SECONDARY PUMP - EAST TOWERS

PUMP HEAD CALCULATION FOR PHASE III

WATER FLOW
SI.NO

LEVEL

DESCRIPTION

SIZE DIA
INCH

LENGTH / EQ.
LENGTH

QTY
MTR
L/S

GPM

1 L/S = 15.85 GPM

FT.
(A)

VELOCITY
(FPS)

1 MTR = 3.281 FT

FRICTION
LOSS /
100 FT.
(B)

TOTAL
FRICTION
LOSS
(FT. OF
WATER)

TOTAL
FRICTION
LOSS (Kpa)

DARCY
Chart

F=
(AxB)/100

T = F x 2.898

FROM DC TO PUMP
SUCTION HEADER

Basement

IV

20

516.19

8181.55

4.70

PIPE

20

516.19

8181.55

2.00

6.56

9.00

1.05

0.07

0.21

TEE

20

516.19

8181.55

30.49

100.01

9.00

1.05

1.05

3.13

PIPE

20

258.09

4090.77

2.00

6.56

4.51

0.28

0.02

0.05

TEE

20

258.09

4090.77

30.49

100.01

4.51

0.28

0.28

0.83

PIPE

14

258.09

4090.77

2.00

6.56

9.50

1.82

0.12

0.36

IV

14

258.09

4090.77

PIPE

14

258.09

4090.77

1.50

4.92

9.50

1.82

0.09

STRAINER

14

258.09

4090.77

PIPE

14

258.09

4090.77

1.00

3.28

9.50

1.82

0.06

0.18

ELBOW

14

258.09

4090.77

10.37

34.01

9.50

1.82

0.62

1.84

PIPE

14

258.09

4090.77

1.50

4.92

9.50

1.82

0.09

0.27

FLEXIBLE

14

258.09

4090.77

0.40

1.31

9.50

1.82

0.02

0.07

FLEXIBLE

14

258.09

4090.77

0.40

1.31

9.50

1.82

0.02

0.07

PIPE

14

258.09

4090.77

2.50

8.20

9.50

1.82

0.15

0.44

NRV

14

258.09

4090.77

PUMP SUCTION

Basement

1.75
0.27
22.15

PUMP DISCHARGE

Basement

4.67

IV

14

258.09

4090.77

ELBOW 90

14

258.09

4090.77

10.37

34.01

9.50

1.82

0.62

1.75
1.84

PIPE

14

258.09

4090.77

2.00

6.56

9.50

1.82

0.12

0.36

PUMP DISCHARGE
HEADER TO HEAT
EXCHANGER

TEE

20

258.09

4090.77

30.49

100.01

4.51

0.28

0.28

0.83

PIPE

20

258.09

4090.77

0.75

2.46

4.51

0.28

0.01

0.02

TEE

20

516.19

8181.55

30.49

100.01

9.00

1.05

1.05

3.13

PIPE

20

516.19

8181.55

1.00

3.28

9.00

1.05

0.03

0.10

TEE

20

516.19

8181.55

30.49

100.01

9.00

1.05

1.05

3.13

ELBOW 45

20

516.19

8181.55

7.93

26.01

9.00

1.05

0.27

0.81

PIPE

20

516.19

8181.55

1.00

3.28

9.00

1.05

0.03

0.10

ELBOW 45

20

516.19

8181.55

7.93

26.01

9.00

1.05

0.27

0.81

PIPE

20

516.19

8181.55

0.50

1.64

9.00

1.05

0.02

0.05

TEE

20

516.19

8181.55

7.93

26.01

9.00

1.05

0.27

0.81

PIPE

20

397.65

6302.75

2.00

2.00

6.95

0.64

0.01

0.04

Basement

TEE

20

397.65

6302.76

7.93

26.01

6.95

0.64

0.17

0.50

PIPE

20

279.11

4423.89

2.30

7.54

4.88

0.33

0.02

0.07

TEE

20

279.11

4423.89

7.93

26.01

4.88

0.33

0.09

0.26

PIPE

20

160.57

2545.03

0.75

2.46

2.81

0.12

0.00

0.01

REDUCER

20 - 14

160.57

2545.03

6.10

20.01

2.81

0.12

0.02

0.07

PIPE

14

160.57

2545.03

0.90

2.95

5.92

0.74

0.02

0.07

TEE

14

160.57

2545.03

20.70

67.90

5.92

0.74

0.50

1.50

PIPE

14

107.05

1696.74

2.00

6.56

5.92

0.74

0.05

0.14

Page 1 of 3

REMARKS

Basement

SECONDARY PUMP - EAST TOWERS


PUMP HEAD CALCULATION FOR PHASE III

WATER FLOW
SI.NO

LEVEL

DESCRIPTION

SIZE DIA
INCH

LENGTH / EQ.
LENGTH

QTY
MTR
L/S

GPM

FT.
(A)

