1.

BUILDING CODE - 2009IBC


2. DESIGN LOADS:
A. ROOF LIVE LOAD 20 PSF
B. ROOF SNOWLOAD
a. GROUNDSNOWLOAD, Pg 5.0PSF
b. FLAT ROOF SNOWLOAD, Pf 5.0PSF
c. SNOWEXPOSURE FACTOR, Ce 1.0
d. SNOWLOADIMPORTANCE FACTOR, I 1.0
e. THERMAL FACTOR, Ct, HEATEDSTRUCTURE 1.0
f. DRIFTING PER CODE
C. WINDLOADS
a. BASIC WINDSPEED(3SECONDGUST) 100MPH
b. WINDIMPORTANCE FACTOR, I 1.0
c. OCCUPANCY CATEGORY II
d. WINDEXPOSURE C
e. INTERNAL PRESSURE COEFFICIENT +/- 0.18
f. COMPONENT &CLADDING PRESSURE SEE TABLE 4/S002
D. SEISMIC LOADS
a. OCCUPANCY CATEGORY II
b. SPECTRAL ACCELERATION SITE SPECIFIC
c. SEISMIC IMPORTANCE FACTOR, I 1.0
d. SPECTRAL RESPONSE COEFFICIENTS
SDS .086g
SD1 .055g
e. SITE CLASS D
f. SEISMIC DESIGN CATEGORY A
g. BASIC SEISMIC-FORCE-RESISTING SYSTEM LIGHT FRAMEDWALLS SHEATHEDWITH
WOODSTRUCTURAL PANELS RATEDFOR SHEAR RESISTANCE
h. RESPONSE MODIFICATION FACTOR, R 6 1/2
i. SEISMIC RESPONSE COEFFICIENT, Cs 0.01
j. DESIGN BASE SHEAR 1,875#
k. ANALYSIS PROCEDURE EQUIVALENT LATERAL FORCE
E. DESIGN DEADLOAD
a. ROOF TRUSS TOP CHORD 10 PSF (1)
b. ROOF TRUSS BOTTOMCHORD 10 PSF (2)
c. UNDER HUNG DUCT WORK, LIGHTING ETC. 10 PSF
(1.) TRUSS MANUFACTURER SHALL ADDMECHANICAL ROOF TOP UNIT LOADS AS REQUIREDPER
PLAN.
(2.) ADD UNDER HUNG LOADS TO BOTTOMCHORDS AS REQUIRED. TRUSS MANUFACTURER SHALL
COORDINATE WITH ARCHITECTURAL REFLECTIVE CEILING PLANANDM.E.P. PLANS.
F. THE STRUCTURAL SYSTEMS SHOWN ON THESE DOCUMENTS HAVE BEEN DESIGNEDFOR THE FINAL, IN
PLACE USAGE OF THE STRUCTURE BASED ON THE INTENDEDOCCUPANCY ANDCODE REQUIREMENTS.
WHILE GENERAL CONSTRUCTABILITY HAS BEEN CONSIDERED, THE STRUCTURAL SYSTEMS HAVE NOT
BEEN DESIGNEDTO ACCOMMODATE SPECIFIC CONSTRUCTION MEANS ANDMETHODS THAT MIGHT BE
UTILIZEDBY THE CONTRACTOR.
1. SPECIAL INSPECTIONS
A. THE FOLLOWING ITEMS REQUIRE SPECIAL INSPECTION IN ACCORDANCE WITH THE BUILDING CODE.
a. REINFORCEDMASONRY CONSTRUCTION - LEVEL 1INSPECTION
b. CONCRETE &MASONRY GROUT DESIGN MIX
c. PLACING OF CONCRETE ANDREINFORCING STEEL
d. BOLTS &ANCHORS EMBEDDEDIN CONCRETE &MASONRY
e. STRUCTURAL STEEL FABRICATIONS
f. STRUCTURAL STEEL BOLTING &WELDING
g. INSPECTION OF ROOF DECK ATTACHMENT
h. IN-SITU STRUCTURAL FRAMING
i. POST INSTALLEDANCHORS IN MASONRY AND CONCRETE
j. WOODTRUSS FABRICATIONS
k. WOOD TRUSS ATTACHMENT
l. SHEAR WALL ATTACHMENTS ANDANCHORS
m. IN-SITU SOILS, EXCAVATIONS, FILLING &COMPACTION
B. THE CONTRACTOR SHALL REQUEST SPECIAL INSPECTION OF THE ITEMS LISTEDABOVE PRIOR TO
THOSE ITEMS BECOMING INACCESSIBLE ANDUNOBSERVABLE DUE TO PROGRESSIONOF THE WORK.
4. STRUCTURAL ENGINEER SITE OBSERVATIONS
A. THE CONTRACT STRUCTURAL DRAWINGS ANDSPECIFICATIONS REPRESENT THE FINISHEDSTRUCTURE,
AND, EXCEPT WHERE SPECIFICALLY SHOWN, DO NOT INDICATE THE METHODOR MEANS OF
CONSTRUCTION. THE CONTRACTOR SHALL SUPERVISE ANDDIRECT THE WORK ANDSHALL BE SOLELY
RESPONSIBLE FOR ALL CONSTRUCTION MEANS, METHODS, PROCEDURES, TECHNIQUES, AND
SEQUENCE.
B. THE ENGINEER SHALL NOT HAVE CONTROL NOR CHARGE OF, AND SHALL NOT BE RESPONSIBLE FOR,
CONSTRUCTION MEANS, METHODS, TECHNIQUES, SEQUENCES, OR PROCEDURES, FOR SAFETY
PRECAUTIONS ANDPROGRAMS IN CONNECTION WITH THE WORK, FOR THE ACTS OR OMISSION OF THE
CONTRACTOR, SUBCONTRACTOR, OR ANY OTHER PERSONS PERFORMING ANY OF THE WORK, OR FOR
THE FAILURE OF ANY OF THEMTO CARRY OUT THE WORK IN ACCORDANCE WITH THE CONTRACT
DOCUMENTS.
C. PERIODIC SITE OBSERVATION BY FIELDREPRESENTATIVES OF PMA ENGINEERING IS SOLELY FOR THE
PURPOSE OF DETERMINING IF THE WORK OF THE CONTRACTOR IS PROCEEDING INGENERAL
ACCORDANCE WITH THE STRUCTURAL CONTRACT DOCUMENTS. THIS LIMITEDSITE OBSERVATION
SHOULD NOT BE CONSTRUED AS EXHAUSTIVE OR CONTINUOUS TO CHECK THE QUALITY OR QUANTITY
OF THE WORK, BUT RATHER PERIODIC IN AN EFFORT TO GUARDTHE OWNER AGAINST DEFECTS OR
DEFICIENCIES IN THE WORK OF THE CONTRACTOR.
5. CONTRACTOR SHALL FIELDVERIFY ALL EXISTING DIMENSIONS PRIOR TO FABRICATION.
6. REFERENCE THE SPECIFICATION FOR ADDITIONAL REQUIREMENTS.
7. SEE ARCHITECTURAL, MECHANICAL, ANDELECTRICAL DRAWINGS FOR OTHER PERTINENT INFORMATION
RELATEDTO THE STRUCTURAL WORK ANDCOORDINATE AS REQUIRED. THESE STRUCTURAL DRAWINGS ARE
INTENDEDTO BE UTILIZEDAS A COMPLETE SET OF DOCUMENTS THAT REPRESENT THE BUILDINGS
STRUCTURAL SYSTEMS. NO SINGLE SHEET OR SERIES OF SHEETS IS INTENDEDTO STANDALONE. TYPICAL
DETAILS ARE NOT CUT AT SPECIFIC LOCATIONS THROUGHOUT THE DRAWINGS, BUT ARE TO BE APPLIED
WHERE REQUIRED. THESE STRUCTURAL DRAWINGS ARE INTENDEDTO BE INCLUDEDIN A COMPLETE SET OF
CONSTRUCTION DOCUMENTS, INCLUDING BUT NOT LIMITEDTO: ARCHITECTURAL DRAWINGS, CIVIL
DRAWINGS, ANDMECHANICAL/ ELECTRICAL/ PLUMBING DRAWINGS. CONTRACTOR SHALL VERIFY
COORDINATION OF THESE DRAWINGS WITH CONTENTS OF ABOVE DRAWING SETS SPECIFIEDANDONLY
PROCEEDWITH BIDDING ANDCONSTRUCTION AFTER SUCH HAS TAKEN PLACE.
8. THE BUILDING IS NOT STRUCTURALLY STABLE UNTIL ALL CONNECTIONS, FRAMING, SHEAR WALLS,
DIAPHRAGMS, PERMANENT BRACING, METAL DECKING, ANDEXTERIOR LOAD-BEARING WALLS ARE COMPLETE
ANDHAVE ACHIEVEDTHEIR DESIGN STRENGTH. CONTRACTOR IS SOLELY RESPONSIBLE FOR MAINTAINING
STRUCTURAL STABILITY DURING ERECTION ANDCONSTRUCTION. TEMPORARY BRACING SYSTEMS ARE NOT
TO BE REMOVEDUNTIL STRUCTURAL WORK IS COMPLETE.
9. REINFORCING STEEL:
A. ALL REINFORCING STEEL SHALL BE ASTMA615GRADE 60, EXCEPT WELDEDREINFORCING WHICH SHALL
BE ASTMA706GRADE 60.
B. ALL WELDEDWIRE FABRIC SHALL BE ASTMA185ANDA82COLDDRAWNWIRE.
C. ALL ACCESSORIES FOR SUPPORTING REINFORCING SHALL BE GALVANIZEDOR HAVE PLASTIC-COATED
FEET.
D. PROVIDE CORNER BARS AT THE EXTERIOR FACE OF ALL WALL ANDFOOTING CORNERS EQUAL TO
HORIZONTAL BARS.
E. PROVIDE AT LEAST TWO VERTICAL #5BARS AT ALL STEPS IN FOUNDATION WALLS, FOOTINGS, AND
GRADE BEAMS.
F. REINFORCING SHALL BE DETAILED, FABRICATED, PLACED, ANDSUPPORTEDINACCORDANCE WITH ACI
315, LATEST EDITION.
G. THE FOLLOWING ADDITIONAL REINFORCING STEEL SHALL BE PROVIDEDIN STOCK LENGTHS FOR
GENERAL J OB USE AS DIRECTEDBY THE ENGINEER.
5 - #4X30-0 5 - #5X30-0
H. STANDARDCOVERAGE OF REINFORCING, UNLESS OTHERWISE SHOWN, SHALL BE AS FOLLOWS:
CAST AGAINST EARTH, PERMANENTLY EXPOSEDTO WEATHER 3"
EXPOSEDTO EARTH &WEATHER (FORMED) 2"
NOT EXPOSEDTO EARTH OR WEATHER: SLABS, WALLS 3/4"
I. ALL LAP SPLICES SHALL BE CLASS B UNLESS NOTEDOTHERWISE.
J . FOR REINFORCING BAR LAP LENGTHS IN CONCRETE, SEE TABLE 3/S002.
10. CONCRETE:
A. CAST-IN-PLACE CONCRETE CONSTRUCTION SHALL CONFORMTO THE LATEST AMERICANCONCRETE
INSTITUTE DOCUMENTS, ACI-301, 305, 306, 315, 318AND347UNLESS OTHERWISE NOTEDIN THESE
CONTRACT DOCUMENTS.
B. ALL CONCRETE, UNLESS OTHERWISE NOTED, SHALL DEVELOP A 28DAY COMPRESSIVE STRENGTH OF
4,000PSI ANDHAVE MAXIMUMWATER/CEMENT RATIO OF 0.53.
C. CONCRETE EXPOSEDTO WEATHER, VEHICLES AND/OR DEICING CHEMICALS SHALL BE AIR-ENTRAINED
WITH 6%(+/-) 1.5%ENTRAINED AIR BY VOLUME AT POINT OF DISCHARGE. DO NOT ALLOWAIR CONTENT
OF TROWELEDFINISHEDFLOORS TO EXCEED3%.
D. ALL CONCRETE SHALL BE PROPORTIONEDFOR A MAXIMUMALLOWABLE UNIT SHRINKAGE OF 0.055%
MEASUREDAT 28DAYS AFTER CURING IN LIME WATER AS DETERMINEDBY ASTMC 157(USING AIR
STORAGE).
E. THE CONCRETE SLAB-ON-GRADE HAS BEEN DESIGNEDFOR ITS FINAL USE ANDNOT FOR
CONSTRUCTION CONSIDERATIONS. CONTRACTOR SHALL COORDINATE THE SLAB DESIGN WITH
CONSTRUCTION NEEDS. THE SLAB DESIGN INDICATEDON THESE DRAWINGS IS TO BE CONSIDEREDA
MINIMUM. SUBMIT CHANGES TO THE SLAB DESIGN TO THE ENGINEER OF RECORDFOR REVIEW.
F. IT IS THE INTENT OF THESE CONCRETE SPECIFICATIONS THAT THE CONTRACTOR SUPPLY CONCRETE
MIXES WITH A MINIMUMAMOUNT OF WATER IN ORDER TO LIMIT PLASTIC SHRINKAGE CRACKING IN
FRESHLY PLACEDCONCRETE. IT IS EXPECTEDTHAT PRODUCING WORKABILITY FOR CONCRETE MIXES
WILL REQUIRE THE ADDITION OF WATER-REDUCING AND/OR SUPER-PLASTICIZING CHEMICAL
ADMIXTURES.
G. CONCRETE SLUMP SHALL BE A MAXIMUMOF 4" +/- 1" (ASTMC-143) AS DELIVEREDIN THE FIELD.
CONTRACTOR MAY USE CHEMICAL ADMIXTURES TO ATTAIN A MAXIMUMSLUMP OF 8" FOR WORKABILITY.
