H-MA
2.5
32.5
1.1
2.4
2.5
NS80H-MA
2.5
32.5
1.5
3.1
4
NS80H-MA
6.3
82
2.2
4.5
5
NS80H-MA
6.3
82
3
5.8
6.3
NS80H-MA
6.3
82
4
8
12.5
NS80H-MA
12.5
163
5.5
10.5
12.5
NS80H-MA
12.5
163
7.5
13.7
25
NS80H-MA
25
325
10
19
25
NS80H-MA
25
325
11
20
25
NS80H-MA
25
325
15
26.5
50
NS80H-MA
50
550
18.5
33
50
NS80H-MA
50
550
22
39
50
NS80H-MA
50
550
30
52
80
NS80H-MA
80
1040
37
63
80
NS80H-MA
80
1040
45
76
80
NS80H-MA
80
1040
(1) Valid for 480 V NEMA.
(2) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.
(3) For installation with a class 30 relay, a derating of 20 % must be apply on circuit breakers.
H
65 kA
Contactors (2)
Type
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
Thermal relays
Type
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
LT6-P0M
L
-
158
04/11/2009 16:00:22
Type 2 coordination
(IEC 60947-4-1) 440 V
DB115221
Complementary
technical information
B
20 kA
-
Motors
P (kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
55
I (A) 440 V
1
1.4
1.7
2.4
3.1
4.5
5.8
8
10.5
13.7
19
20
26.5
33
39
52
63
76
90
Ie max (A)
2.5
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
25
25
25
50
50
50
80
80
80
100
Circuit breakers
Type
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
NSX100-MA
Rating (A)
2.5
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
25
25
25
50
50
50
100
100
100
100
75
125
150
NSX160-MA
150
1950
90
140
150
NSX160-MA
150
1950
110
132
178
210
185
220
265
265
320
400
500
500
630
F
N
H
S
35 kA
50 kA
65 kA
90 kA
30 kA
42 kA
65 kA
90 kA
LRD class 10 A, LR9 class 10.
Contactors (3)
Type
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D40
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D115
LC1-F115
LC1-D150
LC1-F150
LC1-D150
LC1-F150
LC1-F185
LC1-F225
LC1-F265
LC1-F265
LC1-F330
LC1-F400
LC1-F500
LC1-F500
LC1-F630
L
130 kA
130 kA
130 kA
Thermal relays
Type
Irth (A) (1)
LTM R08
0.4/8
LTM R08
0.4/8
LTM R08
0.4/8
LTM R08
0.4/8
LTM R08
0.4/8
LTM R08
0.4/8
LTM R08
0.4/8
LTM R27
1.35/27
LTM R27
1.35/27
LTM R27
1.35/27
LTM R27
1.35/27
LTM R27
1.35/27
LTM R100
5/100
LTM R100
5/100
LTM R100
5/100
LTM R100
5/100
LTM R100
5/100
LTM R100
5/100
LTM R100
5/100
LTM R08
LTM R08
on CT
on CT
on CT
on CT
on CT
on CT
on CT
on CT
on CT
on CT
on CT
on CT
on CT
NSX250-MA
220
2420
LTM R08
NSX250-MA
220
2860
LTM R08
NSX400-MA
320
3500
160
256
NSX400-MA
320
3500
LTM R08
200
310
NSX400-MA
320
4000
LTM R08
220
353
NSX630-MA
500
5500
LTM R08
250
400
NSX630-MA
500
6500
LTM R08
300
460
NSX630-MA
500
6500
LTM R08
NS630bL
800
8000
LTM R08
Micrologic 5.0 - LR off
335
540
630
NS800L
800
8000
LC1-F630
LTM R08
on CT
Micrologic 5.0 - LR off
375
575
630
NS800L
800
8000
LC1-F630
LTM R08
on CT
Micrologic 5.0 - LR off
400
611
720
NS800L
800
9600
LC1-F780
LTM R08
on CT
Micrologic 5.0 - LR off
450
720
720
NS800L
800
9600
LC1-F780
LTM R08
on CT
Micrologic 5.0 - LR off
1000
10000
LC1-F780
500
800
800
NS1000L
LTM R08
on CT
Micrologic 5.0 - LR off
(1) For installation with a class 30 relay, a derating of 20 % must be apply on circuit breakers.
(2) Valid for 480 V NEMA.
(3) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.
Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.
159
04/11/2009 16:00:23
Type 2 coordination
(IEC 60947-4-1) 500/525 V
Complementary
technical information
DB115222
Motors
P (kW)
10
11
15
18.5
22
30
37
45
55
75
90
110
Circuit breakers
NSX100/160/250
Micrologic 2.2M/6.2M
NSX160/250
Micrologic 2.2M/6.2M
NSX400/630
Micrologic 2.3M/6.3M
NS800L Micrologic 5.0
B
F
N
H
S
L
15/12 kA 25/22 kA 36/35 kA 50/35 kA 65/40 kA 70/50 kA
Starting
Micrologic
Normal (class)
Long (class)
100 kA
5.0
10
20
Circuit breakers
Contactors (1)
Type
Dcl./t.u.
Irth (A)
Irm (A)
Type
NSX100
Micrologic 2.2 or 6.2
12/25
13Irth
LC1-D80
NSX100
Micrologic 2.2 or 6.2
12/25
13Irth
LC1-D80
NSX100
Micrologic 2.2 or 6.2
12/25
13Irth
LC1-D80
NSX100
Micrologic 2.2 or 6.2
25/50
13Irth
LC1-D80
NSX100
Micrologic 2.2 or 6.2
25/50
13Irth
LC1-D80
NSX100
Micrologic 2.2 or 6.2
25/50
13Irth
LC1-D80
NSX100
Micrologic 2.2 or 6.2
50/100
13Irth
LC1-D80
NSX100
Micrologic 2.2 or 6.2
50/100
13Irth
LC1-D80
NSX100
Micrologic 2.2 or 6.2
50/100
13Irth
LC1-D115 or LC1-F115
NSX160
Micrologic 2.2 or 6.2
70/150
13Irth
LC1-D115 or LC1-F115
NSX160
Micrologic 2.2 or 6.2
70/150
13Irth
LC1-D150 or LC1-F150
NSX250
Micrologic 2.2 or 6.2
100/220
13Irth
LC1-F185
NSX400
Micrologic 2.3 or 6.3
160/320
13Irth
LC1-F185
132
185
185
220
NSX250
Micrologic 2.2 or 6.2
100/220
13Irth
LC1-F265
NSX400
Micrologic 2.3 or 6.3
160/320
13Irth
LC1-F265
160
220
220
265
NSX400
Micrologic 2.3 or 6.3
160/320
13Irth
LC1-F265
200
280
280
320
NSX400
Micrologic 2.3 or 6.3
160/320
13Irth
LC1-F400
220
310
310
500
NSX630
Micrologic 2.3 or 6.3
250/500
13Irth
LC1-F500
250
360
360
500
NSX630
Micrologic 2.3 or 6.3
250/500
13Irth
LC1-F500
315
445
445
500
NSX630
Micrologic 2.3 or 6.3
250/500
13Irth
LC1-F500
630
NS800L
Micrologic 5.0
320/800
7200
LC1-F630
335
460
460
630
NS800L
Micrologic 5.0
320/800
8800
LC1-F630
355
500
500
630
NS800L
Micrologic 5.0
320/800
8800
LC1-F630
375
530
530
630
NS800L
Micrologic 5.0
320/800
8800
LC1-F630
400
570
570
710
NS800L
Micrologic 5.0
320/800
9600
LC1-F780
450
630
630
710
NS800L
Micrologic 5.0
320/800
9600
LC1-F780
(1) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.
Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.
I (A) 500 V
15
18.4
23
28.5
33
45
55
65
75
105
130
155
I (A) 525 V
15
18.4
23
28.5
33
45
55
65
75
105
130
155
Ie max (A)
25
25
25
50
50
50
80
80
100
115
150
185
160
04/11/2009 16:00:25
Complementary
technical information
Type 2 coordination
(IEC 60947-4-1) 690 V
DB115218
Circuit breakers
NS100L-STR22ME
NS400L-STR43ME
NS630LB/NS800LB - Micrologic 5.0
Starting
Normal (class)
Long (class)
Motors
P (kW)
10
15
18.5
22
30
37
45
55
75
Circuit breakers
Ie max (A)
Type
Trip unit/t.u.
20
NS100L
STR22ME
20
NS100L
STR22ME
25
NS100L
STR22ME
40
NS100L
STR22ME
50
NS100L
STR22ME
50
NS100L
STR22ME
50
NS100L
STR22ME
63
NS100L
STR22ME
80
NS100L
STR22ME
165
NS400L
STR43ME
90
94
165
NS400L
STR43ME
110
113
165
NS400L
STR43ME
132
135
165
NS400L
STR43ME
160
165
165
NS400L
STR43ME
200
203
230
NS400L
STR43ME
220
224
230
NS400L
STR43ME
250
253
255
NS400L
STR43ME
315
315
500
NS630LB
Micrologic 5.0
355
355
500
NS630LB
Micrologic 5.0
400
400
500
NS630LB
Micrologic 5.0
500
500
500
NS630LB
Micrologic 5.0
560
560
630
NS800LB
Micrologic 5.0
630
630
630
NS800LB
Micrologic 5.0
(1) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.
(2) Ii for Micrologic 5.0 control unit.
I (A) 690 V
11.5
17
20.2
24.2
33
40
47
58
76
Irth (A)
12/20
12/20
12/20
24/40
30/50
30/50
30/50
48/80
60/100
60/120
60/120
100/200
100/200
100/200
160/320
160/320
160/320
630
630
630
630
800
800
L
75 kA
75 kA
75 kA
STR43ME
10
20
Contactors (1)
Type
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1F-115
LC1F-115
LC1F-265
LC1F-265
LC1F-265
LC1F-265
LC1F-265
LC1F-330
LC1F-330
LC1F-400
LC1-F630
LC1-F630
LC1-F630
LC1-F630
LC1-F630
LC1-F630
161
04/11/2009 16:00:26
Complementary
technical information
Type 2 coordination
(IEC 60947-4-1) 690 V
DB115219
Circuit breakers
NS100L-MA
NS400L-MA
NS630LB/NS800LB - Micrologic 5.0
Starting (1): normal
other
Motors
Circuit breakers
P (kW)
I (A) 690 V
Ie max (A)
Type
Rating (A)
0.75
1.2
1.6
NS100L MA
2,5
1
1.5
2
NS100L MA
2,5
1.5
2
2.5
NS100L MA
2,5
2.2
2.8
4
NS100L MA
6,3
3
3.8
4
NS100L MA
6,3
4
4.9
6
NS100L MA
6,3
5.5
6.6
8
NS100L MA
12,5
7.5
8.9
10
NS100L MA
12,5
10
11.5
13
NS100L MA
25
15
17
18
NS100L MA
25
18.5
20.2
25
NS100L MA
25
22
24.2
25
NS100L MA
25
25
27.5
32
NS100L MA
50
30
33
40
NS100L MA
50
37
40
50
NS100L MA
50
45
47
50
NS100L MA
50
55
58
80
NS100L MA
100
75
76
80
NS100L MA
100
90
94
100
NS400L MA
320
110
113
150
NS400L MA
320
132
135
150
NS400L MA
320
160
165
165
NS400L MA
320
200
203
230
NS400L MA
320
220
224
230
NS400L MA
320
250
253
255
NS400L MA
320
315
315
500
NS630LB
Micrologic 5.0 - LR off
355
355
500
NS630LB
Micrologic 5.0 - LR off
400
400
500
NS630LB
Micrologic 5.0 - LR off
500
500
500
NS630LB
Micrologic 5.0 - LR off
560
560
630
NS800LB
Micrologic 5.0 - LR off
630
630
630
NS800LB
Micrologic 5.0 - LR off
(1) For long starting (class 20), see the correspondence table for thermal relay.
(2) Reversers: replace LC1 by LC2; star-delta starter: replace LC1 by LC3.
(3) Ii for Micrologic 5.0 control unit.
L
75 kA
75 kA
75 kA
LRD class 10 A
class 10
Contactors (2)
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D40
LC1-D40
LC1-D40
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1-D80
LC1F-115
LC1F-115
LC1F-265
LC1F-265
LC1F-265
LC1F-265
LC1F-330
LC1F-330
LC1F-400
LC1-F630
LC1-F630
LC1-F630
LC1-F630
LC1-F630
LC1-F630
Thermal relays
Type
Irth (A)
LRD-06
1/1,6
LRD-06
1,25/2
LRD-07
1,6/2,5
LRD-33 08
2,5/4
LRD-33 08
2,5/4
LRD-33 10
4/6
LRD-33 12
5,5/8
LRD-33 14
7 /10
LRD-33 16
9/13
LRD-33 21
12/18
LRD-33 22
17/25
LRD-33 22
17/25
LRD-33 53
23/32
LRD-33 55
30/40
LRD-33 57
37/50
LRD-33 57
37/50
LR9-F53 63
48/80
LR9-F53 63
48/80
LR9-F53 67
60/100
LR9-F53 69
90/150
LR9-F53 69
90/150
LR9-F53 71
132/220
LR9-F73 75
200/330
LR9-F73 75
200/330
LR9-F73 75
200/330
LR9-F73 79
300/500
LR9-F73 79
300/500
LR9-F73 79
300/500
LR9-F73 81
380/630
LR9-F73 81
380/630
LR9-F73 81
380/630
162
04/11/2009 16:00:26
Type 1 coordination
(IEC 60947-4-1)
DB115219
Complementary
technical information
"Iq" breaking performance: equal to the breaking capacity of the circuit breaker alone.
Starting (1): normal
LR2 class 10 A, LR9 class 10.
Motors
220/230 V
P
I
(kW) (A)
380 V
P
(kW)
0.37
0.55
0.75
I
(A)
1.2
1.6
3
415 V
P
(kW)
0.37
0.55
0.75
440 V (2)
P
I
(kW) (A)
0.37 1
0.55 1.4
0.75 1.7
1.1
2.4
I
(A)
1.1
1.5
1.8
2.8
3.7
5
6.6
8.5
1.1
1.5
2.2
3
4
2.5
3.5
4.8
6.5
8.2
1.5
2.2
3
4
500/525 V
P
I
(kW) (A)
0.55 1.2
0.75 1.5
660/690 V
P
I
(kW) (A)
0.75 1.2
1
1.5
1.1
1.5
2
2.6
3.1
4.5
5.8
7.9
3
4
5.5
5
6.5
9
1.5
2.2
3
4
5.5
2
2.8
3.8
4.9
6.6
7.5
8.9
10
11.5
15
18.5
17
21.3
0.37
1.8
0.55
2.8
1.1
1.5
2.2
4.4
6.1
8.7
1.1
1.5
2.2
3
4
3
4
11.5
14.5
5.5
7.5
11.5
15.5
5.5
7.5
9
11
14
17
5.5
7.5
9
10.4
13.7
16.9
7.5
9
10
12
14
15
5.5
20
11
22
11
21
11
20.1
11
18.4
7.5
28
15
30
15
28
15
26.5
18.5
22
28.5
33
11
39
37
44
22
25
40
47
22
39
15
18.5
22
30
34.6
52
30
51.5
30
45
33
39
18.5
64
30
59
30
37
55
66
37
42
37
37
64
55
22
75
37
72
45
80
45
49
55
45
76
80
Circuit breakers
Type
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D12
LC1-D18
LC1-D18
LC1-D18
LC1-D25
LC1-D25
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D50
LC1-D50
LC1-D65
LC1-D65
LC1-D65
LC1-D80
LC1-D80
LC1-D115
LC1-F115
LRD-06
LRD-06
LRD-07
LRD-07
LRD-08
LRD-08
LRD-10
LRD-12
LRD-14
LRD-14
LRD-16
LRD-21
LRD-21
LRD-16
LRD-22
LRD-21
LRD-22
LRD-32
LRD-33 55
LRD-33 57
LRD-33 57
LRD-33 59
LRD-33 57
LRD-33 59
LRD-33 61
LRD-33 57
LRD-33 63
LR9-D53 67
LR9-F53 63
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
Rating
(A)
2.5
2.5
2.5
2.5
6.3
6.3
6.3
12.5
12.5
12.5
12.5
25
25
25
25
25
50
50
50
50
50
50
50
80
80
80
80
80
Irth (1)
(A)
1/1.6
1/1.6
1.6/2.5
1.6/2.5
2.5/4
2.5/4
4/6
5.5/8
7/10
7/10
9/13
12/18
12/18
9/13
16/24
12/18
16/24
23/32
30/40
37/50
37/50
48/65
37/50
48/65
55/70
37/50
63/80
60/100
48/80
55
60
75
80
(1) For installation with a class 30 relay, a derating of 20 % must be apply on circuit breakers.
(2) Valid for 480 V NEMA.
(3) Reversers: replace LC1 by LC2.
Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.
163
04/11/2009 16:00:27
Type 1 coordination
(IEC 60947-4-1)
DB115219
Complementary
technical information
"Iq" breaking performance: equal to the breaking capacity of the circuit breaker alone.
Starting (1): normal
LRD class 10, others class 10.
Motors
220/230 V
P
I
(kW) (A)
380 V
P
(kW)
0.37
0.55
0.75
I
(A)
1.2
1.6
2
415 V
P
(kW)
0.37
0.55
0.75
440 V (2)
P
I
(kW) (A)
0.37 1
0.55 1.4
0.75 1.7
1.1
2.4
I
(A)
1.1
1.5
1.8
2.8
3.7
5
6.6
8.5
1.1
1.5
2.2
3
4
2.5
3.5
4.8
6.5
8.2
1.5
2.2
3
4
500/525 V
P
I
(kW) (A)
0.55 1.2
0.75 1.5
660/690 V
P
I
(kW) (A)
0.75 1.2
1
1.5
1.1
1.5
2
2.6
3.1
4.5
5.8
7.9
3
4
5.5
5
6.5
9
1.5
2.2
3
4
5.5
2
2.8
3.8
4.9
6.6
7.5
8.9
10
11.5
15
18.5
17
21.3
30
34.6
33
37
39
42
45
49
0.37
1.8
0.55
2.8
1.1
1.5
2.2
4.4
6.1
8.7
1.1
1.5
2.2
3
4
3
4
11.5
14.5
5.5
7.5
11.5
15.5
5.5
7.5
9
11
14
17
5.5
7.5
9
10.4
13.7
16.9
7.5
9
10
12
14
15
5.5
20
11
22
11
21
11
20.1
11
18.4
7.5
28
15
30
15
28
15
26.5
11
39
18.5
22
37
44
22
25
40
47
22
39
59
30
55
30
37
45
15
18.5
52
64
30
22
75
37
72
25
85
45
85
37
45
72
80
18.5
22
28.5
33
30
45
51.5
64
37
55
76
55
80
Circuit breakers
Type
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
Type
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D12
LC1-D12
LC1-D18
LC1-D18
LC1-D18
LC1-D25
LC1-D25
LC1-D32
LC1-D32
LC1-D40
LC1-D40
LC1-D50
LC1-D65
LC1-D65
LRD-06
LRD-06
LRD-07
LRD-07
LRD-08
LRD-08
LRD-10
LRD-33 12
LRD-33 14
LRD-33 14
LRD-33 16
LRD-33 21
LRD-33 21
LRD-33 16
LRD-33 22
LRD-33 21
LRD-33 22
LRD-33 32
LRD-33 55
LRD-33 57
LRD-33 57
LRD-33 57
LRD-33 59
Irth (1)
(A)
1/1.6
1/1.6
1.6/2.5
1.6/2.5
2.5/4
2.5/4
4/6
5.5/8
7/10
7/10
9/13
12/18
12/18
9/13
16/24
12/18
16/24
23/32
30/40
37/50
37/50
37/50
48/65
100
100
LC1-D80
LC1-D80
LRD-33 57
LRD-33 63
37/50
63/80
100
LC1-D95
LRD-33 65 80/104
55
60
100
LC1-D115 LR9-D53 63 48/80
30
100
55
100
55
96
75
80
100
LC1-D115 LR9-D53 67 60/100
(1) For installation with a class 30 relay, a derating of 20 % must be apply on circuit breakers.
(2) Valid for 480 V NEMA.
(3) Reversers: replace LC1 by LC2.
Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.
164
04/11/2009 16:00:29
Type 1 coordination
(IEC 60947-4-1)
DB115220
Complementary
technical information
"Iq" breaking performance: equal to the breaking capacity of the circuit breaker alone.
Starting (1): normal
class 10.
Motors
220/230 V
P
I
(kW) (A)
37
125
45
150
55
180
Circuit breaker
380 V
P
(kW)
55
75
90
110
I
(A)
105
140
170
415 V
P
I
(kW) (A)
75
135
440 V (2)
P
I
(kW) (A)
75
124
90
160
210
110
200
90
110
132
75
250
132
250
132
230
90
312
160
300
160
270
110
360
200
380
220
380
150
480
220
420
250
480
160
220
250
250
156
180
215
256
360
300
480
300
570
300
510
335
540
200
630
335
630
335
580
375
590
220
700
375
700
375
650
400
650
400
750
400
690
450
720
450
800
500
900
450
750
500
830
132
190
160
132
160
228
200
281
220
310
315
335
430
520
800
660/690 V
P
I
(kW) (A)
90
100
110
120
401
160
250
500/525 V
P
I
(kW) (A)
75
110
90
130
110
156
355
375
400
450
500
560
600
200
220
140
175
220
240
250
270
335
335
445
460
375
450
400
480
500
530
570
630
500
560
700
760
830
530
580
Type
Rating Type
(A)
NSX160B/F/N/H/S/L MA 150
LC1-D150
LC1-F150
NSX250B/F/N/H/S/L MA 220
LC1-F185
Irth
(A)
LR9-D53 69 90/150
LR9-F53 69 100/160
LR9-F53 71 132/220
NSX250B/F/N/H/S/L MA 220
NSX250B/F/N/H/S/L MA 220
LC1-F225
LC1-F265
LR9-F53 71 132/220
LR9-F53 71 132/220
NSX400F/N/H/S/L
Micrologic 1.3M
NSX400F/N/H/S/L
Micrologic 1.3M
NSX630F/N/H/S/L
Micrologic 1.3M
NSX630F/N/H/S/L
Micrologic 1.3M
NSX630F/N/H/S/L
Micrologic 1.3M
NSX630F/N/H/S/L
Micrologic 1.3M
NSX630F/N/H/S/L
Micrologic 1.3M
NS800N/H-NS1000L
Micrologic 5.0 - LR off
320
LC1-F265
LR9-F73 75 200/330
320
LC1-F330
LR9-F73 75 200/330
500
LC1-F400
LR9-F73 79 300/500
500
LC1-F400
LR9-F73 75 200/330
500
LC1-F500
LR9-F73 79 300/500
500
LC1-F500
LR9-F73 79 300/500
500
LC1-F630
LR9-F73 81 380/630
800
1000
LC1-F630
LR9-F73 81 380/630
800
1000
800
1000
800
1000
800
1000
1000
LC1-F630
LR9-F73 81 380/630
LC1-F800
LR2-F83 83 500/800
LC1-F800
LC1-BL33
LC1-BL33
LR2-F83 83 500/800
LR2-F83 83 500/800
LC1-BM33
LR2-F83 83 500/800
NS800N/H-NS1000L
Micrologic 5.0 - LR off
NS800N/H-NS1000L
Micrologic 5.0 - LR off
NS800N/H-NS1000L
Micrologic 5.0 - LR off
NS800N/H-NS1000L
Micrologic 5.0 - LR off
NS1000N/H
Micrologic 5.0 - LR off
NS1000N/H
Micrologic 5.0 - LR off
NS1250N/H
Micrologic 5.0 - LR off
Type
500
800
1000
LC1-BM33 LR2-F83 85 630/1000
560
900
300
970
560
1000 560
920
600
960
670
920
1250
LC1-BP33 LR2-F83 85 630/1000
600
1100 600
1000 670
1080 750
1020
(1) For long starting (class 20), see the correspondence table for thermal relay.
