You are on page 1of 17

2008-05

Security Level: Internal Use

HUAWEI EMU
By Jefferson Simarmata
www.huawei.com

HUAWEI Confidential

Koneksi antara EMU dan BTS

RJ45
DB9 MON1 UEIU (RJ45)

HUAWEI TECHNOLOGIES Co., Ltd.

HUAWEI Confidential

Page 2

Kabel Power

Connect to SPARE1

HUAWEI TECHNOLOGIES Co., Ltd.

HUAWEI Confidential

Page 3

Switch DIP pada DEMU

SW1 - SW8 SW9 SW16

SW17 SW24

SW25 SW32

SW_RST

HUAWEI TECHNOLOGIES Co., Ltd.

HUAWEI Confidential

Page 4

Alarm Khusus

Sensor Air (banjit) Sensor suhu dan Kelembaban

Asap (kebakaran)
Sensor pintu Door Sensor----> Move to switch 9 (SW9)

Extend Alarm

HUAWEI TECHNOLOGIES Co., Ltd.

HUAWEI Confidential

Page 5

Alarm Khusus
Suhu dan kelembaban Asap

Air

HUAWEI TECHNOLOGIES Co., Ltd.

HUAWEI Confidential

Page 6

Alarm Eksternal

HUAWEI TECHNOLOGIES Co., Ltd.

HUAWEI Confidential

Page 7

Cara mengetahui kerusakan main fail, kerusakan modul rectifier,dan baterai lemah.
Matikan satu MCB utama, cek seluruh kabel output menggunakan multimeter, jika kabel short/open karena alarm ini, 2 alarm akan muncul: 1st Main fail 2nd Module rectifier fail (already give label before) Cek arus beban, pilih configuration low load kemudian atur batas low load lebih tinggi dari arus beban, cek semua kabel output dg Multimeter, jika kabel open/hort karena alarm ini, beri label Battery low voltage Tahan sampai alarm muncul, cek semua kabel output dg multimeter, jika kabel open/hort karena alarm ini, beri label Module rectifier fail Kembalikan ke kondisi normal: Matikan satu MCB AC utama

HUAWEI TECHNOLOGIES Co., Ltd.

HUAWEI Confidential

Page 8

Konfigurasi di LMT

Tambahkan board DEMU di subrack 2 slot 1

HUAWEI TECHNOLOGIES Co., Ltd.

HUAWEI Confidential

Page 9

Mengkonfigurasi board DEMU

- Gate Magnetism disabled karena gat e sensor ke Switch 9 - Water Immersed in low level karena output sensor NO (Normally Open)

HUAWEI TECHNOLOGIES Co., Ltd.

HUAWEI Confidential

Page 10

32 Switch dapat digunakan

Jika output sensor NC (Normally Close), level switch yg valid adalah High level Jika output sensor NO (Normally Open), level switch yg valid adalah Low level

HUAWEI TECHNOLOGIES Co., Ltd.

HUAWEI Confidential

Page 11

Alarm auto clear permit

HUAWEI TECHNOLOGIES Co., Ltd.

HUAWEI Confidential

Page 12

Cara mengganti ID alarm pada basis LMT di ID alarm IM2000 (1)


Use MML and run this command;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=1, SW=OPEN, AID=65384, PT=BOOL; SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=19, SW=OPEN, AID=65420, PT=BOOL; SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=20, SW=OPEN, AID=65422, PT=BOOL; SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=21, SW=OPEN, AID=65424, PT=BOOL; SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=2, SW=OPEN, AID=65386, PT=BOOL; SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=3, SW=OPEN, AID=65388, PT=BOOL; SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=4, SW=OPEN, AID=65390, PT=BOOL; SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=5, SW=OPEN, AID=65392, PT=BOOL; SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=6, SW=OPEN, AID=65394, PT=BOOL; SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=7, SW=OPEN, AID=65396, PT=BOOL; SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=8, SW=OPEN, AID=65398, PT=BOOL; SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=9, SW=OPEN, AID=65400, PT=BOOL; SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=10, SW=OPEN, AID=65402, PT=BOOL; SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=11, SW=OPEN, AID=65404, PT=BOOL; SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=12, SW=OPEN, AID=65406, PT=BOOL;

SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=13, SW=OPEN, AID=65408, PT=BOOL;
SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=14, SW=OPEN, AID=65410, PT=BOOL; SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=15, SW=OPEN, AID=65412, PT=BOOL; SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=16, SW=OPEN, AID=65414, PT=BOOL; SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=17, SW=OPEN, AID=65416, PT=BOOL; SET ALMPORT: SITENAME="Ngroto Rembangan", CN=0, SRN=2, SN=1, PN=18, SW=OPEN, AID=65418, PT=BOOL;

HUAWEI TECHNOLOGIES Co., Ltd.

HUAWEI Confidential

Page 13

Cara mengganti ID alarm pada basis LMT di ID alarm IM2000 (2)


Di LMT buka Alarm Maintenance, klik Query Alarm Configuration

Start Alarm ID from: 65424

Start Alarm ID from: 65384

HUAWEI TECHNOLOGIES Co., Ltd.

HUAWEI Confidential

Page 14

Cara mengganti ID alarm pada basis LMT di ID alarm IM2000 (3)


Setelah konfigurasi Query Alarm

Klik kanan pada nama alarm, klik Set Environment Alarm Configuration
HUAWEI TECHNOLOGIES Co., Ltd. HUAWEI Confidential
Page 15

Cara mengganti ID alarm pada basis LMT di ID alarm IM2000(4)


Alarm name dan alarm saverity setelah konfigurasi;

HUAWEI TECHNOLOGIES Co., Ltd.

HUAWEI Confidential

Page 16

Thank You
www.huawei.com