You are on page 1of 14

X3

X4

(10 AWG RED)

X4

WHT)

X4

WHT)

X4

13

WHT)

X2 POWER CONTROL
RELAY
NO 108
NC

X2 MASTER CONTROL
RELAY
NO 143,812
NC
X2

CPU
PRE-WIRED

121
24V
GND
(16 AWG BLU)

(16 AWG GRY)

(16 AWG WHT)

(16 AWG GRY)

(16 AWG BLU)

14
(14 AWG RED)

CR110

100
OIL HEATER #1
101
HTR102
CB102
1000W (14 AWG
102 102 (14 AWG RED) CR739-1102A
102A (14 AWG RED)
(10 AWG RED)
102
9 5
30A
OIL HEATER #2
OIL HEATER RELAY
103
HTR104
104
1000W (14 AWG
102
(14 AWG RED)
102 (14 AWG RED) CR739-2 104
104
CB105
10 6
X1
105
OIL HEATER #3
OIL HEATER RELAY
105
HTR106
3A
CR739-3
106
1000W (14 AWG
(14 AWG RED)
102 (14 AWG RED)
106
106
12 8
OIL HEATER RELAY
107
POWER
108
ON/OFF
SELECTOR SWITCH
109
CR110
110
111
110
3
4
(16 AWG RED)
A1
A2
CB111
111
10A
112
113
113
(14 AWG RED)
EMERGENCY
114
STOP
CR115
CB115
113
115B
115 PB109 115A 115A
115B
115
(16 AWG RED)
(16 AWG YEL)
(16 AWG RED)
1A
A1
A2
116
117
118
R
118
(16 AWG RED)
(16 AWG WHT)
119
VDC POWER SUPPLY
PS121
120
100W
113
(16 AWG RED)
L
+
1
121
PE
122
N
VDC POWER SUPPLY
PS124
122
123
50W
113 (16 AWG RED) L
+
1
124
PE
125
N
126
127
124
125
128
122
PURGE FAIL
129
PURGE
RELAY
SWITCH
124
130
125
130
A
N.C.
COM
131
132
CR133
125
133
125 PURGE OK
113
RELAY
133
A1
A2
N.O.
COM
NO 830
PURGE OK
134
122
125 NC
G
135
136
CR715
SOL-051A
124
137
125
LOAD (SV-051A)
137
9 5
SOLENOID VALVE
138
CR721
SOL-051B
139
125
UNLD (SV-051B)
139
9 5
SOLENOID VALVE
140
141
120VAC DIO MOD
142
CR115 143
(16 AWG RED)
(16 AWG RED) 143
143
13 14
to 700
115
144
MASTER CONTROL
MC1
CR703
OPS-AUX
OL
145
RELAY
145
9 5
146
(16 AWG RED) 113
147
MC2
to 806
CR709
OL
148
120VAC DIO MOD
148
9 5

(10 AWG WHT)

X2

(10 AWG WHT)

(10 AWG RED)

X1

HMI
GP4601T

121
+
FG

I/S BARRIER
KFD2-PT2-EX1-5

121

+
FG

X2

X2

COMPRESSOR
MOTOR STARTER

X2

OIL PUMP
MOTOR STARTER

NEUTRAL
to 700
X2
LEGEND
CIRCUIT BREAKER
TERMINAL BLOCK POINT IN
MOTOR STARTER PANEL

HEATER ELEMENT

FIELD WIRING TERMINAL

THERMOSTATIC SWITCH

DRAWN BY

TS

DATE

04/29/14

INPUT

COIL

CH#

DRY CONTACT INPUT CHANNEL

CHECKED BY

DATE

OUTPUT

CH#

SOLENOID
N.C.

NORMALLY CLOSED CONTACT

PLUG IN OUTPUT MODULE


PLUG IN FUSE

SALES OFFICE

04/29/14
MIR S.O.

TITLE:

E-STOP

PUSH PULL SWITCH


N.O.

KH

FUSE

AMP

NORMALLY OPEN CONTACT


TRANSIENT SUPPRESSION DIODE
LEVEL SWITCH

CRIMP SPLICE (AMP #87F5699 OR EQUAL)

FACTORY WIRING

WIRE NUTS ARE NOT ACCEPTABLE

FIELD WIRING

PANEL PRODUCTION WIRING

REVISED DRAWINGS
1
TS
ISSUED FOR FABRICATION TS
0
MOD.
REV. NO.
DESCRIPTION
BY

07/24/14 JA
07/29/14
04/29/14 KH
04/29/14
ENGR.
DATE APPRV. DATE

MUSA
CUSTOMER

ENERFLEX
ENERGY
JOB NO.

16547
P.O. NO.

4500114555
DWG. NO.

V-COMPRESSOR, 120VAC
NEMA 4X ENCLOSURE
SHEET NO.

REV. NO.

MAYEKAWA
MT-AD-02
MOD 01
ANALOG INPUT
AD200
1

ALL WIRES 16 AWG


BLUE UNLESS OTHERWISE
SPECIFIED.

