Air System Sizing Summary for VAV Rooftop System

Project Name: Manufacturing Office


Prepared by:

Air System Information


Air System Name:
Air System Type:

Sizing Calculation Information


Calculation Months:

10/21/2005
03:51PM

VAV Rooftop System


VAV

Number of zones:
Floor Area:
Location:

7
6000.0 sqft
St. Louis IAP, Missouri

May to Nov

Central Cooling Coil Sizing Data


Total coil load:
Total coil load:
Sensible coil load:
Coil airflow:
Sensible heat ratio:
Area per unit load:
Load per unit area:

13.9
167.3
116.9
3759
0.699
430.3
27.9

Preheat Coil Sizing Data


Max coil load:
Coil airflow:
Max coil airflow:

Tons
MBH
MBH
CFM

Load occurs at:


OA DB / WB:
Entering DB / WB:
Leaving DB / WB:
Coil ADP:
Bypass Factor:
Resulting RH:
Design supply temp:

Jul 1500
95.0/76.0
83.1/67.6
53.6/52.6
51.0
0.080
45
55.0

9.5 MBH
1280 CFM
3759 CFM

Load occurs at:


Ent DB / Lvg DB:

Des Htg
43.0/50.0 F

Supply Fan Sizing Data


Actual max airflow:
Standard airflow:
Actual max airflow per unit area:

3759 CFM
3668 CFM
0.63 CFM/sqft

Fan motor BHP:


Fan motor kW:
Fan static:

Outdoor Ventilation Air Data


Design airflow:
Airflow per unit floor area:

1280 CFM
0.21 CFM/sqft

Airflow per person:

sqft/Ton
BTU/(hr-sqft)

F
F
F
F
%
F

2.19 BHP
1.63 kW
2.00 in wg

20.00 CFM/person

Zone Sizing Data


Zone Name

1 Conference Room
2 Assistant manager
3 Manager
4 General Perimeter
5 Chief Engineer
6 Engineering
7 General Core

Block Load 4.00

Maximum
Cooling
Sensible
MBH
7.4
3.4
5.5
18.7
5.0
11.9
30.0

Design
Airflow
CFM
351
161
260
886
238
564
1425

Minimum Time of Peak


Maximum
Air Flow
Load Heating Load
CFM
MBH
240
40
40
200
40
120
600

Jul 1500
Jul 1500
Aug 1400
Sep 1400
Aug 1600
Jul 1600
Jul 1600

6.4
3.8
7.6
18.6
6.3
11.4
13.4

Zone
Floor
Area
sqft
375.0
225.0
300.0
1050.0
225.0
675.0
3150.0

Zone
CFM/sqft

0.93
0.72
0.87
0.84
1.06
0.84
0.45

Reheat
Coil
Load
MBH
10.2
4.4
8.2
21.8
7.0
13.3
22.9

Page 1 of 1

System Design Load Summary for VAV Rooftop System


Project Name: Manufacturing Office
Prepared by:

ZONE LOADS
Window and Skylight Solar Loads
Wall Transmission
Roof Transmission
Window Transmission
Skylight Transmission
Door Loads
Floor Transmission
Partitions/Ceilings
Overhead Lighting
Electric Equipment
People
Infiltration
Miscellaneous
Safety Factor
>>Total Zone Loads
Thermostat and Pulldown Adjustment
Plenum Wall Load
Plenum Roof Load
Plenum Lighting Load
Ventilation Load
Supply Fan Load
>> Total System Loads
Central Cooling Coil
Preheat Coil
Terminal Reheat Coils
>> Total Coil Loads
Key:

Block Load 4.00

10/21/2005
03:53PM

DESIGN COOLING
DESIGN HEATING
COOLING DATA AT Jul 1500
HEATING DATA AT DES HTG
COOLING OA DB / WB 95 F / 76 F
HEATING OA DB / WB -6 F / -7.2 F
Details
Sensible
Latent
Details
Sensible
Latent
BTU/hr
BTU/hr
BTU/hr
BTU/hr
504 sqft
11010
504 sqft
2087 sqft
3337
2087 sqft
11261
6000 sqft
12907
6000 sqft
24624
504 sqft
3877
504 sqft
17620
0 sqft
0
0 sqft
0
49 sqft
2133
49 sqft
2048
6000 sqft
0
6000 sqft
4924
850 sqft
481
850 sqft
638
9000 W
25702
0W
0
2100 W
6644
0W
0
64
12132
13120
0
0
0
0
0
6344
1
0
0
0
0
0% / 0%
0
0
0%
0
0
78223
13120
67459
1
11632
0
-2029
0
0%
0
0
0
0%
0
0
0
0%
0
0
0
1280 CFM
24360
37315
436 CFM
34115
0
3759 CFM
5573
1280 CFM
-2365
119788
50435
97181
1
116867
50439
0
0
0
9485
0
87695
116867
50439
97181
0
Positive values are clg loads
Positive values are htg loads
Negative values are htg loads
Negative valuees are clg loads

