You are on page 1of 4

INDUSTRIAL WATER CHILLERS HGL

PROFILE The Heavygel compact industrial chillers of the HGL series have been designed to cope with the most demanding cooling requirements of high outputs in various industrial processes. They are air-cooled units with axial fans for external installation and equipped with screw compressors.

The HGL series comes in two configurations:

with only the internal chiller pump (M) for systems with external tank and user pump(s) without any pump (N)

Tropicalization fitted as standard for continuous operation in environments up to +45C

The Heavygel series uses ecological gas, in respect of the European directives for environmental protection

Electronic controller with microprocessor with easy-to-use immediate interface, fitted with self diagnosis for complete management of the cooling unit.

mod. HGL580/2AM

Possibility of connecting Remote-assistance with Frigel Service via GSM. High efficiency screw compressors, with control of the cooling capacity supplied by means of proportional regulation. Fans with direct current (brushless) motor with speed control. Unlike the traditional step or TRIAC systems, these fans significantly reduce noise, increase the machine reliability and lifetime , reducing the electric consumption of the fans by more than a third. The particular design of the Heavygel chillers permits simplicity of use and easy maintenance of all the parts. Possible combination with the air blast fluid coolers of the Ecodrygel series to create free-cooling type cooling systems. The choice of components, the assembly procedures and the strict final testing of 100% of the production guarantee continuous operating cycles with excellent reliability even in the most difficult conditions. The range includes 8 models with a cooling output ranging from 401 to 947 kW.

Frigel Firenze S.p.A. - Via Barontini, 17/b - loc. Granatieri - 50018 Scandicci (FI) - Italy Tel. +39-055-72209.1 Fax +39-055-7311271 email: sales@frigel.it - www.frigel.it
Frigel Firenze S.p.A. reserves the right to modify the data on this technical sheet at any moment

1/4
HGL_ING50 REV.01

INDUSTRIAL WATER CHILLERS HGL


TECHNICAL DATA

Model
*15/25 kW kW kW

HGL350/2
401 308 290 2
kW N

HGL470/2
537 413 388 2 60 8 2,5 5,5 63 4,4 146 323 55 DN125 4000 5400 2250 2400

HGL580/2
660 508 478 2 75 8 2,5 5,5 82,4 3,8 176 380 56 DN150 4015 5400 2250 2400

HGL700/2
795 612 575 2 90 10 2,5 10 109 5 215 455 57 DN150 5005 6450 2250 2400

HGL/840/2
947 729 685 2 105 12 2,5 10 151 5,5 250 521 58 DN150 5725 7550 2250 2400

Cooling capacity

*10/35 *7/32 N

Compressor
nom.

45 6 2,5 5,5 47,5 2,7 111 227 54 DN100 3500

Fans

axial kW chiller pump kW

Evaporator

mc/h kW

nom mt

Nominal Values
A dB (A) 10 mt. in/out Kg L P H mm mm mm

Sound level Connections Empty weight Width Depth Height

4300 2250 2400

[*] Cooling water temperature / Ambient temperature Supply voltage = 400 Volts 15% 50Hz (available 220V15%; 380V10%; 460V15%; 60Hz) On request : UL/ULC versions

Frigel Firenze S.p.A. - Via Barontini, 17/b - loc. Granatieri - 50018 Scandicci (FI) - Italy Tel. +39-055-72209.1 Fax +39-055-7311271 email: sales@frigel.it - www.frigel.it
Frigel Firenze S.p.A. reserves the right to modify the data on this technical sheet at any moment

2/4
HGL_ING50 REV.01

INDUSTRIAL WATER CHILLERS HGL


TECHNICAL FEATURES

REFRIGERATION EQUIPMENT

screw rotary compressors shell & tube evaporators copper pipe condensers with aluminium fins, designed to withstand extreme climatic conditions (maximum temperature +45C) die-cast aluminium axial fans with direct current (brushless) motor with speed control operating temperature can be set from 0C to +30C

WATER DISTRIBUTION EQUIPMENT


chiller pump, fitted with a high resistance mechanical seal and tropicalized motor completely insulated pipes, tank, connection parts and manifolds

ELECTRICAL AND CONTROL EQUIPMENT

separate thermal protection on each compressor, pump and fan main switch with door lock emergency stop in line with EN 60204/1 standards microprocessor control for regulating and controlling all the functions and displaying the alarms.

FRAME

galvanised steel

Ordering code Example: HGL580/2AM

HGL
Series Cooling capacity

/2
A = Axial M = Chiller pump N = Without pump

ACCESSORIES AND OPTIONALS PMR Heavygel Remote control panel for operating the cooling unit remotely.

Epoxy coating on condensers aluminium fins for installation in aggressive environments.

Frigel Firenze S.p.A. - Via Barontini, 17/b - loc. Granatieri - 50018 Scandicci (FI) - Italy Tel. +39-055-72209.1 Fax +39-055-7311271 email: sales@frigel.it - www.frigel.it
Frigel Firenze S.p.A. reserves the right to modify the data on this technical sheet at any moment

3/4
HGL_ING50 REV.01

INDUSTRIAL WATER CHILLERS HGL


CONFIGURATIONS

Heavygel (M) type configuration for systems with external tank and process pump(s)

Heavygel (N) type configuration for systems with external tank, chiller pump, process pump(s)

INSTALLATION DIAGRAM

Example of connecting several Heavygel (M) in parallel for systems with external tank and process pump(s)

Frigel Firenze S.p.A. - Via Barontini, 17/b - loc. Granatieri - 50018 Scandicci (FI) - Italy Tel. +39-055-72209.1 Fax +39-055-7311271 email: sales@frigel.it - www.frigel.it
Frigel Firenze S.p.A. reserves the right to modify the data on this technical sheet at any moment

4/4
HGL_ING50 REV.01

You might also like