H. NO WATER MAY BE ADDEDTO THE CONCRETE MIX ON SITE UNLESS WATER IS WITHHELDAT THE
BATCHING FACILITY. IF WATER IS WITHHELDAT THE BATCHING FACILITY IT SHOULD BE REFLECTEDON
THE LOAD TICKET. THE TOTAL AMOUNT OF WATER IN THE MIX SHALL NOT EXCEEDWHAT IS NOTEDON
THE APPROVEDMIX. THIS SHALL BE NOTEDIN THE SPECIAL INSPECTOR'S RECORDS.
I. FLY ASH MAY BE USEDAT A RATE NOT TO EXCEED25%OF THE TOTAL CEMENT CONTENT.
J . CHAMFER ALL EXPOSEDCORNERS OF CONCRETE WALLS, BEAMS, ANDCOLUMNS 3/4".
K. ALL CONTROL J OINTS IN CONCRETE SLABS-ON-GRADE SHALL BE CUT TO 1/4OF THE DEPTH. CUT
J OINTS AS SOON AS POSSIBLE AFTER CONCRETE HAS BEEN PLACEDWITHOUT DISLODGING
AGGREGATE, OR USE KEYEDCOLDJ OINT.
L. CONTROL J OINTS SHALL BE PLACEDSO THAT NO AREA BETWEEN J OINTS EXCEEDS 150SQUARE FEET.
M. PRIOR TO PLACING CONCRETE IN ANY LOCATION, IT IS THE RESPONSIBILITY OF THE GENERAL
CONTRACTOR TO HAVE THOROUGHLY CHECKEDANDCOORDINATEDALL DIMENSIONS, ELEVATIONS,
OPENINGS, RECESSES, ANDBLOCKOUTS SHOWN ON THE ARCHITECTURAL, STRUCTURAL, AND
MECHANICAL DRAWINGS. IN THE EVENT ERRORS, CONFLICTS, OR OMISSIONS EXIST, IT SHALL BE THE
CONTRACTOR'S RESPONSIBILITY TO CONTACT THE ARCHITECT OR ENGINEER FOR NECESSARY
CORRECTIVE ACTION.
N. EMBEDDEDITEMS ARE TO BE FURNISHEDANDINSTALLEDBY THE CONTRACTOR PRIOR TO PLACING
CONCRETE.
O. ANCHOR RODS SHALL BE HELD IN PLACE WITH A RIGIDTEMPLATE.
11. MASONRY
A. SPECIAL INSPECTION OF ALL REINFORCEDMASONRY IS REQUIRED.
B. ALL MASONRY WALLS SHALL BE RUNNING BONDUNLESS SPECIFICALLY NOTEDOTHERWISE ONTHE
STRUCTURAL DRAWINGS.
C. REINFORCEDMASONRY SHALL HAVE A MINIMUMCOMPRESSIVE STRENGTH, F'mOF 1500PSI.
CONCRETE MASONRY UNITS SHALL CONFORMTO ASTMC 90, AND HAVE A NET AREA COMPRESSIVE
STRENGTH OF 1900 PSI.
D. MORTAR SHALL BE TYPE S FOR ABOVE GRADE APPLICATIONS ANDTYPE MFOR BELOWGRADE
APPLICATIONS.
E. GROUT SHALL HAVE A MINIMUM28DAY COMPRESSIVE STRENGTH OF 2000PSI.
F. REINFORCING STEEL SHALL BE GRADE 60ANDCONFORMTO ASTMA 615.
G. MAXIMUMHEIGHT OF GROUT POUR SHALL NOT EXCEED4'-8".
H. VERTICAL CELLS TO BE GROUTEDSHALL HAVE VERTICAL ALIGNMENT SUFFICIENT TO MAINTAIN A TOTAL
MINIMUMCLEAR AREA OF 3" X 3". ALL OVERHANGING MORTAR, OBSTRUCTIONS ANDDEBRIS SHALL BE
CLEANEDFROMTHE INSIDE OF CELLS PRIOR TO GROUTING.
I. REINFORCEMENT SHALL BE PLACED PRIOR TO GROUTING.
J . UNITS SHALL BE PLACEDTO THE FULL HEIGHT OF THE GROUT POUR ANDGROUT SHALL BE PLACEDINA
CONTINUOUS LIFT. BETWEEN GROUT POURS, A HORIZONTAL CONSTRUCTION J OINT SHALL BE FORMED
BY STOPPING GROUT 11/2INCHES BELOWA MORTAR J OINT EXCEPT AT THE TOP OF THE WALL.
K. ALL CONCRETE MASONRY WALLS SHALL BE REINFORCEDWITH HORIZONTAL J OINT REINFORCING WITH
#9GAGE (W1.7) SIDE RODS AND#9GAGE (W1.7) CROSS RODS, GALVANIZEDREINFORCING @16" O.C.
VERTICALLY. PROVIDE TRUSS TYPE FOR SINGLE WYTHE CMU WALLS WITH (2) SIDE RODS. PROVIDE
LADDER TYPE FOR TWO WYTHE WALLS WITH (3) SIDE RODS ANDA CAVITY DRIP.
L. ALL CMU WALLS SHALL BE REINFORCEDVERTICALLY AS SPECIFIEDON DRAWINGS WITHTHE SPECIFIED
BAR FOR THAT WALL AT THE ENDS OF WALLS, AT EACH SIDE OF CONTROL OR EXPANSIONJ OINTS, AND
AT EACH SIDE OF EACH OPENING, ALL IN FULLY GROUTEDCELLS. IF REINFORCING IS NOT SHOWN ON
THE DRAWINGS, REINFORCE WITH #5BARS AT 4'-0" ON CENTER.
M. GROUT SOLIDALL REINFORCEDCELLS, CELLS BELOWGRADE, ANDALL CELLS BELOWFINISH FLOOR.
N. PROVIDE BOND BEAMS AT THE BOTTOMANDTOP OF EACH WALL, ABOVE ANDBELOWOPENINGS, AND
WHERE SHOWN. BONDBEAMS SHALL HAVE 2-#5CONTINUOUS ANDBE FULLY GROUTED. VERTICAL
BARS SHALL EXTENDINTO THE BONDBEAM.
O. EXTENDVERTICAL REINFORCING THROUGH BONDBEAMS UNLESS SPECIFICALLY NOTEDOTHERWISE.
P. PROVIDE DOWELS INTO FLOOR OR FOUNDATION AT BOTTOMOF WALL TO MATCH SIZE ANDSPACING OF
VERTICAL WALL REINFORCING. (UNLESS NOTEDOTHERWISE ON DRAWINGS)
Q. STABILIZE TOP OF ALL VERTICALLY REINFORCEDWALLS PER DRAWING DETAILS.
R. MINIMUMLAP LENGTHS REQUIRED(UNLESS NOTEDOTHERWISE):
#4BARS 2'-0" #5BARS 2'-6" #6BARS 3'-0"
#7BARS 3'-6" #8BARS 4'-0" #9 BARS 4'-6
12. STRUCTURAL STEEL:
A. ALL STRUCTURAL STEEL SHALL BE DETAILED, FABRICATED, ANDERECTED IN ACCORDANCE WITH AISC
SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS ALLOWABLE STRESS DESIGNANDPLASTIC DESIGN,
LATEST EDITION ANDAISC CODE OF STANDARDPRACTICE.
B. ALL STRUCTURAL STEEL FOR WIDE FLANGE &WT SHAPES SHALL BE A992 GRADE 50UNLESS NOTED
OTHERWISE ON THE PLANS. ALL ANGLES, PLATES, AND CHANNELS ANDSHALL BE ASTMA36UNLESS
NOTEDOTHERWISE. ALL RECTANGULAR ANDROUND HSS SHAPES SHALL BE ASTMA500, GRADE B.
C. THE CONTRACTOR SHALL PROVIDE SHELF ANGLES, GLASS SUPPORTS, LINTELS ANDOTHER
MISCELLANEOUS STEEL, AS SHOWN ON THE DRAWINGS ANDAS REQUIREDTOPROVIDE SUPPORT
(STABILIZATION) AROUNDANDTHROUGHOUT THE BUILDING. NOT EVERY DETAIL IS SHOWN. SEE
ARCHITECTURAL ANDELEVATOR DRAWINGS FOR ADDITIONAL MISCELLANEOUS STEEL DETAILS.
D. ALL BRICK LEDGER ANGLES ANDLINTEL BEAMS WITHIN EXTERIOR WALLS SHALL BE HOT DIPPED
GALVANIZEDIN ACCORDANCE WITH ASTMA123.
E. BEAMCONNECTIONS SHALL BE FOR SIMPLY SUPPORTEDBEAMS ANDSHALL BE DESIGNEDBY STEEL
FABRICATOR FOR LOADS SHOWN ON DRAWINGS U.N.O. LOADS ANDREACTIONS SHOWN ON THESES
DOCUMENTS ARE NON-FACTORED, WORKING STRESS VALUES.
F. ALL BOLTS SHALL BE 3/4" DIAMETER A-325BOLTS WITH HEAVY HEX HEADS, U.N.O. ON DRAWINGS. ALL
CONNECTIONS SHALL HAVE A MINIMUMOF TWO 3/4" DIAMETER BOLTS, SHUG-TIGHTENTYPE
CONNECTIONS U.N.O. IN THE DOCUMENTS.
G. SHOP WELD ANDFIELD BOLTEDCONNECTIONS ARE PREFERRED, U.N.O.
H. FILLET WELDS NOT SPECIFICALLY SIZEDIN THESE DOCUMENTS SHALL BE THE MINIMUMSIZE IN
ACCORDANCE WITH AWS D1.1LATEST EDITION, DEPENDENT ON THE THINNER PART J OINED, BUT NOT
LESS THAN3/16".
I. ALL STRUCTURAL STEEL WELDS IN THE SHOP OR THE FIELD SHALL BE PERFORMEDBY A QUALIFIED
WELDER ANDSHALL CONFORMTO THE CURRENT REQUIREMENTS OF A.W.S.
J . WELDING ELECTRODES SHALL BE E70XX.
13. POST INSTALLED ANCHORS:
A. THE CONTRACTOR SHALL SUBMIT PRODUCT SPECIFICATIONS WITH RECOMMENDEDDESIGNVALUES
ANDPHYSICAL CHARACTERISTICS FOR EPOXY DOWELS, EXPANSION AND UNDERCUT ANCHORS.
B. THE CONTRACTOR SHALL SUBMIT CERTIFIEDTEST REPORTS (ICC ES EVALUATIONREPORT) SHOWING
COMPLIANCE WITH SPECIFIED PERFORMANCE CHARACTERISTICS ANDPHYSICAL PROPERTIES.
C. EMBEDMENT DEPTH SHALL BE DEFINEDAS THE DISTANCE FROMTHE SURFACE OF THE LOAD-BEARING
BASE MATERIAL TO THE DEEPEST PART OF THE ANCHOR AFTER THE ANCHOR HAS BEENDRIVENINTO
THE HOLE BUT NOT YET EXPANDED.
D. ADHESIVE ANCHORS SHALL BE ACCEPTABLE FOR LONG-TERMLOADING. ONLY NON-EPOXY BASED
ADHESIVES SHALL BE USEDWHEN BASE MATERIAL TEMPERATURES ARE BELOW40DEG F.
E. POST INSTALLEDANCHORS SHALL ONLY BE USEDWHERE SPECIFIEDON THE DRAWINGS. THE
CONTRACTOR SHALL OBTAIN APPROVAL FROMTHE ENGINEER PRIOR TO USING POST INSTALLED
ANCHORS FOR MISSING OR MISPLACEDCAST-IN-PLACE ANCHORS. CARE SHALL BE TAKEN TO AVOID
CONFLICTS WITH EXISTING REINFORCING BARS.
F. ALL POST INSTALLEDANCHORS HOLES SHALL BE DRILLEDANDCLEANEDPER ANCHOR
MANUFACTURER'S SPECIFICATIONS AS SHOWN IN THE CORRESPONDING ICC-ESR REPORT.
G. SUBMITTALS ARE THE CONTRACTOR'S RESPONSIBILITY ANDMUST INCLUDE EVALUATIONREPORTS
FROMTHE INTERNATIONAL CODE COUNCIL.
H. STAINLESS STEEL ANCHORS ARE REQUIREDAT ALL EXPOSEDLOCATIONS.
I. FOR PRODUCTS OTHER THAN THOSE SPECIFIEDBELOW, CONTRACTOR SHALL SUBMIT VALUES OF THE
SUBSTITUTEDPRODUCT THAT IS CAPABLE OF ACHIEVING EQUIVALENT PERFORMANCE VALUES
(MINIMUM) OF THE SPECIFIED PRODUCT USING THE APPROPRIATE DESIGNPROCEDURE AND/OR
STANDARD(S) AS REQUIREDBY THE BUILDING CODE.
J . CONCRETE ANCHORS
a. MECHANICAL ANCHORS FOR USE IN CRACKED ANDUNCRACKED CONCRETE SHALL HAVE BEEN
TESTEDANDQUALIFIEDFOR USE IN ACCORDANCE WITH ACI 355.2ANDICC-ES AC193.
PRE-APPROVED MECHANICAL ANCHORS INCLUDE:
1 SIMPSON STRONG-TIE STRONG-BOLT 2(ICC-ES ESR-3037)
2 SIMPSON STRONG-TIE TITEN-HD(ICC-ES ESR-2713)
3 HILTI KWIK BOLT TZEXPANSION ANCHOR (ICC-ES ESR 1917)
4 HILTI HSL-3HEAVY DUTY EXPANSION ANCHOR (ICC-ES ESR 1545)
5 HILTI HDA UNDERCUT ANCHOR (ICC-ES ESR 1546)
6 HILTI KWIK HUS EZANCHOR (ICC-ES ESR 3027)
b. ADHESIVE ANCHORS FOR USE IN CRACKEDANDUNCRACKED CONCRETE SHALL HAVE BEEN
TESTEDANDQUALIFIEDFOR USE IN ACCORDANCE WITH ACI 355.4ANDICC-ES AC308.
