You are on page 1of 19

Doc.

No: HN29-2-13-0001
Revision: 0
Date: 22-07-2014
Page 1 of 19
0 22-07-2014 Issued for comments BAP DBM PBP QP
PREPARED BY CHECKED BY APPDROVED BY APPROVED BY
QP
PROJECT TITLE:
Document Title:
Data Sheets for all Electrical Equipment
CONCEPTUAL & DETAILED DESIGN FOR RELOCATION
OF FIRE TRAINING FACILITY AT HALUL
CONCEPTUAL & DETAILED DESIGN FOR RELOCATION OF FIRE
TRAINING FACILITY AT HALUL
CLIENT:
QP PROJECT NUMBER:
3460
CONTRACT NO.
LC13105500
DOCUMENT TITLE:
Data Sheets for all Electrical Equipment
DATE REV. NO. DESCRIPTION
L&T INTEGRATED ENGINEERING SERVICES
CONTRACTORS PROJECT NUMBER:
P003658
CLIENT : Date :22/07/2014
PROJECT Revision:0
SUPPLIER DATA
1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
2
2.1
2.2 m
2.3 NOTE 5
2.4
2.5
3
3.1
3.2
3.3
3.4
3.5
3.6
4
4.1
4.2
4.3
4.4
4.5
5
5.1
5.2
5.3
DOC. NO.:HN29-2-13-0001
CONCEPTUAL & DETAILED DESIGN FOR
RELOCATION OF FIRE TRAINING
FACILITY AT HALUL
QATAR PETROLEUM
SHELL DEP STANDARD DEP-33.65.50.32-Gen
BUS TIE
YES

NO
DISTRIBUTION BOARD
QUANTITY OF BOARDS 1
MAIN BREAKER QTY / TYPE PER BOARD
SEE SLD NO.
HN29-2-54-0003-001
FREQUENCY 50 Hz, 1%
NEUTRAL SYSTEM SOLIDLY GROUNDED
OUTPUT VOLTAGE (STEADY STATE) 230 V 5%
NO. OF PHASES
1 Phase + Neutral,
Sinusoidal Waveform
UPSTREAM PROTECTION (SUPPLY BY OTHERS) MCCB
USER NETWORK DATA
OUTPUT POWER
25 kVA
(HOLD)
FAULT LEVEL 35kA FOR 1 Sec.
NEUTRAL SYSTEM SOLIDLY GROUNDED
SPECIAL CONDITIONS (TROPICALISATION, etc.) Tropicalisation
FREQUENCY 50Hz5%
MAXIMUM INDOOR TEMPERATURE 50C
RELATIVE HUMIDITY (INDOOR) 90% RH +/- 10%
VOLTAGE 400V 10%
TYPE
QP STANDARD ES.2.14.0040 RA
PROJECT SPECIFICATION HN29-2-14-0001-001
PLACE OF INSTALLATION
AC UNINTERRUPTIBLE POWER SUPPLY
INTERNATIONAL STANDARDS AND CODES IEC 62040
PHASES NUMBER 3+N+E
TAG NO. UPS-30 XX
Power supply to Telecom and Instrumentation,
Refer to the UPS Sizing Calculations Doc.HN29-
2-12-0001
SUPPLIER / MANUFACTURER :
DESIGN DATA
LED/DISPLAY UNIT
PURPOSE
ALTITUDE (IF > 1000m)
***
ENVIRONMENTAL CONDITIONS
LOCATION
<1000
INDOOR
Document Title:
Data sheets for all electrical equipment
GENERAL DATA
***
SUPPLY NETWORK CHARACTERISTICS (NOTE 7)
Page 2 of 19
CLIENT : Date :22/07/2014
PROJECT Revision:0
SUPPLIER DATA DOC. NO.:HN29-2-13-0001
CONCEPTUAL & DETAILED DESIGN FOR
RELOCATION OF FIRE TRAINING
FACILITY AT HALUL
QATAR PETROLEUM
AC UNINTERRUPTIBLE POWER SUPPLY
DESIGN DATA
Document Title:
Data sheets for all electrical equipment
5.4
5.5
a
b
c
6
6.1
6.2
6.3
6.4
6.5
7
7.1
7.2
7.3
a
b
7.4
7.5
7.6
7.7
7.8
7.9
7.10
7.11
a
b
c
7.12
7.13
7.14
7.15
7.16 RADIO INTERFERE. SUPPRESSION
YES

NO
RESIDUAL RIPPLE BATTERY CURRENT ***
CURRENT HARMONIC REJECTION ***
RIPPLE VOLTAGE WITH BATTERY ***
RIPPLE VOLTAGE WITHOUT BATTERY ***
- EQUALIZING MODE ***
- BOOST MODE ***
RECTIFIER OUTPUT VOLTAGE / VOLTAGE VARIATION 230V 1%
- FLOATING MODE ***
RECTIFIER OUTPUT RATED CURRENT ***
LIMITATION OF RECT. CURRENT (AFTER 10mn, 3mn, 1mn, 10s) ***
BATTERY QTY / SIZING (50%, 100%, ) 2 X 100 %
INPUT PEAK CURRENT ***
RATED POWER (FLOATING MODE)
*** WITH FAN
*** WITHOUT FAN
MAXIMUM ABSORBED LOAD ***
- STAND BY
PARALLEL
HOT
SHARING OF THE LOAD
YES

NO
RECTIFIER QTY / SIZING (50%, 100%) 2 X 100 %
OPERATING CONDITIONS
- STAND ALONE
YES

NO
EARTH LEAK DETECTOR WITH ALARM CONTACT (DC)
YES

NO
RECTIFIER
TYPE (3, 6, 12 PULSES) 12 PULSES
FREQUENCY METER
YES

NO
GENERAL MIMIC DIAGRAM
YES

NO
DISTRIBUTION BOARD DISPLAY
AMMETER
YES

NO
VOLTMETER
YES

NO
- STATUS CONTACTS
YES

NO
- SPARE EQUIPMENT 25%
OUTGOING QTY / TYPE PER BOARD WITH
(The CB shall ensure selectivity with rectifier output protection)
SEE SLD NO.
: HN29-2-54-0003-001 & 002
- TRIPPING COILS
YES

