UPS

12-1029

Valve Regulated Lead Acid Battery


Designed for UPS Standby Power Applications.

FEATURES & bENEFITS

APPLICATIONS

10 year design life @ 25C

Data Centers
Network Operations Centers
Industrial Process Control Facilities
Internet Housing Sites
Semiconductor Manufacturing
Banks & Financial Markets
Power Generation Plants

Absorbent Glass Mat (AGM) technology


for efficient gas recombination of up
to 99% and freedom from electrolyte
maintenance.

Proprietary Fixed Orifice Plate Pasting


technology applying active materials
on both sides of the grid for consistent
cell-to-cell performance, higher
capacity and uniform grid protection.

3 Year Warranty (refer Dynasty warranty


card, 41-9027)

Thermally welded case-to-cover bond to


eliminate leakage.

Patented Long Life Alloy having the


lowest calcium levels in the industry minimizing grid growth, reducing gassing,
and extending battery life.

Can be operated in any orientation.


Upright, side or end mounting
recommended.
Not restricted for air transport - Complies
with IATA/ICAO Special Provisions A67.

Patented UL Recognized Flamearresting vents in each cell for safety and


long life.

Hospitals & Testing Laboratories


Emergency 911 Response Centers

Designed with the same recombination,


thermal runaway prevention, gassing and
flame retardant characteristics of the
Bellcore 4228 compliant Dynasty Telecom
products.

Not restricted for surface transport Classified as non-hazardous material


as related to DOT-CFR Title 49 parts
171-189.
Not restricted for water transport Classified as non-hazardous material per
IMDG Amendment 27.

Flame retardant polypropylene case and


cover compliant with UL94-V2

TECHNICAL DATA

Constant Power Discharge Ratings - Watts per Cell @ 77F (25F)


Operating Time (in minutes) to 1.67 Volts per Cell

Weight

Voltage
12

AH
20 hr*
26.0

5
172

10
117

15
90.9

20
75.4

30
57.2

40
46.5

50
39.3

60
34.1

90
24.6

lbs
21.0

kg
10.0

UPS12-300MR
UPS12-350MR

12
12
12
12

34.6
53.8
78.6
93.2

290
373
546
619

193
261
385
440

148
206
300
350

120
169
245
289

88.9
127
183
216

71.1
102
147
173

59.4
85.1
123
144

51.1
73.3
106
123

36.1
51.9
75.0
85.9

27.3
40.0
58.4
67.4

12.4
18.0
26.5
30.5

UPS12-400MR

12

103

716

506

400

328

244

195

162

139

97.2

75.8

34.4

UPS12-490MRLP

12

115

772

607

488

402

300

240

201

173

122

83.0

38.0

UPS12-490MR

12

141

771

593

488

411

317

258

218

189

135

100.0

45.0

UPS12-540MR

12

149

875

657

537

451

343

277

231

198

139

100.0

45.0

UPS6-620MR

199

938

747

620

530

410

335

283

245

174

72.0

33.0

Model
UPS12-100MR
UPS12-150MR
UPS12-210MR

* Nominal 20 hr rate to 1.75 VPC in Ampere-Hours.

UPS
SPECIFICATIONS
Operating Temperature Range
with temperature compensation

Discharge: -40F (-40C) to +160F (71C)


Charge: -10F (-23C) to +140F (60C)

Nominal Operating Temperature Range

+74F (23C) to +80F (27C)

Recommended Maximum Charging


Current Limit

C/5 amperes @ 20hr rate

Float Charging Voltage

13.65 0.15 VDC average per 12V unit (6.75 to 6.90 per 6V unit)

Maximum AC Ripple (Charger)

0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20

Self Discharge

Battery can be stored up to 6 months at 77F (25C) before a freshening charge is


required. Batteries stored at temperatures greater than 77F (25C) will require
recharge sooner than batteries stored at lower temperatures. See C&D brochure
41-7272, Self-Discharge and Inventory Control for details.