PRE-APPROVED ADHESIVE ANCHORS INCLUDE:
1 SIMPSON STRONG-TIE SET-XP(ICC-ES ESR-2508)
2 HILTI HIT-HY 150 MAX-SD (ICC-ES ESR 1967)
3 HILTI HIT-RE 500-SD (ICC-ES ESR 2322)
K. MASONRY ANCHORS
a. ANCHORAGE TO SOLID-GROUTEDCONCRETE MASONRY
1 MECHANICAL ANDCONCRETE SCREWANCHORS FOR USE IN SOLID-GROUTEDCONCRETE
MASONRY SHALL HAVE BEEN TESTEDANDQUALIFIEDFOR USE IN ACCORDANCE WITH
ICC-ES AC01OR ICC-ES AC106. PRE-APPROVEDMECHANICAL ANDCONCRETE SCREW
ANCHORS INCLUDE:
SIMPSON STRONG-TIE WEDGE-ALL(ICC-ES ESR-1396)
SIMPSON STRONG-TIE TITEN-HD(ICC-ES ESR-1056)
HILTI KWIK HUS EZANCHOR (ICC-ES ESR 3027)
HILTI KWIK HUS ANCHOR (ICC-ES ESR PENDING)
HILTI KWIK BOLT 3 ANCHOR (ICC-ES ESR 1385)
2 ADHESIVE ANCHORS FOR USE IN SOLID-GROUTEDCONCRETE MASONRY SHALL HAVE BEEN
TESTEDANDQUALIFIEDFOR USE IN ACCORDANCE WITH ICC-ES AC58. PRE-APPROVED
ADHESIVE ANCHORS INCLUDE:
SIMPSON STRONG-TIE SET(ICC-ES ESR-1772)
HILTI KWIK HUS EZANCHOR (ICC-ES ESR 3027)
HILTI KWIK HUS ANCHOR (ICC-ES ESR PENDING)
b. ANCHORAGE TO HOLLOWCONCRETE MASONRY/UNREINFORCEDCLAY BRICK MASONRY
1 SCREWANCHORS FOR USE IN HOLLOWCONCRETE MASONRY SHALL HAVE BEEN TESTED
ANDQUALIFIEDIN ACCORDANCE WITH ICC-ES AC106. PRE-APPROVEDSCREWANCHORS
INCLUDE:
SIMPSON STRONG-TIE TITEN-HD(ICC-ES ESR-1056)
2 ADHESIVE ANCHORS WITH SCREEN TUBES SHALL BE TESTEDANDQUALFIEDIN
ACCORDANCE WITH ICC-ES AC58OR AC60, AS APPROPRIATE. THE APPROPRIATE SCREEN
TUBE SHALL BE USEDAS RECOMMENDEDBY THE ADHESIVE MANUFACTURER.
PRE-APPROVED ADHESIVE ANCHORS WITH SCREEN TUBES INCLUDE:
SIMPSON STRONG-TIE SET(ICC-ES ESR-1772)
HILTI HIT-HY20 ANCHOR (ICC-ES ESR 2659)
14. WOOD
A. ALL DESIGN ANDCONSTRUCTION SHALL CONFORMTO THE APPLICABLE BUILDING CODE ANDTHE
CURRENT EDITION OF THE NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION.
B. ALL STUDS ANDPLATES SHALL BE SOUTHERN PINE OR DOUGLAS FIR LARCH NO. 2 (19%MAX. MOISTURE
CONTENT) OR BETTER.
C. ALL EXTERIOR WALLS SHALL SHEATHEDWITH 15/32" APA RATED, EXPOSURE 1, SHEATHING FASTENED
WITH 8dCOMMON NAILS @6" O.C. AT PANEL EDGES ANDBOUNDARIES AND12" O.C. AT INTERMEDIATE
SUPPORTS, UNLESS NOTEDOTHERWISE IN DETAILS ANDSCHEDULES. PROVIDE SOLID2X BLOCKING AT
ALL PANEL EDGES. ALL INTERIOR NON-SHEAR WALLS SHALL BE SHEATHEDWITH5/8"GYPSUM
WALLBOARDFASTENEDTO STUDS WITH TYPE "S" OR "W", NO. 6-11/4" SCREWS AT 6" O.C. EDGES,
BOUNDARY ANDFIELD UNLESS NOTEDOTHERWISE IN DETAILS ANDSCHEDULES.
D. ROOF DECK SHALL BE 19/32" MINIMAL THICKNESS WITH APA STRUCTURAL I RATING, EXPOSURE I
SHEATHING. RUN PANELS PERPENDICULAR TO THE SUPPORTS, STAGGER PANEL ENDS 1
2 PANEL
LENGTH. ATTACH WITH 10d COMMON NAILS OR DEFORMEDNAILS (11/2" MINPENETRATION) @4"O.C. AT
PANEL EDGES ANDBOUNDARIES, AND@6" 0.C. OVER INTERMEDIATE SUPPORTS ALONG THE OUTER
7'-0" ALL SIDES. AT REMAINING AREA SPACE @6" O.C. @PANEL EDGES ANDBOUNDARIES AND@12"
O.C. OVER INTERMEDIATE SUPPORTS
E. WOODPLATES, SILLS ANDSLEEPERS WHICH REST ON CONCRETE SLABS, ARE IN DIRECT CONTACT
WITH THE EARTH, ANDSILLS WHICH REST ON CONCRETE OR MASONRY FOUNDATIONS SHALL BE
BORATE OR ACQ PRESSURE TREATED WOODANDSHALL HAVE APPROVEDMETAL ATTACHMENT.
F. SEE SHEET S006FOR WOODTRUSS GENERAL NOTES.
G. ALL SPECIFIED FASTENERS SHOWN IN THESE DOCUMENTS MUST BE INSTALLEDACCORDING TO THE
MANUFACTURERS INSTRUCTIONS. ALL FASTENERS IN A CONNECTION MUST BE USED. ALL FASTENERS
MUST BE INSTALLEDPRIOR TO LOADING THE CONNECTION.
H. SUBSTITUTIONS FOR SIMPSON STRONG TIE CO., INC'S PRODUCTS MUST BE PRE-APPROVEDIN WRITING
BY THE ENGINEER OR ARCHITECT. SUBSTITUTION REQUESTS MUST BE ACCOMPANIEDBY EVALUATION
REPORTS FROMTHE INTERNATIONAL CODE COUNCIL.
I. PARALLEL STRANDLUMBER (PSL) MEMBERS SHALL CONFORMTO THE FOLLOWING:
E=2,000,000PSI
Fb=2,900PSI
Fv=290PSI
FOUNDATIONS:
A. FOUNDATIONS ARE DESIGNEDTO BEAR ON A MINIMUM60" THICK PADOF SELECT FILL EXTENDED
HORIZONTALLY 5'-0" BEYONDTHE FACE OF THE BUILDING TO REDUCE THE ESTIMATEDP.V.R. TO ONE
INCH OR LESS.
B. COMPLY WITH ALL ASPECTS OF THE GEOTECHNICAL REPORT NO 12G9177, DATEDNOVEMBER 2012BY
QC LABORATORIES, INC.
C. THE GENERAL CONTRACTOR ANDFOUNDATION CONTRACTOR SHALL UNDERSTANDTHE SURVEY AND
GEOTECHNICAL REPORT BEFORE BIDDING THE WORK. RECOMMENDATIONS CONTAINEDIN THE
GEOTECHNICAL REPORT SHALL BE INCLUDED IN THE CONTRACTOR'S WORK, UNLESS SPECIFIEDOR
DETAILED OTHERWISE.
D. CONTRACTOR SHALL REMOVE EXISTING FOOTINGS ANDFOUNDATIONS THAT ARE LOCATEDWITHINTHE
FOOTPRINT OF THE NEWBUILDING.
E. CONTRACTOR SHALL NOTIFY ENGINEER OF ANY UNUSUAL SOIL CONDITIONS THAT ARE IN VARIANCE
WITH THE GEOTECHNICAL REPORT OR WHEN DIFFERENT BEARING MATERIAL IS EVIDENT ANDTHERE IS
A QUESTION OF BEARING CAPACITY.
F. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL ANDDISPOSAL OF UNSUITABLE FILL MATERIAL
OR ORGANIC MATERIAL.
SUBMITTALS:
A. SHOP DRAWINGS ARE ANAIDFOR FIELD PLACEMENT, ANDARE SUPERSEDEDBY THE STRUCTURAL
DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO MAKE CERTAINTHAT
ALL CONSTRUCTION IS IN FULL AGREEMENT WITH THE LATEST STRUCTURAL DRAWINGS. A SET OF
APPROVEDSHOP DRAWINGS MUST BE FILEDWITH THE CITY ENGINEER BY THE CONTRACTOR.
B. THE CONTRACTOR SHALL SUPPLY THE ENGINEER ANDARCHITECT WITH THE SHOP DRAWINGS INPDF
FORMAT A MINIMUMOF THREE WEEKS PRIOR TO FABRICATION.
C. THE REVIEWOF SHOP DRAWINGS BY THE ENGINEER IS ONLY FOR GENERAL COMPLIANCE WITH THE
STRUCTURAL DRAWINGS ANDSPECIFICATIONS. THE REVIEWDOES NOT GUARANTEE INANY WAY THAT
THE SHOP DRAWINGS ARE CORRECT NOR DOES IT INFER THAT THEY SUPERSEDE THE THE
STRUCTURAL DRAWINGS.
D. THE CONTRACTOR SHALL REVIEWANDAPPROVE THE SHOP DRAWINGS PRIOR TO SUBMITTAL TOTHE
ENGINEER.
E. SHOP DRAWINGS SHALL BE SUBMITTEDFOR ARCHITECTURAL ANDENGINEERING REVIEWPRIOR TO
FABRICATION ANDINSTALLATION FOR STRUCTURAL STEEL MEMBERS ANDCONNECTIONS, EMBEDMENT
PLATES, PRE-MANUFACTURED WOODBEAMS ANDTRUSSES ANDMETAL STAIRS ANDRAILING, WITH
DETAILS NECESSARY FOR INSTALLATION FOR THE ENGINEER'S APPROVAl.
F. CALCULATIONS SEALEDBY AN ENGINEER LICENSEDIN THE J URISDICTION OF THE PROJ ECT MUST BE
SUBMITTEDWITH THE SHOP DRAWINGS FOR METAL STAIRS ANDRAILING, ANDWOODTRUSSES.
G. LAYOUT PLANS OF EMBEDMENT PLATES, IF THEY EXIST, MUST BE PROVIDEDWITH THE SUBMITTAL FOR
REVIEW.
H. STRUCTURAL CONSTRUCTION DRAWINGS MAY NOT BE COPIEDBY THE SHOP DRAWING PRODUCER
WITHOUT WRITTEN PERMISSION BY THE STRUCTURAL ENGINEER.
I. ALL CHANGES TO THE STRUCTURAL DRAWINGS FOUNDIN THE SHOP DRAWINGS MUST BE CLEARLY
MARKEDANDSUMMARIZEDIN A SEPARATE RFI FORMAT.
S301 FOUNDATION SECTIONS
S201 ROOF FRAMING PLAN
GENERAL NOTES
FRAMING SECTIONS
S003
S001
S002
S401
TYPICAL DETAILS
FOUNDATION PLAN S101
TYPICAL DETAILS
S004 TYPICAL DETAILS
S005
FRAMING SECTIONS S402
S302 FOUNDATION SECTIONS
S006 TRUSS DIAGRAMS
TYPICAL DETAILS
S202 SHEAR WALL PLAN
STRUCTURAL GENERAL NOTES
S001
1 STRUCTURAL SHEET INDEX
S001
2
NUMBER F-51
FIRMREGISTRATION
21834 Northwest Freeway
Cypress, TX 77429
281-664-1600
Fax 281-664-1601
www.barryengineering.com
DRAWING NUMBER:
DRAWINGTITLE:
REVISIONS: DATE: NO.
LANDLORDREVIEWISSUE DATE:
TENANT REVIEWISSUE DATE:
BID ISSUE DATE:
PERMIT ISSUE DATE: 4-25-2013
CONSTRUCTIONISSUE DATE:
PROJ ECT NO.:
DRAWN BY: TP
CHECKED BY: MB
103 Carlos G. Parker
Blvd., N.W.
Taylor, TX 76574
engineer is an offense under the
on this document was authorized
The seal and signature appearing
by Michael E. Barry, P.E. 82583
a sealed document without proper
notification to the responsible
Texas EngineeringAct.
on the signed date above. Alterationof
BEI PROJ ECT #: 13-020
REVISION1 1 5-21-13
50-55'
+11.8
5
3
4
1
2
ZONE
HEIGHT
0-15'
+8.8 -21.8
-36.4
-55.0
+21.8 -23.6
-29.1
15-20'
+9.4 -23.3
-38.9
-58.6
+23.3 -25.2
-31.1
20-25' 25-30'
+10.2 -25.2
-42.2
-63.6
+25.2 -27.3
-33.7
30-35'
+10.6 -26.1
-43.7
-65.9
+26.1 -28.3
-34.9
35-40'
+10.9 -26.9
-44.9
-67.7
+26.9 -29.1
-35.9
40-45'
+11.1 -27.6
-46.1
-69.5
+27.6 -29.8
-36.8
45-50'
+11.4 -28.1
-47.0
-70.9
+28.1 -30.4
-37.6
+11.6 -28.7
-47.9
-72.2
+28.7 -31.0
-38.3
55-60'
-29.2
-48.8
-73.6
+29.2 -31.6
-39.0
+9.8 -24.3
-40.7
-61.3
+24.3 -26.3
-32.5
COMPONENTS &CLADDING WIND PRESSURES (PSF)
100 MPH (3 SEC GUST), EXPOSURE C
+8.8
+8.8
+21.8
+9.4
+9.4
+23.3
+9.8
+9.8
+24.3
+10.2
+10.2
+25.2
+10.6
+10.6
+26.1
+10.9
+10.9
+26.9
+11.1
+11.1
+27.6
+11.4
+11.4
+28.1
+11.6
+11.6
+28.7
+11.8
+11.8
+29.2
NOTE:
WINDZONES ARE IN ACCORDANCE WITH ASCE 7, FIGURE 6-3.
