ELECTRICAL SCHEMATIC DRAWING - GE ZENITH ZTE SERIES TRANSFER SWITCHES - STANDARD (OPEN) TRANSITION TYPE - 225 TO 400A LEGEND,

FEATURES, OPERATION, AND ACCESSORIES


1.0 CONTROL CONFIGURATION GROUPS
ZTE SWITCHES ARE CONFIGURED TO ONE (1) OF THE FOLLOWING FIVE (5) OPTION PACKAGES. NOTE: ATS CATALOG NUMBER SCHEME, DIGIT #9, INDICATES THE INSTALLED CONTROL PACKAGE CONFIGURATION A B C D M DESCRIPTION STANDARD PACKAGE FOR AUTOMATIC ATS. INCLUDES FULL FUNCTION ATS CONTROL, DIAGNOSTICS, USER CONTROL SWITCHES, (4) USER-CONFIGURABLE INPUTS, AND (4) USER-CONFIGURABLE OUTPUTS ALL FEATURES IN "A" PLUS: USER-CONFIGURABLE ANALOG & DIGITAL ALARMS, 20-CHANNEL DATA LOGGER, 10-CHANNEL WAVEFORM CAPTURE, AUTO LOAD SHED FEATURE ALL FEATURES IN "B" PLUS: (4) ADDITIONAL USER-CONFIGURABLE INPUTS AND OUTPUTS (TOTAL 8 INPUTS, 8 OUTPUTS) ALL FEATURES IN "C" PLUS: (4) ADDITIONAL USER-CONFIGURABLE INPUTS AND OUTPUTS (TOTAL 12 INPUTS, 12 OUTPUTS), FLEXLOGIC USER-PROGRAMMABLE CUSTOM LOGIC EDITOR STANDARD PACKAGE FOR MANUAL ATS. INCLUDES FULL FUNCTION ATS CONTROL, DIAGNOSTICS, USER CONTROL SWITCHES (SEE ITEM #4), (4) USER-CONFIGURABLE INPUTS, AND (4) USER-CONFIGURABLE OUTPUTS

5.0 SEQUENCE OF OPERATIONS


NOTE: SEE O&M MANUAL FOR ADDITIONAL SEQUENCE OF OPERATION DETAILS AND DIAGNOSTICS. RELATED RELATED USER USER SETTINGS SETTINGS SETTING SETTING OF OF PREFERRED PREFERRED SOURCE SOURCE SOURCE SOURCE FAILURE FAILURE SETTINGS SETTINGS START DELAY FOR DELAY GENERATOR START LOCATION LOCATION OF SETTINGS OF IN SETTINGS MENUIN MENU SETPOINT-SETPOINT->OPERATION->OPERATION >S1 (S2) ->S1 (S2) SETTINGS SETPOINT-SETPOINT->OP ERATION >OPERATION--->S1 (S2) >S1 (S2) SETTINGS SETTINGS SETPOINT-SETPOINT->OPERATION >OPERATION--->TIMERS >TIMERS

6.0 STANDARD INDICATORS, PUSHBUTTONS, AND ANNUNCIATION

STATE STATE

DESCRIPTION STATE DESC. CONNECTED TO CONNECTED TO PREFERRED PREFERRED SOURCE SOURCE PREFERRED PREFERRED SOURCE FAILURE SOURCE FAILURE PREFERRED PREFERRED SOURCE FAIL SOURCE FAIL TIMER TIMER START STARTTOR GENERA GENERATOR NON-PREFERRED NON-PREFERRED SOURCE SOURCE LE AVAILAB AVAILABLE NON-PREFERRED SOURCE NON-PREFERRED STABILITY TIMER SOURCE STABILITY TIMER COMMIT TRANSFER TO NON-PREFER COMMIT RED SOURCE TRANSFER TO NON-PREFERRED SOURCE (S13)

FUNCTION: WHAT ATS DOES: STAY ON PREFERRED SOURCE UNTIL FAILURE IS DETECTED OR A TEST STAY IS ON PREFERRED SOURCE UNTIL IT DETECTS A FAILURE WITH LOAD INITIATED. (NOTE: JUMP TO STEP #3 IF TEST WITH LOAD)

ZTE OPERATOR DISPLAY (DOOR MOUNTED)