NO
AUTOMATIC TRANSFER SEQUENCE
YES

NO
Page 3 of 19
CLIENT : Date :22/07/2014
PROJECT Revision:0
SUPPLIER DATA DOC. NO.:HN29-2-13-0001
CONCEPTUAL & DETAILED DESIGN FOR
RELOCATION OF FIRE TRAINING
FACILITY AT HALUL
QATAR PETROLEUM
AC UNINTERRUPTIBLE POWER SUPPLY
DESIGN DATA
Document Title:
Data sheets for all electrical equipment
7.17
7.18
7.19
7.20
7.21
8
8.1
8.2
8.3
8.4
8.5
8.6
8.7
8.8
9
9.1
9.2
9.3
9.4
10
10.1
10.2
10.3 a
b
c
10.4
10.5 OPERATION ON BATTERY
LOCAL
REMOTE
BOOST
MANUAL / AUTOMATIC OPERATION
LOCAL
REMOTE
OPERATIONAL MODE FLOATING
EQUALIZING
RECTIFIER MONITORING (NOTE 1 )
MAINS ON
LOCAL
REMOTE
RECTIFIER RUNNING
LOCAL
REMOTE
RECTIFIER OUTPUT CURRENT
YES

NO
AC AMMETER & VOLTMETER WITH SELECTOR SWITCHES FOR
RECTIFIER INPUTS
YES

NO
RECTIFIER MEASURE DISPLAY (NOTE 1)
DC VOLTMETER
YES

NO
BATTERY CURRENT AMMETER
YES

NO
DC OUTPUT VOLTAGE ADJUSTMENT
LOCAL
REMOTE
DC CURRENT LIMIT ADJUSTMENT
YES

NO
BOOST OPERATION DURATION TIMER
YES

NO
BATTERY ISOLATION SWITCH
LOCAL
REMOTE
CHANGEOVER FLOATING / EQUALIZING
LOCAL
REMOTE
BOOST OPERATION
LOCAL
REMOTE
RECTIFIER CONTROL
RECTIFIER ON / OFF
LOCAL

REMOTE
RECTIFIER INPUT ISOLATING SWITCH
LOCAL

REMOTE
POWER FACTOR 4/4, 3/4, 2/4, 1/4 ***
EXECUTION
THYRISTOR

IGBT TRANSISTOR*
AUTOMATIC BOOST OPERATION
YES

NO
EFFICIENCY 4/4, 3/4, 2/4, 1/4 ***
AUTOMATIC CHANGEOVER FLOATING / EQUALIZING
YES

NO
Page 4 of 19
CLIENT : Date :22/07/2014
PROJECT Revision:0
SUPPLIER DATA DOC. NO.:HN29-2-13-0001
CONCEPTUAL & DETAILED DESIGN FOR
RELOCATION OF FIRE TRAINING
FACILITY AT HALUL
QATAR PETROLEUM
AC UNINTERRUPTIBLE POWER SUPPLY
DESIGN DATA
Document Title:
Data sheets for all electrical equipment
10.6
10.7
11
11.1
11.2
11.3
11.4
11.5
11.6
11.7 DC EARTH FAULT
11.8
11.9
12
12.1
12.2
12.3
12.4
12.5
13
13.1
13.2
13.3
a
b
c
a ***WITH FAN
b
13.5
- SHARING OF THE LOAD
YES

NO
***WITHOUT FAN
INVERTER (NOTE 1&3 )
OUTPUT VOLTAGE REGULATION
RATED POWER
OPERATING CONDITIONS
- STAND ALONE
YES

NO
- STAND BY
PARALLEL

HOT
PULSE WIDTH MODULATION TECHNOLOGY
YES

NO
INVERTER QTY (50%, 100% ) 2 X 100 %
ANTI CONDENSATION HEATERS
YES

NO
PROTECTION AGAINST EXTERNAL SURGES
WEIGHT
kg
***
COOLING MODE
NATURAL
FORCED
YES

NO
RECTIFIER STACK OVER TEMPERATURE
LOCAL
REMOTE
RECTIFIER CUBICLE(NOTE NO.3)
LENGTH / DEPTH / HEIGHT
mm
***
BATTERY OVERCURRENT
LOCAL
REMOTE
LOCAL
REMOTE
COOLING FAN FAILURE
LOCAL
REMOTE
DC UNDERVOLTAGE
LOCAL
REMOTE
RECTIFIER OVERCURRENT
LOCAL
REMOTE
RECTIFIER FAILURE
LOCAL
REMOTE
DC OVERVOLTAGE
LOCAL
REMOTE
IMMINENT DISCHARGED BATTERY
LOCAL
REMOTE
RECTIFIER FAULT DISPLAY (NOTE 1 )
MAINS FAILURE
LOCAL
REMOTE
EQUALIZING / BOOST INHIBITION
YES

NO
13.4
Page 5 of 19
CLIENT : Date :22/07/2014
PROJECT Revision:0
SUPPLIER DATA DOC. NO.:HN29-2-13-0001
CONCEPTUAL & DETAILED DESIGN FOR
RELOCATION OF FIRE TRAINING
FACILITY AT HALUL
QATAR PETROLEUM
AC UNINTERRUPTIBLE POWER SUPPLY
DESIGN DATA
Document Title:
Data sheets for all electrical equipment
a
b
c
13.6
13.7
a
b
13.8
13.9
a
b
13.10
13.11
a
b
13.12
13.13
13.14
14
14.1
14.2
14.3
14.4
14.5
15
15.1
15.2
15.3
15.4
16
16.1
BYPASS INPUT VOLTMETER
YES