Equalize charge and


cycle service voltage

14.40 to 14.80 VDC average per 12V unit @ 77F (25C) (7.20 to 7.40 VDC per 6V unit.)

Terminal: Flag

0.22 in. clearance hole to accept 0.1875 in. or 10-32 bolt (UPS12-100MR)

Terminal: Inserted

Threaded copper alloy insert terminal to accept


10-32 UNF bolt (UPS12-150MR, UPS12-210MR)
1
4-20 UNC bolt (UPS12-300MR, UPS12-350MR, UPS12-400MR, UPS12-490MRLP, UPS12-490MR,
UPS12-540MR, UPS6-620MR)

Terminal Hardware Annual Retorque

32 in.-lbs (3.48 N-m) (UPS12-100MR)

Terminal Hardware Initial Torque:


Inserted Terminal

40 in.-lbs. (4.5 N-m) (UPS12-100MR)


30 in.-lbs. (3.4 N-m) (UPS12-150MR, UPS12-210MR)
110 in.-lbs. (12.4 N-m) (UPS12-300MR, UPS12-350MR, UPS12-400MR, UPS12-490MRLP, UPS12-490MR,
UPS12-540MR, UPS6-620MR)

DIMENSIONS
Battery Termination
UPS12-100MR

UPS12-150MR

1.33
33.88

0.75
19.0

UPS 12-300MR

5.07
6.37
(128.8) (161.7)

6.86
(174.3)

UPS12-150MR

7.76
(197.1)

7.54
(191.4)

5.19
(131.9)

5.02
6.52
(127.6) (165.7)

6.80
(172.7)

UPS12-210MR

9.0
(228.6)

8.86
(225.1)

5.48
(139.2)

5.31
7.89
(134.8) (200.3)

8.07
(205.1)

UPS12-300MR

10.27
(260.9)

10.17
(258.4)

6.83
(173.4)

6.65
7.89
(168.9) (200.3)

8.01
(203.5)

UPS12-350MR

12.04
(305.8)

11.95
(303.5)

6.83
(173.4)

6.65
7.94
(168.9) (201.6)

8.06
(204.8)

13.42
UPS12-490MRLP (340.9)

12.75
(323.7)

6.80
(172.7)

6.54
8.40
(166.0) (213.2)

8.52
(216.4)

UPS12-490MR
UPS12-540MR

13.57
(344.7)

12.74
(323.6)

6.80
(172.7)

6.63
10.81
(168.4) (274.5)

10.93
(277.7)

UPS6-620MR

12.63
(320.8)

12.51
(317.8)

6.97
(177.0)

6.83
8.82
(173.4) (224.0)

8.94
(227.2)

1.13
28.70

1/4-20 UNC

1.22
31.10

1/4-20 UNC

0.67
17.1

1.33
33.7
0.13
3.2

UPS6-620MR

3.50
89.0

1/4-20 UNC

1.22
31.10
0.13
3.18

5.17
(131.3)

UPS12-490MR/UPS12-540MR

0.13
3.18

6.45
(163.7)

0.98
24.9

0.19
4.7

0.19
4.7

6.54
(166.2)

UPS12-400MR/UPS12-490MRLP

1.31
33.32

UPS12-100MR

UPS12-350MR

0.13
3.18

1.33
33.68

0.13
3.18

0.87
22.2

0.50
12.62

1/4-20 UNC

0.18
4.67

#10-32 UNF

1.73
44.04

0.64
16.18

#10-32 UNF

1.31
33.32

0.66
16.6

0.25
6.42

0.2
5.5 2
6

0.50
12.70

UPS12-400MR

UPS12-210MR

*All dimensions in inches (mm). All dimensions are for reference only. Contact a C&D Representative for complete dimension information.
NOTE: Batteries to be mounted with 0.5 in (1.25 cm) spacing minimum and free air ventilation.

