Parameter Settings (Program)

Program (Motorpact Selected / Connected): Series: Firmware Version: Project: User: Motorpact SoftStart 6,86 - 6,96 a a

14/05/2013 15:01:39

Parameter
Page 1: Basic Configuration Motor Full Load Amps (FLA) Service Factor NEMA Design Overload Class Insulation Class Line Voltage Line Frequency Page 2: Starter Configuration Start Control Mode Jog Voltage Start Ramp #1 Type Initial Voltage #1 Ramp Time #1 Current Limit #1 Initial Current #1 Ramp Time #1 Maximum Current #1 Start Ramp #2 Type Initial Voltage #2 Ramp Time #2 Current Limit #2 Initial Current #2 Ramp Time #2 Maximum Current #2 Kick Start Type Kick Start Voltage Kick Start Time Deceleration Start Deceleration Voltage

Program Setting
100 1,15 B 10 B 4 160 60

Eng. Units
Amps x FLA -

Program Setting Info

Volts Hz

Start Ramp 1 50 Voltage 20 10 350 200 10 350 Disabled 60 10 350 200 10 350 Disabled 65 0,50 Disabled 60

% % sec % FLA % FLA sec % FLA % sec % FLA % FLA sec % FLA % sec %

Parameter
Stop Deceleration Voltage Deceleration Time Timed Output Time Run Delay Time At Speed Delay Time Bypass Pull-In Current Page 3: Phase and Ground Settings Imbalance Alarm Level Imbalance Alarm Delay Imbalance Trip Level Imbalance Trip Delay Undercurrent Alarm Level Undercurrent Alarm Delay Overcurrent Alarm Level Overcurrent Alarm Delay Overcurrent Trip Level Overcurrent Trip Delay Phase Loss Trip Phase Loss Trip Delay Phase Rotation Detection Phase Rotation Trip Delay Ground Fault Alarm Level Ground Fault Alarm Delay Ground Fault Loset Trip Level Ground Fault Loset Trip Delay Ground Fault Hiset Trip Level Ground Fault Hiset Trip Delay Overvoltage Alarm Level Overvoltage Alarm Delay Overvoltage Trip Level Overvoltage Trip Delay Undervoltage Alarm Level Undervoltage Alarm Delay Undervoltage Trip Level Undervoltage Trip Delay Line Frequency Trip Window Line Frequency Trip Delay P/F Lead P/F Alarm P/F Lead Alarm Delay P/F Lead P/F Trip P/F Lead Trip Delay P/F Lag P/F Alarm P/F Lag Alarm Delay P/F Lag P/F Trip P/F Lag Trip Delay Power Demand Period KW Demand Alarm Pickup

Program Setting
30 5 Off 1 1 100

Eng. Units
% sec sec sec sec % FLA

Program Setting Info

15 1,5 20 2,0 Off 2,0 Off 2,0 Off 2,0 Enabled 0,1 ABC 1,0 Off 0,1 Off 0,5 Off 0,008 Off 1,0 10 2,0 Off 1,0 15 2,0 Disabled 1,0 Off 1 Off 1 Off 1 Off 1 10 Off

% FLA sec % FLA sec % FLA sec % FLA sec % FLA sec sec sec % CT sec % CT sec % CT sec % sec % sec % sec % sec Hz sec 1 1

sec

sec

sec

sec minutes kW

Parameter
KVA Demand Alarm Pickup KVAR Demand Alarm Pickup Amps Demand Alarm Pickup Page 4: Relay Assignments O/L Trip 1st O/L Trip 2nd O/L Trip 3rd I/B Trip 1st I/B Trip 2nd I/B Trip 3rd S/C Trip 1st S/C Trip 2nd S/C Trip 3rd Overcurrent Trip 1st Overcurrent Trip 2nd Overcurrent Trip 3rd Stator RTD Trip 1st Stator RTD Trip 2nd Stator RTD Trip 3rd Non Stator RTD Trip 1st Non Stator RTD Trip 2nd Non Stator RTD Trip 3rd G/F Hi Set Trip 1st G/F Hi Set Trip 2nd G/F Hi Set Trip 3rd G/F Lo Set Trip 1st G/F Lo Set Trip 2nd G/F Lo Set Trip 3rd Phase Reversal 1st Phase Reversal 2nd Phase Reversal 3rd Phase Loss Trip 1st Phase Loss Trip 2nd Phase Loss Trip 3rd Accel. Time Trip 1st Accel. Time Trip 2nd Accel. Time Trip 3rd Start Curve Trip 1st Start Curve Trip 2nd Start Curve Trip 3rd I*I*T Start Curve 1st I*I*T Start Curve 2nd I*I*T Start Curve 3rd Learned Start Curve 1st Learned Start Curve 2nd Learned Start Curve 3rd Over Frequency Trip 1st