NO
INVERTER MONITORING (NOTE 1)
SUPPLY ON
LOCAL
REMOTE
OUTPUT INVERTER AMMETER
YES

NO
OUTPUT INVERTER FREQUENCY METER
YES

NO
INVERTER OUTPUT ISOLATION STATIC SWITCH
LOCAL
REMOTE
INVERTER MEASURE DISPLAY (NOTE 1)
OUTPUT INVERTER VOLTMETER
YES

NO
SYNCHRONISING RANGE ADJUSTMENT
LOCAL
REMOTE
LOAD TRANSFER INITIATING
LOCAL
REMOTE
INVERTER CONTROL
INVERTER ON / OFF
LOCAL
REMOTE
AC OUTPUT VOLTAGE ADJUSTMENT
LOCAL
REMOTE
ALLOWABLE OVERLOAD
125% FOR 15 MINUTES AND 150% FOR
1 MINUTE
EFFICIENCY 4/4, 3/4, 2/4, 1/4 ***
- MAXIMUM CURRENT (120%, .) ***
LIMITATION OF INVERT. CURRENT (AFTER 10mn, 3mn, 1mn, 10s) ***
SEMI-CONDUCTOR SIZING
- MAXIMUM TEMPERATURE (125%, ) ***
OUTPUT VOLTAGE HARMONIC
- WITH LINEAR LOAD (THD/SHD) 5% / 3%
- WITH NON LINEAR LOAD ***
- TRANSIENT 100% LOAD CHANGE (%)
- STEADY STATE (%) 5% AT 100% Load
- NETWORK UNSYNCHRONISED (%) 2%
FREQUENCY REGULATION
FREQUENCY ADJUSTMENT (%) 0.25% TO 1%
OUTPUT VOLTAGE ADJUSTMENT (%) 5%
- NETWORK SYNCHRONISED (%) 5%
MIN. ACCEPTABLE CREST FACTOR 3
10%
- VOLTAGE RECOVERY TIME
100 msec TO WITHIN 5%
OF STEADY STATE VOLTAGE
Page 6 of 19
CLIENT : Date :22/07/2014
PROJECT Revision:0
SUPPLIER DATA DOC. NO.:HN29-2-13-0001
CONCEPTUAL & DETAILED DESIGN FOR
RELOCATION OF FIRE TRAINING
FACILITY AT HALUL
QATAR PETROLEUM
AC UNINTERRUPTIBLE POWER SUPPLY
DESIGN DATA
Document Title:
Data sheets for all electrical equipment
16.2
16.3
16.4
16.5
16.6
17
17.1
17.2
17.3
17.4
17.5
17.6
17.7
17.8
17.9
18
18.1
18.2
18.3
18.4
19
19.1
19.2
19.3
19.4
19.5
19.6
19.7
19.8
SERIAL LINK COMMUNICATION REQUIRED
GENERAL MIMIC DIAGRAM YES
AUTODIAGNOSTICS DISPLAY REQUIRED
TYPE OF REMOTE SIGNAL (IF ANY) HARD WIRED
LAMP TEST REQUIRED
FAULT RESET PUSH BUTTONS REQUIRED
RECTIFIER AND INVERTER CUBICLE SIGNALISATION (NOTE 1)
TYPE (LAMPS, LEDS, DISPLAY UNIT) LED/DISPLAY UNIT
SIGNALISATION COLOURS : ON / OFF / FAULT AS PER IEC
COOLING MODE
***NATURAL

FORCED
ANTI CONDENSATION HEATERS
YES

NO
INVERTER CUBICLE
LENGTH / DEPTH / HEIGHT mm ***
WEIGHT
kg
***
COOLING FAN FAILURE
LOCAL
REMOTE
INVERTER STACK OVER TEMPERATURE
LOCAL
REMOTE
EMERG. SUPPLY FAULT
LOCAL
REMOTE
AC EARTH FAULT
LOCAL
REMOTE
SYNCHRONIZING FAULT
LOCAL
REMOTE
OPERATION ON EMERG. TRANSFO.
LOCAL
REMOTE
OUTPUT VOLTAGE DEVIATION
LOCAL
REMOTE
OUTPUT OVERLOAD
LOCAL
REMOTE
STATIC SWITCH BYPASSED
LOCAL
REMOTE
INVERTER FAULT DISPLAY (NOTE 1)
INVERTER FAILURE
LOCAL
REMOTE
ALTERNATIVE / BY PASS AVAILABLE
LOCAL
REMOTE
INVERTER / BYPASS SYNCHRONISED
LOCAL
REMOTE
RUNNING
LOCAL
REMOTE
LOAD ON INVERTER / BY PASS
LOCAL
REMOTE
Page 7 of 19
CLIENT : Date :22/07/2014
PROJECT Revision:0
SUPPLIER DATA DOC. NO.:HN29-2-13-0001
CONCEPTUAL & DETAILED DESIGN FOR
RELOCATION OF FIRE TRAINING
FACILITY AT HALUL
QATAR PETROLEUM
AC UNINTERRUPTIBLE POWER SUPPLY
DESIGN DATA
Document Title:
Data sheets for all electrical equipment
20
20.1 ACCESS
20.2
20.3
20.4
20.5
20.6
20.7
20.8
20.9
21
21.1
22.2
22.3
23
23.1
23.2
23.3
a
b
c
23.4
24
24.1
24.2
24.3
24.4
24.5
24.6
24.7
24.8
24.9
24.10 INSULATION CLASS F (SEE NOTE 8)
CONNECTION SYMBOL AND VECTOR GROUP ***
INSULATION SCREEN (DRY TYPE, OIL SEALED) DRY
RATED FREQUENCY 50Hz5%
NO. OF PHASES (PRIMARY) 3+N+E
RATED PRIMARY VOLTAGE 400V10%
RATED SECONDARY VOLTAGE AT NO LOAD ***
QUANTITY 1
RATED POWER ***
FOR MANUAL BY PASS, INTERLOCKING SHALL ENSURE FULL
SAFETY AND AVOID WRONG OPERATIONS
YES
BYPASS TRANSFORMER
MANUFACTURER / TYPE ***
- WITH, WITHOUT BREAKING WITHOUT BREAKING
- OPERATING TIME < 0.5millisecs
CHANGE OVER INVERTER / TRANSFORMER
- MANUAL, AUTOMATIC BOTH
STATIC SWITCH
QUANTITY
SEE SLD NO. :HN29-
2-54-0003
STATIC, ELECTROMECHANICAL STATIC
PROTECTION AGAINST EXTERNAL SURGES
YES

