Protection Coordination Report

Owner

ASIAN PAINTS LIMITED

Project:

ASIAN PAINTS LIMITED.,


PAINT PLANT SRIPERUMBUDUR,CHENNAI

Contractor:

POWER TECH ENGINEERS,

Compiled by

Interface Electronics Pvt Ltd,Chennai


Email:ife@vsnl.com
website:www.ifepwrana.com
mobile:9884370326

Executive Summary
Introduction
Project:
Owner:
Electrical Contractor:
ElectricalDistribution System
Power System Data

ASIAN PAINTS Ltd,PAINT PLANT-SRIPERUMBUDUR,CHENNAI


ASIAN PAINTS Ltd,PAINT PLANT-SRIPERUMBUDUR,CHENNAI
POWERTECH ENGINEERS
33 kV,0.415 kV Power Distribution System

Max Source Fault level (assumed) 1500 MVA sec at 33 kV


Min Source Fault level (assumed) 750 MVA sec at 33 kV
Tools used:
Paladin Design Base 5- an Electrical Design software
Protection Coordination

Conclusion

The short circuit currents at various busbars are calculated based on the
above assumptions. Calculated Short circuit currents are tabulated in the
report and also shown in the SLD.
Selectivity of relays and circuit breakers were worked out based on the
cable size and flow of short circuit currents.
Time current characterstic curves are generated for every path and
verified .
Settings for each device,short circuit currents at every busbars,detailed
calculations for the settings are given in the following pages. While doing
this exercise certain discrepencies were noticed and these are brought
out seperately under heading 'Comments and Observations'.

SINGLE LINE DIAGRAM

SINGLE LINE DIAGRAM OF ELECTRICAL DISTRIBUTION SYSTEM FOR COORDINATION STUDY

GRID

TNEB
Vs: 33000 V

33kV OD PNL BD
50
51

DG1
Vs: 415 V

GEN

GEN

DG 3
Vs: 415 V

DG2_IC

GEN
HVP_IC

50
51

33KV_3PNL_BD
Vs: 33000 V

DG3_IC
HVP_OG1

HVP_OG2

50
51

DG S205
Vs: 415 V

BD_DG S205_1

BD DG3

BD DG2

BD DG1
DG1_IC

DG PNL
Vs: 415 V

DG2
Vs: 415 V

CAB:MAIN

GEN

DG PNL S205

50
51

DG PNL_OG

17F2

6F2

7F2

BD_TRF2

BD_TRF1

MAIN MV PNL SECT1 EB BUS


Vs: 415 V

MVP_IC1

MAIN MV PNL SECT2 EB BUS


Vs: 415 V

BD_DG S205_2

TRF2

CAB:TRF2

CAB:TRF1

BD DGPNL

TRF1

2F3

2F1

4F3

MCC 21
Vs: 415 V

MCC 21_IC

16F1

MCC 15
Vs: 415 V

MCC 15_IC

19F3

19F1

20F3

20F1

MAIN MV PNL SECT2 DG BUS


Vs: 415 V
22F3

22F1

23f3

23F1

24F3

24F1

25F3

25F1

27F3

27F1

28F3

28F1

MCC 18_IC
MCC 18
Vs: 415 V

MCC 17_IC
MCC 17
Vs: 415 V

MCC16_IC
MCC 16
Vs: 415 V

MCC19_IC
MCC 19
Vs: 415 V

MCC20_IC
MCC 20
Vs: 415 V

MCCXXX_IC
MCC XXX
Vs: 415 V

MCC22_IC
MCC 22
Vs: 415 V

MCC23_IC

REV. DATE

29F3

29F1

CAB:MCC24

MCC 14_IC

16F3

CAB:MCC23

MCC 14
Vs: 415 V

15F1

CAB:MCC22

MCC 8_IC

15F3

CAB:MCCXXX

MCC 8
Vs: 415 V

14F1

CAB:MCC20

MCC 4_IC

14F3

CAB:MCC19

MCC 4
Vs: 415 V

13F1

CAB:MCC16

MPDB_IC

13F3

CAB:MCC17

MPDB
Vs: 415 V

12F1

26F

CAB:MCC18

MLDB_IC

12F3

CAB:MCC15

MLDB
Vs: 415 V

11F1

CAB:MCC21

MCC 2_IC

11F3

CAB:MCC14

MCC 2
Vs: 415 V

10F1

CAB:MCC8

MCC 5_IC

10F3

CAB:MCC4

MCC 5
Vs: 415 V

9F1

CAB:MPDB

MCC 3_IC

9F3

CAB:MLDB

MCC 3
Vs: 415 V

4F1

CAB:MCC2

MCC 1_IC
MCC 1
Vs: 415 V

3F1

CAB:MCC5

CAB:MCC1

MCC13_IC

3F3

CAB:MCC3

CAB:MCC13
MCC13
Vs: 415 V

IF1

21F

MAIN MV PNL SECT1 DG BUS


Vs: 415 V

IF3

MAIN MV PNL SECT3 EB BUS


Vs: 415 V

MVP_IC2

MCC24_IC

MCC 23
Vs: 415 V

ECO#

MCC 24
Vs: 415 V

DESCRIPTION

DWN APP

TH IS DR A WI N G IS P RO P R IETA R Y I N FO R M AT IO N

Your Company Name


Address
Address
Phone and web site

DRA WN B Y/D ATE :

DWG No.:

EN G. APP./DA TE:
MFG . APP ./ DATE :

S CAL E:

PART No.:
DWG S IZ E :

REV.

Short Circuit Current Report

SHORT CIRCUIT CURRENTS WHEN 1010 kVA DG FEEDING.

GRID

TNEB
Vs: 33000 V

33kV OD PNL BD
50
51

DG1
Vs: 415 V
Ik" : 34640.29A

DG2
Vs: 415 V
Ik" : 34640.29A

GEN

DG 3
Vs: 415 V
Ik" : 34682.97A

DG2_IC

GEN
HVP_IC

50
51

33KV_3PNL_BD
Vs: 33000 V

DG3_IC
HVP_OG1

HVP_OG2

50
51

DG S205
Vs: 415 V
Ik" : 15662.58A

BD_DG S205_1

BD DG3

BD DG2

BD DG1
DG1_IC

DG PNL
Vs: 415 V
Ik" : 34775.29A

GEN

CAB:MAIN

GEN

DG PNL S205

50
51

DG PNL_OG

17F2

6F2

7F2

BD_TRF2

BD_TRF1

MAIN MV PNL SECT1 EB BUS


Vs: 415 V

MVP_IC1

MAIN MV PNL SECT2 EB BUS


Vs: 415 V

BD_DG S205_2

TRF2

CAB:TRF2

CAB:TRF1

BD DGPNL

TRF1

IF3

IF1

2F1

3F1

4F1

9F1

10F1

11F1

12F1

13F3

21F
15F1

16F3

20F3

20F1

22F3

22F1

23f3

23F1

24F3

24F1

25F3

25F1

27F3

27F1

28F3

28F1

29F3

29F1

CAB:MCC19

CAB:MCC20

CAB:MCCXXX

CAB:MCC22

CAB:MCC23

CAB:MCC24

MCC 15_IC

19F1

CAB:MCC16

MCC 15
Vs: 415 V

19F3

CAB:MCC17

MCC 21_IC
MCC 21
Vs: 415 V
Ik" : 11834.47A

16F1

26F

MAIN MV PNL SECT2 DG BUS


Vs: 415 V
Ik" : 15580.12A

CAB:MCC18

MCC 14 MCC 14_IC


Vs: 415 V
Ik" : 11834.47A

15F3

CAB:MCC15

MCC 8_IC

14F1

CAB:MCC21

MCC 8
Vs: 415 V

14F3

CAB:MCC14

MCC 4_IC
MCC 4
Vs: 415 V
Ik" : 11834.47A

13F1

CAB:MCC8

MPDB
MPDB_IC
Vs: 415 V
Ik" : 13591.75A

12F3

CAB:MCC4

MLDB_IC
MLDB
Vs: 415 V
Ik" : 13591.75A

11F3

CAB:MPDB

MCC 2_IC
MCC 2
Vs: 415 V
Ik" : 14992.52A

10F3

CAB:MLDB

MCC 5_IC
MCC 5
Vs: 415 V
Ik" : 14563.9A

9F3

CAB:MCC2

MCC 3
MCC 3_IC
Vs: 415 V
Ik" : 14234.63A

4F3

CAB:MCC5

MCC 1_IC
MCC 1
Vs: 415 V
Ik" : 14234.63A

3F3

CAB:MCC3

CAB:MCC1

CAB:MCC13
MCC13_IC
MCC13
Vs: 415 V
Ik" : 11834.47A

2F3

MAIN MV PNL SECT3 EB BUS


Vs: 415 V

MVP_IC2

MAIN MV PNL SECT1 DG BUS


Vs: 415 V
Ik" : 15576.43A

MCC 18_IC
MCC 18
Vs: 415 V
Ik" : 13591.75A

MCC 17_IC
MCC 17
Vs: 415 V
Ik" : 14234.63A

MCC16_ICMCC 16
Vs: 415 V
Ik" : 14904.8A

MCC19_ICMCC 19
Vs: 415 V
Ik" : 14245.13A

MCC20_ICMCC 20
Vs: 415 V
Ik" : 14245.13A

MCCXXX_IC
MCC XXX
Vs: 415 V
Ik" : 9482.41A

MCC22_ICMCC 22
Vs: 415 V
Ik" : 13604.02A

MCC23_IC
MCC 23
Vs: 415 V
Ik" : 13604.02A

MCC24_IC
MCC 24
Vs: 415 V
Ik" : 14934.04A

REV. DATE

ECO#

DESCRIPTION

DWN APP

TH IS DR A WI N G IS P RO P R IETA R Y I N FO R M AT IO N

Your Company Name


Address
Address
Phone and web site

DRA WN B Y/D ATE :

DWG No.:

EN G. APP./DA TE:
MFG . APP ./ DATE :

S CAL E:

PART No.:
DWG S IZ E :

REV.

