You are on page 1of 140

‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬

‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺘﺤﺩﻴﺩ ﻗﺩﺭﺓ ﺍﻷﺤﻤﺎل ﺍﻟﻤﻴﻜﺎﻨﻴﻜﻴﺔ‬ ‫‪-١‬‬


‫ﺃﻋﻤﺎل ﺍﻟﻤﺼﺎﻋﺩ‬ ‫‪١-١‬‬
‫‪ ١-١-١‬ﻋﺎﻡ‬
‫ﺘﺴﺘﺨــﺩﻡ ﻭﺴﺎﺌــل ﺍﻟﻨﻘــل ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﻜﺎﻓــﺔ ﺃﻨـــﻭﺍﻉ ﺍﻟﻤﺒﺎﻨــﻰ‬ ‫)ﺃ(‬
‫ﺍﻟﺴﻜﻨﻴﺔ ﻭﺍﻟﺘﺠﺎﺭﻴﺔ ﻭﺍﻹﺩﺍﺭﻴﺔ ﻭﻤﺒﺎﻨﻰ ﺍﻟﺨﺩﻤﺎﺕ ﻜﻭﺴﻴﻠﺔ ﻟﻨﻘل ﺍﻟﺭﻜـﺎﺏ ﻭﺍﻟﺒﻀـﺎﺌﻊ‬
‫ﻭﺘﻜﻭﻥ ﺍﻟﺤﺭﻜﺔ ﻓﻰ ﻭﺴﺎﺌل ﺍﻟﻨﻘل ﺇﻤﺎ ﺭﺃﺴﻴﺔ ﻜﻤﺎ ﻓـﻰ ﻤﺼﺎﻋـــﺩ ﺍﻟﺭﻜــﺎﺏ‬
‫ﻭﺍﻟﺨﺩﻤـﺎﺕ ﻭﺍﻟﺒﻀﺎﺌــﻊ ﻭﻤﺼﺎﻋﺩ ﺍﻟﻤﺭﻀﻰ ﻭﻜﺫﻟﻙ ﻤﺼﺎﻋﺩ ﻨﻘل ﺍﻟﻁﻌﺎﻡ ﺒـﻴﻥ‬
‫ﺍﻷﺩﻭﺍﺭ ﻤﻥ ﺍﻟﻤﻁﺎﺒﺦ ﺃﻭ ﻓﻰ ﻨﻘل ﺍﻟﻭﺜﺎﺌﻕ ﺃﻭ ﺍﻟﻜﺘﺏ )‪ (Dumb waiter‬ﺃﻭ ﻤﺎﺌﻠﺔ ﻜﻤﺎ‬
‫ﻓﻰ ﺍﻟﺴﻼﻟــﻡ ﺍﻟﻤﺘﺤﺭﻜﺔ )‪ (Escalators‬ﺃﻭ ﺍﻟﻤﻨﺤﺩﺭﺍﺕ ﺍﻟﻤﺘﺤﺭﻜـﺔ )‪ (Ramps‬ﺃﻭ‬
‫ﺃﻓﻘﻴﺔ ﻜﻤﺎ ﻓﻰ ﺍﻷﺭﺼﻔﺔ ﻭﺍﻟﻤﺸﺎﻴﺎﺕ ﺍﻟﻤﺘﺤﺭﻜﺔ )‪.(Moving walks‬‬
‫ﻭﺘﻨﻘﺴﻡ ﻤﺼﺎﻋﺩ ﺍﻟﺭﻜﺎﺏ ﺇﻟﻰ ﺃﺭﺒﻌﺔ ﺃﻗﺴﺎﻡ ﺭﺌﻴﺴﻴﺔ‪:‬‬
‫‪ -‬ﻤﺼﺎﻋﺩ ﻟﻸﻏﺭﺍﺽ ﺍﻟﻌﺎﻤﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻰ ﺍﻟﺘﺠﺎﺭﻴﺔ‪.‬‬
‫‪ -‬ﻤﺼﺎﻋﺩ ﺍﻟﻤﺒﺎﻨﻰ ﺍﻟﺴﻜﻨﻴﺔ‪.‬‬
‫‪ -‬ﻤﺼﺎﻋﺩ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻰ ﺍﻟﻤﺅﺴﺴﻴﺔ‪.‬‬
‫‪ -‬ﻤﺼﺎﻋﺩ ﻓﻰ ﺍﻟﻤﺨﺎﺯﻥ‪.‬‬
‫)ﺏ( ﻭﻴﻤﻜﻥ ﺃﻥ ﺘﻜﻭﻥ ﻤﺼﺎﻋﺩ ﺍﻟﺭﻜﺎﺏ ﺇﻤﺎ ﻤﺠﺭﻭﺭﺓ ﺃﻭ ﺘﻌﻤل ﻫﻴﺩﺭﻭﻟﻴﻜﻴﺎﹰ‪.‬‬
‫ﻴﺘﻜﻭﻥ ﺍﻟﻤﺼﻌﺩ ﻤﻥ ﺍﻟﻜﺎﺒﻴﻨﺔ‪ ،‬ﻜﺎﺒﻼﺕ ﺍﻟﺠﺭ‪ ،‬ﻤﺎﻜﻴﻨﺎﺕ ﺍﻟﻤﺼﻌﺩ ﻭﻤﻌـﺩﺍﺕ ﺍﻟـﺘﺤﻜﻡ‬
‫ﻭﺜﻘل ﺍﻟﻤﻭﺍﺯﻨﺔ ﻭﺩﻻﺌل ﺍﻟﺤﺭﻜﺔ‪.‬‬
‫)ﺕ( ﺘﻘــﻭﻡ ﺍﻟﻤﺎﻜﻴﻨـﺎﺕ ﺒﺠـﺭ ﺍﻟﻜﺎﺒﻴﻨـﺔ ﻋــﻥ ﻁﺭﻴـﻕ ﻤﺠﻤﻭﻋـﺔ ﻤﺘﻭﺍﺯﻴﺔ ﻤﻥ‬
‫ﺍﻟﺤﺒﺎل )ﻤﻥ ‪ ٤‬ﺇﻟﻰ ‪ ٨‬ﺍﻋﺘﻤﺎﺩﺍﹰ ﻋﻠﻰ ﺴﺭﻋﺔ ﺍﻟﻜﺎﺒﻴﻨﺔ ﻭﺤﻤﻭﻟﺘﻬـﺎ‪ ،‬ﻭﻴﺘـﻭﺯﻉ ﻭﺯﻥ‬
‫ﺍﻟﻜﺎﺒﻴﻨﺔ ﺒﺤﻤﻭﻟﺘﻬﺎ ﺒﻴﻥ ﻫﺫﻩ ﺍﻟﺤﺒﺎل ﺒﺎﻟﺘﺴﺎﻭﻯ(‪.‬‬
‫)ﺙ( ﺘﻤﺭ ﺍﻟﺤﺒﺎل ﺍﻟﻤﺜﺒﺘﺔ ﺒﺄﻋﻠﻰ ﺍﻟﻜﺎﺒﻴﻨﺔ ﻓﻭﻕ ﻁﺎﺭﺓ ﺫﺍﺕ ﻤﺠﺎﺭﻯ ﻴﺘﻡ ﺘﺩﻭﻴﺭﻫﺎ ﺒﻭﺍﺴـﻁﺔ‬
‫ﻤﺎﻜﻴﻨﺔ ﺍﻟﺠﺭ ﺍﻟﺘﻰ ﻴﺩﻴﺭﻫﺎ ﻤﺤﺭﻙ ﺜﻡ ﺘﻤﺭ ﺇﻟﻰ ﺃﺴﻔل ﺤﻴﺙ ﺜﻘل ﺍﻟﻤﻭﺍﺯﻨﺔ‪.‬‬
‫)ﺝ( ﻋﻨــﺩ ﻤــﺭﻭﺭ ﺍﻟﺤﺒــﺎل ﻓــﻭﻕ ﺍﻟﻁﺎﺭﺓ ﺍﻟﺘﻰ ﺘﺤﺘﻭﻯ ﻋﻠﻰ ﻤﺠﺎﺭﻯ ﻟﻬـﺫﻩ‬
‫ﺍﻟﺤﺒﺎل‪ ،‬ﻓــﺈﻥ ﻗــﺩﺭﺓ ﺍﻟﺭﻓــﻊ ﺘﺘــﻡ ﺒﻭﺍﺴﻁﺔ ﺍﻟﻁﺎﺭﺓ ﻤﻥ ﺨﻼل ﺍﻟﺤﺒـﺎل‬
‫ﻓﻰ ﻤﺠﺎﺭﻴﻬﺎ‪ ،‬ﻭﻴﺴﻤــﻰ ﺍﻟﻨﻅــﺎﻡ ﻓﻰ ﻫــﺫﻩ ﺍﻟﺤﺎﻟــﺔ ﻨﻅﺎﻡ ﻤﺯﻭﺩ ﺒﻤﺎﻜﻴﻨﺔ‬
‫ﺠﺭ ﺃﺤﺎﺩﻴﺔ ﺍﻟﻠﻔﺔ ) ‪ ،(Single-wrap traction machine‬ﻭﻴﺒـﻴﻥ ﺸـﻜل )‪) (١-١‬ﺃ(‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺍﻟﺒﻜﺭﺍﺕ ﺤﻴــﺙ ﺘﺴﻤﻰ ﺍﻟﺒﻜـﺭﺓ )‪" (S‬ﺒﻜــﺭﺓ ﺍﻟـﺩﻟﻴل" )‪(Deflector sheave‬‬


‫ﻭﺍﻟﺒﻜـﺭﺓ )‪" (T‬ﺒﺒﻜﺭﺓ ﺍﻟﺠﺭ" )‪.(Traction sheave‬‬
‫)ﺡ( ﻴﺒﻴﻥ ﺸﻜل )‪) (١-١‬ﺏ( ﺍﻟﺤﺒﺎل ﻤﻠﻔﻭﻓﺔ ﻋﻠﻰ ﺒﻜﺭﺓ ﺍﻟﺠﺭ ﻗﺎﺩﻤﺔ ﻤﻥ ﺍﻟﻜﺎﺒﻴﻨـﺔ ﺜـﻡ‬
‫ﻋﻠﻰ ﺍﻟﺒﻜﺭﺓ ﺍﻟﺜﺎﻨﻭﻴﺔ )‪ (S‬ﻭﻫﻰ ﺒﻜﺭﺓ ﻨﻘل ﺤﺭﻜﺔ )‪ (Idle sheave‬ﺜﻡ ﻤـﺭﺓ ﺃﺨـﺭﻯ‬
‫ﺤﻭل ﺒﻜﺭﺓ ﺍﻟﺠﺭ )‪ (T‬ﺜﻡ ﺇﻟﻰ ﺍﻟﺒﻜﺭﺓ )‪ (S‬ﺜﻡ ﺇﻟﻰ ﺜﻘل ﺍﻟﻤﻭﺍﺯﻨـﺔ‪ ،‬ﻭﻴﻁﻠـﻕ ﻋﻠـﻰ‬
‫ﻁﺭﻴﻘﺔ ﺍﻟﺘﻌﻠﻴﻕ ﺍﻟﻤﺒﻴﻨﺔ ﻓﻰ ﺸﻜل )‪) (١-١‬ﺃ‪،‬ﺏ( ﺒﺄﻨﻬﺎ ﻁﺭﻴﻘﺔ ﺒﻨﺴﺒﺔ ﺘﺤﻤﻴـل ‪،١:١‬‬
‫ﻭﻴﺤﻘﻕ ﻨﻅﺎﻡ ﺍﻟﻤﺎﻜﻴﻨﺔ ﺜﻨﺎﺌﻴﺔ ﺍﻟﻠﻔﺔ )‪ (Double-wrap‬ﻗﻭﺓ ﺸﺩ ﺃﻜﺒـﺭ ﻤـﻥ ﺍﻟﺤﺎﻟـﺔ‬
‫ﺃﺤﺎﺩﻴﺔ ﺍﻟﻠﻔﺔ‪ ،‬ﻭﻟﺫﺍ ﺘﺴﺘﺨﺩﻡ ﻫﺫﻩ ﺍﻟﻁﺭﻴﻘﺔ ﻓﻰ ﺤﺎﻟـﺔ ﺍﻟﺘﺭﻜﻴﺒـﺎﺕ ﺫﺍﺕ ﺍﻟﺴـﺭﻋﺎﺕ‬
‫ﺍﻟﻌﺎﻟﻴﺔ‪.‬‬

‫ﺻﺎﻋﺪة‬ ‫ﺛﻘﻞ‬
‫اﻟﻤﻮازﻧﺔ‬

‫)أ(‬ ‫)ب(‬ ‫)ﺟـ(‬


‫‪1:1‬‬ ‫‪1:1 Roping‬‬ ‫‪2:1 Roping‬‬ ‫)د(‬ ‫)ھـ(‬
‫‪Roping‬‬ ‫‪double‬‬ ‫‪double‬‬ ‫‪1:1 Roping‬‬ ‫‪2:1 Roping,‬‬
‫‪single‬‬ ‫‪wrap‬‬ ‫‪wrap‬‬ ‫‪underslung‬‬
‫ﻣﺎﻛﯿﻨﺔ اﻟﻤﺼﻌﺪ ﻣﺮﻛﺒﺔ أﻋﻠﻰ اﻟﻤﺒﻨﻰ‬ ‫ﻣﺎﻛﯿﻨﺔ اﻟﻤﺼﻌﺪ ﻣﺮﻛﺒﺔ ﺑﺎﻟﺒﺪروم‬

‫ﺷﻜﻞ رﻗﻢ )‪ :(١-١‬ﺗﺮﺗﯿﺒﺎت اﻟﺤﺒﺎل واﻟﺒﻜﺮات ﻓﻲ اﻟﻤﺼﺎﻋﺪ‬

‫)ﺥ( ﻴﺒﻴﻥ ﺸﻜل )‪) (١-١‬ﺩ( ﻁﺭﻴﻘﺔ ﺍﻟﺘﻌﻠﻴﻕ ﺒﻨﺴﺒﺔ ‪ ١:١‬ﻭﻟﻜﻥ ﻤﺎﻜﻴﻨﺔ ﻭﺒﻜﺭﺓ ﺍﻟﺠﺭ‬
‫ﻤﺭﻜﺒــﺘﺎﻥ ﻓﻰ ﻏﺭﻓــﺔ ﻤﺎﻜﻴﻨــﺎﺕ ﺒـﺒـﺩﺭﻭﻡ ﺍﻟﻤﺒﻨﻰ ﻋﻠﻰ ﺍﻟﻌﻜﺱ ﻤﻥ‬
‫ﺍﻟﻨﻅﺎﻡ ﺍﻟﻤﺒﻴﻥ ﻓﻰ )ﺃ ‪ ،‬ﺏ ‪ ،‬ﺝ( ﺤﻴﺙ ﻴﻜﻭﻨﺎ ﻓﻰ ﻏﺭﻓﺔ ﺍﻟﺴﻁﺢ‪.‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻴﺒﻴﻥ ﺸﻜل )‪) (١-١‬ﺠـ( ﻨﻅﺎﻡ ﺍﻟﺘﻌﻠﻴﻕ ﺒﻨﺴﺒﺔ ‪ ١ : ٢‬ﺍﻟﺫﻯ ﻴﺴﺘﺨﺩﻡ ﻓﻰ ﺍﻟﺴﺭﻋﺎﺕ‬ ‫)ﺩ(‬
‫ﺍﻟﻌﺎﻟﻴﺔ )ﻤﻥ ‪ ٢.٥‬ﺇﻟﻰ ‪ ٣.٥‬ﻡ‪/‬ﺙ( ﻭﺫﻯ ﺍﻟﻘﺩﺭﺓ ﺍﻟﻤﻨﺨﻔﻀﺔ ﻟﻠﺘﺤﺭﻴﻙ ﻭﺘﺴﺘﺨﺩﻡ ﻓﻴـﻪ‬
‫ﻤﺎﻜﻴﻨﺎﺕ ﺒﺩﻭﻥ ﺘﺭﻭﺱ ﻜﻤﺎ ﻴﺴﺘﺨﺩﻡ ﺃﻴﻀﺎﹰ ﻓﻰ ﺍﻟﻤﺼـﺎﻋﺩ ﺫﺍﺕ ﺍﻟﺤﻤﻭﻟـﺔ ﺍﻟﺜﻘﻴﻠـﺔ‬
‫ﻭﺍﻟﺴﺭﻋﺎﺕ ﺍﻟﻤﻨﺨﻔﻀﺔ‪.‬‬
‫ﺘﻜﻭﻥ ﻤﺎﻜﻴﻨﺔ ﻭﺒﻜﺭﺓ ﺍﻟﺠﺭ ﻓﻰ ﺍﻟﻨﻅﺎﻡ ﺍﻟﻤﺒﻴﻥ ﻓﻰ ﺸﻜل )‪) (١-١‬ﻫــ( ﻤﺭﻜﺒﺘـﺎﻥ‬ ‫)ﺫ(‬
‫ﺒﻐﺭﻓﺔ ﺒﺎﻟﺒﺩﺭﻭﻡ ﻭﺘﻜﻭﻥ ﻓﻴﻪ ﺍﻟﺤﺒﺎل ﻁﻭﻴﻠﺔ ﻨﺴﺒﻴﺎﹰ ﻭﻴﻤﻜﻥ ﺍﺴﺘﺨﺩﺍﻡ ﻫﺫﺍ ﺍﻟﻨﻅﺎﻡ ﻓـﻰ‬
‫ﺍﻟﻤﺒﺎﻨﻰ ﺍﻟﺴﻜﻨﻴﺔ ﻭﺍﻹﺩﺍﺭﻴﺔ ﺫﺍﺕ ‪ ١٠‬ﻁﻭﺍﺒـﻕ ﻓـﺄﻜﺜﺭ ﻭﺴـﺭﻋﺎﺕ ﺤﺘـﻰ ‪٢‬ﻡ‪/‬ﺙ‬
‫ﻭﻟﺤﻤﻭﻟﺔ ﻜﺒﺎﺌﻥ ﺤﺘﻰ ‪ ٢٠٠٠‬ﻜﺠﻡ‪.‬‬
‫)ﺭ( ﻴﺘﻠﻘﻰ ﻤﺤﺭﻙ ﺍﻟﻤﺼﻌﺩ ﻓﻰ ﻤﻌﻅﻡ ﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﺘﻘﻠﻴﺩﻴـﺔ ﺍﻟﻁﺎﻗـﺔ ﻭﺍﻟﺘـﻰ ﻤﺎﺯﺍﻟـﺕ‬
‫ﺘﺴﺘﺨﺩﻡ ﻓﻰ ﻤﺒﺎﻨﻰ ﺸﻬﻴﺭﺓ ﻓﻰ ﺍﻟﻌﺎﻟﻡ ﻤﻥ ﻤﺠﻤﻭﻋﺔ ﺘﺘﻜﻭﻥ ﻤـﻥ ﻤﺤـﺭﻙ ﻭﻤﻭﻟـﺩ‬
‫)‪ (Motor generator‬ﻜﻤﺎ ﻫﻭ ﻤﻭﻀﺢ ﻓﻰ ﺸﻜل )‪.(٢-١‬‬
‫)ﺯ( ﻴﻤﻜﻥ ﺍﻻﺴﺘﻌﺎﻀﺔ ﺤﺩﻴﺜﺎﹰ ﻋﻥ ﻤﺠﻤﻭﻋﺎﺕ ﻤﺤﺭﻙ‪/‬ﻤﻭﻟﺩ ﻟﺘﻭﻟﻴﺩ ﺘﻴﺎﺭ ﻤﺴﺘﻤﺭ ﻤﺘﻐﻴـﺭ‬
‫ﺍﻟﻘﻴﻤﺔ ﻭﻤﻌﻜﻭﺱ ﺍﻹﺸﺎﺭﺓ ﺒﺎﺴﺘﺨﺩﺍﻡ ﻤﻐﻴﺭﺍﺕ ﺇﺴﺘﺎﺘﻴﻜﻴﺔ )‪.(Static converters‬‬
‫)ﺱ( ﻴﻤﻜﻥ ﻓﻰ ﻤﺎﻜﻴﻨﺎﺕ ﺍﻟﺠﺭ ﺫﺍﺕ ﺍﻟﺘﺭﻭﺱ )‪ (Geared machines‬ﺃﻥ ﻴﻜﻭﻥ ﺍﻟﻤﺤـﺭﻙ‬
‫ﺫﻭ ﻗﺩﺭﺓ ﺼﻐﻴﺭﺓ ﻭﺫﻭ ﺴﺭﻋﺔ ﻤﺎ ﺒﻴﻥ ‪ ٥٠٠‬ﻭ ‪ ١٥٠٠‬ﻟﻔﺔ‪/‬ﺩ ﺍﻋﺘﻤﺎﺩﺍﹰ ﻋﻠﻰ ﺴـﺭﻋﺔ‬
‫ﺍﻟﻤﺼﻌﺩ ﻭﻨﺴﺒﺔ ﺘﺤﻭﻴل ﺍﻟﺘﺭﻭﺱ ﻭﻴﻤﻜﻥ ﺃﻥ ﻴﻌﻤل ﺍﻟﻤﺤﺭﻙ ﺒﺘﻴﺎﺭ ﻤﺘﺭﺩﺩ ﺃﻭ ﺒﺘﻴـﺎﺭ‬
‫ﻤﺴﺘﻤﺭ )ﻴﺴﺘﺨﺩﻡ ﻓﻰ ﻤﺼﺭ ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﺘﺭﺩﺩ(‪.‬‬

‫‪ ٢-١-١‬ﺍﻟﻘﺩﺭﺓ ﺍﻟﻤﻁﻠﻭﺒﺔ ﻟﻠﻤﺼﺎﻋﺩ‬


‫ﺘﺘﺤﺩﺩ ﺍﻟﻘﺩﺭﺓ ﺍﻟﻤﻁﻠﻭﺒﺔ ﻟﻠﻤﺼﺎﻋﺩ ﺍﻟﺭﺃﺴﻴﺔ ﺒﻨﺎﺀ‪ ‬ﻋﻠﻰ ﻗـﺩﺭﺓ ﻤﺎﻜﻴﻨـﺎﺕ ﺍﻟﻤﺼـﻌﺩ‬ ‫)ﺃ(‬
‫)ﺒﺨﻼﻑ ﺍﻟﻘﺩﺭﺓ ﺍﻟﻼﺯﻤﺔ ﻟﺘﺸﻐﻴل ﺍﻷﺒﻭﺍﺏ ﻭﺘﻬﻭﻴﺔ ﻭﺇﻀﺎﺀﺓ ﺍﻟﻜﺎﺒﻴﻨﺔ ﻭﻟﻤﺒﺎﺕ ﺒﻴـﺎﻥ‬
‫ﺍﻷﺩﻭﺍﺭ(‪.‬‬
‫)ﺏ( ﺘﺴﺘﺨﺩﻡ ﺍﻟﻤﺤﺭﻜﺎﺕ ﺫﺍﺕ ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﺘﺭﺩﺩ ﻓﻰ ﺍﻟﺘﻁﺒﻴﻘﺎﺕ ﺫﺍﺕ ﺍﻟﺴﺭﻋﺎﺕ ﺍﻟﻤﻨﺨﻔﻀـﺔ‬
‫)ﻤﺎ ﺒﻴﻥ ‪ ٠.٧٥ ، ٠.١٢٥‬ﻡ‪/‬ﺙ( ﻭﺘﻜﻭﻥ ﺫﺍﺕ ﺴﺭﻋﺔ ﻭﺍﺤﺩﺓ ﺃﻭ ﺴـﺭﻋﺘﻴﻥ‪ ،‬ﻜﻤـﺎ‬
‫ﻴﻤﻜﻥ ﺍﺴﺘﺨﺩﺍﻡ ﻤﺤﺭﻜﺎﺕ ﺘﻴﺎﺭ ﻤﺘﺭﺩﺩ ﺫﺍﺕ ﺴﺭﻋﺎﺕ ﺼـﻐﻴﺭﺓ )‪(Variable speed‬‬
‫ﺃﻭ ﺫﺍﺕ ﺠﻬﺩ ﻤﺘﻐﻴـﺭ )‪ (Variable voltage‬ﺃﻭ ﺫﺍﺕ ﺠﻬـﺩ ﻭﺫﺒﺫﺒـﺔ ﻤﺘﻐﻴـﺭﺘﻴﻥ‬
‫)‪ (Variable voltage, variable frequency) (VVVF‬ﻭﻴﺴﺘﺨﺩﻡ ﻫﺫﺍ ﺍﻟﻨﻭﻉ ﻓـﻰ‬
‫ﻤﺼﺎﻋﺩ ﺍﻟﺭﻜﺎﺏ ﻭﻤﻌﻅﻡ ﻤﺼﺎﻋﺩ ﺍﻟﺒﻀﺎﻋﺔ ﻭﺒﻤﺤﺭﻜﺎﺕ ﺘﺘـﺭﺍﻭﺡ ﻗـﺩﺭﺘﻬﺎ ﺒـﻴﻥ‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫‪٢.٢‬ﻙ‪.‬ﻭ‪ ٧٥ ، .‬ﻙ‪.‬ﻭ‪ .‬ﻭﻴﺒﻴﻥ ﺠﺩﻭل )‪ (١-١‬ﺒﻴﺎﻨﺎﺕ ﻋﻥ ﺍﻟﻤﺼـﺎﻋﺩ ﺒﻤﺎﻜﻴﻨـﺎﺕ‬


‫ﺫﺍﺕ ﺘﺭﻭﺱ ﻭﺒﺩﻭﻥ ﺘﺭﻭﺱ‪.‬‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪ :(١-١‬ﻤﻘﺎﺭﻨﺔ ﺒﻴﻥ ﺍﻟﻤﺼﺎﻋﺩ‬


‫ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻟﻤﺎﻜﻴﻨﺎﺕ ﺠﺭ ﺫﺍﺕ ﺘﺭﻭﺱ ﻭﺒﺩﻭﻥ ﺘﺭﻭﺱ‬

‫ﺍﻟﻌﻤﺭ‬
‫ﺩﺭﺠﺔ‬ ‫ﺍﻻﺤﺘﻴﺎﺝ‬ ‫ﺍﻟﺴﺭﻋﺔ‬ ‫ﺍﺭﺘﻔﺎﻉ ﺍﻟﻤﺒﻨﻰ‬
‫ﺍﻟﺘﻜﻠﻔﺔ‬ ‫ﺍﻻﻓﺘﺭﺍﻀﻰ‬ ‫ﺍﻟﺘﺤﻜﻡ‬ ‫ﺍﻟﻤﺎﻜﻴﻨﺔ‬
‫ﺍﻟﻨﻌﻭﻤﺔ‬ ‫ﻟﻠﺼﻴﺎﻨﺔ‬ ‫)ﻡ‪/‬ﺙ(‬ ‫)ﻡ(‬
‫)ﺴﻨﺔ(‬
‫ﻤﻨﺨﻔﻀﺔ‬ ‫ﻤﻨﺨﻔﻀﺔ ﺇﻟﻰ‬ ‫ﻤﺘﻭﺴﻁ‬ ‫‪٤٠ - ٣٠‬‬ ‫ﺘﻐﻴﻴﺭ‬ ‫‪١ – ٠.٢٥‬‬ ‫‪٤٥ – ١٥‬‬ ‫ﺫﺍﺕ‬
‫ﺇﻟﻰ‬ ‫ﻤﺘﻭﺴﻁﺔ‬ ‫ﺍﻟﺠﻬﺩ‬ ‫‪٢-١‬‬ ‫‪٥٥ – ١٥‬‬ ‫ﺘﺭﻭﺱ‬
‫ﻤﺘﻭﺴﻁﺔ‬
‫ﻋﺎﻟﻴﺔ‬ ‫ﻋﺎﻟﻴﺔ‬ ‫ﻤﻨﺨﻔﺽ‬ ‫ﻏﻴﺭ ﻤﺤﺩﺩ‬ ‫ﺘﻐﻴﻴﺭ‬ ‫<‪٢‬‬ ‫< ‪٥٠‬‬ ‫ﺒﺩﻭﻥ‬
‫ﺍﻟﺠﻬﺩ‬ ‫ﺘﺭﻭﺱ‬

‫)ﺕ( ﺘﻭﺠﺩ ﻓﻰ ﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﺤﺩﻴﺜﺔ ﻤﻌﺩﺍﺕ ﺍﻟﻜﺘﺭﻭﻨﻴﺔ ﻴﺴﻬل ﻤﻌﻬﺎ ﺍﻟﺘﺤﻜﻡ ﻓـﻰ ﻤﺤـﺭﻙ‬
‫ﺍﻟﻤﺼﻌﺩ ﻭﺍﻟﺤﺼﻭل ﻋﻠﻰ ﺘﺭﻜﻴﺒﺎﺕ ﺫﺍﺕ ﺃﻤﺎﻥ ﺯﺍﺌﺩ ﻭﺭﺍﺤﺔ ﻭﺍﻀﺤﺔ ﻓـﻰ ﺘﺸـﻐﻴل‬
‫ﺍﻟﻤﺼﻌﺩ‪.‬‬
‫)ﺙ( ﻴﻤﻜﻥ ﺍﺴﺘﺨﺩﺍﻡ ﻤﺎﻜﻴﻨﺎﺕ ﺠﺭ ﺒﺩﻭﻥ ﺘﺭﻭﺱ ﺘﻌﻤل ﺒﺎﻟﺘﻴﺎﺭ ﺍﻟﻤﺴﺘﻤﺭ ﻟﺘﻐﻴﻴﺭ ﺴـﺭﻋﺎﺕ‬
‫ﺍﻟﺠﺭ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻰ ﺫﺍﺕ ﺍﻻﺭﺘﻔﺎﻋﺎﺕ ﺃﻜﺒﺭ ﻤﻥ ‪ ٥٠‬ﻤﺘﺭﺍﹰ ﻭﻟﻠﺤﻤﻭﻟﺔ ﺍﻟﻜﺒﻴـﺭﺓ ﺤﺘـﻰ‬
‫‪ ٥٠٠٠‬ﻜﺠﻡ ﻭﺒﺴﺭﻋﺔ ﻻ ﺘﻘل ﻋﻥ ‪ ٢‬ﻡ‪/‬ﺙ‪ ،‬ﻭﺘﻜﻭﻥ ﻗﺩﺭﺓ ﺍﻟﻤﺤﺭﻙ ﻤﻥ ‪١٥‬ﻙ‪.‬ﻭﺍﺕ‬
‫ﺇﻟﻰ ‪ ٢٦٠‬ﻙ‪.‬ﻭﺍﺕ‪.‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻟﻮﺣﺔ اﻟﺘﺤﻜﻢ واﻻﺧﺘﺒﺎر ﺗﻌﻤﻞ ﺑﺎﻟﻜﻤﺒﯿﻮﺗﺮ‬

‫ﻣﺠﻤﻮﻋﺔ ﻣﺤﺮك‪ -‬ﻣﻮﻟﺪ‬

‫ﻣﺎﻛﯿﻨﺔ ﺑﺪون ﺗﺮوس‬


‫ﻣﺴﺘﻮى ﻏﺮﻓﺔ اﻟﻤﺎﻛﯿﻨﺎت‬ ‫)ﻣﺤﺮك ﺗﯿﺎر ﻣﺴﺘﻤﺮ(‬

‫ﻣﺴﺘﻮى ﺛﺎﻧﻮي‬ ‫ﺣﺎﻛﻢ اﻟﺤﺮﻛﺔ‬

‫ﻛﺎﺑﻼت ﺣﺎﻛﻢ اﻟﺤﺮﻛﺔ‬


‫دﻻﺋﻞ اﻟﺤﺮﻛﺔ‬
‫ﻣﻔﺎﺗﯿﺢ اﻟﺤﺪ واﻟﻜﺎﻣﺔ‬

‫ﻛﺎﻣﺔ ﻣﻔﺘﺎح اﻟﺘﺒﻄﯿﺊ‬ ‫ﺛﻘﻞ اﻟﻤﻮازﻧﺔ‬

‫ﻛﺎﺑﻼت ﻣﻮازﻧﺔ ﺛﻘﻞ ﺣﺒﺎل اﻟﺠﺮ‬

‫ﻛﺎﺑﻼت اﻟﺠﺮ‬
‫ﻗﺒﺎﻗﯿﺐ دﻻﺋﻞ اﻟﺒﻜﺮ‬
‫ﻣﻔﺘﺎح اﻟﺘﺒﻄﯿﺊ‬
‫ﻣﺸﻐﻞ اﻟﺒﺎب‬ ‫ﺣﻤﺎﻟﺔ‬
‫ﻋﻼّﻗﺎت اﻟﺒﺎب‬

‫اﻟﻜﺎﺑﯿﻨﺔ‬

‫ﺣﺎﻓﺔ اﻷﻣﺎن‬
‫ﻗﺎﻋﺪة‬
‫وﺳﯿﻠﺔ اﻷﻣﺎن‬

‫ذراع اﻟﺘﺼﺎدم اﻟﺰﯾﺘﻲ‬

‫ﻧﮭﺎﯾﺎت اﻟﻤﻮازﻧﺔ‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(٢-١‬ﻤﻜﻭﻨﺎﺕ ﻤﺼﻌﺩ ﻨﻤﻭﺫﺠﻰ ﺒﻤﺎﻜﻴﻨﺔ ﻋﺩﻴﻤﺔ ﺍﻟﺘﺭﻭﺱ‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺒﺎﻹﻀﺎﻓﺔ ﺇﻟﻰ ﺃﻥ ﻤﺎﻜﻴﻨﺎﺕ ﺍﻟﺠﺭ ﺘﻜﻭﻥ ﻓﻰ ﻏﺭﻓﺔ ﺍﻟﻤﺎﻜﻴﻨﺎﺕ ﺃﻋﻠﻰ ﺍﻟﺼـﺎﻋﺩﺍﺕ ﺃﻭ‬
‫ﻓﻰ ﻏﺭﻓــﺔ ﺒﺎﻟﺒــﺩﺭﻭﻡ ﻓﺈﻨﻪ ﻴﻭﺠــﺩ ﻨﻅﺎﻡ ﺤﺩﻴﺙ ﻴﺴـﻤﻰ ﻋـﺩﻴﻡ ﻏـﺭﻑ‬
‫ﻤﺎﻜﻴﻨﺎﺕ )‪ (m/c room less‬ﻭﻻ ﻴﻭﺠﺩ ﺒﻪ ﻏﺭﻓﺔ ﻤﺎﻜﻴﻨﺎﺕ ﻭﺇﻨﻤـﺎ ﺘﺭﻜـﺏ ﺠﻤﻴـﻊ‬
‫ﺍﻟﻤﻬﻤﺎﺕ ﻓﻭﻕ ﺍﻟﺼﺎﻋﺩﺓ ﻤﺒﺎﺸﺭﺓ‪.‬‬
‫)ﺟ( ﻴﺒﻴﻥ ﺸﻜل )‪ (٣-١‬ﻨﻤﻭﺫﺝ ﻟﻤﺎﻜﻴﻨﺔ ﺠﺭ ﺫﺍﺕ ﺴﺭﻋﺔ ﻋﺎﻟﻴﺔ ﻋﺩﻴﻤﺔ ﺍﻟﺘﺭﻭﺱ ﻭﺸـﻜل‬
‫)‪ (٤-١‬ﻨﻤﻭﺫﺝ ﻟﻤﺎﻜﻴﻨﺔ ﺠﺭ ﻤﺼﻌﺩ ﺫﺍﺕ ﺘﺭﻭﺱ‪.‬‬
‫)ﺡ( ﺘﺴــﺘﺨﺩﻡ ﺍﻟﻤﺤﺭﻜــﺎﺕ ﺍﻟﺘﺄﺜﻴﺭﻴــﺔ ﺜﻼﺜﻴــﺔ ﺍﻷﻁــﻭﺍﺭ ﺫﺍﺕ ﺍﻟﺴــﺭﻋﺘﻴﻥ‬
‫‪١٥٠٠/٣٧٥‬ﻟﻔﺔ‪/‬ﺍﻟﺩﻗﻴﻘﺔ ﻤﻊ ﻨﻅﺎﻡ ﺍﻟﺘﺤﻜﻡ ﺫﻱ ﺍﻟﻤﺘﻤﻤﺎﺕ ﺃﻭ ﺍﻟﻤﻴﻜﺭﻭﺒﺭﻭﺴﻴﺴﻭﺭ ﻤﻊ‬
‫ﺜﺒﺎﺕ ﺍﻟﺘﺭﺩﺩ‪.‬‬
‫)ﺥ( ﺘﺴﺘﺨﺩﻡ ﺍﻟﻤﺤﺭﻜﺎﺕ ﺍﻟﺘﺄﺜﻴﺭﻴـﺔ ﺜﻼﺜﻴـﺔ ﺍﻷﻁـﻭﺍﺭ ﺫﺍﺕ ﺴـﺭﻋﺔ ﻭﺍﺤـﺩﺓ ‪١٥٠٠‬‬
‫ﻟﻔﺔ‪/‬ﺍﻟﺩﻗﻴﻘﺔ ﻤﻊ ﻨﻅﺎﻡ ﻤﻐﻴﺭ ﺍﻟﺘﺭﺩﺩ ﻭﺍﻟﺠﻬﺩ ﻭﻴﺴﺘﺨﺩﻡ ﻨﻅﺎﻡ ﺍﻟﺘﺭﻭﺱ ﻟﺘﺤﺩﻴﺩ ﺴـﺭﻋﺔ‬
‫ﺍﻟﻤﺼﻌﺩ‪.‬‬
‫ﺘﻌﺭﻑ ﺍﻟﻘﺩﺭﺓ ﺍﻟﻤﻁﻠﻭﺒﺔ ﻟﻠﻤﺼﻌﺩ ﺒﺄﻨﻬﺎ ﺘﻠﻙ ﺍﻟﺘﻰ ﺘﺤﻘﻕ ﺍﻟﺠﺭ ﺍﻟﻤﻁﻠـﻭﺏ ﻭﻜـﺫﻟﻙ‬ ‫)ﺩ(‬
‫ﺍﻟﺘﻐﻠﺏ ﻋﻠﻰ ﺍﻻﺤﺘﻜﺎﻙ ﻭﺘﺘﻨﺎﺴﺏ ﻫﺫﻩ ﺍﻟﻘﺩﺭﺓ ﺍﻟﻤﻁﻠﻭﺒﺔ ﻤﻊ ﺍﻟﻤﻌﺩل ﺍﻟﺫﻯ ﻴﺘﻡ ﻋﻨﺩﻩ‬
‫ﺍﻟﺸﻐل ﺍﻟﻤﺒﺫﻭل‪:‬‬
‫ﺍﻟﺸﻐل ﺍﻟﻤﺒﺫﻭل )ﻜﺠﻡ‪.‬ﻤﺘﺭ(‬
‫ﻗﺩﺭﺓ ﺍﻟﻤﺤﺭﻙ ﺍﻟﻤﻁﻠﻭﺏ = ﻙ‪.‬‬
‫ﺍﻟﺯﻤﻥ‬
‫ﺤﻴﺙ ﺘﺘﻨﺎﺴﺏ ﻗﺩﺭﺓ ﺍﻟﻤﺤﺭﻙ ﺍﻟﻤﻁﻠﻭﺏ ﻁﺭﺩﻴﺎﹰ ﻤﻊ ﺴﺭﻋﺔ ﺍﻟﻤﺠﻤﻭﻋﺔ ﻭﻴﻜﻭﻥ )ﻙ( ﻫﻭ‬
‫ﺜﺎﺒﺕ ﻤﻌﺎﻤل ﺍﻷﻤﺎﻥ ﻭﺍﻟﻔﻘﺩ‪.‬‬
‫ﻓﻤﺜﻼﹰ ﺍﻟﺼﺎﻋﺩﺓ ﺍﻟﺘﻰ ﺘﺯﻥ ‪ ١٥٠٠‬ﻜﺠﻡ ﺸﺎﻤﻠﺔ ﺍﻟﺤﻤﻭﻟﺔ ﺍﻟﻜﺎﻤﻠﺔ ﻭﻜﺎﻨﺕ ﺍﻟﺤﻤﻭﻟﺔ ﻤـﺜﻼﹰ‬
‫‪ ٩٠٠‬ﻜﺠﻡ ﻭﻭﺯﻥ ﺍﻟﻜﺎﺒﻴﻨﺔ ﺒﻤﺸﺘﻤﻼﺘﻬﺎ ‪ ٦٠٠‬ﻜﺠﻡ ﻓﻴﻜﻭﻥ ﺜﻘل ﺍﻟﻤﻭﺍﺯﻨﺔ ﻓـﻰ ﻨﻅـﺎﻡ‬
‫ﺍﻟﺘﻌﻠﻴﻕ ‪ ١ : ١‬ﻤﺴﺎﻭﻴﺎﹰ ﻟﻨﺼﻑ ﻭﺯﻥ ﺍﻟﺼﺎﻋﺩﺓ ﻭﻨﺼﻑ ﺤﻤﻭﻟﺘﻬـﺎ )‪ ١٢٠٠‬ﻜﺠـﻡ(‪،‬‬
‫ﻭﻓﻰ ﻫﺫﻩ ﺍﻟﺤﺎﻟﺔ ﻴﻜﻭﻥ ﺍﻟﻤﺤﺭﻙ ﻤﺼﻤﻤﺎﹰ ﻋﻠﻰ ﺘﺤﻤﻴل ‪ ٪٥٠‬ﻓﻘﻁ ﻤﻥ ﺍﻟﺤﻤﻭﻟﺔ ﺍﻟﻜﺎﻤﻠﺔ‬
‫ﺼﻌﻭﺩﺍﹰ ﺃﻭ ﻫﺒﻭﻁﺎﹰ ﻤﻀﺎﻓﺎﹰ ﺇﻟﻰ ﺫﻟﻙ ‪ ٪١٠‬ﺯﻴﺎﺩﺓ ﺤﻤﻭﻟﺔ‪.‬‬
‫ﻭﻟﺫﻟﻙ ﻓﺈﻥ ﺍﻟﻘﺩﺭﺓ ﺍﻟﻤﻁﻠﻭﺒﺔ ﻟﺭﻓﻊ ﺼﺎﻋﺩﺓ ﺘﺯﻥ ‪ ١٥٠٠‬ﻜﺠﻡ ﻋﻨﺩ ﺴﺭﻋﺔ ‪ ٣.٦‬ﻡ‪/‬ﺙ‬
‫ﺘﻜﻭﻥ ﺃﻜﺒﺭ ﻤﻥ ﺘﻠﻙ ﺍﻟﻘﺩﺭﺓ ﺍﻟﻼﺯﻤﺔ ﻟﺭﻓﻌﻬﺎ ﻋﻨﺩ ﺴﺭﻋﺔ ‪١‬ﻡ‪/‬ﺙ‪.‬‬
‫ﻴﺒﻴﻥ ﺸﻜل )‪ (٥-١‬ﺭﺴﻡ ﺘﺨﻁﻴﻁﻲ ﻟﺒﻴﺎﻥ ﺍﻟﻔﻘﺩ ﺍﻟﺘﻔﺼﻴﻠﻲ ﻟﻜـل ﻙ‪ .‬ﻭﺍﺕ ﻓـﻲ ﻨﻅـﺎﻡ‬
‫ﺍﻟﻤﺼﺎﻋﺩ ﺍﻟﺘﻲ ﺘﺴﺘﺨﺩﻡ ﻤﺤﺭﻜﺎﺕ ﺒﺘﺭﻭﺱ ﺃﻭ ﺒﺩﻭﻥ ﺘﺭﻭﺱ‪.‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻣﻠﻒ رأﺳﻲ ﻟﺘﺸﻐﯿﻞ اﻟﻔﺮﻣﻠﺔ‬


‫ﯾﺎﯾﺎت اﻟﻔﺮاﻣﻞ‬

‫ﻛﺮﺳﻲ ﻣﺤﻮر اﻟﻤﺤﺮك‬

‫ﺑﻜﺮة اﻟﺠﺮ‬
‫ﻗﺎﻋﺪة اﻟﻤﺤﺮك‬ ‫)ﺑﺪون ﺑﯿﺎن ﺣﺒﺎل اﻟﺠﺮ(‬

‫ﺷﻜﻞ رﻗﻢ )‪ :(٣-١‬ﻣﺎﻛﯿﻨﺔ اﻟﺠﺮ ﺑﺪون ﺗﺮوس )ﻣﺤﺮك ﺗﯿﺎر ﻣﺴﺘﻤﺮ ﻓﻘﻂ(‬

‫ﻃﺎرة اﻟﺠﺮ )ﺑﺪون ﺣﺒﺎل اﻟﺠﺮ(‬


‫ﺗﺠﮭﯿﺰات اﻟﻀﺒﻂ ﻟﺰواﯾﺎ وﺧﻠﻮص‬
‫اﻟﺘﺮوس‬

‫ﻣﻠﻒ أوﺗﻮﻣﺎﺗﯿﻜﻲ ﻟﻠﻔﺮﻣﻠﺔ ﻋﻨﺪ‬


‫اﻟﻤﻜﺎن اﻟﯿﺎي واﻟﺬراع‬

‫ﻣﺤﺮك ﺗﯿﺎر ﻣﺴﺘﻤﺮ أو‬


‫ﺗﯿﺎر ﻣﺘﺮدد‬

‫ﺗﺮس وﻋﺎﻣﻮد‬
‫ﺣﻠﺰوﻧﻲ‬

‫ﺷﺎﺳﯿﺔ ﻣﻦ اﻟﺼﻠﺐ ﻟﻠﻮﺣﺪة‬

‫ﺷﻜﻞ رﻗﻢ )‪ :(٤-١‬ﻣﺎﻛﯿﻨﺔ اﻟﺠﺮ ذات اﻟﺘﺮوس )ﻣﺤﺮك ﺗﯿﺎر ﻣﺴﺘﻤﺮ أو ﻣﺘﺮدد(‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻤﻠﺤﻭﻅﺔ‪:‬‬
‫)‪ (١‬ﻴﻘﻭﻡ ﺍﻟﻤﺤﺭﻙ ﺒﺎﻟﺘﻐﻠﺏ ﻋﻠﻰ ﺍﻻﺤﺘﻜﺎﻙ ﻓﻰ ﺍﻟﻨﻅﺎﻡ ﺒﺎﻹﻀﺎﻓﺔ ﺇﻟﻰ ﺍﻟﻘـﺩﺭﺓ‬
‫ﺍﻟﻼﺯﻤﺔ ﻟﻠﺠﺭ ﻭﻴﺒﻴﻥ ﺍﻟﺸﻜل ﻗﺩﺭﺓ ﺍﻟﻤﺤﺭﻙ ﺍﻟﻤﻁﻠﻭﺒﺔ ﻟﻜل ﻜﺎﺒﻴﻨﺔ‪.‬‬
‫)‪ (٢‬ﻴﻼﺤﻅ ﺃﻥ ﻗﺩﺭﺓ ﻤﺠﻤﻭﻋﺔ ﻤﻭﻟﺩ ‪ /‬ﻤﺤﺭﻙ ﺍﻟﻼﺯﻤﺔ ﻟﺘﻐﺫﻴﺔ ﻤﺤﺭﻙ ﺍﻟﺠـﺭ‬
‫ﺃﻋﻠﻰ ﺒﺤﻭﺍﻟﻰ ‪ ٪٢٠‬ﻤﻥ ﻗﺩﺭﺘﻪ‪.‬‬
‫)‪ (٣‬ﻨﻅﺭﺍﹰ ﻷﻥ ﺍﻻﺤﺘﻜﺎﻙ ﺃﻜﺒﺭ ﻓﻰ ﺤﺎﻟﺔ ﺍﻟﻤﺎﻜﻴﻨﺎﺕ ﺫﺍﺕ ﺍﻟﺘﺭﻭﺱ ﻋﻨﻬﺎ ﻓـﻰ‬
‫ﺍﻟﻤﺎﻜﻴﻨﺎﺕ ﻋﺩﻴﻤﺔ ﺍﻟﺘﺭﻭﺱ‪ ،‬ﻓﺘﻜﻭﻥ ﻗﺩﺭﺓ ﺍﻟﻤﺤﺭﻙ ﻓﻰ ﻫﺫﻩ ﺍﻟﺤﺎﻟﺔ ﺃﻜﺒﺭ‪.‬‬
‫‪ -‬ﺇﺫﺍ ﺘﻡ ﺍﺴﺘﺨﺩﺍﻡ ﺘﺤﻜﻡ ﺇﻟﻴﻜﺘﺭﻭﻨﻰ ﻓﻰ ﻤﺤﺭﻙ ﺍﻟﺠﺭ )ﻴﺘﻡ ﺍﻻﺴﺘﻐﻨﺎﺀ ﻋﻥ ﻤﺠﻤﻭﻋﺔ‬
‫ﺍﻟﻤﺤﺭﻙ ‪ /‬ﺍﻟﻤﻭﻟﺩ(‪ ،‬ﻓﻴﻤﻜﻥ ﺍﺴﺘﺨﺩﺍﻡ ﻨﻔﺱ ﺍﻟﻘﻴﻡ ﺍﻟﻭﺍﺭﺩﺓ ﻓﻰ ﺸﻜل )‪ (٥-١‬ﻁﺎﻟﻤﺎ‬
‫ﺃﻥ ﻤﺤﺭﻙ ﺍﻟﺠﺭ ﻟﻡ ﻴﺘﺄﺜﺭ ﺒﺎﺴﺘﺨﺩﺍﻡ ﻤﺼﺩﺭ ﺍﻟﺘﻐﺫﻴﺔ ﻤﺘﻐﻴﺭ ﺍﻟﺠﻬﺩ‪ ،‬ﻭﻴﻼﺤـﻅ ﺃﻥ‬
‫ﻤﻌﻅﻡ ﺼﺎﻨﻌﻰ ﺍﻟﻤﺼﺎﻋﺩ ﻴﺨﺘﺎﺭﻭﻥ ﻤﺤﺭﻜﺎﺕ ﺒﻘﺩﺭﺍﺕ ﺃﻜﺒﺭ ﻟﻀـﻤﺎﻥ ﺘﻌﺠﻴـل‬
‫ﺃﺴﺭﻉ ﻟﻠﻜﺎﺒﻴﻨﺔ )‪ ،(Rapid acceleration‬ﻤﻤﺎ ﻴﺅﺩﻯ ﺇﻟﻰ ﺍﺴﺘﺨﺩﺍﻡ ﻤﺤﺭﻜﺎﺕ ﺠﺭ‬
‫ﺒﻘﺩﺭﺍﺕ ﺃﻜﺒﺭ ﻤﻥ ﺤﺎﻟﺔ ﺍﺴﺘﺨﺩﺍﻡ ﻤﺠﻤﻭﻋﺔ ﺍﻟﻤﺤﺭﻙ ‪ /‬ﺍﻟﻤﻭﻟﺩ‪.‬‬
‫‪ -‬ﻴﻜﻭﻥ ﺍﻨﺩﻓﺎﻉ ﺍﻟﺘﻴﺎﺭ ﺃﻜﺒﺭ ﻋﻨﺩ ﺒﺩﺀ ﺤﺭﻜﺔ ﻤﺤﺭﻙ ﺍﻟﺠﺭ ﻭﺒﺫﻟﻙ ﺘﻜﻭﻥ ﻤﺘﻁﻠﺒـﺎﺕ‬
‫ﺍﻟﻘﺩﺭﺓ ﻤﻥ ﻤﺠﻤﻭﻋﺔ ﺍﻟﻤﺤﺭﻙ ‪ /‬ﻤﻭﻟﺩ ﻋﺎﻟﻴﺔ ﺘﺤﺕ ﻅﺭﻭﻑ ﺍﻟﺘﺤﻤﻴل ﺍﻟﻌﺎﻟﻴﺔ ﻤﻤﺎ‬
‫ﻴﺅﺩﻯ ﺇﻟﻰ ﺍﺭﺘﻔﺎﻉ ﺍﻟﻘﺩﺭﺓ ﺍﻟﻠﺤﻅﻴﺔ ﻤﻊ ﺍﻨﺨﻔﺎﺽ ﻤﻌﺎﻤل ﺍﻟﻘﺩﺭﺓ‪ ،‬ﻤﻤﺎ ﻴﺅﺩﻯ ﺇﻟـﻰ‬
‫ﺘﺤﻤﻴل ﺍﻟﻤﺴﺘﻬﻠﻙ ﻏﺭﺍﻤﺎﺕ ﻤﻥ ﺸﺭﻜﺔ ﺘﻭﺯﻴﻊ ﺍﻟﻜﻬﺭﺒﺎﺀ‪.‬‬
‫‪ -‬ﻴﻔﻀل ﻓﻰ ﻭﺠﻭﺩ ﻤﺠﻤﻭﻋﺔ ﻤﻥ ﺍﻟﻤﺼﺎﻋﺩ ﺒﺎﻟﻤﺒﻨﻰ‪ ،‬ﺃﻥ ﻴﺘﻡ ﺍﻟﺘﺤﻜﻡ ﻓﻴﻬﺎ ﺘﻨﺎﺴـﻘﻴﺎﹰ‬
‫ﺤﺘﻰ ﺘﻤﻨﻊ ﺤﺭﻜﺔ ﺠﻤﻴﻊ ﺍﻟﻤﺼﺎﻋﺩ ﺁﻨﻴﺎﹰ ﻟﺘﻠﺒﻴﺔ ﻁﻠﺏ ﻭﺍﺤﺩ‪.‬‬
‫‪ -‬ﻴﺠﺏ ﻋﻨﺩ ﻋﻤل ﺫﻟﻙ ﻤﺭﺍﻋﺎﺓ ﺃﻥ ﻴﻜﻭﻥ ﺯﻤﻥ ﺍﻟﺘﺄﺨﺭ ﻓﻰ ﺒـﺩﺀ ﺍﻟﺤﺭﻜـﺔ ﺒﻴﻨﻬـﺎ‬
‫ﺼﻐﻴﺭﺍﹰ ﺠﺩﺍﹰ ﺒﺤﻴﺙ ﻻ ﻴﻨﻌﻜﺱ ﺫﻟﻙ ﺒﺸﻜل ﻤﻠﺤﻭﻅ ﻋﻠﻰ ﺘﺸﻐﻴل ﻨﻅﺎﻡ ﺍﻟﻤﺼﺎﻋﺩ‬
‫ﺒﺎﻟﻤﺒﻨﻰ‪.‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫‪ -‬ﺗﺤﻜﻢ ﺑﺎﺳﺘﺨﺪام ﺟﮭﺪ ﻣﺘﻌﺪد‬ ‫ﻣﻌﺪات اﻟﺠﺮ‪:‬‬


‫اﻟﻘﺪرة اﻟﺪاﺧﻠﺔ‬ ‫ﻟﻠﻮﺣﺪة ‪UMV‬‬ ‫اﻟﻜﻔﺎءة اﻟﻜﻠﯿﺔ‪:‬‬ ‫اﻟﻘﺪرة اﻟﻤﺴﺘﻔﺎدة‬
‫‪ -‬ﻣﺠﻤﻮﻋﺔ ﻣﺤﺮك ‪ /‬ﻣﻮﻟﺪ‬ ‫‪ -‬ﺑﺪون ﺗﺮوس ‪٪٩٥‬‬
‫اﻟﻜﻔﺎءة اﻟﻤﺘﻮﺳﻄﺔ ‪٪٨٠‬‬ ‫‪ -‬ﺑﺎﺳﺘﺨﺪام ﺗﺮوس ‪٪٩٠‬‬

‫ﻓﻘﺪ ‪ ١٦٠‬وات ﻓﻲ ﺣﺎﻟﺔ ﻣﺎﻛﯿﻨﺔ اﻟﺠﺮ ﺑﺪون ﺗﺮوس‬


‫ﻓﻘﺪ ‪ ٢٠٠‬وات‬ ‫ﻓﻘﺪ ‪ ٢٨٠‬وات ﻓﻲ ﺣﺎﻟﺔ ﻣﺎﻛﯿﻨﺔ اﻟﺠﺮ ﺑﺘﺮوس‬

‫‪ ١٠٠٠‬وات‬ ‫‪ ٨٠٠‬وات‬ ‫‪ ٦٤٠‬وات ﺑﺪون ﺗﺮوس‬


‫‪ ٥٢٠‬وات ﺑﺘﺮوس‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(٥-١‬ﺭﺴﻡ ﺘﺨﻁﻴﻁﻲ ﻟﺒﻴﺎﻥ ﺍﻟﻔﻘﺩ ﺍﻟﺘﻔﺼﻴﻠﻰ ﻟﻜل ﻙ‪ .‬ﻭ‪ .‬ﻓﻲ ﻨﻅﺎﻡ ﺍﻟﻤﺼﺎﻋﺩ‬
‫ﺍﻟﺘﻲ ﺘﺴﺘﺨﺩﻡ ﻤﺤﺭﻜﺎﺕ ﺒﺘﺭﻭﺱ ﺃﻭ ﺒﺩﻭﻥ ﺘﺭﻭﺱ‬

‫‪ -‬ﻤﻥ ﺍﻟﻤﻌﺭﻭﻑ ﺃﻥ ﺍﻟﻤﺼﻌﺩ ﺍﻟﻭﺍﺤﺩ ﻴﻜﻭﻥ ﻓﻰ ﺤﺭﻜﺔ ﺤﻭﺍﻟﻰ ‪ ٪٥٠‬ﻓﻘـﻁ ﻤـﻥ‬


‫ﺍﻟﺯﻤﻥ ﻭﻴﻜﻭﻥ ﺒﺎﻗﻰ ﺍﻟﻭﻗﺕ ﻭﺍﻗﻔﺎﹰ ﻋﻨﺩ ﺍﻷﺩﻭﺍﺭ ﺍﻟﻤﺨﺘﻠﻔﺔ‪ ،‬ﻭﻟـﺫﺍ ﻓﺈﻨـﻪ ﺇﺫﺍ ﺯﺍﺩ‬
‫ﻋﺩﺩ ﺍﻟﻜﺒﺎﺌـﻥ ﻓﻰ ﺍﻟﻤﺠﻤﻭﻋـﺔ ﺩﺍﺨـل ﺍﻟﻤﺒﻨـﻰ‪ ،‬ﻓـﺈﻥ ﺍﺤﺘﻤـﺎل ﻋﻤﻠﻬــﺎ‬
‫ﻜﻠﻬـﺎ ﺁﻨﻴـﺎﹰ ﻴﺼﺒـﺢ ﻗﻠﻴــﻼﹰ‪ ،‬ﻜﻤـــﺎ ﻴﺘﻀـــﺢ ﻤـــﻥ ﻗﻴﻤــﺔ‬
‫ﻤﻌﺎﻤـل ﺍﻟﻁﻠـﺏ ﻟﻠﻤﺠﻤﻭﻋـﺔ )‪ (Group demand factor‬ﺍﻟﻤﺒﻴﻥ ﻗﻰ ﺸـﻜل‬
‫)‪.(٦-١‬‬
‫ﻜﻤﺎ ﻴﺒﻴﻥ ﺸﻜل )‪ (٦-١‬ﺍﻟﻌﻼﻗﺔ ﺒﻴﻥ ﺍﻟﺴﺭﻋﺔ ﻭﺍﻟﻘـﺩﺭﺓ ﺍﻟﻤﻁﻠﻭﺒـﺔ ﻋﻨـﺩ ﺃﻭﺯﺍﻥ‬
‫ﺼﺎﻋﺩﺍﺕ ﻤﺨﺘﻠﻔﺔ‪.‬‬
‫ﻤﺜﺎل‪:‬‬
‫ﻓﻰ ﺸﻜل )‪ (٦-١‬ﺇﺫﺍ ﻜﺎﻥ ﻋﺩﺩ ﺍﻟﻜﺒﺎﺌﻥ ﺒﺤﻤﻭﻟﺔ ‪ ١٧٥٠‬ﻜﺠﻡ ﺨﻤﺴﺔ ﻭﺘﺘﺤـﺭﻙ‬
‫ﺒﺴﺭﻋﺔ ‪٣‬ﻡ‪/‬ﺙ‪ ،‬ﻓﺈﻥ ﻜل ﻜﺎﺒﻴﻨﺔ ﺘﺤﺘﺎﺝ ﺇﻟﻰ ﻤﺤﺭﻙ ﺠﺭ ﻗﺩﺭﺓ ‪ ٣٦‬ﻙ‪.‬ﻭ‪.‬‬
‫ﻭﻤﻥ ﺍﻟﺠﺩﻭل ﻓﺈﻥ ﻤﻌﺎﻤل ﺍﻟﻁﻠﺏ ﻟﻠﻤﺠﻤﻭﻋﺔ ﻫﻭ ‪ ٠.٦٧‬ﻭﺒﺫﻟﻙ ﺘﻜـﻭﻥ ﻗـﺩﺭﺓ‬
‫ﺍﻟﺠﺭ ﺍﻟﻠﺤﻅﻴﺔ ﻟﻠﻤﺤﺭﻜﺎﺕ ﻓﻰ ﺍﻟﻤﺠﻤﻭﻋﺔ ﻫﻰ‪ ١٢٠ = ٠.٦٧×٣٦×٥ :‬ﻙ‪.‬ﻭ‪.‬‬
‫ﻓﺈﺫﺍ ﻜﺎﻨﺕ ﺍﻟﻜﻔﺎﺀﺓ ﻟﻤﺠﻤﻭﻋﺔ ﻤﺤﺭﻙ ‪ /‬ﻤﻭﻟﺩ ﻫﻰ ‪ ٪٨٠‬ﻓﺈﻥ ﻤﺎ ﻴﺤﺘﺎﺠﻪ ﻨﻅـﺎﻡ‬
‫ﺍﻟﻤﺼﺎﻋﺩ ﻓﻰ ﺍﻟﻤﺒﻨﻰ ﻫﻭ =‬
‫‪١٢٠‬‬
‫= ‪ ١٥٠‬ﻙ‪.‬ﻭ‪.‬‬
‫‪٠.٨‬‬
‫ﻴﺠﺏ ﺘﻭﺍﻓﺭ ﻫﺫﻩ ﺍﻟﻘﺩﺭﺓ ﻓﻰ ﻨﻅﺎﻡ ﺘﻐﺫﻴﺔ ﺍﻟﻤﺒﻨﻰ ﺒﺎﻟﻘﺩﺭﺓ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ‪.‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫‪ ٣-١-١‬ﻤﺘﻁﻠﺒﺎﺕ ﺍﻟﻁﺎﻗﺔ ﻟﻠﻤﺼﺎﻋﺩ‬


‫ﺘﻜﻭﻥ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻤﺴﺘﻬﻠﻜﺔ ﻓﻰ ﺘﺤﺭﻴﻙ ﺍﻟﻤﺼﻌﺩ ﻫﻰ ﺍﻟﻼﺯﻤﺔ ﻟﻠﺘﻐﻠﺏ ﻋﻠﻰ ﺍﻻﺤﺘﻜـﺎﻙ ﻓـﻰ‬
‫ﺍﻟﻨﻅﺎﻡ ﺒﻤﺎ ﻓﻴﻪ ﺍﻟﺤﺭﺍﺭﺓ ﺍﻟﻤﺘﻭﻟﺩﺓ ﻨﺘﻴﺠﺔ ﻟﻠﻔﺭﺍﻤل ﻤﻀﺎﻓﺎﹰ ﺇﻟﻴﻬﺎ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﺍﻟﻤﻔﻘـﻭﺩﺓ‬
‫ﻓﻰ ﻤﺠﻤﻭﻋﺔ ﻤﺤﺭﻙ ﺍﻟﺠﺭ ﻭﻓﻰ ﻤﺠﻤﻭﻋﺔ ﺍﻟﻤﺤﺭﻙ ‪ /‬ﻤﻭﻟﺩ )ﺇﻥ ﻭﺠﺩﺕ(‪ .‬ﺃﻤـﺎ ﺍﻟﻁﺎﻗـﺔ‬
‫ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻟﺭﻓﻊ ﺍﻟﻜﺎﺒﻴﻨﺔ ﺒﺭﻜﺎﺒﻬﺎ ﻓﻬﻰ ﺒﺒﺴﺎﻁﺔ ﻁﺎﻗﺔ ﻭﻀﻊ )‪ (Potential energy‬ﻴﺘــﻡ‬
‫ﺇﻋﺎﺩﺘﻬــﺎ ﺇﻟﻰ ﻨﻅــﺎﻡ ﺍﻟﻘــﻭﻯ ﺃﺜﻨﺎﺀ ﻫﺒﻭﻁ ﺍﻟﻜﺎﺒﻴﻨـــﺔ ﺒﺭﻜﺎﺒﻬــــﺎ ﻋــﻥ‬
‫ﻁﺭﻴﻕ ﻨﻅﺎﻡ ﺍﺴـﺘﻌﺎﺩﺓ ﺍﻟﻘـﺩﺭﺓ ﺍﻟﻔﺭﻤﻠﻴـﺔ ﺍﻟﻤﺘﻭﻟـﺩﺓ ) ‪(System regenerative braking‬‬
‫ﺍﻟﻤﺴﺘﺨﺩﻡ ﻓﻰ ﻤﻌﻅﻡ ﻨﻅﻡ ﺍﻟﻤﺼﺎﻋﺩ‪.‬‬
‫ﻭﻴﺒﻴﻥ ﺸﻜل )‪ (٦-١‬ﺍﻟﻜﻔﺎﺀﺓ ﺍﻟﺘﻘﺭﻴﺒﻴﺔ ﻟﻤﻜﻭﻨﺎﺕ ﻨﻅﺎﻡ ﻨﻤﻁﻰ ﻭﻤﻥ ﺍﻟﻤﻤﻜﻥ ﻋـﻥ ﻁﺭﻴـﻕ‬
‫ﺍﻟﺒﻴﺎﻨﺎﺕ ﺍﻟﻤﻌﻁﺎﺓ ﺤﺴﺎﺏ ﺍﺴﺘﻬﻼﻙ ﺍﻟﻁﺎﻗﺔ ﻓﻰ ﺍﻟﻨﻅﺎﻡ‪.‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻣﻌﺎﻣﻞ اﻟﻄﻠﺐ‬
‫ﻋﺪد اﻟﻜﺒﺎﺋﻦ‬
‫‪69‬‬ ‫اﻟﻤﺠﻤﻮﻋﺔ‬
‫‪82‬‬
‫ﻗﺪرة اﻟﻤﺤﺮك ﺑﺎﻟﻜﯿﻠﻮوات ﻓﻲ اﻟﻤﻌﺪات ذات اﻟﺘﺮوس‬

‫ﻗﺪرة اﻟﻤﺤﺮك ﺑﺎﻟﻜﯿﻠﻮوات ﻓﻲ اﻟﻤﻌﺪات ﻋﺪﯾﻤﺔ اﻟﺘﺮوس‬ ‫‪63‬‬


‫‪75‬‬ ‫‪2000 kg‬‬
‫‪57‬‬ ‫‪1750 kg‬‬
‫‪67‬‬
‫‪50‬‬
‫‪60‬‬ ‫‪1500 kg‬‬
‫‪45‬‬
‫‪52‬‬ ‫‪1250 kg‬‬
‫‪39‬‬
‫‪45‬‬ ‫‪1000 kg‬‬
‫‪33‬‬
‫‪37.5‬‬
‫‪27‬‬
‫‪30‬‬
‫‪20‬‬
‫‪22.5‬‬
‫‪15‬‬
‫‪15‬‬ ‫‪12‬‬ ‫‪800 kg‬‬
‫‪9‬‬ ‫‪630 kg‬‬
‫‪7.5‬‬ ‫‪6‬‬ ‫‪450 kg‬‬
‫‪3‬‬ ‫‪300 kg‬‬
‫‪0‬‬ ‫‪0‬‬
‫‪0.5‬‬ ‫‪1‬‬ ‫‪1.5‬‬ ‫‪2‬‬ ‫‪2.5‬‬ ‫‪3‬‬ ‫‪3.5‬‬ ‫‪4‬‬ ‫‪4.5‬‬ ‫‪5‬‬
‫ﺳﺮﻋﺔ اﻟﻤﺼﻌﺪ )م‪/‬ث(‬

‫ﺷﻜﻞ رﻗﻢ )‪ :(٦-١‬اﻟﻌﻼﻗﺔ ﺑﯿﻦ ﺳﺮﻋﺔ اﻟﻤﺼﻌﺪ وﻗﺪرة اﻟﻤﺤﺮك ﺑﺎﻟﻜﯿﻠﻮ‪.‬وات ﻋﻨﺪ‬
‫ﺣﻤﻮﻻت ﻛﺒﺎﺋﻦ ﻣﺨﺘﻠﻔﺔ‬

‫ﻤﺜﺎل‪:‬‬
‫ﻓﻰ ﻤﺠﻤﻭﻋﺔ ﻤﺼﺎﻋﺩ ﻤﻨﻔﺫﺓ ﺒﺄﺴﻠﻭﺏ ﺍﻟﺘﻌﻠﻴﻕ ﺒﻨﺴﺒﺔ ‪ ١ : ١‬ﻤﻜﻭﻨـﺔ ﻤـﻥ )‪(٥‬‬
‫ﻜﺒﺎﺌﻥ ﺤﻤﻭﻟﺔ ﻜل ﻤﻨﻬﺎ ‪ ١٧٥٠‬ﻜﺠﻡ ﻭﺘﺘﺤﺭﻙ ﺒﺴﺭﻋﺔ ‪ ٣‬ﻡ‪/‬ﺙ‪ ،‬ﺍﺤﺴﺏ ﺍﻵﺘﻰ‪:‬‬
‫‪ -‬ﺍﻟﺤﺭﺍﺭﺓ ﺍﻟﻤﺘﻭﻟﺩﺓ ﻓﻰ ﻏﺭﻓﺔ ﺍﻟﻤﺎﻜﻴﻨﺎﺕ ﺃﺜﻨﺎﺀ ﻓﺘﺭﺍﺕ ﺍﻟﺫﺭﻭﺓ‪.‬‬
‫‪ -‬ﺍﻟﺘﻜﻠﻔﺔ ﺍﻟﺘﻘﺭﻴﺒﻴﺔ ﻟﻠﻁﺎﻗﺔ ﺍﻟﻤﺴﺘﻬﻠﻜﺔ ﺸﻬﺭﻴﺎﹰ ﺒﺎﺴﺘﺨﺩﺍﻡ ﺘﻌﺭﻴﻔﺔ ﻤﺯﺩﻭﺠﺔ ﺒﻤﻘﺩﺍﺭ‬
‫‪ ٠.٢١‬ﺠﻨﻴﻬﺎﹰ ‪ /‬ﻙ‪.‬ﻭ‪ .‬ﺴﺎﻋﺔ‪.‬‬
‫ﺍﻟﺤـــل‪:‬‬
‫)‪ (١‬ﺃﺜﻨﺎﺀ ﺃﻭﻗﺎﺕ ﺍﻟﺫﺭﻭﺓ ﺘﻌﻤل ﻤﺠﻤﻭﻋﺔ ﺍﻟﻤﺤﺭﻙ ‪ /‬ﻤﻭﻟﺩ ﺒﺎﺴﺘﻤﺭﺍﺭ ﻭﺘﻜـﻭﻥ‬
‫ﻓﻰ ﺤﺎﻟﺔ ﺍﻟﻼﺤﻤل ﺤﻭﺍﻟﻰ ‪ ٪٥٠‬ﻤﻥ ﺍﻟﺯﻤﻥ ﻭﻓﻰ ﺤﺎﻟﺔ ﺍﻟﺤﻤل ﻓـﻰ ‪٪٥٠‬‬
‫ﺍﻟﺒﺎﻗﻴﺔ ﻤﻥ ﺍﻟﻭﻗﺕ‪ ،‬ﻭﻋﻠﻰ ﺫﻟﻙ ﻓﺈﻥ ﺍﺴﺘﺨﺩﺍﻡ ﺭﻗﻡ ﺘﻘﺭﻴﺒﻲ ﻟﻠﻌﻤـل ﻋﻨـﺩ‬
‫ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل ﺒﻤﻘﺩﺍﺭ ‪ ٪٧٠‬ﻤﻥ ﺍﻟﻔﺘﺭﺍﺕ ﺍﻟﺯﻤﻨﻴﺔ ﻫﻭ ﺍﺨﺘﻴﺎﺭ ﺃﻗﺭﺏ ﺇﻟـﻰ‬
‫ﺍﻟﺩﻗﺔ‪.‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫)‪ (٢‬ﻴﻌﻤل ﻤﺤﺭﻙ ﺍﻟﺠﺭ ‪ ٪٥٠‬ﻤﻥ ﺍﻟﻭﻗﺕ ﻋﻠﻰ ﺍﻟﺤﻤل ﻭﻻ ﻴﻌﻤل ‪ ٪ ٥٠‬ﻤـﻥ‬
‫ﺍﻟﻭﻗﺕ‪ ،‬ﻭﺒﺎﻋﺘﺒﺎﺭ ﺃﻥ ﻜﻼ ﺍﻟﻤﺤﺭﻜﻴﻥ ﻴﺴﺤﺒﺎﻥ ‪ ٪٩٠‬ﻤﻥ ﺍﻟﻘﻴﻤﺔ ﺍﻟﻜﺎﻤﻠـﺔ‬
‫ﻟﻠﺤﻤل‪ ،‬ﻭﻋﻠﻰ ﺫﻟﻙ ﻓﺈﻨﻪ ﻟﻠﻜﺎﺒﻴﻨﺔ ﺍﻟﻭﺍﺤﺩﺓ‪:‬‬
‫ﻗﺩﺭﺓ ﻤﺤﺭﻙ ﺍﻟﺠـﺭ = ‪ ٣٦‬ﻙ‪.‬ﻭﺍﺕ )ﻤـﻥ ﺍﻟﻤﺜـﺎل‬
‫ﺍﻟﺴﺎﺒﻕ( ﻭﺒﺎﻋﺘﺒﺎﺭ ﻜﻔﺎﺀﺓ ﺍﻟﻤﺤﺭﻙ ‪٪٨٠‬‬
‫‪٣٦‬‬
‫= ‪٤٥‬‬ ‫ﻗﺩﺭﺓ ﻤﺤﺭﻙ ﻤﺠﻤﻭﻋﺔ ﺍﻟﻤﺤﺭﻙ ‪/‬‬
‫ﻙ‪.‬ﻭ‪.‬‬
‫ﻙ‪.‬ﻭ‪.‬‬ ‫ﻤﻭﻟﺩ =‬
‫‪٠.٨‬‬
‫ﺍﻟﻔﻘﺩ ﻓﻰ ﻤﺠﻤﻭﻋﺔ ﺍﻟﻤﺤﺭﻙ ‪ /‬ﻤﻭﻟﺩ =‬
‫‪ ٤٥‬ﻙ‪.‬ﻭ‪ ٪٩٠ × .‬ﻤﻥ ﺍﻟﺤﻤل × ‪ ٪٧٠‬ﻓﺘـﺭﺓ ﺍﻟﺘﺸـﻐﻴل × ‪ ٪٢٠‬ﻓﻘـﺩ =‬
‫‪ ٥.٦٧‬ﻙ‪.‬ﻭ‪.‬‬
‫ﺘﻜﺎﻓﺊ ﻁﺎﻗﺔ = ‪ ٥.٦٧‬ﻙ‪.‬ﻭ‪.‬ﺴﺎﻋﺔ‬
‫ﺍﻟﻔﻘﺩ ﻓﻰ ﻤﺤﺭﻙ ﺍﻟﺠﺭ =‬
‫‪ ٣٦‬ﻙ‪.‬ﻭ‪ ٪٩٠ × .‬ﻤﻥ ﺍﻟﺤﻤل × ‪ ٪٥٠‬ﻓﺘـﺭﺓ ﺍﻟﺘﺸـﻐﻴل × ‪ ٪٢٠‬ﻓﻘـﺩ =‬
‫‪ ٣.٢٤‬ﻙ‪.‬ﻭ‪.‬‬
‫ﺘﻜﺎﻓﺊ ﻁﺎﻗﺔ ‪ ٣.٢٤‬ﻙ‪.‬ﻭ‪ .‬ﺴﺎﻋﺔ‬
‫ﻤﺠﻤﻭﻉ ﺍﻟﻁﺎﻗﺔ ﻟﻠﻜﺎﺒﻴﻨﺔ = ‪ ٨.٩١ = ٣.٥٤ + ٥.٦٧‬ﻙ‪.‬ﻭﺍﺕ‪ /‬ﺼﺎﻋﺩﺓ‬
‫ﻤﺠﻤﻭﻉ ﺍﻟﻁﺎﻗﺔ ﻟﻌﺩﺩ ‪ ٥‬ﺼﺎﻋﺩﺍﺕ = ‪ ٤٤.٥٥ =٨.٩١×٥‬ﻙ‪.‬ﻭ‪ .‬ﺴﺎﻋﺔ ﻴﺘﻡ‬
‫ﺍﻨﺒﻌﺎﺜﻬﺎ ﺤﺭﺍﺭﻴﺎﹰ ﻓﻰ ﺩﺍﺨل ﻏﺭﻓﺔ ﺍﻟﻤﺎﻜﻴﻨﺎﺕ ﻭﻫﻰ ﻁﺎﻗﺔ ﻓﻘﺩ ﻤﻜﺎﻓﺌﺔ ﻟﻁﺎﻗـﺔ‬
‫ﻓﺭﻥ ﻤﻨﺯﻟﻰ ﻜﺒﻴﺭ ﺒﻁﺎﻗﺔ ﻤﻤﺎ ﻴﺴﺘﺩﻋﻰ ﺘﻬﻭﻴﺔ ﻏﺭﻓﺔ ﺍﻟﻤﺎﻜﻴﻨﺎﺕ ﺠﻴﺩﺍﹰ ﻟﻁـﺭﺩ‬
‫ﺍﻟﺤﺭﺍﺭﺓ ﺨﺎﺭﺝ ﺍﻟﻐﺭﻓﺔ ﻭﻓﻰ ﺒﻌﺽ ﺍﻷﺤﻴﺎﻥ ﻗﺩ ﻴﺴﺘﺩﻋﻰ ﺍﻷﻤﺭ ﺘﻜﻴﻴﻑ ﻫﻭﺍﺀ‬
‫ﻫﺫﻩ ﺍﻟﻐﺭﻓﺔ‪.‬‬
‫ﻤﻠﺤﻭﻅﺔ‪:‬‬
‫ﻻ ﻴﺴﺘﺨﺩﻡ ﻤﻌﺎﻤل ﺘﺒﺎﻴﻥ ﺒﻴﻥ ﺍﻟﻤﺎﻜﻴﻨﺎﺕ ﻫﻨﺎ‪ ،‬ﺤﻴﺙ ﺃﻨﻬﺎ ﺠﻤﻴﻌﻬﺎ ﺘﻌﻤـل ﻭﺃﻥ‬
‫ﺍﻟﺤﺭﺍﺭﺓ ﺘﺭﺍﻜﻤﻴﺔ ﻭﻻ ﻴﺴﺘﺨﺩﻡ ﻤﻌﺎﻤل ﺍﻟﺘﺒﺎﻴﻥ ﺇﻻ ﻟﺤﺴﺎﺏ ﺍﻟﻘﻴﻤـﺔ ﺍﻟﻠﺤﻅﻴـﺔ‬
‫ﻟﻠﺤﻤل ﻓﻘﻁ‪.‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻋﻨﺩ ﺤﺴﺎﺏ ﺘﻜﻠﻔﺔ ﺍﻟﻁﺎﻗﺔ ﺸﻬﺭﻴﺎﹰ ﻟﻠﻤﺼﺎﻋﺩ ﻓﻤﻥ ﺍﻟﻤﻁﻠﻭﺏ ﺘﻘﺩﻴﺭ ﺍﻻﺴﺘﺨﺩﺍﻡ‬
‫ﺍﻟﻜﻠﻰ ﻟﻠﻨﻅﺎﻡ‪ ،‬ﻓﻌﻠﻰ ﺴﺒﻴل ﺍﻟﻤﺜﺎل ﺇﺫﺍ ﻜﺎﻥ ﺍﻟﻨﻅﺎﻡ ﻓﻰ ﻤﺒﻨـﻰ ﻤﻜﺎﺘـﺏ ﻓـﺈﻥ‬
‫ﺘﻔﺼﻴﻠﺔ ﺍﻟﺘﺸﻐﻴل ﻋﻠﻰ ﻤﺩﺍﺭ ﺍﻟﻴﻭﻡ ﻏﺎﻟﺒﺎﹰ ﻤﺎ ﺘﻜﻭﻥ ﻜﺎﻟﺘﺎﻟﻰ‪:‬‬
‫ﻟﻤﺩﺓ ‪ ٢‬ﺴﺎﻋﺔ‬ ‫‪ -‬ﺃﻗﺼﻰ ﺍﺴﺘﺨﺩﺍﻡ ﻟﻠﻤﺼﺎﻋﺩ‬
‫ﻟﻤﺩﺓ ‪ ٢‬ﺴﺎﻋﺔ‬ ‫‪ ٪٧٠ -‬ﻤﻥ ﺃﻗﺼﻰ ﺍﺴﺘﺨﺩﺍﻡ‬
‫ﻟﻤﺩﺓ ‪ ٦‬ﺴﺎﻋﺔ‬ ‫‪ ٪٥٠ -‬ﻤﻥ ﺃﻗﺼﻰ ﺍﺴﺘﺨﺩﺍﻡ‬
‫ﻟﻤﺩﺓ ‪ ١٤‬ﺴﺎﻋﺔ‬ ‫‪ ٪١٠ -‬ﻤﻥ ﺃﻗﺼﻰ ﺍﺴﺘﺨﺩﺍﻡ‬
‫ﻭﻫﺫﺍ ﺍﻟﺘﺸﻐﻴل ﻴﻌﻁﻰ ﻗﻴﻤﺔ ﻤﺘﻭﺴﻁﺔ ‪ ٪٣٢.٥‬ﻤﻥ ﺃﻗﺼﻰ ﺤﻤﻭﻟﺔ ﻟﻠﻤﺠﻤﻭﻋﺔ‪.‬‬
‫ﻭﺘﻜﻭﻥ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻤﺴﺘﻬﻠﻜﺔ ﻟﻜل ﻤﺎﻜﻴﻨﺔ ﻴﻭﻤﻴﺎﹰ =‬
‫‪ ×٪٣٢.٥‬ﺍﻟﻔﻘﺩ ﺍﻟﻜﻠﻰ ×‪ ٢٤‬ﺴﺎﻋﺔ‬
‫= ‪ (٣.٢٤+٥.٦٧)×٠.٣٢٥‬ﻙ‪.‬ﻭ‪ ٢٤×.‬ﺴﺎﻋﺔ‬
‫= ‪٦٩.٥‬ﻙ‪.‬ﻭ ﺴﺎﻋﺔ‪/‬ﻴﻭﻡ‪/‬ﻜﺎﺒﻴﻨﺔ‬
‫ﻭﺒﺫﻟﻙ ﺘﻜﻭﻥ ﺍﻟﺘﻜﻠﻔﺔ ﺍﻟﺸﻬﺭﻴﺔ‬
‫‪ ٠.٢١‬ﺠﻨﻴﻬﺎﹰ‬ ‫‪ ٦٩.٥‬ﻙ‪.‬ﻭ ﺴﺎﻋﺔ‬
‫× ‪ ٢٥‬ﻴﻭﻡ ﺘﺸﻐﻴل ×‬ ‫=‬
‫ﻙ‪.‬ﻭ‪ .‬ﺴﺎﻋﺔ‬ ‫ﻴﻭﻡ‬
‫= ‪ ٣٦٤.٨٦‬ﺠﻨﻴﻬﺎﹰ ‪ /‬ﺸﻬﺭ ‪ /‬ﻜﺎﺒﻴﻨﺔ‬
‫= ‪ ١٨٢٤.٣٢٣‬ﺠﻨﻴﻬﺎﹰ ‪ /‬ﺸﻬﺭ ﻟﻠﻤﺠﻤﻭﻋﺔ‬
‫ﻋﻨﺩ ﺍﺴﺘﺨﺩﺍﻡ ﺘﺤﻜﻡ ﺍﻟﻜﺘﺭﻭﻨﻰ ﻟﻤﺤﺭﻙ ﺍﻟﺠﺭ )ﺜﺎﻴﺭﻴﺴـﺘﻭﺭﺍﺕ( ﺒـﺩﻻﹰ ﻤـﻥ‬
‫ﻤﺠﻤﻭﻋﺔ ﺍﻟﻤﺤﺭﻙ ‪ /‬ﻤﻭﻟﺩ‪ ،‬ﻴﺘﻡ ﺘﺨﻔﻴﺽ ﺍﻟﻘﺩﺭﺓ ﺍﻟﻤﻔﻘﻭﺩﺓ ﻓـﻰ ﺍﻟﻤﺠﻤﻭﻋـﺔ‬
‫ﻭﻜﺫﻟﻙ ﻴﻘل ﺍﻻﺤﺘﻴﺎﺝ ﺇﻟﻰ ﺍﻟﺘﻬﻭﻴﺔ ﺒﺸﻜل ﻤﻠﺤﻭﻅ ﻭﻋﻠﻰ ﺫﻟـﻙ ﻓـﺈﻥ ﺘﻜﻠﻔـﺔ‬
‫ﺍﻟﻁﺎﻗﺔ ﺍﻟﻤﺴﺘﻬﻠﻜﺔ ﺘﻨﺨﻔﺽ ﻟﻘﻴﻤﺔ ﻤﻥ ‪ ٪١٠‬ﺇﻟﻰ ‪ ٪٢٥‬ﻋﻥ ﺤﺎﻟﺔ ﺍﺴـﺘﺨﺩﺍﻡ‬
‫ﻤﺠﻤﻭﻋﺔ ﺍﻟﻤﺤﺭﻙ‪/‬ﻤﻭﻟﺩ ﻭﻴﺘﻡ ﺍﻟﺤﺼﻭل ﻋﻠﻰ ﻭﻓﺭ ﺴﻨﻭﻯ ﻤﻘﺩﺍﺭﻩ‬
‫‪ ١٢‬ﺸﻬﺭﺍﹰ‬ ‫‪١٨٢٤.٣٢٣‬‬
‫= ‪ ٤٣٧٨.٣٧٤‬ﺠﻨﻴﻬﺎﹰ‬ ‫× ‪٪ ٢٠‬‬
‫ﺴﻨﺔ‬ ‫ﺸﻬﺭ‬

‫‪ ٤-١-١‬ﺍﻟﻤﺼﺎﻋﺩ ﺍﻟﻬﻴﺩﺭﻭﻟﻴﻜﻴﺔ‬
‫‪ -‬ﻴﻌﻤل ﻫﺫﺍ ﺍﻟﻤﺼﻌﺩ ﺒﻤﻜﺒﺱ ﻴﺘﺤﺭﻙ ﻫﻴﺩﺭﻭﻟﻴﻜﻴﺎﹰ ﻴﻜﻭﻥ ﻤﺜﺒﺘﺎﹰ ﺒﺄﺴﻔل ﺍﻟﻜﺎﺒﻴﻨﺔ ﻴﺭﻓﻌﻬـﺎ ﺃﻭ‬
‫ﻴﺨﻔﻀﻬﺎ ﻭﺒﺫﻟﻙ ﻻ ﻴﻜﻭﻥ ﻫﻨﺎﻙ ﺍﺤﺘﻴﺎﺝ ﻟﺤﺒﺎل ﺃﻭ ﻁﻨﺎﺒﻴﺭ ﺃﻭ ﻤﺠﻤﻭﻋﺔ ﺍﻟﻤﺤﺭﻙ‪/‬ﻤﻭﻟـﺩ‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻜﻤﺎ ﻫﻭ ﺍﻟﺤﺎل ﻓﻰ ﻤﺼﺎﻋﺩ ﺍﻟﺭﻜﺎﺏ ﺍﻟﻌﺎﺩﻴﺔ ﻭﺘﻜﻭﻥ ﻭﺴﺎﺌل ﺍﻷﻤﺎﻥ ﻭﺍﻟـﺘﺤﻜﻡ ﺒﺴـﻴﻁﺔ‬
‫ﻭﻏﻴﺭ ﻤﻌﻘﺩﺓ ﻤﻤﺎ ﻴﺠﻌل ﻫﺫﺍ ﺍﻟﻨﻭﻉ ﻤﻥ ﺍﻟﻤﺼﺎﻋﺩ ﻤﻨﺎﺴﺒﺎﹰ ﺠﺩﺍﹰ ﻭﺍﻗﺘﺼﺎﺩﻴﺎﹰ ﻓـﻰ ﺤﺎﻟـﺔ‬
‫ﺘﺤﺭﻴﻙ ﺍﻟﻜﺎﺒﻴﻨﺔ ﺒﺴﺭﻋﺎﺕ ﻤﻨﺨﻔﻀﺔ )ﺤﺘﻰ ‪١‬ﻡ‪/‬ﺙ( ﻟﻤﺴﺎﻓﺎﺕ ﻏﻴﺭ ﻤﺭﺘﻔﻌﺔ )ﺤﺘـﻰ ‪٢٥‬‬
‫ﻤﺘﺭﺍﹰ( ﻭﺨﺎﺼﺔ ﺇﺫﺍ ﻜﺎﻨﺕ ﺤﻔﺭﺓ ﺍﻻﺴﻁﻭﺍﻨﺎﺕ ﺍﻟﻬﻴﺩﺭﻭﻟﻴﻜﻴﺔ ﺃﺴـﻔل ﺍﻟﻜﺎﺒﻴﻨـﺔ ﻻ ﺘﻤﺜـل‬
‫ﻤﺸﻜﻠﺔ ﻤﻌﻤﺎﺭﻴﺔ‪.‬‬
‫ﻴﺒﻴﻥ ﺸﻜل )‪ (٧-١‬ﺍﻟﺘﺠﻬﻴﺯﺍﺕ ﺍﻟﻤﻁﻠﻭﺒﺔ ﻟﻠﻤﺼﻌﺩ ﺍﻟﻬﻴﺩﺭﻭﻟﻴﻜﻰ ﺤﻴﺙ ﺘﻜـﻭﻥ ﻫﻨـﺎﻙ‬
‫ﻤﻀﺨﺔ ﻟﺩﻓﻊ ﺍﻟﺯﻴﺕ ﺇﻟﻰ ﺍﻟﻤﻜﺒﺱ ﺍﻟﻬﻴﺩﺭﻭﻟﻴﻜﻲ ﻤﻥ ﺨﺯﺍﻥ ﺍﻟﺯﻴﺕ‪.‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻛﺎﺑﯿﻨﺔ ﺣﻤﻮﻟﺔ ‪ ٧٥٠‬ﻛﺠﻢ‬

‫ﻣﻜﺒﺲ ذو ﻛﺒﺎس ﺗﻠﯿﺴﻜﻮﺑﻲ‬


‫أﻗﺼﻰ ﻋﺪد ﻟﻸﺑﻮاب ‪٣‬‬
‫أﻗﺼﻰ ارﺗﻔﺎع‪٦.٧ :‬م‬
‫ﺧﺰان زﯾﺖ واﻟﻤﻀﺨﺔ‬

‫ﺣﻔﺮة ﻏﯿﺮ ﻋﻤﯿﻘﺔ‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(٧-١‬ﻤﺼﻌﺩ ﻫﻴﺩﺭﻭﻟﻴﻜﻰ ﻤﺯﻭﺩ ﺒﻜﺎﺒﻴﻨﺔ ﺭﻜﺎﺏ ﺤﻤﻭﻟﺔ ‪ ٧٥٠‬ﻜﺠﻡ‬


‫ﺴﺭﻋﺔ ‪ ٠.٣٧٥‬ﻡ‪/‬ﺙ ﻻﺭﺘﻔﺎﻉ ﺤﻭﺍﻟﻰ ‪ ٨‬ﻡ‬

‫‪ -‬ﻤﻥ ﺍﻟﻌﻴﻭﺏ ﺍﻟﺭﺌﻴﺴﻴﺔ ﻟﻠﻤﺼﻌﺩ ﺍﻟﻬﻴﺩﺭﻭﻟﻴﻜﻰ ﺘﻜﻠﻔﺔ ﺍﻟﺘﺸﻐﻴل ﺍﻟﻤﺭﺘﻔﻌﺔ‪ ،‬ﻓﺒﺴـﺒﺏ‬


‫ﻏﻴﺎﺏ ﺜﻘل ﺍﻟﻤﻭﺍﺯﻨﺔ ﻴﺤﺘﺎﺝ ﻫﺫﺍ ﺍﻟﻤﺼﻌﺩ ﺇﻟﻰ ﻤﺤﺭﻙ ﺒﻘـﺩﺭﺓ ﻜﺒﻴـﺭﺓ ﻟﺘﺸـﻐﻴل‬
‫ﻤﻀﺨﺔ ﺍﻟﺯﻴﺕ ﻭﺘﻜﻭﻥ ﻜل ﺍﻟﻁﺎﻗﺔ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻤﻔﻘﻭﺩﺓ ﺤﺭﺍﺭﻴﺎﹰ‪.‬‬
‫ﻤﺜﺎل‪:‬‬
‫ﻴﺤﺘﺎﺝ ﻤﺼﻌﺩ ﻫﻴﺩﺭﻭﻟﻴﻜﻰ ﻴﺤﺭﻙ ﻭﺯﻨﺎﹰ ﻤﻘﺩﺍﺭﻩ ‪ ١٧٥٠‬ﻜﺠﻡ ﺒﺴـﺭﻋﺔ ‪٠.٦٢٥‬‬
‫ﻡ‪/‬ﺙ ﻓﻰ ﻤﺒﻨﻰ ﻤﺨﺎﺯﻥ ﺇﻟﻰ ﻤﺤﺭﻙ ﻟﻤﻀﺨﺔ ﺍﻟﺯﻴـﺕ ﻗـﺩﺭﺓ ‪ ٣٠‬ﻙ‪.‬ﻭ‪ ،.‬ﻓـﺈﺫﺍ‬
‫ﻜﺎﻨﺕ ﺍﻟﻭﺤﺩﺓ ﺘﻌﻤل ‪ ١٠‬ﺴﺎﻋﺎﺕ‪/‬ﻴﻭﻡ ﻟﻤﺩﺓ ‪ ٦‬ﺃﻴﺎﻡ ﻓﻰ ﺍﻷﺴﺒﻭﻉ‪ ،‬ﻭﺒﺎﻋﺘﺒـﺎﺭ ﺃﻥ‬
‫ﻨﺴﺒﺔ ﺍﻟﺘﺸﻐﻴل ﺍﻟﻌﺎﺩﻴﺔ ﻫﻰ ‪) ٪٦٠‬ﻤﻠﺤﻭﻅﺔ‪ :‬ﺍﻟﻤﺤﺭﻙ ﻴﻌﻤل ﻓﻘـﻁ ﻓـﻰ ﺍﺘﺠـﺎﻩ‬
‫ﺍﻟﺭﻓﻊ( ‪ ،‬ﻭﺒﺫﻟﻙ ﺘﻜﻭﻥ‪:‬‬
‫ﺍﻟﻁﺎﻗﺔ ﺍﻟﻤﺴﺘﻬﻠﻜﺔ ‪ /‬ﻴﻭﻡ =‬
‫‪١‬‬ ‫‪ ٣٠‬ﻙ‪.‬ﻭ‬
‫= ‪ ١١٠‬ﻙ‪.‬ﻭ‪ .‬ﺴﺎﻋﺔ‬ ‫× ‪ ١٠ × ٪٦٠‬ﺴﺎﻋﺔ ×‬
‫‪٢‬‬ ‫ﻜﻔﺎﺀﺓ ‪٪٨٢‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻭﺘﻜﻭﻥ ﺘﻜﻠﻔﺔ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻤﺴﺘﻬﻠﻜﺔ ﺸﻬﺭﻴﺎﹰ =‬


‫‪ ٤.٣٣‬ﺃﺴﺒﻭﻉ‬ ‫‪ ٦‬ﺃﻴﺎﻡ‬ ‫‪ ١١٠‬ﻙ‪.‬ﻭ‪.‬ﺴﺎﻋﺔ‬
‫× ‪ ٠.٢١‬ﺠﻨﻴﻬﺎﹰ‪/‬ﻙ‪.‬ﻭ‪.‬ﺴﺎﻋﺔ‬ ‫×‬ ‫×‬
‫ﺸﻬﺭ‬ ‫ﺃﺴﺒﻭﻉ‬ ‫ﻴﻭﻡ‬
‫= ‪ ٦٠٠‬ﺠﻨﻴﻬﺎﹰ ‪ /‬ﺸﻬﺭ‬

‫ﻤﻠﺤﻭﻅﺔ‪:‬‬
‫ﺒﻤﻘﺎﺭﻨﺔ ﻫﺫﻩ ﺍﻟﻘﻴﻤﺔ ﺒﺎﻟﺘﻜﻠﻔﺔ ﺍﻟﺸﻬﺭﻴﺔ ﻟﻠﻤﺼﻌﺩ ﺍﻟﻌﺎﺩﻯ ﺍﻟـﺫﻱ ﻴﻌﻤـل ﺒﻤﺤـﺭﻙ‬
‫ﻜﻬﺭﺒﺎﺌﻲ ﻭﻜﺎﻨﺕ ‪ ٣١٦.٢٥‬ﺠﻨﻴﻬﺎﹰ‪/‬ﺸﻬﺭ‪/‬ﻜﺎﺒﻴﻨﺔ ‪ ،‬ﻴﺘﻀﺢ ﺍﺭﺘﻔﺎﻉ ﺘﻜﻠﻔﺔ ﺍﻟﺘﺸـﻐﻴل‬
‫ﻓﻰ ﺤﺎﻟﺔ ﺍﻟﻤﺼﻌﺩ ﺍﻟﻬﻴﺩﺭﻭﻟﻴﻜﻰ ﻭﺘﺄﺜﻴﺭ ﻭﺠﻭﺩ ﺜﻘل ﺍﻟﻤﻭﺍﺯﻨـﺔ ﻓـﻰ ﺍﻟﻤﺼـﻌﺩ‬
‫ﺍﻟﻌﺎﺩﻱ‪.‬‬

‫‪ ٥-١-١‬ﺍﻟﺴﻼﻟﻡ ﺍﻟﻤﺘﺤﺭﻜﺔ‬
‫‪ -‬ﺘﻘﻭﻡ ﻫﺫﻩ ﺍﻟﺴﻼﻟﻡ ﺒﺘﻭﻓﻴﺭ ﺍﻟﺭﺍﺤﺔ ﻭﺍﻷﻤﺎﻥ ﻭﺴﺭﻋﺔ ﻨﻘل ﺍﻷﺤﻤﺎل ﺍﻟﺤﻴﺔ ﺒﺼﻔﺔ ﻤﺴﺘﻤﺭﺓ‬
‫ﻋﻨﺩ ﺴﺭﻋﺔ ﺜﺎﺒﺘﺔ ﻭﺒﺩﻭﻥ ﻓﺘﺭﺍﺕ ﺍﻨﺘﻅﺎﺭ‪.‬‬
‫‪ -‬ﺘﺼﻤﻡ ﻫﺫﻩ ﺍﻟﺴﻼﻟﻡ ﻋﺎﺩﺓ ﻟﻠﻌﻤل ﺒﺴﺭﻋﺘﻴﻥ ﻟﻠﺤﺭﻜﺔ ‪ ٠.٤٥‬ﻡ‪/‬ﺙ ﻭ ‪ ٠.٦‬ﻡ‪/‬ﺙ ﻭﺘﻜـﻭﻥ‬
‫ﺍﻟﺴﺭﻋﺔ ﺍﻟﻌﺎﻟﻴﺔ ﺃﺜﻨﺎﺀ ﻓﺘﺭﺍﺕ ﺍﻟﺫﺭﻭﺓ ﻭﺍﻟﺴﺭﻋﺔ ﺍﻟﻤﻨﺨﻔﻀﺔ ﻓﻰ ﺨـﻼﻑ ﺫﻟـﻙ ﻭﻫـﻰ‬
‫ﺍﻟﻤﻔﻀﻠﺔ ﻋﻤﻭﻤﺎﹰ ﺤﻴﺙ ﺘﻤﺜل ﺍﻟﺴﺭﻋﺔ ﺍﻟﻌﺎﻟﻴﺔ ﻤﺸﺎﻜل ﻟﺒﻌﺽ ﺍﻟﺭﻜﺎﺏ‪.‬‬
‫‪ -‬ﻴﺘﻡ ﺘﺤﺭﻴﻙ ﺍﻟﺴﻠﻡ ﻓﻰ ﺤﺎﻻﺕ ﺍﻻﺭﺘﻔﺎﻋﺎﺕ ﺤﺘﻰ ‪ ٢٠‬ﻤﺘﺭﺍﹰ ﻋﻨﺩ ﻨﻘﻁﺔ ﻭﺍﺤـﺩﺓ ﻭﺫﻟـﻙ‬
‫ﺒﺎﺴﺘﺨﺩﺍﻡ ﻤﺤﺭﻙ ﻭﺍﺤﺩ ﻴﻘﻭﻡ ﺒﺘﺩﻭﻴﺭ ﻜﺎﺘﻴﻨﺔ ﺍﻟﺘﺤﺭﻴﻙ ﺍﻟﺭﺌﻴﺴﻴﺔ ﺍﻟﺘﻰ ﺘﺘـﻭﻟﻰ ﺘﺤﺭﻴـﻙ‬
‫ﻜﺎﺘﻴﻨﺔ ﺍﻟﺩﺭﺝ ﻭﺘﺴﺤﺒﻬﺎ ﺠﻤﻴﻌﻬﺎ ﻤﻤﺎ ﻴﺅﺩﻯ ﺇﻟﻰ ﺘﺤﺭﻴﻙ ﺍﻟﺘﺠﻤﻴﻌﺔ ﺒﺎﻟﻜﺎﻤل ﻭﻜﻤﺎ ﻴﺘﻀﺢ‬
‫ﻤﻥ ﺸﻜل )‪.(٨-١‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻛﺎﺗﯿﻨﺔ ﺗﺤﺮﯾﻚ اﻟﺒﻜﺮة‬ ‫ﺳﻄﺢ‬


‫ﺑﻜﺮة ﺗﺤﺮﯾﻚ دراﺑﺰﯾﻦ اﻟﯿﺪ‬
‫ﺗﺮس ﻣﺴﻨﻦ ﻋﻠﻮى‬ ‫ﻣﺒﯿﺖ اﻟﻤﻨﺤﻨﻰ اﻟﻌﻠﻮي‬
‫ﻟﺘﺤﺮﯾﻚ اﻟﻘﻤﺔ‬
‫ﻛﺎﺗﯿﻨﺔ اﻟﺪرج‬
‫ﻋﺮض‬
‫ﻓﺮاﻣﻞ ﻃﻮارئ‬ ‫اﻟﻤﻨﺸﺄ‬

‫ﻣﺎﻛﯿﻨﺔ اﻟﺘﺤﺮﯾﻚ‬
‫ﺑﻜﺮة ﺷﺪ دراﺑﺰﯾﻦ‬
‫اﻟﯿﺪ‬ ‫ﻣﺠﺮى وﺣﻤﺎﯾﺔ‬
‫ﻛﺎﺗﯿﻨﺔ اﻟﺘﺤﺮﯾﻚ‬
‫اﻟﺮﺋﯿﺴﯿﺔ‬
‫ﻏﺮﻓﺔ اﻟﻤﺎﻛﯿﻨﺎت اﻟﺨﺎرﺟﯿﺔ ﻻرﺗﻔﺎﻋﺎت‬
‫اﻛﺒﺮ ﻣﻦ ‪ ٧.٥‬م‬ ‫ﺗﺮس ﻣﺴﻨﻦ‬
‫ﺳﻔﻠﻲ‬

‫وﺳﯿﻠﺔ ﺷﺪ‬
‫اﻟﻌﺮﺑﺔ‬
‫ﺷﻜﻞ رﻗﻢ )‪ :(٨-١‬ﻧﻤﻮذج ﺗﺤﺮﯾﻚ اﻟﺴﻠﻢ اﻟﻜﮭﺮﺑﺎﺋﻲ ﺑﺎﻟﺘﺼﻤﯿﻢ اﻟﺘﻘﻠﯿﺪي ﻓﻲ وﺟﻮد ﻧﻈﺎم‬
‫اﻟﺘﺤﺮﯾﻚ ﻓﻲ أﻋﻠﻰ ﻧﻘﻄﺔ ﻟﻼرﺗﻔﺎﻋﺎت ﻣﺎ ﺑﯿﻦ ‪ ٢.٥‬و ‪ ١٨‬ﻣﺘﺮاً‪.‬‬

‫‪ -‬ﻓﻰ ﺤﺎﻟﺔ ﺯﻴﺎﺩﺓ ﺍﺭﺘﻔﺎﻉ ﺍﻟﻤﺴﺎﻓﺔ ﺍﻟﺘﻰ ﻴﻨﻘل ﺒﻴﻨﻬﺎ ﺍﻟﺴﻠﻡ‪ ،‬ﻓﺘﻜﻭﻥ ﻫﻨﺎﻙ ﻤﺤﺭﻜﺎﺕ ﻤﻨﺘﺸﺭﺓ‬
‫ﻋﻠﻰ ﻁﻭل ﺍﻟﻭﺤﺩﺓ ﻭﻴﺒﻴﻥ ﺠﺩﻭل )‪ (٢-١‬ﻗﺩﺭﺍﺕ ﺍﻟﻤﺤﺭﻜﺎﺕ ﺍﻟﻤﻁﻠﻭﺒـﺔ ﻟﻼﺭﺘﻔﺎﻋـﺎﺕ‬
‫ﺍﻟﻤﺨﺘﻠﻔﺔ ﻭﻁﺒﻘﺎﹰ ﻟﻌﺭﺽ ﺍﻟﺴﻠﻡ‪ ،‬ﻭﻴﻭﻀﺢ ﺸﻜل )‪ (٩-١‬ﺭﺴـﻤﺎﹰ ﺘﺨﻁﻴﻁﻴـﺎﹰ ﻟﻠﻭﺤـﺩﺍﺕ‬
‫ﺍﻟﻤﺘﻜﺭﺭﺓ ﻭﻓﻴﻬﺎ ﻴﺘﻡ ﺘﻭﺯﻴﻊ ﻭﺤﺩﺍﺕ ﺍﻟﺘﺤﺭﻴﻙ ﻋﻠﻰ ﻁﻭل ﺍﻟﺴﻠﻡ ﺒﺎﻷﻋـﺩﺍﺩ ﺍﻟﻤﺘﻜـﺭﺭﺓ‬
‫ﺍﻟﻀﺭﻭﺭﻴﺔ ﻟﻼﺭﺘﻔﺎﻉ ﺍﻟﻤﻁﻠﻭﺏ‪.‬‬
‫ﻭﻴﺒﻴﻥ ﺸﻜل )‪ (١٠-١‬ﻨﻅﺎﻡ ﻤﻴﻜﻨﺔ ﺘﺸﻐﻴل ﺍﻟﺴﻠﻡ ﺫﻭ ﺍﻟﻭﺤـﺩﺍﺕ ﺍﻟﻤﺘﻜـﺭﺭﺓ‪ ،‬ﻭﺘﺼـﻨﻴﻑ‬
‫ﺍﻟﻤﺤﺭﻜﺎﺕ ﺍﻟﻤﻭﺯﻋﺔ ﻋﻠﻰ ﻁﻭل ﺍﻟﺴﻠﻡ ﻗﻭﺓ ﻤﺤﺭﻜﺔ ﻋﻠﻰ ﻁﻭل ﻜﺎﺘﻴﻨﺔ ﺍﻟﺘﺤﺭﻴﻙ‪.‬‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪ :(٢-١‬ﻤﺤﺭﻜﺎﺕ ﺍﻟﺴﻼﻟﻡ ﺍﻟﻤﺘﺤﺭﻜﺔ‬

‫‪١٢١٠‬‬ ‫‪٨١٠‬‬ ‫ﻋﺭﺽ ﺍﻟﺴﻠﻡ )ﻤﻡ(‬


‫ﻤﻥ ‪ ٠.٤٥‬ﺇﻟﻰ ‪٠.٦‬‬ ‫ﻤﻥ ‪ ٠.٤٥‬ﺇﻟﻰ ‪٠.٦‬‬ ‫ﺍﻟﺴﺭﻋﺔ )ﻡ‪/‬ﺙ(‬
‫‪٧.٥‬‬ ‫‪٧.٥‬‬ ‫ﻗﺩﺭﺓ ﺍﻟﻤﺤﺭﻙ ﺍﻟﻭﺍﺤﺩ )ﻙ‪.‬ﻭ(‬
‫‪٦.٥‬‬ ‫‪١٠‬‬ ‫ﻤﺤﺭﻙ ﻭﺍﺤﺩ‬ ‫ﺃﻗﺼﻰ ﺍﺭﺘﻔﺎﻉ‬
‫‪١٣.٥‬‬ ‫‪٢٠‬‬ ‫‪ ٢‬ﻤﺤﺭﻙ‬ ‫ﻴﺨﺩﻤﻪ ﺍﻟﺴﻠﻡ‬
‫‪٢٠‬‬ ‫‪٣٠‬‬ ‫‪ ٣‬ﻤﺤﺭﻜﺎﺕ‬ ‫ﻋﻨﺩ ﺍﺴﺘﺨﺩﺍﻡ‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ارﺗﻔﺎع ﻏﯿﺮ ﻣﺤﺪود‬


‫ﯾﺘﺤﺪد ﻋﺪد اﻟﻤﺤﺮﻛﺎت ﻛﻞ ‪٥‬م‬
‫)ﻣﺴﺎﻓﺔ ﺑﻤﺤﺮك وﻣﺴﺎﻓﺔ ﺑﺪون ﻣﺤﺮك(‬

‫أﻗﺼﻰ ارﺗﻔﺎع ‪١٠‬م‬


‫ﻋﺪد ‪ ٢‬ﻣﺤﺮك‬

‫أﻗﺼﻰ ارﺗﻔﺎع ‪ ٥‬م‬


‫ﻋﺪد ‪ ١‬ﻣﺤﺮك‬

‫ﺷﻜﻞ رﻗﻢ )‪ :(٩-١‬ﻧﻈﺎم ﺑﻮﺣﺪات ﺗﻜﺮارﯾﺔ ﯾﺘﺤﺪد ﺑﮫ ﻋﺪد ﺑﻜﺮ اﻟﺘﺤﺮﯾﻚ ﺑﺎرﺗﻔﺎع ﻣﺴﺎﻓﺔ اﻟﻨﻘﻞ‬
‫ﺑﺎﻟﺴﻠﻢ اﻟﻜﮭﺮﺑﺎﺋﻲ ﻋﺮض ‪ ٨١٠‬ﻣﻢ‬

‫دراﺑﺰﯾﻦ ﯾﺪ ودﻟﯿﻞ‬
‫ﻣﺴﺘﻤﺮ‬

‫ﺗﺤﺮﯾﻚ دراﺑﺰﯾﻦ اﻟﯿﺪ‬

‫ﺗﺤﺮﯾﻚ ﯾﺪ اﻟﺘﻮﻗﯿﺖ‬

‫ﻣﺒﯿﺖ ﺑﻜﺮة‬
‫ﻣﺒﯿﺖ ﺑﻜﺮة‬ ‫اﻟﺪرج‬
‫ﺗﻮﺟﯿﮫ اﻟﺪرج‬

‫وﺣﺪة ﺗﺤﺮﯾﻚ‬

‫ﺷﻜﻞ رﻗﻢ )‪ :(١٠-١‬ﻧﻈﺎم اﻟﺘﺤﺮﯾﻚ اﻟﺤﺪﯾﺚ ﺑﺎﺳﺘﺨﺪام ﻣﺤﺮﻛﺎت ﻓﻲ أﻣﺎﻛﻦ‬


‫ﻣﺨﺘﻠﻔﺔ ﻋﻠﻰ اﻣﺘﺪاد ﺳﻠﻢ اﻟﺘﺤﺮﯾﻚ اﻟﻜﮭﺮﺑﺎﺋﻲ‪.‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻤﺘﻁﻠﺒﺎﺕ ﺍﻟﻘﺩﺭﺓ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻟﻠﺴﻼﻟﻡ ﺍﻟﻤﺘﺤﺭﻜﺔ‬


‫ﻴﺘـــﻡ ﺇﺩﺍﺭﺓ ﺍﻟﺴﻼﻟﻡ ﺒﻤﺤــﺭﻜﺎﺕ ﻜﻬــﺭﺒﺎﺌﻴﺔ ﺤﺜﻴﺔ ﺜﻼﺜﻴــﺔ ﺍﻷﻁﻭﺍﺭ ﻋﻨـﺩ ‪٥٠‬‬
‫ﺃﻭ ‪٦٠‬ﻫﺭﺘﺯ‪.‬‬
‫ﻭﻴﺒﻴﻥ ﺠﺩﻭل )‪ (٣-١‬ﻗﺩﺭﺍﺕ ﺍﻟﻤﺤﺭﻜﺎﺕ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻓﻰ ﺘﺤﺭﻴﻙ ﺍﻟﺴﻠﻡ ﺇﻟﻰ ﺍﺭﺘﻔﺎﻋﺎﺕ ﻻ‬
‫ﺘﺯﻴﺩ ﻋﻥ ‪ ٦.٥‬ﻤﺘﺭﺍﹰ‪.‬‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪ :(٣-١‬ﺍﻟﻘﺩﺭﺓ ﺍﻟﻨﻤﻭﺫﺠﻴﺔ ﻟﻠﻤﺤﺭﻜﺎﺕ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻤﻊ ﺍﻟﺴﻼﻟﻡ ﺍﻟﻤﺘﺤﺭﻜﺔ‬

‫ﻗﺩﺭﺓ ﺍﻟﻤﺤﺭﻙ‬ ‫ﺍﻻﺭﺘﻔﺎﻉ‬ ‫ﺍﻟﺴﺭﻋﺔ‬ ‫ﻋﺭﺽ ﺍﻟﺴﻠﻡ‬


‫)ﻙ‪.‬ﻭ(‬ ‫)ﻡ(‬ ‫)ﻡ‪/‬ﺙ(‬ ‫)ﻤﻡ(‬
‫‪٣.٧٥‬‬ ‫‪٤.٢٥‬‬ ‫‪ -‬ﻤﻥ ‪ ٠.٤٥‬ﺇﻟﻰ ‪٠.٦‬‬ ‫‪٨١٠‬‬
‫‪٥.٠٠‬‬ ‫‪٥.٢‬‬ ‫‪ -‬ﻤﻥ ‪ ٠.٤٥‬ﺇﻟﻰ ‪٠.٦‬‬
‫‪٥.٠٠‬‬ ‫‪٥.٢٠‬‬ ‫‪٠.٤٥ -‬‬
‫‪٧.٥‬‬ ‫‪٦.٤٠‬‬ ‫‪٠.٤٥ -‬‬ ‫‪١٢١٠‬‬
‫‪١١.٢‬‬ ‫‪٧.٦٠‬‬ ‫‪ -‬ﻤﻥ ‪ ٠.٤٥‬ﺇﻟﻰ ‪٠.٦‬‬

‫ﻤﻠﺤﻭﻅﺔ‪:‬‬
‫)‪ (١‬ﻤﻥ ﺍﻟﻤﻭﺼﻰ ﺒﻪ ﻋﺩﻡ ﺘﻐﺫﻴﺔ ﺃﻜﺜﺭ ﻤﻥ ‪ ٤‬ﺴﻼﻟﻡ ﻤﻥ ﻤﻐـﺫﻯ ﻜﻬﺭﺒـﺎﺌﻰ ﻭﺍﺤـﺩ‬
‫)‪.(Single electric feeder‬‬
‫)‪ (٢‬ﻻ ﻴﻨﺼﺢ ﺃﻴﻀﺎﹰ ﺒﺘﻐﺫﻴﺔ ﺠﻤﻴﻊ ﺍﻟﺴﻼﻟﻡ ﻟﻤﺒﻨﻰ ﻤﻬﻤﺎ ﻜـﺎﻥ ﻋـﺩﺩﻫﺎ ﻤـﻥ ﻨﻔـﺱ‬
‫ﺍﻟﻤﻐﺫﻯ‪.‬‬
‫)‪ (٣‬ﻨﻅﺭﺍﹰ ﻷﻥ ﺭﺍﻜﺒﻰ ﺍﻟﺴﻼﻟﻡ ﺍﻟﻤﺘﺤﺭﻜﺔ ﻟﻥ ﺘﻌﺎﻕ ﺤﺭﻜﺘﻬﻡ ﺇﺫﺍ ﺍﻨﻘﻁﻌـﺕ ﺍﻟﺘﻐﺫﻴـﺔ‬
‫ﺍﻟﻌﻤﻭﻤﻴﺔ‪ ،‬ﻓﻼ ﻴﺘﻁﻠﺏ ﺍﻷﻤﺭ ﺘﻐﺫﻴﺔ ﺍﻟﺴﻼﻟﻡ ﻤﻥ ﺍﻟﻤﺼﺎﺩﺭ ﺍﻻﺤﺘﻴﺎﻁﻴﺔ ﻟﻠﻘﻭﻯ‪.‬‬
‫)‪ (٤‬ﻴﺠﺏ ﺘﻬﻭﻴﺔ ﻏﺭﻓﺔ ﺍﻟﻤﺤﺭﻙ ﻭﻤﺭﺍﻋﺎﺓ ﺃﻥ ﺤـﻭﺍﻟﻰ ‪ ٪ ٤٠‬ﻤـﻥ ﺍﻟﻘـﺩﺭﺓ ﺘﻔﻘـﺩ‬
‫ﺤﺭﺍﺭﻴﺎﹰ‪ ،‬ﻓﻌﻠﻰ ﺴﺒﻴل ﺍﻟﻤﺜﺎل ﺇﺫﺍ ﻜـﺎﻥ ﺍﻟﻤﺤـﺭﻙ ﺒﻘـﺩﺭﺓ ‪ ٧.٥‬ﻙ‪.‬ﻭ‪ .‬ﻓﺘﻜـﻭﻥ‬
‫ﺍﻟﺤﺭﺍﺭﺓ ﺍﻟﻤﻔﻘﻭﺩﺓ ﻤﻨﻪ ﻓﻰ ﺍﻟﻤﻜﺎﻥ‪:‬‬
‫)‪ ٧.٥×٠.٤‬ﻙ‪.‬ﻭ‪ ١٠٢٥٠ ~ (٣٤١٥.٢ × .‬ﻭ‪.‬ﺡ‪.‬ﺏ‪/‬ﺴﺎﻋﺔ‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫‪ ٦-١-١‬ﺍﻟﺤﺼﺎﺌﺭ ﻭﺍﻟﻤﻨﺤﺩﺭﺍﺕ ﺍﻟﻤﺘﺤﺭﻜﺔ )‪(Moving walks and ramps‬‬