201
202

200

CBL200 BROWN

200

+24V

SUCTION
PRESSURE

CH 1

PT-1
SP
-1 - 10 kg/cm2

203

BLACK
SHLD

203

01+

204
205

206

01-

SHLD

207
208

210
211

209

CBL209 BROWN

209

+24V
PT-2
DP
-1 - 30 kg/cm2

CH 2
5

212

BLACK
SHLD

212

DISCHARGE
PRESSURE

02+

213
214

6-

215

02-

SHLD

216
217
218
219
220

218

CBL218 BROWN

+24V
PT-3
OP
-1 - 30 kg/cm2

CH 3
8

221

BLACK
SHLD

221

OIL
PRESSURE

03+

222
223

224

03-

SHLD

225
226

228
229

10

227

CBL227 BROWN

227

+24V
PT-4
OF
-1 - 30 kg/cm2

230

CH 4
11

230

BLACK
SHLD

OIL FILTER
PRESSURE

04-

231
232

12

233

04-

SHLD

234
235

CBL236 BLACK (1)

236
1

+24V

TT-1
ST
-50 - +50 C

237
2

238

13

236

BLACK (2)
SHLD

239

SUCTION
TEMPERATURE

CH 5
14

239
05+

240
241

15

242

05-

SHLD

243
244
245
246
247
248
LEGEND
CIRCUIT BREAKER
TERMINAL BLOCK POINT IN
MOTOR STARTER PANEL

HEATER ELEMENT

FIELD WIRING TERMINAL

THERMOSTATIC SWITCH

DRAWN BY

TS

DATE

04/29/14

INPUT

COIL

CH#

DRY CONTACT INPUT CHANNEL

CHECKED BY

DATE

OUTPUT

CH#

SOLENOID

FUSE

AMP

N.C.

NORMALLY CLOSED CONTACT

N.O.

NORMALLY OPEN CONTACT

PLUG IN OUTPUT MODULE


PLUG IN FUSE

KH
SALES OFFICE

04/29/14
MIR S.O.

TITLE:

E-STOP

PUSH PULL SWITCH


TRANSIENT SUPPRESSION DIODE
LEVEL SWITCH

CRIMP SPLICE (AMP #87F5699 OR EQUAL)

FACTORY WIRING

WIRE NUTS ARE NOT ACCEPTABLE

FIELD WIRING

PANEL PRODUCTION WIRING

REVISED DRAWINGS
1
TS
ISSUED FOR FABRICATION TS
0
MOD.
REV. NO.
DESCRIPTION
BY

07/24/14 JA
07/29/14
04/29/14 KH
04/29/14
ENGR.
DATE APPRV. DATE

MUSA
CUSTOMER

ENERFLEX
ENERGY
JOB NO.

16547
P.O. NO.

4500114555
DWG. NO.

V-COMPRESSOR, 120VAC
NEMA 4X ENCLOSURE
SHEET NO.

REV. NO.

ALL WIRES 16 AWG


BLUE UNLESS OTHERWISE
SPECIFIED.

300

AD200
16

300

CBL300 BLACK (1)

+24V
1

301
302

CH 6

2
-

TT-2
ST
0 - +150 C

17

303

BLACK (2)
SHLD

303

DISCHARGE
TEMPERATURE

06+

304
305

18

306

06-

307

SHLD

308

19

309

CBL309 BLACK (1)

309

+24V
1

310

311

CH 7

TT-3
OT
0 - +150 C

20

312

BLACK (2)
SHLD

312

OIL
TEMPERATURE

07+

313
314

21

315

07-

316

SHLD

317

319

320

22

318

CBL318 BLACK (1)

318

OIL SUMP
TEMPERATURE

CH 8

TT-4
OST
0 - +150 C

23

321

BLACK (2)
SHLD

321
322
323

24

324
325

SHLD

326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
24V+

345

(16 AWG BLU)

+24

24V+

from 125

+24V IN

346
347
COM

348

(16 AWG GRY)

COM

COM

from 126

COM

349

LEGEND
CIRCUIT BREAKER
TERMINAL BLOCK POINT IN
MOTOR STARTER PANEL

HEATER ELEMENT

FIELD WIRING TERMINAL

THERMOSTATIC SWITCH

DRAWN BY

TS

DATE

04/29/14

INPUT

COIL

CH#

DRY CONTACT INPUT CHANNEL

CHECKED BY

DATE

OUTPUT

CH#

SOLENOID

AMP

N.C.

NORMALLY CLOSED CONTACT

PLUG IN OUTPUT MODULE


PLUG IN FUSE

SALES OFFICE

04/29/14
MIR S.O.

TITLE:

E-STOP

PUSH PULL SWITCH


N.O.

KH

FUSE

NORMALLY OPEN CONTACT


TRANSIENT SUPPRESSION DIODE
LEVEL SWITCH

CRIMP SPLICE (AMP #87F5699 OR EQUAL)

FACTORY WIRING

WIRE NUTS ARE NOT ACCEPTABLE

FIELD WIRING

PANEL PRODUCTION WIRING

REVISED DRAWINGS
1
TS
ISSUED FOR FABRICATION TS
0
MOD.
REV. NO.
DESCRIPTION
BY

07/24/14 JA
07/29/14
04/29/14 KH
04/29/14
ENGR.
DATE APPRV. DATE

MUSA
CUSTOMER

ENERFLEX
ENERGY
JOB NO.