Short Circuit Detailed Report 1 no 1010 kVA DG Set Feed


3P Fault - IEC60909 Method at the Following Times
Bus Description
Pre fault Instantan 1/2 cycle
voltage in
eus
sym
Volts
current
current
in A
in Amps
DG 3
DG PNL
DG S205
DG1
DG2
MAIN MV PNL SECT1 DG BUS
MAIN MV PNL SECT2 DG BUS
MCC 1
MCC 14
MCC 16
MCC 17
MCC 18
MCC 19
MCC 2
MCC 20
MCC 21
MCC 22
MCC 23
MCC 24
MCC 3
MCC 4
MCC 5
MCC XXX
MCC13
MLDB
MPDB

415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

88288
88523
39870
88180
88180
39651
39661
36235
25763
37941
36235
33240
36262
38165
36262
25763
33401
33401
38016
36235
25763
37074
16840
25763
33240
33240

34683
34775
15663
34640
34640
15576
15580
14235
11834
14905
14235
13592
14245
14993
14245
11834
13604
13604
14934
14235
11834
14564
9482
11834
13592
13592

1 cycle
sym
current
in Amps
29663
29730
13384
29632
29632
13321
13323
12342
10541
12832
12342
11868
12349
12896
12349
10541
11876
11876
12852
12342
10541
12583
8764
10541
11868
11868

3 cycle
sym
current
in Amps
25299
25348
11406
25277
25277
11361
11362
10651
9315
11007
10651
10304
10656
11054
10656
9315
10309
10309
11020
10651
9315
10827
8009
9315
10304
10304

5 cycle
sym
current
in Amps
22267
22304
10034
22250
22250
9999
10000
9450
8403
9725
9450
9180
9454
9762
9454
8403
9185
9185
9735
9450
8403
9586
7398
8403
9180
9180

8 cycle standard
sym
sym
current
current
in Amps in Amps
22267
22304
10034
22250
22250
9999
10000
9450
8403
9725
9450
9180
9454
9762
9454
8403
9185
9185
9735
9450
8403
9586
7398
8403
9180
9180

3127
3127
1404
3126
3126
1404
1404
1393
1372
1398
1393
1388
1393
1399
1393
1372
1388
1388
1398
1393
1372
1396
1364
1372
1388
1388

Short Circuit Detailed Report 1 no 1010 kVA DG Set Feed


LL Fault - IEC60909 Method at the Following Times
Bus Description
Pre fault Instantan 1/2 cycle
voltage in
eus
sym
Volts
current
current
in A
in Amps
DG 3
DG PNL
DG S205
DG1
DG2
MAIN MV PNL SECT1 DG BUS
MAIN MV PNL SECT2 DG BUS
MCC 1
MCC 14
MCC 16
MCC 17
MCC 18
MCC 19
MCC 2
MCC 20
MCC 21
MCC 22
MCC 23
MCC 24
MCC 3
MCC 4
MCC 5
MCC XXX
MCC13
MLDB
MPDB

415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

76460
76664
34529
76366
76366
34339
34347
31381
22312
32858
31381
28786
31404
33052
31404
22312
28926
28926
32923
31381
22312
32107
14584
22312
28786
28786

30036
30116
13564
29999
29999
13490
13493
12328
10249
12908
12328
11771
12337
12984
12337
10249
11781
11781
12933
12328
10249
12613
8212
10249
11771
11771

1 cycle
sym
current
in Amps
25689
25747
11590
25662
25662
11536
11538
10689
9129
11113
10689
10278
10695
11169
10695
9129
10285
10285
11130
10689
9129
10898
7590
9129
10278
10278

3 cycle
sym
current
in Amps
21910
21952
9878
21890
21890
9839
9840
9224
8067
9532
9224
8923
9228
9573
9228
8067
8928
8928
9544
9224
8067
9376
6936
8067
8923
8923

5 cycle
sym
current
in Amps
19284
19316
8689
19269
19269
8659
8660
8184
7277
8422
8184
7950
8187
8454
8187
7277
7954
7954
8431
8184
7277
8302
6407
7277
7950
7950

8 cycle standard
sym
sym
current
current
in Amps in Amps
19284
19316
8689
19269
19269
8659
8660
8184
7277
8422
8184
7950
8187
8454
8187
7277
7954
7954
8431
8184
7277
8302
6407
7277
7950
7950

4966
4968
2231
4965
4965
2229
2230
2199
2137
2214
2199
2183
2199
2216
2199
2137
2183
2183
2215
2199
2137
2206
2104
2137
2183
2183

Short Circuit Detailed Report 1 no 1010 kVA DG Set Feed


LG Fault - IEC60909 Method at the Following Times
Bus Description
Pre fault Instantan 1/2 cycle
voltage in
eus
sym
Volts
current
current
in A
in Amps
DG 3
DG PNL
DG S205
DG1
DG2
MAIN MV PNL SECT1 DG BUS
MAIN MV PNL SECT2 DG BUS
MCC 1
MCC 14
MCC 16
MCC 17
MCC 18
MCC 19
MCC 2
MCC 20
MCC 21
MCC 22
MCC 23
MCC 24
MCC 3
MCC 4
MCC 5
MCC XXX
MCC13
MLDB
MPDB

415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

87688
88177
39870
87455
87455
39415
39425
32485
20342
35978
32485
28289
32639
36423
32639
20342
28407
28407
36029
32485
20342
34393
15921
20342
28289
28289

34447
34639
15663
34355
34355
15484
15488
12935
9481
14134
12935
11892
12945
14308
12945
9481
11903
11903
14153
12935
9481
13511
8478
9481
11892
11892

1 cycle
sym
current
in Amps
29490
29630
13384
29423
29423
13253
13256
11358
8637
12259
11358
10558
11365
12389
11365
8637
10565
10565
12272
11358
8637
11793
7853
8637
10558
10558

3 cycle
sym
current
in Amps
25174
25275
11406
25125
25125
11311
11313
9914
7802
10584
9914
9307
9918
10680
9918
7802
9312
9312
10593
9914
7802
10239
7204
7802
9307
9307

5 cycle
sym
current
in Amps
22170
22248
10034
22132
22132
9961
9962
8868
7156
9395
8868
8384
8871
9470
8871
7156
8388
8388
9402
8868
7156
9125
6682
7156
8384
8384

8 cycle standard
sym
sym
current
current
in Amps in Amps
22170
22248
10034
22132
22132
9961
9962
8868
7156
9395
8868
8384
8871
9470
8871
7156
8388
8388
9402
8868
7156
9125
6682
7156
8384
8384

7930
7940
3570
7926
7926
3561
3561
3416
3149
3488
3416
3347
3416
3498
3416
3149
3347
3347
3488
3416
3149
3452
3098
3149
3347
3347

Short Circuit Detailed Report 1 no 1010 kVA DG Set Feed


LLG Fault - IEC60909 Method at the Following Times
Bus Description
Pre fault Instantan 1/2 cycle
voltage in
eus
sym
Volts
current
current
in A
in Amps
DG 3
DG PNL
DG S205
DG1
DG2
MAIN MV PNL SECT1 DG BUS
MAIN MV PNL SECT2 DG BUS
MCC 1
MCC 14
MCC 16
MCC 17
MCC 18
MCC 19
MCC 2
MCC 20
MCC 21
MCC 22
MCC 23
MCC 24
MCC 3
MCC 4
MCC 5
MCC XXX
MCC13
MLDB
MPDB

415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

88238
88504
39870
88116
88116
39635
39645
35442
24048
37557
35442
31801
35478
37831
35478
24048
31958
31958
37752
35442
24048
36478
17759
24048
31801
31801

34663
34768
15663
34615
34615
15570
15574
13923
11096
14754
13923
13138
13937
14861
13937
11096
13154
13154
14830
13923
11096
14330
9816
11096
13138
13138

1 cycle
sym
current
in Amps
29649
29724
13384
29614
29614
13316
13319
12118
9966
12725
12118
11534
12128
12804
12128
9966
11545
11545
12781
12118
9966
12417
9007
9966
11534
11534

3 cycle
sym
current
in Amps
25290
25344
11406
25265
25265
11358
11360
10492
8876
10932
10492
10063
10498
10989
10498
8876
10070
10070
10972
10492
8876
10709
8176
8876
10063
10063

5 cycle
sym
current
in Amps
22260
22301
10034
22241
22241
9996
9998
9329
8054
9669
9329
8996
9334
9713
9334
8054
9001
9001
9700
9329
8054
9498
7516
8054
8996
8996

8 cycle standard
sym
sym
current
current
in Amps in Amps
22260
22301
10034
22241
22241
9996
9998
9329
8054
9669
9329
8996
9334
9713
9334
8054
9001
9001
9700
9329
8054
9498
7516
8054
8996
8996

4498
4495
2016
4499
4499
2019
2019
2023
1965
2027
2023
2012
2023
2026
2023
1965
2013
2013
2034
2023
1965
2025
2080
1965
2012
2012

SHORT CIRCUIT CURRENTS WHEN 3 X 750 kVA DG SETS FEEDING

GRID

TNEB
Vs: 33000 V
Ik" : 13121.6A

33kV OD PNL BD
50
51

DG1
Vs: 415 V

GEN

GEN

DG 3
Vs: 415 V

DG2_IC

GEN
HVP_IC

50
51

33KV_3PNL_BD
Vs: 33000 V
Ik" : 13016.53A

DG3_IC
HVP_OG1

HVP_OG2

50
51

DG S205
Vs: 415 V

BD_DG S205_1

BD DG3

BD DG2

BD DG1
DG1_IC

DG PNL
Vs: 415 V

DG2
Vs: 415 V

CAB:MAIN

GEN

DG PNL S205

50
51

DG PNL_OG

17F2

6F2

BD_DG S205_2

BD_TRF2

MAIN MV PNL SECT2 EB BUS


Vs: 415 V
Ik" : 43941.42A

CAB:TRF2

7F2

TRF2

BD_TRF1

MAIN MV PNL SECT1 EB BUS


Vs: 415 V
Ik" : 43835.55A

CAB:TRF1

BD DGPNL

TRF1

MVP_IC1

IF1

2F1

3F1

4F1

9F1

10F1

11F1

12F1

13F1

14F1

15F1

16F1

19F1

20F3

20F1

MAIN MV PNL SECT2 DG BUS


Vs: 415 V
22F3

22F1

23f3

23F1

24F3

24F1

25F3

25F1

27F3

27F1

28F3

28F1

29F3

29F1

CAB:MCC17

CAB:MCC16

CAB:MCC19

CAB:MCC20

CAB:MCCXXX

CAB:MCC22

CAB:MCC23

CAB:MCC24

MCC 15
MCC 15_IC
Vs: 415 V
Ik" : 16677.93A

19F3

26F

CAB:MCC18

MCC 21_IC
MCC 21
Vs: 415 V
Ik" : 20776.14A

16F3

CAB:MCC15

MCC 14 MCC 14_IC


Vs: 415 V
Ik" : 20776.14A

15F3

CAB:MCC21

MCC 8_IC
MCC 8
Vs: 415 V
Ik" : 20776.14A

14F3

CAB:MCC14

MCC 4_IC
MCC 4
Vs: 415 V
Ik" : 20776.14A

13F3

CAB:MCC8

MPDB
MPDB_IC
Vs: 415 V
Ik" : 28867.47A

12F3

CAB:MCC4

MLDB_IC
MLDB
Vs: 415 V
Ik" : 28867.47A

11F3

CAB:MPDB

MCC 2_IC
MCC 2
Vs: 415 V
Ik" : 38586.86A

10F3

CAB:MLDB

MCC 5_IC
MCC 5
Vs: 415 V
Ik" : 35068.21A

9F3

CAB:MCC2

MCC 3
MCC 3_IC
Vs: 415 V
Ik" : 32732.8A

4F3

CAB:MCC5

MCC 1_IC
MCC 1
Vs: 415 V
Ik" : 32732.8A

3F3

CAB:MCC3

CAB:MCC1

CAB:MCC13
MCC13_IC
MCC13
Vs: 415 V
Ik" : 20696.84A

2F3

21F

MAIN MV PNL SECT1 DG BUS


Vs: 415 V

IF3

MAIN MV PNL SECT3 EB BUS


Vs: 415 V
Ik" : 43835.55A

MVP_IC2

MCC 18_IC
MCC 18
Vs: 415 V
Ik" : 28744.18A

MCC 17_IC
MCC 17
Vs: 415 V
Ik" : 32732.8A

MCC16_ICMCC 16
Vs: 415 V
Ik" : 37656.91A

MCC19_ICMCC 19
Vs: 415 V
Ik" : 32732.8A

MCC20_ICMCC 20
Vs: 415 V
Ik" : 32732.8A

MCCXXX_IC
MCC XXX
Vs: 415 V
Ik" : 12502.83A

MCC22_ICMCC 22
Vs: 415 V
Ik" : 28744.18A

MCC23_IC
MCC 23
Vs: 415 V
Ik" : 28744.18A

MCC24_IC
MCC 24
Vs: 415 V
Ik" : 38114.16A

REV. DATE

ECO#

DESCRIPTION

DWN APP

TH IS DR A WI N G IS P RO P R IETA R Y I N FO R M AT IO N

Your Company Name


Address
Address
Phone and web site

Electrical One-Line Diagram


for S hort Circuit Study and Protection Coordination
Short Circuit Currents for source fault 750 MV A
DRA WN B Y/D ATE :