NO
MANUAL BY PASS SWITCH
YES

NO
MAXIMUM ALLOWABLE SHORT CIRCUIT CURRENT
YES

NO
GLOBAL NOISE LEVEL AT FULL LOAD <70dB (A)
BY PASS
- TREATMENT
MANUFACTURER STD OR QP SPEC
NO.: QP-SPC-L-002, WHICHEVER IS
MORE ONEROUS
- COLOUR RAL 7035
DEGREE OF PROTECTION (IP) IP 42
PAINTING
OVERALL LENGTH / DEPTH / HEIGHT mm ***
WEIGHT
kg
***
RECTIFIER AND INVERTER CUBICLE GENERAL CHARACTERISTICS
FRONT
CABLE ENTRY TOP
Page 8 of 19
CLIENT : Date :22/07/2014
PROJECT Revision:0
SUPPLIER DATA DOC. NO.:HN29-2-13-0001
CONCEPTUAL & DETAILED DESIGN FOR
RELOCATION OF FIRE TRAINING
FACILITY AT HALUL
QATAR PETROLEUM
AC UNINTERRUPTIBLE POWER SUPPLY
DESIGN DATA
Document Title:
Data sheets for all electrical equipment
24.11 TYPE OF COOLING
24.12
24.13
24.14
24.15
24.16
24.17
24.18
24.19
25
25.1
25.2 230 V DC
25.3
25.4
25.5
25.6
25.7
25.8
25.9
a
b
c
d
25.10
a
b
25.11
25.12
a
b
c
25.13
a
b
25.14
a
b
25.15
a
CHARGING TIME IN BOOST MODE
- 80% CAPACITY ***
- 80% CAPACITY ***
- 100% CAPACITY ***
- BATTERY END OF DISCHARGE ***
CHARGING TIME IN EQUALIZING MODE UP TO
SHORT CIRCUIT CURRENT AT
- BATTERY FULLY CHARGED ***
- EQUALIZING MODE ***
- BOOST MODE ***
LOAD CURRENT
- FLOATING MODE ***
- AFTER 1 HOURS OF DISCHARGE (h/Ah) ***
AUTONOMY 60 MINUTES
CAPACITY ***
- BATTERY FULLY CHARGED (Ah)
***
(SEE NOTE 11)
- BOOST MODE ***
- END OF DISCHARGE AT 20C ***
- FLOATING MODE ***
- EQUALIZING MODE ***
NUMBER OF CELLS ***
VOLTAGE PER CELL
- LEAD ACID, CADMIUM-NICKEL NICKEL- CADMIUM
RATED VOLTAGE ***
TYPE (VENTED, GAS RECOMBINATION, )
- VENTED, GAS RECOMBINATION GAS RECOMBINATION TYPE
BATTERY
MANUFACTURER ***
QUANTITY / SIZING (50%, 100% )
2 X 100%
(SEE NOTE 10 & 11)
NOMINAL OUTPUT VOLTAGE
TYPE OF ENCLOSURE (TRANSFO. BOX, IN A PANEL,.) ***
VOLTAGE REGULATOR
STABILISER REQUIRED AS PER QP
SPECIFICATION NO.: ES.2.14.0040RA
TOTAL LOSSES ***
SHORT CIRCUIT IMPEDANCE AT 75C ***
PEAK CURRENT ***
NO LOAD LOSSES ***
OFF CIRCUIT TAP CHANGER ***
TAP RANGE / STEPS ***
AN
Page 9 of 19
CLIENT : Date :22/07/2014
PROJECT Revision:0
SUPPLIER DATA DOC. NO.:HN29-2-13-0001
CONCEPTUAL & DETAILED DESIGN FOR
RELOCATION OF FIRE TRAINING
FACILITY AT HALUL
QATAR PETROLEUM
AC UNINTERRUPTIBLE POWER SUPPLY
DESIGN DATA
Document Title:
Data sheets for all electrical equipment
b
25.16
a
b
25.17
a
b
25.18
26.0
26.1
a
b
26.2
a
b
c
26.3
a
b
c
26.4
a
b
26.5
26.6
a
b
26.7
a
b
27
27.1
27.2
27.3
27.4
27.5
YES