00

CONTROL SENSES THE FAILURE OF THE DESIGNATED PREFERRED SOURCE CONTROL SENSES THE FAILURE OF THE DESIGNATED PREFERRED SOURCE CONTROL INITIATES A TIME DELAY (P) ON STARTING OF GENERATOR IN CONTROL INITIATES A TIME (P) ON STARTING OF GENERATOR IN CASE OF DELAY FAST RETURN OF SOURCE CASE OF FAST RETURN OF SOURCE SENDS START COMMAND TO THE GENRATOR ON EXPIRATION OF TIME CONTROL SENDS A START COMMAND TO THE GENERATOR ON DELAY (P) IN #2 ABOVE EXPIRATION OF THE TIME DELAY (P) IN #2 ABOVE CONTROL DETECTS THAT THE NON-PREFERRED SOURCE IS AVAILABLE CONTROL DETECTS THAT THE NON-PREFERRED SOURCE IS AVAILABLE CONTROL INITIATES A TIME DELAY (W) TO PERMIT ENGINE TO STABILIZE. CONTROL INITIATES A TIME DELAY (W) TO PERMIT THE GENERATOR TO IF (S13) IS SET TO "ENABLED" - CONTROL DISCONNECT THE PREFERRED STABILIZE BEFORE TRANSFER OF THE LOAD. SOURCE AND CONNECT THE NON- PREFERRED SOURCE EVEN IF THE PREFERRED SOURCE RETURNS BEFORE EXPIRATION OF TIME DELAY (W) IF (S13) IS SET TO "ENABLED" - IN CONTROL WILL INITIATE THE TRANSFER #5 ABOVE. SEQUENCE EVEN IF THE PREFERRED SOURCE RETURNS BEFORE EXPIRATION OF TIME DELAY (W) IN #5 ABOVE. IF (S13) IS SET TO "DISABLED" AND PREFERRED SOURCE RETURNS BEFORE EXPIRATION OF TIME DELAY (W) IN #5 ABOVE, CONTROL REMOVES START IF (S13) ISSIGNAL SET TO AND "DISABLED" AND PREFERRED SOURCE RETURNS BEFORE STAYS CONNECTED TO PREFERRED SOURCE. EXPIRATION OF TIMESWITCH DELAY (W) #5 ABOVE, CONTROL REMOVES IF AUTO/MANUAL SETIN TO "AUTO" OR "MANUAL S2 TO S1 START ONLY SIGNAL AND STAYS CONNECTED TO PREFERRED SOURCE. (S5)" ATS WILL CONNECT TO THE NON-PREFERRED SOURCE UPON IF AUTO/MANUAL EXPIRATION SWITCHOF SET TIME TO "AUTO" DELAY OR (W)"MANUAL IN #5 ABOVE. S2 TO S1 ONLY (S5)" ATS WILL AUTOMATICALL INITIATE THE TRANSFER SEQUENCE IF AUTO/MANUAL UPON EXPIRATION SWITCH SET OF TIME TO "MANUAL DELAY (W) S1IN TO #5 S2, ABOVE. S2 TO S2 (S12)" ATS WILL WAIT FOR PERMISSIVE SIGNAL BEFORE CONNECTING TO NONIF PREFERRED AUTO/MANUAL SOURCE. SWITCH PERMISSIVE SET TO "MANUAL SIGNAL IS S1 OPERATOR TO S2, S2 PB TO ON S2 (S12)" 'STATU S' ATS WILL WAIT SCREEN FOR A PERMISSIVE OR CUSTOMER SIGNAL INPUT BEFORE SIGNAL. INITIATING THE TRANSFER SEQUENCE. PERMISSIVE SIGNAL EITHER AN OPERATOR CONTROL WILL CONNECT THE LOAD TO THEIS NON-PREFERRED SOURCE PUSHBUTTON ON THEOF 'STATUS' SCREEN OR CUSTOMER SIGNAL. AFTER EXPIRATION TIME DELAY (W) IN #5 ABOVE) INPUT OR RECIEPT OF PERMISSIVE SIGNAL IN #7 ABOVE) CONTROL WILL OPEN THE PREFERRED SOURCE AND CONNECT LOAD CONTROL WILL DELAY ACTIVATION OF SOURCE 2 FAILURETHE (UNDER TO THE NON-PREFERRED SOURCE AFTER EXPIRATION OF CONNECTION TIME DELAY (W) VOLTS/FREQ) TO PERMIT GENSET TO STABILIZE AFTER OF IN #5 ABOVE) OR RECIEPT OF PERMISSIVE SIGNAL IN #7 ABOVE) LOAD CONTROL WILL DELAY ACTIVATION OF SOURCE 2 FAILURE (UNDER CONTROL WILL TO SENSE THE GENERATOR RETURN OF THE PREFERRE VOLTS/FREQ) PERMIT SETDESIGNATED TO STABILIZE AFTER D SOURCE CONNECTION OF LOAD CONTROL WILL SENSE THE RETURN OF THE DESIGNATED PREFERRED SOURCE, OR INITIATES DETECT THAT THE TEST WITH LOAD OPERATION HAS BEEN CONTROL A TIME DELAY (T) TO PERMIT UTILITY POWER TO CANCELLED. STABILIZE IF AUTO/MANUAL SWITCH IS TO SET TO "AUTO" ATS WILL RECONTROL INITIATESSELECT A TIME DELAY (T) PERMIT UTILITY POWER TO CONNECT TO THE PREFERRED SOURCE UPON EXPIRATION OF TIME DELAY STABILIZE (T) IN #12 ABOVE. IFAUTO/MANUAL AUTO/MANUALSWITCH SELECT SET SWITCH IS SET TOS2 "AUTO" ATS WILL IF TO "MANUAL TO S1 ONLY (S5)" OR AUTOMATICALL THE RE-TRANSFER SEQUENCE UPON IVE "M ANUAL S1 TO S2,INITIATE S2 TO S2 (S12)" ATS WILL WAIT FOR PERMISS EXPIRATION OF TIME (T) INSOURCE. #11. SIGNAL BEFORE RE-CONNECTING TO DELAY PREFERRED PERMISSIVE SIGNAL IS OPERATOR PB ON 'STATUS' SCREEN OR CUSOMER INPUT IF AUTO/MANUAL SWITCH IS SET SIGNAL TO "MANUAL S1 TO S2, S2 TO S2 (S12)" ATS WILL WAIT FOR PERMISSIVE SIGNAL BEFORE INITIATING SOUR THE CE ATS WILL DISCONNECT THE LOAD FROM THE NON-PREFERRED RETRANSFER SEQUENCE. PERMISSIVE SIGNAL IS AFTER EITHER AN OPERATOR AND RECONNECT TO THE PREFERRED SOURCE EXPIRATION OF PUSHBUTTON ON THE 'STATUS' SCREEN OR CUSTOMER INPUT SIGNAL. TIME DELAY (T) IN #11 ABOVE OR RECIEPT OF PERMISSIVE SIGNAL IN #12 ABOVE) ATS WILL DISCONNECT THE LOAD FROM THE NON-PREFERRED SOURCE ATS WILL CONTINUE SEND START SIGNAL TO GENERATOR TO PERMI AND RECONNECT TOTO THE PREFERRED SOURCE AFTER EXPIRATION OF T UNLOADED RUNNING AND COOLDOWN OF GENSET TIME DELAY (T) IN #11 ABOVE OR RECIEPT OF PERMISSIVE SIGNAL IN #12 ABOVE) ATS WILL REMOVAL GENERATOR START SIGNAL AFTER EXPIRATION OF COOLDOWN TIME DELAY #16 ABOVE CONTROL WILL CONTINUE TO SEND STARTIN SIGNAL TO GENERATOR TO PERMIT UNLOADED RUNNING AND COOLDOWN OF GENSET CONTROL WILL REMOVE THE GENERATOR START SIGNAL AFTER EXPIRATION OF COOLDOWN TIME DELAY IN #14 ABOVE

2 3

2.0 STANDARD CONTROL INTERFACE SIGNALS


ZTE SWITCHES SUPPORT THE FOLLOWING STANDARD INTERFACE SIGNALS. SEE CUSTOMER CONNECTION DIAGRAM FOR TERMINAL LOCATIONS AND DETAILS SIGNAL (CODE) ENGINE START SIGNAL (E) REMOTE TEST SIGNAL (Q2) SOURCE 1 CONNECTED TO LOAD (A4) SOURCE 2 CONNECTED TO LOAD (A3) BYPASS MTS CONNECTED TO SOURCE 1 BYPASS MTS CONNECTED TO SOURCE 2 DESCRIPTION START SIGNAL FROM ATS TO GENSET IN EVENT OF LOSS OF PREFERRED SOURCE MAINTAINED CONTACT (CLOSE FOR TEST) FROM BUILDING CONTROL SYSTEM TO SIMULATE AN OUTAGE CONDITION. SWITCH WILL START GENERATOR AND TRANSFER LOAD. SWITCH WILL RETURN TO PREFERRED SOURCE UPON REMOVAL OF TEST SIGNAL. AUXILIARY CONTACT INDICATING LOAD IS CONNECTED TO ATS SOURCE #1 AUXILIARY CONTACT INDICATING LOAD IS CONNECTED TO ATS SOURCE #2 AUXILIARY CONTACT INDICATING THAT OPERATOR HAS MANUALLY BYPASSED SOURCE 1 TO THE LOAD (BYPASS ATS ONLY) AUXILIARY CONTACT INDICATING THAT OPERATOR HAS MANUALLY BYPASSED SOURCE 2 TO THE LOAD (BYPASS ATS ONLY) RATINGS FORM 'C' CONTACTS, 10A @ 28VDC/120VAC FORM 'C' CONTACT, RATED FOR 28VDC, 1A MINIMUM QTY (2) N/O CONTACTS, 10A @ 28VDC/120 VAC QTY (2) N/O CONTACTS, 10A @ 28VDC/120 VAC QTY (1) N/O CONTACT, 10A @ 28VDC/120 VAC QTY (1) N/O CONTACT, 10A @ 28VDC/120 VAC

