SUMRIO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 FINALIDADE .....................................................................................................................1 CONCEITOS BSICOS.....................................................................................................1 ROTEIRO DE CONSULTA A NORMA...............................................................................2 CONDIES GERAIS DE FORNECIMENTO ...................................................................2 ENTRADA DE SERVIO...................................................................................................5 ESCOLHA DA SUBESTAO APROPRIADA ..................................................................8 MEDIO........................................................................................................................10 PROTEO ....................................................................................................................12 ATERRAMENTO .............................................................................................................17 EQUIPAMENTOS E ACESSRIOS ................................................................................18 DETERMINAO DO TIPO DE ENTRADA DE SERVIO ..............................................21 CLCULO DA DEMANDA PROVVEL ...........................................................................21 PROJETO ELTRICO .....................................................................................................23 PEDIDO DE LIGAO ....................................................................................................24 SEGURANA..................................................................................................................25 CASOS OMISSOS ..........................................................................................................27
NORTDE103
FINALIDADE
Esta norma tem por finalidade estabelecer os critrios, condies gerais, e limites de fornecimento de energia eltrica em tenso de distribuio primria 34,5 KV, na rea de concesso da ENERSUL, para as instalaes consumidoras novas, bem como em reformas e ampliaes das unidades j existentes. 2 2.1 CONCEITOS BSICOS CONSUMIDOR
a pessoa fsica ou jurdica ou comunho de fato ou de direito legalmente representada, que ajustar com a ENERSUL o fornecimento de energia eltrica e ficar responsvel por todas as obrigaes regulares e/ou contratuais. 2.2 UNIDADE CONSUMIDORA
Corresponde ao conjunto de cargas e respectivos sistemas eltricos associados, de um nico consumidor, para o qual efetuada a medio individualizada de energia, em um nico ponto. 2.3 PONTO DE ENTREGA
o ponto at o qual a ENERSUL se obriga a fornecer energia eltrica, com participao nos investimentos necessrios, bem como responsabilizando-se pela execuo dos servios de operao e pela manuteno, no sendo necessariamente o ponto de medio. 2.4 ENTRADA DE SERVIO
Conjunto de equipamentos, condutores e acessrios instalados entre o ponto de derivao da rede de distribuio da ENERSUL e a proteo, medio ou transformao, inclusive. 2.5 RAMAL DE LIGAO
Conjunto de condutores, equipamentos e respectivos acessrios de conexo que liga a rede de distribuio da ENERSUL ao ponto de entrega. 2.6 RAMAL DE ENTRADA
Conjunto de condutores, equipamentos e acessrios que interligam o ponto de entrega ao ponto de proteo, medio ou transformao, inclusive. 2.7 SUBESTAO
Instalao eltrica da unidade consumidora destinada a receber o fornecimento de energia em tenso de distribuio primria, com uma ou mais das funes de manobra, proteo, transformao ou medio.
Soma das potncias nominais dos equipamentos de uma unidade consumidora. 3 ROTEIRO DE CONSULTA A NORMA
Com a finalidade de orientar a consulta a esta Norma, apresentamos o seguinte roteiro: a) b) c) d) 4 4.1 Conhecer as Condies Gerais de Fornecimento (item 4); Verificar a subestao apropriada (item 6); Verificar a necessidade de projeto eltrico (item 13); Verificar as informaes atinentes ao Pedido de Ligao (item 14);
A presente Norma aplicvel ao fornecimento de energia eltrica s unidades consumidoras individuais, a serem atendidas na tenso de distribuio primria de 34,5 KV por rede area a 3 (trs) condutores, na freqncia nominal de 60 Hz. 4.2 LIMITES DE FORNECIMENTO
A ENERSUL efetuar o fornecimento de energia, na tenso de distribuio primria de 34,5 kV, nos locais onde essa tenso seja disponvel, s unidade consumidoras, cujas instalaes se enquadrem em pelo menos uma das situaes a seguir: a) b) Possua carga instalada superior a 75 KW, e a demanda contratada ou estimada pela ENERSUL para o fornecimento seja igual ou inferior a 2.500 KW; Possua um ou mais dos seguintes aparelhos: c) Motor monofsico da classe de 120 V, superior a 2 CV; Motor monofsico da classe de 220 V, superior a 6 CV; Motor trifsico da classe de 220 V, superior a 20 CV; Aparelho de raio X com potncia superior a 20 kVA; Mquina de solda com transformador, 220 V, 2 fases superior a l5 kVA Mquina de solda com transformador, 220 V, 3 fases superior a 20 kVA; Mquina de solda, grupo motor-gerador, superior a 20 CV.
NORTDE103
Nota: - A ENERSUL poder, a seu critrio, fornecer energia na tenso de 34,5 KV fora dos limites acima, quando as condies tcnicas e econmicas do seu sistema o permitirem. 4.3 REVENDA OU FORNECIMENTO DE ENERGIA ELTRICA A TERCEIROS
vedado ao consumidor, assenhorar-se dos direitos da ENERSUL, estendendo redes que se interliguem com redes de outrem, para fornecimento de energia eltrica, ainda que graciosamente. 4.4 FATOR DE POTNCIA
Todos os consumidores devero manter o fator de potncia indutivo mdio de suas instalaes, o mais prximo possvel da unidade. Caso a ENERSUL verifique, atravs de medio apropriada em carter transitrio ou permanente, de acordo com os critrios fixados na Resoluo 456 da ANELL, fator de potncia inferior 0,92 %, ser efetuado o ajuste de faturamento previsto na legislao vigente. A montagem de dispositivo para correo de fator de potncia, no lado de tenso primria, de instalaes ligadas rede de distribuio, dever ser previamente analisada pela ENERSUL. A instalao dos equipamentos para correo do fator de potncia dever ser efetuada preferencialmente de forma distribuda junto as cargas do cliente, de modo a serem energizados simultaneamente com estas. 4.5 AUMENTO DE CARGA
Todo e qualquer aumento de carga pretendido, alm do limite correspondente ao seu tipo de fornecimento, dever ser previamente solicitado pelo interessado e autorizado pela ENERSUL, cabendo ainda a verificao quanto a necessidade da apresentao de projeto eltrico, em caso de alterao ou ampliao da configurao existente. 4.6 PREPARAO DA ENTRADA DE SERVIO
A ENERSUL propiciar, atravs de seus rgo tcnicos, toda a orientao necessria perfeita execuo da entrada de servio, cabendo ao consumidor prepar-la, observando os requisitos mnimos aqui fixados, ficando ao encargo desta concessionria a instalao e ligao dos equipamentos de medio. Para os casos em que dever ser apresentado o projeto eltrico, visando a anlise da ENERSUL, caso o cliente execute obras, antes do parecer da mesma, este estar sujeito a efetuar as alteraes que se fizerem necessrias, de forma que a mesma fique de acordo com o projeto analisado. Nos casos que no se faz necessria a apresentao do projeto, porm exista algum particularidade especifica que difere do exposto na presente norma, a ENERSUL dever ser consultada.
Os equipamentos de medio instalados na unidade consumidora e seu acesso privativo so de propriedade da ENERSUL, cabendo ao consumidor zelar pela sua integridade e privacidade. Os lacres dos medidores e caixas onde forem instalados os equipamentos de medio e proteo, somente podem ser rompidos pela ENERSUL ou por empresa contratada por esta, sempre com apresentao das credenciais dos funcionrios, sob pena de cobranas conforme artigo 36 da Resoluo 456 de 29 de Novembro de 2000 da ANEEL. 4.8 CARACTERSTICAS INDESEJVEIS
Os equipamentos eltricos das unidades consumidoras, no devero provocar fenmenos eltricos indesejveis, ex: queda de tenso, flutuao de tenso, interferncia, baixo fator de potncia, etc., acima dos nveis de tolerncia aceitveis ao bom desempenho de outras unidades consumidoras do sistema eltrico, especificados por normas da ABNT ou da ENERSUL. Na eventualidade da ocorrncia de distrbios acima dos nveis aceitveis, as correes e eventuais danos e ressarcimentos sero de responsabilidade do consumidor proprietrio da carga causadora das perturbaes, conforme Resoluo 456 da ANEEL de 29/11/2000. 4.9 GERAO PRPRIA
No ser permitido paralelismo (ligao) ao sistema eltrico da ENERSUL de geradores cuja propriedade seja do consumidor ou terceiros por qualquer perodo de tempo que seja. Para evitar qualquer possibilidade de paralelismo, os projetos das instalaes eltricas devero apresentar uma das seguintes solues: a) Instalao de uma chave reversvel de acionamento manual ou eltrica, com travamento mecnico, separando os circuitos alimentadores do Sistema da ENERSUL e do gerador particular, de modo a reverter o fornecimento; Construo de circuito de emergncia, independente do circuito de instalao normal, alimentado por gerador particular. Deve ser vedada, e sinalizada a interligao do circuito de emergncia com o circuito alimentado pela Rede ENERSUL.
b)
Em caso de alguma particularidade no projeto de gerao prpria do consumidor, este poder efetuar consulta a ENERSUL por escrito, encaminhando o mesmo em anexo. 4.10 REGULAMENTO a) b) c) Sero ligados rede de distribuio da ENERSUL, somente as instalaes cujas entradas de servio forem executadas em conformidade com esta Norma. O consumidor o responsvel por manter em bom estado de conservao, os componentes da entrada de servio, a partir do ponto de entrega. Caso seja constatada qualquer deficincia tcnica ou de segurana, o consumidor
NORTDE103
ser notificado das irregularidades existentes, devendo providenciar os reparos necessrios dentro do prazo pr-fixado pela ENERSUL. d) O consumidor responsvel pelos eventuais danos causados aos materiais e equipamentos de propriedade da ENERSUL, instalados dentro dos seus limites de propriedade.
5 5.1
5.1.1 CONDUTORES a) b) Condutores do ramal de ligao devero ser de alumnio n; O dimensionamento dos condutores dever obedecer a tabela n. 1, anexa.
5.1.2 INSTALAO a) b) c) d) No permitida a existncia de mais de um ramal de ligao para a mesma unidade consumidora; O ramal de ligao com comprimento menor de 5 m poder adotar estrutura N-2 no posto de transformao; O primeiro ponto de fixao na propriedade do consumidor dever estar afastado, no mximo, 10 metros do limite da propriedade com a via pblica; O ramal de ligao deve atender tambm s seguintes prescries: Entrar de preferncia pela frente do imvel e sempre que possvel, em ngulo reto com o alinhamento da via pblica; No dever passar por rea construda; No dever passar sobre terrenos de terceiros; No dever ser acessvel de janelas e sacadas, etc., devendo, os condutores, manter os afastamento mnimos especificados no desenho n. 15; Respeitar as normas estabelecidas pelos Poderes Pblicos, principalmente nas travessias, quando devero manter os afastamentos mnimo na condio de flecha mxima, com solo de: Sobre trilhos de estrada de ferro no eletrificada 9,0 m; Sobre rodovias 7,5 m; Ruas e avenidas 6,0 m; Caminhos exclusivamente para pedestres 5,0 m.
5.2.1 CONDUTORES Os condutores do ramal de entrada devero ter as seguintes caractersticas: 5.2.1.1 RAMAL DE ENTRADA AREO Devero ser de alumnio n dimensionados de acordo com a tabela n. 1. 5.2.1.2 BARRAMENTO EM AT a) b) Material: fio de cobre n, tubo ao, barra retangular, ou vergalho de cobre. No ser permitido uso de cabo; Seo: Dimensionado conforme tabela n. 3.
5.2.1.3 CONDUTORES EM BT a) b) c) Material: Cobre, prprio para instalao em eletroduto; Isolamento: classe 750 V; 70 C no mnimo; Seo: Dimensionamento conforme tabela 6, desta Norma.
5.2.2 INSTALAO 5.2.2.1 BARRAMENTO EM AT a) b) A instalao do barramento est detalhada nos desenhos anexos a esta Norma; Nas subestaes, o barramento dever ter a seqncia de fases identificadas pela ENERSUL, devendo ser marcada com tinta adequada, nas seguintes cores: Fase A Azul Fase B Vermelha
Fase C Branco A ENERSUL identificar as fases A, B e C. c) d) Nas emendas e derivaes devero ser previstos conectores apropriados, sem uso de solda; Para sada area dos condutores em tenso de 34,5 kV, a altura mnima, em relao ao solo dever ser de 6,00 m.
5.2.2.2 CONDUTORES DE B.T. a) Quando a medio for localizada no lado de baixa tenso 220/127 V (potncia instalada at 300 kVA, inclusive), os condutores devero ser: Protegidos por eletrodutos rgidos de dimetro adequado dimensionados pela tabela n. 6, desde os terminais secundrios dos transformador at a entrada na caixa dos equipamentos de medio.
b)
Quando os TCs. empregados forem do tipo barra a ligao dos condutores aos
NORTDE103
mesmos devero ser efetuada com terminais apropriados. c) Nos casos em que a sada dos condutores de baixa tenso, aps a medio, area, dever haver, com relao ao solo, uma altura igual ou superior a: 5.3 5,50m, em locais acessveis a veculos pesados; 4,0m, em entrada de garagens residenciais, estacionamentos outros locais no acessveis a veculos pesados; 3,50m, em locais acessveis apenas a pedestres; 4,50m, em reas rurais (cultivadas ou no).