Page 1 of 1

System Psychrometrics for VAV Rooftop System


Project Name: Manufacturing Office
Prepared by:

10/21/2005
03:56PM

Location: St. Louis IAP ,Missouri


Altitude: 673
Data for: Jul DESIGN COOLING DAY, 1500
0.020

1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
5. Room Air

0.018
0.016
1

0.012
2

0.010
5
3 4

0.008
0.006

Specific Humidity ( lb/lb )

0.014

0.004
0.002
0.000
30

Block Load 4.00

40

50

60
70
Temperature (F)

80

90

100

Page 1 of 1

Ventilation Sizing Summary for VAV Rooftop System


Project Name: Manufacturing Office
Prepared by:

10/21/2005
04:01PM

Summary
Ventilation Sizing Method:
Design Ventilation Airflow Rate:
Uncorrected Outdoor Airflow Rate:

ASHRAE Std 62-2001


1985 CFM
1280 CFM

ASHRAE Std 62 Analysis Details


Critical Space:
Critical Space Outdoor Air Fraction (Z):

1 Conference Room
0.685

Uncorrected Outdoor Air Fraction (X):


Corrected Outdoor Air Fraction (Y):
Required System Ventilation Airflow:

0.329
0.511
1985 CFM

Space Ventilation Analysis Table


Zone Name

1 Conference Room
2 Assistant manager
3 Manager
4 General Perimeter
5 Chief Engineer
6 Engineering
7 General Core
Totals

Block Load 4.00

Floor Area
sqft

Maximum
Occupants

375.0
225.0
300.0
1050.0
225.0
675.0
3150.0

12.0
2.0
2.0
10.0
2.0
6.0
30.0

Maximum
Supply Air
CFM
350.5
161.5
260.1
885.9
237.6
563.9
1425.4
3885.0

Required
Outside Air
CFM/person
20.00
20.00
20.00
20.00
20.00
20.00
20.00

Required
Outside Air
CFM/sqft
0.00
0.00
0.00
0.00
0.00
0.00
0.00

Required
Required Uncorrected Uncorrected
Outside Air Outside Air Outdoor Air Outdoor Air
CFM (% of supply)
CFM
Ratio (Z)
0.0
0.0
240.0
0.685
0.0
0.0
40.0
0.248
0.0
0.0
40.0
0.154
0.0
0.0
200.0
0.226
0.0
0.0
40.0
0.168
0.0
0.0
120.0
0.213
0.0
0.0
600.0
0.421
1280.0
0.685

Corrected
Outdoor Air
CFM
179.1
82.5
132.9
452.7
121.4
288.1
728.4
1985.2

Page 1 of 1

Hourly Air System Design Day Loads for VAV Rooftop System
Project Name: Manufacturing Office
Prepared by:

Hour

OA
TEMP F

SUPPLY
AIRFLOW
CFM

0000
0100
0200
0300
0400
0500
0600
0700
0800
0900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300

80.0
79.1
78.2
77.4
76.9
76.7
77.1
78.0
79.6
82.0
84.8
87.9
90.8
93.0
94.5
95.0
94.5
93.2
91.2
88.8
86.4
84.4
82.6
81.1

0
0
0
0
0
72
182
3759
3759
3759
3759
3759
3759
3759
3759
3759
3759
3759
3759
0
0
0
0
0

Block Load 4.00

10/21/2005
03:57PM

DESIGN MONTH: Jul


CENTRAL
CENTRAL
CENTRAL
COOLING
COOLING
HEATING
SENSIBLE TOTAL MBH
COIL MBH
MBH
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.2
2.2
0.0
5.7
5.7
0.0
94.5
144.0
0.0
96.0
145.6
0.0
99.0
148.7
0.0
102.6
152.5
0.0
106.9
156.9
0.0
111.0
161.2
0.0
114.1
164.4
0.0
116.1
166.5
0.0
116.9
167.3
0.0
116.0
166.4
0.0
114.0
164.3
0.0
110.7
160.9
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

PREHEAT
COIL MBH

TERMINAL
COOLING
COILS MBH

TERMINAL
HEATING
COILS MBH

0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

Page 1 of 1