16547
P.O. NO.

4500114555
DWG. NO.

V-COMPRESSOR, 120VAC
NEMA 4X ENCLOSURE
SHEET NO.

REV. NO.

MAYEKAWA
MT-AD-02
MOD 02
ANALOG INPUT
AD400
1
400

+24V

401

CH 9

402

403

09+

404
405

406

09-

407
408

409

+24V

410

CH 10

411
L1-7

412

10+

413
414

415

10-

416
417

418

+24V

419

CH 11

420

421

11+

422
423

424

11-

425
426
426

427
428
429
430

CT

CT

426

10
+24V

DV420
CT
4-20MA

COMPRESSOR
MOTOR AMPS

CH 12

430

11

430

12+

431
432

434

12

433

12-

434
435

13

436

+24V

437

CH 13

438

14

439

13+

440
441

15

442

13-

443
444
445
446
447
448
449
LEGEND
CIRCUIT BREAKER
TERMINAL BLOCK POINT IN
MOTOR STARTER PANEL

HEATER ELEMENT

FIELD WIRING TERMINAL

THERMOSTATIC SWITCH

DRAWN BY

TS

DATE

04/29/14

INPUT

COIL

CH#

DRY CONTACT INPUT CHANNEL

CHECKED BY

DATE

OUTPUT

CH#

SOLENOID

FUSE

AMP

N.C.

NORMALLY CLOSED CONTACT

N.O.

NORMALLY OPEN CONTACT

PLUG IN OUTPUT MODULE


PLUG IN FUSE

KH
SALES OFFICE

04/29/14
MIR S.O.

TITLE:

E-STOP

PUSH PULL SWITCH


TRANSIENT SUPPRESSION DIODE
LEVEL SWITCH

CRIMP SPLICE (AMP #87F5699 OR EQUAL)

FACTORY WIRING

WIRE NUTS ARE NOT ACCEPTABLE

FIELD WIRING

PANEL PRODUCTION WIRING

REVISED DRAWINGS
1
TS
ISSUED FOR FABRICATION TS
0
MOD.
REV. NO.
DESCRIPTION
BY

07/24/14 JA
07/29/14
04/29/14 KH
04/29/14
ENGR.
DATE APPRV. DATE

MUSA
CUSTOMER

ENERFLEX
ENERGY
JOB NO.

16547
P.O. NO.

4500114555
DWG. NO.

V-COMPRESSOR, 120VAC
NEMA 4X ENCLOSURE
SHEET NO.

REV. NO.

AD400
16
500

+24V

501

CH 14

502

17

503

14+

504
505

18

506

14-

507
508

19

509

+24V

510
511
512
513
514

3
2
1

12
11
10

6
5
4

9
8
7

512

BLK

20
15A+

CBL514

515

21

515

15A-

WHT

516

SHLD

SHLD

517

CH 15A

22

TB3

518

+24V

519

CH 16A

520

23

521

16A+

522
523

24

524

16A-

525
526

25

527

LF1

528

CH 15B

529

26

530

LF2

531
532

27

533

LF3

534
535

28

536

HF1

537

CH 16B

538

29

539

HF2

540
541

30

542

HF3

543
544
121

545

24+

121

(16 AWG BLU)

from 121

+24V IN

546
547
122

548

(16 AWG GRY)

COM

122

from 122

COM

549

LEGEND
CIRCUIT BREAKER
TERMINAL BLOCK POINT IN
MOTOR STARTER PANEL

HEATER ELEMENT

FIELD WIRING TERMINAL

THERMOSTATIC SWITCH

COIL

DRAWN BY

TS

DATE

04/29/14

INPUT

CH#

DRY CONTACT INPUT CHANNEL

CHECKED BY

DATE

OUTPUT

CH#

SOLENOID

FUSE

AMP

N.C.

NORMALLY CLOSED CONTACT

PLUG IN OUTPUT MODULE


PLUG IN FUSE

04/29/14
MIR S.O.

TITLE:

E-STOP

PUSH PULL SWITCH


N.O.

KH
SALES OFFICE

NORMALLY OPEN CONTACT


TRANSIENT SUPPRESSION DIODE
LEVEL SWITCH

CRIMP SPLICE (AMP #87F5699 OR EQUAL)

FACTORY WIRING

WIRE NUTS ARE NOT ACCEPTABLE

FIELD WIRING

PANEL PRODUCTION WIRING

1
REVISED DRAWINGS
TS
0
ISSUED FOR FABRICATION TS
MOD.
REV. NO.
DESCRIPTION
BY

07/24/14 JA
07/29/14
04/29/14 KH
04/29/14
ENGR.
DATE APPRV. DATE

MUSA
CUSTOMER

ENERFLEX
ENERGY
JOB NO.