1/4-20 UNC

UPS
SPECIFICATIONS
Model

Cells per
Unit

Maximum Discharge
Current (AMPS)

Short Circuit Current


(AMPS @ 0.1 sec)

Ohms Impedance
60 Hz ()

UPS12-100MR
UPS12-150MR
UPS12-210MR
UPS12-300MR
UPS12-350MR

6
6
6
6
6

500
500
600
800
800

1750
2500
3000
3600
4200

0.0060
0.0060
0.0045
0.0040
0.0030

UPS12-400MR
UPS12-490MRLP
UPS12-490MR
UPS12-540MR
UPS6-620MR

6
6
6
6
3

800
800
800
800
800

5100
6000
5000
5000
4350

0.0025
0.0022
0.0023
0.0023
0.0012

Additional product details available on the C&D Battery Sizing Program at www.cdstandbypower.net. Cabinet systems also available.

UPS12-100MR
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60

5
157
168
172
174
179

10
114
115
117
118
119

15
87.5
89.6
90.9
91.5
92.5

20
72.1
74.4
75.4
75.9
76.8

30
54.9
56.5
57.2
57.6
58.3

40
45.0
46.0
46.5
46.9
47.4

45
41.5
42.1
42.6
42.9
43.4

50
38.5
38.9
39.3
39.7
40.1

60
33.7
33.8
34.1
34.5
34.8

90
24.0
24.4
24.6
24.8
25.0

Constant Current Discharge Ratings - Amperes @ 77F (25C)


Operating Time to End Point Voltage (in hours)
End Point
Volts/Cell
1.90
1.85
1.80
1.75

.083
50.8
63.2
71.8
85.5

.25
32.9
38.1
41.6
45.7

.5
22.5
25.3
27.5
28.7

.75
17.1
18.6
20.3
21.4

1
13.8
15.0
16.1
17.0

2
8.29
8.99
9.42
9.74

3
6.04
6.56
6.83
6.99

5
3.95
4.30
4.46
4.54

8
2.61
2.84
2.95
3.00

10
2.15
2.33
2.42
2.45

12
1.82
1.98
2.05
2.08

20
1.14
1.24
1.28
1.30

24
0.96
1.05
1.08
1.10

72
0.34
0.37
0.38
0.39

100
0.24
0.26
0.27
0.28

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.

UPS12-150MR
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60

5
273
284
290
294
297

10
182
188
193
196
200

15
140
144
148
149
152

20
115
117
120
122
124

30
85.7
87.1
88.9
90.0
91.0

40
68.8
69.8
71.1
71.8
72.5

45
62.7
63.6
64.7
65.3
65.9

50
57.6
58.4
59.4
60.0
60.5

60
49.7
50.3
51.1
51.5
51.9

90
35.0
35.7
36.1
36.4
36.6

20
1.64
1.69
1.73

24
1.38
1.41
1.45

72
0.47
0.48
0.49

Constant Current Discharge Ratings - Amperes @ 77F (25C)


Operating Time to End Point Voltage (in hours)
End Point
Volts/Cell
1.85
1.80
1.75

1
22.8
24.2
25.4

2
13.0
13.6
14.1

3
9.08
9.46
9.80

5
5.70
5.91
6.11

8
3.76
3.90
4.00

10
3.10
3.21
3.28

12
2.64
2.72
2.79

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.

UPS
UPS12-210MR
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60

5
341
366
373
378
391

10
243
253
261
262
265

15
193
200
206
205
207

20
162
166
169
170
172

30
123
125
127
128
129

40
99.0
100
102
102
103

45
90.3
91.1
92.6
93.3
94.0

50
83.0
83.6
85.1
85.7
86.3

60
71.5
71.8
73.3
73.8
74.2

90
50.6
50.4
51.9
52.1
52.3

Constant Power Discharge Ratings - Amperes @ 77F (25C)


Operating Time to End Point Voltage (in hours)
End Point
Volts/Cell
1.85
1.80
1.75

1
32.6
34.8
36.7

2
19.1
20.3
21.1

3
13.6
14.4
14.9

5
8.68
9.20
9.43

8
5.79
6.12
6.25

10
4.72
5.00
5.05

12
4.01
4.24
4.28

20
2.51
2.65
2.69

24
2.12
2.23
2.27

72
0.73
0.76
0.77

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.