ROOF ANGLE 0 - 7 (FLAT ROOF)
PRESSURES ARE BASEDON AN EFFECTIVE WINDAREA OF 10SQUARE FEET.
6000
3000
5000
4000
REINFORCING STEEL SPLICE LENGTH
SMALLER
#6 AND
LARGER
#7 AND
53db
49db
44db
40db
72db
61db
55db
51db
SMALLER
74db
64db
57db
52db
92db
81db
72db
65db
SMALLER
86db
74db
66db
60db
107db
92db
83db
75db
SMALLER
111db
96db
86db
78db
139db
120db
108db
99db
NOTES:
1. TABULATED SPLICE LENGTH VALUES ARE BASED
ON UNCOATEDBARS, FY =60 ksi.
2. BAR LAP SPLICE LENGTH SHALL BE AS NOTEDIN
THE DOCUMENTS ANDAS REQUIREDIN NOTE 3BELOW.
3. REQUIREDLAP SPLICE LENGTH =TABULATEDSPLICE
LENGTH MULTIPLIEDBY ALL APPLICABLE
ADJ USTMENT FACTORS.
A. FOR CLASS A SPLICE =0.769
B. FOR LIGHTWEIGHT CONCRETE =1.3
C. FOR EPOXY COATEDBARS =1.2
1. FOR EPOXY COATEDBARS W/ COVER LESS
THAN 3db OR CLEAR SPACING LESS THAN
6db =1.5
D. FOR Fy OTHER THAN 60ksi =Fy(ACTUAL)/60
4. REQUIREDLAP SPLICE LENGTH SHALL, UNDER NO
CIRCUMSTANCES, BE LESS THAN12".
TYPE & BARS WITH CLEAR SPACING
CLEAR COVER NOT LESS THAN db
STIRRUPS OR TIES THROUGHOUT THE SPLICE
LENGTH NOT LESS THAN CODE MINIMUM.
OR
BARS WITH CLEAR SPACING NOT LESS THAN2db
CLEAR COVER NOT LESS THAN db.
TYPE & : ALL OTHER CASES
TYPE
CLASS B SPLICE
BOTTOM/VERT. BAR
TYPE
CLASS B SPLICE
TOP BAR
TYPE
CLASS B SPLICE
BOTTOM/VERT. BAR
TYPE
CLASS B SPLICE
TOP BAR
LARGER LARGER LARGER
#6 AND #7 AND #6 AND #7 AND #6 AND #7 AND
db =DIAMETER OF BAR (INCHES)
CONCRETE
STRENGTH
F'C, PSI
OLD
POUR POUR
BUILDING OR
STRUCTURE
1/2" EXP J OINT MAT'L w/
REMOVABLE CAP STRIP. SEAL
TOP WITH GREY CONST SEALANT
T
/4
SAWCUT OR FORMED
FILL w/ SEALANT &
BACKING ROD
CONTRACTOR MAY SUBSTITUTE
SMOOTH DOWELS FOR KEY.
CONTACT ENGINEER FOR DETAILS.
NEW
1
"
2T
ISOLATION CONSTRUCTION
T
CONTROL
2
T
CONFORMTO ASTMA615M, GRADE 420
METRIC BAR SUBSTITUTIONS SHALL
INCH POUND
BAR MARK
ALLOWABLE METRIC BAR SUBSTITUTIONS
#8
#9
#11
#10
#14
#18
#4
#5
#6
#7
#3
BAR MARK
#25
#29
#43
#36
#57
#32
#13
#16
#19
#22
#10
METRIC
V
E
R
T
S
T
E
P
P
E
R
P
L
A
N
HORIZDIM=
VERT STEP DIM
P
E
R
D
E
T
A
IL
S
P
E
R
D
E
T
A
IL
S
PER PLAN OR
AT WALL PANEL J OINT
COORDw/ PANEL SUPPLIER
4
5
M
IN
9
0

M
A
X
CLASS B SPLICE
CLASS B SPLICE
STDHK
STDHK
SPLICE BARS
MATCHCONTINUOUS
GRADE BEAMBARS
NOTE:
WHERE VERT STEP DIMENSION
DOES NOT EXCEEDGRADE BEAM
DEPTH, BOTTOMBARS OF TOP
GRADE BEAMMAY BE LAPPEDWITH
TOP BARS OF BOTTOMGRADE BEAM
ANDSPLICE BARS
MAY BE OMITTED
(2) #5VERT BARS w/
STDHOOK EA END
BOTTOMGRADE
BEAMREINF PER
DETAILS (TYP)
GRADE BEAMTIES
PER DETAILS (TYP)
TOP REINF IN
GRADE BEAMPER
DETAILS (TYP)
STEEL STL
EXTERIOR EXT
FINISHED
FOUNDATION
FOOTING
GRADE BEAM
HORIZONTAL
GALVANIZED
HORIZ
FIN
FND
GALV
FLR
FTG
G.B.
GA
FLOOR
GAUGE
UNLESS NOTED OTHERWISE
WELDED WIRE FABRIC W.W.F.
T.O.
T&B
VAR
U.N.O.
TYP
VERT
w/
TOP OF....(ADDITEM)
TOP &BOTTOM
VARIES
WITH
TYPICAL
VERTICAL
CENTER OF GRAVITY OF STRANDS
A.B. ANCHOR BOLT
CMU CONCRETE MASONRY UNIT
DRAWING
DIAMETER
DIMENSION
CONCRETE
EACH WAY
EXISTING
CONTINUOUS
EACH FACE
ELEVATION
EXPANSION
DWG
ELEV
EXIST
E.F.
EQ
E.W.
EXP
EQUAL
DEG
CONC
CONT
CTR
DIA
DTL
DIM
CENTER
DEGREE
DETAIL
BALANCE
BUILDING
BEARING
BETWEEN
CONTROL J OINT
CAST-IN-PLACE CONCRETE
CENTER LINE
ARCHITECTURAL PLANS
BTWN
C.G.S.
CL
C.J .
CIP
CLR
COL
CLEAR
COLUMN
BLDG
@
BM
BAL
ARCH
BRG
BOT
BEAM
AT
BOTTOM
ABOVE FINISH FLOOR
ALTERNATE
A.F.F.
ALT
J OINT J T
LONG LEG HORIZONTAL
LONG LEG VERTICAL
POUNDS PER SQUARE FOOT
POUNDS PER SQUARE INCH
OPP OPPOSITE
SECT
SQ
STD
SPA
SIM
SPECS
SHT
PSF
REINF
SCHED
PSI
RAD
PC
PT
SPECIFICATION
STANDARD
SQUARE
SHEET
SECTION
SIMILAR
SPACING
REINFORCEMENT
POST TENSION
RADIUS
SCHEDULE
PRECAST
MISC
MK
N.T.S.
O.C.
OPNG
O.F.
MIN
MANUF
LLV
LBS
LLH
MAX
MAS
K
MISCELLANEOUS
NOT TO SCALE
ON CENTER
OUTSIDE FACE
MINIMUM
MARK
OPENING
MANUFACTURER
KIP (1000LBS)
POUNDS
MASONRY
MAXIMUM
I.F.
J ST
INSIDE FACE
J OIST
F.S. FAR SIDE
N.S. NEAR SIDE
FIELD VERIFY F.V.
GRADE
BEAM
(1) ADDITIONAL
TIE EA SIDE OF
SLEEVE
SLAB
OPEN OR
BACKFILL
PIPE TRENCH
PARALLEL
TO FTG
6
"
M
IN
1
4
"
M
IN
PROVIDE STEEL OR PVC SLEEVE
w/ I.D. 2" GREATER THANO.D. OF
PIPE
6
"
M
IN
LEAN CONC FILL AROUND
SLEEVE BEFORE POURING
FOOTING. FILL SHALL BE
SAME WIDTH AS FTG
OR GREATER
STEP GRADE BEAM
SO AS NOT TO
EXCEED3'-0"
TRENCH MUST
BE ABOVE
THIS LINE
6
"
M
IN
1
3
6
"
M
A
X
8
"
M
IN
1'-4"
P
E
R
A
R
C
H
PER ARCH
#4 BAR CONT
#4HOOKEDDOWEL
@ 24" O.C.
6"
3"
NON-SHRINK
CONCRETE
AROUNDCOL
COL &BASE
PLATE PER PLAN
ISOLATION
J OINT
EDGE OF GRADE BEAM
&FOOTING BELOW(TYP.)
2-#5x66" MID-DEPTH OF SLAB
AT PERIMETER
OF BLOCK OUT
2-#3x18" EACH FACE - DRILL AND
EPOXY INTO ADJ ACENT SLAB WITH
HILTI HIT RE500EPOXY
6
GRADE BEAMREINFORCEMENT
TO BE CONTINUOUS
THRU FOOTING - SEE 6/S301FOR DETAIL
COMPONENTS &CLADDING WIND PRESSURES TABLE
S002
4
REINFORCING STEEL SPLICE LENGTH TABLE
S002
3
TYPICAL SLAB J OINT DETAILS
N.T.S. S002
5 TYPICAL GRADE BEAM STEP DETAIL
N.T.S. S002
6
METRIC BAR CHART
S002
2 STRUCTURAL ABBREVIATIONS
S002
1
PIPE @ GRADE BEAM DETAIL
N.T.S. S002
7 SECTION @ CURB
N.T.S. S002
8 SLAB BLOCKOUT DETAIL
N.T.S. S002
9
NUMBER F-51
FIRMREGISTRATION
21834 Northwest Freeway
Cypress, TX 77429
281-664-1600
Fax 281-664-1601
www.barryengineering.com
DRAWING NUMBER:
DRAWINGTITLE:
REVISIONS: DATE: NO.
LANDLORDREVIEWISSUE DATE:
TENANT REVIEWISSUE DATE:
BID ISSUE DATE:
PERMIT ISSUE DATE: 4-25-2013
CONSTRUCTIONISSUE DATE:
PROJ ECT NO.:
DRAWN BY: TP
CHECKED BY: MB
103 Carlos G. Parker
Blvd., N.W.
Taylor, TX 76574
engineer is an offense under the
on this document was authorized
The seal and signature appearing
by Michael E. Barry, P.E. 82583
a sealed document without proper
notification to the responsible
Texas EngineeringAct.
on the signed date above. Alterationof
BEI PROJ ECT #: 13-020
REVISION1 1 5-21-13
NOTE:
ALL STUDS SHOWN ARE 2X
INTERSECTIONS CORNERS
SHEATHING
PER GENERAL
NOTES
(TYP)
SEC
SECTION A
1/2" PLYWOOD
FILLER EA SIDE
OF CENTER 2x
TOP PLATE CONT OVER HEADER
SPLICE PER TYP. DETAILS
TOENAIL 4-12d
EACH FACE
INFILL STUDS
TOENAIL TO
HEADER w/
MIN (2) 16d
4-8d TOENAIL
EACHEND
* HEADER BEAM
* HEADER: PER SCHEDULE 5/S003.
(NOTE: DOOR SIMILAR, OMIT LOWER WALL FRAMING).
T.O. SLAB ELEV.
ROOF TRUSSES
KING STUDS
PER SCHEDULE
EA SIDE
TRIMMERS PER SCHEDULE
EA SIDE
STUDS (TYP)
RE: PLAN FOR
SIZE &SPACING
RE: ARCH
RE: ARCH
CONVENTIONAL FRAMING
BELOWWINDOWS
ATTACH PER 6/S003
DOUBLE SILL
AS OCCURS
PROVIDE SIMPSON A33AT
TOP OF EA HEADER TO
J AMBS. FASTEN PER MFR.
SPECIFICATIONS (TYP)
H2
#OF
TRIMMERS HEADER SIZE
(#OF HEADERS)
PLAN MARK
HEADER SCHEDULE
KING STUDS
#OF
SIDE OF OPENING
(1) 2x6EA (2) 2x6EA
SIDE OF OPENING
NOTES:
1. USE (3) 1/4" THICK BEADS OF LIQUIDNAILS CONSTRUCTION ADHESIVE BTWN EA PLY OF BUILT UP
HEADERS.
2. VERIFY LENGTH OF HEADERS w/ STRUCTURAL &ARCHITECTURAL PLANS.
3. WALL OPENING FRAMING ELEVATION PER 4/S003.
H4
SIDE OF OPENING
(4) 2x6EA
SIDE OF OPENING
H3
SIDE OF OPENING
(2) 2x6EA
SIDE OF OPENING
(3) 2x10
H5
SIDE OF OPENING
(3) 2x6EA
SIDE OF OPENING
3 1/2x11 1/4LVL
(3) 2x12
(3) 2x8
(1) 2x6EA
(1) 2x6EA
(1) 2x6EA
H1
SIDE OF OPENING
(1) 2x6EA (2) 2x6EA
SIDE OF OPENING
(3) 2x6
H6
SIDE OF OPENING
(3) 2x6EA
SIDE OF OPENING
5 1/4x11 1/4LVL
(1) 2x6EA
1 1/4" EDGE
3
"
10dNAILS
(TYP)
2
1
/2
"
2
1
/2
"
DOUBLE STUD
3"
9
"
9
"
3
"
1"EDGE
3
"
10dNAILS
(TYP)
3
"
3
"
3 1/2"
9
"
9
"
3
"
TRIPLE STUD
T.O.