16547
P.O. NO.

4500114555
DWG. NO.

V-COMPRESSOR, 120VAC
NEMA 4X ENCLOSURE
SHEET NO.

REV. NO.

MAYEKAWA
MT-DA-02-A
MOD 03
ANALOG OUTPUT
BA600
1
600
601

CH 1

602

603

600
1+

603
01-

604
605

606

SHLD
FG

607
608

609
610

CH 2

611

612

609
2+

612
02-

613
614

615

SHLD
FG

616
617

618
CH 3

619
620

618
03+

621

621
03-

622
623

624

SHLD
FG

625
626

10

627
CH 4

628
629

04+

11

630

04-

631
632

12

633

FG

634
635

636

121
+24V IN

(16 AWG BLU)

121
from 121

637
638

639

122

(16 AWG GRY) 122

COM

from 122

640
641
642
643
644
645
646
LEGEND
CIRCUIT BREAKER
TERMINAL BLOCK POINT IN
MOTOR STARTER PANEL

HEATER ELEMENT

FIELD WIRING TERMINAL

THERMOSTATIC SWITCH

COIL

DRAWN BY

TS

DATE

04/29/14

INPUT

CH#

DRY CONTACT INPUT CHANNEL

CHECKED BY

DATE

OUTPUT

CH#

SOLENOID

AMP

N.C.

NORMALLY CLOSED CONTACT

N.O.

NORMALLY OPEN CONTACT

PLUG IN OUTPUT MODULE

KH

FUSE

PLUG IN FUSE

SALES OFFICE

04/29/14
MIR S.O.

TITLE:

E-STOP

PUSH PULL SWITCH


TRANSIENT SUPPRESSION DIODE
LEVEL SWITCH

CRIMP SPLICE (AMP #87F5699 OR EQUAL)

FACTORY WIRING

WIRE NUTS ARE NOT ACCEPTABLE

FIELD WIRING

PANEL PRODUCTION WIRING

1
REVISED DRAWINGS
TS
ISSUED FOR FABRICATION TS
0
MOD.
REV. NO.
DESCRIPTION
BY

07/24/14 JA
07/29/14
04/29/14 KH
04/29/14
ENGR.
DATE APPRV. DATE

MUSA
CUSTOMER

ENERFLEX
ENERGY
JOB NO.

16547
P.O. NO.

4500114555
DWG. NO.

V-COMPRESSOR, 120VAC
NEMA 4X ENCLOSURE
SHEET NO.

REV. NO.

143
from 143
120VAC DIO MOD

(16 AWG RED)

700

MAYEKAWA
MT-DIOA-01-A
MOD 04
DIGITAL IN / OUT
BA700
1A

X2
from 148
NEUTRAL
X2

701
702
COMPRESSOR
MOTOR
STARTER

703
704
705

1B

CR703

703

COMPRESSOR
MOTOR STARTER

CH. 01

NO 145
NC

2A
(16 AWG RED)

706

X2

707
708
OIL PUMP
MOTOR STARTER

709

2B

CR709

709

OIL PUMP
MS

CH. 02

710
711

NO 148
NC

3A
(16 AWG RED)

712

X2

713
714
COMPRESSOR
LOAD SV

715

3B

CR715

715

(SV-051A) LOAD
SOLENIOD RELAY

CH. 03

716
717

NO 137
NC

4A
(16 AWG RED)

718

X2

719
720
COMPRESSOR
UNLOAD SV

721

CR721

721

(SV-051B) UNLOAD
SOLENIOD RELAY

CH. 04

722
723
724

4B

143

(16 AWG RED)

NO 139
NC

5A
X2

726

5B

727

727

(16 AWG WHT)

725
727

CH. 05

728
729

6A
(16 AWG RED)

730
731
732

6B

733

733

CH. 06

734
735
(16 AWG RED)

736

7A
X2

737
738

7B

739

CR739

739

CH. 07

740
741
(16 AWG RED)

742

OIL HEATER
RELAY
NO 102,104,106
NC

8A

743
744

8B

745

745

745

CH. 08

746
747

120VAC DIO
to 800
X2

748
749

120VAC DIO MOD


to 800
143
LEGEND
CIRCUIT BREAKER

TERMINAL BLOCK POINT IN


MOTOR STARTER PANEL

HEATER ELEMENT

FIELD WIRING TERMINAL

THERMOSTATIC SWITCH

DRAWN BY

TS

DATE

04/29/14

INPUT

COIL

CH#

DRY CONTACT INPUT CHANNEL

CHECKED BY

DATE

OUTPUT

CH#

SOLENOID

FUSE

AMP

N.C.

NORMALLY CLOSED CONTACT

N.O.

NORMALLY OPEN CONTACT

PLUG IN OUTPUT MODULE


PLUG IN FUSE

KH
SALES OFFICE

04/29/14
MIR S.O.