(2) Reversers: replace LC1 by LC2.
Note: where more than one association is possible for a rated power, if the motor starting current is high or unknown, the highest association shoud be applied.
165
04/11/2009 16:00:30
Type 1 coordination
(IEC 60947-4-1)
DB115222
Complementary
technical information
"Iq" breaking performance: equal to the breaking capacity of the circuit breaker alone.
Starting
Micrologic
Normal (class)
Long (class)
Motors
220/230 V
P
I
(kW) (A)
7,5
28
11
39
15
19
22
25
52
64
75
85
30
37
45
55
100
125
150
180
380 V
P
(kW)
15
19
22
30
I
(A)
30
37
44
59
37
45
72
85
55
75
90
105
140
170
110
210
415 V
P
(kW)
15
22
25
30
I
(A)
28
40
47
55
37
440 V (1)
P
I
(kW) (A)
15
26,5
22
39
72
30
37
45
51,5
64
76
55
75
100
135
55
75
96
124
90
160
110
200
90
110
132
156
180
215
75
90
250
312
132
160
250
300
132
160
230
270
160
110
360
380
360
401
250
220
250
480
380
420
480
220
150
200
220
250
430
300
480
256
500/525 V
P
I
(kW) (A)
19
28,5
22
33
30
45
37
55
75
90
110
110
130
156
132
190
160
200
228
281
310
445
460
500
530
570
630
160
520
300
570
300
510
335
540
220
315
335
355
375
400
200
630
335
630
335
580
375
590
450
220
700
375
700
375
650
400
650
400
750
400
690
450
720
250
300
800
450
800
450
750
500
900
500
830
500
560
920 600
1000 670
55
80
500
560
600
800
900
960 670
1080 750
660/690 V
P
I
(kW) (A)
30
33
37
34,6
39
42
45
49
55
75
90
110
60
80
100
120
132
160
140
175
200
220
250
335
220
240
270
335
375
450
400
480
500
560
700
760
830
530
580
5.0
10
20
Circuit breakers
Contactors (2)
Type
Trip unit
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX160B/F/N/H/S/L
Irth
(A)
25/50
25/50
25/50
48/80
50/100
48/80
50/100
50/100
50/100
70/150
Type
LC1-D32
LC1-D40
LC1-D50
LC1-D65
LC1-D65
LC1-D80
LC1-D95
LC1-D115 or LC1-F115
LC1-D115 or LC1-F115
LC1-D150 or LC1-F150
LC1-F185
LC1-F225
LC1-F265
NSX400F/N/H/S/L
NSX400F/N/H/S/L
LC1-F265
LC1-F330
NSX630F/N/H/S/L
NSX630F/N/H/S/L
NSX630F/N/H/S/L
NSX630F/N/H/S/L
250/500
250/500
250/500
250/500
LC1-F400
LC1-F500
LC1-F500
LC1-F630
NS800N/H
NS1000L
NS800N/H
NS1000L
NS800N/H
NS1000L
NS800N/H
NS1000L
NS800N/H
NS1000L
NS1000N/H
Micrologic 5.0
LC1-F630
Micrologic 5.0
320/800
400/1000
320/800
400/1000
320/800
400/1000
320/800
400/1000
320/800
400/1000
400/1000
NS1000N/H
Micrologic 5.0
400/1000 LC1-BM33
Micrologic 5.0
Micrologic 5.0
Micrologic 5.0
Micrologic 5.0
LC1-F630
LC1-F800
LC1-F800
LC1-BL33
LC1-BL33
LC1-BM33
166
04/11/2009 16:00:32
Type 1 coordination
(IEC 60947-4-1)
DB103921
Complementary
technical information
Motors
220/230 V
P
I
(kW) (A)
0.55
2.8
1.1
4.4
1.5
6.1
2.2
8.7
3
11.5
4
14.5
5.5
20
7.5
11
28
39
15
52
18.5
64
22
0.55
1.1
1.5
2.2
3
4
5.5
380 V
P
(kW)
1.5
2.2
3
4
5.5
7.5
I
(A)
3.7
5
6.6
8.5
11.5
15.5
11
15
18.5
22
22
30
37
44
30
37
59
72
75
2.8
4.4
6.1
8.7
11.5
14.5
20
1.5
2.2
3
4
5.5
7.5
3.7
5
6.6
8.5
11.5
15.5
7.5
11
28
39
22
30
37
44
15
11
15
18.5
22
52
18.5
64
30
37
59
72
22
75
25
85
45
85
30
100
(1) Valid for 480 V NEMA.
415 V
P
(kW)
1.5
2.2
3
4
5.5
7.5
9
11
15
22
25
I
(A)
3.5
4.8
6.5
8.2
11
14
17
21
28
40
47
30
37
55
66
45
1.5
2.2
3
4
5.5
7.5
9
11
15
22
25
80
3.5
4.8
6.5
8.2
11
14
17
21
28
40
47
30
37
55
66
45
55
440 V (1)
P
I
(kW) (A)
1.5
3.1
2.2
4.5
3
5.8
4
7.9
5.5
10.4
7.5
13.7
9
16.9
11
20.1
15
26.5
22
39
30
51.5
37
64
45
1.5
2.2
3
4
5.5
7.5
9
11
15
22
76
3.1
4.5
5.8
7.9
10.4
13.7
16.9
20.1
26.5
39
30
51.5
37
64
80
45
76
100
55
96
Circuit breakers
Type
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NS80H-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
NSX100B/F/N/H/S/L-MA
Rating
(A)
6.3
6.3
12.5
12.5
12.5
25
25
25
50
50
50
80
80
80
80
80
6.3
6.3
12.5
12.5
12.5
25
25
25
50
50
100
100
100
100
100
100
100
100
Contactors
Thermal relays
Type
Type
LC3-D09
LC3-D09
LC3-D09
LC3-D09
LC3-D09
LC3-D09
LC3-D12
LC3-D12
LC3-D18
LC3-D18
LC3-D32
LC3-D32
LC3-D32
LC3-D40
LC3-D40
LC3-D50
LC3-D09
LC3-D09
LC3-D09
LC3-D09
LC3-D09
LC3-D09
LC3-D12
LC3-D12
LC3-D18
LC3-D18
LC3-D32
LC3-D32
LC3-D32
LC3-D40
LC3-D40
LC3-D50
LC3-D50
LC3-D50
LRD-07
LRD-08
LRD-08
LRD-10
LRD-12
LRD-14
LRD-16
LRD-16
LRD-21
LRD-22
LRD-32
LRD-32
LRD-32
LR2-D33 55
LR2-D33 57
LR2-D33 57
LRD-07
LRD-08
LRD-08
LRD-10
LRD-12
LRD-14
LRD-16
LRD-16
LRD-21
LRD-22
LRD-32
LRD-32
LRD-32
LR2-D33 55
LR2-D33 57
LR2-D33 57
LR2-D33 57
LR2-D33 59
Irth
(A)
1.6/2.5
2.5/4
2.5/4
4/6
5.5/8
7/10
9/13
9/13
12/18
17/25
23/32
23/32
23/32
30/40
37/50
37/50
1.6/2.5
2.5/4
2.5/4
4/6
5.5/8
7/10
9/13
9/13
12/18
17/25
23/32
23/32
23/32
30/40
37/50
37/50
37/50
48/65
167
04/11/2009 16:00:34
Type 1 coordination
(IEC 60947-4-1)
Complementary
technical information
DB103923
Motors
220/230 V
P
I
(kW) (A)
37
45
55
125
150
380 V
P
(kW)
55
75
75
I
(A)
105
140
140
90
170
440 V (1)
P
I
(kW) (A)
75
135
75
124
NSX160B/F/N/H/S/L-MA
NSX160B/F/N/H/S/L-MA
NSX160B/F/N/H/S/L-MA
Rating
(A)
150
150
150
90
160
90
156
NSX250B/F/N/H/S/L-MA
220
110
180
NSX250B/F/N/H/S/L-MA
220
NSX250B/F/N/H/S/L-MA
220
NSX250B/F/N/H/S/L-MA
220
180
110
210
Circuit breakers
415 V
P
I
(kW) (A)
110
200
132
75
250
132
250
132
230
90
110
312
360
270
380
480
300
380
420
480
160
220
150
160
200
220
250
250
430
160
520
300
570
300
335
215
Type
256
360
401
510
300
335
480
540
580
375
590
320
500
500
500
500
800
1000
800
1000
Contactors
Thermal relays
Type
Type
LC3-D80
LC3-D80
LC3-D115
LC3-F115
LC3-D115
LC3-F115
LC3-D115
LC3-F115
LC3-D115
LC3-F115
LC3-D150
LC3-F150
LC3-D150
LC3-F150
LC3-F185
LC3-F265
LC3-F265
LC3-F330
LC3-F330
LC3-F400
LR2-D33 59
LR2-D33 63
LR9-D53 67
LR9-F53 67
LR9-D53 67
LR9-F53 67
LR9-D53 69
LR9-F53 67
LR9-D53 69
LR9-F53 69
LR9-D53 69
LR9-F53 69
LR9-D53 69
LR9-F53 69
LR9-F53 71
LR9-F73 75
LR9-F73 75
LR9-F73 75
LR9-F73 75
LR9-F73 75
LC3-F400
LR9-F73 79
Irth
(A)
48/65
63/80
60/100
60/100
90/150
90/150
90/150
90/150
132/220
200/330
200/330
200/330
200/330
200/330
300/500
168
04/11/2009 16:00:35
Type 1 coordination
(IEC 60947-4-1)
DB114968
Complementary
technical information
Motors
220/230 V
P
I
(kW) (A)
7.5
28
11
39
15
380 V
P
(kW)
15
18.5
22
I
(A)
30
37
44
415 V
P
(kW)
15
22
25
I
(A)
28
40
47
30
51.5
30
37
55
66
37
64
45
80
45
76
55
100
55
96
75
135
75
124
90
110
160
200
90
110
132
156
180
215
160
220
250
256
360
401
52
18.5
64
22
25
30
75
85
100
440 V (1)
P
I
(kW) (A)
15
26.5
22
39
30
37
59
72
45
85
55
75
75
90
110
105
140
140
170
210
250
300
380
420
480
132
160
220
230
270
380
250
430
570
300
510
300
335
480
540
335
580
375
590
37
45
125
150
55
180
75
90
110
250
312
360
150
480
132
160
200
220
250
160
520
300
Circuit breakers
Contactors
Type
Trip unit
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX160B/F/N/H/S/L
NSX160B/F/N/H/S/L
NSX160B/F/N/H/S/L
NSX250B/F/N/H/S/L
NSX250B/F/N/H/S/L
NSX250B/F/N/H/S/L
NSX400F/N/H/S/L
NSX400F/N/H/S/L
NSX630F/N/H/S/L
NSX630F/N/H/S/L
NSX630F/N/H/S/L
NSX630F/N/H/S/L
NS800N/H
NS1000L
NS800N/H
NS1000L
Irth
(A)
25/50
25/50
25/50
50/100
50/100
50/100
50/100
50/100
50/100
50/100
70/150
70/150
70/150
100/220
100/220
100/220
160/320
160/320
250/500
250/500
250/500
250/500
320/800
400/1000
320/800
400/1000
Type
LC3-D18
LC3-D18
LC3-D32
LC3-D32
LC3-D32
LC3-D40
LC3-D40
LC3-D50
LC3-D50
LC3-D50
LC3-D80
LC3-D80
LC3-D115 or LC3-F115
LC3-D115 or LC3-F115
LC3-D115 or LC3-F115
LC3-D150 or LC3-F150
LC3-D150 or LC3-F150
LC3F-185
LC3-F265
LC3-F265
LC3-F330
LC3-F330
LC3-F400
LC3-F400
169
04/11/2009 16:00:37
170
04/11/2009 16:00:37
Complementary
technical information
The table below indicates the minimum and maximum fuse sizes depending on the rating of the
switch and the applicable reference standard.
Example:
An INFp160 can receive BS fuse-links in sizes A2, A3
or A4, which correspond to the following ratings:
b A2 size:
v 2 to 32 A for gG fuse-links
v 32M35 to 32M63 for gM fuse-links
b A3 size:
v 35 to 63 A for gG fuse-links
v 63M80 to 63M100 for gM fuse-links
b A4 size:
v 80 to 100 A for gG fuse-links
v 100M125 to 100M200 for gM fuse-links.
DB115223
INFp32
INFD40
INFp63
INFp100
INFC125
INFp160
INFp200
INFp250
INFp400
INFp630
INFp800
INFT100N
ISFT100
ISFp160
ISFp250
ISFp400
ISFp630
BS
min.
A1
max.
A2
A2
A2
A3
A4
A2
B1
B1
B1
C1
C1
A4
B2
B3
B4
C3
C3
DIN
min.
max.
000
000
000
00
000
0
0
0
3
3
000
000
000
1
2
3
00
0
1
2
3
3
000
000
00
1
2
3
NFC
min.
10 x 38
max.
14 x 51
14 x 51
22 X 58
22 x 58
22 x 58
Fupact characteristics
The local emergency-off switch must have the AC23 characteristic for the rated
motor current.
Motor starting characteristics are the following:
b peak current:
8 to 10 In
b duration of peak current: 20 to 30 ms
b starting current Id:
4 to 8 In
b starting time td: 2 to 4 seconds.
Short-circuit protection of motors is ensured by aM or gM (1) fuse-links that are sized
to take into account the above characteristics.
Fupact offers a wide range of fuse utilisations, whatever the applicable reference
standard.
(1) A gM fuse-link is in fact simply a derated gG fuse-link.
171
04/11/2009 16:00:38
Complementary
technical information
230/240 V
P(kW)
0.37
1
0.8
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
55
75
90
110
132
150
160
(HP)
0.5
0.7
1
1.5
2
2.9
4
5.3
7.3
10
13
15
20
25
29
40
49
60
73
100
120
147
176
200
213
In (A)
1.9
2.7
3.6
4.5
6.3
9
11.7
15.2
19.8
26
34
38
51
63
74
99
125
144
177
245
296
354
408
484
496
Fupact
INFB32
INFB32
INFB32
INFB32
INFB32
INFB32
INFB32
INFB32
INFB32
INFB32
INFB32
INFB63
INFB63
INFB100
INFB100
INFB200
INFB200
INFB200
INFB250
INFB250
INFB400
INFB630
INFB800
INFB800
INFB800
gG/gM
gG 6
gG 10
gG 16
gG 16
gG 20
20M25
20M32
32M40
32M50
32M50
63M80
63M80
63M100
100M160
100M160
gG 200
200M250
200M250
315M400
315M400
400M450
gG 630
gG 800
gG 800
gG 800
415V
P(kW)
0.37
1
0.8
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
55
75
90
110
132
150
160
200
240
280
(HP)
0.5
0.7
1
1.5
2
2.9
4
5.3
7.3
10
13.3
15
20
25
29
40
49
60
73
100
120
147
176
200
213
267
320
373
In (A)
1.1
1.5
2
2.5
3.5
5
6.5
8.4
11
14.4
19.1
21
28
35
41
55
69
80
98
136
164
196
226
268
275
358
428
488
Fupact
INFB32
INFB32
INFB32
INFB32
INFB32
INFB32
INFB32
INFB32
INFB32
INFB32
INFB32
INFB32
INFB32
INFB63
INFB63
INFB63
INFB100
INFB100
INFB200
INFB200
INFB200
INFB250
INFB250
INFB400
INFB400
INFB630
INFB800
INFB800
gG/gM
gG 4
gG 6
gG 10
gG 10
gG 16
gG 16
gG 20
20M25
20M32
32M40
32M50
32M50
32M63
63M80
63M80
63M100
100M160
100M160
gG 200
200M250
200M315
315M400
315M400
400M500
400M500
gG 630
gG 800
gG 800
172
04/11/2009 16:00:39
Complementary
technical information
230/240 V
P(kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
380/400V
(HP)
0.49
0.73
1
1.5
2
2.9
4
5.3
7.3
10
13
15
20
25
29
40
49
In (A)
1.9
2.7
3.6
4.5
6.3
9
11.7
15.2
19.8
26
34
38
51
63
74
99
125
Fupact
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC63
INFC63
INFC63
INFC63
-
gG
6
10
16
16
20
25
32
40
50
50
80
80
100
160
160
200
250
Fupact
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC63
INFC63
INFC63
INFC125
INFC125
INFC125
INFC125
aM
2
4
4
6
8
10
12
16
20
32
40
40
63
80
80
100
125
P(kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
55
(HP)
0.49
0.73
1
1.5
2
2.9
4
5.3
7.3
10
13
15
20
25
29
40
49
60
73
In (A)
1.1
1.5
2
2.5
3.5
5
6.5
8.4
11
14
19
21
28
35
41
55
69
80
98
Fupact
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC63
INFC63
INFC63
INFC63
-
gG
4
6
10
10
16
16
20
25
32
40
50
50
63
80
80
100
160
160
200
Fupact
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC63
INFC63
INFC63
INFC125
INFC125
INFC125
aM
2
2
2
4
4
6
8
10
12
16
25
25
32
40
50
63
80
80
100
P(kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
55
415 V
P(kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
55
(HP)
0.49
0.73
1
1.5
2
2.9
4
5.3
7.3
10
13
15
20
25
29
40
49
60
73
In (A)
1.1
1.6
2.2
2.7
3.8
5.5
7.1
9.2
12
16
21
23
31
38
45
60
75
87
107
Fupact
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC63
INFC63
INFC63
INFC63
-
gG
4
6
10
10
16
16
20
25
32
40
50
50
80
80
100
125
160
200
200
Fupact
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC63
INFC63
INFC63
INFC125
INFC125
INFC125
aM
2
2
4
4
4
6
8
10
12
16
25
25
32
40
50
63
80
100
125
(HP)
0.49
0.73
1
1.5
2
2.9
4
5.3
7.3
10
13
15
20
25
29
40
49
60
73
In (A)
1
1.4
1.9
2.4
3.3
4.7
6.1
7.9
10.4
14
18
20
26
33
39
52
65
75
92
Fupact
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC63
INFC63
INFC63
INFC63
INFC63
INFC63
-
gG
4
6
6
10
10
16
16
20
25
40
50
50
63
80
80
100
160
160
200
Fupact
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC63
INFC63
INFC63
INFC125
INFC125
INFC125
aM
2
2
2
4
4
6
6
8
10
16
20
20
32
40
40
50
80
80
100
440 V
173
04/11/2009 16:00:41
Complementary
technical information
500 V
P(kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
55
525/550 V
(HP)
0.49
0.73
1
1.5
2
2.9
4
5.3
7.3
10
13
15
20
25
29
40
49
60
73
660/690V
P(kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
55
75
(HP)
0.49
0.73
1
1.5
2
2.9
4
5.3
7.3
10
13
15
20
25
29
40
49
60
73
100
In (A)
0.9
1.2
1.5
2.2
2.9
3.9
5.2
6.8
9.2
12
16
18
23
28
33
45
53
64
78
Fupact
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC63
INFC63
INFC63
INFC63
INFC63
-
gG
4
4
6
6
10
10
16
20
25
32
32
40
50
63
80
100
100
160
160
Fupact
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC63
INFC63
INFC63
INFC63
INFC125
INFC125
aM
2
2
2
2
4
4
6
8
10
12
16
20
25
32
40
50
63
80
80
In (A)
0.7
0.9
1.1
1.6
2.2
2.8
3.8
4.9
6.7
9
12
13
17
22
24
32
39
47
57
77
Fupact
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC63
INFC63
INFC63
INFC63
INFC63
INFC63
INFC63
-
gG
2
4
4
6
6
10
10
16
20
25
32
32
40
50
50
80
80
100
125
160
Fupact
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC63
INFC63
INFC63
INFC63
INFC63
INFC63
INFC125
aM
2
2
2
2
4
4
6
6
8
10
12
16
20
25
25
32
40
50
63
80
P(kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
55
(HP)
0.49
0.73
1
1.5
2.0
2.9
4
5.3
7.3
10
13
15
20
25
29
40
49
60
73
In (A)
0.8
1.1
1.4
2.1
2.8
3.7
4.9
6.5
8.7
12
15
17
22
27
31
43
50
61
74
Fupact
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC63
INFC63
INFC63
INFC63
INFC63
INFC63
-
gG
4
4
6
6
10
10
16
20
25
32
32
40
50
63
80
100
100
125
160
Fupact
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC32
INFC63
INFC63
INFC63
INFC63
INFC63
INFC125
aM
2
2
2
2
4
4
6
8
10
12
16
20
25
32
40
50
63
63
80
174
04/11/2009 16:00:44
Complementary
technical information
415 V
P(kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
55
75
90
110
132
150
160
200
240
280
300
320
355
375
230/240 V
aM
0.49
0.73
1
1.5
2
2.9
4
5.3
7.3
10
13
15
20
25
29
40
49
60
73
100
120
147
176
200
213
267
1.9
2.7
3.6
4.5
6.3
9.0
11.7
15.2
19.8
26
34
38
51
63
74
99
125
144
177
245
296
354
408
484
496
646
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD63
INFD160
INFD160
INFD200
INFD200
INFD200
INFD250
INFD400
INFD400
INFD630
INFD630
INFD630
INFD630
-
6
10
16
16
20
25
32
40
50
50
80
80
100
160
160
200
250
250
355
400
450
630
800
800
800
-
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD63
INFD160
INFD160
INFD160
INFD160
INFD160
INFD200
INFD400
INFD400
INFD400
INFD630
INFD630
INFD630
INFD800
2
4
4
6
8
10
12
16
20
32
40
40
63
80
80
100
125
160
200
250
315
355
450
500
500
800
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
55
75
90
110
132
150
160
200
240
280
300
320
(HP)
0.49
0.73
1
1.5
2
2.9
4
5.3
7.3
10
13
15
20
25
29
40
49
60
73
100
120
147
176
200
213
267
320
373
400
427
473
500
533
In (A)
1
1.4
1.9
2.4
3.3
4.7
6.1
7.9
10.4
14
18
20
26
33
39
52
65
75
92
128
155
185
213
253
259
338
404
460
495
507
560
575
611
Fupact
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD63
INFD160
INFD160
INFD160
INFD200
INFD250
INFD250
INFD400
INFD400
INFD400
INFD630
INFD630
INFD630
INFD630
-
gG
4
6
6
10
10
16
16
20
25
40
50
50
63
80
80
100
160
160
200
250
315
355
400
450
500
630
800
800
800
-
Fupact
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD63
INFD160
INFD160
INFD160
INFD160
INFD160
INFD200
INFD250
INFD400