NO
THERMOMETER
AUTOMATIC FILLING DEVICE
YES

NO
YES

NO
PORTABLE VOLTMETER
- EQUALIZING / BOOST MODE ***
ACCESSORIES
PORTABLE EARTH FAULT DETECTOR
YES

NO
YES

NO
DENSIMETER
- EQUALIZING / BOOST MODE ***
HEAT DISSIPATION
- FLOATING MODE ***
OVERALL WEIGHT
kg
***
REQUIRED VENTILATION
- FLOATING MODE ***
- CUBICLE ***
- STEEL STAND
*** (Lowest shelf shall be at least
1 metre above ground)
- VOLUME OF ELECTROLYTE l ***
OVERALL LENGTH / DEPTH / HEIGHT mm
- LENGTH / DEPTH / HEIGHT mm ***
- WEIGHT WITH ELECTROLYTE kg ***
- NO. OF TIERS / STEPS ***
DIMENSIONS / WEIGHT PER CELL
- CUBICLE WITH FIXING FRAME NO
- ON STEEL STANDS WITH PROPER FOOT INSULATION
REQUIRED
(PART OF UPS/BATTERY SUPPLIER)
- BATTERY CHARGER ROOM
MOUNTING
BATTERY INSTALLATION(NOTE 2 &4 )
LOCATION
- BATTERY ROOM - WELL VENTILATED YES (Exhaust Fan)
- ELECTROLYTE DELIVERED DRY ***
MAXIMUM STORAGE TIME BEFORE FIRST CHARGING OF
BATTERIES
***
DELIVERY CONDITIONS
- CELLS DELIVERED FILLED, DRY ***
- BOOST CHARGE ***
- FLOAT CHARGE ***
- 100% CAPACITY ***
BATTERY HYDROGEN EMISSION
Page 10 of 19
CLIENT : Date :22/07/2014
PROJECT Revision:0
SUPPLIER DATA DOC. NO.:HN29-2-13-0001
CONCEPTUAL & DETAILED DESIGN FOR
RELOCATION OF FIRE TRAINING
FACILITY AT HALUL
QATAR PETROLEUM
AC UNINTERRUPTIBLE POWER SUPPLY
DESIGN DATA
Document Title:
Data sheets for all electrical equipment
27.6
27.7
27.8
a
b
27.9
27.10
27.11
NOTE 1:
NOTE 2:
NOTE 3:
NOTE 4:
NOTE 5:
NOTE 6:
NOTE 7:
NOTE 8:
NOTE 9:
NOTE 10:
NOTE 11:
BATTERY SIZING CALCULATION TO BE SUBMITTED BY UPS SUPPLIER
- TRIPPING COIL
YES

