3.

Tablero A: panel de distribucin de 30 circuitos, de 3 fases, 277/480V.


Ia = 700 amp, Ib = 700 amp, Ic = 752 amp.
Tablero B: panel de distribucin de 18 circuitos, de 3 fases, 120/208 V.
Ia = 92 amp, Ib = 87 amp, Ic = 82 amp.
Tablero C: panel de distribucin de 30 circuitos, de 3 fases, 120/208 V.
Ia = 41 amp, Ib = 38 amp, Ic = 38 amp.
Tablero F: panel de distribucin de 30 circuitos, de 3 fases, 277/480 V.
3 Mot de Ind. 10 Hp, 2 Mot. R.D. 5 Hp., Y 2 Mot R.D. de 15 Hp.
Todos los Mot son de 3 fases.

Calcule toda la informacin restante. INCLUYA EL MDP, EL ATS, LAS PROTECCIONES, LOS
TRANFORMADORES Y EL INTERRUPTOR PRICIPAL. TOME EN CUENTA QUE EL FACTOR DE
POTENCIA ES DE 83% Y QUE SE DEBE LLEVAR A 94% EN EL INTERRUPTOR PRINCIPAL.
El transformador esta a 55 pies del IP, el MDP est a 35 pies del IP y todos los tableros estn a
122 pies del MD

Tablero F
MOTOR

Ind. 10 HP

14

16

30

Overloa
d
(1.15 x
In)
16

Ind. 10 HP

14

16

30

16

18

Ind. 10 HP

14

16

30

16

18

R.D

7.6

20

10

5 HP

I
nominal
(Amp)

Desconecta
dor
(1.15 x In)

1.25x
In
18

Circuito Ramal
Conductores
3C#12 THHN + 1C#10AWG
de
3C#12 THHN + 1C#10AWG
de
3C#12 THHN + 1C#10AWG
de
3C#12 THHN + 1C#10AWG
de

1 tubo PVC
1 tubo PVC
1 tubo PVC
1 tubo PVC

Protecciones
De 3p T.I
2.5 x
In
2.5 x
In
2.5 x
In
1.5 x
In

35

40

35

40

35

40

11

20

R.D

5 HP

7.6

20

10

R.D

15 HP

21

24

30

24

26

R.D 1 5 HP

21

24

30

24

26

3C#12 THHN + 1C#10AWG 1 tubo PVC


de
3C#10 THHN + 1C#10AWG 1 tubo PVC
de
3C#10 THHN + 1C#10AWG 1 tubo PVC
de

1.5 x
In
1.5 x
In
1.5 x
In

I sin M ms grande= 78.2 A


Ip en el TF= 99.2 A
21x1.25 + 21 + 7.6 + 7.6 + 14 + 14 + 14= 104.5 A
40 + 78.2 = 118.2
104.5 A
A/3p

3 C# 2 THHN + C#2/0 AWG 1 tub PVC de 1 de dimetro

118.2A

TABLERO 1 PARA EL MDP


CIRCUITO RAMAL
CARGA
S

TA
TF

In
(Amp)

752
99.2

PROT DE
3P T.I.

1.25 X In

940 A
(21X1.25 +
78.2)= 104.5
A

3C#500 kcm THHN/fase +


3C#500 kcm THHN + 1C#2/0
AWG
en 3 tubos PVC de 3 de

800

3C #2 THHN + 1 C#2/0
AWG
1 tub PVC de 1 de

104. 110
5

110

11

20

32

40

32

40

IP
TX

851.2X1. 3C#500 kcm THHN/fase + 3C#500


kcm THHN + 1 C#2/0 AWG
25 =
en
3 tubos PVC de 3 de
1064 A

851.2
P=1.73
VI
I=851.2
707.7
kVA

100
0

V=480
707.7/0.83=
853 kVA

TX = 1000 KVA EN 277/480

Corriente en el tablero TA es 940 A..........utilizando un cable de 500 kcmil que maneja 380 A, 940/380=
2.47 cables......se utilizaran 3 cables 500 kcm
Corriente del IP es 1064 A..........utilizando un cable de 500 kcmil que maneja 380 A, 1064/380= 2.8
cables......se utilizaran 3 cables 500 kcm
1000 A /3P
TABLERO 2 PARA EL MDP
CIRCUITO RAMAL
CARGA
S

In
(Amp)

1.25 X In
115 A

TB

92
51.3 A

TC
IP

41
133

PROT DE
3P T.I.