SOURCE SOURCE RETURN RETURN SETTINGS SETTINGS STABILIZE DELAY TIMER XFER TO NON PREFERRED SRC COMMIT XFER SWITCH COMMIT (S13) XFER SWITCH (S13)

5 5

6 6

SETPOINT-SETPOINT-ERATION >OP >OPERATION--->S1 (S2) >S1 (S2) SETTINGS SETTINGS SETPOINT->OPERATION SETPOINT--->TIMERS >OPERATION->TIMERS HOME->SETPOINT->CONTROL HOME-or GREEN >SETPOINT-'CONTROL' >CONTROL PUSHBUTTO or GREEN 'CONTROL' PUSHBUTTO HOME->SETPOINT->CONTROL HOME-or GREEN >SETPOINT-'CONTROL' >CONTROL PUSHBUTTO or GREEN N 'CONTROL' PUSHBUTTON

INDICATOR SOURCE AVAIL LED'S SOURCE CONN LED'S ALARM LED TD ACTIVE

XFER INHIBIT ALARM RESET TEST INFO CONTROL HOME UP/DOWN ARROW ESC' KEY ENTER' KEY HELP' KEY USB PORT 5 x SOFT KEYS (BLUE ARROWS)

7 7

3.0 NETWORKING AND METERING OPTIONS


ZTE SWITCHES MAY BE CONFIGURED WITH BUILT-IN NETWORKING AND METRING OPTIONS. SEE TRANSFER SWTICH CATALOG NUMBER DIGITS #13 AND #14 AND THE TABLE BELOW TO DETERMINE INSTALLED OPTIONS DIGIT #13 D, G, H, J, L, M, N, OR O DIGIT #14 X S E DESCRIPTION INCLUDES POWER QUALITY METERING. INCLUDES (2) CT'S FOR SINGLE PHASE, (3) CT'S FOR 3PH/3W OR (4) CT'S FOR 3PH/4W SYSTEMS. DESCRIPTION NO COMMUNICATIONS INCLUDES BUILT-IN SERIAL (RS-485) MODBUS RTU COMMUNICATIONS INCLUDES BUILT-IN SERIAL (RS-485) MODBUS RTU COMMUNICATIONS AND ETHERNET/TCPIP COMMUNICATIONS. NOTE: COMMUNICATION PORTS MAY BE USED SIMULTANEOUSLY. 8 89

AUTO/ MANUAL SELECT SWITCH PERMISSIVE AUTO/ MANUAL SELECT SWITCH PERMISSIVE (S5) CONNECT TO NON-PREFERRED SOURCE CONNECT GEN TO NON-PREFERRED STABILIZATION SOURCE TIMER GEN RED PREFER STABILIZATION SOURCE TIMER AVAILABLE PREFERRED PREFERRED SOURCE SO URCE RETURN AVAILABLE TIMER PREFERRED SOURCE RETURN TIMER AUTO/MANUAL SELECT SWITCH PERMISSIVE AUTO/MANUAL SELECT SWITCH PERMISSIVE (S5) RE-CONNECT TO PREFERRED SOURCE RE-CONNECT TO GENERATOR PREFERRED COOLDOWN SOURCE GENERATOR STOP GENERATOR COOLDOWN GENERATOR STOP

AUTO /MAN SELECT SWITCH AUTO /MAN SELECT SWITCH

DESCRIPTION S1 (GREEN) AND S2 (RED) INDICATE SOURCE HEALTHY S1 (GREEN) AND S2 (RED) INDICATE SOURCES CONNECTED TO LOAD RED LED, INDICATIES AN ACTIVE ALARM. SEE STATUS SCREEN (HOME->STATUS) FOR DETAILED ALARM MESSAGE RED LED, INDICATES CONTROLLER IS TIMING FOR NEXT ACTION. SEE STATUS SCREEN (HOME-->STATUS) FOR DESCRIPTION OF THE TIME DELAY AND DISPLAY OF REMAINING TIME INDICATES ATS IS READY TO TRANSFER TO A SOURCE, BUT IS RECEIVING AN INHIBIT TRANSFER SIGNAL. INHIBIT COMMAND MAY BE LOCAL DISCONNECT SWITCH (DS), LOCAL OR REMOTE AUTO/MANUAL SWITCH, OR INHIBIT TRANSFER SIGNALS USED TO RESET LATCHED ALARM CONDITIONS. JUMP BUTTON TO TEST MENU. JUMP BUTTON TO RUN REPORT. JUMP BUTTON TO CONTROL MENU. JUMP BUTTON TO HOME SCREEN PERMITS UP/DOWN SCROLLING WITHIN SCREEN BRINGS OPERATOR TO PREVIOUS SCREEN SELECTS ITEMS WITHIN MENU SYSTEM AND CONFIRMS OPERATIONS TRIGGERS MENU-DEPENDENT HELP POPUP MESSAGE PERMITS CALIBRATION UPLOAD/MODIFY/DOWNLOAD USING ENERVISTA SETUP SOFTWARE. MENU-DEPENDENT PUSHBUTTONS. FUNCTION OF PUSHBUTTON IS INDICATED ON GRAPHICAL SCREEN ABOVE BUTTON.

GEN DIP TIMER TIME DELAY SOURCE FOR GEN RETURN SAG SETTINGS SOURCE X FER PREF RETURN SOURCE SETTINGS TIMER DELAY XFER TO PREFERRED SRC AUTO /MAN SELECT SWITCH AUTO /MAN SELECT SWITCH

9 10

SETPOINT->OPERATION -->TIMERS SETPOINT-SETPOINT->OPERATION >OPERATION--->S1 (S2) >TIMERS SETTINGS SETPOINT->OPERATION-SETPOINT->S1 (S2) >OPERATION SETTINGS -->TIMERS SETPOINT->OPERATION-HOME->TIMERS >SETPOINT->CONTROL or GREEN HOME-NTROL' 'CO >SETPOINT-PUSHBUTTO >CONTROL N or GREEN 'CONTROL' PUSHBUTTON