STUD
B.O.
STUD
T.O.
STUD
B.O.
STUD
NOTCH
SILL PLATE
1
/3
O
F
S
IL
L
P
L
A
T
E
M
IN
IM
U
M
SIMPSON ST22STRAP
W/ (14) 16d NAILS
SHOT PINS
PER SHEAR WALL
SCHEDULE
2X STUDS @16"O.C.
TYPICAL U.N.O.
CONCRETE SLAB
ON GRADE
TYP 2xWALL STUD
SEE PLAN FOR SPACING
2x6 WALL
SILL PLATE
NOTE
REF. SHEAR WALL
SCHEDULE ON S004
FOR SHEAR WALL
ANCHORAGE
REQUIREMENTS
USE 1/2" DIA. AR-1
PER 11/S003@48"
O.C. AT ALL WALLS
NOT INDICATEDAS
SHEAR WALLS.
7
"
3
"
P
R
O
J
E
C
T
IO
N
AR-1
HEAVY HEX NUT
&OVERSIZE
WASHER (TYP
U.N.O.)
AR-1 ALTERNATE
T
H
R
D
P
R
O
J
E
C
T
IO
N
E
M
B
E
D
6
"
STDNUT
&OVERSIZE
WASHER (TYP
U.N.O.)
1
2" THREADED
ROD
SET ROD w/
HILTI HIT
RE500
EPOXY
NOTE:
NOTCHES TO OCCUR @ TOP OR
BOTTOMTHIRD OF WALL STUD
6
0
%
M
A
X
D
IA
M
O
F
S
T
U
D
W
ID
T
H
EXTERIOR ANDBEARING STUDS
NOTE:
NOTCH ANDBORING NOT
TO OCCUR IN SAME STUD
SECTION.
25%MAXIMUMNOTCH
7/8" MAX @2x4STUDS
1 3/8" MAX @ 2x6STUDS
40%MAXIMUMNOTCH
1 3/8" MAX @ 2x4STUDS
2 1/8" MAX @ 2x6STUDS
40%MAXIMUMSTUDWIDTH
1 3/8" DIA MAX @ 2x4STUDS,
2 1/4" DIA MAX @ 2x6STUDS
60%MAXIMUMSTUDWIDTH
2" MAX DIA @ 2x4 STUDS,
3 1/4" DIA @ 2x6STUDS
5/8" MINIMUMEDGE
DISTANCE TYP ALL STUDS
1 1/2" 1 1/2"
2" DIA MAX @ 2x4
STUDS. 3 1/4" DIA
MAX @2x6 STUDS
DOUBLE STUDS
NON-BEARING STUDS
COORDOPENING
SIZE w/ ARCH AND
MEP DRAWINGS
SIMPSON HU44TF
HANGER
4x4AS REQ'D
ROOF TRUSS
ROOF TRUSS PER PLAN
4x MUST BE PLACED
OVER PANEL POINTS.
INCREASE SIZE OF
CURB IF REQ'D
6'-0" MAX
NOTE:
VERIFY HEIGHT w/
EQUIPMENT MANUFACTURER
4 x CUT TO FIT (4x8MIN)
PROVIDE FULL BRG AT EA
ENDTO EA TRUSS
SIMPSON A35EA
SIDE OF 4xHEADER
@EA TRUSS
CANT STRIP
2xAS REQ'D IN'U'
TYPE HANGERS
LEVEL PLATFORM
METAL CAP OVER
ROLL ROOFING
OVER 3/4" PLYWOOD
ROOF TRUSS
ROOFING
PER PLAN
WOODTRUSS PER PLAN
2x STUDS @16:O.C.
U.N.O. RE: ARCH
(2) 2x PLATES
SIMPSON DTC TRUSS
CLIPS @ 16"O.C. U.N.O.
(LLV) SHIMMING ON
HORIZONTAL LEG MAY BE
REQUIREDTOACHIEVE
CLEARANCE
NOTE:
PROVIDE BLOCKING FOR
FINISH MATERIALS AS NEEDED
2
"
C
L
R
TYPICAL WOOD FRAMING DETAILS
N.T.S. S003
1
TYPICAL WALL OPENING ELEVATION
N.T.S. S003
4 TYPICAL HEADER SCHEDULE
S003
5 TYPICAL BUILT UP STUD DETAILS
N.T.S. S003
6 TYPICAL WALL PLATE NOTCH DETAIL
N.T.S. S003
7
TYPICAL INTERIOR WALL CONN
N.T.S. S003
8 TYPICAL ANCHOR BOLT DETAILS
N.T.S. S003
11
TYPICAL WOOD FRAMING DETAILS
N.T.S. S003
2 TYPICAL RTU SUPPORT DETAILS
N.T.S. S003
3
NUMBER F-51
FIRMREGISTRATION
21834 Northwest Freeway
Cypress, TX 77429
281-664-1600
Fax 281-664-1601
www.barryengineering.com
DRAWING NUMBER:
DRAWINGTITLE:
REVISIONS: DATE: NO.
LANDLORDREVIEWISSUE DATE:
TENANT REVIEWISSUE DATE:
BID ISSUE DATE:
PERMIT ISSUE DATE: 4-25-2013
CONSTRUCTIONISSUE DATE:
PROJ ECT NO.:
DRAWN BY: TP
CHECKED BY: MB
103 Carlos G. Parker
Blvd., N.W.
Taylor, TX 76574
engineer is an offense under the
on this document was authorized
The seal and signature appearing
by Michael E. Barry, P.E. 82583
a sealed document without proper
notification to the responsible
Texas EngineeringAct.
on the signed date above. Alterationof
BEI PROJ ECT #: 13-020
REVISION1 1 5-21-13
TYPICAL NON-LOAD BEARING WALL CONN
NTS S003
9 TYPICAL SILL PLATE CONNECTION DETAILS
NTS S003
10
OPENING
PER PLAN
TOP PLATE PER
OTHER DETAILS
SHEAR WALL PER PLAN
SILL PLATE ANCHORAGE
PER 2/S004
ENDOF WALL PER PLAN
FASTENER SPACING @
INTERMEDIATE FRAMING
MEMBERS PER GENERAL NOTES
BUILT-UP STUDS @ SHEAR
WALL ENDS CONNECT
PER 6/S003
2
'-0
"
STAGGER HORIZPLYWOOD
J OINTS
VERT PLYWOODJ OINTS
MAY BE CONT
TRUSS PER PLAN
TRUSS/STUDSPACING &
SIZE PER PLAN/DETAILS
FASTENER SPACING @
PANEL EDGES PER
GENERAL NOTES
TRUSS BEARING
ELEV
2x6 BLOCKING @ PANEL
J OINTS IF NO STUD@ J OINT
HOLDOWN PER
SCHEDULE (TYP)
2x BLOCKING @ ALL PANEL
EDGES, PER 4/S004
ROOF TRUSS BEYOND
PER PLAN
2x6 BLOCKING @
SHEATHING
J OINTS.
FASTEN EACH
END
OF BLOCKING
USING
3-3"-0.131" NAILS
MINIMUM
SHEATHING
PER PLAN
AT WALLS
AT ROOF
SHEATHING PER PLAN
2x4 BLOCKING @
SHEATHING J OINTS.
FASTEN EACHEND
OF BLOCKING USING (3)
8d NAILS MINIMUM
SIMPSON HOLDDOWNANCHOR.
USE ALL SPECIFIED FASTENERS
PER SCHEDULE 2/S004
BUILT-UP STUD@ END
OF WALL
PER SHEAR WALL
SCHEDULE. FASTEN
TOGETHER PER 6/S003
SIMPSON ANCHOR
PER SCHEDULE 2/S004
2BLOCKS
MINIMUM
BLOCKING TRUSS AS REQ'DTO
TRANSFER ROOF DIAPHRAGM
SHEAR OUT OF ROOF SHEATHING
TO SHEAR WALLS (4'-0" O.C. MAX)
TOP PLATE PER
OTHER DETAILS
SHEAR WALL
PER PLAN
PROVIDE SIMPSON 1" WIDE x16GA COIL
STRAP UNDER ROOF SHEATHING. FASTEN
ROOF SHEATHING THRU COIL STRAP TO
BLOCKING FOR DIAPHRAGMEDGE NAILING
PATTERN PER GENERAL NOTES
PROVIDE 2x6BLOCKING
BETWEEN EA TRUSS
REFERENCE NOTE:
A BEAMSIZE PER SCHEDULE (TYP).
B PERPENDICULAR BEAMAS OCCURS
(NOT SHOWN).
C 3/16" CAP PLATE @T.O. COL, SEAL
WELD ALL AROUND.
D "N" QUANTITY OF 3/4" BOLTS @
3" O.C. IN HORIZSSL HOLES.
E 3/4" BOLTS IN STDHOLES.
F 5/16" MIN THICKNESS DBL CLIP
ANGLES OR BENT PLATE.
G WIDE FLANGE COLUMN.
BEAM-TO-BEAM BEAM-TO-COL
BEAM-TO-COL NOTE:
1. ALL BOLTS SHALL BE 3/4" DIAMETER, ASTM
A325.
2. ALL BOLTS SHALL HAVE HEAVY HEX NUTS.
3. NUTS SHALL BE TIGHTENEDTO SNUG TIGHT
CONDITION.
4. CLIP ANGLES MAY BE SHOP WELDEDTO BEAM
WEB PER AISC.
5. FOR BEAMS WITH AXIAL LOADS PER PLAN, BOLTS &
CONNECTIONS SHALL BE SLIP-CRITICAL PER AISC
GUIDELINES.
18
18
15
15
12
12
9
9
8
6
6
MINIMUM
6
LENGTH, "L" (IN) 3/4" BOLTS IN WEB
G
E
D
A
W36 6
D
3"
MAX
NOTE:
FABRICATOR SHALL BE RESPONSIBLE FOR DESIGN AND
DETAIL OF EACH CONNECTION FOR LOADS SHOWN ON
PLANS IN ACCORDANCE WITH THE SPECIFICATION AND
THE GENERAL STRUCTURAL NOTES.
SUGGESTED CONNECTION DETAILS ARE SHOWN.
FABRICATOR MAY OPT TO USE OTHER AISC APPROVED
CONNECTIONS IN LIEU OF THOSE SHOWN HEREIN.
3"
MAX
B
5/16
5/16
TYP C
A
L
MINIMUM CONNECTION SCHEDULE
2
2
3
2
MINIMUM "N" QUANTITY
4
4
3
3
W8
W12
W14
BEAMSIZE
W10
W24
W21
W18
W16
6
5
W33
W30
W27 5
HSS
COL
5/16
5/16
PL3/8" SHEAR
TAB
C
A
D
L
L
B USE FACE
MOUNTEDSHEAR
TAB PER SCHEDULE
HSS COL
PL3/8" THROUGH
PLATE
TYPE B
STUDWALL
TYPE B
(GYP) (GYP)
STUDWALL
TYPE A
(OSB)
TYPE B
(GYP)
TYPE A
STUDWALL
TYPE A
(OSB) (OSB)
A
B
A
B
1
1
/2
"
T
Y
P
.
1 1/2" TYP.
A
B
5
1
/2
"
5 1/2"
1 1/2" 1 1/2" EQ. EQ.
PLATE
ORIENTATION
PER PLAN
1 1/2" TYP.
SOLID2x6 BLOCKING
ATTACH WITH3-3"x
0.131" NAILS EACH
ENDINTO TOP CHORD
OF TRUSS AND
SIMPSON LTP4
MID-SPAN EACH BLOCK
WALL STUDS PER PLAN
FLUSH BEAMPER PLAN
ROOF DECKING ANDFASTENING
PER GENERAL NOTES
SIMPSON CS16PER PLAN.
FASTEN TO TRUSS OR BLOCKING
WITH 10d NAILS @8"O.C. MAX.
SPACING
3
SIMPSON H2.5A @EACHTRUSS
SIMPSON CS16x30EACH END
J OIST OR RAFTER
2x4 FLAT BLOCKING @EDGE
J OINTS OF PLYWOODPER
4/S004
2'-0"
MIN
ROOF TRUSS
EDGE OF PLYWOOD
EDGE NAILEDAS
REQ'DPER GENERAL
NOTES
FIELD NAILEDAS
REQ'DPER
GENERAL NOTES
BOUNDRY
PERIMETER
BOUNDARY NAILED
AS REQ'DPER
GENERAL NOTES
PLYWOOD
PER PLAN
2
'-0
"
M
IN
2
'-0
"
M
IN
S
T
A
G
G
E
R
P
A
N
E
L
S
NOTES:
1. RUN LONG DIMENSION OF PLYWOODPANELS PERPENDICULAR TO
J OIST OR TRUSS.
2. STAGGER ENDJ OINTS 2'-0" MINIMUM, AS SHOWN.
3. NAILS SHALL HAVE A MINIMUM3/8" EDGE DISTANCE.
4. NAILS SHALL BE OF THE SIZE ANDPENETRATION SPECIFIEDPER
THE GENERAL NOTES.
5. ANY OPENING SHALL BE FULLY BLOCKED&NAILEDTO MATCH
BOUNDRY CONDITIONS.
