Protection functions Setting ranges

Functions Settings Time delay


ANSI 50/51 - Phase overcurrent
Tripping curve Tripping time delay Reset time
Definite time DT
SIT, LTI, VIT, EIT, UIT (1) DT
RI DT
IEC: SIT/A, LTI/B, VIT/B, EIT/C DT or IDMT
IEEE: MI (D), VI (E), EI (F) DT or IDMT
IAC: I, VI, EI DT or IDMT
Is set point 0.1 to 24 In Definite time Inst.; 0.05 s to 300 s
0.1 to 2.4 In IDMT 0.1 s to 12.5 s at 10 Is
Reset time Definite time (DT; timer hold) Inst.; 0.05 s to 300 s
IDMT (IDMT; reset time) 0.5 s to 20 s
Confirmation None
By negative sequence overvoltage
By undervoltage

3 ANSI 50V/51V - Voltage-restrained phase overcurrent


Tripping curve Tripping time delay Reset time
IDMT DT
SIT, LTI, VIT, EIT, UIT (1) DT
RI DT
IEC: SIT/A, LTI/B, VIT/B, EIT/C DT or IDMT
IEEE: MI (D), VI (E), EI (F) DT or IDMT
IAC: I, VI, EI DT or IDMT
Is set point 0.1 to 24 In Definite time Inst.; 0.05 s to 300 s
0.1 to 2,4 In IDMT 0.1 s to 12.5 s at 10 Is
Reset time Definite time (DT; timer hold) Inst.; 0.05 s to 300 s
IDMT (IDMT; reset time) 0.5 s to 20 s
ANSI 50N/51N or 50G/51G - Earth fault
Tripping curve Tripping time delay Reset time
Definite time DT
SIT, LTI, VIT, EIT, UIT (1) DT
RI DT
IEC: SIT/A,LTI/B, VIT/B, EIT/C DT or IDMT
IEEE: MI (D), VI (E), EI (F) DT or IDMT
IAC: I, VI, EI DT or IDMT
Is0 set point 0.1 to 15 In0 Definite time Inst.; 0.05 s to 300 s
0.1 to 1 In0 IDMT 0.1 s to 12.5 s at 10 Is0
Reset time Definite time (DT; timer hold) Inst.; 0.05 s to 300 s
IDMT (IDMT; reset time) 0.5 s to 20 s
ANSI 50 BF - Breaker failure
Presence of current 0.2 to 2 In
Operating time 0.05 s to 30 s
ANSI 46 - Negative sequence / unbalance
Definite time 0.1 to 5 Ib 0.1 s to 300 s
IDMT 0.1 to 0.5 Ib (Schneider Electric) 0.1 to 1Ib (IEC, IEEE) 0.1 s to 1 s
Tripping curve Schneider Electric
IEC: SIT/A, LTI/B, VIT/B, EIT/C
IEEE: MI (D), VI (E), EI (F)
ANSI 67 - Directional phase overcurrent
Tripping curve Tripping time delay Reset time
Definite time DT
SIT, LTI, VIT, EIT, UIT (1) DT
RI DT
CEI: SIT/A, LTI/B, VIT/B, EIT/C DT or IDMT
IEEE: MI (D), VI (E), EI (F) DT or IDMT
IAC: I, VI, EI DT or IDMT
Is set point 0.1 to 24 In Definite time Inst.; 0.05 s to 300 s
0.1 to 2.4 In IDMT 0.1 s to 12.5 s at 10 Is
Reset time Definite time (DT; timer hold) Inst.; 0.05 s to 300 s
IDMT (IDMT; reset time) 0.5 s to 20 s
Characteristic angle 30°, 45°, 60°
Note: general settings In, Ib, In0, Unp and Vnp are described in the chapter "Metering functions" page 2/2: characteristics.
(1) Tripping as of 1.2 Is.

3/2