10 11

4.0 NON-STANDARD CONTROL OPTIONS


THE FOLLOWING OPTIONS MAY BE INSTALLED ON THE ATS. SEE TRANSFER SWITCH CATALOG NUMBER DIGITS #9, #13, AND #14 AND THE TABLE BELOW TO DETERMINE INSTALLED OPTIONS ORDER CODE DIGIT # VALUE FEATURE FEATURE DESCRIPTION

11

12

12

13

A, E, F, G, H, I, J, OR 0

REMOTE LOAD SHED

B, C, OR D

AUTO LOAD SHED

PROVISIONS ON POWER PANEL TO PERMIT TRANSFER OF SWITCH FROM LIVE NONPREFERRED SOURCE TO EITHER DEAD CENTER POSITION (DELAY-TYPE AND CLOSED TYPE ATS ONLY) OR DE-ENERGIZED PREFERRED SOURCE. ACTIVATES ON REMOTE CONTACT SIGNAL FROM BUILDING AUTOMATION OR PARALLELING SWITCHGEAR SYSTEM. SWITCH DISCONNECTS THE LOAD IMMEDIATELY UPON RECEIPT OF THE LOAD SHED SIGNAL, AND RETURNS TO LIVE SOURCE AFTER REMOVAL OF LOAD SHED SIGNAL. CONTROL INCLUDES PROVISIONS FOR AUTOMATIC DISCONNECTION FROM NON-PREFERRED SOURCE IN EVENT OF UNDERFREQUENCY, UNDERVOLTAGE, OR OVERPOWER/KW. EACH SETPOINT IS INDEPENDENTLY SETABLE, WITH INDIVIDUAL TIME DELAYS. IF SWITCH IS CONFIGURED WITH LOAD SHED (DIGIT #13 ABOVE) SWITCH CAN BE CONFIGURED TO MOVE TO CENTER OFF OR DE-ENERGIZED NON-PREFERRED SOURCE. IF SWITCH DOES NOT INCLUDE LOAD SHED, A USER-CONFIGURABLE OUTPUT MAY BE ASSIGNED TO AUTO LOAD SHED FEATURE TO PERMIT SHUNT TRIP OF DOWNSTREAM LOAD(S). ONCE ACTIVATED, AUTO LOAD SHED REQUIRES MANUAL/USER RESET VIA MENU RESET PUSHBUTTON OR CONFIGURABLE AUTO LOAD SHED RESET INPUT. CHICAGO ALARM/CTAP FUNCTION. INCLUDES AUDIBLE ALARM UPON CONNECTION TO NON-PREFERRED SOURCE. EXTENDED ENGINE START RELAY - ADJ 0.5 SEC TO 300 SEC INCLUDES (2) CT'S FOR SINGLE PHASE, (3) CT'S FOR 3PH/3W OR (4) CT'S FOR 3PH/4W SYSTEMS. ADDS POWER QUALITY METERING.

13

ELEMENT LAST & NEXT EXERCISE TIME LAST TRANSFER TIMES s1-->s2, AND s2-->S1 SWITCH AMP, VOLT RATING AND TYPE PREFERRED SOURCE SETTING SOURCE VOLTAGES, FREQUENCY LOAD AMPS, KW, KVAR, PF (REQUIRES METERING OPTION) ALARM STATUS, STATUS OF TIMERS CURRENT CONFIGURATION / ASSIGNENT OF CUSTOMER INPUTS CURRENT CONFIGURATION / ASSIGNENT OF CUSTOMER OUTPUTS CURRENT CONFIGURATION OF LOAD CONTROL RELAYS (ELEVATOR, LOAD PRESIGNAL) S1 FAIL/RESTORE SETTINGS S2 FAIL/RESTORE SETTINGS TIME DELAY ADJUSTMENTS EVENT LOG STATISTICS CONTROL SWITCHES

LOCATION IN MENU HOME SCREEN HOME SCREEN HOME SCREEN HOME SCREEN HOME-->VALUES HOME-->VALUES HOME-->STATUS HOME-->STATUS-->INPUTS HOME-->STATUS-->OUTPUTS HOME-->SETPOINT-->CONFIG HOME-->SETPOINT-->OPERATION-->S1 SETTING HOME-->SETPOINT-->OPERATION-->S2 SETTING HOME-->SETPOINT-->OPERATION-->TIMERS HOME-->DIAG HOME-->DIAG-->STATS HOME-->SETPOINT-->CONTROL OR GREEN 'CONTROL' PUSHBUTTON HOME-->EXERCISER HOME-->EXERCISER-->SETUP-->ENTER HOME-->EXERCISER-->TEST OR GREEN 'TEST' PUSHBUTTON

14 13 15 14 15

ENGINE COOLDOW N TIMER DELAY FOR ENGINE COOLDOWN

SETPOINT->OPERATION -->TIMERS SETPOINT->OPERATION->TIMERS

EXERCISER STATUS SET EXERCISER TYPE TEST

13 13 13

B, E, H, I, J, K, L, OR M C, F, I, J, K, M, N, OR O D, G, H, J, L, M, N OR O

CTAP P2 MPQ

g ZENITH CONTROLS
CHICAGO, IL 60609 USA

REVISION:

ECN :

S-8713
ENG:

THIS DRAWING CONTAINS PROPRIETARY AND CONFIDENTIAL INFORMATION.


DUPLICATION, REPRODUCTION OR USE OF THIS DOCUMENT OR ITS CONTENTS IN ANY FORM OTHER THAN AS EXPRESSLY PERMITTED BY ZENITH CONTROLS, INC. IS STRICTLY PROHIBITED.

DATE: 04/30/08

DRAFT: CE

CE

APPLICATION MX350 JOB / MODEL : MX350

DRAWING NUMBER:

DESCRIPTION : ESTABLISHED

91A-2000

1 OF 8

REV:

ELECTRICAL SCHEMATIC DRAWINGS - GE ZENITH ZTE SERIES TRANSFER SWITCHES - OPEN TRANSITION TYPE - 225 TO 400A LEGEND, FEATURES, OPERATION, ACCESSORIES
THE FOLLOWING SETTINGS AND ADJUSTMENTS ARE AVAILABLE WITHIN THE ZTE TRANSFER SWITCH. REFER TO THE ZTE OPERATIONS AND MAINTENANCE MANUAL FOR ADDITIONAL DETAILS. NOTE: SWITCH NOMINAL VOLTAGE AND FREQUENCY SETTINGS ARE INDICATED ON THE NAMEPLATE.