‫‪ -‬ﻴﺘﻭﻟﻰ ﻫﺫﺍ ﺍﻟﻨﻭﻉ ﻤﻥ ﺍﻟﻤﺼﺎﻋﺩ ﺍﻟﻨﻘل ﺇﻤﺎ ﺃﻓﻘﻴﺎﹰ ﻓﻘﻁ ﺃﻭ ﺃﻓﻘﻴﺎﹰ ﻭﺭﺃﺴﻴﺎﹰ ﻓﻰ ﺸﻜل ﺘﺠﻤﻴﻌﻰ‬
‫)ﻨﺴﺒﺔ ﺍﻟﻤﻴل ﻻ ﺘﺯﻴﺩ ﻋﻥ ‪ ٥‬ﺩﺭﺠﺎﺕ ﻓﻰ ﺤﺎﻟﺔ ﺍﻟﺤﺼـﺎﺌﺭ ﻭ‪ ١٥‬ﺩﺭﺠـﺔ ﻓـﻰ ﺤﺎﻟـﺔ‬
‫ﺍﻟﻤﻨﺤﺩﺭﺍﺕ ﺍﻟﻤﺘﺤﺭﻜﺔ(‪.‬‬
‫‪ -‬ﻴﺴﺘﺨﺩﻡ ﻫﺫﺍ ﺍﻟﻨﻭﻉ ﻓﻰ ﺍﻟﻤﻁﺎﺭﺍﺕ ﻟﻨﻘل ﺍﻷﻓﺭﺍﺩ ﻭﻋﺭﺒﺎﺕ ﺍﻷﻤﺘﻌـﺔ ﺭﺃﺴـﻴﺎﹰ ﺃﻭ ﻨﻘـل‬
‫ﺍﻷﻓﺭﺍﺩ ﺍﻟﺫﻴﻥ ﻗﺩ ﻻ ﻴﻤﻜﻨﻬﻡ ﺍﺴﺘﺨﺩﺍﻡ ﺍﻟﺴﻼﻟﻡ ﺍﻟﻤﺘﺤﺭﻜﺔ‪ ،‬ﻜﻤﺎ ﻴﺴﺘﺨﺩﻡ ﺃﻴﻀﺎﹰ ﻓﻰ ﻨﻘـل‬
‫ﺍﻷﺸﻴﺎﺀ ﻜﺒﻴﺭﺓ ﺍﻟﺤﺠﻡ ﻭﺘﺴﺘﺨﺩﻡ ﺃﻴﻀﺎﹰ ﻓﻰ ﺘﺠﻤﻌﺎﺕ ﺍﻟﺘﺴﻭﻕ ﻤﺘﻌﺩﺩﺓ ﺍﻟﻁﻭﺍﺒﻕ ﺤﻴـﺙ ﻻ‬
‫ﺘﻨﺎﺴﺏ ﺍﻟﺴﻼﻟﻡ ﺍﻟﻤﺘﺤﺭﻜﺔ ﺍﻨﺘﻘﺎل ﺍﻷﻓﺭﺍﺩ ﺒﻌﺭﺒﺎﺕ ﺍﻟﻤﺸﺘﺭﻴﺎﺕ ﺒﻴﻥ ﺍﻟﻤﺴﺘﻭﻴﺎﺕ ﺍﻟﻤﺨﺘﻠﻔﺔ‬
‫ﺃﻭ ﺍﻨﺘﻘﺎﻟﻬﻡ ﺇﻟﻰ ﺃﻤﺎﻜﻥ ﺍﻨﺘﻅﺎﺭ ﺍﻟﺴﻴﺎﺭﺍﺕ ﺍﻟﻤﻭﺠﻭﺩﺓ ﺒﺴﻁﺢ ﺍﻟﻤﺒﻨﻰ‪.‬‬
‫‪ -‬ﻻ ﻴﻤﻜﻥ ﻫﻨﺎ ﺘﺤﺩﻴﺩ ﺒﻴﺎﻨﺎﺕ ﻋﻥ ﻗﺩﺭﺍﺕ ﺍﻟﻤﺤﺭﻜﺎﺕ ﺍﻟﻤﻁﻠﻭﺒﺔ ﻟﺘﺤﺭﻴﻙ ﻫﺫﺍ ﺍﻟﻨﻭﻉ ﻤـﻥ‬
‫ﻭﺴﺎﺌل ﺍﻟﻨﻘل‪ ،‬ﻭﻴﺠﺏ ﺍﻟﺭﺠﻭﻉ ﺇﻟﻰ ﺍﻟﻤﺼﻨﻊ ﻓﻰ ﻁﻠﺏ ﻤﻌﺭﻓﺔ ﺍﻟﻘﺩﺭﺓ ﺍﻟﻤﻁﻠﻭﺒﺔ‪.‬‬
‫‪ -‬ﻴﺒﻴﻥ ﺸﻜل )‪ (١١-١‬ﺤﺼﺎﺌﺭ ﻤﺘﺤﺭﻜﺔ ﻟﻠﻤﺸﺎﻩ ﺜﻨﺎﺌﻴﺔ ﺍﻟﻤﻤﺭﺍﺕ ﻓﻰ ﺃﺤـﺩ ﺍﻟﻤﻁـﺎﺭﺍﺕ‬
‫ﺒﻌﺭﺽ ‪١‬ﻡ ﻟﻜل ﻤﻤﺸﻰ ﻭﺒﻁﻭل ‪٥٥‬ﻡ ﻭﺘﺩﺍﺭ ﻜل ﻤﻨﻬﺎ ﺒﻤﺤﺭﻙ ﻭﺍﺤﺩ ﻭﺘﺘﺤـﺭﻙ ﻓـﻰ‬
‫ﺍﺘﺠﺎﻫﻴﻥ ﻤﺘﻀﺎﺩﻴﻥ‪.‬‬
‫‪ -‬ﻴﺒﻴﻥ ﺸﻜل )‪ (١٢-١‬ﻤﻨﺤﺩﺭ ﻤﺘﺤﺭﻙ ﻴﻨﻘل ﻤﺎ ﺒﻴﻥ ﺩﻭﺭﻴﻥ ﻓﻰ ﻤﺠﻤﻊ ﺘﺠﺎﺭﻯ ﻭﻴﻤﻜـﻥ‬
‫ﺃﻥ ﻴﻜﻭﻥ ﺒﻌﺭﺽ ‪ ٦٦٠‬ﻤﻡ ﻟﺭﺍﻜﺏ ﻭﺍﺤﺩ ﺃﻭ ﺒﻌﺭﺽ ‪١٠٠٠‬ﻤﻡ ﻟﺭﺍﻜﺒﻴﻥ ﻭﻴﻜﻭﻥ ﻋﺎﺩﺓ‬
‫ﺒﺯﻭﺍﻴﺎ ﺍﻨﺤﺩﺍﺭ ﻭﺴﺭﻋﺎﺕ ﻤﺨﺘﻠﻔﺔ‪.‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(١١-١‬ﺤﺼﺎﺌﺭ ﻤﺘﺤﺭﻜﺔ ﻓﻰ ﺍﺘﺠﺎﻫﻴﻥ ﻤﺘﻀﺎﺩﻴﻥ‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(١٢-١‬ﻤﻨﺤﺩﺭﺍﺕ ﻤﺘﺤﺭﻜﺔ ﺒﻴﻥ ﺩﻭﺭﻴﻥ ﻓﻰ ﻤﺠﻤﻊ ﺘﺠﺎﺭﻯ‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺃﻋﻤﺎل ﺘﻜﻴﻴﻑ ﺍﻟﻬﻭﺍﺀ ﺒﺎﻟﻤﺒﺎﻨﻰ‬ ‫‪٢-١‬‬


‫ﻋﺎﻡ‬
‫)‪ (١‬ﻴﺘﻡ ﺍﺴﺘﺨﺩﺍﻡ ﺍﻟﻬﻭﺍﺀ ﻟﺘﺩﻓﺌﺔ ﺃﻭ ﺘﺒﺭﻴﺩ ﺤﻴﺯ ﻟﻤﺎ ﻟﺫﻟﻙ ﻤﻥ ﻓﻭﺍﺌـﺩ ﻤﺤـﺩﺩﺓ ﻤﻨﻬـﺎ ﺃﻥ‬
‫ﺘﺤﺭﻴﻙ ﺍﻟﻬﻭﺍﺀ ﻓﻰ ﺍﻟﻤﻜﺎﻥ ﻴﻀﻤﻥ ﺘﺤﻘﻴﻕ ﺸﺭﻭﻁ ﺫﺍﺕ ﻨﺴﻕ ﻭﺍﺤﺩ ﻭﺍﻨﺘﺸﺎﺭ ﻤﺘﺴﺎﻭ‬
‫ﻟﺩﺭﺠﺎﺕ ﺤﺭﺍﺭﺓ ﻤﻨﺎﺴﺒﺔ ﻓﻰ ﻜل ﺃﺠﺯﺍﺀ ﺍﻟﺒﻴﺕ‪.‬‬
‫)‪ (٢‬ﻴﺘﻡ ﺩﻓﻊ ﻫﻭﺍﺀ ﺨﺎﺭﺠﻰ ﺇﻟﻰ ﺍﻟﻤﻜﺎﻥ ﻟﺘﻘﻠﻴل ﺍﻟﺭﻭﺍﺌﺢ ﺍﻟﻜﺭﻴﻬﺔ ﺃﻭ ﻴﺘﻡ ﺴﺤﺏ ﺍﻟﻬـﻭﺍﺀ‬
‫ﺨﺎﺭﺝ ﺍﻷﻤﺎﻜﻥ ﺒﺎﺴﺘﺨﺩﺍﻡ ﻤﺭﺍﻭﺡ ﺴﺤﺏ‪ ،‬ﻜﻤﺎ ﻓـﻰ ﺍﻟﻤﻁـﺎﺒﺦ ﻭﺍﻟﻤﻐﺎﺴـل ﻭﻓـﻰ‬
‫ﺍﻟﺤﻤﺎﻤﺎﺕ‪.‬‬
‫)‪ (٣‬ﻴﻤﻜﻥ ﺍﻟﻠﺠﻭﺀ ﺇﻟﻰ ﺘﻜﻴﻴﻑ ﺍﻟﻬﻭﺍﺀ ﻤﺭﻜﺯﻴﺎﹰ ﻭﻨﻘﻠﻪ ﺇﻟـﻰ ﺍﻷﻤـﺎﻜﻥ ﺍﻟﻤـﺭﺍﺩ ﺘﻜﻴﻴﻔﻬـﺎ‬
‫ﺒﺎﺴﺘﺨﺩﺍﻡ ﻤﺠﺎﺭﻯ ﻭﻤﺨﺎﺭﺝ ﻫﻭﺍﺀ‪.‬‬
‫)‪ (٤‬ﻗﺩ ﻴﺤﺘﺎﺝ ﺍﻷﻤﺭ ﺇﻟﻰ ﺍﺴﺘﺨﺩﺍﻡ ﻨﻅﻡ ﻟﺘﺭﻁﻴﺏ ﺍﻟﻬﻭﺍﺀ ﺍﻟﻤﻜﻴﻑ ﺼﻴﻔﺎﹰ ﻭﻗـﺩ ﻴﺘﻁﻠـﺏ‬
‫ﺍﻷﻤﺭ ﺍﺴﺘﺨﺩﺍﻡ ﻨﻅﻡ ﻟﻨﺯﻉ ﺍﻟﺭﻁﻭﺒﺔ ﻤﻨﻪ‪.‬‬
‫)‪ (٥‬ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ ﺍﻟﻤﺤﺭﻜﺎﺕ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻓﻰ ﺇﺩﺍﺭﺓ ﺍﻟﻤﺭﺍﻭﺡ ﺒﻘﺩﺭﺓ ﻜﻬﺭﺒﺎﺌﻴﺔ ﻜﺎﻓﻴـﺔ‬
‫ﻟﻠﺘﻐﻠﺏ ﻋﻠﻰ ﺍﺤﺘﻜﺎﻙ ﺍﻟﻬﻭﺍﺀ ﺒﺎﻟﺠﺩﺭﺍﻥ ﺍﻟﺩﺍﺨﻠﻴﺔ ﻟﻤﺠﺎﺭﻯ ﺍﻟﻬﻭﺍﺀ ﺴﻭﺍﺀ ﻟﻠﺘﻐﺫﻴـﺔ ﺃﻭ‬
‫ﺍﻟﺭﺠﻭﻉ ﻭﻤﻥ ﺨﻼل ﻤﻠﻔﺎﺕ ﺍﻟﺘﻜﻴﻴﻑ ﺴﻭﺍﺀ ﻜﺎﻨﺕ ﻟﻠﺘﺒﺭﻴﺩ ﺃﻭ ﺍﻟﺘﺩﻓﺌﺔ ﻭﻜﺫﻟﻙ ﻟﻠﺘﻐﻠﺏ‬
‫ﻋﻠﻰ ﺍﻻﺤﺘﻜﺎﻙ ﻓﻰ ﺍﻟﻔﻼﺘﺭ ﻭﻤﺨﺎﺭﺝ ﺍﻟﻬﻭﺍﺀ ﻭﺤﻭﺍﻜﻤﻬﺎ )‪.(Control dampers‬‬
‫ﺃﻋﻤﺎل ﺍﻟﺘﺩﻓﺌﺔ ﺒﺎﺴﺘﺨﺩﺍﻡ ﺘﺴﺨﻴﻥ ﺍﻟﻬﻭﺍﺀ ﺒﻤﻘﺎﻭﻤﺎﺕ ﻜﻬﺭﺒﺎﺌﻴﺔ‬ ‫)ﺃ(‬
‫‪ -‬ﻤﻥ ﺍﻟﻤﻤﻜﻥ ﺍﺴﺘﺨﺩﺍﻡ ﺴﺨﺎﻨﺎﺕ ﺒﻤﻘﺎﻭﻤﺎﺕ ﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻐﺭﻑ ﺍﻟﻤﺨﺘﻠﻔـﺔ ﻜـل‬
‫ﻤﻨﻬﺎ ﻴﻌﻤل ﺒﺤﺎﻜﻡ ﻟﺩﺭﺠﺔ ﺍﻟﺤﺭﺍﺭﺓ )‪ (Thermostat‬ﻭﺫﻟﻙ ﻟﻀﺒﻁ ﺩﺭﺠﺔ ﺍﻟﺤﺭﺍﺭﺓ‬
‫ﻋﻨﺩ ﺍﻟﻘﻴﻤﺔ ﺍﻟﻤﻁﻠﻭﺒﺔ‪.‬‬
‫‪ -‬ﻴﻤﻜﻥ ﺘﺨﻔﻴﺽ ﺩﺭﺠﺔ ﺍﻟﺤﺭﺍﺭﺓ ﺒﺎﻟﻐﺭﻑ ﻏﻴﺭ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﺃﻭ ﺤﺘﻰ ﻴﻤﻜﻥ ﻓﺼـل‬
‫ﺍﻟﺴﺨﺎﻨﺎﺕ ﻋﻨﻬﺎ ﺒﺎﺴﺘﺨﺩﺍﻡ ﻤﻔﺘﺎﺡ‪ ،‬ﺃﻤﺎ ﺍﻟﺤﺠﺭﺍﺕ ﻏﻴﺭ ﺍﻟﻤﺸﻐﻭﻟﺔ ﻤﺜـل ﻏـﺭﻑ‬
‫ﺍﻟﻨﻭﻡ ﺃﺜﻨﺎﺀ ﺴﺎﻋﺎﺕ ﺍﻟﻨﻬﺎﺭ‪ ،‬ﻓﺘﻜﻭﻥ ﻤﻔﺼﻭﻟﺔ ﻭﻻ ﻴﺘﻡ ﺘﺸﻐﻴل ﺍﻟﺘﺩﻓﺌﺔ ﺒﻬﺎ ﺇﻻ ﻓـﻰ‬
‫ﺤﻴﻨﻪ ﻟﻠﻭﺼﻭل ﺇﻟﻰ ﺩﺭﺠﺔ ﺍﻟﺤﺭﺍﺭﺓ ﺍﻟﻤﻁﻠﻭﺒﺔ‪.‬‬
‫ﻴﺒﻴﻥ ﺠﺩﻭل )‪ (٤-١‬ﻗﺩﺭﺍﺕ ﺍﻟﺴﺨﺎﻨﺎﺕ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻓﻰ ﻭﺤﺩﺍﺕ ﺘﺩﻓﺌﺔ ﺍﻟﻤﻨـﺎﺯل ﻤـﻥ‬
‫ﺍﻟﻨﻭﻉ ﺍﻟﺤﺎﺌﻁﻰ‪ ،‬ﻭﻴﻤﻜﻥ ﺒﻨﺎﺀ ﻤﺠﻤﻭﻋﺎﺕ ﻤﻨﻬﺎ ﺩﺍﺨل ﻭﺤـﺩﺓ ﺍﻟﺴـﺨﺎﻨﺎﺕ ﺍﻟﻭﺍﺤـﺩﺓ ﺃﻭ‬
‫ﺘﻜﺭﺍﺭ ﺍﻟﻭﺤﺩﺍﺕ ﺩﺍﺨل ﺍﻟﻤﻜﺎﻥ ﺍﻟﻭﺍﺤﺩ‪.‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪ :(٤-١‬ﻗﺩﺭﺍﺕ ﻭﺤﺩﺍﺕ ﺍﻟﺴﺨﺎﻨﺎﺕ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻓﻰ ﻭﺤﺩﺍﺕ ﺍﻟﺘﺩﻓﺌﺔ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ‬

‫ﺍﻟﻤﺴﺎﺤﺔ ﺍﻟﻤﺨﺩﻭﻤﺔ‬ ‫ﻁﻭل ﺍﻟﻭﺤﺩﺓ‬ ‫ﻋﺭﺽ ﺍﻟﻭﺤﺩﺓ‬ ‫ﺍﻟﺴﻌﺔ ﺍﻟﺤﺭﺍﺭﻴﺔ‬ ‫ﻗﺩﺭﺓ ﺍﻟﺴﺨﺎﻨﺎﺕ‬
‫)ﻡ‪(٢‬‬ ‫)ﻤﻡ(‬ ‫)ﻤﻡ(‬ ‫)ﻭ‪.‬ﺡ‪.‬ﺏ‪/‬ﺴﺎﻋﺔ(‬ ‫)ﻭﺍﺕ(‬
‫‪٢‬‬ ‫‪٣٥٥‬‬ ‫‪٢٠٠‬‬ ‫‪١١٩٤‬‬ ‫‪٣٥٠‬‬
‫‪٦–٤‬‬ ‫‪٧٥٠‬‬ ‫‪٢٠٠‬‬ ‫‪٢٥٥٩‬‬ ‫‪٧٥٠‬‬
‫‪١٦ - ١٢‬‬ ‫‪١٥٠٠‬‬ ‫‪٢٠٠‬‬ ‫‪٦٨٢٤‬‬ ‫‪٢٠٠٠‬‬

‫)ﺏ( ﻭﺤﺩﺍﺕ ﺍﻟﺘﺒﺭﻴﺩ ﻟﻠﻤﻨﺎﺯل‬


‫‪ -‬ﻴﺘﻡ ﺘﺒﺭﻴﺩ ﺍﻟﻤﻨﺎﺯل ﺍﻟﺼﻐﻴﺭﺓ ﺒﻁﺭﻴﻘﺔ ﺒﺴﻴﻁﺔ ﺒﺎﺴﺘﺨﺩﺍﻡ ﻭﺤﺩﺓ ﺘﺘﻜﻭﻥ ﻤﻥ ﻀﺎﻏﻁ‬
‫)ﻜﺒﺎﺱ( ﻭﻤﻜﺜﻑ ﻭﻤﺒﺨﺭ ﻭﺩﺍﺌﺭﺓ ﻭﺴﻁ ﺍﻟﺘﺒﺭﻴـﺩ ﻭﺒﺎﺴـﺘﺨﺩﺍﻡ ﺘﺒﺭﻴـﺩ ﺍﻟﻬـﻭﺍﺀ‬
‫ﺒﺎﻟﻬﻭﺍﺀ‪.‬‬
‫ﻭﻜﻤﺎ ﻫﻭ ﻤﻭﻀﺢ ﻓﻰ ﺸﻜل )‪ (١٣-١‬ﻭﺍﻟﺫﻯ ﻴﻭﻀﺢ ﺭﺴﻤﺎﹰ ﺘﺨﻁﻴﻁﻴـﺎﹰ ﻟﺠﻬـﺎﺯ‬
‫ﺘﻜﻴﻴﻑ ﺍﻟﻬﻭﺍﺀ ﻤﻥ ﻨﻭﻉ ﺍﻟﺸـﺒﺎﻙ )‪ ،(Window type AC‬ﻭﺒـﻪ ﻋـﺎﺩﺓ ﺜﻼﺜـﺔ‬
‫ﻤﺤﺭﻜﺎﺕ ﻭﺍﺤﺩ ﻟﻤﺭﻭﺤﺔ ﺍﻟﻤﺒﺨﺭ ﻭﺍﻟﺜﺎﻨﻰ ﻟﻤﺭﻭﺤﺔ ﺘﺒﺭﻴـﺩ ﺍﻟﻤﻜﺜـﻑ ﻭﺍﻟﺜﺎﻟـﺙ‬
‫ﻟﻀﺎﻏﻁ ﻭﺴﻁ ﺍﻟﺘﺒﺭﻴﺩ )ﺍﻟﻔﺭﻴﻭﻥ(‪.‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫اﻟﻤﻜﺎن اﻟﺨﺎرﺟﻲ‬ ‫اﻟﻤﻜﺎن اﻟﺪاﺧﻠﻲ‬

‫ﻣﺮوﺣﺔ اﻟﻤﺒﺨﺮ‬
‫واﻟﻤﺤﺮك‬ ‫ھﻮاء ﻣﻜﯿﻒ ﻣﻨﺰوع‬
‫اﻟﺮﻃﻮﺑﺔ ﻣﻊ ﺑﻌﺾ‬
‫ھﻮاء ﺳﺎﺧﻦ‬ ‫اﻟﮭﻮاء اﻟﺨﺎرﺟﻲ ﻟﺘﻜﯿﯿﻒ‬
‫اﻟﻤﻜﺎن‬
‫ﻣﻠﻒ اﻟﻤﺒﺨﺮ )ﻟﻠﺘﺒﺮﯾﺪ(‬
‫ﯾﺒﺮد ھﻮاء اﻟﻐﺮﻓﺔ وﯾﻜﺜﻒ‬
‫اﻟﺮﻃﻮﺑﺔ اﻟﺰاﺋﺪة ﺑﮫ‬
‫ﺣﻮض ﺗﺠﻤﯿﻊ ﻣﯿﺎه اﻟﺘﻜﺜﯿﻒ‬
‫وﻃﺮدھﺎ إﻟﻰ اﻟﺨﺎرج‬
‫ﻣﺮوﺣﺔ ﺗﺒﺮﯾﺪ اﻟﻤﻜﺜﻒ‬ ‫ﺑﺎﻟﺴﺮﯾﺎن اﻟﻄﺒﯿﻌﻰ أو‬
‫ﺑﻤﺤﺮﻛﮭﺎ‬ ‫ﺑﻤﻀﺨﺔ ﺧﺎﺻﺔ‬

‫ھﻮاء ﺑﺎرد‬ ‫ھﻮاء راﺟﻊ‬


‫ﻓﻠﺘﺮ ﻟﻠﺘﻨﻘﯿﺔ‬ ‫)ﺳﺎﺧﻦ وﻣﺤﻤﻞ‬
‫ﺑﺎﻟﺮﻃﻮﺑﺔ(‬
‫ﺧﺮوج اﻟﻤﯿﺎه‬
‫اﻟﻤﺘﻜﺎﺛﻔﺔ ﻣﻦ‬
‫اﻟﺮﻃﻮﺑﺔ‬ ‫ﺿﺎﻏﻂ ﻛﺒﺎس وﺳﻂ اﻟﺘﺒﺮﯾﺪ‬ ‫ﻗﯿﻤﺔ ﻣﺘﺤﻜﻢ ﻓﯿﮭﺎ ﻣﻦ اﻟﮭﻮاء‬
‫)اﻟﻔﺮﯾﻮن( ﺑﺎﻟﻤﺤﺮك‬ ‫اﻟﺨﺎرﺟﻲ ﺑﻐﺮض ﺗﺠﺪﯾﺪ‬
‫ھﻮاء اﻟﻤﻜﺎن اﻟﻤﻜﯿﻒ‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(١٣-١‬ﺩﺍﺌﺭﺓ ﺍﻟﺘﺒﺭﻴﺩ ﻓﻲ ﻭﺤﺩﺓ ﺘﻜﻴﻴﻑ ﻫﻭﺍﺀ ﻁﺭﺍﺯ ﺸﺒﺎﻙ‬

‫‪ -‬ﻴﻤﻜــﻥ ﻋﻜــﺱ ﺩﻭﺭﺓ ﻭﺴﻁ ﺍﻟﺘﺒﺭﻴﺩ ﻟﺘﺴﺨﻴﻥ ﺍﻟﻬﻭﺍﺀ ﺒﺎﻟﻤﻜﺎﻥ ﺍﻟﻤﺭﺍﺩ ﺘﻜﻴﻴﻔﻪ‬
‫ﺸﺘﺎﺀ ﺒﺎﺴﺘﺨﺩﺍﻡ ﻨﻔﺱ ﺍﻟﻀﺎﻏﻁ ﻭﻴﺴﻤﻰ ﺍﻟﺠﻬﺎﺯ ﻓـﻰ ﻫـﺫﻩ ﺍﻟﺤﺎﻟـﺔ "ﻤﻀـﺨﺔ‬
‫ﺤﺭﺍﺭﻴﺔ" )‪ ،(Heat pump‬ﻜﻤﺎ ﻴﻤﻜﻥ ﺍﺴﺘﺨﺩﺍﻡ ﺴﺨﺎﻥ ﻜﻬﺭﺒﺎﺌﻲ ﺃﻤـﺎﻡ ﻤﺭﻭﺤـﺔ‬
‫ﺍﻟﻤﺒﺨﺭ ﻤﻊ ﻓﺼل ﺍﻟﻀﺎﻏﻁ ﻭﻤﺭﻭﺤﺔ ﺍﻟﻤﻜﺜﻑ ﺸﺘﺎﺀ ﻓﻰ ﻫﺫﻩ ﺍﻟﺤﺎﻟﺔ‪.‬‬
‫‪ -‬ﺘﻜﻭﻥ ﻭﺤﺩﺍﺕ ﺍﻟﺸﺒﺎﻙ ﺫﺍﺕ ﺍﻟﺴﺨﺎﻨﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻋﺎﺩﺓ ﺒﺎﻟﺴـﻌﺎﺕ ﻭﺍﻟﻘـﺩﺭﺍﺕ‬
‫ﺍﻟﻤﺒﻴﻨﺔ ﻓﻰ ﺠﺩﻭل )‪ (٥-١‬ﻭﺫﻟﻙ ﻟﻠﻭﺤﺩﺍﺕ ﺍﻟﻤﺯﻭﺩﺓ ﺒﺴﺨﺎﻨﺎﺕ ﻜﻬﺭﺒﺎﺌﻴﺔ ﻟﻠﺘﺩﻓﺌﺔ‪.‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪ :(٥-١‬ﻗﺩﺭﺍﺕ ﻭﺤﺩﺍﺕ ﺍﻟﺘﻜﻴﻴﻑ ﻁﺭﺍﺯ ﺸﺒﺎﻙ ﺒﺴﺨﺎﻨﺎﺕ ﻜﻬﺭﺒﺎﺌﻴﺔ )ﺍﻟﻀﺎﻏﻁ ﻻ ﻴﻌﻤل(‬

‫ﺍﻟﻤﺴﺎﺤﺔ‬ ‫ﺍﻟﻘﺩﺭﺓ ﺒﺩﻭﻥ‬ ‫ﺍﻟﻘﺩﺭﺓ ﺍﻟﺤﺭﺍﺭﻴﺔ‬


‫ﺠﻬﺩ ﺍﻟﺘﺸﻐﻴل‬ ‫ﺍﻟﻘﺩﺭﺓ ﻤﻊ‬
‫ﺍﻟﻤﺨﺩﻭﻤﺔ‬ ‫ﺴﺨﺎﻨﺎﺕ‬
‫)ﻓﻭﻟﺕ‪/‬ﻫﺭﺘﺯ‪/‬ﻋﺩﺩ‬ ‫ﺍﻟﺴﺨﺎﻨﺎﺕ‬
‫)ﻡ‪(٢‬‬ ‫)ﺘﺒﺭﻴﺩ ﻓﻘﻁ(‬ ‫)ﻁﻥ ﺘﺒﺭﻴﺩ(‬ ‫ﻭ‪.‬ﺡ‪.‬ﺏ‪/‬ﺴﺎﻋﺔ‬
‫ﺍﻷﻁﻭﺍﺭ(‬ ‫)ﻙ‪.‬ﻭ‪(.‬‬
‫)ﻙ‪.‬ﻭ‪(.‬‬
‫‪١٢ – ١٠‬‬ ‫‪١/٥٠/٢٢٠‬‬ ‫‪٢.٢٠٠‬‬ ‫‪١.٥٤٠‬‬ ‫‪١‬‬ ‫‪١٢٠٠٠‬‬
‫‪١٨ – ١٥‬‬ ‫‪١/٥٠/٢٢٠‬‬ ‫‪٣.٧٥٠‬‬ ‫‪٢.٣٦٥‬‬ ‫‪١.٥‬‬ ‫‪١٨٠٠٠‬‬
‫‪٢٥ – ٢٠‬‬ ‫‪١/٥٠/٢٢٠‬‬ ‫‪٤.٣٢٥‬‬ ‫‪٣.٣٥٠‬‬ ‫‪٢‬‬ ‫‪٢٤٠٠٠‬‬
‫‪٣٠ - ٢٥‬‬ ‫‪١/٥٠/٢٢٠ -‬‬
‫‪٥.٠٠‬‬ ‫‪٤.٠٠‬‬ ‫‪٣.٠٠‬‬ ‫‪٣٦٠٠٠‬‬
‫‪٣/٥٠/٣٨٠ -‬‬

‫‪ -‬ﻴﻤﻜﻥ ﻭﻀﻊ ﺍﻟﻤﻜﺜﻑ ﺫﻯ ﺍﻟﻀﻭﻀﺎﺀ ﺍﻟﻌﺎﻟﻴﺔ ﻨﻭﻋﺎﹰً ﻤﺎ ﻓﻰ ﻤﻜـﺎﻥ ﺒﻌﻴـﺩ ﻋـﻥ‬


‫ﺍﻟﻤﺒﺨﺭ ﺒﺎﻟﻨﺴﺒﺔ ﻟﺩﺍﺌﺭﺓ ﺍﻟﺘﻜﻴﻴﻑ ﻭﺒﺎﻟﺘﺎﻟﻰ ﺍﻟﺤﺼﻭل ﻋﻠﻰ ﻤﻜﻴﻑ ﺃﻜﺜـﺭ ﻤﻼﺌﻤـﺔ‬
‫ﻭﺭﺍﺤﺔ ﻭﻴﻨﺘﺞ ﻤﺎ ﻴﺴﻤﻰ ﺒﺎﻟﻭﺤﺩﺓ ﺍﻟﻤﻨﻔﺼﻠﺔ )‪ (Split unit‬ﻭﻜﻤﺎ ﻫﻭ ﻤﺒـﻴﻥ ﻓـﻰ‬
‫ﺸﻜل )‪.(١٤-١‬‬
‫‪ -‬ﻴﻤﻜﻥ ﻋﻜﺱ ﺩﻭﺭﺓ ﻭﺴﻁ ﺍﻟﺘﺒﺭﻴﺩ ﻟﻴﺴﺨﻥ ﺍﻟﻬﻭﺍﺀ ﺒﺎﻟﻤﻜﺎﻥ ﺍﻟﻤﺭﺍﺩ ﺘﻜﻴﻴﻔـﻪ ﻜﻤـﺎ‬
‫ﻴﻤﻜﻥ ﺃﻴﻀﺎﹰ ﺍﺴﺘﺨﺩﺍﻡ ﺴﺨﺎﻥ ﻜﻬﺭﺒﺎﺌﻰ ﺃﻤﺎﻡ ﻤﺭﻭﺤﺔ ﺍﻟﻤﺒﺨﺭ‪.‬‬
‫ﻴﺒﻴﻥ ﺸﻜل )‪ (١٥-١‬ﺒﻌﺽ ﻁﺭﻕ ﺘﺭﻜﻴﺏ ﺍﻟﻭﺤﺩﺓ ﺍﻟﺩﺍﺨﻠﻴﺔ ﻭﺍﻟﻭﺤﺩﺓ ﺍﻟﺨﺎﺭﺠﻴـﺔ‬
‫ﻟﻭﺤﺩﺍﺕ ﺍﻟﺘﻜﻴﻴﻑ ﺍﻟﻤﻨﻔﺼﻠﺔ‪.‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫أﻗﺼﻰ ﺑﻌﺪ ﺣﻮاﻟﻲ ‪ ٢٠ – ١٥‬م‬

‫اﻟﻐﺮﻓﺔ اﻟﻤﺮاد‬
‫ھﻮاء ﺧﺎرﺟﻲ‬ ‫اﻟﺪاﺧﻞ‬ ‫ﺗﻜﯿﯿﻔﮭﺎ‬

‫اﻟﻜﺒﺎس‬
‫ﻓﺮﯾﻮن‬

‫ﻃﺮد ﺣﺮارة اﻟﻀﺎﻏﻂ )اﻟﻜﺒﺎس(‬ ‫ﺗﺒﺮﯾﺪ ﺑﺈﺳﺘﺨﺪام اﻹﻧﺘﺸﺎر اﻟﻤﺒﺎﺷﺮ‬


‫وﻣﻜﻹﻒ ﯾﺒﺮد ﺑﺎﻟﮭﻮاء‬ ‫ﻓﻲ اﻟﻤﺒﺨﺮ‬

‫ﺷﻜﻞ رﻗﻢ )‪ :(١٤-١‬رﺳﻢ ﺗﺨﻄﯿﻄﻲ ﻟﺪاﺋﺮة اﻟﻮﺣﺪة اﻟﻤﻨﻔﺼﻠﺔ‬

‫داﺧﻞ اﻟﺤﺠﺮة‬ ‫ﺧﺎرج اﻟﺤﺠﺮة‬ ‫ﺳﻘﻒ‬ ‫ﺧﺎرج اﻟﺤﺠﺮة‬


‫داﺧﻞ اﻟﺤﺠﺮة‬
‫اﻟﺤﺎﺋﻂ‬
‫ﺷﺒﺎك أو ﺣﺎﺋﻂ‬ ‫اﻟﺨﺎرﺟﻲ‬

‫‪ ٩٠٠‬ﻣﻢ‬ ‫ﺗﻮﺻﯿﻠﺔ‬
‫اﻟﻮﺣﺪة اﻟﺪاﺧﻠﯿﺔ‬ ‫‪ ٩٠٠‬ﻣﻢ‬
‫ﻋﻠﻰ اﻷﻗﻞ‬ ‫ﻋﻠﻰ اﻷﻗﻞ‬
‫اﻟﻮﺣﺪة اﻟﺪاﺧﻠﯿﺔ‬
‫اﻟﻮﺣﺪة‬ ‫اﻟﻮﺣﺪة‬
‫اﻟﺨﺎرﺟﯿﺔ‬ ‫أرﺿﯿﺔ‬ ‫اﻟﺨﺎرﺟﯿﺔ‬

‫) ب ( اﻟﻮﺣﺪة اﻟﺪاﺧﻠﯿﺔ ﻣﺮﻛﺒﺔ ﻋﻠﻰ اﻷرﺿﯿﺔ‬ ‫)أ( اﻟﻮﺣﺪة اﻟﺪاﺧﻠﯿﺔ ﻣﺮﻛﺒﺔ ﻋﻠﻰ اﻟﺤﺎﺋﻂ‬

‫اﻟﻮﺣﺪة اﻟﺪاﺧﻠﯿﺔ‬
‫ﺣﺎﺋﻂ ﺧﺎرﺟﻲ أو‬ ‫ﺧﺎرج اﻟﺤﺠﺮة‬
‫ﺷﺒﺎك‬
‫داﺧﻞ اﻟﺤﺠﺮة‬ ‫اﻟﻮﺣﺪة اﻟﺨﺎرﺟﯿﺔ‬

‫)ت( اﻟﻮﺣﺪة اﻟﺪاﺧﻠﯿﺔ ﻣﻌﻠﻘﺔ ﺑﺎﻟﺴﻘﻒ‬

‫ﺷﻜﻞ رﻗﻢ )‪ :(١٥-١‬اﻟﻮﺣﺪات اﻟﻤﻨﻔﺼﻠﺔ )‪(Split Units‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻴﺒﻴﻥ ﺠﺩﻭل )‪ (٦-١‬ﺴﻌﺎﺕ ﻭﻗﺩﺭﺍﺕ ﺍﻟﻭﺤﺩﺍﺕ ﺍﻟﻤﻨﻔﺼﻠﺔ ﻭﺍﻟﺘﻰ ﻴﻤﻜﻥ ﺃﻥ ﺘﻜﻭﻥ‬


‫ﻭﺤــﺩﺍﺕ ﺤﺎﺌﻁﻴــﺔ ﺃﻭ ﺴﻘﻔﻴـــﺔ )‪ (Exposed floor or ceiling unit‬ﺃﻭ‬
‫ﺴﻘﻔﻴﺔ ﻏﺎﻁﺴﺔ ﻓﻭﻕ ﺍﻟﺴﻘﻑ ﺍﻟﻤﺴﺘﻌﺎﺭ )‪.(Concealed unit‬‬
‫ﻴﻤﻜﻥ ﺒﻨﺎﺀ ﻭﺤﺩﺍﺕ ﻤﻨﻔﺼﻠﺔ ﺤﺘﻰ ﺴﻌﺔ ‪ ١٥‬ﻁﻥ ﺘﺒﺭﻴﺩ ﻤﺯﻭﺩﺓ ﺒﻌﺩﺩ ‪ ٢‬ﻜﺒـﺎﺱ‬
‫ﻗﺩﺭﺓ ‪ ٧‬ﻙ‪.‬ﻭ‪ .‬ﺒﻤﺭﻭﺤﺔ ﻤﻜﺜﻑ ﻗﺩﺭﺓ ‪ ٠.٤٤‬ﻙ‪.‬ﻭ‪ .‬ﻭﻤﺭﻭﺤـﺔ ﻤﺒﺨـﺭ ﺘﻜـﻭﻥ‬
‫ﻗﺩﺭﺘﻬﺎ ﻓﻰ ﺤﺩﻭﺩ ‪ ٢.٢٥‬ﻙ‪.‬ﻭ‪.‬‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪ :(٦-١‬ﺴﻌﺎﺕ ﻭﻗﺩﺭﺍﺕ ﺍﻟﻭﺤﺩﺍﺕ ﺍﻟﻤﻨﻔﺼﻠﺔ )ﺍﻟﻜﺒﺎﺱ ﻻ ﻴﻌﻤل(‬

‫ﺍﻟﻤﺴﺎﺤﺔ‬ ‫ﻗﺩﺭﺓ ﺍﻟﻭﺤﺩﺓ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ‬ ‫ﺍﻟﻘﺩﺭﺓ ﺍﻟﺤﺭﺍﺭﻴﺔ‬


‫ﺍﻟﻤﺨﺩﻭﻤﺔ‬ ‫ﺒﺎﻟﺴﺨﺎﻥ‬
‫ﺠﻬﺩ ﺍﻟﺘﺸﻐﻴل‬ ‫ﺘﺒﺭﻴﺩ ﻓﻘﻁ‬ ‫)ﻁﻥ‬
‫)ﻡ‪(٢‬‬ ‫ﺍﻟﻜﻬﺭﺒﺎﺌﻰ‬ ‫)ﻭ‪.‬ﺡ‪.‬ﺏ‪/‬ﺴﺎﻋﺔ(‬
‫)ﻙ‪.‬ﻭ‪(.‬‬ ‫ﺘﺒﺭﻴﺩ(‬
‫)ﻙ‪.‬ﻭ‪(.‬‬
‫‪١٢ – ١٠‬‬ ‫‪١/٥٠/٢٢٠‬‬ ‫‪١.٥‬‬ ‫‪١.٥٤٠‬‬ ‫‪١‬‬ ‫‪١٢٠٠٠‬‬
‫‪١٨ – ١٥‬‬ ‫‪١/٥٠/٢٢٠‬‬ ‫‪١.٦‬‬ ‫‪١.٩٣٠‬‬ ‫‪١.٥‬‬ ‫‪١٨٠٠٠‬‬
‫‪٢٥ – ٢٠‬‬ ‫‪١/٥٠/٢٢٠‬‬ ‫‪٢.٦٧٠‬‬ ‫‪٢.٦٧٠‬‬ ‫‪٢‬‬ ‫‪٢٤٠٠٠‬‬
‫‪٣٠ - ٢٥‬‬ ‫‪١/٥٠/٢٢٠‬‬ ‫‪٤.٢٠‬‬ ‫‪٣.٧٤٥‬‬ ‫‪٣‬‬ ‫‪٣٦٠٠٠‬‬
‫‪٤٠ – ٣٥‬‬ ‫‪٣/٥٠/٣٨٠‬‬ ‫‪٤.٥٠‬‬ ‫‪٣.٥‬‬ ‫‪٣.٥‬‬ ‫‪٤٢٠٠٠‬‬
‫‪٥٠ – ٤٠‬‬ ‫‪٣/٥٠/٣٨٠‬‬ ‫‪٥.٠٠‬‬ ‫‪٤.٥‬‬ ‫‪٤‬‬ ‫‪٤٨٠٠٠‬‬
‫‪٦٠ - ٥٠‬‬ ‫‪٣/٥٠/٣٨٠‬‬ ‫‪٧.٠٠‬‬ ‫‪٦.٢٥‬‬ ‫‪٥‬‬ ‫‪٦٠٠٠٠‬‬

‫ﻤﻠﺤﻭﻅﺔ‪:‬‬
‫ﻓﻲ ﺤﺎﻟﺔ ﻋﻤل ﺍﻟﺴﺨﺎﻨﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﺈﻥ ﺍﻟﻀﺎﻏﻁ ﻻ ﻴﻌﻤل‪.‬‬
‫)ﺕ( ﺍﻟﻭﺤﺩﺍﺕ ﺍﻟﻘﺎﺌﻤﺔ ﺒﺫﺍﺘﻬﺎ )‪(Package units‬‬
‫‪ -‬ﻴﻤﻜﻥ ﺒﻨﺎﺀ ﻭﺤﺩﺍﺕ ﺘﻜﻴﻴﻑ ﻫﻭﺍﺀ ﻗﺎﺌﻤﺔ ﺒﺫﺍﺘﻬﺎ ﻟﻠﺘﺩﻓﺌﺔ ﻭﺍﻟﺘﺒﺭﻴﺩ ﻭﺘﻜﻭﻥ ﺍﻟﻭﺤـﺩﺓ‬
‫ﺇﻤﺎ ﺭﺃﺴﻴﺔ ﺃﻭ ﺃﻓﻘﻴﺔ ﻜﻤﺎ ﻴﻤﻜﻥ ﻭﻀﻌﻬﺎ ﺇﻤﺎ ﻋﻠﻰ ﺍﻟﺴﻁﺢ ﺃﻭ ﺒﺎﻟﺒﺩﺭﻭﻡ‪.‬‬
‫‪ -‬ﻴﺘﻡ ﻋﺎﺩﺓ ﻨﻘل ﺍﻟﻬﻭﺍﺀ ﺍﻟﻤﻜﻴﻑ ﻤﻨﻬﺎ ﺒﺎﺴﺘﺨﺩﺍﻡ ﺸﺒﻜﺔ ﻤﺠـﺎﺭﻯ ﻫـﻭﺍﺀ ﻤﻌﺯﻭﻟـﺔ‬
‫ﻟﻬـﻭﺍﺀ ﺍﻟﺘﻐﺫﻴــﺔ ﻭﻫـﻭﺍﺀ ﺍﻟﺭﺍﺠﻊ ﻭﻜﻤﺎ ﻫﻭ ﻭﺍﻀﺢ ﻓﻰ ﺍﻷﺸﻜﺎل ﺍﻟﻤﺒﻴﻨﺔ ﻓﻰ‬
‫ﺸﻜل )‪.(١٦-١‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫دﺧﻮل ھﻮاء ﺗﺒﺮﯾﺪ‬


‫اﻟﻤﻜﺜﻒ‬

‫ﺧﺮوج ھﻮاء اﻟﻤﻜﺜﻒ‬

‫ﺧﺮوج اﻟﮭﻮاء اﻟﻤﻜﯿﻒ‬


‫إﻟﻰ ﻣﺠﺎري اﻟﮭﻮاء‬

‫دﺧﻮل اﻟﮭﻮاء اﻟﺮاﺟﻊ‬

‫)أ( ﻣﻜﻮﻧﺎت اﻟﻮﺣﺪة اﻟﻘﺎﺋﻤﺔ ﺑﺬاﺗﮭﺎ‬

‫ﻣﺠﺎري ھﻮاء ﻣﻌﺰوﻟﺔ‬


‫ﺣﺮارﯾﺎً ﻟﻠﺘﻐﺬﯾﺔ واﻟﺮاﺟﻊ‬
‫ﻤﺠﺎﺭﻱ ﻫﻭﺍﺀ ﻤﻌﺯﻭﻟﺔ ﺤﺭﺍﺭﻴﺎﹰ‬

‫ﺘﻐﺫﻴﺔ ﺭﺍﺠﻊ‬

‫)ﺕ( ﺘﺭﻜﻴﺒﺎﺕ ﻤﻜﺸﻭﻓﺔ ﻓﻭﻕ ﺍﻟﺴﻁﺢ‬ ‫)ﺏ( ﺍﻟﻭﺤﺩﺓ ﺘﺩﻓﻊ ﺍﻟﻬﻭﺍﺀ ﺃﻓﻘﻴﺎ ﺇﻟﻰ ﺍﻟﻤﻜﺎﻥ ﺍﻟﻤﺭﺍﺩ ﺘﻜﻴﻴﻔﻪ‬

‫ﺷﻜﻞ رﻗﻢ )‪ :(١٦-١‬اﻟﻮﺣﺪات اﻟﻤﻨﻔﺼﻠﺔ )‪(Split Units‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫)ﺙ( ﺍﻟﺘﻜﻴﻴﻑ ﺍﻟﻤﺭﻜﺯﻱ ) ‪(Central Station Air Conditioning‬‬


‫‪ -‬ﻴﺅﺩﻯ ﻫﺫﺍ ﺍﻟﻨﻭﻉ ﻤﻥ ﺍﻟﺘﺼﻤﻴﻡ ﺇﻟﻰ ﺍﻟﺘﻭﻓﻴﺭ ﻓﻰ ﺍﺴﺘﺨﺩﺍﻡ ﺍﻟﻤﻌﺩﺍﺕ ﻭﺍﻻﻗﺘﺼـﺎﺩ‬
‫ﻓﻰ ﺍﻟﻁﺎﻗﺔ ﺇﻟﻰ ﺃﻗﺼﻰ ﺩﺭﺠﺔ‪ ،‬ﻭﻴﺘﻡ ﺍﺴـﺘﺨﺩﺍﻤﻪ ﻓـﻰ ﺍﻟﻤﺒـﺎﻨﻰ ﺍﻟﻜﺒﻴـﺭﺓ ﺫﺍﺕ‬
‫ﺍﻹﺸﻐﺎل ﺍﻟﻌﺎﻟﻰ ﻤﺜل ﺍﻟﻔﻨﺎﺩﻕ ﻭ ﺍﻟﻤﺴﺘﺸﻔﻴﺎﺕ ﻭﺍﻟﻤﺴﺎﺭﺡ ﺍﻟﻜﺒﻴﺭﺓ‪.‬‬
‫‪ -‬ﻴﺘﻡ ﻓﻰ ﻫﺫﺍ ﺍﻟﻨﻅـﺎﻡ ﺍﺴﺘﺨﺩﺍﻡ ﻤﻭﻟﺩﺍﺕ ﺍﻟﻤﺎﺀ ﺍﻟﻤـﺜﻠﺞ )‪ (Water chillers‬ﺍﻟﺘـﻰ‬
‫ﺘﻜﻭﻥ ﺇﻤﺎ ﺫﺍﺕ ﻜﺒﺎﺴﺎﺕ ﺘﺭﺩﺩﻴﺔ )‪ (Reciprocating‬ﺃﻭ ﺤﻠﺯﻭﻨﻴـﺔ )‪ (Screw‬ﺃﻭ‬
‫ﻁــﺎﺭﺩﺓ ﻤﺭﻜـﺯﻴـﺔ )‪ (Centrifugal‬ﻤـﻊ ﻭﺤـﺩﺍﺕ ﻤﻨﺎﻭﻟــﺔ ﺍﻟﻬــﻭﺍﺀ‬
‫)‪ (Air handling units‬ﻭﺍﻟﺘﻰ ﺘﺤﺘﻭﻯ ﻋﻠﻰ ﻗﻁﺎﻋﺎﺕ ﻟﻤﺭﺍﻭﺡ ﺘﻐﺫﻴـﺔ ﺍﻟﻬـﻭﺍﺀ‬
‫ﻭﺭﺍﺠﻊ ﺍﻟﻬﻭﺍﺀ )‪ (Supply and return air fans‬ﻭﻗﻁﺎﻉ ﻤﻠﻑ ﺍﻟﺘﺒﺭﻴﺩ )ﺍﻟﺫﻯ ﻴﺘﻡ‬
‫ﺘﻐﺫﻴﺘﻪ ﺒﺎﻟﻤﺎﺀ ﺍﻟﻤﺜﻠﺞ( ﻭﻗﻁﺎﻉ ﻤﻠﻑ ﺍﻟﺘﺴﺨﻴﻥ )ﻗﺩ ﻴﻜﻭﻥ ﺍﻟﺘﺴﺨﻴﻥ ﺒﺎﺴﺘﺨﺩﺍﻡ ﻤﻠﻑ‬
‫ﻴﻐﺫﻯ ﻤﻥ ﻤﺎﺀ ﺴﺎﺨﻥ ﻤﻥ ﻏﻼﻴﺔ ﺃﻭ ﻴﻜـﻭﻥ ﺍﻟﺘﺴـﺨﻴﻥ ﻜﻬﺭﺒﺎﺌﻴـﺎﹰ ﺒﺎﺴـﺘﺨﺩﺍﻡ‬
‫ﻤﻘﺎﻭﻤﺎﺕ( ﻭﻗﻁﺎﻉ ﺘﺭﺸﻴﺢ ﺍﻟﻬﻭﺍﺀ ﻭﻗﻁﺎﻉ ﻀـﺒﻁ ﺩﺭﺠـﺔ ﺍﻟﺭﻁﻭﺒـﺔ ﺍﻟﻨﺴـﺒﻴﺔ‬
‫ﺒﺎﻟﻬﻭﺍﺀ ﺍﻟﻤﻜﻴﻑ‪.‬‬
‫‪ -‬ﺘﺒﻨﻰ ﻫﺫﻩ ﺍﻟﻭﺤﺩﺍﺕ ﺇﺫﺍ ﻜﺎﻥ ﻤﻜﺜﻔﻬﺎ ﻴﺒﺭﺩ ﺒﺎﻟﻬﻭﺍﺀ ﺤﺘﻰ ‪ ٣٥٠‬ﻁﻥ ﺘﺒﺭﻴﺩ ﻭﺃﻜﺒﺭ‬
‫ﻤﻥ ﺫﻟﻙ ﺇﺫﺍ ﻜﺎﻥ ﻴﺒﺭﺩ ﺒﺎﻟﻤﺎﺀ ﺒﺎﺴﺘﺨﺩﺍﻡ ﺃﺒﺭﺍﺝ ﺘﺒﺭﻴﺩ‪.‬‬
‫‪ -‬ﻴﺒﻴﻥ ﺸﻜل )‪ (١٧-١‬ﺭﺴﻤﺎﹰ ﺘﺨﻁﻴﻁﻴﺎﹰ ﻟﺩﺍﺌﺭﺓ ﺘﻜﻴﻴﻑ ﻤﺭﻜﺯﻯ ﺒﺎﺴﺘﺨﺩﺍﻡ ﻭﺤـﺩﺓ‬
‫ﺘﺜﻠﻴﺞ ﻤﻴﺎﻩ ﻭﻭﺤﺩﺓ ﻤﻨﺎﻭﻟﺔ ﻫﻭﺍﺀ ﻭﺩﺍﺌﺭﺓ ﺘﺴﺨﻴﻥ ﺒﺎﺴﺘﺨﺩﺍﻡ ﻏﻼﻴﺔ ﻤﻴﺎﻩ ﺴﺎﺨﻨﺔ‪.‬‬
‫‪ -‬ﻴﺒﻴﻥ ﺸﻜل )‪ (١٨-١‬ﺒﺭﺝ ﺘﺒﺭﻴﺩ ﻟﻤﻴﺎﻩ ﻤﻜﺜﻑ ﻭﺤﺩﺓ ﺘﺜﻠﻴﺞ ‪.‬‬
‫‪ -‬ﻴﺒﻴـﻥ ﺸـــﻜل )‪ (١٩-١‬ﻭﺤــﺩﺓ ﺘﺜﻠﻴــﺞ ﻤﻴــﺎﻩ ﻴﺒــﺭﺩ ﻤﻜﺜﻔﻬــﺎ‬
‫ﺒﺎﻟﻬـﻭﺍﺀ ﻭﺘﺤﺘـﺎﺝ ﺇﻟـﻰ ﻗــﺩﺭﺓ ﻜﻬﺭﺒﺎﺌﻴــﺔ ﻟﻠﻀﻭﺍﻏـــﻁ ﻭﻟﻤـﺭﺍﻭﺡ‬
‫ﺘﺒﺭﻴﺩ ﺍﻟﻤﻜﺜﻑ ﻜﻤﺎ ﺘﺤﺘﺎﺝ ﺇﻟﻰ ﻗــــﺩﺭﺓ ﻟﻠﻤﻌــــﺩﺍﺕ ﺍﻟﻤﻠﺤﻘــــﺔ‬
‫ﺒﻬـــﺎ ﻤﺜل ﻭﺤﺩﺓ ﺃﻭ ﻭﺤﺩﺍﺕ ﻤﻨﺎﻭﻟﺔ ﺍﻟﻬﻭﺍﺀ )‪ (Air handling units‬ﻭﻜـﺫﻟﻙ‬
‫ﻁﻠﻤﺒﺔ ﺃﻭ ﻁﻠﻤﺒﺎﺕ ﺍﻟﻤﻴﺎﻩ ﺍﻟﻤﺜﻠﺠﺔ‪.‬‬
‫‪ -‬ﻴﺒﻴـﻥ ﺠﺩﻭل )‪ (٧-١‬ﺒﻌﺽ ﺍﻟﺒﻴﺎﻨﺎﺕ ﺍﻟﻀﺭﻭﺭﻴﺔ ﻓـﻰ ﺘﺤﺩﻴـﺩ ﻗـﺩﺭﺓ ﻨﻅـﺎﻡ‬
‫ﺍﻟﺘﻜﻴﻴﻑ ﻭﺍﻹﻀﺎﺀﺓ ﻟﻸﻤﺎﻜﻥ ﺍﻟﻤﺨﺘﻠﻔﺔ ﻭﺍﻟﺘﻰ ﺘﻔﻴﺩ ﻤﺒﺩﺌﻴﺎﹰ ﻓﻰ ﺘﺤﺩﻴـﺩ ﺍﻟﻘـﺩﺭﺍﺕ‬
‫ﺍﻟﻤﻁﻠﻭﺒﺔ ﻋﻨﺩ ﺍﻟﺘﺨﻁﻴﻁ‪.‬‬
‫ﻭﻴﻼﺤﻅ ﺃﻥ ﺍﻟﻘﻴﻡ ﺍﻟﻭﺍﺭﺩﺓ ﺒﺎﻟﺠﺩﻭل ﻓﻴﻤﺎ ﻴﺨﺹ ﺍﻟﺘﺒﺭﻴﺩ ﻭﻜﻤﻴﺔ ﺍﻟﻬﻭﺍﺀ ﺍﻟﻤﻁﻠﻭﺏ‬
‫ﺘﻐﻴﻴﺭﻫﺎ ﻓﻰ ﺍﻟﻤﻜﺎﻥ ﻫﻰ ﻋﻠﻰ ﺃﺴﺎﺱ ﺃﻥ ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺍﻟﻬﻭﺍﺀ ﺍﻟﺨﺎﺭﺠﻰ ﻋﺎﺩﻴﺔ‬
‫)‪ْ ٣٥‬ﻡ(‪ .‬ﻭﻓﻰ ﺤﺎﻟﺔ ﺇﺫﺍ ﻤﺎ ﺘﻐﻴﺭﺕ ﺩﺭﺠﺔ ﺍﻟﺤﺭﺍﺭﺓ ﻋﻥ ﺫﻟﻙ ﺘﺘﻐﻴﺭ ﺍﻟﻘـﻴﻡ ﻓـﻰ‬
‫ﺍﻟﺠﺩﻭل‪.‬‬

‫‪١‬‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬

‫ﻃﻠﻤﺒﺔ‬
‫ﻣﺮوﺣﺔ اﻟﮭﻮاء‬
‫اﻟﺮاﺟﻊ‬ ‫ﻏﻼﯾﺔ‬
‫ﻃﺮد اﻟﮭﻮاء‬ ‫ھﻮاء راﺟﻊ‬
‫ﻣﺼﺪر ھﻮاء ﺳﺎﺧﻦ‬
‫ﻣﺮوﺣﺔ اﻟﮭﻮاء‬
‫اﻟﺪاﺧﻞ‬
‫ﻣﺨﻤﺪات‬ ‫ﻣﻠﻒ ﺗﺴﺨﯿﻦ‬
‫ھﻮاء ﻃﺎزج‬
‫ﻣﺴﺨﻦ أوﻟﻲ‬
‫ﻣﺼﺎﻓﻲ‬ ‫ﻣﻠﻒ ﺗﺒﺮﯾﺪ‬ ‫ﻣﺼﺪر ھﻮاء ﺑﺎرد‬

‫‪١‬‬
‫ﻣﺒﺮدات اﻟﻤﯿﺎه‬
‫ﻃﻠﻤﺒﺔ‬
‫داﺋﺮة اﻟﻤﯿﺎه اﻟﻤﺒﺮدة‬
‫ﺸﻜل ﺭﻗﻡ )‪ :(١٧-١‬ﺭﺴﻡ ﺘﺨﻁﻴﻁﻲ ﻟﺩﺍﺌﺭﺓ ﺍﻟﺘﻜﻴﻴﻑ ﺍﻟﻤﺭﻜﺯﻯ ﺒﺎﺴﺘﺨﺩﺍﻡ ﻭﺤﺩﺓ ﺘﺜﻠﻴﺞ ﻤﻴﺎﻩ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬

‫ﻴﺒﺭﺩ ﻤﻜﺜﻔﻬﺎ ﺒﺎﻟﻬﻭﺍﺀ ﻭﺒﻬﺎ ﻭﺤﺩﺍﺕ ﻤﻨﺎﻭﻟﺔ ﺍﻟﻬﻭﺍﺀ ﺘﺤﺘﻭﻯ ﻋﻠﻰ ﻗﻁﺎﻋﻴﻥ‬
‫ﻟﻤﺭﻭﺤﺔ ﺍﻟﺘﻐﺫﻴﺔ ﻭﺴﺤﺏ ﻫﻭﺍﺀ ﺍﻟﺭﺍﺠﻊ‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪ :(٧-١‬ﺍﻟﺒﻴﺎﻨﺎﺕ ﺍﻟﻤﻁﻠﻭﺒﺔ ﻋﻨﺩ ﺍﻟﺘﺨﻁﻴﻁ ﻟﺘﺤﺩﻴﺩ ﺍﻟﻘﺩﺭﺍﺕ ﺍﻟﻼﺯﻤﺔ‬


‫ﻓﻰ ﺃﻋﻤﺎل ﺍﻹﻀﺎﺀﺓ ﻭﺘﻜﻴﻴﻑ ﺍﻟﻬﻭﺍﺀ‬

‫ﻜﻤﻴﺔ ﺍﻟﻬﻭﺍﺀ )ﻡ‪/٣‬ﺴﺎﻋﺔ ﻟﻜل ﻡ‪(٢‬‬ ‫ﺍﻟﺘﺒﺭﻴﺩ‬ ‫ﻗﺩﺭﺓ ﺍﻹﻀﺎﺀﺓ‬ ‫ﻤﺴﺎﺤﺔ ﺍﻷﺸﻐﺎل‬
‫ﺩﺍﺨﻠﻰ‬ ‫ﺸﻤﺎل‬ ‫ﺸﺭﻕ ‪-‬ﺠﻨﻭﺏ ‪-‬ﻏﺭﺏ‬ ‫ﻡ‪/٢‬ﻁﻥ ﺘﺒﺭﻴﺩ‬ ‫)ﻭﺍﺕ‪/‬ﻡ‪(٢‬‬ ‫)ﻡ‪/٢‬ﺸﺨﺹ(‬ ‫ﺍﻟﻤﻜﺎﻥ‬
‫ﻋﺎﻟﻴﺔ‬ ‫ﻤﻨﺨﻔﻀﺔ‬ ‫ﻋﺎﻟﻴﺔ‬ ‫ﻤﻨﺨﻔﻀﺔ‬ ‫ﻋﺎﻟﻴﺔ‬ ‫ﻤﻨﺨﻔﻀﺔ‬ ‫ﻋﺎﻟﻴﺔ‬ ‫ﻤﻨﺨﻔﻀﺔ‬ ‫ﻋﺎﻟﻴﺔ‬ ‫ﻤﻨﺨﻔﻀﺔ‬ ‫ﻋﺎﻟﻴﺔ‬ ‫ﻤﻨﺨﻔﻀﺔ‬
‫‪--‬‬ ‫‪--‬‬ ‫‪٢٤‬‬ ‫‪١٠‬‬ ‫‪٣٠‬‬ ‫‪١٥‬‬ ‫‪٣٢‬‬ ‫‪٤٢‬‬ ‫‪٤٣‬‬ ‫‪١٠‬‬ ‫‪١٠‬‬ ‫‪٣٠‬‬ ‫ﺸﻘﺔ ﻓﻰ ﻤﺒﻨﻰ ﻤﺭﺘﻔﻊ‬
‫‪٥٥‬‬ ‫‪١٨‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪٨‬‬ ‫‪٣٧‬‬ ‫‪٣٢‬‬ ‫‪١٠‬‬ ‫‪١‬‬ ‫‪١٠‬‬ ‫ﻤﺩﺭﺠﺎﺕ‪،‬ﻜﻨﺎﺌﺱ‪،‬ﻤﺴﺎﺭﺡ‬
‫‪٣٥‬‬ ‫‪١٥‬‬ ‫‪٣٧‬‬ ‫‪١٧‬‬ ‫‪٤٠‬‬ ‫‪١٨‬‬ ‫‪١٤‬‬ ‫‪٢٢‬‬ ‫‪٦٥‬‬ ‫‪٢١‬‬ ‫‪٢‬‬ ‫‪٣‬‬ ‫ﻤﺩﺍﺭﺱ‪،‬ﻤﻌﺎﻫﺩ‪-‬ﺠﺎﻤﻌﺎﺕ‬
‫‪١٠٠‬‬ ‫‪٣٧‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪٩‬‬ ‫‪٢٢‬‬ ‫‪٦٥‬‬ ‫‪٣٢‬‬ ‫‪٢.٥‬‬ ‫‪٥‬‬ ‫ﻋﻨﺎﺒﺭ ﺘﺠﻤﻴﻊ ﻓﻰ ﻤﺼﺎﻨﻊ‬
‫‪٧٠‬‬ ‫‪٣٠‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪١٠‬‬ ‫‪١٨‬‬ ‫‪١٣٠‬‬ ‫‪٩٧‬‬ ‫‪١٠‬‬ ‫‪١٩‬‬ ‫ﺼﻨﺎﻋﺎﺕ ﺨﻔﻴﻔﺔ‬
‫‪١٢٠‬‬ ‫‪٤٦‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪٦‬‬ ‫‪٩‬‬ ‫‪٦٤٥‬‬ ‫‪١٦٢‬‬ ‫‪١٩‬‬ ‫‪٢٨‬‬ ‫ﺼﻨﺎﻋﺎﺕ ﺜﻘﻴﻠﺔ‬
‫‪--‬‬ ‫‪--‬‬ ‫‪١٢‬‬ ‫‪٦‬‬ ‫‪١٢‬‬ ‫‪٦‬‬ ‫‪١٥‬‬ ‫‪٢٦‬‬ ‫‪٢١‬‬ ‫‪١٠‬‬ ‫‪٢.٥‬‬ ‫‪٧‬‬ ‫ﻏﺭﻑ ﻭﻋﻨﺎﺒﺭ ﻤﺭﻀﻰ‬
‫ﺒﺎﻟﻤﺴﺘﺸﻔﻴﺎﺕ‬
‫‪٢٠‬‬ ‫‪١٧‬‬ ‫‪٢٢‬‬ ‫‪١٨‬‬ ‫‪٢٧‬‬ ‫‪١٨‬‬ ‫‪١٥‬‬ ‫‪٤١‬‬ ‫‪٢٢‬‬ ‫‪١٠‬‬ ‫‪٥‬‬ ‫‪١٠‬‬ ‫ﻤﻨﺎﻁﻕ ﻋﺎﻤﺔ‬
‫‪Public areas‬‬
‫‪--‬‬ ‫‪--‬‬ ‫‪٢٥‬‬ ‫‪١٦.٥‬‬ ‫‪٢٨‬‬ ‫‪١٨‬‬ ‫‪٢١‬‬ ‫‪٣٣‬‬ ‫‪٣٢‬‬ ‫‪١١‬‬ ‫‪٩.٥‬‬ ‫‪١٨.٥‬‬ ‫ﻓﻨﺎﺩﻕ ‪ ،‬ﻤﻭﺘﻴﻼﺕ ‪ ،‬ﻨﺯل‬
‫‪٢٠‬‬ ‫‪١٦.٥‬‬ ‫‪٢٤‬‬ ‫‪١٦.٥‬‬ ‫‪٣٨.٥‬‬ ‫‪١٨‬‬ ‫‪١٨.٥‬‬ ‫‪٣١.٥‬‬ ‫‪٣٢‬‬ ‫‪١١‬‬ ‫‪٤‬‬ ‫‪٧.٥‬‬ ‫ﻤﻜﺘﺒﺎﺕ ﻭﻤﺘﺎﺤﻑ‬
‫‪٣٣‬‬ ‫‪١٤.٥‬‬ ‫‪١٤.٥‬‬ ‫‪٤.٥‬‬ ‫‪١٦.٥‬‬ ‫‪٤.٥‬‬ ‫‪١٧.٥‬‬ ‫‪٣٣.٥‬‬ ‫‪٩٧‬‬ ‫‪٤٣‬‬ ‫‪٧.٥‬‬ ‫‪١٢‬‬ ‫ﻤﺒﺎﻨﻰ ﻤﻜﺎﺘﺏ ‪Office‬‬
‫‪buildings‬‬
‫‪--‬‬ ‫‪--‬‬ ‫‪١٤.٥‬‬ ‫‪٤.٥‬‬ ‫‪١٦.٥‬‬ ‫‪٤.٥‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪٨٦‬‬ ‫‪٢١.٥‬‬ ‫‪٩.٥‬‬ ‫‪١٤‬‬ ‫ﻤﻜﺎﺘﺏ ﺨﺎﺼﺔ ‪Private‬‬
‫‪offices‬‬
‫‪--‬‬ ‫‪١٦.٥‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪١٠٨‬‬ ‫‪٥٤‬‬ ‫‪٦.٥‬‬ ‫‪٩.٥‬‬ ‫ﻤﻨﺎﻁﻕ ﺫﺍﺕ ﻤﺒﺎﻨﻰ ﺤﺠﻤﻴﺔ‬
‫‪٢٥.٥‬‬ ‫‪--‬‬ ‫‪٢٤‬‬ ‫‪٩‬‬ ‫‪٢٩.٥‬‬ ‫‪١٤‬‬ ‫‪٣٥‬‬ ‫‪٥٦‬‬ ‫‪٤٣‬‬ ‫‪١١‬‬ ‫‪١٩‬‬ ‫‪٥٦‬‬ ‫ﻜﺒﻴﺭﺓ‬ ‫ﻤﻨﺎﻁﻕ‬
‫‪٢٤‬‬ ‫‪١٤.٥‬‬ ‫‪٢٢‬‬ ‫‪٩‬‬ ‫‪٢٥.٥‬‬ ‫‪١٣‬‬ ‫‪٣٧‬‬ ‫‪٦٥‬‬ ‫‪٣٢‬‬ ‫‪٧.٥‬‬ ‫‪١٩‬‬ ‫‪٥٦‬‬ ‫ﻤﺘﻭﺴﻁﺔ‬ ‫ﺴﻜﻨﻴﺔ‬
‫‪٣٦.٥‬‬ ‫‪١٦.٥‬‬ ‫‪٣٨.٥‬‬ ‫‪٢٢‬‬ ‫‪٦٨‬‬ ‫‪٣٣‬‬ ‫‪٧.٥‬‬ ‫‪١٢.٥‬‬ ‫‪٢١.٥‬‬ ‫‪١٦٢‬‬ ‫‪١.٢‬‬ ‫‪١.٥‬‬ ‫ﻜﺒﻴﺭﺓ‬
‫ﻤﻁﺎﻋﻡ‬
‫‪٢٢‬‬ ‫‪١٦.٥‬‬ ‫‪٣٣‬‬ ‫‪١١‬‬ ‫‪٥٥‬‬ ‫‪٢٧.٥‬‬ ‫‪٩.٥‬‬ ‫‪١٤‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫ﻤﺘﻭﺴﻁﺔ‬
‫‪٣٦.٥‬‬ ‫‪١٢.٨‬‬ ‫‪٤٧.٥‬‬ ‫‪١١‬‬ ‫‪٧٧‬‬ ‫‪٢٧.٥‬‬ ‫‪١٠‬‬ ‫‪٢٢‬‬ ‫‪٩٧‬‬ ‫‪٣٢‬‬ ‫‪٢.٣‬‬ ‫‪٤.٢‬‬ ‫ﺼﺎﻟﻭﻨﺎﺕ ﺘﺠﻤﻴل ﻭﺤﻼﻗﺔ‬
‫‪٢٢‬‬ ‫‪١٦.٥‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪٢١‬‬ ‫‪٣١.٥‬‬ ‫‪٤٣‬‬ ‫‪٢١.٥‬‬ ‫‪١.٩‬‬ ‫‪٢.٨‬‬ ‫ﺍﻟﺒﺩﺭﻭﻡ‬
‫‪٣٦.٥‬‬ ‫‪١٤.٥‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪١٤‬‬ ‫‪٣٢.٥‬‬ ‫‪٩٧‬‬ ‫‪٣٧.٥‬‬ ‫‪١.٥‬‬ ‫‪٤.٢‬‬ ‫ﺩﻭﺭ ﺍﻟﻤﺩﺨل‬
‫‪٢٠‬‬ ‫‪١٤.٥‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪٢٦‬‬ ‫‪٣٧‬‬ ‫‪٣٧.٥‬‬ ‫‪٢١.٥‬‬ ‫‪٣.٧‬‬ ‫‪٧‬‬ ‫ﺍﻷﺩﻭﺍﺭ ﺍﻟﻌﻠﻴﺎ‬
‫‪٢٤‬‬ ‫‪١١‬‬ ‫‪٢٥.٥‬‬ ‫‪١٢.٨‬‬ ‫‪٢٩.٥‬‬ ‫‪١٤.٥‬‬ ‫‪١٧‬‬ ‫‪٣٢‬‬ ‫‪٤٣‬‬ ‫‪١١‬‬ ‫‪٢.٨‬‬ ‫‪٤.٥‬‬ ‫ﺃﺩﻭﺍﺭ ﺒﻴﻊ‬
‫ﺍﻟﻤﻼﺒﺱ‬
‫ﻤﺤﻼﺕ‬
‫‪٢٠‬‬ ‫‪١٣‬‬ ‫‪٣٣‬‬ ‫‪١٨.٥‬‬ ‫‪٥٥‬‬ ‫‪٢٩‬‬ ‫‪١٠‬‬ ‫‪١٦.٥‬‬ ‫‪٣٢‬‬ ‫‪١١‬‬ ‫‪١.٦‬‬ ‫‪٣.٢٥‬‬ ‫ﺃﺩﻭﺍﺭ ﺒﻴﻊ‬
‫ﺘﺠﺎﺭﻴﺔ‬
‫ﺍﻟﻌﻁﻭﺭ‬
‫‪٢٤‬‬ ‫‪٩‬‬ ‫‪٢٩‬‬ ‫‪١١‬‬ ‫‪٣٨.٥‬‬ ‫‪١٢.٨‬‬ ‫‪١١‬‬ ‫‪٣٢‬‬ ‫‪٥٤‬‬ ‫‪١٦‬‬ ‫‪١.٤‬‬ ‫‪٣.٢٥‬‬ ‫ﺃﺩﻭﺍﺭ ﺒﻴﻊ‬
‫ﺒﺘﺨﻔﻴﻀﺎﺕ‬
‫‪٢٢‬‬ ‫‪١٤.٥‬‬ ‫‪٣٣‬‬ ‫‪١٨‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪١٤‬‬ ‫‪٢٨‬‬ ‫‪٣٢‬‬ ‫‪١١‬‬ ‫‪١.٩‬‬ ‫‪٤.٥‬‬ ‫ﺃﺩﻭﺍﺭ ﺒﻴﻊ‬
‫ﺍﻷﺤﺫﻴﺔ‬
‫‪٤٦‬‬ ‫‪٢٠‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪٢٢‬‬ ‫‪١٥‬‬ ‫‪٣٤‬‬ ‫‪٢١.٥‬‬ ‫‪١١‬‬ ‫‪٤.٦‬‬ ‫‪٩.٣‬‬ ‫ﻤﻭﻻﺕ ‪Malls‬‬
‫ﺘﻜﻴﻴﻑ ﻤﺭﻜﺯﻯ ﻋﺎﻡ‪:‬‬
‫‪٢٦.٥‬‬ ‫‪--‬‬ ‫‪ -‬ﺃﺤﻴﺎﺀ ﺤﻀﺭﻴﺔ‬
‫‪٢٢.٣‬‬ ‫‪--‬‬ ‫‪ -‬ﺍﻟﻤﻌﺎﻫﺩ ‪ /‬ﻤﺩﻥ ﺠﺎﻤﻌﻴﺔ‬
‫‪١٨.٥‬‬ ‫‪--‬‬ ‫‪ -‬ﻤﺭﺍﻜﺯ ﺘﺠﺎﺭﻴﺔ‬
‫‪٣٥‬‬ ‫‪--‬‬ ‫‪ -‬ﻤﺭﺍﻜﺯ ﺴﻜﻨﻴﺔ‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫‪ -‬ﻴﺒﻴﻥ ﺸﻜل )‪ (٢٠-١‬ﺒﺭﺝ ﺘﺒﺭﻴﺩ ﻴﺨﺩﻡ ﻤﺒﻨﻰ ﻜﺒﻴﺭ ﻭﻴﺘﻡ ﺭﻓﻊ ﺍﻟﻤﻴﺎﻩ ﺇﻟﻰ ﺍﻟﺒـﺭﺝ‬
‫ﺒﺎﺴﺘﺨﺩﺍﻡ ﻁﻠﻤﺒﺎﺕ‪.‬‬
‫‪ -‬ﻴﻤﻜﻥ ﺃﻥ ﺘﺼل ﺴﻌﺎﺕ ﻭﺤﺩﺍﺕ ﺘﺜﻠﻴﺞ ﺍﻟﻤﻴﺎﻩ ﺤﺘﻰ ‪ ٨٥٠‬ﻁﻥ ﺘﺒﺭﻴﺩ ﻭﻗﺩ ﺘﻌﻤـل‬
‫ﺒﺠﻬﺩ ﺘﺸﻐﻴل ‪ ٣٨٠‬ﻓﻭﻟﺕ‪ ٥٠/‬ﻫﺭﺘﺯ‪/‬ﺜﻼﺜﻲ ﺍﻷﻁﻭﺍﺭ ﻭﻴـﺘﻡ ﺘﻘـﻭﻴﻡ ﻤﺤـﺭﻙ‬
‫ﺍﻟﻀﺎﻏﻁ ﺒﻁﺭﻴﻘﺔ ﺴﺘﺎﺭ‪/‬ﺩﻟﺘﺎ ﺃﻭ ﺍﻟﺘﻘﻭﻴﻡ ﺍﻟﻠﻴﻥ )‪ (Soft starters‬ﻭﺘﻭﺠﺩ ﻭﺤـﺩﺍﺕ‬
‫ﺘﻌﻤل ﺒﺠﻬﻭﺩ ﺘﺸﻐﻴل ‪ ٣٣٠٠‬ﻓﻭﻟﺕ ‪ ٦٦٠٠ ،‬ﻓﻭﻟﺕ‪ ،‬ﻭﻗﺩ ﺘﺼل ﻗﺩﺭﺓ ﺍﻟﻤﺤﺭﻙ‬
‫ﻓﻰ ﺍﻟﻭﺤﺩﺍﺕ ﺍﻟﻜﺒﻴﺭﺓ ﺇﻟﻰ ‪ ٧٥٠‬ﻙ‪.‬ﻭ‪ .‬ﻭﻜﻤﺎ ﻫﻭ ﻤﻭﻀﺢ ﻓﻰ ﺸﻜل )‪.(١٩-١‬‬
‫‪ -‬ﺘﻭﺠـــﺩ ﺤﺎﻟﻴﺎﹰ ﻓﻰ ﺍﻟﺘﺭﻜﻴﺒـﺎﺕ ﻭﺤﺩﺍﺕ ﺘﺴـﺘﺨﺩﻡ ﺍﻟﺘﺒﺭﻴـﺩ ﺒﺎﻻﻤﺘﺼـﺎﺹ‬
‫)‪ (Cooling by Absorption‬ﻭﺘﺼل ﺴﻌﺎﺘﻬﺎ ﺤﺘﻰ ‪ ١٠٠٠‬ﻁﻥ ﺘﺒﺭﻴـﺩ‪ ،‬ﺤﻴـﺙ‬
‫ﻴﺘﻡ ﺇﻨﺘﺎﺝ ﻤﺎﺀ ﻤﺜﻠﺞ ﺒﺎﺴﺘﺨﺩﺍﻡ ﺒﺨﺎﺭ ﺃﻭ ﺤﺘﻰ ﺇﺸﻌﺎل ﻨﺎﺭ ﻤﺒﺎﺸـﺭﺓ)‪(Direct fire‬‬
‫ﻟﺘﺴﺨﻴﻥ ﻤﺤﻠﻭل ﻤﻠﺤﻰ )‪ (Lithium bromide‬ﻓﻰ ﻋﻤﻠﻴﺔ ﺇﻋﺎﺩﺓ ﺘﻭﻟﻴﺩ ﺍﻟﻤﻠﺢ ﺒﻌﺩ‬
‫ﻨﺯﻉ ﺒﺨﺎﺭ ﺍﻟﻤﺎﺀ ﻤﻥ ﺍﻟﻤﺤﻠﻭل ﻭﺍﻟﺤﺼﻭل ﻋﻠﻰ ﻭﺴﻁ ﻤﺎﺌﻰ ﺫﻭ ﺩﺭﺠﺔ ﺤـﺭﺍﺭﺓ‬
‫ﻤﻨﺨﻔﻀﺔ ﻴﻘﻭﻡ ﺒﺘﺒﺭﻴﺩ ﺍﻟﻤﺎﺀ ﻭﺘﺜﻠﻴﺠﻪ ﻻﺴﺘﺨﺩﺍﻤﻪ ﻓﻰ ﺘﻜﻴﻴﻑ ﻫﻭﺍﺀ ﺍﻟﻤﺒﻨﻰ ‪.‬‬
‫‪ -‬ﻴﺘﻡ ﺘﺒﺭﻴﺩ ﻤﻜﺜﻔﺎﺕ ﻫﺫﻩ ﺍﻟﻭﺤﺩﺍﺕ ﺒﺎﻟﻤﺎﺀ ﻭﻴﺴﺘﺨﺩﻡ ﻟﻬﺫﺍ ﺍﻟﻐﺭﺽ ﺃﺒـﺭﺍﺝ ﺘﺒﺭﻴـﺩ‬
‫ﺫﺍﺕ ﻤﺭﺍﻭﺡ ﻀﺨﻤﺔ ﻭﻤﺯﻭﺩﺓ ﺒﻁﻠﻤﺒﺎﺕ ﻤﻴﺎﻩ ﻀﺨﻤﺔ ﺃﻴﻀﺎﹰ ﺤﺴﺏ ﺴﻌﺔ ﺍﻟﻭﺤﺩﺓ‪.‬‬
‫‪ -‬ﻴﺒﻴﻥ ﺸﻜل )‪ (٢٠-١‬ﺭﺴﻤﺎﹰ ﺘﺨﻁﻴﻁﻴﺎﹰ ﻟـﺩﺍﺌﺭﺓ ﺍﻟﺘﺒﺭﻴـﺩ ﻓـﻰ ﻭﺤـﺩﺓ ﺍﻟﺘﺒﺭﻴـﺩ‬
‫ﺒﺎﻻﻤﺘﺼﺎﺹ‪.‬‬
‫‪ -‬ﺘﺤﺘﺎﺝ ﻭﺤﺩﺍﺕ ﺍﻟﺘﺒﺭﻴﺩ ﺒﺎﻻﻤﺘﺼﺎﺹ ﻟﻤﺼﺩﺭ ﻗﺩﺭﺓ ﻜﻬﺭﺒﺎﺌﻴﺔ ﺍﺼـﻐﺭ ﺒﺸـﻜل‬
‫ﻤﻠﺤﻭﻅ ﻟﻼﺴﺘﻐﻨﺎﺀ ﻋﻥ ﺍﻟﻘﺩﺭﺓ ﺍﻟﻀﺨﻤﺔ ﺍﻟﻼﺯﻤﺔ ﻟﻠﻀـﻭﺍﻏﻁ ﻤﻘﺎﺭﻨـﺔ ﺒﺤﺎﻟـﺔ‬
‫ﺍﻟﻭﺤﺩﺍﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻭﺘﺤﺘﺎﺝ ﻫﺫﻩ ﺍﻟﻭﺤﺩﺓ ﻓﻘﻁ ﺇﻟﻰ ﻗﺩﺭﺓ ﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻘﻁ ﻟﺘﻐﺫﻴـﺔ‬
‫ﺍﻟﻁﻠﻤﺒﺎﺕ ﻭﻫﻰ ﻁﻠﻤﺒﺎﺕ ﻤﻴﺎﻩ ﺍﻟﻤﺒﺨﺭ ﻭﻁﻠﻤﺒﺘﻰ ﺍﻟﻤﺤﻠـﻭل ﻭﻁﻠﻤﺒـﺎﺕ ﺃﺒـﺭﺍﺝ‬
‫ﺍﻟﺘﺒﺭﻴﺩ‪.‬‬
‫‪ -‬ﻴﺒﻴﻥ ﺸﻜل )‪ (٢١-١‬ﺼﻭﺭﺓ ﻟﻭﺤﺩﺓ ﺘﺜﻠﻴﺞ ﻤﻴﺎﻩ ﺒﺎﻻﻤﺘﺼﺎﺹ ﺴﻌﺔ ‪ ٣٣٠‬ﻁـﻥ‬
‫ﺘﺒﺭﻴﺩ ﻭﻻ ﺘﺤﺘﺎﺝ ﺇﻟﻰ ﻗﺩﺭﺓ ﻜﻬﺭﺒﺎﺌﻴﺔ ﺃﻜﺒﺭ ﻤﻥ ‪ ٤٠‬ﻙ‪.‬ﻭ‪.‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(١٨-١‬ﺒﺭﺝ ﺘﺒﺭﻴﺩ ﻟﻤﻴﺎﻩ ﻤﻜﺜﻑ ﻭﺤﺩﺓ ﺘﺜﻠﻴﺞ ﻤﻴﺎﻩ ﻟﻤﺒﻨﻰ ﻜﺒﻴﺭ‬

‫ﻟﻮﺣﺔ ﺗﺸﻐﯿﻞ وﺗﺤﻜﻢ ﻓﻲ‬


‫اﻟﻮﺣﺪة‬ ‫ﻣﺤﺮك اﻟﻀﺎﻏﻂ ﺿﺎﻏﻂ اﻟﻔﺮﯾﻮن‬

‫اﻟﻤﺒﺨﺮ‬

‫اﻟﻤﻜﺜﻒ‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(١٩-١‬ﻭﺤﺩﺓ ﺘﺜﻠﻴﺞ ﻤﻴﺎﻩ ﺒﻀﺎﻏﻁ )ﻜﺒﺎﺱ( ﻁﺎﺭﺩ ﻤﺭﻜﺯﻯ ﺒﻘﺩﺭﺍﺕ ﺤﺘﻰ‬
‫‪ ٨٥٠‬ﻁﻥ ﺘﺒﺭﻴﺩ ﻭﻴﺒﺭﺩ ﻤﻜﺜﻔﻬﺎ ﺒﺎﻟﻤﺎﺀ ﺒﺎﺴﺘﺨﺩﺍﻡ ﺒﺭﺝ ﺘﺒﺭﻴﺩ‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺑﺨﺎر اﻟﻤﺎء‬

‫ﻣﻜﺜﻒ‬ ‫اﻟﻤﺎء اﻟﻤﺘﻜﺜﻒ‬


‫ﺑﺨﺎر‬
‫ﻣﺤﻠﻮل‬

‫ﺑﺨﺎر اﻟﻤﺎء‬
‫ﻣﺒﺎدل ﺣﺮاري‬

‫ﻣﺒﺨﺮ‬ ‫‪ ْ ٤٥‬م‬
‫ﻣﺤﻠﻮل ﻣﺨﻔﻒ‬

‫وﺣﺪة إﻣﺘﺼﺎص ﻣﺎء ﻣﺘﻜﺜﻒ‬ ‫ﺣﻤﻞ اﻟﺘﺒﺮﯾﺪ‬

‫ﻣﺤﻠﻮل ﻣﻠﺤﻲ‬ ‫ﻣﺎء‬ ‫‪ ْ ٥٥‬م‬

‫ﻃﻠﻤﺒﺔ‬ ‫ﻃﻠﻤﺒﺔ‬

‫ﺷﻜﻞ رﻗﻢ )‪ :(٢٠-١‬وﺣﺪة ﺗﺒﺮﯾﺪ ﺑﺎﻻﻣﺘﺼﺎص‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(٢١-١‬ﻭﺤﺩﺓ ﺘﺜﻠﻴﺞ ﻤﻴﺎﻩ ﺘﻌﻤل ﺒﺎﻻﻤﺘﺼﺎﺹ ﻭﻴﺘﻡ ﺘﺴﺨﻴﻥ‬


‫ﺍﻟﻤﺤﻠﻭل ﺒﺎﻟﻐﺎﺯ ﺍﻟﻁﺒﻴﻌﻰ‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺍﻟﻁﻠﻤﺒﺎﺕ ﻭﺍﻟﺴﺨﺎﻨﺎﺕ‬ ‫‪٣-١‬‬


‫ﻁﻠﻤﺒﺎﺕ ﺭﻓﻊ ﺍﻟﻤﻴﺎﻩ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻰ‬ ‫)ﺃ(‬
‫)‪ (١‬ﺘﻜﻭﻥ ﺘﻐﺫﻴﺔ ﺍﻟﻤﻴﺎﻩ ﻟﻠﻤﺒﺎﻨﻰ ﺍﻟﻤﻨﺨﻔﻀﺔ )ﺫﺍﺕ ﺍﻟﻁﺎﺒﻘﻴﻥ ﺃﻭ ﺍﻟﺜﻼﺜـﺔ ﻁﻭﺍﺒـﻕ(‬
‫ﻤﻥ ﻤﺼـﺩﺭ ﻤـﺭﻓﻕ ﻤﻴﺎﻩ ﺍﻟﺸﺭﺏ ﻤﺒﺎﺸﺭﺓ ﺍﻋﺘﻤﺎﺩﺍﹰ ﻋﻠﻰ ﻀـﻐﻁ ﺍﻟﺸـﺒﻜﺔ‬
‫)‪ ٣.٥‬ﺒﺎﺭ ﺇﻟﻰ ‪ ٤.٨‬ﺒﺎﺭ( ﻭﻫﻭ ﻀﻐﻁ ﻜﺎﻑ ﻟﺩﻓﻊ ﺍﻟﻤﺎﺀ ﻤﻥ ﺍﻟﺼﻨﺎﺒﻴﺭ ﻋﻨـﺩ‬
‫ﻀﻐﻁ ﻴﺘﺭﺍﻭﺡ ﻤﺎ ﺒﻴﻥ )‪ ٠.٣٥‬ﺒﺎﺭ ﻭ ‪ ١.٣٥‬ﺒـﺎﺭ( ﺒﻌـﺩ ﺍﻟﺘﻐﻠـﺏ ﻋﻠـﻰ‬
‫ﺍﻻﺤﺘﻜﺎﻙ ﻓﻰ ﺍﻟﻤﻭﺍﺴﻴﺭ ﻭﺍﻟﺼﻨﺎﺒﻴﺭ‪.‬‬
‫)‪ (٢‬ﻴﺘﻡ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻰ ﻤﺘﻭﺴﻁﺔ ﺍﻻﺭﺘﻔﺎﻉ ﺤﺘﻰ ‪ ٣٠‬ﻤﺘﺭﺍﹰ )ﺤـﻭﺍﻟﻰ ‪ ١٠‬ﻁﻭﺍﺒـﻕ(‬
‫ﻀﺦ ﺍﻟﻤﺎﺀ ﻤﻥ ﺍﻟﻤﺼﺩﺭ ﺍﻟﺭﺌﻴﺴﻲ ﻤﺒﺎﺸﺭﺓ )ﺃﻭ ﻤﻥ ﺨﺯﺍﻥ ﺃﺭﻀﻰ ﺒﺎﻟﺒـﺩﺭﻭﻡ‬
‫ﻴﻤﻸ ﻤﻥ ﺍﻟﺸﺒﻜﺔ ﺍﻟﻌﻤﻭﻤﻴﺔ ﺘﺜﺎﻗﻠﻴﺎﹰ( ﺇﻟﻰ ﺨﺯﺍﻥ ﻋﻠﻭﻯ ﻓﻭﻕ ﺴﻁﺢ ﺍﻟﻤﺒﻨﻰ )ﺃﻭ‬
‫ﻓﻭﻕ ﺸﺨﺸﻴﺨﺔ ﺍﻟﺴﻠﻡ(‪ ،‬ﻭﻴﻼﺤﻅ ﺃﻥ ﺍﻟﻀﻐﻁ ﻋﻨﺩ ﺍﻷﺩﻭﺍﺭ ﺃﺴـﻔل ﺍﻟﺨـﺯﺍﻥ‬
‫ﻤﺒﺎﺸﺭﺓ ﻴﻜﻭﻥ ﻤﻨﺨﻔﻀﺎﹰ‪ ،‬ﻭﻻ ﺒﺩ ﻤﻥ ﺍﺴﺘﺨﺩﺍﻡ ﻤﻀﺨﺔ ﺼﻐﻴﺭﺓ ﻟﺭﻓﻊ ﺍﻟﻀﻐﻁ‬
‫ﻭﺘﺭﻜﺏ ﺒﺎﻟﺴﻁﺢ )ﻗـﺩﺭﺓ ﺤـﻭﺍﻟﻰ ‪ ١.٥‬ﻙ‪.‬ﻭ‪ (.‬ﻤـﺯﻭﺩﺓ ﺒﺨـﺯﺍﻥ ﺘﻤـﺩﺩ‬
‫)‪ (Expansion tank‬ﺘﻌﻤل ﺘﻠﻘﺎﺌﻴﺎﹰ ﻭﺫﻟﻙ ﻟﻀﻤﺎﻥ ﻀﻐﻁ ﺃﻋﻠـﻰ ﻋﻨـﺩ ﻫـﺫﻩ‬
‫ﺍﻷﺩﻭﺍﺭ‪.‬‬
‫)‪ (٣‬ﻴﺘﻭﻟﻰ ﺭﻓﻊ ﺍﻟﻤﻴﺎﻩ ﺇﻟﻰ ﺍﻟﺨﺯﺍﻥ ﺍﻟﻌﻠﻭﻯ ﻓﻭﻕ ﺴﻁﺢ ﺍﻟﻤﺒﻨﻰ ﻁﻠﻤﺒﺔ ﻜﻬﺭﺒﺎﺌﻴـﺔ‬
‫ﺘﻌﻤل ﺒﻤﺤﺭﻙ ﻓﻰ ﺤﺩﻭﺩ ‪ ٧.٥‬ﻙ‪.‬ﻭ‪ .‬ﻟﻤﻠﺊ ﺍﻟﺨﺯﺍﻥ ﻭﺘﻌﻤل ﺘﻠﻘﺎﺌﻴﺎﹰ ﻤﻥ ﻤﻔﺘﺎﺡ‬
‫ﻤﻨﺴﻭﺏ )‪ .(Level switch‬ﻭﻴﻭﺠﺩ ﻋﺎﺩﺓ ﻁﻠﻤﺒﺘﺎﻥ ﺃﺤﺩﻫﻤﺎ ﺘﻌﻤـل ﻭﺍﻟﺜﺎﻨﻴـﺔ‬
‫ﺍﺤﺘﻴﺎﻁﻴﺔ‪.‬‬
‫ﻭﻴﻤﻜﻥ ﺘﺤﺩﻴﺩ ﻗﺩﺭﺍﺕ ﺍﻟﻤﺤﺭﻜﺎﺕ ﺤﺴﺏ ﺍﻻﺭﺘﻔﺎﻉ ﻭﻜﻤﻴﺔ ﺍﻟﻤﻴﺎﻩ ﻤﻥ ﻗـﻭﺍﻨﻴﻥ‬
‫ﺍﻟﻬﻴﺩﺭﻭﻟﻴﻜﺎ‪.‬‬
‫ﻴﺒﻴﻥ ﺸﻜل )‪ (٢٢-١‬ﺭﺴﻤﺎﹰ ﺘﺨﻁﻴﻁﻴﺎﹰ ﻟﻨﻅﺎﻡ ﺘﻐﺫﻴﺔ ﺨـﺯﺍﻥ ﻋﻠـﻭﻯ ﻟﻤﺒﻨـﻰ‬
‫ﻤﻜﻭﻥ ﻤﻥ ‪ ٦٤‬ﻁﺎﺒﻘﺎﹰ ﺘﻡ ﺘﻘﺴﻴﻤﻪ ﺇﻟﻰ ﺜﻼﺜﺔ ﻤﻨﺎﻁﻕ ﺘﺘﻭﻟﻰ ﺍﻟﺭﻓﻊ ﻟﻜل ﻤﻨﻁﻘﺔ‬
‫ﻤﺠﻤﻭﻋﺔ ﻤﻥ ﻁﻠﻤﺒﺘﻴﻥ‪.‬‬
‫)‪ (٤‬ﻴﻤﻜــﻥ ﻓﻰ ﺍﻟﻤﺒﺎﻨــﻰ ﻤﺘﻭﺴﻁــﺔ ﺍﻻﺭﺘﻔـﺎﻉ ﺍﺴﺘﺨﺩﺍﻡ ﻀﻐﻁ ﺜﺎﺒـﺕ‬
‫ﻋــﻥ ﻁﺭﻴــﻕ ﺨﺯﺍﻥ ﺘﻤــﺩﺩ )‪ (Expansion tank‬ﻭﺤﺴﺎﺱ ﻟﻠﻀﻐﻁ‬
‫)‪ .(Pressure-stat‬ﻴﺒﻴﻥ ﺸﻜل )‪ (٢٣-١‬ﺃ ‪ ،‬ﺏ ﺭﺴﻤﺎﹰ ﺘﺨﻁﻴﻁﻴﺎﹰ ﻟﻠﺘﻐﺫﻴﺔ ﺇﻟﻰ‬
‫ﺃﻋﻠﻰ ﻋﻨﺩ ﻀﻐﻁ ﺜﺎﺒﺕ‪ .‬ﻭﻴﻤﻜﻥ ﺃﻥ ﺘﻜﻭﻥ ﻫﻨـﺎﻙ ﻤﺠﻤﻭﻋـﺔ ﻤـﻥ ﺜﻼﺜـﺔ‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻁﻠﻤﺒﺎﺕ ﺘﻌﻤل ﻭﺍﺤﺩﺓ ﻤﻨﻬﺎ ﺃﻭ ﺍﺜﻨﺘﺎﻥ ﺃﻭ ﺜﻼﺜﺔ ﺤﺴﺏ ﺍﻻﺤﺘﻴﺎﺝ‪ ،‬ﻜﻤﺎ ﻴﻤﻜـﻥ‬
‫ﺃﻥ ﺘﻜﻭﻥ ﻫﺫﻩ ﺍﻟﻤﻀﺨﺎﺕ ﻤﺯﻭﺩﺓ ﺒﻤﺤﺭﻜﺎﺕ ﻤﺘﻐﻴﺭﺓ ﺍﻟﺴﺭﻋﺔ ﻭﺒﺎﻟﺘﺎﻟﻰ ﻴﻤﻜﻥ‬
‫ﺍﻟﺤﺼﻭل ﻋﻠﻰ ﻋﺩﺩ ﻜﺒﻴﺭ ﻤﻥ ﻤﻌﺩﻻﺕ ﺍﻟﻀﺦ ﻤﺎ ﺒـﻴﻥ ﺍﻟﺼـﻔﺭ ﻭﺍﻟﻘﻴﻤـﺔ‬
‫ﺍﻟﻘﺼﻭﻯ‪ ،‬ﺤﻴﺙ ﺘﻌﻤل ﻫﺫﻩ ﺍﻟﻤﻀﺨﺎﺕ ﻁﺒﻘﺎﹰ ﻟﺘﺘﺎﺒﻊ ﻤﻌﻴﻥ ﺤﻴﺙ ﺘﻌﻤل ﺃﺼﻐﺭ‬
‫ﻤﻀﺨﺔ )‪ (Jokey pump‬ﻋﻨﺩ ﺃﻗل ﺴﺭﻋﺔ ﺜﻡ ﻴﻘﻭﻡ ﺤﺴﺎﺱ ﺍﻟﻀﻐﻁ ﻭﻟﻭﺤـﺔ‬
‫ﺍﻟﺘﺸﻐﻴل ﻭﺍﻟﺘﺤﻜﻡ ﺒﺘﺘﺎﺒﻊ ﺍﻟﺘﺸﻐﻴل ﺒﻴﻥ ﺍﻟﻁﻠﻤﺒﺘﻴﻥ ﺍﻟﻜﺒﻴﺭﺘﻴﻥ ﺒﺤﻴـﺙ ﺘﻌﻤـﻼﻥ‬
‫ﺒﺎﻟﺘﺒﺎﺩل‪.‬‬
‫)‪ (٥‬ﻨﻅﺭﺍﹰ ﻷﻥ ﺘﺸﻐﻴل ﺍﻟﻤﺠﻤﻭﻋﺔ ﻤﻥ ﺜﻼﺜﺔ ﻁﻠﻤﺒﺎﺕ ﻭﻗﺕ ﺍﻟﺫﺭﻭﺓ ﻓﻰ ﺍﻟﻤﺒﻨﻰ ﻗﺩ‬
‫ﻴﺅﺜﺭ ﻋﻠﻰ ﻀﻐﻁ ﺍﻟﻤﻴﺎﻩ ﻓﻰ ﺍﻟﻤﺎﺴﻭﺭﺓ ﺍﻟﺭﺌﻴﺴﻴﺔ ﺒﺎﻟﺸـﺎﺭﻉ‪ ،‬ﻓﻘـﺩ ﺘﻀـﻁﺭ‬
‫ﺍﻟﺴﻠﻁﺎﺕ ﺇﻟﻰ ﺇﺠﺒﺎﺭ ﺍﻟﻤﻼﻙ ﺒﺒﻨﺎﺀ ﺨﺯﺍﻥ ﺃﺭﻀﻰ ﺒﺎﻟﺒﺩﺭﻭﻡ ﻟﻠﺴـﺤﺏ ﻤﻨـﻪ‪،‬‬
‫ﻭﻜﻤﺎ ﻫﻭ ﻤﻭﻀﺢ ﻓﻰ ﺸﻜل )‪ (٢٣-١‬ﺏ‪.‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺍﻟﺴﻁﺢ‬
‫ﻤﻴﺎﻩ ﺍﻻﺴﺘﺨﺩﺍﻡ‬
‫ﺍﻟﻌﺎﻡ‬
‫ﺨﺯﺍﻥ ﻤﻨﻁﻘﺔ ‪٣‬‬

‫ﺸﺨﺸﻴﺨﺔ‬
‫ﺍﻟﺴﻠﻡ‬

‫ﻤﻨﻁﻘﺔ ‪ ٣‬ﻤﻥ‬
‫ﺍﻟﺩﻭﺭ‪ ٤٦‬ﺇﻟﻲ‬
‫ﻤﻴﺎﻩ ﺍﻻﺴﺘﺨﺩﺍﻡ‬ ‫ﺍﻟﺩﻭﺭ‪٦٤‬‬
‫ﺍﻟﻌﺎﻡ‬ ‫ﺨﺯﺍﻥ ﻤﻨﻁﻘﺔ ‪٢‬‬
‫ﺃﻗﺼﻰ ﺍﺭﺘﻔﺎﻉ ﻓﻭﻕ‬
‫ﺃﻋﻠﻰ‬
‫ﺍﻟﺘﺩﻭﻴﺭ‬
‫ﻤﺨﺎﺭﺝ ﺒﻤﻨﻁﻘﺔ ‪٣‬‬
‫ﺴﺨﺎﻥ ﺍﻟﻤﻴﺎﻩ‬
‫ﻤﻨﻁﻘﺔ ‪٣‬‬

‫ﻤﻨﻁﻘﺔ ‪ ٢‬ﻤﻥ‬
‫ﺍﻟﺩﻭﺭ‪ ٢٤‬ﺇﻟﻲ‬

‫ﻤﻴﺎﻩ ﺍﻻﺴﺘﺨﺩﺍﻡ‬ ‫ﺍﻟﺩﻭﺭ‪٤٥‬‬


‫ﺍﻟﻌﺎﻡ‬ ‫ﺨﺯﺍﻥ ﻤﻨﻁﻘﺔ ‪١‬‬

‫ﺍﻟﺘﺩﻭﻴﺭ‬

‫ﺴﺨﺎﻥ ﺍﻟﻤﻴﺎﻩ‬
‫ﺃﻗﺼﻰ ﺍﺭﺘﻔﺎﻉ‬
‫ﻤﻨﻁﻘﺔ ‪٢‬‬
‫ﻓﻭﻕ ﺃﻋﻠﻰ‬
‫ﻤﺨﺭﺝ ﺒﻤﻨﻁﻘﺔ‬ ‫ﺘﻔﺭﻴﻌﺎﺕ‬ ‫ﻤﻨﻁﻘﺔ ‪ ١‬ﻤﻥ‬
‫ﺍﻟﺩﻭﺭ ﺍﻷﻭل ﺇﻟﻲ‬
‫‪١‬‬
‫ﺍﻟﺩﻭﺭ‪٢٣‬‬

‫ﺘﻔﺭﻴﻌﺎﺕ‬
‫‪2nd‬‬

‫ﺍﻟﺘﺩﻭﻴﺭ‬ ‫ﺴﺨﺎﻥ ﻤﻴﺎﻩ‬


‫ﻤﻨﻁﻘﺔ ‪١‬‬

‫ﺨﺯﺍﻥ‬ ‫ﻁﻠﻤﺒﺎﺕ‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(٢٢-١‬ﺭﺴﻡ ﺘﺨﻁﻴﻁﻰ ﻟﻁﻠﻤﺒﺎﺕ ﺭﻓﻊ ﺍﻟﻤﻴﺎﻩ ﻟﺨﺯﺍﻨﺎﺕ ﻋﻠﻭﻴﺔ ﻭﻜﺫﻟﻙ‬
‫ﺴﺨﺎﻨﺎﺕ ﺍﻟﻤﻴﺎﻩ ﺍﻟﻌﺎﻤﺔ ﺒﻨﺎﻁﺤﺎﺕ ﺍﻟﺴﺤﺎﺏ ﻭﺘﻡ ﻓﻴﻬﺎ ﺘﻘﺴﻴﻡ ﺍﻟﻤﺒﻨﻰ ﺇﻟﻰ ﺜﻼﺜﺔ ﻤﻨﺎﻁﻕ‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺍﻟﺴﻁﺢ‬

‫ﺘﻐﺫﻴﺔ ﺇﻟﻲ ﺃﻋﻠﻰ‬

‫ﻟﻭﺤﺔ ﺘﺤﻜﻡ‬ ‫ﺤﺴﺎﺱ ﻀﻐﻁ‬

‫ﻟﻮﺣﺔ ﺗﺤﻜﻢ‬ ‫ﺣﺴﺎس‬


‫ﺿﻐﻂ‬
‫ﺨﺯﺍﻥ‬
‫ﻣﺼﺪر‬
‫اﻟﻤﯿﺎه‬
‫ﻃﻠﻤﺒﺔ‬ ‫اﻟﺮﺋﯿﺴﻰ‬ ‫ﻃﻠﻤﺒﺎت‬
‫ﻤﺼﺩﺭ ﺍﻟﺸﺎﺭﻉ‬ ‫ﺟﻮﻛﻰ‬
‫اﻟﻤﯿﺎه ﺟﻮﻛﻰ‬
‫ﻃﻠﻤﺒﺎت‬
‫ﺍﻟﺒﺩﺭﻭﻡ‬ ‫رﺋﯿﺴﯿﺔ‬

‫) ﺃ ( ﺭﺴﻡ ﺘﺨﻁﻴﻁﻲ ﻟﻠﺘﻐﺫﻴﺔ ﺇﻟﻲ ﺃﻋﻠﻰ ﻤﻥ ﺍﻟﺸﺒﻜﺔ‬ ‫)ﺏ( ﺭﺴﻡ ﺘﺨﻁﻴﻁﻲ ﻟﻠﺘﻐﺫﻴﺔ ﺇﻟﻲ ﺃﻋﻠﻰ ﻭﻟﻜﻥ‬
‫ﺍﻟﻌﻤﻭﻤﻴﺔ ﻤﺒﺎﺸﺭﺓ )ﻀﻐﻁ ﺜﺎﺒﺕ(‬ ‫ﺍﻟﺴﺤﺏ ﻤﻥ ﺨﺯﺍﻥ ﺃﺭﻀﻲ )ﻀﻐﻁ ﺜﺎﺒﺕ(‬

‫ﺷﻜﻞ رﻗﻢ )‪ :(٢٣-١‬رﺳﻢ ﺗﺨﻄﯿﻄﻰ ﻟﻠﺘﻐﺬﯾﺔ ﺑﺎﻟﻤﺎء إﻟﻰ أﻋﻠﻰ ﻋﻨﺪ ﺿﻐﻂ ﺛﺎﺑﺖ‬
‫ﻟﻠﻤﺒﺎﻧﻰ ﻣﺘﻮﺳﻄﺔ اﻻرﺗﻔﺎع‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻴﺒﻴﻥ ﺸﻜل )‪ (٢٤-١‬ﺍﻟﻁﻠﻤﺒﺎﺕ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻟﺭﻓﻊ ﻀﻐﻁ ﺍﻟﻤﻴﺎﻩ ﻭﺘﻭﺼـﻴﻠﻬﺎ‬


‫ﺇﻟﻰ ﺍﻷﺩﻭﺍﺭ ﺍﻟﻌﻠﻴﺎ ﺒﺎﻟﻌﻤﺎﺭﺍﺕ ﺍﻟﺴﻜﻨﻴﺔ ﻤﺘﻭﺴﻁﺔ ﺍﻻﺭﺘﻔـﺎﻉ‪ .‬ﻭﻗـﺩ ﺘﻭﺠـﺩ‬
‫ﻭﺤﺩﺍﺕ ﻤﺘﻌﺩﺩﺓ ﻴﻤﻜﻥ ﺃﻥ ﻴﺼل ﻋﺩﺩﻫﺎ ﺇﻟﻰ ‪ ٦‬ﻤﻀﺨﺎﺕ ﻭﻴﻤﻜﻥ ﺍﺴـﺘﺨﺩﺍﻡ‬
‫ﻨﻔﺱ ﺍﻷﺴﻠﻭﺏ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻰ ﺍﻟﺴﻜﻨﻴﺔ ﺃﻭ ﺍﻟﺘﺠﺎﺭﻴﺔ ﺃﻭ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻰ ﺍﻟﻌﺎﻤـﺔ ﺃﻭ‬
‫ﺍﻟﻔﻨﺎﺩﻕ ﺃﻭ ﺍﻟﻤﺴﺘﺸﻔﻴﺎﺕ‪.‬‬
‫ﻭﺘﺼـل ﺍﻟﻘــﺩﺭﺓ ﻓﻰ ﺍﻟﻤﺠﻤﻭﻋﺔ ﺇﻟﻰ ‪ ٢.٩٨ × ٦‬ﻙ‪.‬ﻭ‪ .‬ﻋﻨـﺩ ﺴـﺭﻋﺔ‬
‫‪٢٩٠٠‬ﻟﻔﺔ‪/‬ﺩ ﻭﺠﻬﺩ ‪ ٣/٥٠/٣٨٠‬ﻭﺘﻘﻭﻡ ﺒﺭﻓﻊ ‪٤٠‬ﻡ‪/٣‬ﺴﺎﻋﺔ ﻋﻨﺩ ‪ ٥‬ﺒﺎﺭ‪.‬‬
‫ﻭﻴﻤﻜﻥ ﺤﺴﺎﺏ ﻗﺩﺭﺓ ﻤﺤﺭﻙ ﺍﻟﻁﻠﻤﺒﺔ )‪ (P‬ﻤﻥ ﺍﻟﻤﻌﺎﺩﻟﺔ )‪ (١-١‬ﺍﻟﺘﺎﻟﻴﺔ‪:‬‬
‫‪ω.Q × H‬‬
‫=‪P‬‬ ‫‪× 0.746 KW‬‬ ‫)‪(1-1‬‬
‫‪75 × η‬‬
‫ﺤﻴﺙ‪:‬‬
‫‪ : Q‬ﻤﻌﺩل ﺍﻟﺘﺼﺭﻑ )ﻡ‪/٣‬ﺙ(‬
‫‪ : H‬ﺍﻟﺭﺍﻓﻊ ﺍﻻﺴﺘﺎﺘﻴﻜﻰ )ﻡ(‬
‫‪ : η‬ﺍﻟﻜﻔﺎﺀﺓ )ﺤﻭﺍﻟﻰ ‪(٪ ٨٠‬‬
‫‪ : ω‬ﺍﻟﻜﺜﺎﻓﺔ = ‪) ١٠٠٠‬ﻜﺠﻡ‪/‬ﻡ‪(٣‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫)ﺏ( ﻤﺠﻤﻭﻋﺔ ﻤﻥ ﺃﺭﺒﻌﺔ ﻁﻠﻤﺒﺎﺕ ﺘﻘﻭﻡ ﺒﺭﻓﻊ ﺍﻟﻤﻴﺎﻩ‬


‫ﻤﻥ ‪ ٤‬ﺇﻟﻲ ‪ ١٠‬ﺒﺎﺭ‬

‫) ﺃ ( ﻤﻀﺨﺔ ﺭﻓﻊ ﻤﺭﻜﺒﺔ ﻋﻠﻰ ﺨﻁ ﺍﻟﻁﺭﺩ ﻭﻋﺩﺩ‬


‫)‪ (٢‬ﺨﺯﺍﻥ ﺘﻤﺩﺩ‬

‫ﺷﻜﻞ رﻗﻢ )‪ :(٢٤-١‬ﻃﻠﻤﺒﺎت رﻓﻊ اﻟﻀﻐﻂ )‪(Booster pumps‬‬


‫ﻟﺘﻐﺬﯾﺔ اﻟﻤﺒﺎﻧﻰ ﻣﺘﻮﺳﻄﺔ اﻻرﺗﻔﺎع‬
‫‪.‬‬

‫ﻭﻴﻭﻀﺢ ﺠﺩﻭل )‪ (٨-١‬ﻗﺩﺭﺓ ﻁﻠﻤﺒﺎﺕ ﺍﻟﻤﻴﺎﻩ ﺤﺴﺏ ﻤﻌﺩل ﺍﻟﺘﺼﺭﻑ ﻋﻨﺩ ﺭﻓﻊ )‪ (١٠‬ﺒﺎﺭ‬
‫ﻭﺘﻌﻤل ﻋﻨﺩ ﺠﻬﺩ ‪ ٣٨٠‬ﻓﻭﻟﺕ ﺜﻼﺜﻲ ﺍﻷﻁﻭﺍﺭ‪.‬‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪ :(٨-١‬ﻗﺩﺭﺓ ﻁﻠﻤﺒﺎﺕ ﺍﻟﻤﻴﺎﻩ ﺤﺴﺏ ﻤﻌﺩل ﺍﻟﺘﺼﺭﻑ ﻋﻨﺩ ﺭﻓﻊ )‪ (١٠‬ﺒﺎﺭ‬

‫ﻗﺩﺭﺓ ﺍﻟﻁﻠﻤﺒﺔ‬ ‫ﻤﻌﺩل ﺍﻟﺘﺼﺭﻑ‬


‫)ﻙ‪.‬ﻭﺍﺕ(‬ ‫)ﻡ‪/٣‬ﺴﺎﻋﺔ(‬
‫‪٥.٥‬‬ ‫‪١٨‬‬
‫‪٧.٥‬‬ ‫‪٢١.٦‬‬
‫‪٧.٥‬‬ ‫‪٢٢.٤‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫)ﺏ( ﻁﻠﻤﺒﺎﺕ ﺍﻟﺤﺭﻴﻕ‬