Program Setting
Off Off Off

Eng. Units
kVA kVAr Amps

Program Setting Info

Trip (Aux1) None None Trip (Aux1) None None Trip (Aux1) None None Trip (Aux1) None None None None None None None None Trip (Aux1) None None Trip (Aux1) None None Trip (Aux1) None None Trip (Aux1) None None Trip (Aux1) None None Trip (Aux1) None None Trip (Aux1) None None Trip (Aux1) None None None

1 9 9 1 9 9 1 9 9 1 9 9 0 9 9 0 9 9 1 9 9 1 9 9 1 9 9 1 9 9 1 9 9 1 9 9 1 9 9 1 9 9 0

Parameter
Over Frequency Trip 2nd Over Frequency Trip 3rd Under Frequency Trip 1st Under Frequency Trip 2nd Under Frequency Trip 3rd Tach Accel Trip 1st Tach Accel Trip 2nd Tach Accel Trip 3rd Inhibits Trip 1st Inhibits Trip 2nd Inhibits Trip 3rd O/L Warning 1st O/L Warning 2nd O/L Warning 3rd Overcurrent Alarm 1st Overcurrent Alarm 2nd Overcurrent Alarm 3rd Shunt Trip 1st Shunt Trip 2nd Shunt Trip 3rd Ground Fault Alarm 1st Ground Fault Alarm 2nd Ground Fault Alarm 3rd Under Current Alarm 1st Under Current Alarm 2nd Under Current Alarm 3rd I/B Alarm 1st I/B Alarm 2nd I/B Alarm 3rd Stator RTD Alarm 1st Stator RTD Alarm 2nd Stator RTD Alarm 3rd Non-Stator RTD Alarm 1st Non-Stator RTD Alarm 2nd Non-Stator RTD Alarm 3rd RTD Failure Alarm 1st RTD Failure Alarm 2nd RTD Failure Alarm 3rd Self Test Fail 1st Self Test Fail 2nd Self Test Fail 3rd Thermal Register 1st Thermal Register 2nd Thermal Register 3rd Motor Running 1st Motor Running 2nd Motor Running 3rd

Program Setting
None None Trip (Aux1) None None None None None Alarm (Aux2) None None Alarm (Aux2) None None Alarm (Aux2) None None None None None Alarm (Aux2) None None None None None Alarm (Aux2) None None None None None None None None None None None Trip (Aux1) None None Alarm (Aux2) None None Aux3 None None

Eng. Units
-

Program Setting Info


9 9 1 9 9 0 9 9 2 9 9 2 9 9 2 9 9 0 9 9 2 9 9 0 9 9 2 9 9 0 9 9 0 9 9 0 9 9 1 9 9 2 9 9 3 9 9

Parameter
Run Delay Time 1st Run Delay Time 2nd Run Delay Time 3rd Timed Output 1st Timed Output 2nd Timed Output 3rd At Speed 1st At Speed 2nd At Speed 3rd TCB Fault 1st TCB Fault 2nd TCB Fault 3rd External Input #2 1st External Input #2 2nd External Input #2 3rd Dual Ramp 1st Dual Ramp 2nd Dual Ramp 3rd Thermostat 1st Thermostat 2nd Thermostat 3rd Power Factor Alarm 1st Power Factor Alarm 2nd Power Factor Alarm 3rd U/V Alarm 1st U/V Alarm 2nd U/V Alarm 3rd O/V Alarm 1st O/V Alarm 2nd O/V Alarm 3rd Undervoltage Trip 1st Undervoltage Trip 2nd Undervoltage Trip 3rd Overvoltage Trip 1st Overvoltage Trip 2nd Overvoltage Trip 3rd Power Factor Trip 1st Power Factor Trip 2nd Power Factor Trip 3rd KW Demand Alarm 1st KW Demand Alarm 2nd KW Demand Alarm 3rd KVA Demand Alarm 1st KVA Demand Alarm 2nd KVA Demand Alarm 3rd KVAR Demand Alarm 1st KVAR Demand Alarm 2nd

