GENERATOR ROOM VENTILATION CALCULATION Generator capacity = 750

Ventilating air (cu.m/min.) = = = = = SH = = dT= = ECA = = H H V D

(H/(D*SH*DT))+Engine Combustion Air Total Heat Radiation in (KW) (for engine + generator) (Ref. To specs. Sheet) 125.5 Ventilating air (cu.m/min.) Density of air (kg/m3) 1.07 Specific heat of air ( kw.min/Kg.C) 0.017 Temp. Rise inside engine room ( deg.C) 10 Engine Combustion Air (Exhaust gas flow ) (Ref. To specs. Sheet) 120
7,182

Radiator fan air flow =

17.6 1056
37,256

THEN :Ventilating air ( V ) = V = INTAKE LOUVER SIZE 810 28,564

Consider Air Velocity = Total Air Quantity = Louver Area =


Important Notes :-

1000 28,564 29 2.7 1- clean , cool , dry air circulates around the switchgear , flows through the rear of the generator , across the engine , and discharges through the radiator 2- Cool air shoul always be available for the engine air cleaner (air filter ). 3- For best ventilation results , air should flow first across the generator then to both sides of the engine . 4- Inlets located at the end of the room will provide adequate ventilation only to the engine nearast the inlet. 5- Air flow restriction should be 0.5 inch W.G

KVA

KW

At 54 deg. C

deg.C

cu.m/min cu.m/hr. cu.m/sec. cu.m/min cu.ft/min.

cu.m/min cu.ft/min.

ft/min.
cu.ft/min.

Sq.ft Sq.m