5.3.1 CONDUTORES a) 5.4 Os cabos sero, isolados para 35kV, unipolares, prprios para uso subterrneo;
INSTALAO
O ramal de entrada subterrneo dever obedecer as condies abaixo, alm das estabelecidas pelos Poderes Pblicos tais como: Prefeituras Municipais, AGESUL, DNIT, etc. a) b) c) d) As extremidades dos cabos devero ser protegidas com muflas terminais, classe 35kV, de formas e dimenses adequadas. As derivaes subterrneas de entrada em alta tenso, devero obedecer o desenho n. 19 desta Norma; No sero permitidas emendas nos condutores; A blindagem dos cabos subterrneos e as muflas terminais devero ser ligados ao sistema de aterramento, por meio de condutor de cobre n de bitola no inferior a 16 mm2; Os cabos instalados ao longo das paredes, postes ou noutras superfcies, devero ser protegidos por meio de eletrodutos galvanizados. Nas sadas verticais dos cabos, as altura mnimas dos eletrodutos de proteo, devero ser: g) Em instalaes interiores 0,60m; Em instalaes exteriores 5,50m.
e) f)
Os cabos subterrneos podero ser instalados dentro de dutos, canaletas ou galerias, segundo o tipo de cabo empregado e situados a uma profundidade nunca inferior a 0,60m; Os dutos devero ser assentados e as canaletas construdas de forma a resistirem aos esforos externos e os provenientes da instalao dos cabos, considerando as condies prprias do solo;
h)
NORTDE103
i) j) k) l)
Tanto as canaletas como os dutos devero ser instalados com as extremidades em desnvel , de modo a permitir o escoamento das guas para as caixas contguas: As canaletas devero ser fechadas com tampa de concreto ou chapa de ferro; O eletroduto no poder sofrer curvas superiores a 45 , devendo nestas condies ser previsto uma caixa de passagem; A caixa de passagem dever ser construda em alvenaria ou concreto, com impermeabilizao adequada, dispor de tampa de ferro ou concreto armado, de acordo com os esforos a que poder ser submetida, e possuir dimenses de 0,80 x 0,80m x com profundidade mxima de 0,80 cm;
m) O fundo da caixa dever situar-se a 0,20 metros abaixo da parte inferior do duto de nvel mais baixo e possuir sistema de drenagem adequado; n) o) p) q) O raio de curvatura do cabo no dever ser inferior a 20 (vinte) vezes o dimetro do mesmo; No ponto de entrega da entrada de servio subterrnea, dever ser instalado um pra-raios por fase, conforme ilustra o desenho n 19; O ramal de entrada subterrneo no dever passar em terreno de terceiros; A derivao subterrnea, dever ser instalada em frente e no mesmo lado do consumidor, ainda que a rede area tronco esteja localizada no lado oposto da via pblica. Neste ltimo caso a travessia da via pblica ser area; Para cabos unipolares, dever ser previsto um cabo de reserva, provido de muflas terminais; Nos ramais maiores do que 30 metros, recomenda-se instalar caixa de passagem de 30 em 30 metros.
r) s)
6 6.1
Em funo da potncia nominal do transformador de servio, a subestao de transformao dever obedecer os desenhos anexos, conforme detalhado abaixo: a) b) c) d) Subestao de transformao e medio em BT, (posto), potncia at 30 kVA, inclusive, conforme os desenhos n. s 02 e 03. Subestao de transformao e medio em BT, (posto), potncia de 45 a 112,5 kVA, inclusive, conforme desenhos n. s 04 e 05. Subestao de transformao e medio em BT (posto) potncia de 45 a 225 kVA, inclusive, conforme desenhos n. s 06 e 07. Subestao de transformao e medio em BT potncia at 300 kVA, inclusive, conforme desenho n. 08.
NORTDE103
e) f) g) h) i) j)
Subestao de medio em AT e transformao, potncia entre 300 kVA, exclusive a 1000 kVA, inclusive, conforme desenho n. 10 e 11. Subestao de medio em AT para distribuio por centro de cargas, conforme desenhos n. s 09. Subestao de medio em AT e proteo, para distribuio por centro de cargas e potncia de 1000 kVA, exclusive at 2500 kVA, inclusive, conforme desenho n. 12. Subestao de medio em AT, proteo e transformao, potncia entre 1000 kVA, exclusive at 2500 kVA, inclusive, conforme desenho n. 13. Subestao de medio em AT, potncia at 1000 kVA, inclusive com conjunto de medio, conforme desenho n. 14. Para potncia entre 300 kVA e 2.500 kVA, permitido o uso de cubculo blindado para proteo, medio e manobra, desde que, previamente aprovado pela ENERSUL.
6.2
CARACTERSTICAS CONSTRUTIVAS
A Subestao dever ter: a) Localizao junto ao alinhamento da propriedade particular com a via pblica, salvo recuo estabelecido por rgos governamentais. b) c) Mediante acordo entre ENERSUL e o consumidor, poder ser tolerado localizao diferente, nunca maior que 100 m, em zona urbana. Diante de situaes de caractersticas atpica, poder ser efetuada consulta prvia a ENERSUL;
Seus equipamentos dispostos de modo a oferecer condies adequadas de operao, manuteno e segurana, conforme detalhado nos desenhos anexos; Transformador se servio, com tenses secundrias de 220/127V, onde a medio for em BT. Para tenso secundrias diferentes de 220/127 V, dever ser consultada a ENERSUL, com antecedncia (obs item 10.8 d);
d) e)
Caractersticas de construo definitiva, e ser de material incombustvel; Sua rea protegida externamente, com uma cerca de tela metlica galvanizada, com malha de 50 mm, no mximo, arame 12 BWG no mnimo, e postes de concreto ou cano de ferro galvanizado de dimetro mnimo de 3", conforme desenho n. 17; O acesso, em qualquer caso, atravs de porto de 2 folhas, feito em tela metlica galvanizada, com malha de 50 mm, nas dimenses de 3,00 m x 1,70 m, de abrir para fora, com apoio e fechadura, e apresentar facilidade de abertura pelo lado interno, conforme desenho n 17; O piso da rea coberto com uma camada de 10 cm de pedra britada n. 2, o qual
f)
g)
NORTDE103
10
dever estar 5 cm abaixo de qualquer outro piso, interno ou externo, cujo acabamento destes seja em concreto; h) i) j) k) A cota do piso sempre acima da cota mdia da rea de construo. Quando necessrio, dever ser previsto sistema de drenagem de guas pluviais; Uma placa, fixada pelo lado de fora do porto de acesso, com os seguintes dizeres: PERIGO ALTA TENSO ; Uma chave faca por fase de 200 A, NBI 150 kV, instalada na primeira estrutura posterior subestao, para a distribuio ao(s) centro(s) de carga(s); Seus equipamentos de controle, proteo e manobra na baixa tenso, instalados em um conjunto separado, de modo a permitir o acesso fcil e com segurana de pessoa qualificada, sempre que possvel sem a necessidade de interrupo do circuito de alta tenso; Condies para a sada de linhas de distribuio para dentro da propriedade, destinadas alimentao de transformadores situados prximos aos centros de carga, sempre quando esta subestao for exclusiva para a medio for em A.T.;
l)
m) Um para-raio instalado por fase, sempre quando aps esta subestao o circuito de A. T., conter de mais de 100 m de comprimento. n) o) Condies para que todos os equipamentos fiquem firmemente fixados inclusive os de medio. Diagramas unifilares, de fcil acesso, quando j em operao, conforme aprovado; para eventuais consultas quando de visitas peridicas da ENERSUL.
7 7.1
MEDIO MEDIO EM BT
7.1.1 A medio ser no lado de BT para potncia at 300 kVA, inclusive, desde que sejam obedecidos os seguintes requisitos: a) b) Exista um nico transformador em servio. As tenses sejam 220/127 V.
7.1.2 A medio ser composta dos seguintes equipamentos, em funo da potncia instalada na unidade de consumo: a) Potncia at 30 kVA; b) 01 (um) medidor polifsico de kWh, 3 elementos, 4 fios 120V , 15 A
Potncia de 45 kVA; 01 (um) medidor polifsico de kWh e KVARh, eletrnico ,3 elementos, 4 fios 120 V , 2,5 A;
NORTDE103 c)
11
03 (trs) TCs ,classe 0,6 kV , exatido 0,3 C 12,5; 01 (uma) chave de aferio de 10 plos.
Potncia de 75 kVA e 300 kVA inclusive: 01 (um) medidor polifsico de kW/kWh e KVARh, eletrnico, 3 elementos, 4 fios, 120 V, 2,5 A; 03 (trs) TCs, classe 0,6 kV, exatido 0,3 C 12,5; 01 (uma) chave de aferio de 10 plos.
7.1.3 Nas medies em baixa tenso, os equipamentos sero alojados em caixas prprias para esse fim, padro ENERSUL, detalhadas a partir do desenho n. 01 desta Norma. Nas caixas individuais devero ser fabricadas por firmas cadastradas e com modelos aprovados pela ENERSUL. As caixas podero ser instaladas, conforme tipo de entrada de servio, ilustradas nos desenhos anexos a est norma. 7.2 MEDIO EM AT
7.2.1 A medio ser em alta tenso para potncias acima de 300 kVA e tambm: a) b) Quando existir mais de um transformador de servio na mesma unidade de consumo; Quando as tenses de BT forem diferentes de 220/127 V, desde que previamente analisados pela ENERSUL (obs item 10.8.d).
7.2.2 Normalmente, a medio ser composta dos seguintes equipamentos: 01 (um) medidor polifsico de kW/kWh e KVARh, eletrnico, 3 elementos, 4 fios, 120V, 2,5 A; 03 (trs) TCs, uso externo, classe 34,5 kV, 60 Hz, classe exatido 0,3 C50; 03 (trs) TPs uso externo, classe 34,5 kV, relao 34.500/R3 115 V, potncia trmica mnima 1.000 VA, classe de exatido 0,3 P75; 01 (uma) chave de aferio de 10 plos.
7.2.3 As instalaes dos equipamentos devero ser feitas conforme abaixo: a) b) c) Os TCs e TPs sero assentados em pilares de concreto, conforme desenho n. 16, ou no caso de posto de medio em estrutura H, conforme desenho n. 09 ; As caixas de passagens dos circuitos de medio, a partir dos TPS e TCS, devero ter dispositivos para lacres da Enersul, em no mnimo dois lados ( opostos ); Os medidores e demais equipamentos sero alojados em caixas padro ENERSUL, instalados conforme desenhos anexos esta Norma.
NORTDE103
12
d) 8 8.1
PROTEO GENERALIDADES a) b) c) d) Toda instalao dever ter proteo geral individual contra curto-circuito e sobrecarga, adequada e coordenada com a proteo da ENERSUL. Toda instalao dever ter proteo geral individual contra curto-circuito e sobrecarga, adequada e coordenada com a proteo da ENERSUL. Os dispositivos de proteo devero ter capacidade de interrupo compatvel com os nveis de curto-circuito disponveis no ponto de instalao. A instalao de chaves seccionadoras e chaves fusveis devem ser feitas de forma a impedir seu fechamento pela ao da gravidade, devendo as partes mveis ficar sem tenso, quando abertas. Quando a medio for em MT, esta dever ser instalada imediatamente aps o ponto de tomada de energia e a proteo geral da instalao, disjuntor ou religador de MT, dever ficar imediatamente aps a esta medio. Em instalaes abrigadas, sendo a proteo por fusveis, obrigatria a instalao de chaves seccionadoras com ao simultnea, abertura sob carga, dotadas de alavanca de manobra, equipada com fusveis limitadores de corrente, no sendo permitido o uso de chave fusvel de distribuio em cmaras, cabines ou cubculos. Para mais segurana recomendvel o intertravamento eltrico da seccionadora com o disjuntor de BT. Antes do disjuntor, em cabines abrigadas, dever ser instalada uma chave seccionadora tripolar, com ao simultnea, dotada de alavanca de manobra, exceto quando utilizado disjuntor extravel. No caso de haver mais de um transformador e proteo geral provida de disjuntor, devero ser instaladas chaves seccionadoras antes deles, providas ou no de fusvel tipo limitador de corrente, desde que vivel uma coordenao seletiva com o disjuntor de proteo geral, sem prejuzo da coordenao deste ltimo com a proteo da ENERSUL. Os equipamentos que so operados manualmente devero permitir o uso de dispositivo mecnico para evitar o seu religamento. Cada parte de uma instalao que possa ser isolada de outras partes dever possuir meios que permitam o seu aterramento e curto-circuitamento.
e)
f)
g)
h)
i) j)
13
8.2.1 RAMAL DE LIGAO a) Fornecimento at 750kVA, inclusive b) Na derivao do ramal, instalar um conjunto de Chave Fusvel, com elo fusvel dimensionado de acordo com a tabela 07A.
8.2.2 SUBESTAES TRANSFORMADORA a) Cabine, subestao ou posto de transformao, com capacidade instalada de at 300kva: Deve ser instalada pelo interessado uma chave seccionadora tripolar de abertura simultnea com ou sem carga e um jogo de fusveis limitadores, descrito anteriormente, de corrente nominal recomendada pelo fabricante e adequada para coordenao com fusveis de expulso tipo K, instalados no poste de sada do ramal, ou disjuntor geral trifsico, acionado atravs de rels secundrios com as funes 50 e 51, fase e neutro (onde fornecido o neutro). No caso de se optar pela seccionadora, adicionalmente, a proteo geral, na baixa tenso, deve ser realizada atravs de disjuntor. Transformadores em paralelo devem ter um nico disjuntor. Em caso de utilizao de chave de abertura sem carga, colocar placa advertindo para no oper-la sob carga.
b)
Em cabine ou subestao ao tempo com capacidade instalada acima de 300kVA e at o limite previsto por esta norma. O cliente deve instalar um disjuntor geral trifsico, com as seguinte caractersticas: classe de tenso : 36,2 kV corrente nominal transformadores : de acordo com a capacidade instalada dos
capacidade mnima de interrupo simtrica : 650MVA. NBI : 170kV. Freqncia : 60Hz. sem religamento automtico, salvo em casos especiais, sujeitos consulta rea de Engenharia da ENERSUL.
NORTDE103
14
Bobina de Mnima Tenso fica a critrio do cliente, em funo das caractersticas das suas cargas ou do seu processo industrial, a opo pela utilizao de bobina de mnima tenso. Nos casos de subestao ao tempo, o disjuntor poder ser substitudo por religador automtico com caractersticas eltricas bsicas mnimas iguais do disjuntor, desde que o religador seja ajustado para bloquear aps a primeira operao, ou seja, no dever fazer nenhum religamento. A proteo de sobrecorrente ser feita por rels de sobrecorrente secundrios, com unidades de operao instantnea e temporizada (funo 50/51) e 50N/51N, que sero ligados ao circuito primrio atravs de TCs do tipo a seco. Os TCs devero ser dimensionados para no saturarem para a corrente assimtrica mxima, no ponto de entrega ou 10kA, o que for maior. Para o correto funcionamento dos rels digitais e para o funcionamento da bobina de abertura do disjuntor, durante a ocorrncia de curtos-circuitos prximos ao seu ponto de instalao, devero ser previstas fontes auxiliares para a sua alimentao. A alimentao auxiliar poder ser: Um banco de baterias e seu carregador; No-break, que dever ser alimentado atravs do secundrio de um dos transformadores a serem protegidos pelo disjuntor; Transformador de distribuio; TPs, trip capacitivo e rel de subtenso (funo 27), com temporizao na desernegizao (recomenda-se que o ajuste para operao do rel de subtenso seja inferior a 80% da tenso de fornecimento e o tempo de operao seja maior que 6s). Do lado da entrada do disjuntor e aps a medio, dever ser instalado uma chave faca de abertura sem carga, de classe de tenso e corrente nominal adequados, para possibilitar a manuteno do disjuntor. Recomenda-se que o interessado adquira os equipamentos de proteo, somente aps a anlise do projeto pela ENERSUL.
c)
Projeto de proteo quando a cabine for protegida com disjuntor, mesmo nos casos em que no h exigncia desta instalao, dever ser apresentado um projeto de proteo, contendo, no mnimo, as seguintes documentaes: Diagrama funcional, mostrando a atuao das protees, etc. Diagrama unifilar, mostrando a localizao dos principais componentes (TC, TP, disjuntor, chaves, etc.). Valores de curto-circuito no ponto de entrega. Potncia instalada e demanda prevista.