BLOCKING DETAIL
N.T.S. S004
4
SHEAR WALL ELEVATION
N.T.S. S004
1
BEAM CONNECTION DETAILS
N.T.S. S004
8
STUD SCHEDULE
N.T.S. S004
6
TYPICAL CS16 ROOF STRAP DETAIL
N.T.S. S004
7A
WALL HOLDDOWN DETAIL
N.T.S. S004
5
SHEAR WALL SCHEDULE
N.T.S. S004
2
ROOF DIAPHRAGM ATTACHMENT
N.T.S. S004
3
BASE PLATE DETAILS
N.T.S. S004
9
NUMBER F-51
FIRMREGISTRATION
21834 Northwest Freeway
Cypress, TX 77429
281-664-1600
Fax 281-664-1601
www.barryengineering.com
DRAWING NUMBER:
DRAWINGTITLE:
REVISIONS: DATE: NO.
LANDLORDREVIEWISSUE DATE:
TENANT REVIEWISSUE DATE:
BID ISSUE DATE:
PERMIT ISSUE DATE: 4-25-2013
CONSTRUCTIONISSUE DATE:
PROJ ECT NO.:
DRAWN BY: TP
CHECKED BY: MB
103 Carlos G. Parker
Blvd., N.W.
Taylor, TX 76574
engineer is an offense under the
on this document was authorized
The seal and signature appearing
by Michael E. Barry, P.E. 82583
a sealed document without proper
notification to the responsible
Texas EngineeringAct.
on the signed date above. Alterationof
BEI PROJ ECT #: 13-020
REVISION1 1 5-21-13
DIAPHRAGM CHORD DETAILS
N.T.S. S004
7
PERFORATED SHEAR WALL DETAIL
N.T.S. S004
2A
FLUSH BEAMPER PLAN
ROOF DECKING ANDFASTENING
PER GENERAL NOTES
SIMPSON H2.5A @EACHTRUSS
CONTINUOUS DOUBLE TOP
PLATE OVER FLUSH BEAM
SIMPSON LTP4BETWEEN
EACH TRUSS INTO FLUSH
BEAM
SIMPSON CS 16x30EACH END
TRIMMER ANDKING STUDS
PER SCHEDULE 5/S003
SIMPSON LTT19WITH 5
8"x10" THREADED ROD.
EPOXY WITH HILTI HIT RE500EPOXY, 7"
EMBEDMENT. OMIT IF SHEAR WALL HOLD DOWNIS
PRESENT.
RAKE AND CAULK
RAKE &
CAULK
PREFORMED GASKET
SASH UNITS
RAKE AND CAULK
NOTE:
COORDINATE LOCATION OF
CONTROL J OINTS w/ ARCH
DRAWINGS
BUILDING
PAPER
CONCRETE
FILL
SPECIAL CONTROL
J OINT UNITS
PREFABRICATED CORNER
HORIZJ OINT REINF
MATCH VERT SPACING OF
CONT HORIZJ OINT REINF
NOTE:
CONTINUOUS HORIZONTAL
J OINT REINFORCING NOT
SHOWN, RE: GEN NOTES
VERT WALL REINF
IN FULLY GROUTED CELLS
RE: GEN NOTES
4'-0" MAX OPENING
BONDBEAMLINTEL
AS REQ'D
VERT EA SIDE
OF OPENING
FULLY GROUTED
VERTICAL CELL (TYP)
AS REQ'D
1 1/2" x 16GA
U-CHANNEL BRIDGING
TYPICAL STUD
1 1/2" x 1 1/2" x 16GA CLIP
ANGLE FASTENED w/ (4) #10-16
SCREWS AS SHOWN: ANGLE
LENGTH SHALL NOT BE LESS
THAN 1/2DEPTH OF STUD
1 1/2" x 16GA
U-CHANNEL BRIDGING
NOTE:
ALL METAL STUDFRAMING
ON THIS PROJ ECT MUST
BE BRACEDAS SHOWN
@ 48" O.C. VERTICALLY.
ALT 2
1/8
1/8 FULL
FULL
ALT 1
TYPICAL STUD
OPTION1
1/4" HILTI KWIK
BOLT II w/ 2"
EMBEDMENT @16" O.C.
OPTION2
1/4" x 1 1/2"TAPCON
ANCHORS @ 16" O.C.
OPTION3
HILTI X-EDNI 16P8
POWDER ACTUATED
FASTENERS @16" O.C.
#12-14TEK SCREWS
BOTH SIDES, TYP
T&B EA STUD
WOODTOP PLATE @
J OIST BEARING
550T125-43 METAL TRACK
(2) #10 WOODSCREWS IN
HORIZONTAL LEG OF CLIP
ANGLE
METAL STUDPER
FRAMING PLAN
16GA CLIP ANGLE
(2) #12 SCREWS IN VERT
LEG OF CLIP ANGLE
1. LIGHT GAGE METAL FRAMING:
A. ALL LIGHT GAGE METAL FRAMING ANDCONNECTIONS SHALL BE DESIGNED, FABRICATED, AND
ERECTEDIN ACCORDANCE WITH AISI "SPECIFICATION FOR THE DESIGN OF COLDFORMEDSTEEL
STRUCTURAL MEMBERS" ANDNAAMMML/SFA 540"LIGHTWEIGHT STEEL FRAMING SYSTEMS
MANUAL."
B. ALL LIGHT GAGE METAL FRAMING IDENTIFICATION SHOWN IN THESE DOCUMENTS IS INACCORDANCE
WITH THE STEEL STUDMANUFACTURERS ASSOCIATION(SSMA).
C. ALL STRUCTURAL MEMBERS SHALL BE FORMEDFROMSTEEL HAVING A GALVANIZEDCOATING
MEETING THE REQUIREMENTS OF ASTMA-653. STEEL MATERIAL SHALL HAVE A MINIMUMYIELD
STRESS OF 33KSI EXCEPT MEMBERS OF 54MIL THICKNESS OR HEAVIER SHALL HAVE A MINIMUM
YIELD STRESS OF 50KSI.
D. ALL CONNECTIONS SHALL BE MADE WITH A MINIMUMOF (4) #10-16 SCREWS OR EQUIVALENT WELDS.
(UNLESS NOTEDOTHERWISE ON THE DRAWINGS)
E. ALL SCREWS SHALL BE OF THE DIAMETER ANDSIZE INDICATEDON THE DRAWINGS, ANDSHALL BE
THOSE MANUFACTUREDANDTESTEDBY ITWBUILDEX. MINIMUMSPACING ANDEDGE DISTANCE FOR
SCREWS SHALL BE THE GREATER OF EITHER 1/2INCH OR 3X SHANK DIAMETER, UNLESS NOTED
OTHERWISE ON THE DRAWINGS. SCREWPENETRATION THROUGH J OINEDMATERIALS SHALL NOT BE
LESS THAN THREE EXPOSEDTHREADS. SELECT SCREWS WITH AN ADEQUATE CUTTING TIP TO
ACCOMMODATE THE TOTAL THICKNESS TO BE DRILLED. DRILLING MUST BE COMPLETEDBEFORE
THE THREADS ENGAGE THE MATERIAL. WHERE SCREWATTACHMENTS ARE MADE TO FRAMING
COMPONENTS OF DIFFERENT THICKNESSES, THE THINNEST COMPONENT MUST BE PENETRATED
FIRST. (UNLESS NOTEDOTHERWISE) ALL SCREWS ARE TYPE 'T1'.
F. WELDING SHALL BE DONE IN ACCORDANCE WITH AWS D1.3- LATEST EDITION, STRUCTURAL
WELDING CODE, SHEET STEEL.
G. SUGGESTEDWELD METAL ANDPROCESS FOR SHOP WELDING ARE: 70ksi WELDMETAL STRENGTH
(MINIMUM). SUGGESTED METHODS FOR FIELDWELDING: 1/8" (UNLESS NOTEDOTHERWISE) E70XX
(MINIMUM) ELECTRODE - SMAW; OR"GASLESS" MIG.
H. MINIMUMWELDTHROAT THICKNESS (t) MUST MATCH OR EXCEEDTHE BASE STEEL THICKNESS OF
THE THINNEST CONNECTEDPART UNLESS NOTEDOTHERWISE.
I. SEQUENCING OF WELDS SHALL BE SO AS TO AVOIDDISTORTION OF MEMBERS. REPLACE ALL
MEMBERS WHEN BURN THROUGH OCCURS DURING WELDING.
J . ALL FRAMING COMPONENTS SHALL BE CUT SQUARELY FOR ATTACHMENT TO PERPENDICULAR
MEMBERS OR AS REQUIREDON ANGULAR FIT AGAINST ABUTTING MEMBERS. MEMBERS SHALL BE
HELDPOSITIVELY IN PLACE UNTIL PROPERLY FASTENED.
K. NO SPLICES IN STUDS, J OISTS, OR OTHER LOADCARRYING MEMBERS MAY BE MADE WITHOUT PRIOR
ENGINEERING REVIEWANDSPECIFIC DETAILS FOR ANY SUCH SPLICE(S).
L. TRACK MEMBERS SHALL MATCH DEPTH ANDMIL THICKNESS (GAGE) OF STUDS UNLESS NOTED
OTHERWISE.
2. LOAD-BEARING METAL STUDS
A. THIS PROJ ECT HAS A LOAD BEARING METAL STUDSYSTEM. SUCCESSFUL METAL STUD
CONTRACTOR SHALL PROVIDE SHOP DRAWINGS THAT INCLUDE FULLY DETAILEDWALL ELEVATIONS
SHOWING THE SIZE ANDLOCATION OF ALL LIGHT GAGE METAL FRAMING ON THIS PROJ ECT. SHOP
DRAWINGS SHALL INCLUDE DETAILS SHOWING SCREWTYPES ANDLOCATIONS, ANDWELDLENGTHS,
SIZES ANDLOCATIONS.
B. MECHANICAL BRIDGING, SPACEDAT THE INTERVALS DESCRIBEDHEREIN, SHALL BE INSTALLED
PRIOR TO THE ATTACHMENT OF FACING MATERIALS.
C. MECHANICAL BRIDGING SHALL BE INSTALLED, IN THE FORMOF COLDROLLEDCHANNELS AND
CONNECTION CLIPS, IN ALL WALLS ON THIS PROJ ECT. SEE TYPICAL LIGHT GAGE METAL FRAMING
DETAILS ON THE DRAWINGS FOR SPECIFIC REQUIREMENTS.
D. ALL LIGHT GAGE METAL FRAMING SHOWN ON THESE DOCUMENTS IS BASEDONTHE PHYSICAL AND
STRUCTURAL PROPERTIES OF CSJ METAL STUDS ANDFRAMING MANUFACTUREDBY DIETRICH
INDUSTRIES. ANY SUBSTITUTIONS MUST MEET THE MINIMUMPROPERTIES PROVIDEDBY THESE
MEMBERS, AND MUST BE APPROVEDIN WRITING BY THE ENGINEER.
SIMPSON RSP4(2) TYP. @ EACH
STUD
SIMPSON RSP4(2)
TYP. @EACH STUD
SIMPSON H2.5A @EACH
TRUSS
TYP METAL STUD BOTTOM TRACK
N.T.S. S005
4 TYP METAL STUD BRACING
N.T.S. S005
5 TOP TRACK CONNECTION
N.T.S. S005
6 METAL STUD GENERAL NOTES
N.T.S. S005
7
N.T.S. S005
9 NOT USED
S005
10
CONTROL J OINT DETAIL
N.T.S S005
1 CORNER REINFORCEMENT DETAIL
N.T.S S005
2 BOND BEAM LINTEL DETAIL
N.T.S S005
3
NUMBER F-51
FIRMREGISTRATION
21834 Northwest Freeway
Cypress, TX 77429
281-664-1600
Fax 281-664-1601
www.barryengineering.com
DRAWING NUMBER:
DRAWINGTITLE:
REVISIONS: DATE: NO.
LANDLORDREVIEWISSUE DATE:
TENANT REVIEWISSUE DATE:
BID ISSUE DATE:
PERMIT ISSUE DATE: 4-25-2013
CONSTRUCTIONISSUE DATE:
PROJ ECT NO.:
DRAWN BY: TP
CHECKED BY: MB
103 Carlos G. Parker
Blvd., N.W.
Taylor, TX 76574
engineer is an offense under the
on this document was authorized
The seal and signature appearing
by Michael E. Barry, P.E. 82583
a sealed document without proper
notification to the responsible
Texas EngineeringAct.
on the signed date above. Alterationof
BEI PROJ ECT #: 13-020
REVISION1 1 5-21-13
TYPICAL INTERIOR LOAD
BEARING FLUSH BEAM UPLIFT
RESISTANCE HARDWARE DETAIL
N.T.S. S005
9
TYPICAL INTERIOR LOAD
BEARING WALL UPLIFT
RESISTANCE HARDWARE DETAIL
2x T&B CHORD
CROSS PIECE AS
REQ'DPER TRUSS
SUPPLIER
TRUSSES EA SIDE
PER PLAN
BLOCKING TRUSS
ROOF TRUSS NOTES:
1. SEE SHEET S001FOR STRUCTURAL GENERAL NOTES.
2. THIS WORK INCLUDES THE COMPLETE FURNISHINGS ANDINSTALLATION OF ALL OPENWEB
TRUSSES AS SHOWN ON THE DRAWINGS HEREIN SPECIFIEDANDNECESSARY TO COMPLETE THE
WORK.
3. WEB MEMBERS ARE SHOWN ON DIAGRAMS FOR GRAPHICAL PURPOSES ONLY. DESIGN AND
ARRANGEMENT OF WEB MEMBERS ARE THE RESPONSIBILITY OF THE TRUSS SUPPLIER.
4. ROOF PITCH ANDSOFFIT GEOMETRY SHOWN FOR REFERENCE ONLY. SEE ARCHDRAWINGS FOR
INFORMATION.