DWG No.:

EN G. APP./DA TE:
MFG . APP ./ DATE :

S CAL E:

PART No.:
DWG S IZ E :

REV.

Short Circuit Detailed Report 3 nos 750 kVA DG Sets Feed


3P Fault - IEC60909 Method at the Following Times
Bus Description
Pre fault Instantan 1/2 cycle
voltage in
eus
sym
Volts
current
current
in A
in Amps
DG 3
DG PNL
DG1
DG2
MAIN MV PNL SECT1 DG BUS
MAIN MV PNL SECT2 DG BUS
MCC 1
MCC 14
MCC 16
MCC 17
MCC 18
MCC 19
MCC 2
MCC 20
MCC 21
MCC 22
MCC 23
MCC 24
MCC 3
MCC 4
MCC 5
MCC XXX
MCC13
MLDB
MPDB

415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

88288
88523
88180
88180
87937
87872
63245
36273
76586
63245
53364
62657
79990
62657
36273
52940
52940
79216
63245
36273
69654
20560
36273
53364
53364

34683
34775
34640
34640
34545
34519
28043
19174
31072
28043
25315
27971
31600
27971
19174
25242
25242
31278
28043
19174
29546
12278
19174
25315
25315

1 cycle
sym
current
in Amps
29663
29730
29632
29632
29563
29546
24771
17729
27035
24771
22678
24720
27421
24720
17729
22625
22625
27177
24771
17729
25900
11857
17729
22678
22678

3 cycle
sym
current
in Amps
25299
25348
25277
25277
25228
25216
21725
16236
23399
21725
20145
21691
23678
21691
16236
20107
20107
23496
21725
16236
22563
11362
16236
20145
20145

5 cycle
sym
current
in Amps
22267
22304
22250
22250
22212
22204
19494
15040
20803
19494
18241
19468
21017
19468
15040
18212
18212
20874
19494
15040
20150
10916
15040
18241
18241

8 cycle standard
sym
sym
current
current
in Amps in Amps
22267
22304
22250
22250
22212
22204
19494
15040
20803
19494
18241
19468
21017
19468
15040
18212
18212
20874
19494
15040
20150
10916
15040
18241
18241

3127
3127
3126
3126
3126
3126
3073
2968
3099
3073
3047
3073
3103
3073
2968
3047
3047
3100
3073
2968
3086
2905
2968
3047
3047

Short Circuit Detailed Report 3 nos 750 kVA DG Sets Feed


LL Fault - IEC60909 Method at the Following Times
Bus Description
Pre fault Instantan 1/2 cycle
voltage in
eus
sym
Volts
current
current
in A
in Amps
DG 3
DG PNL
DG1
DG2
MAIN MV PNL SECT1 DG BUS
MAIN MV PNL SECT2 DG BUS
MCC 1
MCC 14
MCC 16
MCC 17
MCC 18
MCC 19
MCC 2
MCC 20
MCC 21
MCC 22
MCC 23
MCC 24
MCC 3
MCC 4
MCC 5
MCC XXX
MCC13
MLDB
MPDB

415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

76460
76664
76366
76366
76156
76099
54772
31413
66325
54772
46215
54262
69273
54262
31413
45848
45848
68603
54772
31413
60322
17805
31413
46215
46215

30036
30116
29999
29999
29917
29895
24286
16605
26909
24286
21924
24223
27367
24223
16605
21860
21860
27088
24286
16605
25587
10633
16605
21924
21924

1 cycle
sym
current
in Amps
25689
25747
25662
25662
25603
25587
21452
15354
23413
21452
19640
21408
23747
21408
15354
19594
19594
23536
21452
15354
22430
10269
15354
19640
19640

3 cycle
sym
current
in Amps
21910
21952
21890
21890
21848
21838
18815
14060
20265
18815
17446
18785
20506
18785
14060
17413
17413
20348
18815
14060
19540
9840
14060
17446
17446

5 cycle
sym
current
in Amps
19284
19316
19269
19269
19236
19229
16882
13025
18016
16882
15797
16860
18201
16860
13025
15772
15772
18077
16882
13025
17451
9454
13025
15797
15797

8 cycle standard
sym
sym
current
current
in Amps in Amps
19284
19316
19269
19269
19236
19229
16882
13025
18016
16882
15797
16860
18201
16860
13025
15772
15772
18077
16882
13025
17451
9454
13025
15797
15797

4966
4968
4965
4965
4963
4963
4809
4505
4885
4809
4732
4808
4897
4808
4505
4732
4732
4888
4809
4505
4848
4256
4505
4732
4732

Short Circuit Detailed Report 3 nos 750 kVA DG Sets Feed


LG Fault - IEC60909 Method at the Following Times
Bus Description
Pre fault Instantan 1/2 cycle
voltage in
eus
sym
Volts
current
current
in A
in Amps
DG 3
DG PNL
DG1
DG2
MAIN MV PNL SECT1 DG BUS
MAIN MV PNL SECT2 DG BUS
MCC 1
MCC 14
MCC 16
MCC 17
MCC 18
MCC 19
MCC 2
MCC 20
MCC 21
MCC 22
MCC 23
MCC 24
MCC 3
MCC 4
MCC 5
MCC XXX
MCC13
MLDB
MPDB

415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

87688
88177
87455
87455
87010
86942
51654
26405
67058
51654
41704
51259
70851
51259
26405
41444
41444
68394
51654
26405
58624
19281
26405
41704
41704

34447
34639
34355
34355
34181
34154
23354
13698
27877
23354
19943
23300
28708
23300
13698
19897
19897
28000
23354
13698
25470
11118
13698
19943
19943

1 cycle
sym
current
in Amps
29490
29630
29423
29423
29297
29279
21054
12933
24597
21054
18278
21014
25228
21014
12933
18242
18242
24685
21054
12933
22729
10690
12933
18278
18278

3 cycle
sym
current
in Amps
25174
25275
25125
25125
25034
25022
18826
12115
21561
18826
16606
18797
22033
18797
12115
16579
16579
21622
18826
12115
20131
10206
12115
16606
16606

5 cycle
sym
current
in Amps
22170
22248
22132
22132
22062
22053
17136
11435
19343
17136
15299
17114
19717
17114
11435
15277
15277
19389
17136
11435
18196
9784
11435
15299
15299

8 cycle standard
sym
sym
current
current
in Amps in Amps
22170
22248
22132
22132
22062
22053
17136
11435
19343
17136
15299
17114
19717
17114
11435
15277
15277
19389
17136
11435
18196
9784
11435
15299
15299

7930
7940
7926
7926
7917
7916
7219
6065
7556
7219
6902
7217
7607
7217
6065
6900
6900
7560
7219
6065
7386
5756
6065
6902
6902

Short Circuit Detailed Report 3 nos 750 kVA DG Sets Feed


LG Fault - IEC60909 Method at the Following Times
Bus Description
Pre fault Instantan 1/2 cycle
voltage in
eus
sym
Volts
current
current
in A
in Amps
DG 3
DG PNL
DG1
DG2
MAIN MV PNL SECT1 DG BUS
MAIN MV PNL SECT2 DG BUS
MCC 1
MCC 14
MCC 16
MCC 17
MCC 18
MCC 19
MCC 2
MCC 20
MCC 21
MCC 22
MCC 23
MCC 24
MCC 3
MCC 4
MCC 5
MCC XXX
MCC13
MLDB
MPDB

415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

88238
88504
88116
88116
87857
87782
59649
33650
73786
59649
49531
59079
77364
59079
33650
49122
49122
76433
59649
33650
66341
22331
33650
49531
49531

34663
34768
34615
34615
34514
34484
26621
17709
30223
26621
23553
26533
30876
26533
17709
23469
23469
30610
26621
17709
28383
13214
17709
23553
23553

1 cycle
sym
current
in Amps
29649
29724
29614
29614
29542
29522
23691
16332
26422
23691
21287
23629
26901
23629
16332
21224
21224
26705
23691
16332
25038
12670
16332
21287
21287

3 cycle
sym
current
in Amps
25290
25344
25265
25265
25213
25200
20922
14927
22962
20922
19070
20878
23309
20878
14927
19024
19024
23168
20922
14927
21935
12049
14927
19070
19070

5 cycle
sym
current
in Amps
22260
22301
22241
22241
22201
22192
18865
13813
20471
18865
17377
18832
20738
18832
13813
17341
17341
20630
18865
13813
19666
11503
13813
17377
17377

8 cycle standard
sym
sym
current
current
in Amps in Amps
22260
22301
22241
22241
22201
22192
18865
13813
20471
18865
17377
18832
20738
18832
13813
17341
17341
20630
18865
13813
19666
11503
13813
17377
17377

4498
4495
4499
4499
4501
4501
4425
4215
4491
4425
4340
4421
4501
4421
4215
4336
4336
4525
4425
4215
4463
4439
4215
4340
4340

