Client : Consultant : Project :

M/s. TSL M/s. TCE 40MW DG Power Plant

Site Conditions Maximum Ambient/Design Temperature Maximum Altitude above Sea Level 50 1000 C Mtr

System Voltage/ Cable Conductor Details CT Supply PT Supply DC Supply-1 DC Supply-2 1Ph AC Supply 3Ph AC Supply 1A 110 V 220 V 24 V 230 V 415 V Al. Al. Al. Cu. Cu. for >16 Sq. mm. Cu. for >16 Sq. mm. for >16 Sq. mm.

Cable Voltage Drop Details During Normal Operation Transformer to Motor PCC to MCC MCC to Motor During Starting Condition

Power Factor 0.82

Voltage Drop 3% 5% 2% 3%

0.3

10 %

Cable Grouping Factor Details Grouping Factor for Single Core Grouping Factor for Multi Core 0.81 0.594 0.6873 0.6612