Plug-In Purge Timer For The CB 780/CB 784 System

INSTALLATION INSTRUCTIONS
1. 2. 3. 4. 5. 6. Remove the Keyboard Display Module, Dust Cover or DATA CONTROLBUS MODULETM. Remove the current Purge Timer (if installed in the Relay Module) by pulling upward on the plastic support cover (see Fig. 1).l Make sure the new Purge Timer selected has the desired timing period. Properly orient the Purge Timer with the opening in the Relay Module, and insert the Purge Timer into the opening of the Relay Module compartment (see Fig. 1). Reinstall the Keyboard Display Module, Dust Cover or DATA CONTROLBUS MODULETM in the Relay Module and restore power to the device. Run the burner system through at least one complete cycle to be sure that the system is operating as desired.

APPLICATION
The Plug-In Purge Timer provides the prepurge timing for the CB 780/CB 784 Relay Modules. Part Number 833-2730 833-2731 833-2732 833-2733 Prepurge Time 30 sec 60 sec 90 sec 2.5 min

INSTALLATION

WARNING

Fire or Explosion Hazard. Can cause serious injury, death or property damage. Verification of safety requirements must be performed EACH TIME the control is installed on a burner to prevent possible hazardous burner operation. Fig. 1. Plug-In Purge Timer Installation

CAUTION

Electrical Shock Hazard. Can cause serious injury, death or property damage. Disconnect power supply before installing Purge Timer to prevent electrical shock or equipment damage. More than one power supply disconnect may be involved.

CB Manual Part Number 750-257


U.S. Registered Trademark. Brand and product names shown are Trademarks of their respective owners M.S. Rev. 01-08