UPS12-300MR
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60

5
493
525
546
564
579

10
360
379
385
395
402

15
281
293
300
302
306

20
232
240
245
247
250

30
175
179
183
183
186

40
141
144
147
147
150

45
129
131
134
134
137

50
119
120
123
124
126

60
103
104
106
107
109

90
73.5
74.0
75.0
76.2
77.7

20
3.62
3.83
3.93

24
3.05
3.22
3.30

72
1.05
1.08
1.10

50
138
141
144
145
147

60
119
121
123
124
126

90
84.3
84.9
85.9
86.5
87.6

20
4.56
4.39
4.66

24
3.84
3.69
3.92

72
1.29
1.32
1.34

Constant Current Discharge Ratings - Amperes @ 77F (25C)


Operating Time to End Point Voltage (in hours)
End Point
Volts/Cell
1.85
1.80
1.75

1
48.3
51.1
52.7

2
28.1
29.3
30.1

3
19.9
20.7
21.2

5
12.6
13.1
13.4

8
8.36
8.84
9.16

10
6.82
7.23
7.46

12
5.79
6.13
6.32

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.

UPS12-350MR
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60

5
534
596
619
638
669

10
410
425
440
455
471

15
327
337
350
358
367

20
272
280
289
296
302

30
205
211
216
220
223

40
165
169
173
175
177

45
150
154
157
159
161

Constant Current Discharge Ratings - Amperes @ 77F (25C)


Operating Time to End Point Voltage (in hours)
End Point
Volts/Cell
1.85
1.80
1.75

1
53.0
58.8
62.6

2
31.8
34.5
36.3

3
22.9
24.6
25.8

5
14.8
15.7
16.4

8
10.6
10.1
11.0

10
8.73
8.35
8.98

12
7.38
7.09
7.57

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.

UPS
UPS12-400MR
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60

5
612
678
716
740
767

10
470
490
506
515
530

15
374
388
400
403
411

20
310
323
328
332
337

30
232
241
244
247
249

40
186
193
195
197
199

45
169
176
177
179
180

50
155
161
162
164
165

60
134
138
139
140
142

90
94.7
96.6
97.2
98.1
99.2

20
4.8
5.03
5.17

24
4.06
4.23
4.35

72
1.38
1.43
1.46

50
195
198
201
202
204

60
168
171
173
174
175

90
121
121
122
123
124

20
5.42
5.59
5.75

24
4.54
4.69
4.83

72
1.48
1.50
1.54

50
210
215
218
220
222

60
183
187
189
191
193

90
132
134
135
137
138

20
6.66
6.88
7.06

24
5.64
5.82
5.98

72
1.93
1.99
2.03

Constant Current Discharge Ratings - Amperes @ 77F (25C)


Operating Time to End Point Voltage (in hours)
End Point
Volts/Cell
1.85
1.80
1.75

1
56.2
62.1
67.9

2
33.7
36.5
39.2

3
24.4
26.1
27.8

5
15.7
16.7
17.6

8
10.8
11.4
11.9

10
8.85
9.38
9.73

12
7.56
8.00
8.26

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.

UPS12-490MRLP
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60

5
633
738
772
803
839

10
541
587
607
631
652

15
456
474
488
500
512

20
385
395
402
411
418

30
290
295
300
303
307

40
232
237
240
242
244

45
212
216
219
220
222

Constant Current Discharge Ratings - Amperes @ 77F (25C)


Operating Time to End Point Voltage (in hours)
End Point
Volts/Cell
1.85
1.80
1.75

1
77.5
82.7
86.1

2
44.2
46.3
47.9

3
31.1
32.4
33.4

5
19.7
20.5
21.1

8
12.9
13.3
13.7

10
10.5
10.8
11.1

12
8.81
9.09
9.36

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.

