VOLTAGE DROP& CABLE SIZING CALCULATIONS

Note:
Cable lengths used are for voltage drop calculations only. Actual length of the cables to be measured by the contractor.

Page 1 of 3

IES

Project

Head Office

Part of structure APARTMENT FOR SALE


Date of Issue
Rev. No.
0

P.0.Box 111
Manama, Kingdom of Bahrain

Job ref.

XXXXX

2008086
Sheet no.
1 of 2

Cable Size mm2 or Busduct


Rating

Write "C" for Cable or "B"


for Busduct

Type (XLPE for Cable & CU


/ AL for Busduct)

Operating Voltage (V)

Length ( Mt)

TCL in KW

MD in KW

MD in KVA

Power Factor

ACB/ MCCB Rating

Voltage Drop/A/M (mV)

% Voltage Drop Allowed (%)

Max. Voltage Drop allowed


(V)

Load Current A

Act. Voltage Drop (v)

Act. % Voltage Drop (%)

Installation Type. G/A/D

Cable/ Busduct
Derating Factor

Voltage drop within limit?

Cable or Busduct
Current Rating (A)

Load Current (A)

MCCB Rating (A)

Cable Derated Current (A)

MCCB rating within load


current?

Cable size can be reduced?

MP-AS1-001

Number of Cores

Cable From

Number of Runs

Cable
Ref.

Single/ Three Phase

VOLTAGE DROP CALCULATIONS

TRANSFORMER 01

1000

XLPE

400

30

1808

1158

1447

0.8

2500

0.160

0.3

1.2

2089

1.43

0.36

0.8

CHECK

8498

2089

2500

6798

OK

CHECK

Connected To

B
1

SMP-AS1-301

MP-AS1-001

120

XLPE

400

25

138

77

97

0.8

250

0.37

2.0

8.0

140

1.29

0.32

0.8

OK

353

140

250

282

OK

NO

SMP-AS1-401

MP-AS1-001

120

XLPE

400

30

138

77

97

0.8

250

0.37

2.0

8.0

140

1.55

0.39

0.8

OK

353

140

250

282

OK

NO

SMP-AS1-501

MP-AS1-001

120

XLPE

400

35

138

77

97

0.8

250

0.37

2.0

8.0

140

1.81

0.5

0.8

OK

353

140

250

282

OK

NO

SMP-AS1-601

MP-AS1-001

120

XLPE

400

40

138

77

97

0.8

250

0.37

2.0

8.0

140

2.06

0.5

0.8

OK

353

140

250

282

OK

NO

SMP-AS1-701

MP-AS1-001

120

XLPE

400

45

138

77

97

0.8

250

0.37

2.0

8.0

140

2.32

0.6

0.8

OK

353

140

250

282

OK

NO

SMP-AS2-801

MP-AS1-001

120

XLPE

400

50

138

77

97

0.8

250

0.37

2.0

8.0

140

2.58

0.6

0.8

OK

353

140

250

282

OK

NO

SMP-AS1-901

MP-AS1-001

120

XLPE

400

55

138

77

97

0.8

250

0.37

2.0

8.0

140

2.84

0.7

0.8

OK

353

140

250

282

OK

NO

SMP-AS1-1001

MP-AS1-001

120

XLPE

400

60

152

84

106

0.8

250

0.37

2.0

8.0

152

3.38

0.8

0.8

OK

353

152

250

282

OK

NO

SMP-AS1-1101

MP-AS1-001

120

XLPE

400

65

152

84

106

0.8

250

0.37

2.0

8.0

152

3.66

0.9

0.8

OK

353

152

250

282

OK

NO

10

SMP-AS1-1201

MP-AS1-001

70

XLPE

400

70

72

42

52

0.8

160

0.60

2.0

8.0

75

3.16

0.8

0.8

OK

251

75

160

201

OK

CHECK

11

SMP-AS1-1301

MP-AS1-001

185

XLPE

400

75

78

78

98

0.8

300

0.26

2.0

8.0

141

2.74

0.7

0.8

OK

463

141

300

370

OK

CHECK

12

SMP-AS1-001

MP-AS1-001

185

XLPE

400

25

187

150

188

0.8

300

0.26

2.0

8.0

271

1.76

0.4

0.8

OK

463

271

300

370

OK

CHECK

13

SMP-AS1-002

MP-AS1-001

95

XLPE

400

25

104

83

104

0.8

200

0.45

2.0

8.0

150

1.68

0.4

0.8

OK

304

150

200

243

OK

CHECK

12

SMP-AS1-B01-CHWP

MP-AS1-001

95

XLPE

400

40

95

95

119

0.8

200

0.45

2.0

8.0

171

3.09

0.8

0.8

OK

304

171

200

243

OK

CHECK

15

SPARE

16

SPARE

IES

Project

Head Office

Part of structure APARTMENT FOR SALE


Date of Issue
Rev. No.
0

P.0.Box 111
Manama, Kingdom of Bahrain

Job ref.