INFD400
INFD400
INFD630
INFD630
INFD630
INFD630
INFD630
INFD630
INFD630
aM
2
2
2
4
4
6
6
8
10
16
20
20
32
40
40
50
80
80
100
125
160
200
250
250
315
355
400
450
500
500
630
630
630
P(kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
55
75
90
110
132
150
160
200
240
280
300
320
355
375
400
450
440 V
(HP)
0.49
0.73
1
1.5
2
2.9
4
5.3
7.3
10
13
15
20
25
29
40
49
60
73
100
120
147
176
200
213
267
320
373
400
427
473
500
In (A)
1.1
1.5
2
2.5
3.5
5
6.5
8.4
11
14
19
21
28
35
41
55
69
80
98
136
164
196
226
268
275
358
428
488
525
538
605
610
Fupact
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD63
INFD63
INFD160
INFD160
INFD200
INFD200
INFD250
INFD250
INFD400
INFD400
INFD400
INFD630
INFD630
INFD630
-
gG
4
6
10
10
16
16
20
25
32
40
50
50
63
80
80
100
160
160
200
250
315
355
400
450
500
630
800
800
-
Fupact
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD63
INFD63
INFD160
INFD160
INFD160
INFD160
INFD200
INFD200
INFD250
INFD400
INFD400
INFD400
INFD630
INFD630
INFD630
INFD630
INFD630
INFD630
aM
2
2
2
4
4
6
8
10
12
16
25
25
32
40
50
63
80
80
100
160
200
200
250
315
315
400
450
500
630
630
630
630
P(kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
55
75
90
110
132
150
160
200
240
280
300
320
355
375
400
380/400V
gG Fupact
gG Fupact
aM
0.49
0.73
1
1.5
2
2.9
4
5.3
7.3
10
13
15
20
25
29
40
49
60
73
100
120
147
176
200
213
267
320
373
400
427
1.1
1.6
2.2
2.7
3.8
5.5
7.1
9.2
12
16
21
23
31
38
45
60
75
87
107
149
179
214
247
293
300
391
467
533
573
588
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD63
INFD63
INFD160
INFD200
INFD200
INFD200
INFD250
INFD400
INFD400
INFD400
INFD630
INFD630
INFD630
-
4
6
10
10
16
16
20
25
32
40
50
50
80
80
100
125
160
200
200
250
355
400
450
500
630
800
800
-
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD63
INFD63
INFD160
INFD160
INFD160
INFD160
INFD200
INFD250
INFD250
INFD400
INFD400
INFD400
INFD630
INFD630
INFD630
INFD630
2
2
4
4
4
6
8
10
12
16
25
25
32
40
50
63
80
100
125
160
200
250
250
315
315
400
500
630
630
630
(HP)
0.49
0.73
1
1.5
2
2.9
4
5.3
7.3
10
13
15
20
25
29
40
49
60
73
100
120
147
176
200
213
267
320
373
400
427
473
500
533
600
In (A)
0.9
1.2
1.5
2.2
2.9
3.9
5.2
6.8
9.2
12
16
18
23
28
33
45
53
64
78
106
130
155
187
211
225
280
338
386
415
435
488
515
552
630
Fupact
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD63
INFD63
INFD160
INFD160
INFD200
INFD200
INFD250
INFD250
INFD400
INFD400
INFD400
INFD630
INFD630
INFD630
INFD630
INFD630
-
gG
4
4
6
6
10
10
16
20
25
32
32
40
50
63
80
100
100
160
160
200
250
315
355
400
400
450
630
800
800
800
800
-
Fupact
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD63
INFD160
INFD160
INFD160
INFD160
INFD160
INFD200
INFD250
INFD400
INFD400
INFD400
INFD630
INFD630
INFD630
INFD630
INFD630
INFD630
INFD630
INFD630
aM
2
2
2
2
4
4
6
8
10
12
16
20
25
32
40
50
63
80
80
125
160
160
200
250
250
315
355
400
450
450
500
500
630
630
500 V
175
04/11/2009 16:00:48
Complementary
technical information
525/550 V
P(kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
55
75
90
110
132
150
160
200
240
280
300
320
355
375
(HP)
0.49
0.73
1
1.5
2
2.9
4
5.3
7.3
10
13
15
20
25
29
40
49
60
73
100
120
147
176
200
213
267
320
373
400
427
473
500
660/690V
In (A)
0.8
1.1
1.4
2.1
2.8
3.7
4.9
6.5
8.7
12
15
17
22
27
31
43
50
61
74
101
123
147
178
200
214
266
321
366
394
413
464
490
Fupact
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD63
INFD63
INFD63
INFD63
INFD200
INFD250
INFD400
INFD400
INFD630
INFD630
INFD630
INFD630
-
gG
4
4
6
6
10
10
16
20
25
32
32
40
50
63
80
100
100
125
160
200
250
250
355
400
400
450
-
Fupact
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD63
INFD63
INFD63
INFD160
INFD160
INFD160
INFD250
INFD250
INFD250
INFD250
INFD400
INFD400
INFD400
INFD400
INFD630
INFD630
INFD630
aM
2
2
2
2
4
4
6
8
10
12
16
20
25
32
40
50
63
63
80
100
125
160
200
200
250
315
355
400
400
450
500
500
P(kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
30
37
45
55
75
90
110
132
150
160
200
240
280
300
320
355
375
400
450
(HP)
0.49
0.73
1
1.5
2
2.9
4
5.3
7.3
10
13
15
20
25
29
40
49
60
73
100
120
147
176
200
213
267
320
373
400
427
473
500
533
600
In (A)
0.7
0.9
1.1
1.6
2.2
2.8
3.8
4.9
6.7
9
12
13
17
22
24
32
39
47
57
77
93
113
134
152
162
203
244
284
305
325
354
374
400
455
Fupact
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD63
INFD63
INFD63
INFD63
INFD200
INFD250
INFD250
INFD250
INFD400
INFD400
INFD630
INFD630
INFD630
INFD630
-
gG
2
4
4
6
6
10
10
16
20
25
32
32
40
50
50
80
80
100
125
160
200
250
250
315
315
400
450
500
500
-
Fupact
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD40
INFD63
INFD63
INFD63
INFD160
INFD160
INFD160
INFD250
INFD250
INFD250
INFD250
INFD250
INFD400
INFD400
INFD630
INFD630
INFD630
INFD630
INFD630
aM
2
2
2
2
4
4
6
6
8
10
12
16
20
25
25
32
40
50
63
80
100
125
160
160
160
200
250
315
315
355
355
400
400
450
176
04/11/2009 16:00:56
Type 2 coordination
(IEC 60947-4-1) 380/415 V
Complementary
technical information
Motors
P (kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
Switch-fuse (1)
Type
INFC32 or INFD40
INFC32 or INFD40
INFC32 or INFD40
INFC32 or INFD40
INFC32 or INFD40
INFC32 or INFD40
INFC32 or INFD40
INFC32 or INFD40
INFC32 or INFD40
INFC32 or INFD40
INFC32 or INFD40
INFC32 or INFD40
INFC32 or INFD40
INFC63 or INFD40
18.5
37
34
40
INFC63 or INFD40
22
43
40
50
INFC63 or INFD63
30
59
55
63
INFC63 or INFD63
37
72
66
80
INFC125 or INFD160
45
85
80
100
INFC125 or INFD160
INFD200
55
105
100
115
INFC125 or INFD160
INFD200
75
140
135
150
INFD160
INFD200
90
170
160
185
INFD200
INFD250
110
210
200
220
INFD250
INFD400
132
250
230
250
INFD250
INFD400
160
300
270
265
INFD400
INFD630
200
380
361
400
INFD400
INFD630
250
460
430
500
INFD630
280
520
475
630
INFD630
300
565
500
630
INFD630
335
610
560
630
INFD630
355
630
590
630
INFD630
(1) INFC for NFC cylindrical ferrule / INFD for NH-type DIN fuse-link.
(2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 with LC3.
I (A) 380 V
1.2
1.6
2
2.8
3.7
5.3
7
9
12
16
21
23
30
I (A) 415 V
1.1
1.5
1.8
2.6
3.4
4.8
6.5
8.2
11
14
19
21
28
Ie Max (A)
1.6
1.6
2.5
2.5
4
6
6
8
12
16
24
24
32
Class 10 A/10
Fuse-link type
gG rating (A) aM rating (A)
4
2
6
2
10
4
10
4
16
4
16
6
20
8
25
10
32
12
40
16
50
25
50
25
32
80
80
40
100
50
125
63
160
80
100
200
125
200
160
250
200
355
250
400
250
450
315
630
400
800
800
500
800
630
630
630
630
Contactors (2)
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D25
LC1-D25
LC1-D25
LC1-D32
LC1-D32
LC1-D40
Thermal relays
Type
Irth (A)
LRD 06
1/1.6
LRD 06
1/1.6
LRD 07
1.6/2.5
LRD 07
1.6/2.5
LRD 08
2.5/4
LRD 10
4/6
LRD 10
4/6
LRD 12
5.5/8
LRD 16
9/13
LRD 21
12/18
LRD 22
16/24
LRD 22
16/24
LRD 3352
23/32
LC1-D40
LC1-D50
LC1-D65
LC1-D80
LC1-D115
LRD 3355
LRD 3357
LRD 3359
LRD 3363
LR9-D53 67
30/40
37/50
48/65
63/80
60/100
LC1-D115
LR9-D53 69
90/150
LC1-D150
LR9-D53 69
90/150
LC1-F265
LR9-F53 71
132/220
LC1-F330
LR9-F53 71
132/220
LC1-F330
LR9-F73 75
200/330
LC1-F400
LR9-F73 75
200/330
LC1-F500
LR9-F73 79
300/500
LC1-F500
LC1-F630
LC1-F630
LC1-F630
LC1-F630
LR9-F73 79
LR9-F73 81
LR9-F73 81
LR9-F73 81
LR9-F73 81
300/500
380/630
380/630
380/630
380/630
177
04/11/2009 16:00:59
Type 2 coordination
(IEC 60947-4-1) 380/415 V
Complementary
technical information
Motors
P (kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
Switch-fuse (1)
Fuse-link type
Type
gG rating (A) aM rating (A)
INFC32 or INFD40
4
2
INFC32 or INFD40
6
2
INFC32 or INFD40
10
4
INFC32 or INFD40
10
4
INFC32 or INFD40
16
4
INFC32 or INFD40
16
6
INFC32 or INFD40
20
8
INFC32 or INFD40
25
10
INFC32 or INFD40
32
12
INFC32 or INFD40
40
16
INFC32 or INFD40
50
25
INFC32 or INFD40
50
25
INFC32 or INFD40
32
INFC63 or INFD40
80
40
INFC63 or INFD40
80
40
18.5
37
34
22
43
40
50
INFC63 or INFD63
100
50
30
59
55
63
INFC63 or INFD63
125
63
37
72
66
65
INFC125 or INFD160
160
80
45
85
80
80
INFC125 or INFD160
100
INFD200
200
55
105
100
115
INFC125 or INFD160
125
INFD200
200
75
140
135
150
INFD160
160
INFD200
250
90
170
160
185
INFD200
200
INFD250
355
250
110
210
200
225
INFD250
INFD400
400
132
250
230
250
INFD250
250
INFD400
450
INFD400
315
160
300
270
315
INFD630
630
400
INFD400
400
200
380
361
800
INFD630
460
430
500
INFD630
800
500
250
475
630
INFD630
800
630
280
520
565
500
630
INFD630
630
300
560
630
INFD630
630
335
610
590
630
INFD630
630
355
630
(1) INFC for NFC cylindrical ferrule / INFD for NH-type DIN fuse-link.
(2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 with LC3.
(3) Current transformer built into the relay.
(4) For use with a class 20 or class 30 relay, apply respectively a derating of 20 % and 37 %.
I (A) 380 V
1.2
1.6
2
2.8
3.7
5.3
7
9
12
16
21
23
30
I (A) 415 V
1.1
1.5
1.8
2.6
3.4
4.8
6.5
8.2
11
14
19
21
28
Ie Max (A)
2
2
4
4
4
6
8
10
12
16
25
25
32
Contactors (2)
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D25
LC1-D25
LC1-D25
LC1-D32
LC1-D32
LC1-D40
Thermal relays
Type
Irth (A)
LTM R08
0.4/8 (3)
LTM R08
0.4/8 (3)
LTM R08
0.4/8 (3)
LTM R08
0.4/8 (3)
LTM R08
0.4/8 (3)
LTM R08
0.4/8 (3)
LTM R08
0.4/8 (3)
LTM R27
1.35/27 (3)
LTM R27
1.35/27 (3)
LTM R27
1.35/27 (3)
LTM R27
1.35/27 (3)
LTM R27
1.35/27 (3)
LTM R100 5/100 (3)
LC1-D40
LC1-D50
LC1-D65
LC1-D80
LC1-D115
LTM R100
LTM R100
LTM R100
LTM R100
LTM R100
5/100 (3)
5/100 (3)
5/100 (3)
5/100 (3)
5/100 (3)
LC1-D115
LTM R08
On CT
LC1-D150
LTM R08
On CT
LC1-D265
LTM R08
On CT
LC1-F330
LTM R08
On CT
LC1-F330
LTM R08
On CT
LC1-F400
LTM R08
On CT
LC1-F500
LTM R08
On CT
LC1-F500
LC1-F630
LC1-F630
LC1-F630
LC1-F630
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
On CT
On CT
On CT
On CT
On CT
178
04/11/2009 16:01:04
Complementary
technical information
Type 2 coordination
(IEC 60947-4-1) 440 V
Schneider Electric switch-disconnector fuses and contactors
Performance: Ue = 440 V (3) - "Iq" 100 kA
Starting
Motors
P (kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
Switch-fuse (1)
Fuse-link type
Type
gG rating (A)
INFC32 or INFD40
4
INFC32 or INFD40
6
INFC32 or INFD40
6
INFC32 or INFD40
10
INFC32 or INFD40
10
INFC32 or INFD40
16
INFC32 or INFD40
16
INFC32 or INFD40
20
INFC32 or INFD40
25
INFC32 or INFD40
40
INFC32 or INFD40
INFC63 or INFD40
50
11
20
20
INFC32 or INFD40
INFC63 or INFD40
50
15
26
32
INFC32 or INFD40
INFC63 or INFD40
63
18.5
33
40
INFC63 or INFD40
80
22
39
40
INFC63 or INFD40
80
30
52
50
INFC63 or INFD63
100
37
65
65
INFC125 or INFD160
INFD160
160
45
75
80
INFC125 or INFD160
INFD160
160
55
92
100
INFC125 or INFD160
INFD160
200
75
128
125
INFD160
INFD200
250
90
155
150
INFD160
INFD250
315
110
185
200
INFD200
INFD250
355
132
213
220
INFD250
INFD400
400
160
259
315
INFD400
500
200
338
330
INFD400
INFD630
630
250
423
400
INFD630
800
280
460
450
INFD630
800
300
495
500
INFD630
800
355
560
630
INFD630
375
575
630
INFD630
400
611
630
INFD630
(1) INFC for NFC cylindrical ferrule / INFD for NH-type DIN fuse-link.
(2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 with LC3.
(3) Valid for 480V NEMA network.
I (A) 440 V
1
1.4
1.9
2.4
3.3
4.7
6.1
7.9
10.4
14
18
Ie Max (A)
1.6
1.6
2.5
2.5
4
6
6
8
10
16
20
Class 10 A/10
aM rating (A)
2
2
2
4
4
6
6
8
10
16
20
20
32
40
40
50
80
80
100
125
160
200
250
315
355
400
450
500
630
630
630
Contactors (2)
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D25
LC1-D32
Thermal relays
Type
LRD 06
LRD 06
LRD 07
LRD 07
LRD 08
LRD 10
LRD 10
LRD 12
LRD 16
LRD 21
LRD 22
Irth (A)
1/1.6
1/1.6
1.6/2.5
1.6/2.5
2.5/4
4/6
4/6
5.5/8
9/13
12/18
16/24
LC1-D32
LRD 22
16/24
LC1-D32
LRD 32
23/32
LC1-D40
LC1-D40
LC1-D50
LC1-D80
LRD 3355
LRD 3355
LRD 3359
LRD 3359
30/40
30/40
48/65
48/65
LC1-D80
LRD 3363
63/80
LC1-D115
LR9-D53 67
60/100
LC1-D150
LR9-D53 69
90/150
LC1-D185
LR9-D53 69
90/150
LC1-F265
LR9-F53 71
132/220
LC1-F265
LR9-F53 71
132/220
LC1-F330
LC1-F400
LR9-F73 75
LR9-F73 75
200/330
200/330
LC1-F500
LC1-F500
LC1-F500
LC1-F630
LC1-F630
LC1-F630
LR9-F73 79
LR9-F73 79
LR9-F73 79
LR9-F73 81
LR9-F73 81
LR9-F73 81
300/500
300/500
300/500
380/630
380/630
380/630
179
04/11/2009 16:01:04
Complementary
technical information
Type 2 coordination
(IEC 60947-4-1) 440 V
Schneider Electric switch-disconnector fuses and contactors
Performance: Ue = 440 V (5) - "Iq" 100 kA
Starting
Motors
P (kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
Switch-fuse (1)
Fuse-link type
Type
gG rating (A)
aM rating (A)
INFC32 or INFD40
4
2
INFC32 or INFD40
6
2
INFC32 or INFD40
6
2
INFC32 or INFD40
10
4
INFC32 or INFD40
10
4
INFC32 or INFD40
16
6
INFC32 or INFD40
16
6
INFC32 or INFD40
20
8
INFC32 or INFD40
25
10
INFC32 or INFD40
40
16
INFC32 or INFD40
20
INFC63 or INFD40
50
11
20
20
INFC32 or INFD40
20
INFC63 or INFD40
50
32
15
26
27
INFC32 or INFD40
INFC63 or INFD40
63
33
40
INFC63 or INFD40
80
40
18.5
22
39
40
INFC63 or INFD63
80
40
30
52
50
INFC63 or INFD63
100
50
37
65
80
INFC125 or INFD160
80
INFD160
160
45
75
80
INFC125 or INFD160
80
INFD160
160
55
92
100
INFC125 or INFD160
100
INFD160
200
75
128
125
INFD160
125
INFD200
250
90
155
160
INFD160
160
INFD250
315
200
110
185
200
INFD200
INFD250
355
132
213
250
INFD250
250
INFD400
400
INFD400
500
315
160
259
315
INFD400
355
200
338
355
INFD630
630
400
INFD630
800
400
250
423
460
450
INFD630
800
450
280
495
500
INFD630
800
500
300
560
630
INFD630
630
355
575
630
INFD630
630
375
400
611
630
INFD630
630
(1) INFC for NFC cylindrical ferrule / INFD for NH-type DIN fuse-link.
(2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 with LC3.
(3) Current transformer built into the relay.
(4) For use with a class 20 or class 30 relay, apply respectively a derating of 20 % and 37 %.
(5) Valid for 480 V NEMA network.
I (A) 440 V
1
1.4
1.8
2.4
3.3
4.7
6.1
7.9
10.4
14
18
Ie Max (A)
2
2
2
4
4
6
6
8
10
16
20
Contactors (2)
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D25
LC1-D25
LC1-D32
Thermal relays
Type
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
LTM R27
LTM R27
LTM R27
Irth (A)
0.4/8 (3)
0.4/8 (3)
0.4/8 (3)
0.4/8 (3)
0.4/8 (3)
0.4/8 (3)
0.4/8 (3)
0.4/8 (3)
1.35/27 (3)
1.35/27 (3)
1.35/27 (3)
LC1-D32
LTM R27
1.35/27 (3)
LC1-D32
LTM R27
1.35/27 (3)
LC1-D40
LC1-D40
LC1-D50
LC1-D80
LTM R100
LTM R100
LTM R100
LTM R100
5/100 (3)
5/100 (3)
5/100 (3)
5/100 (3)
LC1-D80
LTM R100
5/100 (3)
LC1-D115
LTM R100
5/100 (3)
LC1-D150
LTM R08
On CT
LC1-F185
LTM R08
On CT
LC1-F265
LTM R08
On CT
LC1-F265
LTM R08
On CT
LC1-F330
LC1-F400
LTM R08
LTM R08
On CT
On CT
LC1-F500
LC1-F500
LC1-F500
LC1-F630
LC1-F630
LC1-F630
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
On CT
On CT
On CT
On CT
On CT
On CT
180
04/11/2009 16:01:05
Complementary
technical information
Type 2 coordination
(IEC 60947-4-1) 500 V
Schneider Electric switch-disconnector fuses and contactors
Performance: Ue = 500 V - "Iq" 100 kA
Starting
Motors
P (kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
Switch-fuse (1)
Fuse-link type
Type
gG rating (A)
INFC32 or INFD40
4
INFC32 or INFD40
4
INFC32 or INFD40
6
INFC32 or INFD40
6
INFC32 or INFD40
10
INFC32 or INFD40
10
INFC32 or INFD40
16
INFC32 or INFD40
20
INFC32 or INFD40
25
INFC32 or INFD40
32
32
INFC32 or INFD40
INFC32 or INFD40
40
INFC32 or INFD40
50
INFC63 or INFD40
32
INFC63 or INFD40
63
18.5
28.5
22
33
40
INFC63 or INFD40
80
45
50
INFC63 or INFD63
100
30
55
63
INFC63 or INFD63
100
37
45
65
70
INFC125 or INFD160
INFD160
160
55
75
80
INFC125 or INFD160
INFD160
160
75
105
115
INFD160
INFD200
200
90
130
150
INFD160
INFD200
250
110
156
160
INFD200
INFD250
315
132
187
200
INFD250
355
INFD400
400
160
230
250
INFD400
450
200
280
315
240
338
355
INFD630
630
400
INFD630
800
280
386
450
INFD630
800
300
415
450
INFD630
800
320
425
478
500
INFD630
800
355
500
INFD630
375
482
400
534
500
INFD630
450
630
630
INFD630
(1) INFC for NFC cylindrical ferrule / INFD for NH-type DIN fuse-link.
