Site

A 41,139.00 BTU/hr
Area = 122.074 Sqm
Co-efficient = 337
B 0 BTU/hr
C 800.00 BTU/hr
Occupants = 2 Nos
Co-efficient = 400
D 232,220.00 BTU/hr
Type - 1 (Via UPS load)
Total UPS load 80 Kva
Power Factor 0.85
Total watts 68000 Watts
(or)
Type - 2 (Direct)
Sum of Heat gains 0 BTU/hr
(by server manufacturer)
E 866.00 BTU/hr
Total watts (1.67W / sft) = 203.863 Watts
Co-efficient = 4.25
275,025.00
BTU/hr
23.00 TR
Only yellow highlighted cells to be entered
TOTAL TR
LIGHTING BTU
AC UNIT SIZING
TOTAL HEAT GAINS
ROOM BTU
WINDOW BTU
OCCUPANTS BTU
EQUIPMENT BTU - Servers, Routers, etc
Only yellow highlighted cells to be entered