NORTDE103
15
Dimensionamento dos TCs (relao, capacidade nominal, saturao, etc.). Caractersticas da proteo. Clculo do ajuste da proteo. Tipo e caractersticas da fonte auxiliar. Para permitir a elaborao do projeto de proteo, a ENERSUL fornecer ao projetista/interessado os seguintes dados: Correntes de curto-circuito no ponto de tomada de energia (atual e mximo). Impedncias Z1 e Zo no ponto de tomada de energia. O tempo de atuao da proteo projetada dever ser no mximo de 0,3 segundos para a corrente de curto-circuito no ponto de tomada de energia. Considerar na proteo a montante as curvas IEC 255, sendo extremamente inversa para a fase e muito inversa para o neutro. Os ajustes, calibrao e aferio devero ser executados pelo interessado, e informados a ENERSUL atravs de um laudo tcnico. Tanto a proteo referida, como o restante do sistema de proteo interno instalao particular, so de competncia e responsabilidade do interessado, que dever executa-lo e mant-lo conforme o projeto apresentado ENERSUL.
d)
Proteo do transformador auxiliar Quando for prevista a instalao de transformador auxiliar em cabine, o mesmo deve ser protegido por fusveis limitadores de corrente e chave seccionadora tripolar de abertura com ou sem carga.
e)
Operao e manobra dos equipamentos de proteo: A operao e manobra dos equipamentos de proteo sempre devem ser feitas por pessoal tcnico especializado, conforme a NR-10 da Portaria 3214/MTbE/78, sendo imprescindvel a utilizao de luvas isolantes de borracha classe adequada a classe de tenso de 36,2kV. Estrados-isolados e bastes adequados para trabalhos em 36,2kV.
8.3
DESCARGAS ATMOSFRICAS
Para proteo contra descargas atmosfricas, devem ser utilizados jogos de pra-raios de invlucro polimrico, a xidos metlicos, sem centelhador, providos de desligador automtico, para uso em redes de distribuio area, tenso nominal de 30kV para sistemas de classe 36,2kV e corrente de descarga nominal de 10kA. a) Subestao de transformao ao tempo:
NORTDE103 b)
16
Subestao de transformao abrigado em alvenaria (cabine) com entrada area: Instalar os pra-raios na parte externa da cabine, junto s buchas de passagem da mdia tenso.
c)
Subestao de transformao abrigado (cabine) com entrada subterrnea: Instalar pra-raios no ponto de tomada do ramal. No interior do posto de transformao abrigado tambm obrigatria a instalao de pra-raios junto as muflas de entrada.
d)
Quando aps o posto de medio ou transformao existir linha primria area, h necessidade da instalao de jogos de pra-raios nas suas extremidades.
8.4
SUBTENSO
Recomenda-se que em casos que haja cargas sensveis ou casos especiais que necessitem de proteo especfica atravs de rels de subtenso, que o cliente deve providenci-las conforme NBR-14039. Preferencialmente, que a proteo contra subtenso seja instalada na rede secundria, junto carga que efetivamente exige este tipo de proteo. 8.5 FALTA DE FASE
Recomenda-se que em caos que haja motores, cargas sensveis ou casos especiais que necessitem de proteo especfica atravs de rels de falta de fase, que o cliente deve providenci-las conforme NBR-14039. Preferencialmente, que a proteo contra falta de fase seja instalada na rede secundria, junto carga que efetivamente exige este tipo de proteo. 8.6 DEMAIS CRITRIOS DE PROTEO NO CITADOS NESTA NORMA DEVEM SER ATENTADOS PELO PROJETISTA PARTICULAR EM ATENDIMENTO AO DISPOSTO NA NORMA NBR -14039. PROTEO EM BAIXA TENSO a) Sobrecorrente A proteo contra sobrecorrente em baixa tenso deve garantir a proteo do(s) transformador(es) contra correntes de sobrecarga e curto-circuito, para que no haja reduo da sua vida til, sendo que o dispositivo de proteo deve permitir a sua coordenao seletiva com a proteo geral de mdia tenso. Para proteo geral em postos de transformao at 300kVA, deve-se instalar disjuntor, localizados depois do medidor. Deve ser executada pelo consumidor de acordo com o que estabelece esta Norma, observadas ainda as exigncias das normas NBR-5410 e NBR-14039.
8.7
NORTDE103
17
O condutor neutro deve ser isolado, devidamente identificado, tendo sua cobertura/isolao (no sendo permitido enfitamento) na cor azul claro, e no conter dispositivo capaz de causar sua interrupo, assegurando assim sua continuidade.
b)
Subtenso A proteo contra subtenso no exigida pela ENERSUL. Caso o consumidor julgue imprescindvel a sua instalao, os equipamentos de proteo contra subtenses devem localizar-se preferencialmente junto s cargas.
9 9.1
ATERRAMENTO VALOR DA RESISTNCIA DE TERRA a) b) O sistema de aterramento dever ter um valor de resistncia mxima de 10 (dez) ohms em qualquer poca do ano: Somente em casos especiais, mediante prvia autorizao da ENERSUL, ser permitido tratamento do solo para enquadramento da resistncia de terra, dentro dos limites fixados acima.
9.2
ELETRODOS
Os eletrodos de terra devem ser hastes de ao cobreado de comprimento mnimo de 2.400 mm e dimetro de 16 mm. 9.3 CONDUTORES a) A interligao dos pra-raios e a descida a malha de terra (condutor de aterramento), devem ser feitas atravs de condutor de cobre nu ou ao cobreado, bitola mnima de 25 mm2; A interligao dos eletrodos deve ser feita atravs de condutores de cobre nu ou de ao cobreado, bitola mnima de 25 mm2. Nunca inferior a bitola do condutor de aterramento; A ligao de partes metlicas normalmente sem tenso, ao sistema de aterramento, deve se feita atravs de condutor de cobre nu ou de ao cobreado, bitola mnima 16 mm2. Enquadram-se neste caso: portes metlicos, suportes de isoladores, carcaa de transformadores, grades de proteo, carcaa de disjuntores, caixas de medio, etc.
b)
c)
9.4
INSTALAO:
9.4.1 CONDUTORES: a) Os pra-raios devem ter o condutor de aterramento prprio e independente para
NORTDE103
18
descida a malha de terra, o mais curto possvel, evitando-se curvas e ngulos pronunciados; b) Os condutores de terra devem obedecer aos seguintes requisitos quanto instalao: Firmemente ligado aos eletrodos por meio de conectores de aperto, sendo permitido o uso de solda do tipo exotrmica; No devem ser embutidos nem colocados em eletrodutos de material magntico;
9.4.2 ELETRODOS: a) b) A distncia entre os eletrodos devem ser no mnimo de 2.400 mm; Os eletrodos de terra, devero ser protegidos com caixa de alvenaria ou concreto, nas dimenses de 400 mm x 400 mm x 400 mm, com tampa de concreto da seguinte maneira: Em Posto Pelo menos uma caixa para ligao e medio da resistncia da terra Em Subestao Pelo menos uma caixa para cada setor ou seja:
Uma para o setor de proteo; Uma para o setor de medio; Uma para o de transformao, para ligao e medio de resistncia.
9.4.3 OUTROS: Devem ser atendidas as demais exigncias da NBR-14039, da ABNT. 10 EQUIPAMENTOS E ACESSRIOS
10.1 POSTES Os postes a serem utilizados devero obedecer as especificaes da ESPTDE-205 - Postes de Concreto para Redes de Distribuio. 10.2 CAIXAS PARA EQUIPAMENTOS DE MEDIO a) b) Os equipamentos de medio devero ser alojados em caixas prprias para esse fim. As caixas devero ser fabricadas por firmas cadastradas, e com modelos previamente aprovados pela ENERSUL.
19
Para proteo contra sobretenso, como descarga atmosfrica e outras, devero ser instalados pra-raios em cruzetas, um em cada fase, nas entradas e sadas de AT, nos pontos de mudana da impedncia caracterstica de linha, com a seguinte especificao: Tipo xido de zinco - polimrico Tenso nominal: 30 kV; Tenso disruptiva sob freqncia industrial (mnima) 45 kV; Tenso disruptiva de impulso onda plena (mxima) 136 kV; Tenso disjuntiva de impulso, frente de onda (mxima) 143 kV; Tenso residual para corrente de descarga e 5 kA (mxima); Corrente de descarga: 10 kA
10.4 CHAVE FUSVEL Caractersticas Bsicas Tipo de distribuio; Tenso Nominal 36,2 kV; Nvel bsico de isolamento 150 kV; Corrente Nominal 100 e 200 A; Capacidade de interrupo simtrica 3.0 KA no mnimo; Para uso ao tempo.
10.5 CHAVE FACA Caracterstica Bsicas: Unipolar; Para uso ao tempo; Tenso Nominal: 36,2 kV; Nvel Bsico de Isolamento:150 kV; Corrente Nominal: 400 A.
10.6 DISJUNTOR DE AT Caractersticas Bsicas: Disjuntor a pequeno volume de leo ou a gs, trifsico; Classe de tenso: 34,5 kV;
NORTDE103
20
Freqncia: 60 Hz; Corrente Nominal: 630 A em regime contnuo; Capacidade de interrupo simtrica: 500 MVA; Nvel Bsico de Isolamento: 150 kV; Operao: - Abertura livre, mecnica e eltrica; Provido de indicador visual de operao para as posies aberto e fechado; Equipados com rels de sobrecorrente, primrios ou secundrios.
10.7 RELS DE SOBRECORRENTE Podem ser: a) b) Primrios -Ligados diretamente ao sistema de potncia AT; Secundrios -Ligados atravs de Transformador de Corrente (TC).
10.8 TRANSFORMADOR DE POTNCIA - PRINCIPAL O transformador de potncia dever, em todas as suas partes, satisfazer as condies fixadas pela ABNT em suas mais recentes publicaes e revises e, ainda: a) b) c) O nvel de isolamento, no lado de tenso superior dever ser de 34,5 kV e no lado de tenso inferior 1,2 kV; O nvel bsico de Impulso, no lado de tenso superior dever ser de 150 kV e no lado de tenso inferior de 30 kV; Dever ter o enrolamento primrio ligado em tringulo, e com taps para ligaes de 36.000, 35.250, 34.500, 33.750 e 33.000 Volts, e o enrolamento secundrio ligado em estrela com neutro acessvel para as tenses de 220/127 Volts; Somente ser permitido a utilizao de tenses diferentes de 220/127 Volts na BT, no caso de haver mais que dois transformadores na mesma instalao, ou a potncia do nico transformador seja acima de 300 kVA. Caso em contrrio dever ser consultado a ENERSUL, antes de qualquer providncia.
d)
10.9 TRANSFORMADOR AUXILIAR Nas instalaes em que a medio for feita em alta tenso, permitido a instalao de um Transformador Auxiliar, cuja aplicao recomendada nos seguintes casos: a) b) Fornecimento de energia em tenso secundria diferente da tenso do transformador principal; Instalao que no necessite uso contnuo dos transformadores de servio de grande potncia. Nestes casos, o Transformados Auxiliar recomendado para atender pequenas cargas, como por exemplo, iluminao noturna.
NORTDE103
21
Nas subestaes com medio em AT, poder ter instalado um transformador de potencial para a alimentao da iluminao artificial da mesma, aps a medio. OBS: Para quaisquer das situaes anteriores, a instalao dever estar aps a medio da concessionria. 11 DETERMINAO DO TIPO DE ENTRADA DE SERVIO
11.1 Para a determinao do tipo da entrada de alimentao da unidade consumidora devese: a) b) c) d) e) f) Dispor da relao de cargas a serem atendidas, e suas potncias nominais. Determinar a Demanda mxima, provvel do conjunto, com base no roteiro do item 12 dessa norma. Obs: Eventuais consideraes especificas devem ser apresentadas pelo projetista no projeto a ser analisado pela ENERSUL. Sabendo-se a Demanda Mxima, escolher a potncia do Transformador de alimentao. De posse da potncia do transformador, consultar o item 6 dessa norma, a fim de verificar em que situao se enquadra. Uma vez determinado o tipo da entrada de servio, deve-se consultar as tabelas e desenhos correspondentes, anexos a esta norma.
11.2 Para Entradas de Servios (com transformao e medio), que se enquadrem dentro da condio, em que no so exigidas a apresentao de projetos eltricos, o clculo da demanda provvel tambm dever ser feito. Tal calculo, dever estar de acordo com os critrios fixados no item 12 desta Norma; 12 CLCULO DA DEMANDA PROVVEL
Estes clculos devero ser efetuados com o objetivo de dar suporte ao dimensionamento das instalaes de entrada de energia. imprescindvel a apresentao destes junto com o projeto a ser encaminhado para a anlise da ENERSUL. O clculo da demanda provvel dever ser feito pela seguinte expresso: D = a + b + c + d + e + f, onde: a = Demanda em KW das potncias para iluminao e tomadas, calculadas segundo a tabela n. 13; b = Demanda, em KW, de todos os aparelhos de aquecimento, (chuveiro, aquecedores, foges, etc), calculada segundo a tabela n. 12; c = Demanda, em KW dos condicionadores de ar segundo a tabela n. 11;
NORTDE103
22
d = Demanda, em KW dos motores e das mquinas de solda tipo motor-gerador, calculada segundo a tabela n. 14; e = Demanda, em KW das mquinas de solda a transformador, conforme indicado abaixo: 100% da potncia, em KW, da maior mquina de solda, mais; 70 % da potncia, em KW, da 2 maior mquina de solda, mais; 40 % da potncia, em KW, da 3maior mquina de solda, mais; 30 % da potncia, em KW, das demais mquinas de solda.
f = Demanda, em KW, dos aparelhos de Raio X, conforme indicado a seguir: 100% da potncia, em KW, do maior aparelho do Raio X, mais; 70% da potncia, em KW, dos aparelhos de Raio X, que trabalham ao mesmo tempo, mais; 20% da potncia, em KW, dos demais aparelhos de Raio X.