(2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 with LC3.
I (A) 500 V
0.8
1.2
1.5
2
2.8
3.8
5
6.5
9
12
15
18.4
23
Ie Max (A)
1
1.6
1.6
2
4
4
6
8
10
12
16
20
24
Class 10 A/10
aM rating (A)
2
2
2
2
4
4
6
8
10
12
16
20
25
32
40
50
63
80
80
125
160
160
200
250
315
355
400
450
450
500
500
630
630
Contactors (2)
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D25
LC1-D25
LC1-D25
LC1-D25
LC1-D32
Thermal relays
Type
LRD 05
LRD 06
LRD 06
LRD 07
LRD 08
LRD 08
LRD 10
LRD 12
LRD 16
LRD 16
LRD 21
LRD 22
LRD 22
Irth (A)
0.63/1
1/1.6
1/1.6
1.6/2.5
2.5/4
2.5/4
4/6
5.5/8
9/13
9/13
12/18
16/24
16/24
LC1-D32
LC1-D40
LC1-D50
LC1-D65
LC1-D80
LRD 32
LRD 3355
LRD 3357
LRD 3359
LRD 3361
23/32
30/40
37/50
48/65
55/70
LC1-D115
LRD 3363
63/80
LC1-D115
LR9-D53 69
90/150
LC1-D150
LR9-D53 69
90/150
LC1-F185
LR9-F53 71
132/220
LC1-F265
LC1-F265
LC1-F400
LC1-F400
LC1-F500
LC1-F500
LC1-F500
LC1-F500
LC1-F630
LC1-F630
LC1-F630
LR9-F53 71
LR9-F73 75
LR9-F73 75
LR9-F73 79
LR9-F73 79
LR9-F73 79
LR9-F73 79
LR9-F73 79
LR9-F73 81
LR9-F73 81
LR9-F73 81
132/220
200/330
200/330
300/500
300/500
300/500
300/500
300/500
380/630
380/630
380/630
181
04/11/2009 16:01:06
Complementary
technical information
Type 2 coordination
(IEC 60947-4-1) 500 V
Schneider Electric switch-disconnector fuses and contactors
Performance: Ue = 500 V - "Iq" 100 kA
Starting
Motors
P (kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
Switch-fuse (1)
Fuse-link type
Type
gG rating ( A)
aM rating (A)
INFC32 or INFD40
4
2
INFC32 or INFD40
4
2
INFC32 or INFD40
6
2
INFC32 or INFD40
6
2
INFC32 or INFD40
10
4
INFC32 or INFD40
10
4
INFC32 or INFD40
16
6
INFC32 or INFD40
20
8
INFC32 or INFD40
25
10
INFC32 or INFD40
32
12
INFC32 or INFD40
32
16
INFC32 or INFD40
40
20
INFC32 or INFD40
25
INFC63 or INFD40
50
32
INFC63 or INFD40
63
32
18.5
28.5
22
33
40
INFC63 or INFD40
80
40
30
45
50
INFC63 or INFD63
100
50
37
55
63
INFC63 or INFD63
100
63
45
65
70
INFC125 or INFD160
80
INFD160
160
55
75
80
INFC125 or INFD160
80
INFD160
160
75
105
115
INFD160
125
INFD200
200
90
130
150
INFD160
160
INFD200
250
160
110
156
160
INFD200
INFD250
315
132
187
200
INFD250
355
200
INFD400
400
250
160
230
250
INFD400
450
315
200
280
315
240
338
355
INFD630
630
355
400
INFD630
800
400
280
386
450
INFD630
800
450
300
415
450
INFD630
800
450
320
425
478
500
INFD630
800
500
355
500
INFD630
500
375
482
400
534
500
INFD630
630
450
630
630
INFD630
630
(1) INFC for NFC cylindrical ferrule / INFD for NH-type DIN fuse-link.
(2) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 with LC3.
(3) Current transformer built into the relay.
(4) For use with a class 20 or class 30 relay, apply respectively a derating of 20 % and 37 %.
I (A) 500 V
0.8
1.2
1.5
2
2.8
3.8
5
6.5
9
12
15
18.4
23
Ie Max (A)
1
1.6
1.6
2
4
4
6
8
10
12
16
20
24
Contactors (2)
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D25
LC1-D25
LC1-D25
LC1-D25
LC1-D32
Thermal relays
Type
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
LTM R27
LTM R27
LTM R27
LTM R27
LTM R27
Irth (A)
0.4/8 (3)
0.4/8 (3)
0.4/8 (3)
0.4/8 (3)
0.4/8 (3)
0.4/8 (3)
0.4/8 (3)
0.4/8 (3)
1.35/27 (3)
1.35/27 (3)
1.35/27 (3)
1.35/27 (3)
1.35/27 (3)
LC1-D32
LC1-D40
LC1-D50
LC1-D65
LC1-D80
LTM R100
LTM R100
LTM R100
LTM R100
LTM R100
5/100 (3)
5/100 (3)
5/100 (3)
5/100 (3)
5/100 (3)
LC1-D115
LTM R100
5/100 (3)
LC1-D115
LTM R08
On CT
LC1-D150
LTM R08
On CT
LC1-F185
LTM R08
On CT
LC1-F265
LC1-F265
LC1-F400
LC1-F400
LC1-F500
LC1-F500
LC1-F500
LC1-F500
LC1-F630
LC1-F630
LC1-F630
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
On CT
On CT
On CT
On CT
On CT
On CT
On CT
On CT
On CT
On CT
On CT
182
04/11/2009 16:01:07
Type 2 coordination
(IEC 60947-4-1) 525/550 V
Complementary
technical information
Motors
P (kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
Class 10 A/10
Switch-fuse (2)
Fuse-link type
Type
gG rating (A) aM rating (A)
INFC32 or INFD40
4
2
INFC32 or INFD40
4
2
INFC32 or INFD40
6
2
INFC32 or INFD40
6
2
INFC32 or INFD40
10
4
INFC32 or INFD40
10
4
INFC32 or INFD40
16
6
INFC32 or INFD40
20
8
INFC32 or INFD40
25
10
INFC32 or INFD40
12
32
INFC63 or INFD40
16
10
15
15.2
16
INFC32 or INFD40
32
INFC63 or INFD40
11
18.4
16.7
24
INFC32 or INFD40
20
40
INFC63 or INFD40
23
21.9
24
INFC32 or INFD40
25
15
50
INFC63 or INFD40
32
INFC63 or INFD40
63
32
18.5
28.5
26.6
22
33
31
40
INFC63 or INFD40
40
80
INFC63 or INFD63
45
43
50
INFC63 or INFD63
50
30
INFD63
100
55
50
63
INFC63 or INFD63
63
37
INFD63
100
45
65
61
70
INFC63 or INFD63
63
INFD63
125
55
75
74
80
INFC63 or INFD160
80
INFD200
160
75
105
101
115
INFD160
100
INFD250
200
90
130
123
125
INFD160
125
INFD400
250
160
110
156
147
160
INFD250
INFD400
250
132
187
178
200
INFD250
200
INFD630
355
250
160
214
204
250
INFD250
400
INFD630
INFD400
315
200
266
254
315
450
INFD630
321
307
355
INFD400
355
240
400
INFD400
400
280
366
350
400
INFD400
400
300
394
376
450
INFD630
450
320
413
394
464
443
500
INFD630
500
355
490
467
500
INFD630
500
375
(1) Coordination table built with 690 V fuse-links (80 kA for NFC fuse-links, 100 kA for DIN fuse-links).
(2) INFC for NFC cylindrical ferrule / INFD for NH-type DIN fuse-link.
(3) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 with LC3.
I (A) 525 V
0.8
1.2
1.5
2
2.8
3.8
5
6.5
9
12
I (A) 550 V
0.8
1.1
1.4
2.1
2.8
3.7
4.9
6.5
8.7
11.8
Ie Max (A)
1
1.6
1.6
2.5
4
4
6
8
10
12
Contactors (3)
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D25
LC1-D25
Thermal relays
Type
Irth (A)
LRD 05
0.63/1
LRD 06
1/1.6
LRD 06
1/1.6
LRD 07
1.6/2.5
LRD 08
2.5/4
LRD 08
2.5/4
LRD 10
4/6
LRD 12
5.5/8
LRD 16
9/13
LRD 16
9/13
LC1-D25
LRD 21
12/18
LC1-D25
LRD 22
16/24
LC1-D32
LRD 22
16/24
LC1-D32
LC1-D40
LRD 32
LRD 3355
23/32
30/40
LC1-D50
LRD 3357
37/50
LC1-D65
LRD 3359
48/65
LC1-D80
LRD 3361
55/70
LC1-D115
LRD 3363
63/80
LC1-D115
LR9-D53 69
90/150
LC1-D150
LR9-D53 69
90/150
LC1-F185
LR9-F53 71
132/220
LC1-F265
LR9-F53 71
132/220
LC1-F265
LR9-F73 75
200/330
LC1-F400
LR9-F73 75
200/330
LC1-F400
LC1-F500
LC1-F500
LC1-F500
LC1-F500
LC1-F630
LR9-F73 79
LR9-F73 79
LR9-F73 79
LR9-F73 79
LR9-F73 79
LR9-F73 81
300/500
300/500
300/500
300/500
300/500
380/630
183
04/11/2009 16:01:08
Type 2 coordination
(IEC 60947-4-1) 525/550 V
Complementary
technical information
Motors
P (kW)
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
Switch-fuse (2)
Fuse-link type
Type
gG rating ( A) aM rating (A)
INFC32 or INFD40
4
2
INFC32 or INFD40
4
2
INFC32 or INFD40
6
2
INFC32 or INFD40
6
2
INFC32 or INFD40
10
4
INFC32 or INFD40
10
4
INFC32 or INFD40
16
6
INFC32 or INFD40
20
8
INFC32 or INFD40
25
10
INFC32 or INFD40
12
INFC63 or INFD40
32
10
15
15.2
16
INFC32 or INFD40
16
INFC63 or INFD40
32
11
18.4
16.7
20
INFC32 or INFD40
20
INFC63 or INFD40
40
15
23
21.9
25
INFC32 or INFD40
25
INFC63 or INFD40
50
18.5
28.5
26.6
32
INFC63 or INFD40
63
32
22
33
31
40
INFC63 or INFD40
40
INFC63 or INFD63
80
30
45
43
50
INFC63 or INFD63
50
INFD63
100
37
55
50
63
INFC63 or INFD63
63
INFD63
100
45
65
61
63
INFC63 or INFD63
63
INFD63
125
55
75
74
80
INFC63 or INFD160
80
INFD200
160
75
105
101
100
INFD160
100
INFD250
200
90
130
123
125
INFD160
125
INFD400
250
110
156
147
160
INFD250
160
INFD400
250
132
187
178
200
INFD250
200
INFD630
355
160
214
204
250
INFD250
250
INFD630
400
200
266
254
315
INFD400
315
INFD630
450
240
321
307
355
INFD400
355
280
366
350
400
INFD400
400
300
394
376
400
INFD400
400
320
413
394
450
INFD630
450
355
464
443
500
INFD630
500
375
490
467
500
INFD630
500
(1) Coordination table built with 690 V fuse-links (80 kA for NFC fuse-links, 100 kA for DIN fuse-links).
(2) INFC for NFC cylindrical ferrule / INFD for NH-type DIN fuse-link.
(3) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 with LC3.
(4) For use with a class 20 or class 30 relay, apply respectively a derating of 20 % and 37 %.
(5) Current transformer built into the relay.
I (A) 525 V
0.8
1.2
1.5
2
2.8
3.8
5
6.5
9
12
I (A) 550 V
0.8
1.1
1.4
2.1
2.8
3.7
4.9
6.5
8.7
11.8
Ie Max (A)
2
2
2
2
4
4
6
8
10
12
Contactors (3)
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D25
LC1-D25
Thermal relays
Type
Irth (A)
LTM R08
0.4/8 (5)
LTM R08
0.4/8 (5)
LTM R08
0.4/8 (5)
LTM R08
0.4/8 (5)
LTM R08
0.4/8 (5)
LTM R08
0.4/8 (5)
LTM R08
0.4/8 (5)
LTM R08
0.4/8 (5)
LTM R27
1.35/27 (5)
LTM R27
1.35/27 (5)
LC1-D25
LTM R27
1.35/27 (5)
LC1-D25
LTM R27
1.35/27 (5)
LC1-D32
LTM R27
1.35/27 (5)
LC1-D32
LC1-D40
LTM R100
LTM R100
5/100 (5)
5/100 (5)
LC1-D50
LTM R100
5/100 (5)
LC1-D65
LTM R100
5/100 (5)
LC1-D80
LTM R100
5/100 (5)
LC1-D115
LTM R100
5/100 (5)
LC1-D115
LTM R08
On CT
LC1-D150
LTM R08
On CT
LC1-F185
LTM R08
On CT
LC1-F265
LTM R08
On CT
LC1-F265
LTM R08
On CT
LC1-F400
LTM R08
On CT
LC1-F400
LC1-F500
LC1-F500
LC1-F500
LC1-F500
LC1-F630
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
On CT
On CT
On CT
On CT
On CT
On CT
184
04/11/2009 16:01:09
Complementary
technical information
Type 2 coordination
(IEC 60947-4-1) 660/690 V
Schneider Electric switch-disconnector fuses and contactors
Performance: Ue = 660/690 V - "Iq" 80/100 kA (1)
Starting
Motors
P (kW)
0.75
1
1.5
2.2
3
4
5.5
7.5
11
Switch-fuse (2)
Fuse-link type
Type
gG rating (A)
aM rating (A)
INFC32 or INFD40
4
2
INFC32 or INFD40
6
2
6
4
INFC32 or INFD40
INFC32 or INFD40
10
4
INFC32 or INFD40
10
6
INFC32 or INFD40
16
6
INFC32 or INFD40
20
8
INFC32 or INFD40
25
10
INFC32 or INFD40
16
32
INFC63 or INFD40
20
15
17
20
INFC32 or INFD40
40
INFC63 or INFD40
22
24
INFC63 or INFD40
50
25
18.5
22
24
32
INFC63 or INFD40
50
25
32
32
INFC63 or INFD40
32
30
80
INFC63 or INFD63
40
INFC63 or INFD63
80
40
37
39
45
47
50
INFC63 or INFD63
50
INFD63
100
55
57
63
INFC63 or INFD63
63
INFD63
125
75
77
80
INFC125 or INFD160
80
INFD200
160
90
93
100
INFD160
100
INFD250
200
113
125
INFD160
125
110
INFD250
250
132
134
160
INFD250
250
160
160
160
162
160
INFD250
INFD400
315
200
200
203
200
INFD250
400
INFD630
223
250
INFD250
250
220
450
INFD630
INFD400
315
250
253
315
500
INFD630
355
315
320
355
INFD630
400
INFD630
400
355
354
400
400
450
INFD630
450
450
455
500
INFD630
500
(1) Coordination table built with 690 V fuse-links (80 kA for NFC fuse-links, 100 kA for DIN fuse-links).
(2) INFC for NFC cylindrical ferrule / INFD for NH-type DIN fuse-link.
(3) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 with LC3.
I (A) 690 V
1.1
1.6
2.2
2.8
3.8
4.9
6.7
8.9
12.8
Ie Max (A)
1.6
1.6
2.5
4
4
6
8
10
13
Class 10 A/10
Contactors (3)
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D25
LC1-D25
Thermal relays
Type
LRD 06
LRD 06
LRD 07
LRD 08
LRD 08
LRD 10
LRD 12
LRD 16
LRD 16
Irth (A)
1/1,6
1/1,6
1.6/2.5
2.5/4
2.5/4
4/6
5.5/8
9/13
9/13
LC1-D25
LRD 22
16/24
LC1-D32
LC1-D40
LC1-D40
LRD 22
LRD 3322
LRD 3355
16/24
23/32
30/40
LC1-D65
LC1-D80
LRD 3357
LRD 3357
37/50
37/50
LC1-D115
LRD 3359
48/65
LC1-D115
LRD 3363
63/80
LC1-D150
LR9-D53 69
90/150
LC1-F185
LR9-D53 69
90/150
LC1-F265
LC1-F265
LR9-F53 71
LR9-F53 71
132/220
132/220
LC1-F400
LR9-F73 75
200/330
LC1-F400
LR9-F73 75
200/330
LC1-F400
LR9-F73 75
200/330
LC1-F500
LC1-F630
LC1-F630
LC1-F630
LR9-F73 79
LR9-F73 79
LR9-F73 79
LR9-F73 79
300/500
300/500
300/500
300/500
185
04/11/2009 16:01:09
Complementary
technical information
Type 2 coordination
(IEC 60947-4-1) 660/690 V
Schneider Electric switch-disconnector fuses and contactors
Performance: Ue = 660/690 V - "Iq" 80/100 kA (1)
Starting
Motors
P (kW)
0.75
1
1.5
2.2
3
4
5.5
7.5
11
Switch-fuse (2)
Switch-fuse type
Type
gG rating (A)
aM rating (A)
INFC32 or INFD40
4
2
INFC32 or INFD40
6
2
INFC32 or INFD40
6
4
INFC32 or INFD40
10
4
INFC32 or INFD40
10
6
INFC32 or INFD40
16
6
INFC32 or INFD40
20
8
INFC32 or INFD40
25
10
INFC32 or INFD40
16
INFC63 or INFD40
32
20
15
17
20
INFC32 or INFD40
INFC63 or INFD40
40
22
25
INFC63 or INFD40
50
25
18.5
22
24
25
INFC63 or INFD40
50
25
30
32
32
INFC63 or INFD40
32
INFC63 or INFD63
80
40
INFC63 or INFD63
80
40
37
39
45
47
50
INFC63 or INFD63
50
INFD63
100
55
57
63
INFC63 or INFD63
63
INFD63
125
75
77
80
INFC125 or INFD160
80
INFD200
160
90
93
100
INFD160
100
INFD250
200
113
125
INFD160
125
110
INFD250
250
132
134
160
INFD200
160
INFD250
250
160
160
162
160
INFD200
INFD400
315
200
200
203
200
INFD200
400
INFD630
223
250
INFD250
250
220
450
INFD630
INFD400
315
250
253
315
500
INFD630
INFD400
355
315
320
355
400
INFD400
400
355
354
400
400
450
INFD630
450
450
455
500
INFD630
500
(1) Coordination table built with 690 V fuse-links (80 kA for NFC fuse-links, 100 kA for DIN fuse-links).
(2) INFC for NFC cylindrical ferrule / INFD for NH-type DIN fuse-link.
(3) Reversers: replace LC1 with LC2; star-delta starter: replace LC1 with LC3.
(4) For use with a class 20 or class 30 relay, apply respectively a derating of 20 % and 37 %.
(5) Current transformer built into the relay.
I (A) 690 V
1.1
1.6
2.2
2.8
3.8
4.9
6.7
8.9
12.8
Ie Max (A)
2
2
4
4
6
6
8
10
16
Contactors (3)
Type
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D09
LC1-D25
LC1-D25
Thermal relays
Type
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
LTM R08
LTM R27
LTM R27
Irth (A)
0.4/8 (5)
0.4/8 (5)
0.4/8 (5)
0.4/8 (5)
0.4/8 (5)
0.4/8 (5)
0.4/8 (5)
1.35/27 (5)
1.35/27 (5)
LC1-D25
LTM R27
1.35/27 (5)
LC1-D32
LC1-D40
LC1-D40
LTM R27
LTM R27
LTM R100
1.35/27 (5)
1.35/27 (5)
5/100 (5)
LC1-D65
LC1-D80
LTM R100
LTM R100
5/100 (5)
5/100 (5)
LC1-D115
LTM R100
5/100 (5)
LC1-D115
LTM R100
5/100 (5)
LC1-D150
LTM R100
5/100 (5)
LC1-F185
LTM R08
On CT
LC1-F265
LTM R08
On CT
LC1-F265
LTM R08
On CT
LC1-F400
LTM R08
On CT
LC1-F400
LTM R08
On CT
LC1-F400
LTM R08
On CT
LC1-F500
LC1-F630
LC1-F630
LC1-F630
LTM R08
LTM R08
LTM R08
LTM R08
On CT
On CT
On CT
On CT
186
04/11/2009 16:01:10
Complementary
technical information
Use of LV switches
DB115214
187
04/11/2009 16:01:12
Complementary
technical information
Use of LV switches
DB125826
IEC 947.3
UTE VDE BS
CEI UNE
Switch-disconnector
Isolation permits a circuit or a device to be disconnected from the rest of the
electrical installation, in order to guarantee the safety of those who have to achieve
repairs or maintenance.
Normally, all circuits in an electrical installation must be capable of being isolated. In
practice, to ensure optimal continuity of service, an isolating device is installed at the
start of every circuit distribution.
Certain switches allow this function to be achieved in addition to their circuit control
function.
Therefore a switch-disconnector must display the symbol (illustrated opposite),
visibly on the front face of the installed device.
Isolating function
Installation standards stipulate the requirements which must be respected in order
for a device to carry out its isolating function.
It must:
b be with equipped with omnipolar isolation, that is to say that the live conductors,
including the neutral (with the exception of the PEN conductor which must never be
isolated) must be isolated simultaneously
b be lockable in the open position so as to prevent any risk of unvolontary
reclosing this is imperative for industrial devices
b conform to a standard which guarantees its suitability for isolation
b It must also meet overvoltage withstand requirements. However, if the isolation is
explicitly recognized by a manufacturing standard, for example IEC 60947-1/3 for
industrial switch-disconnectors, a device which complies with this isolation standard
is judged to comply fully with the conditions required by installation standards.
The manufacturing standard guarantees its use for isolation suitability for the user.