NO
TOOL BOX
CABLE FROM BATTERY TO UPS SHALL BE VALIDATED BY UPS SUPPLIER.
NAMEPLATES
YES

NO
CONNECTIONS
YES

NO
HOLD: SHALL BE INFORMED AS PER FINAL CALCULATION AND LOAD SCHEDULE.
BATTERY LOAD DISCHARGE ISOLATOR
YES

NO
LOAD BANK FOR TESTING THE AC UPS SYSTEM SHALL BE SUPPLIED BY THE VENDOR.
- TYPE MCCB (SEE NOTE 9)
YES

NO
FIXING ACCESSORIES
YES

NO
TEMPERATURE RISE IS TO BE LIMITED TO CLASS B
ISOLATING BREAKER
YES

NO
DESIGN AMBIENT AIR TEMPERATURE OF 50 DEGREE C SHALL BE CONSIDERED SO AS TO WITHSTAND THE HVAC
FAILURE CONDITIONS.
THE BATTERY ISOLATING BREAKER IS TO BE LOCATED IN THE BATTERY ROOM, Ex d RATED HAVING SHUNT TRIP
INTERCONNECTED WITH F&G PANEL TO STOP CHARGING IN CASE OF GAS DETECTION
MEASUREMENT DISPLAY, MONITORING DISPLAY, FAULT DISPLAY AND CUBICLE SIGNALIZATION DISPLAY SHALL
HAVE SERIAL LINK FACILITY FOR REMOTE INDICATION. VENDOR SHALL PROVIDE AND ESTABLISH SERIAL LINK
COMMUNICATION WITH PLANT MAIN CONTROL SYSTEM.
NOTE : * * * : MANUFACTURER TO SPECIFY
THE 3 PHASE FAULT LEVEL FOR MCCB IS 35kA FOR 1 SEC WHICH WILL BE CONFIRMED AT THE LATER STAGE.
ALL PANEL VENTILATION SHALL BE SUCTION TYPE WITH THE FAN AND OUTLET MOUNTED AT THE TOP PART OF
THE VERTICAL PANEL AND A FILTERED INPUT MOUNTED AT THE BOTTOM OF THE PANEL. THE FILTER SHALL BE
REPLACED MONTHLY OR AS NECESSARY UNTIL THE END OF THE FINAL PLANT HAND-OVER. FAN SHALL BE
MONITORED FOR FAN FAILURE ALARM.
TRANSIENT SUPPRESSION/ABSORPTION EQUIPMENT SHALL BE SUPPLIED ON THE INCOMING SUPPLY TO AVOID
FAILURE OF RECTIFIER SIDE POWER ELECTRONICS DUE TO SUPPLY-SIDE TRANSIENTS.
AUTOMATIC BOOST WILL BE INHIBITED BY FAILURE OF THE BATTERY ROOM VENT EXHAUST FAN
Page 11 of 19
CLIENT : Date :22/07/2014
PROJECT Revision:0
SUPPLIER DATA
A
B
C
1.0
1.1
1.2
2.0
2.1
2.2
3.0
3.1
4.0
4.1
4.2
4.3
4.4
4.5
5.0
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.9
6.0
6.1
LT POWER CABLE
CONCEPTUAL & DETAILED DESIGN FOR
RELOCATION OF FIRE TRAINING FACILITY
AT HALUL
ARMOUR
DOC. NO:HN29-2-13-0001-001
Frequency 50 Hz +/-5%
DESIGN DATA
Supplier
Manufacturer
Country of orgin
Specification and QP Standard
HN29-2-14-0001
&ES.2.14.0070 RA
SYSTEM REQUIRMENT
STANDARD
Manufacturing Standard IEC 60228, IEC 60502, IEC 60227
VOLTAGE DESIGNATION
Max conductor temperature (on
load)
Max conductor temperature (on
fault)
250C (XLPE)
Shape of conductor Circular
CONDUCTOR
Material
Size
90C (XLPE)
Material XLPE
Minimum radial thickness of insulation (mm) Vendor to furnish
INNER INSULATION
Colour Coding
4 Cores Red, Yellow, Blue & Black
3 Cores - Red, Yellow, Blue
1 Core - Black
Fillers
Solidly extruded non-fibrous, Non
hygroscopic fillers, as required
Inner Bedding Extruded PVC
Inner Sheath PVC ST2
Insulation Screening Not Required
Conductor screening Not Required
Binder tape Required
Material
Galvanized round Steel Wire Armour for
multicore cables (SWB up to 10mm and SWA
for 16mm & above)
Voltage 400V+/-10%
Power Cables 600/1000V
High Conductive Electrolytic
Copper conductor As per IEC
60228
Document Title:
Data sheets for all electrical equipment
Later
Qatar Petroleum
Page 12 of 19
CLIENT : Date :22/07/2014
PROJECT Revision:0
SUPPLIER DATA
LT POWER CABLE
CONCEPTUAL & DETAILED DESIGN FOR
RELOCATION OF FIRE TRAINING FACILITY
AT HALUL
DOC. NO:HN29-2-13-0001-001 DESIGN DATA
Document Title:
Data sheets for all electrical equipment
Qatar Petroleum
6.2
6.3
7.0
7.1
7.2
7.3
8.0
9.0
10.0
10.1
10.2
10.3
11.0
11.1
11.2
12.0
12.1
12.2
12.3
12.4
12.5
12.6
12.7
12.8
12.9
12.10
13.0
13.1
13.2
MINIMUM PERMISSIBLE BENDING RADIUS
ELECTRICAL DATA
OUTER SHEATH
Armour wire size (mm)
Total cable diameter over
armour (mm)
Vendor to furnish
Vendor to furnish
Material
PVC ST2, flame retardant as per
IEC-60332-3.
Minimum radial thickness of insulation (mm)
Black
Vendor to furnish
Dielectric loss angle (Tan) Vendor to furnish
Vendor to furnish
Maximum specific DCconductor resistance at 20C (Ohm/km) Vendor to furnish
Maximum specific AC conductor resistance at 90C (Ohm/km)
OXYGEN INDEX > 30
Vendor to furnish
Colour coding
COMPLETED CABLE
Maximum drum length
(without joints) (m)
< 17%
Weight per meter Vendor to furnish
Vendor to furnish
Positive/negative sequence impedance (Ohm/km) Vendor to furnish
ACIDIC EMMISSION
during laying (mm) Vendor to furnish
for sealing ends (mm) Vendor to furnish
Minimum insulation resistance at 20C(Ohm)
Short circuit current rating (kA) Vendor to furnish
Vendor to furnish
Vendor to furnish
Emergency overloading of cables Vendor to furnish
Maximum specific working capacitance under full load condition
(F/km)