SHORT CIRCUIT CURRENTS WHEN GRID FEEDING AND SOURCE FAULT IS 1500 MVA SEC

GRID

TNEB
Vs: 33000 V
Ik" : 26243.19A

33kV OD PNL BD
50
51

DG1
Vs: 415 V

GEN

GEN

DG 3
Vs: 415 V

DG2_IC

GEN
HVP_IC

50
51

33KV_3PNL_BD
Vs: 33000 V
Ik" : 25825.24A

DG3_IC
HVP_OG1

HVP_OG2

50
51

DG S205
Vs: 415 V

BD_DG S205_1

BD DG3

BD DG2

BD DG1
DG1_IC

DG PNL
Vs: 415 V

DG2
Vs: 415 V

CAB:MAIN

GEN

DG PNL S205

50
51

DG PNL_OG

17F2

6F2

BD_DG S205_2

BD_TRF2

MAIN MV PNL SECT2 EB BUS


Vs: 415 V
Ik" : 44877.88A

CAB:TRF2

7F2

TRF2

BD_TRF1

MAIN MV PNL SECT1 EB BUS


Vs: 415 V
Ik" : 44765.75A

CAB:TRF1

BD DGPNL

TRF1

MVP_IC1

IF1

2F1

3F1

4F1

9F1

10F1

11F1

12F1

13F1

14F1

15F1

16F1

19F1

20F3

20F1

MAIN MV PNL SECT2 DG BUS


Vs: 415 V
22F3

22F1

23f3

23F1

24F3

24F1

25F3

25F1

27F3

27F1

28F3

28F1

29F3

29F1

CAB:MCC17

CAB:MCC16

CAB:MCC19

CAB:MCC20

CAB:MCCXXX

CAB:MCC22

CAB:MCC23

CAB:MCC24

MCC 15
MCC 15_IC
Vs: 415 V
Ik" : 16766.34A

19F3

26F

CAB:MCC18

MCC 21_IC
MCC 21
Vs: 415 V
Ik" : 20944.16A

16F3

CAB:MCC15

MCC 14 MCC 14_IC


Vs: 415 V
Ik" : 20944.16A

15F3

CAB:MCC21

MCC 8_IC
MCC 8
Vs: 415 V
Ik" : 20944.16A

14F3

CAB:MCC14

MCC 4_IC
MCC 4
Vs: 415 V
Ik" : 20944.16A

13F3

CAB:MCC8

MPDB
MPDB_IC
Vs: 415 V
Ik" : 29225.47A

12F3

CAB:MCC4

MLDB_IC
MLDB
Vs: 415 V
Ik" : 29225.47A

11F3

CAB:MPDB

MCC 2_IC
MCC 2
Vs: 415 V
Ik" : 39284.62A

10F3

CAB:MLDB

MCC 5_IC
MCC 5
Vs: 415 V
Ik" : 35627.55A

9F3

CAB:MCC2

MCC 3
MCC 3_IC
Vs: 415 V
Ik" : 33210.06A

4F3

CAB:MCC5

MCC 1_IC
MCC 1
Vs: 415 V
Ik" : 33210.06A

3F3

CAB:MCC3

CAB:MCC1

CAB:MCC13
MCC13_IC
MCC13
Vs: 415 V
Ik" : 20862.99A

2F3

21F

MAIN MV PNL SECT1 DG BUS


Vs: 415 V

IF3

MAIN MV PNL SECT3 EB BUS


Vs: 415 V
Ik" : 44765.75A

MVP_IC2

MCC 18_IC
MCC 18
Vs: 415 V
Ik" : 29097.73A

MCC 17_IC
MCC 17
Vs: 415 V
Ik" : 33210.06A

MCC16_ICMCC 16
Vs: 415 V
Ik" : 38315.42A

MCC19_ICMCC 19
Vs: 415 V
Ik" : 33210.06A

MCC20_ICMCC 20
Vs: 415 V
Ik" : 33210.06A

MCCXXX_IC
MCC XXX
Vs: 415 V
Ik" : 12541.46A

MCC22_ICMCC 22
Vs: 415 V
Ik" : 29097.73A

MCC23_IC
MCC 23
Vs: 415 V
Ik" : 29097.73A

MCC24_IC
MCC 24
Vs: 415 V
Ik" : 38795.23A

REV. DATE

ECO#

DESCRIPTION

DWN APP

TH IS DR A WI N G IS P RO P R IETA R Y I N FO R M AT IO N

Your Company Name


Address
Address
Phone and web site

Electrical One-Line Diagram


for S hort Circuit Study and Protection Coordination
Short Circuit Currents for source fault 1500 MVA
DRA WN B Y/D ATE :

DWG No.:

EN G. APP./DA TE:
MFG . APP ./ DATE :

S CAL E:

PART No.:
DWG S IZ E :

REV.

Short Circuit Detailed Report for source Fault 1500MVA Sec


3P Fault - IEC60909 Method at the Following Times
Bus Description
Pre fault Instantan 1/2 cycle
voltage in
eus
sym
Volts
current
current
in A
in Amps
TNEB
33KV_3PNL_BD
MAIN MV PNL SECT1 EB BUS
MAIN MV PNL SECT2 EB BUS
MAIN MV PNL SECT3 EB BUS
MCC 1
MCC 14
MCC 15
MCC 16
MCC 17
MCC 18
MCC 19
MCC 2
MCC 20
MCC 21
MCC 22
MCC 23
MCC 24
MCC 3
MCC 4
MCC 5
MCC 8
MCC XXX
MCC13
MLDB
MPDB

33000
33000
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

74227
73045
113266
114240
113266
66820
37597
28408
83137
66820
55834
66820
87251
66820
37597
55834
55834
86336
66820
37597
74100
37597
20874
37385
56309
56309

26243
25825
44766
44878
44766
33210
20944
16766
38315
33210
29098
33210
39285
33210
20944
29098
29098
38795
33210
20944
35628
20944
12541
20863
29225
29225

1 cycle
sym
current
in Amps
26243
25825
44766
44878
44766
33210
20944
16766
38315
33210
29098
33210
39285
33210
20944
29098
29098
38795
33210
20944
35628
20944
12541
20863
29225
29225

3 cycle
sym
current
in Amps
26243
25825
44766
44878
44766
33210
20944
16766
38315
33210
29098
33210
39285
33210
20944
29098
29098
38795
33210
20944
35628
20944
12541
20863
29225
29225

(GRID FEED)

5 cycle
sym
current
in Amps
26243
25825
44766
44878
44766
33210
20944
16766
38315
33210
29098
33210
39285
33210
20944
29098
29098
38795
33210
20944
35628
20944
12541
20863
29225
29225

8 cycle standard
sym
sym
current
current
in Amps in Amps
26243
25825
44766
44878
44766
33210
20944
16766
38315
33210
29098
33210
39285
33210
20944
29098
29098
38795
33210
20944
35628
20944
12541
20863
29225
29225

26243
25825
44766
44878
44766
33210
20944
16766
38315
33210
29098
33210
39285
33210
20944
29098
29098
38795
33210
20944
35628
20944
12541
20863
29225
29225

Short Circuit Detailed Report for source Fault 1500MVA Sec


LL Fault - IEC60909 Method at the Following Times
Bus Description
Pre fault Instantan 1/2 cycle
voltage in
eus
sym
Volts
current
current
in A
in Amps
TNEB
33KV_3PNL_BD
MAIN MV PNL SECT1 EB BUS
MAIN MV PNL SECT2 EB BUS
MAIN MV PNL SECT3 EB BUS
MCC 1
MCC 14
MCC 15
MCC 16
MCC 17
MCC 18
MCC 19
MCC 2
MCC 20
MCC 21
MCC 22
MCC 23
MCC 24
MCC 3
MCC 4
MCC 5
MCC 8
MCC XXX
MCC13
MLDB
MPDB

33000
33000
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

74227
72864
98326
99218
98326
57948
32586
24616
72124
57948
48410
57948
75699
57948
32586
48410
48410
74904
57948
32586
64272
32586
18085
32401
48822
48822

26243
25761
38879
38977
38879
28817
18158
14530
33260
28817
25241
28817
34104
28817
18158
25241
25241
33678
28817
18158
30920
18158
10866
18087
25352
25352

1 cycle
sym
current
in Amps
26243
25761
38879
38977
38879
28817
18158
14530
33260
28817
25241
28817
34104
28817
18158
25241
25241
33678
28817
18158
30920
18158
10866
18087
25352
25352

3 cycle
sym
current
in Amps
26243
25761
38879
38977
38879
28817
18158
14530
33260
28817
25241
28817
34104
28817
18158
25241
25241
33678
28817
18158
30920
18158
10866
18087
25352
25352

(GRID FEED)

5 cycle
sym
current
in Amps
26243
25761
38879
38977
38879
28817
18158
14530
33260
28817
25241
28817
34104
28817
18158
25241
25241
33678
28817
18158
30920
18158
10866
18087
25352
25352

8 cycle standard
sym
sym
current
current
in Amps in Amps
26243
25761
38879
38977
38879
28817
18158
14530
33260
28817
25241
28817
34104
28817
18158
25241
25241
33678
28817
18158
30920
18158
10866
18087
25352
25352

26243
25761
38879
38977
38879
28817
18158
14530
33260
28817
25241
28817
34104
28817
18158
25241
25241
33678
28817
18158
30920
18158
10866
18087
25352
25352

Short Circuit Detailed Report for source Fault 1500MVA Sec


LG Fault - IEC60909 Method at the Following Times
Bus Description
Pre fault Instantan 1/2 cycle
voltage in
eus
sym
Volts
current
current
in A
in Amps
TNEB
33KV_3PNL_BD
MAIN MV PNL SECT1 EB BUS
MAIN MV PNL SECT2 EB BUS
MAIN MV PNL SECT3 EB BUS
MCC 1
MCC 14
MCC 15
MCC 16
MCC 17
MCC 18
MCC 19
MCC 2
MCC 20
MCC 21
MCC 22
MCC 23
MCC 24
MCC 3
MCC 4
MCC 5
MCC 8
MCC XXX
MCC13
MLDB
MPDB

33000
33000
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

74227
72265
126822
129190
126822
57446
27939
24093
78252
57446
45370
57446
83546
57446
27939
45370
45370
80123
57446
27939
66259
27939
20073
27822
45683
45683

26243
25550
50604
50753
50604
28943
15225
13743
37005
28943
23661
28943
38661
28943
15225
23661
23661
37330
28943
15225
32515
15225
11821
15185
23746
23746

1 cycle
sym
current
in Amps
26243
25550
50604
50753
50604
28943
15225
13743
37005
28943
23661
28943
38661
28943
15225
23661
23661
37330
28943
15225
32515
15225
11821
15185
23746
23746

3 cycle
sym
current
in Amps
26243
25550
50604
50753
50604
28943
15225
13743
37005
28943
23661
28943
38661
28943
15225
23661
23661
37330
28943
15225
32515
15225
11821
15185
23746
23746

(GRID FEED)

5 cycle
sym
current
in Amps
26243
25550
50604
50753
50604
28943
15225
13743
37005
28943
23661
28943
38661
28943
15225
23661
23661
37330
28943
15225
32515
15225
11821
15185
23746
23746

8 cycle standard
sym
sym
current
current
in Amps in Amps
26243
25550
50604
50753
50604
28943
15225
13743
37005
28943
23661
28943
38661
28943
15225
23661
23661
37330
28943
15225
32515
15225
11821
15185
23746
23746

26243
25550
50604
50753
50604
28943
15225
13743
37005
28943
23661
28943
38661
28943
15225
23661
23661
37330
28943
15225
32515
15225
11821
15185
23746
23746