188
558E4800.indd 188
23/11/2009 11:04:48
Complementary
technical information
Use of LV switches
Utilization category
Frequent
operations
AC-21A
Non frequent
operations
AC-21B
Characteristic
applications
189
04/11/2009 16:01:15
Complementary
technical information
Choice criteria
Network characteristics
Nominal voltage, nominal frequency and nominal current are determined in the same
way as for a circuit-breaker:
b nominal voltage = nominal voltage of the network
b frequency = network frequency
b nominal current = rated current of a value immediately higher than the
downstream load current. Note that the rated current is defined for a given ambient
temperature and that a derating may have to be taken into account.
Location and application
This determines the type and characteristics or main functions that the switch must
possess. There are 3 function levels (see table opposite):
b basic functions, virtually common to all switch types:
v isolation, control, padlocking, safety.
b additional characteristic functions
v direct formulation of the needs of the user and of the switch environment, i.e.:
- industrial type performance
- need for emergency stopping
- lsc level
- type of interlocking
- type of control
- utilization category
- mounting system.
b specific functions
v linked to operation and to installation requirements, i.e.:
- earth leakage protection
- motor mechanisms
- remote opening (emergency stop function)
- withdrawability.
The following table enables choice of switch according to requirements.
b choice table
Comparison of the application table K (see page191) and the switch technical data
table M (see page193) lets you specify which switch range should be used.
Coordination
All switches must be protected by an overcurrent protection device placed upstream.
The "additional technical information" tables below give the SCPD (circuit-breaker
or fuse) guaranteeing proper coordination with switches in event of a downstream
short-circuit, according to the electrodynamic withstand or the short-circuit making
capacity of the device.
190
04/11/2009 16:01:16
Complementary
technical information
Current range
LV switch basic functions
Circuit on-load control
Isolation
Padlocking the isolated status
Padlocking
Additional functions / technical data
Maximum short-circuit level
Motor
mechanism
technical
data
Handle
AC21A
AC22A
AC23
AC3
Rotary
Direct front
Front extended
Side extended
Mounting
On plate
Symmetrical rail
(45 mm tip)
Specific functions
Earth leakage protection
Other
Draw-out, auxiliary
switches, auxiliary
releases, remote
control
Emergency stop
Table K
b compulsory.
v possible.
Power
distribution
switchboards
Industrial
switchboards
and automation
cubicles
400 to 6300 A
40 to 630 A
20 to 160 A
y 125 A
Yes
Yes
Yes
Yes
b
b
b
b
By isolation with positive break indication or visible isolation
b
b
b
b
20 to 80 kA
b
b
v
b I y 160 A:
15 to 25 kA
b I y 400 A:
20 to 80 kA
b
v
b I y 63 A: 15 kA
10 kA
Automation
enclosures
Local isolation
enclosures
y 40/125 A
10 to 630 A
Yes
b
Yes
b
3 to 5 kA
b I y 63 A: 10 kA
b I y 160 A: 25 kA
b
v
b I y 630 A: 25 kA
b
v
b
b
b
v
b
v
v
v
v
v
b
v
b
v
v
b
b
b
b I y 63 A
b
v
b
b
v
191
04/11/2009 16:01:17
Complementary
technical information
Products
Subdistribution
switchboards
400-6300 A
20-160 A
400-630 A
400-630 A
Vario
(Telemecanique)
Multi 9 I/ID
(modular profile)
Multi 9 I-NA
(modular profile)
Interpact INS
b
v (1)
(modular profile)
NG125 NA
(modular profile)
Interpact INS
b
b
v (1)
(industrial)
Compact NA
v
b
v (1)
(industrial)
Masterpact HI/HF
b
(industrial)
Table L
b very common
v fairly common.
(1) Fairly common, but totally suitable for these application types.
Small tertiary
distribution
enclosures
y 125 A
Automation
enclosures
Local isolation
switches
Local isolation
enclosures
y 40/125 A
10-630 A
v
b
b
b
b
b
192
04/11/2009 16:01:18
Complementary
technical information
Vario
Multi 9
I
I-NA
ID
Interpact
NG125NA INS
INV
b
b
b (3)
b
b
IN
Compact
NA/NI CMI
b
b
b
b
Masterpact
NI
HI
b
b
b
b
HF
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b (8)
b
b
b (8)
b
b
b (8)
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b (4)
b (1)
b (2)
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
193
04/11/2009 16:01:20
194
04/11/2009 16:01:20
DB125665
Complementary
technical information
Use of LV switches
Switch-disconnectors protection
By Compact NSX
Type/maximum rating (A)
Isc max. (380/415 V)
kA rms
Making capacity (380/415 V)
kA peak
Type/maximum rating (A)
Isc max. (380/415 V)
kA rms
Making capacity (380/415 V)
kA peak
Type/maximum rating (A)
Isc max. (380/415 V)
kA rms
Making capacity (380/415 V)
kA peak
By fuse
Type aM (1) maximum rating (A)
Isc max. (500 V)
kA rms
Making capacity (500 V)
kA peak
Type gl (2) maximum rating (A)
Isc max. (500 V)
kA rms
Making capacity (500 V)
kA peak
(1)
Type gl maximum rating (A)
Isc max. (500 V)
kA rms
Making capacity (500 V)
kA peak
Type BS (2) maximum rating (A)
Isc max. (500 V)
kA rms
Making capacity (500 V)
kA peak
Type BS (1) maximum rating (A)
Isc max. (500 V)
kA rms
Making capacity (500 V)
kA peak
(1) Protection by external thermal relay obligatory.
(2) Without extandernal thermal relay.
NG160NA
NSX160F/160
36
75
NSX160N/160
50
105
NG160N/160
25
52
160
33
69
125
100
220
160
100
220
125 and 100M125
80
176
160 and 100M160
80
176
195
04/11/2009 16:01:21
Complementary
technical information
Use of LV switches
Switch-disconnectors protection
Compact NSX
By 380/415 V circuit breaker Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
By 440/480 V (1)
Type/maximum rating (A)
circuit breaker
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
By 500 V circuit breaker
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
(1) Suitable for NEMA 480 V voltage.
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
196
558E4800.indd 196
20/11/2009 14:28:57
Complementary
technical information
Use of LV switches
Switch-disconnectors protection
NSX100NA
NSX160NA
NSX250NA
NSX400NA
NSX630NA
NSX100B/100
25
53
NSX100F/100
36
76
NSX100N/100
50
105
NSX100H/100
70
154
NSX100S/100
100
220
NSX100L/100
150
330
NSX100B/100
20
40
NSX100F/100
35
74
NSX100N/100
50
105
NSX100H/100
65
143
NSX100S/100
90
198
NSX100L/100
130
286
NSX100B/100
15
30
NSX100F/100
25
52
NSX100N/100
36
76
NSX100H/100
50
105
NSX100S/100
65
143
NSX100L/100
70
154
NSX160B/160
25
53
NSX160F/160
36
76
NSX160N/160
50
105
NSX160H/160
70
154
NSX160S/160
100
220
NSX160L/160
150
330
NSX160B/160
20
40
NSX160F/160
35
74
NSX160N/160
50
105
NSX160H/160
65
143
NSX160S/160
90
198
NSX160L/160
130
286
NSX160B/160
15
30
NSX160F/160
30
63
NSX160N/160
36
76
NSX160H/160
50
105
NSX160S/160
65
143
NSX160L/160
70
154
NSX250B/250
25
53
NSX250F/250
36
76
NSX250N/250
50
105
NSX250H/250
70
154
NSX250S/250
100
220
NSX250L/250
150
330
NSX250B/250
20
40
NSX250F/250
35
74
NSX250N/250
50
105
NSX250H/250
65
143
NSX250S/250
90
198
NSX250L/250
130
286
NSX250B/250
15
30
NSX250F/250
30
63
NSX250N/250
36
76
NSX250H/250
50
105
NSX250S/250
65
143
NSX250L/250
70
154
NSX400F/400
36
76
NSX400N/400
50
105
NSX400H/400
70
154
NSX400S/400
100
220
NSX400L/400
150
330
-
NSX630F/630
36
76
NSX630N/630
50
105
NSX630H/630
70
154
NSX630S/630
100
220
NSX630L/630
150
330
-
NSX400F/400
35
74
NSX400N/400
50
105
NSX400H/400
65
143
NSX400S/400
90
198
NSX400L/400
130
286
-
NSX630F/630
35
74
NSX630N/630
50
105
NSX630H/630
65
143
NSX630S/630
90
198
NSX630L/630
130
286
-
NSX400F/400
25
52
NSX400N/400
30
63
NSX400H/400
50
105
NSX400S/400
65
143
NSX400L/400
70
154
NSX630F/630
25
52
NSX630N/630
30
63
NSX630H/630
50
105
NSX630S/630
65
143
NSX630L/630
70
154
197
04/11/2009 16:01:26
Complementary
technical information
Use of LV switches
Switch-disconnectors protection
Compact NSX
By 525 V circuit breaker
By 500 V fuse
kA rms
kA peak
kA rms
kA peak
kA efg.
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA efg.
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
198
558E4800.indd 198
20/11/2009 14:29:47
Complementary
technical information
Use of LV switches
Switch-disconnectors protection
NSX100NA
NSX160NA
NSX250NA
NSX400NA
NSX630NA
NSX100F/100
22
46
NSX100N/100
35
74
NSX100H/100
35
74
NSX100S/100
40
85
NSX100L/100
50
105
NSX100F/100
8
14
NSX100N/100
10
17
NSX100S/100
15
30
NSX100L/100
20
40
NSX160F/160
22
46
NSX160N/160
22
46
NSX160H/160
22
46
NSX160S/160
22
46
NSX160L/160
22
46
NSX160F/160
8
14
NSX160N/160
10
17
NSX160S/160
15
30
NSX160L/160
20
40
NSX250F/250
22
46
NSX250N/250
22
46
NSX250H/250
22
46
NSX250S/250
22
46
NSX250L/250
22
46
NSX250F/250
8
14
NSX250N/250
10
17
NSX250S/250
15
30
NSX250L/250
20
40
NSX400F/400
20
42
NSX400N/400
22
46
NSX400H/400
22
46
NSX400S/400
22
46
NSX400L/400
22
46
NSX400F/400
10
17
NSX400N/400
20
42
NSX400S/400
25
52
NSX400L/400
35
74
NSX630F/630
20
42
NSX630N/630
22
46
NSX630H/630
22
46
NSX630S/630
22
46
NSX630L/630
22
46
NSX630F/630
10
17
NSX630N/630
20
42
NSX630S/630
25
52
NSX630L/630
35
74
100
100
220
80
100
220
100
100
220
80 and 63M80
80
176
160 and 100M160
80
176
160
100
220
125
100
220
160
100
220
125 and 100M125
80
176
160 and 100M160
80
176
250
100
220
200
100
220
250
100
220
160 and 100M160
80
176
250 and 200M250
80
176
400
100
220
315
100
220
400
100
220
315 and 200M315
80
176
355 and 315M355
80
176
630
100
220
500
100
220
630
100
220
500
80
176
450 and 400M450
80
176
199
04/11/2009 16:01:33
Complementary
technical information
Use of LV switches
Switch-disconnectors protection
Compact NS
By 380/415 V circuit breaker
By 440/480 V (1)
circuit breaker
Masterpact NT H1
By 220/690 V circuit breaker
Masterpact NT L1
By 220/525 V circuit breaker Type/maximum rating (A)
Isc max.
Making capacity
By 690 V
Type/maximum rating (A)
Isc max.
Making capacity
Masterpact NW N1-H1-H2-H3
By 220/440-480 V (1)
Type/maximum rating (A)
circuit breaker
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
By 500/525 V circuit breaker Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
By 690 V circuit breaker
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Masterpact NW L1
By 220/690 V
Type/maximum rating (A)
circuit breaker
Isc max.
Making capacity
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
200
04/11/2009 16:01:39
Complementary
technical information
Use of LV switches
Switch-disconnectors protection
NS630bNA
NS800NA
NS1000NA
NS1250NA
NS1600NA
NS630bN/630
50
105
NS630bH/630
70
154
NS630bL/630
150
330
NS630bN/630
50
105
NS1600H-bH/1600
65
143
NS630bL/630
130
286
NS630bN/630
40
84
NS630bH/630
50
105
NS630bL/630
100
220
NS630bN/630
30
63
NS630bH/630
42
88
NS630bL/630
25
53
NS800N/800
50
105
NS800H/800
70
154
NS800L/800
150
330
NS800N/800
50
105
NS1600H-bH/1600
65
143
NS800L/800
130
286
NS800N/800
40
84
NS800H/800
50
105
NS800L/800
100
220
NS800N/800
30
63
NS800H/800
42
88
NS800L/800
25
53
NS1000N/1000
50
105
NS1000H/1000
70
154
NS1000L/1000
150
330
NS1000N/1000
50
105
NS2000H/2000
65
143
NS1000L/1000
130
286
NS1000N/1000
40
84
NS1000H/1000
50
105
NS1000L/1000
100
220
NS1000N/1000
30
63
NS1000H/1000
42
88
NS1000L/1000
25
53
NS1250N/1250
50
105
NS1250H/1250
70
154
NS1600N-bN/1600
50
105
NS1600H-bH/1600
70
154
NS1250N/1250
50
105
NS2500H/2500
65
143
NS1600N-bN/1600
50
105
NS3200H/3200
65
143
NS1250N/1250
40
84
NS1250H/1250
50
105
NS1600N-bN/1600
40
84
NS1600H-bH/1600
50
105
NS1250N/1250
30
63
NS1250H/1250
42
88
NS1600N-bN/1600
30
63
NS1600H-bH/1600
42
88
NT06H1/630
25/42
53/88
NT08H1/800
25/42
53/88
NT10H1/1000
25/42
53/88
NT12H1/1000
25/42
53/88
NT16H1/160
25/42
53/88
NT06L1/630
100
220
NT06L1/630
25
53
NT08L1/800
100
220
NT08L1/800
25
53
NT10L1/1000
100
220
NT10L1/1000
25
53
NT12L1/1250
100
220
NT12L1/1250
25
53
NT16L1/160
100
220
NT16L1/160
25
53
NW08N1/630
25/42
53/88
NW08H1/630
25/50
53/105
NW08H2/630
25/50
53/105
NW08N1/630
25/40
53/84
NW08H1/630
25/40
53/84
NW08H2/630
25/40
53/84
NW08N1/630
25/30
53/63
NW08H1/630
25/30
53/63
NW08H2/630
25/30
53/63
NW08N1/800
25/42
53/88
NW08H1/800
25/50
53/105
NW08H2/800
25/50
53/105
NW08N1/800
25/40
53/84
NW08H1/800
25/40
53/84
NW08H2/800
25/40
53/84
NW08N1/800
25/30
53/63
NW08H1/800
25/30
53/63
NW08H2/800
25/30
53/63
NW10N1/1000
25/42
53/88
NW10H1/1000
25/50
53/105
NW10H2/1000
25/50
53/105
NW10N1/1000
25/40
53/84
NW10H1/1000
25/40
53/84
NW10H2/1000
25/40
53/84
NW10N1/1000
25/30
53/63
NW10H1/1000
25/30
53/63
NW10H2/1000
25/30
53/63
NW12N1/1250
25/42
53/88
NW12H1/1250
25/50
53/105
NW12H2/1250
25/50
53/105
NW12N1/1250
25/40
53/84
NW12H1/1250
25/40
53/84
NW12H2/1250
25/40
53/84
NW12N1/1250
25/30
53/63
NW12H1/1250
25/30
53/63
NW12H2/1250
25/30
53/63
NW16N1/160
25/4
53/88
NW16H1/1600
25/50
53/105
NW16H2/1600
25/50
53/105
NW16N1/160
25/40
53/84
NW16H1/1600
25/40
53/8
NW16H2/160
25/40
53/84
NW16N1/160
25/3
53/6
NW16H1/160
25/30
53/6
NW16H2/160
25/30
53/6
NW08L1/630
25
53
NW08L1/800
25
53
NW10L1/1000
25
53
NW12L1/1250
25
53
NW16L1/160
25
53
201
04/11/2009 16:01:40
Complementary
technical information
Use of LV switches
Switch-disconnectors protection
Compact NS
By 380/415 V circuit breaker Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
By 440/480 V (1)
Type/maximum rating (A)
circuit breaker
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
By 500/525 V circuit breaker Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
By 690 V circuit breaker
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Masterpact NT H1
By 220/690 V circuit breaker
Type/maximum rating (A)
Isc max.
Making capacity
Masterpact NT L1
By 220/525 V circuit breaker Type/maximum rating (A)
Isc max.
Making capacity
By 690 V
Type/maximum rating (A)
Isc max.
Making capacity
Masterpact NW N1-H1-H2-H3
By 220/440-480 V (1)
Type/maximum rating (A)
circuit breaker
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
By 500/525 V circuit breaker Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
By 690 V circuit breaker
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Type/maximum rating (A)
Isc max.
Making capacity
Masterpact NW L1
By 220/690 V circuit breaker Type/maximum rating (A)
Isc max.