12.1 OBSERVAES: Para o clculo da demanda provvel das instalaes devero ser: a) Consideradas as ampliaes de cargas previstas ou provveis. Tal considerao visa somente subsidiar o dimensionamento das instalaes de entrada de energia do consumidor, para que estas no tenham que sofrer alteraes parciais ou totais, quando do aumento da carga. Isto no implica portanto, que a ENERSUL deva ter disponibilidade de seu sistema eltrico, para o pronto atendimento ao incremento da carga considerada, no momento de sua solicitao. Neste caso recomenda-se que a ENERSUL seja consultada antecipadamente, e com tempo suficiente para avaliaes, se haver ou no a necessidade de reforos ao seu sistema eltrico, bem como para as devidas providencias, visando o atendimento do consumidor na data pretendida, se possvel; b) Considerada a potncia requerida pelas cargas a serem atendidas, no ponto eltrico de sua alimentao, ou seja no a potncia que o fabricante do equipamento muitas vezes estabelece no dado de placa ( por exemplo motores eltricos, onde a potncia disponvel nominal informada no ponto de acoplamento com a carga a ser acionada); Desconsideradas as potncias dos aparelhos de reserva.
c)
23
13.1 ELABORAO 13.1.1 exigida a apresentao do projeto eltrico para as subestaes com potncia superior a 300 kVA ou para os casos omissos esta Norma. 13.1.2 O projeto dever ser encaminhado por carta ENERSUL e apresentado em 04 (quatro) vias de igual teor, conter a ART (Anotao de Responsabilidade Tcnica) de elaborao do projeto e ser assinada: pelo Engenheiro Eletricista responsvel, registrado no CREA, e pelo consumidor. Dever fazer parte do projeto os itens abaixo relacionados: a) b) Memorial Descritivo: Descrio geral dos critrios adotados na elaborao do projeto; Relao de carga, clculo da demanda provvel da Unidade de Consumo e previso da data de ligao; Se houver previso de aumento de carga, essa dever ser detalhada, indicando inclusive, a data provvel da efetivao; c) d) e) Planta de localizao da subestao e do ramal de entrada, indicando a rede da ENERSUL; Projeto da subestao em escala mnima de 1:50, formato A 1, contendo o esquema unifilar geral e a planta de situao em escala 1:1000; Em formato A1, os detalhes do projeto dos seguintes itens: f) g) Sistema de aterramento; Chave reversora, se houver gerao prpria; Ramal de entrada subterrneo; Cerca externa; Servio de drenagem; Bases para instalaes dos transformadores; Porto de acesso a subestao.
Relao de materiais, contendo especificao detalhada dos materiais e equipamentos utilizados na montagem da subestao e do ramal de ligao. Demais detalhes que o projetista julgar importante, para anlise da ENERSUL, antes de sua execuo.
13.2 ANLISE E APROVAO Aps o recebimento do projeto, a ENERSUL proceder anlise, dentro do prazo de 45 dias.
24
A execuo da entrada de servio, aps a aprovao do projeto eltrico, dever obedecer rigorosamente as condies constantes do mesmo. Recomenda-se que o inicio das obras ocorra somente aps o parecer da anlise do projeto pela ENERSUL, tendo em vista que a antecipao desta pode implicar em custos adicionais ao interessado, visando a adequao ao referido parecer e por sua vez a esta Norma. Nos casos em que no houver a necessidade da apresentao de projeto, as instalaes devero ser rigorosamente executadas de forma a atender as normas da ENERSUL, sob pena de requerer alteraes, nas mesmas condies anteriores descritas. Os casos com caractersticas especificas, que no se enquadrem nas situaes aqui apresentadas, podero ser consultados previamente a ENERSUL, de forma a esclarecer eventuais dvidas do projetista / executor das obras. Por ocasio da solicitao do pedido de vistoria da entrada de servio, ser exigida a guia de anotao de responsabilidade tcnica ART, de execuo da instalao eltrica, do CREA MS, devidamente preenchida e autenticada mecanicamente. 13.4 VALIDADE E APROVAO A aprovao do projeto ter a validade de 18 (dezoito) meses para execuo. Aps este prazo, dever ser feito nova consulta ENERSUL, contemplando-se no projeto a ser encaminhado, as atualizaes necessrias, de forma a atender as normas vigentes. Caso no haja nenhuma alterao a ser efetuada para tal, dever ser encaminhado o projeto anterior aprovado para revalidao. 14 PEDIDO DE LIGAO
A solicitao do fornecimento de energia eltrica a ENERSUL, deve ser formalizada atravs do Pedido de Ligao efetuado pelo interessado, nas Agncias de Atendimento da Empresa. Para o Pedido de Ligao devem ser fornecidos os dados que permitam o seu correto preenchimento para fins cadastrais, ou seja: a) b) c) Nome do consumidor. Ramo de atividade e nome da Empresa, se for o caso. Documento de identificao.
Para consumidores residenciais, a identificao exigida deve ser atravs de um dos documentos abaixo: Carto de Identificao do Contribuinte; Registro Geral de Identificao; Ttulo de Eleitor;
NORTDE103
25
Para no residenciais, so exigidos todos os seguintes documentos: d) e) Cadastro Nacional de Pessoa Jurdica; Contrato social; Estatuto; Inscrio Estadual; Alvar de Funcionamento.
Relao de cargas a serem ligadas. Projeto eltrico aprovado. Para as subestaes que necessitam de projeto eltrico, conforme item 13.1.1. Relatrio de ensaio e diagrama de ligao do transformador. Contrato de fornecimento: Para fins de contrato de fornecimento, devero ser apresentados, ainda, em fotocpia os seguintes documentos: Quando se tratar de Sociedade Annima(S/A): Estatuto Oficiais atualizados da Empresa; Publicao da Ata da Assemblia Geral de Acionistas que elegeu a atual Diretoria; Certido de Registro na Junta Comercial; Certido de Registro no Cadastro Nacional de Pessoa Jurdica (CNPJ).
f) g)
Quando se tratar de companhia limitada LTDA ou firma individual: Contrato social com registro na Junta Comercial, ou em cartrio, tratando-se de sociedade Civil), atualizado; Certido de Registro no Cadastro Nacional de Pessoa Jurdica (CNPJ). OBS: A assinatura do Contrato de Demanda preceder a efetivao da ligao. 15 SEGURANA
Recomenda-se os seguintes procedimentos a fim de resguardar a segurana do pessoal e dos equipamentos em subestaes de consumidores:
26
Toda e qualquer manobra somente poder ser feita por pessoa capacitada e devidamente autorizada; Quando for autorizada a execuo de uma manobra, a ordem deve ser transmitida com clareza e preciso, deve-se certificar que a pessoa encarregada da manobra, entendeu corretamente a ordem dada; Antes de executar qualquer manobra deve-se planej-la e concentrar-se com ateno sobre o que se vai fazer, agindo calmamente e com segurana. Deve-se certificar do que no h perigo de acidentes; Todas as manobras, mesmo as que so feitas por meio de volantes ou alavancas, devem ser efetuadas pisando-se em estrado isolado e usando luvas de borracha com isolao adequada tenso de servio; Antes de se usar os equipamentos de segurana (basto, capacete, cintos, luvas de borracha, estrados isolados, extintor de incndio, etc.), deve-se verificar o estado em que esses equipamentos se encontram, e se so apropriados para o servio a executar; Nunca deve-se desligar as chaves-facas, ou chaves fusveis destinadas abertura sem carga, quando houver carga ligada nos circuitos dessas chaves; Deve-se colocar em lugar visvel, um quadro com o diagrama unifilar da instalao (utilizando a simbologia padronizada pela ABNT), a fim de facilitar a manobra.
c)
d)
e)
f) g)
15.2 CUIDADOS DIVERSOS REFERENTES AO RECINTO DAS INSTALAES a) b) c) d) e) f) g) Deve-se colocar na entrada, em lugar visvel, uma placa com a descrio PERIGO DE MORTE ALTA TENSO, com os smbolos indicativos do risco existente; Deve-se proibir a entrada de pessoas estranhas e no habilitadas; Deve-se conservar a entrada de acesso livre e desimpedida; No se deve guardar materiais ou ferramentas no recinto das instalaes; Deve-se ter mo, recursos para a iluminao de emergncia (faroletes, lanternas, etc), para se locomover com segurana, se houver falta de energia; Quando sair do recinto, deve-se fechar a porta, e no deixar a chave ao alcance de pessoas estranhas; Em caso de incndio, na subestao do consumidor, deve-se desligar a energia e utilizar somente extintores adequados (CO2 ou p qumico), ou areia seca, NUNCA DEVE-SE UTILIZAR GUA OU EXTINTOR DE ESPUMA.
27
Os dispositivos desta Norma aplicam-se s condies normais de fornecimento de energia eltrica. Os casos omissos, ou aqueles cujas caractersticas excepcionais exijam um tratamento parte, devero ser consultados previamente, e se necessrio encaminhados formalmente, para estudo e deciso de rgos competentes na ENERSUL.
NORTDE103
28
POTNCIA
(kVA)
BITOLA MNIMA
(mm)
25 35
4 6
FIO (AWG) 4 4
NORTDE103
TABELA 4 CORRENTE DE AJUSTE DE RELS PRIMRIOS
29
POTNCIA EM TRANSFORMADOR (kVA) 1001 1051 1101 1151 1201 1251 1301 1351 1401 1451 1501 1551 1601 1651 1701 1751 1801 1851 1901 1951 2001 2051 2101 2151 2201 2251 2301 2351 2401 2451 a a a a a a a a a a a a a a a a a a a a a a a a a a a a a a 1050 1100 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600 1650 1700 1750 1800 1850 1900 1950 2000 2050 2100 2150 2200 2250 2300 2350 2400 2450 2500
CORRENTE DE AJUSTE (A) 19,5 20,0 21,0 22,0 23,0 24,0 25,0 26,0 27,0 27,5 28,5 29,5 30,5 31,5 32,0 33,0 34,0 35,0 36,0 37,0 38,0 38,5 39,5 40,5 41,5 42,5 43,0 44,0 45,0 46,0
NORTDE103
OBSERVAES REFERENTES A TABELA 04 :
30
1) Os transformadores de reserva no devem ser considerados na potncia; 2) Os rels devem ser instantneos; 3) A corrente nominal dos reles deve ser escolhida de maneira a permitir a corrente de ajuste indicada na tabela; 4) Se os rels forem secundrios, a corrente de ajuste dever ser calculada e apresentado a memria de clculo, juntamente com o projeto para anlise e aprovao.
POTNCIA (KVA)
CORRENTE (A)
POTNCIA (KVA)
CORRENTE (A)
POTNCIA (KVA)
CORRENTE (A)
POTNCIA (KVA)
CORRENTE (A)
NORTDE103
TABELA 6 FORNECIMENTO EM ALTA TENSO COM MEDIO NA BAIXA TENSO 220/127V
31
TRAFO (KVA)
FUSVEL (A)
1) Entre parntesis indica-se o condutor neutro quando sua bitola for diferente da do condutor fase. 2) A corrente nominal do disjuntor termomagntico referida a 40 C. 3) A chave blindada poder ser substituda por um disjuntor termomagntico tripolar. 4) Os fusveis quando empregados, sero retardados tipo NH. 5) A bitola indicada para os condutores o valor mnimo admissvel. Para cargas situadas a grandes distncias, redimensionar os condutores usados aps a medio. 6) Os condutores devero ser prprios para a temperatura de at 70 C no mnimo. 7) Multiplicando a corrente (em ampres) na tabela 5 pela constante 156,2 obteremos a corrente na Baixa Tenso. (220 V).
NORTDE103
TABELA 7 ESCOLHA DE ELOS FUSVEIS PARA PROTEO DE TRANSFORMADORES
32
TRANSFORMADORES TRIFSICOS POTNCIA NOMINAL (kVA) 15 30 45 75 112,5 150 225 300 500 750 1000 1H 1H 2H 2H 3H 5H 6K 10 K 10 K 15 K 15K ELO FUSVEL CHAVE FUSVEL (AMPERES) 100 100 100 100 100 100 100 200 200 200 200
POTNCIA INSTALADA (KVA) At 200 De 201 a 500 De 501 A 1000 De 1001 a 2500
OBSERVAES:
ELO FUSVEL 10 K 15 K 25 K 40 K
1) A tabela refere-se em todos os casos, a tenso nominal de 34.500 Volts entre fases. 2) No cmputo da potncia total instalada no devero ser considerados os transformadores de reserva. 3) Quando a soma das potncias em transformadores no constar da tabela, dever ser adotado o elo fusvel indicado para a potncia imediatamente superior.
NORTDE103
TABELA 8 PROTEO GERAL EM BAIXA TENSO
33
TRANSFORMADORES TRIFSICOS POTNCIA (kVA) 15 30 45 75 112,5 150 225 300 500 750 1000 FUSVEL (A) 40 100 125 200 300 400 600 800 2 x 630 2 x 1000 3 x 1000 DISJUNTOR TERMOMAGNTICO (A) 40 90 125 200 300 400 600 800 1600 2000 3000
NOTAS
1) Para transformadores trifsicos de 500 a 750 kVA, a tabela indica dois fusveis por fase e para transformadores de 1000 kVA, trs fusveis por fase 2) Todos os fusveis so do tipo NH retardados 3) Esta tabela no se aplica a transformadores com medio em baixa tenso, para os quais vale a tabela 6 4) No caso de se usar proteo com fusveis, a chave blindada dever ter capacidade conveniente, no mnimo de corrente nominal igual a dos fusveis.
NORTDE103
TABELA 9 DISPOSITIVO DE PARTIDA DE MOTORES TRIFSICOS
34
TIPO
MTODO DE PARTIDA
Reostato
NOTAS
1) Em substituio a chave estrela-tringulo permitem-se as chaves de reatncia, desde que reduzam a tenso de partida a, pelo menos, 65 %. 2) No caso de compensadores, a tenso de partida deve ser reduzida no mnimo a 65 %. 3) Para o tipo rotor bobinado, deve existir um bloqueio que impea a partida do motor com as escovas levantadas.
NORTDE103
TABELA 10 POTNCIA DOS CONDICIONADORES DE AR
35
CAPACIDADE TRMICA (Btu/h) At 6000 7100 A 10000 12000 A 14000 16000 18000 A 19000 21000 A 26500 27000 A 30000
Para capacidade superior aos valores constante na tabela acima, o dimensionamento dever ser feito em funo dos dados tcnicos do fabricante.
100 86 80 78 75 70 65 60
NORTDE103
TABELA 12 FATORES DE APARELHOS DE AQUECIMENTO
36
NMERO DE APARELHOS POTNCIA DE POTNCIA POTNCIA ACIMA DE AT 3,5 KW ACIMA DE 3,5 KW 3,5 kW 80 65 55 50 45 43 40 36 35 34 32 32 32 32 32 16 17 18 19 20 21 22 23 24 25 26 a 30 31 a 40 41 a 50 51 a 60 61 ou mais 39 38 37 36 35 34 33 32 31 30 30 30 30 30 30 28 28 28 28 28 26 26 26 26 26 24 22 20 18 16
NORTDE103
TABELA 13 CARGA MNIMA DE DEMANDA PARA INSTALAES DE ILUMINAO E TOMADAS
37
DESCRIO
CARGA MNIMA
(W/ m)
POTNCIA INSTALADA
(kW)
FATOR DE DEMANDA
(%)
Auditrios, Sales p/ Exposies e semelhantes Bancos, Lojas e semelhantes Indstria e semelhantes Barbearias, Sales de Beleza e semelhantes Clubes e semelhantes Escolas e semelhantes Edifcios de escritrios, Escritrios Garagens comerciais e semelhantes Hospitais e semelhantes Hotis e semelhantes Igrejas e semelhantes Prdio de Apartamentos e Residncias Restaurantes e semelhantes Consultrio Mdicos e semelhantes
15 40 30 30 30 30 5 20 20 15 30 20 30
Total Total Total Total Total Para os primeiros 12 kW. Para o que exceder de 12 kW. Para os primeiros 20 KW. Para o que exceder de 20 kW. Total Para os primeiros 50 kW. Para o que exceder de 50 kW. Para os primeiros 20 kW. Para o que exceder de 20 kW. Total Para os primeiros 3 kW. De 3 kW a 120 KW Acima de 120 KW Total Para os primeiros 50 kW. Para o que exceder de 50 kW.