Short Circuit Detailed Report for source Fault 1500MVA Sec


LLG Fault - IEC60909 Method at the Following Times
Bus Description
Pre fault Instantan 1/2 cycle
voltage in
eus
sym
Volts
current
current
in A
in Amps
TNEB
33KV_3PNL_BD
MAIN MV PNL SECT1 EB BUS
MAIN MV PNL SECT2 EB BUS
MAIN MV PNL SECT3 EB BUS
MCC 1
MCC 14
MCC 15
MCC 16
MCC 17
MCC 18
MCC 19
MCC 2
MCC 20
MCC 21
MCC 22
MCC 23
MCC 24
MCC 3
MCC 4
MCC 5
MCC 8
MCC XXX
MCC13
MLDB
MPDB

33000
33000
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

76952
75639
122814
124501
122814
63894
35339
28858
82871
63894
52018
63894
87694
63894
35339
52018
52018
86214
63894
35339
72140
35339
23002
35167
52479
52479

27206
26742
48853
48909
48853
31918
19587
16890
38652
31918
27119
31918
40010
31918
19587
27119
27119
39392
31918
19587
34977
19587
13747
19526
27255
27255

1 cycle
sym
current
in Amps
27206
26742
48853
48909
48853
31918
19587
16890
38652
31918
27119
31918
40010
31918
19587
27119
27119
39392
31918
19587
34977
19587
13747
19526
27255
27255

3 cycle
sym
current
in Amps
27206
26742
48853
48909
48853
31918
19587
16890
38652
31918
27119
31918
40010
31918
19587
27119
27119
39392
31918
19587
34977
19587
13747
19526
27255
27255

(GRID FEED)

5 cycle
sym
current
in Amps
27206
26742
48853
48909
48853
31918
19587
16890
38652
31918
27119
31918
40010
31918
19587
27119
27119
39392
31918
19587
34977
19587
13747
19526
27255
27255

8 cycle standard
sym
sym
current
current
in Amps in Amps
27206
26742
48853
48909
48853
31918
19587
16890
38652
31918
27119
31918
40010
31918
19587
27119
27119
39392
31918
19587
34977
19587
13747
19526
27255
27255

27206
26742
48853
48909
48853
31918
19587
16890
38652
31918
27119
31918
40010
31918
19587
27119
27119
39392
31918
19587
34977
19587
13747
19526
27255
27255

SHORT CIRCUIT CURRENTS WHEN GRID FEEDING AND SOURCE FAULT IS 750 MVA SEC

GRID

TNEB
Vs: 33000 V
Ik" : 13121.6A

33kV OD PNL BD
50
51

DG1
Vs: 415 V

GEN

GEN

DG 3
Vs: 415 V

DG2_IC

GEN
HVP_IC

50
51

33KV_3PNL_BD
Vs: 33000 V
Ik" : 13016.53A

DG3_IC
HVP_OG1

HVP_OG2

50
51

DG S205
Vs: 415 V

BD_DG S205_1

BD DG3

BD DG2

BD DG1
DG1_IC

DG PNL
Vs: 415 V

DG2
Vs: 415 V

CAB:MAIN

GEN

DG PNL S205

50
51

DG PNL_OG

17F2

6F2

BD_DG S205_2

BD_TRF2

MAIN MV PNL SECT2 EB BUS


Vs: 415 V
Ik" : 43941.42A

CAB:TRF2

7F2

TRF2

BD_TRF1

MAIN MV PNL SECT1 EB BUS


Vs: 415 V
Ik" : 43835.55A

CAB:TRF1

BD DGPNL

TRF1

MVP_IC1

IF1

2F1

3F1

4F1

9F1

10F1

11F1

12F1

13F1

14F1

15F1

16F1

19F1

20F3

20F1

MAIN MV PNL SECT2 DG BUS


Vs: 415 V
22F3

22F1

23f3

23F1

24F3

24F1

25F3

25F1

27F3

27F1

28F3

28F1

29F3

29F1

CAB:MCC17

CAB:MCC16

CAB:MCC19

CAB:MCC20

CAB:MCCXXX

CAB:MCC22

CAB:MCC23

CAB:MCC24

MCC 15
MCC 15_IC
Vs: 415 V
Ik" : 16677.93A

19F3

26F

CAB:MCC18

MCC 21_IC
MCC 21
Vs: 415 V
Ik" : 20776.14A

16F3

CAB:MCC15

MCC 14 MCC 14_IC


Vs: 415 V
Ik" : 20776.14A

15F3

CAB:MCC21

MCC 8_IC
MCC 8
Vs: 415 V
Ik" : 20776.14A

14F3

CAB:MCC14

MCC 4_IC
MCC 4
Vs: 415 V
Ik" : 20776.14A

13F3

CAB:MCC8

MPDB
MPDB_IC
Vs: 415 V
Ik" : 28867.47A

12F3

CAB:MCC4

MLDB_IC
MLDB
Vs: 415 V
Ik" : 28867.47A

11F3

CAB:MPDB

MCC 2_IC
MCC 2
Vs: 415 V
Ik" : 38586.86A

10F3

CAB:MLDB

MCC 5_IC
MCC 5
Vs: 415 V
Ik" : 35068.21A

9F3

CAB:MCC2

MCC 3
MCC 3_IC
Vs: 415 V
Ik" : 32732.8A

4F3

CAB:MCC5

MCC 1_IC
MCC 1
Vs: 415 V
Ik" : 32732.8A

3F3

CAB:MCC3

CAB:MCC1

CAB:MCC13
MCC13_IC
MCC13
Vs: 415 V
Ik" : 20696.84A

2F3

21F

MAIN MV PNL SECT1 DG BUS


Vs: 415 V

IF3

MAIN MV PNL SECT3 EB BUS


Vs: 415 V
Ik" : 43835.55A

MVP_IC2

MCC 18_IC
MCC 18
Vs: 415 V
Ik" : 28744.18A

MCC 17_IC
MCC 17
Vs: 415 V
Ik" : 32732.8A

MCC16_ICMCC 16
Vs: 415 V
Ik" : 37656.91A

MCC19_ICMCC 19
Vs: 415 V
Ik" : 32732.8A

MCC20_ICMCC 20
Vs: 415 V
Ik" : 32732.8A

MCCXXX_IC
MCC XXX
Vs: 415 V
Ik" : 12502.83A

MCC22_ICMCC 22
Vs: 415 V
Ik" : 28744.18A

MCC23_IC
MCC 23
Vs: 415 V
Ik" : 28744.18A

MCC24_IC
MCC 24
Vs: 415 V
Ik" : 38114.16A

REV. DATE

ECO#

DESCRIPTION

DWN APP

TH IS DR A WI N G IS P RO P R IETA R Y I N FO R M AT IO N

Your Company Name


Address
Address
Phone and web site

Electrical One-Line Diagram


for S hort Circuit Study and Protection Coordination
Short Circuit Currents for source fault 750 MV A
DRA WN B Y/D ATE :

DWG No.:

EN G. APP./DA TE:
MFG . APP ./ DATE :

S CAL E:

PART No.:
DWG S IZ E :

REV.

Short Circuit Detailed Report for source Fault 750MVA Sec


3P Fault - IEC60909 Method at the Following Times
Bus Description
Pre fault
Instantan 1/2 cycle
voltage in
eus
sym
Volts
current current
in A
in Amps
TNEB
33KV_3PNL_BD
MAIN MV PNL SECT1 EB BUS
MAIN MV PNL SECT2 EB BUS
MAIN MV PNL SECT3 EB BUS
MCC 1
MCC 14
MCC 15
MCC 16
MCC 17
MCC 18
MCC 19
MCC 2
MCC 20
MCC 21
MCC 22
MCC 23
MCC 24
MCC 3
MCC 4
MCC 5
MCC 8
MCC XXX
MCC13
MLDB
MPDB

33000
33000
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

37113
36816
111285
111857
111285
66138
37381
28286
82077
66138
55357
66138
86082
66138
37381
55357
55357
85191
66138
37381
73260
37381
20815
37171
55824
55824

13122
13017
43836
43941
43836
32733
20776
16678
37657
32733
28744
32733
38587
32733
20776
28744
28744
38114
32733
20776
35068
20776
12503
20697
28867
28867

1 cycle
sym
current
in Amps
13122
13017
43836
43941
43836
32733
20776
16678
37657
32733
28744
32733
38587
32733
20776
28744
28744
38114
32733
20776
35068
20776
12503
20697
28867
28867

3 cycle
sym
current
in Amps
13122
13017
43836
43941
43836
32733
20776
16678
37657
32733
28744
32733
38587
32733
20776
28744
28744
38114
32733
20776
35068
20776
12503
20697
28867
28867

(GRID FEED)
5 cycle
sym
current
in Amps
13122
13017
43836
43941
43836
32733
20776
16678
37657
32733
28744
32733
38587
32733
20776
28744
28744
38114
32733
20776
35068
20776
12503
20697
28867
28867

8 cycle standard
sym
sym
current current
in Amps in Amps
13122
13017
43836
43941
43836
32733
20776
16678
37657
32733
28744
32733
38587
32733
20776
28744
28744
38114
32733
20776
35068
20776
12503
20697
28867
28867

13122
13017
43836
43941
43836
32733
20776
16678
37657
32733
28744
32733
38587
32733
20776
28744
28744
38114
32733
20776
35068
20776
12503
20697
28867
28867

Short Circuit Detailed Report for source Fault 750MVA Sec


(GRID FEED)
LL Fault - IEC60909 Method at the Following Times
Bus Description
Pre fault
Instantan 1/2 cycle 1 cycle
3 cycle
5 cycle
8 cycle standard
voltage in
eus
sym
sym
sym
sym
sym
sym
Volts
current current current current current current current
in A
in Amps in Amps in Amps in Amps in Amps in Amps
TNEB
33KV_3PNL_BD
MAIN MV PNL SECT1 EB BUS
MAIN MV PNL SECT2 EB BUS
MAIN MV PNL SECT3 EB BUS
MCC 1
MCC 14
MCC 15
MCC 16
MCC 17
MCC 18
MCC 19
MCC 2
MCC 20
MCC 21
MCC 22
MCC 23
MCC 24
MCC 3
MCC 4
MCC 5
MCC 8
MCC XXX
MCC13
MLDB
MPDB

33000
33000
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

37113
36771
96829
97415
96829
57434
32423
24525
71325
57434
48051
57434
74818
57434
32423
48051
48051
74041
57434
32423
63638
32423
18040
32240
48457
48457

13122
13000
38175
38268
38175
28457
18031
14464
32763
28457
24975
28457
33577
28457
18031
24975
24975
33164
28457
18031
30498
18031
10837
17962
25082
25082

13122
13000
38175
38268
38175
28457
18031
14464
32763
28457
24975
28457
33577
28457
18031
24975
24975
33164
28457
18031
30498
18031
10837
17962
25082
25082