Making capacity
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
202
04/11/2009 16:01:41
Complementary
technical information
Use of LV switches
Switch-disconnectors protection
NS1600bNA
NS2000NA
NS2500NA
NS3200NA
NS1600N/bN/1600
50/70
105/154
NS1600H/bH/1600
70/85
154/187
NS1600N/bN/1600
50/65
105/143
NS1600H/bH/1600
65/85
143/187
NS1600N/bN/1600
40/65
84/143
NS1600H/BH/1600
50/65
105/143
NS1600N/bN/1600
30/65
63/143
NS1600H/bH/1600
42/65
88/143
NS2000N/2000
70
154
NS2000H/2000
85
187
NS2000N/2000
65
143
NS2000H/2000
85
187
NS2000N/2000
65
143
NS2000H/2000
65
143
NS2000N/2000
65
143
NS2000H/2000
65
143
NS2500N/2500
70
154
NS2500H/2500
85
187
NS2500N/2500
65
143
NS2500H/2500
85
187
NS2500N/2500
65
143
NS2500H/2500
65
143
NS2500N/2500
65
143
NS2500H/2500
65
143
NS3200N/3200
70
154
NS3200H/320
85
187
NS3200N/3200
65
143
NS3200H/3200
85
187
NS3200N/3200
65
143
NS3200H/3200
65
143
NS3200N/3200
65
143
NS3200H/3200
65
143
NT16H1/1600
30/42
63/88
NT16L1/1600
100
220
NT16L1/1600
25
50
NW16N1/1600
50/88
50/88
NW16H1/1600
65
143
NW16H2/1600
70
154
NW20H1/2000
65
143
NW20H2/2000
70
154
NW20H3/2000
70
154
-
NW25H1/2500
65
143
NW25H2/2500
70
154
NW25H3/2500
70
154
-
NW32H1/3200
65
143
NW32H2/3200
70
154
NW32H3/3200
70
154
-
NW20H1/3000
65
143
NW20H2/2000
65
143
NW20H3/2000
65
143
-
NW25H1/2500
65
143
NW25H2/2500
65
143
NW25H3/2500
65
143
-
NW32H1/3200
65
143
NW32H2/3200
65
143
NW32H3/3200
65
143
-
NW20H1/2000
65
143
NW20H2/2000
65
143
NW20H3/2000
65
143
NW25H1/2500
65
143
NW25H2/2500
65
143
NW25H3/2500
65
143
NW32H1/3200
65
143
NW32H2/3200
65
143
NW32H3/3200
65
143
NW20L1/2000
100
220
NW16N1/1600
50/88
50/88
NW16H1/1600
75
143
NW16H2/1600
70
154
NW16N1/1600
42
88
NW16H1/1600
65
143
NW16H2/1600
65
143
NW16L1/1600
100
220
203
04/11/2009 16:01:42
Complementary
technical information
Protection of switchdisconnectors
By Compact NSX
By circuit breaker 380/415 V
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
204
04/11/2009 16:01:44
Protection of switchdisconnectors
Complementary
technical information
INS63
INS80
INS100
INS125
INS160
NSX100B/40
25
52
NSX100F/40
36
75
NSX100N/40
36
75
NSX100H/S/L/40
36
75
NSX160B/40
25
52
NSX160F/40
25
52
NSX160N/40
25
52
NSX160H/S/L/40
25
52
-
NSX100B/63
25
52
NSX100F/63
36
75
NSX100N/63
36
75
NSX100H/S/L/63
36
75
NSX160B/63
25
52
NSX160F/63
25
52
NSX160N/63
25
52
NSX160H/S/L/63
25
52
-
NSX100B/80
25
52
NSX100F/80
36
75
NSX100N/80
36
75
NSX100H/S/L/80
36
75
NSX160B/80
25
52
NSX160F/80
25
52
NSX160N/80
25
52
NSX160H/S/L/80
25
52
-
NSC100N/40
18
37
NG125N/40
25
52
NG125H/40
36
75
NG125L/40
50
105
NG160N/40
25
52
NSC100N/63
18
37
NG125N/63
25
52
NG125H/63
36
75
NG125L/63
50
105
NG160N/63
25
52
NSC100N/80
18
37
NG125N/80
25
52
NG125H/80
36
75
NG125L/80
50
105
NG160N/80
25
52
NSX100B/100
25
52
NSX100F/100
36
75
NSX100N/100
36
75
NSX100H/S/L/100
36
75
NSX160B/100
25
52
NSX160F/100
36
75
NSX160N/100
50
105
NSX160H/S/L/100
70
154
NSX250B/100
25
52
NSX250F/100
36
75
NSX250N/100
50
105
NSX250H/S/L/100
70
154
NSC100N/100
18
37
NG125N/100
25
52
-
NSX160B/125
25
52
NSX160F/125
36
75
NSX160N/125
50
105
NSX160H/S/L/125
70
154
NSX250B/125
25
52
NSX250F/125
36
75
NSX250N/125
50
105
NSX250H/S/L/125
70
154
-
NSX160B/160
25
52
NSX160F/160
36
75
NSX160N/160
50
105
NSX160H/S/L/160
70
154
NSX250B/160
25
52
NSX250F/160
36
75
NSX250N/160
50
105
NSX250H/S/L/160
70
154
-
NG125N/125
25
52
-
NG160N/100
25
52
NG160N/125
25
52
NG160N/160
25
52
205
04/11/2009 16:01:45
Complementary
technical information
Protection of switchdisconnectors
By Compact NSX
By circuit breaker
440/480 V (1)
By circuit breaker
500/525 V
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
206
04/11/2009 16:01:52
Protection of switchdisconnectors
Complementary
technical information
INS63
INS80
INS100
INS125
INS160
NSX100B/40
20
40
NSX100F/40
35
73
NSX100N/40
35
73
NSX100H/S/L/40
35
73
NSX160B/40
20
40
NSX160F/40
25
52
NSX160N/40
25
52
NSX160H/S/L/40
25
52
-
NSX100B/63
20
40
NSX100F/63
35
73
NSX100N/63
35
73
NSX100H/S/L/63
35
73
NSX160B/63
20
40
NSX160F/63
25
52
NSX160N/63
25
52
NSX160H/S/L/63
25
52
-
NSX100B/80
20
40
NSX100F/80
35
73
NSX100N/80
35
73
NSX100H/S/L/80
35
73
NSX160B/80
20
40
NSX160F/80
25
52
NSX160N/80
25
52
NSX160H/S/L/80
25
52
-
NSC100N/40
18
37
NSX100B/40
15
30
NSX100F/40
18
36
NSX100N/40
18
36
NSX100H/S/L/40
25
53
NSX160B/40
15
30
NSX160F/40
15
30
NSX160N/40
15
30
NSX160H/S/L/40
15
30
-
NSC100N/63
18
37
NSX100B/63
15
30
NSX100F/63
18
36
NSX100N/63
18
36
NSX100H/S/L/63
25
53
NSX160B/63
15
30
NSX160F/63
15
30
NSX160N/63
15
30
NSX160H/S/L/63
15
30
-
NSC100N/80
18
37
NSX100B/80
15
30
NSX100F/80
18
36
NSX100N/80
18
36
NSX100H/S/L/80
25
53
NSX160B/80
15
30
NSX160F/80
15
30
NSX160N/80
15
30
NSX160H/S/L/80
15
30
-
NSX160B/125
20
40
NSX160F/125
35
73
NSX160N/125
35
73
NSX160H/S/L/125
65
143
NSX250B/125
20
40
NSX250F/125
35
73
NSX250N/125
35
73
NSX250H/S/L/125
65
143
-
NSX160B/160
20
40
NSX160F/160
35
73
NSX160N/160
35
73
NSX160H/S/L/160
65
143
NSX250B/160
20
40
NSX250F/160
35
73
NSX250N/160
35
73
NSX250H/S/L/160
65
143
-
NSC100N/40
18
37
NSC100N/63
18
37
NSC100N/80
18
37
NSX100B/100
20
40
NSX100F/100
35
73
NSX100N/100
35
73
NSX100H/S/L/100
65
143
NSX160B/100
20
40
NSX160F/100
35
73
NSX160N/100
35
73
NSX160H/S/L/100
65
143
NSX250B/100
20
40
NSX250F/100
35
73
NSX250N/100
35
73
NSX250H/S/L/100
65
143
NSC100N/100
18
37
NSX100B/100
15
30
NSX100F/100
18
36
NSX100N/100
18
36
NSX100H/S/L/100
25
53
NSX160B/100
15
30
NSX160F/100
15
30
NSX160N/100
15
30
NSX160H/S/L/100
22
46
NSX250B/100
15
30
NSX250F/100
15
30
NSX250N/100
15
30
NSX250H/S/L/100
22
46
NSC100N/100
18
37
NSX160B/125
15
30
NSX160F/125
22
46
NSX160N/125
22
46
NSX160H/S/L/125
22
46
NSX250B/125
15
30
NSX250F/125
22
46
NSX250N/125
22
46
NSX250H/S/L/125
22
46
-
NSX160B/160
15
30
NSX160F/160
22
46
NSX160N/160
22
46
NSX160H/S/L/160
22
46
NSX250B/160
15
30
NSX250F/160
22
46
NSX250N/160
22
46
NSX250H/S/L/160
22
46
-
207
04/11/2009 16:01:52
Complementary
technical information
Protection of switchdisconnectors
By Compact NSX
By circuit breaker 690 V
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
By 500 V fuse
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
208
04/11/2009 16:01:56
Protection of switchdisconnectors
Complementary
technical information
INS63
INS80
INS100
INS125
INS160
NSC100N/40
18
37
NSC100N/63
18
37
NSC100N/80
18
37
NSX100B/100
6
9
NSX100F/100
8
14
NSX100N/100
10
17
NSX100H/S/L/100
10
17
NSX160B/100
6
9
NSX160F/100
8
14
NSX160N/100
10
17
NSX160H/S/L/100
10
17
NSX250B/100
6
9
NSX250F/100
8
14
NSX250N/100
10
17
NSX250H/S/L/100
10
17
NSC100N/100
18
37
NSX160B/125
6
9
NSX160F/125
8
14
NSX160N/125
10
17
NSX160H/S/L/125
10
17
NSX250B/125
6
9
NSX250F/125
8
14
NSX250N/125
10
17
NSX250H/S/L/125
10
17
-
NSX160B/160
6
9
NSX160F/160
8
14
NSX160N/160
10
17
NSX160H/S/L/160
10
17
NSX250B/160
6
9
NSX250F/160
8
14
NSX250N/160
10
17
NSX250H/S/L/160
10
17
-
125
100
220
32
100
120
100
100
220
32
80
176
125 and 100M125
80
176
-
125
100
220
50
100
120
100
100
220
50 and 32M50
80
176
125 and 100M125
80
176
-
125
100
220
50
100
120
100
100
220
63 and 32M63
80
176
125 and 100M125
80
176
-
200
100
220
100
100
220
125/160
100/50
220/105
100 and 63M100
80
176
160 and 100M160
80
176
125
100
220
100
100
220
125
100
220
200
100
220
125
100
220
125/160
100/50
220/105
125 and 100M125
80
176
160 and 100M160
80
176
125
100
220
125
100
220
125
100
220
200
100
220
80
100
220
125/160
100/50
220/105
80 and 63M80
80
176
160 and 100M160
80
176
125
100
220
80
100
220
125
100
220
209
04/11/2009 16:01:57
Complementary
technical information
Protection of switchdisconnectors
INS/INV100 to INS/INV630 by
Compact NSX circuit breaker
DB125667
By Compact NSX
By circuit breaker 380/415 V
By circuit breaker
440/480 V (1)
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
NSX100-160-250B/100
25
52
NSX100-160-250F/100
36
75
NSX100-160-250N/100
50
105
NSX100-160-250H/100
70
154
NSX100-160-250S/100
100
220
NSX100-160-250L/100
150
330
NSX100-160-250B/100
20
40
NSX100-160-250F/100
35
73
NSX100-160-250N/100
50
105
NSX100-160-250H/100
65
143
NSX100-160-250S/100
90
198
NSX100-160-250L/100
130
286
NSX100-160-250B/100
15
30
NSX100F/100
25
52
NSX160-250F/100
30
63
NSX100-160-250N/100
36
75
NSX100-160-250H/100
50
105
NSX100-160-250S/100
65
143
NSX100-160-250L/100
70
154
NSX160-250B/160
25
52
NSX160-250F/160
36
75
NSX160-250N/160
50
105
NSX160-250H/160
70
154
NSX160-250S/160
100
220
NSX160-250L/160
150
330
NSX160-250B/160
20
40
NSX160-250F/160
35
73
NSX160-250N/160
50
105
NSX160-250H/160
65
143
NSX160-250S/160
90
198
NSX160-250L/160
130
286
NSX160-250B/160
15
30
-
NSX160-250H/160
30
63
NSX160-250N/160
36
75
NSX160-250H/160
50
105
NSX160-250S/160
65
143
NSX160-250L/160
70
154
210
04/11/2009 16:02:00
Protection of switchdisconnectors
Complementary
technical information
INS/INV100 to INS/INV630 by
Compact NSX circuit breaker
INS250-200 /
INV200
INS/INV250
INS/INV320
INS/INV400
INS/INV500
INS/INV630
NSX250B/200
25
52
NSX250F/200
36
75
NSX250N/200
50
105
NSX250H/200
70
154
NSX250S/200
100
220
NSX250L/200
150
330
NSX250B/200
20
40
NSX250F/200
35
73
NSX250N/200
50
105
NSX250H/200
65
143
NSX250S/200
90
198
NSX250L/200
130
286
NSX250B/200
15
30
-
NSX250N/250
25
52
NSX250F/250
36
75
NSX250N/250
50
105
NSX250H/250
70
154
NSX250S/250
100
220
NSX250L/250
150
330
NSX250B/250
20
40
NSX250F/250
35
73
NSX250N/250
50
105
NSX250H/250
65
143
NSX250S/250
90
198
NSX250L/250
130
286
NSX250B/250
15
30
-
NSX400-630F/320
36
75
NSX400-630N/320
50
105
NSX400-630H/320
70
154
NSX400-630S/320
100
220
NSX400-630L/320
150
330
-
NSX400-630F/400
36
75
NSX400-630N/400
50
105
NSX400-630H/400
70
154
NSX400-630S/400
100
220
NSX400-630L/400
150
330
-
NSX630F/500
36
75
NSX630N/500
50
105
NSX630H/500
70
154
NSX630S/500
100
220
NSX630L/500
150
330
-
NSX630F/630
36
75
NSX630N/630
50
105
NSX630H/630
70
154
NSX630S/630
100
220
NSX630L/630
150
330
-
NSX400-630F/320
35
73
NSX400-630N/320
50
105
NSX400-630H/320
65
143
NSX400-630S/320
90
198
NSX400-630L/320
130
286
-
NSX400-630F/400
35
73
NSX400-630N/400
50
105
NSX400-630H/400
65
143
NSX400-630S/400
90
198
NSX400-630L/400
130
286
-
NSX630F/500
35
73
NSX630N/500
50
105
NSX630H/500
65
143
NSX630S/500
90
198
NSX630L/500
130
286
-
NSX630F/630
35
73
NSX630N/630
50
105
NSX630H/630
65
143
NSX630S/630
90
198
NSX630L/630
130
286
-
NSX250F/200
30
63
NSX250N/200
36
75
NSX250H/200
50
105
NSX250S/200
65
143
NSX250L/200
70
154
NSX250F/250
30
63
NSX250N/250
36
75
NSX250H/250
50
105
NSX250S/250
65
143
NSX250L/250
70
154
NSX400-630F/320
25
52
NSX400-630N/320
30
63
NSX400-630H/320
50
105
NSX400-630S/320
65
143
NSX400-630L/320
70
154
NSX400-630F/400
25
52
NSX400-630N/400
30
63
NSX400-630H/400
50
105
NSX400-630S/400
65
143
NSX400-630L/400
70
154
NSX630F/500
25
52
NSX630N/500
30
63
NSX630H/500
50
105
NSX630S/500
65
143
NSX630L/500
70
154
NSX630F/630
25
52
NSX630N/630
30
63
NSX630H/630
50
105
NSX630S/630
65
143
NSX630L/630
70
154
211
04/11/2009 16:02:00
Complementary
technical information
Protection of switchdisconnectors
INS/INV100 to INS/INV630 by
Compact NSX circuit breaker
DB125667
By Compact NSX
By circuit breaker 525 V
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
By 500 V fuse
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
NSX100-160-250B/100
12
24
NSX100-160-250F/100
22
47
NSX100-160-250N/100
35
73
NSX100-160-250H/100
35
73
NSX100-160-250S/100
40
81
NSX100-160-250L/100
50
105
NSX100-160-250B/100
6
9
NSX100-160-250F/100
8
14
NSX100-160-250N/100
10
17
NSX100-160-250H/100
10
17
NSX100-160-250S/100
15
30
NSX100-160-250L/100
20
40
NSX160-250B/160
12
24
NSX160-250F/160
22
47
NSX160-250N/160
35
73
NSX160-250H/160
35
73
NSX160-250S/160
40
81
NSX160-250L/160
50
105
NSX160-250B/160
6
9
NSX160-250F/160
8
14
NSX160-250N/160
10
17
NSX160-250H/160
10
17
NSX160-250S/160
15
30
NSX160-250L/160
20
40
315
100
220
80
100
220
225/355
100/50
220/105
80 and 63M80
80
176
250 and 200M250
80
176
250
100
220
80
100
220
200
100
220
315
100
220
125
100
220
225/355
100/50
220/105
125 and 100M125
80
176
250 and 200M250
80
176
250
100
220
125
100
220
200
100
220
212
04/11/2009 16:02:07
Protection of switchdisconnectors
Complementary
technical information
INS/INV100 to INS/INV630 by
Compact NSX circuit breaker
INS250-200 /
INV200
INS/INV250
INS/INV320
INS/INV400
INS/INV500
INS/INV630
NSX250B/200
12
24
NSX250F/200
22
47
NSX250N/200
35
73
NSX250H/200
35
73
NSX250S/200
40
81
NSX250L/200
50
105
NSX250B/200
6
9
NSX250F/200
8
14
NSX250N/200
10
17
NSX250H/200
10
17
NSX250S/200
15
30
NSX250L/200
20
40
NSX250B/250
12
24
NSX250F/250
22
47
NSX250N/250
35
73
NSX250H/250
35
73
NSX250S/250
40
81
NSX250L/250
50
105
NSX250B/250
6
9
NSX250F/250
8
14
NSX250N/250
10
17
NSX250H/250
10
17
NSX250S/250
15
30
NSX250L/250
20
40
NSX400-630F/320
22
47
NSX400-630N/320
22
47
NSX400-630H/320
35
73
NSX400-630S/320
40
81
NSX400-630L/320
50
105
-
NSX400-630F/400
22
47
NSX400-630N/400
22
47
NSX400-630H/400
35
73
NSX400-630S/400
40
81
NSX400-630L/400
50
105
-
NSX630F/500
22
47
NSX630N/500
22
47
NSX630H/500
35
73
NSX630S/500
40
81
NSX630L/500
50
105
-
NSX630F/630
22
47
NSX630N/630
22
47
NSX630H/630
35
73
NSX630S/630
40
81
NSX630L/630
50
105
-
NSX400-630F/320
8
14
NSX400-630N/320
10
17
NSX400-630H/320
10
17
NSX400-630S/320
15
30
NSX400-630L/320
20
40
NSX400-630F/400
8
14
NSX400-630N/400
10
17
NSX400-630H/400
10
17
NSX400-630S/400
15
30
NSX400-630L/400
20
40
NSX630F/500
8
14
NSX630N/500
10
17
NSX630H/500
10
17
NSX630S/500
15
30
NSX630L/500
20
40
NSX630F/630
8
14
NSX630N/630
10
17
NSX630H/630
10
17
NSX630S/630
15
30
NSX630L/630
20
40
315
100
220
160
100
220
225/355
100/50
220/105
160 and 100M160
80
176
250 and 200M250
80
176
250
100
220
160
100
220
200
100
220
315
100
220
200
100
220
225/355
100/50
220/105
200 and 100M200
80
176
250 and 200M250
80
176
250
100
220
200
100
220
200
100
220
630
50
105
250
100
220
630
50
105
250 and 200M250
80
176
355 and 315M355
80
176
630
50
105
250
100
220
630
50
105
630
50
105
315
100
220
630
50
105
315 and 200M250
80
176
355 and 315M355
80
176
630
50
105
315
100
220
630
50
105
630
50
105
400
100
220
630
50
105
400
80
176
450 and 400M450
80
176
630
50
105
400
100
220
630
50
105
630
50
105
500
100
220
500/630
100/50
220/105
450 and 400M450
80
176
450 and 400M450
80
176
630
50
105
500
100
220
500/630
100/50
220/105
213
04/11/2009 16:02:09
Complementary
technical information
Protection of switchdisconnectors
By Compact NS
By circuit breaker 380/415 V
By circuit breaker
440/480 V (1)
By circuit breaker
500/525 V
By circuit breaker
690 V
By Masterpact NT H1
By circuit breaker
220/690 V
By Masterpact NT H2
By circuit breaker
220/690 V
By Masterpact NT L1
By circuit breaker
220/525 V
By circuit breaker
690 V
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
214
04/11/2009 16:02:11
Complementary
technical information
Protection of switchdisconnectors
INS/INV800
INS/INV1000
INS/INV1250
INS/INV1600
INS/INV2000
INS/INV2500
NS630bN/630
35
75
NS630bH/630
35
75
NS630bL/630
150
330
NS630bN/630
35
75
NS630bH/630
35
75
NS630bL/630
130
286
NS630bN/630
35
75
NS630bH/630
35
75
NS630bL/630
100
220
NS630bN/630
30
63
NS630bH/630
35
75
NS630bL/630
25
53
NS800N/800
35
75
NS800H/800
35
75
NS800L/800
150
330
NS800N/800
35
75
NS800H/800
35
75
NS800L/800
130
286
NS800N/800
35
75
NS800H/800
35
75
NS800L/800
100
220
NS800N/800
30
63
NS800H/800
35
75
NS800L/800
25
53
NS1000N/1000
35
75
NS1000H/1000
35
75
NS1000L/1000
150
330
NS1000N/1000
35
75
NS1000H/1000
35
75
NS1000L/1000
130
286
NS1000N/1000
35
75
NS1000H/1000
35
75
NS1000L/1000
100
220
NS1000N/1000
30
63
NS1000H/1000
35
75
NS1000L/1000
25
53
NS1250N/1250
35
75
NS1250H/1250
35
75
-
NS1600N - NS1600bN/1600
35
75
NS1600H - NS1600bH/1600
35
75
-
NS2000N/2000
50
105
NS2000H/2000
50
105
-
NS2500N/2500
50
105
NS2500H/2500
50
105
-
NS1250N/1250
35
75
NS1250H/1250
35
75
-
NS1600N - NS1600bN/1600
35
75
NS1600H - NS1600bH/1600
35
75
-
NS2000N/2000
50
105
NS2000H/2000
50
105
-
NS2500N/2500
50
105
NS2500H/2500
50
105
-
NS1250N/1250
35
75
NS1250H/1250
35
75
-
NS1600N - NS1600bN/1600
35
75
NS1600H - NS1600bH/1600
35
75
-
NS2000N/2000
50
105
NS2000H/2000
50
105
-
NS2500N/2500
50
105
NS2500H/2500
50
105
-
NS1250N/1250
30
63
NS1250H/1250
35
75
-
NS1600bN/1600
30
63
NS1600bH/1600
35
75
-
NS2000N/2000
50
105
NS2000H/2000
50
105
-
NS2500N/2500
50
105
NS2500H/2500
50
105
-
NT06H1/630
35
75
NT08H1/800
35
75
NT10H1/1000
35
75
NT12H1/1250
35
75
NT16H1/1600
35
75
NT06H2/630
35
75
NT08H2/800
35
75
NT10H2/1000
35
75
NT12H2/1250
35
75
NT16H2/1600
35
75
NT06L1/630
100
220
NT06L1/630
25
53
NT08L1/800
100
220
NT08L1/800
25
53
NT10L1/1000
100
220
NT10L1/1000
25
53
NT12L1/1250
100
220
NT12L1/1250
25
53
NT16L1/1600
100
220
NT16L1/1600
25
53
215
04/11/2009 16:02:11
Complementary
technical information
Protection of switchdisconnectors
INS/INV630b to INS/INV2500 by
Masterpact NW circuit breakers
DB125669
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
kA rms
kA peak
216
558E4800.indd 216
20/11/2009 14:31:25
Protection of switchdisconnectors
Complementary
technical information
INS/INV630b to INS/INV2500 by
Masterpact NW circuit breakers
INS/INV630b
INS/INV800
INS/INV1000
INS/INV1250
INS/INV1600
INS/INV2000
INS/INV2500
NW08N1/630
35
75
NW08H1/630
35
75
NW08H2/630
35
75
-
NW08N1/800
35
75
NW08H1/800
35
75
NW08H2/800
35
75
-
NW10N1/1000
35
75
NW10H1/1000
35
75
NW10H2/1000
35
75
-
NW12N1/1250
35
75
NW12H1/1250
35
75
NW12H2/1250
35
75
-
NW16N1/1600
35
75
NW16H1/1600
35
75
NW16H2/1600
35
75
-
NW08N1/630
35
75
NW08H1/630
35
75
NW08H2/630
35
75
-
NW08N1/800
35
75
NW08H1/800
35
75
NW08H2/800
35
75
-
NW10N1/1000
35
75
NW10H1/1000
35
75
NW10H2/1000
35
75
-
NW12N1/1250
35
75
NW12H1/1250
35
75
NW12H2/1250
35
75
-
NW16N1/1600
35
75
NW16H1/1600
35
75
NW16H2/1600
35
75
-
NW20H1/2000
50
105
NW20H2/2000
50
105
NW20H3/2000
50
105
-
NW25H1/2500
50
105
NW25H2/2500
50
105
NW25H3/2500
50
105
-
NW08N1/630
35
75
NW08H1/630
35
75
NW08H2/630
35
75
-
NW08N1/800
35
75
NW08H1/800
35
75
NW08H2/800
35
75
-
NW10N1/1000
35
75
NW10H1/1000
35
75
NW10H2/1000
35
75
-
NW12N1/1250
35
75
NW12H1/1250
35
75
NW12H2/1250
35
75
-
NW16N1/1600
35
75
NW16H1/1600
35
75
NW16H2/1600
35
75
-
NW20H1/2000
50
105
NW20H2/2000
50
105
NW20H3/2000
50
105
-
NW25H1/2500
50
105
NW25H2/2500
50
105
NW25H3/2500
50
105
-
NW20H1/2000
50
105
NW20H2/2000
50
105
NW20H3/2000
50
105
NW25H1/2500
50
105
NW25H2/2500
50
105
NW25H3/2500
50
105
NW08L1/630
35
75
NW08L1/800
35
75
NW10L1/1000
35
75
NW12L1/1250
35
75
NW16L1/1600
35
75
NW20L1/2000
50
105
1000/1250
100
220
500
100
220
1000/1250
80/50
176/105
500
80
176
1000/1250
80/50
176/105
1000/1250
100
220
500
100
220
1000/1250
80/50
176/105
1000/1250
100
220
630
100
220
1000/1250
80/50
176/105
630
80
176
1000/1250
80/50
176/105
1000/1250
100
220
630
100
220
1000/1250
80/50
176/105
1000/1250
100
220
800
100
220
1000/1250
80/50
176/105
800
80
176
1000/1250
80/50
176/105
1000/1250
100
220
800
100
220
1000/1250
80/50
176/105
1000/1250
100
220
1000
80
176
1000/1250
80/50
176/105
1000
80
176
1000/1250
80/50
176/105
1000/1250
100
220
1000
80
176
1000/1250
80/50
176/105
1000/1250
100
220
1000/1250
80/50
176/105
1000/1250
80/50
176/105
1000/1250
80/50
176/105
1000/1250
80/50
176/105
1000/1250
100
220
1000/1250
80/50
176/105
1000/1250
80/50
176/105
217
558E4800.indd 217
20/11/2009 14:31:26
Complementary
technical information
Protection of switchdisconnectors
DB115722
By fuse 500 V
By fuse 500 V
INS40
INS63
INS80
125
100
220
32
100
220
100
100
220
32
80
176
125 & 100M125
80
176
125
100
220
50
100
220
100
100
220
50 & 32M50
80
176
125 & 100M125
80
176
125
100
220
63
100
220
100
100
220
63 & 32M63
80
176
125 & 100M125
80
176
INS/INV400
INS/INV500
INS/INV630
800
100
220
315
100
220
630
50
105
315 & 200M315
80
176
355 & 315M355
80
176
800
100
220
315
100
220
630
50
105
800
100
220
400
100
220
630
50
105
400
80
176
450 & 400M450
80
176
800
100
220
400
100
220
630
50
105
800
100
220
500
100
220
500/630
100/50
220/105
500
80
176
450 & 400M450
80
176
800
100
220
500
100
220
500/630
100/50
220/105
218
04/11/2009 16:02:16
Protection of switchdisconnectors
Complementary
technical information
INS125
INS160
INS250-100
INV100
INS250-160
INV160
INS250-200
INV200
INS/INV250
INS/INV320
200
100
220
80
100
220
125/160
100/50
220/105
80 & 63M80
80
176
160 & 100M160
80
176
200
100
220
100
100
220
125/160
100/50
220/105
100 & 63M100
80
176
160 & 100M160
80
176
200
100
220
125
100
220
125/160
100/50
220/105
125 & 100M125
80
176
160 & 100M160
80
176
315
100
220
80
100
220
225/355
100/50
220/105
80 & 63M80
80
176
250 & 200M250
80
176
315
100
220
125
100
220
225/355
100/50
220/105
125 & 100M125
80
176
250 & 200M250
80
176
315
100
220
160
100
220
225/355
100/50
220/105
160 & 100M160
80
176
250 & 200M250
80
176
315
100
220
200
100
220
225/355
100/50
220/105
200 & 100M200
80
176
250 & 200M250
80
176
800
100
220
250
100
220
630
50
105
250 & 200M250
80
176
355 & 315M355
80
176
INS/INV630b
INS/INV800
INS/INV1000
INS/INV1250
INS/INV1600
INS/INV2000
INS/INV2500
1000/1250
100
220
500
100
220
1000/1250
80/50
176/105
500
80
176
1000/1250
80/50
176/105
1000/1250
100
220
500
100
220
1000/1250
80/50
176/105
1000/1250
100
220
630
100
220
1000/1250
80/50
176/105
630
80
176
1000/1250
80/50
176/105
1000/1250
100
220
630
100
220
1000/1250
80/50
176/105
1000/1250
100
220
800
100
220
1000/1250
80/50
176/105
800
80
176
1000/1250
80/50
176/105
1000/1250
100
220
800
100
220
1000/1250
80/50
176/105
1000/1250
100
220
1000
80
176
1000/1250
80/50
176/105
1000
80
176
1000/1250
80/50
176/105
1000/1250
100
220
1000
80
176
1000/1250
80/50
176/105
1000/1250
100
220
1000/1250
80/50
176/105
1000/1250
80/50
176/105
1000/1250
80/50
176/105
1000/1250
80/50
176/105
1000/1250
100
220
1000/1250
80/50
176/105
1000/1250
80/50
176/105
219
04/11/2009 16:02:20
220
04/11/2009 16:02:20
Protection of LV/LV
transformers and capacitors
Complementary
technical information
DB115215
Inrush currents
When LV/LV transformers are switched on, very high inrush currents are produced
which must be taken into account when choosing overcurrent protection devices.