5. DESIGN CRITERIA:
a. PRODUCTS: THE OPEN WEB TRUSSES SHALL BE DESIGNEDTO FIT THE DIMENSIONS
ANDLOADS INDICATED ON THE PLANS ANDGENERAL NOTES.
b. OPEN WEB TRUSSES SHALL BE FABRICATEDANDERECTED(INCLUDING BRIDGING) IN
ACCORDANCE WITH THE LATEST SPECIFICATIONS OF THE NES REPORT NO. NER-148,
ANSI/TPI ANDALL OSHA REQUIREMENTS.
c. TRUSSES SHALL BE DESIGNEDFOR GRAVITY LOADS PER GENERAL NOTES 2A, 2B AND
2E ANDLATERAL LOADS ANDUPLIFT GENERATEDBY WINDANDSEISMIC LOADING PER
GENERAL NOTES 2C AND2D.
d. AT A MINIMUM, ENDS OF BRIDGING SHALL HAVE DIAGONAL CROSS BRACING BETWEEN
THE LAST TWO OPEN WEB TRUSSES IN ADDITION TO HORIZONTAL BRIDGING.
e. OPEN WEB TRUSSES SHALL BE DESIGNEDTO LIMIT THE MAXIMUMLIVE LOAD
DEFLECTION TO SPAN/480 ANDMAXIMUMTOTAL LOADDEFLECTION TO SPAN/360.
6. DESIGN OF ROOF TRUSSES SHALL INCLUDE ALL NECESSARY BRACING, BRIDGING AND/OR
CONNECTIONS, INCLUDING UPLIFT TO TRANSMIT THE REQUIREDLOADS INTO THE STRUCTURE.
1. TRUSS SPACING SHALL NOT EXCEED24" UNLESS SPECIFIEDOTHERWISE ON THE DETAILS.
2. TRUSS SUPPLIER SHALL PROVIDE A MINIMUMOVERALL TRUSS DEPTH OF 24"REGARDLESS OF
DIMENSIONING SHOWN PER THE ARCHITECTURAL DRAWINGS. TRUSS SUPPLIER SHALL NOTIFY
THE ARCHITECT/ENGINEER IMMEDIATELY IF THE 24" MINIMUMTRUSS DEPTH CANNOT BE
ATTAINED.
3. THESE PRODUCTS SHALL BE DESIGNEDANDMANUFACTURED TO THE STANDARDS SET FORTH IN
THE NATIONAL EVALUATION SERVICE, INC. (NES) REPORT NO. NER-148OR ICBO EVALUATION
SERVICE REPORT NO. PFC- 4354.
4. MATERIALS SHALL COMPLY WITH THE NES REPORT NO. NER-148OR ICBOES REPORT NO.
PFC-4345. CHORDMEMBERS, WEB MEMBERS, CONNECTING PINS ANDBEARING
HARDWARE/ATTACHMENTS SHALL BE OF MATERIAL ANDSIZE AS REQUIREDBY DESIGN.
5. ALL TRUSSES MUST BE SECURELY BRACEDBOTH DURING ERECTION ANDPERMANENTLY AS
REQUIREDBY THE TRUSS MANUFACTURER. CONTRACTOR SHALL BE RESPONSIBLE FOR
TEMPORARY FIELDBRACING TO ASSURE ROOF TRUSSES ARE INSTALLEDAT THE PROPER
SPACING ANDARE STRAIGHT ANDPLUMB.
6. TRUSS BOTTOMCHORDS SHALL BE PERMANENTLY CONNECTEDBY BRIDGING. BRIDGING
REQUIREMENTS SHALL BE DETERMINEDBY THE TRUSS DESIGNER/MANUFACTURER, BUT SHALL
CONSIST OF NOT LESS THAN 2-INCH BY 3-INCH LUMBER, DOUBLE NAILEDAT EACHTRUSS
LOCATION. SPACING OF BRIDGING SHALL NOT EXCEED8'-O" O.C.
7. WEB MEMBER PLANE BRIDGING SHALL BE DETERMINEDBY THE TRUSS
DESIGNER/MANUFACTURER.
8. METAL PLATE CONNECTEDWOOD TRUSSES SHALL BE DESIGNED, FABRICATED, ANDERECTEDIN
ACCORDANCE WITH THE CURRENT ANSI/TPI. THE TRUSS FABRICATOR SHALL SUPPLY ALL
HARDWARE ANDFASTENERS FOR J OINING MEMBERS SUPPLIEDBY THE TRUSS FABRICATORS.
9. CONTRACTOR SHALL NOT CUT, NOTCH OR BORE HOLES IN WOODTRUSSES UNLESS APPROVEDBY
THE WOODTRUSS DESIGNER.
10. CONTRACTOR SHALL BE RESPONSIBLE FOR TEMPORARY FIELD BRACING TO ASSURE ROOF
TRUSSES ARE INSTALLEDAT THE PROPER SPACING ANDTHAT THEY ARE STRAIGHT ANDPLUMB.
11. TRUSSES SHALL BE MANUFACTUREDIN A PLANT UNDER THE SUPERVISION OF A THIRD-PARTY
INSPECTION AGENCY.
12. EACH OF THE TRUSSES SHALL BE IDENTIFIEDBY A STAMP INDICATING THE TRUSS SERIES, NER OR
ICBO ES EVALUATION REPORT NUMBER, MANUFACTURER'S NAME, PLANT NUMBER ANDTHE
INDEPENDENT INSPECTION AGENCY'S LOGO.
13. OPEN WEB TRUSSES, IF STOREDPRIOR TO INSTALLATION, SHALL BE STOREDINA VERTICAL
POSITION ANDPROTECTEDFROMTHE WEATHER. THEY SHALL BE HANDLEDWITHCARE SO THEY
ARE NOT DAMAGED. THEY ARE TO BE INSTALLEDIN ACCORDANCE WITH THE PLANS ANDANY
J OIST DRAWINGS ANDINSTALLATION SUGGESTIONS. TEMPORARY CONSTRUCTION LOADS THAT
CAUSE STRESSES BEYONDDESIGN LIMITS ARE NOT PERMITTED. INSTALLATION BRACING IS TOBE
PROVIDEDBY THE TRUSS SUPPLIER TO KEEP THE TRUSSES STRAIGHT ANDPLUMB AS REQUIRED
ANDTO ENSURE ADEQUATE LATERAL SUPPORT FOR THE INDIVIDUAL TRUSSES ANDTHE ENTIRE
SYSTEMUNTIL THE SHEATHING MATERIAL HAS BEENAPPLIED.
14. THE PRODUCTS DELIVEREDSHALL BE FREE FROMMANUFACTURING ERRORS OR DEFECTS IN
WORKMANSHIP ANDMATERIAL. THE PRODUCTS WHEN CORRECTLY INSTALLEDANDMAINTAINED
SHALL BE WARRANTEDTO PERFORMAS DESIGNEDFOR THE NORMAL ANDEXPECTEDLIFE OF THE
BUILDING.
15. CODE COMPLIANT DESIGN OF WOOD ROOF TRUSSES IS A DEFERREDSUBMITTAL INACCORDANCE
WITH THE GENERAL STRUCTURAL NOTES, NOTE 14A. SUBMITTAL DOCUMENTS SHALL INCLUDE
SUBSTANTIATING STRUCTURAL CALCULATIONS. CALCULATIONS ANDDRAWINGS SHALL BE
STAMPEDANDSIGNEDBY A REGISTEREDPROFESSIONAL ENGINEER IN THE STATE OF
TEXAS. SUBMITTAL DOCUMENTS SHALL BE SUBMITTEDTO THE EOR FOR REVIEWOF CONFORMITY
WITH THESE DOCUMENTS ANDTO THE CITY FOR PLAN CHECK ANDCODE REVIEWPRIOR TO
INSTALLATION.
PROVIDE MIN. 2x6VERTICAL
TRUSS MEMBER AT TOWER WALL
2
'-0
"
2
'-0
"
BEARING ON WALL, GIRDER TRUSS
OR BEAM- REF. PLAN
TRUSS DIAGRAMS
N.T.S. S006
1
NUMBER F-51
FIRMREGISTRATION
21834 Northwest Freeway
Cypress, TX 77429
281-664-1600
Fax 281-664-1601
www.barryengineering.com
DRAWING NUMBER:
DRAWINGTITLE:
REVISIONS: DATE: NO.
LANDLORDREVIEWISSUE DATE:
TENANT REVIEWISSUE DATE:
BID ISSUE DATE:
PERMIT ISSUE DATE: 4-25-2013
CONSTRUCTIONISSUE DATE:
PROJ ECT NO.:
DRAWN BY: TP
CHECKED BY: MB
103 Carlos G. Parker
Blvd., N.W.
Taylor, TX 76574
engineer is an offense under the
on this document was authorized
The seal and signature appearing
by Michael E. Barry, P.E. 82583
a sealed document without proper
notification to the responsible
Texas EngineeringAct.
on the signed date above. Alterationof
BEI PROJ ECT #: 13-020
REVISION1 1 5-21-13
HSS
5x5x1/4
8'-1 1/4" 31'-8" 31'-9 1/2" 12'-8 3/4"
1
'-2
3
/4
"
2
5
'-7
1
/2
"
1
8
'-7
1
/4
"
1
4
'-3
1
/4
"
1
'-2
3
/4
"
#
PLAN LEGENDS:
H1 = HEADER PER SCHEDULE 5/S003.
SIMPSON CS16 STRAP PER 7A/S004.
WALL WITH HEADER OVER OPENING
PER DETAILS 4&5/S003.
W16
BEAMSIZE
AS REQ'D
COLUMN SIZE
AS REQ'D HSS5x5
T1
TRUSS DESIGNATION
PER 1/S005
H2 H2 H2
H1 H1
HSS
5x5x1/4
HSS
5x5x1/4
HSS
5x5x1/4
HSS
5x5x1/4(HIGH)
HSS
5x5x1/4
HSS
5x5x1/4
HSS
5x5x1/4
H
2
H
2
H
2
H1
H3 H3
H4
H
6
H
1
H
2
H
2
H
2
H
4
H
4
H
5
H
4
H
4
W
1
6
x
4
0
W
1
6
x
2
6
W
1
6
x
2
6
T1
T1
T1
T1
T1
T1
T1
T2
T2
T2
T2
T2
T2
T2
T2
T2
T2
T2
T2
T2
T2
T2
T2
T2
T2
T2
T2
T2
T3
T3
T3
T3
T3
T3
T3
T3
T3
T3
T3
T3
T3
T3
T3
T3
T3
T3
T3
T3
T3
T5
T4
T4
T4
T4
T4
T4
T4
T4
T4
T4
T4
T4
T4
T4
T4
T4
T4
T5
T5
T5
T4
T4
T4
T4
T4
T4
T4
G
T
G
T
G
T
G
T
G
T
G
T
G
T
G
T
G
T
G
T
G
T
G
T
G
T
G
T
G
T
HSS
5x5x1/4
HSS
5x5x1/4
HSS
5x5x1/4
HSS
5x5x1/4
HSS 8x4x1/4
HSS 8x4x1/4
H
S
S
8
x
4
x
1
/4
H
S
S
8
x
4
x
1
/4
G
T
G
T
T4
T4
T4
T4
T4
G
T
T4
T4
T4
T4
T4
T4
T5
G
T
G
T
G
T
G
T
G
T
G
T
G
T
G
T
G
T
G
T
T3
T3
T3
T3
T3
T3
G
T
G
T
G
T
G
T
G
T
G
T
G
T
G
T
T3
T3
T3
T3
T3
T3
T3
T3
T3
2
x
8
@
2
4
"
O
.C
.
5'-2 1/4"
W16x26
T5 T4
T4
T4 T5
T5
T5
PROVIDE 3-2x10BLOCKING BETWEEN
TRUSSES - FASTEN TO VERTICAL TRUSS
MEMBERS WITH SIMPSON LUS210-3
SIMPSON CS16x10' LONG
SIMPSON CS16x10' LONG SIMPSON CS16x10' LONG
SIMPSON CS16x10' LONG
H4
1. REFER TO S006FOR PREFABRICATED WOOD TRUSS PROFILES.
2. UNLESS SHOWN OR NOTEDOTHERWISE, ALL NAILS ARE COMMON NAILS. UNLESS SHOWN OR
NOTEDOTHERWISE, WOOD MEMBERS SHALL BE CONNECTEDPER FASTENING SCHEDULE IN
CHAPTER 23, TABLE 2304.9.1OF THE INTERNATIONAL BUILDING CODE U.N.O.
3. CONTRACTOR SHALL COORDINATE UNDER HUNG EQUIPMENT WITH ARCH &TRUSS SUPPLIER.
4. TRUSS SUPPLIER SHALL COORDINATE RTU OPENING REQUIREMENTS w/ TRUSS SPACING.
TRUSSES MAY REQUIRE SPACING LARGER THAN 24" O.C. THEREFORE TRUSS SUPPLIER SHALL
PROVIDE GIRDER TRUSSES, BLOCKING &BRIDGING AS REQ'DPER MEP DWGS.
5. TRUSS SUPPLIER SHALL DESIGN BOTTOMCHORDOF TRUSS FOR ADDITIONAL 50PLF FOR
ARCHITECTURAL SOFFIT. REF. ARCH DWGS FOR LOCATIONS
PLAN NOTES:
T3
T3
T4
T3
T3
T3
T3
DESIGN TRUSSES FOR ADDITIONAL WALL
LINE LOAD OF 400 PLF DL AND200PLF LL
FROMTOWER
ROOF FRAMING PLAN
1/4" =1'-0" S201
1
NORTH
NUMBER F-51
FIRMREGISTRATION
21834 Northwest Freeway
Cypress, TX 77429
281-664-1600
Fax 281-664-1601
www.barryengineering.com
DRAWING NUMBER:
DRAWINGTITLE:
REVISIONS: DATE: NO.