10.0 PROGRAMMABLE ENGINE EXERCISER


A PROGRAMMABLE ENGINE EXERCISER IS PROVIDED AS A STANDARD CONTROL FEATURE ON ALL ZTE TRANSFER SWITCHES. TWO (2) DIFFERENT TYPES OF EXERCISERS ARE CONFIGURABLE IN THE CONTROLLER: PERIODIC EXERCISER: IF ENABLED, THE ATS WILL PERFORM A TEST FUNCTION ON A PERIODIC BASIS, DEPENDING ON THE EXERCISER SETTING TYPE. o PROGRAMMBLE TYPES: THE TYPE IS USER PROGRAMMABLE AS DAILY, WEEKLY, 14 DAYS, OR 28 DAYS o # PROGRAMABLE EVENTS: UP TO (7) SEPARATE TEST EVENTS MAY BE PROGRAMMED, EACH WITH START TIME, START DATE, AND RUN DURATION. o OPERATION DESCRPTION: EACH TEST EVENT WILL AUTOMATICALLY RE-INITIATE EVERY DAY, WEEK, 14 DAYS, OR 28 DAYS IN ACCORDANCE WITH THE EXERCISER SETTING. o RANGES: ENGINE RUN DURATION RANGE IS 0 MIN: 1 SEC TO 59 MIN: 59 SEC CLOCK EXERCISER: IF ENABLED, THE ATS WILL PERFORM A TEST FUNCTION AT SPECIFIC DATES/TIMES SETUP IN THE CONTROLLER BY THE USER/OPERATOR. o PROGRAMMBLE TYPES: THE TYPE IS USER PROGRAMMABLE AS 365 DAYS o # PROGRAMABLE EVENTS: UP TO (24) SEPARATE TEST EVENTS MAY BE PROGRAMMED, EACH WITH START TIME, START DATE, AND RUN DURATION. o OPERATION DESCRPTION: EACH TEST EVENT WILL BE INITIATED AT THE DATE/TIME SET FOR EACH EVENT. o RANGES: RUN DURATION RANGE IS 0 MIN: 1 SEC TO 59 MIN: 59 SEC

12.0 DRAWING LEGEND


ITEM/SYMBOL AC AUX A3-1,2,3 A4-1,2,3 CE CEO CN SEO CPU CT1,2,3 CTTB CV DC DS E1,2,3 EN K- CARD L-CARD N1,2,3 NN OIP PA3 PSU Q2 RCE RCN RSS SCR-E SCR-EO SCR-N SCR-NO SE SEO YES SLE SLN SN SNO N/A N/A NO SOL-1 SOL-2 SS T1,2,3 TN UTA VT1 VT2 DESCRIPTION CONNECTION PLUG CONNECTION PLUG SOURCE 2 POSITION CONTACT SOURCE 1 POSTION CONTACT SOURCE 2 MAIN TRANSFER OPRATOR SOURCE 2 OPEN MAIN TRANSFER OPRATOR SOURCE 1 MAIN TRANSFER OPRATOR SOURCE 1 OPEN MAIN TRANSFER OPRATOR CENTRAL PROCESSING UNIT CURRENT TRANSFORMER CURRENT TRANSFORMER TERMINAL BLOCK CONTROL VOLTAGE CONNECTION PLUG DISCONNECT SWITCH SOURCE 2 EMERGENCY LINE SOURCE 2 EMERGENCY NEUTRAL LINE MX350 NON CONFIGURABLE INPUT/OUTPUT CARD MX350 CONFIGURABLE INPUT/OUTPUT CARD SOURCE 1 EMERGENCY LINE SOURCE 1 EMERGENCY NEUTRAL LINE OPERATOR INTERFACE PANEL CONNECTION PLUG MX350 POWER SUPPLY MODULE REMOTE SYSTEM TEST CONTACT RECTIFIER CAPACITOR, EMERGENCY RECTIFIER CAPACITOR, NORMAL SECONDARY SOLENOID RECTIFIER SILICON CONTROL RECTIFIER, COMMAND TO CLOSE SOURCE 2 SILICON CONTROL RECTIFIER, COMMAND TO OPEN SOURCE 2 SILICON CONTROL RECTIFIER, COMMAND TO CLOSE SOURCE 1 SILICON CONTROL RECTIFIER, COMMAND TO OPEN SOURCE 2 SOURCE 2 LIMIT SWITCH (CLOSE WHEN ATS IS IN SOURCE 2 POSITION SOURCE 2 LIMIT SWITCH (CLOSE WHEN ATS IS IN SOURCE 2 OPEN POSITION) TRANSFER TO EMERGENCY RELAY TRANSFER TO NORMAL RELAY SOURCE 1 LIMIT SWITCH (CLOSE WHEN ATS IS IN SOURCE 1 POSITION SOURCE 1 LIMIT SWITCH (CLOSE WHEN ATS IS IN SOURCE 2 OPEN POSITION) LIMIT SWITCH SOLENOID, SOURCE 1 LIMIT SWITCH SOLENOID, SOURCE 2 SECONDARY SOLENOID LOAD LINES LOAD NEUTRAL LINE UNIVERSAL TRANSFORMER ASSEMBLY SOURCE 1 VOLTAGE SENSING CARD SOURCE 2 VOLTAGE SENSING CARD

7.0 NORMAL/PREFERRED & EMERGENCY/ALTERNATE SOURCE FAILURE SETTINGS


PARAMETER UNDERVOLTAGE UNDERFREQUENCY OVERVOLTAGE OVERFREQUENCY VOLTAGE IMBALANCE * VOLTAGE IMBALANCE TIME DELAY * RANGE OF SETTINGS 75% TO 99% NOMINAL 45.0 TO 59.9 HZ 105% TO 110% NOMINAL 50.1 TO 63.0 HZ 5% TO 20% PHASE-PHASE 1 TO 60 SECONDS DEFAULT SETTING 80% UTIL: 59 HZ GEN: 54 HZ 110% OFF 10% 30 SEC LOCATION ON DISPLAY
(FOLLOW LISTED NAVIGATION)

HOME>SETPOINT>OPERATION>S1 SETTINGS (OR S2 SETTINGS) SAME AS ABOVE SAME AS ABOVE SAME AS ABOVE HOME>SETPOINT>CONTROL> ALARMS HOME>SETPOINT>CONTROL> ALARMS

8.0 NORMAL/PREFERRED & EMERGENCY/ALTERNATE SOURCE RETURN SETTINGS


PARAMETER UNDERVOLTAGE UNDERFREQUENCY OVERVOLTAGE OVERFREQUENCY VOLTAGE IMBALANCE * RANGE OF SETTINGS 85% TO 100% NOMINAL 45.1 TO 60.0 HZ 103% TO 108% NOMINAL 50.0 TO 62.9 HZ 5% TO 20% PHASE-PHASE DEFAULT SETTING 90% UTIL: 59.5 HZ GEN: 57 HZ 105% OFF 10% 30 SEC LOCATION ON DISPLAY
(FOLLOW LISTED NAVIGATION)

HOME>SETPOINT>OPERATION>S1 SETTINGS (OR S2 SETTINGS) SAME AS ABOVE SAME AS ABOVE SAME AS ABOVE HOME>SETPOINT>CONTROL> ALARMS HOME>SETPOINT>CONTROL> ALARMS

