Motor Calculation Sheet

As Per IS : 4029 CL.NO.3.2


Sample Calculation By Summation of Losses Method
KW
FLI
Pole
Particulars
Connection
No Load Test
1)
Cold Resistance
Temp.Cold
Input
Current
IR Losses
No Load Losses
Locked Rotor Calculation
1)
Connection
2)
Voltage (Vsc)
3)
Current (I Ssc)
4)
Input
5)
I sc at Rated Volt
6)
Current (I Ssc)
7)
Psc at Rated Volt
8)
Rotor Out put
9)
Tst/Tfl (%)
10)
Ist/Ifl (PU)
Efficiency Calculation
1)
Reference Temp
2)
W1
3)
W2
4)
Resistance at Ref
5)
Input
6)
Load Current
ST.IR Losses
7)
8)
Stator Losses
9)
Rated Speed
10)
Frequency
11)
SYNC.Speed
12)
Slip
13)
Rotor Cu.Losses
14)
Stray Losses
15)
Total Losses
16)
OUTPUT
17)
% Efficiency
18)
Power Factor
19)
% Loading

180
306
4

Formula Used
Star - 3 and Delta - 1
At Volt

Unit
Volt

Ohm/Phase
(w1+w2) x C.T.Ratio x Wattmater Const./1000
I Measured x C.T.Ratio
I X Cold resi/Phase/1000
Input - IR Losses

C
KW
AMP
KW
KW

Star - 3 and Delta - 1


I Measured x C.T.Ratio
(w1+w2) x C.T.Ratio x Wattmater Const./1000
Rated Volt/Voltage (Vsc) x Current (I Ssc)
Current (I Ssc) x Cold Resistance/1000
(Rated Volt/Voltage (Vsc)) x Input
(Psc at Rated Volt-Isc)*R
Rotor Out put/Rated Out put x 100
I sc Rated / Full Current

Volt
AMP
KW
Amp
KW
KW
KW
%
PU

of Load Test

(234.5+T.Ref)/(234.5+T.Cold) x Cold Resi


(w1+w2) x CT Ratio x Watt meter Const/1000
I Mesured * CT Ratio
FL Current x Res.at Ref Temperature
ST.IR Losses + No load Losses

120 x Freq./Pole
(Sync.speed-Load Speed)/Sync.Speed
(Stator Input-Stator loss) x Slip
(Stator Input-Stator loss) x 0.005
(8+13+14)
INPUT - TOTAL LOSSES
(output/Input) x 100
1/?(1+3((w1+w2)/(w1+w2))^2)
Out put / Rating

C
KW
KW
/ph
kw
Amp
kw
KW
RPM
HZ
RPM
PU
KW
KW
KW
KW
%

Calculation
1
415
0.02846
32.7
5.94
78.01
0.17319504
5.76680496

0.173195
5.766805

1
81.54
305.94
13.25
1557.089772
69.00208275
343.2184751
273.0479303
151.6932946
508.8528666

1557.09
69.00208
343.2185
1389.685
151.6933
508.8529

95
124.01
69.41
0.035095696
193.42
300.75
3.174425454
8.941230414
1484
49.9
1497
0.008684035
1.602020043
0.922393848
11.4656443
181.9543557
94.07215164
0.878718951
101.0857532