133X1.25 =
166.25 A

4C #2 THHN + 1 C#8
AWG
1 tub PVC de 1 de
4C #6 THHN + 1 C#10
AWG 1 tub PVC de
de
4C#2/0 THHN + 1 C#6
AWG en 1 tubo PVC de

100
50
141
A

150

2 de
TX

P=1.73
VI
I=133
47.92
kVA

V=208
47.92/0.83=
57.74 kVA

TX = 75 KVA EN 120/208

La proteccin 150 A /3P

CAIDAS DE VOLTAJE

Vc= 2 500 x851.2X55/1000x3cond = 0.83 V (Tx al


Ip)
%V= (0.83 V/277V) X100= 0.30%

Vc= 2IL/1000

Vc= 2 500 x851.2X35/1000 x3cond= 0.53 V (Ip al


MDP)
%V= (0.53 V /277V) X100= 0.19%
Vc= 2 500 x752X122/ (1000x3cond) = 1.62 V (MDP
al TA)
%V= (1.62 V /277V) X100= 0.58%
Vc= 2 2 x99.2X122/1000 = 4.87 V (MDP al TF)

Resistividad:

500= 0.0265 /Kpies


2 = 0.201 /Kpies
1 = 0.160 /Kpies
0.30% + 0.19% + 1.76%= 2.25 % 5%
0.30% + 0.19% + 0.58%= 1.07 % 5%
Conductores dentro del lmite de cada

Vc= 2 2/0 x133X55/1000 = 1.48 V (Tx al Ip)


%V= (1.48 V/120V) X100= 1.23%
Vc= 2 2/0 x133X35/1000 = 0.94 V (Ip al MDP)
%V= (0.94 V /120V) X100= 0.784%

Resistividad:
2/0= 0.101 /Kpies
1/0= 0.127 /Kpies
2 = 0.201 /Kpies
6 = 0.510 /Kpies
4 = 0.321 /Kpies
3 = 0.254 /Kpies

Vc= 2 2 x92X122/1000 = 4.51 V (MDP al TA)


%V= (4.51 V /120V) X100= 3.76% (EXCESIVO)
Vc= 2 1/0 X92X122/1000 = 2.85 V
%V= (2.85 V /120V) X100= 2.38%
Vc= 2 2/0 X92X122/1000 = 2.27 V
%V= (2.27 V /120V) X100= 1.89% (para el limite 3%
Ip a la carga)
Vc= 2 6 x41X122/1000 = 5.10 V (MDP al TF)
%V= (5. 10 V /120V) X100= 4.25%(EXCESIVO)
Vc= 2 4X41X122/1000 = 3.21 V
%V= (3.21 V /120V) X100= 2.68%
Vc= 2 3X41X122/1000 = 2.54 V
%V= (2.54V /120V) X100= 2.12% (para el limite 3% Ip
a la carga)

1.23%+
1.23%+
1.23%+
1.23%+

0.784%+
0.784%+
0.784%+
0.784%+

2.38%=
2.68%=
1.89%=
2.12%=

4.39
4.69
3.90
4.13

%
%
%
%

5%
5%
5%
5%

Conductores redimensionados
Cambio de Cable de #4 a #1/0 y #6 a #4

CORRIENTE DE CORTOCIRCUITO

Ipc 3 = (1000 KVAx1000)/ (3x480) = 1203 A


Icc= 1203/0.06= 20050 Ampcc Simtrica
Z1= (500 X55/1000)/3=0.000486
Z2= (500 X35/1000)/3=0.000309
Z3= (2 X122/1000)/1=0.024522

Z4= (500 X122/1000)/3=0.00108

IccIp= 1203 / (0.06+ Z1)=19889 A


IccMDP= 1203 / (0.06+ Z1+ Z2)=19788 A
IccTF= [1203 / (0.06+ Z1+ Z2+ Z3)] + 21X7= 14247 A
Z4)=19442 A

IccTA= 1203 / (0.06+ Z1+ Z2+

Se puede utilizar tableros de 22 000 (todos los elementos con capacidades


interruptivas de 22 000)

Ipc 3 = (75 KVAx1000)/ (3x208) = 208.2 A


Icc= 208/0.03= 6933 Ampcc Simtrica
Z1= (2/0 X55/1000)/1=0.0005556
Z2= (2/0 X35/1000)/1=0.0003535
Z3= (1/0 X122/1000)/1=0.015494

Z4= (4 X122/1000)/1=0.03916

IccIp= 208 / (0.03+ Z1)=6813.8 A


IccMDP= 208 / (0.03+ Z1+ Z2)=6735.9 A
IccTB= 208 / (0.03+ Z1+ Z2+ Z3) = 4486.8 A
IccTC= 208 / (0.03+ Z1+ Z2+ Z4)=2971.4 A
Se puede utilizar tableros de 10 000 (todos los elementos con capacidades de 10
000)
BANCO DE CAPACITORES

Qi = S sen (cos-1 0.83) = 1000 sen (cos-1 0.83)


=557.6 KVA
Qf= S sen (cos-1 0.94) = 1000 sen (cos-1 0.94) =
341.18 KVA
Qnecesario= 557.6 - 341.18=216.4 KVA
Qnecesario 217.5 KVA 220 KVA

BANCO DE CAPACITORES

Qi = S sen (cos-1 0.83) = 75 sen (cos-1 0.83) =25.59


KVA
Qf= S sen (cos-1 0.94) = 75 sen (cos-1 0.94) = 41.83
KVA
Qnecesario= 25.59 - 41.83 =16.24 KVA
Qnecesario 20 KVA

DIAGRAMA UNIFILAR