11.0 STANDARD CONTROL SWITCHES


SWITCH FUNCTION (CODE) PREFERRED SOURCE SELECT SWITCH (S3) DESCRIPTION LOCATION OF APPLICABLE CONTROL SETTINGS IN ZTE DISPLAY HOME-->SETPOINT->CONTROL or GREEN 'CONTROL' PUSHBUTTON ADJUST RANGE FACT ORY DEFAU LT S1 REMOTE ACTIVATION PERMITTED (CUSTOMER CONFIG INPUT) YES

VOLTAGE IMBALANCE 1 TO 60 SECONDS TIME DELAY * * AVAILABLE 3-PHASE UNITS ONLY

PERMITS USER SELECTION OF THE PREFERRED SOURCE IF SET TO ENABLED/YES: CONTROL WILL CONNECT TO THE NON-PREFERRED SOURCE EVEN IF PREFERRED RETURNS BEFORE EXPIRATION OF PREFERRED SOURCE FAILURE TIME DELAY IF SET TO DISABELED/NO: CONTROL WILL REMOVE START SIGNAL AND STAY CONNECTED TO THE PREFERRED SOURCE IF PREFERRED RETURNS BEFORE EXPIRATION OF PREFERRED SOURCE FAILURE TIME DELAY INITIATES A TEST WITH LOAD, USING FIXED (SMALL) TIME DELAY SETTINGS

S1 OR S2

9.0 TIME DELAY SETTINGS


DESCRIPION ON DISPLAY DELAY FOR GENERATOR START DELAY XFER TO NONPREFERRED SRC TIME DELAY FOR GEN SAG DELAY XFER TO PREFERRED SRC DELAY FOR ENGINE COOLDOWN EXTENDED DESCRIPION DELAY FROM FAILURE OF PREFERRED SOURCE TO SENDING OF START SIGNAL TO GENERATOR DELAY ON TRANSFER TO NONPREFERRED SOURCE AFTER SENSING THAT SOURCE IS HEALTHY DELAY ON SENSING OF ALTERNATE SOURCE FAILURE TO PERMIT GENSET TO RECOVER FROM LOAD IMPACT DELAY ON RE-TRANSFER TO PREFERRED SOURCE TO ENSURE SOURCE IS HEALTHY AND 2ND FAILURE IS UNLIKELY DELAY TO PERMIT UNLOADED RUNNING OF GENSET FOR COOLDOWN SETTING RANGE 0 TO 10 SEC
(0 TO 259 MIN IF 120 VAC EXTERNAL POWER SUPPLY CONNECTED)

DEFAULT SETTING

LOCATION ON DISPLAY
(FOLLOW LISTED NAVIGATION)

COMMIT TRANSFER TO S2 (S13)

HOME-->SETPOINT->CONTROL or GREEN 'CONTROL' PUSHBUTTON

ENABLED (YES), DISABLED (NO)

DISAB ELED (NO)

3 SEC.

HOME>SETPOINT> OPERATION>TIMERS FAST TEST SWITCH

0 SEC TO 259 MINUTES (15,540 SEC).


NOTE: BYPASS OF TIME DELAY PERMITTED VIA PUSHBUTTON ON STATUS SCREEN

3 SEC.

SAME AS ABOVE TEST WITH LOAD (TSL) INITIATES A TEST WITH LOAD, USING SAME TIME DELAY SETTINGS AS THOSE FOR ACTUAL OUTAGE CONDITION

0 SEC TO 30 SEC.
NOTE: BYPASS OF TIME DELAY PERMITTED VIA PUSHBUTTON ON STATUS SCREEN

OFF/ 0 SEC. 30 MINUTES 5 MINUTES

SAME AS ABOVE TEST NO LOAD (TSNL) INITIATES A STARTING OF GENERATOR BY ATS, BUT NO TRANSFER OF LOAD AWAY FROM PREFERRED SOURCE IF SET TO "AUTO": SWITCH WILL AUTOMATICALY CONNECT TO THE SOURCES UPON EXPIRATION OF ASSOCIATED TIME DELAYS IF SET TO "MANUAL S2 TO S1 ONLY (S5)" SWITCH WILL NOT AUTOMATICALLY RETURN TO PREFERRED SOURCE. SWITCH WILL WAIT FOR OPERATOR TO GIVE PERMISSIVE [SOFT SWITCH ON STATUS SCREEN] OR RECEIPT OF USER CONFIGURABLE CUSTOMER INPUT CONFIGURED TO "MANUAL XFER S2 TO S1 (S5)" FEATURE IF SET TO "MANUAL S1 TO S2, S2 TO S1 (S12)" SWITCH WILL NOT AUTOMATICALLY CONNECT TO THE NON-PREFERRED SOURCE, OR RETURN TO PREFERRED SOURCE. SWITCH WILL WAIT FOR OPERATOR TO GIVE PERMISSIVE [SOFT SWITCH ON STATUS SCREEN] OR RECEIPT OF USER CONFIGURABLE CUSTOMER INPUT CONFIGURED TO "MANUAL XFER S1 -2 AND S2-1 (S12)" FEATURE

0 SEC TO 259 MINUTES.


NOTE: BYPASS OF TIME DELAY PERMITTED VIA PUSHBUTTON ON STATUS SCREEN

SAME AS ABOVE

HOME-->EXERSISER->TEST-->FASTTEST or GREEN 'TEST' PUSHBUTTON THEN 'FASTTEST' HOME-->EXERSISER->TEST-->XFERLOAD or GREEN 'TEST' PUSHBUTTON THEN 'XFERLOAD' HOME-->EXERSISER->TEST-->NOXFER or GREEN 'TEST' PUSHBUTTON THEN 'NOXFER'

N/A

N/A

YES

N/A

N/A

YES

0 MIN:0 SEC TO 60MIN:0SEC.


NOTE: BYPASS OF TIME DELAY PERMITTED VIA PUSHBUTTON ON STATUS SCREEN

SAME AS ABOVE

9.5 IN-PHASE MONITOR FOR TRANSFER OF LOADS


CONTROL INCLUDES AN IN-PHASE MONITOR FEATURE AS A STANDARD FEATURE ON ALL SWITCHES CONFIGURED FOR UTILITY-TO-GENERATOR TRANSFER. SWITCHES CONFIGURED FOR UTILITY-TO-UTILITY OR GENERATOR-TOGENERATOR TRANSFER DO NOT INCLUDE THE INPHASE MONITOR FUNCTION, AS THIS FUNCTION MAY INHIBIT NORMAL OPERATION OF THE TRANSFER SWITCH DESCRIPTION: IF ENABLED, CONTROL WILL INHIBIT THE TRANSFER OF LOADS BETWEEN TWO LIVE SOURCES UNTIL THE PHASE ANGLE OF BOTH SOURCES IS WITHIN A PRE-SET PHASE DEGREE WINDOW. THE IN-PHASE MONITOR WILL BE ACTIVATED DURING TRANSFER TO THE NON-PREFERRED SOURCE DURING A TEST WITH LOAD, OR DURING RETURN TO THE PREFERRED SOURCE (AFTER A TEST WITH LOAD OR OUTAGE EVENT). FACTORY SETTING: 10 ELECTRICAL DEGREES

AUTO/ MANUAL SELECT SWITCH (S5, S12)

HOME-->SETPOINT->CONTROL or GREEN 'CONTROL' PUSHBUTTON

"AUTO", "MANUAL S1 TO S2, S2 TO S1 (S12)", "MANUAL S2 TO S1 ONLY (S5)"

AUTO

YES

g ZENITH CONTROLS
CHICAGO, IL 60609 USA

REVISION: A DATE: 04/30/08

ECN: S-8713 DRAFT: CE ENG: CE

THIS DRAWING CONTAINS PROPRIETARY AND CONFIDENTIAL INFORMATION.