TITLE:

E-STOP

PUSH PULL SWITCH


TRANSIENT SUPPRESSION DIODE
LEVEL SWITCH

CRIMP SPLICE (AMP #87F5699 OR EQUAL)

FACTORY WIRING

WIRE NUTS ARE NOT ACCEPTABLE

FIELD WIRING

PANEL PRODUCTION WIRING

REVISED DRAWINGS
1
TS
0
ISSUED FOR FABRICATION TS
MOD.
REV. NO.
DESCRIPTION
BY

07/24/14 JA
07/29/14
04/29/14 KH
04/29/14
ENGR.
DATE APPRV. DATE

MUSA
CUSTOMER

ENERFLEX
ENERGY
JOB NO.

16547
P.O. NO.

4500114555
DWG. NO.

V-COMPRESSOR, 120VAC
NEMA 4X ENCLOSURE
SHEET NO.

REV. NO.

113
from 147
120VAC DIO MOD

ALL WIRES 16 AWG


BLUE UNLESS OTHERWISE
SPECIFIED.

143
from 749
120VAC DIO MOD

X2
from 747
120VAC DIO

BA700
9A

(16 AWG RED)

800
801
802

9B

803
CH. 09

804
805

10A

(16 AWG RED)

806
807
808

10B

809

812
813
814

ALARM

CH. 10

810
811

809

CR115
23

11A

812A

24

COMPRESSOR
EMERGENCY STOP

CH. 11

MASTER CONTROL
RELAY

11B

812B

815

ALARM OUTPUT
X2 (SUPPLIED AND
INSTALLED BY OTHERS)

816
817

MSRB

818
819
820

12A

818A

CH. 12

COMPRESSOR
MOTOR STARTER

12B

818B

821

COMPRESSOR
MOTOR STARTER
READBACK

822
823

13A

824A

824

#1 COMPRESSOR
CUTOUT INTERLOCK

CH. 13

825
JUMPER

826

13B

824B

827
828
829

14A

CR133

830
831
832

PURGE OK
CUTOUT INTERLOCK

CH. 14

PURGE OK
RELAY

14B

833
834
835

15A

836A

836

#3 COMPRESSOR
CUTOUT INTERLOCK

CH. 15

837
JUMPER

838

15B

836B

839
840
841

CRSS

842
843
844

16A

842A

CH. 16

REMOTE START / STOP


RELAY
842B

845

COMPRESSOR
REMOTE START/STOP

16B

846
847
848
849

LEGEND
CIRCUIT BREAKER
TERMINAL BLOCK POINT IN
MOTOR STARTER PANEL

HEATER ELEMENT

FIELD WIRING TERMINAL

THERMOSTATIC SWITCH

DRAWN BY

TS

DATE

04/29/14

INPUT

COIL

CH#

DRY CONTACT INPUT CHANNEL

CHECKED BY

DATE

OUTPUT

CH#

SOLENOID

FUSE

AMP

N.C.

NORMALLY CLOSED CONTACT

N.O.

NORMALLY OPEN CONTACT

PLUG IN OUTPUT MODULE


PLUG IN FUSE

KH
SALES OFFICE

04/29/14
MIR S.O.

TITLE:

E-STOP

PUSH PULL SWITCH


TRANSIENT SUPPRESSION DIODE
LEVEL SWITCH

CRIMP SPLICE (AMP #87F5699 OR EQUAL)

FACTORY WIRING

WIRE NUTS ARE NOT ACCEPTABLE

FIELD WIRING

PANEL PRODUCTION WIRING

REVISED DRAWINGS
1
TS
0
ISSUED FOR FABRICATION TS
MOD.
REV. NO.
DESCRIPTION
BY

07/24/14 JA
07/29/14
04/29/14 KH
04/29/14
ENGR.
DATE APPRV. DATE

MUSA
CUSTOMER

ENERFLEX
ENERGY
JOB NO.

16547
P.O. NO.

4500114555
DWG. NO.

V-COMPRESSOR, 120VAC
NEMA 4X ENCLOSURE
SHEET NO.

REV. NO.

MAYEKAWA
MT-DIO2-01
DIGITAL IN / OUT

143
from 143
120VAC EXPAN DIO MOD

X2
from 144
NEUTRAL

1A
900
901
902

1B

903
904

905

2A

906
907
908

2B

909
-

910
911
REM-LD

912

N.O.

3A

912A

REMOTE (LOW STAGE) LOAD INPUT


(OPTIONAL)

COM

913
914

3B

912B

915

916
917
REM-UNLD

918

N.O.

4A

918A

REMOTE (LOW STAGE) UNLOAD INPUT


(OPTIONAL)

COM

919
920

4B

918B

921

922
923
924
925
926
927
928
929
930
931
932
933
934
935
936
937
938
939
940
941
942
943
944
945

X2

946
947
948

END

143
END

949
LEGEND
CIRCUIT BREAKER
TERMINAL BLOCK POINT IN
MOTOR STARTER PANEL

HEATER ELEMENT

FIELD WIRING TERMINAL

THERMOSTATIC SWITCH

DRAWN BY

TS

DATE

04/29/14

INPUT

COIL

CH#

DRY CONTACT INPUT CHANNEL

CHECKED BY

DATE

OUTPUT

CH#

SOLENOID

FUSE

AMP

N.C.