‫ﻋﺎﻡ‬
‫)‪ (١‬ﻴﻤﻜﻥ ﺃﻥ ﺘﺴﺘﺨﺩﻡ ﻁﻠﻤﺒﺔ ﻤﻨﻔﺭﺩﺓ ﻟﻀﺦ ﺍﻟﻤﻴﺎﻩ ﻋﻨﺩ ﺤﺩﻭﺙ ﺤﺭﻴـﻕ‪ ،‬ﻓﻌﻠـﻰ‬
‫ﺴﺒﻴل ﺍﻟﻤﺜﺎل ﻗﺩ ﻴﻜﻭﻥ ﺘﺼﺭﻓﻬﺎ ﺤﻭﺍﻟﻰ ‪٤٠‬ﻡ‪/٣‬ﺴﺎﻋﺔ ﻋﻨﺩ ﺭﻓﻊ ﺤـﻭﺍﻟﻰ ‪١٠‬‬
‫ﺒﺎﺭ ﻭﺘﻜﻭﻥ ﻗﺩﺭﺓ ﻤﺤﺭﻜﻬﺎ ﺍﻟﻜﻬﺭﺒﺎﺌﻰ ‪ ٢٢‬ﻙ‪.‬ﻭ‪ .‬ﻋﻨﺩ ﺴﺭﻋﺔ ‪ ٢٩٠٠‬ﻟﻔـﺔ‪/‬ﺩ‬
‫ﻭﺠﻬﺩ ‪.٣/٥٠/٣٨٠‬‬
‫)‪ (٢‬ﻴﺠﺏ ﺃﻥ ﺘﺤﻘﻕ ﻨﻅﻡ ﺍﻹﻁﻔﺎﺀ ﺒﺎﻟﻤﺎﺀ ﻓﻰ ﺍﻟﻤﻨﺎﻁﻕ ﺍﻟﻜﺒﻴﺭﺓ ﺃﻭ ﺍﻟﻤﺒﺎﻨﻰ ﺸـﺎﻫﻘﺔ‬
‫ﺍﻻﺭﺘﻔﺎﻉ ﺍﻟﺘﻭﺍﺯﻥ ﺍﻟﻬﻴﺩﺭﻭﻟﻴﻜﻰ ﺒﻴﻥ ﺃﺒﻌﺩ ﻭﺃﻗﺭﺏ ﻨﻘﻁﺔ ﻟﻤﺤﻁﺔ ﺍﻟﻀﺦ‪.‬‬
‫)‪ (٣‬ﻴﻤﻜﻥ ﺃﻥ ﻴﺘﻡ ﺇﺩﺍﺭﺓ ﺍﻟﻤﻀﺨﺔ ﻤﻥ ﺍﻟﻤﺤﺭﻙ ﺍﻟﻜﻬﺭﺒﺎﺌﻰ ﺇﻤﺎ ﻤﺒﺎﺸـﺭﺓ )ﺒـﺩﻭﻥ‬
‫ﺍﺴﺘﺨﺩﺍﻡ ﻜﻭﺒﻠﻨﺞ( ﺃﻭ ﺒﺎﺴﺘﺨﺩﺍﻡ ﻜﻭﺒﻠﻨﺞ‪.‬‬
‫ﺍﺴﺘﺨﺩﺍﻡ ﻁﻠﻤﺒﺔ ﻜﻬﺭﺒﺎﺌﻴﺔ ﻭﺃﺨﺭﻯ ﺘﺩﺍﺭ ﺒﻤﺎﻜﻴﻨﺔ ﺩﻴﺯل‬
‫)‪ (١‬ﻓﻰ ﻤﻌﻅﻡ ﺍﻟﻤﺒﺎﻨﻰ ﻴﻜﻭﻥ ﻓﻰ ﻤﺤﻁﺔ ﺍﻟﻀﺦ ﻁﻠﻤﺒﺔ ﺘﺩﺍﺭ ﺒﻤﺤﺭﻙ ﻜﻬﺭﺒـﺎﺌﻰ‬
‫ﻭﺃﺨﺭﻯ ﺘﺩﺍﺭ ﺒﻭﺍﺴﻁﺔ ﻤﺤﺭﻙ ﺩﻴﺯل ﻴﻘﻭﻡ ﺘﻠﻘﺎﺌﻴﺎﹰ ﻋﻨﺩ ﺤﺩﻭﺙ ﺤﺭﻴﻕ ﻭﺘﺘﻭﻟﻰ‬
‫ﻁﻠﻤﺒﺔ ﺠﻭﻜﻰ )‪ (Jokey pump‬ﺇﻴﺠﺎﺩ ﻀـﻐﻁ ﻋﻠـﻰ ﻤﺠﻤـﻊ ﺍﻟﻤﻭﺍﺴـﻴﺭ‬
‫)‪ (Header‬ﺍﻟﺭﺌﻴﺴﻲ ﻴﺅﺩﻯ ﺇﻟﻰ ﻋﻤل ﺍﻟﻁﻠﻤﺒﺎﺕ ﺒﺎﺴﺘﺨﺩﺍﻡ ﺤﺴـﺎﺱ ﻀـﻐﻁ‬
‫ﻭﻟﻭﺤﺔ ﺘﺸﻐﻴل‪.‬‬
‫)‪ (٢‬ﻴﺒﻴﻥ ﺠﺩﻭل )‪ (٩-١‬ﻗﺩﺭﺓ ﻤﺤﺭﻙ ﻁﻠﻤﺒﺎﺕ ﺍﻟﺤﺭﻴﻕ ﺤﺴﺏ ﺍﻟﺴﺭﻋﺔ‪.‬‬
‫)‪ (٣‬ﻴﺒﻴﻥ ﺸﻜل )‪ (٢٥-١‬ﻨﻤﺎﺫﺝ ﻟﻬﺫﻩ ﺍﻷﻨﻅﻤﺔ ﻭﻟﻭﺤﺔ ﺍﻟﺘﺸﻐﻴل‪.‬‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪ :(٩-١‬ﻗﺩﺭﺓ ﻤﺤﺭﻙ ﻁﻠﻤﺒﺎﺕ ﺍﻟﺤﺭﻴﻕ ﺤﺴﺏ ﺍﻟﺴﺭﻋﺔ‬


‫ﻋﻨﺩ ﺭﻓﻊ ﻤﺎﻨﻭﻤﺘﺭﻯ )‪ (١٠‬ﺒﺎﺭ ﻭﺘﻌﻤل ﻋﻨﺩ ﺠﻬﺩ ‪٣/٥٠/٣٨٠‬‬

‫ﻗﺩﺭﺓ ﺍﻟﻤﺤﺭﻙ‬ ‫ﺍﻟﺴﺭﻋﺔ‬


‫ﻡ‬
‫)ﻙ‪.‬ﻭﺍﺕ(‬ ‫)ﻟﻔﺔ‪/‬ﺩ(‬
‫‪١٥‬‬ ‫‪١‬‬
‫‪٢٠‬‬ ‫‪١٥٠٠‬‬ ‫‪٢‬‬
‫‪٣٥‬‬ ‫‪٣‬‬
‫‪٧٧‬‬ ‫‪٤‬‬
‫‪١٠٢‬‬ ‫‪٥‬‬
‫‪١٣٠‬‬ ‫‪٦‬‬
‫‪٢٩٠٠‬‬
‫‪١٥٥‬‬ ‫‪٧‬‬
‫‪١٧٥‬‬ ‫‪٨‬‬
‫‪٢٠٥‬‬ ‫‪٩‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻁﻠﻤﺒﺔ ﺒﺎﻟﻤﺤﺭﻙ ﺍﻟﻜﻬﺭﺒﺎﺌﻲ‬

‫ﻁﻠﻤﺒﺔ ﺠﻭﻜﻲ ﺭﺃﺴﻴﺔ‬


‫ﻟﻭﺤﺔ ﺘﻘﻭﻴﻡ ﻤﺤﺭﻙ ﺍﻟﻁﻠﻤﺒﺔ‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(٢٥-١‬ﻨﻤﺎﺫﺝ ﻟﻁﻠﻤﺒﺔ ﻜﻬﺭﺒﺎﺌﻴﺔ ﻭﻁﻠﻤﺒﺔ ﺘﻌﻤل ﺒﻤﺎﻜﻴﻨﺔ ﺩﻴﺯل‬


‫ﻓﻰ ﻤﺤﻁﺔ ﻹﻁﻔﺎﺀ ﺍﻟﺤﺭﻴﻕ ﺒﺎﻟﻤﺎﺀ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻰ‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫)ﺕ( ﻁﻠﻤﺒﺎﺕ ﺍﻟﺼﺭﻑ ﺍﻟﺼﺤﻰ‬


‫)‪ (١‬ﻴﺘﻡ ﺭﻓﻊ ﻤﻴﺎﻩ ﺍﻟﺼﺭﻑ ﻤﻊ ﺍﻟﻤﺨﻠﻔﺎﺕ ﻭﺍﻟﻔﻀﻼﺕ ﻤـﻥ ﺍﻟﻤﺒـﺎﻨﻰ ﻭﺍﻟﺘـﻰ ﻻ‬
‫ﻴﻤﻜﻥ ﺼﺭﻓﻬﺎ ﺘﺜﺎﻗﻠﻴﺎﹰ ﻭﻴﻜﻭﻥ ﺫﻟﻙ ﺒﻭﺍﺴﻁﺔ ﻤﺤﻁﺔ ﻁﻠﻤﺒﺎﺕ ﺨﺎﺼـﺔ ﺘﻘـﻭﻡ‬
‫ﺒﺭﻓﻌﻬﺎ ﺇﻟﻰ ﺨﻁﻭﻁ ﺼﺭﻑ ﺍﻟﻤﺠﺎﺭﻯ ﺍﻟﻌﻤﻭﻤﻴﺔ‪.‬‬
‫)‪ (٢‬ﺘﺴﺘﺨﺩﻡ ﻟﻬﺫﺍ ﺍﻟﻐﺭﺽ ﻁﻠﻤﺒﺎﺕ ﻏﺎﻁﺴﺔ ﺘﻌﻤل ﻜﻬﺭﺒﺎﺌﻴﺎﹰ ﺒﻁﺭﻴﻘﺔ ﺘﻠﻘﺎﺌﻴﺔ‪.‬‬
‫)‪ (٣‬ﻴﺒﻴﻥ ﺸﻜل )‪ (٢٦-١‬ﻤﺤﻁﺔ ﻟﺭﻓﻊ ﻤﻴﺎﻩ ﺼﺭﻑ )ﺒـﺩﻭﻥ ﻓﻀـﻼﺕ( ﻭﺍﻟﺘـﻰ‬
‫ﻴﻁﻠﻕ ﻋﻠﻴﻬﺎ )‪ (Waste water‬ﻭﺘﺘﻜﻭﻥ ﻤﻥ ﻁﻠﻤﺒﺘـﻴﻥ ﻭﻋﻭﺍﻤـﺎﺕ ﺍﻟـﺘﺤﻜﻡ‬
‫ﻭﺍﻹﻨﺫﺍﺭ ﻋﻨﺩ ﺍﺭﺘﻔﺎﻉ ﻤﻨﺴﻭﺏ ﺍﻟﻤﻴﺎﻩ ﻓﻰ ﺍﻟﺒﻴﺎﺭﺓ ﻋﻥ ﺍﻟﺤﺩ ﺍﻟﻤﺴﻤﻭﺡ‪.‬‬
‫)‪ (٤‬ﻴﺒﻴﻥ ﺸﻜل )‪ (٢٧-١‬ﻨﻤﺎﺫﺝ ﻁﻠﻤﺒﺎﺕ ﺼﺭﻑ ﺴﻭﺍﺌل ﺒﺩﻭﻥ ﻤﺨﻠﻔﺎﺕ ﺜﻘﻴﻠـﺔ‪،‬‬
‫ﻭﺸﻜل )‪ (٢٨-١‬ﻨﻤﺎﺫﺝ ﻟﻁﻠﻤﺒﺎﺕ ﺼﺭﻑ ﺴﻭﺍﺌل ﺒﺎﻟﻤﺨﻠﻔﺎﺕ‪.‬‬
‫)‪ (٥‬ﺘﺼل ﻗﺩﺭﺓ ﺍﻟﻤﺤﺭﻜﺎﺕ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻓﻰ ﺍﻟﻨﻤﺎﺫﺝ ﺍﻟﻤﺒﻴﻨﺔ ﻓﻰ ﺸـﻜل )‪(٢٨-١‬‬
‫ﺇﻟﻰ ‪ ١٠‬ﻙ‪.‬ﻭ‪ .‬ﻭﻗﺩ ﺘﺼل ﻓﻰ ﺍﻟﻨﻤﺎﺫﺝ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻓﻰ ﺼﺭﻑ ﺴﻭﺍﺌل ﺒﻬـﺎ‬
‫ﻤﻭﺍﺩ ﺼﻠﺒﺔ ﺇﻟﻰ ‪ ١٥‬ﻙ‪.‬ﻭ‪ .‬ﻋﻨﺩ ﺠﻬـﺩ ‪ ٣/٥٠/٣٨٠‬ﻭﺘﻜـﻭﻥ ﻋـﺎﺩﺓ ﻓـﻰ‬
‫ﻤﺠﻤﻭﻋﺔ ﻁﻠﻤﺒﺘﻴﻥ ﺃﻭ ﺜﻼﺜﺔ‪.‬‬
‫)‪ (٦‬ﻴﺠﺏ ﺃﻥ ﺘﻌﻤل ﺍﻟﻁﻠﻤﺒﺎﺕ ﺍﻟﻤﻐﻤﻭﺭﺓ ﺒﺎﻟﺘﺒﺎﺩل ﺘﻔﺎﺩﻴﺎﹰ ﻟﺘﻠﻑ ﺘﻠﻙ ﺍﻟﺘـﻰ ﺘﻅـل‬
‫ﺒﺩﺍﺨﻠﻬﺎ ﻤﻴﺎﻩ ﺍﻟﺼﺭﻑ‪ ،‬ﺇﺫﺍ ﺒﻘﻴﺕ ﺩﻭﻨﻤﺎ ﻋﻤل ﻟﻔﺘﺭﺓ ﻁﻭﻴﻠﺔ‪ .‬ﻭﻴﻜـﻭﻥ ﺫﻟـﻙ‬
‫ﺒﺎﺴﺘﺨﺩﺍﻡ ﺩﺍﺌﺭﺓ ﺍﻨﺘﻘﺎﺀ ﺘﻠﻘﺎﺌﻴﺔ ﺘﻘﻭﻡ ﺒﺘﺸﻐﻴل ﺍﻟﻁﻠﻤﺒﺘﻴﻥ ﺘﺒﺎﺩﻟﻴﺎﹰ ﺒﻌﺩ ﻜل ﺘﻭﻗﻑ‪.‬‬
‫)‪ (٧‬ﻟﺤﺴﺎﺏ ﻗﺩﺭﺓ ﺍﻟﻁﻠﻤﺒﺔ ﺘﺴﺘﺨﺩﻡ ﺍﻟﻤﻌﺎﺩﻟﺔ )‪:(٢-١‬‬
‫‪Q.H .ω‬‬
‫=‪P‬‬ ‫] ‪× 0.746 [kW‬‬ ‫)‪(1-2‬‬
‫‪75 × η‬‬
‫ﺤﻴﺙ‪:‬‬
‫‪ : Q‬ﻤﻌﺩل ﺍﻟﺘﺼﺭﻑ )ﻡ‪/٣‬ﺙ(‬
‫‪ : H‬ﺍﻟﺭﺍﻓﻊ ﺍﻻﺴﺘﺎﺘﻴﻜﻰ )ﻡ(‬
‫‪ : ω‬ﺍﻟﻜﺜﺎﻓﺔ = )ﻟﻠﻤﻴﺎﻩ ‪ ١٠٠٠‬ﻭﻟﻠﻔﻀﻼﺕ ‪ ١٢٠٠‬ﻜﺠﻡ‪/‬ﻡ‪(٣‬‬
‫‪ : η‬ﺍﻟﻜﻔﺎﺀﺓ )ﺤﻭﺍﻟﻰ ‪(٪ ٧٥‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺍﻟﺒﻴﺎﻥ‪:‬‬
‫‪ - ١‬ﻁﻠﻤﺒﺘﺎﻥ ﻤﻐﻤﻭﺭﺘﺎﻥ‪.‬‬ ‫‪٥‬‬
‫‪ - ٢‬ﻭﺼﻠﺔ ﻋﻠﻰ ﺸﻜل ﺤﺭﻑ ‪.Y‬‬
‫‪ - ٣‬ﺼﻤﺎﻡ ﻋﺩﻡ ﺭﺠﻭﻉ‪.‬‬ ‫‪٤‬‬
‫‪ - ٤‬ﺤﻠﻘﺔ ﻤﺼﻴﺩﺓ ﺍﻻﻨﺩﻓﺎﻉ‬ ‫‪٧‬‬
‫‪٢‬‬
‫‪٢‬‬
‫ﺍﻟﻌﻜﺴﻲ‪.‬‬ ‫‪٦‬‬
‫‪ - ٥‬ﻤﺴﺘﻭﻯ ﺍﻻﻨﺩﻓﺎﻉ ﺍﻟﻌﻜﺴﻲ‪.‬‬
‫‪ - ٦‬ﺒﻴﺎﺭﺓ ﺍﻟﺼﺭﻑ ﺍﻟﺭﺌﻴﺴﻴﺔ‬
‫)ﺍﻟﻤﻁﺒﻕ(‪.‬‬
‫‪ - ٧‬ﻟﻭﺤﺔ ﺍﻟﺘﺸﻐﻴل ﻭﺍﻟﺘﺤﻜﻡ‪.‬‬
‫‪ - ٨‬ﻤﻔﺎﺘﻴﺢ ﻋﻭﺍﻤﺔ ﻟﻠﺘﺤﻜﻡ ﻓﻲ‬
‫‪٣‬‬
‫ﺍﻟﻤﻨﺴﻭﺏ ﻭﺍﻹﻨﺫﺍﺭ‪.‬‬

‫‪٨‬‬
‫‪١‬‬
‫‪٨‬‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(٢٦-١‬ﻁﻠﻤﺒﺎﺕ ﻜﻬﺭﺒﺎﺌﻴﺔ ﻤﻐﻤﻭﺭﺓ ﻟﺭﻓﻊ ﻤﻴﺎﻩ ﺼﺭﻑ ﻤﻥ ﺒﻴﺎﺭﺓ ﺘﺠﻤﻴﻊ‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫) ﺃ ( ﻁﻠﻤﺒﺔ ﺭﻓﻊ ﻤﻴﺎﻩ ﺼﺭﻑ ﻭﺘﺠﻤﻴﻊ‬ ‫)ﺏ( ﻁﻠﻤﺒﺔ ﺭﻓﻊ ﻤﻴﺎﻩ ﺼﺭﻑ ﻭﺘﺠﻤﻴﻊ ﺫﺍﺕ‬ ‫)ﺠـ( ﻁﻠﻤﺒﺔ ﺼﺭﻑ ﺼﻨﺎﻋﻲ ﺫﺍﺕ ﺒﺩﻥ‬

‫ﻤﻁﺭ ﺫﺍﺕ ﺒﺩﻥ ﺒﻼﺴﺘﻴﻙ ﻭﺘﻌﻤل ﺘﻠﻘﺎﺌﻴﺎﹰ‬ ‫ﺒﺩﻥ ﻤﻥ ﺍﻟﺼﻠﺏ ﺍﻟﺫﻱ ﻻ ﻴﺼﺩﺃ ﻭﻤﺤﺭﻙ‬ ‫ﻤﻌﺩﻨﻲ ﻭﺘﺴﺤﺏ ﺴﻭﺍﺌل ﻋﺎﻤﺔ ﻭﺘﺘﺤﻤل‬

‫ﻭﻤﺤﻤﻴﺔ ﻀﺩ ﺯﻴﺎﺩ ﺍﻟﺤﻤل‪.‬‬ ‫ﻤﻀﺎﺩ ﻟﻼﻨﻔﺠﺎﺭ ﻭﺘﻌﻤل ﻤﻊ ﻤﻴﺎﻩ ﺒﺩﺭﺠﺎﺕ‬ ‫ﺩﺭﺠﺎﺕ ﺤﺭﺍﺭﺓ ﺤﺘﻰ ‪ ْ ٩٥‬ﻡ‬
‫ﺤﺭﺍﺭﺓ ﺤﺘﻰ ‪ ْ ٣٥‬ﻡ‬

‫ﺷﻜﻞ رﻗﻢ )‪ :(٢٧-١‬ﻧﻤﺎذج ﻟﻄﻠﻤﺒﺎت ﺻﺮف ﺳﻮاﺋﻞ‬

‫ﻓﺘﺤﺔ اﻟﻄﺮد‬

‫ﻓﺘﺤﺔ اﻟﻤﺺ ﻋﻠﯿﮭﺎ ﺷﺒﻜﺔ ﻣﻨﺎﺳﺒﺔ ﻟﺤﺠﻢ اﻟﻔﻀﻼت اﻟﻤﺴﻤﻮح ﻣﺮورھﺎ ﺑﺎﻟﻄﻠﻤﺒﺔ‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(٢٨-١‬ﻨﻤﺎﺫﺝ ﻁﻠﻤﺒﺎﺕ ﺼﺭﻑ ﻓﻀﻼﺕ )‪(Sewage pumps‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫)ﺙ( ﺴﺨﺎﻨﺎﺕ ﺤﻤﺎﻤﺎﺕ ﺍﻟﺴﺒﺎﺤﺔ‬


‫)‪ (١‬ﻴﺘﻡ ﻋﺎﺩﺓ ﺍﺴﺘﺨﺩﺍﻡ ﺴﺨﺎﻨﺎﺕ ﺍﻟﺯﻴﺕ ﺃﻭ ﺴﺨﺎﻨﺎﺕ ﺍﻟﺒﺨـﺎﺭ ﻟﺘﺴـﺨﻴﻥ ﺍﻟﻤـﺎﺀ‬
‫ﺍﻟﻤﺴﺘﺨﺩﻡ ﻓﻰ ﺤﻤﺎﻤﺎﺕ ﺍﻟﺴﺒﺎﺤﺔ ﻭﻗﺩ ﻴﺘﻡ ﺃﺤﻴﺎﻨﺎﹰ ﺍﺴﺘﺨﺩﺍﻡ ﺍﻟﻜﻬﺭﺒﺎﺀ ﻓﻰ ﻋﻤﻠﻴﺔ‬
‫ﺍﻟﺘﺴﺨﻴﻥ‪.‬‬
‫)‪ (٢‬ﻴﺠﺏ ﺃﻥ ﺘﺯﻭﺩ ﺤﻤﺎﻤﺎﺕ ﺍﻟﺴﺒﺎﺤﺔ ﺒﻭﺴﺎﺌل ﻟﻠﺘﺤﻜﻡ ﻟﻠﺤﺩ ﻤﻥ ﺍﺭﺘﻔـﺎﻉ ﺩﺭﺠـﺔ‬
‫ﺤﺭﺍﺭﺓ ﺍﻟﻤﺎﺀ ﺤﺘﻰ ﻻ ﺘﺯﻴﺩ ﻋﻥ ‪ْ ٢٦.٥‬ﻡ )ﻴﺴﺘﺜﻨﻰ ﻤـﻥ ﺫﻟـﻙ ﺍﻟﺤﻤﺎﻤـﺎﺕ‬
‫ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻷﻏﺭﺍﺽ ﺍﻟﻌﻼﺝ‪.‬‬
‫)‪ (٣‬ﺒﺎﻟﻨﺴﺒﺔ ﻟﻠﺤﻤﺎﻤﺎﺕ ﺍﻟﻤﻜﺸﻭﻓﺔ ﻓﻰ ﺍﻷﻨﺩﻴﺔ ﻭﺍﻟﻔﻨﺎﺩﻕ ﻭﺍﻟﻘﺭﻯ ﺍﻟﺴـﻴﺎﺤﻴﺔ ﻓﻴـﺘﻡ‬
‫ﺍﻟﺘﺤﻜﻡ ﻓﻰ ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺍﻟﻤﺎﺀ ﺒﺤﻴﺙ ﻴﺘﻭﻗﻑ ﺍﻟﺘﺴـﺨﻴﻥ ﺘﻠﻘﺎﺌﻴـﺎﹰ ﺇﺫﺍ ﻗﻠـﺕ‬
‫ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺍﻟﻬﻭﺍﺀ ﺍﻟﺨﺎﺭﺠﻰ ﻋﻥ ‪ْ ١٦‬ﻡ )ﺘﻭﻓﻴﺭﺍﹰ ﻟﻠﻁﺎﻗﺔ(‪.‬‬
‫ﺍﻟﺴﺨﺎﻨﺎﺕ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻓﻰ ﺘﺴﺨﻴﻥ ﺍﻟﻤﻴﺎﻩ ﻓﻰ ﺍﻟﻤﻨﺎﺯل ﺍﻟﺼﻐﻴﺭﺓ‬
‫ﻴﺒﻴﻥ ﺠﺩﻭل )‪ (١٠-١‬ﻗﺩﺭﺓ ﺍﻟﺩﺨﻭل ﻟﻠﺴﺨﺎﻨﺎﺕ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻓـﻰ ﺍﻟﻤﻨـﺎﺯل‬ ‫)ﺃ(‬
‫ﺍﻟﺼﻐﻴﺭﺓ )ﻋﺎﺌﻠﺔ ﺃﻭ ﻋﺎﺌﻠﺘﻴﻥ( ﺒﺎﺴﺘﺨﺩﺍﻡ ﺍﻟﻜﻬﺭﺒﺎﺀ ﻭﺘﻜﻭﻥ ﻫـﺫﻩ ﺍﻟﺴـﺨﺎﻨﺎﺕ‬
‫ﻤﺭﻜﺯﻴﺔ ﻭﺘﻭﻀﻊ ﺒﺎﻟﺒﺩﺭﻭﻡ ﻭﻴﺘﻡ ﺍﻟﺘﻭﺯﻴﻊ ﻤﻨﻬﺎ ﺒﺎﺴﺘﺨﺩﺍﻡ ﺸﺒﻜﺔ ﻤﻴﺎﻩ ﺨﺎﺼـﺔ‬
‫ﻭﻴﺘﻡ ﻓﻴﻬﺎ ﺍﺴﺘﺨﺩﺍﻡ ﻁﻠﻤﺒﺔ ﺘﻘﻠﻴﺏ ﻟﻀﻤﺎﻥ ﺒﻘﺎﺀ ﺍﻟﻤﺎﺀ ﺴﺎﺨﻥ ﻭﻜﺫﻟﻙ ﻁﻠﻤﺒـﺎﺕ‬
‫ﺍﻟﺭﻓﻊ ﺇﻥ ﺍﻗﺘﻀﺕ ﺍﻟﻀﺭﻭﺭﺓ‬
‫)ﺏ( ﻓﻰ ﺍﻟﻤﺒﺎﻨﻰ ﺍﻟﺴﻜﻨﻴﺔ ﺫﺍﺕ ﺍﻟﺸﻘﻕ ﺘﺴﺘﺨﺩﻡ ﺃﺤﻴﺎﻨﺎﹰ ﺴﺨﺎﻨﺎﺕ ﻜﻬﺭﺒﺎﺌﻴـﺔ ﻗﺎﺌﻤـﺔ‬
‫ﺒﺫﺍﺘﻬــﺎ )ﻏﻴﺭ ﻤﺭﻜﺯﻴﺔ( ﻭﺘﻭﻀـــﻊ ﺒﺎﻟﻘــﺭﺏ ﻤـﻥ ﺩﻭﺭﺍﺕ ﺍﻟﻤﻴـﺎﻩ‬
‫ﺒﺴﻌﺎﺕ ﺤﺘﻰ ‪ ١٠٠ ، ٧٠ ، ٥٠ ، ٣٠‬ﻟﺘﺭﺍ ﻗﺩ ﺘﺼل ﻗﺩﺭﺓ ﺍﻟﺴﺨﺎﻨﺎﺕ ﺒﻬـﺎ‬
‫ﻤﺎ ﺒﻴﻥ ‪ ١.٢‬ﻙ‪.‬ﻭ‪ .‬ﻭﺤﺘﻰ ‪ ٤.٥‬ﻙ‪.‬ﻭ‪.‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻷﻭل‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪ (١٠-١‬ﺃﻗل ﺴﻌﺔ ﺤﺭﺍﺭﻴﺔ ﻟﺴﺨﺎﻨﺎﺕ ﻤﻴﺎﻩ ﻤﺭﻜﺯﻴﺔ‬


‫ﺨﺎﺼﺔ ﺒﻭﺤﺩﺍﺕ )ﺴﻜﻨﻴﺔ ﻋﺎﺌﻠﺔ ﻭﻋﺎﺌﻠﺘﻴﻥ(‬
‫‪1‬‬ ‫‪1‬‬ ‫‪1‬‬
‫ﻋﺩﺩ ﺍﻟﺤﻤﺎﻤﺎﺕ‬ ‫‪1 to 1‬‬ ‫‪2 to 2‬‬ ‫‪3 to 3‬‬
‫‪2‬‬ ‫‪2‬‬ ‫‪2‬‬
‫ﻋﺩﺩ ﺤﺠﺭﺍﺕ ﺍﻟﻨﻭﻡ‬ ‫‪1‬‬ ‫‪2‬‬ ‫‪3‬‬ ‫‪2‬‬ ‫‪3‬‬ ‫‪4‬‬ ‫‪5‬‬ ‫‪3‬‬ ‫‪4‬‬ ‫‪5‬‬ ‫‪6‬‬
‫ﺴﻌﺔ ﺨﺯﺍﻥ ﺍﻟﺴﺨﺎﻥ ﺒﺎﻟﻠﺘﺭ‬ ‫‪75 115 150 150 190 190 250 140 250 250 300‬‬
‫ﺍﻟﻘﺩﺭﺓ ﺒﺎﻟﻜﻴﻠﻭﻭﺍﺕ‬ ‫‪2.5‬‬ ‫‪3.5‬‬ ‫‪4.5‬‬ ‫‪4.5‬‬ ‫‪5.5‬‬ ‫‪5.5‬‬ ‫‪5.5‬‬ ‫‪5.5‬‬ ‫‪5.5‬‬ ‫‪5.5‬‬ ‫‪5.5‬‬
‫ﻜﻤﻴﺔ ﺍﻟﺴﺤﺏ ﻤﻥ ﺍﻟﺨﺯﺍﻥ ﻓﻰ‬
‫‪115 170 225 220 270 270 330 270 330 380 385‬‬
‫ﺴﺎﻋﺔ ﻭﺍﺤﺩﺓ ﺒﺎﻟﻠﺘﺭ‬
‫ﻤﻴﺎﻩ ﺍﻻﺴﺘﻌﻭﺍﺽ )ﻟﺘﺭ‪/‬ﺴﺎﻋﺔ(‬ ‫‪3‬‬ ‫‪55‬‬ ‫‪68‬‬ ‫‪68‬‬ ‫‪84‬‬ ‫‪84‬‬ ‫‪84‬‬ ‫‪84‬‬ ‫‪84‬‬ ‫‪84‬‬ ‫‪84‬‬

‫ﻨﺼﻑ ﺤﻤﺎﻡ ﻴﻌﻨﻰ ﺩﻭﺭﺓ ﻤﻴﺎﻩ ﺼﻐﻴﺭﺓ ﺒﺤﻭﺽ ﻓﻘﻁ‪.‬‬ ‫* ﻤﻠﺤﻭﻅﺔ‪:‬‬


‫‪1‬‬
‫‪2‬‬
‫)ﺕ( ﻗﺩ ﺘﺴﺘﺨﺩﻡ ﺴﺨﺎﻨﺎﺕ ﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻭﺭﻴﺔ )ﺒﺩﻭﻥ ﺨﺯﺍﻨﺎﺕ( ﺘﺭﻜﺏ ﻋﻠﻰ ﺨـﻁ ﺍﻟﻤﻴـﺎﻩ‬
‫ﺍﻟﺴﺎﺨﻥ ﺍﻟﺭﺌﻴﺴﻰ ﻭﻗﺩ ﺘﺼل ﻗﺩﺭﺘﻬﺎ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﺤﺘـﻰ ‪ ٢٢‬ﻙ‪.‬ﻭﺍﺕ ﻋﻨـﺩ ﺠﻬـﺩ‬
‫‪ ٣/٥٠/٣٨٠‬ﻭﺫﻟﻙ ﺒﺎﻟﻤﻨﺎﺯل ﻭﺍﻟﻔﻴﻼﺕ ﻟﺘﺴﺨﻴﻥ ﻤﻴﺎﻩ ﺤﻤﺎﻤﺎﺕ ﺍﻟﺠﺎﻜﻭﺯﻯ ﻭﻜـﺫﻟﻙ‬
‫ﺒﺎﻟﻤﺴﺘﺸﻔﻴﺎﺕ ﺍﻟﺘﻰ ﺘﺤﺘﺎﺝ ﺇﻟﻰ ﻤﻴﺎﻩ ﺴﺎﺨﻨﺔ ﻓﻭﺭﻴﺔ‪.‬‬

‫‪١‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺘﺼﻤﻴﻡ ﺃﻋﻤﺎل ﺍﻹﻨﺎﺭﺓ ﻭﺍﻟﻘﻭﻯ‬ ‫‪-٢‬‬

‫ﺘﺼﻤﻴﻡ ﺃﻋﻤﺎل ﺍﻹﻨﺎﺭﺓ‬ ‫‪١-٢‬‬

‫ﻴﺠﺏ ﻋﻨﺩ ﺍﻟﺘﺨﻁﻴﻁ ﻟﺘﺼﻤﻴﻡ ﺘﺭﻜﻴﺒﺎﺕ ﺍﻹﻨﺎﺭﺓ ﺍﻟﺩﺍﺨﻠﻴﺔ ﻤﺭﺍﻋﺎﺓ ﺍﻟﻌﻭﺍﻤل ﺍﻵﺘﻴﺔ‪:‬‬

‫)‪ (١‬ﻤﺴﺘﻭﻯ ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ ﺍﻟﻤﻁﻠﻭﺒﺔ ﺤﺴﺏ ﻨﻭﻋﻴﺔ ﺍﺴﺘﺨﺩﺍﻡ ﺍﻟﻤﻜﺎﻥ‪.‬‬

‫)‪ (٢‬ﺃﻨﻅﻤﺔ ﺍﻹﻨﺎﺭﺓ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﺤﺴﺏ ﻨﻭﻋﻴﺔ ﺍﺴﺘﺨﺩﺍﻡ ﺍﻟﻤﻜﺎﻥ‪.‬‬

‫)‪ (٣‬ﻁﺒﻴﻌﺔ ﺍﻟﻤﻭﻗﻊ ﻭﺃﻟﻭﺍﻥ ﺍﻟﺤﻭﺍﺌﻁ ﻭﺍﻷﺴﻘﻑ ﻭﻤﺴﺎﺤﺔ ﻭﻨﺴﺏ ﺃﺒﻌﺎﺩ ﺍﻟﺴـﻁﺢ ﺍﻟﻤـﺭﺍﺩ‬
‫ﺇﻀﺎﺀﺘﻪ ﻭﻤﻭﺍﺩ ﺍﻟﺘﺸﻁﻴﺏ‪.‬‬

‫)‪ (٤‬ﺍﺨﺘﻴﺎﺭ ﺃﻨﻭﺍﻉ ﺍﻟﻤﺼﺎﺒﻴﺢ ﻭﻤﺴﺘﻭﻯ ﺘﺜﺒﻴﺕ ﻭﺘﺭﻜﻴﺏ ﻭﺤﺩﺍﺕ ﺍﻹﻨﺎﺭﺓ‪.‬‬

‫)‪ (٥‬ﺘﻭﺯﻴﻊ ﻭﺤﺩﺍﺕ ﺍﻹﻨﺎﺭﺓ‪.‬‬

‫)‪ (٦‬ﻤﺴﺘﻭﻴﺎﺕ ﺍﻟﺒﻬﺭ‪.‬‬

‫)‪ (٧‬ﻤﺴﺘﻭﻴﺎﺕ ﺘﻤﻴﻴﺯ ﺃﻟﻭﺍﻥ ﺍﻷﺠﺴﺎﻡ ﺩﺍﺨل ﺍﻟﻤﻜﺎﻥ‪.‬‬

‫ﻤﺴﺘﻭﻯ ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ‬ ‫)ﺃ(‬

‫‪ -‬ﻴﻌﺘﻤﺩ ﻤﺴﺘﻭﻯ ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ ﺍﻟﻤﻁﻠﻭﺏ ﻷﻱ ﻫﺩﻑ ﻤﺭﺌﻰ ﻋﻠﻰ ﺍﻟﻌﻭﺍﻤل ﺍﻵﺘﻴﺔ‪:‬‬

‫)‪ (١‬ﻨﻭﻉ ﺍﻟﻌﻤل‪.‬‬

‫)‪ (٢‬ﻓﺘﺭﺓ ﺍﻟﻌﻤل‪.‬‬

‫)‪ (٣‬ﺠﻭﺩﺓ ﺍﻹﻨﺘﺎﺝ ﺍﻟﻤﻁﻠﻭﺏ‪.‬‬

‫)‪ (٤‬ﻤﺘﻭﺴﻁ ﻋﻤﺭ ﻤﺠﻤﻭﻋﺔ ﺍﻟﻌﻤل ﺃﻭ ﺍﻷﺸﺨﺎﺹ ﺍﻟﺫﻴﻥ ﻴﺘﻡ ﺘﺼﻤﻴﻡ ﻤﺴـﺘﻭﻯ‬
‫ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ ﻟﻬﻡ‪.‬‬

‫‪ -‬ﻴﻭﻀﺢ ﺍﻟﺠﺩﻭل )‪ (١-٢‬ﻤﺴﺘﻭﻯ ﺸﺩﺓ ﺍﻹﻀـﺎﺀﺓ ﺍﻟﻤﻁﻠـﻭﺏ ﻓـﻰ ﺍﻟﻔﺭﺍﻏـﺎﺕ‬


‫ﺍﻟﻤﺨﺘﻠﻔﺔ ﺩﺍﺨل ﺍﻟﻨﻭﻋﻴﺎﺕ ﺍﻟﻤﺨﺘﻠﻔﺔ ﻤﻥ ﺍﻟﻤﺒﺎﻨﻰ )ﺴﻜﻨﻴﺔ‪ ،‬ﺘﺠﺎﺭﻴﺔ‪ ،‬ﻤﺴﺘﺸـﻔﻴﺎﺕ‪،‬‬
‫‪٠٠‬ﺍﻟﺦ(‪.‬‬

‫‪ -‬ﻭﻴﺒﻴﻥ ﺸﻜل )‪ (١-٢‬ﺭﺴﻤﺎ ﺘﺨﻁﻴﻁﻴﺎ ﻟﻠﺨﻁﻭﺍﺕ ﺍﻟﻤﺘﺒﻌﺔ ﻓﻰ ﺘﺼـﻤﻴﻡ ﺃﻋﻤـﺎل‬


‫ﺍﻹﻨﺎﺭﺓ ﺍﻟﺩﺍﺨﻠﻴﺔ‪.‬‬

‫‪٢‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺘﺼﻤﻴﻡ ﺃﻋﻤﺎل ﺍﻹﻨﺎﺭﺓ‬

‫ﻭﻅﻴﻔﺔ ﺍﺴﺘﺨﺩﺍﻡ ﺍﻟﻤﻜﺎﻥ‬ ‫ﻁﺒﻴﻌﺔ ﺍﻟﻤﻭﻗﻊ ﻭﺃﺒﻌﺎﺩ ﺍﻟﻘﺎﻋﺔ‬


‫ﻗﺎﻋﺔ ﻤﺤﺎﻀﺭﺍﺕ‪ ،‬ﻤﻌﺎﻤل‪ ،‬ﺍﻟﺦ‪.‬‬ ‫ﻭﻤﻭﺍﺩ ﺍﻟﺘﺸﻁﻴﺏ‬

‫ﺃﻨﻅﻤﺔ ﺍﻹﻨﺎﺭﺓ‬
‫ﺍﻟﺤﺩ ﺍﻷﺩﻨﻰ ﺍﻟﻤﻁﻠﻭﺏ ﻟﺸﺩﺓ‬ ‫)ﻤﺒﺎﺸﺭﺓ‪ ،‬ﻏﻴﺭ ﻤﺒﺎﺸﺭﺓ‪ ،‬ﺍﻟﺦ‪(.‬‬

‫ﺍﻹﻨﺎﺭﺓ‬

‫ﺍﺨﺘﻴﺎﺭ ﻭﺤﺩﺓ ﺍﻹﻨﺎﺭﺓ‬

‫ﺘﺤﺩﻴﺩ ﻤﻌﺎﻤل ﺍﻻﺴﺘﻔﺎﺩﺓ‬

‫ﺨﺼﺎﺌﺹ ﻭﺤﺩﺓ ﺍﻹﻨﺎﺭﺓ‬ ‫ﺘﺤﺩﻴﺩ ﻤﻌﺎﻤل ﺍﻟﺼﻴﺎﻨﺔ‬


‫)ﺍﻟﻜﻔﺎﺀﺓ‪ ،‬ﻤﻘﺩﺍﺭ ﺍﻟﻔﻴﺽ ﺍﻟﻀﻭﺌﻰ(‬

‫ﺍﻟﺤﺩ ﺍﻷﺩﻨﻰ ﻟﻌﺩﺩ ﻭﺤﺩﺍﺕ ﺍﻹﻨﺎﺭﺓ‬

‫ﻨﺴﺒﺔ‬
‫)ﺍﻟﻤﺴﺎﻓﺔ ﺍﻟﺒﻴﻨﻴﺔ ‪ /‬ﺍﻻﺭﺘﻔﺎﻉ(‬

‫ﺘﻭﺯﻴﻊ ﻭﺤﺩﺍﺕ ﺍﻹﻨﺎﺭﺓ‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(١-٢‬ﺭﺴﻡ ﺘﺨﻁﻴﻁﻰ ﻟﺨﻁﻭﺍﺕ ﺘﺼﻤﻴﻡ ﺃﻋﻤﺎل ﺍﻹﻨﺎﺭﺓ ﺍﻟﺩﺍﺨﻠﻴﺔ‬

‫‪٢‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫)ﺏ( ﺨﻁﻭﺍﺕ ﺘﺼﻤﻴﻡ ﺍﻹﻨﺎﺭﺓ ﺍﻟﺩﺍﺨﻠﻴﺔ‬

‫‪ -‬ﻤﻊ ﻤﺭﺍﻋﺎﺓ ﻁﺒﻴﻌﺔ ﺍﺴﺘﺨﺩﺍﻡ ﺍﻟﻤﻜﺎﻥ‪ ،‬ﻴﺘﻡ ﺘﺤﺩﻴﺩ ﻤﺎ ﻴﻠﻰ‪:‬‬

‫)‪ (١‬ﻤﺴﺘﻭﻯ ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ ﺍﻟﻤﻁﻠﻭﺏ ﻭﺫﻟﻙ ﺒﺎﻻﺴﺘﻌﺎﻨﺔ ﺒﺎﻟﺠﺩﻭل )‪.(١-٢‬‬

‫)‪ (٢‬ﺃﻨﻅﻤﺔ ﺘﻭﺯﻴﻊ ﺍﻹﻀﺎﺀﺓ ﺍﻟﺘﻰ ﻴﺘﻡ ﺍﺴﺘﺨﺩﺍﻤﻬﺎ‪.‬‬

‫)‪ (٣‬ﻨﻭﻉ ﺃﻭ ﺃﻨﻭﺍﻉ ﺍﻟﻤﺼﺎﺒﻴﺢ ﻭﻭﺤﺩﺍﺕ ﺍﻹﻨﺎﺭﺓ ﺍﻟﺘﻰ ﺴﻴﺘﻡ ﺍﺴﺘﺨﺩﺍﻤﻬﺎ‪.‬‬

‫‪ -‬ﻴﺘﻡ ﺘﺤﺩﻴﺩ ﻤﻌﺎﻤل ﺍﻟﺤﺠﺭﺓ )‪ (Ri‬ﻁﺒﻘﺎﹰ ﻷﺒﻌﺎﺩ ﺍﻟﻤﻜﺎﻥ‪ :‬ﺍﻟﻁـﻭل )‪ (L‬ﻭﺍﻟﻌـﺭﺽ‬


‫)‪ (W‬ﻭﻤﻨﺴﻭﺏ ﺘﻌﻠﻴﻕ ﻭﺤﺩﺓ ﺍﻹﻨﺎﺭﺓ ﻭﻜﺫﻟﻙ ﻁﺒﻘﺎ ﻟﻸﻨﻅﻤـﺔ ﺍﻟﻤﺴـﺘﺨﺩﻤﺔ ﻓـﻰ‬
‫ﺘﻭﺯﻴﻊ ﺍﻹﻨﺎﺭﺓ ﻤﻥ ﺍﻟﺠﺩﻭل )‪.(٢-٢‬‬

‫‪ -‬ﻴﺘـﻡ ﺘﺤﺩﻴــﺩ ﻤﻌﺎﻤـل ﺍﻻﺴﺘﻔــﺎﺩﺓ )‪ (u‬ﻟﻭﺤــﺩﺓ ﺍﻹﻨـــﺎﺭﺓ ﻁﺒﻘــﺎﹰ‬


‫ﻟﻨﻭﻋﻴﺔ ﺍﻟﻭﺤﺩﺓ ﻭﻤﻌﺎﻤل ﺍﻟﺤﺠﺭﺓ ﻭﻤﻌﺎﻤل ﺍﻨﻌﻜـﺎﺱ ﺍﻟﻀـﻭﺀ ﻋﻠـﻰ ﺍﻟﺴـﻘﻑ‬
‫ﻭﺍﻟﺤﻭﺍﺌﻁ‪ ،‬ﻭﺫﻟﻙ ﻤﻥ ﺍﻟﺠﺩﻭل )‪.(٣-٢‬‬

‫‪ -‬ﻴﺘﻡ ﺘﺤﺩﻴﺩ ﻤﻌﺎﻤل ﺍﻟﺼﻴﺎﻨﺔ )‪ (m‬ﻟﻭﺤﺩﺓ ﺍﻹﻨﺎﺭﺓ ﻁﺒﻘﺎ ﻟﻁﺒﻴﻌﺔ ﺍﻟﻤﻭﻗﻊ‪ .‬ﻭﺘﺘﺭﺍﻭﺡ ﻗﻴﻤﺔ‬
‫ﻤﻌﺎﻤل ﺍﻟﺼﻴﺎﻨﺔ ﻤﻥ ‪ ٠.٧٦‬ﺇﻟﻰ ‪ ١‬ﻓﻰ ﺤﺎﻟﺔ ﺍﻟﺼﻴﺎﻨﺔ ﺍﻟﺩﻭﺭﻴﺔ ﺍﻟﻤﻨﺘﻅﻤـﺔ‪ ،‬ﻓـﻰ‬
‫ﺤﻴﻥ ﺘﺒﻠﻎ ﻗﻴﻤﺘﻪ ﻤﻥ ‪ ٠.٦٦‬ﺇﻟﻰ ‪ ٠.٧٥‬ﻓﻰ ﺤﺎﻟﺔ ﺍﻟﺼـﻴﺎﻨﺔ ﻏﻴـﺭ ﺍﻟﻤﻨﺘﻅﻤـﺔ‬
‫ﻟﻭﺤﺩﺍﺕ ﺍﻹﻨﺎﺭﺓ‪.‬‬

‫‪ -‬ﻴﺘﻡ ﺤﺴﺎﺏ ﻋﺩﺩ ﻭﺤﺩﺍﺕ ﺍﻹﻨﺎﺭﺓ )‪ ( N‬ﺍﻟﻤﻁﻠﻭﺒﺔ ﻤﻥ ﺍﻟﻤﻌﺎﺩﻟﺔ )‪:(١-٢‬‬


‫‪E x A‬‬
‫= ‪N‬‬ ‫)‪(2-1‬‬
‫‪u x m x η lamp x P‬‬

‫ﺤﻴﺙ ‪:‬‬

‫‪ :‬ﻤﺘﻭﺴﻁ ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ ﺍﻟﻤﻁﻠﻭﺒﺔ )ﻟﻭﻜﺱ(‪.‬‬ ‫‪E‬‬

‫‪ :‬ﻤﺴﺎﺤﺔ ﺍﻟﺴﻁﺢ ﺍﻟﻤﺭﺍﺩ ﺇﻀﺎﺀﺘﻪ )ﻤﺘﺭ‪.(٢‬‬ ‫‪A‬‬

‫‪ :‬ﻤﻌﺎﻤل ﺍﻻﺴﺘﻔﺎﺩﺓ‪.‬‬ ‫‪u‬‬

‫‪ :‬ﻤﻌﺎﻤل ﺍﻟﺼﻴﺎﻨﺔ‪.‬‬ ‫‪m‬‬

‫‪ : η lamp‬ﻜﻔﺎﺀﺓ ﺍﻟﻤﺼﺒﺎﺡ )ﻟﻭﻤﻥ‪/‬ﻭﺍﺕ(‪.‬‬

‫‪ :‬ﻗﺩﺭﺓ ﺍﻟﻤﺼﺒﺎﺡ )ﻭﺍﺕ(‪،‬‬ ‫‪P‬‬

‫‪٢‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫‪ :‬ﻋﺩﺩ ﺍﻟﻤﺼﺎﺒﻴﺢ ﻓﻰ ﻜل ﻭﺤﺩﺓ ﺇﻀﺎﺀﺓ‪.‬‬ ‫‪N‬‬

‫‪ -‬ﻋﻨﺩﻤﺎ ﺘﻜﻭﻥ ﻗﻴﻤﺔ )‪ (N‬ﺍﻟﻤﺤﺴﻭﺒﺔ ﻤﻥ ﺍﻟﻌﻼﻗﺔ ﺍﻟﺴﺎﺒﻘﺔ ﻋﺩﺩﺍﹰ ﻜﺴﺭﻴﺎﹰ‪ ،‬ﻴﺘﻡ ﺘﻘﺭﻴﺏ‬
‫ﺍﻟﻘﻴﻤﺔ ﺍﻟﻤﺤﺴﻭﺒﺔ ﺇﻟﻰ ﺍﻟﻌﺩﺩ ﺍﻟﺼﺤﻴﺢ ﺍﻟﺘﺎﻟﻰ ﻤﺒﺎﺸﺭﺓ‪) ،‬ﻤﺜـﺎل‪ ١٠.٣ :‬ﺘﺼـﺒﺢ‬
‫‪١١‬ﻭﻫﻜﺫﺍ(‪.‬‬

‫‪ -‬ﻴﻤﻜﻥ ﺯﻴﺎﺩﺓ ﻋﺩﺩ ﻭﺤﺩﺍﺕ ﺍﻹﻨﺎﺭﺓ ﺇﻟﻰ ﺍﻟﺭﻗﻡ ﺍﻟﺫﻯ ﻴﺤﻘﻕ ﻋﺩﺓ ﺤﻠﻭل ﻟﺘﻭﺯﻴﻊ ﻫﺫﻩ‬
‫ﺍﻟﻭﺤــﺩﺍﺕ‪) ،‬ﻓﻤﺜﻼ ‪ ١١‬ﻴﻤﻜــﻥ ﺯﻴﺎﺩﺘﻬــﺎ ﺇﻟﻰ ‪ ١٢‬ﻭﺍﻟﺘـــﻰ ﺘﻌﻁـﻰ‬
‫ﺘﻭﺯﻴﻊ ‪ ٢‬ﺼــﻑ × ‪٦‬ﻭﺤﺩﺍﺕ ﺇﻀﺎﺀﺓ ﺃﻭ ‪ ٣‬ﺼﻔﻭﻑ × ‪ ٤‬ﻭﺤﺩﺍﺕ(‪.‬‬

‫‪ -‬ﻴﺘﻡ ﺘﺤﺩﻴﺩ ﻨﺴﺒﺔ ﺍﻟﻤﺴﺎﻓﺔ ﺍﻟﺒﻴﻨﻴﺔ ﻟﻭﺤﺩﺍﺕ ﺍﻹﻨﺎﺭﺓ ‪/‬ﺍﻻﺭﺘﻔﺎﻉ )‪ (d/h‬ﺃﻭ ﺘﺤﺩﺩ ﻤـﻥ‬
‫ﺍﻟﺠﺩﻭل )‪.(٤-٢‬‬

‫‪ -‬ﻴﺘﻡ ﺘﺤﺩﻴﺩ ﺘﻭﺯﻴﻊ ﻭﺤﺩﺍﺕ ﺍﻹﻨﺎﺭﺓ ﻓﻰ ﺍﻟﻤﺴﺎﺤﺔ ﺍﻟﻤﻀﺎﺀﺓ )ﻋﺩﺩ ﺍﻟﻭﺤـﺩﺍﺕ ﻓـﻰ‬
‫ﺍﻟﺼﻑ‪ ،‬ﻋﺩﺩ ﺍﻟﺼﻔﻭﻑ(‪.‬‬

‫‪ -‬ﻴﺘﻡ ﺤﺴﺎﺏ ﺘﻭﺯﻴﻊ ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ ﺍﻟﺭﺃﺴﻴﺔ ﻓﻰ ﺍﻟﻤﻜﺎﻥ ﻋﻨﺩ ﻨﻘـﺎﻁ ﻤﻌﻴﻨـﺔ ﻓـﻰ‬
‫ﻤﺴﺘﻭﻯ ﺍﻟﺸﻐل ﺃﻭ ﺨﺎﺭﺠﻪ ﻤﻥ ﺍﻟﻌﻼﻗﺔ‪:‬‬
‫‪N‬‬ ‫‪I i cosθ i‬‬
‫=‪E‬‬ ‫∑‬ ‫)‪(2-2‬‬
‫‪i =1‬‬ ‫‪(ri ) 2‬‬

‫ﺤﻴﺙ ‪:‬‬
‫‪ : N‬ﻋﺩﺩ ﻭﺤﺩﺍﺕ ﺍﻹﻀﺎﺀﺓ‬
‫‪ : Ii‬ﻜﺜﺎﻓﺔ ﺍﻹﻀﺎﺀﺓ ﻟﻠﻭﺤﺩﺓ ‪ ، i‬ﻜﺎﻨﺩﻻ ﺃﻭ ﺸﻤﻌﺔ‬
‫‪ : θ i‬ﺍﻟﺯﻭﺍﻴﺔ ﺒﻴﻥ ﺍﻟﺸﻌﺎﻉ ﺍﻟﻭﺍﺼل ﻤﻥ ﻭﺤﺩﺓ ﺍﻹﻨﺎﺭﺓ ﺇﻟﻰ ﺍﻟﻨﻘﻁﺔ ﺍﻟﺘـﻰ ﻴـﺘﻡ‬
‫ﺤﺴﺎﺏ ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ ﻋﻨﺩﻫﺎ ﻭﻤﺤﻭﺭ ﻭﺤﺩﺓ ﺍﻹﻀﺎﺀﺓ ‪ ، i‬ﺃﻨﻅـﺭ ﺸـﻜل‬
‫)‪.(٢-٢‬‬
‫‪ : ri‬ﺍﻟﻤﺴﺎﻓﺔ ﺒﻴﻥ ﻭﺤﺩﺓ ﺍﻹﻀﺎﺀﺓ ﻭﺍﻟﻨﻘﻁﺔ ﺍﻟﺘﻰ ﻴـﺘﻡ ﻋﻨـﺩﻫﺎ ﺤﺴـﺎﺏ ﺸـﺩﺓ‬
‫ﺍﻹﻀﺎﺀﺓ‪.‬‬
‫‪ -‬ﺇﺫﺍ ﻜﺎﻥ ﻫﻨﺎﻙ ﺘﻔﺎﻭﺕ ﻜﺒﻴﺭ ﻓﻰ ﺘﻭﺯﻴﻊ ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ‪ ،‬ﻓﺈﻨﻪ ﻴﻤﻜﻥ ﺇﻋﺎﺩﺓ ﺘﻭﺯﻴـﻊ‬
‫ﺃﻭ ﺯﻴﺎﺩﺓ ﻭﺤﺩﺍﺕ ﺍﻹﻀﺎﺀﺓ ﻓﻰ ﺃﻤﺎﻜﻥ ﻤﺤﺩﺩﺓ ﺤﺘﻰ ﻴﺘﺤﻘﻕ ﺍﻟﺘﻭﺯﻴﻊ ﺍﻟﻤﻁﻠﻭﺏ‪.‬‬

‫‪٢‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫‪L1‬‬ ‫‪L2‬‬ ‫‪L3‬‬ ‫ﻭﺤﺩﺍﺕ ﺍﻹﻨﺎﺭﺓ ‪L4‬‬


‫) ‪( I1‬‬ ‫) ‪( I2‬‬ ‫) ‪( I3‬‬ ‫) ‪( I4‬‬

‫‪θ‬‬ ‫‪θ‬‬ ‫‪θ‬‬

‫‪r1‬‬ ‫‪r2‬‬ ‫‪r3‬‬ ‫‪r4‬‬

‫ﺳﻄﺢ اﻟﺸﻐﻞ‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(٢-٢‬ﺤﺴﺎﺏ ﺘﻭﺯﻴﻊ ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ‬

‫‪٢‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪ :(١-٢‬ﻤﺴﺘﻭﻯ ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ ﻓﻰ ﺍﻟﻔﺭﺍﻏﺎﺕ ﺍﻟﻤﺨﺘﻠﻔﺔ ﻟﻠﻤﺒﺎﻨﻰ‬

‫ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ )ﻟﻭﻜﺱ(‬ ‫ﺍﻟﻤﻜﺎﻥ‬


‫‪١٢٠‬‬ ‫ﺴــﻼﻟﻡ‬
‫‪٦٠‬‬ ‫ﻤﻤﺭﺍﺕ‬
‫ﻏﺭﻑ ﻤﻌﻴﺸﺔ ‪:‬‬
‫‪١٥٠‬‬ ‫ﻋـﺎﻡ‬
‫‪٣٠٠‬‬ ‫ﻗﺭﺍﺀﺓ‬
‫‪١٢٠‬‬ ‫ﻏﺭﻓﺔ ﻁﻌﺎﻡ‬
‫‪١٢٠‬‬ ‫ﻏﺭﻓﺔ ﻨﻭﻡ‬ ‫ﺍﻟﻤﺒﺎﻨﻰ ﺍﻟﺴﻜﻨﻴﺔ‬
‫ﻤﻁﺒـﺦ ‪:‬‬
‫‪١٢٠‬‬ ‫ﻋﺎﻡ‬
‫‪٥٠٠‬‬ ‫ﻓﻭﻕ ﺃﺴﻁﺢ ﺍﻟﻌﻤل‬
‫‪٣٠٠‬‬ ‫ﺤﻤﺎﻡ‪:‬‬
‫ﺤﺠﺭﺓ ﻤﻜﺘﺏ ‪:‬‬
‫‪٣٠٠‬‬ ‫‪ -‬ﻋﺎﻡ‬
‫‪٥٠٠‬‬ ‫‪ -‬ﻓﻭﻕ ﺴﻁﺢ ﺍﻟﻤﻜﺘﺏ‬
‫‪١٢٠‬‬ ‫ﺇﺴﺘﻘﺒﺎل‪ ،‬ﻗﺎﻋﺎﺕ ﺍﺴﺘﺭﺍﺤﺔ‬
‫‪٣٠٠‬‬ ‫ﺼﺎﻻﺕ ﺇﺠﺘﻤﺎﻋﺎﺕ‬
‫ﺍﻟﻤﻜﺎﺘﺏ‬
‫‪٣٠٠‬‬ ‫ﺤﺠﺭﺓ ﺘﺼﻭﻴﺭ ﻭﻁﺒﺎﻋﺔ‬
‫‪٥٠٠‬‬ ‫ﺤﺠﺭﺓ ﺍﻟﺭﺴﻡ ﺍﻟﺘﺨﻁﻴﻁﻰ‬
‫‪١٠٠٠‬‬ ‫ﺤﺠﺭﺓ ﺍﻟﺭﺴﻡ ﺍﻟﻤﻌﻤﺎﺭﻯ ﺍﻟﻬﻨﺩﺴﻰ‬
‫ﺃﺭﻓﻑ ﺍﻟﻜﺘﺏ ‪:‬‬
‫‪٣٠٠‬‬ ‫ﺍﻟﻤﺴﺘﺨﺩﻤﺔ‬
‫‪٦٠‬‬ ‫ﻏﻴﺭ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ‬
‫ﺃﻋﻤﺎل ﺍﻟﻔﻬﺭﺴﺔ ‪:‬‬
‫‪١٠٠٠‬‬ ‫ﺤﺠﺭﺍﺕ ﺍﻟﺨﺭﺍﺌﻁ‬
‫ﺍﻟﻤﻜﺘﺒﺎﺕ‬
‫‪٣٠٠‬‬ ‫ﺤﺠﺭﺍﺕ ﺍﻟﺘﺼﻭﻴﺭ‬
‫ﺍﻟﻘﺭﺍﺀﺓ ‪:‬‬
‫‪٣٠٠‬‬ ‫ﻗﺭﺍﺀﺓ ﻤﻜﺘﺒﻴﺔ‬
‫‪٣٠٠‬‬ ‫ﺸﺎﺸﺎﺕ ﺍﻟﻌﺭﺽ ﺍﻟﻤﺭﺌﻰ‬
‫‪٦٠‬‬ ‫ﻗﺭﺍﺀﺓ ﺍﻟﻤﻴﻜﺭﻭﻓﻴﺵ‬

‫‪٢‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺘﺎﺒﻊ ﺠﺩﻭل ﺭﻗﻡ )‪ :(١-٢‬ﻤﺴﺘﻭﻯ ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ ﻓﻰ ﺍﻟﻔﺭﺍﻏﺎﺕ ﺍﻟﻤﺨﺘﻠﻔﺔ ﻟﻠﻤﺒﺎﻨﻰ‬

‫ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ )ﻟﻭﻜﺱ(‬ ‫ﺍﻟﻤﻜﺎﻥ‬


‫‪١٢٠‬‬ ‫ﺍﻟﺭﺩﻫﺎﺕ‪ ،‬ﺍﻟﺴﻼﻟﻡ‪ ،‬ﺍﻟﻤﺼﺎﻋﺩ‬
‫‪٣٠٠‬‬ ‫ﺤﺠﺭﺍﺕ ﺍﻟﻌﻼﺝ ﺍﻟﻁﺒﻴﻌﻰ‬
‫ﻋﻴﺎﺩﺍﺕ ﺨﺎﺼﺔ ‪:‬‬
‫‪١٢٠‬‬ ‫ﻏﺭﻓﺔ ﺍﻨﺘﻅﺎﺭ‬
‫‪٥٠٠‬‬ ‫ﻏﺭﻓﺔ ﻓﺤﺹ‬
‫ﺍﻷﺴﻨﺎﻥ ‪:‬‬
‫‪٣٠٠‬‬ ‫ﻋﺎﻡ‬
‫‪٥٠٠‬‬ ‫ﺼﻴﻨﻴﺔ ﺍﻷﺩﻭﺍﺕ‬
‫‪٣٠٠٠‬‬ ‫ﻓﺠﻭﺓ ﺍﻟﻔﻡ‬
‫ﻤﻌﻤل ﺍﻷﺴﻨﺎﻥ ‪:‬‬
‫‪٣٠٠‬‬ ‫ﻋﺎﻡ‬
‫‪٥٠٠‬‬ ‫ﻤﻨﻀﺩﺓ ﺍﻟﻌﻤل‬
‫‪١٠٠٠‬‬ ‫ﺇﻀﺎﺀﺓ ﻗﻁﻌﺔ ﺍﻟﺸﻐل‬
‫ﺍﻟﻤﻌﺎﻤل ‪:‬‬
‫‪٥٠٠‬‬ ‫ﺃﺨﺫ ﺍﻟﻌﻴﻨﺎﺕ‬
‫‪١٠٠٠‬‬ ‫ﻤﻌﻤل ﺍﻷﻨﺴﺠﺔ‬
‫‪٣٠٠‬‬ ‫ﺤﺠﺭﺓ ﺍﻟﻔﺤﺹ ﺍﻟﻤﺠﻬﺭﻯ‬ ‫ﺍﻟﻤﺴﺘﺸﻔﻴﺎﺕ‬
‫‪٥٠٠٠‬‬ ‫ﺍﻟﺘﺤﺎﻟﻴل ﺍﻟﻜﻴﻤﻴﺎﺌﻴﺔ‬
‫‪١٠٠٠‬‬ ‫ﺍﻟﺘﺤﺎﻟﻴل ﺍﻟﺒﻜﺘﺭﻟﻴﻭﺠﻴﺔ‬
‫‪٥٠٠‬‬ ‫ﺘﺤﻠﻴل ﺍﻟﺩﻡ‬
‫ﻏﺭﻓﺔ ﺍﻟﻌﻤﻠﻴﺎﺕ ‪:‬‬
‫‪٥٠٠‬‬ ‫ﺍﻟﺘﺤﻀﻴﺭ ﻭﺍﻟﺘﺨﺩﻴﺭ‬
‫‪١٠٠٠‬‬ ‫ﻋﺎﻡ ﺒﻐﺭﻑ ﺍﻟﻌﻤﻠﻴﺎﺕ‬
‫‪- ٢٥٠٠٠‬‬ ‫ﻤﺎﺌﺩﺓ ﺍﻟﻌﻤﻠﻴﺎﺕ‬
‫‪١٠٠٠٠٠‬‬
‫ﻏﺭﻑ ﺍﻟﻤﺭﻀﻰ ‪:‬‬
‫‪٦٠‬‬ ‫ﻋﺎﻡ‬
‫‪٣٠٠‬‬ ‫ﻗﺭﺍﺀﺓ‬
‫ﺍﻷﺸﻌﺔ ‪:‬‬
‫ﻗﺴﻡ ﺍﻟﺘﺸﺨﻴﺹ‬
‫‪٣٠‬‬ ‫ﺤﺠﺭﺓ ﺍﻷﺸﻌﺔ‬
‫‪١٠٠٠‬‬ ‫ﻓﺭﺯ ﺍﻷﻓﻼﻡ‬
‫‪٥٠٠‬‬ ‫ﺘﺤﻀﻴﺭ ﺍﻟﺒﺎﺭﻴﻭﻡ‬

‫‪٢‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺘﺎﺒﻊ ﺠﺩﻭل ﺭﻗﻡ )‪ :(١-٢‬ﻤﺴﺘﻭﻯ ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ ﻓﻰ ﺍﻟﻔﺭﺍﻏﺎﺕ ﺍﻟﻤﺨﺘﻠﻔﺔ ﻟﻠﻤﺒﺎﻨﻰ‬

‫ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ)ﻟﻭﻜﺱ(‬ ‫ﺍﻟﻤﻜﺎﻥ‬


‫ﻗﺴﻡ ﺍﻟﻌﻼﺝ ﺍﻹﺸﻌﺎﻋﻰ‬
‫‪٥٠٠‬‬ ‫ﺘﺤﻀﻴﺭ ﺍﻟﻨﻅﺎﺌﺭ‬
‫ﺘﺎﺒﻊ ﺍﻟﻤﺴﺘﺸﻔﻴﺎﺕ‬
‫‪٦٠‬‬ ‫ﺤﺠﺭﺓ ﺍﻷﺸﻌﺔ ﺍﻟﻤﻘﻁﻌﻴﺔ‬
‫‪٥٠٠‬‬ ‫ﺤﺠﺭﺓ ﺼﻴﺎﻨﺔ ﺍﻷﺠﻬﺯﺓ‬
‫‪١٢٠‬‬ ‫ﺍﻟﻤﻤﺭﺍﺕ ﻭﺍﻟﺴﻼﻟﻡ ﻭﺍﻟﻤﺼﺎﻋﺩ‬
‫‪٥٠٠‬‬ ‫ﺍﻻﺴﺘﻘﺒﺎل‬
‫ﺤﺠﺭﺍﺕ ﺍﻟﻨﻭﻡ ‪:‬‬
‫‪١٥٠‬‬ ‫ﻋﺎﻡ‬ ‫ﺍﻟﻔﻨﺎﺩﻕ‬
‫‪٣٠٠‬‬ ‫ﻁﺎﻭﻟﺔ ﺍﻟﻜﺘﺎﺒﺔ ‪ ،‬ﺃﻤﺎﻜﻥ ﺍﻟﺘﺯﻴﻥ‬
‫‪٣٠٠‬‬ ‫ﺤﻤﺎﻤﺎﺕ‬
‫‪١٢٠‬‬ ‫ﺍﻟﻤﻁﻌﻡ‬
‫‪٣٠٠‬‬ ‫ﺍﻟﻔﺼﻭل‬
‫‪٥٠٠‬‬ ‫ﺍﻟﺴﺒﻭﺭﺓ‬
‫‪٥٠٠‬‬ ‫ﺍﻟﻤﻌﺎﻤل‬
‫‪٥٠٠‬‬ ‫ﺤﺠﺭﺍﺕ ﺍﻟﺭﺴﻡ‬ ‫ﺍﻟﻤﺩﺍﺭﺱ‬
‫‪٣٠٠‬‬ ‫ﻗﺎﻋﺎﺕ ﺍﻹﺠﺘﻤﺎﻋﺎﺕ‬
‫‪٥٠٠‬‬ ‫ﺍﻟﻭﺭﺵ‬
‫‪١٢٠‬‬ ‫ﺼﺎﻟﺔ ﺍﻟﻁﻌﺎﻡ‬
‫ﺩﺍﺨل ﺍﻟﻤﻜﺎﻥ ‪:‬‬
‫‪٣٠٠‬‬ ‫ﺇﻀﺎﺀﺓ ﻋﺎﻤﺔ‬
‫‪٧٥٠‬‬ ‫ﺇﻀﺎﺀﺓ ﺃﻤﺎﻜﻥ ﻴﺭﺍﺩ ﻟﻔﺕ ﺍﻟﻨﻅﺭ ﺇﻟﻴﻬﺎ‬
‫ﺍﻟﻤﺤﻼﺕ ﻭﺍﻟﻤﺘﺎﺠﺭ‬
‫ﻓﺎﺘﺭﻴﻨﺎﺕ ﺍﻟﻌﺭﺽ ‪:‬‬
‫‪٥٠٠‬‬ ‫ﺇﻀﺎﺀﺓ ﻋﺎﻤﺔ‬
‫‪٣٠٠٠‬‬ ‫ﺇﻀﺎﺀﺓ ﺃﺠﺯﺍﺀ ﻫﺎﻤﺔ ﻴﺭﺍﺩ ﻟﻔﺕ ﺍﻟﻨﻅﺭ ﺍﻟﻴﻬﺎ‬
‫ﺍﻟﻨﺠﺎﺭﺓ ‪:‬‬ ‫ﻭﺭﺵ‬
‫‪٢٠٠‬‬ ‫ﺘﻘﺴﻴﻡ ﻭﺘﻔﺼﻴل ﺍﻟﺨﺸﺏ‬ ‫ﻁﺎﻭﻟﺔ‬
‫‪٢٠٠‬‬ ‫ﺘﺠﻤﻴﻊ‬ ‫ﻁﺎﻭﻟﺔ‬
‫‪٥٠٠‬‬ ‫ﺘﺸﻁﻴﺏ‬ ‫ﻁﺎﻭﻟﺔ‬
‫ﺍﻟﻭﺭﺵ‬
‫ﻭﺭﺵ ﺍﻟﻠﺤﺎﻡ ‪:‬‬
‫‪٥٠٠‬‬ ‫ﻟﺤﺎﻡ ﻤﺘﻭﺴﻁ ﺍﻟﺩﻗﺔ‬
‫‪١٠٠٠‬‬ ‫ﻟﺤﺎﻡ ﻋﺎﻟﻰ ﺍﻟﺩﻗﺔ‬
‫‪٣٠٠٠‬‬ ‫ﻟﺤﺎﻡ ﺒﺎﻟﻎ ﺍﻟﺩﻗﺔ‬

‫‪٢‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺘﺎﺒﻊ ﺠﺩﻭل ﺭﻗﻡ )‪ :(١-٢‬ﻤﺴﺘﻭﻯ ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ ﻓﻰ ﺍﻟﻔﺭﺍﻏﺎﺕ ﺍﻟﻤﺨﺘﻠﻔﺔ ﻟﻠﻤﺒﺎﻨﻰ‬

‫ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ)ﻟﻭﻜﺱ(‬ ‫ﺍﻟﻤﻜﺎﻥ‬


‫ﻭﺭﺵ ﺍﻟﺴﺒﺎﻜﺔ ‪:‬‬
‫‪٣٠٠‬‬ ‫ﺍﻟﺘﻨﻅﻴﻑ‬
‫ﻗﻭﺍﻟﺏ ﺍﻟﻤﺴﺒﻭﻜﺎﺕ ‪:‬‬
‫ﺘﺎﺒﻊ ﺍﻟﻭﺭﺵ‬
‫‪٥٠٠‬‬ ‫ﻜﺒﻴﺭﺓ‬
‫‪١٠٠٠‬‬ ‫ﻤﺘﻭﺴﻁﺔ‬
‫‪٣٠٠‬‬ ‫ﻓﻙ ﺍﻟﻘﻭﺍﻟﺏ‬
‫ﺍﻟﻐﺯل ‪:‬‬
‫‪٣٠٠‬‬ ‫ﺘﻤﺸﻴﻁ‪ ،‬ﺴﺤﺏ‪ ،‬ﻟﻑ ﺍﻟﺒﺎﻻﺕ‬
‫‪٥٠٠‬‬ ‫ﻓﺭﺯ ﻭﺘﺼﻨﻴﻑ ﺍﻟﺘﻴﻠﺔ‬
‫‪٥٠٠‬‬ ‫ﺍﻟﻐﺯل ﻭﺍﻟﻔﺘل‬
‫ﻨﺴﺞ ﺍﻟﻘﻤﺎﺵ‬
‫‪١٠٠٠‬‬ ‫ﻨﺴﺞ ‪ ،‬ﺤﻴﺎﻜﺔ‬
‫ﻤﺼﺎﻨﻊ ﺍﻟﻨﺴﻴﺞ‬
‫‪١٥٠٠‬‬ ‫ﻓﺤﺹ‬
‫ﺘﺸﻁﻴﺏ ﺍﻟﻘﻤﺎﺵ ‪:‬‬
‫‪٣٠٠‬‬ ‫ﺘﻨﻅﻴﻑ‪ ،‬ﺘﺒﻴﻴﺽ‬
‫‪٥٠٠‬‬ ‫ﺼﺒﺎﻏﺔ‬
‫‪٥٠٠‬‬ ‫ﺼﻘل ﻭﻤﻌﺎﻟﺠﺔ ﺘﺸﻁﻴﺏ‬
‫‪١٥٠٠‬‬ ‫ﻓﺤﺹ‬
‫‪٥٠٠‬‬ ‫ﻟﻭﺤﺔ ﻤﻔﺎﺘﻴﺢ ﺍﻟﺤﺭﻭﻑ – ﺁﻻﺕ ﺍﻟﻁﺒﺎﻋﺔ‬
‫‪١٠٠٠‬‬ ‫ﻤﺭﺍﺠﻌﺔ ﻋﻴﻨﺎﺕ ﺍﻟﺘﺠﻤﻴﻊ‬
‫‪١٠٠٠‬‬ ‫ﺃﻋﻤﺎل ﺨﺎﺼﺔ ﺒﺘﺤﺩﻴﺩ ﻭﻁﺒﺎﻋﺔ ﺍﻷﻟﻭﺍﻥ‬
‫ﺍﻟﺘﻐﻠﻴﻑ ‪:‬‬ ‫ﺍﻟﻁﺒﺎﻋﺔ‬
‫‪٣٠٠‬‬ ‫ﺍﻟﺜﻨﻰ ﻭﺍﻟﺘﺠﻤﻴﻊ‬
‫‪٥٠٠‬‬ ‫ﺍﻟﻘﻁﻊ‬
‫‪١٠٠٠‬‬ ‫ﺍﻟﻔﺤﺹ‬
‫‪٥٠٠‬‬ ‫ﺘﺠﻤﻴﻊ ﺍﻟﻬﻴﺎﻜل‬
‫‪١٠٠٠‬‬ ‫ﺘﺠﻤﻴﻊ ﺍﻷﺠﺯﺍﺀ ﻭﺘﺭﻜﻴﺒﻬﺎ‬
‫‪١٠٠٠‬‬ ‫ﺃﻋﻤﺎل ﺍﻟﺴﺒﺎﻜﺔ‬
‫ﻤﺼﺎﻨﻊ ﺍﻟﺴﻴﺎﺭﺍﺕ‬
‫‪٥٠٠٠‬‬ ‫ﺍﻟﻔﺤﺹ ﺍﻟﺩﻗﻴﻕ ﻟﻠﻤﺴﺒﻭﻜﺎﺕ‬
‫‪١٠٠٠‬‬ ‫ﺍﻟﺘﻠﻤﻴﻊ ﻭﺍﻟﺼﻘل ﻭﺍﻟﺘﻨﺠﻴﺩ‬
‫‪٣٠٠٠‬‬ ‫ﺍﻟﺘﺠﻤﻴﻊ ﺍﻟﻨﻬﺎﺌﻰ ﻭﺍﻟﺘﺸﻁﻴﺏ ﻭﺍﻟﻔﺤﺹ‬

‫‪٢‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺘﺎﺒﻊ ﺠﺩﻭل ﺭﻗﻡ )‪ :(١-٢‬ﻤﺴﺘﻭﻯ ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ ﻓﻰ ﺍﻟﻔﺭﺍﻏﺎﺕ ﺍﻟﻤﺨﺘﻠﻔﺔ ﻟﻠﻤﺒﺎﻨﻰ‬

‫ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ)ﻟﻭﻜﺱ(‬ ‫ﺍﻟﻤﻜﺎﻥ‬


‫ﻭﺤﺩﺍﺕ ﺍﻟﻤﻌﺎﻟﺠﺔ ‪:‬‬
‫‪٦٠‬‬ ‫ﺍﻟﻤﻀﺨﺎﺕ‬
‫‪٣٠٠‬‬ ‫ﺍﻟﻀﺎﻏﻁﺎﺕ‬
‫ﻤﺼﺎﻨﻊ‬
‫‪٦٠‬‬ ‫ﺃﺠﻬﺯﺓ ﻤﺭﻜﺒﺔ ﻋﻠﻰ ﻭﺤﺩﺍﺕ ﺍﻟﻤﻌﺎﻟﺠﺔ‬
‫ﺍﻟﺒﺘﺭﻭﻜﻴﻤﺎﻭﻴﺎﺕ‬
‫‪٥٠٠‬‬ ‫ﻭﺤﺩﺍﺕ ﻤﻌﺎﻟﺠﺔ ﺍﻟﻠﺩﺍﺌﻥ‬
‫ﺍﻟﻐﻼﻴﺎﺕ ‪:‬‬
‫‪٣٠٠‬‬ ‫‪ -‬ﻤﻌﺩﺍﺕ ﺨﺎﺭﺠﻴﺔ‬
‫‪١٥٠‬‬ ‫‪ -‬ﻤﻌﺩﺍﺕ ﺩﺍﺨﻠﻴﺔ‬

‫‪٢‬‬
‫ﺠﺩﻭل ﺭﻗﻡ )‪ :(٢-٢‬ﻤﻌﺎﻤل ﺍﻟﺤﺠﺭﺓ )‪(Ri‬‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬

‫ﺇﺭﺘﻔﺎﻉ ﺍﻟﺴﻘﻑ )ﻡ(‬


‫ﺇﻀﺎﺀﻩ ﻏﻴﺭ ﻤﺒﺎﺸﺭﺓ‬
‫‪١٥.٠-١١.١٠‬‬ ‫‪١٠.٨٠-٩.١٠‬‬ ‫‪٩.٠ – ٧٥٠‬‬ ‫‪٧.٢٠ – ٦.٣٠‬‬ ‫‪٦.٠٠ – ٥١٠‬‬ ‫‪٥.٠٠ – ٤.٢٠‬‬ ‫‪٤.٠٠ – ٣.٦٠‬‬ ‫‪٣.٥٠ – ٣.٠٠‬‬ ‫‪٢.٨٥ – ٢.٧٠‬‬
‫ﺃﻭ ﺸﺒﻪ ﻏﻴﺭ ﻤﺒﺎﺸﺭﺓ‬
‫ﻤﻨﺴﻭﺏ ﺍﻟﺘﻌﻠﻴﻕ ﻓﻭﻕ ﺴﻁﺢ ﺍﻟﺸﻐل )ﻡ(‬
‫ﺇﻀﺎﺀﺓ ﻤﺒﺎﺸﺭﺓ‬
‫‪١٥.٠٠-١١.١٠‬‬ ‫‪١٠.٨٠-٩.١٠‬‬ ‫‪٩.٠٠ – ٧.٥٠‬‬ ‫‪٧.٢٠ – ٦.١٠‬‬ ‫‪٦.٠٠ – ٥.١٠‬‬ ‫‪٥.٠ – ٤.٢٠‬‬ ‫‪٤.٠ – ٣.٦٠‬‬ ‫‪٣.٥٠ – ٣.٠٠‬‬ ‫‪٢.٨٥-٢.٧٠‬‬ ‫‪٢.٥٥-٢.٤٠‬‬ ‫‪٢.٢٥-٢.١٠‬‬
‫ﺃﻭ ﺸﺒﻪ ﻤﺒﺎﺸﺭﺓ‬
‫ﻁﻭل ﺍﻟﺤﺠﺭﺓ‬
‫ﻤﻌﺎﻤل ﺍﻟﺤﺠﺭﺓ‬
‫)ﻡ(‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪٣.٠٠ – ٢.٤٠‬‬
‫‪J‬‬ ‫‪I‬‬ ‫‪J‬‬ ‫‪H‬‬ ‫‪٤.٢٠ – ٣.٠٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪٦.٠٠-٤.٢٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪G‬‬ ‫‪٩.٠٠-٦.٠٠‬‬

‫‪٢‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪١٢.٦٠-٩.٠٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪H‬‬ ‫ﺃﻜﺒﺭ ﻤﻥ ‪١٢.٦٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪٤.٢٠ – ٣.٠٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪٦.٠٠-٤.٢٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪٩.٠٠-٦.٠٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪١٢.٦٠-٩.٠٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪١٨.٠-١٢.٦٠‬‬
‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪H‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫ﺃﻜﺒﺭ ﻤﻥ ‪١٨.٠٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪٤.٢٠ – ٣.٠٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪٦.٠٠-٤.٢٠‬‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬

‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪٩.٠٠-٦.٠٠‬‬


‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪١٢.٦٠-٩.٠٠‬‬
‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪١٨.٠-١٢.٦٠‬‬
‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪E‬‬ ‫ﺃﻜﺒﺭ ﻤﻥ ‪١٨.٠٠‬‬
‫ﺘﺎﺒﻊ ﺠﺩﻭل ﺭﻗﻡ )‪ :(٢-٢‬ﻤﻌﺎﻤل ﺍﻟﺤﺠﺭﺓ )‪(Ri‬‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬

‫ﺇﺭﺘﻔﺎﻉ ﺍﻟﺴﻘﻑ )ﻡ(‬


‫‪– ٢.٧٠‬‬ ‫ﺇﻀﺎﺀﻩ ﻏﻴﺭ ﻤﺒﺎﺸﺭﺓ‬
‫‪١٥.٠-١١.١٠‬‬ ‫‪١٠.٨٠-٩.١٠‬‬ ‫‪٩.٠ – ٧٥٠‬‬ ‫‪٧.٢٠ – ٦.٣٠‬‬ ‫‪٦.٠٠ – ٥١٠‬‬ ‫‪٥.٠٠ – ٤.٢٠‬‬ ‫‪٤.٠٠ – ٣.٦٠‬‬ ‫‪٣.٥٠ – ٣.٠٠‬‬
‫‪٢.٨٥‬‬ ‫ﺃﻭ ﺸﺒﻪ ﻏﻴﺭ ﻤﺒﺎﺸﺭﺓ‬
‫ﻤﻨﺴﻭﺏ ﺍﻟﺘﻌﻠﻴﻕ ﻓﻭﻕ ﺴﻁﺢ ﺍﻟﺸﻐل )ﻡ(‬
‫‪-١١.١٠‬‬ ‫‪-٩.١٠‬‬ ‫‪– ٧.٥٠‬‬ ‫‪– ٦.١٠‬‬ ‫‪– ٥.١٠‬‬ ‫‪– ٣.٠٠‬‬ ‫‪-٢.١٠‬‬ ‫ﺇﻀﺎﺀﺓ ﻤﺒﺎﺸﺭﺓ‬
‫‪٥.٠ – ٤.٢٠‬‬ ‫‪٤.٠ – ٣.٦٠‬‬ ‫‪٢.٨٥-٢.٧٠‬‬ ‫‪٢.٥٥-٢.٤٠‬‬
‫‪١٥.٠٠‬‬ ‫‪١٠.٨٠‬‬ ‫‪٩.٠٠‬‬ ‫‪٧.٢٠‬‬ ‫‪٦.٠٠‬‬ ‫‪٣.٥٠‬‬ ‫‪٢.٢٥‬‬ ‫ﺃﻭ ﺸﺒﻪ ﻤﺒﺎﺸﺭﺓ‬
‫ﻋﺭﺽ ﺍﻟﺤﺠﺭﺓ‬ ‫ﻤﻌﺎﻤل ﺍﻟﺤﺠﺭﺓ‬ ‫ﻁﻭل ﺍﻟﺤﺠﺭﺓ‬
‫)ﻡ(‬ ‫)ﻡ(‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪٦.٠٠-٤.٢٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪٩.٠٠-٦.٠٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪١٢.٦٠-٩.٠٠‬‬
‫‪٢.٧٠-٢.٥٥‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪E‬‬ ‫‪١٨.٠-١٢.٦٠‬‬

‫‪٢‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪J‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪٢٧.٠-١٨.٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫ﺃﻜﺒﺭ ﻤﻥ ‪٢٧.٠٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪٦.٠٠-٤.٢٠‬‬
‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪٩.٠٠-٦.٠٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪J‬‬ ‫‪H‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪١٢.٦٠-٩.٠٠‬‬
‫‪٣.١٥-٢.٨٥‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪G‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪١٨.٠-١٢.٦٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪G‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪٣٣.٠٠-١٨.٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫ﺃﻜﺒﺭ ﻤﻥ‪٣٣.٠٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪F‬‬ ‫‪٩.٠٠-٦.٠٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪E‬‬ ‫‪F‬‬ ‫‪١٢.٦٠-٩.٠٠‬‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬

‫‪J‬‬ ‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪E‬‬ ‫‪١٨.٠-١٢.٦٠‬‬
‫‪٣.٧٥-٣.٣٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪J‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪E‬‬ ‫‪٢٧.٠٠-.١٨.٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪D‬‬ ‫‪E‬‬ ‫‪٤٢.٠٠-٢٧.٠٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪H‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪D‬‬ ‫‪D‬‬ ‫ﺃﻜﺒﺭ ﻤﻥ‪٤٢.٠٠‬‬
‫ﺘﺎﺒﻊ ﺠﺩﻭل ﺭﻗﻡ )‪ :(٢-٢‬ﻤﻌﺎﻤل ﺍﻟﺤﺠﺭﺓ )‪(Ri‬‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬

‫ﺇﺭﺘﻔﺎﻉ ﺍﻟﺴﻘﻑ )ﻡ(‬


‫‪-١١.١٠‬‬ ‫‪-٩.١٠‬‬ ‫‪– ٦.٣٠‬‬ ‫‪– ٤.٢٠‬‬ ‫‪– ٣.٦٠‬‬ ‫‪– ٣.٠٠‬‬ ‫‪– ٢.٧٠‬‬ ‫ﺇﻀﺎﺀﻩ ﻏﻴﺭ ﻤﺒﺎﺸﺭﺓ‬
‫‪٩.٠ – ٧٥٠‬‬ ‫‪٦.٠٠ – ٥١٠‬‬
‫‪١٥.٠‬‬ ‫‪١٠.٨٠‬‬ ‫‪٧.٢٠‬‬ ‫‪٥.٠٠‬‬ ‫‪٤.٠٠‬‬ ‫‪٣.٥٠‬‬ ‫‪٢.٨٥‬‬ ‫ﺃﻭ ﺸﺒﻪ ﻏﻴﺭ ﻤﺒﺎﺸﺭﺓ‬
‫ﻤﻨﺴﻭﺏ ﺍﻟﺘﻌﻠﻴﻕ ﻓﻭﻕ ﺴﻁﺢ ﺍﻟﺸﻐل )ﻡ(‬
‫‪– ٧.٥٠‬‬ ‫‪– ٦.١٠‬‬ ‫‪– ٥.١٠‬‬ ‫‪– ٣.٠٠‬‬ ‫ﺇﻀﺎﺀﺓ ﻤﺒﺎﺸﺭﺓ‬
‫‪١٥.٠٠- ١١.١٠‬‬ ‫‪١٠.٨٠-٩.١٠‬‬ ‫‪٥.٠ – ٤.٢٠‬‬ ‫‪٤.٠ – ٣.٦٠‬‬ ‫‪٢.٨٥-٢.٧٠‬‬ ‫‪٢.٥٥-٢.٤٠‬‬ ‫‪٢.٢٥-٢.١٠‬‬
‫‪٩.٠٠‬‬ ‫‪٧.٢٠‬‬ ‫‪٦.٠٠‬‬ ‫‪٣.٥٠‬‬ ‫ﺃﻭ ﺸﺒﻪ ﻤﺒﺎﺸﺭﺓ‬
‫ﻋﺭﺽ ﺍﻟﺤﺠﺭﺓ‬
‫ﻤﻌﺎﻤل ﺍﻟﺤﺠﺭﺓ‬ ‫ﻁﻭل ﺍﻟﺤﺠﺭﺓ‬ ‫ﻋﺭﺽ ﺍﻟﺤﺠﺭﺓ‬
‫)ﻡ(‬ ‫)ﻡ(‬ ‫)ﻡ(‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪E‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪٩–٦‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪I‬‬ ‫‪G‬‬ ‫‪G‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪١٣ – ٩‬‬
‫‪٤.٠٥-٣.٩٠‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪D‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪١٨ – ١٣‬‬ ‫‪٨-٦‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪H‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪D‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪٢٧ – ١٨‬‬
‫‪٤٢ – ٢٧‬‬

‫‪٢‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪C‬‬ ‫‪C‬‬ ‫‪C‬‬
‫‪J‬‬ ‫‪I‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪C‬‬ ‫‪C‬‬ ‫‪C‬‬ ‫ﺃﻜﺒﺭ ﻤﻥ ‪٤٢‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪١٣ – ٩‬‬
‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪H‬‬ ‫‪H‬‬ ‫‪F‬‬ ‫‪D‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪C‬‬ ‫‪١٨ – ١٣‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪٢٧ – ١٨‬‬
‫‪٥.٥٥-٤.٨٠‬‬ ‫‪١٠ – ٨.١٠‬‬
‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪٤٢ – ٢٧‬‬
‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪٥٤ - ٤٢‬‬
‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫ﺃﻜﺒﺭ ﻤﻥ ‪٥٤‬‬
‫‪J‬‬ ‫‪I‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪H‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪١٣ – ٩‬‬
‫‪J‬‬ ‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪١٨ – ١٣‬‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬

‫‪J‬‬ ‫‪J‬‬ ‫‪H‬‬ ‫‪H‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪C‬‬ ‫‪A‬‬ ‫‪٢٧ – ١٨‬‬
‫‪٦.٤٥-٥.٧٠‬‬ ‫‪١١.٧ – ١٠‬‬
‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪٤٢ – ٢٧‬‬
‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪٦٠ -٤٢‬‬
‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫ﺃﻜﺒﺭ ﻤﻥ ‪٦٠‬‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺘﺎﺒﻊ ﺠﺩﻭل ﺭﻗﻡ )‪ :(٢-٢‬ﻤﻌﺎﻤل ﺍﻟﺤﺠﺭﺓ )‪(Ri‬‬


‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬

‫ﺇﺭﺘﻔﺎﻉ ﺍﻟﺴﻘﻑ )ﻡ(‬


‫ﺇﻀﺎﺀﻩ ﻏﻴﺭ ﻤﺒﺎﺸﺭﺓ‬
‫‪١٥.٠-١١.١٠‬‬ ‫‪١٠.٨٠-٩.١٠‬‬ ‫‪٩.٠ – ٧٥٠‬‬ ‫‪٧.٢٠ – ٦.٣٠‬‬ ‫‪٦.٠٠ – ٥١٠‬‬ ‫‪٥.٠٠ – ٤.٢٠‬‬ ‫‪٤.٠٠ – ٣.٦٠‬‬ ‫‪٣.٥٠ – ٣.٠٠‬‬ ‫‪٢.٨٥ – ٢.٧٠‬‬
‫ﺃﻭ ﺸﺒﻪ ﻏﻴﺭ ﻤﺒﺎﺸﺭﺓ‬
‫ﻤﻨﺴﻭﺏ ﺍﻟﺘﻌﻠﻴﻕ ﻓﻭﻕ ﺴﻁﺢ ﺍﻟﺸﻐل )ﻡ(‬
‫‪-١١.١٠‬‬ ‫ﺇﻀﺎﺀﺓ ﻤﺒﺎﺸﺭﺓ‬
‫‪١٠.٨٠-٩.١٠‬‬ ‫‪٩.٠٠ – ٧.٥٠‬‬ ‫‪٧.٢٠ – ٦.١٠‬‬ ‫‪٦.٠٠ – ٥.١٠‬‬ ‫‪٥.٠ – ٤.٢٠‬‬ ‫‪٤.٠ – ٣.٦٠‬‬ ‫‪٣.٥٠ – ٣.٠٠‬‬ ‫‪٢.٨٥-٢.٧٠‬‬ ‫‪٢.٥٥-٢.٤٠‬‬ ‫‪٢.٢٥-٢.١٠‬‬
‫‪١٥.٠٠‬‬ ‫ﺃﻭ ﺸﺒﻪ ﻤﺒﺎﺸﺭﺓ‬
‫ﻤﻌﺎﻤل ﺍﻟﺤﺠﺭﺓ‬ ‫ﻁﻭل ﺍﻟﺤﺠﺭﺓ‬ ‫ﻋﺭﺽ‬
‫)ﻡ(‬ ‫ﺍﻟﺤﺠﺭﺓ‬
‫‪J‬‬ ‫‪I‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪C‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪١٨ – ١٣‬‬ ‫)ﻡ(‬
‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪٢٧ – ١٨‬‬
‫‪J‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪٤٢ – ٢٧‬‬ ‫‪١٣.٥-١٢‬‬
‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪٦٠ -٤٢‬‬
‫‪I‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫ﺃﻜﺒﺭ ﻤﻥ ‪٦٠‬‬
‫‪J‬‬ ‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪١٨ – ١٣‬‬

‫‪٢‬‬
‫‪J‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪٢٧ – ١٨‬‬
‫‪I‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪C‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪٤٢ – ٢٧‬‬ ‫‪١٦.٥-١٣‬‬
‫‪I‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪C‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪٦٠ -٤٢‬‬
‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪C‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫ﺃﻜﺒﺭ ﻤﻥ ‪٦٠‬‬
‫‪I‬‬ ‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪٢٧ – ١٨‬‬
‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪٤٢ – ٢٧‬‬
‫‪٢٠.١٠-١٦‬‬
‫‪H‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪٦٠ -٤٢‬‬
‫‪H‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫ﺃﻜﺒﺭ ﻤﻥ ‪٦٠‬‬
‫‪I‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪٢٧ – ١٨‬‬
‫‪H‬‬ ‫‪F‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪٤٢ – ٢٧‬‬
‫‪٢٧ - ٢٠‬‬
‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪٦٠ -٤٢‬‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬

‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫ﺃﻜﺒﺭ ﻤﻥ ‪٦٠‬‬
‫‪H‬‬ ‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪٢٧ – ١٨‬‬
‫‪C‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪٤٢ – ٢٧‬‬
‫ﺃﻜﺒﺭ ﻤﻥ ‪٢٧‬‬
‫‪G‬‬ ‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪٦٠ -٤٢‬‬
‫‪F‬‬ ‫‪E‬‬ ‫‪D‬‬ ‫‪C‬‬ ‫‪C‬‬ ‫‪B‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫‪A‬‬ ‫ﺃﻜﺒﺭ ﻤﻥ ‪٦٠‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪ :(٣-٢‬ﻤﻌﺎﻤل ﺍﻻﺴﺘﻔﺎﺩﺓ )‪ (u‬ﻟﻭﺤﺩﺍﺕ ﺍﻹﻨﺎﺭﺓ‬

‫‪Ceiling‬‬ ‫‪75 %‬‬ ‫‪50 %‬‬ ‫‪30 %‬‬

‫‪No‬‬ ‫‪Polar curve‬‬ ‫‪LUMINAIRE‬‬ ‫‪Walls‬‬ ‫‪50%‬‬ ‫‪30%‬‬ ‫‪10%‬‬ ‫‪50%‬‬ ‫‪30%‬‬ ‫‪10%‬‬ ‫‪30%‬‬ ‫‪10%‬‬

‫‪Room Index‬‬ ‫‪COEFFICIENT OF UTILIZATION‬‬


‫‪J‬‬ ‫‪.38‬‬ ‫‪.36‬‬ ‫‪.35‬‬ ‫‪.38‬‬ ‫‪.36‬‬ ‫‪.35‬‬ ‫‪.36‬‬ ‫‪.35‬‬
‫‪I‬‬ ‫‪.46‬‬ ‫‪.45‬‬ ‫‪.44‬‬ ‫‪.45‬‬ ‫‪.44‬‬ ‫‪.43‬‬ ‫‪.44‬‬ ‫‪.42‬‬
‫‪H‬‬ ‫‪.49‬‬ ‫‪.49‬‬ ‫‪.48‬‬ ‫‪.49‬‬ ‫‪.48‬‬ ‫‪.47‬‬ ‫‪.48‬‬ ‫‪.47‬‬
‫‪G‬‬ ‫‪.53‬‬ ‫‪.52‬‬ ‫‪.51‬‬ ‫‪.52‬‬ ‫‪.51‬‬ ‫‪.50‬‬ ‫‪.51‬‬ ‫‪.49‬‬
‫‪F‬‬ ‫‪.55‬‬ ‫‪.54‬‬ ‫‪.53‬‬ ‫‪.53‬‬ ‫‪.53‬‬ ‫‪.52‬‬ ‫‪.53‬‬ ‫‪.51‬‬
‫‪1‬‬ ‫‪E‬‬ ‫‪.57‬‬ ‫‪.57‬‬ ‫‪.36‬‬ ‫‪.37‬‬ ‫‪.56‬‬ ‫‪.55‬‬ ‫‪.55‬‬ ‫‪.54‬‬
‫‪D‬‬ ‫‪.61‬‬ ‫‪.59‬‬ ‫‪.58‬‬ ‫‪.59‬‬ ‫‪.58‬‬ ‫‪.57‬‬ ‫‪.57‬‬ ‫‪.56‬‬
‫‪C‬‬ ‫‪.62‬‬ ‫‪.61‬‬ ‫‪.59‬‬ ‫‪.60‬‬ ‫‪.59‬‬ ‫‪.58‬‬ ‫‪.58‬‬ ‫‪.37‬‬
‫‪B‬‬ ‫‪.63‬‬ ‫‪.62‬‬ ‫‪.61‬‬ ‫‪.61‬‬ ‫‪.60‬‬ ‫‪.59‬‬ ‫‪.59‬‬ ‫‪.58‬‬
‫‪A‬‬ ‫‪.64‬‬ ‫‪.63‬‬ ‫‪.62‬‬ ‫‪.62‬‬ ‫‪.61‬‬ ‫‪.60‬‬ ‫‪.60‬‬ ‫‪.59‬‬
‫‪J‬‬ ‫‪.31‬‬ ‫‪.26‬‬ ‫‪.23‬‬ ‫‪.30‬‬ ‫‪.26‬‬ ‫‪.23‬‬ ‫‪.26‬‬ ‫‪.23‬‬
‫‪I‬‬ ‫‪.38‬‬ ‫‪.34‬‬ ‫‪.31‬‬ ‫‪.37‬‬ ‫‪.33‬‬ ‫‪.31‬‬ ‫‪.33‬‬ ‫‪.31‬‬
‫‪H‬‬ ‫‪.41‬‬ ‫‪.38‬‬ ‫‪.34‬‬ ‫‪.41‬‬ ‫‪.38‬‬ ‫‪.34‬‬ ‫‪.37‬‬ ‫‪.34‬‬
‫‪G‬‬ ‫‪.45‬‬ ‫‪.41‬‬ ‫‪.39‬‬ ‫‪.44‬‬ ‫‪.41‬‬ ‫‪.39‬‬ ‫‪.40‬‬ ‫‪.39‬‬
‫‪F‬‬ ‫‪.47‬‬ ‫‪.44‬‬ ‫‪.41‬‬ ‫‪.46‬‬ ‫‪.43‬‬ ‫‪.41‬‬ ‫‪.43‬‬ ‫‪.41‬‬
‫‪2‬‬ ‫‪E‬‬ ‫‪.51‬‬ ‫‪.48‬‬ ‫‪.46‬‬ ‫‪.50‬‬ ‫‪.48‬‬ ‫‪.46‬‬ ‫‪.46‬‬ ‫‪.46‬‬
‫‪D‬‬ ‫‪.55‬‬ ‫‪.52‬‬ ‫‪.50‬‬ ‫‪.54‬‬ ‫‪.52‬‬ ‫‪.50‬‬ ‫‪.51‬‬ ‫‪.50‬‬
‫‪C‬‬ ‫‪.56‬‬ ‫‪.54‬‬ ‫‪.52‬‬ ‫‪.55‬‬ ‫‪.53‬‬ ‫‪.52‬‬ ‫‪.52‬‬ ‫‪.51‬‬
‫‪B‬‬ ‫‪.59‬‬ ‫‪.57‬‬ ‫‪.55‬‬ ‫‪.58‬‬ ‫‪.56‬‬ ‫‪.54‬‬ ‫‪.55‬‬ ‫‪.54‬‬
‫‪A‬‬ ‫‪.60‬‬ ‫‪.58‬‬ ‫‪.56‬‬ ‫‪.59‬‬ ‫‪.57‬‬ ‫‪.56‬‬ ‫‪.56‬‬ ‫‪.55‬‬
‫‪J‬‬ ‫‪.25‬‬ ‫‪.22‬‬ ‫‪.20‬‬ ‫‪.24‬‬ ‫‪.22‬‬ ‫‪.20‬‬ ‫‪.22‬‬ ‫‪.20‬‬
‫‪I‬‬ ‫‪.31‬‬ ‫‪.28‬‬ ‫‪.26‬‬ ‫‪.29‬‬ ‫‪.28‬‬ ‫‪.26‬‬ ‫‪.28‬‬ ‫‪.26‬‬
‫‪H‬‬ ‫‪.34‬‬ ‫‪.31‬‬ ‫‪.29‬‬ ‫‪.32‬‬ ‫‪.31‬‬ ‫‪.29‬‬ ‫‪.30‬‬ ‫‪.28‬‬
‫‪G‬‬ ‫‪.36‬‬ ‫‪.33‬‬ ‫‪.32‬‬ ‫‪.34‬‬ ‫‪.33‬‬ ‫‪.31‬‬ ‫‪.32‬‬ ‫‪.30‬‬
‫‪F‬‬ ‫‪.38‬‬ ‫‪.35‬‬ ‫‪.34‬‬ ‫‪.36‬‬ ‫‪.34‬‬ ‫‪.33‬‬ ‫‪.34‬‬ ‫‪.32‬‬
‫‪3‬‬ ‫‪E‬‬ ‫‪.40‬‬ ‫‪.39‬‬ ‫‪.38‬‬ ‫‪.39‬‬ ‫‪.37‬‬ ‫‪.36‬‬ ‫‪.37‬‬ ‫‪.35‬‬
‫‪D‬‬ ‫‪.43‬‬ ‫‪.41‬‬ ‫‪.40‬‬ ‫‪.42‬‬ ‫‪.40‬‬ ‫‪.39‬‬ ‫‪.39‬‬ ‫‪.38‬‬
‫‪C‬‬ ‫‪.45‬‬ ‫‪.43‬‬ ‫‪.42‬‬ ‫‪.44‬‬ ‫‪.41‬‬ ‫‪.40‬‬ ‫‪.40‬‬ ‫‪.40‬‬
‫‪B‬‬ ‫‪.48‬‬ ‫‪.45‬‬ ‫‪.44‬‬ ‫‪.47‬‬ ‫‪.43‬‬ ‫‪.42‬‬ ‫‪.42‬‬ ‫‪.41‬‬
‫‪A‬‬ ‫‪.50‬‬ ‫‪.47‬‬ ‫‪.46‬‬ ‫‪.48‬‬ ‫‪.46‬‬ ‫‪.45‬‬ ‫‪.45‬‬ ‫‪.44‬‬
‫‪J‬‬ ‫‪.52‬‬ ‫‪.49‬‬ ‫‪.47‬‬ ‫‪.51‬‬ ‫‪.49‬‬ ‫‪.47‬‬ ‫‪.48‬‬ ‫‪.47‬‬
‫‪I‬‬ ‫‪.55‬‬ ‫‪.53‬‬ ‫‪.51‬‬ ‫‪.54‬‬ ‫‪.52‬‬ ‫‪.51‬‬ ‫‪.51‬‬ ‫‪.50‬‬
‫‪H‬‬ ‫‪.57‬‬ ‫‪.55‬‬ ‫‪.53‬‬ ‫‪.56‬‬ ‫‪.54‬‬ ‫‪.53‬‬ ‫‪.53‬‬ ‫‪.53‬‬
‫‪G‬‬ ‫‪.58‬‬ ‫‪.57‬‬ ‫‪.55‬‬ ‫‪.57‬‬ ‫‪.56‬‬ ‫‪.55‬‬ ‫‪.55‬‬ ‫‪.54‬‬
‫‪F‬‬ ‫‪.59‬‬ ‫‪.58‬‬ ‫‪.57‬‬ ‫‪.58‬‬ ‫‪.57‬‬ ‫‪.56‬‬ ‫‪.56‬‬ ‫‪.56‬‬
‫‪4‬‬ ‫‪E‬‬ ‫‪.61‬‬ ‫‪.60‬‬ ‫‪.59‬‬ ‫‪.60‬‬ ‫‪.59‬‬ ‫‪.58‬‬ ‫‪.58‬‬ ‫‪.57‬‬
‫‪D‬‬ ‫‪.63‬‬ ‫‪.62‬‬ ‫‪.61‬‬ ‫‪.61‬‬ ‫‪.61‬‬ ‫‪.60‬‬ ‫‪.60‬‬ ‫‪.59‬‬
‫‪C‬‬ ‫‪.64‬‬ ‫‪.64‬‬ ‫‪.63‬‬ ‫‪.63‬‬ ‫‪.63‬‬ ‫‪.62‬‬ ‫‪.62‬‬ ‫‪.61‬‬
‫‪B‬‬ ‫‪.65‬‬ ‫‪.65‬‬ ‫‪.64‬‬ ‫‪.64‬‬ ‫‪.64‬‬ ‫‪.63‬‬ ‫‪.63‬‬ ‫‪62‬‬
‫‪A‬‬ ‫‪.66‬‬ ‫‪.66‬‬ ‫‪.65‬‬ ‫‪.65‬‬ ‫‪.65‬‬ ‫‪.64‬‬ ‫‪.64‬‬ ‫‪.63‬‬
‫‪J‬‬ ‫‪.38‬‬ ‫‪.32‬‬ ‫‪.28‬‬ ‫‪.37‬‬ ‫‪.32‬‬ ‫‪.28‬‬ ‫‪.31‬‬ ‫‪.28‬‬
‫‪I‬‬ ‫‪.47‬‬ ‫‪.42‬‬ ‫‪.39‬‬ ‫‪.46‬‬ ‫‪.41‬‬ ‫‪.38‬‬ ‫‪.40‬‬ ‫‪.37‬‬
‫‪H‬‬ ‫‪.51‬‬ ‫‪.47‬‬ ‫‪.44‬‬ ‫‪.50‬‬ ‫‪.47‬‬ ‫‪.43‬‬ ‫‪.46‬‬ ‫‪.43‬‬
‫‪G‬‬ ‫‪.55‬‬ ‫‪.51‬‬ ‫‪.48‬‬ ‫‪.54‬‬ ‫‪.51‬‬ ‫‪.47‬‬ ‫‪.50‬‬ ‫‪.47‬‬
‫‪F‬‬ ‫‪.58‬‬ ‫‪.54‬‬ ‫‪.51‬‬ ‫‪.57‬‬ ‫‪.53‬‬ ‫‪.51‬‬ ‫‪.52‬‬ ‫‪.50‬‬
‫‪5‬‬ ‫‪E‬‬ ‫‪.63‬‬ ‫‪.60‬‬ ‫‪.57‬‬ ‫‪.62‬‬ ‫‪.59‬‬ ‫‪.56‬‬ ‫‪.58‬‬ ‫‪.53‬‬
‫‪D‬‬ ‫‪.68‬‬ ‫‪.64‬‬ ‫‪.61‬‬ ‫‪.66‬‬ ‫‪.64‬‬ ‫‪.61‬‬ ‫‪.63‬‬ ‫‪.60‬‬
‫‪C‬‬ ‫‪.70‬‬ ‫‪.67‬‬ ‫‪.63‬‬ ‫‪.68‬‬ ‫‪.65‬‬ ‫‪.64‬‬ ‫‪.64‬‬ ‫‪.62‬‬
‫‪B‬‬ ‫‪.73‬‬ ‫‪.70‬‬ ‫‪.68‬‬ ‫‪.71‬‬ ‫‪.68‬‬ ‫‪.67‬‬ ‫‪.67‬‬ ‫‪.66‬‬
‫‪A‬‬ ‫‪.74‬‬ ‫‪.72‬‬ ‫‪.70‬‬ ‫‪.72‬‬ ‫‪.70‬‬ ‫‪.68‬‬ ‫‪.69‬‬ ‫‪.67‬‬
‫‪J‬‬ ‫‪.34‬‬ ‫‪.29‬‬ ‫‪.25‬‬ ‫‪.33‬‬ ‫‪.29‬‬ ‫‪.25‬‬ ‫‪.28‬‬ ‫‪.25‬‬
‫‪I‬‬ ‫‪.42‬‬ ‫‪.38‬‬ ‫‪.35‬‬ ‫‪.41‬‬ ‫‪.37‬‬ ‫‪.34‬‬ ‫‪.37‬‬ ‫‪.34‬‬
‫‪H‬‬ ‫‪.46‬‬ ‫‪.42‬‬ ‫‪.39‬‬ ‫‪.44‬‬ ‫‪.42‬‬ ‫‪.39‬‬ ‫‪.41‬‬ ‫‪.39‬‬
‫‪G‬‬ ‫‪.50‬‬ ‫‪.46‬‬ ‫‪.43‬‬ ‫‪.48‬‬ ‫‪.45‬‬ ‫‪.41‬‬ ‫‪.44‬‬ ‫‪.41‬‬
‫‪F‬‬ ‫‪.53‬‬ ‫‪.49‬‬ ‫‪.46‬‬ ‫‪.51‬‬ ‫‪.47‬‬ ‫‪.44‬‬ ‫‪.47‬‬ ‫‪.44‬‬
‫‪6‬‬ ‫‪E‬‬ ‫‪.57‬‬ ‫‪.54‬‬ ‫‪.51‬‬ ‫‪.56‬‬ ‫‪.52‬‬ ‫‪.50‬‬ ‫‪.52‬‬ ‫‪.50‬‬
‫‪D‬‬ ‫‪.61‬‬ ‫‪.58‬‬ ‫‪.55‬‬ ‫‪.59‬‬ ‫‪.56‬‬ ‫‪.54‬‬ ‫‪.56‬‬ ‫‪.54‬‬
‫‪C‬‬ ‫‪.63‬‬ ‫‪.60‬‬ ‫‪.57‬‬ ‫‪.61‬‬ ‫‪.58‬‬ ‫‪.56‬‬ ‫‪.58‬‬ ‫‪.56‬‬
‫‪B‬‬ ‫‪.66‬‬ ‫‪.64‬‬ ‫‪.61‬‬ ‫‪.64‬‬ ‫‪.60‬‬ ‫‪.59‬‬ ‫‪.60‬‬ ‫‪.59‬‬
‫‪A‬‬ ‫‪.67‬‬ ‫‪.63‬‬ ‫‪.62‬‬ ‫‪.66‬‬ ‫‪.62‬‬ ‫‪.61‬‬ ‫‪.62‬‬ ‫‪.60‬‬
‫‪J‬‬ ‫‪.33‬‬ ‫‪.28‬‬ ‫‪.25‬‬ ‫‪.33‬‬ ‫‪.28‬‬ ‫‪.25‬‬ ‫‪.28‬‬ ‫‪.25‬‬
‫‪I‬‬ ‫‪.41‬‬ ‫‪.37‬‬ ‫‪.34‬‬ ‫‪.40‬‬ ‫‪.36‬‬ ‫‪.33‬‬ ‫‪.36‬‬ ‫‪.33‬‬
‫‪H‬‬ ‫‪.45‬‬ ‫‪.41‬‬ ‫‪.38‬‬ ‫‪.44‬‬ ‫‪.41‬‬ ‫‪.38‬‬ ‫‪.40‬‬ ‫‪.38‬‬
‫‪G‬‬ ‫‪.48‬‬ ‫‪.45‬‬ ‫‪.42‬‬ ‫‪.48‬‬ ‫‪.45‬‬ ‫‪.42‬‬ ‫‪.43‬‬ ‫‪.42‬‬
‫‪F‬‬ ‫‪.51‬‬ ‫‪.48‬‬ ‫‪.45‬‬ ‫‪.50‬‬ ‫‪.47‬‬ ‫‪.45‬‬ ‫‪.46‬‬ ‫‪.45‬‬
‫‪7‬‬ ‫‪E‬‬ ‫‪.55‬‬ ‫‪.53‬‬ ‫‪.50‬‬ ‫‪.55‬‬ ‫‪.52‬‬ ‫‪.50‬‬ ‫‪.51‬‬ ‫‪.50‬‬
‫‪D‬‬ ‫‪.60‬‬ ‫‪.57‬‬ ‫‪.54‬‬ ‫‪.58‬‬ ‫‪.56‬‬ ‫‪.54‬‬ ‫‪.55‬‬ ‫‪.54‬‬
‫‪C‬‬ ‫‪.61‬‬ ‫‪.59‬‬ ‫‪.56‬‬ ‫‪.60‬‬ ‫‪.57‬‬ ‫‪.56‬‬ ‫‪.57‬‬ ‫‪.55‬‬
‫‪B‬‬ ‫‪.64‬‬ ‫‪.62‬‬ ‫‪.60‬‬ ‫‪.62‬‬ ‫‪.60‬‬ ‫‪.59‬‬ ‫‪.60‬‬ ‫‪.58‬‬
‫‪A‬‬ ‫‪.63‬‬ ‫‪.63‬‬ ‫‪.61‬‬ ‫‪.64‬‬ ‫‪.62‬‬ ‫‪.60‬‬ ‫‪.61‬‬ ‫‪.60‬‬

‫‪٢‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺘﺎﺒﻊ ﺠﺩﻭل ﺭﻗﻡ )‪ :(٣-٢‬ﻤﻌﺎﻤل ﺍﻻﺴﺘﻔﺎﺩﺓ )‪ (u‬ﻟﻭﺤﺩﺍﺕ ﺍﻹﻨﺎﺭﺓ‬

‫‪Ceiling‬‬ ‫‪75 %‬‬ ‫‪50 %‬‬ ‫‪30 %‬‬

‫‪No‬‬ ‫‪Polar‬‬ ‫‪LUMINAIRE‬‬ ‫‪Walls‬‬ ‫‪50%‬‬ ‫‪30%‬‬ ‫‪10%‬‬ ‫‪50%‬‬ ‫‪30%‬‬ ‫‪10%‬‬ ‫‪30%‬‬ ‫‪10%‬‬

‫‪curve‬‬ ‫‪Room‬‬
‫‪Index‬‬
‫‪COEFFICIENT OF UTILIZATION‬‬

‫‪J‬‬ ‫‪.29‬‬ ‫‪.26‬‬ ‫‪.23‬‬ ‫‪.28‬‬ ‫‪.26‬‬ ‫‪.23‬‬ ‫‪.25‬‬ ‫‪.23‬‬


‫‪I‬‬ ‫‪.35‬‬ ‫‪.32‬‬ ‫‪.31‬‬ ‫‪.35‬‬ ‫‪.32‬‬ ‫‪.30‬‬ ‫‪.32‬‬ ‫‪.30‬‬
‫‪H‬‬ ‫‪.38‬‬ ‫‪.36‬‬ ‫‪.34‬‬ ‫‪.38‬‬ ‫‪.36‬‬ ‫‪.34‬‬ ‫‪.35‬‬ ‫‪.34‬‬
‫‪G‬‬ ‫‪.41‬‬ ‫‪.39‬‬ ‫‪.37‬‬ ‫‪.41‬‬ ‫‪.39‬‬ ‫‪.37‬‬ ‫‪.38‬‬ ‫‪.37‬‬
‫‪F‬‬ ‫‪.44‬‬ ‫‪.41‬‬ ‫‪.39‬‬ ‫‪.42‬‬ ‫‪.41‬‬ ‫‪.39‬‬ ‫‪.40‬‬ ‫‪.39‬‬
‫‪8‬‬ ‫‪E‬‬ ‫‪.46‬‬ ‫‪.45‬‬ ‫‪.42‬‬ ‫‪.46‬‬ ‫‪.44‬‬ ‫‪.42‬‬ ‫‪.44‬‬ ‫‪.42‬‬
‫‪D‬‬ ‫‪.50‬‬ ‫‪.48‬‬ ‫‪.46‬‬ ‫‪.49‬‬ ‫‪.47‬‬ ‫‪.46‬‬ ‫‪.46‬‬ ‫‪.46‬‬
‫‪C‬‬ ‫‪.51‬‬ ‫‪.49‬‬ ‫‪.47‬‬ ‫‪.50‬‬ ‫‪.48‬‬ ‫‪.47‬‬ ‫‪.48‬‬ ‫‪.46‬‬
‫‪B‬‬ ‫‪.53‬‬ ‫‪.51‬‬ ‫‪.50‬‬ ‫‪.52‬‬ ‫‪.50‬‬ ‫‪.49‬‬ ‫‪.49‬‬ ‫‪.49‬‬
‫‪A‬‬ ‫‪.54‬‬ ‫‪.52‬‬ ‫‪.50‬‬ ‫‪.53‬‬ ‫‪51‬‬ ‫‪.50‬‬ ‫‪.50‬‬ ‫‪.49‬‬
‫‪J‬‬ ‫‪.38‬‬ ‫‪.32‬‬ ‫‪.28‬‬ ‫‪.37‬‬ ‫‪.32‬‬ ‫‪.28‬‬ ‫‪.31‬‬ ‫‪.28‬‬
‫‪I‬‬ ‫‪.47‬‬ ‫‪.42‬‬ ‫‪.39‬‬ ‫‪.46‬‬ ‫‪.41‬‬ ‫‪.38‬‬ ‫‪.41‬‬ ‫‪.38‬‬
‫‪H‬‬ ‫‪.51‬‬ ‫‪.47‬‬ ‫‪.43‬‬ ‫‪.50‬‬ ‫‪.47‬‬ ‫‪.43‬‬ ‫‪.46‬‬ ‫‪.43‬‬
‫‪G‬‬ ‫‪.55‬‬ ‫‪.51‬‬ ‫‪.47‬‬ ‫‪.54‬‬ ‫‪.51‬‬ ‫‪.47‬‬ ‫‪.49‬‬ ‫‪.47‬‬
‫‪F‬‬ ‫‪.58‬‬ ‫‪.54‬‬ ‫‪.51‬‬ ‫‪.56‬‬ ‫‪.63‬‬ ‫‪.51‬‬ ‫‪.52‬‬ ‫‪.51‬‬
‫‪9‬‬ ‫‪E‬‬ ‫‪.63‬‬ ‫‪.59‬‬ ‫‪.56‬‬ ‫‪.62‬‬ ‫‪.59‬‬ ‫‪.56‬‬ ‫‪.58‬‬ ‫‪.56‬‬
‫‪D‬‬ ‫‪.67‬‬ ‫‪.64‬‬ ‫‪.61‬‬ ‫‪.66‬‬ ‫‪.63‬‬ ‫‪.61‬‬ ‫‪.63‬‬ ‫‪.61‬‬
‫‪C‬‬ ‫‪.69‬‬ ‫‪.67‬‬ ‫‪.64‬‬ ‫‪.67‬‬ ‫‪.65‬‬ ‫‪.63‬‬ ‫‪.64‬‬ ‫‪.63‬‬
‫‪B‬‬ ‫‪.72‬‬ ‫‪.70‬‬ ‫‪.67‬‬ ‫‪.71‬‬ ‫‪.68‬‬ ‫‪.67‬‬ ‫‪.67‬‬ ‫‪.66‬‬
‫‪A‬‬ ‫‪.74‬‬ ‫‪.71‬‬ ‫‪.69‬‬ ‫‪.72‬‬ ‫‪.70‬‬ ‫‪.68‬‬ ‫‪.69‬‬ ‫‪.67‬‬