UPS12-490MR
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60

5
655
740
771
799
838

10
527
573
593
614
640

15
443
470
488
497
513

20
382
400
411
419
429

30
300
310
317
321
325

40
247
253
258
261
264

45
227
233
237
239
241

Constant Current Discharge Ratings - Amperes @ 77F (25C)


Operating Time to End Point Voltage (in hours)
End Point
Volts/Cell
1.85
1.80
1.75

1
80.8
86.4
91.0

2
48.4
51.3
53.5

3
34.8
36.7
38.2

5
22.4
23.4
24.4

8
15.0
15.6
16.2

10
12.3
12.7
13.1

12
10.5
10.8
11.1

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.

UPS
UPS12-540MR
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60

5
728
833
875
912
959

10
564
626
657
683
701

15
471
511
537
550
560

20
406
433
451
462
468

30
318
332
343
349
353

40
261
269
277
280
283

45
239
246
252
255
258

50
221
226
231
234
237

60
191
195
198
201
203

90
136
138
139
141
143

20
7.05
7.29
7.46

24
5.98
6.18
6.31

72
2.00
2.07
2.11

50
274
278
283
288
295

60
238
241
245
250
256

90
169
171
174
178
183

20
9.27
9.66
9.96

24
7.85
8.10
8.42

72
2.73
2.83
2.87

Constant Current Discharge Ratings - Amperes @ 77F (25C)


Operating Time to End Point Voltage (in hours)
End Point
Volts/Cell
1.85
1.80
1.75

1
82.7
89.6
98.9

2
49.5
53.1
57.0

3
35.6
38.1
40.3

5
22.9
24.4
25.5

8
15.0
15.9
16.5

10
12.6
13.2
13.6

12
10.9
11.3
11.7

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.

UPS6-620MR
Constant Power Discharge Ratings - Watts Per Cell @ 77F (25C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60

5
862
890
938
951
1000

10
681
718
747
763
794

15
573
602
620
634
655

20
497
517
530
542
557

30
392
403
410
419
429

40
323
330
335
342
349

45
297
302
307
313
320

Constant Current Discharge Ratings - Amperes @ 77F (25C)


Operating Time to End Point Voltage (in hours)
End Point
Volts/Cell
1.85
1.80
1.75

1
106
114
121

2
63.6
67.6
71.2

3
46.2
48.8
50.9

5
30.1
31.6
32.6

8
20.3
21.2
21.9

10
16.9
17.6
18.1

12
14.5
15.1
15.6

Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.

High Rate Max Part Number

Manufacturer Approved Premium Replacement for:

UPS12-100MR
UPS12-150MR
UPS12-210MR
UPS12-300MR
UPS12-350MR
UPS12-400MR
UPS12-490MRLP
UPS12-490MR
UPS12-540MR
UPS6-620MR

UPS12-100FR
UPS12-140FR & MR12-150
UPS12-170FR, UPS12-200FR & MR12-210
UPS12-270FR & MR12-300
UPS12-310FR & MR12-350
UPS12-370FR & MR12-400
UPS12-475FR, MR12-490 & UPS12-490MR (Low profile high rate applications)
UPS12-475FR & MR12-490 (Extended run applications)
UPS12-530FR & MR12-540
UPS6-620FR

1400 Union Meeting Road


P.O. Box 3053 Blue Bell, PA 19422-0858
(215) 619-2700 Fax (215) 619-7899 (800) 543-8630
customersvc@cdtechno.com
www.cdtechno.com

Any data, descriptions or specifications presented herein are subject to revision by C&D Technologies, Inc. without
notice. While such information is believed to be accurate as indicated herein, C&D Technologies, Inc. makes no
warranty and hereby disclaims all warranties, express or implied, with regard to the accuracy or completeness of
such information. Further, because the product(s) featured herein may be used under conditions beyond its control,
C&D Technologies, Inc. hereby disclaims all warranties, either express or implied, concerning the fitness or suitability of such product(s) for any particular use or in any specific application or arising from any course of
dealing or usage of trade. The user is solely responsible for determining the suitability of the product(s)
featured herein for users intended purpose and in users specific application.
Copyright 2010 C&D TECHNOLOGIES, INC.

Printed in U.S.A.