Surge impedance (Ohm/km) Vendor to furnish
Zero sequence impedance (Ohm/km) Vendor to furnish
MARKING AND IDENTIFICATION
Manufacturers name
No. of cores and conductor size
To be provided on cable (at every 3M interval).
To be provided on cable.
Overall diameter (on drum)
(mm)
Page 13 of 19
CLIENT : Date :22/07/2014
PROJECT Revision:0
SUPPLIER DATA
LT POWER CABLE
CONCEPTUAL & DETAILED DESIGN FOR
RELOCATION OF FIRE TRAINING FACILITY
AT HALUL
DOC. NO:HN29-2-13-0001-001 DESIGN DATA
Document Title:
Data sheets for all electrical equipment
Qatar Petroleum
13.3
13.4
13.5
14.0
14.1
14.2
NOTE 1:
NOTE 2:
ABBREVIATIONS:
PVC
XLPE
SWA
SWA
AWA
Reference standard
Insulation voltage
Construction designation
To be provided on cable.
To be provided on cable.
To be provided on cable.
NOTES
Manufactures to submit individual data sheets for each type of Cable for
Approval
Vendor to furnish Type Test, Sample Test certificates for each type of cables
supplied
TESTING
Type Test
Routine Test (FAT) & Site Test
ES. 2.14.0070 Rev.A
and HN29-2-14-0001
Required
Required
POLY VINYL CHOLRIDE
CROSS LINKED POLYETHLENE
STEEL WIRE ARMOUR
STEEL WIRE BRAIDED
ALUMINIUM WIRE ARMOUR
Page 14of 19
CLIENT : Date :22/07/2014
PROJECT Revision:0
SUPPLIER DATA
A
B
C
1.0
1.1
1.2
2.0
2.1
2.2
3.0
3.1
4.0
4.1
4.2
4.3
4.4
4.5
5.0
5.1
5.2
5.3
6.0
7.0
8.0
8.1
8.2
8.3
9.0
9.1
9.2
EARTHING CABLE
CONCEPTUAL & DETAILED DESIGN FOR
RELOCATION OF FIRE TRAINING FACILITY
AT HALUL
Document Title:
Data sheets for all electrical equipment
DESIGN DATA
Supplier
Manufacturer
Country of orgin
DOC. NO.:HN29-2-13-0001
SYSTEM REQUIRMENT
Voltage 400V+/-10%
Frequency 50 Hz +/-5%
STANDARD
Specification and QP Standard
HN29-2-14-0001
&ES.2.14.0070 RA
Manufacturing Standard IEC 60228, IEC 60227
VOLTAGE DESIGNATION
Power Cables 600/1000V
CONDUCTOR
Max conductor temperature (on
fault)
160C (PVC)
Shape of conductor Circular /stranded
Material
High purity Electrolytic Stranded Copper
conductor As per IEC 60228
Size
Max conductor temperature (on
load)
70C (PVC)
Later
OUTER SHEATH
Material
ST2 PVC, flame retardant
as per IEC-60332-3.
Colour coding Yellow with Green stripes
Minimum radial thickness of insulation (mm) Vendor to furnish
OXYGEN INDEX > 30
ACIDIC EMMISSION < 17%
COMPLETED CABLE
Overall diameter (on drum)
(mm)
Vendor to furnish
Maximum drum length
(without joints) (m)
Vendor to furnish
Weight per meter Vendor to furnish
MINIMUM PERMISSIBLE BENDING RADIUS
during laying (mm) Vendor to furnish
for sealing ends (mm) Vendor to furnish
Qatar Petroleum
Page 15 of 19
CLIENT : Date :22/07/2014
PROJECT Revision:0
SUPPLIER DATA
EARTHING CABLE
CONCEPTUAL & DETAILED DESIGN FOR
RELOCATION OF FIRE TRAINING FACILITY
AT HALUL
Document Title:
Data sheets for all electrical equipment
DESIGN DATA DOC. NO.:HN29-2-13-0001
Qatar Petroleum
10.0
10.1
10.2
10.3
10.4
10.5
10.6
10.7
10.8
10.9
10.10
11.0
11.1
11.2
11.3
11.4
11.5
12.0
12.1
12.2
NOTE 1:
NOTE 2:
ABBREVIATIONS:
PVC
ELECTRICAL DATA
Maximum specific DCconductor resistance at 20C (Ohm/km) Vendor to furnish
Maximum specific AC conductor resistance at 85C (Ohm/km) Vendor to furnish
Minimum insulation resistance at 20C(Ohm) Vendor to furnish
Dielectric loss angle (Tan) Vendor to furnish
Maximum specific working capacitance under full load condition
(F/km)
Vendor to furnish
Surge impedance (Ohm/km) Vendor to furnish
Zero sequence impedance (Ohm/km) Vendor to furnish
Positive/negative sequence impedance (Ohm/km) Vendor to furnish
Short circuit current rating (kA) Vendor to furnish
Emergency overloading of cables Vendor to furnish
MARKING AND IDENTIFICATION
Manufacturers name To be provided on cable (at every 3M interval).
No. of cores and conductor size To be provided on cable.
Reference standard To be provided on cable.
Insulation voltage To be provided on cable.
Construction designation To be provided on cable.
TESTING
ES. 2.14.0070 Rev.A
and HN29-2-14-0001
Type Test Required
Routine Test (FAT) & Site Test Required
NOTES
Manufactures to submit individual data sheets for each type of Cable for
Approval
Vendor to furnish Type Test, Sample Test certificates for each type of cables
supplied
POLY VINYL CHOLRIDE
Page 16 of 19
Date :22/07/2014
PROJECT Revision:0
SUPPLIER DATA
1.0
1.1
1.2
1.3
2.0
2.1
2.2
2.3 NOTE 3
2.4
2.5
2.6
2.7
3.0
3.1
3.2
3.3
3.4
3.5
3.6
3.7
4.0
4.1
4.2
5.0
5.1
5.2
5.3
5.4
5.5
5.6
5.7 DISTRIBUTED / NOT DISTRIBUTED DISTRIBUTED
NEUTRAL SYSTEM:
NEUTRALSHALL BE BROUGHT TO THE
SWITCHBOARD /SOLIDLY EARTHED
INTERNAL ARC WITHSTAND CAPACITY 35kA (Min) for 1sec, in accordance with IEC 61641