‫*‬
‫‪J‬‬ ‫‪.33‬‬ ‫‪.28‬‬ ‫‪.26‬‬ ‫‪.32‬‬ ‫‪.28‬‬ ‫‪.26‬‬ ‫‪.28‬‬ ‫‪.26‬‬
‫‪I‬‬ ‫‪.39‬‬ ‫‪.36‬‬ ‫‪.34‬‬ ‫‪.39‬‬ ‫‪.35‬‬ ‫‪.34‬‬ ‫‪.34‬‬ ‫‪.34‬‬
‫‪H‬‬ ‫‪.43‬‬ ‫‪.40‬‬ ‫‪.38‬‬ ‫‪.42‬‬ ‫‪.40‬‬ ‫‪.38‬‬ ‫‪.39‬‬ ‫‪.38‬‬
‫‪G‬‬ ‫‪.46‬‬ ‫‪.43‬‬ ‫‪.41‬‬ ‫‪.45‬‬ ‫‪.43‬‬ ‫‪.41‬‬ ‫‪.42‬‬ ‫‪.41‬‬
‫‪F‬‬ ‫‪.48‬‬ ‫‪.46‬‬ ‫‪.43‬‬ ‫‪.47‬‬ ‫‪.45‬‬ ‫‪.43‬‬ ‫‪.45‬‬ ‫‪.43‬‬
‫‪10‬‬ ‫‪E‬‬ ‫‪.52‬‬ ‫‪.50‬‬ ‫‪.47‬‬ ‫‪.51‬‬ ‫‪.49‬‬ ‫‪.47‬‬ ‫‪.48‬‬ ‫‪.47‬‬
‫‪D‬‬ ‫‪.55‬‬ ‫‪.53‬‬ ‫‪.51‬‬ ‫‪.54‬‬ ‫‪.52‬‬ ‫‪.51‬‬ ‫‪.52‬‬ ‫‪.51‬‬
‫‪C‬‬ ‫‪.57‬‬ ‫‪.55‬‬ ‫‪.52‬‬ ‫‪.56‬‬ ‫‪.53‬‬ ‫‪.52‬‬ ‫‪.53‬‬ ‫‪.52‬‬
‫‪B‬‬ ‫‪.59‬‬ ‫‪.57‬‬ ‫‪.56‬‬ ‫‪.57‬‬ ‫‪.56‬‬ ‫‪.55‬‬ ‫‪.55‬‬ ‫‪.54‬‬
‫‪A‬‬ ‫‪.60‬‬ ‫‪.58‬‬ ‫‪.56‬‬ ‫‪.59‬‬ ‫‪.57‬‬ ‫‪.56‬‬ ‫‪.56‬‬ ‫‪.55‬‬
‫‪J‬‬ ‫‪.27‬‬ ‫‪.24‬‬ ‫‪.23‬‬ ‫‪.27‬‬ ‫‪.24‬‬ ‫‪.23‬‬ ‫‪.24‬‬ ‫‪.23‬‬
‫‪I‬‬ ‫‪.33‬‬ ‫‪.32‬‬ ‫‪.28‬‬ ‫‪.33‬‬ ‫‪.30‬‬ ‫‪.28‬‬ ‫‪.30‬‬ ‫‪.28‬‬
‫‪H‬‬ ‫‪.36‬‬ ‫‪.34‬‬ ‫‪.32‬‬ ‫‪.36‬‬ ‫‪.34‬‬ ‫‪.32‬‬ ‫‪.34‬‬ ‫‪.32‬‬
‫‪G‬‬ ‫‪.39‬‬ ‫‪.36‬‬ ‫‪.35‬‬ ‫‪.38‬‬ ‫‪.36‬‬ ‫‪.35‬‬ ‫‪.36‬‬ ‫‪.34‬‬
‫‪F‬‬ ‫‪.41‬‬ ‫‪.39‬‬ ‫‪.37‬‬ ‫‪.40‬‬ ‫‪.38‬‬ ‫‪.37‬‬ ‫‪.38‬‬ ‫‪.37‬‬
‫‪11‬‬ ‫‪E‬‬ ‫‪.44‬‬ ‫‪.42‬‬ ‫‪.40‬‬ ‫‪.43‬‬ ‫‪.42‬‬ ‫‪.40‬‬ ‫‪.42‬‬ ‫‪.40‬‬
‫‪D‬‬ ‫‪.47‬‬ ‫‪.45‬‬ ‫‪.43‬‬ ‫‪.46‬‬ ‫‪.44‬‬ ‫‪.43‬‬ ‫‪.43‬‬ ‫‪.42‬‬
‫‪C‬‬ ‫‪.48‬‬ ‫‪.46‬‬ ‫‪.45‬‬ ‫‪.47‬‬ ‫‪.45‬‬ ‫‪.45‬‬ ‫‪.44‬‬ ‫‪.43‬‬
‫‪B‬‬ ‫‪.50‬‬ ‫‪.48‬‬ ‫‪.47‬‬ ‫‪.49‬‬ ‫‪.47‬‬ ‫‪.46‬‬ ‫‪.46‬‬ ‫‪.45‬‬
‫‪A‬‬ ‫‪.51‬‬ ‫‪.49‬‬ ‫‪.48‬‬ ‫‪.50‬‬ ‫‪.48‬‬ ‫‪.47‬‬ ‫‪.47‬‬ ‫‪.46‬‬
‫‪J‬‬ ‫‪.26‬‬ ‫‪.23‬‬ ‫‪.21‬‬ ‫‪.26‬‬ ‫‪.23‬‬ ‫‪.21‬‬ ‫‪.23‬‬ ‫‪.21‬‬
‫‪I‬‬ ‫‪.32‬‬ ‫‪.29‬‬ ‫‪.24‬‬ ‫‪.31‬‬ ‫‪.28‬‬ ‫‪.27‬‬ ‫‪.28‬‬ ‫‪.27‬‬
‫‪H‬‬ ‫‪.35‬‬ ‫‪.32‬‬ ‫‪.31‬‬ ‫‪.34‬‬ ‫‪.32‬‬ ‫‪.31‬‬ ‫‪.32‬‬ ‫‪.30‬‬
‫‪G‬‬ ‫‪.37‬‬ ‫‪.35‬‬ ‫‪.33‬‬ ‫‪.37‬‬ ‫‪.35‬‬ ‫‪.33‬‬ ‫‪.34‬‬ ‫‪.33‬‬
‫‪F‬‬ ‫‪.39‬‬ ‫‪.37‬‬ ‫‪.35‬‬ ‫‪.38‬‬ ‫‪.37‬‬ ‫‪.35‬‬ ‫‪.37‬‬ ‫‪.33‬‬
‫‪12‬‬ ‫‪E‬‬ ‫‪.42‬‬ ‫‪.40‬‬ ‫‪.38‬‬ ‫‪.41‬‬ ‫‪.40‬‬ ‫‪.38‬‬ ‫‪.40‬‬ ‫‪.38‬‬
‫‪D‬‬ ‫‪.45‬‬ ‫‪.43‬‬ ‫‪.41‬‬ ‫‪.44‬‬ ‫‪.42‬‬ ‫‪.41‬‬ ‫‪.41‬‬ ‫‪.40‬‬
‫‪C‬‬ ‫‪.46‬‬ ‫‪.45‬‬ ‫‪.42‬‬ ‫‪.45‬‬ ‫‪.43‬‬ ‫‪.42‬‬ ‫‪.42‬‬ ‫‪.41‬‬
‫‪B‬‬ ‫‪.48‬‬ ‫‪.46‬‬ ‫‪.45‬‬ ‫‪.47‬‬ ‫‪.45‬‬ ‫‪.44‬‬ ‫‪.44‬‬ ‫‪.43‬‬
‫‪A‬‬ ‫‪.49‬‬ ‫‪.47‬‬ ‫‪.46‬‬ ‫‪.48‬‬ ‫‪.46‬‬ ‫‪.45‬‬ ‫‪.45‬‬ ‫‪.44‬‬
‫‪J‬‬ ‫‪.33‬‬ ‫‪.31‬‬ ‫‪.30‬‬ ‫‪.33‬‬ ‫‪.34‬‬ ‫‪.30‬‬ ‫‪.30‬‬ ‫‪.29‬‬
‫‪I‬‬ ‫‪.40‬‬ ‫‪.38‬‬ ‫‪.38‬‬ ‫‪.39‬‬ ‫‪.38‬‬ ‫‪.37‬‬ ‫‪.38‬‬ ‫‪.36‬‬
‫‪H‬‬ ‫‪.43‬‬ ‫‪.42‬‬ ‫‪.41‬‬ ‫‪.42‬‬ ‫‪.41‬‬ ‫‪.41‬‬ ‫‪.41‬‬ ‫‪.40‬‬
‫‪G‬‬ ‫‪.46‬‬ ‫‪.45‬‬ ‫‪.44‬‬ ‫‪.46‬‬ ‫‪.44‬‬ ‫‪.43‬‬ ‫‪.44‬‬ ‫‪.43‬‬
‫‪F‬‬ ‫‪.49‬‬ ‫‪.47‬‬ ‫‪.46‬‬ ‫‪.47‬‬ ‫‪.46‬‬ ‫‪.45‬‬ ‫‪.46‬‬ ‫‪.45‬‬
‫‪13‬‬ ‫‪E‬‬ ‫‪.51‬‬ ‫‪.50‬‬ ‫‪.49‬‬ ‫‪.50‬‬ ‫‪.49‬‬ ‫‪.48‬‬ ‫‪.49‬‬ ‫‪.47‬‬
‫‪D‬‬ ‫‪.55‬‬ ‫‪.52‬‬ ‫‪.51‬‬ ‫‪.53‬‬ ‫‪.52‬‬ ‫‪.50‬‬ ‫‪.51‬‬ ‫‪.50‬‬
‫‪C‬‬ ‫‪.55‬‬ ‫‪.54‬‬ ‫‪.52‬‬ ‫‪.54‬‬ ‫‪.53‬‬ ‫‪.52‬‬ ‫‪.52‬‬ ‫‪.51‬‬
‫‪B‬‬ ‫‪.56‬‬ ‫‪.55‬‬ ‫‪.54‬‬ ‫‪.55‬‬ ‫‪.53‬‬ ‫‪.53‬‬ ‫‪.53‬‬ ‫‪.52‬‬
‫‪A‬‬ ‫‪.57‬‬ ‫‪.56‬‬ ‫‪.55‬‬ ‫‪.56‬‬ ‫‪.55‬‬ ‫‪.53‬‬ ‫‪.54‬‬ ‫‪.53‬‬
‫‪J‬‬ ‫‪.29‬‬ ‫‪.27‬‬ ‫‪.26‬‬ ‫‪.29‬‬ ‫‪.27‬‬ ‫‪.26‬‬ ‫‪.27‬‬ ‫‪.26‬‬
‫‪I‬‬ ‫‪.35‬‬ ‫‪.34‬‬ ‫‪.33‬‬ ‫‪.35‬‬ ‫‪.33‬‬ ‫‪.33‬‬ ‫‪.33‬‬ ‫‪.34‬‬
‫‪H‬‬ ‫‪.38‬‬ ‫‪.37‬‬ ‫‪.36‬‬ ‫‪.37‬‬ ‫‪.36‬‬ ‫‪.36‬‬ ‫‪.36‬‬ ‫‪.35‬‬
‫‪G‬‬ ‫‪.40‬‬ ‫‪.39‬‬ ‫‪.39‬‬ ‫‪.40‬‬ ‫‪.39‬‬ ‫‪.38‬‬ ‫‪.38‬‬ ‫‪.38‬‬
‫‪F‬‬ ‫‪.43‬‬ ‫‪.42‬‬ ‫‪.40‬‬ ‫‪.44‬‬ ‫‪.40‬‬ ‫‪.39‬‬ ‫‪.40‬‬ ‫‪.39‬‬
‫‪14‬‬ ‫‪E‬‬ ‫‪.45‬‬ ‫‪.44‬‬ ‫‪.43‬‬ ‫‪.44‬‬ ‫‪.43‬‬ ‫‪42‬‬ ‫‪.43‬‬ ‫‪.42‬‬
‫‪D‬‬ ‫‪.48‬‬ ‫‪.46‬‬ ‫‪.45‬‬ ‫‪.46‬‬ ‫‪.45‬‬ ‫‪.44‬‬ ‫‪.45‬‬ ‫‪.44‬‬
‫‪C‬‬ ‫‪.48‬‬ ‫‪.47‬‬ ‫‪.45‬‬ ‫‪.47‬‬ ‫‪.46‬‬ ‫‪.45‬‬ ‫‪.45‬‬ ‫‪.45‬‬
‫‪B‬‬ ‫‪.50‬‬ ‫‪.48‬‬ ‫‪.47‬‬ ‫‪.48‬‬ ‫‪.47‬‬ ‫‪.46‬‬ ‫‪.46‬‬ ‫‪.46‬‬
‫‪A‬‬ ‫‪.50‬‬ ‫‪.49‬‬ ‫‪.48‬‬ ‫‪.49‬‬ ‫‪.48‬‬ ‫‪.47‬‬ ‫‪.48‬‬ ‫‪.46‬‬

‫‪٢‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
(‫ ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ‬:‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‬

‫( ﻟﻭﺤﺩﺍﺕ ﺍﻹﻨﺎﺭﺓ‬u) ‫ ﻤﻌﺎﻤل ﺍﻻﺴﺘﻔﺎﺩﺓ‬:(٣-٢) ‫ﺘﺎﺒﻊ ﺠﺩﻭل ﺭﻗﻡ‬

Ceiling 75 % 50 % 30 %
Polar curve Walls 50% 30% 10% 50% 30% 10% 30% 10%
No LUMINAIRE
Room
COEFFICIENT OF UTILIZATION
Index
J .23 .20 .19 .25 .20 .49
Plastic I .27 .24 .22 .29 .25 .23
Metal H .30 .27 .25 .32 .28 .26
G .32 .29 .28 .35 .32 .30
F ٣٤. .31 .30 .38 .34 .32
15 E .36 .33 .32 .41 .38 .36
D .38 .35 .34 .43 .40 .39
Metal Plastic C .39 .37 .36 .45 .42 .44
B .41 .39 .38 .47 .44 .43
A .42 .40 .39 .48 .46 .45
J .29 .26 .23 .28 .26 .23 .25 .23
I .35 .32 .34 .35 .32 .30 .32 .30
H .38 .36 .34 .38 .36 .34 .35 .34
G .41 .39 .37 .44 .39 .37 .38 .37
F .44 .44 .39 .42 .41 .39 .40 .39
16 E .46 .45 .42 .46 .44 .42 .44 .42
D .50 .48 .46 49 .47 .46 .46 .46
C .51 .49 .47 .50 .48 .47 .48 .46
B .53 .51 .50 .52 .50 .49 .49 .49
A .54 .52 .50 .53 .51 .50 .50 .49
J .29 .26 .23 .27 .25 .23 .25 .22
I .35 .32 .34 .33 .31 .30 .30 .28
H .38 .36 .35 .36 .34 .33 .33 .31
G .41 .39 .38 .39 .37 .35 .35 .34
F .44 .42 .40 .44 .39 .37 .37 .36
17 E .47 .45 .43 .44 .42 .41 .39 .38
D .51 .48 .46 .47 .45 .43 .42 .41
C .52 .50 .47 .48 .46 .45 .43 .42
B .54 .52 .50 .50 .48 .47 .44 .43
A .55 .53 .51 .51 .49 .48 .46 .44
J .21 .17 .14 .20 .16 .14 .16 .14
I .26 .22 .20 .25 .21 .19 .21 .19
H .29 .25 .23 .28 .25 .22 .24 .22
G .32 .28 .25 .30 .27 .25 .26 .24
F .34 .30 .27 .33 .30 .27 .29 .27
18 E .38 .34 .34 .36 .33 .34 .32 .30
D .41 .37 .34 .39 .36 .34 .35 .33
C .42 .39 .36 .41 .38 .36 .37 .36
B .45 .42 .39 .42 .40 .39 .39 .38
A .47 .44 .41 .45 .42 .40 .41 .39
J .24 .20 .19 .23 .20 .17 .19 .17
I .30 .26 .23 .29 .23 .23 23 .23
H .33 .29 .27 .32 .29 .26 .28 .26
G .36 .32 .30 .34 .32 .29 .30 .29
F .39 .35 .32 .37 .34 .31 .33 .31
19 E .42 .39 .35 .41 .38 .33 .36 .34
D .45 .42 .39 .44 .41 .38 .40 .38
C .47 .44 .41 .45 .42 .40 .41 .39
B .50 .47 .44 .48 .45 .43 .44 .42
A .52 .49 .46 .50 .47 .45 .45 .44
J .23 .19 .17 .23 .18 .16 .17 .16
I .29 .25 .22 .28 .24 .21 .23 .21
H .32 .28 .23 .31 .28 .25 .26 .24
G .36 .32 .29 .34 .30 .27 .29 .26
F .40 .33 .31 .37 .33 .30 .31 .29
20 E .43 .39 .35 .41 .37 .34 .35 .32
D .47 .42 .39 .44 .40 .37 .38 .36
C .49 .45 .41 .46 .42 .39 .40 .38
B .52 .48 .45 .49 .45 .43 .43 .41
A .54 .51 .47 .51 .47 .45 .44 .43
J .29 .24 .22 .29 .23 .20 .22 .20
I .37 .32 .28 .36 .30 .27 .29 .27
H .44 .35 .32 .39 .34 .32 .33 .30
G .46 .41 .37 .43 .38 .34 .37 .33
F .51 .44 .39 .47 .42 .39 .39 .37
21 E .55 .49 .44 .52 .47 .43 .44 .41
D .60 .53 .49 .56 .51 .47 .48 .46
C .62 .57 .52 .58 .53 .50 .51 .48
B .66 .61 .57 .62 57 .54 .54 .52
A .68 .64 .60 .63 .60 .57 .56 .55

٢
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺘﺎﺒﻊ ﺠﺩﻭل ﺭﻗﻡ )‪ :(٣-٢‬ﻤﻌﺎﻤل ﺍﻻﺴﺘﻔﺎﺩﺓ )‪ (u‬ﻟﻭﺤﺩﺍﺕ ﺍﻹﻨﺎﺭﺓ‬

‫‪Ceiling‬‬ ‫‪75 %‬‬ ‫‪50 %‬‬ ‫‪30 %‬‬


‫‪Polar‬‬ ‫‪Walls‬‬ ‫‪50%‬‬ ‫‪30%‬‬ ‫‪10%‬‬ ‫‪50%‬‬ ‫‪30%‬‬ ‫‪10%‬‬ ‫‪30%‬‬ ‫‪10%‬‬
‫‪No‬‬ ‫‪LUMINAIRE‬‬ ‫‪Room‬‬
‫‪curve‬‬ ‫‪Index‬‬
‫‪COEFFICIENT OF UTILIZATION‬‬
‫‪J‬‬ ‫‪.24‬‬ ‫‪.20‬‬ ‫‪.16‬‬ ‫‪.22‬‬ ‫‪.18‬‬ ‫‪.16‬‬ ‫‪.17‬‬ ‫‪.15‬‬
‫‪I‬‬ ‫‪.30‬‬ ‫‪.25‬‬ ‫‪.23‬‬ ‫‪.27‬‬ ‫‪.23‬‬ ‫‪.21‬‬ ‫‪.22‬‬ ‫‪.19‬‬
‫‪H‬‬ ‫‪.33‬‬ ‫‪.29‬‬ ‫‪.26‬‬ ‫‪.31‬‬ ‫‪.27‬‬ ‫‪.24‬‬ ‫‪.23‬‬ ‫‪.22‬‬
‫‪G‬‬ ‫‪.37‬‬ ‫‪.33‬‬ ‫‪.30‬‬ ‫‪.34‬‬ ‫‪.30‬‬ ‫‪.27‬‬ ‫‪.27‬‬ ‫‪.25‬‬
‫‪F‬‬ ‫‪.44‬‬ ‫‪.36‬‬ ‫‪.32‬‬ ‫‪.36‬‬ ‫‪.33‬‬ ‫‪.31‬‬ ‫‪.31‬‬ ‫‪.27‬‬
‫‪22‬‬ ‫‪E‬‬ ‫‪.45‬‬ ‫‪.41‬‬ ‫‪.37‬‬ ‫‪.44‬‬ ‫‪.37‬‬ ‫‪.33‬‬ ‫‪.33‬‬ ‫‪.30‬‬
‫‪D‬‬ ‫‪.49‬‬ ‫‪.44‬‬ ‫‪.40‬‬ ‫‪.44‬‬ ‫‪.40‬‬ ‫‪.37‬‬ ‫‪.36‬‬ ‫‪.33‬‬
‫‪C‬‬ ‫‪.51‬‬ ‫‪.47‬‬ ‫‪.43‬‬ ‫‪.46‬‬ ‫‪.42‬‬ ‫‪.39‬‬ ‫‪.38‬‬ ‫‪.35‬‬
‫‪B‬‬ ‫‪.55‬‬ ‫‪.51‬‬ ‫‪.47‬‬ ‫‪.49‬‬ ‫‪.43‬‬ ‫‪.43‬‬ ‫‪.40‬‬ ‫‪.38‬‬
‫‪A‬‬ ‫‪.57‬‬ ‫‪.53‬‬ ‫‪.50‬‬ ‫‪.51‬‬ ‫‪.47‬‬ ‫‪.45‬‬ ‫‪.42‬‬ ‫‪.40‬‬
‫‪J‬‬ ‫‪.26‬‬ ‫‪.22‬‬ ‫‪.18‬‬ ‫‪.25‬‬ ‫‪.20‬‬ ‫‪.17‬‬ ‫‪.19‬‬ ‫‪.15‬‬
‫‪I‬‬ ‫‪.32‬‬ ‫‪.28‬‬ ‫‪.24‬‬ ‫‪.30‬‬ ‫‪.26‬‬ ‫‪.23‬‬ ‫‪.25‬‬ ‫‪.22‬‬
‫‪H‬‬ ‫‪.35‬‬ ‫‪.31‬‬ ‫‪.29‬‬ ‫‪.33‬‬ ‫‪.30‬‬ ‫‪.28‬‬ ‫‪.29‬‬ ‫‪.27‬‬
‫‪G‬‬ ‫‪.38‬‬ ‫‪.34‬‬ ‫‪.31‬‬ ‫‪.36‬‬ ‫‪.33‬‬ ‫‪.30‬‬ ‫‪.31‬‬ ‫‪.29‬‬
‫‪F‬‬ ‫‪.42‬‬ ‫‪.37‬‬ ‫‪.34‬‬ ‫‪.38‬‬ ‫‪.35‬‬ ‫‪.34‬‬ ‫‪.33‬‬ ‫‪.32‬‬
‫‪23‬‬ ‫‪E‬‬ ‫‪.45‬‬ ‫‪.42‬‬ ‫‪.40‬‬ ‫‪.43‬‬ ‫‪.39‬‬ ‫‪.37‬‬ ‫‪.37‬‬ ‫‪.33‬‬
‫‪D‬‬ ‫‪.49‬‬ ‫‪.46‬‬ ‫‪.43‬‬ ‫‪.46‬‬ ‫‪.43‬‬ ‫‪.40‬‬ ‫‪.40‬‬ ‫‪.39‬‬
‫‪C‬‬ ‫‪.51‬‬ ‫‪.48‬‬ ‫‪.45‬‬ ‫‪.47‬‬ ‫‪.45‬‬ ‫‪.43‬‬ ‫‪.43‬‬ ‫‪.41‬‬
‫‪B‬‬ ‫‪.54‬‬ ‫‪.51‬‬ ‫‪.48‬‬ ‫‪.50‬‬ ‫‪.48‬‬ ‫‪.46‬‬ ‫‪.45‬‬ ‫‪.44‬‬
‫‪A‬‬ ‫‪.55‬‬ ‫‪.53‬‬ ‫‪.50‬‬ ‫‪.52‬‬ ‫‪.49‬‬ ‫‪.48‬‬ ‫‪.46‬‬ ‫‪.45‬‬
‫‪J‬‬ ‫‪.28‬‬ ‫‪.25‬‬ ‫‪.23‬‬ ‫‪.23‬‬ ‫‪.21‬‬ ‫‪.19‬‬ ‫‪.18‬‬ ‫‪.16‬‬
‫‪I‬‬ ‫‪.34‬‬ ‫‪.31‬‬ ‫‪.29‬‬ ‫‪.28‬‬ ‫‪.26‬‬ ‫‪.25‬‬ ‫‪.22‬‬ ‫‪.21‬‬
‫‪H‬‬ ‫‪.37‬‬ ‫‪.34‬‬ ‫‪.33‬‬ ‫‪.31‬‬ ‫‪.29‬‬ ‫‪.28‬‬ ‫‪.25‬‬ ‫‪.24‬‬
‫‪G‬‬ ‫‪.41‬‬ ‫‪.38‬‬ ‫‪.36‬‬ ‫‪.34‬‬ ‫‪.32‬‬ ‫‪.30‬‬ ‫‪.27‬‬ ‫‪.26‬‬
‫‪F‬‬ ‫‪.43‬‬ ‫‪.41‬‬ ‫‪.38‬‬ ‫‪.35‬‬ ‫‪.33‬‬ ‫‪.32‬‬ ‫‪.29‬‬ ‫‪.27‬‬
‫‪24‬‬ ‫‪E‬‬ ‫‪.46‬‬ ‫‪.44‬‬ ‫‪.42‬‬ ‫‪.38‬‬ ‫‪.37‬‬ ‫‪.35‬‬ ‫‪.31‬‬ ‫‪.30‬‬
‫‪D‬‬ ‫‪.50‬‬ ‫‪.47‬‬ ‫‪.45‬‬ ‫‪.41‬‬ ‫‪.39‬‬ ‫‪.37‬‬ ‫‪.33‬‬ ‫‪.32‬‬
‫‪C‬‬ ‫‪.52‬‬ ‫‪.49‬‬ ‫‪.46‬‬ ‫‪.42‬‬ ‫‪.40‬‬ ‫‪.39‬‬ ‫‪.34‬‬ ‫‪.33‬‬
‫‪B‬‬ ‫‪.54‬‬ ‫‪.51‬‬ ‫‪.50‬‬ ‫‪.44‬‬ ‫‪.42‬‬ ‫‪.41‬‬ ‫‪.36‬‬ ‫‪.35‬‬
‫‪A‬‬ ‫‪.56‬‬ ‫‪.53‬‬ ‫‪.51‬‬ ‫‪.46‬‬ ‫‪.43‬‬ ‫‪.42‬‬ ‫‪.37‬‬ ‫‪.36‬‬
‫‪J‬‬ ‫‪.26‬‬ ‫‪.23‬‬ ‫‪.20‬‬ ‫‪.23‬‬ ‫‪.21‬‬ ‫‪.19‬‬ ‫‪.19‬‬ ‫‪.17‬‬
‫‪I‬‬ ‫‪.31‬‬ ‫‪.28‬‬ ‫‪.27‬‬ ‫‪.28‬‬ ‫‪.26‬‬ ‫‪.24‬‬ ‫‪.23‬‬ ‫‪.20‬‬
‫‪H‬‬ ‫‪.35‬‬ ‫‪.32‬‬ ‫‪.30‬‬ ‫‪.31‬‬ ‫‪.28‬‬ ‫‪.27‬‬ ‫‪.26‬‬ ‫‪.24‬‬
‫‪G‬‬ ‫‪.38‬‬ ‫‪.35‬‬ ‫‪.33‬‬ ‫‪.34‬‬ ‫‪.31‬‬ ‫‪.30‬‬ ‫‪.28‬‬ ‫‪.27‬‬
‫‪F‬‬ ‫‪.41‬‬ ‫‪.38‬‬ ‫‪.35‬‬ ‫‪.36‬‬ ‫‪.34‬‬ ‫‪.32‬‬ ‫‪.30‬‬ ‫‪.28‬‬
‫‪25‬‬ ‫‪E‬‬ ‫‪.44‬‬ ‫‪.42‬‬ ‫‪.39‬‬ ‫‪.39‬‬ ‫‪.37‬‬ ‫‪.35‬‬ ‫‪.32‬‬ ‫‪.31‬‬
‫‪D‬‬ ‫‪.48‬‬ ‫‪.45‬‬ ‫‪.42‬‬ ‫‪.42‬‬ ‫‪.39‬‬ ‫‪.38‬‬ ‫‪.34‬‬ ‫‪.33‬‬
‫‪C‬‬ ‫‪.50‬‬ ‫‪.49‬‬ ‫‪.44‬‬ ‫‪.43‬‬ ‫‪.41‬‬ ‫‪.39‬‬ ‫‪.35‬‬ ‫‪.34‬‬
‫‪B‬‬ ‫‪.53‬‬ ‫‪.50‬‬ ‫‪.48‬‬ ‫‪.46‬‬ ‫‪.43‬‬ ‫‪.42‬‬ ‫‪.37‬‬ ‫‪.36‬‬
‫‪A‬‬ ‫‪.54‬‬ ‫‪.52‬‬ ‫‪.50‬‬ ‫‪.47‬‬ ‫‪.45‬‬ ‫‪.43‬‬ ‫‪.39‬‬ ‫‪.37‬‬
‫‪J‬‬ ‫‪.28‬‬ ‫‪.23‬‬ ‫‪.21‬‬ ‫‪.23‬‬ ‫‪.20‬‬ ‫‪.18‬‬ ‫‪.17‬‬ ‫‪.16‬‬
‫‪I‬‬ ‫‪.33‬‬ ‫‪.30‬‬ ‫‪.28‬‬ ‫‪.28‬‬ ‫‪.25‬‬ ‫‪.23‬‬ ‫‪.22‬‬ ‫‪.20‬‬
‫‪H‬‬ ‫‪.36‬‬ ‫‪.33‬‬ ‫‪.31‬‬ ‫‪.30‬‬ ‫‪.28‬‬ ‫‪.26‬‬ ‫‪.24‬‬ ‫‪.23‬‬
‫‪G‬‬ ‫‪.39‬‬ ‫‪.36‬‬ ‫‪.34‬‬ ‫‪.33‬‬ ‫‪.30‬‬ ‫‪.29‬‬ ‫‪.26‬‬ ‫‪.25‬‬
‫‪F‬‬ ‫‪.42‬‬ ‫‪.39‬‬ ‫‪.36‬‬ ‫‪.35‬‬ ‫‪.32‬‬ ‫‪.31‬‬ ‫‪.28‬‬ ‫‪.26‬‬
‫‪26‬‬ ‫‪E‬‬ ‫‪.45‬‬ ‫‪.42‬‬ ‫‪.40‬‬ ‫‪.38‬‬ ‫‪.36‬‬ ‫‪.34‬‬ ‫‪.30‬‬ ‫‪.29‬‬
‫‪D‬‬ ‫‪.48‬‬ ‫‪.45‬‬ ‫‪.43‬‬ ‫‪.40‬‬ ‫‪.38‬‬ ‫‪.36‬‬ ‫‪.32‬‬ ‫‪.31‬‬
‫‪C‬‬ ‫‪.50‬‬ ‫‪.47‬‬ ‫‪.44‬‬ ‫‪.42‬‬ ‫‪.39‬‬ ‫‪.38‬‬ ‫‪.33‬‬ ‫‪.32‬‬
‫‪B‬‬ ‫‪.53‬‬ ‫‪.50‬‬ ‫‪.48‬‬ ‫‪.43‬‬ ‫‪.41‬‬ ‫‪.40‬‬ ‫‪.35‬‬ ‫‪.34‬‬
‫‪A‬‬ ‫‪.54‬‬ ‫‪.52‬‬ ‫‪.49‬‬ ‫‪.45‬‬ ‫‪.43‬‬ ‫‪.41‬‬ ‫‪.36‬‬ ‫‪.33‬‬
‫‪J‬‬ ‫‪.27‬‬ ‫‪.24‬‬ ‫‪.22‬‬ ‫‪.24‬‬ ‫‪.22‬‬ ‫‪.21‬‬ ‫‪.21‬‬ ‫‪.19‬‬
‫‪I‬‬ ‫‪.33‬‬ ‫‪.30‬‬ ‫‪.29‬‬ ‫‪.29‬‬ ‫‪.27‬‬ ‫‪.26‬‬ ‫‪.25‬‬ ‫‪.23‬‬
‫‪H‬‬ ‫‪.36‬‬ ‫‪.34‬‬ ‫‪.32‬‬ ‫‪.32‬‬ ‫‪.30‬‬ ‫‪.029‬‬ ‫‪.28‬‬ ‫‪.26‬‬
‫‪G‬‬ ‫‪.39‬‬ ‫‪.37‬‬ ‫‪.35‬‬ ‫‪.36‬‬ ‫‪.33‬‬ ‫‪.32‬‬ ‫‪.30‬‬ ‫‪.28‬‬
‫‪F‬‬ ‫‪.43‬‬ ‫‪.40‬‬ ‫‪.37‬‬ ‫‪.38‬‬ ‫‪.35‬‬ ‫‪.34‬‬ ‫‪.31‬‬ ‫‪.30‬‬
‫‪27‬‬ ‫‪E‬‬ ‫‪.46‬‬ ‫‪.43‬‬ ‫‪.41‬‬ ‫‪.41‬‬ ‫‪.38‬‬ ‫‪.37‬‬ ‫‪.34‬‬ ‫‪.32‬‬
‫‪D‬‬ ‫‪.50‬‬ ‫‪.46‬‬ ‫‪.44‬‬ ‫‪.43‬‬ ‫‪.41‬‬ ‫‪.39‬‬ ‫‪.36‬‬ ‫‪.35‬‬
‫‪C‬‬ ‫‪.52‬‬ ‫‪.49‬‬ ‫‪.46‬‬ ‫‪.45‬‬ ‫‪.43‬‬ ‫‪.41‬‬ ‫‪.37‬‬ ‫‪.36‬‬
‫‪B‬‬ ‫‪.55‬‬ ‫‪.52‬‬ ‫‪.50‬‬ ‫‪.47‬‬ ‫‪.45‬‬ ‫‪.44‬‬ ‫‪.38‬‬ ‫‪.37‬‬
‫‪A‬‬ ‫‪.56‬‬ ‫‪.54‬‬ ‫‪.52‬‬ ‫‪.49‬‬ ‫‪.47‬‬ ‫‪.45‬‬ ‫‪.40‬‬ ‫‪.38‬‬
‫‪J‬‬ ‫‪.18‬‬ ‫‪.14‬‬ ‫‪.13‬‬ ‫‪.14‬‬ ‫‪.12‬‬ ‫‪.10‬‬ ‫‪.08‬‬ ‫‪.08‬‬
‫‪I‬‬ ‫‪.22‬‬ ‫‪.19‬‬ ‫‪.17‬‬ ‫‪.18‬‬ ‫‪.13‬‬ ‫‪.14‬‬ ‫‪.12‬‬ ‫‪.11‬‬
‫‪H‬‬ ‫‪.25‬‬ ‫‪.22‬‬ ‫‪.20‬‬ ‫‪.20‬‬ ‫‪.18‬‬ ‫‪.16‬‬ ‫‪.14‬‬ ‫‪.13‬‬
‫‪G‬‬ ‫‪.28‬‬ ‫‪.25‬‬ ‫‪.22‬‬ ‫‪.22‬‬ ‫‪.20‬‬ ‫‪.18‬‬ ‫‪.16‬‬ ‫‪.15‬‬
‫‪F‬‬ ‫‪.30‬‬ ‫‪.27‬‬ ‫‪.24‬‬ ‫‪.24‬‬ ‫‪.22‬‬ ‫‪.20‬‬ ‫‪.17‬‬ ‫‪.16‬‬
‫‪28‬‬ ‫‪E‬‬ ‫‪.34‬‬ ‫‪.30‬‬ ‫‪.28‬‬ ‫‪.27‬‬ ‫‪.24‬‬ ‫‪.22‬‬ ‫‪.19‬‬ ‫‪.18‬‬
‫‪D‬‬ ‫‪37‬‬ ‫‪.33‬‬ ‫‪.31‬‬ ‫‪.29‬‬ ‫‪.26‬‬ ‫‪.25‬‬ ‫‪.21‬‬ ‫‪.20‬‬
‫‪C‬‬ ‫‪.39‬‬ ‫‪.36‬‬ ‫‪.33‬‬ ‫‪30‬‬ ‫‪.28‬‬ ‫‪.26‬‬ ‫‪.22‬‬ ‫‪.21‬‬
‫‪B‬‬ ‫‪.42‬‬ ‫‪.39‬‬ ‫‪37‬‬ ‫‪.32‬‬ ‫‪.30‬‬ ‫‪.28‬‬ ‫‪.24‬‬ ‫‪.23‬‬
‫‪A‬‬ ‫‪.44‬‬ ‫‪.41‬‬ ‫‪.39‬‬ ‫‪.34‬‬ ‫‪.32‬‬ ‫‪.30‬‬ ‫‪.23‬‬ ‫‪.24‬‬
‫‪J‬‬ ‫‪.16‬‬ ‫‪.13‬‬ ‫‪.11‬‬ ‫‪.12‬‬ ‫‪.10‬‬ ‫‪.08‬‬ ‫‪.06‬‬ ‫‪.05‬‬
‫‪I‬‬ ‫‪.20‬‬ ‫‪.16‬‬ ‫‪.15‬‬ ‫‪.13‬‬ ‫‪.13‬‬ ‫‪.11‬‬ ‫‪.08‬‬ ‫‪.06‬‬
‫‪H‬‬ ‫‪.23‬‬ ‫‪.20‬‬ ‫‪.17‬‬ ‫‪.17‬‬ ‫‪.14‬‬ ‫‪.13‬‬ ‫‪.10‬‬ ‫‪.08‬‬
‫‪G‬‬ ‫‪.26‬‬ ‫‪.23‬‬ ‫‪.20‬‬ ‫‪.20‬‬ ‫‪.17‬‬ ‫‪.15‬‬ ‫‪.11‬‬ ‫‪.10‬‬
‫‪F‬‬ ‫‪.29‬‬ ‫‪.26‬‬ ‫‪.22‬‬ ‫‪.22‬‬ ‫‪.19‬‬ ‫‪.17‬‬ ‫‪.12‬‬ ‫‪.11‬‬
‫‪29‬‬ ‫‪E‬‬ ‫‪.32‬‬ ‫‪.29‬‬ ‫‪.26‬‬ ‫‪.24‬‬ ‫‪.21‬‬ ‫‪.19‬‬ ‫‪.13‬‬ ‫‪.12‬‬
‫‪D‬‬ ‫‪.36‬‬ ‫‪.32‬‬ ‫‪.30‬‬ ‫‪.26‬‬ ‫‪.24‬‬ ‫‪.22‬‬ ‫‪.15‬‬ ‫‪.14‬‬
‫‪C‬‬ ‫‪.38‬‬ ‫‪.35‬‬ ‫‪.32‬‬ ‫‪.28‬‬ ‫‪.25‬‬ ‫‪.24‬‬ ‫‪.16‬‬ ‫‪.15‬‬
‫‪B‬‬ ‫‪.42‬‬ ‫‪.39‬‬ ‫‪.36‬‬ ‫‪.30‬‬ ‫‪.29‬‬ ‫‪.27‬‬ ‫‪.18‬‬ ‫‪.17‬‬
‫‪A‬‬ ‫‪.44‬‬ ‫‪.41‬‬ ‫‪.39‬‬ ‫‪.33‬‬ ‫‪.30‬‬ ‫‪.29‬‬ ‫‪.19‬‬ ‫‪.18‬‬

‫‪٢‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪ (٤-٢‬ﻤﻨﺴﻭﺏ ﺍﻟﺘﻌﻠﻴﻕ ﻭﺍﻟﻤﺴﺎﻓﺎﺕ ﺍﻟﺒﻴﻨﻴﺔ ﻟﻭﺤﺩﺍﺕ ﺍﻹﻨﺎﺭﺓ‬

‫ﺇﻀﺎﺀﺓ‬ ‫ﺇﻀﺎﺀﺓ‬ ‫ﺇﻀﺎﺀﺓ ﻤﺒﺎﺸﺭﺓ ‪ -‬ﺸﺒﻪ ﻤﺒﺎﺸﺭﺓ‪-‬‬ ‫ﺇﻀﺎﺀﺓ ﻏﻴﺭ ﻤﺒﺎﺸﺭﺓ‬


‫ﻤﺒﺎﺸﺭﺓ‬ ‫ﻤﺒﺎﺸﺭﺓ‬ ‫ﺃﻭ ﺘﻨﺎﺜﺭﻴﻪ‬ ‫ﺃﻭ ﺸﺒﻪ ﻏﻴﺭ ﻤﺒﺎﺸﺭﺓ‬
‫ﺸﺒﻪ ﻤﺭﻜﺯﻩ‬ ‫ﻤﺭﻜﺯﻩ‬
‫ﺃﻗﺼﻰ‬ ‫ﺃﻗﺼﻰ‬ ‫ﺃﻗﺼﻰ‬ ‫ﺍﻟﻤﺴﺎﻓﺔ‬ ‫ﻤﻨﺴﻭﺏ‬ ‫ﺃﻗﺼﻰ‬ ‫ﺘﺩﻟﻰ‬ ‫ﺍﻟﻤﺴﺎﻓﺔ‬ ‫ﺍﺭﺘﻔﺎﻉ‬
‫ﻤﺴﺎﻓﺔ ﺒﻴﻥ‬ ‫ﻤﺴﺎﻓﺔ ﺒﻴﻥ‬ ‫ﻤﺴﺎﻓﺔ‬ ‫ﻤﻥ‬ ‫ﺍﻟﺘﻌﻠﻴﻕ‬ ‫ﻤﺴﺎﻓﺔ‬ ‫ﺍﻟﻭﺤﺩﺓ‬ ‫ﻤﻥ‬ ‫ﺍﻟﺴﻘﻑ‬
‫ﺍﻟﻭﺤﺩﺍﺕ‬ ‫ﺍﻟﻭﺤﺩﺍﺕ‬ ‫ﺒﻴﻥ‬ ‫ﺍﻟﺤﻭﺍﺌﻁ‬ ‫)ﻡ(‬ ‫ﺒﻴﻥ‬ ‫)ﻡ(‬ ‫ﺍﻟﺤﻭﺍﺌﻁ‬ ‫)ﻡ(‬
‫)ﻡ(‬ ‫)ﻡ(‬ ‫ﺍﻟﻭﺤﺩﺍﺕ‬ ‫)ﻡ(‬ ‫ﺍﻟﻭﺤﺩﺍﺕ‬ ‫)ﻡ(‬
‫)ﻡ(‬ ‫)ﻡ(‬
‫‪٠.٧٥‬‬ ‫‪١.٦٥‬‬ ‫‪٢.٢٥‬‬ ‫‪٠.٩٠‬‬ ‫‪٢.٤٠‬‬ ‫‪٢.٧٠‬‬ ‫‪–٠.٣٠‬‬ ‫‪٠.٩٠‬‬ ‫‪٢.٤٠‬‬
‫‪٠.٩٠‬‬
‫‪٠.٩٠‬‬ ‫‪١.٨٠‬‬ ‫‪٢.٧٠‬‬ ‫‪٠.٩٠‬‬ ‫‪٢.٧٠‬‬ ‫‪٣.١٥‬‬ ‫‪-٠.٤٥‬‬ ‫‪٠.٩٠‬‬ ‫‪٢.٧٠‬‬
‫‪٠.٩٠‬‬
‫‪١.٢٠‬‬ ‫‪٢.١٠‬‬ ‫‪٣.١٥‬‬ ‫‪١.٠٥‬‬ ‫‪٣.٠٠‬‬ ‫‪٣.٧٥‬‬ ‫‪-٠.٦٠‬‬ ‫‪١.٠٥‬‬ ‫‪٣.٠٠‬‬
‫‪١.٣٥‬‬ ‫‪٢.٤٠‬‬ ‫‪٣.٦٠‬‬ ‫‪١.٠٥‬‬ ‫‪٣.٣٠‬‬ ‫‪٤.٠٥‬‬ ‫‪٠.٩٠‬‬ ‫‪١.٠٥‬‬ ‫‪٣.٣٠‬‬
‫‪١.٥٠‬‬ ‫‪٢.٧٠‬‬ ‫‪٤.٠٥‬‬ ‫‪١.٢٠‬‬ ‫‪٣.٦٠‬‬ ‫‪٤.٥٠‬‬ ‫‪-٠.٧٥‬‬ ‫‪١.٢٠‬‬ ‫‪٣.٦٠‬‬
‫‪١.٢٠‬‬
‫‪١.٦٥‬‬ ‫‪٣.٠٠‬‬ ‫‪٤.٥٠‬‬ ‫‪١.٢٠‬‬ ‫‪٣.٩٠‬‬ ‫‪٥.١٠‬‬ ‫‪١.٢٠‬‬ ‫‪٣.٩٠‬‬
‫‪-٠.٩٠‬‬
‫‪١.٨٠‬‬ ‫‪٣.٣٠‬‬ ‫‪٤.٩٥‬‬ ‫‪١.٥٠‬‬ ‫‪٤.٢٠‬‬ ‫‪٥.٧٠‬‬ ‫‪١.٥٠‬‬ ‫‪٤.٢٠‬‬
‫‪١.٢٠‬‬
‫‪١.٩٥‬‬ ‫‪٣.٦٠‬‬ ‫‪٥.٤٠‬‬ ‫‪١.٥٠‬‬ ‫‪٤.٥٠‬‬ ‫‪٦.٠٠‬‬ ‫‪١.٥٠‬‬ ‫‪٤.٥٠‬‬
‫‪٢.١٠‬‬ ‫‪٣.٩٠‬‬ ‫‪٦.٠٠‬‬ ‫‪١.٨٠‬‬ ‫‪٤.٨٠‬‬ ‫‪٦.٦٠‬‬ ‫‪-١.٢٠‬‬ ‫‪١.٨٠‬‬ ‫‪٤.٨٠‬‬
‫‪٢.٤٠‬‬ ‫‪٤.٦٥‬‬ ‫‪٦.٦٠‬‬ ‫‪١.٨٠‬‬ ‫‪٥.٤٠‬‬ ‫‪٧.٢٠‬‬ ‫‪١.٥٠‬‬ ‫‪١.٨٠‬‬ ‫‪٥.٤٠‬‬
‫‪٢.٧٠‬‬ ‫‪٥.٢٥‬‬ ‫‪٧.٥٠‬‬ ‫‪٢.١٠‬‬ ‫‪ ٦.٠٠‬ﺃﻭ‬ ‫‪٨.٤٠‬‬ ‫‪-١.٢٠‬‬ ‫‪٢.١٠‬‬ ‫ﺃﻜﺜﺭ ﻤﻥ‬
‫ﺃﻜﺜﺭ‬ ‫‪١.٨٠‬‬ ‫‪٥.٤٠‬‬

‫‪٢‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻤﺜﺎل‪:‬‬

‫ﺼﺎﻟﺔ ﺭﺴﻡ ﺫﺍﺕ ﺃﺒﻌﺎﺩ ‪٣.٢٠×٧×١٥‬ﻡ ﻤﻁﻠﻭﺏ ﺇﻀﺎﺀﺘﻬﺎ ﺒﺎﺴـﺘﺨﺩﺍﻡ ﻤﺠﻤﻭﻋـﺔ ﻤـﻥ‬
‫ﻜﺸﺎﻓﺎﺕ ﻓﻠﻭﺭﻴﺔ ﻁﺭﺍﺯ ﻟﻭﻓﺭ ‪١٢٠‬ﺴﻡ ‪ ٢‬ﻟﻤﺒـﺔ ‪ ٤٠‬ﻭﺍﺕ‪ .‬ﺍﺤﺴـﺏ ﻋـﺩﺩ ﺍﻟﻜﺸـﺎﻓﺎﺕ‬
‫ﺍﻟﻤﻁﻠﻭﺒﺔ ﻭﺘﻭﺯﻴﻌﻬﺎ ﻭﻗﻴﻤﺔ ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﻐﺫﻯ ﻟﺩﻭﺍﺌﺭ ﺍﻹﻨﺎﺭﺓ ؟‬

‫ﺍﻟﺤل‪:‬‬

‫ﻤﻥ ﺠﺩﻭل ﻤﻌﺎﻴﻴﺭ ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ )‪ (١-٢‬ﻨﺠﺩ ﺃﻥ ﺸﺩﺓ ﺍﻹﻀﺎﺀﺓ ﺍﻟﻤﻁﻠﻭﺒﺔ ﻟﺼﺎﻟﺔ ﺍﻟﺭﺴـﻡ‬
‫‪ ٥٠٠‬ﻟﻭﻜﺱ‪.‬‬

‫ﺤﻴﺙ ﺃﻥ ﻜﺸﺎﻓﺎﺕ ﺍﻟﻠﻭﻓﺭ ﻤﻥ ﻨﻭﻉ ﺍﻹﻀﺎﺀﺓ ﺍﻟﻤﺒﺎﺸﺭﺓ ﻭﺒﺎﻋﺘﺒﺎﺭ ﺃﻥ ﺍﺭﺘﻔـﺎﻉ ﺘﺭﺍﺒﻴـﺯﺍﺕ‬


‫ﺍﻟﺭﺴﻡ )‪١‬ﻡ( ﻓﺈﻥ ﻤﻨﺴﻭﺏ ﺘﻌﻠﻴﻕ ﺍﻟﻜﺸﺎﻓﺎﺕ ﻓﻭﻕ ﺴﻁﺢ ﺍﻟﺘﺸﻐﻴل ﻴﻜـﻭﻥ ‪٢.٢٠‬ﻡ‪ .‬ﻭﺒـﺫﻟﻙ‬
‫ﻴﻤﻜﻥ ﺇﻴﺠﺎﺩ ﻤﻌﺎﻤل ﺍﻟﺤﺠﺭﺓ )‪ (Ri‬ﻤﻥ ﺍﻟﺠﺩﻭل )‪ (٢-٢‬ﺒﺩﻻﻟﺔ ﻁﻭل ﻭﻋـﺭﺽ ﺍﻟﺼـﺎﻟﺔ‬
‫ﻭﻨﺠﺩ ﺃﻥ ﻤﻌﺎﻤل ﺍﻟﺤﺠﺭﺓ ﻫﻭ )‪.(C‬‬

‫ﺒﻔﺭﺽ ﺃﻥ ﻤﻌﺎﻤل ﺇﻨﻌﻜﺎﺱ ﺍﻟﻀﻭﺀ ﻤﻥ ﺍﻟﺤﻭﺍﺌﻁ ‪ ٠.٥‬ﻭﻤﻥ ﺍﻟﺴﻘﻑ ‪ ، ٠.٧٥‬ﻴﻤﻜﻥ ﺇﻴﺠﺎﺩ‬


‫ﻤﻌﺎﻤل ﺍﻻﺴﺘﻔﺎﺩﺓ ﻤﻥ ﺍﻟﺠﺩﻭل )‪ (٣-٢‬ﻟﻠﻜﺸﺎﻑ ﺍﻟﻠﻭﻓﺭ ﻭﻫﻭ ﻴﺴﺎﻭﻯ ‪.٠.٥٧‬‬

‫ﻭﻤﻥ ﺤﻴﺙ ﺃﻥ ﻜﻔﺎﺀﺓ ﺍﻟﻠﻤﺒﺎﺕ ﺍﻟﻔﻠﻭﺭﻴﺔ ﻫﻰ ‪ ٨٠‬ﻟﻴـﻭﻤﻥ ‪ /‬ﻭﺍﺕ‪ ،‬ﻟـﺫﺍ ﻴﻜـﻭﻥ ﺍﻟﻔـﻴﺽ‬
‫ﺍﻟﻀﻭﺌﻰ ﻤﻥ ﺍﻟﻜﺸﺎﻑ ﺍﻟﻔﻠﻭﺭﻯ ‪ ٢‬ﻟﻤﺒﺔ ﻗﺩﺭﻩ ‪ ٤٠‬ﻭﺍﺕ ﻫﻭ ‪ ٣٢٠٠‬ﻟﻴﻭﻤﻥ‪.‬‬

‫ﻭﺒﻔﺭﺽ ﺃﻥ ﻤﻌﺎﻤل ﺍﻟﺼﻴﺎﻨﺔ ‪ ٠.٨‬ﻴﻤﻜﻥ ﺇﻴﺠﺎﺩ ﻋﺩﺩ ﺍﻟﻜﺸﺎﻓﺎﺕ ﻤﻥ ﺍﻟﻤﻌﺎﺩﻟﺔ )‪(٣-٢‬‬


‫) ‪500 × (15 × 7‬‬
‫= ‪N‬‬
‫‪0 . 57 × 0 . 8 × 40 × 80‬‬ ‫)‪(2-3‬‬
‫∴‬ ‫‪N = 17 . 98 ~ 18‬‬

‫ﻭﻴﻤﻜﻥ ﺘﻭﺯﻴﻌﻬﺎ ﻋﻠﻰ ﺃﺴﺎﺱ ‪ ٦‬ﺼﻔﻭﻑ‪ ،‬ﺒﻭﺍﻗﻊ ‪ ٣‬ﻜﺸﺎﻓﺎﺕ ﻓﻰ ﺍﻟﺼﻑ‪ ،‬ﻟﺘﻜـﻭﻥ ﻨﺴـﺒﺔ‬
‫ﻋﺩﺩ ﺍﻟﻜﺸﺎﻓﺎﺕ ﻓﻰ ﺍﻻﺘﺠﺎﻩ ﺍﻟﻁﻭﻟﻰ ‪ :‬ﻋﺩﺩ ﺍﻟﻜﺸﺎﻓﺎﺕ ﻓﻰ ﺍﻻﺘﺠﺎﻩ ﺍﻟﻌﺭﻀـﻰ ﻫـﻭ ‪١ : ٢‬‬
‫ﻭﻫﻰ ﺘﺴﺎﻭﻯ ﺘﻘﺭﻴﺒﺎﹰ ﻨﺴﺒﺔ ﺍﻟﻁﻭل ‪ :‬ﺍﻟﻌﺭﺽ )‪.(٧ : ١٥‬‬

‫ﻭﻤﻥ ﺍﻟﺠﺩﻭل )‪ (٤-٢‬ﻨﺠﺩ ﺃﻥ ﺍﻟﻤﺴﺎﻓﺔ ﺒﻴﻥ ﺍﻟﻜﺸﺎﻓﺎﺕ ﻭﺍﻟﺤﻭﺍﺌﻁ ﻟﻺﻀﺎﺀﺓ ﺍﻟﻤﺒﺎﺸﺭﺓ ﻋﻨـﺩ‬
‫ﻤﻨﺴﻭﺏ ﺘﻌﻠﻴﻕ ‪٢.٤٠‬ﻡ ﻫﻭ ﺤﻭﺍﻟﻰ ‪٠.٩٠‬ﻡ‪.‬‬

‫ﻭﻴﻭﻀﺢ ﺸﻜل )‪ (٣-٢‬ﺭﺴﻡ ﺘﺨﻁﻴﻁﻰ ﻟﺘﻭﺯﻴﻊ ﺍﻟﻜﺸﺎﻓﺎﺕ‪.‬‬

‫‪٢‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻭﺒﺎﻋﺘﺒﺎﺭ ﺃﻥ ﺍﻟﻘﺩﺭﺓ ﺍﻟﻤﻔﻘﻭﺩﺓ ﻓﻰ ﺍﻟﻤﻠﻔﻴﻥ ﺍﻟﻜﺎﺒﺤﻴﻥ ﻟﻜل ﻜﺸﺎﻑ ﻫﻰ )‪ ١١‬ﻭﺍﺕ(‪ ،‬ﺘﺼـﺒﺢ‬


‫ﺍﻟﻘﺩﺭﺓ ﺍﻟﻤﺴﺘﻬﻠﻜﺔ ﻟﻜل ﻜﺸﺎﻑ ﻫﻰ ‪ ٩١‬ﻭﺍﺕ‪.‬‬

‫ﺒﺘﻭﺼﻴل ﻜل ‪ ٦‬ﻜﺸﺎﻓﺎﺕ ﻋﻠﻰ ﻁﻭﺭ ﻭﺍﺤﺩ ﻴﻜﻭﻥ ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﻐﺫﻯ ﻟﻬﺫﻩ ﺍﻟﺩﺍﺌﺭﺓ‪:‬‬
‫‪6 × 91‬‬
‫=‪I‬‬ ‫‪= 3.54 A‬‬
‫‪0.7 × 220‬‬

‫وذﻟﻚ ﺑﺎﻋﺘﺒﺎر أن ﻣﻌﺎﻣﻞ اﻟﻘﺪرة ﻟﻠﻜﺸﺎف ﺑﻤﻜﺜﻒ ھﻮ ‪.٠.٧‬‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(٣-٢‬ﺭﺴﻡ ﺘﺨﻁﻴﻁﻰ ﻟﺘﻭﺯﻴﻊ ﺍﻟﻜﺸﺎﻓﺎﺕ‬

‫‪٢‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺘﺼﻤﻴﻡ ﺃﻋﻤﺎل ﺍﻟﻘﻭﻯ‬ ‫‪٢-٢‬‬

‫ﻋﺎﻡ‪:‬‬

‫)‪ (١‬ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ ﺍﻟﻤﻘﺎﺒﺱ ﺍﻟﻤﺴﺘﻌﻤﻠﺔ ﻓﻰ ﺍﻟﺘﻤﺩﻴﺩﺍﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴـﺔ ﻟﻠﻤﺒـﺎﻨﻰ ﻟﺘﻐﺫﻴـﺔ‬


‫ﺍﻷﺠﻬﺯﺓ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻤﻁﺎﺒﻘﺔ ﻟﻠﻤﻭﺍﺼﻔﺎﺕ ﺍﻟﻜﻬﺭﻭﺘﻘﻨﻴﺔ ﺍﻟﺩﻭﻟﻴـﺔ ﺭﻗـﻡ )‪(IEC 309‬‬
‫ﻭﺭﻗﻡ )‪.(IEC 889‬‬

‫)‪ (٢‬ﻴﺠﺏ ﺃﻥ ﻴﺤﻘﻕ ﺍﻟﻤﻘﺒﺱ ﺘﻼﻤﺴﺎﹰ ﻗﻭﻴﺎﹰ ﻤﻴﻜﺎﻨﻴﻜﻴﺎﹰ ﻭﻜﻬﺭﺒﺎﺌﻴﺎﹰ ﻤـﻊ ﺃﺼـﺎﺒﻊ ﺍﻟﻘـﺎﺒﺱ‬
‫ﺍﻟﻤﻨﺎﺴﺏ ﻟﻪ‪.‬‬

‫)‪ (٣‬ﻴﺠﺏ ﺃﻥ ﻴﻜﻭﻥ ﻤﻘﺎﺱ ﻓﺘﺤﺔ ﻗﻁﺏ ﺍﻷﺭﻀﻰ ﻓﻰ ﺍﻟﻤﻘﺒﺱ ﻟﻠﺩﻭﺍﺌﺭ ﺃﺤﺎﺩﻴﺔ ﺍﻷﻁـﻭﺍﺭ‬
‫ﺃﻭ ﺜﻼﺜﻴﺔ ﺍﻷﻁﻭﺍﺭﻤﺨﺘﻠﻔﺎﹰ ﻋﻥ ﻤﻘﺎﺱ ﻓﺘﺤﺔ ﻁﺭﻑ ﺍﻟﺘﻼﻤﺱ ﺍﻟﻤﻜﻬﺭﺏ ﻭﻓﺘﺤﺔ ﻁﺭﻑ‬
‫ﺍﻟﺘﻼﻤﺱ ﻟﻠﻁﺭﻑ ﺍﻟﻤﺘﻌﺎﺩل ﻁﺒﻘﺎﹰ ﻟﻤﺎ ﺘﻨﺹ ﻋﻠﻴﻪ ﺍﻟﻤﻭﺍﺼﻔﺎﺕ ﺍﻟﻘﻴﺎﺴﻴﺔ ﺍﻟﺒﺭﻴﻁﺎﻨﻴـﺔ‬
‫ﺭﻗﻡ )‪.(BS 4343‬‬

‫)‪ (٤‬ﻴﺠﺏ ﺃﻥ ﻴﺠﻬﺯ ﺍﻟﻤﻘﺒﺱ ﺒﻭﺴﻴﻠﺔ ﺒﺤﻴﺙ ﻴﻼﻤﺱ ﻁﺭﻑ ﺍﻷﺭﻀﻰ ﻓﻴﻪ ﺠﺴـﻡ ﺍﻟﻌﻠﺒـﺔ‬
‫ﺍﻟﻤﻌﺩﻨﻴﺔ ﺍﻟﺘﻰ ﻴﺭﻜﺏ ﺒﻬﺎ‪.‬‬

‫)‪ (٥‬ﻴﺠﺏ ﺃﻥ ﻴﻜﻭﻥ ﻤﻘﺎﺱ ﻗﺎﻋﺩﺓ ﺍﻟﻤﻘﺒﺱ ﺍﻟﻤﺤﺘﻭﻴﺔ ﻋﻠﻰ ﺃﻁﺭﺍﻑ ﺍﻟـﺘﻼﻤﺱ ﺒﺎﻷﺒﻌـﺎﺩ‬
‫ﺍﻟﻤﻨﺎﺴﺒﺔ ﺒﺤﻴﺙ ﻻ ﺘﻘل ﺍﻟﻤﺴﺎﻓﺔ ﺍﻟﺒﻴﻨﻴﺔ ﺒﻴﻥ ﺘﻠﻙ ﺍﻟﻘﺎﻋﺩﺓ ﻭﺠـﺩﺭﺍﻥ ﺍﻟﻌﻠﺒـﺔ ﺍﻟﺘـﻰ‬
‫ﺴﺘﺭﻜﺏ ﺒﻬﺎ ﻋﻥ ‪٦.٣٥‬ﻤﻡ ﻭﻻ ﺘﻘل ﺍﻟﻤﺴﺎﻓﺔ ﺍﻟﺒﻴﻨﻴﺔ ﺒﻴﻥ ﺘﻠﻙ ﺍﻟﻘﺎﻋﺩﺓ ﻭﻗﺎﻉ ﺍﻟﻌﻠﺒـﺔ‬
‫ﻋﻥ ‪١٤‬ﻤﻡ‪.‬‬

‫)‪ (٦‬ﻴﻜﻭﻥ ﻭﺠﻪ ﻋﻠﺒﺔ ﺍﻟﻤﻘﺒﺱ ﻤﺼﻨﻭﻋﺎﹰ ﻤـﻥ ﻤﺎﺩﺓ ﻋﺎﺯﻟـﺔ ﺼﻠﺒﺔ ﻏﻴﺭ ﻗﺎﺒﻠﺔ ﻟﻼﺸﺘﻌﺎل‬
‫ﻭﻻ ﺘﻠﻴﻥ ﻋﻨﺩ ﺍﺭﺘﻔﺎﻉ ﺩﺭﺠﺔ ﺤﺭﺍﺭﺘﻬﺎ ﺇﻟﻰ ‪ْ ٨٥‬ﻡ‪ ،‬ﻭﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ ﻏﻴـﺭ ﻗﺎﺒﻠـﺔ‬
‫ﻟﻠﺘﺸﻭﻩ ﻭﺍﻻﻨﺒﻌﺎﺝ ﻋﻨﺩ ﺍﻻﺴﺘﻌﻤﺎل ﺍﻟﻌﺎﺩﻯ‪.‬‬

‫)‪ (٧‬ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ ﺍﻟﻤﻘﺎﺒﺱ ﺍﻟﻤﻔﺭﺩﺓ ﺃﻭ ﺍﻟﻤﺯﺩﻭﺠﺔ ﻤﻥ ﺍﻟﻨﻭﻉ ﺫﻯ ﺍﻟﻘﻁﺒـﻴﻥ ﻭﺍﻟﻘﻁـﺏ‬


‫ﺍﻟﻤﺅﺭﺽ‪.‬‬

‫)‪ (٨‬ﻴﺠﺏ ﺃﻥ ﻴﻜﻭﻥ ﻤﺒﻴﻨﺎﹰ ﺃﻭ ﻤﻭﻀﺤﺎﹰ ﻋﻠﻰ ﺍﻟﻤﻘﺎﺒﺱ ﻜﻼﹰ ﻤﻥ ﺍﻟﻘﻴﻤـﺔ ﺍﻟﻤﻘﻨﻨـﺔ ﻟﻠﺘﻴـﺎﺭ‬
‫ﻭﺍﻟﺠﻬﺩ ﺒﺤﺭﻭﻑ ﺒﺎﺭﺯﺓ‪.‬‬

‫‪٢‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫)‪ (٩‬ﻓﻰ ﺤﺎﻟﺔ ﺘﺭﻜﻴﺏ ﻤﻘﺎﺒﺱ ﻟﺘﻐﺫﻴﺔ ﺃﺠﻬـﺯﺓ ﺫﺍﺕ ﺃﻏﻠﻔـﺔ ﻤﻌﺩﻨﻴـﺔ ﻤﺜـل ﺍﻟﻐﺴـﺎﻻﺕ‬
‫ﻭﺍﻟﺴﺨﺎﻨﺎﺕ ﻭﻤﺎ ﻴﻤﺎﺜﻠﻬﺎ‪ ،‬ﻴﺭﺍﻋﻰ ﺃﻥ ﻴﻜﻭﻥ ﻟﻬﺎ ﻗﻁﺏ ﺘﺄﺭﻴﺽ ﺇﻀﺎﻓﻰ ﻴﻭﻓﺭ ﺍﻟﻭﻗﺎﻴﺔ‬
‫ﻀﺩ ﺘﻜﻬﺭﺏ ﺍﻷﻏﻠﻔﺔ ﺍﻟﻤﻌﺩﻨﻴﺔ‪.‬‬

‫)‪ (١٠‬ﻴﺭﺍﻋﻰ ﺃﻥ ﺘﻜﻭﻥ ﺍﻟﻤﻘﺎﺒﺱ ﺍﻟﻤﺭﻜﺒﺔ ﻓﻰ ﺍﻷﺭﻀﻴﺎﺕ ﻤﻥ ﺍﻟﻨـﻭﻉ ﺍﻟﺼـﺎﻤﺩ ﻟﻠﻤﻴـﺎﻩ‬


‫ﻟﻀﻤﺎﻥ ﺃﻻ ﻴﻨﺘﺞ ﻋﻨﻬﺎ ﺨﻁﺭﺍﹰ ﺃﻭ ﺘﻠﻔﺎﹰ ﻟﻠﻌﺯل ﻋﻨﺩ ﻏﺴل ﺍﻷﺭﻀﻴﺎﺕ‪.‬‬

‫)‪ (١١‬ﻴﺭﺍﻋﻰ ﺃﻥ ﺘﻜﻭﻥ ﺍﻟﻤﻘﺎﺒﺱ ﺍﻟﻤﺭﻜﺒﺔ ﺨﺎﺭﺝ ﺍﻟﻤﺒﻨﻰ ﻤﻥ ﺍﻟﻨﻭﻉ ﺍﻟﺼﺎﻤﺩ ﻟﻠﻤﻴﺎﻩ ﺴـﻭﺍﺀ‬
‫ﻜﺎﻨﺕ ﺨﺎﺭﺝ ﺃﻭ ﺩﺍﺨل ﺍﻟﺤﺎﺌﻁ ﻤﺯﻭﺩﺓ ﺒﻐﻁﺎﺀ ﻤﺤﻜﻡ ﻟﻤﻨﻊ ﻭﺼـﻭل ﻤﻴـﺎﻩ ﺍﻟﻤﻁـﺭ‬
‫ﻟﻸﻗﻁﺎﺏ ﺍﻟﻤﻜﻬﺭﺒﺔ‪.‬‬

‫ﺍﺸﺘﺭﺍﻁﺎﺕ ﺘﺼﻤﻴﻤﻴﺔ ﻷﻋﻤﺎل ﺍﻟﻘﻭﻯ‪:‬‬

‫)‪ (١‬ﺇﺫﺍ ﻤﺎ ﻜﺎﻨﺕ ﺍﻟﻤﻘﺎﺒﺱ ﻋﺭﻀﻪ ﻟﻠﺘﻠﻑ ﺍﻟﻤﻴﻜﺎﻨﻴﻜﻰ‪ ،‬ﻓﺈﻨﻪ ﻴﺠﺏ ﻭﻀﻌﻬﺎ ﺩﺍﺨل ﺃﻏﻠﻔـﺔ‬
‫ﻤﻌﺩﻨﻴﺔ ﻤﺘﻴﻨﺔ ﻤﺅﺭﻀﺔ‪.‬‬

‫)‪ (٢‬ﻋﻨﺩ ﺍﺴﺘﺨﺩﺍﻡ ﺠﻬﻭﺩ ﻤﺨﺘﻠﻔﺔ ﺃﻭ ﺃﻨﻭﺍﻉ ﻤﺨﺘﻠﻔﺔ ﻤﻥ ﺍﻟﺘﻴﺎﺭ‪ ،‬ﻴﺭﺍﻋﻰ ﺃﻥ ﺘﻜﻭﻥ ﻤﻘﺎﺒﺱ‬
‫ﻜل ﺠﻬﺩ ﺃﻭ ﻨﻭﻉ ﻤﺨﺘﻠﻔﺔ ﺘﻤﺎﻤﺎﹰ ﻋﻥ ﺍﻷﺨﺭﻴﺎﺕ ﺤﺘﻰ ﻻ ﻴﺤﺩﺙ ﺨﻁﺄ ﻓﻰ ﺍﺴـﺘﺨﺩﺍﻡ‬
‫ﻗﻭﺍﺒﺱ ﺃﺤﺩ ﺍﻷﻨﻭﺍﻉ ﻟﻨﻭﻉ ﺁﺨﺭ‪.‬‬

‫)‪ (٣‬ﻴﺭﺍﻋﻰ ﻋﻨﺩ ﺍﺴﺘﻌﻤﺎل ﻋﺩﺩ ﻤﻥ ﻤﺂﺨﺫ ﺍﻟﻘﻭﻯ ﺒﺤﺠﺭﺓ ﻤﺴﺎﺤﺘﻬﺎ ‪ ٥٠‬ﻤﺘﺭﺍﹰ ﻤﺭﺒﻌـﺎﹰ ﺃﻭ‬
‫ﺃﻗل ﻤﻭﺯﻋﺔ ﻋﻠﻰ ﺃﻜﺜﺭ ﻤﻥ ﺩﺍﺌﺭﺓ ﻓﺭﻋﻴﺔ ﻨﻬﺎﺌﻴﺔ‪ ،‬ﺃﻥ ﺘﻜﻭﻥ ﺠﻤﻴﻌﻬﺎ ﻋﻠـﻰ ﻨﻔـﺱ‬
‫ﻁﻭﺭ ﺍﻟﺘﻴﺎﺭ ﻭﺫﻟﻙ ﻟﻤﻨﻊ ﺍﺤﺘﻤﺎل ﻭﺠﻭﺩ ﺘﻴﺎﺭ ﺒﺠﻬﺩ ‪ ٣٨٠‬ﻓﻭﻟﺕ ﺒـﻴﻥ ﺃﻯ ﺴـﻠﻜﻴﻥ‬
‫ﻤﻭﺼﻠﻴﻥ ﺇﻟﻰ ﻤﺄﺨﺫﻴﻥ ﺒﻨﻔﺱ ﺍﻟﺤﺠﺭﺓ‪.‬‬

‫ﻭﻓﻰ ﺤﺎﻟﺔ ﺍﻟﺤﺠﺭﺍﺕ ﺫﺍﺕ ﺍﻟﻤﺴﺎﺤﺔ ﺃﻜﺒﺭ ﻤﻥ ﺫﻟﻙ‪ ،‬ﺇﺫﺍ ﺍﻗﺘﻀﻰ ﺍﻷﻤـﺭ ﻀـﺭﻭﺭﺓ‬
‫ﺘﻭﺯﻴﻊ ﺍﻟﻤﺂﺨﺫ ﻋﻠﻰ ﺩﻭﺍﺌﺭ ﻓﺭﻋﻴﺔ ﻨﻬﺎﺌﻴﺔ ﺘﻐﺫﻯ ﻤﻥ ﺃﻁﻭﺍﺭ ﻤﺨﺘﻠﻔﺔ ﻤـﻥ ﻤﺼـﺩﺭ‬
‫ﺍﻟﺘﻴﺎﺭ‪ ،‬ﻴﺭﺍﻋﻰ ﺘﺭﻜﻴﺏ ﺍﻟﻤﺂﺨﺫ ﺒﺤﻴﺙ ﻴﺨﺩﻡ ﻜل ﻁﻭﺭ ﻤﻥ ﺃﻁﻭﺍﺭ ﺍﻟﺘﻴـﺎﺭ ﻤﺴـﺎﺤﺔ‬
‫ﻤﺴﺘﻘﻠﺔ ﺒﺎﻟﺤﺠﺭﺓ ﻭﺫﻟﻙ ﻟﺘﻔﺎﺩﻯ ﺃﻥ ﻴﻠﻤﺱ ﺸﺨﺹ ﺠﻬﺎﺯﻴﻥ ﻴﻐﺫﻯ ﻜل ﻤﻨﻬﻤـﺎ ﻤـﻥ‬
‫ﻤﺄﺨﺫ ﻋﻠﻰ ﻁﻭﺭ ﻴﺨﺎﻟﻑ ﺍﻟﻁﻭﺭ ﺍﻟﻤﻐﺫﻯ ﻟﻠﺠﻬﺎﺯ ﺍﻵﺨﺭ‪ ،‬ﻭﻓﻰ ﻫﺫﻩ ﺍﻟﺤﺎﻟـﺔ ﻴﺠـﺏ‬
‫ﺘﻤﻴﻴﺯ ﻏﻁﺎﺀ ﻜل ﻤﺄﺨﺫ ﺒﻌﻼﻤﺔ ﻁﻭﺭ ﺍﻟﺘﻐﺫﻴﺔ‪.‬‬

‫)‪ (٤‬ﻴﺭﺍﻋﻰ ﻓﻰ ﺤﺎﻟﺔ ﺍﺴﺘﺨﺩﺍﻡ ﻤﺂﺨﺫ ﻗﻭﻯ ﺫﺍﺕ ﺴﻌﺔ ‪١٦‬ﺃﻤﺒﻴﺭ ﻓﺄﻜﺜﺭ ﺃﻥ ﺘﻭﺼـل ﻜـل‬
‫ﻤﻨﻬﺎ ﻤﺒﺎﺸﺭﺓ ﺒﺩﺍﺌﺭﺓ ﻨﻬﺎﺌﻴﺔ ﺨﺎﺼﺔ ﺒﻬﺎ ﺇﻟﻰ ﻟﻭﺤﺎﺕ ﺍﻟﻤﺼﺎﻫﺭ ﺃﻭ ﺍﻟﻘﻭﺍﻁﻊ‪ ،‬ﻭﺇﺫﺍ ﻤﺎ‬

‫‪٢‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻜﺎﻨﺕ ﻫﻨﺎﻙ ﻀﺭﻭﺭﺓ ﻟﺘﻭﺼﻴل ﺃﻜﺜﺭ ﻤﻥ ﻤﺨﺭﺝ ﻤﻥ ﻫﺫﺍ ﺍﻟﻨﻭﻉ ﻋﻠﻰ ﺩﺍﺌﺭﺓ ﻭﺍﺤـﺩﺓ‬
‫ﻓﻰ ﻤﻜﺎﻥ ﻭﺍﺤﺩ ﻴﺴﺘﺨﺩﻡ ﻓﻴﻪ ﺠﻬﺎﺯ ﻭﺍﺤﺩ ﻤﺘﻨﻘل ﻓﻼ ﻴﺠﺏ ﺃﻥ ﻴﺯﻴﺩ ﻋﺩﺩ ﺍﻟﻤﺨـﺎﺭﺝ‬
‫ﻋﻥ ﺃﺭﺒﻌﺔ‪.‬‬

‫)‪ (٥‬ﻴﺭﺍﻋﻰ ﻋﻨﺩ ﺍﺴﺘﺨﺩﺍﻡ ﻤﻘﺎﺒﺱ ﺃﻭ ﻤﺄﺨﺫ ﻗﻭﻯ ﻋﻠﻰ ﺠﺎﻨﺒﻰ ﺤﺎﺌﻁ ﺃﻥ ﺘﺘـﺭﻙ ﻤﺴـﺎﻓﺔ‬
‫ﺃﻓﻘﻴﺔ ﻓﻴﻤﺎ ﺒﻴﻨﻬﻤﺎ ﻤﻘﺩﺍﺭﻫﺎ ‪١٥٠‬ﻤﻡ ﻋﻠﻰ ﺍﻷﻗل ﻟﺘﺠﻨﺏ ﺍﻨﺘﻘﺎل ﺍﻟﺼﻭﺕ ﻤﻥ ﺨﻼﻟﻬﺎ‪.‬‬

‫)‪ (٦‬ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ ﺍﻟﻤﻘﺎﺒﺱ ﻓﻰ ﺍﻟﺤﻤﺎﻤﺎﺕ ﺃﻭ ﺍﻟﻤﻁﺎﺒﺦ ﺃﻭ ﻤﺎ ﻴﻤﺎﺜﻠﻬﺎ ﻓﻰ ﺃﻤﺎﻜﻥ ﺒﺤﻴﺙ‬


‫ﻻ ﺘﻜﻭﻥ ﻓﻰ ﻤﺘﻨﺎﻭل ﺍﻟﺫﺭﺍﻉ ﻟﺸﺨﺹ ﻤﺒﻠل ﺒﺎﻟﻤﻴﺎﻩ‪.‬‬

‫)‪ (٧‬ﻴﺠﺏ ﻤﺭﺍﻋﺎﺓ ﺍﺨﺘﻴﺎﺭ ﺩﺭﺠﺔ ﺍﻟﺤﻤﺎﻴـﺔ )ﺩ ﺡ( ﺍﻟﻤﻨﺎﺴـﺒﺔ ﻟﻠﻤﻘـﺒﺱ ﻓـﻰ ﺍﻷﻤـﺎﻜﻥ‬
‫ﺍﻟﻤﻌﺭﻀﺔ ﻟﻠﻤﻴﺎﻩ ﺃﻭ ﺍﻷﺘﺭﺒﺔ‪.‬‬

‫)‪ (٨‬ﻻ ﻴﺴﻤﺢ ﺒﻭﺠﻭﺩ ﻤﻘﺎﺒﺱ ﻓﻰ ﺤﻴﺯ ﺍﻟﻤﻐﺎﻁﺱ ﻭﻜﺒﺎﺌﻥ ﺍﻻﺴﺘﺤﻤﺎﻡ‪.‬‬

‫)‪ (٩‬ﻴﻜﻭﻥ ﻤﻨﺴﻭﺏ ﺘﺭﻜﻴﺏ ﺍﻟﻤﻘﺎﺒﺱ ﻤﻥ ‪ ٠.٣‬ﺇﻟﻰ ‪ ٠.٤‬ﻡ ﻤﻥ ﺍﻷﺭﻀﻴﺔ ﺍﻟﻨﻬﺎﺌﻴـﺔ ﻓـﻰ‬
‫ﺍﻷﻤﺎﻜﻥ ﺍﻟﺴﻜﻨﻴﺔ ﻭﺍﻟﻤﻜﺎﺘﺏ ﺒﺎﺴﺘﺜﻨﺎﺀ ﺍﻟﻤﻁﺎﺒﺦ ﻭﺍﻟﺤﻤﺎﻤﺎﺕ ﻓﺘﻜﻭﻥ ﻋﻠﻰ ﻤﻨﺴﻭﺏ ﻤﻥ‬
‫‪ ١.٢‬ﺇﻟﻰ ‪ ١.٣٥‬ﻡ‪.‬‬

‫)‪ (١٠‬ﻴﺠﺏ ﺃﻻ ﺘﺯﻴﺩ ﺍﻟﻤﺴﺎﻓﺔ ﺍﻷﻓﻘﻴﺔ ﺒﻴﻥ ﻤﺨﺭﺝ ﺍﻟﻤﻘﺒﺱ ﻭﺍﻟﺤﺎﺌﻁ ﺍﻟﻌﻤـﻭﺩﻯ ﻋـــﻥ‬
‫‪١.٨٠‬ﻡ ﻭﺒﻴﻥ ﻤﺨـﺭﺝ ﺍﻟﻤﻘﺒﺱ ﻭﺍﻟﻤﺨﺭﺝ ﺍﻟﺫﻯ ﻴﻠﻴﻪ ﻋﻥ ‪٣.٦٥‬ﻡ‪ ،‬ﺃﻨﻅـﺭ ﺸـﻜل‬
‫)‪.(٤-٢‬‬

‫)‪ (١١‬ﻴﺤﻅﺭ ﺘﺭﻜﻴﺏ ﺍﻟﻤﻘﺎﺒﺱ ﺃﻓﻘﻴﺎﹰ ﻋﻠﻰ ﺃﺴﻁﺢ ﺘﺭﺍﺒﻴﺯﺍﺕ ﺍﻟﻤﻌﺎﻤل ﺃﻭ ﻤﺎ ﻴﺸﺎﺒﻬﻬﺎ ﻟﻤﻨـﻊ‬
‫ﺘﺭﺍﻜﻡ ﺍﻷﺘﺭﺒﺔ ﻭﺍﻟﺭﻁﻭﺒﺔ ﺩﺍﺨل ﺃﺠﺯﺍﺌﻬﺎ ﺍﻟﻤﻜﻬﺭﺒﺔ‪ ،‬ﺃﻨﻅﺭ ﺸﻜل )‪.(٥-٢‬‬

‫ﻭﻴﻭﻀﺢ ﺠﺩﻭل )‪ (٥-٢‬ﺃﻨﻭﺍﻉ ﺍﻟﻤﻘﺎﺒﺱ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻭﺒﻴﺎﻨﺎﺘﻬﺎ ﺍﻟﻔﻨﻴﺔ‪.‬‬

‫)‪ (١٢‬ﻴﺭﺍﻋﻰ ﺃﻻ ﻴﺯﻴﺩ ﻋﺩﺩ ﻤﺨﺎﺭﺝ ﺍﻹﻨﺎﺭﺓ ﺃﻭ ﺍﻟﻤﺂﺨﺫ ﺍﻟﻜﻬﺭﺒﻴﺔ ﺍﻟﺘﻰ ﺘﺴﺘﻌﻤل ﻟﻭﺤـﺩﺍﺕ‬
‫ﺍﻹﻨﺎﺭﺓ ﻭﺍﻟﺘﻰ ﺘﺤﻤل ﻋﻠﻰ ﺩﺍﺌﺭﺓ ﻓﺭﻋﻴﺔ ﻨﻬﺎﺌﻴﺔ ﻭﺍﺤﺩﺓ ﻋﻥ ﻋﺸﺭﺓ ﻤﺨﺎﺭﺝ‪.‬‬

‫)‪ (١٣‬ﻴﺠﺏ ﻤﺭﺍﻋﺎﺓ ﺍﻟﺒﻨﻭﺩ ﺍﻟﺨﺎﺼﺔ ﺒﻤﻘﻁﻊ ﻤﻭﺼﻼﺕ ﺍﻟﺩﻭﺍﺌﺭ ﺍﻟﻔﺭﻋﻴﺔ ﺍﻟﻨﻬﺎﺌﻴﺔ ﻟﻤﺨـﺎﺭﺝ‬
‫ﻭﺤﺩﺍﺕ ﺍﻹﻀﺎﺀﺓ ﻭﺍﻟﻤﺂﺨﺫ ﺒﺎﻟﻤﺠﻠﺩ ﺍﻟﺜﺎﻨﻰ ﻟﻠﻜﻭﺩ ﺍﻟﻤﺼﺭﻯ ﻟﻠﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ‪.‬‬

‫‪٢‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫< ‪ ١.٨‬م‬ ‫< ‪ ٣.٦٥‬م‬ ‫< ‪ ١.٨‬م‬

‫‪ ٠.٣٥‬م‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(٤-٢‬ﺃﻗﺼﻰ ﻤﺴﺎﻓﺔ ﺒﻴﻥ ﺍﻟﻤﻘﺎﺒﺱ ﻭﺒﻌﻀﻬﺎ ﺍﻟﺒﻌﺽ ﻭﺒﻴﻥ ﺍﻟﻤﻘﺎﺒﺱ ﻭﺍﻟﺤﺎﺌﻁ ﺍﻟﻤﺠﺎﻭﺭ‬

‫ﻣﻘﺒﺲ ﻣﺰدوج ﺻﺎﻣﺪ ﻟﻠﻤﯿﺎه‬


‫)ﻣﺮﻛﺐ رأﺳﯿﺎً(‬

‫اﻟﺴﻄﺢ اﻟﻤﻌﺮض ﻟﻠﻤﯿﺎه‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(٥-٢‬ﻭﻀﻊ ﺍﻟﻤﻘﺎﺒﺱ ﺒﺘﺭﺍﺒﻴﺯﺍﺕ ﺍﻟﻤﻌﺎﻤل‬

‫‪٢‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻨﻰ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪ :(٥-٢‬ﺃﻨﻭﺍﻉ ﺍﻟﻤﻘﺎﺒﺱ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ‬

‫ﻋﺩﺩ‬ ‫ﺍﻟﺠﻬﺩ‬ ‫ﺍﻟﺴﻌﺔ‬


‫ﺍﻻﺴﺘﺨﺩﺍﻡ‬ ‫ﺍﻟﻌﺩﺩ‬ ‫ﺍﻟﻨﻭﻉ‬ ‫ﻡ‬
‫ﺍﻷﻁﺭﺍﻑ‬ ‫)ﻓﻭﻟﺕ(‬ ‫)ﺃﻤﺒﻴﺭ(‬
‫ﺍﻷﺤﻤﺎل ﺍﻟﻌﺎﺩﻴﺔ‬ ‫‪٣‬‬ ‫‪٢٥٠‬‬ ‫‪١٠‬‬ ‫‪١‬‬ ‫ﻤﻘﺒﺱ‬ ‫‪١‬‬
‫ﺃﺒﺎﺠﻭﺭﺓ ‪ +‬ﻤﻜﻨﺴﺔ – ﺭﺍﺩﻴﻭ –‬ ‫‪1Ph +‬‬ ‫ﺒﺭﻴﺯﺓ‬
‫ﺘﻠﻴﻔﺯﻴﻭﻥ ‪ -‬ﺃﻟﺦ‬ ‫‪N+E‬‬ ‫ﺃﺤﺎﺩﻯ‬
‫ﺃﺤﻤﺎل ﺍﻟﻘﻭﻯ ﻜﺎﻟﺴﺨﺎﻥ‬ ‫‪٣‬‬ ‫‪٢٥٠‬‬ ‫‪١٦‬‬ ‫‪١‬‬ ‫ﻤﻘﺒﺱ‬ ‫‪٢‬‬
‫‪(1Ph +‬‬ ‫ﺒﺭﻴﺯﺓ‬
‫)‪N+E‬‬ ‫ﺃﺤﺎﺩﻯ‬
‫ﺃﺤﻤﺎل ﺍﻟﺨﺩﻤﺔ ﺍﻟﻌﺎﺩﻴﺔ ﻭﺍﻟﺘﻰ ﺘﺘﻁﻠﺏ‬ ‫‪٣‬‬ ‫‪٢٥٠‬‬ ‫‪١٠‬‬ ‫‪٢‬‬ ‫ﻤﻘﺒﺱ‬ ‫‪٣‬‬
‫ﺃﻜﺜﺭ ﻤﻥ ﻤﺼﺩﺭ ﻤﺘﺠﺎﻭﺭ ﻜﺎﻟﻔﻴﺩﻴﻭ‬ ‫‪(1Ph +‬‬ ‫ﺒﺭﻴﺯﺓ‬
‫ﻭ ﺍﻟﺘﻠﻴﻔﺯﻴﻭﻥ‬ ‫)‪N+E‬‬ ‫ﻤﺯﺩﻭﺝ‬
‫ﺃﺤﻤﺎل ﺍﻟﻘﻭﻯ ﺍﻟﺨﺎﺼﺔ ﺒﺎﻟﺼﻴﺎﻨﺔ‬ ‫‪٥‬‬ ‫‪٤٠٠‬‬ ‫‪، ٢٥ ، ١٦‬‬ ‫‪١‬‬ ‫ﻤﻘﺒﺱ‬ ‫‪٤‬‬
‫ﻜﻤﻨﺸﺎﺭ ﻜﻬﺭﺒﻰ‪ ،‬ﻤﺜﻘﺎﺏ ﻤﺤﻤﻭل‪،‬‬ ‫‪(3Ph +‬‬ ‫‪، ٦٣ ، ٥٠‬‬ ‫ﺒﺭﻴﺯﺓ‬
‫‪ ..‬ﺃﻟﺦ‬ ‫)‪N+E‬‬ ‫‪٢٥٠ ، ١٢٥‬‬ ‫ﺜﻼﺜﻰ‬

‫‪٢‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻟﺙ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺘﻘﺩﻴﺭ ﺍﻟﻁﻠﺏ ﺍﻷﻗﺼﻰ ﻟﻠﺤﻤل‬ ‫‪-٣‬‬


‫ﺨﻭﺍﺹ ﺍﻷﺤﻤﺎل‬ ‫‪١-٣‬‬
‫ﺍﻟﺘﻌﺎﺭﻴﻑ‪:‬‬
‫ﺍﻟﻁﻠﺏ ﺍﻟﻜﻬﺭﺒﺎﺌﻲ ﻟﻠﻤﻨﺸﺄ‪:‬‬
‫ﻴﻌﺭﻑ ﺍﻟﻁﻠﺏ ﺍﻟﻜﻬﺭﺒﺎﺌﻲ ﻷﻱ ﻤﻨﺸﺄﺓ ﺒﺄﻨﻪ ﺍﻟﺤﻤل ﺍﻟﻤﺘﻭﺴﻁ ﻤﻘﺎﺴﺎﹰ ﺒﻭﺤﺩﺍﺕ ﺍﻟﻜﻴﻠﻭ ﻓﻭﻟـﺕ‬
‫ﺃﻤﺒﻴﺭ‪ ،‬ﻭﺍﻟﻜﻴﻠﻭ ﻭﺍﺕ‪ ،‬ﻭﺍﻟﻜﻴﻠﻭ ﻓﺎﺭ‪ ،‬ﻭﺍﻷﻤﺒﻴﺭ ﻟﻬﺫﻩ ﺍﻟﻤﻨﺸﺄﺓ ﺨﻼل ﻓﺘﺭﺓ ﺯﻤﻨﻴـﺔ ﻤﺤـﺩﺩﺓ‪،‬‬
‫ﻭﺘﺴﻤﻲ ﺒﻔﺘﺭﺓ ﺍﻟﻁﻠﺏ ﻋﻠﻰ ﺍﻟﺤﻤل‪ ،‬ﻭﻴﺩﺨل ﻓﻲ ﺘﺤﺩﻴـﺩ ﻫـﺫﻩ ﺍﻟﻔﺘـﺭﺓ ﺍﻟﺜﺎﺒـﺕ ﺍﻟﺯﻤﻨـﻲ‬
‫ﺍﻟﺤﺭﺍﺭﻱ ﻟﻠﻤﻨﺸﺄﺓ‪ ،‬ﻭﻓﺘﺭﺓ ﺍﺴﺘﻤﺭﺍﺭ ﺍﻟﺤﻤل‪ ،‬ﻭﻋﻠﻰ ﻫﺫﺍ ﻓﻤﻥ ﺍﻟﻼﺯﻡ ﺘﺤﺩﻴﺩ ﺍﻟﻔﺘـﺭﺓ ﺍﻟﺘـﻲ‬
‫ﻴﺤﺴﺏ ﺨﻼﻟﻬﺎ ﺍﻟﻁﻠﺏ ﺍﻟﻜﻬﺭﺒﺎﺌﻲ‪ ،‬ﻭﺇﻻ ﻓﻘﺩ ﻤﻌﻨﺎﻩ‪.‬‬
‫ﻴﺒﻴﻥ ﺸﻜل )‪ (١-٣‬ﻤﻨﺤﻨﻲ ﺍﻟﺤﻤل ﺍﻟﻴﻭﻤﻲ ﻟﺤﻤل ﻜﻬﺭﺒﺎﺌﻲ ﺘﻡ ﺍﻟﺤﺼﻭل ﻋﻠﻴﻪ ﻋﻠﻰ ﺍﻤﺘﺩﺍﺩ‬
‫‪ ٢٤‬ﺴﺎﻋﺔ ﺒﻭﺍﺴﻁﺔ ﺠﻬﺎﺯ ﻗﻴﺎﺱ ﻤﺨﻤﺩ ﺤﺘﻰ ﻻ ﻴﺴﺠل ﺍﻟﺘﻐﻴﺭﺍﺕ ﺍﻟﺴﺭﻴﻌﺔ ﻓﻲ ﺍﻟﺤﻤل ﻤﻊ‬
‫ﺍﻟﺯﻤﻥ ﺤﻴﺙ ﻨﺠﺩ ﺃﻨﻪ ﻋﻨﺩ ﺤﺴﺎﺏ ﺍﻟﻁﻠﺏ ﺍﻟﻜﻬﺭﺒﺎﺌﻰ ﻋﻠﻰ ﺃﺴﺎﺱ ﻓﺘﺭﺓ ﺯﻤﻨﻴﺔ ﻗـﺩﺭﻫﺎ ‪١٥‬‬
‫ﺩﻗﻴﻘﺔ ﻴﻜﻭﻥ ﺍﻟﻁﻠﺏ ﺍﻷﻗﺼﻰ ﺒﻨﻅﺎﻡ ﺍﻟﻭﺤﺩﺓ )‪ (P.U.) (١‬ﻭﻋﻨﺩ ﺇﻋـﺎﺩﺓ ﺤﺴـﺎﺏ ﺍﻟﻁﻠـﺏ‬
‫ﺍﻟﻜﻬﺭﺒﻰ ﻋﻠﻰ ﺃﺴﺎﺱ ﺴﺎﻋﺔ ﻜﺎﻤﻠﺔ ﻴﻜﻭﻥ ﺍﻟﻁﻠـﺏ ﺍﻷﻗﺼـﻰ ﺒﻨﻅـﺎﻡ ﺍﻟﻭﺤـﺩﺓ )‪(٠.٩٦‬‬
‫)‪.(P.U.‬‬

‫‪٣‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻟﺙ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫أﻗﺼﻰ ﻃﻠﺐ ﺧﻼل ‪ ١٥‬دﻗﯿﻘﺔ‬ ‫أﻗﺼﻰ ﻃﻠﺐ ﺧﻼل‬


‫‪ ١‬ﺳﺎﻋﺔ‬
‫‪٠.٩٦‬‬
‫اﻟﺤﻤﻞ ﻣﻨﺴﻮب ﻟﻠﺤﻤﻞ اﻷﻗﺼﻰ )‪(PU‬‬

‫‪ ١‬ﺳﺎﻋﺔ‬

‫‪0.2341‬‬ ‫ﻣﺘﻮﺳﻂ اﻟﻄﻠﺐ‬

‫اﻟﺰﻣﻦ )ﺳﺎﻋﺔ(‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(١-٣‬ﺘﻐﻴﺭ ﺍﻟﻁﻠﺏ ﻋﻠﻰ ﺍﻟﺤﻤل ﻤﻊ ﺍﻟﻔﺘﺭﺓ ﺍﻟﺯﻤﻨﻴﺔ ﻟﺤﺴﺎﺏ ﺍﻟﻁﻠﺏ‬
‫)ﻤﻨﺤﻨﻰ ﺍﻟﺤﻤل ﺍﻟﻴﻭﻤﻲ(‬

‫ﺍﻟﻁﻠﺏ ﺍﻷﻗﺼﻰ ﻋﻠﻰ ﺍﻟﺤﻤل‪:‬‬


‫ﻫﻭ ﺃﻜﺒﺭ ﻁﻠﺏ ﻴﺤﺩﺙ ﺨﻼل ﻓﺘﺭﺓ ﺯﻤﻨﻴﺔ ﻤﺤﺩﺩﺓ ﻭﻴﻘﺎﺱ ﺒﻭﺤﺩﺍﺕ ﺍﻟﻜﻴﻠـﻭ ﻭﺍﺕ‪ ،‬ﻭﺍﻟﻜﻴﻠـﻭ‬
‫ﻓﻭﻟﺕ ﺃﻤﺒﻴﺭ‪ ،‬ﻭﺍﻟﻜﻴﻠﻭ ﻓﺎﺭ‪ ،‬ﻭﺍﻷﻤﺒﻴﺭ‪ ،‬ﻭﻴﻌﺘﺒﺭ ﺍﻟﻁﻠﺏ ﺍﻷﻗﺼﻰ ﻋﻠﻰ ﺍﻟﺤﻤل ﻫﻭ ﺍﻻﻫﺘﻤـﺎﻡ‬
‫ﺍﻷﻜﺒﺭ ﻟﻤﺨﻁﻁﻲ ﻤﻨﻅﻭﻤﺎﺕ ﺍﻟﻘﻭﻯ ﺍﻟﻜﻬﺭﺒﻴﺔ ﺤﻴﺙ ﻴﻤﺜل ﺃﻗﺼﻰ ﻅﺭﻭﻑ ﺘﺸﻐﻴل ﻋﺎﺩﻴـﺔ‬
‫ﺘﺘﻌﺭﺽ ﻟﻬﺎ ﺍﻟﻤﻨﻅﻭﻤﺔ ﺴﻭﺍﺀ‪ ‬ﻤﻥ ﺤﻴﺙ ﺍﻟﺘﺤﻤﻴل ﺍﻟﺤﺭﺍﺭﻱ ﻟﻠﻤﻌﺩﺍﺕ ﺃﻭ ﺍﻻﻨﺨﻔـﺎﺽ ﻓـﻲ‬
‫ﺍﻟﺠﻬﺩ‪.‬‬
‫ﻭﻴﻼﺤﻅ ﻀﺭﻭﺭﺓ ﺘﺤﺩﻴﺩ ﺍﻟﻔﺘﺭﺓ ﺍﻟﺯﻤﻨﻴﺔ ﺍﻟﺘﻲ ﻴﺘﻡ ﺨﻼﻟﻬﺎ ﺤﺴﺎﺏ ﺍﻟﻁﻠﺏ‪ ،‬ﻭﻜـﺫﻟﻙ ﺍﻟﻔﺘـﺭﺓ‬
‫ﺍﻟﺯﻤﻨﻴﺔ ﺍﻟﺘﻲ ﻴﻌﺘﺒﺭ ﺨﻼﻟﻬﺎ ﻜﺄﻜﺒﺭ ﻁﻠﺏ‪ ،‬ﻭﻋﻠﻰ ﻫﺫﺍ ﻓﺈﻥ ﺍﻟﻁﻠﺏ ﺍﻷﻗﺼﻰ ﻟﻤﺩﺓ ﺭﺒﻊ ﺴﺎﻋﺔ‬
‫ﻴﻭﻤﻴﺎﹰ ﻫﻭ ﺃﻜﺒﺭ ﻁﻠﺏ ﻟﻠﺤﻤل ﺍﻟﻜﻬﺭﺒﻲ ﻟﻤﺩﺓ ﺭﺒﻊ ﺴﺎﻋﺔ ﺨﻼل ﻤﺩﺓ ﻴﻭﻡ ﻜﺎﻤـل‪ ،‬ﻭﻜـﺫﻟﻙ‬
‫ﺍﻟﻁﻠﺏ ﺍﻷﻗﺼﻰ ﻟﻤﺩﺓ ﻨﺼﻑ ﺴﺎﻋﺔ ﻓﻰ ﺍﻟﺸﻬﺭ‪ ،‬ﻭﺍﻟﻁﻠﺏ ﺍﻷﻗﺼﻰ ﻟﻤﺩﺓ ﺴﺎﻋﺔ ﺴﻨﻭﻴﺎﹰ‪.‬‬

‫‪٣‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻟﺙ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫)‪(Demand Factor‬‬ ‫ﻤﻌﺎﻤل ﺍﻟﻁﻠﺏ‪:‬‬


‫ﻫﻭ ﻨﺴﺒﺔ ﺍﻟﻁﻠﺏ ﺍﻷﻗﺼﻰ ﻟﻠﺤﻤل ﻓﻰ ﻤﻨﻅﻭﻤﺔ ﻜﻬﺭﺒﻴﺔ ﺇﻟﻰ ﻤﺠﻤـﻭﻉ ﻤﻘﻨﻨـﺎﺕ ﺍﻷﺤﻤـﺎل‬
‫ﺍﻟﻤﺘﺼﻠﺔ ﺒﻬﺫﻩ ﺍﻟﻤﻨﻅﻭﻤﺔ‪.‬‬
‫ﻤﻌﺎﻤل ﺍﻻﺴﺘﺨﺩﺍﻡ‪(Utilization Factor) ( F ld ) :‬‬

‫ﻫﻭ ﻨﺴﺒﺔ ﺍﻟﻁﻠﺏ ﺍﻷﻗﺼﻰ ﻟﺤﻤل ﻤﺎ ﺇﻟﻰ ﺍﻟﻘﺩﺭﺓ ﺍﻻﺴﻤﻴﺔ ﻟﻤﻌﺩﺓ ﺘﻐﺫﻴﺔ ﻫﺫﺍ ﺍﻟﺤﻤل‪.‬‬
‫ﻤﻌﺎﻤل ﺍﻟﺤﻤل‪(Load Factor)( LF ) :‬‬
‫ﻫﻭ ﻨﺴﺒﺔ ﻤﺘﻭﺴﻁ ﺍﻟﺤﻤل ﺨﻼل ﻓﺘﺭﺓ ﺯﻤﻨﻴﺔ ﻤﻌﻴﻨﺔ ﺇﻟﻰ ﺃﻗﺼﻰ ﺤﻤل ﻴﺴﺠل ﺨﻼل ﺘﻠﻙ‬
‫ﺍﻟﻔﺘﺭﺓ‪.‬‬
‫)‪(١-٣‬‬ ‫ﺍﻟﻁﺎﻗﺔ ﺍﻟﻔﻌﻠﻴﺔ ﺍﻟﻤﺴﺘﻬﻠﻜﺔ )ﻙ‪.‬ﻭﺍﺕ‪.‬ﺴﺎﻋﺔ(‬
‫ﻤﻌﺎﻤل ﺍﻟﺤﻤل =‬
‫ﺃﻗﺼﻰ ﻁﻠﺏ )ﻙ‪.‬ﻭﺍﺕ( × ﺍﻟﻔﺘﺭﺓ ﺍﻟﺯﻤﻨﻴﺔ )ﺴﺎﻋﺔ(‬
‫ﻤﻌﺎﻤل ﺍﻟﺘﺒﺎﻴﻥ‪(Diversity Factor) (FD ) :‬‬
‫ﻫﻭ ﺍﻟﻨﺴﺒﺔ ﺒﻴﻥ ﻤﺠﻤﻭﻉ ﺍﻟﻁﻠﺒﺎﺕ ﺍﻟﻘﺼﻭﻯ ﻟﻸﺤﻤﺎل ﻟﻸﺠﺯﺍﺀ ﺍﻟﻤﺨﺘﻠﻔﺔ ﻤﻥ ﺍﻟﻤﻨﻅﻭﻤﺔ‬
‫ﺍﻟﻜﻬﺭﺒﻴﺔ ﺇﻟﻰ ﺍﻟﻁﻠﺏ ﺍﻷﻗﺼﻰ ﻟﻠﺤﻤل ﻟﻜﺎﻤل ﺍﻟﻤﻨﻅﻭﻤﺔ‪.‬‬
‫‪D1 + D2 + D3 + L + Dn‬‬ ‫‪1‬‬
‫= ‪FD‬‬ ‫=‬ ‫)‪(3-2‬‬
‫‪D1+ 2 + 3 +L+ n‬‬ ‫‪Fc‬‬
‫ﻤﻌﺎﻤل ﺍﻟﺘﻁﺎﺒﻕ‪(Coincidence Factor) (FC ) :‬‬
‫ﻫﻭ ﺍﻟﻨﺴﺒﺔ ﺒﻴﻥ ﺍﻟﻁﻠﺏ ﺍﻷﻗﺼﻰ ﻟﺤﻤل ﻜﺎﻤل ﺍﻟﻤﻨﻅﻭﻤﺔ ﺍﻟﻜﻬﺭﺒﻴﺔ ﺇﻟﻰ ﻤﺠﻤـﻭﻉ ﺍﻟﻁﻠﺒـﺎﺕ‬
‫ﺍﻟﻘﺼﻭﻯ ﻷﺤﻤﺎل ﺍﻷﺠﺯﺍﺀ ﺍﻟﻤﺨﺘﻠﻔﺔ ﻤﻥ ﻫﺫﻩ ﺍﻟﻤﻨﻅﻭﻤﺔ‪.‬‬
‫‪D1+ 2 + 3 +L+ n‬‬ ‫‪1‬‬
‫= ‪Fc‬‬ ‫=‬ ‫)‪(3-3‬‬
‫‪D1 + D2 + D3 + L + Dn FD‬‬
‫ﺘﺒﺎﻴﻥ ﺍﻷﺤﻤﺎل‪(Load Diversity) ( LD ) :‬‬
‫ﻫﻭ ﺍﻟﻔﺭﻕ ﺒﻴﻥ ﻤﺠﻤﻭﻉ ﺍﻟﻁﻠﺒﺎﺕ ﺍﻟﻘﺼﻭﻯ ﻷﺠﺯﺍﺀ ﺍﻷﺤﻤﺎل ﺍﻟﻤﺨﺘﻠﻔـﺔ ﻤـﻥ ﺍﻟﻤﻨﻅﻭﻤـﺔ‬
‫ﺍﻟﻜﻬﺭﺒﻴﺔ ﻭﺍﻟﻁﻠﺏ ﺍﻷﻗﺼﻰ ﻟﻬﺫﻩ ﺍﻟﻤﻨﻅﻭﻤﺔ ﻨﺘﻴﺠﺔ ﻻﺨﺘﻼﻑ ﺍﻟﺘﻭﻗﻴﺘﺎﺕ ﺍﻟﺯﻤﻨﻴﺔ‪.‬‬
‫ﻭﻴﻤﻜﻥ ﺍﻟﺘﻌﺒﻴﺭ ﻋﻥ ﺫﻟﻙ ﻋﻠﻰ ﺍﻟﻨﺤﻭ ﺍﻟﺘﺎﻟﻰ‪:‬‬

‫‪LD = (D1 + D2 + D3 + L + Dn ) − D1+2 +3+Ln‬‬ ‫)‪(3-4‬‬

‫‪٣‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻟﺙ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺤﺴﺎﺏ ﻤﻌﺎﻤﻼﺕ ﺍﻟﺘﺒﺎﻴﻥ ﻭﺍﻟﺘﻁﺎﺒﻕ‬ ‫‪٢-٣‬‬


‫ﻴﺘﻡ ﺤﺴﺎﺏ ﻤﻌﺎﻤل ﺍﻟﺘﻁﺎﺒﻕ ﺒﻨﺎﺀ‪ ‬ﻋﻠﻰ ﻗﻴﺎﺴﺎﺕ ﺍﻷﺤﻤﺎل ﺍﻟﺘﻲ ﻟﻬﺎ ﻤﻌﺎﻤﻼﺕ ﺃﺤﻤﺎل ﻤﺘﻘﺎﺭﺒﺔ‬
‫ﻭﻴﺭﺘﺒﻁ ﻤﻌﺎﻤل ﺍﻟﺘﻁﺎﺒﻕ ﻟﻌﺩﺩ ) ‪ (n‬ﻤﻥ ﺍﻷﺤﻤﺎل ) ‪ (Fcn‬ﺒﻤﻌﺎﻤل ﺍﻟﺘﻁﺎﺒﻕ ﻟﻌـﺩﺩ ﻻ ﻨﻬـﺎﺌﻲ‬
‫ﻤﻥ ﺍﻷﺤﻤﺎل ) ∞‪ (Fc‬ﺒﺎﻟﻤﻌﺎﺩﻟﺔ )‪:(٥-٣‬‬
‫‪ 1 − Fc∞ ‬‬
‫‪Fcn = Fc∞ + ‬‬ ‫‪‬‬ ‫)‪(3-5‬‬
‫‪ n ‬‬
‫ﻭﻤﻥ ﺜﻡ ﻓﻌﻨﺩ ﺃﺨﺫ ﻋﻴﻨﺔ ﻤﻥ ﺍﻷﺤﻤﺎل ﻋﺩﺩﻫﺎ ) ‪ (n‬ﺤﻴﺙ ‪ n‬ﺘﺘﺭﺍﻭﺡ ﻤﺎ ﺒﻴﻥ ‪٢٠‬ﻭ‪٥٠‬‬
‫ﺤﻤﻼ ﻓﺈﻥ ﻤﻌﺎﻤل ﺘﻁﺎﺒﻕ ﻜل ﺤﻤل ﻫﻭ‬
‫= ‪Fcn‬‬
‫‪D1 +2 +L+n n‬‬
‫=‬ ‫ﻤﺘﻭﺴﻁ ﻤﺴﺎﻫﻤﺔ ﻜل ﺤﻤل ﻓﻲ ﺍﻟﻁﻠﺏ ﺍﻷﻗﺼﻰ‬
‫‪D1 + D2 + L + Dn‬‬ ‫‪n‬‬
‫ﻤﺘﻭﺴﻁ ﺍﻟﻁﻠﺏ ﺍﻷﻗﺼﻰ ﻟﻜل ﺤﻤل‬
‫ﻭﺒﻤﻌﺭﻓﺔ ﻫﺫﻩ ﺍﻟﻘﻴﺎﺴﺎﺕ ﻴﻤﻜﻥ ﺤﺴﺎﺏ ∞‪ Fc‬ﻤﻥ ﺍﻟﻤﻌﺎﺩﻟﺔ )‪(٦-٣‬‬
‫‪nFcn − 1‬‬
‫= ∞‪Fc‬‬ ‫)‪(3-6‬‬
‫‪n −1‬‬

‫ﺍﻟﻁﻠﺏ ﺍﻷﻗﺼﻰ ﻭﻤﻌﺎﻤل ﺍﻟﺘﺒﺎﻴﻥ ‪Maximum Demand and Diversity Factor‬‬ ‫‪٣-٣‬‬
‫ﻋﺎﻡ‬
‫ﻴﻘﺩﻡ ﻫﺫﺍ ﺍﻟﺠﺯﺀ‪ -‬ﺍﻟﻤﻌﻠﻭﻤﺎﺕ ﻭﺍﻹﺭﺸﺎﺩﺍﺕ ﺍﻟﻼﺯﻤﺔ ﻟﺘﺤﺩﻴﺩ ﻗﻴﻤﺔ ﺍﻟﺤﻤل ﺍﻷﻗﺼـﻰ‬ ‫)ﺃ(‬
‫ﺍﻟﻤﻁﻠﻭﺏ ﻟﻠﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﺍﻟﺘﻲ ﺘﻘﻭﻡ ﺒﺘﻐﺫﻴﺔ ﺍﻷﺠﻬـﺯﺓ ﺸـﺎﺌﻌﺔ ﺍﻻﺴـﺘﺨﺩﺍﻡ‬
‫ﺒﺎﻹﻀﺎﻓﺔ ﺇﻟﻰ ﺍﻟﻤﻼﺤﻅﺎﺕ ﺍﻟﻼﺯﻤﺔ ﻟﺘﻁﺒﻴﻕ ﻤﻌﺎﻤل ﺍﻟﺘﺒﺎﻴﻥ ﺍﻟﻤﺴﻤﻭﺡ‪.‬‬
‫)ﺏ( ﺍﻟﺒﻴﺎﻨﺎﺕ ﺍﻟﻭﺍﺭﺩﺓ ﻓﻲ ﻫﺫﺍ ﺍﻟﺠﺯﺀ ﺍﺭﺸﺎﺩﻴﺔ ﺤﻴﺙ ﻴﺘﻌﺫﺭ ﺘﺤﺩﻴﺩ ﻤﻌﺎﻤل ﺍﻟﺘﺒﺎﻴﻥ ﺒﺩﻗـﺔ‬
‫ﻟﻜل ﺃﻨﻭﺍﻉ ﺍﻟﺘﺭﻜﻴﺒﺎﺕ )ﺘﻌﺘﻤﺩ ﻋﻠﻰ ﻤﻭﻗﻊ ﺍﻻﺴﺘﺨﺩﺍﻡ(‪.‬‬
‫)ﺕ( ﻤﻥ ﺍﻟﻤﻤﻜﻥ ﺃﻥ ﺘﺯﻴﺩ ﺃﻭ ﺘﻘل ﺍﻷﺭﻗﺎﻡ ﻓﻲ ﺍﻟﺠﺩﻭل )‪ (١-٣‬ﻭﺫﻟﻙ ﻁﺒﻘـﺎﹰ ﻟﻅـﺭﻭﻑ‬
‫ﺘﺸﻐﻴل ﺍﻟﻤﻌﺩﺍﺕ ﻭﺍﻷﺩﻭﺍﺕ ﺒﻬﺫﻩ ﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﺘﻲ ﻴﺘﻭﻗﻌﻬﺎ ﺍﻟﻤﺼﻤﻡ‪.‬‬
‫)ﺙ( ﻴﺤﺴﺏ ﺍﻟﺘﻴﺎﺭ ﺍﻷﻗﺼﻰ ﺍﻟﻤﻁﻠﻭﺏ ﻟﻠﺩﻭﺍﺌﺭ ﺍﻟﻨﻬﺎﺌﻴﺔ ﺃﻭ ﺍﻟﻔﺭﻋﻴﺔ ﺒﺠﻤﻊ ﺘﻴﺎﺭﺍﺕ ﻜﺎﻓـﺔ‬
‫ﻨﻘﻁ ﺍﻻﺴﺘﺨﺩﺍﻡ )ﺍﻟﻤﺂﺨﺫ ﻭﺍﻟﺒﺭﺍﻴﺯ( ﻭﺍﻷﺠﻬﺯﺓ ﺍﻟﺜﺎﺒﺘﺔ ﻋﻠﻰ ﺍﻟـﺩﻭﺍﺌﺭ ﻤـﻊ ﺘﻁﺒﻴـﻕ‬
‫ﻤﻌﺎﻤل ﺍﻟﻁﻠﺏ ﺍﻟﻤﻨﺎﺴﺏ ﻁﺒﻘﺎﹰ ﻟﻤﺎ ﻫﻭ ﻤﻭﻀﺢ ﺒﺎﻟﺠـﺩﻭل )‪ (١-٣‬ﺃﻭ ﻜﻤـﺎ ﻴﻘـﺭﺭ‬
‫ﺍﻟﻤﻬﻨﺩﺱ ﺍﻟﻤﺼﻤﻡ‪.‬‬
‫)ﺝ( ﻴﺘﻡ ﺘﺤﺩﻴﺩ ﺍﻟﺘﻴﺎﺭ ﺍﻟﻔﻌﻠﻲ ﺍﻟﻤﻁﻠﻭﺏ ﻟﺩﺍﺌﺭﺓ ﺘﻐﺫﻱ ﺩﻭﺍﺌﺭ ﻋﻤﻭﻤﻴﺔ )ﻨﻬﺎﺌﻴﺔ( ﺒﺎﺴﺘﻌﻤﺎل‬
‫ﻤﻌﺎﻤﻼﺕ ﺍﻟﺘﺒﺎﻴﻥ ﺍﻟﻤﻭﻀﺤﺔ ﻓﻲ ﺠﺩﻭل )‪ (٢-٣‬ﺍﻟﺘﻲ ﺘﻁﺒﻕ ﻋﻠﻰ ﺍﻟﺘﻴﺎﺭﺍﺕ ﺍﻟﻔﻌﻠﻴـﺔ‬