100 100 100 100 100 100 50 100 70 100 50 20 50 40 100 100 35 25 100 50 20
NORTDE103
NOTAS REFERENTE A TABELA 13
38
1) A tabela se refere a carga mnima das instalaes eltricas para iluminao e tomadas at 600 W, em funo da rea da construo, com os respectivos fatores de demanda. 2) Em quaisquer dos casos constantes desta tabela, nas reas destinadas a corredores e passagens, bem como almoxarifados, rouparias e depsitos de materiais em geral, ser considerada a carga mnima de 5 W/m2 com demanda de 100 %. 3) Os alimentadores do recinto em que, por natureza toda a carga seja utilizada simultaneamente (sala de operaes, sales de baile, recepes e semelhantes) devero ser considerados com o fator de demanda de 100 %. 4) No caso de lojas, dever-se- computar uma carga de 700 W/m2 de vitrine, medida horizontalmente ao longa de sua base.
NORTDE103
TABELA 14 FATORES DE DEMANDA DE MOTORES E MQUINAS DE SOLDA TIPO MOTOR GERADOR
39
De 1/6 a 1,0
90
80
70
60
85 78 70
75 70 63
65 60 58
58 55 50
Foram adotados valores mdios do fator de potncia e rendimento, conforme indicao do fabricante.
NORTDE103
40
320
350
0 20
450
540
2 20
620
600
2 20
OBS: TODAS AS CAIXAS ACIMA DEVERO TER DISPOSITIVO PARA LACRES, BEM COMO AS DE PASSAGEM NAS FIAES DOS SECUNDRIOS DOS TCs E TPs.
620
NORTDE103
DESENHO 02 SUBESTAO DE TRANSFORMAO E MEDIO EM BAIXA TENSO POTNCIA AT 30 KVA INCLUSIVE MURETA
41
150
150
100
950 34 39 41 200
400
400
150
100
4 3 8
10-13 43-35-37
14 15
DIAGRAMA UNIFILAR
8200
16
22
26 1700 9 27
NOTAS:
1) TODAS AS MEDIDAS SO MNIMAS E ESTO EM MILMETROS; 2) O DISJUNTOR DE PROTEO GERAL DEVER OBEDECER TABELA 6.
VER NOTA 5
200
17 18
12
NORTDE103
RELAO DE MATERIAIS
42
Item Unid
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 p p p p p p p p kg kg p p kg p p p p p m p p par m m kg p p p p p kg p p p p p p p p p p p
Quantidade C
01 V 02 03 03 03 02 04 V V 03 10 V 02 01 06 02 04 V 02 02 02 V V V 01 01 V 01 01 V 02 04 06 02 01 16 04 07 04 -
DISCRIMINAO
Poste de concreto 300 Kgf Pasta anti-xido Cruzeta de concreto 90 x 90 x 2000 mm Isolador de pino para 27 kV Isolador de pino para 27 kV Pra-Raios tipo vlvula classe 30 kV com ferragens Sela para cruzeta de 112,5 mm Mo francesa normal de 726 mm Fio de cobre nu 16 mm2 Fio de cobre nu 25 mm2 Conector tipo parafuso fendido tamanho adequado Conector paralelo de alumnio bimetlico tamanho adequado Grampo de cerca Suporte para instalao de transformador Transformador de distribuio trifsico Cinta para poste de concreto com parafusos e porcas tam. adequado Armao secundria de 2 estribos Isolador de porcelana para baixa tenso tipo roldana Eletroduto de ferro esmaltado Curva de 135 Luva de emenda Bucha e contra bucha Arame de ferro galvanizado n. 12 BWG Condutor de cobre isolado para 750 v Condutor de cobre nu (neutro) Caixa para medidor trifsico Mureta de alvenaria Haste para terra com conector adequado Caixa de alvenaria para aterramento Caixa de passagem para sada subterrnea (opcional) Cabo de cobre nu 25 mm2 p/ interlig. das hastes e desc. dos P/Raios Parafuso de rosca dupla ( passante) 16 mm (5/8) comp. adequado Parafuso cabea quadrada 16 mm (5/8) comp. adequado Parafuso cabea quadrada 16 mm (5/8) x 128 mm (5) Parafuso francs de 16 mm (5/8) x 45 mm (1 3/4) Parafuso francs de 16 mm (5/8) x 150 mm (6) Parafuso Porca quadrada para parafuso de 16 mm (5/8) Porca quadrada para parafuso de 9,5 mm ( 3/8) Arruela quadrada 57 mm ( 2 1/4) com ferro 18 mm (11/16) Arruela redonda com furo 11 mm (7/16) Arruela de presso furo 17,5 mm (11/16)
DT
01 V 02 03 03 03 04 V V 03 10 V 02 01 04 02 04 V 02 02 02 V V V 01 01 V 01 01 V 02 02 04 04 01 14 04 07 04 01
NORTDE103
43
DESENHO 03 SUBESTAO DE TRANSFORMAO E MEDIO EM BAIXA TENSO POTNCIA AT 30 KVA INCLUSIVE SEM MURETA
150
150
100
400
400
150
100
4 3 8
10-13 43-35-37
11
17 18
8200
DIAGRAMA UNIFILAR
16 24-25 20 21 19 VER ITEM 5.2.2.2.B 6000 REDE DIST. ENERSUL 23
22
26 1700 9
27
VER DETALHES
FRENTE
CORTE AA
CORTE BB
NOTAS:
1) TODAS AS MEDIDAS SO MNIMAS E ESTO EM MILMETROS; 2) O DISJUNTOR DE PROTEO GERAL DEVER OBEDECER TABELA 6.
NORTDE103
RELAO DE MATERIAIS
44
Item Unid
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 p p p p p p p p kg kg p p kg p p p p p m p p par m m kg p p p p p kg p p p p p p p p p p p
Quantidade C
01 V 02 03 06 03 02 04 V V 03 10 V 02 01 07 02 04 V 02 02 02 V V V 01 01 V 01 01 V 02 04 06 02 01 04 04 04 07 -
DISCRIMINAO
Poste de concreto 300 Kgf Pasta anti-xida Cruzeta de concreto 90 x 90 x 2000 mm Isolador de pino para 27 kV Isolador de pino para 27 kV Pra-Raios tipo vlvula classe 30 kV com ferragens Sela para cruzeta de 112,5 mm Mo francesa normal de 726 mm Fio de cobre nu 16 mm2 Fio de cobre nu 25 mm2 Conector tipo parafuso fendido tamanho adequado Conector paralelo de alumnio bimetlico tamanho adequado Grampo de cerca Suporte para instalao de transformador Transformador de distribuio trifsico Cinta para poste de concreto com parafusos e porcas tam. adequado Armao secundria de 2 estribos Isolador de porcelana para baixa tenso tipo roldana Eletroduto de ferro esmaltado Curva de 135 Luva de emenda Bucha e contra bucha Arame de ferro galvanizado n. 12 BWG Condutor de cobre isolado para 750 v Condutor de cobre nu (neutro) Caixa para medidor trifsico Suporte para caixa de medio Haste para terra com conector adequado Caixa de alvenaria para aterramento Caixa de passagem para sada subterrnea (opcional) Cabo de cobre nu 25 mm2 p/ interlig. das hastes e desc dos P/Raios Parafuso de rosca dupla ( passante) 16 mm (5/8) comp. adequado Parafuso cabea quadrada 16 mm (5/8) comprimento adequado Parafuso cabea quadrada de 16 mm (5/8) x 125 mm ( 5) Parafuso francs de 16 mm (5/8) x 45 mm (1 3/4) Parafuso francs de 16 mm (5/8) x 150 mm (6) Parafuso Porca e arruela de 5 mm (3/16) x 19,5 mm (3/4) Porca quadrada para parafuso de 16 mm ( 5/8) Porca quadrada para parafuso de 9,5 mm (3/8) Arruela quadrada 57 mm com furo de 18 mm Arruela redonda com furo 11 mm
DT
01 V 02 03 06 03 04 V V 03 10 V 02 01 05 02 04 V 02 02 02 V V V 01 01 V 01 01 V 02 02 04 04 01 04 04 04 07 01
NORTDE103
45
DESENHO 04 SUBESTAO DE TRANSFORMAO E MEDIO EM BAIXA TENSO POTNCIA DE 45 KVA A 112,5 KVA INCLUSIVE EM MURETA
150
150
100
950 38 43 45 200
400
400
150
100
4 3 8
1000
10-13 39-41-46
11 9
26
15
14
DIAGRAMA UNIFILAR
6400 12 200
27
17 18
16 23
20 21
31
22 28 29 30
1700
2200 9
2200
26
27
33-36
RESISTNC IA MX. 10
NO TAS:
1) TODAS AS M EDIDAS SO M NIMAS E ESTO EM MILMETROS; 2) O DISJUNTO R DE PROTEO GERAL DEVER OBEDECER TABELA 6; 3) CAIXA DE TC E M EDIO CO M DISPOSITIVO PARA LACRES.
6000
NORTDE103
RELAO DE MATERIAIS
46
Item Unid
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 p p p p p p p p kg kg p p kg p p p p p m p p par m m kg p p p p p kg p p p kg p p p p p p
Quantidade C
01 V 02 03 03 03 02 04 V V 03 10 V 02 01 06 02 04 V 02 02 02 V V V 01 01 01 01 06 01 V 01 01 V 02 06 06 02 01
DISCRIMINAO
Poste de concreto 600 Kgf Pasta anti-xido Cruzeta de concreto 90 x 90 x 2000 mm Isolador de pino para 27 kV Pino para isolador 27 kV Pra-Raios tipo vlvula classe 30 kV com ferragens Sela para cruzeta de 112,5 mm Mo francesa normal de 726 mm Fio de cobre nu 16 mm2 Fio de cobre nu 25 mm2 Conector tipo parafuso fendido Conector paralelo de alumnio bimetlico tamanho adequado Grampo de cerca Suporte para instalao de transformador Transformador de distribuio trifsico Cinta para poste de concreto com parafusos e porcas tam. adequado Armao secundria de 2 estribos Isolador de porcelana para BT tipo roldana Eletroduto de ferro esmaltado Curva de 135 Luva de emenda Bucha e contra bucha Arame de ferro galvanizado n. 12 BWG Condutor de cobre isolado para 750 v Condutor de cobre nu (neutro) Caixa para medidores de demanda e energia radioativa Caixa para transformador de corrente Caixa blindada para chave faca tripolar ou disjuntor termomagntico Chave faca com fusvel tipo NH ou disj. termomagntico dimenso adequado Terminal Estanhado dimensionamento adequado Mureta de alvenaria de 2.200 x 2.000 largura adequada Haste para terra com conector adequado Caixa de alvenaria para aterramento Caixa de passagem para sada subterrnea (opcional) Cabo de cobre nu 25 mm2 p/ interlig. das hastes e descidas dos P/Raios Parafuso passante 5/8comprimento adequado Parafuso cabea quadrada 16 mm (5/8) comprimento adequado Parafuso cabea quadrada 16 mm (5/8), 125 mm ( 5) Parafuso francs de 16 mm (5/8) x 45 mm (1 3/4) Parafuso francs de 16 mm (5/8) x 150 mm (6) Parafuso
DT
01 V 02 03 03 03 04 V V 03 10 V 02 01 04 02 04 V 02 02 02 V V V 01 01 01 01 06 01 V 01 01 V 02 02 04 04 01
NORTDE103
47
Item
42 43 44 45 46
Uni
p p p p p
Quantidade C
16 04 10 04 -
DISCRIMINAO
Porca quadrada para parafuso de 16 mm (5/8) Porca quadrada para parafuso de 9,5 mm ( 3/8) Arruela quadrada 57 mm ( 2 1/4) com furo 18 mm (11/16) Arruela redonda com furo 11 mm (7/16) Arruela de presso furo 17,5 mm (11/16)
DT
14 04 10 04 01
NORTDE103
48
DESENHO 05 SUBESTAO DE TRANSFORMAO E MEDIO E MEDIO EM BAIXA TENSO POTNCIA DE 45 KVA A 112,5 KVA INCLUSIVE SEM MURETA
150
100
950 36 42 44
400
150
400
100
4 3
8 10 13 37 39 45 11 9 CHAVE OU DISJUNTOR DE PROTEO GERAL 14 23-24 20 15 21 26 23-24 200 12 16 SEGUE P/ CH. PROTEO GERAL 27-28-29 REDE DIST. ENERSUL 22 26 MEDIO ENERSUL 1
DIAGRAMA UNIFILAR
19
18 17
21
21 30
25 1700
7 34-40
46
FRENTE
CORTE AA
CORTE BB
NOTAS:
1) TODAS AS MEDIDAS SO MNIMAS E ESTO EM MILMETROS; 2) O DISJUNTOR DE PROTEO GERAL DEVER OBEDECER TABELA 6; 3) CAIXAS DE TC's E MEDIO COM DISPOSITIVO PARA LACRE.