Program Setting
None None None None None None Aux4 None None Trip (Aux1) None None None None None None None None Trip (Aux1) None None None None None Alarm (Aux2) None None Alarm (Aux2) None None Trip (Aux1) None None Trip (Aux1) None None None None None None None None None None None None None

Eng. Units
-

Program Setting Info


0 9 9 0 9 9 4 9 9 1 9 9 0 9 9 0 9 9 1 9 9 0 9 9 2 9 9 2 9 9 1 9 9 1 9 9 0 9 9 0 9 9 0 9 9 0 9

Parameter
KVAR Demand Alarm 3rd Amps Demand Alarm 1st Amps Demand Alarm 2nd Amps Demand Alarm 3rd Bypass Discrepancy 1st Bypass Discrepancy 2nd Bypass Discrepancy 3rd Page 5: Relay Configuration Trip (AUX1) Fail-Safe Alarm (AUX2) Fail-Safe AUX3 Relay Fail-Safe AUX4 Relay Fail-Safe AUX5 Relay Fail-Safe AUX6 Relay Fail-Safe AUX7 Relay Fail-Safe AUX8 Relay Fail-Safe Trip (AUX1) Relay Latched Alarm (AUX2) Relay Latched AUX3 Relay Latched AUX4 Relay Latched AUX5 Relay Latched AUX6 Relay Latched AUX7 Relay Latched AUX8 Relay Latched Page 6: User I/O Configuration Tach Ramp Time Tachometer Scale Selection Manual Tach Scale 4.0 mA Manual Tach Scale 20.0 mA Tach Accel Trip Mode Select Tach Underspeed Trip PT Tach Overspeed Trip PT Tach Accel Trip Delay Analog Output #1 Analog Output #1 4mA Analog Output #1 20mA Analog Output #2 Analog Output #2 4mA Analog Output #2 20mA TCB Fault, Input #1 TCB Fault Type, Input #1 TCB Fault Time Delay, Input #1 Name Ext. Input #1 External Input #2 External Input #2 Type External Input #2 Time Delay Name Ext. Input #2

Program Setting
None None None None Trip (Aux1) None None

Eng. Units
-

Program Setting Info


9 0 9 9 1 9 9

No No No No No No No No Yes No No No No No No No

0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0

20 Disabled 0 2 000 Disabled 1 650 1 850 1 RMS Current 0 250 % Motor Load 0 1 000 Enabled Normally Open 1

sec RPM RPM RPM RPM sec 4 0 0

sec

1 0

Disabled Normally Open 0

sec

0 0

Parameter
Dual Ramp, Input #3 Dual Ramp Type, Input #3 Dual Ramp Time Delay, Input #3 Name Ext. Input #3 Thermostat, Input #4 Thermostat Type, Input #4 Thermostat Time Delay, Input #4 Name Ext. Input #4 Page 7: Custom Acceleration Curve Custom Accel Curve Curve A Current Limit Curve A Voltage Level 1 Curve A Ramp Time 1 Curve A Voltage Level 2 Curve A Ramp Time 2 Curve A Voltage Level 3 Curve A Ramp Time 3 Curve A Voltage Level 4 Curve A Ramp Time 4 Curve A Voltage Level 5 Curve A Ramp Time 5 Curve A Voltage Level 6 Curve A Ramp Time 6 Curve A Voltage Level 7 Curve A Ramp Time 7 Curve A Voltage Level 8 Curve A Ramp Time 8 Curve B Current Limit Curve B Voltage Level 1 Curve B Ramp Time 1 Curve B Voltage Level 2 Curve B Ramp Time 2 Curve B Voltage Level 3 Curve B Ramp Time 3 Curve B Voltage Level 4 Curve B Ramp Time 4 Curve B Voltage Level 5 Curve B Ramp Time 5 Curve B Voltage Level 6 Curve B Ramp Time 6 Curve B Voltage Level 7 Curve B Ramp Time 7 Curve B Voltage Level 8 Curve B Ramp Time 8 Curve C Current Limit Curve C Voltage Level 1 Curve C Ramp Time 1

Program Setting
Dual Ramp Normally Open 0

Eng. Units
sec

Program Setting Info


2 0

Enabled Normally Closed 1

1 1

Disabled 350 25 2 30 2 37 2 45 2 55 2 67 2 82 2 100 2 350 25 2 30 2 37 2 45 2 55 2 67 2 82 2 100 2 350 25 2