‫‪٣‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻟﺙ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻟﺠﻤﻴﻊ ﺍﻟﻤﻌﺩﺍﺕ ﻭ ﺍﻷﺠﻬﺯﺓ ﺍﻟﻤﻐﺫﺍﺓ ﺒﻬﺫﻩ ﺍﻟﺩﺍﺌﺭﺓ ﻭﻟـﻴﺱ ﺒﺠﻤـﻊ ﺍﻟﺘﻴـﺎﺭ ﺍﻟﻔﻌﻠـﻲ‬
‫ﺍﻟﻤﻁﻠﻭﺏ ﻟﻠﺩﻭﺍﺌﺭ ﺍﻟﻌﻤﻭﻤﻴﺔ )ﺍﻟﻨﻬﺎﺌﻴﺔ( ﺍﻟﻤﻐﺫﺍﺓ‪.‬‬
‫)ﺡ( ﻴﻤﻜﻥ ﻭﻜﻁﺭﻴﻘﺔ ﻤﺭﺍﺩﻓﺔ ﻟﺤﺴﺎﺏ ﺍﻟﺘﻴﺎﺭ ﺍﻟﻔﻌﻠﻲ ﺍﻟﻤﻁﻠﻭﺏ ﻟﺩﺍﺌﺭﺓ ﺘﻐﺫﻴﺔ ﻋـﺩﺩ ﻤـﻥ‬
‫ﺍﻟﺩﻭﺍﺌﺭ ﺍﻟﻌﻤﻭﻤﻴﺔ )ﺍﻟﻨﻬﺎﺌﻴﺔ( ﺒﺄﻥ ﻴﺘﻡ ﺍﻟﺠﻤﻊ ﺍﻟﺠﺒﺭﻱ ﻟﻠﺘﻴﺎﺭﺍﺕ ﺍﻟﻔﻌﻠﻴـﺔ ﺍﻟﻤﻁﻠﻭﺒـﺔ‬
‫ﻟﻬﺫﻩ ﺍﻟﺩﻭﺍﺌﺭ ﺍﻟﻤﻁﺒﻕ ﻋﻠﻴﻬﺎ ﻤﻌﺎﻤل ﺍﻟﺘﺒﺎﻴﻥ ﻭﻴﻁﺒﻕ ﻋﻠﻴﻬـﺎ ﻤﻌﺎﻤـل ﺘﺒـﺎﻴﻥ ﺁﺨـﺭ‬
‫ﺒﺨﻼﻑ ﺍﻟﻤﺫﻜﻭﺭ ﻓﻲ ﺍﻟﺠﺩﻭل )‪ (٢-٣‬ﺘﺤﺩﺩ ﻗﻴﻤﺘﻪ ﺒﻭﺍﺴـﻁﺔ ﺍﻟﻤﻬﻨـﺩﺱ ﻤﺼـﻤﻡ‬
‫ﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﻭﻴﺘﻭﻗﻑ ﺘﺤﺩﻴﺩ ﻫﺫﻩ ﺍﻟﻘﻴﻤﺔ ﻋﻠﻰ ﻨﻤﻁ ﺍﻻﺴـﺘﺨﺩﺍﻡ ﻟﻠﻤﻭﻗـﻊ ﺃﻭ ﺍﻟﻤﻜـﺎﻥ‬
‫ﻭﻴﻜﻭﻥ ﺫﻟﻙ ﻋﻠﻰ ﻤﺴﺌﻭﻟﻴﺘﻪ‪.‬‬
‫)ﺥ( ﺒﻌﺩ ﺘﺤﺩﻴﺩ ﺘﻴﺎﺭ ﺍﻟﺘﺼﻤﻴﻡ ﻟﺠﻤﻴﻊ ﺍﻟﺩﻭﺍﺌﺭ‪ ،‬ﻴﺘﻡ ﺘﺤﺩﻴﺩ )ﺍﺨﺘﻴﺎﺭ( ﻤﻘﻁـﻊ ﻤﻭﺼـﻼﺕ‬
‫ﺍﻟﺩﻭﺍﺌﺭ ﻋﻠﻰ ﺃﻥ ﻴﺘﻡ ﻤﺭﺍﺠﻌﺔ ﺍﻟﺤﺩ ﺍﻟﻤﺴﻤﻭﺡ ﺒﻪ ﻓﻲ ﻫﺒﻭﻁ ﺍﻟﺠﻬﺩ‪.‬‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪ :(١-٣‬ﺒﻴﺎﻥ ﺘﻘﺩﻴﺭ ﺍﻟﺘﻴﺎﺭ ﺍﻟﺘﺼﻤﻴﻤﻰ ﻟﻤﻭﺼﻼﺕ ﺍﻟﺩﺍﺌﺭﺓ‬


‫ﺍﻟﻤﻐﺫﻴﺔ ﻟﻠﻤﺂﺨﺫ ﺃﻭ ﺍﻷﺠﻬﺯﺓ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻰ‬

‫ﺍﻟﺘﻴﺎﺭ ﺍﻟﺘﺼﻤﻴﻤﻲ‬ ‫ﻨﻭﻉ ﺍﻟﻤﺄﺨﺫ ﺃﻭ ﺍﻷﺠﻬﺯﺓ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ‬


‫ﻋﻠﻰ ﺍﻷﻗل ‪ ٠.٥‬ﺃﻤﺒﻴﺭ ﻟﻠﺒﺭﻴﺯﺓ ﺍﻟﻭﺍﺤﺩﺓ‬ ‫ﻤﺂﺨﺫ ﺴﻌﺔ ‪ ٢‬ﺃﻤﺒﻴﺭ‬
‫ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﻘﻨﻥ )‪ (Rated‬ﻟﻠﺒﺭﻴﺯﺓ‬ ‫ﻤﺂﺨﺫ )ﺒﺭﺍﻴﺯ( ﺒﺨﻼﻑ ﺍﻟﻤﺂﺨﺫ ﺴﻌﺔ ‪ ٢‬ﺃﻤﺒﻴﺭ‬
‫ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﻜﺎﻓﺊ ﻟﺘﻴﺎﺭ ﺍﻟﺤﻤل ﻋﻠﻰ ﺃﻻ ﻴﻘل ﻋﻥ ‪ ١٠٠‬ﻭﺍﺕ‬ ‫ﻤﺨﺭﺝ ﺍﻹﻀﺎﺀﺓ‬
‫ﻟﻜل ﻤﺨﺭﺝ‪.‬‬
‫ﺍﻟﺴﺎﻋﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻭﻤﺂﺨﺫ ﺍﻟﺤﻼﻗﺔ ﻭﻤﺤﻭﻻﺕ ﺍﻷﺠﺭﺍﺱ ﻴﻤﻜﻥ ﺘﺠﺎﻫﻠﻬﺎ ﻜﺤﻤل ﻋﻠﻰ ﺍﻟﺩﻭﺍﺌﺭ‬
‫ﻭﺠﻤﻴﻊ ﺍﻷﺠﻬﺯﺓ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻜﺄﺤﻤﺎل ﻻ ﺘﺯﻴﺩ ﻗﺩﺭﺘﻬﺎ ﻋﻥ‬
‫‪ ٥‬ﻑ‪.‬ﺃ‪.‬‬
‫‪١٠‬ﺃﻤﺒﻴﺭ ‪ ٪٣٠ +‬ﻤﻥ ﺒﻘﻴﺔ ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﻘـﻨﻥ ﻭﻓـﻲ ﺤﺎﻟـﺔ‬ ‫ﺠﻬﺎﺯ ﻁﻬﻲ ﻜﻬﺭﺒﺎﺌﻲ ﻟﻭﺤﺩﺓ ﺴﻜﻨﻴﺔ‬
‫ﻭﺠﻭﺩ ﻤﺨﺭﺝ ﺒﺭﻴﺯﺓ ﺇﻀﺎﻓﻲ ﻀﻤﻥ ﻭﺤﺩﺓ ﺘﺤﻜﻡ ﺍﻟﺠﻬﺎﺯ‬
‫ﻴﻀﺎﻑ ‪ ٥‬ﺃﻤﺒﻴﺭ ﺇﻟﻰ ﺍﻟﻨﺎﺘﺞ‪.‬‬
‫‪ ٪١٠٠‬ﻤﻥ ﻟﻠﺘﻴﺎﺭ ﺍﻟﻤﻘﻨﻥ‪.‬‬ ‫ﺠﻤﻴﻊ ﺍﻷﺠﻬﺯﺓ ﺍﻟﺜﺎﺒﺘﺔ ﺍﻷﺨﺭﻯ‬

‫ﻤﻠﺤﻭﻅﺔ‪:‬‬
‫‪ -‬ﻴﺠﺏ ﺃﻥ ﺘﺼﻤﻡ ﺩﻭﺍﺌﺭ ﺍﻹﻨﺎﺭﺓ ﺍﻟﻌﻤﻭﻤﻴﺔ ﺒﺤﻴﺙ ﺘﻜﻭﻥ ﻗـﺎﺩﺭﺓ ﻋﻠـﻰ ﺤﻤـل ﺍﻟﺘﻴـﺎﺭ‬
‫ﺍﻹﺠﻤﺎﻟﻲ ﺸﺎﻤﻠﺔ ﺘﻴﺎﺭ ﺍﻟﻤﺼﺒﺎﺡ ﻭﺃﺠﻬﺯﺓ ﺘﺸﻐﻴﻠﻪ ﻭﺃﻴﺔ ﺘﻭﺍﻓﻘﻴـﺎﺕ )‪ (Harmonics‬ﻗـﺩ‬

‫‪٣‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻟﺙ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺘﻜﻭﻥ ﻤﻭﺠﻭﺩﺓ ﺒﺎﻟﺩﺍﺌﺭﺓ ﻭﺫﻟﻙ ﻓﻲ ﺤﺎﻟﺔ ﺍﻟﺩﻭﺍﺌﺭ ﺍﻟﻌﻤﻭﻤﻴﺔ )ﺍﻟﻨﻬﺎﺌﻴﺔ( ﻟﻺﻨـﺎﺭﺓ ﻭﺍﻟﺘـﻲ‬
‫ﺘﻐﺫﻱ ﻤﺼﺎﺒﻴﺢ ﺍﻟﺘﻔﺭﻴﻎ ﺍﻟﻜﻬﺭﺒﺎﺌﻲ‪.‬‬
‫‪ -‬ﻴﺘﻡ ﺘﺤﺩﻴﺩ ﺍﻟﺤﻤل ﻭﻓﻰ ﺤﺎﻟﺔ ﻋﺩﻡ ﺘﻭﺍﻓﺭ ﻤﻌﻠﻭﻤﺎﺕ ﻜﺎﻓﻴﺔ ﻴﺤﺴﺏ ﻜﺎﻵﺘﻲ‪:‬‬
‫ﺍﻟﺤﻤل )ﻓﻭﻟﺕ‪ .‬ﺃﻤﺒﻴﺭ( = ﻗﺩﺭﺓ ﺍﻟﻤﺼﺒﺎﺡ ﺒﺎﻟﻭﺍﺕ × ‪) ١.٨‬ﻋﻠﻰ ﺍﻷﻗل(‬
‫ﻭﻴﻼﺤﻅ ﺃﻥ ﺭﻗﻡ ‪ ١.٨‬ﻤﺒﻨﻲ ﻋﻠﻰ ﺃﺴﺎﺱ ﺃﻥ ﺘﻜﻭﻥ ﺍﻟﺩﺍﺌﺭﺓ ﺫﺍﺕ ﻤﻌﺎﻤل ﻗﺩﺭﺓ ﻴﺴـﺎﻭﻱ‬
‫ﺃﻭ ﻴﺯﻴﺩ ﻋﻥ ‪ ،٠.٨٥‬ﻤﻊ ﻤﺭﺍﻋﺎﺓ ﺍﻟﻔﻘﺩ ﺍﻟﻨﺎﺘﺞ ﻋـﻥ ﺃﺠﻬـﺯﺓ ﺍﻟﺘﺸـﻐﻴل ﻭﻋـﻥ ﺘﻴـﺎﺭﺍﺕ‬
‫ﺍﻟﺘﻭﺍﻓﻘﻴﺎﺕ‪.‬‬
‫ﺠﺩﻭل ﺭﻗﻡ )‪ :(٢-٣‬ﺤﺎﻻﺕ ﺍﻟﺴﻤﺎﺡ ﺒﺎﺴﺘﺨﺩﺍﻡ ﻤﻌﺎﻤﻼﺕ ﺍﻟﺘﺒﺎﻴﻥ ﻟﺘﺤﺩﻴﺩ ﺍﻟﺘﻴﺎﺭ‬
‫ﺍﻟﺘﺼﻤﻴﻤﻰ ﻟﻠﺩﻭﺍﺌﺭ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻰ‬

‫ﻤﻜﺎﺘﺏ ﻭﻤﺘﺎﺠﺭ ﻭﻤﺒﺎﻥ‬


‫ﻓﻨﺎﺩﻕ ﺼﻐﻴﺭﺓ ﺃﻭ ﻤﺒﺎﻨﻲ ﻋﺎﻤﺔ‬ ‫ﻭﺤﺩﺓ ﺴﻜﻨﻴﺔ ﺃﻭ‬ ‫ﻋﻤﺎﺭﺍﺕ ﺘﺘﻜﻭﻥ ﻤﻥ ﻋﺩﺓ‬
‫ﻋﺎﻤﺔ ﺨﻼﻑ ﺍﻟﻭﺭﺵ‬ ‫ﻨﻭﻉ ﺍﻟﺤﻤل‬
‫ﻟﻠﻨﻭﻡ ﻭﺍﻟﻤﻌﻴﺸﺔ‬ ‫ﻭﺤﺩﺍﺕ ﺴﻜﻨﻴﺔ ﺨﺎﺼﺔ‬ ‫ﻭﺤﺩﺍﺕ ﺴﻜﻨﻴﺔ‬
‫ﻭﺍﻟﻤﺼﺎﻨﻊ‬
‫‪ ٪٩٠‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﻠﻲ‬ ‫‪ ٪٧٥‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﻠﻲ‬ ‫‪ ٪٦٦‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﻠﻲ‬ ‫‪ ٪٥٠‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﻠﻲ‬ ‫ﺍﻹﻨﺎﺭﺓ‬
‫‪ ٪١٠٠‬ﻤـــﻥ ﺍﻟﺘﻴـــﺎﺭ‬ ‫‪ ٪١٠٠‬ﻤﻥ ﺍﻟﺘﻴﺎﺭ ﺍﻟﺘﺼـﻤﻴﻤﻲ‬ ‫‪ ٪١٠٠‬ﻤــﻥ ﺍﻟﺘﻴــﺎﺭ‬ ‫‪ ٪١٠٠‬ﻤـــﻥ ﺍﻟﺘﻴـــﺎﺭ‬ ‫ﺍﻟﻤﺂﺨﺫ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ‬
‫ﺍﻟﺘﺼﻤﻴﻤﻲ ﻷﻜﺒـﺭ ﻤﺂﺨـﺫ‬ ‫ﻷﻜﺒﺭ ﻤﺂﺨﺫ ﺒﺎﻟﺩﺍﺌﺭﺓ‪.‬‬ ‫ﺍﻟﺘﺼﻤﻴﻤﻲ ﻷﻜﺒﺭ ﻤﺂﺨﺫ‬ ‫ﺍﻟﺘﺼﻤﻴﻤﻲ ﻷﻜﺒـﺭ ﻤﺂﺨـﺫ‬ ‫)ﺍﻟﺒﺭﺍﻴﺯ(‬
‫ﺒﺎﻟﺩﺍﺌﺭﺓ‬ ‫‪ ٪٤٠+‬ﻤﻥ ﺍﻟﺘﻴﺎﺭ ﺍﻟﺘﺼـﻤﻴﻤﻲ‬ ‫ﺒﺎﻟﺩﺍﺌﺭﺓ‪.‬‬ ‫ﺒﺎﻟﺩﺍﺌﺭﺓ‪.‬‬
‫‪ ٪٧٥+‬ﻤــﻥ ﻤﺠﻤــﻭﻉ‬ ‫ﻟﺒﺎﻗﻲ ﻤﺂﺨﺫ ﺍﻟﺩﺍﺌﺭﺓ‪.‬‬ ‫ـﻭﻉ‬‫‪ ٪٤٠+‬ﻤـﻥ ﻤﺠﻤـ‬ ‫‪ ٪٤٠ +‬ﻤــﻥ ﻤﺠﻤــﻭﻉ‬
‫ﺍﻟﺘﻴﺎﺭﺍﺕ ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﻟﺒﺎﻗﻲ‬ ‫‪ ٪٧٥+‬ﻤﻥ ﺍﻟﺘﻴﺎﺭ ﺍﻟﺘﺼـﻤﻴﻤﻲ‬ ‫ﺍﻟﺘﻴﺎﺭﺍﺕ ﺍﻟﺘﺼـﻤﻴﻤﻴﺔ‬ ‫ﺍﻟﺘﻴﺎﺭﺍﺕ ﺍﻟﺘﺼﻤﻴﻤﻴﺔ ﻟﺒﺎﻗﻲ‬
‫ﻤﺂﺨﺫ ﺍﻟﺩﺍﺌﺭﺓ‬ ‫ﻟﺒﺎﻗﻲ ﺍﻟﻤﺂﺨﺫ ﻓﻲ ﺩﻭﺍﺌﺭ ﺍﻷﻤﺎﻜﻥ‬ ‫ﻟﺒﺎﻗﻲ ﻤﺂﺨﺫ ﺍﻟﺩﺍﺌﺭﺓ‪.‬‬ ‫ﻤﺂﺨﺫ ﺍﻟﺩﺍﺌﺭﺓ‬
‫ﺍﻟﻌﺎﻤﺔ ﺒﺎﻟﻤﺒﻨﻲ‪.‬‬
‫‪ ٪١٠٠‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل‬ ‫‪ ٪١٠٠‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل ﻷﻜﺒﺭ‬ ‫ـﺎﻟﻲ‬
‫ـﻥ ﺇﺠﻤـ‬‫‪ ٪١٠٠‬ﻤـ‬ ‫‪ ٪١٠٠‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل‬ ‫ﺍﻷﺠﻬﺯﺓ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ‬
‫ﻷﻜﺒﺭ ﺠﻬﺎﺯ‬ ‫ﺠﻬﺎﺯ‬ ‫ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل ﻟﻤﺠﻤﻭﻉ‬ ‫ﻷﻜﺒﺭ ﺠﻬﺎﺯ‪.‬‬ ‫ﺍﻟﺜﺎﺒﺘﺔ ﺨﻼﻑ‬
‫‪ ٪٧٥+‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل‬ ‫ـل‬
‫‪ ٪٨٠+‬ﻤـﻥ ﺍﻟﺤﻤـل ﺍﻟﻜﺎﻤـ‬ ‫ﺍﻷﺠﻬﺯﺓ ﺤﺘﻰ ﺴﻌﺔ ‪١٠‬‬ ‫‪ ٪٥٠+‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل‬ ‫ﺍﻟﻤﺤﺭﻜﺎﺕ‬
‫ﻟﺒﺎﻗﻲ ﺍﻷﺠﻬﺯﺓ‪.‬‬ ‫ﻟﻠﺠﻬﺎﺯ ﺍﻷﻭل ﺍﻟﺫﻱ ﻴﻠﻲ ﺃﻜﺒـﺭ‬ ‫ﺃﻤﺒﻴﺭ‬ ‫ﻟﻠﺠﻬﺎﺯ ﺍﻷﻭل ﺍﻟﺫﻱ ﻴﻠـﻲ‬ ‫ﻭﺍﻟﺴﺨﺎﻨﺎﺕ ﻭﺃﺠﻬﺯﺓ‬
‫ﺠﻬﺎﺯ‬ ‫‪ ٪٥٠+‬ﻤــﻥ ﺍﻟﺤﻤــل‬ ‫ﺃﻜﺒﺭ ﺠﻬﺎﺯ‬ ‫ﺍﻟﻁﻬﻲ‬
‫‪ ٪٦٠+‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل ﻟﺒﺎﻗﻲ‬ ‫ﻟﻸﺠﻬﺯﺓ ﺍﻟﺘﻰ ﺤﻤﻠﻬـﺎ‬ ‫‪ ٪٣٣+‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل‬
‫ﺍﻷﺠﻬﺯﺓ‬ ‫ﻴﺯﻴﺩ ﻋﻥ ‪ ١٠‬ﺃﻤﺒﻴﺭ‬ ‫ﻟﻠﺠﻬﺎﺯ ﺍﻟﺜﺎﻨﻲ ﺍﻟﺫﻱ ﻴﻠـﻲ‬
‫ﺃﻜﺒﺭ ﺠﻬﺎﺯ‬
‫‪ ٪٢٠+‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل‬
‫ﻟﺒﺎﻗﻲ ﺍﻷﺠﻬﺯﺓ‬
‫‪ ٪١٠٠‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل‬ ‫‪ ٪١٠٠‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل ﻷﻜﺒﺭ‬ ‫‪ ٪١٠٠‬ﻤــﻥ ﺍﻟﺤﻤــل‬ ‫‪ ٪١٠٠‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل‬ ‫ﺃﺠﻬﺯﺓ ﺍﻟﻁﻬﻲ‬
‫ﻷﻜﺒﺭ ﺠﻬﺎﺯ‪.‬‬ ‫ﺠﻬﺎﺯ‪.‬‬ ‫ﺍﻟﻜﺎﻤل ﻟﻸﺠﻬﺯﺓ ﺤﺘـﻰ‬ ‫ﻷﻜﺒﺭ ﺠﻬﺎﺯ‬ ‫ﺍﻟﺜﺎﺒﺘﺔ‬
‫‪ ٪٨٠+‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل‬ ‫ـل‬
‫‪ ٪٨٠+‬ﻤـﻥ ﺍﻟﺤﻤـل ﺍﻟﻜﺎﻤـ‬ ‫‪ ١٠‬ﺃﻤﺒﻴﺭ‪.‬‬ ‫‪ ٪٥٠+‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل‬
‫ﻟﻠﺠﻬﺎﺯ ﺍﻷﻭل ﺍﻟﺫﻱ ﻴﻠـﻲ‬ ‫ﻟﻠﺠﻬﺎﺯ ﺍﻷﻭل ﺍﻟﺫﻱ ﻴﻠﻲ ﺃﻜﺒـﺭ‬ ‫‪ ٪٣٠+‬ﻤــﻥ ﺍﻟﺤﻤــل‬ ‫ﻟﻠﺠﻬﺎﺯ ﺍﻷﻭل ﺍﻟﺫﻱ ﻴﻠـﻲ‬
‫ﺃﻜﺒﺭ ﺠﻬﺎﺯ‪.‬‬ ‫ﺠﻬﺎﺯ‪.‬‬ ‫ﺍﻟﻤﻘﻨﻥ ﺍﻟﺯﺍﺌﺩ ﻋﻠﻰ ‪١٠‬‬ ‫ﺃﻜﺒﺭ ﺠﻬﺎﺯ‬
‫‪ ٪٦٠+‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل‬ ‫‪ ٪٦٠+‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل ﻟﺒﺎﻗﻲ‬ ‫ﺃﻤﺒﻴﺭ‬ ‫‪ ٪٣٣‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤـل‬
‫ﻟﺒﺎﻗﻲ ﺍﻷﺠﻬﺯﺓ‬ ‫ﺍﻷﺠﻬﺯﺓ‬ ‫‪ ٥+‬ﺃﻤﺒﻴــﺭ ﺇﺫﺍ ﻜــﺎﻥ‬ ‫ﻟﻠﺠﻬﺎﺯ ﺍﻟﺜﺎﻨﻲ ﺍﻟﺫﻱ ﻴﻠـﻲ‬
‫ﻴﻭﺠﺩ ﺒﺎﻟﺠﻬﺎﺯ ﻤﺨـﺭﺝ‬ ‫ﺃﻜﺒﺭ ﺠﻬﺎﺯ‬
‫ﺇﻀﺎﻓﻲ‪.‬‬ ‫‪ ٪٢٠+‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل‬
‫ﻟﺒﺎﻗﻲ ﺍﻷﺠﻬﺯﺓ‬
‫‪ ٪١٠٠‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل‬ ‫‪ ٪١٠٠‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل ﻷﻜﺒﺭ‬ ‫‪ ٪١٠٠‬ﻤﻥ ﺍﻟﺤﻤل‬ ‫‪ ٪١٠٠‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل‬ ‫ﺍﻟﻤﺤﺭﻜﺎﺕ‬
‫ﻷﻜﺒﺭ ﻤﺤﺭﻙ‬ ‫ﻤﺤﺭﻙ‬ ‫ﺍﻟﻜﺎﻤل ﻷﻜﺒﺭ ﻤﺤﺭﻙ‬ ‫ﻷﻜﺒﺭ ﻤﺤﺭﻙ‬ ‫ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ "ﺨﻼﻑ‬
‫‪ ٪٨٠+‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل‬ ‫‪ ٪٥٠+‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل ﻟﺒﺎﻗﻲ‬ ‫‪ ٪٥٠ +‬ﻤﻥ ﺍﻟﺤﻤل‬ ‫‪ ٪٥٠ +‬ﻤﻥ ﺍﻟﺤﻤل ﻟﺒﺎﻗﻲ‬ ‫ﻤﺤﺭﻜﺎﺕ ﺍﻟﻤﺼﺎﻋﺩ‬

‫‪٣‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻟﺙ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻤﻜﺎﺘﺏ ﻭﻤﺘﺎﺠﺭ ﻭﻤﺒﺎﻥ‬


‫ﻓﻨﺎﺩﻕ ﺼﻐﻴﺭﺓ ﺃﻭ ﻤﺒﺎﻨﻲ ﻋﺎﻤﺔ‬ ‫ﻭﺤﺩﺓ ﺴﻜﻨﻴﺔ ﺃﻭ‬ ‫ﻋﻤﺎﺭﺍﺕ ﺘﺘﻜﻭﻥ ﻤﻥ ﻋﺩﺓ‬
‫ﻋﺎﻤﺔ ﺨﻼﻑ ﺍﻟﻭﺭﺵ‬ ‫ﻨﻭﻉ ﺍﻟﺤﻤل‬
‫ﻟﻠﻨﻭﻡ ﻭﺍﻟﻤﻌﻴﺸﺔ‬ ‫ﻭﺤﺩﺍﺕ ﺴﻜﻨﻴﺔ ﺨﺎﺼﺔ‬ ‫ﻭﺤﺩﺍﺕ ﺴﻜﻨﻴﺔ‬
‫ﻭﺍﻟﻤﺼﺎﻨﻊ‬
‫ﻟﻠﻤﺤﺭﻙ ﺍﻟﺫﻱ ﻴﻠﻲ ﺃﻜﺒـﺭ‬ ‫ﺍﻟﻤﺤﺭﻜﺎﺕ‪.‬‬ ‫ﻟﺒﺎﻗﻲ ﺍﻟﻤﺤﺭﻜﺎﺕ‬ ‫ﺍﻟﻤﺤﺭﻜﺎﺕ‬ ‫ﺍﻟﺘﻲ ﻟﻬﺎ ﺍﻋﺘﺒﺎﺭﺍﺕ‬
‫ﻤﺤﺭﻙ‪.‬‬ ‫ﺨﺎﺼﺔ"‬
‫‪ ٪٦٠+‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل‬
‫ﻟﺒﺎﻗﻲ ﺍﻟﻤﺤﺭﻜﺎﺕ‪.‬‬
‫ﺘﻘﺩﺭ ﺒﻤﻌﺭﻓﺔ ﺍﻟﻤﺨﺘﺼـﻴﻥ‬ ‫‪ ٪١٠٠‬ﻤﻥ ﺍﻟﺤﻤل ﻷﻜﺒﺭ ﺴﺨﺎﻥ‬ ‫ﺍﻟﺴﺨﺎﻨﺎﺕ‬
‫ﺘﺒﻌﺎﹰ ﻟﻅـﺭﻭﻑ ﺍﻟﺘﺸـﻐﻴل‬ ‫‪ ٪١٠٠+‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل ﻟﻠﺴﺨﺎﻥ ﺍﻟﺫﻱ ﻴﻠﻲ ﺃﻜﺒﺭ ﺴﺨﺎﻥ‬ ‫ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻤﺘﻘﻁﻌﺔ‬
‫ﺍﻟﻔﻌﻠﻴﺔ ﺍﻟﻤﺤﺘﻤﻠﺔ‪.‬‬ ‫‪ ٪٢٥+‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل ﻟﺒﺎﻗﻲ ﺍﻟﺴﺨﺎﻨﺎﺕ‪.‬‬ ‫ﺍﻟﺘﺸﻐﻴل‬
‫ﺍﻟﺴﺨﺎﻨﺎﺕ‬
‫‪ ٪١٠٠‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل ﻓﻲ ﺠﻤﻴﻊ ﺍﻟﺤﺎﻻﺕ‪.‬‬ ‫ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻤﺴﺘﻤﺭﺓ‬
‫ﺍﻟﺘﺸﻐﻴل‬
‫)‪ (١‬ﻟﺤﺴﺎﺏ ﻤﻐﺫﻴﺎﺕ ﺍﻟﻌﻤﺎﺭﺍﺕ ﺍﻟﺴﻜﻨﻴﺔ ﺍﻟﻤﻜﻭﻨﺔ ﻤﻥ ﻋﺩﺓ ﻭﺤﺩﺍﺕ ﺴﻜﻨﻴﺔ‪ ،‬ﺘﺅﺨﺫ ﺍﻟﻘـﻴﻡ‬
‫ﺍﻟﺨﺎﺼﺔ ﺒﻬﺫﻩ ﺍﻟﻌﻤﺎﺭﺍﺕ ﻭﻻ ﻴﺅﺨﺫ ﻤﺠﻤﻭﻉ ﺍﻟﻘﻴﻡ ﺍﻟﺨﺎﺼـﺔ ﺒﺎﻟﻭﺤـﺩﺍﺕ ﺍﻟﺴـﻜﻨﻴﺔ‬
‫ﺍﻟﻤﻜﻭﻨﺔ ﻤﻨﻬﺎ ﺍﻟﻌﻤﺎﺭﺓ‪.‬‬
‫)‪ (٢‬ﺘﻌﺘﺒﺭ ﺍﻟﺴﺨﺎﻨﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻤﻌﺩﺓ ﻤﺘﻘﻁﻌـﺔ ﺍﻟﺘﺸـﻐﻴل‪ ،‬ﺇﺫﺍ ﺯﺍﺩﺕ ﻗـﺩﺭﺘﻬﺎ ﻋـﻥ‬
‫‪٣‬ﻜﻴﻠﻭﻭﺍﺕ‪ ،‬ﺤﻴﺙ ﺃﻥ ﻤﻌﺩل ﺍﺴﺘﻬﻼﻜﻬﺎ ﺍﻟﻜﻠﻲ ﻟﻠﻜﻬﺭﺒﺎﺀ ﺒﺎﻟﻨﺴﺒﺔ ﻟﺴﻌﺘﻬﺎ ﻴﻌﻨـﻲ ﺃﻥ‬
‫ﺘﺸﻐﻴﻠﻬﺎ ﺴﻴﻜﻭﻥ ﻤﺘﻘﻁﻌﺎﹰ ﻭﺘﺴﺘﺨﺩﻡ ﻟﻠﺘﺴﺨﻴﻥ ﺍﻟﻭﻗﺘﻲ ﺍﻟﺴﺭﻴﻊ‪.‬‬
‫)‪ (٣‬ﻴﺠﺏ ﺃﻥ ﻴﺘﻡ ﺒﺎﻟﻨﺴﺒﺔ ﻟﻠﻌﻤﺎﺭﺍﺕ ﺍﻟﺴﻜﻨﻴﺔ ﺍﻟﻜﺒﻴﺭﺓ ﻭﺍﻟﻔﻨـﺎﺩﻕ ﺍﻟﻜﺒﻴـﺭﺓ ﻭﺍﻟﻤﺼـﺎﻨﻊ‬
‫ﺍﻟﻜﺒﻴﺭﺓ‪ .... ،‬ﺍﻟﺦ‪ ،‬ﺇﺠﺭﺍﺀ ﺍﻟﺘﺼﻤﻴﻡ ﺒﻭﺍﺴﻁﺔ ﻤﻬﻨﺩﺱ ﻜﻬﺭﺒﺎﺀ ﻨﻘﺎﺒﻲ ﻋﻠـﻰ ﺩﺭﺠـﺔ‬
‫ﻋﺎﻟﻴﺔ ﻤﻥ ﺍﻟﻜﻔﺎﺀﺓ ﻭﻴﺘﻡ ﺍﻟﺭﺠﻭﻉ ﺃﻴﻀﺎﹰ ﺇﻟﻰ ﺍﻟﺸﺭﻜﺎﺕ ﺍﻟﻤﺼﻨﻌﺔ ﻟﻸﺠﻬﺯﺓ‪.‬‬

‫ﺤﺴﺎﺏ ﺍﻟﻁﻠﺏ ﺍﻷﻗﺼﻰ ﺍﻟﻤﻁﻠﻭﺏ ﻟﻤﺒﻨﻲ ﺒﻤﻌﻠﻭﻤﻴﺔ ﺍﻟﻤﺴﺎﺤﺔ ﻭﺘﻘﺩﻴﺭ ﻤﺴﺘﻭﻯ ﺍﻻﺴﻜﺎﻥ‬ ‫‪٤-٣‬‬
‫)‪ (١‬ﻴﻘﺩﺭ ﺍﻟﻁﻠﺏ ﻋﻠﻰ ﺍﻟﺤﻤل ﺒﺎﻟﻜﻴﻠﻭ ﻓﻭﻟﺕ ﺃﻤﺒﻴﺭ ﻟﻜل ﻤﺎﺌﺔ ﻤﺘﺭ ﻤﺭﺒﻊ ﻤـﻥ ﺍﻟﻤﺒـﺎﻨﻲ‬
‫ﺍﻟﺘﻲ ﻻ ﻴﺯﻴﺩ ﺍﺭﺘﻔﺎﻋﻬﺎ ﻋﻥ ‪ ١٥‬ﻁﺎﺒﻘﺎﹰ ﺤﺴﺏ ﺍﻟﻤﻭﻀﺢ ﺒﺎﻟﺠﺩﻭل )‪ (٣-٣‬ﻭﻟﻠﻤﺒـﺎﻨﻲ‬
‫ﺍﻟﺘﻲ ﻴﺯﻴﺩ ﺍﺭﺘﻔﺎﻋﻬﺎ ﻋﻥ ‪ ١٥‬ﻁﺎﺒﻘﺎﹰ ﺤﺴﺏ ﺍﻟﻤﻭﻀﺢ ﺒﺎﻟﺠﺩﻭل )‪.(٤-٣‬‬
‫)‪ (٢‬ﻴﺤﺩﺩ ﺍﺭﺘﻔﺎﻉ ﺍﻟﻌﻘﺎﺭ ﺒﻤﻘﺩﺍﺭ ﻤﺭﺓ ﻭﻨﺼﻑ ﻋﺭﺽ ﺍﻟﺸﺎﺭﻉ‪ ،‬ﻭﻴﺤﺴﺏ ﺍﺭﺘﻔـﺎﻉ ﻜـل‬
‫ﺩﻭﺭ ﺒﻤﺘﻭﺴﻁ ‪٣‬ﻤﺘﺭ‪.‬‬
‫)‪ (٣‬ﻴﺘﻡ ﺍﻻﺴﺘﺭﺸﺎﺩ ﺒﺎﻟﺠﺩﻭل )‪ (٦-٣) ، (٥-٣‬ﻓﻰ ﻨﻁﺎﻕ ﺍﻟﻘﺎﻫﺭﺓ ﺍﻟﻜﺒﺭﻯ‪.‬‬
‫)‪ (٤‬ﻴﺘﻡ ﺍﻟﺭﺠﻭﻉ ﺇﻟﻰ ﺸﺭﻜﺎﺕ ﺍﻟﺘﻭﺯﻴﻊ ﺍﻟﻤﺨﺘﺼﺔ ﺒﺎﻟﻨﺴﺒﺔ ﻟﻠﻤﺤﺎﻓﻅﺎﺕ ﺍﻷﺨﺭﻯ‪.‬‬

‫‪٣‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻟﺙ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪ :(٣-٣‬ﻨﻤﺎﺫﺝ ﻨﻤﻁﻴﺔ ﻟﻠﻁﻠﺏ ﻋﻠﻰ ﺍﻟﺤﻤل ﺒﻭﺤﺩﺍﺕ ﺍﻟﻤﺒﺎﻨﻲ ﺍﻟﺴﻜﻨﻴﺔ‬
‫ﺍﻟﺘﻰ ﻴﻘل ﺍﺭﺘﻔﺎﻋﻬﺎ ﻋﻥ ‪ ١٥‬ﻁﺎﺒﻘﺎﹰ‬

‫ﻁﻠﺏ ﺍﻟﺤﻤل ﻟﻜل ﻤﺎﺌﺔ ﻤﺘﺭ ﻤﺭﺒﻊ‬

‫)ﻙ‪.‬ﻑ‪.‬ﺃ(‬

‫ﺇﺩﺍﺭﻯ‬ ‫ﺴﻜﻨﻰ‬

‫‪٢ – ١.٥‬‬ ‫ﺇﺴﻜﺎﻥ ﻤﻨﺨﻔﺽ ﺍﻟﺘﻜﺎﻟﻴﻑ‬

‫‪١٢ - ٦‬‬ ‫‪٤ – ٢.٥‬‬ ‫ﺇﺴﻜﺎﻥ ﻤﺘﻭﺴﻁ‬

‫‪١٠ - ٦‬‬ ‫ﺇﺴﻜﺎﻥ ﻓﺎﺨﺭ‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪ :(٤-٣‬ﻨﻤﺎﺫﺝ ﻨﻤﻁﻴﺔ ﻟﻠﻁﻠﺏ ﻋﻠﻰ ﺍﻟﺤﻤل ﺒﻭﺤﺩﺍﺕ ﺍﻟﻤﺒﺎﻨﻲ ﺍﻟﺴﻜﻨﻴﺔ‬
‫ﺍﻟﺘﻲ ﻴﺯﻴﺩ ﺍﺭﺘﻔﺎﻋﻬﺎ ﻋﻥ ‪ ١٥‬ﻁﺎﺒﻘﺎﹰ‬

‫ﻁﻠﺏ ﺍﻟﺤﻤل ﻟﻜل ﻤﺎﺌﺔ ﻤﺘﺭ ﻤﺭﺒﻊ‬

‫)ﻙ‪.‬ﻑ‪.‬ﺃ(‬

‫ﺇﺩﺍﺭﻯ‬ ‫ﺴﻜﻨﻰ‬

‫‪١٢‬‬ ‫‪١٠ - ٨‬‬

‫‪٣‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻟﺙ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪ :(٥-٣‬ﺍﻟﺴﻌﺎﺕ ﺍﻟﻨﻤﻁﻴﺔ ﻟﻭﺤﺩﺍﺕ ﺍﻟﻤﺒﺎﻨﻰ‬


‫ﺍﻟﺘﻰ ﻻ ﻴﺯﻴﺩ ﺍﺭﺘﻔﺎﻋﻬﺎ ﻋﻥ ‪ ١٥‬ﺩﻭﺭﺍﹰ ﺒﺎﻟﻘﺎﻫﺭﺓ ﺍﻟﻜﺒﺭﻯ‬

‫ﺍﻟﺴﻌﺔ‬ ‫ﺍﻟﺴﻌﺔ‬ ‫ﺍﻟﺴﻌﺔ‬


‫‪٢‬‬ ‫‪٢‬‬ ‫‪٢‬‬
‫ﻙ‪.‬ﻑ‪.‬ﺃ‪ ١٠٠/‬ﻡ‬ ‫ﻙ‪.‬ﻑ‪.‬ﺃ‪ ١٠٠/‬ﻡ‬ ‫ﻙ‪.‬ﻑ‪.‬ﺃ‪ ١٠٠/‬ﻡ‬
‫ﺃﺴﻡ ﺍﻟﻤﻨﻁﻘﺔ‬ ‫ﺃﺴﻡ ﺍﻟﻤﻨﻁﻘﺔ‬ ‫ﺃﺴﻡ ﺍﻟﻤﻨﻁﻘﺔ‬
‫ﻤﺤﻼﺕ ﺃﻭ‬ ‫ﻤﺤﻼﺕ ﺃﻭ‬ ‫ﻤﺤﻼﺕ ﺃﻭ‬
‫ﻤﻜﺎﺘﺏ‬ ‫ﺴﻜﻥ‬ ‫ﻤﻜﺎﺘﺏ‬ ‫ﺴﻜﻥ‬ ‫ﻤﻜﺎﺘﺏ‬ ‫ﺴﻜﻥ‬
‫ﺍﻟﺩﻗﻰ‬ ‫ﺍﻟﺴﻴﺩﺓ ﺯﻴﻨﺏ‬ ‫ﺸﺒﺭﺍ‬
‫ﻤﺩﻴﻨﺔ‬
‫ﺍﻟﻤﻬﻨﺩﺴﻴﻥ‬ ‫‪٤‬‬ ‫‪٢‬‬ ‫ﻀﺭﻴﺢ ﺴﻌﺩ‬ ‫‪١٢‬‬ ‫‪٣‬‬ ‫ﺸﺎﺭﻉ ﺸﺒﺭﺍ‬
‫ﻤﺩﻴﻨﺔ‬
‫ﺍﻟﻀﺒﺎﻁ‬ ‫‪٤‬‬ ‫‪٢‬‬ ‫ﻋﺎﺒﺩﻴﻥ‬ ‫‪٨‬‬ ‫‪١.٥‬‬ ‫ﺭﻭﺽ ﺍﻟﻔﺭﺝ‬
‫ﺍﻟﻌﺠﻭﺯﺓ‬ ‫‪٤‬‬ ‫‪٢‬‬ ‫ﻤﺼﺭ ﺍﻟﻘﺩﻴﻤﺔ‬ ‫‪٨‬‬ ‫‪١.٥‬‬ ‫ﺠﺯﻴﺭﺓ ﺒﺩﺭﺍﻥ‬
‫‪٥‬‬ ‫ﺍﻟﺩﻗﻰ‬ ‫‪٤‬‬ ‫‪٢‬‬ ‫ﺍﻟﺴﻴﺩﺓ ﺯﻴﻨﺏ‬ ‫‪٨‬‬ ‫‪١.٥‬‬ ‫ﺠﺴﺭ ﺍﻟﺒﺤﺭ‬
‫ﺍﻟﺼﺤﻔﻴﻴﻥ‬ ‫‪٤‬‬ ‫‪٢‬‬ ‫ﺯﻴﻥ ﺍﻟﻌﺎﺒﺩﻴﻥ‬ ‫‪١٢‬‬ ‫‪٤‬‬ ‫ﺃﻏﺎﺨﺎﻥ‬
‫ﺍﻷﻭﻗﺎﻑ‬ ‫‪٦‬‬ ‫‪٣‬‬ ‫ﺍﻟﻤﻨﻴل‬ ‫‪٩‬‬ ‫‪٣‬‬ ‫ﺃﺭﺽ ﺸﺭﻴﻑ‬
‫ﺍﻟﻤﻌﻠﻤﻴﻥ‬ ‫‪٩‬‬ ‫‪٦‬‬ ‫ﺠﺎﺩﺭﻥ ﺴﻴﺘﻰ‬ ‫‪٦‬‬ ‫‪١.٥‬‬ ‫ﺍﻟﺯﺍﻭﻴﺔ ﺍﻟﺤﻤﺭﺍﺀ‬
‫ﻭﺍﻟﺸﺭﺍﺒﻴﺔ‬
‫ﺍﻟﺠﻴﺯﺓ‬ ‫ﺍﻟﻘﻠﻌﺔ‬ ‫‪٨‬‬ ‫‪١.٥‬‬ ‫ﺒﺎﻗﻰ ﺍﻟﻤﻨﺎﻁﻕ‬
‫ﺒﻴﻥ‬ ‫ﺍﻟﺨﺭﻁﺔ ﺍﻟﻘﺩﻴﻤﺔ‬
‫‪٣‬‬ ‫‪٣‬‬ ‫‪١.٥‬‬ ‫ﺍﻟﺤﻠﻤﻴﺔ‬
‫ﺍﻟﺴﺭﺍﻴﺎﺕ‬ ‫ﺍﺒﻭ ﺴﺒﺤﺔ‬
‫‪٣‬‬ ‫ﻤﻴﺕ ﻋﻘﺒﺔ‬ ‫‪٣‬‬ ‫‪١.٥‬‬ ‫ﺍﻟﺴﻴﺩﺓ ﻋﺎﺌﺸﺔ‬ ‫‪٦‬‬ ‫‪١.٥‬‬ ‫ﻋﻴﻥ ﺸﻤﺱ‬
‫ﺩﺭﺏ ﺍﻟﺤﺼﺭ‬
‫ﺍﻟﺤﻠﻤﻴﺔ ﺍﻟﻘﺩﻴﻤﺔ‬
‫ﺩﺍﻴﺭ ﺍﻟﻨﺎﺤﻴﺔ‬ ‫‪٤‬‬ ‫‪٢‬‬ ‫ﻋﺒﺩ ﺍﻟﺭﺤﻤﻥ‬ ‫‪٦‬‬ ‫‪١.٥‬‬ ‫ﺍﻟﻤﻁﺭﻴﺔ‬
‫ﺒﻭﻻﻕ‬ ‫ﺍﻟﺤﻠﻤﻴﺔ ﺍﻟﺠﺩﻴﺩﺓ‬
‫‪٤‬‬ ‫‪٢‬‬ ‫‪٦‬‬ ‫‪١.٥‬‬ ‫ﺍﻟﻭﺍﻴﻠﻰ‬
‫ﺍﻟﺩﻜﺭﻭﺭ‬ ‫ﻤﺼﻁﻔﻰ ﺴﺭﻯ‬
‫‪١.٥‬‬
‫ﻤﻴﺕ ﻋﻘﺒﺔ‬ ‫‪٤‬‬ ‫‪٢‬‬ ‫ﺍﻟﺩﺭﺏ ﺍﻷﺤﻤﺭ‬ ‫‪٦‬‬ ‫‪٣‬‬ ‫ﺍﻟﻘﺒﺔ‬
‫ﺍﻟﺒﻠﺩ‬
‫ﺃﺭﺽ ﺍﻟﻠﻭﺍﺀ‬ ‫‪٦‬‬ ‫‪٣‬‬ ‫ﺵ ﺍﻷﺯﻫﺭ‬
‫ﺇﻤﺒﺎﺒﺔ‬ ‫‪٤‬‬ ‫‪٢‬‬ ‫ﺵ ﺒﻭﺭ ﺴﻌﻴﺩ‬ ‫ﺍﻟﻌﺒﺎﺴﻴﺔ‬
‫ﻤﻴﺩﺍﻥ ﺒﺭﻜﺔ‬
‫ﺍﻟﻬﺭﻡ‬ ‫‪٤‬‬ ‫‪٢‬‬ ‫ﺍﻟﻔﻴل‬ ‫‪٨‬‬ ‫‪٣‬‬ ‫ﺍﻟﻌﺒﺎﺴﻴﺔ ﻭﺍﻟﻅﺎﻫﺭ‬
‫‪٥‬‬ ‫ﺸﺎﺭﻉ ﺍﻟﻬﺭﻡ‬ ‫ﺍﻟﻤﻌﺎﺩﻯ‬ ‫‪٨‬‬ ‫‪٣‬‬ ‫ﻤﺼﺭ ﻭﺍﻟﺴﻭﺩﺍﻥ‬
‫ﺍﻟﻁﺎﻟﺒﻴﺔ‬ ‫‪٧‬‬ ‫‪٣‬‬ ‫ﺍﻟﻤﻌﺎﺩﻯ ﺍﻟﺠﺩﻴﺩﺓ‬ ‫‪٩‬‬ ‫‪٣‬‬ ‫ﻤﺩﻴﻨﺔ ﻨﺼﺭ‬
‫ﺃﺭﺽ ﺍﻟﻠﻭﺍﺀ‬ ‫‪٧‬‬ ‫‪٣‬‬ ‫ﺍﻟﻤﺎﻨﺠﻭ‬ ‫‪٩‬‬ ‫‪٣‬‬ ‫ﺍﻟﺠﻤﺎﻟﻴﺔ‬
‫‪٣‬‬ ‫ﺍﻟﺠﻴﺯﺓ‬ ‫‪٧‬‬ ‫‪٣‬‬ ‫ﺤﺩﺍﺌﻕ ﺍﻟﻤﻌﺎﺩﻯ‬ ‫‪٦‬‬ ‫‪٣‬‬ ‫ﺒﺎﻗﻰ ﺍﻟﻤﻨﺎﻁﻕ‬
‫ﺍﻟﺭﺒﻴﻊ‬
‫ﺍﻟﺠﻴﺯﻯ‬ ‫ﻋﺯﺒﺔ ﺠﺒﺭﻴل‬ ‫ﺸﺒﺭﺍ ﺍﻟﺨﻴﻤﺔ‬
‫ﻋﺯﺒﺔ ﺍﺒﻭ‬ ‫ﻓﺎﻴﺩﺓ ﻜﺎﻤل‬ ‫‪٦‬‬ ‫‪٢‬‬ ‫ﻤﺴﺎﻜﻥ ﺍﻟﻀﺒﺎﻁ‬
‫ﻗﺘﺎﺘﺔ‬
‫ﺩﻭﻻﺭ‬ ‫ﻤﺼﺭ ﺍﻟﻘﺩﻴﻤﺔ‬ ‫‪٤‬‬ ‫‪١.٥‬‬ ‫ﺃﺭﺽ ﺃﺒﻭ ﺴﻌﺩﻩ‬
‫ﻓﻜﻴﻬﺔ‬ ‫‪٢‬‬ ‫‪١.٥‬‬ ‫ﺩﺍﺭ ﺍﻟﺴﻼﻡ‬ ‫‪٤‬‬ ‫‪١.٥‬‬ ‫ﺍﻟﺼﺒﺎﻏﺔ‬
‫ﻭﺍﻟﺘﺠﻬﻴﺯ‬
‫ﻤﻨﻴل ﺸﻴﺤﺔ‬ ‫ﺍﻟﺒﺴﺎﺘﻴﻥ‬ ‫‪٤‬‬ ‫‪١.٥‬‬ ‫ﺒﻬﺘﻴﻡ‬
‫ﺍﻟﻤﻨﻭﺍﺕ‬ ‫ﻁﺭﺓ ﺍﻟﺒﻠﺩ‬ ‫‪٤‬‬ ‫‪١.٥‬‬ ‫ﺃﺭﺽ ﻨﻭﺒﺎﺭ‬
‫‪١.٥‬‬ ‫ﻁﻤﻭﻩ‬ ‫ﻋﺯﺒﺔ ﻨﺎﻓﻊ‬ ‫ﺒﻭﻻﻕ‬
‫ﺍﻟﻤﻨﻴﺏ‬ ‫ﻜﻭﺘﺴﺘﻴﻜﺎ‬ ‫‪٦‬‬ ‫‪٣‬‬ ‫ﺍﻟﻘﻠﻠﻰ‬
‫ﻜﻔﺭ‬ ‫ﻤﻨﻁﻘﺔ ﺇﺯﺍﻟﺔ‬
‫ﻁﻬﺭﻤﺱ‬ ‫‪٧‬‬ ‫‪٤‬‬ ‫ﺍﻟﺴﺭﺍﻴﺎﺕ‬ ‫‪١٢‬‬ ‫‪٨‬‬ ‫ﻋﺸﺵ ﺍﻟﺘﺭﺠﻤﺎﻥ‬
‫ﻜﻔﺭ ﻏﻁﺎﻁ‬ ‫‪٧‬‬ ‫‪٤‬‬ ‫ﺩﺠﻠﺔ‬ ‫‪٨‬‬ ‫‪٤‬‬ ‫ﺍﻟﻤﻭﺴﻜﻰ‬
‫ﻨﺯﻟﺔ ﺍﻟﺴﻤﺎﻥ‬ ‫‪٧‬‬ ‫‪٤‬‬ ‫ﺍﻟﺠﻭﻟﻑ‬ ‫‪١٢‬‬ ‫‪٨‬‬ ‫ﻋﺎﺒﺩﻴﻥ‬
‫ﻜﻔﺭ ﻨﺼﺎﺭ‬ ‫‪٤‬‬ ‫ﺤﻠﻭﺍﻥ‬ ‫‪١٢‬‬ ‫‪٨‬‬ ‫ﻭﺴﻁ ﺍﻟﻤﺩﻴﻨﺔ‬
‫‪٤‬‬ ‫‪٢‬‬ ‫ﺇﺴﻜﺎﻥ ﻓﻭﻕ‬ ‫‪٤‬‬ ‫‪٢‬‬ ‫ﻋﺎﺒﺩﻴﻥ ﺍﻟﺒﻠﺩ‬
‫ﺍﻟﻤﺘﻭﺴﻁ‬
‫‪٤‬‬ ‫‪٢‬‬ ‫ﺇﺴﻜﺎﻥ ﺍﻟﻤﺤﺎﻓﻅﺔ‬ ‫‪١٢‬‬ ‫‪٨‬‬ ‫ﺍﻟﺯﻤﺎﻟﻙ‬
‫ﻓﻭﻕ ﺍﻟﻤﺘﻭﺴﻁ‬
‫‪٣‬‬ ‫‪٢‬‬ ‫ﺇﺴﻜﺎﻥ ﻤﺘﻭﺴﻁ‬
‫‪١.٥‬‬ ‫ﺇﺴﻜﺎﻥ ﺸﻌﺒﻰ‬

‫‪٣‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻟﺙ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪ (٦-٣‬ﺍﻟﺴﻌﺎﺕ ﺍﻟﻨﻤﻁﻴﺔ ﻟﻭﺤﺩﺍﺕ ﺍﻟﻤﺒﺎﻨﻰ ﺍﻟﺘﻰ ﻴﺯﻴﺩ ﺍﺭﺘﻔﺎﻋﻬﺎ ﻋﻥ ‪ ١٥‬ﺩﻭﺭﺍﹰ‬

‫ﺍﻟﺴﻌﺔ ﻙ‪.‬ﻑ‪.‬ﺃ‪ ١٠٠/.‬ﻤﺘﺭ ﻤﺭﺒﻊ‬


‫ﺍﻟﻤﻨﻁﻘﺔ‬
‫ﻤﺤﻼﺕ ﺃﻭ ﻤﻜﺎﺘﺏ‬ ‫ﻤﺴﻜﻥ‬
‫ﺠﻤﻴﻊ ﺍﻟﻤﻭﺍﻗﻊ ﺒﺎﻟﻘﺎﻫﺭﺓ‬
‫‪١٢‬‬ ‫‪٨‬‬
‫ﺍﻟﻜﺒﺭﻯ‬

‫ﺃﻤﺜﻠﺔ ﺘﻁﺒﻴﻘﻴﺔ‬ ‫‪٥-٣‬‬


‫ﻤﺜﺎل )‪:(١‬‬
‫ﻤﺎ ﻫـﻭ ﺍﻟﺘﻴﺎﺭ ﺍﻟﺘﺼﻤﻴﻤﻲ ﻟﺠﻬﺎﺯ ﺘﻜﻴﻴﻑ ‪ ١.٥‬ﺤﺼﺎﻥ ﻴﻌﻤل ﻋﻠﻰ ﺠﻬـﺩ ‪ ٢٢٠‬ﻓﻭﻟـﺕ‬
‫ﻭﻤﻌﺎﻤل ﻗﺩﺭﺓ ‪ ٠.٨٥‬ﻭﻜﻔﺎﺀﺓ ‪٪٨٠‬‬
‫ﺍﻟﺤﻤل = ‪ ١١١٩ = ٧٤٦ × ١.٥‬ﻭﺍﺕ‬ ‫ﺍﻟﺤل‪:‬‬
‫ﺍﻟﺤﻤل ﺒﺎﻟﻭﺍﺕ‬
‫ﺍﻟﺘﻴﺎﺭ ﺍﻟﺘﺼﻤﻴﻤﻰ =‬
‫ﺍﻟﺠﻬﺩ×ﻤﻌﺎﻤل ﺍﻟﻘﺩﺭﺓ×ﺍﻟﻜﻔﺎﺀﺓ‬
‫‪١١١٩‬‬
‫=‪٧.٥‬ﺃﻤﺒﻴﺭ‬ ‫ﺍﻟﺘﻴﺎﺭ ﺍﻟﺘﺼﻤﻴﻤﻰ ﻟﺠﻬﺎﺯ ﺍﻟﺘﻜﻴﻴﻑ =‬
‫‪٠.٨ × ٠.٨٥ × ٢٢٠‬‬

‫ﻤﺜﺎل )‪:(٢‬‬
‫ﻤﺎ ﻫﻭ ﺃﺩﻨـﻰ ﺘﻴﺎﺭ ﺘﺼﻤﻴﻤﻲ ﻤﺴﻤﻭﺡ ﺒﻪ ﻟﺩﺍﺌﺭﺓ ﺘﺤﺘﻭﻯ ﻋﻠﻰ ﺴﺕ )ﻤﺂﺨـﺫ ﻜﻬﺭﺒﻴـﺔ(‬
‫ﺒﺭﺍﻴﺯ ﺴﻌﺔ ‪ ٢‬ﺃﻤﺒﻴﺭ؟‬
‫ﻤﻥ ﺠﺩﻭل )‪ :(١-٣‬ﺍﻟﺒﺭﻴﺯﺓ ﺴﻌﺔ ‪ ٢‬ﺃﻤﺒﻴﺭ ﺘﺤﺴﺏ ﻋﻠـﻰ ﺍﻷﻗـل ‪ ٠.٥‬ﺃﻤﺒﻴـﺭ‬ ‫ﺍﻟﺤل‪:‬‬
‫ﻓﻴﻜﻭﻥ ﺃﺩﻨﻰ ﺘﻴــﺎﺭ ﺘﺼﻤﻴﻤــﻲ ﻤﺴﻤــﻭﺡ ﺒﻪ ﻟﻬـﺫﻩ ﺍﻟـﺩﺍﺌﺭﺓ = ﻋـﺩﺩ‬
‫ﺍﻟﺒﺭﺍﻴﺯ × ﺴﻌﺔ ﺃﻗل ﺘﻴﺎﺭ ﺒﺎﻷﻤﺒﻴﺭ = ‪ ٣ = ٠.٥ × ٦‬ﺃﻤﺒﻴﺭ‬

‫ﻤﺜﺎل )‪:(٣‬‬
‫ﻤﺒﻨﻰ ﻴﺤﺘﻭﻯ ﻋﻠﻰ ﻋﺩﺓ ﻭﺤﺩﺍﺕ ﺴﻜﻨﻴﺔ ﻴﺸﺘﻤل ﻋﻠﻰ ﺍﻷﺤﻤﺎل ﺍﻟﺘﺎﻟﻴﺔ‪:‬‬
‫)‪ (١‬ﺃﺤﻤﺎل ﺇﻨﺎﺭﺓ ‪ ٧٥‬ﻙ‪.‬ﻭ‪ .‬ﻭﻤﻌﺎﻤل ﻗﺩﺭﺓ = ‪. ١‬‬
‫)‪ ٣٠ (٢‬ﺩﺍﺌﺭﺓ ﻟﻠﻤﺂﺨﺫ ﺍﻟﻜﻬﺭﺒﻴﺔ ﺘﺤﺘﻭﻯ ﻜل ﺩﺍﺌﺭﺓ ﻋﻠﻰ ﺴﺕ ﻤﺂﺨﺫ ﻜـل ﻤﻨﻬـﺎ ﺒﺴـﻌﺔ‬
‫‪٢‬ﺃﻤﺒﻴﺭ‪.‬‬

‫‪٣‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻟﺙ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫)‪ ١٠ (٣‬ﺴﺨﺎﻨﺎﺕ ﻜﻬﺭﺒﻴﺔ ﻤﺘﻘﻁﻌﺔ ﺍﻟﺘﺸﻐﻴل ﻭﺍﻟﺤﻤل ﺍﻹﺴﻤﻰ ﻟﻜـل ﻤﻨﻬـﺎ ‪ ١.٥‬ﻙ‪.‬ﻭ‪.‬‬
‫ﻭﻤﻌﺎﻤل ﻗﺩﺭﺓ = ‪. ١‬‬
‫ﺍﻟﻤﻁﻠﻭﺏ‪:‬‬
‫ﺘﺤﺩﻴﺩ ﺍﻟﺤﻤل ﺍﻷﻗﺼﻰ ﻟﻬﺫﺍ ﺍﻟﻤﺒﻨﻰ ﻤﻊ ﺍﻟﺴﻤﺎﺡ ﺒﺎﺴﺘﺨﺩﺍﻡ ﻤﻌﺎﻤﻼﺕ ﺍﻟﺘﺒـﺎﻴﻥ ﻓـﻰ‬
‫ﺤﺎﻟﺔ‪:‬‬
‫ﺇﺫﺍ ﻜﺎﻥ ﺍﻟﻤﺒﻨﻰ ﻋﻤﺎﺭﺓ ﺴﻜﻨﻴﺔ‪.‬‬ ‫)ﺃ(‬
‫)ﺏ( ﺇﺫﺍ ﻜﺎﻥ ﺍﻟﻤﺒﻨﻰ ﺴﻭﻕ ﺘﺠﺎﺭﻯ‪.‬‬
‫ﺍﻟﺤل‪:‬‬
‫ﻓﻰ ﺤﺎﻟﺔ ﺍﺴﺘﺨﺩﺍﻡ ﺍﻟﻤﺒﻨﻰ ﻜﻌﻤﺎﺭﺓ ﺴﻜﻨﻴﺔ ﻤﻜﻭﻨﺔ ﻤﻥ ﻋﺩﺓ ﻭﺤﺩﺍﺕ ﺴﻜﻨﻴﺔ )ﺠﺩﻭل‬ ‫)ﺃ(‬
‫‪.(٢-٣‬‬
‫= ‪ ٣٧.٥ = ٧٥ × ٪٥٠‬ﻙ‪.‬ﻭﺍﺕ = ‪ ٣٧.٥‬ﻙ‪.‬ﻑ‪.‬ﺃ‬ ‫ﺤﻤل ﺍﻹﻨﺎﺭﺓ‬
‫ﺤﻤل ﺩﺍﺌﺭﺓ ﺍﻟﻤﺂﺨﺫ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﺒﺎﻷﻤﺒﻴﺭ = ‪ ٦ = ٥ × ٢ × ٠.٤٠ + ٢‬ﺃﻤﺒﻴﺭ‬
‫‪٢٢٠ × ٦‬‬ ‫ﺤﻤل ﺍﻟﺩﺍﺌﺭﺓ ﺍﻟﻜﻬﺭﺒﻴﺔ ﺒﺎﻟﻜﻴﻠﻭ ﻓﻭﻟﺕ‬
‫= ‪ ١.٣٢‬ﻙ‪.‬ﻑ‪.‬ﺃ‬ ‫=‬
‫‪١٠٠٠‬‬ ‫ﺃﻤﺒﻴﺭ‬
‫= ‪ ٣٠‬ﺩﺍﺌﺭﺓ × ‪ ٣٩.٦ = ١.٣٢‬ﻙ‪.‬ﻑ‪.‬ﺃ‬ ‫ﺍﻟﺤﻤل ﺍﻟﻜﻠﻰ ﻟﻠﻤﺄﺨﺫ‬
‫‪٦ =(١.٥×٨)٪٢٥+١.٥+١.٥‬ﻙ‪.‬ﻭﺍﺕ)‪٦‬‬
‫=‬ ‫ﺤﻤل ﺍﻟﺴﺨﺎﻨﺎﺕ ﺍﻟﻜﻬﺭﺒﻴﺔ‬
‫ﻙ‪.‬ﻑ‪.‬ﺃ(‬
‫= ‪ ٨٣.١ = ٦ + ٣٩.٦ + ٣٧.٥‬ﻙ‪.‬ﻑ‪.‬ﺃ‬ ‫ﺍﻟﺤﻤل ﺍﻟﻜﻠﻰ‬
‫)ﺏ( ﻓﻰ ﺤﺎﻟﺔ ﺍﺴﺘﺨﺩﺍﻡ ﺍﻟﻤﺒﻨﻰ ﻜﺴﻭﻕ ﺘﺠﺎﺭﻯ‬
‫‪ ٦٧.٥ = ٧٥ × ٪٩٠‬ﻙ‪.‬ﻭﺍﺕ )ﻙ‪.‬ﻑ‪.‬ﺃ(‬ ‫=‬ ‫ﺤﻤل ﺍﻹﻨﺎﺭﺓ‬
‫‪ ٩.٥٨ = (٢ × ٥) ٪٧٥ + ٢‬ﺃﻤﺒﻴﺭ‬ ‫=‬ ‫ﺤﻤل ﺩﺍﺌﺭﺓ ﺍﻟﻤﺂﺨﺫ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ‬
‫‪٢٢٠ × ٩.٥٨‬‬
‫= ‪ ٢.١٠٨‬ﻙ‪.‬ﻑ‪.‬ﺃ‬ ‫=‬ ‫ﺤﻤل ﺍﻟﺩﺍﺌﺭﺓ ﺒﺎﻟﻔﻭﻟﺕ ﺃﻤﺒﻴﺭ‬
‫‪١٠٠٠‬‬
‫‪ ٣٠‬ﺩﺍﺌﺭﺓ × ‪ ٦٣.٢٣ = ٢.١٠٨‬ﻙ‪.‬ﻑ‪.‬ﺃ‬ ‫=‬ ‫ﺤﻤل ﺍﻟﺒﺭﺍﻴﺯ‬
‫‪ ١٥ = ١.٥ × ١٠‬ﻙ‪.‬ﻑ‪.‬ﺃ‬ ‫=‬ ‫ﺤﻤل ﺍﻟﺴﺨﺎﻨﺎﺕ‬
‫‪ ١٤٥.٧٣ = ١٥ + ٦٣.٢٣ + ٦٧.٥‬ﻙ‪.‬ﻑ‪.‬ﺃ‬ ‫=‬ ‫ﺍﻟﺤﻤل ﺍﻟﻜﻠﻰ‬

‫‪٣‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻟﺙ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻤﺜﺎل )‪:(٤‬‬
‫ﻓﻴﻼ )ﻭﺤﺩﺓ ﺴﻜﻨﻴﺔ ﺨﺎﺼﺔ( ﻤﻁﻠﻭﺏ ﺘﺤﺩﻴﺩ ﺍﻟﺤﻤل ﺍﻟﻜﻬﺭﺒﺎﺌﻰ ﻟﻬﺎ ‪ ،‬ﻭﻫﻰ ﺘﺤﺘﻭﻯ ﻋﻠـﻰ‬
‫ﺍﻵﺘﻰ‪:‬‬
‫)‪ (١‬ﻋﺩﺩ ﻤﻥ ﻤﺨﺎﺭﺝ ﺍﻹﻨﺎﺭﺓ ﺒﺈﺠﻤﺎﻟﻰ ‪ ١٥٠٠٠‬ﻭﺍﺕ‬
‫)‪ (٢‬ﻤﺂﺨﺫ ﻜﻬﺭﺒﺎﺌﻴﺔ‪ :‬ﺴﻌﺔ ‪ ٢‬ﺃﻤﺒﻴﺭ ﺒﻌﺩﺩ ‪ ٣٠/‬ﺩﺍﺌﺭﺓ )ﻜل ﺩﺍﺌﺭﺓ ﺘﺤﺘﻭﻯ ﻋﻠﻰ ﻋﺩﺩ ﺴﺕ‬
‫ﻤﺂﺨﺫ(‪.‬‬
‫)‪ (٣‬ﺃﺠﻬﺯﺓ ﻜﻬﺭﺒﺎﺌﻴﺔ‪:‬‬
‫‪ -‬ﺒﺎﺏ ﺠﺭﺍﺝ ﻴﻌﻤل ﺒﻤﻭﺘﻭﺭ ‪ ١.٢‬ﺤﺼﺎﻥ‬
‫‪ -‬ﺠﻬﺎﺯ ﺃﻟﻌﺎﺏ ﺭﻴﺎﻀﻴﺔ ﺒﻘﺩﺭﺓ ‪ ١٤٠٠‬ﻭﺍﺕ‬
‫‪ -‬ﻋﺩﺩ ‪ ٧ /‬ﺃﺠﻬﺯﺓ ﺘﻜﻴﻴﻑ‪:‬‬
‫ﻋﺩﺩ ‪ ٢ /‬ﺒﻘﺩﺭﺓ ‪ ٣.٥‬ﺤﺼﺎﻥ )‪ ٢.٦‬ﻙ‪.‬ﻭﺍﺕ(‬
‫ﻋﺩﺩ ‪ ٣ /‬ﺒﻘﺩﺭﺓ ‪ ٢.٥‬ﺤﺼﺎﻥ )‪ ١.٩‬ﻙ‪.‬ﻭﺍﺕ(‬
‫ﻋﺩﺩ ‪ ٢ /‬ﺒﻘﺩﺭﺓ ‪ ٢‬ﺤﺼﺎﻥ )‪ ١.٥‬ﻙ‪.‬ﻭﺍﺕ(‬
‫)‪ (٤‬ﺃﺠﻬﺯﺓ ﺍﻟﻁﻬﻰ‪:‬‬
‫‪ -‬ﺠﻬﺎﺯ ﻁﻬﻰ ﺭﺌﻴﺴﻰ ﻜﻬﺭﺒﺎﺌﻰ ﺒﻘﺩﺭﺓ ‪ ٦٠٠٠‬ﻭﺍﺕ‬
‫‪ -‬ﻋﺩﺩ ‪ ٢ /‬ﺠﻬﺎﺯ ﻁﻬﻰ ﻜﻬﺭﺒﺎﺌﻰ ﻓﺭﻋﻰ ﻗﺩﺭﺓ ‪ ٢٠٠٠‬ﻭﺍﺕ‬
‫‪ -‬ﻋﺩﺩ ‪ ١ /‬ﺠﻬﺎﺯ ﺘﺴﺨﻴﻥ ﻜﻬﺭﺒﺎﺌﻰ ﻗﺩﺭﺓ ‪ ١٢٠٠‬ﻭﺍﺕ‬
‫)‪ (٥‬ﻁﻠﻤﺒﺎﺕ ﺘﻌﻤل ﺒﻤﻭﺘﻭﺭ ﻜﻬﺭﺒﺎﺌﻰ‪:‬‬
‫‪ -‬ﻁﻠﻤﺒﺔ ﻀﺦ ﻤﻴﺎﻩ ﺒﻘﺩﺭﺓ ‪ ١.٦‬ﻙ‪.‬ﻭﺍﺕ‬
‫‪ -‬ﻁﻠﻤﺒﺔ ﺭﻯ ﺤﺩﺍﺌﻕ ﺒﻘﺩﺭﺓ ‪ ٢.٨‬ﻙ‪.‬ﻭﺍﺕ‬
‫‪ -‬ﻁﻠﻤﺒﺔ ﻜﺴﺢ ﺒﺎﻟﺒﺩﺭﻭﻡ ﺒﻘﺩﺭﺓ ‪ ٠.٦‬ﻙ‪.‬ﻭﺍﺕ‬
‫)‪ (٦‬ﺍﻟﺴﺨﺎﻨﺎﺕ ﻭﻤﺎ ﻴﻤﺎﺜﻠﻬﺎ‪:‬‬
‫‪ -‬ﻋﺩﺩ ‪ ٢ /‬ﺴﺨﺎﻥ ﻤﻥ ﺍﻟﻨﻭﻉ ﺍﻟﺫﻯ ﻴﻌﻤل ﻤﺴﺘﻤﺭﺍﹰ ﺒﺴﻌﺔ ‪ ٣‬ﻙ‪.‬ﻭﺍﺕ‬
‫‪ -‬ﻋﺩﺩ ‪ ١ /‬ﺴﺨﺎﻥ ﻤﻥ ﺍﻟﻨﻭﻉ ﺍﻟﺫﻯ ﻴﻌﻤل ﻤﺴﺘﻤﺭﺍﹰ ﺒﺴﻌﺔ ‪ ٢‬ﻙ‪.‬ﻭﺍﺕ‬
‫‪ -‬ﻋﺩﺩ ‪ ١ /‬ﺴﺨﺎﻥ ﻟﺤﻅﻰ ﺒﺴﻌﺔ ‪ ٦‬ﻙ‪.‬ﻭﺍﺕ‬
‫‪ -‬ﺠﻬﺎﺯ ﺴﺨﺎﻥ ﻟﻠﺘﺴﺨﻴﻥ ﻟﺠﻬﺎﺯ ﺍﻟﺠﺎﻜﻭﺯﻯ ﺒﺴﻌﺔ ‪ ٥‬ﻙ‪.‬ﻭﺍﺕ‬
‫‪ -‬ﺠﻬﺎﺯ ﺴﺨﺎﻥ ﻟﻠﺘﺴﺨﻴﻥ ﺒﻐﺭﻓﺔ ﺍﻟﺴﺎﻭﻨﺎ ﺒﺴﻌﺔ ‪ ٤‬ﻙ‪.‬ﻭﺍﺕ‬

‫‪٣‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻟﺙ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺍﻟﺤل‪:‬‬
‫ﻤﻥ ﺠﺩﻭل )‪ (٤-٣‬ﺍﻟﻌﻤﻭﺩ ﺍﻟﺨﺎﺹ ﺒﻭﺤﺩﺓ ﺴﻜﻨﻴﺔ ﺨﺎﺼﺔ‪:‬‬
‫)‪ (١‬ﺍﻹﻨﺎﺭﺓ‪ :‬ﺘﺤﺴﺏ ‪ ٪٦٦‬ﻤﻥ ﺃﺤﻤﺎل ﺍﻹﻨﺎﺭﺓ‬
‫‪ ٩.٩ = ١٥٠٠٠ × ٪٦٦‬ﻙ‪.‬ﻭﺍﺕ‬
‫)‪ (٢‬ﺍﻟﻤﺂﺨﺫ‪ :‬ﺤﻤل ﺩﺍﺌﺭﺓ ﺍﻟﻤﺄﺨﺫ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﺒﺎﻷﻤﺒﻴﺭ‪:‬‬
‫‪٤٠‬‬
‫× ‪ ٦ = ٥ × ٢‬ﺃﻤﺒﻴﺭ‬ ‫‪+٢‬‬
‫‪١٠٠‬‬
‫ﺤﻤل ﺍﻟﺩﺍﺌﺭﺓ ﺍﻟﻜﻬﺭﺒﻴﺔ ﺒـﺎﻟﻜﻴﻠﻭﻭﺍﺕ = ‪١.١٢٢ = ٠.٨٥ × ٢٢٠ × ٦‬‬
‫ﻙ‪.‬ﻭﺍﺕ ﺒﺎﻋﺘﺒﺎﺭ ﻤﻌﺎﻤل ﻗﺩﺭﺓ ‪٠.٨٥‬‬
‫ﺍﻟﺤﻤل ﺍﻟﻜﻠﻰ ﻟﻠﻤﺄﺨﺫ = ‪ ٣٣.٦٦ = ٣٠ × ١.١٢٢‬ﻙ‪.‬ﻭﺍﺕ‬
‫)‪ (٣‬ﺍﻷﺠﻬﺯﺓ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ‪:‬‬
‫‪ ٪١٠٠‬ﻤــﻥ ﺇﺠﻤﺎﻟﻰ ﺍﻟﺤﻤــل ﺍﻟﻜﺎﻤــل ﻟﻤﺠﻤــﻭﻉ ﺍﻷﺠﻬـﺯﺓ ﺤﺘﻰ ﺴﻌﺔ‬
‫‪ ١٠‬ﺃﻤﺒﻴﺭ ])‪ ١.٨٧‬ﻙ‪.‬ﻭﺍﺕ( ﻋﻠﻰ ﺃﺴﺎﺱ ‪ ٠.٨٥‬ﻤﻌﺎﻤـل ﻗـﺩﺭﺓ[ ‪ ٪٥٠ +‬ﻤـﻥ‬
‫ﺍﻟﺤﻤل ﻟﻸﺠﻬﺯﺓ ﺍﻟﺘﻰ ﺤﻤﻠﻬﺎ ﻴﺯﻴﺩ ﻋﻥ ‪ ١٠‬ﺃﻤﺒﻴﺭ‬
‫)‪[١.٩ × ٣ + ٢.٦ × ٢ ] ٪ ٥٠ + (١.٥ × ٢ + ١.٤ + ٠.٧٤٦ × ١.٢‬‬
‫‪٥٠‬‬
‫]‪١٠.٧٥=٥.٤+٥.٣=[٥.٧+٥.٢‬ﻙ‪.‬ﻭ‬ ‫= )‪+ (٣ + ١.٤ + ٠.٩‬‬
‫‪١٠٠‬‬
‫)‪ (٤‬ﺃﺠﻬﺯﺓ ﺍﻟﻁﻬﻰ‪:‬‬
‫‪ ٪١٠٠‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل ﻟﻸﺠﻬﺯﺓ ﺤﺘﻰ ‪ ١٠‬ﺃﻤﺒﻴﺭ ‪ ٪٣٠ +‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻤﻘـﻨﻥ‬
‫ﺍﻟﺯﺍﺌﺩ ﻋﻠﻰ ‪ ١٠‬ﺃﻤﺒﻴﺭ )‪ ٢.٢‬ﻙ‪.‬ﻭﺍﺕ ﻋﻠﻰ ﺃﺴﺎﺱ ﻤﻌﺎﻤل ﻗﺩﺭﺓ ﻭﺍﺤﺩ ﺼﺤﻴﺢ(‪.‬‬
‫= )‪ ٧.٠٠ = (٦) ٪٣٠ + (١.٢ + ٢.٠٠ × ٢‬ﻙ‪.‬ﻭﺍﺕ‬
‫)‪ (٥‬ﺍﻟﻤﺤﺭﻜﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ‪:‬‬
‫‪ ٪١٠٠‬ﻤﻥ ﺍﻟﺤﻤــل ﺍﻟﻜﺎﻤــل ﻷﻜﺒــﺭ ﻤﺤــﺭﻙ ‪ ٪٥٠ +‬ﻤﻥ ﺍﻟﺤﻤــل‬
‫ﻟﺒﺎﻗـﻰ ﺍﻟﻤﺤﺭﻜﺎﺕ = ‪ ٣.٩ = [٠.٦ + ١.٦ ] ٪٥٠ + [٢.٨] ٪١٠٠‬ﻙ‪.‬ﻭﺍﺕ‬

‫‪٣‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻟﺙ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫)‪ (٦‬ﺍﻟﺴﺨﺎﻨﺎﺕ ﻭﻤﺎ ﻤﺎﺜﻠﻬﺎ‪:‬‬


‫ﺍﻟﺴﺨﺎﻨﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻤﺘﻘﻁﻌﺔ ﺍﻟﺘﺸﻐﻴل‪:‬‬ ‫)ﺃ(‬
‫‪ ٪١٠٠‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل ﻷﻜﺒﺭ ﺴﺨﺎﻥ ‪ ٪١٠٠ +‬ﻤـﻥ ﺍﻟﺤﻤـل ﺍﻟﻜﺎﻤـل‬
‫ﻟﻠﺴﺨﺎﻥ ﺍﻟﺫﻯ ﻴﻠﻰ ﺃﻜﺒﺭ ﺴـﺨﺎﻥ ‪ ٪ ٢٥ +‬ﻤـﻥ ﺍﻟﺤﻤـل ﺍﻟﻜﺎﻤـل ﻟﺒـﺎﻗﻰ‬
‫ﺍﻟﺴﺎﺨﺎﻨﺎﺕ‬
‫= ‪ ١٢ = (٤) ٪٢٥ + ٥ + ٦‬ﻙ‪.‬ﻭﺍﺕ‬
‫)ﺏ( ﺍﻟﺴﺨﺎﻨﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻤﺴﺘﻤﺭﺓ ﺍﻟﺘﺸﻐﻴل‪:‬‬
‫‪ ٪١٠٠‬ﻤﻥ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل ﻓﻰ ﺠﻤﻴﻊ ﺍﻟﺤﺎﻻﺕ‬
‫= ‪ ٨ = ٢ + ٣ × ٢‬ﻙ‪.‬ﻭﺍﺕ‬
‫ﺍﻹﺠﻤﺎﻟﻴﺎﺕ‪:‬‬
‫)‪٦‬ﺏ(‬ ‫)‪٦‬ﺃ(‬ ‫)‪(٥‬‬ ‫)‪(٤‬‬ ‫)‪(٣‬‬ ‫)‪(٢‬‬ ‫)‪(١‬‬
‫= ‪ ٨٥.٢١‬ﻙ‪.‬ﻭﺍﺕ‬
‫‪٨+‬‬ ‫‪١٢‬‬ ‫‪+٣.٩‬‬ ‫‪+٧‬‬ ‫‪+١٠.٧٥‬‬ ‫‪+٣٣.٦٦‬‬ ‫‪+ ٩.٩‬‬
‫ﻤﻼﺤﻅﺔ‪:‬‬
‫ﺇﺫﺍ ﺘﻡ ﺠﻤﻊ ﺠﻤﻴﻊ ﺍﻷﺤﻤﺎل ﺠﻤﻌﺎﹰ ﺠﺒﺭﻴﺎﹰ ﻨﺠﺩﻫﺎ ‪ ١٣٧.٧٢٢‬ﻙ‪.‬ﻭﺍﺕ ﻓﻴﻜﻭﻥ‪:‬‬
‫‪٨٥.٢١‬‬
‫= ‪٪٦١.٨٧‬‬ ‫ﻤﻌﺎﻤل ﺍﻟﺘﺒﺎﻴﻥ ﺍﻹﺠﻤﺎﻟﻰ )‪= (diversity factor‬‬
‫‪١٣٧.٧٢٢‬‬

‫ﻤﺜﺎل )‪:(٥‬‬
‫ﻤﺒﻨﻰ ﺴﻜﻨﻰ ﻤﺴﺎﺤﺘﻪ ‪ ٣٥٠‬ﻤﺘﺭ ﻤﺭﺒﻊ ﻓﻰ ﻤﻨﻁﻘﺔ ﻤﺘﻭﺴﻁﺔ ﺍﻗﺘﺼﺎﺩﻴﺔ ﻭﻴﺘﻜﻭﻥ ﻤﻥ ﺴﺘﺔ‬
‫ﻁﻭﺍﺒﻕ؟‬
‫ﺍﻟﻤﻁﻠﻭﺏ‪:‬‬
‫ﺤﺴﺎﺏ ﺍﻟﺤﻤل ﺍﻷﻗﺼﻰ ﻟﻬﺫﺍ ﺍﻟﻤﺒﻨﻰ‬
‫ﺍﻟﺤﻤل ﺍﻷﻗﺼﻰ ﻋﻠﻰ ﺃﺴﺎﺱ ﺇﺴﻜﺎﻥ ﻤﺘﻭﺴﻁ‪ ٤ :‬ﻙ‪.‬ﻑ‪.‬ﺃ ‪ ١٠٠ /‬ﻤﺘﺭ‬
‫‪٣٥٠‬‬
‫× ‪ ٦‬ﺩﻭﺭ × ‪ ٨٤ = ٤‬ﻙ‪.‬ﻑ‪.‬ﺃ‬ ‫ﺍﻟﺤﻤل ﺍﻷﻗﺼﻰ =‬
‫‪١٠٠‬‬

‫‪٣‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻟﺙ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻤﺜﺎل )‪:(٦‬‬
‫ﻤﺒﻨﻰ ﺴﻜﻨﻰ ﺘﺠﺎﺭﻯ ﻋﻠﻰ ﻤﺴﺎﺤﺔ ‪ ٦٠٠‬ﻡ‪ ٢‬ﻋﺒﺎﺭﺓ ﻋﻥ‪:‬‬
‫‪ -‬ﺩﻭﺭ ﺒﺩﺭﻭﻡ ﺠﺭﺍﺝ ﻭﺨﺩﻤﺎﺕ‬
‫‪ -‬ﻋﺩﺩ ‪ ٢ /‬ﺩﻭﺭ )ﺃﺭﻀﻰ ‪ +‬ﻤﻴﺯﺍﻨﻴﻥ( ﺘﺠﺎﺭﻯ‬
‫‪ -‬ﻋﺩﺩ‪ ١٦/‬ﺩﻭﺭ ﻤﺘﻜﺭﺭ ﺒﻜل ﺩﻭﺭ ﻋﺩﺩ‪ ٥/‬ﺸﻘﺔ‬
‫‪ -‬ﻋﺩﺩ‪ ٣/‬ﻤﺼﻌﺩ ﻜﻬﺭﺒﺎﺌﻰ ﻜل ﻤﻨﻬﻡ ‪ ١٥‬ﻙ‪.‬ﻭﺍﺕ‬
‫‪ -‬ﻤﺤﻁــﺔ ﻁﻠﻤﺒــﺎﺕ ﻤﻴﺎﻩ ﻟﺭﻓــﻊ ﺍﻟﻤﻴﺎﻩ ﺇﻟﻰ ﺍﻟﺨﺯﺍﻥ ﺍﻟﻌﻠﻭﻯ ﺒﻬﺎ ﻋﺩﺩ‪ ٣/‬ﻁﻠﻤﺒـﺔ‬
‫ﺭﻓﻊ ﻤﻴﺎﻩ ﻗﺩﺭﺓ ‪ ١٧.٥‬ﺤﺼﺎﻥ ﻭﻜﻔﺎﺀﺓ ‪ ٪٨٨‬ﺃﺤﺩﻫﻤﺎ ﺍﺤﺘﻴﺎﻁﻴﺔ‪.‬‬
‫‪ -‬ﻤﺤﻁﺔ ﻁﻠﻤﺒﺔ ﻜﺴﺢ ﻤﻴﺎﻩ ﻤﻥ ﺍﻟﺒﺩﺭﻭﻡ ﺒﻬﺎ ﻋﺩﺩ‪ ٢ /‬ﻁﻠﻤﺒﺔ ﻗﺩﺭﺓ ‪ ٦.٥‬ﺤﺼﺎﻥ ﻭﻜﻔـﺎﺀﺓ‬
‫‪ ٪٨٧‬ﺃﺤﺩﻫﻤﺎ ﺍﺤﺘﻴﺎﻁﻴﺔ‬
‫ﺤﺴﺎﺏ ﺴﻌﺔ ﺍﻟﻤﺤﻭل )ﺍﻟﻤﺤﻭﻻﺕ( ﺍﻟﻼﺯﻤﺔ ﻟﺘﻐﺫﻴﺔ ﺍﻟﻤﺒﻨﻰ‪:‬‬ ‫ﺍﻟﻤﻁﻠﻭﺏ‪:‬‬
‫ﺍﻟﺤل‪:‬‬
‫ﻴﺭﺠﻊ ﺇﻟﻰ ﺍﻟﺠﺩﻭل )‪(٤-٣‬‬
‫‪ -‬ﻁﻠﺏ ﺍﻟﺤﻤل ﻟﻜل ‪١٠٠‬ﻡ‪ ٢‬ﺴﻜﻨﻰ ‪ ١٠ – ٨‬ﻙ‪.‬ﻑ‪.‬ﺃ‬
‫‪ -‬ﻁﻠﺏ ﺍﻟﺤﻤل ﻟﻜل ‪١٠٠‬ﻡ‪ ٢‬ﺘﺠﺎﺭﻯ ‪ ١٢‬ﻙ‪.‬ﻑ‪.‬ﺃ‬
‫‪ ٢‬ﻙ‪.‬ﻑ‪.‬ﺃ‬
‫= ‪ ١٢‬ﻙ‪.‬ﻑ‪.‬ﺃ‬ ‫‪٢‬‬
‫)‪ (١‬ﺍﻟﺒﺩﺭﻭﻡ ﺒﻤﺴﺎﺤﺔ ‪ ٦٠٠‬ﻡ‪× ٢‬‬
‫‪ ١٠٠‬ﻡ‬
‫‪٢‬‬
‫)‪ (٢‬ﺍﻟﺘﺠﺎﺭﻯ ﻋﺩﺩ‪ ٢/‬ﺩﻭﺭ × ‪ ٦٠٠‬ﻡ‪ ١٢٠٠ = ٢‬ﻡ‬
‫‪١٢‬‬
‫= ‪ ١٤٤‬ﻙ‪.‬ﻑ‪.‬ﺃ‬ ‫‪× ١٢٠٠‬‬
‫‪١٠٠‬‬
‫‪٢‬‬
‫)‪ (٣‬ﺍﻟﺴﻜﻨﻰ ﻋﺩﺩ‪ ١٦/‬ﺩﻭﺭ × ‪ ٦٠٠‬ﻡ‪ ٩٦٠٠ = ٢‬ﻡ‬
‫‪ ١٠‬ﻙ‪.‬ﻑ‪.‬ﺃ‬
‫= ‪ ٩٦٠‬ﻙ‪.‬ﻑ‪.‬ﺃ‬ ‫‪٢‬‬
‫‪× ٩٦٠٠‬‬
‫‪ ١٠٠‬ﻡ‬
‫)‪ (٤‬ﺍﻟﻤﺩﺍﺨل‪+‬ﺍﻟﺴﻼﻟﻡ‪+‬ﻏﺭﻑ ﺍﻟﺴﻁﺢ )ﻴﻤﻜﻥ ﺃﺨﺫﻫﺎ ﺠﻤﻴﻌﺎﹰ ﻤﺜل ﺍﻟﺒﺩﺭﻭﻡ(=‪١٢‬ﻙ‪.‬ﻑ‪.‬ﺃ‬
‫ﻭﺒﺫﻟﻙ ﻴﻜﻭﻥ ﺇﺠﻤﺎﻟﻰ ﺃﺤﻤﺎل ﺍﻹﻨﺎﺭﺓ‪ ١١٢٨ = ١٢ + ٩٦٠ + ١٢ + ١٤٤ :‬ﻙ‪.‬ﻑ‪.‬ﺃ‬

‫‪٣‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺜﺎﻟﺙ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫)‪ (٥‬ﺃﺤﻤﺎل ﺍﻟﻘﻭﻯ‪:‬‬


‫‪ ١٥ × ٣‬ﻙ‪.‬ﻭﺍﺕ‬
‫= ‪ ٥٣‬ﻙ‪.‬ﻑ‪.‬ﺃ‬ ‫* ‪ ٣‬ﻤﺼﻌﺩ‪:‬‬
‫‪) ٠.٨٥‬ﻤﻌﺎﻤل ﺍﻟﻘﺩﺭﺓ(‬

‫‪٠.٧٤٦×١٧.٥×٢‬‬
‫= ‪ ٣٥‬ﻙ‪.‬ﻑ‪.‬ﺃ‬ ‫* ‪ ٢‬ﻁﻠﻤﺒﺔ ﻤﻴﺎﻩ‪:‬‬
‫‪)٠.٨٥‬ﻤﻌﺎﻤل ﺍﻟﻘﺩﺭﺓ(×‪)٠.٨٨‬ﺍﻟﻜﻔﺎﺀﺓ(‬

‫‪ ٦.٥‬ﺤﺼﺎﻥ × ‪٠.٧٤٦‬‬
‫= ‪ ٦.٦‬ﻙ‪.‬ﻑ‪.‬ﺃ‬ ‫* ‪ ١‬ﻁﻠﻤﺒﺔ ﻜﺴﺢ ﻤﻴﺎﻩ‪:‬‬
‫‪)٠.٨٥‬ﻤﻌﺎﻤل ﺍﻟﻘﺩﺭﺓ(×‪)٠.٨٧‬ﻜﻔﺎﺀﺓ(‬
‫ﺇﺠﻤﺎﻟﻰ ﺃﺤﻤﺎل ﺍﻟﻘﻭﻯ‪ ٩٥ ≅ ٦.٦ + ٣٥ + ٥٣ :‬ﻙ‪.‬ﻑ‪.‬ﺃ‬
‫* ﻓﺈﺫﺍ ﻤﺎ ﺃﻀﻴﻔﺕ ﺃﺤﻤﺎل ﺍﻹﻨﺎﺭﺓ ﻜﺎﻤﻠﺔ ﺩﻭﻥ ﺘﻁﺒﻴﻕ ﻤﻌﺎﻤﻼﺕ ﺘﺒﺎﻴﻥ ﻋﻠﻴﻬﺎ ﺇﻟـﻰ‬
‫ﺃﺤﻤﺎل ﺍﻟﻘﻭﻯ ﺘﺼﺒﺢ ﺍﻟﻘﻴﻤﺔ ﺍﻹﺠﻤﺎﻟﻴﺔ ﻟﻠﻁﻠﺏ=‪ ١٢٢٣=٩٥+١١٢٨‬ﻙ‪.‬ﻑ‪.‬ﺃ‬
‫‪١٢٢٣‬‬
‫= ‪١٥٢٨.٧٥‬‬ ‫ﺴﻌﺔ ﺍﻟﻤﺤﻭل ﻋﻠﻰ ﺃﺴﺎﺱ ﺃﻥ ﺍﻟﺘﺤﻤﻴل ‪ ٪٨٠‬ﻤﻥ ﺍﻟﺴﻌﺔ =‬
‫‪٪ ٨٠‬‬
‫ﻭﺘﻜﻭﻥ ﺴﻌﺔ ﺍﻟﻤﺤﻭل ﺍﻟﻤﻨﺎﺴﺒﺔ ﻫﻰ ‪ ٢٠٠٠‬ﻙ‪.‬ﻑ‪.‬ﺃ‬
‫* ﺃﻤﺎ ﺇﺫﺍ ﺴﻤﺤﺕ ﻅﺭﻭﻑ ﺍﻟﻤﻜﺎﻥ ﻭﺸﺭﻜﺔ ﺘﻭﺯﻴﻊ ﺍﻟﻜﻬﺭﺒـﺎﺀ ﻭﻨﺴـﺒﺔ ﺍﻹﺸـﻐﺎل‬
‫ﺒﺎﻟﻤﺒﻨﻰ ﺒﺘﻁﺒﻴﻕ ﻤﻌﺎﻤل ﺘﺒﺎﻴﻥ ﻓﺈﻥ ﺘﻁﺒﻴﻘﻪ ﻴﺘﻡ ﻓﻘﻁ ﻋﻠﻰ ﺃﺤﻤـﺎل ﺍﻹﻨـﺎﺭﺓ ﺃﻤـﺎ‬
‫ﺃﺤﻤﺎل ﺍﻟﻘﻭﻯ ﻓﻼ ﻴﻁﺒﻕ ﻋﻠﻴﻬﺎ ﻤﻌﺎﻤﻼﺕ ﺘﺒﺎﻴﻥ‪.‬‬
‫ﻓﺈﺫﺍ ﻤﺎ ﺍﻓﺘﺭﺽ ﻤﻌﺎﻤل ﺘﺒﺎﻴﻥ ﻗﻴﻤﺘﻪ ‪٪٦٨‬‬
‫ﻴﻜﻭﻥ ﺍﻟﺤﻤل ﺍﻟﻤﻁﻠﻭﺏ = ‪ ٨٦٢ = ٩٥ + ٪٦٨ × ١١٢٨‬ﻙ‪.‬ﻑ‪.‬ﺃ‬
‫‪٨٦٢‬‬
‫= ‪ ١٠٧٧‬ﻙ‪.‬ﻑ‪.‬ﺃ‬ ‫ﻭﺘﻜﻭﻥ ﺴﻌﺔ ﺍﻟﻤﺤﻭل ﺍﻟﻤﻨﺎﺴﺏ =‬
‫‪٪٨٠‬‬
‫ﻭﻴﻜﻭﻥ ﺍﻟﻤﺤﻭل ﺍﻟﻤﻨﺎﺴﺏ ﺒﺴﻌﺔ ‪ ١٥٠٠‬ﻙ‪.‬ﻑ‪.‬ﺃ‪.‬‬

‫‪٣‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺭﺍﺒﻊ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺘﺤﺩﻴﺩ ﺴﻌﺔ ﻤﺤﻭل ﺍﻟﺘﻭﺯﻴﻊ ﺍﻟﻼﺯﻡ ﻟﺘﻐﺫﻴﺔ ﺍﻟﺤﻤل‬ ‫‪-٤‬‬


‫ﻋﺎﻡ‬
‫ﻴﺘﻡ ﺘﺤﺩﻴﺩ ﺴﻌﺔ ﻤﺤﻭل ﺍﻟﺘﻭﺯﻴﻊ ﺍﻟﻼﺯﻡ ﻟﺘﻐﺫﻴﺔ ﺍﻟﻤﻨﺸﺄﺓ ﺒﻨﺎﺀ‪ ‬ﻋﻠـﻰ ﺃﻗﺼـﻰ ﻁﻠـﺏ‬ ‫)ﺃ(‬
‫ﻜﻬﺭﺒﻲ ﻤﺘﻭﻗﻊ ﻟﻬﺫﻩ ﺍﻟﻤﻨﺸﺄﺓ ﻭﺫﻟﻙ ﻁﺒﻘﺎﹰ ﻟﻤﺎ ﻴﻠﻲ‪:‬‬
‫ﺴﻌﺔ ﺍﻟﻤﺤﻭل=‪ ×١.٢٥‬ﺃﻗﺼﻰ ﻁﻠﺏ ﻜﻬﺭﺒﻲ )ﻙ‪.‬ﻑ‪.‬ﺃ( )ﺒﻤﻌﻨﻰ ﺃﻥ ﺍﻟﻤﺤﻭل ﻴﺤﻤل‬
‫ﻓﻘﻁ ﺒـ ‪ ٪٨٠‬ﻤﻥ ﺴﻌﺘﻪ(‬
‫)ﺏ( ﺘﻜﻭﻥ ﺍﻟﺤﺩﻭﺩ ﺍﻟﻤﺴﻤﻭﺡ ﺒﻬﺎ ﻟﻼﺭﺘﻔﺎﻉ ﻓﻲ ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﻤﺤﻭﻻﺕ ﺍﻟﺘﻭﺯﻴـﻊ ﻋﻨـﺩ‬
‫ﺘﺤﻤﻴﻠﻬﺎ ﺒﺎﻟﺴﻌﺔ ﺍﻹﺴﻤﻴﺔ ﻟﻬﺎ ﺒﺼﻔﺔ ﻤﺴﺘﻤﺭﺓ )ﻟﻤﺩﺓ ﻻ ﺘﻘل ﻋﻥ ‪ ٦‬ﺴـﺎﻋﺎﺕ( ﻋﻠـﻰ‬
‫ﺍﻟﻨﺤﻭ ﺍﻟﺘﺎﻟﻰ‪:‬‬
‫)‪ (١‬ﻴﺠﺏ ﺃﻻ ﻴﺘﺠﺎﻭﺯ ﺍﻻﺭﺘﻔﺎﻉ ﻓﻲ ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺍﻟﺯﻴﺕ ﺃﻋﻠﻰ ﺨـﺯﺍﻥ ﺍﻟﺘﻤـﺩﺩ‬
‫‪ْ ٤٥‬ﻡ‪.‬‬
‫ﻴﻜﻭﻥ ﻤﺘﻭﺴﻁ ﺍﻻﺭﺘﻔﺎﻉ ﻓﻲ ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺍﻟﻤﻠﻔﺎﺕ )ﻭﺍﻟﺘﻲ ﺘﻘﺎﺱ ﻋﻥ ﻁﺭﻴﻕ‬
‫ﻗﻴﺎﺱ ﻤﻘﺎﻭﻤﺔ ﺍﻟﻤﻠﻔﺎﺕ( ‪°٦٠‬ﻡ‪.‬‬
‫)‪ (٢‬ﻻ ﻴﺠﺏ ﺃﻥ ﺘﺭﺘﻔﻊ ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺍﻟﺯﻴﺕ ﻓﻰ ﺨﺯﺍﻥ ﺍﻟﺘﻤﺩﺩ ﻭﻜﺫﻟﻙ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﺍﻟﻜﻬﺭﺒﻴﺔ ﺒﺤﻴﺙ ﻻ ﺘﺴﺒﺏ ﻀﺭﺭﺍﹰ ﻋﻠﻰ ﺍﻟﻤﺤﻴﻁ ﺍﻟﺨﺎﺭﺠﻲ‪.‬‬
‫ﻭﻴﺘﻡ ﻋﻤﻭﻤﺎﹰ ﺇﺘﺒﺎﻉ ﺍﻹﺭﺸﺎﺩﺍﺕ ﺍﻟﺨﺎﺼﺔ ﺒﺎﻟﻤﺼـﻨﻊ ﻓـﻲ ﺘﺭﻜﻴـﺏ ﻭﺘﺸـﻐﻴل‬
‫ﺍﻟﻤﺤﻭل‪.‬‬

‫ﺘﺤﺩﻴﺩ ﺴﻌﺔ ﻤﺤﻭل ﺍﻟﺘﻭﺯﻴﻊ‬ ‫‪١-٤‬‬


‫ﺘﺒﺭﻴﺩ ﺍﻟﻤﺤﻭﻻﺕ‬ ‫)ﺃ(‬
‫ﻴﺤﺩﺩ ﺍﻟﻤﺼﻨﻊ ﻁﺭﻴﻘﺔ ﺘﺒﺭﻴﺩ ﺍﻟﻤﺤﻭل‪ ،‬ﺒﺎﺴﺘﺨﺩﺍﻡ ﺃﺭﺒﻊ ﺤﺭﻭﻑ‪ ،‬ﻴﺭﻤـﺯ ﺍﻟﺤﺭﻓـﺎﻥ‬
‫ﺍﻷﻭﻻﻥ ﺇﻟﻲ ﺍﻟﻤﻭﺍﺌﻊ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻓﻲ ﺘﺒﺭﻴﺩ ﺍﻟﻤﻠﻔﺎﺕ ﺩﺍﺨل ﺍﻟﻤﺤﻭل‪ ،‬ﻭﻭﺴﻴﻠﺔ ﺩﻓـﻊ‬
‫ﻫﺫﻩ ﺍﻟﻤﻭﺍﺌﻊ‪ ،‬ﻭ ﻴﺭﻤﺯ ﺍﻟﺤﺭﻓﺎﻥ ﺍﻵﺨﺭﺍﻥ ﺇﻟﻲ ﺍﻟﻤﻭﺍﺌﻊ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻟﺘﺒﺭﻴـﺩ ﺠﺴـﻡ‬
‫ﺍﻟﻤﺤﻭل ﻤﻥ ﺍﻟﺨﺎﺭﺝ‪ ،‬ﻭﻭﺴﻴﻠﺔ ﺩﻓﻊ ﺍﻟﻤﻭﺍﺌﻊ‪ ،‬ﻭ ﻴﺤﺘـﻭﻱ ﺍﻟﺠـﺩﻭل )‪ (١-٤‬ﻋﻠـﻲ‬
‫ﺍﻟﺭﻤﻭﺯ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻓﻲ ﻫﺫﺍ ﺍﻟﻨﻅﺎﻡ‬

‫‪٤‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺭﺍﺒﻊ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪-:(١-٤‬ﺠﺩﻭل ﺘﻭﻀﻴﺤﻲ ﻟﻠﺤﺭﻭﻑ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻓﻲ ﻫﺫﺍ ﺍﻟﻨﻅﺎﻡ‬

‫ﺍﻟﺭﻤﺯ‬ ‫ﺴﺭﻴﺎﻥ ﺍﻟﻤﺎﺌﻊ‬ ‫ﺍﻟﺭﻤﺯ‬ ‫ﺍﻟﻤﺎﺌﻊ ﺍﻟﻤﺒﺭﺩ‬


‫ﺯﻴﺕ ﻤﻌﺩﻨﻲ ﺃﻭ ﺯﻴﺕ ﺍﺼﻁﻨﺎﻋﻲ ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ‬
‫‪N‬‬ ‫ﻁﺒﻴﻌﻲ‬ ‫‪O‬‬
‫ﺍﺸﺘﻌﺎﻟﻪ ≥‪ °٣٠٠‬ﻡ‬
‫‪L‬‬ ‫ﺯﻴﻭﺕ ﺍﺼﻁﻨﺎﻋﻴﺔ ﺃﺨﺭﻱ‬
‫‪G‬‬ ‫ﻏﺎﺯ ﻭ ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺇﺸﺘﻌﺎﻟﻪ ≥‪ °٣٠٠‬ﻡ‬
‫‪F‬‬ ‫ﺍﺼﻁﻨﺎﻋﻲ‬
‫‪A‬‬ ‫ﻫﻭﺍﺀ‬
‫‪W‬‬ ‫ﻤﺎﺀ‬

‫ﻤﺜﺎل‪:‬‬
‫ﻤﺤﻭل ﺯﻴﺘﻲ )ﻴﺒﺭﺩ ﺩﺍﺨﻠﻴﺎﹰ ﺒﺴﺭﻴﺎﻥ ﺍﻟﺯﻴﺕ ﺴـﺭﻴﺎﻨﺎﹰ ﻁﺒﻴﻌﻴـﺎﹰ ﻭﻴﺒـﺭﺩ‬ ‫‪: ONAN‬‬
‫ﺍﻟﺠﺴﻡ ﻤﻥ ﺍﻟﺨﺎﺭﺝ ﺒﺴﺭﻴﺎﻥ ﺍﻟﻬﻭﺍﺀ ﺤﻭﻟﻪ ﺴﺭﻴﺎﻨﺎﹰ ﻁﺒﻴﻌﻴﺎﹰ ﺃﻴﻀﺎﹰ(‬
‫)ﺏ( ﺃﻗﺼﻰ ﺘﺤﻤﻴل ﻴﻭﻤﻰ ﻟﻠﺤﻔﺎﻅ ﻋﻠﻰ ﺴﻼﻤﺔ ﺍﻟﻤﺤﻭﻻﺕ‬
‫‪Daily Peak Load of Transformer Nameplate Rating to Give Normal‬‬
‫‪Life Expectancy‬‬
‫)‪ (١‬ﻴﻤﻜﻥ ﺘﺸﻐﻴل ﺍﻟﻤﺤﻭﻻﺕ ﻋﻨﺩ ﺩﺭﺠﺎﺕ ﺤﺭﺍﺭﺓ ﺍﻟﺯﻴـﺕ ﺃﻋﻠـﻰ ﻤـﻥ ‪ْ ٩٥‬ﻡ‪،‬‬
‫ﻟﻔﺘﺭﺍﺕ ﻗﺼﻴﺭﺓ ﻤﺤﺩﺩﺓ ﺒﺩﻭﻥ ﺃﻥ ﺘﺴﺒﺏ ﻤﺨﺎﻁﺭ ﺘﺫﻜﺭ ﻋﻠﻰ ﺍﻟﻤﺤﻭل‪ ،‬ﻜﺫﻟﻙ‬
‫ﻴﻤﻜﻥ ﺘﺸﻐﻴﻠﻬﺎ ﻟﻔﺘﺭﺍﺕ ﺃﻁﻭل ﻋﻨﺩ ﺩﺭﺠﺎﺕ ﺤﺭﺍﺭﺓ ﺃﻗل ﻤﻥ ‪ْ ٩٥‬ﻡ‪.‬‬
‫ﻋﺎﺩﺓ ﺘﺘﻜﻭﻥ ﺩﻭﺭﺓ ﺍﻟﺘﺤﻤﻴل ﺍﻟﻴﻭﻤﻰ )‪ (Daily load‬ﻤﻥ ﺃﺤﻤﺎل ﻤﺘﻐﻴﺭﺓ ﺨﻼل‬
‫ﺍﻟﻴﻭﻡ‪ ،‬ﻭﻴﻤﻜﻥ ﺃﻥ ﻨﻘﺴﻡ ﺍﻟﺩﻭﺭﺓ ﺇﻟﻰ ﻤﺭﺍﺤل ﺒﺤﻴﺙ ﻴﻜﻭﻥ ﺍﻟﺤﻤل ﺜﺎﺒﺘﺎﹰ ﺘﻘﺭﻴﺒﺎﹰ‬
‫ﻓﻰ ﻜل ﻤﺭﺤﻠﺔ‪ ،‬ﻜﻤﺎ ﻴﻤﻜﻥ ﺤﺴﺎﺏ ﺍﻟﺤﻤل ﺍﻟﻤﻜﺎﻓﺊ ﻟﺩﻭﺭﺓ ﺍﻟﺘﺤﻤﻴل ﺍﻟﻴـﻭﻤﻰ‬
‫ﻤﻥ ﺍﻟﻤﻌﺎﺩﻟﺔ )‪:(١-٤‬‬

‫‪L12 t1 + L22 t2 + .... + L2n t n‬‬


‫= ‪Equivalent load‬‬ ‫)‪(4-1‬‬
‫‪t1 + t2 ............. + t n‬‬

‫ﺤﻴﺙ‪:‬‬
‫‪ L1 , L2 , Ln‬ﺃﺤﻤﺎل ﺍﻟﻤﺭﺍﺤل ﺍﻟﻤﺨﺘﻠﻔﺔ‬
‫‪ t1 , t 2 , t n‬ﻓﺘﺭﺓ ﻜل ﻤﺭﺤﻠﺔ‬

‫‪٤‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺭﺍﺒﻊ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫)‪ (٢‬ﻴﺠﺏ ﻋﻨﺩ ﺘﺤﻤﻴل ﺍﻟﻤﺤﻭﻻﺕ ﻋﻨﺩ ﺩﺭﺠﺎﺕ ﺤـﺭﺍﺭﺓ ﺃﻜﺒـﺭ ﻤـﻥ ‪ْ ٥٠‬ﻡ ﺃﻻ‬
‫ﺘﺘﻌﺩﻯ ﺤﺩﻭﺩ ﺍﻟﺘﺤﻤﻴل ﻓﺘﺭﺓ ﺯﻤﻨﻴﺔ ﻤﻌﻴﻨﺔ‪ ،‬ﻤﺤﺩﺩﺓ ﺒﺎﻟﻤﻭﺍﺼـﻔﺎﺕ ﺍﻟﻘﻴﺎﺴـﻴﺔ‬
‫ﺍﻟﻌﺎﻟﻤﻴﺔ‪ ،‬ﺤﺘﻰ ﻻ ﻴﺘﺄﺜﺭ ﺍﻟﻤﺤﻭل ﻭﻴﻘل ﻋﻤﺭﻩ ﺍﻻﻓﺘﺭﺍﻀﻰ‪ ،‬ﻭﻴﺠـﺏ ﻋﻤـل‬
‫ﺘﻭﺍﺯﻥ ﻟﺩﻭﺭﺓ ﺍﻟﺤﻤل ﺍﻟﻴﻭﻤﻰ‪ ،‬ﺒﺤﻴﺙ ﻴﺘﻡ ﺘﺤﻤﻴل ﺍﻟﻤﺤـﻭل ﺒﺤﻤـل ﺼـﻐﻴﺭ‬
‫ﻟﻔﺘﺭﺍﺕ ﺃﺨﺭﻯ‪ ،‬ﺜﻡ ﺘﺤﻤﻴﻠﻪ ﻟﻔﺘﺭﺓ ﺯﻤﻨﻴﺔ ﺼﻐﻴﺭﺓ ﺒﺎﻟﺤﻤـل ﺍﻟﺯﺍﺌـﺩ‪ ،‬ﻭﻴـﺘﻡ‬
‫ﺍﻟﻜﺸﻑ ﻋﻠﻰ ﺠﻤﻴﻊ ﺃﺠﺯﺍﺀ ﺍﻟﻤﺤﻭل‪ ،‬ﺒﻌﺩ ﺘﺸﻐﻴﻠﻪ ﺒﺯﻴﺎﺩﺓ ﺤﻤل )ﻤﺜل‪ :‬ﻨﻬﺎﻴـﺔ‬
‫ﺍﻟﻜﺎﺒﻼﺕ – ﻨﻘﻁ ﺍﻟﺘﻘﺴﻴﻡ ‪ ،‬ﺇﻥ ﺃﻤﻜﻥ‪ ،‬ﻋﻭﺍﺯل ﺍﻻﺨﺘﺭﺍﻕ ‪.(....‬‬
‫ﻴﻭﻀﺢ ﺠﺩﻭل )‪ (٢-٤‬ﺃﻗﺼﻰ ﺘﺤﻤﻴل ﻴﻭﻤﻰ ﻟﻠﻤﺤﻭﻻﺕ ﺒﺩﻻﻟﺔ ﺩﺭﺠـﺔ ﺍﻟﺤـﺭﺍﺭﺓ‬
‫ﺍﻟﻤﺤﻴﻁ ﻟﻠﺤﻔﺎﻅ ﻋﻠﻰ ﻋﻤﺭﻫﺎ ﺍﻻﻓﺘﺭﺍﻀﻰ‪٠‬‬
‫‪Daily peak load of Transformer nameplate rating to give normal life expectancy‬‬

‫‪٤‬‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬

‫ﺟﺪول رﻗﻢ )‪ :(٢-٤‬أﻗﺼﻰ ﺣﻤﻞ ﯾﻮﻣﻰ ﻛﻨﺴﺒﺔ ﻣﻦ اﻟﺤﻤﻞ اﻟﻤﻘﻨﻦ‬


‫اﻟﻤﺬﻛﻮر ﺑﻠﻮﺣﺔ ﺑﯿﺎن اﻟﻤﺤﻮل‪ ،‬ﻟﺤﻔﺎظ ﻋﻠﻰ ﻋﻤﺮ اﻟﻤﺤﻮل‬
‫زﻣﻦ‬
‫أﻗﺼﻰ‬
‫ﺣﻤﻞ‬
‫)ﺳﺎﻋﺔ(‬
‫درﺟﺔ اﻟﺤﺮارة اﻟﻤﺤﯿﻄﺔ ) ْ م(‬ ‫درﺟﺔ اﻟﺤﺮارة اﻟﻤﺤﯿﻄﺔ ) ْ م(‬ ‫درﺟﺔ اﻟﺤﺮارة اﻟﻤﺤﯿﻄﺔ ) ْ م(‬

‫‪٤‬‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺭﺍﺒﻊ‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺭﺍﺒﻊ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺍﻟﺘﺤﻤﻴل ﺍﻟﺯﺍﺌﺩ ﻟﻠﻤﺤﻭﻻﺕ‬ ‫‪٢-٤‬‬


‫ﺍﻟﻤﺤﻭﻻﺕ ﺍﻟﻤﻐﻤﻭﺭﺓ ﻓﻰ ﺍﻟﺯﻴﺕ‬ ‫)ﺃ(‬
‫ﺠﺩﻭل )‪ (٣-٤‬ﻴﺤﺘﻭﻯ ﻋﻠﻰ ﻗﺩﺭﺓ ﺍﻟﺘﺤﻤﻴل ﺍﻟﺯﺍﺌﺩ )ﻜﻨﺴﺒﺔ ﻤـﻥ ﺍﻟﻘـﺩﺭﺓ ﺍﻟﻤﻘﻨﻨـﺔ‬
‫ﻟﻠﻤﺤﻭﻻﺕ ﺍﻟﻤﻐﻤﻭﺭﺓ ﻓﻰ ﺍﻟﺯﻴﺕ‪ ،‬ﻁﺒﻘﺎﹰ ﻟﻠﻤﻭﺍﺼـﻔﺎﺕ ﺍﻟﻘﻴﺎﺴـﻴﺔ ﺍﻷﻟﻤﺎﻨﻴـﺔ )‪(DIN‬‬
‫ﻴﺠﺏ ﺃﻻ ﺘﺘﻌﺩﻯ ﻤﺘﻭﺴﻁ ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺍﻟﻤﻠﻔﺎﺕ ‪ْ ١٠٥‬ﻡ‪ ،‬ﺇﺫﺍ ﻜﺎﻥ ﻤﺘﻭﺴﻁ ﺩﺭﺠـﺔ‬
‫ﻭﺴﻁ ﺍﻟﺘﺒﺭﻴﺩ ﺨﻼل ﺍﻟﺩﻭﺭﺓ ‪ْ ٢٥‬ﻡ‪ ،‬ﻭﺇﺫﺍ ﻜﺎﻨﺕ ﺍﻟﻤﺤﻭﻻﺕ ﻤﺠﻬﺯﺓ ﺒﻤﺭﺍﻭﺡ ﺘﺒﺭﻴـﺩ‬
‫ﻭﻟﻜﻥ ﺍﻟﻤﺭﺍﻭﺡ ﻤﻌﺯﻭﻟﺔ ﻓﻴﺠﺏ ﺃﻥ ﻴﻜﻭﻥ ﺍﻟﺘﺤﻤﻴـل ‪ ٪٦٠‬ﻤـﻥ ﺍﻟﻘـﺩﺭﺓ ﺍﻟﻤﻘﻨﻨـﺔ‬
‫ﻟﻠﻤﺤﻭل‪.‬‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪-:(٣-٤‬ﻓﺘﺭﺓ ﺯﻴﺎﺩﺓ ﺍﻟﺤﻤل ﻟﻠﻤﺤﻭﻻﺕ ﺍﻟﻤﻐﻤﻭﺭﺓ ﻓﻰ ﺍﻟﺯﻴﺕ‬

‫ﻤﺩﺓ ﺍﻟﺘﺤﻤﻴل ﺍﻟﺯﺍﺌﺩ ﺒﺎﻋﺘﺒﺎﺭ ﺍﻟﺤﻤل ﺍﻟﺯﺍﺌﺩ ﻨﺴﺒﺔ ﻤﻥ‬ ‫ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺍﻟﺯﻴﺕ ْﻡ ﻋﻨﺩ ﺒﺩﺍﻴﺔ‬
‫ﻨﺴﺒﺔ ﺍﻟﺘﺤﻤﻴل‬
‫ﺍﻟﻤﻘﻨﻥ‬ ‫ﺯﻴﺎﺩﺓ ﺍﻟﺤﻤل ﺘﺒﻌﺎﹰ ﻟﺤﺎﻟﺔ ﺍﻟﺘﺒﺭﻴﺩ‬
‫ﺍﻟﺴﺎﺒﻘﺔ ‪ ٪‬ﻤﻥ‬
‫‪٪٥٠‬‬ ‫‪٪٤٠‬‬ ‫‪٪٣٠‬‬ ‫‪٪٢٠‬‬ ‫‪٪١٠‬‬ ‫ﺘﺒﺭﻴﺩ ﻤﻴﺎﻩ –‬ ‫ﺘﺒﺭﻴﺩ ﻫﻭﺍﺀ‬
‫ﻗﻴﻤﺔ ﻗﺩﺭﺓ‬
‫ﺘﺒﺭﻴﺩ ﺯﻴﺕ‬ ‫ﻁﺒﻴﻌﻰ ﺃﻭ‬
‫ﺩﻗﻴﻘﺔ‬ ‫ﺩﻗﻴﻘﺔ‬ ‫ﺩﻗﻴﻘﺔ‬ ‫ﺴﺎﻋﺔ‬ ‫ﺴﺎﻋﺔ‬ ‫ﺍﻟﻤﺤﻭل‬
‫ﻭﻫﻭﺍﺀ ﻤﺩﻓﻭﻉ‬ ‫ﻤﺭﺍﻭﺡ‬
‫‪١٥‬‬ ‫‪٣٠‬‬ ‫‪٦٠‬‬ ‫‪١.٥‬‬ ‫‪٣‬‬ ‫‪٤٩‬‬ ‫‪٥٥‬‬ ‫‪٥٠‬‬
‫‪٨‬‬ ‫‪١٥‬‬ ‫‪٣٠‬‬ ‫‪١‬‬ ‫‪٢‬‬ ‫‪٦٠‬‬ ‫‪٦٨‬‬ ‫‪٧٥‬‬
‫‪٤‬‬ ‫‪٨‬‬ ‫‪١٥‬‬ ‫‪٠.٥‬‬ ‫‪١‬‬ ‫‪٦٨‬‬ ‫‪٧٨‬‬ ‫‪٩٠‬‬