XXXX

2008086
Sheet no.
2 of 2

Cable Size mm2 or Busduct


Rating

Write "C" for Cable or "B"


for Busduct

Type (XLPE for Cable & CU


/ AL for Busduct)

Operating Voltage (V)

Length ( Mt)

TCL in KW

MD in KW

MD in KVA

Power Factor

ACB/ MCCB Rating

Voltage Drop/A/M (mV)

% Voltage Drop Allowed (%)

Max. Voltage Drop allowed


(V)

Load Current A

Act. Voltage Drop (v)

Act. % Voltage Drop (%)

Installation Type. G/A/D

Cable/ Busduct
Derating Factor

Voltage drop within limit?

Cable or Busduct
Current Rating (A)

Load Current (A)

MCCB Rating (A)

Cable Derated Current (A)

MCCB rating within load


current?

Cable size can be reduced?

MP-AS1-002

Number of Cores

Cable From

Number of Runs

Cable
Ref.

Single/ Three Phase

VOLTAGE DROP CALCULATIONS

TRANSFORMER 02

1000

XLPE

400

30

1786

1166

1458

0.8

2500

0.160

0.3

1.2

2104

1.44

0.36

0.8

CHECK

8498

2104

2500

6798

OK

CHECK

Connected To

B
1

SMP-AS2-301

MP-AS1-002

120

XLPE

400

30

162

90

112

0.8

250

0.37

2.0

8.0

162

1.79

0.45

0.8

OK

353

162

250

282

OK

NO

SMP-AS2-401

MP-AS1-002

120

XLPE

400

35

162

90

112

0.8

250

0.37

2.0

8.0

162

2.09

0.52

0.8

OK

353

162

250

282

OK

NO

SMP-AS2-501

MP-AS1-002

120

XLPE

400

40

162

90

112

0.8

250

0.37

2.0

8.0

162

2.39

0.6

0.8

OK

353

162

250

282

OK

NO

SMP-AS2-601

MP-AS1-002

120

XLPE

400

45

162

90

112

0.8

250

0.37

2.0

8.0

162

2.69

0.7

0.8

OK

353

162

250

282

OK

NO

SMP-AS2-701

MP-AS1-002

120

XLPE

400

50

162

90

112

0.8

250

0.37

2.0

8.0

162

2.99

0.7

0.8

OK

353

162

250

282

OK

NO

SMP-AS2-801

MP-AS1-002

120

XLPE

400

55

162

90

112

0.8

250

0.37

2.0

8.0

162

3.29

0.8

0.8

OK

353

162

250

282

OK

NO

SMP-AS2-901

MP-AS1-002

120

XLPE

400

60

162

90

112

0.8

250

0.37

2.0

8.0

162

3.59

0.9

0.8

OK

353

162

250

282

OK

NO

SMP-AS2-1001

MP-AS1-002

50

XLPE

400

65

38

23

29

0.8

125

0.87

2.0

8.0

41

2.33

0.6

0.8

OK

197

41

125

158

OK

CHECK
NO

SMP-AS2-1101

MP-AS1-002

120

XLPE

400

70

64

64

80

0.8

250

0.37

2.0

8.0

115

2.99

0.7

0.8

OK

353

115

250

282

OK

10

SMP-AS2-001

MP-AS1-002

120

XLPE

400

25

152

132

165

0.8

250

0.37

2.0

8.0

238

2.20

0.6

0.8

OK

353

238

250

282

OK

NO

11

EMP-AS1-001

MP-AS1-002

240

XLPE

400

30

400

320

400

0.8

630

0.21

2.0

8.0

577

1.82

0.5

0.8

OK

1092

577

630

874

OK

CHECK

12

SPARE

13

SPARE

You might also like