European Installation Bus(EIB) Cables

PE Insulation, PVC Outer Sheath European Installation Bus(EIB) Cables


EIB 2Y(St)Y 2x2x0.8

PVC Outer Sheath PE Insulation Solid Copper Conductor

Overall AL/Polyester Tape With Tinned Copper Drain Wire

APPLICATION EIB installation consists of sensors and actuators. The E.I.B. concept allows intergration of Building Management Systems (B.M.S.) over one common system. Lighting, blinds, heating and ventilation can be automatically controlled through the E.I.B cable. This dramatically reduces the cabling required in a modern building. They can be installed over, in, or below the plaster, in pipes and pipe ducts, in dry, moist, and wet areas, as well as outside, provided they are protected against direct exposure to the sun.

STANDARDS
Basic design to European Standard EN 50090

CABLE CONSTRUCTION Type/Cable Construction Inner Conductor Conductor Insulation Insulation Colour Stranding Element Screen Drain Wire Outer Sheath 1 Quad Plain copper conductors 0.8mm PE White,yellow,red,black Cores twisted into a quad Aluminium/polyester foil screen Solid copper PVC 2 Pair Plain copper conductors 0.8mm PE White,yellow,red,black Cores twisted into pairs, pairs laid up Aluminium/polyester foil screen Stranded tinned copper PVC

ADDISON

ADDISON
cOLOUR Code
Insulation Colour: Pair1: Red/Black; Pair2: White/Yellow Sheath Colour: Green

Electrical Properties
Test Voltage Working Voltage Conductor resistance Insulation resistance Mutual capacitance@800Hz Unbalanced capacitance 4000V MaX.150V 37.0 Ohm/km @ 20C 1000Mhms*km @ 20C 60nF/km max 300pF/100m maX

TECHNICAL DATA:
Approx.Weight (kg/km) Nominal diameter(mm) Min. Bending Radius (Laying) Operating temperature, min Operating temperature, max
150V

62 6.1 10 x OD mm -20C(fixed) +70C(fixed)

57 6.1 10 x OD mm -5C (installation) +50C (installation)

N
EN 50090 Standard

Rated Voltage

Caledonian

www.caledonian-cables.co.uk

www.addison-cables.com