LANDLORDREVIEWISSUE DATE:
TENANT REVIEWISSUE DATE:
BID ISSUE DATE:
PERMIT ISSUE DATE: 4-25-2013
CONSTRUCTIONISSUE DATE:
PROJ ECT NO.:
DRAWN BY: TP
CHECKED BY: MB
103 Carlos G. Parker
Blvd., N.W.
Taylor, TX 76574
engineer is an offense under the
on this document was authorized
The seal and signature appearing
by Michael E. Barry, P.E. 82583
a sealed document without proper
notification to the responsible
Texas EngineeringAct.
on the signed date above. Alterationof
BEI PROJ ECT #: 13-020
REVISION1 1 5-21-13
HIGH ROOF FRAMING PLAN
1/4" =1'-0" S201
2
NORTH
8'-1 1/4" 31'-8" 31'-9 1/2" 12'-8 3/4"
1
'-2
3
/4
"
2
5
'-7
1
/2
"
1
8
'-7
1
/4
"
1
4
'-3
1
/4
"
1
'-2
3
/4
"
PLAN LEGENDS:
LATERAL SHEAR WALL PER 2/S004. REFER TO SHEET S004FOR SHEAR
BLOCKING REQUIREMENTS.
5'-2 1/4"
SHEAR WALL FRAMING PLAN
1/4" =1'-0" S202
1
NORTH
NUMBER F-51
FIRMREGISTRATION
21834 Northwest Freeway
Cypress, TX 77429
281-664-1600
Fax 281-664-1601
www.barryengineering.com
DRAWING NUMBER:
DRAWINGTITLE:
REVISIONS: DATE: NO.
LANDLORDREVIEWISSUE DATE:
TENANT REVIEWISSUE DATE:
BID ISSUE DATE:
PERMIT ISSUE DATE: 4-25-2013
CONSTRUCTIONISSUE DATE:
PROJ ECT NO.:
DRAWN BY: TP
CHECKED BY: MB
103 Carlos G. Parker
Blvd., N.W.
Taylor, TX 76574
engineer is an offense under the
on this document was authorized
The seal and signature appearing
by Michael E. Barry, P.E. 82583
a sealed document without proper
notification to the responsible
Texas EngineeringAct.
on the signed date above. Alterationof
BEI PROJ ECT #: 13-020
REVISION1 1 5-21-13
PLAN VIEW PLAN VIEW AT CORNER
SECTION
T.O. SLAB
ELEV PER
PLAN
PROVIDE (2) - #5CORNER BARS X
TOP ANDBOTTOMAT ALL GRADE
BEAMENDINTERSECTIONS AND
CORNERS.
PROVIDE SAME SIZE
NUMBER ANDSPACING
AS HORIZONTAL BAR
REINFORCING
TYPICAL GRADE BEAM INTERSECTION
NTS S302
1
NOT USED
S302
4
NOT USED
S302
8
NOT USED
S302
5
NOT USED
S302
9
NOT USED
S302
6
NOT USED
S302
10
NOT USED
S302
7
NOT USED
S302
11
NOT USED
S302
3
NUMBER F-51
FIRMREGISTRATION
21834 Northwest Freeway
Cypress, TX 77429
281-664-1600
Fax 281-664-1601
www.barryengineering.com
DRAWING NUMBER:
DRAWINGTITLE:
REVISIONS: DATE: NO.
LANDLORDREVIEWISSUE DATE:
TENANT REVIEWISSUE DATE:
BID ISSUE DATE:
PERMIT ISSUE DATE: 4-25-2013
CONSTRUCTIONISSUE DATE:
PROJ ECT NO.:
DRAWN BY: TP
CHECKED BY: MB
103 Carlos G. Parker
Blvd., N.W.
Taylor, TX 76574
engineer is an offense under the
on this document was authorized
The seal and signature appearing
by Michael E. Barry, P.E. 82583
a sealed document without proper
notification to the responsible
Texas EngineeringAct.
on the signed date above. Alterationof
BEI PROJ ECT #: 13-020
REVISION1 1 5-21-13
NOT USED
S302
2
S 2x6STUDWALL L
AWNING &
ATTACHMENTS
PER ARCH
T.O. OPENING
ELEV PER ARCH
BLOCKING &FLASHING
PER ARCH
TRUSS PER
PLAN
BLOCKING TRUSS AS
REQUIREDPER 7/S004
DOUBLE TOP PLATE
PER OTHER DETAILS
EXTERIOR FINISH
REF. ARCH FOR TYPE
ROOF SHEATHING
PER PLAN
TOP PLATE PER
OTHER DETAILS
2x6LEDGER CONT
GLAZING SYSTEM
PER ARCH
HEADER BEAM
PER PLAN T.O. OPENING
ELEV PER ARCH
HEADER BEAM
PER PLAN
TOP PLATE
PER OTHER DETAILS
EXTERIOR FINISH
REF. ARCH FOR TYPE
S 2x6STUDWALL L
BLOCKING &FLASHING
PER ARCH
TRUSS PER
PLAN
DOUBLE TOP PLATE
PER OTHER DETAILS
EXTERIOR FINISH
REF ARCH FOR TYPE
ROOF SHEATHING
PER PLAN
TOP PLATE PER
OTHER DETAILS
2x6LEDGER CONT
BLOCKING TRUSS AS
REQUIREDPER 7/S004
S 2x6STUDWALL L
T.O. OPENING
ELEV PER ARCH
BLOCKING &FLASHING
PER ARCH
TRUSS PER
PLAN
DOUBLE TOP PLATE
PER OTHER DETAILS
EXTERIOR FINISH
REF ARCH FOR TYPE
ROOF SHEATHING
PER PLAN
TOP PLATE PER
OTHER DETAILS
2x6LEDGER CONT
GLAZING SYSTEM/
OPENING PER ARCH
HEADER BEAM
PER PLAN
S 2x6STUDWALL L
TRUSS PER
PLAN (TYP)
2x6STUDWALL
PER PLAN
AWNING &
ATTACHMENTS
PER ARCH
HEADER BEAM
PER PLAN
GLAZING SYSTEM
PER ARCH
T.O. OPENING
ELEV PER ARCH
BLOCKING &FLASHING
PER ARCH
TOP PLATE PER
OTHER DETAILS
8d NAILS @
6" O.C.
2x6BLOCK
@ 24" O.C.
EXTERIOR FINISHES
REF ARCH FOR TYPE
T.O. OPENING
ELEV PER ARCH
2x STUDWALL
PER PLAN
HEADER BEAM
PER PLAN
HEADER BEAM
PER PLAN
T.O. OPENING
ELEV PER ARCH
BOUNDARY NAIL
PATTERN N1PER 3/S004
OR GENERAL NOTES
SEC
B-B
SECTION B-B
CONT 2xNAILER
FASTEN TO BEAM
W/D.177"x21
2" LONG
SHOT PINS @12" O.C.
TOP AND BOTTOM
STAGGERED.
NAIL SHEATHING TO
FACE OF RAFTERS
EXTERIOR FINISH
REF ARCH FOR TYPE
TOE NAIL OTHER SIDE w/ (2)
SIMPSON SDS 1/4x3 1/2
WOODSCREWS AS REQ'D
TOP PLATE PER
OTHER DETAILS
NAIL SHEATHING TO
FACE OF RAFTERS
LAP LEDGER SPLICE w/
SIMPSON MSTA 30STRAP
TIE w/ FULL FASTENERS
2X6LEDGER CONT
BOUNDARY NAIL
PATTERN N1PER 3/S004
OR GENERAL NOTES
STEEL BEAMPER PLAN
CONT 2xNAILER
FASTEN TO BEAM
W/D.177"x21
2" LONG
SHOT PINS @12" O.C.
TOP AND BOTTOM
STAGGERED.
COUNTERSINK BOLTS
IN TOP MEMBER REF
02/S402 FOR NAILER
ATTACHMENT
S 2x6STUDWALL L
TRUSS PER
PLAN (TYP)
2x6STUDWALL
PER PLAN
BLOCKING &FLASHING
PER ARCH
TOP PLATE PER
OTHER DETAILS
8d NAILS @
6" O.C.
LAP LEDGER SPLICE w/
SIMPSON MSTA 30STRAP
TIE w/ FULL FASTENERS
2x6BLOCK
@ 24" O.C.
SECTION
3/4" =1'-0" S401
1 SECTION
3/4" =1'-0" S401
2 SECTION
3/4" =1'-0" S401
3 SECTION
3/4" =1'-0" S401
4
SECTION
3/4" =1'-0" S401
5 SECTION
3/4" =1'-0" S401
8 SECTION
3/4" =1'-0" S401
7 SECTION
3/4" =1'-0" S401
6
NUMBER F-51
FIRMREGISTRATION
21834 Northwest Freeway
Cypress, TX 77429
281-664-1600
Fax 281-664-1601
www.barryengineering.com
DRAWING NUMBER:
DRAWINGTITLE:
REVISIONS: DATE: NO.
LANDLORDREVIEWISSUE DATE:
TENANT REVIEWISSUE DATE:
BID ISSUE DATE:
PERMIT ISSUE DATE: 4-25-2013
CONSTRUCTIONISSUE DATE:
PROJ ECT NO.:
DRAWN BY: TP
CHECKED BY: MB
103 Carlos G. Parker
Blvd., N.W.
Taylor, TX 76574
engineer is an offense under the
on this document was authorized
The seal and signature appearing
by Michael E. Barry, P.E. 82583
a sealed document without proper
notification to the responsible
Texas EngineeringAct.
on the signed date above. Alterationof
BEI PROJ ECT #: 13-020
REVISION1 1 5-21-13
1/4
L3x3x1
4"x3"
BEARING SEAT
1/4 HSS REF
PLAN
TOP CHORDBRG
PREFABRICATED
WOODTRUSS PER PLAN.
STAGGER TRUSSES
SO EA TRUSS
BEARS FULLY ON
TOP PLATE
SHEAR WALL PER PLAN
ROOFING/INSULATION
PER ARCH
ROOF SHEATHING
PER PLAN
2-2x TOP PLATE
CONTINUOUS 2-2x6 BLOCKING OVER SHEAR WALLS
SIMPSON LTP4@24" O.C.
10d NAILS @6"O.C. ROOF DECKING ANDFASTENING PER
GENERAL NOTES
7A
S004
TOP CHORDBRG
PREFABRICATED
WOOD TRUSS.
STAGGER TRUSSES
SO EA TRUSS
BEARS FULLY ON
WOODNAILER
STEEL BEAMPER PLAN
1
2" THRU BOLTS @
12"O.C. STAGGERED
ROOFING/INSULATION
PER ARCH
ROOF SHEATHING
PER PLAN
SIMPSON H2.5A
ANCHOR EACH
ENDOF TRUSS
2-2xCONTINUOUS NAILER
TO MATCH BEAMFLANGE
WIDTH.
TRUSS PER PLAN
S 2x STUDWALL L
EXTERIOR FINISH
REF ARCH FOR TYPE
TOP PLATE PER
OTHER DETAILS
COOLER/FREEZER
PER ARCH
ROOFING &INSULATION
PER ARCH
NOTE:
SEE OTHER DETAILS FOR
PARAPET INFORMATION.
2x6STUD WALL PER PLAN.
PROVIDE (2) 2x6STUDS
BELOWEA TRUSS BEARING
LOCATION
BLOCKING TRUSS AS
REQUIREDPER 7/S004
SIMPSON H2.5A
ANCHOR
STEEL BEAMPER PLAN
L3x3x
1
4"x4"
NEAR SIDE
ANDFAR SIDE
OF COLUMN.
HSS TOWER
COLUMN
3
8" STIFFENER PLATE EACH
SIDE @ COLUMN BEARING
1/4
B
TOE NAIL OTHER SIDE w/ (2)
SIMPSON SDS 1/4x3 1/2
WOODSCREWS AS REQ'D
EXTERIOR FINISH
REF ARCH FOR TYPE
HEADER BEAM
PER PLAN
GLAZING SYSTEM
PER ARCH
T.O. OPENING
ELEV PER ARCH
TRUSS
ATTACHMENT TO
TOP PLATE PER
TRUSS SUPPLIER
PROVIDE MIN. 2x6
VERTICAL TRUSS
MEMBER @ TOWER
WALL
SHEATHING AS
SPECIFIED
6x6POST
PER PLAN
SIMPSON
HUCQ612-SDS
(TYP)
HEADER PER
PLAN (TYP)
SIMPSON
HGA10kt (TYP)
SEC
A-A
TYP
SECTION A-A
SIMPSON
HUCQ612-SDS
6x6POST
PER PLAN
SIMPSON HGA10kt
HEADER
PER PLAN
TYP HSS BEAM TO HSS COLUMN
3/4" =1'-0" S402
1
SECTION
3/4" =1'-0" S402
6
SECTION
3/4" =1'-0" S402
2 SECTION
3/4" =1'-0" S402
3
SECTION
3/4" =1'-0" S402
5 SECTION
1 1/2" =1'-0" S402
7
SECTION
3/4" =1'-0" S402
4
NUMBER F-51
FIRMREGISTRATION
21834 Northwest Freeway
Cypress, TX 77429
281-664-1600
Fax 281-664-1601
www.barryengineering.com
DRAWING NUMBER:
DRAWINGTITLE:
REVISIONS: DATE: NO.
LANDLORDREVIEWISSUE DATE:
TENANT REVIEWISSUE DATE:
BID ISSUE DATE:
PERMIT ISSUE DATE: 4-25-2013
CONSTRUCTIONISSUE DATE:
PROJ ECT NO.:
DRAWN BY: TP
CHECKED BY: MB
103 Carlos G. Parker
Blvd., N.W.
Taylor, TX 76574
engineer is an offense under the
on this document was authorized
The seal and signature appearing
by Michael E. Barry, P.E. 82583
a sealed document without proper
notification to the responsible
Texas EngineeringAct.
on the signed date above. Alterationof
BEI PROJ ECT #: 13-020