13122
13000
38175
38268
38175
28457
18031
14464
32763
28457
24975
28457
33577
28457
18031
24975
24975
33164
28457
18031
30498
18031
10837
17962
25082
25082

13122
13000
38175
38268
38175
28457
18031
14464
32763
28457
24975
28457
33577
28457
18031
24975
24975
33164
28457
18031
30498
18031
10837
17962
25082
25082

13122
13000
38175
38268
38175
28457
18031
14464
32763
28457
24975
28457
33577
28457
18031
24975
24975
33164
28457
18031
30498
18031
10837
17962
25082
25082

13122
13000
38175
38268
38175
28457
18031
14464
32763
28457
24975
28457
33577
28457
18031
24975
24975
33164
28457
18031
30498
18031
10837
17962
25082
25082

Short Circuit Detailed Report for source Fault 750MVA Sec


(GRID FEED)
LG Fault - IEC60909 Method at the Following Times
Bus Description
Pre fault
Instantan 1/2 cycle 1 cycle
3 cycle
5 cycle
8 cycle standard
voltage in
eus
sym
sym
sym
sym
sym
sym
Volts
current current current current current current current
in A
in Amps in Amps in Amps in Amps in Amps in Amps
TNEB
33KV_3PNL_BD
MAIN MV PNL SECT1 EB BUS
MAIN MV PNL SECT2 EB BUS
MAIN MV PNL SECT3 EB BUS
MCC 1
MCC 14
MCC 15
MCC 16
MCC 17
MCC 18
MCC 19
MCC 2
MCC 20
MCC 21
MCC 22
MCC 23
MCC 24
MCC 3
MCC 4
MCC 5
MCC 8
MCC XXX
MCC13
MLDB
MPDB

33000
33000
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

37113
36618
125380
127425
125380
57153
27870
24041
77708
57153
45188
57153
82925
57153
27870
45188
45188
79552
57153
27870
65869
27870
20038
27753
45498
45498

13122
12946
49914
50057
49914
28734
15172
13703
36652
28734
23526
28734
38272
28734
15172
23526
23526
36968
28734
15172
32247
15172
11795
15132
23609
23609

13122
12946
49914
50057
49914
28734
15172
13703
36652
28734
23526
28734
38272
28734
15172
23526
23526
36968
28734
15172
32247
15172
11795
15132
23609
23609

13122
12946
49914
50057
49914
28734
15172
13703
36652
28734
23526
28734
38272
28734
15172
23526
23526
36968
28734
15172
32247
15172
11795
15132
23609
23609

13122
12946
49914
50057
49914
28734
15172
13703
36652
28734
23526
28734
38272
28734
15172
23526
23526
36968
28734
15172
32247
15172
11795
15132
23609
23609

13122
12946
49914
50057
49914
28734
15172
13703
36652
28734
23526
28734
38272
28734
15172
23526
23526
36968
28734
15172
32247
15172
11795
15132
23609
23609

13122
12946
49914
50057
49914
28734
15172
13703
36652
28734
23526
28734
38272
28734
15172
23526
23526
36968
28734
15172
32247
15172
11795
15132
23609
23609

Short Circuit Detailed Report for source Fault 750MVA Sec


(GRID FEED)
LLG Fault - IEC60909 Method at the Following Times
Bus Description
Pre fault
Instantan 1/2 cycle 1 cycle
3 cycle
5 cycle
8 cycle standard
voltage in
eus
sym
sym
sym
sym
sym
sym
Volts
current current current current current current current
in A
in Amps in Amps in Amps in Amps in Amps in Amps
TNEB
33KV_3PNL_BD
MAIN MV PNL SECT1 EB BUS
MAIN MV PNL SECT2 EB BUS
MAIN MV PNL SECT3 EB BUS
MCC 1
MCC 14
MCC 15
MCC 16
MCC 17
MCC 18
MCC 19
MCC 2
MCC 20
MCC 21
MCC 22
MCC 23
MCC 24
MCC 3
MCC 4
MCC 5
MCC 8
MCC XXX
MCC13
MLDB
MPDB

33000
33000
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415
415

38476
38147
121226
122546
121226
63437
35136
28734
82116
63437
51712
63437
86847
63437
35136
51712
51712
85382
63437
35136
71561
35136
22933
34966
52168
52168

13603
13487
48091
48141
48091
31586
19437
16801
38167
31586
26882
31586
39489
31586
19437
26882
26882
38882
31586
19437
34578
19437
13701
19377
27014
27014

13603
13487
48091
48141
48091
31586
19437
16801
38167
31586
26882
31586
39489
31586
19437
26882
26882
38882
31586
19437
34578
19437
13701
19377
27014
27014

13603
13487
48091
48141
48091
31586
19437
16801
38167
31586
26882
31586
39489
31586
19437
26882
26882
38882
31586
19437
34578
19437
13701
19377
27014
27014

13603
13487
48091
48141
48091
31586
19437
16801
38167
31586
26882
31586
39489
31586
19437
26882
26882
38882
31586
19437
34578
19437
13701
19377
27014
27014

13603
13487
48091
48141
48091
31586
19437
16801
38167
31586
26882
31586
39489
31586
19437
26882
26882
38882
31586
19437
34578
19437
13701
19377
27014
27014

13603
13487
48091
48141
48091
31586
19437
16801
38167
31586
26882
31586
39489
31586
19437
26882
26882
38882
31586
19437
34578
19437
13701
19377
27014
27014

SETTING CALCULATIONS
FOR TRANSFORMERS &
DG SETS

Setting Calculation for Transformers 2.5 MVA TR1 & TR2

433 V

33
4000A

50/1 A
2500 kVA
Transformer capacity

PT

Primary Voltage
Secondary Voltage
Transformer HV side CT details CTHV
Turns Ratio
Transformer LV side CT details CTLV
Turns Ratio
Percentage Impedance of Transformer
Fault Current at 33 kV Bus
Fault current at 0.415 kV Bus
Transformer HV side current as per name plate
Relay drop off Ratio
HV Pick up Current

Vp
Vs

Transformer HV side CT Secondary Pick up Current


IDMT setting at 33 kV side
Minimum Setting proposed on HV side Ip
Curve
Transformer LV side current as per name plate
Relay drop off Ratio
LV Pick up Current

Transformer LV side CT Secondary Pick up Current


Relay setting for over current

2500

33
0.433
50/1
CTRP 50
4000/1
CTRS 4000
Z
7.50%
13000
38175
43.74
0.95
1.1 x HV Currrent/ Drop off ratio
=1.1 x 43.74/0.95
50.65
Isfl
1.01
1
1
Extreme Inverse
3333.50
0.95
1.1 x LV Currrent/ Drop off ratio
=1.1 x 3333.43/0.95
3859.84
=3859.76/4000
0.964960526

Minimum Setting proposed on LV side Ip


Fault current at 0.415kV Bus as per report,for MINIMUM SOURCE Fault
HV side current due to fault at 0.415 kV bus
HV side CT Secondary current due to fault at 0.415kV bus
HV side Current fault at Transformer HV side
HV side CT current due to fault at Transformer HV side
Setting proposed on HV side relay I>>

1
38175.00
500.90
10.02
13000.00
260.00
10.02 x 1.2=12.02

Minimum Setting proposed on HV side relay I>>

12.00

Minimum Setting proposed on LV side relay I>>

kVA
kV
kV

Amps
Amps
Amps

Amps
Amps
Amps
Amps
Amps

Setting Calculation for Generator 1010 kVA

415 V
2000A
1010 kVA
Generatorr capacity

PT

Rated Voltage
Generator ACB rating
CT ratio
Turns Ratio
sub transient Reactance of Generator
Fault Current at 0.415 kV Bus
Rated current of Generator
Pick up Current

Vs

1010

0.415
2000
CTRP 2000/1
CTRS 2000
9.00%
15612
1405
1.1 x HV Currrent
=1.1 x 1405
1545.50
Isfl
1545/2000
0.7725
0.75

Generator ACB Setting


Setting for DG set ACB
Minimum Setting proposed

415 V
1200A
750 kVA

kVA
kV
Amps

Amps
Amps

Setting Calculation for Generator 1010 kVA

415 V
1200A
750 kVA
Generatorr capacity

PT

Rated Voltage
Generator ACB rating
CT ratio
Turns Ratio
sub transient Reactance of Generator
Fault Current at 0.415 kV Bus
Rated current of Generator
Pick up Current

Vs

Generator ACB Setting


Setting for DG set ACB
Minimum Setting proposed

750

0.415
1200
CTRP 1200/1
CTRS 1200
9.00%
11593
1043
1.1 x HV Currrent
=1.1 x 1043
1147.30
Isfl
1147/1200
0.955833333
0.95

kVA
kV
Amps

Amps
Amps

SETTING DETAILS FOR


33 kV PANELS

Setting Details for 33 kV Outdoor Panel


33kV Outdoor Panel
Relay type: CDG 61

SCOPE OF FUNCTION
Address

Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Enabled/Disabled

Setting
Enabled

Range

Setting

10..50000 A
1A/5A

120A

Range
ON/OFF
2.5,3.75,5,6.25,7.5,8.75,
10
0.05..1
s, oo

Setting
ON
6.25
1

Range
ON/OFF
0.5,1.0,1.5,2
0.1..1 s, oo

Setting
ON
1
0.2

Power System Data 1


Title Setting
CTs
Main Protection CT
CT rated primary
CT rated secondary
REF Protection CT
Phase over current Protection: 50/51
Setting name
Units
FCT 50/51
Ip pickup
Ip
Tp time dial
Tp
Ground over current Protection: 50N/51 N
Setting name
Units
FCT 50N / 51 N
51N pickup
Ip
51N time dial
Tp

5A

Setting Details for 33 kV 3PNL Board


1 Incomer
Relay type: 7SJ6001-4EA00-0DA0/BB

SCOPE OF FUNCTION
Address

Setting Title
Fault Records
Function 50/51
Function 50N/51N

Setting Range
Enabled/Disabled

Setting
Enabled

Range

Setting

10..50000 A
1A/5A

100A

Range
ON/OFF
0.1..35.00 A
0.00..60.00 s
0.1..35.00 A
0.00..60.00 s
0.1..4.00 A
0.05..15 s, oo
Normal Inverse ,Very
Inverse ,Extremely
Inverse ,Long Inverse

Setting
ON
8
0.3

Power System Data 1


Title Setting
Main Protection CT
CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units
FCT 50/51
50-2 Pickup
I>>
50-2 Delay
T I>>
50-1Pickup
I>
50-1Delay
T-I>
Ip pickup
Ip
Tp time dial
Tp
IEC Curve
CTs

Ground over current Protection: 50N/51 N


Setting name
Units
FCT 50N / 51 N
50N-2 Pickup
I>>
50N-2 Delay
T I>>
50N-1Pickup
I>
50N-1Delay
T-I>
51N pickup
Ip
51N time dial
Tp
IEC Curve

Range
ON/OFF
0.05..35.00 A
0.00..60.00 s
0.05..35.00 A
0.00..60.00 s
0.25..20.00
0.05..15 s, oo
Normal Inverse ,Very
Inverse ,Extremely
Inverse ,Long Inverse

