ANSI 50/51 - Phase overcurrent Tripping curve Tripping time delay Reset time Definite time DT SIT, LTI, VIT, EIT, UIT (1) DT RI DT IEC: SIT/A, LTI/B, VIT/B, EIT/C DT or IDMT IEEE: MI (D), VI (E), EI (F) DT or IDMT IAC: I, VI, EI DT or IDMT Is set point 0.1 to 24 In Definite time Inst.; 0.05 s to 300 s 0.1 to 2.4 In IDMT 0.1 s to 12.5 s at 10 Is Reset time Definite time (DT; timer hold) Inst.; 0.05 s to 300 s IDMT (IDMT; reset time) 0.5 s to 20 s Confirmation None By negative sequence overvoltage By undervoltage
Tripping curve Tripping time delay Reset time IDMT DT SIT, LTI, VIT, EIT, UIT (1) DT RI DT IEC: SIT/A, LTI/B, VIT/B, EIT/C DT or IDMT IEEE: MI (D), VI (E), EI (F) DT or IDMT IAC: I, VI, EI DT or IDMT Is set point 0.1 to 24 In Definite time Inst.; 0.05 s to 300 s 0.1 to 2,4 In IDMT 0.1 s to 12.5 s at 10 Is Reset time Definite time (DT; timer hold) Inst.; 0.05 s to 300 s IDMT (IDMT; reset time) 0.5 s to 20 s ANSI 50N/51N or 50G/51G - Earth fault Tripping curve Tripping time delay Reset time Definite time DT SIT, LTI, VIT, EIT, UIT (1) DT RI DT IEC: SIT/A,LTI/B, VIT/B, EIT/C DT or IDMT IEEE: MI (D), VI (E), EI (F) DT or IDMT IAC: I, VI, EI DT or IDMT Is0 set point 0.1 to 15 In0 Definite time Inst.; 0.05 s to 300 s 0.1 to 1 In0 IDMT 0.1 s to 12.5 s at 10 Is0 Reset time Definite time (DT; timer hold) Inst.; 0.05 s to 300 s IDMT (IDMT; reset time) 0.5 s to 20 s ANSI 50 BF - Breaker failure Presence of current 0.2 to 2 In Operating time 0.05 s to 30 s ANSI 46 - Negative sequence / unbalance Definite time 0.1 to 5 Ib 0.1 s to 300 s IDMT 0.1 to 0.5 Ib (Schneider Electric) 0.1 to 1Ib (IEC, IEEE) 0.1 s to 1 s Tripping curve Schneider Electric IEC: SIT/A, LTI/B, VIT/B, EIT/C IEEE: MI (D), VI (E), EI (F) ANSI 67 - Directional phase overcurrent Tripping curve Tripping time delay Reset time Definite time DT SIT, LTI, VIT, EIT, UIT (1) DT RI DT CEI: SIT/A, LTI/B, VIT/B, EIT/C DT or IDMT IEEE: MI (D), VI (E), EI (F) DT or IDMT IAC: I, VI, EI DT or IDMT Is set point 0.1 to 24 In Definite time Inst.; 0.05 s to 300 s 0.1 to 2.4 In IDMT 0.1 s to 12.5 s at 10 Is Reset time Definite time (DT; timer hold) Inst.; 0.05 s to 300 s IDMT (IDMT; reset time) 0.5 s to 20 s Characteristic angle 30°, 45°, 60° Note: general settings In, Ib, In0, Unp and Vnp are described in the chapter "Metering functions" page 2/2: characteristics. (1) Tripping as of 1.2 Is.