% FLA % sec % sec % sec % sec % sec % sec % sec % sec % FLA % sec % sec % sec % sec % sec % sec % sec % sec % FLA % sec

Parameter
Curve C Voltage Level 2 Curve C Ramp Time 2 Curve C Voltage Level 3 Curve C Ramp Time 3 Curve C Voltage Level 4 Curve C Ramp Time 4 Curve C Voltage Level 5 Curve C Ramp Time 5 Curve C Voltage Level 6 Curve C Ramp Time 6 Curve C Voltage Level 7 Curve C Ramp Time 7 Curve C Voltage Level 8 Curve C Ramp Time 8 Page 8: Overload Curve Configuration Run Curve Locked Rotor Time Run Locked Rotor Current Start Curve Locked Rotor Time Start Locked Rotor Current Area Under Curve Protection Max I*I*T Start Current Over Curve Learned Start Curve Bias Time for Sampling Acceleration Time Limit Coast Down Timer Number of Starts Per Hour Time Between Starts Time Page 9: RTD Configuration Use NEMA Temp for RTD Values # of RTD Used for Stator RTD Voting RTD #1 Description Stator Phase A1 Type Stator Phase A1 Alarm Level Stator Phase A1 Trip Level RTD #2 Description Stator Phase A2 Type Stator Phase A2 Alarm Level Stator Phase A2 Trip Level RTD #3 Description Stator Phase B1 Type Stator Phase B1 Alarm Level Stator Phase B1 Trip Level RTD #4 Description Stator Phase B2 Type Stator Phase B2 Alarm Level

Program Setting
30 2 37 2 45 2 55 2 67 2 82 2 100 2

Eng. Units
% sec % sec % sec % sec % sec % sec % sec

Program Setting Info

O/L Class 600 O/L Class 600 Disabled 368 Disabled 10 30 30 Disabled Disabled 5 % FLA FLA*FLA *sec % sec sec min max min 0 0 % FLA

Disabled 4 Disabled STATOR PHAS A1 Off Off Off STATOR PHAS A2 Off Off Off STATOR PHAS B1 Off Off Off STATOR PHAS B2 Off Off

C C

C C

C C

Parameter
Stator Phase B2 Trip Level RTD #5 Description Stator Phase C1 Type Stator Phase C1 Alarm Level Stator Phase C1 Trip Level RTD #6 Description Stator Phase C2 Type Stator Phase C2 Alarm Level Stator Phase C2 Trip Level RTD #7 Description End Bearing Type End Bearing Alarm Level End Bearing Trip Level RTD #8 Description Shaft Bearing Type Shaft Bearing Alarm Level Shaft Bearing Trip Level RTD #9 Description RTD #9 Type RTD #9 Alarm Level RTD #9 Trip Level RTD #10 Description RTD #10 Type RTD #10 Alarm Level RTD #10 Trip Level RTD #11 Description RTD #11 Type RTD #11 Alarm Level RTD #11 Trip Level RTD #12 Description RTD #12 Type RTD #12 Alarm Level RTD #12 Trip Level Page 10: Security Set Password Set Level 2 Password Set Level 3 Password Page 11: Communications Set Access Code Remote Start/Stop Page 12: System Setpoints Metering Data Page # Metering Data Screen # RTD Failure Alarm Thermal Register Minimum Thermal Register Alarm Thermal Alarm Delay Stopped Cool Down Time

Program Setting
Off STATOR PHAS C1 Off Off Off STATOR PHAS C2 Off Off Off END BEARING Off Off Off SHAFT BEARING Off Off Off

Eng. Units
C

Program Setting Info

C C

C C

C C

C C

Off Off Off

C C

Off Off Off

C C

Off Off Off

C C

Off Off Off

C C

100 1 000

1 Disabled 0

1 1 Disabled 15 90 10 30 % % sec min 0

Parameter
Running Cool Down Time Hot Stall Time Cold Stall Time Relay Measured Cool Rates Motor Design Ambient Temp Motor Design Run Temperature Motor Stator Max Temp I/B Input to Thermal Register Use Calculated K or Assign

Program Setting
15 1/2 O/L Class O/L Class Disabled 40 80 Ins Cls Enabled 7

Eng. Units
min

Program Setting Info

C % max C -