8 8

1A

0.7
5
Inverse

Setting
ON
NA
NA
NA
NA
0.12
2
Inverse

Under Voltage Protection


SCOPE OF FUNCTION
Address

Setting Title
Fault Records
Function 27

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting
Main Protection CT
PT rated primary
PT rated secondary

Range

Setting

33000 V
110 V

33000

40-80% adjustable in
seven equal steps

80%

Setting Range
Enabled/Disabled

Setting
Enabled

Range

Setting

10..50000 A
1A/5A

50A

Range
ON/OFF
0.1..35.00 A
0.00..60.00 s
0.1..35.00 A
0.00..60.00 s
0.1..4.00 A
0.05..15 s, oo
Normal Inverse ,Very
Inverse ,Extremely
Inverse ,Long Inverse

Setting
ON
12
0.15

Other functions are disabled


Power System Data 1
PTs

Undervoltage Relay VAGM 22- 2 nos


27-Pickup
27<

12:00 AM

2 Outgoing to Transformers 1 and 2


Relay type: 7SJ6001-4EA00-0DA0/BB

SCOPE OF FUNCTION
Address

Setting Title
Fault Records
Function 50/51
Function 50N/51N

Power System Data 1


Title Setting
Main Protection CT
CT rated primary
CT rated secondary
Phase over current Protection: 50/51
Setting name
Units
FCT 50/51
50-2 Pickup
I>>
50-2 Delay
T I>>
50-1Pickup
I>
50-1Delay
T-I>
Ip pickup
Ip
Tp time dial
Tp
IEC Curve
CTs

Ground over current Protection: 50N/51 N


Setting name
Units
FCT 50N / 51 N
50N-2 Pickup
I>>
50N-2 Delay
T I>>
50N-1Pickup
I>
50N-1Delay
T-I>
51N pickup
Ip
51N time dial
Tp
IEC Curve

Range
ON/OFF
0.05..35.00 A
0.00..60.00 s
0.05..35.00 A
0.00..60.00 s
0.25..20.00
0.05..15 s, oo
Normal Inverse ,Very
Inverse ,Extremely
Inverse ,Long Inverse

8 8

1A

1.15
5
Normal
Inverse

Setting
ON
NA
NA
NA
NA
0.2
1.5
Normal
Inverse

SETTING DETAILS FOR


MV PANEL

Setting Details for MV Panel


Location of
Device
device
description and
release

Sevice ID

Breaker
Set
Current In

Phase Current Settings


OVERLOAD PROTECTION
SETTING RANGE IR=In
X

1F1

400 A MCCB

MCC 13

1F3

400 A MCCB

MCC 13

2F1

1250 A ACB

MCC 1

2F3

1600 A ACB

MCC 1

4F1

1000 A ACB

MCC 3

4F3

1000 A ACB

MCC 3

5F1

1000 A ACB

MCC 5

5F3

1000 A ACB

MCC 5

9F1

1250 A ACB

MCC 2

9F3

1250 A ACB

MCC 2

10F1

630A MCCB

MLDB

10F3

630A MCCB

MLDB

11F1

630A MCCB

MPDB

11F3

630A MCCB

MPDB

12F1

400 A MCCB

MCC 4

12F3

400 A MCCB

MCC 4

13F1

250 A MCCB

MCC 8

13F3

250 A MCCB

MCC 8

14F1

1000A ACB

MCC 14

14F3

1000A ACB

MCC 14

15F1

630A MCCB

MCC 21

15F3

630A MCCB

MCC 21

16F1

250 A MCCB

MCC 15

16F3

250 A MCCB

MCC 15

19F1

630A MCCB

MCC 18

19F3

630A MCCB

MCC 18

20F1

1000 A ACB

MCC 17

20F3

1000 A ACB

MCC 17

22F1

1600A ACB

MCC 16

22F3

1600A ACB

MCC 16

23F1

1600A ACB

MCC19

400 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.95400 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.951250 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0


1600 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
1000 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
1000 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
1000 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
1000 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
1250 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
1250 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
630 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.95630 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.95630 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.95630 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.95400 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.95400 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.95250 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.95250 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.951000 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
1000 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
630 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.95630 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.95250 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.95250 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.95630 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.95630 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.951000 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
1000 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
1600 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
1600 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
1600 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0

Long time
Pick up
Current
setting (I1)

0.7
0.7
0.65
0.5
0.8
0.8
0.95
0.95
0.95
0.95
0.85

Primary
Current

Setting range for time2

lag class tR at I t

time
lag
setting
in sec

280 -

280 -

812.5 2-3.5-5.5-8-10-14-1721-25-30 s
800 2-3.5-5.5-8-10-14-1721-25-30 s
800 2-3.5-5.5-8-10-14-1721-25-30 s
800 2-3.5-5.5-8-10-14-1721-25-30 s
950 2-3.5-5.5-8-10-14-1721-25-30 s
950 2-3.5-5.5-8-10-14-1721-25-30 s
1187.5 2-3.5-5.5-8-10-14-1721-25-30 s
1187.5 2-3.5-5.5-8-10-14-1721-25-30 s
535.5 -

0.85

535.5 -

0.85

535.5 -

0.85

535.5 -

0.7

280 -

0.7

280 -

0.95

237.5 -

0.95

237.5 -

0.4

0.4

400 2-3.5-5.5-8-10-14-1721-25-30 s
400 2-3.5-5.5-8-10-14-1721-25-30 s
252 -

0.4

252 -

0.7

175 -

0.7

175 -

0.85

535.5 -

0.85

535.5 -

0.4

0.8
0.8
0.95
0.95
0.5

Ground Current Settings

Short-time delayed short-circuit protection

800 2-3.5-5.5-8-10-14-1721-25-30 s
800 2-3.5-5.5-8-10-14-1721-25-30 s
1520 2-3.5-5.5-8-10-14-1721-25-30 s
1520 2-3.5-5.5-8-10-14-1721-25-30 s
800 2-3.5-5.5-8-10-14-1721-25-30 s

2
2
2
2
2
2
2
2

2
2

2
2
2
2
2

Setting range Isd


= In ...

1.5-2-2.5-3-4-5-6-7-810 xIR
1.5-2-2.5-3-4-5-6-7-810 xIR
1.25-1.5-2-2.5-3-4-6-810-12 x In
1.25-1.5-2-2.5-3-4-6-810-12 x In
1.25-1.5-2-2.5-3-4-6-810-12 x In
1.25-1.5-2-2.5-3-4-6-810-12 x In
1.25-1.5-2-2.5-3-4-6-810-12 x In
1.25-1.5-2-2.5-3-4-6-810-12 x In
1.25-1.5-2-2.5-3-4-6-810-12 x In
1.25-1.5-2-2.5-3-4-6-810-12 x In
1.5-2-2.5-3-4-5-6-7-810 xIR
1.5-2-2.5-3-4-5-6-7-810 xIR
1.5-2-2.5-3-4-5-6-7-810 xIR
1.5-2-2.5-3-4-5-6-7-810 xIR
1.5-2-2.5-3-4-5-6-7-810 xIR
1.5-2-2.5-3-4-5-6-7-810 xIR
1.5-2-2.5-3-4-5-6-7-810 xIR
1.5-2-2.5-3-4-5-6-7-810 xIR
1.25-1.5-2-2.5-3-4-6-810-12 x In
1.25-1.5-2-2.5-3-4-6-810-12 x In
1.5-2-2.5-3-4-5-6-7-810 xIR
1.5-2-2.5-3-4-5-6-7-810 xIR
1.5-2-2.5-3-4-5-6-7-810 xIR
1.5-2-2.5-3-4-5-6-7-810 xIR
1.5-2-2.5-3-4-5-6-7-810 xIR
1.5-2-2.5-3-4-5-6-7-810 xIR
1.25-1.5-2-2.5-3-4-6-810-12 x In
1.25-1.5-2-2.5-3-4-6-810-12 x In
1.25-1.5-2-2.5-3-4-6-810-12 x In
1.25-1.5-2-2.5-3-4-6-810-12 x In
1.25-1.5-2-2.5-3-4-6-810-12 x In

Short
time Pick
up
Current
Settint
(Isd)

Primary
Current

Setting range for


delay time tsd in ms

Instantaneous short-circuit protection


Short time
delay in
sec (Tsd) in
ms

Setting
range Ii =
In ...

Instantaneo
us Current
setting (I3)