5500 B B
NORTDE103
RELAO DE MATERIAIS
49
C
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 p p p p p p p p kg kg p p kg p p p p p m p p m m kg p p p p p p p p kg p p p p p p p p p p p p 01 V 02 03 03 03 02 04 V V 03 10 V 02 01 08 02 04 V 02 02 V V V 01 01 01 01 06 01 V 01 V 02 04 06 02 01 04 16 04 07 04 -
DT
01 V 02 03 03 03 04 V V 03 10 V 02 01 06 02 04 V 02 02 V V V 01 01 01 01 06 01 V 01 V 02 02 04 04 01 04 14 04 07 04 01 Poste de concreto 600 Kgf Pasta anti-xida Cruzeta de concreto 90 x 90 x 2000 mm Isolador de pino para 27 kV Isolador de pino para 27 kV pra-raios tipo vlvula classe 30 kV com ferragens Sela para cruzeta de 112,5 mm Mo francesa normal de 726 mm Fio de cobre nu 16 mm2 Fio de cobre nu 25 mm2 Conector tipo parafuso fendido Conector paralelo de alumnio bimetlico tamanho adequado Grampo de cerca Suporte para instalao de transformador Transformador de distribuio trifsico Cinta para poste de concreto com parafusos e porcas Armao secundria de 2 estribos Isolador de porcelana para BT tipo roldana Eletroduto de ferro esmaltado Curva de 90 Luva de emenda Arame de ferro galvanizado n. 12 BWG Condutor de cobre isolado para 750 v Condutor de cobre nu (neutro) Caixa para medidores de demanda e energia reativa Caixa para transformador de corrente Caixa Blindada para chave faca tripolar ou disjuntor termomagntico Chave faca com fus. tipo NH ou disj. termom. dimens adequado Terminal estanhado dimensionamento adequado Suporte para caixa de TC e medio, tamanho adequado Haste para terra com conector adequado Caixa de alvenaria para aterramento Cabo de cobre nu 25 mm2 p/ interlig. das hastes e desc dos P/Raios Parafuso passante 5/8 comp. adequado Parafuso cabea quadrada 16 mm (5/8) comprimento adequado Parafuso cabea quadrada 16 mm (5/8), 125 mm ( 5) Parafuso francs de 16 mm (5/8) x 45 mm (1 3/4) Parafuso francs de 16 mm (5/8) x 150 mm (6) Parafuso Parafuso com porca e arruela de 5 mm x 19,5 mm Porca quadrada para parafuso de 16 mm (5/8) Porca quadrada para parafuso de 9,5 mm (3/8) Arruela quadrada 57 mm ( 2 1/4) com furo 18 mm (11/16) Arruela redonda com furo 11 mm (7/16) Arruela de presso furo 17,5 mm (11/16)
NORTDE103
50
DESENHO 06 SUBESTAO DE TRANSFORMAO E MEDIO EM BAIXA TENSO POTNCIA DE 45 A 225 KVA INCLUSIVE EM MURETA
250 150
150
150
650
500
150 250
150 200 5-6 7 MEDIO ENERSUL 1000 CHAVE OU DISJUNTOR DE PROTEO GERAL 38 1
3 10 11 13 40 41
9 2750 13 42
23 16
14 4 VER DET. PG N 85
DIAGRAMA UNIFILAR
39 43 44
200
18
17
45
20
26
5500
9 34 24 29 30 25 9 31 32 33
RESISTNCIA MX. 10
NOTAS:
1) TODAS AS MEDIDAS SO MNIMAS E ESTO EM MILMETROS; 2) O DISJUNTOR DE PROTEO GERAL DEVER OBEDECER TABELA 6; 3) CAIXAS DE TC's E MEDIO COM DISPOSITIVO PARA LACRE.
2000
NORTDE103
RELAO DE MATERIAIS
51
Item
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43
Uni
p p p p p p p p kg kg p p kg kg m p p p p p p m p p par m m kg p p p p p p p p kg p p p p p
Quantidade C
02 V 02 02 03 03 03 04 V V 03 10 V 02 V 01 01 04 04 02 04 V 02 02 02 V V V 01 01 01 01 06 01 V 01 01 V 10 04 44 44
DISCRIMINAO
Poste de concreto 300 Kgf Pasta anti-xido Cruzeta de ao perfilado cantoneira 75 x 75 x 8 mm e 2400 mm Cruzeta de ao perfilado cantoneira de 75 x 75 x 8 mm e 2.600 mm de comprimento Isolador de pino para 27 kV Isolador de pino para 27 kV Pra-Raios tipo vlvula classe 30 kV com ferragens Sela para cruzeta de madeira 112,5 mm Fio de cobre nu 16 mm2 Fio de cobre nu 25 mm2 Conector tipo parafuso fendido Conector paralelo de alumnio bimetlico tamanho adequado Grampo de cerca Prensa fio com trs (03) parafusos Cabo de ao de 1/4 SM Transformador de distribuio trifsico Suporte para fixao de eletroduto Pea de madeira de 115 x 135 mm, comprimento adequado Cinta para poste de concreto com parafusos e porcas tam. adequado Armao secundria de 2 estribos Isolador de porcelana para baixa tenso tipo roldana Eletroduto de ferro esmaltado Curva de 135 Luva de emenda Bucha e contra bucha Arame de ferro galvanizado n. 12 BWG Condutor de cobre isolado para 750 v Condutor de cobre nu (neutro) Caixa para medidores de demanda e energia reativa Caixa para transformadores de corrente tamanho adequado Caixa blindada para chave faca tripolar ou disjuntor termomagntico Chave faca com fus. tipo NH ou disjuntor termom. dimens. adequado Terminal estanhado dimensionamento adequado Mureta de alvenaria 2.200 x 2.000 largura adequada Haste para terra com conector adequado Caixa de alvenaria para aterramento Caixa de passagem para sada subterrnea (opcional) Cabo de cobre nu 25 mm2 para interligao das hastes de terra Parafuso passante 16 mm (5/8) comprimento adequado Parafuso cabea quadrada 16 mm (5/8) comprimento adequado Parafuso francs de 16 mm (5/8) x 150 mm (6) Porca quadrada para parafuso de 16 mm (5/8) Arruela quadrada 57 mm ( 2 1/4) com furo 18 mm (11/16)
DT
02 V 02 02 03 03 03 V V 03 10 V 02 V 01 01 04 02 04 V 02 02 02 V V V 01 01 01 01 06 01 V 01 01 V 10 02 42 44
NORTDE103
DESENHO 07 SUBESTAO DE TRANSFORMAO E MEDIO EM BAIXA TENSO POTNCIA DE 45 A 225 KVA INCLUSIVE SEM MURETA
52
38
2750
15
14
18 16
28 4 17 40-41 36 22 31-32 23
DIAGRAMA UNIFILAR
30
21
5500
34 33
CAIXA DE ATERRAMENTO
RESISTNCIA MX. 10
42
FRENTE
CORTE AA
MN. 5,00m B B
CORTE BB
NOTAS:
1) TODAS AS MEDIDAS SO MNIMAS E ESTO EM MILMETROS; 2) O DISJUNTOR DE PROTEO GERAL DEVER OBEDECER TABELA 6; 3) CAIXAS DE TC's E MEDIO COM DISPOSITIVO PARA LACRE.
NORTDE103
RELAO DE MATERIAIS
53
Item
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
Uni
p p p p p p p p kg kg p p kg kg m p p p p p m p par p p p m p p m m kg p p kg p p p p p p p
Quantidade C
02 V 02 02 03 03 03 04 V V 03 10 V 02 V 01 04 08 02 04 V 02 04 01 01 01 V 06 02 V V V V 01 V 10 04 01 44 41 04
DISCRIMINAO
Poste de concreto 300 Kgf Pasta anti-xido Cruzeta de ao perfilado cantoneira de 75 x 75 x 8 mm e 2400 mm Cruzeta de ao perfilado cantoneira de 75 x 75 x 8 mm e 2.600 mm de comprimento Isolador de pino para 27 kV Isolador de pino para 27 kV Pra-Raios tipo vlvula classe 30 kV com ferragens Sela para cruzeta de madeira 112,5 mm Fio de cobre nu 16 mm2 Fio de cobre nu 25 mm2 Conector tipo parafuso fendido Conector paralelo de alumnio bimetlico tamanho adequado Grampo de cerca Prensa fio com trs (03) parafusos Cabo de ao de 1/4 SM Transformador de distribuio trifsico Pea de madeira de 115 x 135 mm, comprimento adequado Cinta para poste de concreto com parafusos e porcas tam. adequado Armao secundria de 2 estribos Isolador de porcelana para baixa tenso tipo roldana Eletroduto de ferro esmaltado Curva de 90 Bucha e contra bucha Caixa para medidores de demanda e energia reativa Caixa para transformadores de corrente tamanho adequado Caixa blindada para chave faca tripolar ou disjuntor termomagntico Chave faca com fus. tipo NH ou disjuntor termom. dimens. adequado Terminal estanhado dimensionamento Suporte para caixa e TC e medio, tamanho adequado Arame de ferro galvanizado n. 12 BWG Condutor de cobre isolado para 750 V Condutor de cobre nu (neutro) Haste para terra com conector adequado Caixa de alvenaria para aterramento Cabo de cobre nu 25 mm2 para interligao das hastes de terra Parafuso passante 16 mm (5/8) comprimento adequado Parafuso cabea quadrada 16 mm (5/8) comprimento adequado Parafuso francs de 16 mm (5/8) x 150 mm (6) Parafuso Porca quadrada para parafuso de 16 mm (5/8) Arruela quadrada 57 mm ( 2 1/4) com furo 18 mm (11/16) Parafuso com porca e arruela de 5 mm x 19,5 mm
DT
02 V 02 02 03 03 03 V V 03 10 V 02 V 01 04 06 02 04 V 02 04 01 01 01 V 06 02 V V V V 01 V 10 02 01 42 41 04
NORTDE103
54
DESENHO 08 SUBESTAO DE TRANSFORMAO E MEDIO EM BAIXA TENSO POTNCIA AT 300 KVA - INCLUSIVE
18
11 3 16 17 19 33
6000 MNIMO
4 5 15 20 21 2600
PERIGO
34
22 40 23
ALTA TENSO
34 42
100
31
12
30
32
1500
2000
1500
1500
CORTE -AA
9-10 150 6-7 500 MN. 13 37-38-39-40
500 MN.
1050
1050
150
32
44-45-46-47 35
43
PLANTA
25 1700
26 29
27 28 2000
DETALHE B
NOTAS:
1) A BASE DO TRANSFORMADOR DEVER SER CONFECCIONADO CONFORME SUA POTNCIA E CARACTERSTICAS DO SOLO; 2) CAIXAS DE PASSAGEM, A PARTIR DO TRANSFORMADOR, CAIXAS DE TC's E MEDIO COM DISPOSITIVO PARA LACRE.
NORTDE103
RELAO DE MATERIAIS
55
Item
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
Uni
p p p p p p p p p p p p p m kg kg p p kg p p m p p p p p p p p p p kg m p p p p p p p -
Quantidade C
02 V 03 03 03 03 03 09 03 03 03 V 10 V V V 04 06 V 01 01 V 01 01 01 01 01 01 06 V 01 03 V V 01 01 10 14 12 01 V
DISCRIMINAO
Poste de concreto 300 Kgf Pasta anti-xida Cruzeta de madeira de lei 90 x 112,5 x 3.000 mm Isolador de pino para 27kV Isolador de pino para 27 kV Manilha sapatilha de ao laminado ou ferro nodular Ala preformada tamanho adequado Isolador de disco de 150 mm (6) Gancho de suspenso Olhal para parafuso 16 mm (5/8) Pra-Raios tipo vlvula classe 30 kV, c/ ferragens Conector adequado Sela para cruzeta de madeira de 112,5 mm Canaleta com tampa de ferro com disp. para lacres Fio de cobre nu (ver tabela n. 3) Fio de cobre nu 25 mm2 Conector tipo parafuso fendido Conector paralelo de alumnio bimetlico tamanho adequado Grampo de cerca Transformador de distribuio trifsico Cx. de blindagem p/ buchas secund. do transformador tamanho adequadado c/dispositivos para lacres. Eletroduto de ferro esmaltado bitola e comprimento adequado Base de concreto para o transformador Mureta de alvenaria 2.200 x 2.000 mm, espessura adequada Caixa para medidores de demanda e energia reativa Caixa para transformadores de corrente tamanho adequado Caixa blindada para chave faca tripolar ou disjuntor termomagntico Chave faca com fus. tipo NH ou disjuntor termom. dimens. Adequado Terminal estanhado dimensionamento adequado Haste de terra c/ conector adequado Caixa de alvenaria para aterramento Caixa de passagem para sada subterrnea com dispositivos para lacres Cabo de cobre nu 25 mm2 para interligao das hastes de terra Cerca externa metlica galvanizada com malha de 50 mm, mximo Porto de 2 folhas em tela metlica galvanizada, malha 50 mm, medindo 3,00 x 1,70 m, abrindo para fora Parafuso passante 16 mm (5/8") comprimento adequado Parafuso cabea quadrada 16 mm (5/8") comprimento adequado Parafuso francs de 16 mm (5/8") x 150 mm (6") Porca quadrada para parafuso 16 mm (5/8") Arruela quadra 57 mm, (2 1/4") c/ furo de 18 mm (11/16") Parafuso Pedra brita n. 2
DT
02 V 03 03 03 03 03 09 03 03 03 V V V V 04 06 V 01 01 V 01 01 01 01 01 01 06 V 01 03 V V 01 01 02 06 12 12 01 V
NORTDE103
56
Item
43 44 45 46 47
Uni
p p p p p
Quantidade C
01 02 02 02 02
DISCRIMINAO
Placa de advertncia Cordoalha flexvel cobre tranado tipo BD 12 da BURNDY ou similar Conector para aterramento, ligao cordoalha - tubo, tipo GG 18-1, da BURNDY ou similar Conector para aterramento, ligao cordoalha - tubo, tipo GD 1526, da BURNDY ou similar Cano galvanizado com uma extremidade rasgada para chumbar, de 200 mm por 25,4 mm
DT
02 02 02 02 02
NORTDE103
57
DESENHO 09 POSTO DE TRANSFORMAO EM ALTA TENSO COM POTNCIA ACIMA DE 300 KVA AT 1000 KVA INCLUSIVE
300
300
450 200
1000
700
300
33 8 19
1700
17-20
31
16 1
700
700
2300 21
25
23
1700 22 32 15
24-26
4300
CAIXA DE ATERRAMENTO
28-29
12 1800 30 27 31
NOTAS:
1) OS TRANSFORMADORES PARA INSTRUMENTO DEVERO SER FIXADOS DIRETAMENTE A CRUZETA ATRAVS DE PARAFUSOS DE CABEA QUADRADA, BITOLA E COMPRIMENTO ADEQUADO E, COM AUXLIO DE UMA CHAPA DE FERRO, QUANDO OS FUROS DESTE NO COINCIDIREM NA CRUZETA; 2) TODAS AS CAIXAS DE PASSAGEM, A PARTIR DOS TP's E TC's DEVERO TER DISPOSITIVO PARA LACRE.
NORTDE103
RELAO DE MATERIAIS
58
Quantidade Item
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34
Uni
DISCRIMINAO
C
p p p p p p p p p p p p p p p kg kg p p kg p p m m p p p p par p kg p p p 02 V 06 03 03 06 06 18 06 06 06 V 01 20 11 V V 02 10 V 03 03 V V 03 01 V 01 01 01 V 04 01
DT
02 V 06 03 03 06 06 18 06 06 06 V 01 07 V V 02 10 V 03 03 V V 03 01 V 01 01 01 V 04 04 01 Poste de concreto 300 Kgf Pasta anti-xida Cruzeta de madeira de lei 110 x 130 x 3.500 mm Isolador de pino para 27 kV Isolador de pino para 27 kV Manilha sapatilha de ao laminado ou ferro nodular Ala preformada tamanho adequado Isolador de disco de 150 mm (6) Gancho de suspenso Olhal para parafuso 16 mm (5 /8) Pra-Raios tipo vlvula classe 30 kV, c/ ferragens Conector adequado Parafuso Sela para cruzeta de madeira, tamanho adequado Cinta para poste de concreto com parafuso e porcas tam. adeqdo Fio de cobre nu (ver tabela n. 3) Fio de cobre nu 25 mm2 Conector tipo parafuso fendido Conector paralelo de alumnio bimetlico tamanho adequado Grampo de cerca Transformador de corrente Transformador de potencial Eletroduto rgido de 25,4 mm (1) Eletroduto rgido de 38 mm (1 ) Caixa de passagem uso externo de 50 x 50 x 100 mm, com espelho e dispositivos para lacres Caixa de passagem uso externo de 150 x 120 x 65 mm, com espelho e dispositivos para lacres Haste de terra c/ conector adequado Caixa para medidores de demanda e energia reativa Bucha e conta bucha Caixa de alvenaria para aterramento Cabo de cobre nu n. 25 mm 2 para interligao das hastes de terra e descida dos pra-raios Parafuso passante 16 mm (5/8) comp. adequado Parafuso cabea quadrada 16 mm (5/8)comprimento adequado Mureta de alvenaria
NORTDE103
DESENHO 10 SUBESTAO DE MEDIO EM ALTA TENSO COM POTNCIA DE 300 KVA EXCLUSIVE AT 1000 KVA - INCLUSIVE
59
11 19 9-10 8 14
17 18 20 29 1 16
6000 MNIMO
4 15 5 PLACA DE ADVERTNCIA 21 34
PERIGO
22
2600
23
24
23
ALTA TENSO
P.A. 38
100
P.A.
