Air System Sizing Summary for GDC-CONTROL-ELECTRIC

Project Name: THAI BINH - HAM RONG Prepared by: pve 04/11/2014 04:27PM

Air System Information


Air System Name Equipment Class Air System Type GDC-CONTROL-ELECTRIC SPLT AHU SZCAV Number of zones Floor Area Location 1 65.0 m Thai Binh, Vietnam

Sizing Calculation Information


Zone and Space Sizing Method: Sum of space airflow rates Zone L/s Individual peak space loads Space L/s Calculation Months Sizing Data Jan to Dec Calculated

Central Cooling Coil Sizing Data


Total coil load Sensible coil load Coil L/s at Jul 1300 Max block L/s Sum of peak zone L/s Sensible heat ratio m/kW W/m Water flow @ 5.6 K rise 19.0 15.1 1111 1111 1111 0.798 3.4 291.7 N/A kW kW L/s L/s L/s Load occurs at OA DB / WB Entering DB / WB Leaving DB / WB Coil ADP Bypass Factor Resulting RH Design supply temp. Zone T-stat Check Max zone temperature deviation Jul 1300 37.1 / 36.6 25.6 / 18.7 14.3 / 13.7 13.1 0.100 48 12.8 1 of 1 0.0 C C C C % C OK K

Central Heating Coil Sizing Data


Max coil load Coil L/s at Des Htg Max coil L/s Water flow @ 11.1 K drop 0.4 kW 1111 L/s 1111 L/s N/A Load occurs at W/m Ent. DB / Lvg DB Des Htg 5.4 21.5 / 21.8 C

Supply Fan Sizing Data


Actual max L/s Standard L/s Actual max L/(s-m) 1111 L/s 1109 L/s 17.10 L/(s-m) Fan motor BHP Fan motor kW Fan static 0.06 BHP 0.04 kW 20 Pa

Outdoor Ventilation Air Data


Design airflow L/s L/(s-m) 40 L/s 0.62 L/(s-m) L/s/person 10.00 L/s/person

Hourly Analysis Program v.4.3