‫)ﺏ( ﺍﻟﻤﺤﻭﻻﺕ ﺍﻟﺠﺎﻓﺔ‬


‫ﻴﻭﻀﺢ ﺠﺩﻭل )‪ (٤-٤‬ﻓﺘﺭﺍﺕ ﺯﻴﺎﺩﺓ ﺍﻟﺤﻤل ﻟﻠﻤﺤﻭﻻﺕ ﺍﻟﺠﺎﻓﺔ ﺫﺍﺕ ﻤﺎﺩﺓ ﻋﺯل ﻤﻥ‬
‫ﺍﻟﺩﺭﺠﺔ )‪ (A‬ﺒﻔﺭﺽ ﺃﻥ ﺍﻟﻤﻠﻔﺎﺕ ﺍﻻﺒﺘﺩﺍﺌﻴﺔ ﻤﺒـﺭﺩﺓ ﺒـﺎﻟﻬﻭﺍﺀ ﺍﻟﻤﺤـﻴﻁ ﻤﺒﺎﺸـﺭﺓ‪،‬‬
‫ﻟﻠﻤﺤﻭﻻﺕ ﺍﻟﺠﺎﻓﺔ ﺫﺍﺕ ﻤﺎﺩﺓ ﻋﺯل ﻤﻥ ﺍﻟﺩﺭﺠﺔ )‪ (B‬ﻭﺍﻟﺩﺭﺠﺔ )‪ (E‬ﻴﺴﺘﺨﺩﻡ ﺠـﺩﻭل‬
‫)‪ (٣-٤‬ﻤﻊ ﻤﺭﺍﻋﺎﺓ ﺃﻥ ﺘﻘل ﻨﺴﺒﺔ ﺍﻟﺘﺤﻤﻴل ﺒﻨﺴﺒﺔ ‪ ٪٩٠ ، ٪٨٥‬ﻋﻠﻰ ﺍﻟﺘﻭﺍﻟﻰ‪.‬‬

‫‪٤‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺭﺍﺒﻊ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪-:(٤-٤‬ﻓﺘﺭﺓ ﺯﻴﺎﺩﺓ ﺍﻟﺤﻤل ﻟﻠﻤﺤﻭﻻﺕ ﺍﻟﺠﺎﻓﺔ ﺫﺍﺕ ﻋﺯل ﺩﺭﺠﺔ )‪(A‬‬

‫ﻓﺘﺭﺓ ﺯﻴﺎﺩﺓ ﺍﻟﺤﻤل ﻟﻠﻤﺤﻭﻻﺕ ﻜﻨﺴﺒﺔ ﻤﻥ ﺍﻟﻤﻘﺩﺭﺓ ﺍﻟﻤﻘﻨﻨﺔ‬ ‫ﻨﺴﺒﺔ ﺍﻟﺘﺤﻤﻴل‬


‫‪٪٥٠‬‬ ‫‪٪٤٠‬‬ ‫‪٪٣٠‬‬ ‫‪٪٢٠‬‬ ‫‪٪١٠‬‬ ‫ﺍﻟﺴﺎﺒﻘﺔ ‪ ٪‬ﻤﻥ‬
‫ﻗﻴﻤﺔ ﻗﺩﺭﺓ‬
‫ﺩﻗﻴﻘﺔ‬ ‫ﺩﻗﻴﻘﺔ‬ ‫ﺩﻗﻴﻘﺔ‬ ‫ﺩﻗﻴﻘﺔ‬ ‫ﺩﻗﻴﻘﺔ‬
‫ﺍﻟﻤﺤﻭل‬
‫‪١٢‬‬ ‫‪١٥‬‬ ‫‪٢٠‬‬ ‫‪٣٠‬‬ ‫‪٦٠‬‬ ‫‪٥٠‬‬
‫‪٩‬‬ ‫‪١١‬‬ ‫‪١٥‬‬ ‫‪٢٣‬‬ ‫‪٥٥‬‬ ‫‪٧٥‬‬
‫‪٥‬‬ ‫‪٧‬‬ ‫‪١٠‬‬ ‫‪١٦‬‬ ‫‪٤٥‬‬ ‫‪٩٠‬‬

‫ﺇﺫﺍ ﻜﺎﻨﺕ ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺍﻟﻬﻭﺍﺀ ﻤﺨﺘﻠﻔﺔ ﻋﻥ ﺍﻟﻘﻴﻡ ﺍﻟﻘﻴﺎﺴﻴﺔ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻟﻠﻤﺤـﻭﻻﺕ‬
‫ﻓﻴﺘﻡ ﺍﻟﺭﺠﻭﻉ ﺇﻟﻰ ﺠﺩﻭل )‪ (٥-٤‬ﻟﻠﻤﺤﻭﻻﺕ ﺍﻟﻤﻐﻤﻭﺭﺓ ﻓﻰ ﺍﻟﺯﻴﺕ – ﺘﺒﺭﻴﺩ ﺍﻟﻬﻭﺍﺀ‪.‬‬

‫ﺠﺩﻭل ﺭﻗﻡ )‪-:(٥-٤‬ﺍﻟﺤﻤل ﺍﻟﻤﺴﺘﻤﺭ ﺍﻟﻤﺴﻤﻭﺡ ﻟﻠﻤﺤﻭﻻﺕ ﺍﻟﺯﻴﺘﻴﺔ )ﺘﺒﺭﻴﺩ ﻫﻭﺍﺀ(‬


‫ﻋﻨﺩ ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺘﺨﺘﻠﻑ ﻋﻥ ﺍﻟﻘﻴﻡ ﺍﻟﻘﻴﺎﺴﻴﺔ‬

‫‪١٠ -‬‬ ‫‪٢٠ -‬‬ ‫ﺍﺨﺘﻼﻑ ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺍﻟﻬﻭﺍﺀ ﻋﻥ ﺍﻟﻘﻴﻤﺔ‬


‫‪ْ ٢٠ +‬ﻡ‬ ‫‪ْ ١٠ +‬ﻡ‬ ‫ﺼﻔﺭ‬
‫ْﻡ‬ ‫ْﻡ‬ ‫ﺍﻟﻘﻴﺎﺴﻴﺔ‬

‫‪٨١‬‬ ‫‪٩١‬‬ ‫‪١٠٠‬‬ ‫‪١١١‬‬ ‫‪١٢١‬‬ ‫ﺘﺒﺭﻴﺩ ﻫﻭﺍﺀ ﻋﺎﺩﻯ‬ ‫ﺍﻟﻘﺩﺭﺓ‬


‫ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ‪٪‬‬
‫‪٨٣‬‬ ‫‪٩٢‬‬ ‫‪١٠٠‬‬ ‫‪١٠٩‬‬ ‫‪١١٥‬‬ ‫ﺘﺒﺭﻴﺩ ﻫﻭﺍﺀ ﺒﺎﻟﻤﺭﺍﻭﺡ‬
‫ﻤﻥ ﻗﻴﻤﺔ ﺍﻟﻘﺩﺭﺓ‬
‫‪٨٤‬‬ ‫‪٩٢‬‬ ‫‪١٠٠‬‬ ‫‪١٠٧‬‬ ‫‪١١٥‬‬ ‫ﺍﺴﺘﺨﺩﺍﻡ ﻤﻀﺨﺎﺕ ﻫﻭﺍﺀ‬ ‫ﺍﻟﻤﻘﻨﻨﺔ‬

‫)ﺕ( ﻁﺭﻴﻘﺔ ﺃﺨﺭﻯ ﺘﺴﺘﺨﺩﻡ ﻟﻠﺘﺤﻤﻴل ﺍﻟﺯﺍﺌﺩ ﻟﻠﻤﺤﻭﻻﺕ‬


‫ﻴﻤﻜﻥ ﺘﺤﻤﻴل ﺍﻟﻤﺤﻭﻻﺕ ﺒﻘﺩﺭﺓ ﺃﻜﺜﺭ ﻤﻥ ﺍﻟﺴﻌﺔ ﺍﻻﺴﻤﻴﺔ ﻟﻠﻤﺤـﻭل ﻤـﻊ ﻤﺭﺍﻋـﺎﺓ‬
‫ﺍﻟﺘﺤﻤﻴل ﺍﻟﻤﻌﺘﺎﺩ ﻟﻠﻤﺤﻭل ﻭﺫﻟﻙ ﺒﺎﻻﺴﺘﻌﺎﻨﺔ ﺒﺎﻟﻤﻨﺤﻨﻴﺎﺕ ﺸﻜل )‪ (١-٤‬ﻭ ﺍﻟﺘﻲ ﺘﻤﺜـل‬
‫ﺍﻟﻌﻼﻗﺔ ﺒﻴﻥ ﺍﻟﺘﺤﻤﻴل ﻟﻠﻤﺤﻭل ﻜﻨﺴﺒﺔ ﻤﻥ ﺍﻟﺴﻌﺔ ﺍﻻﺴﻤﻴﺔ )‪ (k1‬ﻭ ﺍﻟﺘﺤﻤﻴـل ﺍﻟﺯﺍﺌـﺩ‬
‫ﻟﻠﻤﺤﻭل ﺍﻟﻤﺴﻤﻭﺡ ﺒﻪ ﻜﻨﺴﺒﺔ ﻤﻥ ﺍﻟﺴﻌﺔ ﺍﻻﺴﻤﻴﺔ )‪ (k2‬ﻭ ﺫﻟﻙ ﻟﻌﺩﺩ ﺴﺎﻋﺎﺕ ﻤﻌﻴﻨﺔ‪،‬‬
‫ﻓﻲ ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ‪ °٣٠‬ﻤﺌﻭﻴﺔ‪.‬‬

‫‪٤‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺭﺍﺒﻊ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(١-٤‬ﻤﻨﺤﻨﻴﺎﺕ ﺍﻟﺘﺤﻤﻴل ﺍﻟﺯﺍﺌﺩ ﻟﻤﺤﻭﻻﺕ ﺍﻟﺘﻭﺯﻴﻊ ﻓﻲ ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ‪ ٣٠‬ﺩﺭﺠﺔ ﻤﺌﻭﻴﺔ‬

‫ﺤﻴﺙ‪:‬‬
‫= ﺍﻟﺤﻤل ﺍﻟﻤﻌﺘﺎﺩ ﻜﻨﺴﺒﺔ ﻤﻥ ﺍﻟﺴﻌﺔ ﺍﻻﺴﻤﻴﺔ‬ ‫‪k1‬‬
‫= ﺍﻟﺤﻤل ﺍﻟﺯﺍﺌﺩ ﺍﻟﻤﺴﻤﻭﺡ ﺒﻪ ﻜﻨﺴﺒﺔ ﻤﻥ ﺍﻟﺴﻌﺔ ﺍﻻﺴﻤﻴﺔ‬ ‫‪k2‬‬
‫= ﻓﺘﺭﺓ ﺍﻟﺘﺤﻤﻴل ﺍﻟﺯﺍﺌﺩ )ﺴﺎﻋﺔ(‪.‬‬ ‫‪t‬‬

‫‪٤‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺭﺍﺒﻊ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺃﻤﺜﻠﺔ ﺘﻁﺒﻴﻘﻴﺔ‬ ‫‪٣-٤‬‬


‫ﻤﺜﺎل )‪:(١‬‬
‫ﻤﺒﻨﻰ ﺇﺩﺍﺭﻯ ﻤﺴﺎﺤﺘﻪ ‪ ١٥٠٠‬ﻤﺘﺭ ﻤﺭﺒﻊ ﻭﻤﻜﻭﻥ ﻤﻥ ‪ ٣٠‬ﻁﺎﺒﻘﺎﹰ‬
‫ﺍﻟﻤﻁﻠﻭﺏ‪:‬‬
‫ﺘﺤﺩﻴﺩ ﺴﻌﺔ ﻤﺤﻭل ﺍﻟﺘﻭﺯﻴﻊ ﺍﻟﻤﻨﺎﺴﺏ ﻟﻬﺫﺍ ﺍﻟﻤﺒﻨﻰ ﻤﻊ ﻋﺩﻡ ﺍﻟﺴﻤﺎﺡ ﺒﺎﻟﺘﺤﻤﻴل ﺍﻟﺯﺍﺌﺩ‪.‬‬
‫ﺍﻟﺤل‪:‬‬
‫‪٢‬‬
‫ﻤﻥ ﺠﺩﻭل )‪ : (٤-٣‬ﻁﻠﺏ ﺍﻟﺤﻤل ‪ ١٢‬ﻙ‪.‬ﻑ‪.‬ﺃ ‪١٠٠ /‬ﻡ‬
‫‪١٥٠٠‬‬
‫× ‪ ٥.٤ = ٣٠ × ١٢‬ﻡ‪.‬ﻑ‪.‬ﺃ‬ ‫ﺍﻟﺤﻤل ﺍﻷﻗﺼﻰ ﻟﻠﻤﺒﻨﻰ =‬
‫‪١٠٠‬‬

‫= ‪ ٦.٧٥‬ﻡ‪.‬ﻑ‪.‬ﺃ ﻭﻋﻠﻰ ﺃﺴﺎﺱ ﺍﻟﺘﺤﻤﻴل ‪ ٪٨٠‬ﻤﻥ ﺴﻌﺔ‬ ‫‪٥.٤‬‬


‫ﺤﻤل ﺍﻟﻤﺤﻭﻻﺕ =‬
‫ﺍﻟﻤﺤﻭﻻﺕ‬ ‫‪٠.٨‬‬
‫ﺍﻟﻤﺤﻭﻻﺕ ﺍﻟﻤﻘﻨﻨﺔ = ‪ ٧.٥ = ٥ × ١.٥‬ﻡ‪.‬ﻑ‪.‬ﺃ‬
‫ﻋﺩﺩ ‪ ٥ /‬ﻤﺤﻭﻻﺕ ﻗﺩﺭﺓ ﻜل ﻤﻨﻬﺎ ‪ ١.٥‬ﻡ‪.‬ﻑ‪.‬ﺃ = ﺇﺠﻤﺎﻟﻴﺎﹰ ‪ ٧.٥‬ﻡ‪.‬ﻑ‪.‬ﺃ‬
‫ﻤﺜﺎل )‪:(٢‬‬
‫ﻤﺤﻭل ﺴﻌﺘﻪ ﺍﻻﺴﻤﻴﺔ ‪ ١٢٥٠‬ﻙ‪.‬ﻑ‪.‬ﺃ‪ ،‬ﻭ ﺍﻟﺤﻤل ﺍﻟﻤﻌﺘﺎﺩ ﻟﻬﺫﺍ ﺍﻟﻤﺤﻭل ﻫﻭ ‪٧٥٠‬ﻙ‪.‬ﻑ‪.‬ﺃ‪،‬‬
‫ﻓﻤﺎ ﻫــﻭ ﺃﻗﺼﻰ ﺘﺤﻤﻴل ﺯﺍﺌﺩ ﻤﺴﻤــﻭﺡ ﺒﻪ ﻟﻤﺩﺓ ﺃﺭﺒﻌـﺔ ﺴـﺎﻋﺎﺕ‪ ،‬ﻭ ﺫﻟـﻙ ﻓـﻲ‬
‫ﺩﺭﺠــﺔ ﺤــﺭﺍﺭﺓ ‪ °٣٠‬ﻤﺌﻭﻴﺔ؟‬
‫ﻤﻥ ﺍﻟﺸﻜل )‪:(١-٤‬‬
‫‪750‬‬
‫= ‪k1‬‬ ‫‪= 0.6 ; t =4 h‬‬
‫‪1250‬‬
‫‪∴k2 =1.19‬‬
‫ﻭﺒﺫﻟﻙ ﻴﻜﻭﻥ ﺃﻗﺼﻲ ﺘﺤﻤﻴل ﺯﺍﺌﺩ ﻤﺴﻤﻭﺡ ﺒﻪ ﻟﻤﺩﺓ ﺃﺭﺒﻌﺔ ﺴﺎﻋﺎﺕ ﻫﻭ‪:‬‬
‫‪S2 = k2. SN = 1.19 * 1250 = 1487.5 kVA‬‬
‫ﻤﺜﺎل )‪:(٣‬‬
‫ﺍﻟﻤﻁﻠﻭﺏ ﺘﺤﺩﻴﺩ ﺴﻌﺔ ﻤﺤﻭل ﺘﻭﺯﻴﻊ ﺒﻨﻅﺎﻡ ﺘﺒﺭﻴﺩ ‪ ONAN‬ﻴﺘﻡ ﺘﺤﻤﻴﻠﻪ ﺒﺤﻤل ﻗﻴﻤﺘﻪ ‪٤٥٠‬‬
‫ﻙ‪.‬ﻑ‪.‬ﺃ ﻟﻤﺩﺓ ﺃﺭﺒﻊ ﺴﺎﻋﺎﺕ‪ ،‬ﻭﺤﻤل ﻗﻴﻤﺘﻪ ‪ ٢٥٠‬ﻙ‪.‬ﻑ‪.‬ﺃ ﻟﻤﺩﺓ ﺍﻟﻌﺸﺭﻴﻥ ﺴﺎﻋﺔ ﺍﻟﺒﺎﻗﻴﺔ‬
‫‪S1= 250 kVA , t1 = 20h‬‬
‫‪S2= 450 kVA , t2 = 4h‬‬
‫‪S2/ S1 = 450 / 250 = 1.8 = k2 / k1‬‬

‫‪٤‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺭﺍﺒﻊ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻤﻥ ﺍﻟﺸﻜــل )‪ (١-٤‬ﺒﺭﺴﻡ ﺍﻟﺨﻁ ‪ 1.8 = k2 / k1‬ﻭﻴﻤﺭ ﺒﻨﻘﻁﺔ ﺍﻷﺼل ; ﻭﺘﻘﺎﻁﻌﻪ ﻤﻊ‬
‫ﺍﻟﻤﻨﺤﻨﻰ ‪ ، t = 4h‬ﻓﺈﻥ ﺍﻟﺴﻌﺎﺕ ﺍﻷﺴﻤﻴﺔ ‪ k2 ، k1‬ﺘﻜﻭﻥ ﻋﻠﻰ ﺍﻟﻨﺤﻭ ﺍﻟﺘﺎﻟﻰ‪:‬‬
‫‪S1 S2‬‬
‫= ‪SN‬‬ ‫=‬
‫‪K1 K2‬‬
‫‪k1 = 0.633 , k2 = 1.14‬‬
‫ﻭﺤﻴﺙ ﺃﻥ‪ S2 = k2 .SN :‬ﺃﻭ ‪ S1 = k1. S N‬ﺘﻜﻭﻥ‪:‬‬
‫‪S1‬‬ ‫‪S‬‬
‫= ‪SN‬‬ ‫‪= 2‬‬
‫‪K1 K2‬‬
‫‪450‬‬ ‫‪250‬‬
‫= ‪SN‬‬ ‫=‬ ‫‪= 394.9 KVA‬‬
‫‪1.14 0.633‬‬
‫ﻭﻟﺫﺍ ﻓﺈﻥ ﺍﻟﻤﺤﻭل ﺍﻟﻤﻨﺎﺴﺏ ﻫﻭ ﻤﺤﻭل ﺴﻌﺘﻪ ‪٤٠٠‬ﻙ‪.‬ﻑ‪.‬ﺃ‪.‬‬

‫ﻤﺜﺎل )‪:(٤‬‬
‫ﺴﻭﻕ ﺘﺠﺎﺭﻯ ﻓﺎﺨﺭ ﻤﺴﺎﺤﺘﻪ ‪ ٤٠٠٠‬ﻤﺘﺭ ﻤﺭﺒﻊ ﻤﻜﻭﻥ ﻤﻥ ﺃﺭﺒﻊ ﻁﻭﺍﺒﻕ‬
‫ﺍﻟﻤﻁﻠﻭﺏ‪:‬‬
‫ﺘﺤﺩﻴﺩ ﺴﻌﺔ ﻤﺤﻭﻻﺕ ﺍﻟﺘﻭﺯﻴﻊ ﺍﻟﻤﻨﺎﺴﺒﺔ ﻟﻠﺴﻭﻕ ﻤﻊ ﺍﻟﺴﻤﺎﺡ ﺒﺎﻟﺘﺤﻤﻴل ﺍﻟﺯﺍﺌﺩ ﺒﻨﺴـﺒﺔ ‪٪١٠‬‬
‫ﻟﻤﺩﺓ ﺴﺎﻋﺘﻴﻥ‪.‬‬
‫‪٢‬‬
‫‪ ١٢ × ٤‬ﻙ‪.‬ﻑ‪.‬ﺃ‬ ‫‪٤٠٠٠‬ﻡ‬
‫= ‪ ١.٩٢‬ﻡ‪.‬ﻑ‪.‬ﺃ‬ ‫×‬ ‫‪٢‬‬
‫ﺍﻟﺤﻤل ﺍﻷﻗﺼﻰ =‬
‫‪١٠٠٠‬‬ ‫‪١٠٠‬ﻡ‬

‫ﻓﻰ ﺤﺎﻟﺔ ﺍﺴﺘﺨﺩﺍﻡ ﻤﺤﻭﻟﻴﻥ ﻓﺈﻥ ﺍﻟﺤﻤل ﻟﻠﻤﺤﻭل ﺍﻟﻭﺍﺤﺩ = ‪ ٩٦٠‬ﻙ‪.‬ﻑ‪.‬ﺃ‬


‫‪S1= 960 kVA , t1 = 22h‬‬
‫‪S2= 1.1S1 = 1056 kVA , t2 = 2h‬‬
‫‪S2‬‬
‫‪=1.1‬‬
‫‪S1‬‬
‫‪K2‬‬
‫‪=1.1‬‬
‫‪K1‬‬
‫ﻤﻥ ﺍﻟﺸﻜل )‪ (١-٤‬ﺒﺭﺴﻡ ﺍﻟﺨﻁ ‪ ١.١ = k2 / k1‬ﻭﻴﻤﺭ ﺒﻨﻘﻁﺔ ﺍﻷﺼـل ﻭﺘﻘﺎﻁﻌـﻪ ﻤـﻊ‬
‫ﺍﻟﻤﻨﺤﻨﻰ ‪t = 2 h‬‬

‫‪K1 = 0.9, k2 = 1‬‬


‫‪960‬‬
‫= ‪SN‬‬ ‫‪= 1066.6 MVA‬‬
‫‪0.9‬‬

‫‪٤‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺘﺼﻤﻴﻡ ﺍﻟﺩﻭﺍﺌﺭ ﺍﻟﻔﺭﻋﻴﺔ‬ ‫‪-٥‬‬


‫ﻋــــــﺎﻡ‬ ‫‪١-٥‬‬
‫‪ -‬ﺘﺸﺘﻤل ﺍﻟﺩﻭﺍﺌﺭ ﺍﻟﻔﺭﻋﻴﺔ ﻋﻠﻲ ﺍﻟﺘﻭﺼﻴﻼﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻤﻥ ﻟﻭﺤﺔ ﺍﻟﺘﻭﺯﻴـﻊ ﺍﻟﺭﺌﻴﺴـﻴﺔ‬
‫ﺒﺎﻟﻤﺒﻨﻲ ﺇﻟﻲ ﺍﻟﻠﻭﺤﺎﺕ ﺍﻟﻔﺭﻋﻴﺔ ﻓﻰ ﻜل ﺩﻭﺭ ﺃﻭ ﻗﺴﻡ ﻤﻥ ﺃﻗﺴﺎﻡ ﺍﻟﻤﺒﻨﻲ ‪ ،‬ﻭﻤﻨﻬـﺎ ﺇﻟـﻲ‬
‫ﺍﻟﻠﻭﺤﺎﺕ ﺍﻟﻔﺭﻋﻴﺔ ﻓﻰ ﻜل ﺸﻘﺔ ﺃﻭ ﻜل ﻤﻥ ﺃﻗﺴﺎﻡ ﺍﻟﺩﻭﺭ ﻭﻤﻥ ﺜﻡ ﺇﻟﻰ ﺍﻟﺩﻭﺍﺌﺭ ﺍﻟﻔﺭﻋﻴـﺔ‬
‫ﺍﻟﻨﻬﺎﺌﻴﺔ ﻟﺘﻐﺫﻴﺔ ﺍﻷﺤﻤﺎل ﺍﻟﻔﺭﺩﻴﺔ‪.‬‬
‫‪ -‬ﻴﺘﻡ ﺘﻭﺯﻴﻊ ﺍﻟﺘﻐﺫﻴﺔ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻋﺎﺩﺓ ﻤﻥ ﺍﻟﻠﻭﺤﺔ ﺍﻟﺭﺌﻴﺴـﻴﺔ ﺒـﺎﻟﻤﺒﻨﻲ ﺇﻟـﻰ ﺍﻟﺠـﺭﺍﺝ‬
‫ﻭﺍﻟﺒﺩﺭﻭﻡ ﻭﺍﻟﺩﻭﺭ ﺍﻷﺭﻀﻲ ﺒﺎﺴﺘﻌﻤﺎل ﻜﺎﺒﻼﺕ ﺩﺍﺨل ﺍﻟﺤـﺎﺌﻁ ﺃﻭ ﻗﻀـﺒﺎﻥ ﻨﺤﺎﺴـﻴﺔ‬
‫ﻤﻼﺌﻤﺔ‪ ،‬ﻓﻰ ﺤﻴﻥ ﺘﻐﺫﻱ ﺍﻷﺩﻭﺍﺭ ﺍﻟﻌﻠﻭﻴﺔ ﻋﻥ ﻁﺭﻴﻕ ﺍﻟﺼـﻭﺍﻋﺩ ﻭﻫـﻰ ﻜـﺎﺒﻼﺕ ﺃﻭ‬
‫ﻗﻀﺒﺎﻥ ﻨﺤﺎﺴﻴﺔ ﻤﻼﺌﻤﺔ ﻭﺘﺘﻡ ﺍﻟﺘﻐﺫﻴﺔ ﺍﻷﻓﻘﻴﺔ ﻓﻲ ﻜل ﺩﻭﺭ ﺇﻟﻰ ﺍﻟﺸـﻘﻕ ﻓـﻰ ﺍﻟﻤﺒـﺎﻨﻰ‬
‫ﺍﻟﺴﻜﻨﻴﺔ ‪ ،‬ﺃﻭ ﺇﻟﻲ ﺍﻷﻗﺴﺎﻡ ﺍﻟﻤﺴﺘﻘﻠﺔ ﻓﻰ ﺍﻟﺩﻭﺭ ﻟﻠﻤﺒﺎﻨﻰ ﺍﻟﺘﺠﺎﺭﻴﺔ ‪ ،‬ﺤﻴﺙ ﻴﺭﻜﺏ ﻓﻲ ﻜل‬
‫ﻤﻨﻬﺎ ﻟﻭﺤﺔ ﺒﻬﺎ ﻋﺩﺍﺩ ﺍﺴﺘﻬﻼﻙ ﺍﻟﻁﺎﻗﺔ ﻭﻨﺒﺎﺌﻁ ﺍﻟﺘﻭﺼﻴل ﻭﺍﻟﻭﻗﺎﻴـﺔ ﻭﻤﻨﻬـﺎ ﺘﺨـﺭﺝ‬
‫ﺍﻟﺩﻭﺍﺌﺭ ﺍﻟﻔﺭﻋﻴﺔ ﻟﺘﻐﺫﻴﺔ ﺃﺤﻤﺎل ﺍﻟﺸﻘﺔ ﺃﻭ ﺍﻟﻘﺴﻡ ﺒﺎﻟﺩﻭﺭ‪.‬‬
‫‪ -‬ﻓﻰ ﺤﺎﻟﺔ ﺘﺭﻜﻴﺏ ﻋﺩﺍﺩﺍﺕ ﺍﺴﺘﻬﻼﻙ ﺍﻟﻁﺎﻗﺔ ﻟﻜل ﺍﻟﺸﻘﻕ )ﺃﻭ ﺃﻗﺴﺎﻡ ﺍﻟﻤﺒﻨﻲ( ﺒﺄﺴﻔﻠﻪ ﻴـﺘﻡ‬
‫ﺘﻐﺫﻴﺔ ﻜل ﺸﻘﺔ )ﺃﻭ ﻗﺴﻡ( ﻋﻠﻲ ﺤﺩﺓ ﺒﺩﺍﺌﺭﺓ ﺼﺎﻋﺩﺓ ﻤﺴﺘﻘﻠﺔ ﻤﻥ ﻤﺨﺭﺝ ﺍﻟﻌﺩﺍﺩ ﺍﻟﺨﺎﺹ‬
‫ﺒﻬﺎ ﻤﺒﺎﺸﺭﺓ ﺇﻟﻰ ﺍﻟﻠﻭﺤﺔ ﺍﻟﻔﺭﻋﻴﺔ )ﺃﻭ ﺍﻟﻠﻭﺤﺎﺕ( ﺒﺎﻟﺸﻘﺔ )ﺃﻭ ﺍﻟﻘﺴﻡ( ﺍﻟﺘﻰ ﺘﺨـﺭﺝ ﻤﻨﻬـﺎ‬
‫ﺍﻟﺩﻭﺍﺌﺭ ﺍﻟﻔﺭﻋﻴﺔ ﻟﺘﻐﺫﻴﺔ ﺍﻷﺤﻤﺎل ﺍﻟﻔﺭﺩﻴﺔ ‪.‬‬
‫ﻤﻠﺤﻭﻅﺔ‪ :‬ﺍﻟﻤﻘﺼﻭﺩ "ﺒﺎﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻯ" ﻓﻰ ﻫﺫﺍ ﺍﻟﺒﺎﺏ ﻫﻭ ﺍﻟﻜـﻭﺩ ﺍﻟﻤﺼـﺭﻯ ﻷﺴـﺱ‬
‫ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒـﺎﻨﻰ ﻁﺒﻘـﺎ‬
‫ﻟﻘﺭﺍﺭ ﺍﻟﺴﻴﺩ ﻭﺯﻴﺭ ﺍﻹﺴﻜﺎﻥ ﻭﺍﻟﻤﺭﺍﻓﻕ ﺭﻗﻡ ‪ ١٧٢‬ﻟﺴﻨﺔ ‪١٩٩٤‬‬

‫ﺨﻁﻭﺍﺕ ﺘﺼﻤﻴﻡ ﺍﻟﺩﻭﺍﺌﺭ ﺍﻟﻔﺭﻋﻴﺔ‬ ‫‪٢-٥‬‬


‫ﻴﺘﻡ ﻋﻤل ﺍﻟﺘﺼﻤﻴﻡ ﻋﻠﻲ ﺨﻁﻭﺍﺕ ﻜﻤﺎ ﻴﻠﻲ ‪:‬‬
‫ﺤﺴﺎﺏ ﺃﻗﺼﻰ ﺘﻴﺎﺭ ﻴﻨﺘﻅﺭ ﻤﺭﻭﺭﻩ ﻓﻰ ﺍﻟﺩﺍﺌﺭﺓ ﻟﺘﻐﺫﻴﺔ ﺃﺤﻤﺎﻟﻬﺎ ‪ ،‬ﻤﻊ ﺃﺨـﺫ ﺘﻁـﻭﺭ‬ ‫)ﺃ(‬
‫ﺍﻷﺤﻤﺎل )ﺇﻥ ﻭﺠﺩ( ﻓﻰ ﺍﻻﻋﺘﺒﺎﺭ ‪.‬‬
‫)ﺏ( ﺘﺤﺩﻴﺩ ﻤﻌﺎﻤﻼﺕ ﺘﺼﺤﻴﺢ ﺴﻌﺔ ﺤﻤل ﻤﻭﺼﻼﺕ ﺍﻟﺩﺍﺌﺭﺓ ﻟﻠﺘﻴﺎﺭ ﻁﺒﻘﺎ ﻟﻁﺭﻴﻘﺔ ﺘﺭﻜﻴﺏ‬
‫ﻜﺎﺒﻼﺕ ﺍﻟﺩﺍﺌﺭﺓ ﻭﻟﻅﺭﻭﻑ ﺘﺸﻐﻴﻠﻬﺎ ﻓﻰ ﺍﻟﻭﺴﻁ ﺍﻟﻤﺤﻴﻁ ﺒﻬﺎ ‪.‬‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫)ﺕ( ﺤﺴﺎﺏ ﺍﻟﺴﻌﺔ ﺍﻟﻤﻁﻠﻭﺒﺔ ﻟﺤﻤل ﺍﻟﺘﻴﺎﺭ ﻓﻰ ﻤﻭﺼﻼﺕ ﺍﻟﺩﺍﺌﺭﺓ ﺒﻌﺩ ﺘﺼﺤﻴﺤﻬﺎ ﻟﺘﻘﺎﺒـل‬
‫ﺍﻻﺸﺘﺭﺍﻁﺎﺕ ﺍﻟﻭﺍﺭﺩﺓ ﻓﻰ ﺠﺩﺍﻭل ﺍﻟﺸﺭﻜﺔ ﺍﻟﻤﺼﻨﻌﺔ ﻟﻠﻜﺎﺒﻼﺕ ‪ ،‬ﻭﺒﺎﻟﺘـﺎﻟﻲ ﺍﺨﺘﻴـﺎﺭ‬
‫ﻤﻘﻁﻊ ﺍﻟﻤﻭﺼﻼﺕ ﻭﺘﺤﺩﻴﺩ ﻤﻌﺎﻤﻼﺘﻬﺎ ‪ ،‬ﻤﻊ ﺇﻤﻜﺎﻥ ﺯﻴﺎﺩﺓ ﻤﺴﺎﺤﺔ ﻤﻘﻁﻊ ﻤﻭﺼﻼﺕ‬
‫ﺍﻟﻜﺎﺒل ﺘﻭﻓﻴﺭﺍ ﻟﺠﺯﺀ ﻤﻥ ﻓﻘﺩ ﺍﻟﻁﺎﻗﺔ ﻓﻰ ﻤﻘﺎﻭﻤﺔ ﺍﻟﻜﺎﺒل ‪.‬‬
‫)ﺙ( ﺤﺴﺎﺏ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﻋﻨﺩ ﻤﺨﺭﺝ ﺍﻟﻠﻭﺤﺔ ﺍﻟﺘﻰ ﺘﻐﺫﻱ ﺍﻟﺩﺍﺌﺭﺓ ‪ ،‬ﻭﺒﺎﻟﺘﺎﻟﻰ ﻴﺘﻡ ﺤﺴـﺎﺏ‬
‫ﺘﻴﺎﺭﻱ ﻀﺒﻁ ﻨﺒﺎﺌﻁ ﺍﻟﻭﻗﺎﻴﺔ ﻀﺩ ﺯﻴﺎﺩﺓ ﺍﻟﺤﻤل ﻭﻀﺩ ﻗﺼﺭ ﺍﻟﺩﺍﺌﺭﺓ ‪ ،‬ﻤﻊ ﻤﺭﺍﺠﻌـﺔ‬
‫ﺇﻤﻜﺎﻨﻴﺔ ﺼﻤﻭﺩ ﻜل ﻤﻥ ﺍﻟﻜﺎﺒل ﻭﻨﺒﻴﻁﺔ ﺍﻟﻭﻗﺎﻴﺔ ﻀﺩ ﻗﺼﺭ ﺍﻟـﺩﺍﺌﺭﺓ ﺨـﻼل ﺯﻤـﻥ‬
‫ﺍﻟﻘﻁﻊ ﻟﻠﻨﺒﻴﻁﺔ ‪ ،‬ﻭﻓﻰ ﺤﺎﻟﺔ ﻋﺩﻡ ﺘﻭﺍﻓﺭ ﺃﻱ ﻤﻥ ﺘﻠﻙ ﺍﻹﻤﻜﺎﻨﻴـﺎﺕ‪ ،‬ﻴﺘﺤـﺘﻡ ﻋﻠـﻰ‬
‫ﺍﻟﻤﺼﻤﻡ ﺇﻤﺎ ﺯﻴﺎﺩﺓ ﻤﺴﺎﺤﺔ ﻤﻘﻁﻊ ﻤﻭﺼﻼﺕ ﺍﻟﺩﺍﺌﺭﺓ ﺃﻭ ﺍﺴﺘﺒﺩﺍل ﻨﺒﻴﻁـﺔ ﺍﻟﻭﻗﺎﻴـﺔ‬
‫ﺒﺄﺨﺭﻯ ﺘﻜﻭﻥ ﺫﺍﺕ ﺴﺭﻋﺔ ﻗﻁﻊ ﺃﻜﺒﺭ ‪ ،‬ﺃﻭ ﺍﺨﺘﻴﺎﺭ ﻨﺒﻴﻁﺔ ﺍﻟﻘﻁﻊ ﺒﺤﻴﺙ ﺘﻜﻭﻥ ﻤـﻥ‬
‫ﺍﻟﻨﻭﻉ ﺍﻟﺫﻯ ﻴﺅﺩﻯ ﺇﻟﻲ ﺍﻟﺤﺩ ﻤﻥ ﺘﻴﺎﺭ ﺍﻟﻘﻁﻊ )ﻤﺜل ﺍﻟﻤﺼﺎﻫﺭ( ‪.‬‬
‫)ﺠ( ﺤﺴﺎﺏ ﻫﺒﻭﻁ ﺍﻟﺠﻬﺩ ﻓﻰ ﺍﻟﺩﺍﺌﺭﺓ ﻋﻨﺩ ﺫﺭﻭﺓ ﺍﻷﺤﻤﺎل ‪ ،‬ﻭﻤﺠﻤﻭﻉ ﺍﻟﻬﺒـﻭﻁ ﺍﻟﻜﻠـﻰ‬
‫ﻟﻠﺠﻬﺩ ﻤﻥ ﻨﻘﻁﺔ ﺘﻐﺫﻴﺔ ﺍﻟﻤﺒﻨﻲ ﺤﺘﻰ ﺃﺒﻌﺩ ﺤﻤل ﻓﻲ ﺍﻟﻤﺒﻨﻲ ‪ ،‬ﻤﻊ ﻋﻤـل ﺍﻟﺘﻌـﺩﻴل‬
‫ﻓﻲ ﻤﻘﻁﻊ ﻤﻭﺼﻼﺕ ﺍﻟﺩﺍﺌﺭﺓ ‪ ،‬ﺃﻭ ﺍﻟﺩﻭﺍﺌﺭ ﺇﻥ ﻟﺯﻡ ‪ ،‬ﺒﻐـﺭﺽ ﺍﻻﻟﺘـﺯﺍﻡ ﺒﺎﻟﺤـﺩ‬
‫ﺍﻷﻗﺼﻲ ﺍﻟﻤﺴﻤﻭﺡ ﺒﻪ ﻟﻬﺒﻭﻁ ﺍﻟﺠﻬﺩ ‪.‬‬

‫‪ ١-٢-٥‬ﺤﺴﺎﺏ ﺃﻗﺼﻲ ﻗﻴﻤﺔ ﻟﻠﺘﻴﺎﺭ ﺍﻟﺫﻯ ﻴﻨﺘﻅﺭ ﻤﺭﻭﺭﻩ ﻓﻰ ﺍﻟﺩﺍﺌﺭﺓ‬


‫ﺒﻌﺩ ﺘﺤﺩﻴﺩ ﺍﻷﺤﻤﺎل ﺍﻟﺘﻲ ﻴﻨﺘﻅﺭ ﺘﻐﺫﻴﺘﻬﺎ ﻤﻥ ﺍﻟﺩﺍﺌﺭﺓ ﻴﺘﻡ ﺤﺴـﺎﺏ ﻗﻴﻤـﺔ ﺍﻟﺘﻴـﺎﺭ ﺍﻟﻤﻘـﻨﻥ‬
‫ﺒﺎﻷﻤﺒﻴﺭ ﻟﻜل ﻤﻥ ﺍﻷﺤﻤﺎل ﻜﻤﺎ ﻴﻠﻰ ‪:‬‬
‫)‪ (١‬ﺒﺎﻟﻨﺴﺒﺔ ﻟﻠﺤﻤل ﺫﻯ ﺍﻟﻁﻭﺭ ﺍﻟﻭﺍﺤﺩ‬
‫ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﻘﻨﻥ = )ﻗﻴﻤﺔ ﺩﺨل ﺍﻟﺤﻤل ﺒﺎﻟﻭﺍﺕ( ‪) /‬ﺍﻟﺠﻬﺩ ﺍﻟﻤﻘﻨﻥ ﻟﻠﻁـﻭﺭ × ﻤﻌﺎﻤـل‬
‫ﺍﻟﻘﺩﺭﺓ ﻟﻠﺤﻤل( ‪.‬‬
‫ﻭﺘﺅﺨﺫ ﻗﻴﻤﺔ ﺩﺨل ﺍﻷﺤﻤﺎل ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﺒـﺎﻟﻭﺍﺕ ) ﻜﻤـﺎ ﻓـﻲ ﺤـﺎﻻﺕ ﺍﻟﺴـﺨﺎﻥ‬
‫ﻭﻤﺼﺎﺒﻴﺢ ﺍﻻﻨﺎﺭﺓ ﻭﺨﻼﻓﻪ ( ﻤﻥ ﻭﺍﻗﻊ ﺒﻁﺎﻗﺔ ﻤﻘﻨﻨﺎﺕ ﺍﻟﺤﻤل ‪.‬‬
‫)‪ (٢‬ﺒﺎﻟﻨﺴﺒﺔ ﻟﻠﺤﻤل ﺫﻯ ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ‬
‫ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﻘﻨﻥ = )ﻗﻴﻤﺔ ﺩﺨل ﺍﻟﺤﻤل ﺒﺎﻟﻭﺍﺕ( ‪ × ١.٧٣٢) /‬ﺍﻟﺠﻬﺩ ﺍﻟﻤﻘﻨﻥ × ﻤﻌﺎﻤل‬
‫ﺍﻟﻘﺩﺭﺓ ﻟﻠﺤﻤل( ﻭﻓﻲ ﺤﺎﻟﺔ ﺃﺤﻤﺎل ﺍﻟﻤﺤﺭﻜﺎﺕ ﺘﺤﺴﺏ ﻗﻴﻤﺔ ﺩﺨل ﺍﻟﺤﻤل ﺒـﺎﻟﻭﺍﺕ =‬
‫)ﻗﻴﻤﺔ ﺍﻟﺨﺭﺝ ﺒﺎﻟﻭﺍﺕ ﺍﻟﻤﺜﺒﺘﺔ ﻓﻰ ﺒﻁﺎﻗﺔ ﺍﻟﺒﻴﺎﻨﺎﺕ( ‪) /‬ﻜﻔـﺎﺀﺓ ﺍﻟﺤﻤـل ) ‪ (η‬ﻋﻨـﺩ‬
‫ﺘﺸﻐﻴﻠﻪ ﺒﻜﺎﻤل ﻗﺩﺭﺘﻪ(‪.‬‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻭﻋﻨﺩﻤﺎ ﻴﻜﻭﻥ ﺍﻟﺤﻤل ﻤﺘﻭﺍﺯﻨﺎ ﻋﻠﻰ ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ‪ ،‬ﻓﺈﻥ ﺘﻴﺎﺭ ﻤﻭﺼـل ﺍﻟﺘﻌـﺎﺩل‬
‫ﻴﻜﻭﻥ ﺼﻔﺭﺍ‪.‬‬
‫)‪ (٣‬ﺒﺎﻟﻨﺴﺒﺔ ﻟﻤﺠﻤﻭﻋﺔ ﺍﻷﺤﻤﺎل ﺍﻟﻤﻐﺫﺍﺓ ﻤﻥ ﺩﺍﺌﺭﺓ ﻭﺍﺤﺩﺓ‬
‫ﻨﻅﺭﺍ ﻷﻥ ﻤﻨﺤﻨﻰ ﺍﻟﺤﻤل ﻴﺨﺘﻠﻑ ﻤﻥ ﺤﻤل ﺇﻟﻰ ﺁﺨﺭ ﻓﺈﻥ ﻗﻴﻤﺔ ﺍﻟﺤﻤـل ﺍﻷﻗﺼـﻰ‬
‫ﺍﻟﻤﻐـﺫﻯ ﻤﻥ ﺍﻟﺩﺍﺌﺭﺓ ﻻ ﺘﺴﺎﻭﻯ ﺍﻟﻤﺠﻤﻭﻉ ﺍﻟﺠﺒﺭﻯ ﻟﻘﻴﻡ ﺍﻟﺤﻤل ﺍﻷﻗﺼﻰ ﻟﻜل ﺤﻤل‬
‫ﻋﻠﻰ ﺤﺩﺓ ﺒل ﺘﻜﻭﻥ ﺃﻗل ﻤﻥ ﺫﻟﻙ ﺍﻟﻤﺠﻤﻭﻉ ﺍﻟﺠﺒـﺭﻯ ‪ ،‬ﺤﻴــﺙ ﺘﺴـﺎﻭﻯ ﺫﻟـﻙ‬
‫ﺍﻟﻤﺠﻤﻭﻉ ﺍﻟﺠﺒﺭﻯ ﻤﻘﺴﻭﻤﺎ ﻋﻠﻰ ﻤﻌﺎﻤل ﺍﻟﺘﺒﺎﻴﻥ ‪ ،‬ﻭﻴﻤﻜﻥ ﺤﺴـﺎﺏ ﻗﻴﻤـﺔ ﺍﻟﺤﻤـل‬
‫ﺍﻷﻗﺼﻰ ﻓﻰ ﺤﺎﻟﺔ ﺘﻌﺩﺩ ﺍﻷﺤﻤﺎل ﻁﺒﻘﺎ ﻟﻠﻭﺍﺭﺩ ﻓﻰ ﺍﻟﺠﺩﻭل )‪ (٢-٣‬ﻓﻰ ﻫﺫﺍ ﺍﻟﻤﺠﻠﺩ‪.‬‬
‫ﻭﺒﻌﺩ ﺘﺤﺩﻴﺩ ﺍﻟﻘﻴﻤﺔ ﺍﻟﻘﺼﻭﻯ ﻟﻠﺤﻤل ﺍﻟﻤﻐﺫﻯ ﻤﻥ ﺍﻟﺩﺍﺌﺭﺓ ﺘﺤﺴﺏ ﺍﻟﻘﻴﻤـﺔ ﺍﻟﻘﺼـﻭﻯ‬
‫ﻟﻠﺘﻴﺎﺭ ﺍﻟﺫﻯ ﻴﻨﺘﻅﺭ ﺃﻥ ﻴﻤﺭ ﻓﻰ ﺍﻟﺩﺍﺌﺭﺓ ‪ ،‬ﻜﻤﺎ ﻭﺭﺩ ﻓﻰ ﺍﻟﺒﻨﺩﻴﻥ ‪ ٢ ، ١‬ﺒﻌﺎﻟﻴﻪ‪.‬‬
‫ﻭﻓﻰ ﺍﻟﺤﺎﻻﺕ ﺍﻟﺘﻰ ﻴﺘﻜﺭﺭ ﻓﻴﻬﺎ ﺘﺸﻐﻴل ﺍﻷﺤﻤﺎل ﻜﻠﻬﺎ ﻓﻰ ﻨﻔـﺱ ﺍﻟﻭﻗـﺕ ﺒﺤﻤﻠﻬـﺎ‬
‫ﺍﻟﻤﻘﻨﻥ ﻴﺠﺏ ﺘﺼﻤﻴﻡ ﺍﻟﺩﺍﺌﺭﺓ ﻋﻠﻰ ﺃﺴﺎﺱ ﺍﻟﻤﺠﻤﻭﻉ ﺍﻟﻜﻠﻰ ﻟﻠﻘﺩﺭﺍﺕ ﺍﻟﻤﻘﻨﻨﺔ ﻟﻸﺤﻤﺎل‬
‫ﻜﻠﻬﺎ ﺒﺩﻭﻥ ﺍﻋﺘﺒﺎﺭ ﻤﻌﺎﻤل ﺘﺒﺎﻴﻥ ‪.‬‬
‫)‪ (٤‬ﺒﺎﻟﻨﺴﺒﺔ ﻟﻤﺠﻤﻭﻋﺔ ﺍﻷﺤﻤﺎل ﻏﻴﺭ ﺍﻟﻤﺘﻭﺍﺯﻨﺔ ﻋﻠﻰ ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ‬
‫ﻭﺫﻟﻙ ﻜﻤﺎ ﻓﻰ ﺤﺎﻻﺕ ﺘﻐﺫﻴﺔ ﺒﻌﺽ ﺍﻷﺤﻤﺎل ﺫﺍﺕ ﺍﻷﻁـﻭﺍﺭ ﺍﻟﺜﻼﺜـﺔ ﺍﻟﻤﺘﻭﺍﺯﻨـﺔ‬
‫ﺒﺎﻹﻀﺎﻓﺔ ﺇﻟﻰ ﺃﺤﻤﺎل ﺫﺍﺕ ﺍﻟﻁﻭﺭ ﺍﻟﻭﺍﺤﺩ ﺘﻭﺯﻉ ﻋﻠﻰ ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ ﻤﻊ ﻤﺤﺎﻭﻟﺔ‬
‫ﺘﺴﺎﻭﻯ ﺍﻟﺘﺤﻤﻴل ﻋﻠﻰ ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ ﻗﺩﺭ ﺍﻹﻤﻜﺎﻥ ‪ ،‬ﻭﻟﻜﻥ ﻗﺩ ﻻ ﻴﺘﻡ ﺍﻟﻭﺼـﻭل‬
‫ﺇﻟﻰ ﺘﺤﻘﻴﻕ ﺍﻟﺘﻭﺍﺯﻥ ﺍﻟﻜﺎﻤل ‪.‬‬
‫ﻭﻫﻨﺎ ﻴﺠﺏ ﺤﺴﺎﺏ ﻗﻴﻤﺔ ﺍﻟﻘﺩﺭﺓ ﻏﻴﺭ ﺍﻟﻔﻌﺎﻟﺔ )‪ (Q‬ﻟﻜـل ﺤﻤـل ﺒﻭﺤـﺩﺓ ﻙ ﻓـﺎﺭ‬
‫)‪ (kVAR‬ﺒﺎﺴﺘﻌﻤﺎل ﺍﻟﻤﻌﺎﺩﻟﺔ )‪: (١-٥‬‬
‫‪Q (in kVAR) = P (in kW) × tanϕ‬‬
‫)‪(5-1‬‬
‫) ‪= P [1 − ( power factor ) 2 ] / ( power factor‬‬

‫ﺃﻭﻻ‪ :‬ﻴﻤﻜﻥ ﺤﺴﺎﺏ ﺘﻴﺎﺭ ﻜل ﻤﻥ ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ ﻭﺘﻴﺎﺭ ﻤﻭﺼل ﺍﻟﺘﻌﺎﺩل ﻋﻨﺩ ﻤﺼﺩﺭ‬
‫ﺍﻟﺘﻐﺫﻴﺔ ﺒﺼﻔﺔ ﺘﻘﺭﻴﺒﻴﺔ ﻜﻤﺎ ﻴﻠﻰ‪:‬‬
‫ﻨﻔﺭﺽ ﺒﺼﻔﺔ ﻤﺒﺩﺌﻴﺔ ﺃﻥ ﺠﻬﻭﺩ ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ ﻤﺘﻭﺍﺯﻨﺔ ‪ ،‬ﺃﻯ ﺃﻥ ﺍﻟﻘﻴﻡ ﺍﻟﻌﺩﺩﻴﺔ‬ ‫)ﺃ(‬
‫ﻟﻜل ﻤﻨﻬﺎ ‪ ٢٢٠‬ﻓﻭﻟﺕ ﻭﺃﻥ ﻤﺘﺠﻬﺎﺘﻬﺎ ﺘﺘﺄﺨﺭ ﻜل ﻋـﻥ ﺍﻵﺨـﺭ ﺒﺯﺍﻭﻴـﺔ ‪١٢٠‬‬
‫ﺩﺭﺠﺔ ‪.‬‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫)ﺏ( ﻭﺒﺎﻟﺘﺎﻟﻰ ﻨﺤﺴﺏ ﻤﺭﻜﺒﺘﻰ ﺘﻴﺎﺭ ﻜل ﻁﻭﺭ ﻜﻤﺎ ﻴﻠﻰ ‪:‬‬


‫ﺍﻟﻤﺭﻜﺒﺔ ﺍﻟﻔﻌﺎﻟﺔ ﻟﺘﻴـﺎﺭ ﺍﻟﻁـﻭﺭ "‪ (Ir1) "١‬ﺒـﺎﻷﻤﺒﻴﺭ = ‪) × ١٠٠٠‬ﻤﺠﻤـﻭﻉ‬
‫ﺍﻟﻘﺩﺭﺍﺕ ﺍﻟﻔﻌﺎﻟﺔ )‪ (P in kW‬ﺍﻟﻤﻐﺫﺍﺓ ﻤﻥ ﺍﻟﻁﻭﺭ "‪٢٢٠ ÷ ("١‬‬
‫ﻭﺘﺅﺨﺫ ﻫﺫﻩ ﺍﻟﻤﺭﻜﺒﺔ ﻓﻰ ﻨﻔﺱ ﺇﺘﺠﺎﻩ ﻤﺘﺠﻪ ﺠﻬﺩ ﺍﻟﻁﻭﺭ "‪. "١‬‬
‫ﻭﺍﻟﻤﺭﻜﺒﺔ ﻏﻴﺭ ﺍﻟﻔﻌﺎﻟﺔ ﻟﺘﻴـﺎﺭ ﺍﻟﻁـﻭﺭ "‪ (Iimg1) "١‬ﺒـﺎﻷﻤﺒﻴﺭ = ‪× ١٠٠٠‬‬
‫)ﻤﺠﻤــﻭﻉ ﺍﻟﻘــﺩﺭﺍﺕ ﻏﻴــﺭ ﺍﻟﻔﻌﺎﻟــﺔ )‪ (Q in kVAR‬ﺍﻟﻤﻐـﺫﺍﺓ ﻤـﻥ‬
‫ﺍﻟﻁﻭﺭ "‪٢٢٠ ÷ ("١‬‬
‫ﻭﺘﺅﺨﺫ ﻫﺫﻩ ﺍﻟﻤﺭﻜﺒﺔ ﻤﺘﺄﺨﺭﺓ ﺒﺯﺍﻭﻴﺔ ‪ ٩٠‬ﺩﺭﺠﺔ ﻋﻥ ﻤﺘﺠﻪ ﺠﻬﺩ ﺍﻟﻁﻭﺭ "‪. "١‬‬
‫ﻭﺘﺘﻜﺭﺭ ﻫﺫﻩ ﺍﻟﺤﺴﺎﺒﺎﺕ ﻟﻠﻁﻭﺭﻴﻥ "‪. "٣" ، "٢‬‬
‫)ﺕ( ﺘﻜﻭﻥ ﺍﻟﻘﻴﻤﺔ ﺍﻟﻌﺩﺩﻴﺔ ﻟﺘﻴﺎﺭ ﺍﻟﻁﻭﺭ "‪[(I r 1 ) 2 + (I img 1 ) 2 ] = "١‬‬

‫ﻭﺘﺘﻜﺭﺭ ﻫﺫﻩ ﺍﻟﺤﺴﺎﺒﺎﺕ ﻟﻠﻁﻭﺭﻴﻥ "‪. "٣" ، "٢‬‬


‫)ﺙ( ﺘﺤﺴﺏ ﺍﻟﻤﺭﻜﺒﺔ ﺍﻟﺤﻘﻴﻘﻴﺔ )‪ (Inr‬ﻭﺍﻟﻤﺭﻜﺒﺔ ﺍﻟﺘﺨﻴﻠﻴﺔ )‪ (Img‬ﻟﺘﻴﺎﺭ ﻤﻭﺼل ﺍﻟﺘﻌﺎﺩل ﻭﻗﻴﻤﺘـﻪ‬
‫ﺍﻟﻌﺩﺩﻴﺔ )‪ ،(In‬ﺃﻨﻅﺭ ﺸﻜل )‪ ،(١-٥‬ﻤﻥ ﺍﻟﻤﻌﺎﺩﻟﺔ )‪ (٢-٥‬ﻜﻤﺎ ﻴﻠﻰ‪:‬‬

‫‪I‬‬ ‫‪=I‬‬ ‫‪− 0.5 (I‬‬ ‫‪+I‬‬ ‫‪) − 0.866 (I‬‬ ‫‪−I‬‬ ‫)‬
‫‪nr‬‬ ‫‪r1‬‬ ‫‪r2‬‬ ‫‪r3‬‬ ‫‪img 2 img 3‬‬
‫‪I‬‬ ‫‪=I‬‬ ‫‪− 0.5 (I‬‬ ‫‪+I‬‬ ‫‪) + 0.866 (I‬‬ ‫) ‪−I‬‬ ‫)‪(5-2‬‬
‫‪ng‬‬ ‫‪img 1‬‬ ‫‪img 2‬‬ ‫‪img 3‬‬ ‫‪r2‬‬ ‫‪r3‬‬
‫] ‪I n = [(I r 1) 2 + (I img 1 ) 2‬‬

‫ﺜﺎﻨﻴﺎ‪ :‬ﻴﻤﻜﻥ ﺤﺴﺎﺏ ﻗﻴﻤﺔ ﺘﻴﺎﺭ ﻜل ﻤﻥ ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﻴﺔ ﻭﺘﻴﺎﺭ ﻤﻭﺼل ﺍﻟﺘﻌﺎﺩل ﻋﻨـﺩ‬
‫ﻨﻘﻁ ﺘﻐﺫﻴﺔ ﺍﻷﺤﻤﺎل ﺍﻟﻤﺨﺘﻠﻔﺔ ﻤﻥ ﺩﺍﺌﺭﺓ ﺍﻟﺘﻭﺯﻴﻊ ﺒﻤﻌﻠﻭﻤﻴﺔ ﺘﺭﺘﻴﺏ ﺘﻐﺫﻴـﺔ ﻫـﺫﻩ‬
‫ﺍﻷﺤﻤﺎل ﻤﻥ ﺍﻟﺩﺍﺌﺭﺓ‪ ،‬ﻭﺫﻟﻙ ﺒﺘﻜﺭﺍﺭ ﺍﻟﺤﺴﺎﺒﺎﺕ ﻋﺎﻟﻴﻪ ﻓﻰ ﺍﻟﺒﻨﺩ ﺃﻭﻻ‪ ،‬ﻤﻊ ﺍﻋﺘﺒﺎﺭ‬
‫ﺍﻷﺤﻤﺎل ﺍﻟﻤﻐﺫﺍﻩ ﺒﻌﺩ ﻜل ﻨﻘﻁﺔ ﻓﻘﻁ ‪ ،‬ﺃﻯ ﺍﻷﺤﻤﺎل ﺍﻟﺘﻰ ﺘﻤـﺭ ﺘﻴﺎﺭﺍﺘﻬـﺎ ﻓـﻰ‬
‫ﻤﻭﺼﻼﺕ ﺍﻟﺩﺍﺌﺭﺓ ﻤﻥ ﺍﻟﻤﺼﺩﺭ ﺤﺘﻰ ﺍﻟﻨﻘﻁﺔ ﺘﺤﺕ ﺍﻻﻋﺘﺒﺎﺭ‪.‬‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫‪V3‬‬
‫‪Iimg3‬‬
‫‪I3‬‬

‫‪Ir3‬‬

‫‪Inr‬‬ ‫‪Ir1‬‬
‫‪Ing‬‬ ‫‪V1‬‬
‫‪In‬‬
‫‪I2‬‬ ‫‪Iimg1‬‬

‫‪I1‬‬
‫‪Iimg2‬‬ ‫‪Ir2‬‬

‫‪V2‬‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(١-٥‬ﻤﺭﻜﺒﺎﺕ ﺘﻴﺎﺭﺍﺕ ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ ﻭﻤﺭﻜﺒﺘﺎ ﺘﻴﺎﺭ ﻤﻭﺼل ﺍﻟﺘﻌﺎﺩل‬

‫ﻭﻋﻨﺩﻤﺎ ﻴﻜﻭﻥ ﻋﺩﻡ ﺍﻟﺘﻭﺍﺯﻥ ﻋﻠﻰ ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ ﻀﺌﻴﻼ ‪ ،‬ﻓـﻴﻤﻜﻥ ﺍﺴـﺘﻌﻤﺎل‬ ‫ﺜﺎﻟﺜﺎ‪:‬‬
‫ﻁﺭﻴﻘﺔ ﺃﻜﺜﺭ ﺘﻘﺭﻴﺒﺎ ﻟﺤﺴﺎﺏ ﻤﺘﻭﺴﻁ ﺘﻴﺎﺭ ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ ) ﻭﺫﻟﻙ ﺒﻔـﺭﺽ ﺃﻥ‬
‫ﺃﺤﻤﺎل ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ ﻤﺘﺴﺎﻭﻴﺔ ﻭﺘﺴﺎﻭﻯ ﻤﺘﻭﺴـﻁ ﺍﻷﺤﻤـﺎل ﺍﻟﻔﻌﻠﻴـﺔ ﻋﻠـﻰ‬
‫ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ(‪ ،‬ﺃﻯ ﺃﻥ ﺍﻟﻘﻴﻤﺔ ﺍﻟﻤﺘﻭﺴﻁﺔ ﻟﻠﻘﺩﺭﺓ ﺍﻟﻔﻌﺎﻟﺔ ﻟﻜل ﻁـﻭﺭ ﻴﻤﻜـﻥ‬
‫ﺤﺴﺎﺒﻬﺎ ﻤﻥ ﺍﻟﻤﻌﺎﺩﻟﺔ )‪(٣-٥‬‬
‫‪Pav = ( P1 + P2 + P3 ) ÷ 3‬‬ ‫‪kW‬‬ ‫)‪(5-3‬‬
‫ﺍﻟﻘﻴﻤﺔ ﺍﻟﻤﺘﻭﺴﻁﺔ ﻟﻠﻘﺩﺭﺓ ﻏﻴﺭ ﺍﻟﻔﻌﺎﻟﺔ ﻟﻜل ﻁﻭﺭ ﻴﻤﻜﻥ ﺤﺴﺎﺒﻬﺎ ﻤـﻥ ﺍﻟﻤﻌﺎﺩﻟـﺔ‬
‫)‪(٤-٥‬‬
‫‪Qav = (Q1 + Q2 + Q3 ) ÷ 3‬‬ ‫‪kVAR‬‬ ‫)‪(5-4‬‬
‫ﻭﺘﻜﻭﻥ ﺍﻟﻘﻴﻤﺔ ﺍﻟﻌﺩﺩﻴﺔ ﺍﻟﻤﺘﻭﺴﻁﺔ ﻟﺘﻴﺎﺭ ﺍﻟﻁﻭﺭ ﻜﻤﺎ ﻓﻲ ﺍﻟﻤﻌﺎﺩﻟﺔ )‪(٥-٥‬‬

‫‪I av = 1000 × [ ( Pav ) 2 + (Qav ) 2 ÷ 220‬‬ ‫‪A‬‬ ‫)‪(5-5‬‬

‫ﻭﻴﻤﻜﻥ ﻓﻰ ﻫﺫﻩ ﺍﻟﻁﺭﻴﻘﺔ ﺍﻟﺘﻘﺭﻴﺒﻴﺔ ﺇﻫﻤﺎل ﺘﻴﺎﺭ ﻤﻭﺼل ﺍﻟﺘﻌـﺎﺩل ﺤﻴـﺙ ﺃﻨﻨـﺎ‬
‫ﻓﺭﻀﻨﺎ ﺃﻥ ﺍﻷﺤﻤﺎل ﻤﺘﻭﺍﺯﻨﺔ ‪.‬‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫‪ ١-١-٢-٥‬ﻤﺜﺎل ﺘﻭﻀﻴﺤﻰ‬
‫ﺍﻟﻤﻁﻠﻭﺏ ﺤﺴﺎﺏ ﺍﻟﻘﻴﻤﺔ ﺍﻟﻘﺼﻭﻯ ﻟﺘﻴﺎﺭﺍﺕ ﺍﻟﺩﻭﺍﺌﺭ ﺍﻟﻔﺭﻋﻴﺔ ﺍﻟﻨﻬﺎﺌﻴﺔ ﺍﻟﺘﻰ ﺘﻘـﻭﻡ ﺒﺘﻐﺫﻴـﺔ‬
‫ﺍﻷﺤﻤﺎل ﺍﻟﻤﺴﺘﻘﻠﺔ ﻓﻰ ﻤﻁﺒﺦ ﺃﺤﺩ ﺍﻟﻔﻨﺎﺩﻕ ‪ ،‬ﻭﻜﺫﺍ ﺍﻟﻘﻴﻤﺔ ﺍﻟﻘﺼﻭﻯ ﻟﺘﻴﺎﺭ ﺍﻟﺩﺍﺌﺭﺓ ﺍﻟﻔﺭﻋﻴـﺔ‬
‫ﺍﻟﺘﻰ ﺘﻐـﺫﻯ ﺍﻟﻤﻁﺒﺦ ﺒﺄﻜﻤـﻠﻪ ﺇﺫﺍ ﻜﺎﻥ ﺠﻬﺩ ﻁﻭﺭ ﺍﻟﺘﻐﺫﻴﺔ ﻫﻭ ‪ ٢٢٠‬ﻓﻭﻟﺕ ﻋﻠﻤـﺎ ﺒـﺄﻥ‬
‫ﺍﻟﻤﻁﺒﺦ ﻴﺤﺘﻭﻯ ﻋﻠﻰ ﺍﻷﺤﻤﺎل ﺍﻟﺘﺎﻟﻴﺔ ‪:‬‬
‫‪ -‬ﻋﺩﺩ ‪ ٣‬ﻓﺭﻥ ﻜﻬﺭﺒﺎﺌﻰ ﺜﻼﺜﻰ ﺍﻷﻁﻭﺍﺭ ﺒﻘﺩﺭﺓ ‪ ١٢‬ﻙ ﻭﺍﺕ ﻟﻜل ﻤﻨﻬﺎ‪.‬‬
‫‪ -‬ﻋﺩﺩ ‪ ٣‬ﺜﻼﺠﺔ ﺜﻼﺜﻴﺔ ﺍﻷﻁﻭﺍﺭ ﺒﻘﺩﺭﺓ ‪ ٣‬ﻙ ﻭﺍﺕ ﻭﻤﻌﺎﻤل ﻗﺩﺭﺓ ‪ ٠.٨‬ﻤﺘﺄﺨﺭ‪.‬‬
‫‪ -‬ﻋﺩﺩ ‪ ٢‬ﺴﺨﺎﻥ ﻤﻴﺎﺓ ﺫﻯ ﻁﻭﺭ ﻭﺍﺤﺩ ﺒﻘﺩﺭﺓ ‪ ٢‬ﻙ ﻭﺍﺕ‪.‬‬
‫‪ -‬ﻋﺩﺩ ‪ ٢‬ﻤﻔﺭﻤﺔ ﻟﺤﻭﻡ ﺫﺍﺕ ﻁﻭﺭ ﻭﺍﺤﺩ ﺒﻘﺩﺭﺓ ‪ ٢‬ﻙ ﻭﺍﺕ ﻭﻤﻌﺎﻤل ﻗﺩﺭﺓ ‪ ٠.٧‬ﻤﺘﺄﺨﺭ‪.‬‬
‫‪ -‬ﻋﺩﺩ ‪ ٢‬ﺁﻟﺔ ﻋﺠﻴﻥ ﺜﻼﺜﻴﺔ ﺍﻷﻁﻭﺍﺭ ﺒﻘﺩﺭﺓ ‪ ٣‬ﻙ ﻭﺍﺕ ﻭﻤﻌﺎﻤل ﻗﺩﺭﺓ ‪ ٠.٨‬ﻤﺘﺄﺨﺭ‪.‬‬
‫‪ -‬ﻋﺩﺩ ‪ ٢‬ﺁﻟﺔ ﺘﺤﻀﻴﺭ ﺍﻟﺨﻀﺭﻭﺍﺕ ﺫﺍﺕ ﻁﻭﺭ ﻭﺍﺤــﺩ ﺒﻘـﺩﺭﺓ ‪ ١‬ﻙ ﻭﺍﺕ ﻭﻤﻌﺎﻤـل‬
‫ﻗﺩﺭﺓ ‪ ٠.٧‬ﻤﺘﺄﺨﺭ‪.‬‬
‫‪ -‬ﻋﺩﺩ ‪ ٢٠٠‬ﻤﺼﺒﺎﺡ ﻓﻠﻭﺭﻯ ﻗﺩﺭﺓ ‪ ١٨‬ﻭﺍﺕ ﻤﺯﻭﺩ ﺒﺒـﺎﺩﺉ ﺇﻨـﺎﺭﺓ ﺍﻟﻜﺘﺭﻭﻨـﻰ ‪ ٤‬ﻭﺍﺕ‬
‫ﻭﻤﻌﺎﻤل ﻗﺩﺭﺓ ﻤﺤﺴﻥ ﺇﻟﻰ ‪ ٠.٩٥‬ﻤﺘﺄﺨﺭ ‪.‬‬
‫ﻴﺘﻡ ﺘﻐﺫﻴﺔ ﻜل ﻤﻥ ﺍﻷﺠﻬﺯﺓ ﺍﻟﻭﺍﺭﺩﺓ ﻋﺎﻟﻴﻪ ﺒﺩﺍﺌﺭﺓ ﻓﺭﻋﻴﺔ ﻨﻬﺎﺌﻴﺔ‪ ،‬ﻜﻤﺎ ﻴﺘﻡ ﺘﻐﺫﻴـﺔ‬ ‫ﺍﻟﺤل‪:‬‬
‫ﻟﻭﺤﺔ ﺍﻹﻨﺎﺭﺓ ﺒﺩﺍﺌﺭﺓ ﺃﺨﺭﻯ‬
‫ﻭﻓﻴﻤﺎ ﻴﻠﻰ ﺤﺴﺎﺏ ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﻘﻨﻥ ﻓﻰ ﻜل ﻤﻥ ﻫﺫﻩ ﺍﻟﺩﻭﺍﺌﺭ ‪ ،‬ﻜﻤﺎ ﺘﺘﻀﻤﻥ ﺍﻟﺤﺴﺎﺒﺎﺕ ﺍﻟﺘﺎﻟﻴﺔ‬
‫ﺘﺤﺩﻴﺩ ﺍﻟﻘﻴﻤﺔ ﺍﻟﻘﺼﻭﻯ ﻟﺘﻴﺎﺭ ﺍﻟﺩﺍﺌﺭﺓ ﺍﻟﻔﺭﻋﻴﺔ ﺍﻟﺘﻰ ﺘﻐﺫﻯ ﺍﻟﻤﻁﺒﺦ ﺒﺄﻜﻤﻠﻪ‪:‬‬
‫‪ -‬ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﻘﻨﻥ ﻟﻠﻔﺭﻥ ﺍﻟﻭﺍﺤﺩ= ‪١٨.٢٣=(١ × ٣٨٠ × ١.٧٣٢ ) / ١٢٠٠٠‬ﺃﻤﺒﻴﺭ‬
‫‪ -‬ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﻘﻨﻥ ﻟﻠﺜﻼﺠﺔ ﺍﻟﻭﺍﺤﺩﺓ = ‪ ٥.٧ =(٠.٨ × ٣٨٠ × ١.٧٣٢) / ٣٠٠٠‬ﺃﻤﺒﻴﺭ‬
‫‪ -‬ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﻘﻨﻥ ﻟﻠﺴﺨﺎﻥ ﺍﻟﻭﺍﺤﺩ = ‪ ٩.٠٩ = (١ × ٢٢٠) / ٢٠٠٠‬ﺃﻤﺒﻴﺭ‬
‫‪ -‬ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﻘﻨﻥ ﻟﻤﻔﺭﻤﺔ ﺍﻟﻠﺤﻭﻡ ﺍﻟﻭﺍﺤﺩﺓ = ‪ ١٣ = ( ٠.٧ × ٢٢٠) / ٢٠٠٠‬ﺃﻤﺒﻴﺭ‬
‫‪ -‬ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﻘﻨﻥ ﻵﻟﺔ ﺍﻟﻌﺠﻴﻥ ﺍﻟﻭﺍﺤﺩﺓ= ‪٥.٧ =(٠.٨ × ٣٨٠ ×١.٧٣٢)/٣٠٠٠‬ﺃﻤﺒﻴﺭ‬
‫‪ -‬ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﻘﻨﻥ ﻵﻟﺔ ﺘﺤﻀﻴﺭ ﺍﻟﺨﻀﺭﻭﺍﺕ ﺍﻟﻭﺍﺤﺩﺓ=‪٦.٥=(٠.٧ ×٢٢٠)/١٠٠٠‬ﺃﻤﺒﻴﺭ‬
‫‪ -‬ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﻘﻨﻥ ﻟﻠﻭﺤـﺔ ﻹﻨـﺎﺭﺓ ﺒﺄﻜﻤﻠﻬـﺎ = )‪(٠.٩٥×٣٨٠×١.٧٣٢) / (٢٢×٢٠٠‬‬
‫=‪ ٧.٠٤‬ﺃﻤﺒﻴﺭ‬
‫‪ -‬ﻋﻠﻤﺎ ﺒﺄﻥ ﺍﻷﺤﻤﺎل ﺜﻼﺜﻴﺔ ﺍﻷﻁﻭﺍﺭ )ﺍﻷﻓﺭﺍﻥ ﻭﺍﻟﺜﻼﺠـﺎﺕ ﻭﺁﻟﺘـﻰ ﺍﻟﻌﺠـﻴﻥ ﻭﻟﻭﺤـﺔ‬
‫ﺍﻹﻨﺎﺭﺓ( ﺘﻐﺫﻯ ﻤﻥ ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ ﺒﺎﻟﺘﺴﺎﻭﻯ ﻓﻰ ﻗﻴﻡ ﺘﻴﺎﺭﺍﺕ ﺍﻷﻁـﻭﺍﺭ‪ ،‬ﻓـﻰ ﺤـﻴﻥ‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺘﻐﺫﻯ ﺍﻷﺤﻤﺎل ﺃﺤﺎﺩﻴﺔ ﺍﻟﻁﻭﺭ ﻤﻥ ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ ﻜﻤـﺎ ﻴﻠـﻰ ‪ ،‬ﺒﻐـﺭﺽ ﻤﺤﺎﻭﻟـﺔ‬
‫ﺍﻟﺘﺴﺎﻭﻯ )ﺒﻘﺩﺭ ﺍﻹﻤﻜﺎﻥ( ﺒﻴﻥ ﻤﺠﻤﻭﻉ ﻜل ﻤﻥ ﺍﻟﻘﺩﺭﺍﺕ ﺍﻟﻔﻌﺎﻟﺔ ﻭﻏﻴﺭ ﺍﻟﻔﻌﺎﻟـﺔ ﻓـﻰ‬
‫ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ ‪ ،‬ﻭﺒﺎﻟﺘﺎﻟﻰ ﺍﻟﺘﺴﺎﻭﻯ ﺒﻴﻥ ﻗﻴﻡ ﺘﻴﺎﺭﺍﺕ ﺃﻁﻭﺍﺭ ﺍﻟـﺩﺍﺌﺭﺓ ﺍﻟﺘـﻰ ﺘﻐـﺫﻯ‬
‫ﺍﻟﻤﻁﺒﺦ ﺒﺄﻜﻤﻠﻪ ‪:‬‬

‫ﺍﻟﻁﻭﺭ )‪(٣‬‬ ‫ﺍﻟﻁﻭﺭ )‪(٢‬‬ ‫ﺍﻟﻁﻭﺭ )‪(١‬‬


‫‪P‬‬ ‫‪Q‬‬ ‫‪P‬‬ ‫‪Q‬‬ ‫‪P‬‬ ‫‪Q‬‬ ‫ﺍﻟﺤﻤل‬
‫ﻙ‪.‬ﻭﺍﺕ‬ ‫ﻙ‪.‬ﻓﺎﺭ‬ ‫ﻙ‪.‬ﻭﺍﺕ‬ ‫ﻙ‪.‬ﻓﺎﺭ‬ ‫ﻙ‪.‬ﻭﺍﺕ‬ ‫ﻙ‪.‬ﻓﺎﺭ‬
‫‪--‬‬ ‫‪--‬‬ ‫‪٢‬‬ ‫‪--‬‬ ‫‪٢‬‬ ‫‪--‬‬ ‫ﺍﻟﺴﺨﺎﻨﺎﻥ‬
‫‪٢‬‬ ‫‪٢.٠٤‬‬ ‫‪٢‬‬ ‫‪٢.٠٤‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫ﻤﻔﺭﻤﺘﺎ ﺍﻟﻠﺤﻭﻡ‬
‫‪١‬‬ ‫‪١.٠٢‬‬ ‫‪--‬‬ ‫‪--‬‬ ‫‪١‬‬ ‫‪١.٠٢‬‬ ‫ﺁﻟﺘﺎ ﺘﺤﻀﻴﺭ ﺍﻟﺨﻀﺭﻭﺍﺕ‬
‫ﻭﺘﻀﺎﻑ ﺇﻟﻰ ﺫﻟﻙ ﺍﻷﺤﻤﺎل ﺜﻼﺜﻴﺔ ﺍﻷﻁﻭﺍﺭ ﻜﻤﺎ ﻴﻠﻰ‪:‬‬
‫‪١٢‬‬ ‫‪--‬‬ ‫‪١٢‬‬ ‫‪--‬‬ ‫‪١٢‬‬ ‫‪--‬‬ ‫ﺍﻷﻓﺭﺍﻥ‬
‫‪٣‬‬ ‫‪٢.٢٥‬‬ ‫‪٣‬‬ ‫‪٢.٢٥‬‬ ‫‪٣‬‬ ‫‪٢.٢٥‬‬ ‫ﺍﻟﺜﻼﺠﺎﺕ‬
‫‪٣‬‬ ‫‪٢.٢٥‬‬ ‫‪٣‬‬ ‫‪٢.٢٥‬‬ ‫‪٣‬‬ ‫‪٢.٢٥‬‬ ‫ﺁﻟﺘﺎ ﺍﻟﻌﺠﻴﻥ‬
‫‪١.٤٧‬‬ ‫‪٠.٤٨‬‬ ‫‪١.٤٧‬‬ ‫‪٠.٤٨‬‬ ‫‪١.٤٧‬‬ ‫‪٠.٤٨‬‬ ‫ﺍﻹﻨﺎﺭﺓ‬
‫ﻭﺒﺫﻟﻙ ﻴﻜﻭﻥ ﻤﺠﻤﻭﻉ ﺍﻷﺤﻤﺎل ﻋﻠﻰ ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ ﻜﻤﺎ ﻴﻠﻰ‪:‬‬
‫‪٢٢.٤٧‬‬ ‫‪٨.٠٤‬‬ ‫‪٢٣.٤٧‬‬ ‫‪٧.٠٢‬‬ ‫‪٢٢.٤٧‬‬ ‫‪٦.٠٠‬‬ ‫ﺍﻟﻤﺠﻤﻭﻉ ﻋﻠﻰ ﻜل ﻁﻭﺭ‬

‫‪ -‬ﺤﻴﺙ ‪ Q ، P‬ﻫﻤﺎ ﺍﻟﻤﺭﻜﺒﺘﺎﻥ ﺍﻟﻔﻌﺎﻟﺔ ﻭﻏﻴﺭ ﺍﻟﻔﻌﺎﻟﺔ ﻋﻠﻰ ﺍﻟﺘﻭﺍﻟﻰ ﻟﻠﻘـﺩﺭﺓ ﺒﺎﻟﻭﺤـﺩﺍﺕ‬
‫ﺍﻟﻤﺒﻴﻨﺔ ﺃﻋﻼﻩ‪.‬‬
‫ﻭﺒﺫﻟﻙ ﺘﻜﻭﻥ ﺍﻟﻤﺭﻜﺒﺘﺎﻥ ﺍﻟﻔﻌﺎﻟﺔ ﻭﻏﻴﺭ ﺍﻟﻔﻌﺎﻟﺔ ﻟﺘﻴﺎﺭ ﻜل ﻁﻭﺭ ﻭﻗﻴﻤﺘﻪ ﺍﻟﻌﺩﺩﻴﺔ ﺒﺎﻷﻤﺒﻴﺭ ﻜﻤﺎ‬
‫ﻴﻠﻰ‪:‬‬

‫ﺍﻟﻘﻴﻤﺔ ﺍﻟﻌﺩﺩﻴﺔ )‪(I‬‬ ‫ﺍﻟﻤﺭﻜﺒﺔ ﻏﻴﺭ ﺍﻟﻔﻌﺎﻟﺔ ) ‪(Iimg‬‬ ‫ﺍﻟﻤﺭﻜﺒﺔ ﺍﻟﻔﻌﺎﻟﺔ )‪(Ir‬‬ ‫ﺍﻟﻁﻭﺭ‬
‫‪١٠٥.٧١٥‬‬ ‫‪٢٧.٢٧٣‬‬ ‫‪١٠٢.١٣٦‬‬ ‫‪١‬‬
‫‪١١١.٣٥٢‬‬ ‫‪٣١.٩٠٩‬‬ ‫‪١٠٦.٦٨٢‬‬ ‫‪٢‬‬
‫‪١٠٨.٤٧٧‬‬ ‫‪٣٦.٥٤٥‬‬ ‫‪١٠٢.١٣٦‬‬ ‫‪٣‬‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻭﻜﺫﻟﻙ ﺘﻜﻭﻥ ﻤﺭﻜﺒﺘﺎ ﺘﻴﺎﺭ ﻤﻭﺼل ﺍﻟﺘﻌﺎﺩل ﻭﻗﻴﻤﺘﻪ ﺍﻟﻌﺩﺩﻴﺔ ﺒﺎﻷﻤﺒﻴﺭﻜﻤﺎ ﻴﻠﻰ ‪:‬‬
‫ﺍﻟﻤﺭﻜﺒﺔ ﺍﻟﺤﻘﻴﻘﻴﺔ )‪(١٠٢.١٣٦ + ١٠٦.٦٨٢)٠.٥ – ١٠٢.١٣٦ = (Inr‬‬
‫– ‪ ١.٧٤٢ = (٣٦.٥٤٥ – ٣١.٩٠٩)٠.٨٦٦‬ﺃﻤﺒﻴﺭ‬
‫ﺍﻟﻤﺭﻜﺒﺔ ﺍﻟﺘﺨﻴﻠﻴﺔ )‪(٣٦.٥٤٥ + ٣١.٩٠٩)٠.٥ – ٢٧.٢٧٣ = (Ing‬‬
‫‪ ٣.٠١٧ – = (١٠٢.١٣٦ – ١٠٦.٦٨٢)٠.٨٦٦ +‬ﺃﻤﺒﻴﺭ‬
‫ﺍﻟﻘﻴﻤﺔ ﺍﻟﻌﺩﺩﻴﺔ )‪ ٣.٤٨٤ = (In‬ﺃﻤﺒﻴﺭ‬
‫ﻤﻼﺤﻅﺎﺕ‪:‬‬
‫)‪ (١‬ﺘﺨﺘﻠﻑ ﻗﻴﻤﺔ ﻭﺍﺘﺠﺎﻩ ﻤﺭﻜﺒﺘﻲ ﺘﻴﺎﺭ ﻤﻭﺼل ﺍﻟﺘﻌﺎﺩل ﻭﻗﻴﻤﺘﻪ ﺍﻟﻌﺩﺩﻴﺔ ﻓﻲ ﺃﺠﺯﺍﺀ ﻫـﺫﺍ‬
‫ﺍﻟﻤﻭﺼل‪ ،‬ﻭﻴﻤﻜﻥ ﺤﺴﺎﺏ ﻫﺫﻩ ﺍﻟﻘﻴﻡ ﻓﻲ ﻜل ﺠـﺯﺀ ﺒﻤﻌﻠﻭﻤﻴـﺔ ﺘﺭﺘﻴـﺏ ﻭﺘﻭﺯﻴـﻊ‬
‫ﺍﻷﺤﻤﺎل ﺫﺍﺕ ﺍﻟﻁﻭﺭ ﺍﻟﻭﺍﺤﺩ ﻭﺒﺎﻋﺘﺒﺎﺭ ﺍﻷﺤﻤﺎل ﺫﺍﺕ ﺍﻟﻁﻭﺭ ﺍﻟﻭﺍﺤـﺩ ﺍﻟﺘـﻲ ﺘﻤـﺭ‬
‫ﺘﻴﺎﺭﺍﺘﻬﺎ ﻓﻲ ﺫﻟﻙ ﺍﻟﺠﺯﺀ ﻤﻥ ﻤﻭﺼل ﺍﻟﺘﻌﺎﺩل ﻭﺍﺴﺘﺒﻌﺎﺩ ﺒﻘﻴﺔ ﺍﻷﺤﻤﺎل ﻤـﻊ ﺘﻜـﺭﺍﺭ‬
‫ﺍﻟﺤﺴﺎﺒﺎﺕ ﺍﻟﺴﺎﺒﻘﺔ‪.‬‬
‫)‪ (٢‬ﺘﺘﺤﻘﻕ ﻜل ﻗﻴﻡ ﺍﻟﻘﺩﺭﺍﺕ ﻭﺍﻟﺘﻴﺎﺭﺍﺕ ﺍﻟﻭﺍﺭﺩﺓ ﺒﻌﺎﻟﻴﻪ ﻓﻘﻁ ﻋﻨﺩ ﺘﻐﺫﻴﺔ ﻜـل ﺍﻷﺤﻤـﺎل‬
‫ﺒﺎﻟﻤﻁﺒﺦ ﺒﻜﺎﻤل ﻗﺩﺭﺍﺘﻬﺎ ﻓﻰ ﻨﻔﺱ ﺍﻟﻭﻗﺕ )ﻜﻤﺎ ﻓﻰ ﺤﺎﻟﺔ ﺍﻹﻋـﺩﺍﺩ ﻟﺤﻔـل ﻤـﺜﻼﹰ(‪،‬‬
‫ﻭﻴﺠﺏ ﺃﺨﺫ ﻫﺫﻩ ﺍﻟﻘﻴﻡ ﻜﺄﺴﺎﺱ ﻟﺘﺼﻤﻴﻡ ﺍﻟﺩﻭﺍﺌﺭ ﻜﻠﻬﺎ ﻟﺘﻼﻓﻰ ﺯﻴـﺎﺩﺓ ﺍﻟﺤﻤـل ﻓـﻰ‬
‫ﺍﻟﺩﻭﺍﺌﺭ ﻓﻰ ﺤﺎﻻﺕ ﺍﻟﻁﻭﺍﺭﺉ ‪.‬‬
‫)‪ (٣‬ﻓﻰ ﺍﻷﺤﻭﺍل ﺍﻟﻌﺎﺩﻴﺔ ﺘﺤﺴﺏ ﺍﻟﻘﻴﻡ ﺍﻟﻘﺼﻭﻯ ﻟﻠﻘﺩﺭﺍﺕ ﻭﺍﻟﺘﻴﺎﺭﺍﺕ ﺒﺄﺨﺫ ﻤﻌﺎﻤل ﺍﻟﺘﺒﺎﻴﻥ‬
‫ﻓﻰ ﺍﻻﻋﺘﺒﺎﺭ ﻜﻤﺎ ﻓﻰ ﺍﻟﺒﻨﺩ ﺍﻟﺘﺎﻟﻰ ‪.‬‬
‫ﻭﺒﺘﻁﺒﻴﻕ ﺍﻟﻁﺭﻴﻘﺔ ﺍﻟﺘﻘﺭﻴﺒﻴﺔ ﺍﻟﻭﺍﺭﺩﺓ ﻓﻰ ﺍﻟﺒﻨﺩ ‪-٤‬ﺝ ﺍﻟﺴﺎﺒﻕ )ﺍﻟﺘﻰ ﺘﻬﻤل ﺩﺭﺠﺔ ﻋﺩﻡ‬
‫ﺍﻟﺘﻭﺍﺯﻥ ﻋﻠﻰ ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ ﻭﺍﻋﺘﺒﺎﺭ ﺤﻤل ﺍﻟﻤﻁﺒﺦ ﻜﻠﻪ ﻜﻤﺎ ﻟﻭ ﻜﺎﻥ ﻤﺘﻭﺍﺯﻨﺎ ﻋﻠﻰ‬
‫ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ( ﺘﻜﻭﻥ ﻗﻴﻡ ﻤﺘﻭﺴﻁﻰ ﺍﻟﻘﺩﺭﺘﻴﻥ ﺍﻟﻔﻌﺎﻟﺔ ﻭﻏﻴـﺭ ﺍﻟﻔﻌﺎﻟـﺔ ﻭﺍﻟﻘﻴﻤـﺔ‬
‫ﺍﻟﻌﺩﺩﻴﺔ ﻟﻤﺘﻭﺴﻁ ﺘﻴﺎﺭ ﺍﻟﻁﻭﺭ ﻜﻤﺎ ﻴﻠﻰ ‪:‬‬
‫= ‪ ٢٢.٨٠٣‬ﻙ ﻭﺍﺕ‬ ‫‪Pav‬‬
‫‪ ٧.٠٢٠ = Qav‬ﻙ ﻓﺎﺭ‬
‫= ‪ ١٠٨.٤٥١‬ﺃﻤﺒﻴﺭ‬ ‫‪Iav‬‬
‫ﻭﻴﻼﺤﻅ ﺃﻥ ﺍﻟﻘﻴﻤﺔ ﺍﻟﻌﺩﺩﻴﺔ ﻟﻤﺘﻭﺴﻁ ﺘﻴﺎﺭﺍﺕ ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ ﻫﻰ ﻗﻴﻤﺔ ﻤﻘﺒﻭﻟﺔ ﻓـﻰ‬
‫ﻫﺫﻩ ﺍﻟﺤﺎﻟﺔ )ﺒﺎﻟﻤﻘﺎﺭﻨﺔ ﻤﻊ ﺍﻟﻘﻴﻡ ﺍﻟﻌﺩﺩﻴﺔ ﻟﺘﻴـﺎﺭﺍﺕ ﺍﻷﻁـﻭﺍﺭ ﺍﻟﺜﻼﺜـﺔ ﺍﻟﻤﺤﺴـﻭﺒﺔ‬
‫ﺒﺎﻟﻁﺭﻴﻘﺔ ﺍﻟﺴﺎﺒﻘﺔ ( ﺤﻴﺙ ﺃﻥ ﻨﺴﺒﺔ ﻋﺩﻡ ﺍﻟﺘﻭﺍﺯﻥ ﻓﻰ ﻫﺫﺍ ﺍﻟﻤﺜﺎل ﻀﺌﻴﻠﺔ ‪.‬‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻭﻜﻤﺎ ﺴﺒﻕ ﻴﻜﻭﻥ ﺘﻴﺎﺭ ﻤﻭﺼل ﺍﻟﺘﻌﺎﺩل ﻋﻠﻰ ﺃﺴﺎﺱ ﻓﺭﺽ ﺘﻭﺍﺯﻥ ﺍﻟﺤﻤـل ﻋﻠـﻰ‬
‫ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ ﺼﻔﺭﺍﹰ‪.‬‬

‫‪ ٢-١-٢-٥‬ﺍﻟﻘﻴﻡ ﺍﻟﻘﺼﻭﻯ ﻟﻠﻘﺩﺭﺍﺕ ﻭﺍﻟﺘﻴﺎﺭﺍﺕ ﻓﻰ ﺍﻷﺤﻭﺍل ﺍﻟﻌﺎﺩﻴﺔ‬


‫ﺘﻅل ﺍﻟﻘﻴﻡ ﺍﻟﻘﺼﻭﻯ ﻟﻠﻘﺩﺭﺍﺕ ﻭﺍﻟﺘﻴﺎﺭﺍﺕ ﻓﻰ ﺍﻟﺩﻭﺍﺌﺭ ﺍﻟﻔﺭﻋﻴﺔ ﺍﻟﻨﻬﺎﺌﻴﺔ ﻜﻤﺎ ﻭﺭﺩﺕ ﻓﻰ ﺍﻟﺒﻨﺩ‬
‫ﺍﻟﺴﺎﺒﻕ ‪.‬‬
‫ﻭﻓﻴﻤﺎ ﻴﺘﻌﻠﻕ ﺒﺎﻟﺩﺍﺌﺭﺓ ﺍﻟﺘﻰ ﺘﻐﺫﻯ ﺍﻟﻤﻁﺒﺦ ﺒﺄﻜﻤﻠﻪ ‪ ،‬ﻓﺈﻨﻪ ﺒﺎﺴـﺘﻌﻤﺎل ﻤﻌـﺎﻤﻼﺕ ﺍﻟﺘﺒـﺎﻴﻥ‬
‫ﺍﻟﻭﺍﺭﺩﺓ ﻓﻰ ﺍﻟﺠﺩﻭل )‪ (٢ - ٣‬ﻓﻲ ﻫﺫﺍ ﺍﻟﻤﺠﻠﺩ‪.‬‬
‫ﺘﻜﻭﻥ ﺍﻟﻘﻴﻡ ﺍﻟﻘﺼﻭﻯ ﻜﻤﺎ ﻴﻠﻰ ‪.‬‬
‫‪ -‬ﺍﻷﻓﺭﺍﻥ ‪ ٢٨.٨ = ١٢ × ٪ ٦٠ + ١٢ × ٪ ٨٠ + ١٢ × ٪ ١٠٠‬ﻙ ﻭﺍﺕ‬
‫‪ -‬ﺍﻟﺜﻼﺠﺎﺕ ‪ ٧.٢ = ٣ × ٪ ٦٠ + ٣ + ٪ ٨٠ + ٣ × ٪ ١٠٠‬ﻙ ﻭﺍﺕ‬
‫‪ -‬ﺍﻟﺴﺨﺎﻨﺎﻥ ‪) ٢ × ٢‬ﺒﺎﻋﺘﺒﺎﺭﻫﻤﺎ ﻴﻌﻤﻼﻥ ﺒﺎﺴﺘﻤﺭﺍﺭ ﻭﻗﺕ ﺍﻟﺫﺭﻭﺓ ( = ‪ ٤‬ﻙ ﻭﺍﺕ‬
‫‪ -‬ﻤﻔﺭﻤﺘﺎ ﺍﻟﻠﺤﻭﻡ ‪ ٣.٦ = ٢ × ٪ ٨٠ + ٢ × ٪ ١٠٠‬ﻙ ﻭﺍﺕ‬
‫‪ -‬ﺁﻟﺘﺎ ﺍﻟﻌﺠﻴﻥ ‪٤ = ٣ × ٪ ٨٠ + ٣ × ٪ ١٠٠‬ﻭ‪ ٥‬ﻙ ﻭﺍﺕ‬
‫‪ -‬ﺁﻟﺘﺎ ﺘﺤﻀﻴﺭ ﺍﻟﺨﻀﺭﻭﺍﺕ ‪ ١.٨ = ١ × ٪ ٨٠ + ١ × ٪ ١٠٠‬ﻙ ﻭﺍﺕ‬
‫‪ -‬ﺍﻹﻨﺎﺭﺓ ‪ ٤.٤ = ٤.٤ × ٪ ١٠٠‬ﻙ ﻭﺍﺕ‬
‫ﻭﺘﻜــﻭﻥ ﺍﻟﻘﻴﻤــﺔ ﺍﻟﻘﺼــﻭﻯ ﻟﺤﻤــل ﺍﻟﻤﻁﺒـــﺦ ﺒﺄﻜﻤﻠـﻪ = ‪ ٥٥.٢‬ﻙ ﻭﺍﺕ‬
‫ﺒﺩﻻ ﻤﻥ ‪ ٦٨.٤١‬ﻙ ﻭﺍﺕ ﻓﻰ ﺤﺎﻻﺕ ﺍﻟﻁﻭﺍﺭﺉ ‪ ،‬ﻭﻜﻤـﺎ ﺴـﺒﻕ ﻴﺠـﺏ ﺃﺨـﺫ ﺤـﺎﻻﺕ‬
‫ﺍﻟﻁﻭﺍﺭﺉ ﻜﺄﺴﺎﺱ ﻟﻠﺘﺼﻤﻴﻡ ﻁﺎﻟﻤﺎ ﺃﻨﻬﺎ ﻤﺘﻜﺭﺭﺓ‪.‬‬
‫ﺘﺤﺩﻴﺩ ﻤﻌﺎﻤﻼﺕ ﺘﺼﺤﻴﺢ ﺴﻌﺔ ﺤﻤل ﻤﻭﺼﻼﺕ ﺍﻟﺩﺍﺌﺭﺓ ﻟﻠﺘﻴﺎﺭ‬ ‫‪٣-٥‬‬
‫ﻋﻨﺩﻤﺎ ﻴﺤﺘﻭﻯ ﻤﺴﺎﺭ ﻜﺎﺒل ﺍﻟﺩﺍﺌﺭﺓ ﻋﻠﻰ ﺃﺠﺯﺍﺀ ﺘﺨﺘﻠﻑ ﻋﻥ ﺒﻌﻀﻬﺎ ﻓﻰ ﻅـﺭﻭﻑ ﺩﺭﺠـﺔ‬
‫ﺤﺭﺍﺭﺓ ﺍﻟﻭﺴﻁ ﺍﻟﻤﺤﻴﻁ ‪ ،‬ﺃﻭ ﻓﻰ ﺘﺠﻤﻴﻊ ﺍﻟﻜﺎﺒل ﻤﻊ ﻜﺎﺒﻼﺕ ﺃﺨﺭﻯ ﻓﻰ ﺤﻴـﺯ ﻤﻐﻠـﻕ ‪ ،‬ﺃﻭ‬
‫ﻟﻤﺭﻭﺭ ﺘﻴﺎﺭ ﺯﺍﺌﺩ ﻟﻤﺩﺓ ﻁﻭﻴﻠﺔ ﻨﺘﻴﺠﺔ ﻟﺒﻁﺀ ﺍﻟﻨﺒﻴﻁﺔ ﺍﻟﻤﺴﺘﻌﻤﻠﺔ ﻟﻭﻗﺎﻴﺔ ﺍﻟﻜﺎﺒل ‪ ،‬ﺃﻭ ﻟﺘﻼﻤﺱ‬
‫ﺍﻟﻜﺎﺒل ﻤﻊ ﻤﺎﺩﺓ ﻋﺎﺯﻟﺔ ﻟﻠﺤﺭﺍﺭﺓ ‪ ،‬ﻓﻴﺠﺏ ﺤﺴﺎﺏ ﻤﻌﺎﻤﻼﺕ ﺍﻟﺘﺼﺤﻴﺢ ﻓﻰ ﻜل ﻤـﻥ ﻫـﺫﻩ‬
‫ﺍﻷﺠﺯﺍﺀ ﻁﺒﻘﺎ ﻟﻠﻅﺭﻭﻑ ﺍﻟﻤﺨﺘﻠﻔﺔ ﻓﻰ ﻜل ﺠﺯﺀ ‪ ،‬ﻤﻊ ﺃﺨﺫ ﺃﻗل ﻗﻴﻤﺔ ﻟﻤﻌﺎﻤـل ﺍﻟﺘﺼـﺤﻴﺢ‬
‫ﺍﻟﻜﻠﻰ )ﻭﻫﻭ ﺤﺎﺼل ﻀﺭﺏ ﻤﻌﺎﻤﻼﺕ ﺍﻟﺘﺼﺤﻴﺢ ﻟﻜل ﻤﻥ ﻅﺭﻭﻑ ﺍﻟﺘﺸﻐﻴل ﻓﻰ ﻜل ﺠﺯﺀ‬
‫ﻤﻥ ﻤﺴﺎﺭ ﺍﻟﻜﺎﺒل( ﻓﻰ ﺍﻷﺠﺯﺍﺀ ﻜﻠﻬﺎ ﻜﺄﺴﺎﺱ ﻟﺘﺤﺩﻴﺩ ﺴﻌﺔ ﺤﻤل ﺍﻟﺘﻴﺎﺭ ﻓﻰ ﺍﻟﻜﺎﺒل ﺒﻜﺎﻤـل‬
‫ﻁﻭل ﻤﺴﺎﺭﻩ‪.‬‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻭﻓﻴﻤﺎ ﻴﻠﻰ ﻨﺒﺫﺓ ﻋﻥ ﻜل ﻤﻥ ﻤﻌﺎﻤﻼﺕ ﺍﻟﺘﺼﺤﻴﺢ ‪:‬‬


‫)‪ (١‬ﻴﺭﺠﻊ ﻓﻰ ﺘﺤﺩﻴﺩ ﻤﻌﺎﻤل ﺘﺄﺜﻴﺭ ﺩﺭﺠﺔ ﺤﺭﺍﺭﻩ ﺍﻟﻭﺴﻁ ﺍﻟﻤﺤﻴﻁ )‪ (Ca‬ﺇﻟﻰ ﺍﻟﺠـﺩﻭل‬
‫)ﻡ‪ (٣/٣‬ﺒﺎﻟﺼﻔﺤﺔ ‪ ٢٢‬ﻡ ﺒﺎﻟﺠﺯﺀ ﺍﻟﺜﺎﻟﺙ ﻤﻥ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻯ ‪ ،‬ﻭﺫﻟﻙ ﻁﺒﻘﺎ ﻟﻨـﻭﻉ‬
‫ﺍﻟﻤﺎﺩﺓ ﺍﻟﻌﺎﺯﻟﺔ ﺩﺍﺨل ﺍﻟﻜﺎﺒل ‪.‬‬
‫)‪ (٢‬ﻤﻌﺎﻤل ﺍﻟﺘﺼﺤﻴﺢ ﻨﺘﻴﺠﺔ ﻟﺘﺠﻤﻴﻊ ﺍﻟﻤﻭﺼﻼﺕ ﺍﻟﺤﺎﻤﻠﺔ ﻟﻠﺘﻴﺎﺭ ﻤﻌﺎ ﻓﻰ ﺤﻴﺯ ﻭﺍﺤﺩ ﻤﺜل‬
‫ﺍﻟﻤﻭﺍﺴﻴﺭ ﺃﻭ ﻤﺠﺎﺭﻯ ﺍﻷﺴﻼﻙ )‪ (Cg‬ﺤﻴﺙ ﻴﻨﺸﺄ ﺘﺴﺨﻴﻥ ﻤﺘﺒﺎﺩل ﺒـﻴﻥ ﺍﻟﻜـﺎﺒﻼﺕ‬
‫ﻭﺒﻌﻀﻬﺎ ‪ ،‬ﻭﺘﺤﺩﺩ ﻗﻴﻤﺔ ﻫﺫﺍ ﺍﻟﻤﻌﺎﻤل ﺒﺎﻟﺭﺠﻭﻉ ﺇﻟﻰ ﺍﻟﺠﺩﻭل )ﻡ‪ (٢/٣‬ﺒﺎﻟﺼﻔﺤﺔ ‪٢٠‬‬
‫ﻡ ﺒﺎﻟﺠﺯﺀ ﺍﻟﺜﺎﻟﺙ ﻤﻥ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻯ ‪ ،‬ﻭﻴﻁﺒﻕ ﻋﻠﻰ ﺍﻟﻜﺎﺒﻼﺕ ﺍﻟﻤﺘﻤﺎﺜﻠـﺔ ﺃﺤﺎﺩﻴـﺔ‬
‫ﺍﻟﻁﻭﺭ ﺃﻭ ﻤﺘﻌﺩﺩﺓ ﺍﻷﻗﻁﺎﺏ ﺍﻟﻤﺠﻤﻌﺔ ﻓﻰ ﻤﺴﺎﺭ ﻭﺍﺤﺩ ‪ ،‬ﻭﻟﻜـﻥ ﻻ ﻴﻁﺒـﻕ ﻋﻠـﻰ‬
‫ﺍﻟﻜﺎﺒﻼﺕ ﺍﻟﻤﺘﺠﺎﻭﺭﺓ ﻋﻨﺩ ﺨﺭﻭﺠﻬﺎ ﻤﻥ ﻟﻭﺤﺔ ﺍﻟﺘﻭﺯﻴﻊ ‪.‬‬
‫)‪ (٣‬ﻤﻌﺎﻤل ﺍﻟﺘﺼﺤﻴﺢ ﻨﺘﻴﺠﺔ ﻟﻤﺭﻭﺭﺍﻟﺘﻴﺎﺭ ﺍﻟﺯﺍﺌﺩ ﺒﺎﻟﻜﺎﻤل ﻟﻤﺩﺓ ﻁﻭﻴﻠﺔ )‪ (Cf‬ﻨﺘﻴﺠﺔ ﻟﺒﻁﺀ‬
‫ﻨﺒﻴﻁﺔ ﺍﻟﻭﻗﺎﻴﺔ ‪ ،‬ﻤﺜل ﺤﺎﻟﺔ ﺍﻟﻭﻗﺎﻴﺔ ﺒﻤﺼﺎﻫﺭ ﺫﺍﺕ ﺨﻭﺍﺹ ﺒﻁﻴﺌـﺔ ﻤﻨﺘﺠـﺔ ﻁﺒﻘـﺎ‬
‫ﻟﻠﻤﻭﺍﺼﻔﺎﺕ ﺍﻟﻜﻬﺭﻭﺘﻘﻨﻴﺔ ﺍﻟﻌﺎﻟﻤﻴﺔ ‪ ،IEC 269-3‬ﻓﻔﻰ ﻫﺫﻩ ﺍﻟﺤﺎﻟـﺔ ﻴﺅﺨـﺫ ﻤﻌﺎﻤـل‬
‫ﺍﻟﺘﺼﺤﻴﺢ = ‪ ، ٠.٧٢٥‬ﻋﻠﻤﺎ ﺒﺄﻥ ﻫﺫﺍ ﺍﻟﻤﻌﺎﻤل ﻓﻰ ﺍﻟﺤﺎﻻﺕ ﺍﻷﺨﺭﻯ = ‪. ١‬‬
‫)‪ (٤‬ﻋﻨﺩﻤﺎ ﻴﻜﻭﻥ ﻤﻥ ﺍﻟﻤﺨﻁﻁ ﺃﻥ ﻴﻤﺭ ﻤﺴﺎﺭ ﺍﻟﻜﺎﺒل ﺒﺎﻟﻘﺭﺏ ﻤـﻥ ﻤﺼـﺩﺭ ﺤـﺭﺍﺭﻯ‬
‫ﻤﻌﺯﻭل )ﻤﺜل ﻤﺎﺴﻭﺭﺓ ﻤﻴﺎﺓ ﺴﺎﺨﻨﺔ( ﺒﺤﻴﺙ ﻤﻥ ﺍﻟﻤﻨﺘﻅﺭ ﺃﻥ ﻴﺘﻼﻤﺱ ﺍﻟﻜﺎﺒل ﻤـﻊ‬
‫ﺍﻟﻤﺎﺩﺓ ﺍﻟﻌﺎﺯﻟﺔ ﻟﻠﻤﺼﺩﺭ ﺍﻟﺤﺭﺍﺭﻯ ﻤﻥ ﺠﻬﺔ ﻭﺍﺤﺩﺓ ﻓﻴﺅﺨﺫ ﻤﻌﺎﻤل ﺍﻟـﺘﻼﻤﺱ ﻤـﻊ‬
‫ﺍﻟﻤﺎﺩﺓ ﺍﻟﻌﺎﺯﻟﺔ ﻟﻠﺤﺭﺍﺭﺓ )‪ ، ١ = (Ci‬ﻓﻰ ﺤﻴﻥ ﺃﻨﻪ ﺇﺫﺍ ﻜﺎﻥ ﺍﻟﻜﺎﺒل ﻨﻔﺴﻪ ﻤﺤﺎﻁﺎ ﻤﻥ‬
‫ﻜل ﺠﻬﻪ ﺒﻌﺯل ﺤﺭﺍﺭﻯ ﻟﺤﻤﺎﻴﺘﻪ ﻤﻥ ﺍﻟﻤﺼﺩﺭ ﺍﻟﺤﺭﺍﺭﻯ ﺍﻟﻘﺭﻴـﺏ ﻓﻴﺅﺨـﺫ)‪= (Ci‬‬
‫‪٠.٥‬‬

‫‪ ١-٣-٥‬ﻤﺜﺎل ﺘﻭﻀﻴﺤﻰ‬
‫ﺍﻟﻤﻁﻠﻭﺏ ﺘﺤﺩﻴﺩ ﻗﻴﻤﺔ ﻤﻌﺎﻤل ﺍﻟﺘﺼﺤﻴﺢ ﺍﻟﻜﻠﻰ ﻟﻜﺎﺒل ﻴﻤﺭ ﻤﺴﺎﺭﻩ ﻓﻲ ﺜﻼﺜﺔ ﻤﻨـﺎﻁﻕ ﺫﺍﺕ‬
‫ﻅﺭﻭﻑ ﺘﺸﻐﻴل ﻤﺨﺘﻠﻔﺔ ﻜﺎﻟﻤﻭﻀﺢ ﻓﻰ ﺍﻟﺸﻜل )‪:(٢-٥‬‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻟﻮﺣﺔ ﻣﺼﺎھﺮ‬

‫ﻛﺎﺑﻼت‬ ‫درﺟﺔ ﺣﺮارة‬ ‫اﻟﻜﺎﺑﻞ ﻣﺤﺎط ﺑﻤﺎدة‬


‫‪M‬‬
‫‪ ٣٠‬أﻣﺒﯿﺮ‬ ‫ﻣﺠﻤﻌﺔ‬ ‫ﻋﺎﻟﯿﺔ ﻟﻠﻮﺳﻂ‬ ‫ﻋﺎزﻟﺔ ﻟﻠﺤﺮارة‬

‫ﻣﺼﮭﺮ ﻃﺒﻘﺎً ﻟﻤﻮاﺻﻔﺎت‬ ‫ﺣﻤﻞ ﻛﮭﺮﺑﺎﺋﻲ‬


‫‪IEC 269-3‬‬
‫اﻟﺠﺰء اﻷول‬ ‫اﻟﺠﺰء اﻟﺜﺎﻧﻲ‬ ‫اﻟﺠﺰء اﻟﺜﺎﻟﺚ‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(٢-٥‬ﺃﺠﺯﺍﺀ ﻤﺴﺎﺭ ﺍﻟﻜﺎﺒل ﺫﺍﺕ ﺍﻟﻅﺭﻭﻑ ﺍﻟﻤﺨﺘﻠﻔﺔ‬

‫‪ -‬ﻴﺨﺭﺝ ﺍﻟﺠﺯﺀ ﺍﻷﻭل ﻤﻥ ﺍﻟﻜﺎﺒل ﻤﻥ ﻟﻭﺤﺔ ﺘﻭﺯﻴﻊ ﻓﺭﻋﻴـﺔ ﻤـﺯﻭﺩﺓ ﺒﻤﺼـﺎﻫﺭ ﺫﺍﺕ‬
‫ﺨﻭﺍﺹ ﺨﺎﺼﺔ ﻭﺒﻁﻴﺌﺔ ﻤﻨﺘﺠﺔ ﻁﺒﻘﺎ ﻟﻠﻤﻭﺍﺼﻔﺎﺕ ﺍﻟﻜﻬﺭﻭﺘﻘﻨﻴﺔ ﺍﻟﻌﺎﻟﻤﻴـﺔ ‪IEC 269-3‬‬
‫ﻭﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺍﻟﻭﺴﻁ ﻓﻰ ﻫﺫﺍ ﺍﻟﺠﺯﺀ ﻫﻰ ‪ْ ٤٠‬ﻡ ‪.‬‬
‫‪ -‬ﻴﻤﺭ ﺍﻟﻜﺎﺒل ﻓﻰ ﺍﻟﺠﺯﺀ ﺍﻟﺜﺎﻨﻰ ﻤﻥ ﺍﻟﻤﺴﺎﺭ ﻤﻨﻔﺭﺩﺍ ﺒﻴﻥ ﻤﺒﻨﻴﻴﻥ ‪ ،‬ﻭﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺍﻟﻭﺴﻁ‬
‫ﺍﻟﻤﺤﻴﻁ ﻗﺩ ﺘﺼل ﺇﻟﻰ ‪ْ ٥٠‬ﻡ ‪.‬‬
‫‪ -‬ﻴﻤﺭ ﺍﻟﻜﺎﺒل ﻓﻰ ﺍﻟﺠــﺯﺀ ﺍﻟﺜﺎﻟﺙ ﻤﻥ ﺍﻟﻤﺴـﺎﺭ ﻤﻨﻔﺭﺩﺍ ﻓﻰ ﻭﺴـﻁ ﻤﺤـﻴﻁ ﺩﺭﺠـﺔ‬
‫ﺤﺭﺍﺭﺘﻪ ‪ْ ٤٥‬ﻡ ‪ ،‬ﻭﻴﺤﺎﻁ ﺍﻟﻜﺎﺒل ﻤﻥ ﻜل ﻨﺎﺤﻴﺔ ﺒﻤﺎﺩﺓ ﻋﺎﺯﻟﺔ ﻤﻥ ﺍﻟﺤﺭﺍﺭﺓ ﻟﻠﻭﻗﺎﻴﺔ ﻤـﻥ‬
‫ﻤﺼﺩﺭ ﺤﺭﺍﺭﻯ ﻗﺭﻴﺏ ‪.‬‬
‫ﺍﻟﺤل‪ :‬ﻤﻌﺎﻤﻼﺕ ﺍﻟﺘﺼﺤﻴﺢ ﻓﻰ ﺍﻷﺠﺯﺍﺀ ﺍﻟﻤﺨﺘﻠﻔﺔ ﻤﻥ ﺍﻟﻤﺴﺎﺭ ﻜﻤﺎ ﻴﻠﻰ ‪.‬‬

‫ﺠﺩﻭل ﻤﻌﺎﻤﻼﺕ ﺍﻟﺘﺼﺤﻴﺢ ﻷﺠﺯﺍﺀ ﺍﻟﻜﺎﺒل‬

‫ﺍﻟﺠﺯﺀ ﺍﻟﺜﺎﻟﺙ‬ ‫ﺍﻟﺠﺯﺀ ﺍﻟﺜﺎﻨﻰ‬ ‫ﺍﻟﺠﺯﺀ ﺍﻷﻭل‬ ‫ﻤﻌﺎﻤﻼﺕ ﺍﻟﺘﺼﺤﻴﺢ‬


‫‪٠.٩١‬‬ ‫‪٠.٨٨‬‬ ‫‪٠.٩٤‬‬ ‫‪Ca‬‬
‫‪١‬‬ ‫‪١‬‬ ‫‪١‬‬ ‫‪Cg‬‬
‫‪٠.٧٢٥‬‬ ‫‪٠.٧٢٥‬‬ ‫‪٠.٧٢٥‬‬ ‫‪Cf‬‬
‫‪٠.٥‬‬ ‫‪١‬‬ ‫‪١‬‬ ‫‪Ci‬‬
‫‪٠.٣٢٩٩‬‬ ‫‪٠.٦٣٨‬‬ ‫‪٠.٦٨١٥‬‬ ‫ﻤﻌﺎﻤل ﺍﻟﺘﺼﺤﻴﺢ ﺍﻟﻜﻠﻰ ‪CF‬‬
‫ﻭﻋﻠﻰ ﻫﺫﺍ ﺍﻷﺴﺎﺱ ﻴﺅﺨﺫ ﻤﻌﺎﻤل ﺍﻟﺘﺼﺤﻴﺢ ﺍﻟﻜﻠﻰ ﻟﻠﻜﺎﺒل ﺒﺄﻜﻤﻠﻪ = ‪٠.٣٢٩٩‬‬
‫ﻁﺒﻘﺎﹰ ﻷﻗل ﻤﻌﺎﻤل ﺘﺼﺤﻴﺢ ﻓﻲ ﺃﺠﺯﺍﺀ ﺍﻟﻜﺎﺒل ‪.‬‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺤﺴﺎﺏ ﺍﻟﺴﻌﺔ ﺍﻟﻤﻁﻠﻭﺒﺔ ﻟﺤﻤل ﺍﻟﺩﺍﺌﺭﺓ ﻟﻠﺘﻴﺎﺭ‬ ‫‪٤-٥‬‬