234.5

0.035096

3.174425
8.94123

1497
0.008684
1.60202
0.922394
11.46564
181.9544
94.07215
0.878719
101.0858

54.6
193.42
0.13802 0.079686

Motor Calculation Sheet


As Per IS : 4029 CL.NO.3.2
Sample Calculation By Summation of Losses Method
KW
FLI
Pole
Particulars
Connection
No Load Test
1)
Cold Resistance
Temp.Cold
Input
Current
IR Losses
No Load Losses
Locked Rotor Calculation
1)
Connection
2)
Voltage (Vsc)
3)
Current (I Ssc)
4)
Input
5)
I sc at Rated Volt
6)
Current (I Ssc)
7)
Psc at Rated Volt
8)
Rotor Out put
9)
Tst/Tfl (%)
10)
Ist/Ifl (PU)
Efficiency Calculation
1)
Reference Temp
2)
W1
3)
W2
4)
Resistance at Ref
5)
Input
6)
Load Current
ST.IR Losses
7)
8)
Stator Losses
9)
Rated Speed
10)
Frequency
11)
SYNC.Speed
12)
Slip
13)
Rotor Cu.Losses
14)
Stray Losses
15)
Total Losses
16)
OUTPUT
17)
% Efficiency
18)
Power Factor
19)
% Loading

18.5
32.6
4

Formula Used
Star - 3 and Delta - 1
At Volt

Unit
Volt

Ohm/Phase
(w1+w2) x C.T.Ratio x Wattmater Const./1000
I Measured x C.T.Ratio
I X Cold resi/Phase/1000
Input - IR Losses

C
KW
AMP
KW
KW

Star - 3 and Delta - 1


I Measured x C.T.Ratio
(w1+w2) x C.T.Ratio x Wattmater Const./1000
Rated Volt/Voltage (Vsc) x Current (I Ssc)
Current (I Ssc) x Cold Resistance/1000
(Rated Volt/Voltage (Vsc)) x Input
(Psc at Rated Volt-Isc)*R
Rotor Out put/Rated Out put x 100
I sc Rated / Full Current

Volt
AMP
KW
Amp
KW
KW
KW
%
PU

of Load Test

(234.5+T.Ref)/(234.5+T.Cold) x Cold Resi


(w1+w2) x CT Ratio x Watt meter Const/1000
I Mesured * CT Ratio
FL Current x Res.at Ref Temperature
ST.IR Losses + No load Losses

120 x Freq./Pole
(Sync.speed-Load Speed)/Sync.Speed
(Stator Input-Stator loss) x Slip
(Stator Input-Stator loss) x 0.005
(8+13+14)
INPUT - TOTAL LOSSES
(output/Input) x 100
1/?(1+3((w1+w2)/(w1+w2))^2)
Out put / Rating

C
KW
KW
/ph
kw
Amp
kw
KW
RPM
HZ
RPM
PU
KW
KW
KW
KW
%

Calculation
1
3300
0.435
32.7
5.94
78.01
2.647218644
3.292781357

2.647219
3.292781

1
68
33.23
1600
1612.632353
1131.253651
3768166.09
2.92582E+11
1.58152E+12
4946.725009

1612.632
1131.254
3768166
1.42E+13
1.58E+12
4946.725

95
124.01
69.41
0.536424027
193.42
300.75
48.51985498
51.81263633
1484
49.9
1497
0.008684035
1.229723265
0.708036818
53.75039642
139.6696036
72.21052817
0.878718951
754.9708302

234.5

0.536424

48.51985
51.81264

1497
0.008684
1.229723
0.708037
53.7504
139.6696
72.21053
0.878719
754.9708

54.6
193.42
0.13802 0.079686

STAR COONECTION
ok calculation Motor srno 135326 TWAD BOARD
Loked rotor test result
Rated Volt
3300
Rated Amp
33
Resistance
0.548
Rated Power
150
Volt

Amp
w1
751.9
33.027

w2

10890000
565353.61

I st at Rated Input at rated Stator Cu.


Volt
voltage kw
Loss
w1+w2
11.56 144.95159 222.6719663 34.542024

% Starting
% Starting
Torque
Current
125.4199618 439.2472403

DELTA CONNECTION
ok calculation Motor srno 135326 TWAD BOARD
Loked rotor test result
Rated Volt
415
Rated Amp
306
Resistance
0.0275
Rated Power
180
Volt

Amp
w1
77.32
304.64

w2

172225
5978.3824

I st at Rated Input at rated Stator Cu.


Volt
voltage kw
Loss
w1+w2
12.84 1635.0957 369.8942042 73.522294

% Starting
% Starting
Torque
Current
164.6510611 534.345002