DUPLICATION, REPRODUCTION OR USE OF THIS DOCUMENT OR ITS CONTENTS IN ANY FORM OTHER THAN AS EXPRESSLY PERMITTED BY ZENITH CONTROLS, INC. IS STRICTLY PROHIBITED.

APPLICATION MX350

DRAWING NUMBER:

DESCRIPTION: ESTABLISHED

JOB/MODEL: MX350

91A-2000

2 OF 8

REV:

GE ZENITH ZTE SERIES TRANSFER SWITCHES ZTE SERIES CATALOG NUMBER SCHEME, USER CONFIGURABLE I/O
13.0 ATS CATALOG NUMBER SCHEME 14.0 USER CONFIGURABLE I/O
ZTE SWITCHES INCLUDE USER CONFIGURABLE INPUTS & OUTPUTS (I/O) THAT MAY BE FIELD-RECONFIGURED TO MEET SITE NEEDS. THE AMOUNT OF I/O DEPENDS ON THE INSTALLED CONTROL CONFIGURATION GROUP (SEE TABLE BELOW) CONFIGURATION OF THE I/O AT TIME OF FACTORY SHIPMENT IS SHOWN ON THE NAMEPLATE ADJACENT TO THE CUSTOMER CONNECTIONS TERMINAL STRIP AND THE ATTACHED TABLE. NEW CONTROL FEATURES MAY BE ADDED IN FIELD BY SETTING THE CURRENT CONTROL FEATURE I/O ADDIGNEMENT TO N/A AND REALLOCATING THE I/O POINT TO A NEW FEATURE. SEE O&M MANUAL FOR COMPLETE PROCEDURE FOR I/O RE-ASSIGNMENT AND LIST OF AVAILABLE FEATURES. TYPE (INPUT/ OUTPUT) OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT ACTIVE WHEN SWITCH IN EXERCISE MODE OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT INPUT INPUT INPUT INPUT INPUT INPUT INPUT INPUT INPUT INPUT INPUT INPUT OUTPUT OUTPUT OUTPUT OUTPUT INPUT INPUT "A" 4 IN/ 4 OUT OUTPUT 1 OUTPUT 2 * * * * * * * N/A N/A * * * OUTPUT 3 * * INPUT 4 * INPUT 1 * INPUT 3 INPUT 2 * * * * * * OUTPUT 4 * * N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

Z1 0 A 2 S 1 A A 1 0 A X X X X XX
DIGIT #1, #2 PRODUCT TYPE Z1 - ATS Z2 - BYPASS ATS OPERATION O OPEN TRANSITION D DELAYED TRANSITION C CLOSED TRANSITION AMPERE RATING A 40A B - 80A C 100A, D 150A, F 225A G- 260A, I 400A, J-600A, K-800A, L-1000A M-1200A, N-1600A, O-2000A, Q-3000A, R-4000A # POLES 2 2 POLE, 3- 3 POLE, 4- 4 POLE DIGIT #6 APPLICATION/SOURCE TYPES S UTILITY TO GENERATOR U UTILTY TO UTILITY G GENERATOR TO GENERATOR 1 ENCLOSURE TYPE X - OPEN (NONE), A NEMA 1, B NEMA 1A C NEMA 3R, D NEMA 3R W/ HEATER E NEMA 4, F NEMA 12, G NEMA 4X CONTROL OPTION PACKAGE A, B, C, OR D: SEE SHEET #1 FOR DESCRIPTION VOLTAGE RATING 2-DIGIT FACTORY CODE. SEE ATS NAMEPLATE FOR RATED VOLTAGE LUG OPTIONS 2-DIGIT FACTORY CODE. SEE O&M MANUAL FOR DETAILS METERING & ACCESSORIES CODE A THRU O OR X. SEE SHEET #1 FOR FURTHER DETAILS COMMUNICATIONS OPTIONS CODE X, S, OR E. SEE SHEET #1 FOR FURTHER DETAILS GROUND BUS OPTIONS CODE X, OR 1-8. SEE O&M FOR DETAILS TVSS OPTIONS CODE X, OR A-G. SEE O&M FOR DETAILS BATTERY CHARGER OPTION CODE X, OR 1-4. SEE O&M FOR DETAILS X

FACTORY DEFAULT I/O CONFIGURATION


OPTION CODE A1 A1E A4 A3 A34N AB3, AB4 EXC ESS ATS2, ATS1 MTS2S1 MTS1S2 TIS2S1, TIS1S2 ALM FTS1 FTS2 NIA CTAP RES TSNL BYPTR BYPWR Q7 Q3 S5R YNR S12R YER S3R S13R LCE1, LCL1 LCE2, LCL2 LCE3-6, LCL3-6 ALS LS1R LS1KW UVS1, UVS2 OVS1/2 UFS1, UFS2 OFS1/2 LLPFA VTHDS1, VTHDS2 CTA LOKWA OCAPA/B/C, NOCA VIAS1, VIAS2 CIA "B" 4 IN/ 4 OUT OUTPUT 1 OUTPUT 2 * * * * * * * N/A N/A * * * OUTPUT 3 * * INPUT 4 * INPUT 1 * INPUT 3 INPUT 2 * * * * * * OUTPUT 4 * * * * * * * * * * * * * * * * "C" 8 IN/ 8 OUT OUTPUT 1 OUTPUT 2 * * * * OUTPUT 6 * * N/A N/A * OUTPUT 7 * OUTPUT 3 OUTPUT 8 * INPUT 4 * INPUT 1 INPUT 5 INPUT 3 INPUT 2 * INPUT 8 INPUT 6 INPUT 7 * * OUTPUT 4 OUTPUT 5 * * * * * * * * * * * * * * * "D" 12 IN/ 12 OUT OUTPUT 1 OUTPUT 2 OUTPUT 12 OUTPUT 11 * * OUTPUT 6 * * N/A N/A * OUTPUT 7 OUTPUT 9 OUTPUT 3 OUTPUT 8 * INPUT 4 * INPUT 1 INPUT 5 INPUT 3 INPUT 2 * INPUT 8 INPUT 6 INPUT 7 INPUT 12 * OUTPUT 4 OUTPUT 5 * OUTPUT 10 INPUT 9 INPUT 10 * * * * * * * * * * * "M" 4 IN/ 4 OUT OUTPUT 1 OUTPUT 2 * * * * * * N/A OUTPUT 3 OUTPUT 4 N/A * * * N/A * INPUT 4 Input 3 N/A N/A N/A N/A N/A INPUT 2 N/A INPUT 2 N/A N/A * * * N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A RECORD SITE SETTING