‫ﺘﻘﺩﻡ ﺸﺭﻜﺎﺕ ﺼﻨﺎﻋﺔ ﺍﻟﻜﺎﺒﻼﺕ ﺠﺩﺍﻭل ﻟﺴﻌﺔ ﺤﻤل ﻜﺎﺒﻼﺘﻬـﺎ ﻟﻠﺘﻴـﺎﺭ‪ ،‬ﻟﻜـل ﻜﺎﺒﻼﺘﻬـﺎ‬
‫ﺍﻟﻤﺼﻨﻭﻋﺔ ﻤﻥ ﺍﻟﻨﺤﺎﺱ ﻭﻤﻥ ﺍﻷﻟﻭﻤﻨﻴﻭﻡ‪ ،‬ﻭﻤﺎﺩﺓ ﺍﻟﻌﺎﺯل ﺒﻰ ﻓﻰ ﺴﻰ ﺃﻭ ﺒﻭﻟﻲ ﺍﻴﺜﻴﻠﻴﻥ‪ ،‬ﺃﻭ‬
‫ﻤﻁﺎﻁ ‪ ،‬ﺃﻭ ﻭﺭﻕ ﻤﺸﺒﻊ ﺒﺎﻟﺯﻴﺕ ‪ ،‬ﺃﻭ ﺨﻼﻓﻪ ‪ ،‬ﺴﻭﺍﺀ ﻟﻠﻜﺎﺒﻼﺕ ﺍﻟﻤﻐﻠﻔﺔ ﺒﺎﻟﺭﺼـﺎﺹ‪ ،‬ﺃﻭ‬
‫ﺍﻟﻤﻜﺴﻭﺓ ﺒﻰ ﻓﻰ ﺴﻰ ‪ ،‬ﺍﻟﻤﺴﻠﺤﺔ ﺃﻭ ﻏﻴﺭ ﺍﻟﻤﺴﻠﺤﺔ ‪ ،‬ﻭﻟﻜل ﺸﻜل ﻤﻥ ﻗﻁﺎﻉ ﺍﻟﻤﻭﺼـﻼﺕ‬
‫ﻓﻰ ﺍﻟﻜﺎﺒل ‪ ،‬ﻭﻋﺩﺩ ﺍﻟﻤﻭﺼﻼﺕ ﺒﺩﺍﺨﻠﻪ‪ ،‬ﻭﺫﻟﻙ ﺘﺤﺕ ﻅﺭﻭﻑ ﻗﻴﺎﺴﻴﺔ ﻤﻥ ﺩﺭﺠﺔ ﺤـﺭﺍﺭﺓ‬
‫ﺍﻟﻭﺴﻁ ﺍﻟﻤﺤﻴﻁ ‪ ،‬ﻟﻜل ﻁﺭﻴﻘﺔ ﻤﻥ ﻁﺭﻕ ﺘﺭﻜﻴﺏ ﺍﻟﻜﺎﺒل ‪.‬‬
‫ﻭﻟﻤﺎ ﻜﺎﻨﺕ ﺍﻟﻅﺭﻭﻑ ﺍﻟﻘﻴﺎﺴﻴﺔ ﺍﻟﻭﺍﺭﺩﺓ ﻓﻰ ﺠﺩﺍﻭل ﺍﻟﻜﺎﺒﻼﺕ ﻗﺩ ﻻ ﺘﺘﻔـﻕ ﻤـﻊ ﻅـﺭﻭﻑ‬
‫ﺍﻟﺘﺸﻐﻴل ﺍﻟﻔﻌﻠﻴﺔ ‪ ،‬ﻓﻴﺘﻡ ﺍﺴﺘﻌﻤﺎل ﻤﻌﺎﻤﻼﺕ ﺍﻟﺘﺼﺤﻴﺢ ﺍﻟﻜﻠﻴﺔ ﻟﺘﺤﺩﻴﺩ ﺴﻌﺔ ﺤﻤل ﺍﻟﺘﻴﺎﺭ ﻋﻨـﺩ‬
‫ﺘﺸﻐﻴل ﺍﻟﻜﺎﺒل ﻋﻠﻰ ﺍﻟﻅﺭﻭﻑ ﺍﻟﻘﻴﺎﺴﻴﺔ ﺍﻟﻭﺍﺭﺩﺓ ﻓﻰ ﺠﺩﺍﻭل ﺍﻟﻜﺎﺒﻼﺕ ‪ ،‬ﻜﻤﺎ ﻴﻠﻰ ‪:‬‬
‫ﺴﻌﺔ ﺤﻤل ﺍﻟﺘﻴﺎﺭ ﻋﻨﺩ ﺘﺸﻐﻴل ﺍﻟﻜﺎﺒل ﻓﻰ ﺍﻟﻅﺭﻭﻑ ﺍﻟﻘﻴﺎﺴﻴﺔ ﻁﺒﻘﺎﹰ ﻟﻠﻘـﻴﻡ ﺍﻟﻤﺩﺭﺠـﺔ ﻓـﻰ‬
‫ﺠﺩﺍﻭل ﺍﻟﺼﺎﻨﻊ =‬
‫ﺃﻗﺼﻰ ﻗﻴﻤﺔ ﻟﻠﺘﻴﺎﺭ ﺍﻟﻤﻨﺘﻅﺭ ﻤﺭﻭﺭﻩ ﺒﺎﻟﻔﻌل ﻓﻰ ﻜﺎﺒﻼﺕ ﺍﻟﺩﺍﺌﺭﺓ‬
‫ﺃﻗل ﻗﻴﻤﺔ ﻟﻤﻌﺎﻤل ﺍﻟﺘﺼﺤﻴﺢ ﺍﻟﻜﻠﻰ ﻷﻯ ﻤﻥ ﺃﺠﺯﺍﺀ ﺍﻟﻜﺎﺒل ﻋﻨﺩ ﺃﻗﺴﻰ ﻅﺭﻭﻑ ﻟﻠﺘﺸﻐﻴل‬

‫ﻭﺒﺎﻟﺭﺠﻭﻉ ﺇﻟﻰ ﺠﺩﺍﻭل ﺍﻟﻜﺎﺒﻼﺕ ﺒﺎﻟﻤﺠﻠﺩ ﺍﻟﺜﺎﻟﺙ ﻤﻥ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﺒﺎﻟﺠﺩﺍﻭل ﻤﻥ ﻡ‪٤/٣‬‬
‫ﺇﻟﻰ ﻡ‪ ٢٧/٣‬ﻴﺘﻡ ﺇﺨﺘﻴﺎﺭ ﻤﺴﺎﺤﺔ ﻤﻘﻁﻊ ﺍﻟﻤﻭﺼﻼﺕ ﺍﻟﻤﻨﺎﻅﺭﺓ ﻟﻘﻴﻤـﺔ ﺍﻟﺘﻴـﺎﺭ ﺍﻟﻤﺴـﺤﻭﺏ‬
‫ﻭﺍﻟﺘﻰ ﺘﺴﻤﺢ ﺒﺈﻤﺭﺍﺭ ﻫﺫﺍ ﺍﻟﺘﻴﺎﺭ ﻋﻨﺩ ﺍﻟﻅﺭﻭﻑ ﺍﻟﻘﻴﺎﺴﻴﺔ ﺍﻟﻤﺩﺭﺠﺔ ﺒﺎﻟﺠﺩﺍﻭل ﺒﺩﻭﻥ ﺍﻹﺨﻼل‬
‫ﺒﺤﺩﻭﺩ ﺇﺭﺘﻔﺎﻉ ﺩﺭﺠﺔ ﺍﻟﺤﺭﺍﺭﺓ ‪ ،‬ﻭﺒﺎﻟﺘﺎﻟﻰ ﻴﺘﻡ ﻤﻌﺭﻓﺔ ﻤﻌﺎﻤﻼﺕ ﺍﻟﻜﺎﺒـل ﻤﺜـل ﻤﻘﺎﻭﻤـﺔ‬
‫ﺍﻟﻤﻭﺼﻼﺕ ﻟﻜل ﻤﺘﺭ ﻁﻭﻟﻰ ﻤﻥ ﺍﻟﻜﺎﺒل ‪ ،‬ﻭﻫﺒﻭﻁ ﺍﻟﺠﻬﺩ ﻟﻠﻤﺘﺭ ﺍﻟﻁﻭﻟﻰ ﻭﻟﻜل ﺃﻤﺒﻴﺭ ﻤـﻥ‬
‫ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﺎﺭ ﻓﻰ ﺍﻟﻜﺎﺒل ﻋﻨﺩ ﻤﻌﺎﻤل ﻗﺩﺭﺓ ﻤﺤﺩﺩ )ﻏﺎﻟﺒﺎ ‪ ٠.٨‬ﻤﺘﺄﺨﺭ ( ﻭﻤﻨﻬﺎ ﻴﻤﻜﻥ ﺤﺴﺎﺏ‬
‫ﻤﻤﺎﻨﻌﺔ ﺍﻟﻤﺘﺭ ﺍﻟﻁﻭﻟﻰ ﻤﻥ ﺍﻟﻜﺎﺒل ‪.‬‬
‫ﻭﻋﻠﻰ ﺴﺒﻴل ﺍﻟﻤﺜﺎل ﻓﻔﻰ ﺍﻟﻤﺜﺎل ﺍﻟﺘﻭﻀﻴﺤﻰ ﺍﻷﺨﻴﺭ ﻋﺎﻟﻴﻪ ‪ ،‬ﺇﺫﺍ ﻜﺎﻥ ﺃﻗﺼﻰ ﺘﻴﺎﺭ ﻴﻨﺘﻅـﺭ‬
‫ﻤﺭﻭﺭﻩ ﻓﻰ ﺍﻟﻜﺎﺒل ﻫﻭ ‪ ٢٣.٧‬ﺃﻤﺒﻴﺭ‪ ،‬ﻓﻴﻜﻭﻥ ﺍﻟﺘﻴﺎﺭ ﺍﻟﺘﺼﻤﻴﻤﻰ ﻟﻬﺫﺍ ﺍﻟﻜﺎﺒل =‬
‫‪ ٧١.٨٤ = ٠.٣٢٩٩ /٢٣.٧‬ﺃﻤﺒﻴﺭ‬
‫ﻭﻴﻜﻭﻥ ﻤﻘﻁﻊ ﻤﻭﺼﻼﺕ ﺍﻟﻜﺎﺒل ﺫﻯ ﺍﻟﻤﻭﺼﻼﺕ ﺍﻟﻨﺤﺎﺴﻴﺔ ﻭﻤﺎﺩﺓ ﻋﺯل ﺒﻰ ﻓﻰ ﺴﻰ ﻤـﻥ‬
‫ﺍﻟﺠﺩﻭل ﺭﻗﻡ ﻡ‪ ٥/٣‬ﻫﻭ ‪١٦ + ٢٥ × ٣‬ﻤﻡ‪. ٢‬‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻫﺫﺍ ﻭﻴﻤﻜﻥ ﺍﺴﺘﻌﻤﺎل ﻜﺎﺒل ﺫﻯ ﻤﻘﻁﻊ ﻤﻭﺼﻼﺕ ﺃﻜﺒﺭ ﺒﻐﺭﺽ ﺍﻟﺘﻭﻓﻴﺭ ﻓﻰ ﺘﻜﻠﻔﺔ ﺍﻟﻘـﺩﺭﺓ‬
‫ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﺍﻟﻤﻔﻘﻭﺩﺓ ﻓﻰ ﻤﻘﺎﻭﻤﺔ ﺍﻟﻜﺎﺒل ‪ ،‬ﻭﻜﺫﺍ ﻟﻺﻗﻼل ﻤﻥ ﻫﺒﻭﻁ ﺍﻟﺠﻬﺩ ﻓﻰ ﺍﻟﻜﺎﺒل ‪ ،‬ﻜﻤﺎ‬
‫ﻴﺘﻴﺢ ﺫﻟﻙ ﻟﻠﻜﺎﺒل ﻤﻘﺎﺒﻠﺔ ﺯﻴﺎﺩﺓ ﺍﻟﺤﻤل ﺍﻟﺫﻯ ﻴﻤﻜﻥ ﻟﻠﺩﺍﺌﺭﺓ ﺘﻐﺫﻴﺘﻪ ﺒﺩﻭﻥ ﻀﺭﻭﺭﺓ ﺍﺴـﺘﺒﺩﺍل‬
‫ﺍﻟﻜﺎﺒل ﺒﺂﺨﺭ ﺫﻯ ﻤﻘﻁﻊ ﻤﻭﺼﻼﺕ ﺃﻜﺒﺭ ‪.‬‬

‫ﺤﺴﺎﺏ ﻫﺒﻭﻁ ﺍﻟﺠﻬﺩ ﻓﻰ ﺍﻟﺩﺍﺌﺭﺓ‬ ‫‪٥-٥‬‬


‫ﺒﺎﺴﺘﻌﻤﺎل ﻤﻌﺎﻤﻼﺕ ﺍﻟﻜﺎﺒل ﺍﻟﻤﺨﺘﺎﺭ ﻴﻜﻭﻥ ﻫﺒﻭﻁ ﺍﻟﺠﻬﺩ ﻟﻠﻁﻭل ﺍﻟﻜﻠﻰ ﻟﻜـﺎﺒﻼﺕ ﺍﻟـﺩﺍﺌﺭﺓ‬
‫ﻤﺴﺎﻭﻴﺎ ﻟﻤﺎ ﻴﻠﻰ ‪:‬‬
‫ﻫﺒﻭﻁ ﺍﻟﺠﻬﺩ ﻓﻰ ﺍﻟﺩﺍﺌﺭﺓ = )ﻫﺒﻭﻁ ﺍﻟﺠﻬﺩ ﻓﻰ ﺍﻟﻜﺎﺒل ﻟﻜل ﻤﺘﺭ ﻁﻭﻟﻰ ﻭﻟﻜل ﺃﻤﺒﻴـﺭ ﻤـﻥ‬
‫ﺘﻴﺎﺭ ﺍﻟﻜﺎﺒل( × ﻁﻭل ﺍﻟﻜﺎﺒل )ﺒﺎﻟﻤﺘﺭ( × ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﺎﺭ ﻓﻰ ﺍﻟﻜﺎﺒل )ﺒﺎﻷﻤﺒﻴﺭ( ﺤﻴﺙ ﺘﺅﺨـﺫ‬
‫ﻗﻴﻤﺔ ﻫﺒﻭﻁ ﺍﻟﺠﻬﺩ ﻟﻜل ﻤﺘﺭ ﻁﻭﻟﻰ ﻭﻟﻜل ﺃﻤﺒﻴﺭ ﻤﻥ ﺘﻴﺎﺭ ﺍﻟﻜﺎﺒل ﻤﻥ ﺍﻟﺠـﺩﻭل ﺍﻟﻤﻨﺎﺴـﺏ‬
‫ﻟﻁﺒﻴﻌﺔ ﺍﻟﻜﺎﺒل ﻤﻥ ﺒﻴﻥ ﺍﻟﺠﺩﺍﻭل ﺭﻗﻡ ﻡ‪ ٥/٣‬ﺇﻟﻰ ﻡ‪ ١٣/٣‬ﺒﺎﻟﻤﻠﺤﻕ ﺍﻟﺜﺎﻟﺙ ﻓـﻰ ﺍﻟﺠـﺯﺀ‬
‫ﺍﻟﺜﺎﻟﺙ ﻤﻥ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻯ ‪.‬‬
‫ﻭﺒﻌﺩ ﺤﺴﺎﺏ ﻫﺒﻭﻁ ﺍﻟﺠﻬﺩ ﻓﻰ ﺍﻟﺩﺍﺌﺭﺓ ﺘﺘﻡ ﻤﺭﺍﺠﻌﺔ ﺍﻟﻬﺒﻭﻁ ﺍﻟﻜﻠﻰ ﻓﻰ ﺍﻟﺠﻬﺩ ﻤﻥ ﻨﻘﻁـﺔ‬
‫ﺘﻐﺫﻴﺔ ﺍﻟﻤﺒﻨﻰ ﺒﺎﻟﻜﻬﺭﺒﺎﺀ ﺤﺘﻰ ﺃﺒﻌﺩ ﺤﻤل ﻓﻰ ﺃﻋﻠﻰ ﺩﻭﺭ ﻓﻰ ﺍﻟﻤﺒﻨﻰ ‪ ،‬ﻭﻟﻤﺎ ﻜﺎﻥ ﺍﻟﻬﺒـﻭﻁ‬
‫ﺍﻟﻜﻠﻰ ﻟﻠﺠﻬﺩ ﻋﻨﺩ ﺍﻟﺤﻤل ﻴﺠﺏ ﺃﻻ ﻴﺘﺠﺎﻭﺯ ‪ ٪ ٢.٥‬ﻓﻴﺠـﺏ )ﺇﻥ ﻟـﺯﻡ( ﺘﻌـﺩﻴل ﻤﻘﻁـﻊ‬
‫ﻤﻭﺼﻼﺕ ﺍﻟﻜﺎﺒل ﻓﻰ ﺍﻟﺩﺍﺌﺭﺓ ﻤﻭﻀﻭﻉ ﺍﻟﺘﺼﻤﻴﻡ ‪ ،‬ﻭﻜﺫﺍ ﻤﻘـﺎﻁﻊ ﻤﻭﺼـﻼﺕ ﻜـﺎﺒﻼﺕ‬
‫ﺍﻟﺩﻭﺍﺌﺭ ﺍﻟﺘﻰ ﺘﻐﺫﻯ ﻟﻭﺤﺔ ﺍﻟﺘﻭﺯﻴﻊ ﺍﻟﺘﻰ ﺘﺨﺭﺝ ﻤﻨﻬﺎ ﺍﻟﺩﺍﺌﺭﺓ ﻤﻭﻀﻭﻉ ﺍﻟﺘﺼـﻤﻴﻡ ‪ ،‬ﺤﺘـﻰ‬
‫ﻴﻤﻜﻥ ﺍﻻﻟﺘﺯﺍﻡ ﺒﺎﻟﺤﺩ ﺍﻟﻤﺴﻤﻭﺡ ﺒﻪ ﻟﻠﻬﺒﻭﻁ ﺍﻟﻜﻠﻰ ﻓﻰ ﺍﻟﺠﻬﺩ‪.‬‬

‫ﺤﺴﺎﺏ ﺘﻴﺎﺭﺍﺕ ﺍﻟﻘﺼﺭ‬ ‫‪٦-٥‬‬


‫ﻴﺠﺏ ﻁﺒﻘﺎ ﻟﻠﻭﺍﺭﺩ ﻓﻰ ﺍﻟﺒﻨﺩ ‪ ٨/٦‬ﺒﺎﻟﺼﻔﺤﺔ ‪ ٢٩٣‬ﻤﻥ ﺍﻟﺠﺯﺀ ﺍﻟﺜﺎﻨﻰ ﻤﻥ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻯ‬
‫ﺤﺴﺎﺏ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﺍﻟﺫﻯ ﻴﻨﺘﻅﺭ ﻤﺭﻭﺭﻩ ﻓﻰ ﺍﻟﺩﺍﺌﺭﺓ ‪ ،‬ﺃﻭ ﺠﺯﺀ ﻤﻨﻬـﺎ ‪ ،‬ﻭﺫﻟـﻙ ﻨﺘﻴﺠـﺔ‬
‫ﻟﺤﺩﻭﺙ ﻗﺼﺭ ﺜﻼﺜﻰ ﺍﻷﻁﻭﺍﺭ ﻗﺭﺏ ﺒﺩﺍﻴﺘﻬﺎ ﻋﻨﺩ ﺨﺭﻭﺠﻬﺎ ﻤﻥ ﻟﻭﺤﺔ ﺍﻟﺘﻭﺯﻴـﻊ ‪ ،‬ﻭﺫﻟـﻙ‬
‫ﺒﻐﺭﺽ‪:‬‬
‫ﺇﺨﺘﻴﺎﺭ ﺴﻌﺔ ﺍﻟﻘﻁﻊ ﺍﻟﻤﻨﺎﺴﺒﺔ ﻟﻨﺒﻴﻁﺔ ﻭﻗﺎﻴﺔ ﻤﻭﺼﻼﺕ ﻫﺫﻩ ﺍﻟﺩﺍﺌﺭﺓ ‪.‬‬ ‫)ﺃ(‬
‫)ﺏ( ﺘﺤﺩﻴﺩ ﻨﻭﻉ ﻭﺴﺭﻋﺔ ﻗﻁﻊ ﻭﺘﻴﺎﺭ ﺘﺸﻐﻴل ﻨﺒﻴﻁﺔ ﺍﻟﻭﻗﺎﻴﺔ ﻀﺩ ﻗﺼﺭ ﺍﻟﺩﺍﺌﺭﺓ ﻟﻠﺘﻨﺴـﻴﻕ‬
‫ﻤﻊ ﺍﻤﻜﺎﻨﻴﺔ ﺼﻤﻭﺩ ﻤﻘﻁﻊ ﻤﻭﺼﻼﺕ ﺍﻟﺩﺍﺌﺭﺓ‪.‬‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻭﺘﺤﺩﺩ ﺍﻟﻘﻴﻤﺔ ﺍﻟﻌﺩﺩﻴﺔ ﻟﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﺜﻼﺜﻰ ﺍﻷﻁﻭﺍﺭ ‪ Is.c‬ﻤﻥ ﺍﻟﻤﻌﺎﺩﻟﺔ )‪:(٦-٥‬‬
‫= ‪Is.c.‬‬ ‫= ‪Us / Zf‬‬ ‫‪1.05 Un / Zf‬‬ ‫)‪(5-6‬‬
‫ﺤﻴﺙ‪:‬‬
‫‪ :Us‬ﺠﻬﺩ ﺍﻟﻁﻭﺭ ﻋﻨﺩ ﺃﻁﺭﺍﻑ ﻤﺼﺩﺭ ﺍﻟﺘﻐﺫﻴﺔ ﺒﺎﻟﻔﻭﻟﺕ ‪ ،‬ﻓﻲ ﺤﺎﻟﺔ ﻋﺩﻡ ﻭﺠﻭﺩ ﺤﻤل‬
‫‪ :Un‬ﺠﻬﺩ ﺍﻟﻁﻭﺭ ﻋﻨﺩ ﺃﻁﺭﺍﻑ ﻤﺼﺩﺭ ﺍﻟﺘﻐﺫﻴﺔ ﺒﺎﻟﻔﻭﻟﺕ ‪ ،‬ﻓﻲ ﺤﺎﻟﺔ ﻭﺠﻭﺩ ﺍﻟﺤﻤل‬
‫‪ :Zf‬ﺍﻟﻘﻴﻤﺔ ﺍﻟﻌﺩﺩﻴﺔ ﻟﻠﻤﻌﺎﻭﻗﺔ ﺍﻟﻜﻠﻴﺔ ﻟﻠﻁﻭﺭ ﻤﻥ ﻤﺼﺩﺭ ﺍﻟﺘﻐﺫﻴﺔ ﺤﺘﻰ ﻤﻭﻗﻊ ﺍﻟﻘﺼـﺭ ‪،‬‬
‫ﻭﺍﻟﺘﻰ ﺘﺴﺎﻭﻯ ﺍﻟﻘﻴﻤﺔ ﺍﻟﻌﺩﺩﻴﺔ ﻟﻠﻤﺠﻤﻭﻉ ﺍﻟﺠﺒﺭﻯ ﻟﻠﻤﻌﺎﻭﻗـﺎﺕ ﺒﺩﺍﻴـﺔ ﻤـﻥ ﻤﻌﺎﻭﻗـﺔ‬
‫ﺍﻟﻤﺼﺩﺭ ﺫﻯ ﺍﻟﺠﻬﺩ ﺍﻟﻤﺘﻭﺴﻁ ﺜﻡ ﻤﺤﻭل ﺘﻐﺫﻴﺔ ﺍﻟﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ ‪ ،‬ﻭﺍﻟﺩﺍﺌﺭﺓ ﺍﻟﺭﺌﻴﺴـﻴﺔ‬
‫ﻟﺘﻐﺫﻴﺔ ﺍﻟﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ‪ ،‬ﻭﻗﻀﺒﺎﻥ ﺍﻟﺘﻭﺯﻴﻊ ﻭﻜﺎﺒﻼﺕ ﺍﻟﺩﻭﺍﺌﺭ ﺍﻟﻔﺭﻋﻴﺔ ﻭﻤﻌﺩﺍﺕ ﺍﻟﻘﻁﻊ‬
‫ﻭﺍﻟﺘﻭﺼﻴل ﻓﻰ ﺍﻟﺩﺍﺌﺭﺓ ﺍﻟﺭﺌﻴﺴﻴﺔ ﻭﺍﻟﺩﻭﺍﺌﺭ ﺍﻟﻔﺭﻋﻴﺔ ﺤﺘﻰ ﻤﻭﻗﻊ ﺍﻟﻘﺼﺭ‪.‬‬
‫ﻭﻓﻴﻤﺎ ﻴﻠﻰ ﺨﻁﻭﺍﺕ ﺤﺴﺎﺏ ﺍﻟﻤﻌﺎﻭﻗﺎﺕ ﺍﻟﻤﺨﺘﻠﻔﺔ ﺍﻟﺩﺍﺨﻠﺔ ﻓﻰ ﺤﺴﺎﺏ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ‪.‬‬

‫‪ ١-٦-٥‬ﺘﺤﺩﻴﺩ ﻗﻴﻡ ﺍﻟﻤﻌﺎﻭﻗﺎﺕ ﺍﻟﺩﺍﺨﻠﺔ ﻓﻰ ﺤﺴﺎﺏ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ‬


‫ﺍﻟﻤﻌﺎﻭﻗﺔ ﺍﻟﻤﻜﺎﻓﺌﺔ ﻟﻤﺼﺩﺭ ﺍﻟﺘﻐﺫﻴﺔ ﺫﻯ ﺍﻟﺠﻬﺩ ﺍﻟﻤﺘﻭﺴﻁ‬ ‫)ﺃ(‬
‫ﻴﻤﻜﻥ ﻋﺎﺩﺓ ﺇﻫﻤﺎل ﻫﺫﻩ ﺍﻟﻤﻌﺎﻭﻗﺔ ﻜﻠﻴﺎ ﻟﺼﻐﺭﻫﺎ ‪ ،‬ﻭﻟﻜﻥ ﻟﺯﻴـﺎﺩﺓ ﺍﻟﺩﻗـﺔ ﺘﺴـﺘﻌﻤل‬
‫ﺍﻟﺼﻴﻐﺔ ﺍﻟﺘﺎﻟﻴﺔ ﻓﻰ ﺤﺴﺎﺏ ﻤﺭﻜﺒﺎﺕ ﻫﺫﻩ ﺍﻟﻤﻌﺎﻭﻗﺔ ﺒﻌﺩ ﺘﺤﻭﻴﻠﻬﺎ ﺇﻟﻰ ﻨﺎﺤﻴﺔ ﺍﻟﺠﻬـﺩ‬
‫ﺍﻟﻤﻨﺨﻔﺽ ‪:‬‬
‫)‪ (١‬ﻋﺎﺩﺓ ﺘﻬﻤل ﻗﻴﻤﺔ ﻤﺭﻜﺒﺔ ﺍﻟﻤﻘﺎﻭﻤﺔ ﺍﻟﻤﻜﺎﻓﺌﺔ ‪ Rs eq‬ﻟﻀﺌﺎﻟﺘﻬﺎ‬
‫)‪ (٢‬ﺘﺤﺴﺏ ﻗﻴﻤﺔ ﻤﺭﻜﺒﺔ ﺍﻟﻤﻤﺎﻨﻌﺔ ﺍﻟﻤﻜﺎﻓﺌﺔ ‪ Xseq‬ﺒـﺎﻟﻤﻠﻠﻲ ﺃﻭﻡ ﻤـﻥ ﺍﻟﻤﻌﺎﺩﻟـﺔ‬
‫)‪ (٧-٥‬ﺍﻟﺘﺎﻟﻴﺔ ‪:‬‬
‫‪Xs eq = 3 Us2 / S.C. kVA = 3 (1.05 x 220)2 / S.C.‬‬ ‫‪kVA‬‬ ‫)‪(5-7‬‬
‫ﺤﻴﺙ ‪ S.C. kVA‬ﻫﻰ ﺴﻌﺔ ﺍﻟﻘﺼﺭ ﻟﻤﻌﺩﺍﺕ ﺍﻟﻭﻗﺎﻴﺔ ﻋﻨﺩ ﺃﻁﺭﺍﻑ ﺍﻟﺘﻐﺫﻴﺔ ﻋﻠﻰ ﺍﻟﺠﻬـﺩ‬
‫ﺍﻟﻤﺘﻭﺴﻁ ﻁﺒﻘﺎ ﻟﻤﺎ ﺘﺤﺩﺩﻩ ﺸﺭﻜﺔ ﺘﻭﺯﻴﻊ ﺍﻟﻜﻬﺭﺒﺎﺀ ﺍﻟﻤﺨﺘﺼﺔ ‪.‬‬
‫ﺘﻜﻭﻥ ﻗﻴﻤﺔ ﻜل ﻤﻥ ‪ Xs eq ، Rs eq‬ﺒﺎﻟﻤﻴﻠﻠﻰ ﺃﻭﻡ ﻭﻁﺒﻘﺎ ﻟﺴﻌﺎﺕ ﺍﻟﻘﺼﺭ ﺍﻷﻜﺜـﺭ ﺘـﺩﺍﻭﻻ‬
‫ﻜﻤﺎ ﻴﻠﻰ‪:‬‬
‫‪Xseq‬‬ ‫‪Rseq‬‬ ‫‪S.C. MVA‬‬
‫‪٠.٦٣٣‬‬ ‫‪٠.٠٩٥‬‬ ‫‪٢٥٠‬‬
‫‪٠.٤٥١٥‬‬ ‫‪٠.٠٦٧٥‬‬ ‫‪٣٥٠‬‬
‫‪٠.٣١٦‬‬ ‫‪٠.٠٤٧‬‬ ‫‪٥٠٠‬‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫)ﺏ( ﻤﺤﻭل ﺘﻐﺫﻴﺔ ﺍﻟﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ‬


‫ﺘﻌﻁﻰ ﺍﻟﻘﻴﻤﺔ ﺍﻟﻌﺩﺩﻴﺔ ﻟﻤﻌﺎﻭﻗﺔ ﺍﻟﻤﺤﻭل ﻋﺎﺩﺓ ﻋﻠﻰ ﺒﻁﺎﻗﺔ ﺒﻴﺎﻨـﺎﺕ ﺍﻟﻤﺤـﻭل ﻓـﻰ‬
‫ﺼﻭﺭﺓ ﻨﺴﺒﺔ ﻫﺒﻭﻁ ﺍﻟﺠﻬﺩ ﻋﻠﻰ ﺍﻟﻤﻌﺎﻭﻗﺔ ﻋﻨﺩ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل ﺇﻟﻰ ﺍﻟﺠﻬـﺩ ﺍﻟﻤﻘـﻨﻥ‬
‫ﻨﺎﺤﻴﺔ ﺍﻟﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ ‪ Us.c‬ﻭﺘﺘﺭﺍﻭﺡ ﻗﻴﻤﺘﻬﺎ ﻋﺎﺩﺓ ﺒﻴﻥ ‪ ٠.٠٧ ، ٠.٠٤‬ﻁﺒﻘـﺎ‬
‫ﻟﻠﺤﻤل ﺍﻟﻤﻘﻨﻥ ﻟﻠﻤﺤﻭل ‪ ،‬ﻭﺒﺎﻟﺘﺎﻟﻰ ﺘﺤﺴﺏ ﺍﻟﻘﻴﻤﺔ ﺍﻟﻌﺩﺩﻴﺔ ﻟﻠﻤﻌﺎﻭﻗﺔ ﺍﻟﻤﻜﺎﻓﺌﺔ ﻟﻠﻤﺤﻭل‬
‫ﺒﺎﻟﻤﻠﻠﻰ ﺃﻭﻡ ﻤﻨﺴﻭﺒﺔ ﺇﻟﻰ ﻨﺎﺤﻴﺔ ﺍﻟﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ ‪ Zs.c‬ﻜﻤﺎ ﻓﻲ ﺍﻟﻤﻌﺎﺩﻟﺔ )‪:(٨-٥‬‬

‫‪Z s .c = 3‬‬
‫‪U s2‬‬
‫‪U s .c = 3‬‬
‫‪(1.05 × 220 )2 U‬‬
‫)‪(5-8‬‬
‫‪kVA × 1000‬‬ ‫‪kVA × 1000‬‬
‫‪s .c‬‬

‫ﺤﻴﺙ‪:‬‬
‫‪ kVA‬ﻫﻰ ﺍﻟﻘﺩﺭﺓ ﺍﻟﻤﻘﻨﻨﺔ ﻟﻠﻤﺤﻭل ) ﻙ‪.‬ﻑ‪.‬ﺃ (‬
‫ﻭﻴﻤﻜﻥ ﺘﻘﺩﻴﺭ ﻗﻴﻤﺔ ﺍﻟﻤﻘﺎﻭﻤﺔ ﺍﻟﻤﻜﺎﻓﺌﺔ ﻟﻠﻤﺤﻭل ﺒﺎﻟﻤﻠﻠﻰ ﺃﻭﻡ ﻤﺤﻭﻟﺔ ﺇﻟﻰ ﻨﺎﺤﻴـﺔ ﺍﻟﺠﻬـﺩ‬
‫ﺍﻟﻤﻨﺨﻔﺽ ﻤﻥ ﻭﺍﻗﻊ ﻗﻴﻤﺔ ﺍﻟﻔﻘﺩ ﻓﻰ ﺍﻟﻨﺤﺎﺱ ﻭﻗﻴﻤﺔ ﺍﻟﺘﻴﺎﺭ ﻨﺎﺤﻴﺔ ﺍﻟﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ ﻋﻨـﺩ‬
‫ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل ﻟﻠﻤﺤﻭل ‪ ،‬ﻜﻤﺎ ﻓﻲ ﺍﻟﻤﻌﺎﺩﻟﺔ )‪: (٩-٥‬‬
‫= ‪Rs.c‬‬ ‫) ‪1000 P cu / (3 I22‬‬ ‫)‪(5-9‬‬

‫ﺤﻴﺙ‪:‬‬
‫‪ I2 ، Pco‬ﻫﻤﺎ ﻗﻴﻤﺘﺎ ﺍﻟﻔﻘﺩ ﻓﻰ ﺍﻟﻨﺤﺎﺱ ﻓﻰ ﺍﻟﻤﺤﻭل ﺒﺎﻟﻭﺍﺕ ‪ ،‬ﻭﺘﻴﺎﺭ ﻨﺎﺤﻴـﺔ ﺍﻟﺠﻬـﺩ‬
‫ﺍﻟﻤﻨﺨﻔﺽ ﺒﺎﻷﻤﺒﻴﺭﻋﻠﻰ ﺍﻟﺘﻭﺍﻟﻰ ﻋﻨﺩ ﺍﻟﺤﻤل ﺍﻟﻜﺎﻤل ﻟﻠﻤﺤﻭل‪.‬‬
‫ﻭﺒﻌﺩ ﺤﺴﺎﺏ ﻗﻴﻤﺔ ﺍﻟﻤﻘﺎﻭﻤﺔ ﺍﻟﻤﻜﺎﻓﺌﺔ ﻟﻠﻤﺤﻭل ﻴﻤﻜﻥ ﺍﺴﺘﻨﺘﺎﺝ ﻗﻴﻤﺔ ﻤﻤﺎﻨﻌﺘﻪ ﺍﻟﻤﻜﺎﻓﺌﺔ ﻤﻥ‬
‫ﺍﻟﻤﻌﺎﻭﻗﺔ ‪ ،Zs.c‬ﻜﻤﺎ ﻓﻲ ﺍﻟﻤﻌﺎﺩﻟﺔ )‪:(١٠-٥‬‬
‫‪2‬‬ ‫‪2‬‬
‫) ‪X s .c = ( Z s .c − Rs.c‬‬ ‫)‪(5-10‬‬
‫ﻫﺫﺍ ﻭﻴﻌﻁﻰ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻯ ﻓﻰ ﺍﻟﺠﺩﻭل ﺭﻗﻡ )‪ (٩/٦‬ﺒﺎﻟﺼﻔﺤﺔ ‪ ٢٩٦‬ﻤـﻥ ﺍﻟﻤﺠﻠـﺩ‬
‫ﺍﻟﺜﺎﻨﻰ ﻗﻴﻤﺎ ﺇﺴﺘﺭﺸﺎﺩﻴﺔ ﻟﻤﺭﻜﺒﺘﻰ ﺍﻟﻤﻘﺎﻭﻤﺔ ﻭﺍﻟﻤﻤﺎﻨﻌﺔ ﺍﻟﻤﻜﺎﻓﺌﺘﻴﻥ ﻟﻠﻤﺤﻭل ﺒـﺎﻟﻤﻠﻠﻰ ﺃﻭﻡ‬
‫ﻤﺤﻭﻟﺘﻴﻥ ﺇﻟﻰ ﻨﺎﺤﻴﺔ ﺍﻟﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ ‪ ،‬ﻭﻴﻤﻜﻥ ﺍﺴﺘﻌﻤﺎل ﻫﺫﻩ ﺍﻟﻘﻴﻡ ﺇﺫﺍ ﺨﻠـﺕ ﺒﻁﺎﻗـﺔ‬
‫ﺍﻟﺒﻴﺎﻨﺎﺕ ﻤﻥ ﻗﻴﻤﺔ ‪ Us.c‬ﺃﻭ ﻤﻥ ﺍﻟﻔﻘﺩ ﻓﻰ ﺍﻟﻨﺤﺎﺱ‪.‬‬
‫ﻭﻓﻴﻤﺎ ﻴﻠﻰ ﺠﺯﺀ ﻤﻥ ﻫﺫﺍ ﺍﻟﺠﺩﻭل ﻟﺒﻌﺽ ﺍﻟﻤﺤﻭﻻﺕ ﺍﻟﺘﻰ ﻴﻜﺜﺭ ﺇﺴﺘﻌﻤﺎﻟﻬﺎ‪.‬‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺠﺩﻭل ﻤﻌﺎﻤﻼﺕ ﺒﻌﺽ ﺍﻟﻤﺤﻭﻻﺕ ﺍﻟﺘﻲ ﻴﻜﺜﺭ ﺍﺴﺘﻌﻤﺎﻟﻬﺎ‬

‫ﺍﻟﻤﻌﺎﻭﻗﺔ ﺍﻟﻤﻜﺎﻓﺌﺔ‬ ‫ﺍﻟﻤﻤﺎﻨﻌﺔ ﺍﻟﻤﻜﺎﻓﺌﺔ‬ ‫ﺍﻟﻤﻘﺎﻭﻤﺔ ﺍﻟﻤﻜﺎﻓﺌﺔ‬ ‫ﻫﺒﻭﻁ ﺍﻟﺠﻬﺩ‬ ‫ﻗﺩﺭﺓ ﺍﻟﻤﺤﻭل‬
‫)‪(Zs.c‬‬ ‫)‪(Xs.c‬‬ ‫)‪(Rs.c‬‬ ‫)‪(Us.c‬‬ ‫)‪(kVA‬‬
‫)ﻤﻠﻠﻰ ﺃﻭﻡ(‬ ‫)ﻤﻠﻠﻰ ﺃﻭﻡ(‬ ‫)ﻤﻠﻠﻰ ﺃﻭﻡ(‬
‫‪١٢٨‬‬ ‫‪١٠٧‬‬ ‫‪٧٠.٣‬‬ ‫‪٠.٠٤‬‬ ‫‪٥٠‬‬
‫‪٦٤‬‬ ‫‪٥٧.٥‬‬ ‫‪٢٨‬‬ ‫‪٠.٠٤‬‬ ‫‪١٠٠‬‬
‫‪٢٥.٦‬‬ ‫‪٢٤.٢‬‬ ‫‪٨.٣‬‬ ‫‪٠.٠٤‬‬ ‫‪٢٥٠‬‬
‫‪١٢.٨‬‬ ‫‪١٢.٣‬‬ ‫‪٣.٥٢‬‬ ‫‪٠.٠٤‬‬ ‫‪٥٠٠‬‬
‫‪٩‬‬ ‫‪٨.٦٣‬‬ ‫‪٢.٥٥‬‬ ‫‪٠.٠٤٥‬‬ ‫‪٨٠٠‬‬
‫‪٨‬‬ ‫‪٧.٧٦‬‬ ‫‪١.٩٤‬‬ ‫‪٠.٠٥‬‬ ‫‪١٠٠٠‬‬

‫ﻭﻴﺠﺏ ﻤﻼﺤﻅﺔ ﺃﻨﻪ ﻓﻰ ﺤﺎﻟﺔ ﺍﺴﺘﺨﺩﺍﻡ ﻋﺩﺩ )ﻥ( ﻤـﻥ ﺍﻟﻤﺤـﻭﻻﺕ ﺍﻟﻤﺘﻤﺎﺜﻠـﺔ ﻋﻠـﻰ‬
‫ﺍﻟﺘﻭﺍﺯﻯ ﻓﻴﺠﺏ ﻗﺴﻤﺔ ﻤﻌﺎﻤﻼﺕ ﺍﻟﻤﺤﻭل ﻋﻠﻰ ﺍﻟﻌﺩﺩ )ﻥ( ﻟﻠﺤﺼﻭل ﻋﻠـﻰ ﻤﻌـﺎﻤﻼﺕ‬
‫ﻤﺠﻤﻭﻋﺔ ﺍﻟﻤﺤﻭﻻﺕ ‪.‬‬
‫)ﺕ( ﻗﻭﺍﻁﻊ ﺍﻟﺩﺍﺌﺭﺓ‬
‫ﻓﻰ ﺤﺎﻟﺔ ﻋﺩﻡ ﻭﺠﻭﺩ ﺒﻴﺎﻨﺎﺕ ﻤﻥ ﺍﻟﺸﺭﻜﺔ ﺍﻟﺼﺎﻨﻌﺔ ﻴﻤﻜﻥ ﺇﻫﻤﺎل ﺍﻟﻤﻘﺎﻭﻤﺔ ﺍﻟﻤﻜﺎﻓﺌـﺔ‬
‫ﻟﻠﻘﺎﻁﻊ ﻭﺍﻋﺘﺒﺎﺭ ﺍﻟﻤﻤﺎﻨﻌﺔ ﺍﻟﻤﻜﺎﻓﺌﺔ ﻓﻰ ﺤﺩﻭﺩ ‪ ٠.١٥‬ﻤﻠﻠﻰ ﺃﻭﻡ ‪.‬‬
‫)ﺙ( ﺍﻟﻜﺎﺒﻼﺕ ﻭﺍﻟﻤﻭﺼﻼﺕ‬
‫ﺘﺘﻤﻴﺯ ﻜﺎﺒﻼﺕ ﺍﻟﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ ﺒﺄﻥ ﻤﻘﺎﻭﻤﺘﻬﺎ ﺃﻜﺒﺭ ﻤﻥ ﻤﻤﺎﻨﻌﺘﻬـﺎ ﺒﺤﻴـﺙ ﺘﻬﻤـل‬
‫ﻋﺎﺩﺓ ﺍﻟﻤﻤﺎﻨﻌﺔ ﻤﻘﺎﺭﻨﺔ ﺒﺎﻟﻤﻘﺎﻭﻤﺔ ﻓﻰ ﺤـﺎﻻﺕ ﻜـﺎﺒﻼﺕ ﺍﻟﺠﻬـﺩ ﺍﻟﻤـﻨﺨﻔﺽ ﺫﺍﺕ‬
‫ﺍﻟﻤﻭﺼﻼﺕ ﺒﻤﻘﻁﻊ ﺃﻗل ﻤﻥ ‪ ٢٥‬ﻤﻡ‪ ، ٢‬ﻓﻰ ﺤﻴﻥ ﺘﺅﺨﺫ ﻗﻴﻤﺔ ﺍﻟﻤﻤﺎﻨﻌﺔ ﻓﻰ ﺤـﺩﻭﺩ‬
‫‪ ٠.٠٧‬ﻤﻠﻠﻰ ﺃﻭﻡ ﺒﻴﻥ ﻤﻭﺼل ﺍﻟﻁﻭﺭ ﻭﺨﻁ ﺍﻟﺘﻌﺎﺩل ﻟﻜل ﻤﺘﺭ ﻁﻭﻟﻰ ﻤـﻥ ﺍﻟﻜﺎﺒـل‬
‫ﺜﻼﺜﻰ ﺍﻷﻁﻭﺍﺭ ‪ ،‬ﻭﻓﻰ ﺤﺩﻭﺩ ‪ ٠.١٥‬ﻤﻠﻠﻰ ﺃﻭﻡ ﺒﻴﻥ ﻤﻭﺼﻠﻰ ﺍﻟﻜﺎﺒل ﺃﺤﺎﺩﻯ ﺍﻟﻁﻭﺭ‬
‫ﻟﻜل ﻤﺘﺭ ﻁﻭﻟﻰ ﻤﻥ ﺍﻟﻜﺎﺒل‪.‬‬
‫ﺒﺎﻟﻤﻠﻠﻰ ﺃﻭﻡ ﻟﻜل ﻤﺘـﺭ ﻁـﻭﻟﻰ ﻤـﻥ ﺍﻟﻤﻌﺎﺩﻟـﺔ‬ ‫ﻭﺘﺤﺴﺏ ﻗﻴﻤﺔ ﻤﻘﺎﻭﻤﺔ ﺍﻟﻤﻭﺼﻼﺕ‬
‫)‪:(١١-٥‬‬
‫‪Req = ρ / A‬‬ ‫)‪(5-11‬‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺤﻴﺙ‪:‬‬
‫‪ ρ‬ﻫﻰ ﺍﻟﻤﻘﺎﻭﻤﺔ ﺍﻟﻨﻭﻋﻴﺔ ﻟﻠﻤﺎﺩﺓ ﺍﻟﻤﺼﻨﻭﻉ ﻤﻨﻬﺎ ﺍﻟﻤﻭﺼل ‪ ،‬ﻭﺘﺅﺨﺫ ﻗﻴﻤﺘﻬﺎ ﻋﻨـﺩﻤﺎ‬
‫ﺘﻜﻭﻥ ﺩﺭﺠﺔ ﺤﺭﺍﺭﺓ ﺍﻟﻤﻭﺼل ‪ ٧٠‬ﺩﺭﺠﺔ ﻤﺌﻭﻴﺔ ﻜﻤﺎ ﻴﻠﻰ ‪:‬‬
‫ﻟﻠﻨﺤﺎﺱ ﺘﺴﺎﻭﻯ ‪ ٢١‬ﻤﻠﻠﻰ ﺃﻭﻡ ‪ .‬ﻤﻡ‪ ٢‬ﻟﻠﻤﺘﺭ ﺍﻟﻁﻭﻟﻰ ﻤﻥ ﺍﻟﻤﻭﺼل ‪.‬‬
‫ﻭﻟﻸﻟﻭﻤﻨﻴﻭﻡ ﺘﺴﺎﻭﻯ ‪ ٣٣‬ﻤﻠﻠﻰ ﺃﻭﻡ ‪ .‬ﻤﻡ‪ ٢‬ﻟﻠﻤﺘﺭ ﺍﻟﻁﻭﻟﻰ ﻤﻥ ﺍﻟﻤﻭﺼل‪.‬‬
‫ﻭﺤﻴﺙ‪:‬‬
‫‪ A‬ﻫﻰ ﻤﺴﺎﺤﺔ ﻤﻘﻁﻊ ﺍﻟﻤﻭﺼل ﺒﺎﻟﻤﻠﻠﻴﻤﺘﺭ ﺍﻟﻤﺭﺒﻊ‪.‬‬
‫ﻭﻓﻰ ﺤﺎﻟﺔ ﺍﺴﺘﻌﻤﺎل ﻋﺩﺓ ﻤﻭﺼﻼﺕ ﻤﺘﻤﺎﺜﻠﺔ ﻋﻠﻰ ﺍﻟﺘﻭﺍﺯﻯ ﻓـﻰ ﺍﻟـﺩﺍﺌﺭﺓ‪ ،‬ﺘﻜـﻭﻥ‬
‫ﺍﻟﻤﻘﺎﻭﻤﺔ ﺍﻟﻤﻜﺎﻓﺌﺔ ﻤﺴﺎﻭﻴﺔ ﻟﻤﻘﺎﻭﻤﺔ ﺍﻟﻤﻭﺼـل ﺍﻟﻭﺍﺤـﺩ ﻤﻘﺴـﻭﻤﺔ ﻋﻠـﻰ ﻋـﺩﺩ‬
‫ﺍﻟﻤﻭﺼﻼﺕ ‪.‬‬
‫)ﺠ( ﻤﺠﺎﺭﻯ ﻗﻀﺒﺎﻥ ﺍﻟﺘﻭﺯﻴﻊ ﺍﻟﺠﺎﻫﺯﺓ‬
‫ﺘﺴﺘﻌﻤل ﻫﺫﻩ ﺍﻟﻘﻀﺒﺎﻥ ﺍﻟﺠﺎﻫﺯﺓ ﺃﺤﻴﺎﻨﺎﹰ ﻟﻠﺘﻭﺼﻴل ﺒﺩﻻ ﻤﻥ ﺍﻟﻜﺎﺒﻼﺕ ﺍﻟﻤﺘﻌـﺩﺩﺓ ﺫﺍﺕ‬
‫ﺍﻟﻤﻘﻁﻊ ﺍﻟﻜﺒﻴﺭ )ﻭﻋﻠﻰ ﺍﻷﺨﺹ ﻓﻰ ﺩﺍﺌﺭﺓ ﺍﻟﺘﻐﺫﻴﺔ ﺍﻟﺭﺌﻴﺴﻴﺔ ﺍﻟﻌﻠﻴﺎ ﻋﻨﺩ ﺍﻟﺨﺭﻭﺝ ﻤﻥ‬
‫ﻤﺤﻭل ﺘﻐﺫﻴﺔ ﺍﻟﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ( ‪ ،‬ﻜﻤﺎ ﺘﺴﺘﻌﻤل ﺃﻴﻀﺎ ﻓﻰ ﺼﻭﺍﻋﺩ ﺍﻷﺩﻭﺍﺭ ﺍﻟﻌﻠﻴـﺎ‬
‫ﻓﻰ ﺍﻟﻤﺒﻨﻰ ﻭﺘﺤﺴﺏ ﻤﻘﺎﻭﻤﺔ ﺍﻟﻁﻭﺭ ﻤﻥ ﻫﺫﻩ ﺍﻟﻘﻀﺒﺎﻥ ﻟﻠﻤﺘﺭ ﺍﻟﻁـﻭﻟﻰ ﺒﺎﺴـﺘﻌﻤﺎل‬
‫ﻨﻔﺱ ﺍﻟﺼﻴﻐﺔ ﺍﻟﺴﺎﺒﻘﺔ ﻟﻤﻘﺎﻭﻤﺔ ﺍﻟﻤﻭﺼﻼﺕ‪ ،‬ﻭﻴﻤﻜﻥ ﻋﺎﺩﺓ ﺇﻫﻤﺎل ﻤﻘﺎﻭﻤﺔ ﺍﻟﻘﻀـﺒﺎﻥ‬
‫ﻓﻴﻤﺎ ﻋﺩﺍ ﺫﻭﺍﺕ ﺍﻟﻤﻘﻁﻊ ﺍﻟﺼﻐﻴﺭ‪.‬‬
‫ﻭﺘﺅﺨﺫ ﻤﻤﺎﻨﻌﺔ ﺍﻟﻁﻭﺭ ﻤﻥ ﻫﺫﻩ ﺍﻟﻘﻀﺒﺎﻥ ﻤﺴﺎﻭﻴﺔ ﻟﻠﻘﻴﻤﺔ ‪ ٠.١٥‬ﻤﻠﻠﻰ ﺃﻭﻡ ﻟﻜل ﻤﺘﺭ‬
‫ﻁﻭﻟﻰ‪.‬‬
‫)ﺡ( ﻗﻀﺒﺎﻥ ﺍﻟﺘﻭﺯﻴﻊ ﺩﺍﺨل ﻟﻭﺤﺎﺕ ﺍﻟﺘﻭﺯﻴﻊ ﺍﻟﻔﺭﻋﻴﺔ‬
‫ﺘﺨﺘﻠﻑ ﺃﻁﻭﺍل ﻫﺫﻩ ﺍﻟﻘﻀﺒﺎﻥ ﻤﻥ ﻨﻘﻁﺔ ﺘﻐﺫﻴﺔ ﺍﻟﻠﻭﺤﺔ ﺇﻟﻰ ﻨﻘﺎﻁ ﺨﺭﻭﺝ ﺍﻟﻜـﺎﺒﻼﺕ‬
‫ﺍﻟﻤﺘﻔﺭﻋﺔ ﻤﻥ ﻟﻭﺤﺔ ﺍﻟﺘﻭﺯﻴﻊ ‪ ،‬ﻭﻋﺎﺩﺓ ﻴﻤﻜﻥ ﺇﻫﻤﺎل ﻤﻌﺎﻭﻗﺔ ﻫﺫﻩ ﺍﻟﻘﻀﺒﺎﻥ‪.‬‬

‫‪ ٢-٦-٥‬ﻤﺜﺎل ﺘﻭﻀﻴﺤﻰ‬
‫ﻴﺒﻴﻥ ﺍﻟﺸﻜل )‪ (٣-٥‬ﺠﺯﺀﺍﹰ ﻤﻥ ﺸﺒﻜﺔ ﺘﻭﺯﻴﻊ ﺍﻟﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ ﺩﺍﺨل ﺃﺤﺩ ﺍﻟﻤﺼﺎﻨﻊ ﻤـﻥ‬
‫ﻟﻭﺤﺔ ﺍﻟﺘﻭﺯﻴﻊ ﺍﻟﺭﺌﻴﺴﻴﺔ ﻟﻠﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ ﺇﻟﻰ ﺃﺤﺩ ﻤﺒﺎﻨﻰ ﺍﻟﻤﺼﻨﻊ ‪ ،‬ﺜﻡ ﺇﻟـﻰ ﻗﺴـﻡ ﻤـﻥ‬
‫ﺃﻗﺴﺎﻡ ﻫﺫﺍ ﺍﻟﻤﺒﻨﻰ ﺤﻴﺙ ﺘﻐﺫﻯ ﺒﻌﺽ ﺍﻷﺤﻤﺎل ﺍﻟﻤﺒﻴﻨﺔ ﻓﻰ ﺍﻟﺭﺴﻡ ‪ ،‬ﻜﻤﺎ ﻴﺒﻴﻥ ﺍﻟﺭﺴﻡ ﺘﻐﺫﻴﺔ‬
‫ﺇﺴﺘﺭﺍﺤﺔ ﺴﻜﻨﻴﺔ ﻤﻥ ﺜﻼﺜﺔ ﺃﺩﻭﺍﺭ ﻓﻰ ﺍﻟﻤﺼﻨﻊ‪ .‬ﻭﺍﻟﻤﻁﻠﻭﺏ ﺤﺴﺎﺏ ﻗﻴﻡ ﺘﻴـﺎﺭﺍﺕ ﺍﻟﻘﺼـﺭ‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺍﻟﺜﻼﺜﻰ ﺍﻷﻁﻭﺍﺭ ﻋﻨﺩ ﻟﻭﺤﺎﺕ ﺍﻟﺘﻭﺯﻴﻊ ﺍﻟﻤﺨﺘﻠﻔﺔ ﻓﻰ ﺍﻟﻤﺼﻨﻊ ‪ ،‬ﻋﻠﻤﺎ ﺒﺄﻥ ﺍﻟﺩﺍﺌﺭﺓ ﺍﻟﻤﻜﺎﻓﺌـﺔ‬
‫ﻟﺘﻐﺫﻴﺔ ﺍﻟﻤﺼﻨﻊ ﻤﻥ ﻤﺼﺩﺭ ﺍﻟﺠﻬﺩ ﺍﻟﻤﺘﻭﺴﻁ ﺇﻟﻰ ﻤﺤﻭل ﺘﻐﺫﻴﺔ ﺍﻟﺠﻬـﺩ ﺍﻟﻤـﻨﺨﻔﺽ ﺜـﻡ‬
‫ﺍﻟﺘﻭﺼﻴﻠﺔ ﺇﻟﻰ ﻟﻭﺤﺔ ﺍﻟﺘﻭﺯﻴﻊ ﺍﻟﺭﺌﻴﺴﻴﺔ ﻟﻠﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ ﻴﻤﻜﻥ ﺘﻤﺜﻴﻠﻬﺎ ﺒﻤﻤﺎﻨﻌـﺔ ﻤﻜﺎﻓﺌـﺔ‬
‫ﻗﻴﻤﺘﻬﺎ ‪ ١٠‬ﻤﻠﻠﻰ ﺃﻭﻡ ‪ ،‬ﻭﻤﻘﺎﻭﻤﺔ ﻤﻜﺎﻓﺌﺔ ﻴﻤﻜﻥ ﺇﻫﻤﺎﻟﻬﺎ‪.‬‬
‫ﺍﻟﺤل ‪:‬‬
‫)‪ (١‬ﺒﺩﺍﻴﺔ ﻴﻤﻜﻥ ﺤﺴﺎﺏ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﻋﻠﻰ ﻗﻀﺒﺎﻥ ﺘﻭﺯﻴﻊ ﺍﻟﻠﻭﺤـﺔ ﺍﻟﺭﺌﻴﺴـﻴﺔ ﻟﻠﺠﻬـﺩ‬
‫ﺍﻟﻤﻨﺨﻔﺽ ﻜﻤﺎ ﻴﻠﻰ ‪:‬‬
‫ﺍﻟﻤﻌﺎﻭﻗﺔ ﺍﻟﻤﻜﺎﻓﺌﺔ = ﺍﻟﻤﻤﺎﻨﻌﺔ ﺍﻟﻤﻜﺎﻓﺌﺔ ﻨﻅﺭﺍ ﻹﻫﻤﺎل ﺍﻟﻤﻘﺎﻭﻤﺔ ﺍﻟﻤﻜﺎﻓﺌﺔ‬
‫ﻭﺒﺎﻟﺘﺎﻟﻰ ﺘﻜﻭﻥ ﻗﻴﻤﺔ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ=) ‪ ٢٣.١ = ١٠/( ٢٢٠ × ١.٠٥‬ﻙ ﺃﻤﺒﻴﺭ‬
‫ﻭﺘﻜــﻭﻥ ﺴﻌــﺔ ﺍﻟﻘﺼﺭ ﺍﻟﻤﻘﻨﻨﺔ ﻟﻠﻘﻭﺍﻁﻊ ﻋﻠﻰ ﻗﻀﺒﺎﻥ ﺘﻭﺯﻴﻊ ﻫـﺫﻩ ﺍﻟﻠﻭﺤـﺔ‬
‫ﺍﻟﺭﺌﻴﺴﻴﺔ ‪ ٣٢‬ﻙ ﺃﻤﺒﻴﺭ ‪.‬‬
‫)‪ (٢‬ﻤﻌﺎﻤﻼﺕ ﺍﻟﻜﺎﺒل ﺍﻷﻟﻭﻤﻨﻴﻭﻡ ﻤﻥ ﺍﻟﻠﻭﺤﺔ ﺍﻟﺭﺌﻴﺴﻴﺔ "ﺃ " ﺇﻟﻰ ﺍﻟﻠﻭﺤﺔ "ﺏ" ﺒﻁﻭل ‪٤٥‬‬
‫ﻤﺘﺭ ﻭﻤﻭﺼﻼﺕ ﻤﻘﻁﻌﻬﺎ ‪ ٧٠ + ١٥٠ × ٣‬ﻤﻡ‪.٢‬‬
‫ﻭﻴﻼﺤﻅ ﺃﻥ ﻤﻭﺼل ﺍﻟﺘﻌﺎﺩل ﻴﺅﺜﺭ ﻓﻘﻁ ﻓﻰ ﺘﻴﺎﺭﺍﺕ ﺍﻟﻘﺼﺭ ﺇﻟﻰ ﺍﻷﺭﺽ ﻭﻻ ﻴﺩﺨل‬
‫ﻓﻰ ﺤﺴﺎﺒﺎﺕ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﺜﻼﺜﻰ ﺍﻷﻁﻭﺍﺭ ‪.‬‬
‫‪ ٩.٩‬ﻤﻠﻠﻰ ﺃﻭﻡ‬ ‫= )‪= ١٥٠ ÷ (٣٣ × ٤٥‬‬ ‫ﻤﻘﺎﻭﻤﺔ ﺍﻟﻜﺎﺒل‬
‫= ‪ ٦.٧٥‬ﻤﻠﻠﻰ ﺃﻭﻡ‬ ‫= ‪٠.١٥ × ٤٥‬‬ ‫ﻤﻤﺎﻨﻌﺔ ﺍﻟﻜﺎﺒل‬
‫‪ ٠.١٥‬ﻤﻠﻠﻰ ﺃﻭﻡ‬ ‫ﻭﺒﺈﻀﺎﻓﺔ ﻤﻤﺎﻨﻌﺔ ﻗﺎﻁﻊ ﺍﻟﺩﺨﻭل ﺇﻟﻰ ﺍﻟﻠﻭﺤﺔ ﺏ‬
‫ﺘﻜﻭﻥ ﺍﻟﻤﻘﺎﻭﻤﺔ ﻭﺍﻟﻤﻤﺎﻨﻌﺔ ﻭﺍﻟﻤﻌﺎﻭﻗﺔ ﺍﻟﻤﻜﺎﻓﺌﺔ ﺍﻟﻜﻠﻴﺔ ﺤﺘﻰ ﻗﻀﺒﺎﻥ ﺘﻭﺯﻴﻊ ﺍﻟﻠﻭﺤـﺔ‬
‫"ﺏ" ﻫﻰ ‪ ١٩.٥٨٦ ، ١٦.٩ ، ٩.٩‬ﻤﻠﻠﻰ ﺃﻭﻡ ﻋﻠﻰ ﺍﻟﺘﻭﺍﻟﻲ ‪.‬‬
‫ﻭﺒﺎﻟﺘﺎﻟﻰ ﺘﻜﻭﻥ ﻗﻴﻤﺔ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﻋﻠﻰ ﻗﻀﺒﺎﻥ ﺘﻭﺯﻴﻊ ﺍﻟﻠﻭﺤﺔ "ﺏ" =‬
‫ﻙ ﺃﻤﺒﻴﺭ‬ ‫)‪١١.٧٩٤ = ١٩.٥٨٦ ÷ (٢٢٠ × ١.٠٥‬‬
‫ﻭﺒﺫﻟﻙ ﻨﺨﺘﺎﺭ ﺴﻌﺔ ﺍﻟﻘﻁﻊ ﺍﻟﻤﻘﻨﻨﺔ ﻟﻜل ﺍﻟﻘﻭﺍﻁﻊ ﻓﻰ ﺍﻟﻠﻭﺤﺔ "ﺏ" = ‪ ١٦‬ﻙ ﺃﻤﺒﻴﺭ‬
‫)‪ (٣‬ﻤﻌﺎﻤﻼﺕ ﺍﻟﻜﺎﺒل ﺍﻟﻨﺤﺎﺴﻰ ﻤﻥ ﺍﻟﻠﻭﺤﺔ "ﺏ" ﺇﻟﻰ ﺍﻟﻠﻭﺤـﺔ "ﺝ" ﺒﻁـﻭل ‪ ١٥‬ﻤﺘـﺭ‬
‫‪٢‬‬
‫ﻭﻤﻘﻁﻊ ﻤﻭﺼﻼﺕ ‪ ٣٥ + ٧٠ × ٣‬ﻤﻡ‬
‫‪ ٤.٥‬ﻤﻠﻠﻰ ﺃﻭﻡ‬ ‫ﻤﻘﺎﻭﻤﺔ ﺍﻟﻜﺎﺒل = )‪= ٧٠ ÷ (٢١ × ١٥‬‬
‫= ‪ ٢.٢٥‬ﻤﻠﻠﻰ ﺃﻭﻡ‬ ‫= ‪٠.١٥ × ١٥‬‬ ‫ﻤﻤﺎﻨﻌﺔ ﺍﻟﻜﺎﺒل‬
‫= ‪ ٠.١٥‬ﻤﻠﻠﻰ ﺃﻭﻡ‬ ‫ﻭﺒﺈﻀﺎﻓﺔ ﻤﻤﺎﻨﻌﺔ ﻗﺎﻁﻊ ﺩﺨﻭل ﺍﻟﻠﻭﺤﺔ "ﺝ"‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺘﻜﻭﻥ ﺍﻟﻤﻘﺎﻭﻤﺔ ﻭﺍﻟﻤﻤﺎﻨﻌﺔ ﻭﺍﻟﻤﻌﺎﻭﻗﺔ ﺍﻟﻤﻜﺎﻓﺌﺔ ﺍﻟﻜﻠﻴﺔ ﺤﺘﻰ ﻗﻀﺒﺎﻥ ﺘﻭﺯﻴﻊ ﺍﻟﻠﻭﺤـﺔ‬
‫"ﺝ" ﻫﻰ ‪ ٢٤.٠٨٠ ، ١٩.٣ ، ١٤.٤‬ﻤﻠﻠﻰ ﺃﻭﻡ ﻋﻠﻰ ﺍﻟﺘﻭﺍﻟﻲ ‪.‬‬
‫ﻭﺒﺎﻟﺘﺎﻟﻰ ﺘﻜﻭﻥ ﻗﻴﻤﺔ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﻋﻠﻰ ﻗﻀﺒﺎﻥ ﺘﻭﺯﻴﻊ ﺍﻟﻠﻭﺤﺔ "ﺝ" =‬
‫)‪ ٩.٥٩٣ = ٢٤.٠٨٠ ÷ (٢٢٠ × ١.٠٥‬ﻙ ﺃﻤﺒﻴﺭ‬
‫ﻭﺒﺫﻟﻙ ﻨﺨﺘﺎﺭ ﺴﻌﺔ ﺍﻟﻘﻁﻊ ﺍﻟﻤﻘﻨﻨﺔ ﻟﻜل ﺍﻟﻘﻭﺍﻁﻊ ﻓﻰ ﺍﻟﻠﻭﺤﺔ "ﺝ" = ‪ ١٦‬ﻙ ﺃﻤﺒﻴﺭ‬

‫ﻟﻮﺣﺔ اﻟﺘﻮزﯾﻊ اﻟﺮﺋﯿﺴﯿﺔ ﻟﻠﺠﮭﺪ‬


‫اﻟﻤﻨﺨﻔﺾ‬
‫اﻟﻠﻮﺣﺔ "أ"‬
‫ﻛﺎﺑﻞ أﻟﻮﻣﻨﯿﻮم ﺑﻄﻮل‬
‫‪١٥٠×٣‬‬

‫ﻛﺎﺑﻞ ﻧﺤﺎس ﺑﻄﻮل ‪٢٥‬م‬


‫‪٢‬‬
‫‪ ١٦×٤‬ﻣﻢ‬
‫‪٤٥‬‬
‫‪+‬م‪ ٧٠‬ﻣﻢ‬

‫ﺻﻮاﻋﺪ ﻟﻸدوار اﻟﻌﻠﯿﺎ‬ ‫ﻟﻮﺣﺔ اﻟﺘﻮزﯾﻊ اﻟﻌﻤﻮﻣﯿﺔ‬


‫‪٢‬‬

‫ﺑﺎﻻﺳﺘﺮاﺣﺔ اﻟﺴﻜﻨﯿﺔ‬

‫اﻟﻠﻮﺣﺔ "ب"‬
‫ﺻﺎﻋﺪ‬
‫ﻛﺎﺑﻞ ﻧﺤﺎس ﺑﻄﻮل ‪١٥‬م‬

‫‪٤‬م‬
‫ﻧﺤﺎس‬
‫‪ ٣٥+٧٠×٣‬ﻣﻢ‬

‫‪٢‬‬
‫اﻟﺪور‬ ‫‪ ١٦×٤‬ﻣﻢ‬
‫اﻟﺪور‬
‫ﺣﻤﻞ‬ ‫ﺣﻤﻞ‬ ‫اﻷرﺿﻲ‬
‫اﻷول‬
‫‪ ٣.٥‬م‬
‫‪٢‬‬

‫اﻟﻠﻮﺣﺔ‬
‫"ج"‬ ‫اﻟﺪور‬
‫اﻟﺜﺎﻧﻲ‬
‫ﻛﺎﺑﻞ ﻧﺤﺎس ﺑﻄﻮل ‪١٠‬م‬

‫‪ ٣.٥‬م‬
‫ﻛﺎﺑﻞ ﻧﺤﺎس ﺑﻄﻮل ‪٦‬م‬

‫‪ ١٠×٤‬ﻣﻢ‬

‫اﻟﺪور‬
‫‪٢٥×٣‬‬
‫ﻣﻢ‬

‫اﻟﺜﺎﻟﺚ‬
‫‪٢‬‬

‫أﺣﻤﺎل‬
‫‪٢‬‬

‫أﺧﺮى‬
‫اﻟﻠﻮﺣﺔ "د"‬ ‫ﻟﻮﺣﺔ اﻹﻧﺎرة‬

‫‪M‬‬
‫أﺣﻤﺎل‬
‫‪٣‬‬ ‫اﻹﻧﺎرة‬
‫ﺍﻟﻤﺼﺎﻨﻊ‬ ‫ﺸﻜل ﺭﻗﻡ )‪ :(٣-٥‬ﺠﺯﺀ ﻤﻥ ﺸﺒﻜﺔ ﺘﻭﺯﻴﻊ ﺍﻟﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ ﺩﺍﺨل ﺃﺤﺩ‬
‫ﻣﺤﺮﻛﺎت‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫)‪ (٤‬ﻤﻌﺎﻤﻼﺕ ﺍﻟﻜﺎﺒل ﺍﻟﻨﺤﺎﺴﻰ ﻤﻥ ﺍﻟﻠﻭﺤﺔ "ﺝ" ﺇﻟﻰ ﺍﻟﻠﻭﺤﺔ "ﺩ" ﺒﻁﻭل ‪ ١٠‬ﻤﺘﺭ ﻭﻤﻘﻁﻊ‬
‫‪٢‬‬
‫ﻤﻭﺼﻼﺕ ‪ ٢٥ × ٣‬ﻤﻡ‬
‫ﻤﻠﻠﻰ ﺃﻭﻡ‬ ‫‪٨.٤‬‬ ‫ﻤﻘﺎﻭﻤﺔ ﺍﻟﻜﺎﺒل = )‪= ٢٥ ÷ (٢١ × ١٠‬‬
‫ﻤﻠﻠﻰ ﺃﻭﻡ‬ ‫‪١.٥‬‬ ‫=‬ ‫= ‪٠.١٥ × ١٠‬‬ ‫ﻤﻤﺎﻨﻌﺔ ﺍﻟﻜﺎﺒل‬
‫‪ ٠.١٥‬ﻤﻠﻠﻰ ﺃﻭﻡ‬ ‫ﻭﺒﺈﻀﺎﻓﺔ ﻤﻤﺎﻨﻌﺔ ﻗﺎﻁﻊ ﺘﺸﻐﻴل ﺍﻟﻤﺤﺭﻙ‬
‫ﺘﻜﻭﻥ ﺍﻟﻤﻘﺎﻭﻤﺔ ﻭﺍﻟﻤﻤﺎﻨﻌﺔ ﻭﺍﻟﻤﻌﺎﻭﻗﺔ ﺍﻟﻤﻜﺎﻓﺌﺔ ﺍﻟﻜﻠﻴﺔ ﺤﺘﻰ ﺍﻟﻠﻭﺤﺔ "ﺩ" ﻫـﻰ ‪،٢٢.٨‬‬
‫‪ ٣٠.٩٦٤ ، ٢٠.٩٥‬ﻤﻠﻠﻰ ﺃﻭﻡ ﻋﻠﻰ ﺍﻟﺘﻭﺍﻟﻲ ‪.‬‬
‫ﻭﺒﺎﻟﺘﺎﻟﻰ ﺘﻜﻭﻥ ﻗﻴﻤﺔ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﻋﻠﻰ ﻗﻀﺒﺎﻥ ﺍﻟﻠﻭﺤﺔ "ﺩ" =‬
‫)‪ ٧.٤٦٠ = ٣٠.٩٦٤ ÷ (٢٢٠ × ١.٠٥‬ﻙ ﺃﻤﺒﻴﺭ‬
‫ﻭﻋﺎﺩﺓ ﻤﺎ ﺘﻜﻭﻥ ﻤﻘﻨﻨﺎﺕ ﻗﺎﻁﻊ ﺘﺸﻐﻴل ﺍﻟﻤﺤﺭﻙ ﻤﺤﺩﺩﺓ ﻤﻥ ﻗﺒل ﺼـﺎﻨﻊ ﺍﻟﻤﺤـﺭﻙ‬
‫ﻭﻟﻜﻥ ﻴﺠﺏ ﺃﻻ ﺘﻘل ﺴﻌﺔ ﺍﻟﻘﻁﻊ ﺍﻟﻤﻘﻨﻨﺔ ﻟﻬﺫﺍ ﺍﻟﻘﺎﻁﻊ ﻋﻥ ‪ ١٠‬ﻙ ﺃﻤﺒﻴﺭ ﻨﻅﺭﺍﹰ ﻷﻨـﻪ‬
‫ﻋﻨﺩ ﺤﺩﻭﺙ ﻗﺼﺭ ﻓﻲ ﺩﺍﺌﺭﺓ ﺘﻐﺫﻴﺔ ﺃﺤﺩ ﺍﻟﻤﺤﺭﻜﺎﺕ ﻓﺈﻥ ﺒﻘﻴﺔ ﺍﻟﻤﺤﺭﻜﺎﺕ ﺍﻟﺘﻲ ﺘﻌﻤل‬
‫ﺘﺴﺎﻫﻡ ﻓﻲ ﺯﻴﺎﺩﺓ ﺘﻴﺎﺭ ﻫﺫﺍ ﺍﻟﻘﺼﺭ‪.‬‬
‫)‪ (٥‬ﻤﻌﺎﻤﻼﺕ ﺍﻟﻜﺎﺒل ﺍﻟﻤﻐﺫﻯ ﻟﻠﻭﺤﺔ ﺍﻹﻨﺎﺭﺓ ﻤﻥ ﺍﻟﻠﻭﺤﺔ "ﺝ" ﺒﻁﻭل ‪ ٦‬ﻤﺘـﺭ ﻭﻤﻘﻁـﻊ‬
‫ﻤﻭﺼﻼﺕ ‪ ١٠‬ﻤﻡ‪ ٢‬ﻤﻥ ﺍﻟﻨﺤﺎﺱ‬
‫= ‪ ١٢.٦‬ﻤﻠﻠﻰ ﺃﻭﻡ‬ ‫‪ -‬ﻤﻘﺎﻭﻤﺔ ﺍﻟﻜﺎﺒل = )‪١٠ ÷ (٢١ × ٦‬‬
‫= ‪ ٠.٩‬ﻤﻠﻠﻰ ﺃﻭﻡ‬ ‫‪ -‬ﻤﻤﺎﻨﻌﺔ ﺍﻟﻜﺎﺒل = ‪٠.١٥ × ٦‬‬
‫= ‪ ٠.١٥‬ﻤﻠﻠﻰ ﺃﻭﻡ‬ ‫‪ -‬ﻭﺒﺈﻀﺎﻓﺔ ﻤﻤﺎﻨﻌﺔ ﻗﺎﻁﻊ ﺍﻟﺩﺨﻭل‬
‫‪ -‬ﺘﻜﻭﻥ ﺍﻟﻤﻘﺎﻭﻤﺔ ﻭﺍﻟﻤﻤﺎﻨﻌﺔ ﻭﺍﻟﻤﻌﺎﻭﻗﺔ ﺍﻟﻤﻜﺎﻓﺌﺔ ﺍﻟﻜﻠﻴﺔ ﺤﺘﻰ ﻗﻀﺒﺎﻥ ﺘﻭﺯﻴﻊ ﻟﻭﺤﺔ‬
‫ﺍﻹﻨﺎﺭﺓ ﻫﻰ ‪ ٣٣.٨١٠ ، ٢٠.٣٥ ، ٢٧.٠٠‬ﻤﻠﻠﻰ ﺃﻭﻡ ﻋﻠﻰ ﺍﻟﺘﻭﺍﻟﻲ ‪.‬‬
‫‪ -‬ﻭﺒﺫﻟﻙ ﺘﻜﻭﻥ ﻗﻴﻤﺔ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﻋﻠﻰ ﻗﻀﺒﺎﻥ ﺘﻭﺯﻴﻊ ﻟﻭﺤﺔ ﺍﻹﻨﺎﺭﺓ =‬
‫‪٠٥‬ﻭ‪ ٦.٨٣٢ = ٣٣.٨١٠ ÷ ٢٢٠ × ١‬ﻙ ﺃﻤﺒﻴﺭ‬
‫ﻭﻋﻠﻰ ﺫﻟﻙ ﻨﺨﺘﺎﺭ ﺴﻌﺔ ﺍﻟﻘﻁﻊ ﺍﻟﻤﻘﻨﻨﺔ ﻟﻘﻭﺍﻁﻊ ﻟﻭﺤﺔ ﺍﻹﻨﺎﺭﺓ = ‪ ١٠‬ﻙ ﺃﻤﺒﻴﺭ ﻭﻫـﻲ‬
‫ﺃﻗﺭﺏ ﻗﻴﻤﺔ ﻗﻴﺎﺴﻴﺔ ﻟﺴﻌﺔ ﺍﻟﻘﻁﻊ‪.‬‬
‫)‪ (٦‬ﻤﻌﺎﻤﻼﺕ ﺍﻟﻜﺎﺒل ﺍﻟﻨﺤﺎﺴﻰ ﺍﻟﻤﻐﺫﻯ ﻟﻺﺴﺘﺭﺍﺤﺔ ﺍﻟﺴﻜﻨﻴﺔ ﻤﻥ ﻟﻭﺤﺔ ﺍﻟﺘﻭﺯﻴﻊ ﺍﻟﺭﺌﻴﺴﻴﺔ‬
‫ﻟﻠﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ ﺒﻁﻭل ‪ ٢٥‬ﻤﺘﺭ ﻭﻤﻘﻁﻊ ﻤﻭﺼﻼﺕ ‪ ١٦ × ٤‬ﻤﻡ‪. ٢‬‬
‫= ‪ ٣٢.٨١٣‬ﻤﻠﻠﻰ ﺃﻭﻡ‬ ‫‪ -‬ﻤﻘﺎﻭﻤﺔ ﺍﻟﻜﺎﺒل = )‪١٦ ÷ (٢١ × ٢٥‬‬
‫ﻤﻠﻠﻰ ﺃﻭﻡ‬ ‫= ‪٣.٧٥‬‬ ‫‪ -‬ﻤﻤﺎﻨﻌﺔ ﺍﻟﻜﺎﺒل = )‪(٠.١٥ × ٢٥‬‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺨﺎﻤﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫‪ -‬ﻭﺒﺈﻀﺎﻓــﺔ ﻤﻤﺎﻨﻌــﺔ ﻗﺎﻁــﻊ ﺩﺨــﻭل ﺍﻟﻠﻭﺤــﺔ ﺍﻟﻌﻤﻭﻤﻴــﺔ ﻓـﻰ‬


‫ﺍﻻﺴﺘﺭﺍﺤـﺔ ‪ ٠.١٥‬ﻤﻠﻠﻰ ﺃﻭﻡ‬
‫‪ -‬ﺘﻜﻭﻥ ﺍﻟﻤﻘﺎﻭﻤﺔ ﻭﺍﻟﻤﻤﺎﻨﻌﺔ ﻭﺍﻟﻤﻌﺎﻭﻗﺔ ﺍﻟﻤﻜﺎﻓﺌﺔ ﺍﻟﻜﻠﻴﺔ ﺤﺘـﻰ ﻗﻀـﺒﺎﻥ ﺘﻭﺯﻴـﻊ‬
‫ﺍﻟﻠﻭﺤﺔ ﺍﻟﻌﻤﻭﻤﻴﺔ ﻟﻺﺴﺘﺭﺍﺤﺔ ﻫﻰ ‪ ٣٥.٦٣٦ ، ١٣.٩ ، ٣٢.٨١٣‬ﻤﻠﻠـﻰ ﺃﻭﻡ‬
‫ﻋﻠﻰ ﺍﻟﺘﺭﺘﻴﺏ‪.‬‬
‫‪ -‬ﻭﺘﻜﻭﻥ ﻗﻴﻤﺔ ﺘﻴﺎﺭ ﺍﻟﻘﺼـﺭ ﻋﻠﻰ ﻗﻀـﺒﺎﻥ ﺘﻭﺯﻴـﻊ ﺍﻟﻠﻭﺤـﺔ ﺍﻟﻌﻤﻭﻤﻴـﺔ ﻓـﻰ‬
‫ﺍﻻﺴﺘﺭﺍﺤﺔ = ‪ ٦.٤٨٢‬ﻙ ﺃﻤﺒﻴﺭ‬
‫‪ -‬ﻭﻟﺫﻟﻙ ﻨﺨﺘــﺎﺭ ﺍﻟﺴﻌــﺔ ﺍﻟﻤﻘﻨﻨﺔ ﻟﻠﻘﻁﻊ ﻟﻜل ﻗﻭﺍﻁـﻊ ﺍﻟﻠﻭﺤـﺔ ﺍﻟﻌﻤﻭﻤﻴـﺔ‬
‫ﻟﻼﺴﺘﺭﺍﺤـﺔ = ‪ ١٠‬ﻙ ﺃﻤﺒﻴﺭ ﻭﻫﻲ ﺃﻗﺭﺏ ﻗﻴﻤﺔ ﻗﻴﺎﺴﻴﺔ ﻟﺴﻌﺔ ﺍﻟﻘﻁﻊ‪.‬‬
‫‪ -‬ﻭﻴﻤﻜﻥ ﺍﺴﺘﻌﻤﺎل ﻨﻔﺱ ﺴﻌﺔ ﺍﻟﻘﻁﻊ ﺍﻟﻤﻘﻨﻨﺔ ﻟﺒﻘﻴﺔ ﺍﻟﻘﻭﺍﻁﻊ ﻓﻰ ﺍﻻﺴﺘﺭﺍﺤﺔ ﺒﺄﻜﻤﻠﻬﺎ‬
‫ﺤﻴﺙ ﻴﻘل ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﻓﻰ ﺃﻨﺤﺎﺀ ﺍﻹﺴﺘﺭﺍﺤﺔ ﻋﻥ ‪ ٦.٤٨٢‬ﻙ ﺃﻤﺒﻴﺭ ‪.‬‬

‫‪ ٣-٦-٥‬ﺍﻟﺘﻨﺴﻴﻕ ﺒﻴﻥ ﺘﻴﺎﺭﺍﺕ ﺍﻟﻘﺼﺭ ﻭﻤﻘﻁﻊ ﻤﻭﺼﻼﺕ ﺍﻟﻜﺎﺒﻼﺕ‬


‫‪ -‬ﺒﻌﺩ ﺤﺴﺎﺏ ﻗﻴﻤﺔ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﺍﻟﺫﻯ ﻴﻤﻜﻥ ﺃﻥ ﻴﺘﻌﺭﺽ ﻟﻪ ﺍﻟﻜﺎﺒل ﺒﻨﺎﺀ ﻋﻠـﻰ ﺍﺨﺘﻴـﺎﺭ‬
‫ﻤﻘﺎﻁﻊ ﺍﻟﻜﺎﺒﻼﺕ ﺍﻟﻤﻐﺫﻴﺔ ﻟﻠﻜﺎﺒل ﻤﻭﻀﻭﻉ ﺍﻟﺤﺴﺎﺏ ﻴﺠﺏ ﺍﻟﺭﺠﻭﻉ ﺇﻟﻰ ﺠﺩﺍﻭل ﺍﻟﺸﺭﻜﺔ‬
‫ﺍﻟﻤﺼﻨﻌﺔ ﻟﻠﻜﺎﺒل ﻟﻠﺘﺄﻜﺩ ﻤﻥ ﺇﻤﻜﺎﻨﻴﺔ ﺼﻤﻭﺩ ﺍﻟﻜﺎﺒل ﺒﻤﻘﻁﻌﻪ ﺍﻟﻤﺨﺘـﺎﺭ ﻟﺴـﺭﻴﺎﻥ ﺘﻴـﺎﺭ‬
‫ﺍﻟﻘﺼﺭ ﻟﻠﻔﺘﺭﺓ ﺍﻟﺘﻰ ﻴﺴﺘﻐﺭﻗﻬﺎ ﺘﺸﻐﻴل ﻨﺒﻴﻁﺔ ﺍﻟﻭﻗﺎﻴﺔ ﻀﺩ ﺍﻟﻘﺼﺭ ‪ ،‬ﻭﺇﻻ ﺘﺤﺘﻡ ﺇﻤﺎ ﺯﻴﺎﺩﺓ‬
‫ﻤﻘﻁﻊ ﻤﻭﺼﻼﺕ ﺍﻟﻜﺎﺒل ﺤﺘﻰ ﻴﻤﻜﻨﻪ ﺍﻟﺼﻤﻭﺩ ﺃﻭ ﺍﺴﺘﺒﺩﺍل ﻨﺒﻴﻁﺔ ﺍﻟﻭﻗﺎﻴﺔ ﺒﺄﺨﺭﻯ ﺘﻜﻭﻥ‬
‫ﺃﺴﺭﻉ ﻓﻰ ﺍﻟﻭﻗﺎﻴﺔ ﺃﻭ ﺘﻜﻭﻥ ﻤﻥ ﺍﻟﻨﻭﻉ ﺍﻟﺫﻯ ﻴﺤﺩ ﻤﻥ ﻗﻴﻤﺔ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ‪.‬‬
‫‪ -‬ﻭﺍﻟﻤﺜﺎل ﻟﺫﻟﻙ ﻫﻭ ﻋﻨﺩ ﺇﺨﺘﻴﺎﺭ ﻤﻘﻁﻊ ﻤﻭﺼﻠﻰ ﻜﺎﺒل ﺍﻹﻨﺎﺭﺓ ﻓﻰ ﻏﺭﻓﺔ ﺘﻐﺫﻴـﺔ ﻤﺤـﻭل‬
‫ﺍﻟﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ ﺍﻟﺨﺎﺹ ﺒﺸﺭﻜﺔ ﺘﻭﺯﻴﻊ ﺍﻟﻜﻬﺭﺒﺎﺀ ﺤﻴﺙ ﻴﻤﻜﻥ ﺍﻻﻜﺘﻔـﺎﺀ ﺒﻜﺎﺒـل ﺫﻯ‬
‫ﻤﻭﺼﻠﻴﻥ ﺒﻤﻘﻁﻊ ‪ ٢‬ﻤﻡ‪ ٢‬ﻭﻫﻭ ﺍﻟﺤﺩ ﺍﻷﺩﻨﻰ ﺍﻟﻤﺴﻤﻭﺡ ﺒـﻪ ﻓـﻰ ﺘﻭﺼـﻴﻼﺕ ﺩﻭﺍﺌـﺭ‬
‫ﺍﻹﻨﺎﺭﺓ‪ ،‬ﻭﻟﻜﻥ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﺍﻟﻤﻌﺭﺽ ﻟﻪ ﺍﻟﻜﺎﺒل ﻓﻰ ﺒﺩﺍﻴﺘﻪ ﻨﺎﺤﻴـــﺔ ﺍﻟﻤﺤـﻭل ﻗـﺩ‬
‫ﻴﺼل ﺇﻟﻰ ﺤــﻭﺍﻟﻰ ‪٣٧‬ﻙ ﺃﻤﺒﻴﺭ ﻓﻰ ﺤﺎﻟــﺔ ﺍﻟﻤﺤــﻭل ﺴﻌــﺔ ‪ ١٠٠٠‬ﻙ ﻑ‬
‫ﺃ )ﻭﻴﺘﻀﺎﻋﻑ ﻫـــﺫﺍ ﺍﻟﺘﻴـﺎﺭ ﻤـﻊ ﺍﻟﻤﺤـﻭل ‪ ٢٠٠٠‬ﻙ‪.‬ﻑ‪.‬ﺃ(‪ ،‬ﻭﻻ ﻴﻤﻜـــﻥ‬
‫ﻟﻠﻤﻭﺼـل ﺒﻤﻘﻁﻊ ‪٢‬ﻤﻡ‪ ٢‬ﺘﺤﻤل ﺘﻴــﺎﺭ ﺍﻟﻘﺼــﺭ ﺍﻟﻤﺫﻜــﻭﺭ ﻁــﻭﺍل ﻓﺘـﺭﺓ‬
‫ﺍﻟﻘﻁﻊ ﺍﻟﻌﺎﺩﻴﺔ ﻟﻘﺎﻁﻊ ﺘﺸﻐﻴل ﻤﺼﺒﺎﺡ ﺍﻹﻨﺎﺭﺓ‪ ،‬ﻭﻟﺫﻟﻙ ﻴﺠــﺏ ﻭﻗﺎﻴــﺔ ﺩﺍﺌـــﺭﺓ‬
‫ﺇﻨــﺎﺭﺓ ﻏﺭﻓــﺔ ﺍﻟﻤﺤﻭل ﺒﻭﺍﺴﻁﺔ ﻤﺼﻬﺭ ﺫﻯ ﺴﻌــﺔ ﻗﻁﻊ ﻋﺎﻟﻴــﺔ ﻭﻴﻜـﻭﻥ‬
‫ﻜــﺫﻟﻙ ﻤــﻥ ﺍﻟﻨــﻭﻉ ﺍﻟﺫﻯ ﻴﺤــﺩ ﻤﻥ ﺘﻴـﺎﺭ ﺍﻟﻘﺼـﺭ ‪rupturing capacity‬‬
‫)‪.(High current limiting fuse‬‬

‫‪٥‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺘﺼﻤﻴﻡ ﻟﻭﺤﺎﺕ ﺍﻟﺘﻭﺯﻴﻊ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ‬ ‫‪-٦‬‬


‫ﺘﺤﺘﺎﺝ ﺍﻟﻤﺒﺎﻨﻰ ﻋﺎﻤﺔ ﻟﻠﻁﺎﻗﺔ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺇﻨﺎﺭﺘﻬﺎ ﻭﺘﺸﻐﻴل ﺍﻟﻤﻌﺩﺍﺕ ﻭﺍﻷﺠﻬﺯﺓ ﺍﻟﻤﻭﺠﻭﺩﺓ‬
‫ﺒﻬﺎ ﻭﺫﻟﻙ ﻓﻰ ﻤﺠﺎﻻﺕ ﻤﺘﻌﺩﺩﺓ ﺃﻫﻤﻬﺎ‪:‬‬
‫‪ -‬ﺍﻹﻀﺎﺀﺓ‪.‬‬
‫‪ -‬ﺍﻟﻤﺼﺎﻋﺩ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ‪.‬‬
‫‪ -‬ﺍﻟﻤﻌﺩﺍﺕ ﻭﺍﻷﺠﻬﺯﺓ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ) ﺍﻟﻤﻁﺎﺒﺦ ‪ ،‬ﺃﺠﻬﺯﺓ ﻤﻨﺯﻟﻴـﺔ ‪ ،‬ﻤﻌـﺩﺍﺕ ﻜﺎﻟﻁﻠﻤﺒـﺎﺕ‬
‫ﺒﺄﻨﻭﺍﻋﻬﺎ ‪ ،‬ﻨﻅﻡ ﺍﻟﻭﻗﺎﻴﺔ ﻤﻥ ﺍﻟﺤﺭﻴﻕ ‪ ،‬ﻨﻅﻡ ﺍﻟﺼﺭﻑ ﺍﻟﺼﺤﻰ ﺒﺎﻟﻁﻠﻤﺒﺎﺕ(‪.‬‬
‫‪ -‬ﺘﻜﻭﻥ ﺍﻟﻤﺒﺎﻨﻰ ﺇﻤﺎ ﻋﻘﺎﺭﺍﺕ ﺴﻜﻨﻴﺔ ‪ ،‬ﻤﺼﺎﻨﻊ ‪ ،‬ﻤﺴﺘﺸﻔﻴﺎﺕ ‪ ،‬ﻤﺒﺎﻨﻰ ﺨﺩﻤﻴـﺔ ﻜﺒـﺭﻯ ‪،‬‬
‫ﻓﻨﺎﺩﻕ ‪ ،‬ﻤﺒﺎﻨﻰ ﺘﺠﺎﺭﻴﺔ ﻭﺇﺩﺍﺭﻴﺔ ﻭﻤﻨﺸﺂﺕ ﺯﺭﺍﻋﻴﺔ ‪ ،‬ﻤﺒـﺎﻨﻰ ﺍﻟﻤﺸـﺭﻭﻋﺎﺕ ﺍﻟﻌﺎﻤـﺔ‬
‫ﻜﺎﻟﻤﻭﺍﻨﻰ ‪ ،‬ﺍﻟﻤﻁﺎﺭﺍﺕ ‪ ،‬ﻭﻜل ﺍﻟﻤﺭﺍﻓﻕ ﺍﻟﻌﺎﻤﺔ‪.‬‬
‫ﻭﺘﻜﻭﻥ ﻭﻅﻴﻔﺔ ﻟﻭﺤﺎﺕ ﺍﻟﺘﻭﺯﻴﻊ ﻟﻠﻤﺒﺎﻨﻰ ﻫﻰ ﺤﻤﺎﻴﺔ ﺍﻷﻓـﺭﺍﺩ ﻭﺍﻟﻤﻤﺘﻠﻜـﺎﺕ ﻤـﻥ ﺍﻷﺫﻯ‪،‬‬
‫ﻭﺍﻟﻭﻗﺎﻴﺔ ﻤﻥ ﺍﻟﺘﻴﺎﺭ ﺍﻟﺯﺍﺌﺩ‪ ،‬ﻭﻤﻥ ﺘﻴﺎﺭﺍﺕ ﺍﻟﻌﻁل ﻭﻜﺫﻟﻙ ﺍﻵﺜﺎﺭ ﺍﻟﺤﺭﺍﺭﻴـﺔ ﺍﻟﻨﺎﺘﺠـﺔ ﻤـﻥ‬
‫ﺍﻟﺘﺸﻐﻴل ﺃﻭ ﻋﻨﺩ ﺍﻷﻋﻁﺎل‪ ،‬ﻭﺫﻟﻙ ﺒﺎﻹﻀﺎﻓﺔ ﺇﻟﻰ ﺍﻟﺘﺤﻜﻡ ﻓـﻰ ﻓﺼـل ﻭﺘﻭﺼـﻴل ﺍﻟﺘﻴـﺎﺭ‬
‫ﺍﻟﻜﻬﺭﺒﺎﺌﻰ ﻤﻊ ﺍﻟﺘﺸﻐﻴل ﺍﻵﻤﻥ ﻷﻯ ﻤﻌﺩﺓ ﺃﻭ ﺠﻬﺎﺯ‪.‬‬
‫ﻋﺎﻡ‬
‫)‪ (١‬ﻴﺘﻡ ﺘﺭﻜﻴﺏ ﻟﻭﺤﺔ ﺘﻭﺯﻴﻊ ﺭﺌﻴﺴﻴﺔ ﻗﺭﻴﺒﺔ ﻤﻥ ﻨﻘﻁﺔ ﺘﻐﺫﻴﺔ ﺍﻟﻤﺒﻨﻰ ﺒﺎﻟﺘﻴﺎﺭ ﺍﻟﻜﻬﺭﺒـﺎﺌﻰ‬
‫ﻭﺘﺘﻔﺭﻉ ﻤﻨﻬﺎ ﺍﻟﻤﻐﺫﻴﺎﺕ ﺍﻟﺭﺌﻴﺴﻴﺔ ﺍﻟﺘﻰ ﺘﻐﺫﻯ ﺍﻟﻠﻭﺤﺎﺕ ﺍﻟﻔﺭﻋﻴﺔ‪.‬‬
‫)‪ (٢‬ﻻ ﻴﺠﻭﺯ ﺘﺭﻜﻴﺏ ﻟﻭﺤﺔ ﺍﻟﺘﻭﺯﻴﻊ ﺍﻟﺭﺌﻴﺴﻴﺔ ﺩﺍﺨل ﺤﺠﺭﺓ ﻤﻐﻠﻘﺔ ﺇﻻ ﺇﺫﺍ ﻜﺎﻨـﺕ ﻫـﺫﻩ‬
‫ﺍﻟﺤﺠﺭﺓ ﻤﺨﺼﺼﺔ ﻟﻠﻭﺤﺔ ﻓﻘﻁ‪ ،‬ﺃﻤﺎ ﺇﺫﺍ ﺘﻡ ﺘﺭﻜﻴﺏ ﺍﻟﻠﻭﺤﺔ ﻓﻰ ﻤﻜﺎﻥ ﻤﻔﺘﻭﺡ‪ ،‬ﻓﻴﺠﺏ‬
‫ﺃﻥ ﺘﻜﻭﻥ ﺒﻌﻴﺩﺓ ﻋﻥ ﻤﺘﻨﺎﻭل ﺍﻟﺠﻤﻬﻭﺭ ﻭﻏﻴﺭ ﺍﻟﻤﺨﺘﺼﻴﻥ ﻭﺘﻜـﻭﻥ ﺩﺍﺨـل ﺤﺎﻭﻴـﺔ‬
‫ﺘﺼﻨﻊ ﻤﻥ ﻤﺎﺩﺓ ﻋﺎﺯﻟﺔ ﻏﻴﺭ ﻗﺎﺒﻠﺔ ﻟﻼﺸﺘﻌﺎل ﺃﻭ ﺘﻜﻭﻥ ﻤﻥ ﺍﻟﺼﺎﺝ‪.‬‬
‫)‪ (٣‬ﻴﻘﺴﻡ ﺍﻟﻤﺒﻨﻰ ﺇﻟﻰ ﻋﺩﺓ ﻤﻨﺎﻁﻕ ﻴﺭﻜﺏ ﻓﻰ ﻜل ﻤﻨﻬﺎ ﻟﻭﺤﺔ ﺘﻭﺯﻴﻊ ﻓﺭﻋﻴﺔ ﻟﻠﺘﺤﻜﻡ ﻓﻰ‬
‫ﺍﻟﺩﻭﺍﺌﺭ ﺍﻟﻌﻤﻭﻤﻴﺔ ﺍﻟﺘﻰ ﺘﻐﺫﻯ ﺍﻟﻤﻨﻁﻘﺔ‪.‬‬
‫)‪ (٤‬ﻴﻔﻀل ﺩﺍﺌﻤﺎﹰ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻰ ﺍﻟﻜﺒﻴﺭﺓ ﺍﻟﻤﻤﺘﺩﺓ ﺃﻓﻘﻴﺎﹰ ﻭﺍﻟﺘﻰ ﺘﺘﻜﻭﻥ ﻤﻥ ﺃﺠﺯﺍﺀ ﻴﻔﺼل ﺒﻴﻨﻬﺎ‬
‫ﻓﻭﺍﺼل ﺘﻤﺩﺩ‪ ،‬ﺃﻥ ﺘﺨﺘﺹ ﻜل ﻟﻭﺤﺔ ﺃﻭ ﻋﺩﺩ ﻤﻥ ﻟﻭﺤﺎﺕ ﺍﻟﺘﻭﺯﻴﻊ ﺍﻟﻔﺭﻋﻴﺔ ﺒﺠـﺯﺀ‬
‫ﻤﻥ ﺃﺠﺯﺍﺀ ﺍﻟﻤﺒﻨﻰ ﻭﺫﻟﻙ ﻟﺘﻘﻠﻴل ﻋﺒﻭﺭ ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﻜﺎﺒﻼﺕ ﻟﻔﻭﺍﺼل ﺍﻟﺘﻤﺩﺩ ﺇﻟـﻰ‬
‫ﺍﻟﺤﺩ ﺍﻷﺩﻨﻰ‪.‬‬

‫‪١/٦‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫)‪ (٥‬ﻴﻔﻀل ﺃﻥ ﺘﻜﻭﻥ ﻟﻭﺤﺎﺕ ﺍﻟﺘﻭﺯﻴﻊ ﺍﻟﺭﺌﻴﺴﻴﺔ ﻭﺍﻟﻔﺭﻋﻴﺔ ﻤﺴﺘﻘﻠﺔ ﻟﻜل ﻤـﻥ ﺘﺭﻜﻴﺒـﺎﺕ‬
‫ﺍﻹﻨﺎﺭﺓ ﻭﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻘﻭﻯ ﻭﺘﻜﻭﻥ ﻤﻐﺫﻴﺎﺕ ﻜل ﻤﻨﻬـﺎ ﻤﻨﻔﺼـﻠﺔ ﻋـﻥ ﺍﻟﻤﻐـﺫﻴﺎﺕ‬
‫ﺍﻷﺨﺭﻯ‪.‬‬
‫ﻭﻴﺠﻭﺯ ﺘﺠﻤﻴﻊ ﻗﻭﺍﻁﻊ ﻭﻤﻔﺎﺘﻴﺢ ﻭﻤﺼﺎﻫﺭ ﻜل ﻤﻥ ﺍﻹﻨﺎﺭﺓ ﻭﺍﻟﻘﻭﻯ ﻓﻰ ﻟﻭﺤﺔ ﻭﺍﺤﺩﺓ‬
‫ﻋﻠﻰ ﺃﻥ ﺘﻜﻭﻥ ﻗﻀﺒﺎﻥ ﺍﻟﺘﻭﺯﻴﻊ ﻭﺃﺠﻬﺯﺓ ﺍﻟﺘﺤﻜﻡ ﻭﻜـﺎﺒﻼﺕ ﺍﻟﺘﻐﺫﻴـﺔ ﻟﻜـل ﻤـﻥ‬
‫ﺘﺭﻜﻴﺒﺎﺕ ﺍﻹﻨﺎﺭﺓ ﻭﺍﻟﻘﻭﻯ ﻤﻨﻔﺼﻠﺔ ﻋﻥ ﺒﻌﻀﻬﺎ ﻭﺒﺸﺭﻁ ﺃﻥ ﺘﻜﻭﻥ ﺍﻟﺘﻐﺫﻴـﺔ ﺒـﻨﻔﺱ‬
‫ﻨﻭﻉ ﻭﺠﻬﺩ ﺍﻟﺘﻴﺎﺭ ﻤﻊ ﻤﺭﺍﻋﺎﺓ ﺘﻤﻴﻴﺯ ﻜل ﻤﻨﻬﻤﺎ‪.‬‬
‫)‪ (٦‬ﻴﺠﺏ ﺘﺭﻙ ﻓﺭﺍﻍ ﻜﺎﻓﻰ ﺤﻭل ﺍﻟﻠﻭﺤﺔ ﻤﻥ ﺠﻬﺔ ﺍﻟﺘﺸﻐﻴل ﻭﺒـﻴﻥ ﻭﺍﺠﻬـﺔ ﺍﻟﻠﻭﺤـﺔ‬
‫ﻭﺍﻟﺤﺎﺌﻁ ﺍﻟﻤﻘﺎﺒل ﻟﻬﺎ ﺃﻭ ﺒﻴﻨﻬﺎ ﻭﺒﻴﻥ ﺍﻟﻠﻭﺤﺔ ﺍﻟﺘﺎﻟﻴﺔ ﺃﻭ ﺍﻟﻤﻌﺩﺍﺕ ﺍﻟﻘﺭﻴﺒـﺔ ﻤﻨﻬـﺎ ﺃﻭ‬
‫ﺒﻴﻨﻬﺎ ﻭﺒﻴﻥ ﺃﻯ ﻋﺎﺌﻕ ﻟﻀﻤﺎﻥ ﺴﻬﻭﻟﺔ ﺍﻟﺘﺸﻐﻴل ﻭﺍﻟﺼﻴﺎﻨﺔ ﻟﻠﻭﺤﺎﺕ‪.‬‬
‫)‪ (٧‬ﻴﺠﺏ ﺘﺄﺭﻴﺽ ﺃﺠﺴﺎﻡ ﺠﻤﻴﻊ ﻟﻭﺤﺎﺕ ﺍﻟﺘﻭﺯﻴﻊ‪.‬‬
‫)‪ (٨‬ﻴﺠﺏ ﺃﻻ ﻴﻘل ﺍﻟﺒﻌﺩ ﺒﻴﻥ ﻤﻭﺼﻼﺕ ﺍﻷﻁﻭﺍﺭ ﺒﻘﻀﺒﺎﻥ ﺍﻟﺘﻭﺯﻴﻊ ﻓﻰ ﺍﻟﻠﻭﺤـﺎﺕ ﻋـﻥ‬
‫‪٢.٥٤‬ﺴﻡ ﻜﻤﺎ ﻴﺠﺏ ﺃﻻ ﺘﻘل ﺍﻟﻤﺴﺎﻓﺔ ﺒﻴﻨﻬﺎ ﻭﺒﻴﻥ ﺃﻯ ﺠﺯﺀ ﻤﺅﺭﺽ ﻓﻰ ﺍﻟﻠﻭﺤﺔ ﻋﻥ‬
‫‪٢.٥٤‬ﺴﻡ‪.‬‬
‫)‪ (٩‬ﻴﺠﺏ ﺃﻥ ﻴﺴﻤﺢ ﺒﻨﺎﺀ ﺍﻟﻠﻭﺤﺔ ﺒﺈﻤﻜﺎﻨﻴﺔ ﺍﻟﺘﻭﺴﻊ ﻤﺴﺘﻘﺒﻼﹰ‪.‬‬

‫ﻟﻭﺤﺎﺕ ﺘﻭﺯﻴﻊ ﺍﻟﺠﻬﺩ ﺍﻟﻤﺘﻭﺴﻁ‬ ‫‪١-٦‬‬


‫ﻴﻠﺯﻡ ﻋﻨﺩ ﺘﺼﻤﻴﻡ ﻟﻭﺤﺎﺕ ﺍﻟﺘﻭﺯﻴﻊ ﻟﻠﺠﻬﺩ ﺍﻟﻤﺘﻭﺴﻁ ﻤﺭﺍﻋﺎﺓ ﺍﻵﺘﻰ‪:‬‬
‫ﺃﻭﻻﹰ‪ :‬ﺍﻟﻤﺒﺎﻨﻰ ﺍﻟﺘﻰ ﺘﺤﺘﺎﺝ ﻟﻁﺎﻗﺔ ﻜﻬﺭﺒﺎﺌﻴﺔ ﺘﺯﻴﺩ ﻋﻥ ‪ ٢٥٠‬ﻜﻴﻠﻭ ﻓﻭﻟـﺕ ﺃﻤﺒﻴـﺭ‪ ،‬ﻴﻠـﺯﻡ‬
‫ﻤﺭﺍﺠﻌﺔ ﺸﺭﻜﺔ ﺘﻭﺯﻴﻊ ﺍﻟﻜﻬﺭﺒﺎﺀ ﻓﻰ ﺍﻟﻤﻨﻁﻘﺔ ﺍﻟﺘﻰ ﺴﻴﻨﺸﺄ ﻓﻴﻬﺎ ﺍﻟﻤﺒﻨﻰ ﻟﻠﺘﺄﻜـﺩ ﻤـﻥ‬
‫ﺘﻭﻓﻴﺭ ﺍﻟﻁﺎﻗﺔ ﻟﺘﻐﺫﻴﺔ ﺍﻟﻤﺒﻨﻰ‪ ،‬ﻭﻫل ﺴﺘﺘﻡ ﺍﻟﺘﻐﺫﻴﺔ ﺒﻐﺭﻓﺔ ﻤﺤﻭﻻﺕ ﺃﻭ ﻜﺸﻙ ﻤﻌـﺩﻨﻰ‬
‫ﻭﻟﻭﺤﺔ ﺤﻠﻘﻴﺔ ﻭﺍﻟﻤﺤﻭل ﻭﻟﻭﺤﺔ ﻀﻐﻁ ﻤﻨﺨﻔﺽ ﻤﻊ ﻤﻜﺜﻔـﺎﺕ ﺘﺤﺴـﻴﻥ ﻤﻌﺎﻤـل‬
‫ﺍﻟﻘﺩﺭﺓ‪ ،‬ﺃﻭ ﻴﻠﺯﻡ ﺇﻨﺸﺎﺀ ﻤﻭﺯﻉ‪ ،‬ﻤﻊ ﺍﻟﻌﻠﻡ ﺃﻥ ﻤﻌﻅﻡ ﺸﺭﻜﺎﺕ ﺘﻭﺯﻴﻊ ﺍﻟﻜﻬﺭﺒﺎﺀ ﻟـﺩﻴﻬﺎ‬
‫ﻗﻁﺎﻉ ﻤﻘﺎﻭﻻﺕ ﻴﻘﻭﻡ ﺒﺘﻭﺭﻴﺩ ﻭﺘﺭﻜﻴﺏ ﺍﻟﻤﻌﺩﺍﺕ ﻭﻗﺩ ﺘﻌﺭﺽ ﺍﻟﻘﻴﺎﻡ ﺒﺎﻟﻌﻤل ﻜـﺎﻤﻼﹰ‬
‫ﻋﻠﻰ ﻨﻔﻘﺔ ﺼﺎﺤﺏ ﺍﻟﻤﺸﺭﻭﻉ‪.‬‬
‫ﺜﺎﻨﻴﺎﹰ‪ :‬ﻓﻰ ﺤﺎﻟﺔ ﻁﻠﺏ ﺇﻨﺸﺎﺀ ﻤﻭﺯﻉ ﻀﻐﻁ ﻤﺘﻭﺴﻁ ﻟﺘﻐﺫﻴﺔ ﺍﻟﻤﺒﻨـﻰ ﻭﺘﺭﻜﻴـﺏ ﻤﺤـﻭﻻﺕ‬
‫ﻭﻟﻭﺤﺎﺕ ﻀﻐﻁ ﻤﻨﺨﻔﺽ‪ ،‬ﻴﻠﺯﻡ ﺃﻥ ﻴﺘﻭﻟﻰ ﺍﺴﺘﺸﺎﺭﻯ ﻤﺘﺨﺼﺹ ﺘﺼﻤﻴﻡ ﺍﻟﻠﻭﺤـﺎﺕ‬
‫ﻭﺍﻟﻤﻬﻤﺎﺕ‪.‬‬

‫‪٢/٦‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺜﺎﻟﺜﺎﹰ‪ :‬ﻴﻠﺯﻡ ﻤﺭﺍﻋﺎﺓ ﺍﻟﺘﺎﻟﻰ ﻋﻨﺩ ﺘﺼﻤﻴﻡ ﺍﻟﻤﻭﺯﻉ )ﻟﻭﺤﺎﺕ ﺍﻟﺠﻬﺩ ﺍﻟﻤﺘﻭﺴﻁ(‪:‬‬
‫)‪ (١‬ﺘﺤﺩﻴﺩ ﺠﻬﺩ ﺍﻟﺘﺸﻐﻴل ‪ ٢٢ – ٢٠ – ١١ – ١٠.٥‬ﻜﻴﻠﻭ ﻓﻭﻟﺕ‪.‬‬
‫)‪ (٢‬ﻤﻌﺭﻓﺔ ﻤﺘﻁﻠﺒﺎﺕ ﺸﺭﻜﺔ ﺘﻭﺯﻴﻊ ﺍﻟﻜﻬﺭﺒﺎﺀ ﺍﻟﻤﺨﺘﺼـﺔ ﻓـﻰ ﻤﻨﻁﻘـﺔ ﺇﻗﺎﻤـﺔ‬
‫ﺍﻟﻤﺸﺭﻭﻉ‪.‬‬
‫)‪ (٣‬ﺘﺼﻨﻊ ﻟﻭﺤﺎﺕ ﺍﻟﺠﻬﺩ ﺍﻟﻤﺘﻭﺴﻁ ﻤﻥ ﺃﻟﻭﺍﺡ ﺼﻠﺏ ﻤﻌﺩﻨﻴﺔ ﺴﻤﻙ ﻻ ﻴﻘل ﻋـﻥ‬
‫‪ ٢.٥‬ﻤﻡ ﻭﺘﻜﻭﻥ ﻤﻁﺎﺒﻘﺔ ﻓﻰ ﺍﻟﺘﺼﻨﻴﻊ ﻟﻠﻤﻭﺍﺼﻔﺎﺕ ﺍﻟﻘﻴﺎﺴﻴﺔ ﺍﻟﻤﺼﺭﻴﺔ ﻡ‪.‬ﻕ‪.‬ﻡ‬
‫)‪ (٨٦‬ﻭﺍﻟﻌﺎﻟﻤﻴﺔ )‪ (IEC-898‬ﻤﻥ ﻁـﺭﺍﺯ )‪ (Metal clad‬ﻭﺍﻟﻘـﺎﻁﻊ ﻗﺎﺒـل‬
‫ﻟﻠﺴﺤﺏ ﻋﻨﺩ ﺍﻟﻔﺼل ﻷﻏﺭﺍﺽ ﺍﻟﺼﻴﺎﻨﺔ ﻭﺘﺄﻤﻴﻥ ﺍﻟﺘﺸﻐﻴل‪.‬‬
‫)‪ (٤‬ﻴﺤﺩﺩ ﻨﻭﻉ ﺍﻟﻘﻭﺍﻁﻊ ﺍﻟﻤﻔﻀل‪ ،‬ﺇﻤﺎ ﺘﺨﻠﺨﻠﻰ )‪ (Vacuum‬ﺃﻭ ﻏﺎﺯﻯ )ﺴـﺎﺩﺱ‬
‫ﻓﻠﻭﺭﻴﺩ ﺍﻟﻜﺒﺭﻴﺕ ‪.(SF6‬‬
‫)‪ (٥‬ﺘﺘﺤﻤل ﺍﻟﻠﻭﺤﺔ ﺴﻌﺔ ﻗﻁﻊ ﻻ ﺘﻘل ﻋﻥ ‪ ٢٥‬ﻜﻴﻠﻭ ﺃﻤﺒﻴﺭ ﻋﻨﺩ ﺠﻬﺩ ‪ ١١‬ﻜﻴﻠـﻭ‬
‫ﻓﻭﻟﺕ ﺃﻭ ‪ ٢٠‬ﻜﻴﻠﻭ ﺃﻤﺒﻴﺭ ﻋﻨﺩ ﺠﻬﺩ ‪ ٢٢‬ﻜﻴﻠﻭ ﻓﻭﻟﺕ‪.‬‬
‫)‪ (٦‬ﺘﻌﻤل ﻟﻭﺤﺎﺕ ﺍﻟﺘﻐﺫﻴﺔ ﻤﻊ ﻟﻭﺤﺔ ﺍﻟﺭﺒﻁ ﺒﻨﻅﺎﻡ ﺘﺄﻤﻴﻥ ﻜﺎﻤـل ﻤـﻊ ﻀـﺭﻭﺭﺓ‬
‫ﻭﺠﻭﺩ ﻤﻔﺘﺎﺡ ﺘﺄﺭﻴﺽ ﻓﻰ ﺍﻟﻠﻭﺤﺎﺕ ﺍﻟﻤﻐﺫﺍﺓ ﺒﻜﺎﺒﻼﺕ ﻟﺘﺄﻤﻴﻥ ﺍﻟﻔﺼـل ﻭﻤـﻥ‬
‫ﺍﻟﻁﺭﺍﺯ ﺍﻟﺫﻯ ﻴﺘﺤﻤل ﺍﻟﺘﻐﺫﻴﺔ ﻋﻠﻰ ﺍﻟﻘﺼﺭ ﻭﺴﻌﺔ ﺍﻟﺘﻴـﺎﺭ ﻟﻬـﺫﻩ ﺍﻟﻘﻭﺍﻁـﻊ‬
‫‪ ١٢٥٠‬ﺃﻤﺒﻴﺭ ﻭﺘﻜﻭﻥ ﺴﻌﺔ ﺘﻴﺎﺭ ﻗﻀﺒﺎﻥ ﺍﻟﺘﻭﺯﻴﻊ ﻨﻔﺱ ﻫﺫﻩ ﺍﻟﺴـﻌﺔ ﻋﻠـﻰ‬
‫ﺍﻷﻗل‪.‬‬
‫)‪ (٧‬ﺘﺯﻭﺩ ﺨﻼﻴﺎ ﺍﻟﺨﺭﻭﺝ ﺒﺴﻜﺎﻜﻴﻥ ﻓﺼل ﻋﻠﻰ ﺍﻟﺤﻤل ﺴﻌﺔ ‪ ٤٠٠‬ﺃﻤﺒﻴﺭ ﻜﺎﻤﻠـﺔ‬
‫ﺒﺎﻟﻤﺼﺎﻫﺭ ﺴﺭﻴﻌﺔ ﺍﻟﻘﻁﻊ ﺍﻟﻤﺘﺼﻠﺔ ﺒﻨﻅﺎﻡ ﻤﻴﻜﺎﻨﻴﻜﻰ ﻟﻔﺼل ﺍﻟﺴﻜﻴﻨﺔ ﻓﻰ ﺤﺎﻟﺔ‬
‫ﺍﻨﺼﻬﺎﺭ ﺃﻯ ﻤﻥ ﺍﻟﻤﺼـﺎﻫﺭﺍﻟﺜﻼﺜﺔ ﻭﺫﻟـﻙ ﻟﻠﻤﺤـﻭﻻﺕ ﺍﻟﺘـﻰ ﻻ ﺘﺠـﺎﻭﺯ‬
‫ﻗﺩﺭﺘﻬﺎ‪ ١٥٠٠‬ﻜﻴﻠﻭ ﻓﻭﻟﺕ ﺃﻤﺒﻴﺭ‪.‬‬
‫)‪ (٨‬ﻴﻠﺯﻡ ﺃﻥ ﻴﺭﻜﺏ ﺒﺨﻠﻴﺔ ﺍﻟﺨﺭﻭﺝ ﻟﻠﻤﺤﻭﻻﺕ ﺫﺍﺕ ﺍﻟﻘﺩﺭﺓ ﺃﻜﺒـﺭ ﻤـﻥ ‪١٥٠٠‬‬
‫ﻜﻴﻠﻭ ﻓﻭﻟﺕ ﺃﻤﺒﻴﺭ ﻗﻭﺍﻁﻊ ﺒﺴﻌﺔ ‪ ٦٣٠‬ﺃﻤﺒﻴﺭ ﻜﺎﻤﻠﺔ ﺒﺄﺠﻬﺯﺓ ﻭﻗﺎﻴﺔ ﻟﻠﺤﻤﺎﻴـﺔ‬
‫ﺤﺴﺏ ﺍﻟﺘﺼﻤﻴﻡ ﻭﺍﻟﻤﻌﺘﻤﺩ ﻤﻥ ﺸﺭﻜﺔ ﺘﻭﺯﻴﻊ ﺍﻟﻜﻬﺭﺒﺎﺀ ﺍﻟﻤﺨﺘﺼﺔ ﻓﻰ ﻤﻨﻁﻘـﺔ‬
‫ﺍﻟﻤﺸﺭﻭﻉ‪.‬‬
‫)‪ (٩‬ﻴﻠﺯﻡ ﺃﻥ ﻴﻜﻭﻥ ﺍﻟﻤﻭﺯﻉ )ﻟﻭﺤﺎﺕ ﺍﻟﺠﻬﺩ ﺍﻟﻤﺘﻭﺴـﻁ( ﻤـﻭﺭﺩﺍ ﻤـﻥ ﺸـﺭﻜﺔ‬
‫ﺼﻨﺎﻋﻴﺔ ﻤﻌﺘﻤﺩﺓ ﻟﺩﻯ ﺸﺭﻜﺔ ﺘﻭﺯﻴﻊ ﺍﻟﻜﻬﺭﺒﺎﺀ ﺍﻟﻤﺨﺘﺼﺔ‪.‬‬