The peak value of the first current wave often reaches 10 to 15 times the rated rms
current of the transformer and may reach values of 20 to 25 times the rated current
even for transformers rated less than 50 kVA.
DB103945
230/240 V 3-phases
400/415 V 1-phase
5 to 6
8 to 9
13 to 16
20 to 25
26 to 32
32 to 40
40 to 50
51 to 64
64 to 80
400/415 V 3-phases
Circuit breakers
Trip unit
Ir max setting
9 to 12
14 to 16
22 to 28
35 to 44
45 to 56
55 to 69
69 to 87
89 to 111
111 to 139
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX100B/F/N/H/S/L
NSX160B/F/N/H/S/L
NSX160B/F/N/H/S/L
NSX250B/F/N/H/S/L
NSX250B/F/N/H/S/L
TM16D
TM25D
TM40D
TM63D
TM80D
TM100D
TM125D
TM160D
TM200D
1
1
1
1
1
1
1
1
1
Compact NSX100 to NS1600 / Masterpact equipped with STR and Micrologic trip unit
Transformer rating (kVA)
230/240 V 1-phase
Protective device
230/240 V 3-phases
400/415 V 3-phases
Circuit breakers
Trip unit
Ir max setting
400/415 V 1-phase
4 to 7
6 to 13
11 to 22
NSX100B/F/N/H/S/L
Micrologic 2.2 or 6.2 40
0.8
9 to 19
16 to 30
27 to 56
NSX100B/F/N/H/S/L
Micrologic 2.2 or 6.2 100 0.8
15 to 30
05 to 50
44 to 90
NSX160B/F/N/H/S/L
Micrologic 2.2 or 6.2 160 0.8
23 to 46
40 to 80
70 to 139
NSX250B/F/N/H/S/L
Micrologic 2.2 or 6.2 250 0.8
37 to 65
64 to 112
111 to 195
NSX400F/N/H/S
Micrologic 2.3 or 6.3 400 0.7
37 to 55
64 to 95
111 to 166
NSX400L
Micrologic 2.3 or 6.3 400 0.6
58 to 83
100 to 144
175 to 250
NSX630F/N/H/S/L
Micrologic 2.3 or 6.3 630 0.6
58 to 150
100 to 250
175 to 436
NS630bN/bH-NT06H1
Micrologic 5.0/6.0/7.0
1
74 to 184
107 to 319
222 to 554
NS800N/H-NT08H1-NW08N1/H1
Micrologic 5.0/6.0/7.0
1
90 to 230
159 to 398
277 to 693
NS1000N/H-NT10H1-NW10N1/H1 Micrologic 5.0/6.0/7.0
1
115 to 288
200 to 498
346 to 866
NS1250N/H-NT12H1-NW12N1/H1 Micrologic 5.0/6.0/7.0
1
147 to 368
256 to 640
443 to 1108
NS1600N/H-NT16H1-NW16N1/H1 Micrologic 5.0/6.0/7.0
1
184 to 460
320 to 800
554 to 1385
NW20N1/H1
Micrologic 5.0/6.0/7.0
1
230 to 575
400 to 1000
690 to 1730
NW25H2/H3
Micrologic 5.0/6.0/7.0
1
294 to 736
510 to 1280
886 to 2217
NW32H2/H3
Micrologic 5.0/6.0/7.0
1
(1) For other windings, please consult us.
If a circuit breaker upstream of a transformer with a transformation ratio of 1 and a rated power of less than 5 kVA is subject to nuisance tripping, before choosing a
circuit breaker with a higher rating, invert the input and the output of the transformer (the inrush current may be doubled if the primary is wound internally rather than
externally).
221
558E4600.indd 221
20/11/2009 14:32:29
Complementary
technical information
Protection of LV/LV
transformers and capacitors
DB115216
Protection of capacitors
056639
Capacitor-bank protection.
10 kVAR
20 kVAR
30 kVAR
50 kVAR
60 kVAR
80 kVAR
105 kVAR
150 kVAR
210 kVAR
315 kVAR
690 V
Capacitor (kVAR)
10 kVAR
20 kVAR
30 kVAR
50 kVAR
60 kVAR
80 kVAR
105 kVAR
150 kVAR
210 kVAR
315 kVAR
405 kVAR
450 kVAR
495 kVAR
540 kVAR
gG fuse-link rating
Fupact
20 A
40 A
63 A
100 A
125 A
160 A
250 A
315 A
450 A
670 A
INFp32 / INFD40
INFp63 / INFD40
INFp63
INFp125
INFp125
INFp250
INFp250
INFp400
INFp630
INFp800
gG fuse-link rating
Fupact
16 A
32 A
40 A
63 A
80 A
100 A
125 A
200 A
250 A
400 A
500 A
560 A
630 A
670 A
INFp32 / INFD40
INFp32 / INFD40
INFp63 / INFD40
INFp63
INFp125
INFp125
INFp160
INFp250
INFp400
INFp400
INFp630
INFp630
INFp800
INFp800
222
04/11/2009 16:02:24
Complementary
technical information
The circuit breaker used to protect a distribution circuit is chosen according to two
fundamental criteria:
b the maximum load current Ib flowing in the supply circuit
b the prospective short-circuit current Isc at a point where the circuit breaker is to be
installed.
The circuit breaker is choosen such that:
v In circuit breaker u Ib
v breaking capacity of the circuit breaker u Isc.
DB115207
DB115937
223
04/11/2009 16:02:25
Complementary
technical information
Example
Consider two 630 kVA/400 V transformer (Usc 4 %) supplying a main LV switchboard
for which the prospective short-circuit current on the busbars is 44 kA.
From the switchboard, a 30-metre long Canalis KVA63 transmission electrical
busbar trunking system (630 A) supplies a Canalis KSA63 trunking system (630A)
for distribution with high-density tap-offs.
A tap-off on the KSA63 trunking supplies a Canalis KSA16 trunking system.
The short-circuit level are respectively:
b 44 kA downstream of circuit-breaker CB1 and at the upstream connection of the
KVA63 trunking
b 33 kA at the junction between the KVA63 transmission trunking and the KSA63
trunking for high-density tap-offs.
What circuit breakers should be chosen for CB1 and CB2 to protect the
installation against short-circuits?
Prospective Isc
Circuit breakers
CB2
33 kA
NSX160F
(36 kA breaking capacity)
50 kA
50 kA
35 kA
35 kA
DB115208
CB1
44 kA
NSX630N
(50 kA breaking capacity)
224
04/11/2009 16:02:26
Complementary
technical information
Voltage: 220/240 V
Type of Canalis busbar trunking KDP20
Isc max. in kA rms
Type of circuit breaker
Isc max. in kA rms
C60
NG
10 kA
15 kA
C60N 10/16/20
C60H 10/16/20
NG125N 10/16/20
20 kA
C60L 10/16/20
C60
NG
10 kA
15 kA
C60N 10/.../25
C60H 10/.../25
NG125N 10/.../25
20 kA
25 kA
C60L 10/.../25
C60
NG
10 kA
15 kA
C60N 10/.../25
C60H 10/.../25
NG125N 10/.../25
20 kA
25 kA
C60L 10/.../25
C60
NG
10 kA
C60N 10/.../40
20 kA
25 kA
C60L 40
C60L 10/.../25
NG125N 10/.../40
50 kA
C60
NG
20 kA
25 kA
C60L 40
C60L 10/.../25
NG125N 10/.../40
50 kA
10 kA
C60N 10/.../40
15 kA
C60H 10/.../40
15 kA
C60H 10/.../40
NG125L 10/.../40
NG125L 10/.../40
225
04/11/2009 16:02:26
Complementary
technical information
C60
NG125
10 kA
15 kA
20 kA
C60N10/16/20
C60H10/16/20 C60L10/16/20
NG125N10/16/20
C60
NG125
10 kA
C60N10/.../25
NG125N10/.../25
15 kA
C60H10/.../25
20 kA
C60L10/.../25
25 kA
C60L10/.../25
15 kA
C60H10/.../25
20 kA
C60L10/.../25
25 kA
C60L10/.../25
15 kA
C60H10/.../40
20 kA
C60L40
NG125N10/.../40
25 kA
C60L10/.../25
20 kA
C60L40
NG125N10/.../40
25 kA
C60L10/.../25
20 kA
25 kA
C60L40
C60
NG125
10 kA
C60N10/.../25
NG125N10/.../25
C60
NG125
10 kA
C60N10/.../40
36 kA
50 kA
NG125H10/.../40
NG125L10/.../40
36 kA
50 kA
NG125H10/.../40
NG125L10/.../40
C60
NG125
10 kA
C60N10/.../40
15 kA
C60H10/.../40
C60
NG125
Compact NSX
10 kA
C60N40
NG125N10//40
15 kA
C60H40
NSX100B/F/N/H/S/L 40A
C60
C120
NG125
Compact NSX
10 kA
C60N63
C120N
15 kA
C60H63
C120H
20 kA
25 kA
C60H63
36 kA
NG125N 63
NG125H 63
NSX100B/F/N/H/S/L
50 kA
NG125L 63
C60
NG125
Compact NSX
10 kA
C120N
15 kA
C120H
20 kA
25 kA
NG125N 100
NSX100B/F/N/H/S/L NSX100B/F/N/H/S/L
NSX160B/F/N/H/S/L NSX160B/F/N/H/S/L
NG125
Compact NSX
10 kA
NG125N125
15 kA
NG125N125
20 kA
NG125N125
25 kA
NG125N125
NSX100B/F/N/H/S/L
NSX160B/F/N/H/S/L
NSX250B/F/N/H/S/L
36 kA
50 kA
NSX100F/N/H/S/L NSX100N/H/S/L
NSX160F/N/H/S/L NSX160N/H/S/L
NSX250F/N/H/S/L NSX250N/H/S/L
226
04/11/2009 16:02:27
Complementary
technical information
Voltage: 380/415 V
Type of Canalis busbar trunking KSA100
Isc max kA rms
Type of circuit breaker NG125
Compact NSX
25 kA
NG125N 100
NSX100B/F/N/H/S/L
36 kA
25 kA
NSX100B/F/N/H/S/L
NSX160B/F/N/H/S/L
NSX250B/F/N/H/S/L
36 kA
NSX100F/N/H/S/L
NSX160F/N/H/S/L
NSX250F/N/H/S/L
50 kA
70 kA
NSX100N/H/S/L NSX100H/S/L
NSX160N/H/S/L NSX160H/S/L
NSX250N/H/S/L
90 kA
NSX100S/L
36 kA
NSX160F/N/H/S/L
NSX250F/N/H/S/L
NSX400F/N/H/S/L
50 kA
70 kA
NSX160N/H/S/L NSX160H/S/L
NSX250N/H/S/L NSX250H/S/L
NSX400N/H/S/L
100 kA
NSX160S/L
NSX250S/L
150 kA
NSX160L
NSX250L
36 kA
NSX250F/N/H/S/L
NSX400F/N/H/S/L
NSX630F/N/H/S/L
NS630b L / LB
50 kA
NSX250N/H/S/L
NSX400N/H/S/L
NSX630N/H/S/L
NS630b L / LB
70 kA
NSX250H/S/L
NSX400H/S/L
NSX630H/S/L
NS630b LB
100 kA
NSX250S/L
NSX400S/L
NSX630S/L
150 kA
NSX250L
NSX400L
NSX630L
36 kA
NSX400F
NSX630F
NS630b N
50 kA
NSX400N
NSX630N
NS630b L / LB
70 kA
NSX400H
NSX630H
NS630b LB
100 kA
NSX400S
NSX630S
NS630b LB
150 kA
NSX400L
NSX630L
36 kA
NSX400F
NSX630F
NS630b L
NS800L
NT06L1
NT08L1
50 kA
NSX400N
NSX630N
NS630b L
NS800L
NT06L1
NT08L1
70 kA
NSX400H
NSX630H
NS630bL
NS800L
NT06L1
NT08L1
100 kA
NSX400S
NSX630S
NS630bL
NS800L
NT06L1
NT08L1
150 kA
NSX400L
NSX630L
NS630b LB
NS800LB
36 kA
NSX630F
NS630bN
NS800N
NS1000N
NT06H1
NT08H1
NT10H1
50 kA
NSX630N
NS630bL
NS800L
NS1000L
NT06L1
NT08L1
NT10L1
70 kA
NSX630H
NS630bL
NS800L
NS1000L
NT06L1
NT08L1
NT10L1
100 kA
NSX630S
NS630bL
NS800L
NS1000L
NT06L1
NT08L1
NT10L1
150 kA
NSX630L
NS630bL
NS800L
NS1000L
NT06L1
NT08L1
NT10L1
36 kA
NS800N
NS1000N
NS1250N
NT08H1
NT10H1
NT12H1
50 kA
NS800L
NS1000L
70 kA
NS800L
NS1000L
100 kA
NS800L
NS1000L
150 kA
NS800L
NS1000L
NT08L1
NT10L1
NT12L1
NT08L1
NT10L1
NT12L1
NT08L1
NT10L1
NT12L1
NT08L1
NT10L1
NT12L1
25 kA
NSX160B/F/N/H/S/L
NSX250B/F/N/H/S/L
NSX400F/N/H/S/L
Compact NS
25 kA
NSX250B/F/N/H/S/L
NSX400F/N/H/S/L
NSX630F/N/H/S/L
NS630b N/H/L/LB
25 kA
NSX400F
NSX630F
NS630b N
y 32 kA
NSX400F
NSX630F
NS630b N
NS800N
NT06H1
NT08H1
Masterpact NT
Masterpact NT
227
04/11/2009 16:02:28
Complementary
technical information
Voltage: 380/415 V
Type of Canalis busbar trunking KTA0800
Isc max kA rms
Type of circuit breaker Compact NSX
Compact NSX
Masterpact NT
Masterpact NW
y 30 kA
50 kA
NSX630F (->36kA) NSX630N/H/S/L
NS630bN
NS800N
NS1000N
NT06 H1
NT08 H1
NT10 H1
NW08H1
NW10H1
65 kA
NSX630H/S/L
NS630bL
NS800L
NS1000L
85 kA
NSX630S/L
100 kA
NSX630L
150 kA
NSX630L
NS630bLB
NS800LB
100 kA
NSX630L
150 kA
NSX630L
NS630bLB
NS800LB
NT06 L1
NT08 L1
NT10 L1
Masterpact NT
Masterpact NW
y 30 kA
50 kA
NSX630F (->36kA) NSX630N/H/S/L
NS630bN
NS800N
NS1000N
NT06 H1
NT08 H1
NT10 H1
NW08H1
NW10H1
65 kA
NSX630H/S/L
NS630bL
NS800L
NS1000L
85 kA
NSX630S/L
NT06 L1
NT08 L1
NT10 L1
Masterpact NT
Masterpact NW
42 kA
NT08H1
NT10H1
NT12H1
NW08N1
NW10N1
NW12N1
50 kA
NS800N
NS1000N
NS1250N
NT08H2
NT10H2
NT12H2
NW08H1
NW10H1
NW12H1
65 kA
85 kA
100 kA
150 kA
NS800L
NS1000L
NT08L1
NT10L1
Masterpact NT
Masterpact NW
42 kA
50 kA
NS800N
NS1000N
NT08H1
NT10H1
NT12H1
NW08N1
NW10N1
NW12N1
NT08H2
NT10H2
NT12H2
65 kA
NS800H
NS1000H
NS1250H
85 kA
100 kA
150 kA
NS800L
NS1000L
NT08L1
NT10L1
NW08H1
NW10H1
NW12H1
NW08L1
NW10L1
NW12L1
65 kA
NS1000L
85 kA
NS1000L
100 kA
NS1000L
150 kA
NS1000L
NT10L1
NT10L1
NT10L1
NT10L1
65 kA
NS1000H
NS1250H
NS1600H
85 kA
100 kA
150 kA
NS1000L
Masterpact NT
Masterpact NW
42 kA
NT10H1
NT12H1
NT16H1
NW10N1
NW12N1
NW16N1
50 kA
NS1000N
NS1250N
NS1600N
NT10H2
NT12H2
NT16H2
NW10H1
NW12H1
NW16H1
Masterpact NT
Masterpact NW
42 kA
NT10H1
NT12H1
NT16H1
NW10N1
NW12N1
NW16N1
50 kA
NS1000N
NS1250N
NS1600N
NT10H2
NT12H2
NT16H2
NW10H1
NW12H1
NW16H1
NT10L1
NW10H1
NW12H1
NW16H1
NW10L1
NW12L1
NW16L1
65 kA
NS1250H
NS1600H
NS1600bN
NS2000N
85 kA
Masterpact NT
Masterpact NW
42 kA
50 kA
NS1250N
NS1600N
NT12H1
NT16H1
NW12N1
NW16N1
NW20H1
NT12H2
NT16H2
NW12H1
NW16H1
NW20H1
100 kA
150 kA
NW12L1
NW16L1
NW20L1
228
04/11/2009 16:02:29
Complementary
technical information
Voltage: 380/415 V
Type of Canalis busbar trunking KTA1600 PER/ KTC1600 PER
Isc max kA rms
Type of circuit breaker Compact NS
Masterpact NT
Masterpact NW
42 kA
NT12H1
NT16H1
NW12N1
NW16N1
NW20H1
50 kA
NS1250N
65 kA
NS1250H
NS1600H
NS1600bN
NS2000N
85 kA
100 kA
150 kA
NS1600bH
NS2000H
NT12H2
NT16H2
NW1H1
NW16H1
NW20H1
NW12L1
NW16L1
NW20L1
42 kA
50 kA
NT16H1
NW16N1
NW20H1
NW25H1
NT16H2
65 kA
NS1600bN
NS2000N
85 kA
NW16H1
NW20H1
NW25H1
100 kA
150 kA
NW 16 L1
NW20L1
42 kA
50 kA
NT16H1
NW16N1
NW20H1
NW25H1
NT16H2
65 kA
NS1600bN
NS2000N
85 kA
NS1600bH
NS2000H
NW16H1
NW20H1
NW25H1
100 kA
150 kA
NW16H2
NW20H2
NW25H2
NW16L1
NW20L1
65 kA
NW20H1
NW25H1
NW32H1
80 kA
NW20H2
NW25H2
NW32H2
100 kA
NW20L1
150 kA
NW20L1
65 kA
NW20H1
NW25H1
NW32H1
80 kA
100 kA
NW20H2
NW25H2
NW32H2
110 kA
NW20L1
NW25H3
NW32H3
65 kA
NW25H1
NW32H1
NW40H1
85 kA
NW25H2
NW32H2
NW40H2
NW40bH1
100 kA
110 kA
100 kA
NW25H2
NW32H2
NW40H2
NW40bH1
110 kA
NW32H3
NW40H3
NW40bH2
100 kA
110 kA
65 kA
NW32H1
NW40H1
NW40bH1
NW50H1
100 kA
NW32H2
NW40H2
NW40bH1
NW50H1
110 kA
NW32H3
NW40H3
NW40bH2
NW50H2
65 kA
NW40H1
95 kA
NW40H2
NW40bH1
NW50H1
NW63H1
65 kA
NW40H1
NW40bH1
NW50H1
NW63H1
95 kA
NW40H2
NW40bH1
NW50H1
NW63H1
65 kA
NW25H1
NW32H1
NW40H1
65 kA
NW32H1
NW40H1
NW40bH1
NW50H1
90 kA
NW32H2
NW40H2
NW40bH1
NW50H1
120 kA
NW40H3
NW40bH2
NW50H2
NW63H2
229
04/11/2009 16:02:30
Complementary
technical information
Voltage: 660/690 V
Type of Canalis busbar trunking KSA100
Isc max kA rms
Type of circuit breaker Compact NSX
10 kA
NSX100N/H/S/L
NSX160N/H/S/L
NSX250N/H/S/L
15 kA
NSX100S/L
NSX160S/L
NSX250S/L
20 kA
NSX100L
75 kA
Compact NS
NS100L
10 kA
NSX100N/H/S/L
NSX160N/H/S/L
NSX250N/H/S/L
15 kA
NSX100S/L
NSX160S/L
NSX250S/L
20 kA
NSX100L
NSX160L
NSX250L
75 kA
Compact NS
NS100L
10 kA
NSX160N/H/S/L
NSX250N/H/S/L
NSX400F/N/H/S/L
15 kA
NSX160S/L
NSX250S/L
NSX400H/S/L
20 kA
NSX160L
NSX250L
NSX400/S/L
35 kA
75 kA
NSX400L
Compact NS
NS400L
10 kA
15 kA
NSX250N/H/S/L NSX250S/L
NSX400F/N/H/S/L
NSX630F/N/H/S/L
20 kA
NSX250L
NSX400H/S/L
NSX630H/S/L
35 kA
75 kA
NSX400L
NSX630L
Compact NS
NS400L
NS630bLB
NS630bN
10 kA
15 kA
NSX400F/N/H/S/L
NSX630F/N/H/S/L
20 kA
