GREATER DAMBULLA WATER SUPPLY PROJECT CONTRACT NO. P&P/WS/EB-INDIA/GDWSS/2011/01
This has reference to your letter No. WABAG-Dambulla/Site/Customer/1405 dated 05 th
September, 2014 and submitted on 09 th September, 2014 requesting the approval for MOC.
Please find below our comments in the same order as above reference.
SI NO ITEM MOC SUGGESTED BY CONTRACTOR OUR REPLY 1 All Ladders except in contact with water Galvanized Iron Not accepted. As per the clause 1.11.5 of civil specification, Ladders shall generally comply with BS 4211. Accordingly, the ladders shall be of designated class A conforming to MOC of Steel Grade 43C of BS 4360. All the other detailing (Bolts, Nuts, Protection coating, Dimension etc) shall conform to the above clause 1.11.5 and BS 4211. 2 Ladders in contact with water Stainless Steel Accepted. 3 Angles for trenches, chambers and manhole covers Galvanized Iron Accepted. Manhole and access covers and frames shall comply with BS 497: Part 1, heavy duty Grade A. Accordingly, manhole covers, inspection covers and frames (except in pipe lines) shall be of Cast iron coated with hot dipped galvanizing. 4 Chequered plates 10mm Aluminium Accepted. 5 Handrails for Intake, WTP and Inamaluwa pump house Stainless Steel Accepted. 6 Handrails for Distribution reservoirs Galvanized Iron Accepted.
Further, detailed drawings for ladders and handrail shall be submitted for approval.
Please be noted that the Clause 1.11.5 of Civil specification has no relationship to handrails of Galvanized Iron and we appreciate of providing Stainless steel handrails for the said locations.