‫‪٣/٦‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻟﻭﺤﺎﺕ ﺘﻭﺯﻴﻊ ﺍﻟﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ‬ ‫‪٢-٦‬‬


‫‪ -‬ﺘﺼﻨﻊ ﺍﻟﻠﻭﺤﺎﺕ ﻤﻥ ﺼﻠﺏ ﻻ ﻴﻘل ﺴﻤﻜﻪ ﻋﻥ ‪ ٢‬ﻤﻡ ﻭﺘﻜـﻭﻥ ﻤﻁﺎﺒﻘـﺔ ﻟﻠﻤﻭﺍﺼـﻔﺎﺕ‬
‫ﺍﻟﻘﻴﺎﺴﻴﺔ ﺍﻟﻤﺼﺭﻴﺔ )ﻡ‪.‬ﻕ‪.‬ﻡ ‪ (٣٦٠‬ﺃﻭ )‪.(IEC 439‬‬
‫‪ -‬ﻻ ﻴﻘل ﺠﻬﺩ ﺍﻟﻌﺯل ﻋﻥ ‪ ١٠٠٠‬ﻓﻭﻟﺕ ﺘﻴﺎﺭ ﻤﺘﻐﻴﺭ ﻭﺘﺘﺤﻤل ﻗﻀﺒﺎﻥ ﺍﻟﺘﻭﺯﻴﻊ ﻭﻗﻭﺍﻁـﻊ‬
‫ﺍﻟﺩﺨﻭل ﻟﻜﺎﺒﻼﺕ ﺍﻟﺘﻐﺫﻴﺔ ﻭﻟﻭﺤﺔ ﺍﻟﺭﺒﻁ )‪ (Coupler‬ﺍﻷﺤﻤﺎل ﺍﻟﻤﺘﻭﻗﻌﺔ ﻟﻠﻤﺸﺭﻭﻉ‪.‬‬
‫‪ -‬ﺘﻜﻭﻥ ﺴﻌﺔ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﻜﺤﺩ ﺃﺩﻨﻰ ﻤﺭﺘﺒﻁﺔ ﺒﻘﺩﺭﺓ ﻤﺤﻭل ﺍﻟﺘﻐﺫﻴﺔ ‪ ،‬ﻓﻌﻠﻰ ﺴﺒﻴل ﺍﻟﻤﺜﺎل‬
‫ﺍﻟﻤﺤﻭل ﻗﺩﺭﺓ ‪ ٥٠٠‬ﻙ‪.‬ﻑ‪.‬ﺃ‪ ، .‬ﺘﻜﻭﻥ ﺍﻷﺤﻤﺎل ﺍﻟﻤﻐﺫﺍﺓ ﻤﻥ ﻫـﺫﺍ ﺍﻟﻤﺤـﻭل ﺒﻘﻭﺍﻁـﻊ‬
‫ﺘﺘﺤﻤل ﺘﻴﺎﺭ ﻗﺼﺭ ﻻ ﻴﻘل ﻋﻥ ‪ ٢٢‬ﻜﻴﻠﻭ ﺃﻤﺒﻴﺭ ﻭﺍﻟﻤﺤﻭل ﻗﺩﺭﺓ ‪ ١٠٠٠‬ﻙ‪.‬ﻑ‪.‬ﺃ‪ .‬ﺘﻜﻭﻥ‬
‫ﺍﻷﺤﻤﺎل ﺍﻟﻤﻐﺫﺍﺓ ﻤﻨﻪ ﺒﻘﻭﺍﻁﻊ ﺘﺘﺤﻤل ﺘﻴﺎﺭ ﻗﺼﺭ ﻻ ﻴﻘل ﻋﻥ ‪ ٤٥‬ﻜﻴﻠﻭ ﺃﻤﺒﻴﺭ‪ ،‬ﻭﻫﻜـﺫﺍ‬
‫ﺤﺴﺏ ﻗﺩﺭﺓ ﻭﺴﻌﺔ ﺍﻟﻤﺤﻭل ﺍﻟﻤﻐﺫﻯ ﻟﻬﺫﻩ ﺍﻷﺤﻤﺎل‪.‬‬
‫‪ -‬ﻴﻠﺯﻡ ﺃﻥ ﻴﺭﺍﻋﻰ ﻓﻰ ﻟﻭﺤﺎﺕ ﺍﻟﻀﻐﻁ ﺍﻟﻤﻨﺨﻔﺽ ﺘﺭﺘﻴﺏ ﻭﺤﺴﺎﺏ ﺴﻌﺔ ﺘﻴﺎﺭ ﺍﻟﻘﻭﺍﻁـﻊ‬
‫ﻭﻤﺭﺍﻋﺎﺓ ﺍﻟﺘﺘﺎﺒﻊ )‪ (Coordination‬ﻟﻠﻘﻭﺍﻁﻊ ﺍﻟﻌﻤﻭﻤﻴﺔ ﺜـﻡ ﺍﻟﻘﻭﺍﻁـﻊ ﺍﻟﻔﺭﻋﻴـﺔ ﻤـﻥ‬
‫ﺍﻟﻠﻭﺤﺎﺕ ﺍﻟﺭﺌﻴﺴﻴﺔ ﺇﻟﻰ ﺍﻟﻠﻭﺤﺎﺕ ﺍﻟﻔﺭﻋﻴﺔ ﻭﺍﻟﺘﺄﻜﺩ ﻤﻥ ﺃﻥ ﻨﻅﺎﻡ ﺍﻟﻭﻗﺎﻴﺔ ﻟﻠﻔﺼل ﻗﺩ ﺘـﻡ‬
‫ﺘﺭﺘﻴﺒﻪ ﻭﻀﺒﻁﻪ ﻟﻀﻤﺎﻥ ﻓﺼل ﺍﻟﻘﺎﻁﻊ ﺍﻷﻗﺭﺏ ﻟﻨﻘﻁﺔ ﺯﻴﺎﺩﺓ ﺍﻟﺤﻤل ﺃﻭ ﺍﻟﻘﺼـﺭ ﺃﻭﻻﹰ‪،‬‬
‫ﺜﻡ ﺍﻟﺫﻯ ﻴﻠﻴﻪ‪ ،‬ﻓﺎﻟﺫﻯ ﻴﻠﻴﻪ ﻓﻰ ﺍﻟﺘﺘﺎﺒﻊ ﺤﺘﻰ ﺍﻟﻘﺎﻁﻊ ﻓﻰ ﺍﻟﻠﻭﺤﺎﺕ ﺍﻟﺭﺌﻴﺴﻴﺔ‪.‬‬
‫‪ -‬ﻴﻔﻀــل ﻓﻰ ﻟﻭﺤــﺎﺕ ﺍﻟﺠﻬـﺩ ﺍﻟﻤﻨﺨﻔﺽ ﻭﺍﻟﺘﻰ ﻴﻜﻭﻥ ﺴﻌﺔ ﺘﻴﺎﺭ ﺍﻟﺨﺭﻭﺝ ﺒﻬـﺎ‬
‫ﺃﻜﺒﺭ ﻤﻥ ‪ ١٥٠٠‬ﺃﻤﺒﻴﺭ ﺍﺴﺘﺨﺩﺍﻡ ﺍﻟﻘﻀﺒﺎﻥ ﺍﻟﺼـﺎﻋﺩﺓ )‪ (Buss-Risers‬ﻭﻫـﻰ ﻋﻠـﺏ‬
‫ﺼﻠﺏ ﺒﻬﺎ ﻤﻭﺼﻼﺕ ﻨﺤﺎﺱ ﺃﻭ ﺃﻟﻭﻤﻨﻴﻭﻡ ﻤﻌﺯﻭﻟﺔ ﺴﺎﺒﻘﺔ ﺍﻟﺘﺼﻨﻴﻊ ﺒﻐـﺭﺽ ﺘﻭﺼـﻴل‬
‫ﺍﻟﺘﻴﺎﺭ ﺍﻟﻜﻬﺭﺒﺎﺌﻰ ﻤﻥ ﺍﻟﻠﻭﺤﺎﺕ ﺍﻟﻌﻤﻭﻤﻴﺔ ﺇﻟﻰ ﺍﻟﻠﻭﺤﺎﺕ ﺍﻟﻔﺭﻋﻴﺔ ﻓﻰ ﺍﻟﻤﺸﺭﻭﻉ ﻭﺩﺍﺨل‬
‫ﺍﻟﻤﺒﺎﻨﻰ‪.‬‬
‫‪ -‬ﻭﻴﻜﻭﻥ ﻟﻬﺫﻩ ﺍﻟﻘﻀﺒﺎﻥ ﺍﻟﺼﺎﻋﺩﺓ ﻤﺨﺎﺭﺝ ﻟﻠﺘﻐﺫﻴﺔ ﺍﻟﻔﺭﻋﻴﺔ ﺒﻨﻅﺎﻡ ﺼـﻨﺎﺩﻴﻕ )ﺜﺎﺒﺘـﺔ( ﺃﻭ‬
‫ﻗﺎﺒﻠﺔ ﻟﻠﺴﺤﺏ )‪ (Plug-In‬ﻭﺘﻌﻤل ﻫـﺫﻩ ﺍﻟﻘﻀـﺒﺎﻥ ﻋﻠـﻰ ﺠﻬـﺩ ﺜﻼﺜـﻰ ﺍﻷﻁـﻭﺍﺭ‬
‫‪٣٨٠‬ﻓﻭﻟﺕ‪ ٢٢٠/‬ﻓﻭﻟﺕ ‪ ٣‬ﺃﻁﻭﺍﺭ ‪ +‬ﺘﻌﺎﺩل ‪ +‬ﺃﺭﻀﻰ‪ ،‬ﻭ ﺫﺒﺫﺒﺔ ‪ ٥٠‬ﻫﺭﺘﺯ‪ .‬ﻭﻤﻁﺎﺒﻘﺔ‬
‫ﻟﻠﻤﻭﺍﺼﻔﺎﺕ ﺍﻟﻘﻴﺎﺴﻴﺔ ﺍﻟﻤﺼﺭﻴﺔ ﻭﻜﺫﻟﻙ ﺍﻟﻤﻭﺍﺼﻔﺎﺕ ﺍﻟﺩﻭﻟﻴﺔ ﺍﻟﻜﻬﺭﻭﺘﻘﻨﻴﺔ )‪.(IEC‬‬

‫ﺘﺤﺩﻴﺩ ﺍﻷﺤﻤﺎل ﻟﻠﻤﺒﻨﻰ‬ ‫‪٣-٦‬‬


‫ﻴﺘﻡ ﺘﺤﺩﻴﺩ ﺍﻷﺤﻤﺎل ﻁﺒﻘﺎ ﻟﻨﻭﻉ ﺍﻟﻤﺒﻨﻰ‪ ،‬ﻭﻓﻴﻤﺎ ﻋﺩﺍ ﺍﻟﻤﻌﺩﺍﺕ ﺍﻟﺨﺎﺼﺔ ﻟﻠﻤﺒﻨﻰ‪ ،‬ﻓﺈﻨـﻪ ﻴـﺘﻡ‬
‫ﺍﺤﺘﺴﺎﺏ ﺍﻷﺤﻤﺎل ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻟﻼﺴﺘﺨﺩﺍﻡ ﺍﻟﻌﺎﻡ ﻋﻠﻰ ﺃﻨﻬﺎ ﺃﺤﻤـﺎل ﺍﻹﻀـﺎﺀﺓ ‪ ،‬ﻤﻐـﺫﻴﺎﺕ‬

‫‪٤/٦‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﺍﻟﻘﺩﺭﺍﺕ ﺍﻟﺼﻐﻴﺭﺓ )ﺍﻟﺒﺭﺍﻴﺯ( ‪ ،‬ﺃﺤﻤﺎل ﺍﻟﺘﻜﻴﻴﻑ ﻋﻠﻰ ﺃﺴﺎﺱ ﺍﻟﻘﺩﺭﺓ ﺍﻟﻼﺯﻤـﺔ ﻟﻜـل ﻤﺘـﺭ‬
‫ﻤﺭﺒﻊ ﺤﺴﺏ ﻨﻭﻉ ﻭﻤﻜﺎﻥ ﺍﻟﻤﺒﻨﻰ‪.‬‬
‫‪ -‬ﻭﻴﺭﺍﻋــﻰ ﻋﻨــﺩ ﺤﺴﺎﺒــﺎﺕ ﺍﻷﺤﻤــﺎل ﺍﻟﻤﺘﻭﻗﻌــﺔ‪ ،‬ﺍﺨﺘﻴـــﺎﺭ ﻤﻌﺎﻤـل‬
‫ﺍﻟﺘﺒﺎﻴﻥ )‪ (Diversity factor‬ﻭﺍﻟﺫﻯ ﻴﺤﺩﺩ ﻁﺒﻘﺎﹰ ﻟﻨﻭﻉ ﺍﻟﺤﻤل ﻭﻗﺩﺭﺘﻪ ﻭﻨﻭﻉ ﺍﻟﻨﺸﺎﻁ‪.‬‬
‫‪ -‬ﺒﻌﺩ ﺘﺤﺩﻴﺩ ﺍﻟﺤﻤل ﺍﻟﺘﻘﺩﻴﺭﻯ ﻟﻠﻤﺒﻨﻰ ﺘﺤﺩﺩ ﺍﻟﻘﺩﺭﺓ ﺍﻟﻤﻁﻠﻭﺒﺔ ﻟﻪ‪ ،‬ﻭﺘﺼﻨﻑ ﺍﻟﻤﺒﺎﻨﻰ ﻤـﻥ‬
‫ﺤﻴﺙ ﺍﻟﻘﺩﺭﺓ ﻋﻠﻰ ﺍﻟﻨﺤﻭ ﺍﻟﺘﺎﻟﻰ‪:‬‬
‫)‪ (١‬ﻤﺒﻨﻰ ﻴﺤﺘﺎﺝ ﻟﻘﺩﺭﺓ ﺘﺴﺎﻭﻯ ﺃﻭ ﺃﻗل ﻤﻥ ‪ ٢٠٠‬ﻙ‪.‬ﻑ‪.‬ﺃ )ﻤﺒﻨﻰ ﻤﺤﺩﻭﺩ(‪.‬‬
‫)‪ (٢‬ﻤﺒﻨﻰ ﻴﺤﺘﺎﺝ ﻟﻘﺩﺭﺓ ﺃﻜﺒﺭ ﻤﻥ ‪ ٢٠٠‬ﻙ‪.‬ﻑ‪.‬ﺃ‪ .‬ﻭﺃﻗل ﻤـﻥ ‪ ٥٠٠‬ﻙ‪.‬ﻑ‪.‬ﺃ )ﻤﺒﻨـﻰ‬
‫ﻤﺘﻭﺴﻁ(‪.‬‬
‫)‪ (٣‬ﻤﺒﻨﻰ ﻴﺤﺘﺎﺝ ﻟﻘﺩﺭﺓ ﺃﻜﺒﺭ ﻤﻥ ‪ ٥٠٠‬ﻙ‪.‬ﻑ‪.‬ﺃ‪ .‬ﻭﺃﻗل ﻤﻥ ‪ ١٠٠٠‬ﻙ‪.‬ﻑ‪.‬ﺃ )ﻤﺒﻨـﻰ‬
‫ﻋﺎﻡ(‪.‬‬
‫)‪ (٤‬ﻤﺒﻨﻰ ﻴﺤﺘﺎﺝ ﻟﻘﺩﺭﺓ ﺃﻜﺒﺭ ﻤﻥ ‪ ١٠٠٠‬ﻙ‪.‬ﻑ‪.‬ﺃ‪ .‬ﻭﺃﻗل ﻤﻥ ‪ ٢٠٠٠‬ﻙ‪.‬ﻑ‪.‬ﺃ )ﻤﺒﻨﻰ‬
‫ﻜﺒﻴﺭ(‪.‬‬
‫)‪ (٥‬ﻤﺒﻨﻰ ﻴﺤﺘﺎﺝ ﻟﻘﺩﺭﺓ ﺃﻜﺒﺭ ﻤﻥ ‪ ٢٠٠٠‬ﻙ‪.‬ﻑ‪.‬ﺃ )ﻤﺒﻨﻰ ﻤﺭﻜﺯﻯ(‪.‬‬
‫ﻴﻠﺯﻡ ﻟﺘﻐﺫﻴﺔ ﻫﺫﻩ ﺍﻟﻁﺭﺍﺯﺍﺕ ﻤﻥ ﺍﻟﻤﺒﺎﻨﻰ ﺒﺎﻟﻁﺎﻗﺔ ﺍﻟﻜﻬﺭﺒﺎﺌﻴـﺔ ‪ ،‬ﺒﻌـﺩ ﺘﺤﺩﻴـﺩ ﻗـﺩﺭﺓ‬
‫ﺍﻷﺤﻤﺎل ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﺍﻟﻤﺘﻭﻗﻌﺔ ﻟﻠﻤﺒﻨﻰ ‪ ،‬ﺍﺨﺘﻴﺎﺭ ﺍﻟﺸﺭﻴﺤﺔ ﺍﻟﺘﻰ ﺘﻠـﺯﻡ ﻟﺘﻐﺫﻴـﺔ ﺍﻟﻤﺒﻨـﻰ‬
‫ﻭﺘﺤﺩﻴﺩ ﻁﺭﺍﺯ ﺍﻟﻤﺒﻨﻰ ) ﻤﺒﻨﻰ ﻤﺤﺩﻭﺩ ‪ /‬ﻤﺒﻨﻰ ﻤﺘﻭﺴﻁ ‪ /‬ﻤﺒﻨﻰ ﻋﺎﻡ ‪ /‬ﻤﺒﻨـﻰ ﻜﺒﻴـﺭ ‪/‬‬
‫ﻤﺒﻨﻰ ﻤﺭﻜﺯﻯ(‪.‬‬
‫ﺘﻜﻭﻥ ﺍﻟﺘﻐﺫﻴﺔ ﻟﻠﻤﺒﻨﻰ ﺤﺴﺏ ﺍﺸﺘﺭﺍﻁﺎﺕ ﺸﺭﻜﺔ ﺘﻭﺯﻴﻊ ﺍﻟﻜﻬﺭﺒﺎﺀ ﺍﻟﻭﺍﻗﻊ ﺍﻟﻤﺒﻨـﻰ ﻓـﻰ‬
‫ﻨﻁﺎﻗﻬﺎ ‪ ،‬ﻭﻴﻠﺯﻡ ﺍﻹﻟﻤﺎﻡ ﺒﻬﺎ ﻤﻥ ﺠﺎﻨﺏ ﺍﻟﻘﺎﺌﻡ ﺒﺎﻟﺘﺼﻤﻴﻡ ‪ ،‬ﻭﻴﻤﻜﻥ ﻤﺭﺍﺠﻌـﺔ ﺸـﺭﻜﺎﺕ‬
‫ﺘﻭﺯﻴﻊ ﺍﻟﻜﻬﺭﺒﺎﺀ ﻻﺴﺘﻴﻀﺎﺡ ﺃﻯ ﺒﻴﺎﻨﺎﺕ ﻟﺘﻴﺴﻴﺭ ﺃﺩﺍﺀ ﺍﻟﻌﻤل‪.‬‬
‫ﻭﺘﻘﻭﻡ ﺸﺭﻜﺎﺕ ﺘﻭﺯﻴﻊ ﺍﻟﻜﻬﺭﺒﺎﺀ ﺒﺘﻐﺫﻴﺔ ﺍﻟﻤﺒﺎﻨﻰ ﻋﻠﻰ ﺍﻟﻨﺤﻭ ﺍﻟﺘﺎﻟﻰ‪:‬‬
‫)‪ (١‬ﺍﻟﻤﺒﻨﻰ ﺍﻟﻤﺤﺩﻭﺩ )ﻗﺩﺭﺓ ﺘﺴﺎﻭﻯ ﺃﻭ ﺃﻗل ﻤﻥ ‪ ٢٠٠‬ﻙ‪.‬ﻑ‪.‬ﺃ( ﻴﺘﻡ ﺍﻟﺘﻐﺫﻴـﺔ ﺒﻜﺎﺒـل‬
‫ﻤﻥ ﺸﺒﻜﺔ ﻀﻐﻁ ﻤﻨﺨﻔﺽ ﻋﻠﻰ ﺠﻬﺩ ﺜﻼﺜﻰ ﺍﻷﻁﻭﺍﺭ"‪ ٢٢٠ / ٣٨٠‬ﻓﻭﻟـﺕ "–‬
‫‪ ٥٠‬ﻫﺭﺘﺯ‪.‬‬
‫‪ -‬ﻭﺘﻘﻭﻡ ﺸﺭﻜﺔ ﺍﻟﺘﻭﺯﻴﻊ ﺒﻌﻤل ﻤﻘﺎﻴﺴﺔ ﻟﻠﺘﻐﺫﻴﺔ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ – ﺘﺸﻤل ﺤﺼﺔ ﺍﻟﻤﺒﻨـﻰ‬
‫ﻤﻥ ﺘﻜﺎﻟﻴﻑ ﺘﻭﻓﻴﺭ ﺍﻟﺘﻐﺫﻴﺔ ﺒﺎﻟﻁﺎﻗﺔ ﺍﻟﻤﺘﻌﺎﻗﺩ ﻋﻠﻴﻬﺎ‪ ،‬ﺤﺴﺏ ﺍﻟﻘـﻭﺍﻨﻴﻥ ﻭﺍﻟﻠـﻭﺍﺌﺢ‬
‫ﺍﻟﻤﻨﻅﻤﺔ ﻟﺫﻟﻙ‪.‬‬

‫‪٥/٦‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫‪ -‬ﻴﺘﻡ ﺘﺭﻜﻴﺏ ﺼﻨﺩﻭﻕ ﻤﺩﺨل ﺍﻟﻌﻤﺎﺭﺓ )ﺃﻭ ﻜﻭﻓﺭﻴﻪ( ﺃﻭ ﺼﻨﺩﻭﻕ ﺘﻭﺯﻴﻊ ﻤﻥ ﺍﻟﻔﻴﺒﺭ‬
‫ﺠﻼﺱ ﻟﺭﺒﻁ ﻜﺎﺒﻼﺕ ﺍﻟﺩﺨﻭل ﻭﻜﺎﺒﻼﺕ ﺍﻟﺨﺭﻭﺝ ﻟﻠﻤﺒﻨﻰ – ﺜﻡ ﻤﻥ ﺨﻼل ﻭﺤﺩﺓ‬
‫ﻗﻁﻊ ﻜﺎﻤﻠﺔ ﻟﻠﻭﻗﺎﻴﺔ ﻜﺎﻟﻤﺼﺎﻫﺭ – ﺃﻭ ﺍﻟﻘﻭﺍﻁﻊ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ‪ ،‬ﻴﺘﻡ ﺨﺭﻭﺝ ﻜـﺎﺒﻼﺕ‬
‫ﺘﻐﺫﻴﺔ ﺍﻟﻤﺒﻨﻰ‪.‬‬
‫ﺘﺒﻴﻥ ﺍﻷﺸﻜﺎل ﺍﻟﺘﺎﻟﻴﺔ ﺒﻌﺽ ﻨﻤﺎﺫﺝ ﻟﻠﻭﺤﺎﺕ ﻜﻬﺭﺒﺎﺌﻴﺔ ﺘﺘﺤﻜﻡ ﻓﻰ ﺍﻟﺘﻐﺫﻴﺔ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ‬
‫ﻟﻠﻤﺒﻨﻰ‪ ،‬ﻭﻫﻰ ﺘﺨﺘﻠﻑ ﻤﻥ ﺸﺭﻜﺔ ﺘﻭﺯﻴﻊ ﻷﺨﺭﻯ ﻭﻟﻜﻥ ﺍﻟﺸﺎﺌﻊ ﻤﻨﻬﺎ ﻜﻤـﺎ ﻫـﻭ‬
‫ﻤﻭﻀﺢ ﻓﻰ ﺸﻜل )‪.(١-٦‬‬
‫ﻴﻭﺠﺩ ﺃﻨﻅﻤﺔ ﺃﺨﺭﻯ ﻟﺘﻐﺫﻴﺔ ﺍﻟﻤﺒﻨﻰ ﻤﺜﺎل ﺫﻟﻙ ﺍﻟﻠﻭﺤﺔ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻤﻥ ﺸﺭﻜﺔ ﺘﻭﺯﻴﻊ‬
‫ﻜﻬﺭﺒﺎﺀ ﺍﻹﺴﻜﻨﺩﺭﻴﺔ ﻜﻤﺎ ﻫﻭ ﻤﺒﻴﻥ ﻓﻰ ﺍﻟﺸﻜل )‪ – (٢-٦‬ﻭﻫﻰ ﻤﺼﻨﻭﻋﺔ ﻤـﻥ‬
‫ﺍﻟﻔﺎﻴﺒﺭ ﺠﻼﺱ – ﻭﻴﺘﻡ ﻟﺤﺎﻡ ﺍﻟﻜﺎﺒﻼﺕ ﺩﺨﻭل ﻭﺨﺭﻭﺝ ﻓﻘﻁ ﻟﻠﻤﺒﻨﻰ – ﺃﻭ ﺩﺨﻭل‬
‫ﻭﺨﺭﻭﺝ ﻭﺘﻭﺯﻴﻊ )ﺨﺭﻭﺝ ﻟﻠﻤﺒﻨﻰ(‪.‬‬

‫‪٦/٦‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫اﻟﺘﻐﺬﯾﺔ‬
‫‪N‬‬
‫اﻟﺠﺴﻢ ﻣﺆرض‬ ‫‪E‬‬
‫اﻟﺘﻐﺬﯾﺔ ﺑﻤﺼﺎھﺮ أو‬
‫ﻣﺴﻤﺎر‬
‫ﻗﻮاﻃﻊ ﺗﯿﺎر ﺣﺴﺐ اﻟﺴﻌﺔ‬
‫اﻟﺘﺄرﯾﺾ‬

‫ﺻﻨﺪوق اﻟﻤﺪﺧﻞ‬
‫)ﻛﻮﻓﺮﯾﮫ(‬
‫دﺧﻮل‪/‬ﺧﺮوج ﻋﻠﻰ ﻗﻮاﻋﺪ‬
‫ﻣﺼﺎھﺮ‬ ‫ﻣﺼﺎھﺮ ﺳﻌﺔ ‪ ٤٠٠‬أ‬

‫‪N‬‬
‫‪E‬‬
‫ﻛﺎﺑﻞ دﺧﻮل‬ ‫ﻛﺎﺑﻞ ﺧﺮوج‬
‫)ﺃ( ﺼﻨﺩﻭﻕ ﻤﺩﺨل ﺍﻟﻌﻤﺎﺭﺓ‬

‫)ﺏ( ﻜﻭﻓﺭﻴﻪ‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(١-٦‬ﻨﻤﻭﺫﺝ ﻟﻭﺤﺔ ﻟﻤﺩﺨل ﺍﻟﻌﻤﺎﺭﺓ ﻭﺍﻟﻜﻭﻓﺭﻴﻪ ﺍﻟﻤﺴﺘﺨﺩﻤﻴﻥ‬


‫ﺒﺸﺭﻜﺘﻲ ﺸﻤﺎل ﻭﺠﻨﻭﺏ ﺍﻟﻘﺎﻫﺭﺓ ﻟﺘﻭﺯﻴﻊ ﻟﻠﻜﻬﺭﺒﺎﺀ‬

‫‪٧/٦‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻟﺤﺎم ‪/‬دﺧﻮل ‪/‬ﺧﺮوج ‪/‬ﺗﻐﺬﯾﺔ وﻏﻄﺎء ﻣﻦ‬ ‫ﺧﺮوج ﻟﻠﻤﺒﻨﻰ‬


‫اﻟﺒﻼﺳﺘﯿﻚ أو ﻣﻦ اﻷﻧﺎﺑﯿﺐ اﻟﺘﻲ ﺗﻨﻜﻤﺶ‬
‫ﺑﺎﻟﺤﺮارة ﻟﺤﻤﺎﯾﺔ اﻟﺘﻮﺻﯿﻼت ﻣﻦ‬ ‫‪R‬‬ ‫‪S‬‬ ‫‪T‬‬ ‫‪N‬‬
‫اﻷﻛﺴﺪة ﻣﻦ اﻟﺠﻮ اﻟﻤﺸﺒﻊ ﺑﺎﻟﺮﻃﻮﺑﺔ‬
‫واﻷﻣﻼح اﻟﻤﺤﯿﻂ ﺑﺎﻟﺘﻮﺻﯿﻼت‬ ‫ﻟﻮﺣﺔ ﻣﺪﺧﻞ اﻟﻌﻤﺎرة‬
‫ﻣﺼﻨﻮﻋﺔ ﻣﻦ اﻟﻔﯿﺒﺮﺟﻼس‬

‫ﻛﺎﺑﻞ اﻟﺘﻐﺬﯾﺔ‬ ‫ﻛﺎﺑﻞ ﺧﺮوج‬


‫ﻟﻤﺒﻨﻰ آﺧﺮ‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(٢-٦‬ﺸﻜل ﻟﻭﺤﺔ ﻤﺩﺨل ﻋﻤﺎﺭﺓ ﻭﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﻓﻲ ﺸﺭﻜﺔ ﺘﻭﺯﻴﻊ ﻜﻬﺭﺒﺎﺀ ﺍﺴﻜﻨﺩﺭﻴﺔ‬

‫‪R‬‬

‫‪PEN‬‬

‫ﻤﺼﻬـﺭ‬

‫‪R‬‬

‫‪N‬‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(٣-٦‬ﻜﻭﻓﺭﻴﻪ ﻟﻠﺘﻭﺼﻴل ﺇﻟﻲ ﻟﻭﺤﺔ ﻋﺩﺍﺩ ﻟﻤﺒﻨﻰ ﻤﺸﺘﺭﻙ ﻭﺍﺤﺩ )‪ ٦٠/٤٠‬ﺃﻤﺒﻴﺭ(‬

‫‪٨/٦‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻭﺘﻭﺠﺩ ﻁﺭﺍﺯﺍﺕ ﺃﺨﺭﻯ ﻤﻥ ﺒﻴﻨﻬﺎ ﻜﻭﻓﺭﻴﻪ ﻋﻠﻰ ﺍﻷﻋﻤﺩﺓ ﺍﻟﻬﻭﺍﺌﻴﺔ – ﻭﻤﺭﻜﺏ ﺒﻪ ﻤﺼـﻬﺭ‬
‫ﺒﺎﻟﻘﺎﻋﺩﺓ ﻟﺘﻐﺫﻴﺔ ﻤﺸﺘﺭﻙ ﻭﺍﺤﺩ ﻟﺴﻌﺔ )‪ (١٠‬ﺃﻤﺒﻴﺭ ﻓﻰ ﻤﺒﻨﻰ ﺭﻴﻔﻰ ﺃﻭ ﺒﺴﻌﺔ ‪ ٦٠/٤٠‬ﺃﻤﺒﻴﺭ‬
‫ﻓﻰ ﻤﺒﻨﻰ ﺤﻀﺭﻯ ﻜﻤﺎ ﻫﻭ ﻤﻭﻀﺢ ﻓﻰ ﺍﻟﺸﻜل )‪ (٣-٦‬ﻭﻫﺫﺍ ﺍﻟﻁﺭﺍﺯ ﺒﺴﻴﻁ ﻭﻗﻠﻴل ﺍﻟﺘﻜﻠﻔﺔ‪.‬‬
‫ﻭﻴﺭﺍﻋﻰ ﻓﻰ ﺼﻨﺩﻭﻕ ﺘﻐﺫﻴﺔ ﻤﺩﺨل ﺍﻟﻌﻤﺎﺭﺓ )ﻟﻭﺤﺔ ﻤﺩﺨل ﺍﻟﻌﻤﺎﺭﺓ( ﻤﺎ ﻴﻠﻰ‪:‬‬
‫ﻴﻤﻨﻊ ﺘﻤﺎﻤﺎﹰ ﻭﻀﻊ ﺃﻯ ﻭﺴﻴﻠﺔ ﻗﻁﻊ ﺃﻭ ﻓﺼل ﻟﺨﻁ ﺍﻟﺘﻌﺎﺩل ﺍﻟﻤﺅﺭﺽ ﻋﻥ ﺍﻟﺸﺒﻜﺔ ﻭﺫﻟﻙ ﻓﻰ‬
‫)‪ (TN-C‬ﻷﻥ ﻗﻁـﻊ ﺘﻭﺼـﻴل‬ ‫ﺤﺎﻟﺔ ﺘﻐﺫﻴﺔ ﺍﻟﻤﺒﻨﻰ ﺒﺎﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ ﺒﻨﻅـﺎﻡ " ﺃﺕ‪-‬ﺵ"‬
‫ﺍﻷﺭﻀﻰ ﻟﺨﻁ ﺍﻟﺘﻌﺎﺩل ﺍﻟﻤﺅﺭﺽ ﻓﻰ ﺍﻟﻤﺒﻨﻰ ﻴﺅﺩﻯ ﻟﺘﺸﻐﻴل ﺍﻟﻤﻌﺩﺍﺕ ﻋﻠـﻰ ﺠﻬـﺩ ‪٣٨٠‬‬
‫ﻓﻭﻟﺕ ﻭﻴﺅﺩﻯ ﺫﻟﻙ ﻟﺘﻠﻔﻬﺎ ﺃﻭ ﺇﻟﻰ ﻤﺸﺎﻜل ﻜﺜﻴﺭﺓ ﺃﺨﺭﻯ‪.‬‬
‫ﺍﺸﺘﺭﺍﻁﺎﺕ ﻴﺠﺏ ﻤﺭﺍﻋﺎﺘﻬﺎ ﻓﻰ ﺘﻐﺫﻴﺔ ﺍﻟﻤﺒﻨﻰ ﻋﻠﻰ ﺍﻟﺠﻬﺩ ﺍﻟﻤـﻨﺨﻔﺽ ﺒﻠﻭﺤـﺔ ﻤـﺩﺨل‬ ‫‪٤-٦‬‬
‫ﺍﻟﻌﻤﺎﺭﺓ‬
‫‪ -‬ﺘﺤﺩﺩ ﻟﻭﺤﺔ ﻤﺩﺨل ﺍﻟﻌﻤﺎﺭﺓ ﺍﻟﺤﺎﻟﺔ ﺍﻟﺘﻰ ﻋﻠﻴﻬﺎ ﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﺩﺍﺨل ﺍﻟﻤﺒﻨﻰ ﻓﻴﻤﺎ‬
‫ﻴﺨﺹ ﺍﻟﺘﻭﺼﻴﻼﺕ ﺍﻟﺩﺍﺨﻠﻴﺔ ﺒﻌﺩ ﺍﻟﻠﻭﺤﺔ ﻭﺍﻟﺘﻰ ﺘﺒﺩﺃ ﺒـﺎﻟﻌﻤﻭﺩ ﺍﻟﺼـﺎﻋﺩ ﺜـﻡ ﻋﻠـﺏ‬
‫ﺼﻨﺎﺩﻴﻕ ﺍﻟﺘﻭﺯﻴﻊ ﻟﻠﺸﻘﻕ ﻭﻟﻭﺤﺔ ﺍﻟﻌﺩﺍﺩ ﺜﻡ ﻟﻭﺤﺔ ﺍﻟﺘﻭﺯﻴﻊ ﻟﻠﻤﺸﺘﺭﻙ ﻭﻜﺫﻟﻙ ﺍﻷﺤﻤـﺎل‬
‫ﺍﻟﺩﺍﺨﻠﻴﺔ ﺒﺎﻟﺸﻘﻕ‪.‬‬
‫‪ -‬ﺘﺘــﻭﻗﻑ ﺠﻭﺩﺓ ﺍﻟﺸﺒﻜﺔ ﺍﻟﺩﺍﺨﻠﻴﺔ ﻟﻠﻤﺸﺘﺭﻙ ﺤﺴﺏ ﻤﻘﺩﺍﺭ ﺍﻟﺘﺴﺭﺏ ﺍﻷﺭﻀﻰ‪ ،‬ﺃﻨﻅـﺭ‬
‫ﺸﻜل )‪.(٤-٦‬‬

‫‪٩/٦‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻋﺪاد‬ ‫ﻋﺪاد‬

‫إﻧﻘﻄﺎع أو ﻓﺼﻞ‬
‫ﺧﻂ اﻟﺘﻌﺎدل‬
‫‪E‬‬
‫‪PEN‬‬ ‫اﻟﻤﺆرض‬ ‫‪N‬‬
‫‪E‬‬

‫ﻛﺎﺑﻞ ﺗﻐﺬﯾﺔ‬ ‫ﻛﺎﺑﻞ ﺗﻐﺬﯾﺔ‬


‫ﻗﻄﺐ‬ ‫اﻟﻤﺒﻨﻰ‬ ‫اﻟﻤﺒﻨﻰ‬
‫ﺗﺄرﯾﺾ‬
‫ﻗﻄﺐ‬
‫ﺗﺄرﯾﺾ‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(٤-٦‬ﺃﺴﻠﻭﺏ ﺘﻭﺼﻴل ﺨﻁ ﺍﻟﺘﻌﺎﺩل ﺍﻟﻤﺅﺭﺽ‬

‫‪١٠/٦‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫اﻟﺼﺎﻋﺪ‬

‫ﻋﻠﺒﺔ ﺗﻮزﯾﻊ‬
‫اﻟﻮﺣﺪات اﻟﺴﻜﻨﯿﺔ‬

‫‪NE‬‬
‫ﻟﻮﺣﺔ اﻟﻌﺪاد‬ ‫ﻟﻮﺣﺔ ﺗﻮزﯾﻊ‬ ‫داﺋﺮة اﻟﺤﻤﻞ‬
‫اﻟﻮﺣﺪة اﻟﺴﻜﻨﯿﺔ‬

‫ﻣﻦ ﺻﻨﺪوق ﺗﻮزﯾﻊ‬


‫اﻟﻌﻤﺎرة‬

‫)ﺃ( ﻨﻤﻭﺫﺝ ﻟﺘﻭﺼﻴل ﺘﻐﺫﻴﺔ ﻭﺤﺩﺓ ﺴﻜﻨﻴﺔ ﻤﻥ ﺼﺎﻋﺩ ﺍﻟﻌﻤﺎﺭﺓ‬

‫‪N R S T‬‬

‫ﺣﻠﻘﺔ ﻗﯿﺎس اﻟﺘﺴﺮب‬


‫اﻷرﺿﻲ‬

‫ﻛﺎﺑﻞ ﺗﻐﺬﯾﺔ‬
‫اﻟﻤﺒﻨﻰ‬

‫ﺟﮭﺎز ﻗﯿﺎس اﻟﺘﺴﺮب‬


‫اﻷرﺿﻲ‬

‫)ﺏ( ﻨﻤﻭﺫﺝ ﻤﺒﺴﻁ ﻟﻘﻴﺎﺱ ﺍﻟﺘﺴﺭﺏ ﺍﻷﺭﻀﻲ‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(٥-٦‬ﻨﻤﻭﺫﺝ ﻟﺘﻭﺼﻴل ﺘﻐﺫﻴﺔ ﻭﺤﺩﺓ ﺴﻜﻨﻴﺔ ﻭﻗﻴﺎﺱ ﺍﻟﺘﺴﺭﺏ ﺍﻷﺭﻀﻲ‬

‫‪١١/٦‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫‪ -‬ﻴﺠﺏ ﺃﻻ ﺘﺘﻌﺩﻯ ﻨﺴﺒﺔ ﺍﻟﺘﺴﺭﺏ ﺍﻷﺭﻀﻰ ﻓﻰ ﺍﻟﺸﺒﻜﺔ ﺍﻟﺩﺍﺨﻠﻴﺔ ﻟﻠﻌﻤﺎﺭﺓ ﺍﻟﻘﻴﻤـﺔ ﺍﻟﺘـﻰ‬
‫ﺘﺤﺩﺩﻫﺎ ﺸﺭﻜﺔ ﺘﻭﺯﻴﻊ ﺍﻟﻜﻬﺭﺒﺎﺀ ﺍﻟﻤﺨﺘﺼﺔ ﻭﻴﺘﻡ ﻗﻴﺎﺱ ﺘﻴﺎﺭ ﺍﻟﺘﺴﺭﺏ ﺍﻷﺭﻀﻰ ﻜﻤﺎ ﻫﻭ‬
‫ﻤﻭﻀﺢ ﺒﺎﻟﺸﻜل )‪-٥-٦‬ﺏ(‪.‬‬
‫‪ -‬ﻴﺠﺏ ﺍﻟﺤﺩ ﻤﻥ ﻗﻴﻤﺔ ﺍﻟﺘﺴﺭﺏ ﺍﻷﺭﻀﻰ ﻭﻟﻤﺎ ﻴﺴﺒﺒﻪ ﻤﻥ ﺨﻁﻭﺭﺓ ﻅﻬﻭﺭ ﺠﻬﺩ ﻜﻬﺭﺒﺎﺌﻰ‬
‫ﻋﻠﻰ ﺍﻷﺠﻬﺯﺓ – ﺩﺍﺨل ﺍﻟﻤﺒﺎﻨﻰ ﻤﻤﺎ ﻴﺅﺩﻯ ﻟﻤﺸﺎﻜل ﻭﺍﻀﺭﺍﺭ ﻟﻸﻓﺭﺍﺩ ﻭﺍﻟﻤﻌﺩﺍﺕ‪.‬‬
‫‪ -‬ﻴﻌﺘﺒﺭ ﻨﻅﺎﻡ ﺍﻟﺘﺄﺭﻴﺽ ﻟﻠﻤﺒﻨﻰ ﻭﺠﻭﺩﺓ ﺍﻟﺘﻭﺼﻴﻼﺕ ﺍﻟﺩﺍﺨﻠﻴﺔ ﺸﺭﻁﺎﻥ ﺃﺴﺎﺴﻴﺎﻥ ﻟﺘـﺄﻤﻴﻥ‬
‫ﺘﻐﺫﻴﺔ ﻜﻬﺭﺒﺎﺌﻴﺔ ﺠﻴﺩﺓ ﺒﻪ‪.‬‬

‫ﻨﻅﺎﻡ ﺍﻟﺘﻐﺫﻴﺔ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻟﻠﻤﺒﺎﻨﻰ ﺍﻟﺴﻜﻨﻴﺔ‬ ‫‪٥-٦‬‬


‫ﻓﻰ ﺤﺎﻟﺔ ﺍﻟﻤﺒﺎﻨﻰ ﺍﻟﺴﻜﻨﻴﺔ ﺍﻟﺨﺎﺼﺔ )ﺃﻭ ﻭﺤﺩﺍﺕ ﺴﻜﻥ ﻋﺎﺌﻠﻰ ﺤﺘﻰ ﻟﻭ ﻜﺎﻨﺕ ﻤﺘﻌﺩﺩﺓ‬ ‫)ﺃ(‬
‫ﺍﻟﻁﻭﺍﺒﻕ(‪:‬‬
‫‪ -‬ﻴﺠﻭﺯ ﺘﺭﻜﻴﺏ ﻋﺩﺍﺩ ﻜﻬﺭﺒﺎﺌﻰ ﻭﺍﺤﺩ ﺴﻌﺔ )‪ (١٠‬ﺃﻤﺒﻴﺭ ﺃﻭ )‪ (٤٠‬ﺃﻤﺒﻴﺭ ﺃﺤـﺎﺩﻯ‬
‫ﺃﻭ ﺜﻼﺜﻰ ﺍﻷﻁﻭﺍﺭ‪.‬‬
‫‪ -‬ﻴﻠﺯﻡ ﺘﺭﻜﻴﺏ ﻋﺩﺍﺩ ﻜﻬﺭﺒﺎﺌﻰ ﻤﻨﺎﺴﺏ ﻟﻠﺨﺩﻤﺎﺕ ﺒﺎﻟﻤﺒﻨﻰ ﻭﺫﻟﻙ ﻟﺘﻐﺫﻴﺔ ﺠﺭﺍﺝ ﺒـﻪ‬
‫ﺨﺩﻤﺎﺕ ﻜﻬﺭﺒﺎﺌﻴﺔ ﻋﺎﻤﺔ ﻤﺜل )ﻁﻠﻤﺒﺎﺕ ﺭﻓﻊ ﻭﻨﺯﺡ ﺍﻟﻤﻴﺎﻩ‪ ،‬ﺇﻨـﺎﺭﺓ ﻋﺎﻤـﺔ ﻓـﻰ‬
‫ﺍﻟﻤﺒﻨﻰ ‪ ،‬ﺃﻯ ﻤﻌﺩﺍﺕ ﻋﺎﻤﺔ ﺃﺨﺭﻯ(‪.‬‬
‫)ﺏ( ﻭﻓﻰ ﺤﺎﻟﺔ ﺍﻟﻤﺒﺎﻨﻰ ﺍﻟﺴﻜﻨﻴﺔ ﺍﻟﻌﺎﻤﺔ )ﺍﻟﻤﺒﺎﻨﻰ ﺫﺍﺕ ﺍﻟﻭﺤﺩﺍﺕ ﺍﻟﺴـﻜﻨﻴﺔ ﺍﻟﻤـﺅﺠﺭﺓ ﺃﻭ‬
‫ﺍﺘﺤﺎﺩ ﻤﻼﻙ ﺃﻭ ﻤﺎ ﻴﺸﺎﺒﻪ ﺫﻟﻙ ﻜﺎﻟﺴﻜﻥ ﺍﻹﺩﺍﺭﻯ(‪:‬‬
‫‪ -‬ﻴﻠﺯﻡ ﺘﺭﻜﻴﺏ ﻟﻭﺤﺔ ﻋﺩﺍﺩ ﻜﻬﺭﺒﺎﺌﻰ ﻟﻜل ﻭﺤﺩﺓ ﺴﻜﻨﻴﺔ ﻭﺘﻜﻭﻥ ﺴﻌﺔ ﺍﻟﻌﺩﺍﺩ )‪(١٠‬‬
‫ﺃﻭ )‪ (٤٠‬ﺃﻤﺒﻴﺭ ﺃﺤﺎﺩﻯ ﺃﻭ ﺜﻼﺜﻰ ﺍﻷﻁﻭﺍﺭ‪.‬‬
‫‪ -‬ﻴﻠﺯﻡ ﺘﺭﻜﻴﺏ ﻟﻭﺤﺔ ﺨﺎﺼﺔ ﺒﻌﺩﺍﺩ ﻟﻠﺨﺩﻤﺎﺕ ﺍﻟﻌﺎﻤﺔ ﺒﺎﻟﻤﺒﻨﻰ‪.‬‬
‫ﻭﻴﻭﻀﺢ ﺸﻜل )‪ (٦-٦‬ﻨﻅﺎﻡ ﺍﻟﺘﻐﺫﻴﺔ ﻟﻠﻤﺒﺎﻨﻰ ﺍﻟﺴﻜﻨﻴﺔ‪.‬‬

‫‪١٢/٦‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫اﻟﻌﻤﻮد اﻟﺼﺎﻋﺪ‬

‫وھﻜﺬا اﻟﻤﺘﻜﺮر‬

‫اﻟﻄﺎﺑﻖ‬
‫‪3 ph + PEN‬‬ ‫‪1 ph + PEN‬‬ ‫اﻟﺪور اﻟﺜﺎﻧﻲ‬

‫)ت(‬ ‫)ب(‬ ‫)أ(‬ ‫)أ(‬ ‫)ب(‬ ‫)ت(‬


‫اﻷﺣﻤﺎل‬ ‫اﻟﻄﺎﺑﻖ‬
‫‪1 ph + PEN‬‬ ‫اﻟﺪور اﻷول‬

‫)ت(‬ ‫)ب(‬ ‫)أ(‬ ‫)أ(‬ ‫)ب(‬ ‫)ت(‬


‫ﻛﺎﺑﻞ ﺧﺮوج‬

‫‪3 ph + PEN‬‬

‫ﻛﺎﺑﻞ اﻷرﺿﻲ‬
‫ﯾﺘﺼﻞ ﺑﺨﻂ اﻟﺘﻌﺎدل‬
‫ﺑﺌﺮ اﻷرﺿﻲ‬
‫ﻛﺎﺑﻞ دﺧﻮل‬ ‫ﻟﻮﺣﺔ ﻣﺪﺧﻞ‬
‫اﻟﻌﻤﺎرة‬

‫ﺤﻴﺙ ﺃﻥ ‪:‬‬
‫ﺼﻨﺩﻭﻕ ﺒﻪ ﻗﺎﻁﻊ ﺘﻠﻘﺎﺌﻰ ﺃﺤﺎﺩﻯ ﺴﻌﺔ ‪ ١٣‬ﺃﻤﺒﻴﺭ ﺃﻭ ‪ ٤٠‬ﺃﻤﺒﻴﺭ‬ ‫)ﺃ(‬
‫)ﺏ( ﻟﻭﺤﺔ ﻋﺩﺍﺩ ﺒﻬﺎ ﻗﺎﻁﻊ ﺘﻠﻘﺎﺌﻰ ﺍﺤﺎﺩﻯ ‪ ١٠‬ﺃﻤﺒﻴﺭ ﺃﻭ‪ ٤٠‬ﺃﻤﺒﻴﺭ‬
‫)ﺕ( ﻟﻭﺤﺔ ﻤﻔﺎﺘﻴﺢ )ﻗﻭﺍﻁﻊ( ﺍﻟﻤﺸﺘﺭﻙ‬
‫ﺸﻜل ﺭﻗﻡ )‪ :(٦-٦‬ﻨﻅﺎﻡ ﺍﻟﺘﻐﺫﻴﺔ ﻟﻠﻤﺒﺎﻨﻰ ﺍﻟﺴﻜﻨﻴﺔ ﺃﻭ ﺍﻹﺩﺍﺭﻴﺔ ﻓﻰ ﻨﻅﺎﻡ‬
‫"ﺃﺕ‪-‬ﺵ")‪(TN-C‬‬

‫‪١٣/٦‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻨﻅﺎﻡ ﺘﻐﺫﻴﺔ ﺍﻟﻤﺒﺎﻨﻰ ﺍﻟﻌﺎﻤﺔ ﻋﻠﻰ ﺍﻟﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ‬ ‫‪٦-٦‬‬


‫ﻴﻨﺩﺭﺝ ﺘﺤﺕ ﺍﺴﻡ ﺍﻟﻤﺒﺎﻨﻰ ﺍﻟﻌﺎﻤﺔ ﻤﺎ ﻴﻠﻰ‪ :‬ﻤﺒﻨﻰ ﺨﺩﻤﺎﺕ ‪ /‬ﻤﺒﻨﻰ ﺇﺩﺍﺭﻯ ‪ /‬ﻤﺒﻨﻰ ﺘﺠﺎﺭﻯ ‪/‬‬
‫ﻤﺴﺘﺸﻔﻰ ‪ /‬ﻭﺭﺸﺔ ﺼﻨﺎﻋﻴﺔ ﺫﺍﺕ ﺘﻐﺫﻴﺔ ﻋﻠﻰ ﺍﻟﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ ﻭﺘﻜﻭﻥ ﻨﻅﻡ ﺍﻟﺘﻐﺫﻴﺔ ﻋﻠـﻰ‬
‫ﺍﻟﻨﺤﻭ ﺍﻟﺘﺎﻟﻰ‪.:‬‬
‫‪ -‬ﻴﺘﻡ ﺘﺭﻜﻴﺏ ﻟﻭﺤﺔ ﺃﻭ ﻟﻭﺤﺎﺕ ﻤﺩﺨل ﺍﻟﻤﺒﻨﻰ ﺤﺴﺏ ﺴﻌﺔ ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﺘﻌﺎﻗـﺩ ﻋﻠﻴـﻪ ﻤـﻊ‬
‫ﺸﺭﻜﺔ ﺘﻭﺯﻴﻊ ﺍﻟﻜﻬﺭﺒﺎﺀ‪ ،‬ﻭﺫﺍﺕ ﻭﻗﺎﻴﺔ ﻀﺩ ﻗﺼﺭ ﺍﻟﺩﺍﺌﺭﺓ ﻁﺒﻘﺎ ﻻﺸﺘﺭﺍﻁﺎﺕ ﺍﻟﺸﺭﻜﺔ‪.‬‬
‫‪ -‬ﻴﺘﻡ ﺘﻭﺼﻴل ﻟﻭﺤﺔ ﺍﻟﻤﺩﺨل ﺇﻟﻰ ﻟﻭﺤﺔ ﺘﻭﺯﻴﻊ ﻋﺎﻤﺔ ﻟﻠﻤﺒﻨﻰ‪.‬‬
‫‪ -‬ﺘﻜﻭﻥ ﺍﻟﺘﻐﺫﻴﺔ ﻋﻠﻰ ﺍﻟﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ ‪ ٣٨٠ × ٣‬ﻓﻭﻟﺕ ‪ ٥٠ /‬ﻫﺭﺘﺯ ﻭﻴﺭﻜﺏ ﺍﻟﻘـﺎﻁﻊ‬
‫ﺍﻟﻌﻤﻭﻤﻰ ﺒﺴﻌﺔ ﺘﻴﺎﺭ ﻤﻨﺎﺴﺒﺔ ﻟﻠﻘﺩﺭﺓ ﺍﻟﻤﺘﻌﺎﻗﺩ ﻋﻠﻴﻬﺎ ﻭﻨﻅﺎﻡ ﺍﻟﺘﻐﺫﻴﺔ ﺍﻟﺸﺎﺌﻊ ﻫـﻭ ﺃﺭﺒﻌـﺔ‬
‫ﺃﺴﻼﻙ ﻤﻨﻬﺎ ﻤﻭﺼل ﺍﻟﺘﻌﺎﺩل ﺍﻟﻤﺅﺭﺽ ﺒﻨﻅﺎﻡ "ﺃﺕ‪-‬ﺵ" )‪. (TN-C‬‬
‫‪ -‬ﺘﻘﻭﻡ ﺸﺭﻜﺔ ﺘﻭﺯﻴﻊ ﺍﻟﻜﻬﺭﺒﺎﺀ ﺍﻟﻤﺨﺘﺼﺔ ﻓﻰ ﺍﻟﻤﻨﻁﻘﺔ ﺒﺘﺭﻜﻴـﺏ ﺃﻭ ﺘﻭﺼـﻴﻑ ﻟﻭﺤـﺔ‬
‫ﻤﺭﻜﺏ ﻋﻠﻴﻬﺎ ﻋﺩﺍﺩ ﻗﻴﺎﺱ ﺍﻟﻁﺎﻗﺔ‪.‬‬
‫‪ -‬ﻗﺩ ﻴﺭﻜﺏ ﻋﺩﺍﺩ ﻭﺍﺤﺩ ﻟﻠﺨـﺩﻤﺎﺕ ﺍﻟﻌﺎﻤـﺔ )ﺇﻨـﺎﺭﺓ ﺍﻟﺴﻠﻡ‪،‬ﺍﻟﻤﺼـﺎﻋﺩ‪،‬ﻁﻠﻤﺒﺎﺕ ﻀـﺦ‬
‫ﺍﻟﻤﻴﺎﺓ‪،‬ﺍﻟﺦ‪ (.‬ﺒﺎﻟﻤﺒﻨﻰ‪.‬‬

‫ﻨﻅﺎﻡ ﺍﻟﺘﻐﺫﻴﺔ ﺍﻟﻤﺘﺒﻊ ﻓﻰ ﻤﺼﺭ ﻟﻠﻤﺒﺎﻨﻰ ﻋﻠﻰ ﺍﻟﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ‬ ‫‪٧-٦‬‬


‫‪ -‬ﻴﺘﻡ ﻓﻰ ﺍﻟﺤـﺎﻻﺕ ﺍﻟﻤﻤﻜـﻥ ﻓﻴﻬﺎ ﻓﺼل ﺘﻐﺫﻴﺔ ﻨﻘﻁــﺔ ﺍﻟﺘﻌﺎﺩل ﻷﻯ ﻤﺒﻨـﻰ ﻟﻨﻅـﺎﻡ‬
‫"ﺃﺕ‪-‬ﺹ")‪ ،(TN-S‬ﺍﺴﺘﺨﺩﺍﻡ ﻗﺎﻁﻊ ﺭﺒﺎﻋﻰ ﺍﻷﻗﻁﺎﺏ ﻟﻔﺼل ﺨﻁ ﺍﻟﺘﻌﺎﺩل ﻭﻓـﻰ ﻜـل‬
‫ﺍﻷﺤﻭﺍل ﻴﺠﺏ ﺘﻭﺼﻴل ﻤﻭﺼل ﺍﻷﺭﻀﻰ ﺍﻟﻭﻗﺎﺌﻰ)‪ (PE‬ﺒﺩﻭﻥ ﻭﺴﻴﻠﺔ ﻟﻔﺼـﻠﻪ ﻋﻨـﺩﻤﺎ‬
‫ﺘﻜﻭﻥ ﺃﺴﻼﻙ ﺍﻟﻘﻭﻯ ﻤﻭﺼﻠﺔ ﺘﻔﺎﺩﻴﺎﹰ ﻟﻠﺼﺩﻤﺔ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ‪.‬‬
‫‪ -‬ﻴﻠﺯﻡ ﺤﺴﺎﺏ ﻤﺴﺘﻭﻯ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﺍﻟﻜﻬﺭﺒﺎﺌﻰ ﺒﻴﻥ ﻁﻭﺭ ﻭﺍﺤﺩ ﻭﺍﻷﺭﻀﻰ ﻭﻜﺫﻟﻙ ﺒﻴﻥ‬
‫ﻁﻭﺭﻴﻥ ﺃﻭ ﺤﺴﺎﺏ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﻋﻠﻰ ﺍﻷﻁﻭﺍﺭ ﺍﻟﺜﻼﺜﺔ ﻭﺍﺨﺘﻴﺎﺭ ﺴﻌﺔ ﺍﻟﻘﻁﻊ ﻟﻠﻘﻭﺍﻁـﻊ‬
‫ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﺍﻟﻤﺴﺘﺨﺩﻤﺔ ﺤﺴﺏ ﻤﻭﻗﻊ ﻟﻭﺤﺔ ﺍﻟﺘﻐﺫﻴﺔ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﻨﻰ‪.‬‬
‫‪ -‬ﻴﺠﺏ ﺍﻻﻟﺘﺯﺍﻡ ﺒﺎﺨﺘﻴﺎﺭ ﺍﻟﻘﺎﻁﻊ ﺍﻟﻌﻤﻭﻤﻰ ﻓﻰ ﺍﻟﻠﻭﺤﺔ ﺒﺴﻌﺔ ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﻘﻨﻥ ﻭﺴﻌﺔ ﺍﻟﻘﻁـﻊ‬
‫ﺍﻟﻤﻨﺎﺴﺒﺔ ﻟﻠﻤﻭﻗﻊ ﻭﻋﺩﻡ ﺍﺨﺘﻴﺎﺭ ﻗﻭﺍﻁﻊ ﺒﺴﻌﺎﺕ ﺃﻜﺒﺭ ﻤﻨﻬﻤﺎ ﺤﻴﺙ ﺃﻥ ﺯﻴﺎﺩﺓ ﺴﻌﺔ ﺘﻴـﺎﺭ‬
‫ﺍﻟﻘﺼﺭ ﻟﻠﻘﺎﻁﻊ ﻗﺩ ﺘﺅﺩﻯ ﻟﻨﺘﺎﺌﺞ ﺴﻴﺌﺔ ﻋﻨﺩ ﺤﺩﻭﺙ ﻗﺼﺭ ﻭﻻ ﻴﻜﻭﻥ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﻗﺎﺩﺭﺍ‬
‫ﻋﻠﻰ ﺘﺸﻐﻴل ﺍﻟﻘﺎﻁﻊ ﺘﻠﻘﺎﺌﻴﺎﹰ ﻁﺒﻘﺎﹰ ﻟﺨﺼﺎﺌﺼﻪ ﻭﻤﻥ ﺜﻡ ﻴﺴﺘﻤﺭ ﻤﺭﻭﺭ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﻤﻤـﺎ‬

‫‪١٤/٦‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻗﺩ ﻴﺅﺩﻯ ﺇﻟﻰ ﺇﺸﻌﺎل ﺤﺭﻴﻕ ﻓﻰ ﺍﻟﻤﻜﺎﻥ ﺃﻭ ﺘﺩﻤﻴﺭ ﻤﻨﻁﻘﺔ ﺍﻟﻘﺼﺭ ﻤﻤﺎ ﻴﻨﺘﺞ ﻋﻨﻪ ﺤﺭﺍﺌﻕ‬
‫ﻓﻰ ﺒﻌﺽ ﺍﻟﺤﺎﻻﺕ ﺩﺍﺨل ﺍﻟﻠﻭﺤﺔ ﻭﺒﺎﻷﺨﺹ ﻋﻨﺩ ﻭﺠﻭﺩ ﻤﻭﺍﺩ ﻗﺎﺒﻠﺔ ﻟﻼﺸﺘﻌﺎل‪.‬‬
‫ﻭﻴﻘﺘﺭﺡ ﻤﺭﺍﺠﻌﺔ ﺍﺴﺘﺸﺎﺭﻯ ﻜﻬﺭﺒﺎﺌﻰ ﻓﻰ ﺘﺤﺩﻴﺩ ﺍﻟﺒﻨﻭﺩ ﺍﻟﺘﺎﻟﻴـﺔ ﺍﻟﺨﺎﺼـﺔ ﺒﻤﻜﻭﻨـﺎﺕ‬
‫ﻟﻭﺤﺎﺕ ﺍﻟﺘﻭﺯﻴﻊ‪:‬‬
‫)‪ (١‬ﺴﻌﺔ ﺍﻟﻘﺎﻁﻊ ﻭﺴﻌﺔ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﻭﻤﺩﻯ ﺘﻐﻴﺭ ﺘﻴﺎﺭ ﻀﺒﻁ ﺍﻟﻭﻗﺎﻴﺔ ﻀﺩ ﺍﻟﻘﺼـﺭ‬
‫ﺍﻟﻼﺯﻤﺔ ﻋﻨﺩ ﻤﻜﺎﻥ ﺘﺭﻜﻴﺏ ﺍﻟﻘﺎﻁﻊ‪.‬‬
‫)‪ (٢‬ﻤﻨﺤﻨﻰ ﻭﻭﻗﺕ ﺍﻟﻔﺼل ﻭﻁﺭﺍﺯ ﺍﻟﻘﺎﻁﻊ ﺍﻟﻤﻨﺎﺴـﺏ ﻟﻸﺤﻤـﺎل ﻤـﻊ ﻤﺭﺍﺠﻌـﺔ‬
‫ﻤﻭﺍﺼﻔﺎﺕ ﻭﻜﺘﺎﻟﻭﺝ ﺍﻟﻤﺼﻨﻊ ﻭﺍﻟﺘﺄﻜﺩ ﻤﻥ ﺍﻟﻤﻁﺎﺒﻘـﺔ ﻟﻠﻤﻭﺍﺼـﻔﺔ ﺍﻟﻜﻬﺭﻭﺘﻘﻨﻴـﺔ‬
‫ﺍﻟﺩﻭﻟﻴﺔ )‪ (IEC -439‬ﺍﻟﺨﺎﺼﺔ ﺒﺎﻻﺨﺘﻴﺎﺭ‪.‬‬
‫)‪ (٣‬ﻤﺭﺍﺠﻌﺔ ﺘﺘﺎﺒﻊ ﻭﻗﺕ ﻭﺴﻌﺔ ﻓﺼل ﺍﻟﻘﻭﺍﻁﻊ ﻋﻨﺩ ﺤﺩﻭﺙ ﻗﺼﺭ ﻭﻤﺭﺍﻋﺎﺓ ﻤـﺎ ﺇﺫﺍ‬
‫ﻜﺎﻨﺕ ﺍﻟﺩﺍﺌﺭﺓ ﺒﻬﺎ ﻤﺼﺎﻫﺭ ﺴﺭﻴﻌﺔ ﺍﻟﻘﻁﻊ‪.‬‬
‫ﻜﻤﺎ ﻴﻠﺯﻡ ﺃﻴﻀﺎﹰ ﻤﺭﺍﺠﻌﺔ ﺍﻟﻨﻘﺎﻁ ﺍﻟﺘﺎﻟﻴﺔ‪:‬‬
‫ﻗﻴﻤﺔ ﺍﻟﻤﻤﺎﻨﻌﺔ ﻓﻰ ﺍﻟﺩﺍﺌﺭﺓ – ﻭﻟﻭ ﺘﻘﺩﻴﺭﻴﺎﹰ‪.‬‬ ‫)ﺃ(‬
‫)ﺏ( ﺃﻁﻭﺍل ﻜﺎﺒﻼﺕ ﺍﻟﺘﻐﺫﻴﺔ ﺒﻴﻥ ﺍﻟﻠﻭﺤﺎﺕ ﻭﻗﻴﻤﺔ ﺍﻟﻤﻤﺎﻨﻌﺔ ﻓﻰ ﺩﺍﺌﺭﺓ ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ‪.‬‬
‫)ﺕ( ﻗﻴﻤﺔ ﻤﻘﺎﻭﻤﺔ ﺍﻷﺭﺽ ﻓﻰ ﻤﻜﺎﻥ ﺘﺭﻜﻴﺏ ﺍﻟﻠﻭﺤﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ‬
‫ﻭﻴﻨﺘﺞ ﻋﻥ ﻋﺩﻡ ﺍﻻﻫﺘﻤﺎﻡ ﻭﺍﻹﻟﻤﺎﻡ ﺒﺎﻟﻨﻘﺎﻁ ﻭﺍﻟﺒﻴﺎﻨﺎﺕ ﺍﻟﺴﺎﺒﻕ ﺫﻜﺭﻫﺎ‪ ،‬ﺃﻥ ﺘﻨـﺘﺞ‬
‫ﺘﺄﺜﻴﺭﺍﺕ ﺒﻴﺌﻴﺔ ﺴﻴﺌﺔ )ﺤﻭﺍﺩﺙ ﻟﻸﻓﺭﺍﺩ ﺃﻭ ﺤﺭﺍﺌﻕ(‪.‬‬

‫ﻨﻅﺎﻡ ﺘﻐﺫﻴﺔ ﺍﻟﻤﺒﺎﻨﻰ ﺍﻟﺘﻰ ﺘﺤﺘﺎﺝ ﻟﻘﺩﺭﺓ ﻜﻬﺭﺒﺎﺌﻴﺔ ﻤﺴﺎﻭﻴﺔ ﺃﻭ ﺃﻜﺒﺭ ﻤﻥ ‪ ٥٠٠‬ﻜﻴﻠﻭ ﻓﻭﻟﺕ‬ ‫‪٨-٦‬‬
‫‪ -‬ﺃﻤﺒﻴﺭ‬
‫ﺘﺘﻁﻠﺏ ﻫﺫﻩ ﺍﻟﻨﻭﻋﻴﺔ ﻤﻥ ﺍﻟﻤﺒﺎﻨﻰ ﻏﺭﻓﺔ ﺨﺎﺼﺔ ﻟﻠﻤﺤﻭﻻﺕ ﺩﺍﺨل ﺍﻟﻤﺒﻨﻰ ‪ ،‬ﻭﻴﺘﻡ ﺘﺼﻤﻴﻤﻬﺎ‬
‫ﺤﺴﺏ ﺍﻟﻤﻭﺍﺼﻔﺎﺕ ﺍﻟﻤﻌﺘﻤﺩﺓ ﻤﻥ ﺸﺭﻜﺔ ﺘﻭﺯﻴﻊ ﺍﻟﻜﻬﺭﺒﺎﺀ ﻓﻰ ﻤﻨﻁﻘﺔ ﺍﻹﺸﻐﺎل )ﺍﻟﻤﻭﺠـﻭﺩ‬
‫ﺒﻪ ﺍﻟﻤﺒﻨﻰ(‪.‬‬
‫ﻭﺘﺤﺘــﻭﻯ ﻫﺫﻩ ﺍﻟﻐﺭﻓﺔ ﺤﺴﺏ ﺸﻜل )‪ (٧-٦‬ﻋﻠﻰ ﻭﺤﺩﺓ ﺘﻭﺯﻴﻊ ﺤﻠﻘﻴﺔ ﻟﻠﺠﻬﺩ ﺍﻟﻤﺘﻭﺴـﻁ‬
‫)‪ ١١‬ﺃﻭ ‪ ٢٢‬ﻜﻴﻠﻭ ﻓﻭﻟﺕ( ﻤﻥ ﺍﻟﺼﺎﺝ ﻤﻊ ﻤﺭﺍﻋﺎﺓ ﺃﻥ ﺒﻌﺽ ﺍﻟﻤﻨﺎﻁﻕ ﺘﺤﺘﺎﺝ ‪ ١٠.٥‬ﻜﻴﻠﻭ‬
‫ﻓﻭﻟﺕ )ﻤﺩﻴﻨﺔ ﺍﻟﻘﺎﻫﺭﺓ( ﻭﻫﻨﺎﻙ ﺒﻌﺽ ﺍﻷﻤﺎﻜﻥ ﺘﺤﺘﺎﺝ ﺇﻟـﻰ ‪ ٢٠‬ﻜﻴﻠـﻭ ﻓﻭﻟـﺕ )ﻤﺩﻴﻨـﺔ‬
‫‪٦‬ﺃﻜﺘﻭﺒﺭ ﻭﻤﺩﻴﻨﺔ ﺸﺭﻡ ﺍﻟﺸﻴﺦ( ﻭﻴﺠﺏ ﺃﻥ ﻴﻜﻭﻥ ﺍﻟﻤﺤﻭل ﻤﻁﺎﺒﻕ ﻟﺫﻟﻙ‪.‬‬

‫‪١٥/٦‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻭﻴﻁﻠﻕ ﻋﻠﻰ ﻟﻭﺤﺎﺕ ﺍﻟﺘﻐﺫﻴﺔ ﺍﻟﺤﻠﻘﻴﺔ ﻤﺴﻤﻰ )‪ (RMU‬ﻭﻫﻰ ﺘﺤﺘﻭﻯ ﻋﻠﻰ ﺨﻠﻴﺘـﻴﻥ ﻟﻜـل‬
‫ﻤﻨﻬﻤﺎ ﻗﺎﻁﻊ ﻋﻠﻰ ﺍﻟﺤﻤل )‪ (LBS‬ﺫﺍﺕ ﻋﺯل ﻫﻭﺍﺌﻰ ﻭﺴـﻌﺔ ‪ ٦٣٠‬ﺃﻤﺒﻴـﺭ ﻭﺫﺍﺕ ﺘﻴـﺎﺭ‬
‫ﻗﺼﺭ ‪ ٢٥‬ﻜﻴﻠﻭ ﺃﻤﺒﻴﺭ ﻋﻨﺩ ﺠﻬﺩ ‪ ١٢‬ﻜﻴﻠﻭ ﻓﻭﻟﺕ‪ ،‬ﺃﻭ ﺫﺍﺕ ﺘﻴﺎﺭ ﻗﺼﺭ‪ ٢٠‬ﻜﻴﻠﻭ ﺃﻤﺒﻴﺭ ﻋﻨﺩ‬
‫ﺠﻬﺩ ‪ ٢٤‬ﻜﻴﻠﻭ ﻓﻭﻟﺕ ﻭﺘﻘﻭﻡ ﻫﺫﻩ ﺍﻟﻘﻭﺍﻁﻊ ﺒﺘﻐﺫﻴﺔ ﻜﺎﺒﻼﺕ ﺍﻟﺤﻠﻘﺔ ﻟﻠﺩﺨﻭل ﺇﻟـﻰ ﻤﺤﻁـﺔ‬
‫ﺍﻟﻤﺤﻭﻻﺕ ﻭﺍﻟﺨﺭﻭﺝ ﻤﻨﻬﺎ ﻟﻠﺸﺒﻜﺔ ﺍﻟﻌﺎﻤﺔ ﻋﻠﻰ ﺍﻟﺠﻬﺩ ﺍﻟﻤﺘﻭﺴﻁ‪.‬‬
‫‪ -‬ﻴﻭﺠﺩ ﻓﻰ ﺍﻟﻠﻭﺤﺔ ﺨﻠﻴﺔ ﻟﻠﺨﺭﻭﺝ ﻟﺘﻐﺫﻴﺔ ﺍﻟﻤﺤﻭل ﻭﻗﺎﻁﻊ ﻋﻠﻰ ﺍﻟﺤﻤل ﻜﺎﻤل ﺒﺎﻟﻤﺼـﺎﻫﺭ‬
‫ﻭﻗﻭﺍﻋﺩﻫﺎ ﻋﻠﻰ ﺍﻟﺠﻬﺩ ﺍﻟﻤﺘﻭﺴﻁ ﺒﺴﻌﺔ ﺘﻴﺎﺭ ﺤﺴﺏ ﻗﺩﺭﺓ ﺍﻟﻤﺤﻭل )‪ ٤٠‬ﺃﻤﺒﻴﺭ ﻟﻤﺤـﻭل‬
‫ﺠﻬﺩ ‪ ٠.٤/١١‬ﻙ‪.‬ﻑ ‪.‬ﻭﻗﺩﺭﺓ ‪ ٥٠٠‬ﻙ‪.‬ﻑ‪.‬ﺃ‪ .‬ﻋﻨﺩ ﺠﻬﺩ ‪ ١١‬ﻙ‪.‬ﻑ( ﻭﺘﻜـﻭﻥ ﺴـﻌﺔ‬
‫ﺍﻟﻘﺎﻁﻊ ﻋﻠﻰ ﺍﻟﺤﻤل ‪ ٤٠٠‬ﺃﻤﺒﻴﺭ ﻭﻤﺠﻬﺯﺍﹰ ﻟﻠﻔﺼل ﺍﻟﺫﺍﺘﻰ ﻓﻰ ﺤﺎﻟﺔ ﺍﻨﺼﻬﺎﺭ ﻭﺼل ﺃﺤﺩ‬
‫ﺃﻁﻭﺍﺭ ﺍﻟﻤﺼﺎﻫﺭ‪.‬‬
‫‪ -‬ﺘﺤﺘﻭﻯ ﺍﻟﻠﻭﺤﺔ ﺃﻴﻀﺎ ﻋﻠﻰ ﺨﻠﻴﺔ ﺒﻬﺎ ﺃﻁﺭﺍﻑ )ﺭﻭﺯﻴﺘـﺔ( ﺘﻭﺼـل ﺇﻟـﻰ ﺃﻁـﺭﺍﻑ‬
‫ﻤﺤﻭﻻﺕ ﺍﻟﺘﻴﺎﺭ ﻭﻤﺤﻭﻻﺕ ﺍﻟﺠﻬﺩ ﻟﺯﻭﻡ ﺘﺭﻜﻴﺏ ﺍﻟﻌﺩﺍﺩﺍﺕ ﻤﻊ ﻭﺠﻭﺩ ﻤﻜـﺎﻥ ﻟﺘﺭﻜﻴـﺏ‬
‫ﻋﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ ﺍﻟﻔﻌﺎﻟﺔ ﻭﻋﺩﺍﺩ ﺍﻟﻁﺎﻗﺔ ﻏﻴﺭ ﺍﻟﻔﻌﺎﻟﺔ ﻭﺫﻟﻙ ﻟﻠﻭﺤﺎﺕ ﺍﻟﺘﻰ ﺘﻐﺫﻯ ﻤﺤﻭل ﻗﺩﺭﺓ‬
‫‪ ١٠٠٠‬ﻙ‪.‬ﻑ‪.‬ﺃ ﺃﻭ ﺍﻜﺒﺭ ﺤﻴﺙ ﺃﻥ ﺍﻟﻤﺤﻭﻻﺕ ﻗﺩﺭﺓ ‪ ٥٠٠‬ﻙ‪.‬ﻑ‪.‬ﺃ ﺃﻭ ﺃﻗل ﻴﺘﻡ ﺘﺭﻜﻴـﺏ‬
‫ﺍﻟﻌﺩﺍﺩﺍﺕ ﻋﻠﻰ ﺍﻟﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ‪.‬‬
‫‪ -‬ﻴﻠﺯﻡ ﺃﻥ ﺘﻜﻭﻥ ﻤﺴﺎﺤﺔ ﻤﻘﻁﻊ ﻗﻀﺒﺎﻥ ﺍﻟﺘﻭﺯﻴﻊ ﺍﻟﺭﺌﻴﺴﻴﺔ ‪٤٠٠‬ﻤﻡ‪.٢‬‬
‫‪ -‬ﻴﻠﺯﻡ ﺃﻻ ﻴﻘل ﺴﻤﻙ ﺍﻟﺼﺎﺝ ﻋﻥ ‪ ٢.٥‬ﻤﻡ ﻗﺒل ﺍﻟﺩﻫﺎﻥ‪.‬‬
‫‪ -‬ﻴﺠﺏ ﺃﻥ ﻴﻌﻤل ﺠﻬﺎﺯ ﺒﻴﺎﻥ ﺘﺴﺭﺏ ﺍﻷﺭﺽ ﻋﻠﻰ ﺠﻬﺩ ‪ ١١٠‬ﻓﻭﻟـﺕ )ﺘﻴـﺎﺭ ﻤﺘـﺭﺩﺩ(‬
‫ﻭﺘﻴﺎﺭ )‪ (٪١٠ ± ٢٥‬ﺃﻤﺒﻴﺭ ﻓﻰ ﺤﺎﻟﺔ ﺘﺭﻜﻴﺏ ﺍﻟﻌﺩﺍﺩ ﺒﻠﻭﺤﺔ ﺍﻟﺠﻬﺩ ﺍﻟﻤﺘﻭﺴﻁ ﻭﻴﻌﻤـل‬
‫ﻋﻠﻰ ﺠﻬﺩ ‪ ٢٢٠‬ﻓﻭﻟﺕ)ﺘﻴﺎﺭ ﻤﺘﺭﺩﺩ( ﻓﻰ ﺤﺎﻟﺔ ﺍﻟﻠﻭﺤﺎﺕ ﺍﻷﺨﺭﻯ ‪.‬‬
‫‪ -‬ﺇﺫﺍ ﻜﺎﻨﺕ ﺨﻼﻴﺎ ﺍﻟﻠﻭﺤﺔ ﻤﻔﺘﻭﺤﺔ ﻤﻥ ﺃﺴﻔل ﻟﺘﺴﻤﺢ ﺒﺎﻨﺘﻘﺎل ﺍﻟﺤﺭﺍﺭﺓ‪ ،‬ﻴﻜﺘﻔـﻰ ﺒﺘﺭﻜﻴـﺏ‬
‫ﺴﺨﺎﻥ ﻭﺍﺤﺩ ﻓﻰ ﺃﺴﻔل ﻤﻨﺘﺼﻑ ﺍﻟﻠﻭﺤﺔ ﻭﺇﺫﺍ ﻜﺎﻨﺕ ﺍﻟﺨﻼﻴـﺎ ﻤﻔﺼـﻭﻟﺔ ﺘﻤﺎﻤـﺎﹰ ﻋـﻥ‬
‫ﺒﻌﻀﻬﺎ ﻤﻥ ﺃﺴﻔل ﻴﺘﻡ ﺘﺭﻜﻴﺏ ﺴﺨﺎﻥ ﻓﻰ ﻜل ﺨﻠﻴﺔ ﻟﻠﺘﺨﻠﺹ ﻤﻥ ﺍﻟﺭﻁﻭﺒﺔ‪.‬‬
‫‪ -‬ﻴﻠﺯﻡ ﺃﻥ ﺘﺯﻭﺩ ﻜل ﺨﻠﻴﺔ ﺃﻋﻠﻰ ﻗﺎﻋﺩﺘﻬﺎ ﺒﻘﻔﻴﺯ ﻤﻥ ﻤﺎﺩﺓ ﻤﻨﺎﺴﺒﺔ ﺒﻪ ﻤﺴـﻤﺎﺭﻴﻥ ﻜـﺎﻤﻠﻴﻥ‬
‫ﺒﺎﻟﺼﻭﺍﻤﻴل ﻭﺍﻟﻭﺭﺩ ﺍﻟﻤﺠﻠﻔﻨﺔ ﻟﺘﺜﺒﻴﺕ ﺍﻟﻜﺎﺒﻼﺕ ﻭﺫﻟﻙ ﺃﺴﻔل ﺍﻟﻘﺎﻁﻊ ﻋﻠﻰ ﺍﻟﺤﻤـل ﻤـﻊ‬
‫ﺘﺠﻬﻴﺯ ﻓﺘﺤﺎﺕ ﺩﺨﻭل ﺍﻟﻜﺎﺒﻼﺕ‪.‬‬
‫‪ -‬ﻴﻠﺯﻡ ﺘﺭﻜﻴﺏ ﺠﻭﺍﻨﺎﺕ ﻜﺎﻭﺘﺵ ﻋﻠﻰ ﺠﻤﻴﻊ ﻓﺘﺤﺎﺕ ﺍﻟﻠﻭﺤﺔ ﻟﺘﺤﻘﻴـﻕ ﺩﺭﺠـﺔ ﺍﻟﺤﻤﺎﻴـﺔ‬
‫ﺍﻟﻤﺤﺩﺩﺓ ﻓﻰ ﺍﻟﻤﻭﺍﺼﻔﺎﺕ‪.‬‬

‫‪١٦/٦‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫‪ -‬ﻴﺠﺏ ﺍﻻﻟﺘﺯﺍﻡ ﺒﺠﻤﻴﻊ ﺍﻟﻤﻭﺍﺼﻔﺎﺕ ﺍﻟﺘﻰ ﺘﻁﻠﺒﻬﺎ ﺸـﺭﻜﺔ ﺘﻭﺯﻴـﻊ ﺍﻟﻜﻬﺭﺒـﺎﺀ ﺒﻤﻨﻁﻘـﺔ‬
‫ﺍﻟﻤﺸﺭﻭﻉ‪.‬‬

‫اﻟﻤﺤﻮل‬

‫ﻣﺮوﺣﺔ ﺳﺤﺐ‬
‫)ﻟﺴﺤﺐ اﻟﮭﻮاء اﻟﺴﺎﺧﻦ‬ ‫ﻛﺎﺑﻞ ﺟﮭﺪ‬
‫ﻣﻦ اﻟﻐﺮﻓﺔ(‬ ‫ﻣﺘﻮﺳﻂ‬
‫ﺧﺮوج‬
‫ﻛﺎﺑﻞ أو ﻛﺎﺑﻼت ﺟﮭﺪ ﻣﻨﺨﻔﺾ أو ﺑﺎرات‬ ‫ﻟﻠﻤﺤﻮل‬
‫ﻧﺤﺎﺳﯿﺔ‬
‫ﻟﻮﺣﺔ اﻟﻀﻐﻂ اﻟﻤﻨﺨﻔﺾ‬
‫ﻛﺎﺑﻞ ﺧﺮوج ﺟﮭﺪ ﻣﺘﻮﺳﻂ‬

‫ﺟﺮﯾﻞ ﺑﺎﻟﺒﺎب أو ﻋﻠﻰ‬ ‫ﻛﺎﺑﻞ دﺧﻮل ﺟﮭﺪ ﻣﺘﻮﺳﻂ‬ ‫‪RMU‬‬


‫اﻟﺤﺎﺋﻂ‬

‫ﺸﻜل ﺭﻗﻡ )‪ :(٧-٦‬ﻏﺭﻓﺔ ﺍﻟﻤﺤﻭل ﻭﻭﻀﻊ ﺍﻟﻤﻌﺩﺍﺕ ﺒﺩﺍﺨﻠﻬﺎ‬

‫ﺃﺸﻜﺎل ﻟﻭﺤﺎﺕ ﺍﻟﺘﻭﺯﻴﻊ‬ ‫‪٩-٦‬‬


‫ﻴﺠﺏ ﺃﻥ ﺘﺘﻁﺎﺒﻕ ﻟﻭﺤﺎﺕ ﺘﻭﺯﻴﻊ ﺍﻟﺠﻬﺩ ﺍﻟﻤﻨﺨﻔﺽ ﺍﻟﺘﻰ ﺘﻌﻤل ﻋﻠﻰ ﺠﻬﻭﺩ ﺤﺘـﻰ ‪١٠٠٠‬‬
‫ﻓﻭﻟﺕ ﺘﻴﺎﺭ ﻤﺘﺭﺩﺩ ﻭ ‪ ٣٠٠٠‬ﻓﻭﻟﺕ ﺠﻬﺩ ﻤﺴﺘﻤﺭ ﻤﻊ ﺍﻟﻤﻭﺍﺼﻔﺎﺕ ﺍﻟﺩﻭﻟﻴـﺔ ﺍﻟﻜﻬﺭﻭﺘﻘﻨﻴـﺔ‬
‫)‪ ،(IEC 439‬ﻭﺘﻨﻘﺴﻡ ﺃﺸﻜﺎل ﻫﺫﻩ ﺍﻟﻠﻭﺤﺎﺕ ﺇﻟﻰ ﻤﺎ ﻴﻠﻰ‪:‬‬
‫‪Open Frame‬‬ ‫ـﻭﺡ‬
‫ـﺎﺭ ﺍﻟﻤﻔﺘــ‬
‫ـﺎﺕ ﺫﺍﺕ ﺍﻹﻁــ‬
‫ﺍﻟﻠﻭﺤــ‬ ‫)ﺃ(‬
‫‪Construction‬‬
‫ﻨﻅﺭﺍﹰ ﻷﻥ ﺍﻷﺠﺯﺍﺀ ﺍﻟﻤﻜﻬﺭﺒﺔ ﺒﻬﺫﺍ ﺍﻟﻨﻭﻉ ﻴﺘﻡ ﺒﻨﺎﺅﻫﺎ ﻤﻜﺸﻭﻓﺔ ﺩﺍﺨل ﺇﻁﺎﺭ ﺍﻟﻠﻭﺤـﺔ‬
‫ﻭﻤﻥ ﺍﻟﻤﻤﻜﻥ ﺍﻟﻭﺼﻭل ﺇﻟﻴﻬﺎ ﻤﻥ ﺠﻤﻴﻊ ﺍﻻﺘﺠﺎﻫﺎﺕ ﻨﺘﻴﺠﺔ ﻟﻌﺩﻡ ﻭﺠﻭﺩ ﻏﻁﺎﺀ‪ ،‬ﻓﺈﻨـﻪ‬
‫ﻻ ﻴﺴﻤﺢ ﺒﺘﺭﻜﻴﺒﻬﺎ ﺇﻻ ﺩﺍﺨل ﺍﻷﻤﺎﻜﻥ ﺍﻟﻤﻐﻠﻘﺔ ﺘﻔﺎﺩﻴﺎﹰ ﻟﺤﺩﻭﺙ ﺍﻟﺼﺩﻤﺔ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ‪.‬‬

‫‪١٧/٦‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫‪Construction Panels‬‬ ‫)ﺏ( ﺍﻟﻠﻭﺤﺎﺕ ﺫﺍﺕ ﺍﻟﺒﻨﺎﺀ‬


‫ﺘﺤﻘﻕ ﻫﺫﻩ ﺍﻟﻠﻭﺤﺎﺕ ﺍﻟﻭﻗﺎﻴﺔ ﻤﻥ ﺍﻟﺘﻼﻤﺱ ﻤﻊ ﺍﻷﺠﺯﺍﺀ ﺍﻟﻤﻜﻬﺭﺒﺔ ﻤﻥ ﻭﺍﺠﻬﺔ ﺍﻟﻠﻭﺤﺔ‬
‫ﻭﻟﻜﻥ ﻻ ﺘﺤﻘﻕ ﺫﻟﻙ ﻤﻥ ﺍﻟﻭﺍﺠﻬﺎﺕ ﺍﻷﺨﺭﻯ ﺍﻟﺘﻰ ﻴﻤﻜـﻥ ﻤﻨﻬـﺎ ﺍﻟﻭﺼـﻭل ﺇﻟـﻰ‬
‫ﻤﻜﻭﻨﺎﺕ ﺍﻟﻠﻭﺤﺔ ﺒﺴﻬﻭﻟﺔ‪ ،‬ﻟﺫﺍ ﻴﺠﺏ ﺃﻥ ﻴﺘﻡ ﺘﺭﻜﻴﺏ ﻫﺫﻩ ﺍﻟﻠﻭﺤـﺎﺕ ﻓـﻰ ﺍﻷﻤـﺎﻜﻥ‬
‫ﺍﻟﻤﻐﻠﻘﺔ ﻓﻘﻁ‪.‬‬
‫‪Cubicle Construction‬‬ ‫)ﺕ( ﺍﻟﻠﻭﺤﺎﺕ ﺫﺍﺕ ﺍﻟﺨﻼﻴﺎ‬
‫ﺘﻜﻭﻥ ﺍﻟﻠﻭﺤﺎﺕ ﻤﻥ ﻫﺫﺍ ﺍﻟﻁﺭﺍﺯ ﻤﻐﻠﻘﺔ ﻤﻥ ﺠﻤﻴﻊ ﺍﻟﺠﻭﺍﻨﺏ ﺒﺤﻴﺙ ﻴﺴﺘﺤﻴل ﻟﻤـﺱ‬
‫ﺍﻷﺠﺯﺍﺀ ﺍﻟﻤﻜﻬﺭﺒﺔ ﺒﻬﺎ ﺃﺜﻨﺎﺀ ﺍﻟﺘﺸﻐﻴل‪ ،‬ﻟﺫﺍ ﻓﺈﻨﻪ ﻤﻥ ﺍﻟﻤﺴﻤﻭﺡ ﺘﺭﻜﻴﺒﻬﺎ ﻓـﻰ ﺃﻤـﺎﻜﻥ‬
‫ﺍﻟﺘﺸﻐﻴل ﺍﻟﻤﻔﺘﻭﺤﺔ‪ .‬ﻭﻴﺼﻨﻊ ﻜل ﻗﺴﻡ ﻤﻥ ﻋﺩﺓ ﺨﻼﻴﺎ ﻭﺘﻜﻭﻥ ﻤﻔـﺭﺩﺍﺕ ﺍﻟﻤﻌـﺩﺍﺕ‬
‫ﻤﺭﻜﺒﺔ ﺨﻠﻑ ﺃﺒﻭﺍﺏ ﺍﻷﻗﺴﺎﻡ ﺍﻟﻤﺨﺘﻠﻔﺔ‪.‬‬
‫‪Withdraw able units‬‬ ‫)ﺙ( ﺍﻟﻠﻭﺤﺎﺕ ﺫﺍﺕ ﺍﻟﻭﺤﺩﺍﺕ ﺍﻟﻘﺎﺒﻠﺔ ﻟﻠﺴﺤﺏ‬
‫ﻴﺘﻡ ﺒﻨﺎﺀ ﻫﺫﻩ ﺍﻟﻭﺤﺩﺍﺕ ﺩﺍﺨل ﺨﻼﻴﺎ ﺍﻟﻠﻭﺤﺔ ﻭﻴﻤﻜﻥ ﺘﻘﺴﻴﻡ ﺍﻟﺨﻠﻴﺔ ﺇﻟﻰ ﺃﻗﺴﺎﻡ ﻤﻨﻔﺼﻠﺔ‬
‫ﻜل ﻤﻨﻬﺎ ﻴﺤﺘﻭﻯ ﻋﻠﻰ ﺇﺤﺩﻯ ﺍﻟﻭﺤﺩﺍﺕ ﺍﻟﻘﺎﺒﻠﺔ ﻟﻠﺴﺤﺏ ﻭﺒﺫﻟﻙ ﻴﻀﻤﻥ ﺍﻷﻤﺎﻥ ﺍﻟﺘـﺎﻡ‬
‫ﻟﻸﻓﺭﺍﺩ ﻭﺍﻟﺴﻬﻭﻟﺔ ﺃﺜﻨﺎﺀ ﺍﻟﺼﻴﺎﻨﺔ‪.‬‬
‫‪Box type construction‬‬ ‫)ﺝ( ﺍﻟﻠﻭﺤﺎﺕ ﺫﺍﺕ ﺍﻟﻁﺭﺍﺯ ﺍﻟﺼﻨﺩﻭﻗﻰ‬
‫ﻭﺘﺘﻜﻭﻥ ﻤﻥ ﻤﺠﻤﻭﻋﺔ ﻤﻥ ﺍﻟﺼﻨﺎﺩﻴﻕ ﺍﻟﻤﺠﻤﻌﺔ ﻤـﻊ ﺒﻌﻀـﻬﺎ ﺒﻁﺭﻴﻘـﺔ ﻤﺄﻤﻭﻨـﺔ‬
‫ﻭﺘﺤﺘﻭﻯ ﻋﻠﻰ ﻭﺤﺩﺍﺕ ﺍﻟﻤﻌﺩﺍﺕ ﻤﺜل ﻗﻀﺒﺎﻥ ﺍﻟﺘﻭﺯﻴـﻊ ﻭﺍﻟﻤﺼـﺎﻫﺭ ﻭﺍﻟﻤﻔـﺎﺘﻴﺢ‬
‫ﻭﺍﻟﻜﻭﻨﺘﺎﻜﺘﻭﺭﺍﺕ‪ .‬ﻭﺘﺤﻭل ﻫﺫﻩ ﺍﻟﺼﻨﺎﺩﻴﻕ ﺩﻭﻥ ﺍﻟﺘﻼﻤﺱ ﻤﻊ ﺍﻷﺠﺯﺍﺀ ﺍﻟﻤﻜﻬﺭﺒـﺔ‪.‬‬
‫ﻭﻴﻤﻜﻥ ﺒﻌﺩ ﺇﻀﺎﻓﺔ ﺤﻭﺍﺠﺯ ﻟﻠﻭﻗﺎﻴﺔ ﻭﺒﺎﺴﺘﺨﺩﺍﻡ ﺩﺭﺠﺔ ﻤﻌﻴﻨﺔ ﻤﻥ ﺍﻟﺤﻤﺎﻴـﺔ )ﻋﻠـﻰ‬
‫ﺍﻷﻗل ‪ (IP 55‬ﺍﺴﺘﻌﻤﺎل ﻫﺫﺍ ﺍﻟﻨﻭﻉ ﻤﻥ ﺍﻟﻠﻭﺤﺎﺕ ﻓﻰ ﺍﻷﻤﺎﻜﻥ ﻋﺎﻟﻴﺔ ﺍﻟﺘﻠﻭﺙ ﺒﺎﻟﻐﺒﺎﺭ‬
‫ﺃﻭ ﺫﺍﺕ ﻅﺭﻭﻑ ﺍﻟﺘﺸﻐﻴل ﺍﻟﻘﺎﺴﻴﺔ )ﻋﻠﻰ ﻋﻜﺱ ﺍﻟﻁﺭﺍﺯﺍﺕ ﺍﻷﺨﺭﻯ(‪.‬‬
‫ﻭﻴﺘﻤﻴﺯ ﻫﺫﺍ ﺍﻟﻨﻭﻉ ﻤﻥ ﺍﻟﻠﻭﺤﺎﺕ ﺒﺎﻵﺘﻰ‪:‬‬
‫‪ -‬ﺸﺩﺓ ﺍﻟﺘﺤﻤل‪.‬‬
‫‪ -‬ﺇﻤﻜﺎﻨﻴﺔ ﺍﻟﺘﻭﺴﻊ‪.‬‬
‫‪ -‬ﺴﻬﻭﻟﺔ ﺍﻟﺒﻨﺎﺀ ﻭﺍﻟﺘﺠﻤﻴﻊ ﻓﻰ ﺍﻟﻤﻭﻗﻊ‪.‬‬
‫‪ -‬ﻗﻠﺔ ﺍﻟﺤﻴﺯ ﺍﻟﻤﻁﻠﻭﺏ ﻟﻠﺘﺭﻜﻴﺏ‪.‬‬
‫‪ -‬ﻤﻨﺎﺴﺒﺘﻪ ﻟﻠﺘﺭﻜﻴﺏ ﺨﺎﺭﺝ ﺍﻟﻤﺒﺎﻨﻰ‪.‬‬

‫‪١٨/٦‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫ﻤﻜﻭﻨﺎﺕ ﺍﻟﻠﻭﺤﺔ‬ ‫‪١٠-٦‬‬


‫ﻗﻀﺒﺎﻥ ﺍﻟﺘﻭﺯﻴﻊ‬ ‫)ﺃ(‬
‫ﻴﺠﺏ ﺍﺴﺘﺨﺩﺍﻡ ﺍﻟﻨﺤﺎﺱ ﺍﻹﻟﻜﺘﺭﻭﻟﻴﺘﻰ ﺒﻨﺴﺒﺔ ﻨﻘﺎﺀ ﺘﻘﺘﺭﺏ ﻤﻥ ‪ ٪٩٩.٩٩٩‬ﻟﻘﻀـﺒﺎﻥ‬
‫ﺍﻟﺘﻭﺯﻴﻊ ﻭﻴﻤﻜﻥ ﺍﺴﺘﺜﻨﺎﺀ‪ ،‬ﺍﺴﺘﺨﺩﺍﻡ ﺍﻷﻟﻭﻤﻨﻴﻭﻡ ﺃﻭ ﺍﻷﻟﻭﻤﻨﻴﻭﻡ ﺍﻟﻤﻐﻁﻰ ﺒﺎﻟﻨﺤـﺎﺱ ﺇﺫﺍ‬
‫ﻭﺭﺩ ﺫﻟﻙ ﺒﺎﻟﺸﺭﻭﻁ ﺍﻟﺨﺎﺼﺔ ﺒﻤﺴﺘﻨﺩﺍﺕ ﺍﻟﻤﺸﺭﻭﻉ‪ .‬ﺘﺘﺤﺩﺩ ﺴﻌﺔ ﻗﻀـﺒﺎﻥ ﺍﻟﺘﻭﺯﻴـﻊ‬
‫ﺤﺴﺏ ﻗﻴﻤﺔ ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﻘﻨﻥ ﻟﻠﻭﺤﺔ ﻓﻰ ﺤﺎﻟﺔ ﺍﻟﺘﺸﻐﻴل ﺍﻟﻌﺎﺩﻯ‪ ،‬ﻭﻜﺫﻟﻙ ﺤﺴـﺏ ﻗﻴﻤـﺔ‬
‫ﺘﻴﺎﺭﺍﺕ ﺍﻟﻘﺼﺭ )ﻤﻥ ﺤﻴﺙ ﺍﻷﺜﺭ ﺍﻟﺤـﺭﺍﺭﻯ ﻭﺍﻟـﺩﻴﻨﺎﻤﻴﻜﻰ(‪ ،‬ﻭﻴﺠـﺏ ﺃﻥ ﺘﺤـﺩﺩ‬
‫ﻤﻘﺎﺴﺎﺕ ﻭﺃﺒﻌﺎﺩ ﺍﻟﻘﻀﺒﺎﻥ ﺤﺴـﺏ ﺍﻟﺘﻭﺼـﻴﺎﺕ ﺍﻟـﻭﺍﺭﺩﺓ ﺒﺎﻟﻤﻭﺍﺼـﻔﺎﺕ ﺍﻟﺩﻭﻟﻴـﺔ‬
‫ﺍﻟﻜﻬﺭﻭﺘﻘﻨﻴﺔ )‪.(IEC 439‬‬
‫)ﺏ( ﺍﻟﻤﺼﺎﻫﺭ‬
‫ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ ﺍﻟﻤﺼﺎﻫﺭ ﻤﻁﺎﺒﻘﺔ ﻟﻠﻤﻭﺍﺼﻔﺎﺕ ﺍﻟﻘﻴﺎﺴـﻴﺔ ﺍﻟﻤﺼـﺭﻴﺔ ﻡ‪.‬ﻕ‪.‬ﻡ ‪٢٦٥‬‬
‫ﻭﺍﻟﻤﻭﺍﺼﻔﺎﺕ ﺍﻟﺩﻭﻟﻴﺔ ﺍﻟﻜﻬﺭﻭﺘﻘﻨﻴﺔ )‪ (IEC 269‬ﻭﺘﻜﻭﻥ ﻤﻥ ﺃﺤﺩ ﺍﻷﻨﻭﺍﻉ ﺍﻟﺘﺎﻟﻴﺔ‪:‬‬
‫‪H.R.C. Fuses‬‬ ‫)‪ (١‬ﻤﺼﺎﻫﺭ ﺴﻜﻴﻨﺔ ﺫﺍﺕ ﺴﻌﺔ ﻗﻁﻊ ﻋﺎﻟﻴﺔ‬
‫ﻭﺘﻜﻭﻥ ﻫﺫﻩ ﺍﻟﻤﺼﺎﻫﺭ ﺫﺍﺕ ﺃﺩﻨﻰ ﻓﻘﺩ ﻓﻰ ﺍﻟﻁﺎﻗﺔ ﻭﺍﻟﺠﻬﺩ ﻭﺘﻜﻭﻥ ﻤﻘﻨﻨـﺔ‬
‫ﻟﺴﻌﺔ ﻗﻁﻊ ﻻ ﺘﻘل ﻋﻥ ‪ ١٠٠‬ﻙ‪.‬ﺃ‪ .‬ﻋﻨﺩ ﻤﻌﺎﻤل ﻗﺩﺭﺓ ‪ ٠.٢‬ﻤﺘﺄﺨﺭ‪.‬‬
‫‪Cylindrical Fuses‬‬ ‫)‪ (٢‬ﺍﻟﻤﺼﺎﻫﺭ ﺍﻻﺴﻁﻭﺍﻨﻴﺔ‬
‫ﻴﺠﺏ ﺃﻥ ﺘﻜﻭﻥ ﻫﺫﻩ ﺍﻟﻤﺼﺎﻫﺭ ﺫﺍﺕ ﺃﺩﻨﻰ ﻓﻘﺩ ﻓﻰ ﺍﻟﻁﺎﻗﺔ ﻭﺍﻟﺠﻬﺩ ﻭﻤﻘﻨﻨﺔ‬
‫ﻟﺴﻌﺔ ﻗﻁﻊ ﺘﺼل ﺇﻟﻰ ‪ ٥٠‬ﻙ‪.‬ﺃ‪.‬‬
‫)‪Miniature circuit breaker (MCB‬‬ ‫)‪ (٣‬ﻗﻭﺍﻁﻊ ﺍﻟﺩﻭﺍﺌﺭ ﺍﻟﻤﻨﻤﻨﻤﺔ‬
‫ﻴﺠﺏ ﺃﻥ ﺘﺘﻁﺎﺒﻕ ﻫﺫﻩ ﺍﻟﻘﻭﺍﻁﻊ ﻤﻊ ﺍﻟﻤﻭﺍﺼﻔﺎﺕ ﺍﻟﻜﻬﺭﻭﺘﻘﻨﻴﺔ )‪(IEC 989‬‬
‫ﻭﺃﻥ ﺘﻌﻤـل ﻫﺫﻩ ﺍﻟﻘﻭﺍﻁﻊ ﻴﺩﻭﻴﺎﹰ ﻭﺘﻘﻭﻡ ﺒﺎﻟﻔﺼل ﺘﻠﻘﺎﺌﻴﺎﹰ‪ ،‬ﻭﺘﺼل ﺴﻌﺔ ﺘﻴﺎﺭﻫﺎ‬
‫ﺍﻟﻤﻘﻨﻥ ﺇﻟﻰ ‪ ١٢٥‬ﺃ )ﺃﺤﺎﺩﻴﺔ ﺃﻭ ﺜﻨﺎﺌﻴﺔ ﺃﻭ ﺜﻼﺜﻴﺔ ﺍﻷﻁـﻭﺍﺭ( ﻭﺘﻜـﻭﻥ ﻫـﺫﻩ‬
‫ﺍﻟﻘﻭﺍﻁﻊ ﻤﺯﻭﺩﺓ ﺒﻌﻨﺎﺼﺭ ﺤﺭﺍﺭﻴﺔ ﻟﻠﻭﻗﺎﻴﺔ ﻀـﺩ ﺯﻴـﺎﺩﺓ ﺍﻟﺘﻴـﺎﺭ ﻭﺃﺨـﺭﻯ‬
‫ﻤﻐﻨﺎﻁﻴﺴﻴﺔ ﻟﻠﻭﻗﺎﻴﺔ ﻀﺩ ﻗﺼﺭ ﺍﻟﺩﺍﺌﺭﺓ ﻭﻴﺠﺏ ﺃﻻ ﺘﻘل ﺴﻌﺔ ﺍﻟﻘﻁـﻊ ﻋـﻥ ‪٦‬‬
‫ﻙ‪.‬ﺃ‪ .‬ﻋﻨﺩ ‪ ٢٢٠‬ﻓﻭﻟﺕ ﻭﻤﻌﺎﻤل ﻗﺩﺭﺓ ﻴﺘﺭﺍﻭﺡ ﻤﺎ ﺒﻴﻥ ‪ ٠.٦ ، ٠.٥‬ﻤﺘـﺄﺨﺭ‬
‫ﻤﻊ ﻤﺭﺍﻋﺎﺓ ﺒﻌﺩ ﻤﻜﺎﻥ ﺍﻟﻘﺎﻁﻊ ﻭﺍﺨﺘﻴﺎﺭ ﺴﻌﺔ ﺍﻟﻘﻁﻊ ﺍﻟﻤﻨﺎﺴﺒﺔ‪.‬‬

‫‪١٩/٦‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫)‪ (٤‬ﻗﻭﺍﻁﻊ ﺩﻭﺍﺌﺭ ﻟﻠﺤﻤﺎﻴﺔ ﻀﺩ ﺍﻟﺘﺴﺭﺏ ﺍﻷﺭﻀﻰ‬


‫)‪Earth leakage protective circuit breakers (ELCB‬‬
‫ﻭﺘﻜﻭﻥ ﻫﺫﻩ ﺍﻟﻘﻭﺍﻁﻊ ﺜﻨﺎﺌﻴﺔ ﺃﻭ ﺭﺒﺎﻋﻴﺔ ﺍﻷﻗﻁﺎﺏ ﻭﻤﻘﻨﻨﺔ ﻟﺘﻴﺎﺭﺍﺕ ﺍﻟﺘﺴﺭﺏ‬
‫ﺍﻟﻼﺯﻤﺔ ﻟﺘﺸﻐﻴﻠﻬﺎ ﻭﻴﻭﺠﺩ ﻨﻭﻋﻴﻥ ﻤﻥ ﻫﺫﻩ ﺍﻟﻘﻭﺍﻁﻊ‪:‬‬
‫‪-‬ﻗﺎﻁﻊ ﻟﻠﺤﻤﺎﻴﺔ ﻀﺩ ﺍﻟﺘﺴﺭﺏ ﺍﻷﺭﻀﻰ ﻴﻌﻤل ﺒﺎﻟﺘﻴﺎﺭ ﺍﻟﻜﻬﺭﺒﺎﺌﻰ‪.‬‬
‫‪-‬ﻗﺎﻁﻊ ﻟﻠﺤﻤﺎﻴﺔ ﻀﺩ ﺍﻟﺘﺴﺭﺏ ﺍﻷﺭﻀﻰ ﻴﻌﻤل ﺒﺎﻟﺠﻬﺩ ﺍﻟﻜﻬﺭﺒﺎﺌﻰ‪.‬‬
‫)‪ (٥‬ﻗﻭﺍﻁﻊ ﺍﻟﺩﻭﺍﺌﺭ ﺍﻷﻭﺘﻭﻤﺎﺘﻴﻜﻴﺔ ﺍﻟﻤﻘﻭﻟﺒﺔ‬
‫)‪Moulded case circuit breakers (MCCB‬‬
‫ﺘﻜﻭﻥ ﺴﻌﺔ ﻫﺫﻩ ﺍﻟﻘﻭﺍﻁﻊ ﺒﻤﻘﻨﻨﺎﺕ ﺘﻴﺎﺭ ﺤﺘﻰ ‪ ٣٢٠٠‬ﺃﻤﺒﻴﺭ ﻭﺴﻌﺔ ﻗﻁـﻊ‬
‫ﻟﻠﺴﻌﺎﺕ ﺍﻟﺼﻐﻴﺭﺓ ﻻ ﺘﻘل ﻋﻥ ‪ ١٥‬ﻙ‪.‬ﺃ‪ .‬ﻭﻴﺯﻭﺩ ﻜل ﻗﻁﺏ ﻤﻥ ﻫﺫﻩ ﺍﻟﻘﻭﺍﻁﻊ‬
‫ﺒﻌﻨﺼﺭ ﺤﺭﺍﺭﻯ ﻗﺎﺒل ﻟﻠﻀﺒﻁ ﻤﻥ ﺤﻭﺍﻟﻰ ‪ ٪٤٠‬ﺤﺘﻰ ‪ ٪١٠٠‬ﻤـﻥ ﺘﻴـﺎﺭ‬
‫ﺍﻟﻘﺎﻁﻊ ﺍﻟﻤﻘﻨﻥ ﻭﺫﻟﻙ ﻟﻠﻭﻗﺎﻴﺔ ﻀﺩ ﺯﻴﺎﺩﺓ ﺍﻟﺘﻴﺎﺭ ﻭﻜﺫﻟﻙ ﻋﻨﺼﺭ ﻤﻐﻨﺎﻁﻴﺴـﻰ‬
‫ﺜﺎﺒﺕ ﺃﻭ ﻗﺎﺒل ﻟﻠﻀﺒﻁ ﻤﻥ ‪ ١.٥‬ﺇﻟﻰ ‪ ١٠‬ﻤﺭﺍﺕ ﺍﻟﺘﻴﺎﺭ ﺍﻟﻤﻘـﻨﻥ‪ ،‬ﻭﻴﺠـﺏ ﺃﻥ‬
‫ﺘﻁﺎﺒﻕ ﻫﺫﻩ ﺍﻟﻘﻭﺍﻁﻊ ﺍﻟﻤﻭﺍﺼﻔﺎﺕ ﺍﻟﺩﻭﻟﻴﺔ ﺍﻟﻜﻬﺭﻭﺘﻘﻨﻴﺔ )‪.(IEC 408‬‬
‫)‪ (٦‬ﻗﻭﺍﻁﻊ ﺍﻟﺩﻭﺍﺌﺭ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﺫﺍﺕ ﺍﻹﻁﺎﺭ ﺍﻟﻤﻔﺘﻭﺡ )‪(Open frame‬‬
‫ﻭﺘﻜﻭﻥ ﻫﺫﻩ ﺍﻟﻘﻭﺍﻁﻊ ﺒﻤﻘﻨﻨﺎﺕ ﺘﻴﺎﺭ ﺤﺘﻰ ‪ ٦٣٠٠‬ﺃﻤﺒﻴﺭ ﻭﺒﺴـﻌﺔ ﻗﻁـﻊ‬
‫ﻤﻨﺎﺴﺒﺔ ﻋﻨﺩ ﺠﻬﺩ ﺜﻼﺜﻰ ﺍﻷﻁﻭﺍﺭ ‪ ٣٨٠‬ﻓﻭﻟﺕ‪ ،‬ﻭﻴﺠـﺏ ﺃﻥ ﺘﻁـﺎﺒﻕ ﻫـﺫﻩ‬
‫ﺍﻟﻘﻭﺍﻁﻊ ﺍﻟﻤﻭﺍﺼﻔﺎﺕ ﺍﻟﺩﻭﻟﻴﺔ ﺍﻟﻜﻬﺭﻭﺘﻘﻨﻴﺔ )‪.(IEC 157-1‬‬
‫)‪ (٧‬ﻗﻭﺍﻁﻊ ﻓﺼل ﻋﻠﻰ ﺍﻟﺤﻤل ‪Load break switches‬‬
‫ﺘﻜﻭﻥ ﻫﺫﻩ ﺍﻟﻘﻭﺍﻁﻊ ﺒﻤﻘﻨﻨﺎﺕ ﺘﻴﺎﺭ ﺤﺘـﻰ ‪ ٢٠٠٠‬ﺃﻤﺒﻴـﺭ ﻭﻤـﻥ ﺍﻟﻨـﻭﻉ‬
‫ﺍﻟﻤﻘﻭﻟﺏ‪ ،‬ﻭﻴﺠــﺏ ﺃﻥ ﺘﻁﺎﺒـــﻕ ﻫـــﺫﻩ ﺍﻟﻘﻭﺍﻁـﻊ ﺍﻟﻤﻭﺍﺼـﻔﺎﺕ‬
‫ﺍﻟﺩﻭﻟﻴﺔ ﺍﻟﻜﻬﺭﻭﺘﻘﻨﻴﺔ )‪.(IEC 408‬‬
‫)‪ (٨‬ﻗﻭﺍﻁﻊ ﻓﺼل ﻋﻠﻰ ﺍﻟﺤﻤل ﺒﺎﻟﻤﺼﺎﻫﺭ ‪Fuses load break switches‬‬
‫ﻭﺘﺘﻜﻭﻥ ﻤﻥ ﺴﻜﻴﻨﺔ ﻗﺎﻁﻊ ﻋﻠﻰ ﺍﻟﺤﻤل ﻤﻁﺎﺒﻘـﺔ ﻟﻤﻭﺍﺼـﻔﺎﺕ ﻗﻭﺍﻁـﻊ‬
‫ﺍﻟﻔﺼل ﻋﻠﻰ ﺍﻟﺤﻤل ﻭﻤﺼﺎﻫﺭ ﻤﻁﺎﺒﻘﺔ ﻟﻤﻭﺍﺼﻔﺎﺕ ﺍﻟﻤﺼـﺎﻫﺭ ﺫﺍﺕ ﺴـﻌﺔ‬
‫ﺍﻟﻘﻁﻊ ﺍﻟﻌﺎﻟﻴﺔ ﻭﺘﻜﻭﻥ ﻫﺫﻩ ﺍﻟﻘﻭﺍﻁﻊ ﺒﻤﻘﻨﻨﺎﺕ ﺘﻴﺎﺭ ﺤﺘﻰ ‪ ٨٠٠‬ﺃﻤﺒﻴﺭ‪.‬‬
‫)‪ (٩‬ﻟﻤﺒﺎﺕ ﺍﻟﺒﻴﺎﻥ‬

‫‪٢٠/٦‬‬
‫ﺍﻟﺩﻟﻴل ﺍﻻﺭﺸﺎﺩﻱ ﻟﺘﻁﺒﻴﻕ ﺍﻟﻜﻭﺩ ﺍﻟﻤﺼﺭﻱ ﻷﺴﺱ ﺘﺼﻤﻴﻡ ﻭﺸﺭﻭﻁ ﺘﻨﻔﻴﺫ‬
‫ﺍﻟﺒﺎﺏ ﺍﻟﺴﺎﺩﺱ‬
‫ﺍﻟﺘﻭﺼﻴﻼﺕ ﻭﺍﻟﺘﺭﻜﻴﺒﺎﺕ ﺍﻟﻜﻬﺭﺒﺎﺌﻴﺔ ﻓﻰ ﺍﻟﻤﺒﺎﻨﻲ )ﺍﻟﻤﺠﻠﺩ ﺍﻷﻭل‪ :‬ﺃﻋﻤﺎل ﺍﻟﺘﺼﻤﻴﻡ(‬

‫)‪ (١٠‬ﺃﺠﻬﺯﺓ ﻗﻴﺎﺱ‬


‫‪ -‬ﺃﻤﻴﺘﺭﺍﺕ ‪ +‬ﻤﺤﻭﻻﺕ ﺍﻟﺘﻴﺎﺭ‬
‫‪ -‬ﻓﻭﻟﺘﻤﻴﺘﺭ ‪ +‬ﺍﻟﺴﻠﻴﻜﺘﻭﺭ )ﻤﻔﺘﺎﺡ ﺇﻨﺘﻘﺎﺀ(‬

‫ﺩﺭﺠﺔ ﺍﻟﺤﻤﺎﻴﺔ ﻭﺘﺤﻤل ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﻟﻠﻭﺤﺎﺕ‬ ‫‪١١-٦‬‬


‫ﻴﺠﺏ ﺃﻥ ﺘﺤﻘﻕ ﺍﻟﻠﻭﺤﺎﺕ ﺍﻻﺸﺘﺭﺍﻁﺎﺕ ﺍﻟﺘﺎﻟﻴﺔ ﺤﺴﺏ ﻭﻅﻴﻔﺔ ﺍﻟﻠﻭﺤﺔ‪:‬‬
‫ﻟﻭﺤﺎﺕ ﺍﻟﺘﻭﺯﻴﻊ ﻟﺘﻐﺫﻴﺔ ﺍﻷﺤﻤﺎل‪:‬‬ ‫)ﺃ(‬
‫‪ -‬ﺘﺘﺤﻤل ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﻭﺤﺘﻰ ‪ ١٧٦‬ﻙ‪.‬ﺃ‬
‫‪ -‬ﻴﻀﻤﻥ ﺍﻟﺒﺩﻥ ﺩﺭﺠﺔ ﺤﻤﺎﻴﺔ ﺤﺘﻰ )‪ (IP 40‬ﻭﻴﻤﻜﻥ ﻁﻠﺒﻬﺎ ﺤﺘﻰ )‪.(IP 54‬‬
‫)ﺏ( ﻟﻭﺤﺎﺕ ﺍﻟﺘﻭﺯﻴﻊ ﻟﺘﻐﺫﻴﺔ ﻟﻭﺤﺎﺕ ﺃﺨﺭﻯ‪:‬‬
‫‪ -‬ﺘﺘﺤﻤل ﺘﻴﺎﺭ ﺍﻟﻘﺼﺭ ﻭﺤﺘﻰ ‪ ٨٠‬ﻙ‪.‬ﺃ‬
‫‪ -‬ﻴﻀﻤﻥ ﺍﻟﺒﺩﻥ ﺩﺭﺠﺔ ﺤﻤﺎﻴﺔ ﺤﺘﻰ )‪.(IP 65‬‬

‫‪٢١/٦‬‬

You might also like