Professional Documents
Culture Documents
Customer :
Naga SS
Address:
Naga Cebu
Purpose of test :
Replacement of CT
Type :
Oil CT's
Specification :
Date Tested:
Place Tested:
Inst. Used:
Equipment:
28-Jun-13
Time Tested:
Switchyard
Weather:
Vanguard TTR
Insts. S.N.:
Replacement Oil CT's Equipment S.N.:
Replacement Oil CT's
4:00 PM
Sunny
Results
REF
Test
Mode
REF
REF
52 CT 123
UST
Satisfactory
Test KV
8.15 kV
Test KV
8.09 kV
Test KV
9.12 kV
0.251 mA
0.000 mA
0.001 mA
Cap
81.96 pF
Cap
0.037 pF
Cap
0.159 pF
Tan
0.0019
Tan
Tan
-0.1730
0.0129
52 CT 125
UST
Satisfactory
Test KV
8.39 kV
Test KV
8.08 kV
Test KV
8.23 kV
0.000 mA
0.000 mA
0.001 mA
Cap
0.030 pF
Cap
0.051 pF
Cap
0.354 pF
Tan
0.2100
Tan
Tan
0.0468
Prepared by:
0.2570
REMARKS