1 L/S = 15.85 GPM

1 MTR = 3.281 FT

VELOCITY
(FPS)

FRICTION
LOSS /
100 FT.
(B)

TOTAL
FRICTION
LOSS
(FT. OF
WATER)

TOTAL
FRICTION
LOSS (Kpa)

DARCY
Chart

F=
(AxB)/100

T = F x 2.898

TEE

14

107.05

1696.74

20.70

67.90

5.92

0.74

0.50

1.50

PIPE

14

53.53

848.45

2.00

6.56

1.97

0.10

0.01

0.02

TEE

14

53.53

848.45

20.70

67.90

1.97

0.10

0.07

0.20

PIPE

53.52

848.29

5.00

16.40

5.44

1.16

0.19

0.57

ELBOW 90

53.52

848.29

6.10

20.01

5.44

1.16

0.23

0.69

IV

53.52

848.29

0.50

FLOW METER

53.52

848.29

20.00

DRV

53.52

848.29

5.83

STRAINER

53.52

848.29

6.67

53.52

848.29

50.00

HEAT EXCHANGER
SUPPLY

Basement

Basement

HEAT EXCHANGER

HEAT EXCHANGER
RETURN

PIPE

53.52

848.29

4.00

13.12

5.44

1.16

0.15

0.45

ELBOW

53.52

848.29

6.10

20.01

5.44

1.16

0.23

0.69

CONTROL VALVE

53.52

848.29

50.00

IV

53.52

848.29

0.50

TEE

14

53.53

848.45

PIPE

14

53.53

848.45

TEE

14

107.05

1696.74

PIPE

14

107.05

1696.74

Basement

HEAT EXCHANGER
HEADER TO DC RETURN

Basement

20.70

67.90

1.97

0.10

0.07

0.20

2.50

8.20

1.97

0.10

0.01

0.02

20.70

67.90

3.95

0.35

0.24

0.71

2.50

8.20

3.95

0.35

0.03

0.09

TEE

14

160.57

2545.03

20.70

67.90

5.92

0.74

0.50

1.50

PIPE

14

160.57

2545.03

1.50

4.92

5.92

0.74

0.04

0.11

REDUCER

14 -- 20

160.57

2545.03

6.10

20.01

5.92

0.74

0.15

0.44

PIPE

20

160.57

2545.03

1.00

3.28

2.81

0.12

0.00

0.01

TEE

20

279.11

4423.89

30.49

100.01

4.88

0.33

0.33

0.98

PIPE

20

279.11

4423.89

2.50

8.20

4.88

0.33

0.03

0.08

TEE

20

397.65

6302.75

30.49

100.01

6.95

0.64

0.64

1.91

PIPE

20

397.65

6302.75

2.50

8.20

6.95

0.64

0.05

0.16

TEE

20

516.19

8181.61

30.49

100.01

9.00

1.05

1.05

3.13

PIPE

20

516.19

8181.61

9.00

29.52

9.00

1.05

0.31

0.92

IV

20

516.19

8181.61

4.70

TOTAL
SAFETY FACTOR (20%)

NET TOTAL
As per Client Requirement - Head Loss Considered (100ft of water)

GRAND TOTAL = 550 Kpa (round off)

Page 2 of 3

209.99
42.00

251.99
298.00

549.99

REMARKS

SECONDARY PUMP - EAST TOWERS


PUMP HEAD CALCULATION FOR PHASE III
LENGTH / EQ.
LENGTH

WATER FLOW
SI.NO

LEVEL

DESCRIPTION

SIZE DIA
INCH

QTY
MTR
L/S

GPM

1 L/S = 15.85 GPM

FT.
(A)

VELOCITY
(FPS)

FRICTION
LOSS /
100 FT.
(B)

TOTAL
FRICTION
LOSS
(FT. OF
WATER)

TOTAL
FRICTION
LOSS (Kpa)

DARCY
Chart

F=
(AxB)/100

T = F x 2.898

1 MTR = 3.281 FT

NOTE:
P = ( Q / Kv )2

P = ( Q / Cv )2

where,

where,
Q = Flow rate of Chilled Water in m3/ hr.

Q = Flow rate of Chilled Water in GPM

Kv = Valve Coefficient

Cv = Valve Coefficient

P = Pressure Drop in bar.

P = Pressure Drop in PSI.

Conversions:
1 bar = 100 KPa
1PSI = 6.895 Kpa

1 l/s = 15.85 GPM

1 m = 3.281 feet

1 l/s = 3.6 m /hr

PREPARED BY : N.NAGARAJAN
ETA

CHECKED BY : FREDRICK JOHN

APPROVED BY : ARUL RAJ

ETA

HYDER

Page 3 of 3