NSX400H/S/L
NSX630H/S/L
25 kA
35 kA
NSX400L
NSX630L
Compact NS
75 kA
NS400L
NS630bLB
NS800LB
NS630bN
NS800N
10 kA
15 kA
NSX400F/N/H/S/L NSX400H/S/L
NSX630F/N/H/S/L NSX630H/S/L
20 kA
NSX400/S/L
NSX630/S/L
30 kA
35 kA
NSX400L
NSX630L
NS630bN
NS800N
NS630bH
NS800H
NS400L
NS630bLB
NS800LB
30 kA
35 kA
75 kA
NS630bN
NS800N
NS1000N
NS630bH
NS800H
NS1000H
NS630bLB
NS800LB
30 kA
NS800N
NS1000N
NS1250N
35 kA
NS800H
NS1000H
NS1250H
NT08H1/H2
NT10H1/H2
NT12H1/H2
NW08N1
NW10N1
NW12N1
75 kA
NS800LB
Compact NS
75 kA
10 kA
15 kA
NSX630F/N/H/S/L NSX630H/S/L
20 kA
NSX630/S/L
Masterpact NT
Masterpact NW
10 kA
15 kA
20 kA
230
04/11/2009 16:02:31
Complementary
technical information
Voltage: 660/690 V
Type of Canalis busbar trunking KTA1000 / KTC1000
Isc max kA rms
Type of circuit breaker Compact NS
30 kA
NS800N
NS1000N
NS1250N
Masterpact NT
Masterpact NW
42 kA
NS800H
NS1000H
NS1250H
NT08H1/H2
NT10H1/H2
NT12H1/H2
NW08N1
NW10N1
NW12N1
50 kA
65 kA
75 kA
NS800LB
100 kA
65 kA
75 kA
NS800LB
100 kA
65 kA
75 kA
100 kA
50 kA
65 kA
75 kA
100 kA
NS1600bN
NS1600bN
NW10H1
NW12H1
NW16H1
NW10H1
NW12H1
NW16H1
NW10L1
NW12L1
NW16L1
50 kA
65 kA
75 kA
NW08H1
NW10H1
NW12H1
30 kA
NS800N
NS1000N
NS1250N
Masterpact NT
Masterpact NW
42 kA
NS800H
NS1000H
NS1250H
NT08H1/H2
NT10H1/H2
NT12H1/H2
NW08N1
NW10N1
NW12N1
50 kA
NW08H1
NW10H1
NW12H1
30 kA
NS1000N
NS1250N
NS1600N
42 kA
NS1000H
NS1250H
NS1600H
50 kA
NS1600bN
Masterpact NT
NT10H1/H2
NT12H1/H2
NT16H1/H2
NW10N1
NW12N1
NW16N1
Masterpact NW
NW10H1
NW12H1
NW16H1
30 kA
NS1000N
NS1250N
NS1600N
Masterpact NT
42 kA
NS1000H
NS1250H
NS1600H
NT10H1/H2
NT12H1/H2
NT16H1/H2
NW10N1
NW12N1
NW16N1
Masterpact NW
30 kA
NS1250N
NS1600N
42 kA
NS1250H
NS1600H
100 kA
NS1600bN
NS2000N
Masterpact NT
NT12H1/H2
NT16H1/H2
NW12N1
NW16N1
Masterpact NW
NW12H1
NW16H1
NW20H1
NW12L1
NW16L1
NW20 L1
65 kA
75 kA
100 kA
NW12H2
NW16H2
NW20H2
NW12L1
NW16L1
NW20L1
30 kA
NS1250N
NS1600N
42 kA
NS1250H
NS1600H
50 kA
NS1600bN
NS2000N
Masterpact NT
Masterpact NW
NT12H1/H2
NT16H1/H2
NW12N1
NW16N1
NW12H1
NW16H1
NW20H1
231
04/11/2009 16:02:31
Complementary
technical information
Voltage: 660/690 V
Type of Canalis busbar trunking KTA2000 / KTC2000
30 kA
NS1600N
42 kA
NS1600H
50 kA
65 kA
75 kA
100 kA
NS1600bN
NS2000N
NS2500N
Masterpact NT
Masterpact NW
NT16H1/H2
NW16N1
30 kA
NS1600N
42 kA
NS1600H
NW16H1
NW20H1
NW25H1
50 kA
65 kA
NW16L1
NW20L1
75 kA
100 kA
NW16H1
NW20H1
NW25H1
NW16H2
NW20H2
NW25H2
NW16L1
NW20H3
NW25H3
65 kA
NS2000N
NS2500N
NS3200N
80 kA
100 kA
NW20H1
NW25H1
NW32H1
NW20H2
NW25H2
NW32H2
NW20L1
65 kA
NS2000N
NS2500N
NS3200N
80 kA
100 kA
NW20H1
NW25H1
NW32H1
NW20H2
NW25H2
NW32H2
NW20H3
NW25H3
NW32H3
65 kA
NS2500N
NS3200N
NW25H1
NW32H1
NW40H1
85 kA
100 kA
NS1600bN
NS2000N
NS2500N
Masterpact NT
Masterpact NW
NT16H1/H2
NW16N1
30 kA
Masterpact NT
Masterpact NW
42 kA
NT16H1/H2
30 kA
Masterpact NT
Masterpact NW
42 kA
50 kA
NT16H1/H2
50 kA
30 kA
42 kA
50 kA
Masterpact NW
30 kA
42 kA
50 kA
Masterpact NW
30 kA
42 kA
30 kA
30 kA
30 kA
42 kA
50 kA
50 kA
65 kA
NS2500N
NS3200N
NW25H1
NW32H1
NW40H1
65 kA
NS3200N
NW32H1
NW40H1
NW25H2
NW32H2
NW40H2
NW40b H1/H2
85 kA
100 kA
NW25H2
NW32H2
NW40H2
NW25H3
NW32H3
NW40H3
NW40bH1/2
85 kA
100 kA
NW32H2
NW40H2
NW40bH1/H2
NW50 H1/H2
65 kA
NS3200N
NW32H1
NW40H1
85 kA
100 kA
NW32H2
NW40H2
NW32H3
NW40H3
NW40bH1/H2
NW50H1/H2
42 kA
50 kA
65 kA
NW40H1
85 kA
NW40H2
95 kA
NW40H3
NW40bH1/H2
NW50H1/H2
NW63H1/H2
42 kA
50 kA
65 kA
NW40H1
75 kA
NW40H2
100 kA
NW40H3
NW40bH1/H2
NW50H1/H2
NW63H1/H2
232
04/11/2009 16:02:32
Complementary
technical information
Cascading
The use of a current-limiting circuit breaker upstream to reinforce the breaking
capacity of a downstream circuit breaker.
Principle
DB115211
Cascading.
Cascading.
233
04/11/2009 16:02:34
Complementary
technical information
In the event of an electrical fault on one outgoing circuit, discrimination is the ability
of the electrical installation to maintain the continuity of electrical power supplied to
the other circuits not concerned by the fault.
As a general rule, cascading and discrimination techniques are applied
independently.
Schneider Electric has developed an exclusive system to conciliate cascading and
discrimination.
This system ensures discrimination up to the reinforced breaking capacity of the
association of circuit breakers CB1 and CB2.
Principle
DB115211
234
04/11/2009 16:02:34
Complementary
technical information
DB120574
Alimentation
NSX400N
Micrologic
KSA/KVA/KVC
315 and 400 A
45
NSX100F
NSX400H
Micrologic
KSA/KVA/KVC
315 and 400 A
70
Micrologic
KSA/KVA/KVC
315 and 400 A
150
NSX160F
NSX100H
KSA
160 A
KSA
100 A
KSA
160 A
70
70
150
150
45
70
70
150
150
45
70
70
70
70
NSX160F
NSX100N
TMD/Micrologic
KSA
100 A
KSA
160 A
TMD/
Micrologic
KSA
100 A
45
45
45
45
NSX400L
NSX160H
TMD/Micrologic
235
04/11/2009 16:02:36
Complementary
technical information
Voltage: 380/415 V
NS1600N
Micrologic 5.0
KTA-16/KTC-16
1600 A
50
NS1600N
Micrologic 5.0
KTA-16/KTC-16
1600 A
50
NSX100F
NSX160F
TMD/Micrologic
KSA
KSA
100 A
160 A
NSX250F
KSA
250 A
NSX400F
NSX630F
Micrologic
KSA/KVA/KVC
315-400 A
500-630 A
NSX100F
40 A
KN
40 A
TMD/Micrologic
63 A
100 A
KN
KN
63 A
100 A
50
50
50
45
40
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
NS1600N
Micrologic 5.0
KTA-16/KTC-16
1600 A
70
NS1600N
Micrologic 5.0
KTA-16/KTC-16
1600 A
70
NSX100F
NSX160F
TMD/Micrologic
KSA
KSA
100 A
160 A
NSX250F
KSA
250 A
NSX400F
NSX630F
Micrologic
KSA/KVA/KVC
315-400 A
500-630 A
NSX100F
40 A
KN
40 A
TMD/Micrologic
63 A
100 A
KN
KN
63 A
100 A
70
70
70
45
40
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
50
50
50
236
04/11/2009 16:02:39
Complementary
technical information
NS1250N
Micrologic 5.0
KTA-12/KTC-13
1200 and 1350 A
50
NS1250N
Micrologic 5.0
KTA-12/KTC-13
1200 and 1350 A
50
NSX100F
NSX160F
TMD/Micrologic
KSA
KSA
100 A
160 A
NSX250F
KSA
250 A
NSX400F
NSX630F
Micrologic
KSA/KVA/KVC
315-400 A
500-630 A
NSX100F
40 A
KN
40 A
TMD/Micrologic
63 A
100 A
KN
KN
63 A
100 A
50
50
50
45
40
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
NS1250H
Micrologic 5.0
KTA-12/KTC-13
1200 and 1350 A
70
NS1250H
Micrologic 5.0
KTA-12/KTC-13
1200 and 1350 A
70
NSX100N
NSX160N
TMD/Micrologic
KSA
KSA
100 A
160 A
NSX250N
KSA
250 A
NSX400N
NSX630N
Micrologic
KSA/KVA/KVC
315-400 A
500-630 A
NSX100N
40 A
KN
40 A
TMD/Micrologic
63 A
100 A
KN
KN
63 A
100 A
70
70
70
45
40
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
70
50
50
50
NS1000N
Micrologic 5.0
KTA-10/KTC-10
1000 A
50
NS1000N
Micrologic 5.0
KTA-10/KTC-10
1000 A
50
NSX100F
NSX160F
TMD/Micrologic
KSA
KSA
100 A
160 A
NSX250F
KSA
250 A
NSX400F
NSX630F
Micrologic
KSA/KVA/KVC
315-400 A
500-630 A
NSX100F
40 A
KN
40 A
TMD/Micrologic
63 A
100 A
KN
KN
63 A
100 A
50
50
50
45
40
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
NS1000H
Micrologic 5.0
KTA-10/KTC-10
1000 A
55
NS1000H
Micrologic 5.0
KTA-10/KTC-10
1000 A
55
NSX100N
NSX160N
TMD/Micrologic
KSA
KSA
100 A
160 A
NSX250N
KSA
250 A
NSX400N
NSX630N
Micrologic
KSA/KVA/KVC
315-400 A
500-630 A
NSX100N
40 A
KN
40 A
TMD/Micrologic
63 A
100 A
KN
KN
63 A
100 A
70
70
70
45
40
70
70
70
70
70
70
70
70
70
70
70
55
55
55
55
55
50
50
50
237
04/11/2009 16:02:40
Complementary
technical information
NS1000L
Micrologic 5.0
KTA-10/KTC-10
1000 A
150
NS1000L
Micrologic 5.0
KTA-10/KTC-10
1000 A
150
NSX100N
NSX160N
TMD/Micrologic
KSA
KSA
100 A
160 A
NSX250N
KSA
250 A
NSX400N
NSX630N
Micrologic
KSA/KVA/KVC
315-400 A
500-630 A
NSX100N
40 A
KN
40 A
TMD/Micrologic
63 A
100 A
KN
KN
63 A
100 A
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
150
50
70
150
150
150
50
50
50
NS800N
Micrologic 5.0
KVA-80/KVC-80
800 A
50
NS800N
Micrologic 5.0
KVA-80/KVC-80
800 A
50
NSX100F
NSX160F
TMD/Micrologic
KSA
KSA
100 A
160 A
NSX250F
KSA
250 A
NSX400F
NSX630F
Micrologic
KSA/KVA/KVC
315-400 A
NSX100F
40 A
KN
40 A
TMD/Micrologic
63 A
100 A
KN
KN
63 A
100 A
50
50
50
35
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
NS800H
Micrologic 5.0
KVA-80/KVC-80
800 A
60
NS800H
Micrologic 5.0
KVA-80/KVC-80
800 A
60
NSX100N
NSX160N
TMD/Micrologic
KSA
KSA
100 A
160 A
NSX250N
KSA
250 A
NSX400N
NSX630N
Micrologic
KSA/KVA/KVC
315-400 A
NSX100N
40 A
KN
40 A
TMD/Micrologic
63 A
100 A
KN
KN
63 A
100 A
70
70
70
35
70
70
70
70
70
70
70
70
70
70
60
60
60
60
50
50
50
NS800L
Micrologic 5.0
KVA-80/KVC-80
800 A
150
NS800L
Micrologic 5.0
KVA-80/KVC-80
800 A
150
NSX100N/H NSX160N/H
TMD/Micrologic
KSA
KSA
100 A
160 A
NSX250N/H
KSA
250 A
NSX400N/H
Micrologic
KSA/KVA/KVC
315-400 A
NSX100N
40 A
KN
40 A
TMD/Micrologic
63 A
100 A
KN
KN
63 A
100 A
150
150
150
150
150
150
150
150
150
150
150
150
150
150
50
70
150
150
50
50
50
238
04/11/2009 16:02:42
Complementary
technical information
NS630bN
Micrologic 5.0
KSA/KVA/KVC
630 A
20
NSX100F
NSX160F
TMD/Micrologic
KSA
KSA
100 A
160 A
50
NS630bH
Micrologic 5.0
KSA/KVA/KVC
630 A
29
NSX250F
KSA
250 A
NSX100N NSX160N
TMD/Micrologic
KSA
KSA
100 A
160 A
50
50
70
50
50
50
50
50
50
NS630bL
Micrologic 5.0
KSA/KVA/KVC
630 A
150
NSX250N
KSA
250 A
NSX100N NSX160N
TMD/Micrologic
KSA
KSA
100 A
160 A
NSX250N
KSA
250 A
70
70
150
150
150
70
70
70
150
150
150
60
70
70
50
70
150
NS630bN
Micrologic 5.0
KSA/KVA/KVC
630 A
29
NS630bH
Micrologic 5.0
KSA/KVA/KVC
630 A
29
NS630bL
Micrologic 5.0
KSA/KVA/KVC
630 A
150
NSX100F
TMD/Micrologic
KN
KN
40 A
63 A
KN
100 A
NSX100N
TMD/Micrologic
KN
KN
40 A
63 A
KN
100 A
NSX100N/H
TMD/Micrologic
KN
KN
40 A
63 A
KN
100 A
50
50
50
70
70
70
150
150
150
50
50
50
70
70
70
150
150
150
50
50
50
50
50
50
50
50
50
NSX630N
Micrologic
KSA/KVA/KVC
500 and 630 A
45
NSX100N NSX160N
TMD/Micrologic
KSA
KSA
100 A
160 A
45
NSX630H
Micrologic
KSA/KVA/KVC
500 and 630 A
70
NSX250N
KSA
250 A
NSX100N NSX160N
TMD/Micrologic
KSA
KSA
100 A
160 A
45
45
70
45
45
45
45
45
45
NSX630L
Micrologic
KSA/KVA/KVC
500 and 630 A
150
NXS250N
KSA
250 A
NSX100N NSX160N
TMD/Micrologic
KSA
KSA
100 A
160 A
NSX250N
KSA
250 A
70
70
150
150
150
70
70
70
150
150
150
70
70
70
70
70
70
NSX630N
Micrologic
KSA/KVA/KVC
500 and 630 A
45
NSX630H
Micrologic
KSA/KVA/KVC
500 and 630 A
70
NSX630L
Micrologic
KSA/KVA/KVC
500 and 630 A
150
NSX100N
TMD/Micrologic
KN
KN
40 A
63 A
KN
100 A
NSX100N
TMD/Micrologic
KN
KN
40 A
63 A
KN
100 A
NSX100N/H
TMD/Micrologic
KN
KN
40 A
63 A
KN
100 A
45
45
45
70
70
70
150
150
150
45
45
45
70
70
70
150
150
150
45
45
45
50
50
50
50
50
50
239
04/11/2009 16:02:43
Complementary
technical information
NSX400N
Micrologic
KSA/KVA/KVC
315 and 400 A
45
NSX400H
Micrologic
KSA/KVA/KVC
315 and 400 A
70
NSX400L
Micrologic
KSA/KVA/KVC
315 and 400 A
150
NSX100F
NSX160F
TMD/Micrologic
KSA
KSA
100 A
160 A
NSX100N NSX160N
TMD/Micrologic
KSA
KSA
100 A
160 A
NSX100N NSX160N
TMD/Micrologic
KSA
KSA
100 A
160 A
45
45
70
70
150
150
45
45
70
70
150
150
45
45
70
70
70
70
NSX400N
Micrologic
KSA/KVA/KVC
315 and 400 A
45
NSX400H
Micrologic
KSA/KVA/KVC
315 and 400 A
70
NSX400L
Micrologic
KSA/KVA/KVC
315 and 400 A
150
NSX100N TMD/Micrologic
40 A
63 A
100 A
KN
KN
KN
40 A
63 A
100 A
NSX100N TMD/Micrologic
40 A
63 A
100 A
KN
KN
KN
40 A
63 A
100 A
NSX100N/H TMD/Micrologic
40 A
63 A
100 A
KN
KN
KN
40 A
63 A
100 A
45
45
45
70
70
70
150
150
150
45
45
45
70
70
70
150
150
150
45
45
45
50
50
50
50
50
50
NSX250N
TDM/Micrologic
KSA/KVA/KVC
200 and 250 A
36
NSX250H
TDM/Micrologic
KSA/KVA/KVC
200 and 250 A
70
NSX250L
TDM/Micrologic
KSA/KVA/KVC
200 and 250 A
150
NSX100F
TMD/Micrologic
KSA-10
100 A
NSX100N
TMD/Micrologic
KSA-10
100 A
NSX100H
TMD/Micrologic
KSA-10
100 A
36
36
36
36
70
150
36
70
70
NSX250N
TDM/Micrologic
KSA/KVA/KVC
200 and 250 A
36
NSX250H
TDM/Micrologic
KSA/KVA/KVC
200 and 250 A
70
NSX250L
TDM/Micrologic
KSA/KVA/KVC
200 and 250 A
150
NSX100F TMD/Micrologic
40 A
63 A
100 A
KN
KN
KN
40 A
63 A
100 A
NSX100N TMD/Micrologic
40 A
63 A
100 A
KN
KN
KN
40 A
63 A
100 A
NSX100N/H TMD/Micrologic
40 A
63 A
100 A
KN
KN
KN
40 A
63 A
100 A
36
36
36
36
36
36
36
36
36
36
36
36
70
70
70
150
150
150
36
36
36
50
50
50
70
50
50
240
04/11/2009 16:02:46
Complementary
technical information
NSX250N
TDM/Micrologic
KSA/KVA/KVC
200 and 250 A
36
NSX250H
TDM/Micrologic
KSA/KVA/KVC
200 and 250 A
70
C60N
16/20
KLE
16-20 A
C60N
25/40
KBA/KBB
25-40 A
C60H
16/20
KLE
16-20 A
C60H
25/40
KBA/KBB
25-40 A
25
25
30
30
25
25
30
30
25
25
30
30
NSX250N
TDM/Micrologic
KSA/KVA/KVC
200 and 250 A
36
NSX250H
TDM/Micrologic
KSA/KVA/KVC
200 and 250 A
70
C60N
40 A
KN
40 A
C60N
63 A
KN
63 A
C60H
40 A
KN
40 A
C60H
63 A
KN
63 A
25
25
30
30
25
25
30
30
25
25
30
30
NSX160N
TDM/Micrologic
KSA
160 A
36
NSX160H
TDM/Micrologic
KSA
160 A
70
C60N
16/20
KLE
17-20 A
C60N
25/40
KBA/KBB
25-40 A
C60H
16/20
KLE
16-20 A
C60H
25/40
KBA/KBB
25-40 A
25
25
40
40
25
25
40
40
25
25
40
40
NSX160N
TDM/Micrologic
KSA
160 A
36
NSX160H
TDM/Micrologic
KSA
160 A
70
C60N
40 A
KN
40 A
C60N
63 A
KN
63 A
C60H
40 A
KN
40 A
C60H
63 A
KN
63 A
25
25
30
30
25
25
30
30
25
25
30
30
241
04/11/2009 16:02:46
LVPED308005EN
558E0000.indd 2
As standards, specifications and designs change from time to time, please ask for confirmation