43 28 27
12
1500
CORTE -AA
2000
1500
2000
3500
1500
P.A. 1500
3 600 43
600
900
P.A.
23 24 1500
33-34-35-36
32
26 25
PLANTA
DETALHE B
39-40-41-42
37 31
1200
NOTA:
1) TODAS AS CAIXAS DE PASSAGENS A PARTIR DOS TP's E TC's DEVERO TER DISPOSIRIVOS PARA LACRES.
DETALHE B
1700
2000
NORTDE103
RELAO DE MATERIAIS
60
Item
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38
Uni
p p p p p p p p p p p p p p p kg kg p p kg p p p m p p p p kg m p p p p p p p -
Quantidade C
04 V 06 03 03 12 12 36 12 12 06 V 01 08 14 V V 04 21 V 03 03 06 V 01 01 V 02 V V 01 06 20 44 32 01 V
DISCRIMINAO
Poste de concreto 300 Kgf Pasta anti-xida Cruzeta de madeira de lei 90 x 112,5 x 3.000 mm Isolador de pino para 27kV Isolador de pino para 27 kV Manilha sapatilha de ao laminado ou ferro nodular Ala preformada tamanho adequado Isolador de disco de 150 mm (6) Gancho de suspenso Olhal para parafuso 16 mm (5/8) Pra-Raios tipo vlvula classe 30 kV, c/ ferragens Conector adequado Parafuso Sela para cruzeta de madeira de 112,5 mm Cinta para poste de concreto com parafuso e porcas tamanho adequado Fio de cobre nu (ver tabela n. 3) Fio de cobre nu 25 mm2 Conector tipo parafuso fendido Conector paralelo de alumnio bimetlico tamanho adequado Grampo de cerca Transformador de corrente Transformador de potencial Base de concreto para TP e TC Eletroduto rgido de 25,4 mm (1) Mureta de alvenaria 2.200 x 2.000 mm, espessura adequada Caixa para medidores de demanda e energia reativa Haste de terra c/ conector adequado Caixa de alvenaria para aterramento Cabo de cobre nu 25 mm2 para interligao das hastes de terra e descida dos pra-raios Cerca externa metlica galvanizada com malha de 50 mm, mximo Porto de 2 folhas em tela metlica galvanizada de 50 mm, medindo 3,00 x 1,70 m Parafuso passante 16 mm (5/8) comprimento adequado Parafuso francs de 16 mm (5/8) x 150 mm (6) Parafuso cabea quadrada 16 mm (5/8) comprimento adequado Porca Quadrada para parafuso 16 mm (5/8) Arruela quadra 57 mm, (2 1/4) c/ furo de 18 mm (11/16) Placa de advertncia Pedra brita n. 2
DT
04 V 06 03 03 12 12 36 12 12 06 V 01 08 10 V V 04 21 V 03 03 06 V 01 01 V 02 V V 01 06 12 04 40 32 01 V
NORTDE103
61
Item
39 40 41 42 43
Uni
p p p p p
Quantidade C
02 02 02 02
DISCRIMINAO
Cordoalha flexvel cobre tranado tipo BD 12 da BURNDY ou similar Conector para aterramento, ligao cordoalha - tubo, tipo GG 18-1, da BURNDY ou similar Conector para aterramento, ligao cordoalha - tubo, tipo GD 1526, da BURNDY ou similar Cano galvanizado com uma extremidade rasgada para chumbar, de 200 mm por 25,4 mm Caixa de passagem com tampa acessvel e dispositivos para lacres.
DT
02 02 02 02
NORTDE103
62
DESENHO 11 SUBESTAO DE MEDIO EM ALTA TENSO E TRANSFORMAO POTNCIA DE 300 KVA EXCLUSIVE AT 1000 KVA INCLUSIVE
11 18 6-7 8 9-10 14 15
16 17 19 33
34
20
4000
21
25
47
1500 26
CORTE -AA
2000
1000
2000
3500
2000
2500
P.A. 1500
13 600 47
3
500 MN.
500 MN.
500 MN.
900
P.A.
900
P.A.
MN.
600
23 23 37-38-39-40
1500
30 29 41
PLANTA
DETALHE B
43-44-45-46 35 1200
500
DETALHE B
NOTA:
1) TODAS AS CAIXAS DE PASSAGENS A PARTIR DOS TP's E TC's DEVERO TER DISPOSIRIVOS PARA LACRES.
1700
2000
NORTDE103
RELAO DE MATERIAIS
63
Item
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
Uni
p p p p p p p p p p p p p p kg kg kg p kg p p p m p p p p p p p p p kg m p p p P P P
Quantidade C
04 V 06 06 06 09 09 27 09 09 03 V 18 15 V V 02 13 V 03 03 06 V 01 01 01 V 01 01 01 V 02 V V 01 06 18 42 30
DISCRIMINAO
Poste de concreto 300 Kgf Pasta anti-xida Cruzeta de madeira de lei 90 x 112,5 x 3.000 mm Isolador de pino para 27kV Isolador de pino para 27 kV Manilha sapatilha de ao laminado ou ferro nodular Ala preformada tamanho adequado Isolador de disco de 150 mm (6) Gancho de suspenso Olhal para parafuso 16 mm (5/8) Pra-Raios tipo vlvula classe 30 kV, c/ ferragens Conector adequado Sela para cruzeta de madeira de 112,5 mm Cinta para poste de concreto com parafuso e porcas tamanho adequado Fio de cobre nu (ver tabela n. 3) Fio de cobre nu 25 mm2 Conector tipo parafuso fendido Conector paralelo de alumnio bimetlico tamanho adequado Grampo de cerca Transformador de corrente Transformador de potencial Base de concreto para TP e TC Eletroduto rgido de 25,4 mm (1) Parafuso Transformador de distribuio trifsico Curva de 90, tamanho adequado Eletroduto rgido pesado de bitola e comprimento adequado Base de concreto para o transformador Mureta de alvenaria 2.200 x 2.000 mm, espessura adequada Caixa para medidores de demanda e energia reativa Haste de terra c/ conector adequado Caixa de alvenaria para aterramento Cabo de cobre nu 25 mm2 para interligao das hastes de terra e descida dos pra-raios Cerca externa metlica galvanizada com malha de 50 mm, mximo Porto de 2 folhas em tela metlica galvanizada de 50 mm, medindo 3,00 x 1,70 m Parafuso passante 16 mm (5/8") comprimento adequado Parafuso francs de 16 mm (5/8") x 150 mm (6") Parafuso cabea quadrada 16 mm (5/8") comprimento adequado Porca quadrada para parafuso 16 mm (5/8") Arruela quadra 57 mm, (2 1/4") c/ furo de 18 mm (11/16")
DT
04 V 06 06 06 09 09 27 09 09 03 V 18 11 V V 02 13 V 03 03 06 V 01 01 01 V V 01 01 01 02 V V 01 06 01 04 38 30
NORTDE103
64
Item
41 42 43 44 45 46 47
Uni
p p p p p p
Quantidade C
01 V 02 02 02 02
DISCRIMINAO
Placa de advertncia Pedra brita n. 2 Cordoalha flexvel cobre tranado tipo BD 12 da BURNDY ou similar Conector para aterramento, ligao cordoalha - tubo, tipo GG 18-1, da BURNDY ou similar Conector para aterramento, ligao cordoalha - tubo, tipo GD 1526, da BURNDY ou similar Cano galvanizado com uma extremidade rasgada para chumbar, de 200 mm por 25,4 mm Caixa de passagem com tampa acessvel e dispositivos para lacres.
DT
01 V 02 02 02 02
NORTDE103
65
DESENHO 12 SUBESTAO DE MEDIO E PROTEO EM ALTA TENSO POTNCIA DE 1000 KVA EXCLUSIVE AT 2500 KVA - INCLUSIVE
11 18 3 9-10
14 30 15 1 15
16-17-19
6000 MNIMO
4 5 24 PLACA DE ADVERTNCIA 20 31
PERIGO
21
2500
22
23
22
ALTA TENSO
100
25
39
1500 29 28
44
12
1500
CORTE -AA
1500
2000
2000
2.60
500
2000
1500
13 600 44 6-7
3 8
900
900
23 33 23 23 34-35-36-37
1500
600
3000 27 26 38 1200
PLANTA
DETALHE B
40-41-42-43
32
4000
NOTAS:
1) TODAS AS MEDIDAS SO MNIMAS E ESTO EM MILMETROS; 2) O DISJUNTOR DE PROTEO GERAL DEVER OBEDECER TABELA 6; 3) TODAS AS CAIXAS DE PASSAGEM, A PARTIR DOS TP's E TC's DEVERO TER DISPOSITIVO PARA LACRE. DETALHE B
1700
2000
NORTDE103
RELAO DE MATERIAIS
66
Item
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
Uni
p p p p p p p p p p p p p p kg kg p p kg p p p m p p p p p p kg m p p p p p p p p
Quantidade C
04 V 06 06 06 12 12 36 12 12 06 V 13 14 V V 04 19 V 03 03 06 V 01 01 01 01 V 02 V V 01 06 18 42 30 01 V 02
DISCRIMINAO
Poste de concreto 300 Kgf Pasta anti-xida Cruzeta de madeira de lei 90 x 112,5 x 3.000 mm Isolador de pino para 27kV Isolador de pino para 27 kV Manilha sapatilha de ao laminado ou ferro nodular Ala preformada tamanho adequado Isolador de disco de 150 mm (6) Gancho de suspenso Olhal para parafuso 16 mm (5/8) Pra-Raios tipo vlvula classe 30 kV, c/ ferragens Conector adequado Sela para cruzeta de madeira de 112,5 mm Cinta para poste de concreto com parafuso e porcas tamanho adequado Fio de cobre nu (ver tabela n. 3) Fio de cobre nu 25 mm2 Conector tipo parafuso fendido Conector paralelo de alumnio bimetlico tamanho adequado Grampo de cerca Transformador de corrente Transformador de potencial Base de concreto para TP e TC Eletroduto rgido de 25,4 mm (1) Disjuntor a leo, classe 34,5 kV Base de concreto para o disjuntor Mureta de alvenaria 2.200 x 2.000 mm, espessura adequada Caixa para medidores de demanda e energia reativa Haste de terra c/ conector adequado Caixa de alvenaria para aterramento Cabo de cobre nu 25 mm2 para interligao das hastes de terra e descida dos pra-raios Cerca externa metlica galvanizada com malha de 50 mm, mximo Porto de 2 folhas em tela metlica galvanizada de 50 mm, medindo 3,00 x 1,70 m Parafuso passante 16 mm (5/8") comprimento adequado Parafuso francs de 16 mm (5/8") x 150 mm (6") Parafuso cabea quadrada 16 mm (5/8") comprimento adequado Porca Quadrada para parafuso 16 mm (5/8") Arruela quadra 57 mm, (2 1/4") c/ furo de 18 mm (11/16") Placa de advertncia Pedra brita n. 2 Cordoalha flexvel cobre tranado tipo BD 12 da BURNDY ou similar
DT
04 V 06 06 06 12 12 36 12 12 06 V 08 V V 04 19 V 03 03 06 V 01 01 01 01 V 02 V V 01 06 10 04 38 30 01 V 02
NORTDE103
67
Item
Uni
Quantidade C DT
02 02 02
DISCRIMINAO
Conector para aterramento, ligao cordoalha - tubo, tipo GG 18-1, da BURNDY ou similar Conector para aterramento, ligao cordoalha - tubo, tipo GD 1526, da BURNDY ou similar Cano galvanizado com uma extremidade rasgada para chumbar, de 200 mm por 25,4 mm Caixa de passam com tampa acessvel e dispositivos para lacres.
41 42 43 44
p p p p
02 02 02
NORTDE103
68
DESENHO 13 SUBESTAO DE MEDIO EM ALTA TENSO E TRANSFORMAO POTNCIA DE 1000 KVA EXCLUSIVE AT 2500 KVA INCLUSIVE
12 19 6-7 8 9-10 14
17 18 20 35 16 PLACA DE ADVERTNCIA
1 15 3
6000 MNIMO
4 5
36
21
4000
22
27
2600
23
24
22 ALTA 400 26
29 30 45 100 37
P.A.
1500 34
13
50
1500 28
33
CORTE -AA
2000
1000 31 DETALHE B 3 18
2000
3500
2000
2500
32
P.A. 3
1000
50
500 MN.
600
500 MN.
900
P.A.
900
600
24 23 39-40-41-42
MN.
500
44
1500
46-47-48-49
1200
PLANTA
DETALHE B
NOTA:
1) TODAS AS CAIXAS DE PASSAGENS A PARTIR DOS TP's E TC's DEVERO TER DISPOSIRIVOS PARA LACRES.
