CLIENT : ADITYA ALUMINIUM

CONTRACTOR : M/s RAMKY INFRASTRUCTURE LIMITED


PROJECT : SUPPLY OF RAW WATER FROM HIRAKUD RESERVOIR TO
ALUMINI SMELTER AND CAPTIVE POWER PLANT LAPANG
DISTRICT,SAMBALPUR,ORRISA

1.00.00

PUMP SHAFT INPUT POWER CALCULATION AS PER IS-1710


PUMP SHAFT INPUT POWER

P=(QXH)/367/PUMPOVERALL EFFICIENCY
WHERE Q IN CUM/HR, H IN MWC, P IN KW

PUMP CAPACITY

2700 CUM/HR

PUMP HEAD

84 MWC

PUMP OVERALL EFFICIENCY

0.85 ASSUMED

PUMP SHAFT INPUT POWER

727 KW

MOTOR RATING CALCULATION

2.00.00

MOTOR RATING CONSIDERING 15% MARGIN


ON PUMP SHAFT INPUT POWER

836 KW

MOTOR EFFICIENCY

0.94 ASSUMED

MOTOR INPUT POWER

889 KW

SELECTED FRAME SIZE

900 KW

UNDER SLUNG CRANE MOTOR

CLASS OF DUTY: MECHANICAL SERVICE CLASS II,IS-3177,INDOOR DUTY & ELECTRICAL SERVICE CLASS 4

2.00.01

M =MASS OF THE RATED LOAD ON THE HOOK+ WEIGHT


OF THE HOOK+ WEIGHT OF HOOK & WIRE ROPE IN TON

2.00.02

V=HOISTING SPEED IN M/MIN

2.00.03

K=SERVICE FACTOR DEPENDING ON ELECTRICAL SERVICE CLASS

2.00.04

E=COMBINED EFFICIENCY FOR GEARS & SHEAVES


N

E =(0.95) X (0.99)

FOR ANTI FRICTION BEARINGS

N=NUMBER OF PAIR OF GEARES


M=NUMBER OF ROTATING SHEAVES BETWEEN DRUM & EQALISER

2.00.05

K2 = FACTOR FOR FREQUENCY & VOLTAGE VARIATION OF 3% & 10% RESPECTIVELY

2.00.06

KW = (M X V X K) / (6.12 X E)

CALCULATION
M =

4 T

V =

6 M / MIN

K =

1 FOR SERVICE CLASS 4

E =

0.9

N =

M =

K2 =

0.9025

KW =

4.4

MOTOR KW
MOTOR KW SELECTED

4.9
15.0

3.00.00

VALVE ACTUATOR
BUTTERFLY VALVE-900
DIA

4.00.00

WINCH MOTOR
MOTOR RATING

5.00.00

KW

LIGHTING
FEEDER RATING

8.00.00

2.0 KW

VENTILATION
Not envisaged since
client's scope is not clear ----

7.00.00

7.5 KW

A C MACHINES
MOTOR POWER

6.00.00

0.75 KW

5.0 KW

WELDING RECEPTACLES
ASSUMED FEDER LOAD

1.5 KW

ERALL EFFICIENCY