Item no: BO 001

Alarm and Control Settings for Composite Marine Boiler

Data Sheet: A-177200-01

Water level settings Top end of upper level glass High water level alarm Feed water pump stop Water level controller set point (normal water level) Feed water pump start Low water level alarm Low-low water level alarm and burner cut off Bottom end of lower level glass Steam pressure settings Steam pressure transmitter maximum Steam pressure safety valves High steam pressure, burner cut-out and alarm Steam dump valve set point Working steam pressure (transmitter set point) Burner automatically stop Burner automatically start Low steam pressure alarm Fuel oil pressure settings for SKVJ burner Fuel oil safety valve Fuel oil pressure control valve set point Start of stand-by fuel oil pump Fuel oil temperature settings for 380 cSt at 50 C and SKVJ burner High fuel oil temperature alarm Fuel oil temperature control valve set point Low fuel oil temperature alarm 90 80 70 C C C 7.0 5.0 2.0 bar bar bar 16.0 8.5 8.0 7.3 7.0 7.0 6.0 4.5 bar bar bar bar bar bar bar bar 653 477 377 327 277 227 177 0 mm mm mm mm mm mm mm mm 100 73 58 50 42 35 27 0 % % % % % % % %

Above data can be modified by SAACKE service engineer, according to the actual situation and customer request during commissioning.

2008-09-19

Page 1 of 1