1700
2000
NORTDE103
RELAO DE MATERIAIS
69
Item Uni
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 p p p p p p p p p p p p p p kg kg kg p p kg p p p m p p p p m p p p p p kg m p p p p p p
Quantidade C
04 V 06 06 06 11 11 30 11 09 01 03 V 16 16 V V 02 15 V 03 03 06 V 01 01 01 01 V 01 01 01 V 02 V V 01 06 16 40 31
DISCRIMINAO
Poste de concreto 300 Kgf Pasta anti-xida Cruzeta de madeira de lei 90 x 112,5 x 3.000 mm Isolador de pino para 27kV Isolador de pino para 27 kV Manilha sapatilha de ao laminado ou ferro nodular Ala preformada tamanho adequado Isolador de disco de 150 mm (6) Gancho de suspenso Olhal para parafuso 16 mm (5/8) Olhal-olhal, ruptura mnima 3000 kgf e furos de 18 mm Pra-Raios tipo vlvula classe 30 kV, c/ ferragens Conector adequado Sela para cruzeta de madeira de 112,5 mm Cinta para poste de concreto com parafuso e porcas tamanho adequado Fio de cobre nu (ver tabela n. 3) Fio de cobre nu 25 mm2 Conector tipo parafuso fendido Conector paralelo de alumnio bimetlico tamanho adequado Grampo de cerca Transformador de corrente Transformador de potencial Base de concreto para TP e TC Eletroduto rgido de 25,4 mm (1) Disjuntor a leo, classe 34,5 kV Base de concreto para o disjuntor Transformador de distribuio Curva de 90, tamanho adequado Eletroduto rgido pesado de bitola e comprimento adequado Base de concreto para o transformador Mureta de alvenaria 2.200 x 2.000 mm, espessura adequada Caixa para medidores de demanda e energia reativa Haste de terra c/ conector adequado Caixa de alvenaria para aterramento Cabo de cobre nu 25 mm2 para interligao das hastes de terra e descida dos pra-raios Cerca externa metlica galvanizada com malha de 50 mm, mximo Porto de 2 folhas em tela metlica galvanizada de 50 mm, medindo 3,00 x 1,70 m Parafuso passante 16 mm (5/8") comprimento adequado Parafuso francs de 16 mm (5/8") x 150 mm (6") Parafuso cabea quadrada 16 mm (5/8") comprimento adequado Porca Quadrada para parafuso 16 mm (5/8") Arruela quadra 57 mm, (2 1/4") c/ furo de 18 mm (11/16")
DT
04 V 06 06 06 11 11 30 11 09 01 03 V 10 V V 02 15 V 03 03 06 V 01 01 01 01 V 01 01 01 V 02 V V 01 06 08 04 36 31
NORTDE103
70
Item
43 44 45 46 47 48 49 50
Uni
p p p p p p
Quantidade C
01 01 V 02 02 02 02
DISCRIMINAO
Parafuso Placa de advertncia Pedra brita n. 2 Cordoalha flexvel cobre tranado tipo BD 12 da BURNDY ou similar Conector para aterramento, ligao cordoalha - tubo, tipo GG 18-1, da BURNDY ou similar Conector para aterramento, ligao cordoalha - tubo, tipo GD 1526, da BURNDY ou similar Cano galvanizado com uma extremidade rasgada para chumbar, de 200 mm por 25,4 mm Caixa de passagem com tampa acessvel e dispositivos para lacres.
DT
01 01 V 02 02 02 02
NORTDE103
71
DESENHO 14 SUBESTAO DE MEDIO EM ALTA TENSO POTNCIA AT 1000 KVA INCLUSIVE COM CONJUNTO DE MEDIO
6-7 3 16 17 19 33 11
18
15
6000 MNIMO
14
4-5
PLACA DE ADVERTNCIA
32
6000 MNIMO
34 20 2600 22
ALTA TENSO
2600
PERIGO
23
21
12 31 41 30
2000
1500
1500
2000
CORTE -AA
9-10
36-37
13
1050
41 28
1050
29 22
PLANTA
1700 2000
DETALHE B
NOTAS:
1) A BASE DO CONJUNTO DEVE SER CONFECCIONADA CONFORME CARACTERSTICAS DO SOLO; 2) TODAS AS CAIXAS DE PASSAGENS A PARTIR DOS TP's E TC's DEVERO TER DISPOSIRIVOS PARA LACRES.
1050
1050
NORTDE103
72
RELAO DE MATERIAIS
Item
01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
Uni
p p p p p p p p p p p p p p kg kg p p kg p p p p p p p p p p p p kg m p p
Quantidade C
04 V V 06 06 06 06 18 06 06 06 V 16 12 V V 06 12 V 01 V V 01 01 02 02 02 06 08 V 02 01 V V 01 30
DISCRIMINAO
Poste de concreto 300 Kgf Pasta anti-xido Cruzeta de madeira de lei 90 x 112,5 x 3.000 mm Isolador de pino para 27kV Isolador de pino para 27 kV Manilha sapatilha de ao laminado ou ferro nodular Ala preformada tamanho adequado Isolador de disco de 150 mm (6) Gancho de suspenso Olhal para parafuso 16 mm (5/8) Pra-Raios tipo vlvula classe 30 kV, c/ ferragens Conector adequado Sela para cruzeta de madeira de 112,5 mm Cinta para poste de concreto com parafuso e porcas tam. adeqdo Fio de cobre nu (ver tabela n. 3) Fio de cobre nu 25 mm2 Conector tipo parafuso fendido Conector paralelo de alumnio bimetlico tamanho adequado Grampo de cerca Conjunto de medio trifsico Pedra brita n. 2 Eletroduto rgido de 25,4 mm (1) Base de concreto para o conjunto de medio Mureta de alvenaria 2.200 x 2.000 mm, espessura adequada Cordoalha flexvel cobre tranado tipo BD 12 da BURNDY ou similar Conector para aterramento, ligao cordoalha tubo, tipo GG 18-1, da BURNDY ou similar Conector para aterramento, ligao cordoalha tubo, tipo GD 1526, da BURNDY ou similar Parafuso passante 16 mm (5/8) comprimento adequado Parafuso francs de 16 mm (5/8) x 150 mm (6) Haste de terra c/ conector adequado Caixa de alvenaria para aterramento Parafuso cabea quadrada 16 mm (5/8) comprimento adequado Cabo de cobre nu 25 mm2 para interligao das hastes de terra e descida dos pra-raios Cerca externa metlica galvanizada com malha de 50 mm, mximo Porto de 2 folhas em tela metlica galvanizada de 50 mm, medindo 3,00 x 1,70 m Porca Quadrada para parafuso 16 mm (5/8)
DT
04 V V 06 06 06 06 18 06 06 06 V 08 V V 06 12 V 01 V V 01 01 02 02 02 06 08 V 02 01 V V 01 30
NORTDE103
73
Item
37 38 39 40 41
Uni
p p p p
Quantidade C
28 01 01 02
DISCRIMINAO
Arruela quadra 57 mm, (2 1/4) c/ furo de 18 mm (11/16) Parafuso Placa de advertncia Cano galvanizado com uma extremidade rasgada para chumbar, de 200 mm por 25,4 mm Caixa de passagem com tampa acessvel e dispositivos para lacres.
DT
28 01 01 02
NORTDE103
74
REDE PRIMRIA
REDE SECUNDRIA B
FIG. 1
AFASTAMENTO VERTICAL ENTRE OS CONDUTORES E A CIMALHA DOS EDIFCIOS
FIG. 2
FIG. 3
AFASTAMENTO VERTICAL ENTRE O PISO DA SACADA E OS CONDUTORES
A B B
3500
4 5
FIG. 4
AFASTAMENTO HORIZONTAL ENTRE OS CONDUTORES E A PAREDE DOS EDIFCIOS
FIG. 5
AFASTAMENTO HORIZONTAL ENTRE OS CONDUTORES E AS SACADAS DOS EDIFCIOS
NOTAS:
1) SE O AFASTAMENTO VERTICAL ENTRE OS CONDUTORES E AS CIMALHAS OU TELHADOS DOS EDIFCIOS EXCEDER AS DIMENSES DADAS NA FIG. 1, NO SE EXIGE AFASTAMENTO HORIZONTAL; 2) SE OS AFASTAMENTOS VERTICAIS DAS FIGs. 2 E 3 NO PUDEREM SER MANTIDOS, EXIGE-SE O AFASTAMENTO HORIZONTAL DA FIG. 5; 3) SE O AFASTAMENTO VERTICAL ENTRE OS CONDUTORES E AS SACADAS EXCEDER AS DIMENSES DAS FIGs. 2 E 3, NO SE EXIGE AFASTAMENTO HORIZONTAL DO BORDO DA SACADA, PORM O AFASTAMENTO DA FIG. 4, DEVE SER MANTIDO; 4) SE NO FOR POSSVEL MANTER OS AFASTAMENTOS ESPECFICADOS NESTE DESENHO, TODOS OS CONDUTORES CUJA TENSO EXCEDA A 300 V. DEVERO SER PROTEGIDOS DE MODO A EVITAR CONTATO ACIDENTAL POR PESSOAS EM JANELAS, SACADAS, TELHADOS OU CIMALHA; 5) OS AFASTAMENTOS NESTE DESENHO SE APLICAM A LINHAS APOIADAS EM POSTES.
NORTDE103
DESENHO 16 DETALHE DA CAIXA DE ATERRAMENTO E DA BASE DE CONCRETO
75
D E TA LH E D A C A IX A D E A TE R R A M E N TO
50 300 50
H A S TE D E C O BR E C O M P R IM E N TO 2m 100
2000
D E TA L H E - 1
C O R TE - A A
D E TA LH E D A B A S E D E C O N C R E TO P A R A TC 's E TP 's
7 00 100
10 0
1450
1800
250
250 1 0 00
50 0
2 50
V IS T A L A TE R A L
V IS TA D E C IM A
N O TAS :
1) TO D A S A S M E D ID A S S O M N IM A S E E S T O E M M ILM E TR O S ; 2) O S P A R A FU S O S P A R A FIX A O D O S TC 'S E TP 'S D E V E R O TE R D IS T N C IA E N TR E E LE S , C O M P A TV E L C O M O S FU R O S D A B A S E D E S TE S E Q U IP A M E N TO S (C O N TA T A R E N E R S U L E M C A S O D E D V ID A );
150
700
150
500
NORTDE103
DESENHO 17 DETALHE DE MONTAGEM DA CERCA E DO PORTO
76
100
363 200 200 200 200 200 100 100 100 100 100 1050 15 CHAPA DE AO
DETALHE DA CERCA
20 22.5 47.5
120
65
22.5
120
47.5
150
150
65
1050
1953
DETALHE D
200
1500
1500 2"
200 SOLDA PLACA DE ADVERTNCIA TELA 50mm ARAME N12 BWG VER DET. B
100
DETALHE DO PORTO
DETALHE A
DOBRADIA
1"
250
DETALHE-B
DETALHE C
NOTA:
1) TODAS AS CAIXAS DE PASSAGENS A PARTIR DOS TP's E TC's DEVERO TER DISPOSIRIVOS PARA LACRES.
NORTDE103
77
DESENHO 18 FIXAO DAS CRUZETAS PARA TRANSFORMADORES DE 45 KVA A 225 KVA INCLUSIVE
APO IO
PEA DE M ADEIRA D E 115 x 135mm x C OM P. ADEQ UADO
C RUZETA DE AO
N OTA:
N A FIXAO D AS CRU ZETAS, PAR A TRANSFO RM ADO R ES AT 150 KVA (EXCLUSIVE) EM POSTE DUPLO T, PODER SER SUPRIM IDO O APO IO.
NORTDE103
DESENHO 19 RAMAL DE ENTRADA UNIPOLAR EM ALTA TENSO CABOS UNIPOLARES
78
650
1350 24 25 26 200
150
400
100
3 8 22 26 28
12
7 23 2 1600
21-25-27
10-11
13 4
15
14
17
5500
600 MN.
600 MN.
18
CAIXA DE ATERRAMENTO
1700
200 MN.
NOTAS:
1) ESTE RAMAL DE SERVIO EMPREGADO EM SUBESTAES COM POTNCIA AT 2.500 KVA; 2) SE FOR NECESSRIO O USO DO CABO UNIPOLAR DE RESERVA, APS SUA LIGAO DEVER SER VERIFICADA A SEQUNCIA DE FASE NA BAIXA TENSO; 3) A CHAVE FUSVEL DEVE TER FUSVEIS ADEQUADOS (CONSULTAR TABELA ANTERIOR); 4) DEVER EXISTIR UM CIRCUITO DE RESERVA (MUFLA TERMINAL, CABOS, ETC) DE ACORDO COM O DESENHO ACIMA; 5) QUANDO A POTNCIA FOR SUPERIOR A 750 KVA, DEVERO SER INSTALADOS CHAVES FACAS EM SUBSTITUIO AS CHAVES FUSVEIS. NESTE CASO ACRESCENTAR UMA CRUZETA NO 1 NVEL; 6) TODAS AS MEDIDAS ESTO EM MILMETROS E SO MEDIDAS MNIMAS.
NORTDE103
79
ITEM 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
UNID p p p p p p p p p p kg kg kg kg p m m p p p p p p p p p p p
DISCRIMINAO
Cruzeta de madeira de lei 90 x 112,5 x 2.400 mm Chave fusvel com elo adequado e com ferragens Pra-Raios tipo vlvula classe 30 kV com ferragens Sela para cruzeta de madeira 112,5 mm Cinta, p/ poste de concreto c/ parafusos e porcas tamanho adequado Mo francesa normal e 726 mm Conector tipo parafuso fendido Conector paralelo de alumnio bimetlico tamanho adequado Grampo de cerca Fio de cobre nu 25 mm2 Fio de cobre nu bitola adequada Cabo de cobre nu 25 mm2 p/ interligao das hastes / desc. dos P/Raios Arame de ferro galvanizado n. 12 BWG Mufla externa para entrada servio subterrneo 27 kV Cabo isolado para 34,5 kV tipo sintenax ou similar dimens. adequado. Eletroduto de ferro galvanizado, dimensionamento adequado Caixa de alvenaria para passagem cabo subterrneo Haste para terra com conector adequado Caixa de alvenaria para aterramento Parafuso de rosca dupla (passante) 16 mm (5/8) comprimento adeqdo Parafuso francs de 16 mm (5/8) x 125 mm (5) Parafuso francs de 16 mm (5/8) (1. 3/4) Parafuso francs de 16 mm (5/8) x 150 mm (6) Porca quadrada para parafuso de 16 mm (5/8) Porca quadrada para parafuso de 9,5 mm (3/8) Arruela quadrada 57 mm (2. 1/4) com furo 18 mm (11/16) Arruela redonda com furo 11 mm (7/16)
NORTDE103
80
CARGA
CARGA
FONTE
FONTE
CARGA
FONTE
NORTDE103
DESENHO 21 DERIVAO DA ENTRADA DE SERVIO AREA COM CHAVE FACA
81
CARG A
CARG A
FONTE
FONTE
CARG A
FONTE
82
C
b
D.T. 10/400
180 190
FRMULA PARA O CLCULO DO DIMETRO DO POSTE, PARA DIMENSIONAMENTO DA CINTA
D= B-(B-b)xh(mm) H
220 220
D
170 x 90 170 x 90
D-> DIMENSO EM UM PONTO ESPECFICO. B-> DIMENSO DA BASE DO POSTE. b-> DIMENSO DO TOPO. H-> ALTURA DO POSTE. h-> ALTURA EM UM PONTO ESPECFICO.
200
8200
7700
H 5945 6255
3500
400 Kg
1600
TOTAL
10m 11m
DIMENSO NO TOPO (mm) DIMENSO NA BASE (mm) DIMENSO NO TOPO (mm) DIMENSO NA BASE (mm)
NOTAS:
1) TODAS AS DIMENSES ESTO EM MILMETROS; 2) SUPORTE PARA TRANSFORMADOR EM POSTE CIRCULAR, DIMETRO 210 E 220m; 3) PARA POSTE DE COMPRIMENTO DIFERENTE DE 10m UTILIZAR A FRMULA ACIMA; 4) A BASE DO POSTE DEVER SER CONCRETADA.