NORMALLY CLOSED CONTACT

N.O.

NORMALLY OPEN CONTACT

PLUG IN OUTPUT MODULE


PLUG IN FUSE

KH
SALES OFFICE

04/29/14
MIR S.O.

TITLE:

E-STOP

PUSH PULL SWITCH


TRANSIENT SUPPRESSION DIODE
LEVEL SWITCH

CRIMP SPLICE (AMP #87F5699 OR EQUAL)

FACTORY WIRING

WIRE NUTS ARE NOT ACCEPTABLE

FIELD WIRING

PANEL PRODUCTION WIRING

REVISED DRAWINGS
1
TS
0
ISSUED FOR FABRICATION TS
MOD.
REV. NO.
DESCRIPTION
BY

07/24/14 JA
07/29/14
04/29/14 KH
04/29/14
ENGR.
DATE APPRV. DATE

MUSA
CUSTOMER

ENERFLEX
ENERGY
JOB NO.

16547
P.O. NO.

4500114555
DWG. NO.

V-COMPRESSOR, 120VAC
NEMA 4X ENCLOSURE
SHEET NO.

REV. NO.

X1

TB1-1

(1)

X2

TB1-2

(2)

CT

TB2-3

TB3

CT
CT

TB2-4
SHLD

TB3
145

TB2-SH
TB1-1B

COMP

OP-AUX

OL

MS
TB4

OIL-PUMP
148

TB1-2B

OL

OPS
TB4

818A

MSRB

TB1-12A

COM

TB3
818B

N.O.

TB1-31

TB3

606

TB2-40

TB3
608

TB2-41
SHLD

TB3

TB2-SH

LEGEND
CIRCUIT BREAKER
TERMINAL BLOCK POINT IN
MOTOR STARTER PANEL

HEATER ELEMENT

FIELD WIRING TERMINAL

THERMOSTATIC SWITCH

DRAWN BY

TS

DATE

04/29/14

INPUT

COIL

CH#

DRY CONTACT INPUT CHANNEL

CHECKED BY

DATE

OUTPUT

CH#

SOLENOID

AMP

N.C.

NORMALLY CLOSED CONTACT

PLUG IN OUTPUT MODULE


PLUG IN FUSE

SALES OFFICE

04/29/14
MIR S.O.

TITLE:

E-STOP

PUSH PULL SWITCH


N.O.

KH

FUSE

NORMALLY OPEN CONTACT


TRANSIENT SUPPRESSION DIODE
LEVEL SWITCH

CRIMP SPLICE (AMP #87F5699 OR EQUAL)

FACTORY WIRING

WIRE NUTS ARE NOT ACCEPTABLE

FIELD WIRING

PANEL PRODUCTION WIRING

1
REVISED DRAWINGS
TS
ISSUED FOR FABRICATION TS
0
MOD.
REV. NO.
DESCRIPTION
BY

07/24/14 JA
07/29/14
04/29/14 KH
04/29/14
ENGR.
DATE APPRV. DATE

MUSA
CUSTOMER

ENERFLEX
ENERGY
JOB NO.

16547
P.O. NO.

4500114555
DWG. NO.

V-COMPRESSOR, 120VAC
NEMA 4X ENCLOSURE
SHEET NO.

REV. NO.

X1

X1

X1

X2

X2

X2

CT

TB1-3

0-5A

TB3

CT
CT

TB1-4

TB3
145

TB1-1B

COMP

OP-AUX

OL

MS
TB4

OIL-PUMP
148

TB1-2B

OL

OPS
TB4

818A

MSRB

TB1-1

COM

TB3
818B

N.O.

TB1-57

TB3

LEGEND
CIRCUIT BREAKER
TERMINAL BLOCK POINT IN
MOTOR STARTER PANEL

HEATER ELEMENT

FIELD WIRING TERMINAL

THERMOSTATIC SWITCH

DRAWN BY

TS

DATE

04/29/14

INPUT

COIL

CH#

DRY CONTACT INPUT CHANNEL

CHECKED BY

DATE

OUTPUT

CH#

SOLENOID

AMP

N.C.

NORMALLY CLOSED CONTACT

PLUG IN OUTPUT MODULE


PLUG IN FUSE

SALES OFFICE

04/29/14
MIR S.O.

TITLE:

E-STOP

PUSH PULL SWITCH


N.O.

KH

FUSE

NORMALLY OPEN CONTACT


TRANSIENT SUPPRESSION DIODE
LEVEL SWITCH

CRIMP SPLICE (AMP #87F5699 OR EQUAL)

FACTORY WIRING

WIRE NUTS ARE NOT ACCEPTABLE

FIELD WIRING

PANEL PRODUCTION WIRING

1
REVISED DRAWINGS
TS
ISSUED FOR FABRICATION TS
0
MOD.
REV. NO.
DESCRIPTION
BY

07/24/14 JA
07/29/14
04/29/14 KH
04/29/14
ENGR.
DATE APPRV. DATE

MUSA
CUSTOMER

ENERFLEX
ENERGY
JOB NO.

16547
P.O. NO.

4500114555
DWG. NO.

V-COMPRESSOR, 120VAC
NEMA 4X ENCLOSURE
SHEET NO.

REV. NO.

X1
X2
GND
X3
X4
GND

PS121

PS124

CR110
A1

CR115

A2

A1

A2

13 NO 23 NO 33 NO 43 NO

13 NO 23 NO 33 NO 43 NO

CF

CF

14 NO 24 NO 34 NO 44 NO

14 NO 24 NO 34 NO 44 NO

CB102
CB105
CB111
CB115

CR133
CR703
CR709
CR715
CR721
CR721

102
102
X1
X1
113
113
113
115A
115B
X2
X2
X2
X2
X2
X2
GND
GND
GND

X2
X2
X2
X2
X2
X2
X2
X2

GND
GND
GND
GND
GROUND
GROUND
GROUND
GROUND

RED,BLK,WHT
ZE1

NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL
NEUTRAL

426,430,434
CT PWR.

103A
104
106
X4
X4
X4
145
148
809

318,321
O. SMP. TEMP

HEATER #1
HEATER #2
HEATER #3
HTR NEUTRAL
HTR NEUTRAL
HTR NEUTRAL
COMP. MTR. STR.
OIL P. MTR. STR.
ALARM

309,312
OIL TEMP

CT

300,303
DIS TEMP

CT

236,239
SUC TEMP

125,137
125,139
125,130
125,133
818A,818B
824A,824B
836A,836B
842A,842B
912A,912B
918A,918B

227,230
FLTR PRESS

LOAD
UNLOAD
PURGE N.C.
PURGE N.O.
MSRB
INTLCK#1
INTLCK#3
CRSS
R. LOAD
R UNLOAD

218,221
OIL PRESS

609,612

209,212
DIS PRESS

600,603

200,203
SUC PRESS

121
121
121
122
122
122

LEGEND
CIRCUIT BREAKER
TERMINAL BLOCK POINT IN
MOTOR STARTER PANEL

HEATER ELEMENT

FIELD WIRING TERMINAL

THERMOSTATIC SWITCH

DRAWN BY

TS

DATE

04/29/14

INPUT

COIL

CH#

DRY CONTACT INPUT CHANNEL

CHECKED BY

DATE

OUTPUT

CH#

SOLENOID

FUSE

AMP

N.C.

NORMALLY CLOSED CONTACT

N.O.

NORMALLY OPEN CONTACT

PLUG IN OUTPUT MODULE


PLUG IN FUSE

KH
SALES OFFICE

04/29/14
MIR S.O.

TITLE:

E-STOP

PUSH PULL SWITCH


TRANSIENT SUPPRESSION DIODE
LEVEL SWITCH

CRIMP SPLICE (AMP #87F5699 OR EQUAL)

FACTORY WIRING

WIRE NUTS ARE NOT ACCEPTABLE

FIELD WIRING

PANEL PRODUCTION WIRING

REVISED DRAWINGS
1
TS
ISSUED FOR FABRICATION TS
0
MOD.
REV. NO.
DESCRIPTION
BY

07/24/14 JA
07/29/14
04/29/14 KH
04/29/14
ENGR.
DATE APPRV. DATE

MUSA
CUSTOMER

ENERFLEX
ENERGY
JOB NO.

16547
P.O. NO.

4500114555
DWG. NO.

V-COMPRESSOR, 120VAC
NEMA 4X ENCLOSURE
SHEET NO.

REV. NO.

24.0000

8.0000

30.0000

8.7980
8.0000
7.0000
(4) PLCS

1.5000

2.2500
24.0000

22.0000

2.0000

0.0000

0.0000

KNOCKOUT FOR
1" CONDUIT (1) PLC.

KNOCKOUT FOR
3/4" CONDUIT (3) PLCS.

KNOCKOUT FOR
1/2" CONDUIT (3) PLCS.

LEGEND
CIRCUIT BREAKER
TERMINAL BLOCK POINT IN
MOTOR STARTER PANEL

HEATER ELEMENT

FIELD WIRING TERMINAL

THERMOSTATIC SWITCH

DRAWN BY

TS

DATE

04/29/14

INPUT

COIL

CH#

DRY CONTACT INPUT CHANNEL

CHECKED BY

DATE

OUTPUT

CH#

SOLENOID

AMP

N.C.

NORMALLY CLOSED CONTACT

PLUG IN OUTPUT MODULE


PLUG IN FUSE

SALES OFFICE

04/29/14
MIR S.O.

TITLE:

E-STOP

PUSH PULL SWITCH


N.O.

KH

FUSE

NORMALLY OPEN CONTACT


TRANSIENT SUPPRESSION DIODE
LEVEL SWITCH

CRIMP SPLICE (AMP #87F5699 OR EQUAL)

FACTORY WIRING

WIRE NUTS ARE NOT ACCEPTABLE

FIELD WIRING

PANEL PRODUCTION WIRING

REVISED DRAWINGS
1
TS
0
ISSUED FOR FABRICATION TS
MOD.
REV. NO.
DESCRIPTION
BY

07/24/14 KH
07/24/14
04/29/14 KH
04/29/14
ENGR.
DATE APPRV. DATE

MUSA
CUSTOMER

ENERFLEX
ENERGY
JOB NO.

16547
P.O. NO.

4500114555
DWG. NO.

V-COMPRESSOR, 120VAC
NEMA 4X ENCLOSURE
SHEET NO.

REV. NO.

QTY.

PART NUMBER

DESCRIPTION

CODE NUMBER

MODEL

48590034

MYPRO TOUCH KIT

50110060

RUBBER VIBRATION MOUNTS

30304192

NEMA 4X HOFFMAN ENCLOSURE

30304168

HOFFMAN BACKPLATE

49358827

AB MASTER CONTROL RELAY

700-CF00D

61860016

NK TECHNOLOGIES 4-20MA CT SENSOR

AT1-420-24L-FT

30307502

P&F SAFETY BARRIER

49358979

CLASS I, DIV II GREEN LIGHT

49358983

CLASS I, DIV II AMBER LIGHT

49359024

CLASS I, DIV II EMERGENCY E-STOP

55080123

YELLOW E-STOP TAG

LWE16300

49359045

AB POWER SUPPLY

1606-XLP100E

49358835

AB 1AMP SINGLE POLE CIRCUIT BREAKER

1489-A1C010

49358840

AB 10AMP SINGLE POLE CIRCUIT BREAKER

1489-A1C100

49358841

AB 15AMP SINGLE POLE CIRCUIT BREAKER

1489-A1C150

49358842

AB 20AMP SINGLE POLE CIRCUIT BREAKER

1489-A1C200

49358843

AB 25AMP SINGLE POLE CIRCUIT BREAKER

1489-A1C250

49358844

AB 30AMP SINGLE POLE CIRCUIT BREAKER

1489-A1C300

36

49358858

AB TERMINAL BLOCK

1492-J3

49358891

AB END BARRIER FOR 1492-J3

1492-EBJ3

49358870

AB TERMINAL BLOCK

1492-J10

49358859

AB GROUND TERMINAL BLOCK

1492-JG3

49358871

AB GROUND TERMINAL BLOCK

1492-JG10

13

49358798

AB TERMINAL BLOCK

1492-JT3M

12

49358857

AB END ANCHOR

1492-EAJ35

49360044

AB END BARRIER FOR 1492-EBJ3TM

1492-EBJ3TM

11

49358967

AB 2 TIER TERMINAL BLOCK

1492-JD3

49358968

END BARRIER FOR 1492-JD3

1492-EBJD3

55060150

IDEC SPDT RELAY SOCKET

SH1B-05

55060152

IDEC DPDT RELAY SOCKET

SH2B-05

55060154

IDEC 3PDT RELAY SOCKET

SH3B-05

55060050

IDEC SP 120VAC RELAY

RH1B-U

55060052

IDEC DPDT 120VAC RELAY

RH2B-U

55060054

IDEC 3PDT 120VAC RELAY

RH3B-U

49358836

3 AMP BREAKER

40259398

1492-J4 TERMINAL BLOCKS

55060049

24VDC RELAY

20204606

SS WINDOW KIT

10102011

PURGE VENT

LEFT HAND Z- PURGE KIT

1002-WPS-CI-YZ-LH

ON/OFF SELECTOR SWITCH

HSS0-SHWE-CBF

220VAC CONTROL OPTION


55060051

IDEC SPDT 220VAC RELAY

RH1B-U

55060053

IDEC DPDT 220VAC RELAY

RH2B-U

55060064

IDEC 3PDT 220VAC RELAY

RH3B-U

49358833

AB 220VAC LIGHT MODULE

800F-N7W

49358828

AB 220VAC MASTER CONTROL RELAY COIL

TA-296

49358835

AB 1AMP SINGLE POLE CIRCUIT BREAKER

1489-A2C010

49358840

AB 5AMP SINGLE POLE CIRCUIT BREAKER

1489-A2C050

49358841

AB 7AMP SINGLE POLE CIRCUIT BREAKER

1489-A2C070

49358842

AB 10AMP SINGLE POLE CIRCUIT BREAKER

1489-A2C100

49358843

AB 15AMP SINGLE POLE CIRCUIT BREAKER

1489-A2C150

DRAWN BY

TS
CHECKED BY

KH
SALES OFFICE

MUSA
CUSTOMER

ENERFLEX
ENERGY
JOB NO.

REVISED DRAWINGS
1
TS
0
ISSUED FOR FABRICATION TS
MOD.
REV. NO.
DESCRIPTION
BY

07/24/14 JA
07/29/14
04/29/14 KH
04/29/14
ENGR.
DATE APPRV. DATE

DATE

04/29/14
DATE

04/29/14
MIR S.O.

16547
P.O. NO.

4500114555
DWG. NO.

TITLE:

V-COMPRESSOR, 120VAC
NEMA 4X ENCLOSURE
SHEET NO.

REV. NO.