1120 100-200-300-400

100 -

1.5

420 100-200-300-400

100 -

5000 100-200-300-400

1.25

2000 100-200-300-400

4000 100-200-300-400

1.25

1250 100-200-300-400

4000 100-200-300-400

1.25

1250 100-200-300-400

5000 100-200-300-400

1.25

1562.5 100-200-300-400

100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10100 -

Primary
Current

Ground-fault protection
Setting range
of the
operating
current Ig

Opera Primar
ting
y
curren Curren
t
t
settin
g Ig

0.6/1.0 x in
0.6/1.0 x in

Setting range of the


delay time tg in ms

Delay
time tg
in ms

0.6

240 100/300

100

0.6

240 100/300

100

7500 A-B-C-D-E

100-200-300-400-500

100

2.2

3520 A-B-C-D-E

100-200-300-400-500

100

6000 A-B-C-D-E

100-200-300-400-500

100

2.2

2200 A-B-C-D-E

100-200-300-400-500

100

6000 A-B-C-D-E

100-200-300-400-500

100

2.2

2200 A-B-C-D-E

100-200-300-400-500

100

7500 A-B-C-D-E

100-200-300-400-500

100

2.2

2750 A-B-C-D-E

100-200-300-400-500

100

2142 100-200-300-400

0.6/1.0 x in

0.6

378 100/300

100

1.5

803.25 100-200-300-400

100 -

0.6/1.0 x in

0.6

378 100/300

100

2142 100-200-300-400

100 -

0.6/1.0 x in

0.6

378 100/300

100

1.5

803.25 100-200-300-400

100 -

0.6/1.0 x in

0.6

378 100/300

100

1120 100-200-300-400

100 -

0.6/1.0 x in

0.6

240 100/300

100

1.5

420 100-200-300-400

100 -

0.6/1.0 x in

0.6

240 100/300

100

950 100-200-300-400

100 -

0.6/1.0 x in

0.6

150 100/300

100

1.5

356.25 100-200-300-400

100 -

0.6/1.0 x in

0.6

150 100/300

100

4000 100-200-300-400

1.25

1250 100-200-300-400

1008 100-200-300-400

1.5

100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10100 -

0.6/1.0 x in

0.6

378 100/300

100

378 100-200-300-400

100 -

0.6/1.0 x in

0.6

378 100/300

100

2.2

6000 A-B-C-D-E

2200 A-B-C-D-E

100-200-300-400-500

100

100-200-300-400-500

100

700 100-200-300-400

100 -

0.6/1.0 x in

0.6

150 100/300

100

1.5

262.5 100-200-300-400

100 -

0.6/1.0 x in

0.6

150 100/300

100

2142 100-200-300-400

100 -

0.6/1.0 x in

0.6

378 100/300

100

1.5

803.25 100-200-300-400

100 -

0.6

378 100/300

100

4000 100-200-300-400

1.25

1250 100-200-300-400

6400 100-200-300-400

1.25

2000 100-200-300-400

6400 100-200-300-400

100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10-

0.6/1.0 x in

6000 A-B-C-D-E

100-200-300-400-500

100

2.2

2200 A-B-C-D-E

100-200-300-400-500

100

9600 A-B-C-D-E

100-200-300-400-500

100

2.2

3520 A-B-C-D-E

100-200-300-400-500

100

9600 A-B-C-D-E

100-200-300-400-500

100

Setting Details for MV Panel


Location of
Device
device
description and
release

Sevice ID

Breaker
Set
Current In

Phase Current Settings


OVERLOAD PROTECTION
SETTING RANGE IR=In
X

23F3

1600A ACB

MCC19

24F1

1600A ACB

MCC 20

24F3

1600A ACB

MCC 20

25F1

250 A MCCB

MCC XXX

25F3

250 A MCCB

MCC XXX

27F1

630 A MCCB

MCC 22

27F3

630 A MCCB

MCC 22

28F1

630 A MCCB

MCC 23

28F3

630 A MCCB

MCC 23

29F1

1600A ACB

MCC 24

29F3

1600A ACB

MCC 24

26F

2500A ACB

INCOMER FROM 1010 kVA DGSET

21F1

4000A ACB

BUS COUPLER ON DG BUS

18F

4000A ACB

INCOMER FROM TRANSFORMER 2

17F

4000A ACB

BUS COUPLER ON EB BUS

8F1

4000A ACB

INCOMER FROM TRANSFORMER 1

6F2

4000A ACB

BUS COUPLER ON EB BUS

7F2

4000A ACB

INCOMER FROM DG SYNC PANEL

1600 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
1600 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
1600 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
250 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.95250 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.95630 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.95630 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.95630 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.95630 0.4-0.45-0.5-0.55-0.60.63-0.7-0.8-0.9-0.951600 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
1600 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
2500 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
4000 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
4000 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
4000 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
4000 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
4000 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0
4000 0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1.0

Long time
Pick up
Current
setting (I1)

0.5
0.5
0.5
0.6

Primary
Current

Setting range for time2

lag class tR at I t

time
lag
setting
in sec

800 2-3.5-5.5-8-10-14-1721-25-30 s
800 2-3.5-5.5-8-10-14-1721-25-30 s
800 2-3.5-5.5-8-10-14-1721-25-30 s
150 -

0.6

150 -

0.85

535.5 -

0.85

535.5 -

0.95

598.5 -

0.95

598.5 -

0.95

1520 2-3.5-5.5-8-10-14-1721-25-30 s
1520 2-3.5-5.5-8-10-14-1721-25-30 s
1500 2-3.5-5.5-8-10-14-1721-25-30 s
1600 2-3.5-5.5-8-10-14-1721-25-30 s
4000 2-3.5-5.5-8-10-14-1721-25-30 s
2800 2-3.5-5.5-8-10-14-1721-25-30 s
4000 2-3.5-5.5-8-10-14-1721-25-30 s
2800 2-3.5-5.5-8-10-14-1721-25-30 s
3400 2-3.5-5.5-8-10-14-1721-25-30 s

0.95
0.6
0.4
1
0.7
1
0.7
0.85

Ground Current Settings

Short-time delayed short-circuit protection

Setting range Isd


= In ...

2 1.25-1.5-2-2.5-3-4-6-810-12 x In
2 1.25-1.5-2-2.5-3-4-6-810-12 x In
2 1.25-1.5-2-2.5-3-4-6-810-12 x In
1.5-2-2.5-3-4-5-6-7-810 xIR
1.5-2-2.5-3-4-5-6-7-810 xIR
1.5-2-2.5-3-4-5-6-7-810 xIR
1.5-2-2.5-3-4-5-6-7-810 xIR
1.5-2-2.5-3-4-5-6-7-810 xIR
1.5-2-2.5-3-4-5-6-7-810 xIR
2 1.25-1.5-2-2.5-3-4-6-810-12 x In
2 1.25-1.5-2-2.5-3-4-6-810-12 x In
2 1.25-1.5-2-2.5-3-4-6-810-12 x In
2 1.25-1.5-2-2.5-3-4-6-810-12 x In
2 1.25-1.5-2-2.5-3-4-6-810-12 x In
2 1.25-1.5-2-2.5-3-4-6-810-12 x In
2 1.25-1.5-2-2.5-3-4-6-810-12 x In
2 1.25-1.5-2-2.5-3-4-6-810-12 x In
2 1.25-1.5-2-2.5-3-4-6-810-12 x In

Short
time Pick
up
Current
Settint
(Isd)

Primary
Current

Setting range for


delay time tsd in ms

1.25

2000 100-200-300-400

Instantaneous short-circuit protection


Short time
delay in
sec (Tsd) in
ms

Primary
Current

Ground-fault protection

Setting
range Ii =
In ...

Instantaneo
us Current
setting (I3)

Setting range
of the
operating
current Ig

Opera Primar
ting
y
curren Curren
t
t
settin
g Ig

Setting range of the


delay time tg in ms

Delay
time tg
in ms

2.2

3520 A-B-C-D-E

100-200-300-400-500

100

9600 A-B-C-D-E

100-200-300-400-500

100

2.2

3520 A-B-C-D-E

100-200-300-400-500

100

0.6/1.0 x in

0.6

150 100/300

100

6400 100-200-300-400

1.25

2000 100-200-300-400

600 100-200-300-400

100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10100 -

1.5

225 100-200-300-400

100 -

0.6/1.0 x in

0.6

150 100/300

100

2142 100-200-300-400

100 -

0.6/1.0 x in

0.6

378 100/300

100

1.5

803.25 100-200-300-400

100 -

0.6/1.0 x in

0.6

378 100/300

100

2394 100-200-300-400

100 -

0.6/1.0 x in

0.6

378 100/300

100

1.5

897.75 100-200-300-400

100 -

0.6/1.0 x in

0.6

378 100/300

100

6400 100-200-300-400

1.25

2000 100-200-300-400

1.5

3750 100-200-300-400

1.25

5000 100-200-300-400

1.5

6000 100-200-300-400

1.25

5000 100-200-300-400

1.5

6000 100-200-300-400

1.25

5000 100-200-300-400

8000 100-200-300-400

100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10100 1.5-2.2-34-6-8-10-

9600 A-B-C-D-E

100-200-300-400-500

100

2.2

3520 A-B-C-D-E

100-200-300-400-500

100

10000 A-B-C-D-E

100-200-300-400-500

100

16000 A-B-C-D-E

100-200-300-400-500

100

24000 A-B-C-D-E

100-200-300-400-500

200

16000 A-B-C-D-E

100-200-300-400-500

100

24000 A-B-C-D-E

100-200-300-400-500

200

16000 A-B-C-D-E

100-200-300-400-500

100

16000 A-B-C-D-E

100-200-300-400-500

100

1010 kVA DG Panel


Relay type: CAG 34
SCOPE OF FUNCTION
Address

Setting Title
Fault Records
Function 87

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting
Main Protection CT
CT rated primary
CT rated secondary
REF Protection CT

Range

Setting

10..50000 A
1A/5A

2000A
1A

Range
ON/OFF
10..40%
0.00..60.00 s

Setting
ON
10%
0

Setting Range
Enabled/Disabled

Setting
Enabled

Range

Setting

10..50000 A
1A/5A

2000A
5A

Range
ON/OFF
0.5,1.0,1.5,2
0.1..1 s, oo

Setting
ON
0.5
0.2

Power System Data 1


CTs

Differential current Protection: 87


Setting name
FCT 87
87 Pickup
87 Delay
Relay type: CDG 11
SCOPE OF FUNCTION
Address

Units
I
T

Setting Title
Fault Records
Function 51N

Other functions are disabled


Power System Data 1
Title Setting
Main Protection CT
CT rated primary
CT rated secondary
REF Protection CT
Ground over current Protection: 50N/51 N
Setting name
Units
FCT 50N / 51 N
51N pickup
Ip
51N time dial
Tp
CTs

750 kVA DG Synchronising Panel


Incomer from 750 kVA DG set
Relay type: CDV62
SCOPE OF FUNCTION
Address

3nos

Setting Title
Fault Records
Function 51

Setting Range
Enabled/Disabled

Setting
Enabled

Title Setting
CTs
Main Protection CT
CT rated primary
CT rated secondary
Over Current current Protection: 51
Setting name
Units
FCT 51
51 Pickup
I

Range

Setting

10..50000 A
1A/5A

1250A
1A

Tp time dial
Earth Fault Protection: 50N
Relay type: CAG 14
SCOPE OF FUNCTION
Address

Tp

0.05..1 s, oo

Setting Title
Fault Records
Function 50N

Setting Range
Enabled/Disabled

Setting
Enabled

Range

Setting

10..50000 A
1A/5A

1250A
1A

Range
ON/OFF
10-40%

Setting
ON
10%

Setting Range
Enabled/Disabled

Setting
Enabled

Range

Setting

10..50000 A
1A/5A

1250A
1A

Range
ON/OFF
5-40%
0-60 sec

Setting
ON
5%
5 sec

Power System Data 1

Range
Setting
ON/OFF
ON
0.5,0.625,0.75,0.875,1.0 1
,1.25,1.5,1.75 &2

Power System Data 1


Title Setting
Main Protection CT
CT rated primary
CT rated secondary
Ground over current Protection: 50N/51 N
Setting name
Units
FCT 50N
50N pickup
Ip
Reverse Power Protection: 32
Relay type:CCUM 31
SCOPE OF FUNCTION
Address
Setting Title
Fault Records
Function32
Power System Data 1
Title Setting
CTs
Main Protection CT
CT rated primary
CT rated secondary
Reverse Power Protection :32
Setting name
Units
FCT32
32 Pickup
P
32 delay (VTT timer)
CTs

TIME CURRENT
CHARACTERISTIC

CURVES

10000
1000

MVP_IC1
MVP BC
HVP_OG1

100

HVP_IC

TRF1 2500.0 KVA


Transformer

Time in Seconds

10

33kV OD PNL BD

.01

.1

Inrush

.5

415 Volt Phase


0 - Path :Grid to MV PNL Incomer

10

100
Current in Amperes X 100
Time-Current Characteristic Curves

1000

10000
12-08-2014
21:11:34
asianpaints_071214

10000
1000
100

MVP_IC1

MVP BC 17F2

10

HVP_OG1

Time in Seconds

33kV OD PNL BD

.01

.1

HVP_IC

.5

415 Volt Ground


0 - Path :Grid to MV PNL Incomer

10

100
Current in Amperes X 100
Time-Current Characteristic Curves

1000

10000
12-09-2014
17:54:54
ASIAN_071214