SOLIDLY GROUNDED / UNEARTHED / IMPEDANCE SOLIDLY GROUNDED
YES
VOLTAGE 400V 10%
FREQUENCY 50Hz 5%
SHORT CIRCUIT POWER 35kA (rms)/1s
CONNECTION REAR/FRONT
CABLES ENTRY TOP
DEGREE OF PROTECTION (IP) Minimum IP 42
INTERNAL SEPARATION (FORM 1, FORM 2, ...) FORM4b
WITHDRAWABLE / PLUG-IN / FIXED / FIXED
MOUNTING: FLOOR/WALL MOUNTED
DESIGN BASIS MEMORANDUM
SEE DOC. NO.: HN29-2-29-0001
SWITCHGEAR GENERAL CHARACTERISTICS
TYPE : SINGLE FRONT
ASSEMBLY EXTERNAL DESIGN (OPEN, DEAD FRONT,
( ENCLOSED, CUBICLE, MULTI-CUBICLE, BOX, MULTI-BOX)
ENCLOSED
MULTICUBICLE
RELATIVE HUMIDITY (INDOOR) 50% RH +/- 10%
RELATIVE HUMIDITY (OUTDOOR) 100%
SPECIAL CONDITIONS TROPICALISATION
PLACE OF INSTALLATION : (INDOOR, OUTDOOR) INDOOR
ALTITUDE < 1000 m
MAXIMUM AMBIENT AIR TEMPERATURE 50C,
DESIGN DATA
GENERAL DATA
MANUFACTURER ***
CONCEPTUAL & DETAILED DESIGN FOR
RELOCATION OF FIRE TRAINING FACILITY AT
HALUL
DOC. NO.:HN29-2-13-0001
CLIENT :
DATA SHEET FOR LV AC DB AND
MCC
STANDARDS / CODES IEC -61439 & IEC 60947
Document Title:
Data sheets for all electrical equipment
GENERAL & PROJECT SPECIFICATION
ES.2.14.0015 RA & HN29-2-14-0001
ENVIRONMENTAL CONDITIONS
PROTECTION:
NETWORK :
TROPICALISATION
Qatar Petroleum
Page 17 of 19
Date :22/07/2014
PROJECT Revision:0
CONCEPTUAL & DETAILED DESIGN FOR
RELOCATION OF FIRE TRAINING FACILITY AT
HALUL
CLIENT :
DATA SHEET FOR LV AC DB AND
MCC
Document Title:
Data sheets for all electrical equipment
Qatar Petroleum
6.0
6.1
6.2
6.3
6.4
6.5
6.6
6.7
7.0
7.1
7.2
7.3
7.4
7.5
7.6
7.7
7.80
7.9
7.10
7.11
7.12
8.0
8.1
8.2
8.3
8.4
8.5
9.0
9.1
9.2
SWITCHGEAR:
LIFTING EYEBOLTS (Y/N) REQUIRED
***
AUXILIARY VOLTAGES :
ACCESSORIES AND MISCELLANEOUS
MOUNTING CHANNELS & FIXING ACCESSORIES(Y/N) REQUIRED
AUXILIARY RELAYS AS PER SPECIFICATION
SWITCHGEAR HEATER 230 VAC,1Ph INTERNAL
CONDUCTOR ( COPPER / ALUMINIUM ) COPPER
CONTACTOR COILS AS PER SPECIFICATION
AUXILIARY RELAYS FIXED
VOLTAGE SUPPLY 230VAC 10%
CONTROL SYSTEM
SECTION AS REQUIRED
EARTH BUS:
MAIN / SECTION
*** MATCHING MAXIMUM SWITCHGEAR GROUND
FAULT LEVEL(MINIMUM1/2 OF Ph CONDUCTOR)
VERTICAL BRANCH / SECTION ***
***
CONDUCTOR COPPER
BARE / INSULATED INSULATED
RATING AS REQUIRED
RATED SHORT-TIME WITHSTAND CURRENT 35kA/1s & As per SLD
RATED PEAK WITHSTAND CURRENT 87.5 kA (Peak) & As per SLD
RATING AS PER SLD DWG NO.3250-HGE-2-53-0001
RATED SHORT DURATION POWER FREQUENCY WITHSTAND VOLTAGE 2.5 Kv for 1 min
RATED IIGHTNING IMPULSE WITHSTAND VOLTAGE 12kV (Peak)
RATED CURRENT AS PER SLD DWG SEE NOTE 2
RATED OPERATIONAL VOLTAGE 400 V
RATED INSULATION VOLTAGE 1000 V
CONDUCTOR ( COPPER / ALUMINIUM ) COPPER
BARE / INSULATED INSULATED
MAIN BUSBAR:
SECTION
DISTRIBUTION BUSBARS:
Page 18 of 19
Date :22/07/2014
PROJECT Revision:0
CONCEPTUAL & DETAILED DESIGN FOR
RELOCATION OF FIRE TRAINING FACILITY AT
HALUL
CLIENT :
DATA SHEET FOR LV AC DB AND
MCC
Document Title:
Data sheets for all electrical equipment
Qatar Petroleum
9.3
9.4
9.5
9.6
9.7
10.0
10.1
10.2
10.3
10.4
10.5
11
11.1
11.2
11.3
12
12.1
12.2
12.3
13
13.1
13.2
14
14.1
15
15.1
15.2
NOTES: **** Supplier/Manufacturer to specify N/A - NOT APPLICABLE
NOTE 1:
NOTE 2:
NOTE 3:
NOTE 4:
NOTE 5:
HEAT LOAD SHALL BE PROVIDED DURING ENGINEERING.
ALL CT/VT RATIO, RATING & ACCURACY CLASS SHALL BE AS PER THE SLD.
FOR EQUIPMENT TAG NUMBER, RATINGS AREFER TO THE FOLLOWING SINGLE LINE DIAGRAMS .
HN29-2-53-0001 KEY SINGLE LINE DIAGRAM
HN29-2-69-0001-001 ELECTRICAL EQUIPMENT LIST &TAG NUMBERING LAYOUT
DESIGN AMBIENT AIR TEMPERATURE OF 50 DEGREE C SHALL BE CONSIDERED TO WITHSTAND THE HVAC FAILURE CONDITIONS.
TYPE TEST CERTIFICATES SHALL BE PROVIDED.
CURRENT TRANSFORMERS FOR MEASUREMENTS
RATIO / QTY AS PER SLD SEE NOTE 2
POWER & CLASS AS PER SLD SEE NOTE 2
CIRCUIT BREAKER (Y/N)
MCCB/MCB AS PER SLD
SEE NOTE 2
DISTRIBUTION OUTGOINGTECHNICAL CHARACTERISTICS
RATIO / QTY AS PER SLD
POWER & CLASS OF ACCURACY AS PER SLD
BREAKING DEVICE (CIRCUIT BREAKER / FUSES / SWITCH) MCCB
CURRENT TRANSFORMERS FOR MEASUREMENTS
INCOMING CUBICLE TECHNICAL CHARACTERISTICS
RATING / TYPE N/A
INCOMING TYPE
LENGTH / WIDTH / HEIGHT in mm. ***
TOTAL WEIGHT (kg) ***
NUMBER & SIZE OF PACKING UNIT ***
FUNCTIONAL UNIT LABELS (FRONT / REAR)
FUNCTIONAL LABEL-FRONT
CAUTIONARY LABEL -REAR
PAINTING SPECIFICATION QP SPEC. QP-SPC-L-002
COLOUR RAL 7032
SWITCHGEAR ARRANGEMENT
PADLOCKING FACILITIES REQUIRED
LANGUAGE ENGLISH
MAIN LABEL (FRONT / REAR) FRONT AND REAR
LABELS
FUTURE EXTENSION SIDE ( RIGHT / LEFT / BOTH ) BOTH
DOOR LOCKING REQUIRED
HANDLING TRUCK (Y/N) YES
SET OF SAFETY DEVICES (Y/N) REQUIRED
Page 19 of 19