FEATURE SOURCE 1 FAILURE SOURCE 2 FAILURE CONNECTED TO SOURCE 1 CONNECTED TO SOURCE 2 CONNECTED TO CENTER (DELAY TYPE ATS ONLY) BYPASS ATS ON SOURCE 1 (BYPASS ATS ONLY) SWITCH EXERCISING ENGINE START SIGNAL ACTIVE AUTO TRANSFER OCCURRED S1S2 OR S2S1 MANUAL TRANSFER TO S2 OCCURED MANUAL TRANSFER TO S1 OCCURED TRANSFER INHIBIT (S2 TO S1, OR S1 TO S2) ON COMMON ALARM (ANY ALARM ACTIVE) FAIL TO TRANSFER TO SOURCE 1 ALARM FAIL TO TRANSFER TO SOURCE 2 ALARM ATS NOT IN AUTO TRANSFER TO SOURCE 2 ALARM (CHICAGO/CTAP) REMOTE ENGINE START NO LOAD TEST BYPASS TIME DELAY ON TRANSFER TO SOURCE 1 BYPASS TIME DELAY ON TRANSFER TO SOURCE 2 INHIBIT TRANSFER TO SOURCE 1 INHIBIT TRANSFER TO SOURCE 2 AUTO/MAN TRANSFER SELECT - SOURCE 2 TO SOURCE 1 MANUAL RE-TRANSFER TO SOURCE 1 AUTO/MAN TRANSFER SELECT - SOURCE 2 TO SOURCE 1 AND SOURCE 1 TO SOURCE 2 MANUAL RE-TRANSFER TO SOURCE 2 PRIME SOURCE SELECTION COMMIT/NO COMMIT TO TRANSFER TO SOURCE 2 PROGRAMMABLE LOAD CONTROL RELAY #1 PROGRAMMABLE LOAD CONTROL RELAY #2 PROGRAMMABLE LOAD CONTROL RELAY #3-#6 AUTO LOAD SHED REMOTE RESET AUTO LOAD SHED LOCAL/REMOTE SELECT AUTO LOAD SHED KW BYPASS SOURCE 1 (OR SOURCE 2) UNDERVOLTAGE SOURCE 1 (OR SOURCE 2) OVERVOLTAGE SOURCE 1 (OR SOURCE 2) UNDERFREQUENCY SOURCE 1 (OR SOURCE 2) OVERFREQUENCY LOW PF ALARM SOURCE 1 (OR SOURCE 2) VOLTAGE THD% ALARM LOAD CURRENT THD% ALARM LOAD KW (OVERLOAD) ALARM OVERCURRENT ALARM (PHASE A, B, C, OR N) SOURCE 1 (OR SOURCE 2) VOLTAGE IMBALANCE LOAD CURRENT UNBALANCE ALARM USER CONFIGURABLE DIGITAL ALARMS DIGITAL INPUTS (UP TO 10) FOR USER CONFIG ALARMS &/OR FLEXLOGIC USER CONFIG DIGITAL ALARMS

EXTENDED DESCRIPTION

DIGIT #3

SOURCE STATUS SWITCH POSITION

DIGIT #4

DIGIT #5

SWITCH STATUS & DIAGNOSTICS

POSTIVE INDICATION OF XFER NOT RECEIVED BY CONTROL SWITCH IS INIHIBITED FROM AUTO OPERATION

DIGIT #7 DIGIT #8

REMOTE CONTROL/ BUILDING INTERFACE

ATS WILL RESPOND WITH START SIGNAL TO GEN ATS WILL START GEN, BUT NOT TRANSFER LOAD WILL CAUSE IMMEDIATE CONNECTION TO SOURCE 1 WILL CAUSE IMMEDIATE CONNECTION TO SOURCE 1 WILL IHHIBIT ATS FROM CONNECTING LOAD TO SOURCE 1 WILL IHHIBIT ATS FROM CONNECTING LOAD TO SOURCE 2 REMOTE CONTROL OF AUTO/MAN SWITCH PERMISSIVE SIGNAL TO TRANSFER IN MANUAL MODE REMOTE CONTROL OF AUTO/MAN SWITCH PERMISSIVE SIGNAL TO TRANSFER IN MANUAL MODE REMOTE SELECTION OF PRIME SOURCE REMOTE SELECTION OF COMMIT/NO COMMIT XFER PROG. AS ELEVATOR PRE-SIGNAL OR LOAD DISC. PROG. AS ELEVATOR PRE-SIGNAL OR LOAD DISC. PROG. AS ELEVATOR PRE-SIGNAL OR LOAD DISC. REMOTE RESET FOR LATCHED AUTO LOAD SHED REMOTE SELECTION TO SHED ATS OR PICKUP CONTROL RELAY ON ACTIVATION OF AUTO LOAD SHED ENABLE/DISABLE ALS PICKUP ON OVER KW

DIGIT #9 DIGIT #10,#11

PROGRAMMABLE LOAD CONTROL RELAYS AUTO LOAD SHED

DIGIT #12

OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT UP TO 10 ALARMS, ACTIVATED BY INPUTS & TIME DELAY SETTING. INCLUDE USER-PROG MESSAGE DISPLAY OUTPUT CONTACT FOR PROGRAMMED DIGITAL ALARMS

DIGIT #13

USER CONFIGURABLE ANALOG ALARMS

DIGIT #14

DIGIT #15 DIGIT #16 DIGIT #17 DIGIT #18

INPUT OUTPUT

CCDI-x CCAD-x

N/A N/A

* *

* *

* *

N/A N/A

g
REVISION: A DATE: 04/30/08 ECN : S-8713 DRAFT: CE ENG:

ZENITH CONTROLS INC.,


CHICAGO, IL 60609 USA

THIS DRAWING CONTAINS PROPRIETARY AND CONFIDENTIAL INFORMATION.


DUPLICATION, REPRODUCTION OR USE OF THIS DOCUMENT OR ITS CONTENTS IN ANY FORM OTHER THAN AS EXPRESSLY PERMITTED BY ZENITH CONTROLS, INC. IS STRICTLY PROHIBITED.

CE

APPLICATION MX350 JOB/MODEL : MX350

DRAWING NUMBER:

DESCRIPTION : ESTABLISHED

91A-2000

3 OF 8

REV: