CANTAKOY HEPP AIR PROPERTIES 27-Apr-10 Leef Val S. Bermudez Roy A. Arbolente
PROPERTIES OF AIR ( CANTAKOY HEPP CONTROL ROOM AND SWITCH GEAR ROOM)
Patm := 101.325kPa Comfort cooling temperature = 22 C twb := 22 C Normal Room Temp. = 32 C tdb := 32 C Solving for the Partial pressure of dry air (Pa): Pv := 2.645kPa (according to steam tables) Pressure at 22 C Table 1 Pa = Patm-Pv Pa := Patm Pv Pa := 101.325kPa 2.645kPa Pa = 98.68 kPa Solving for the Humidity Ratio (W) : Pv Pa 2.645 98.68 kgv W = 0.017 kga
W := .622
W := .622
Solving for the Relative Humidity ( RH) Psat := 4.759kPa (Psat at 32 C ) Pv RH := Psat RH := 2.645 4.759 or 55.6 %
RH = 0.556
Solving for the Enthalphy: KJ Cp := 1.0062 kg K W = 0.017 kgv kga hg := 2560 t := 32 C h := 1.0062 32 + .017 2560 h := Cp t + W hg h = 74.879 KJ kg KJ kg
Solving for the specific volume of air: Pair = 1.2 P =m/v Lswitchgear := 25400mm Wswitchgear := 6070mm hswitchgear := 3500mm kg m
3