You are on page 1of 4

ASHRAE90.

1Table
Equipment
Type

SizeCategory

> 65,000Btu/h
and
<135,000Btu/h

SubCategory or
RatingCondition

MinimumEfficiencya

SplitSystemand
SinglePackage

10.3EER(before1/1/2010)
11.2EER(asof1/1/2010)
11.4IEER(asof1/1/2010)

SplitSystemand
SinglePackage

10.1EER(before1/1/2010)
11.0EER(asof1/1/2010)
11.2IEER(asof1/1/2010)

Electric
Resistance
(orNone)

SplitSystemand
SinglePackage

9.7EER(before1/1/2010)
11.0EER(asof1/1/2010)
11.2IEER(asof1/1/2010)

Allother

SplitSystemand
SinglePackage

9.5EER(before1/1/2010)
10.8EER(asof1/1/2010)
11.0IEER(asof1/1/2010)

Electric
Resistance
(orNone)

SplitSystemand
SinglePackage

9.5EER(before1/1/2010)
10.0EER(asof1/1/2010)
9.7IPLV(before1/1/2010)
10.1IEER(asof1/1/2010)

Allother

SplitSystemand
SinglePackage

9.3EER(before1/1/2010)
9.8EER(asof1/1/2010)
9.5 IPLV(before1/1/2010)
9.9IEER(asof1/1/2010)

Electric
Resistance
(orNone)

SplitSystemand
SinglePackage

9.2EER(before1/1/2010)
9.7EER(asof1/1/2010)
9.4 IPLV(before1/1/2010)
9.8IEER(asof1/1/2010)

Allother

SplitSystemand
SinglePackage

9.0EER(before1/1/2010)
9.5EER(asof1/1/2010)
9.2 IPLV(before1/1/2010)
9.6IEER(asof1/1/2010)

Heating
SectionType
Electric
Resistance
(orNone)
Allother

> 135,000Btu/h
and
<240,000Btu/h
Air
Conditioners,
AirCooled

> 240,000Btu/h
and
<760,000Btu/h

>760,000Btu/h

Reference:ASHRAEStandard90.1Table6.8.1.A2007

Test
Procedure

ARI
340/360

ElectricallyOperatedUnitaryAirConditionersand
CondensingUnitsMinimumEfficiencyRequirements
EquipmentType

SizeCategory

HeatingSection SubCategory or
Type
RatingCondition
All

<65,000Btu/h

> 65,000Btu/h
and
<135,000Btu/h

AirConditioners,
Water and
Evaporatively
Cooled

>135,000Btu/h
and
<240,000Btu/h

Minimum
Efficiencya

SplitSystemandSingle 12.1EER
12.3IEER(asof1/1/2010)
Package

Electric Resistance
(orNone)

SplitSystemandSingle 11.5EER
11.7IEER(asof1/1/2010)
Package

Allother

SplitSystemandSingle 11.3EER
11.5IEER(asof1/1/2010)
Package

Electric Resistance
(orNone)

SplitSystemandSingle 11.0EER
11.2IEER(asof1/1/2010)
Package

Allother

SplitSystemandSingle 10.8EER
11.0IEER(asof1/1/2010)
Package

Electric Resistance
(orNone)

SplitSystemandSingle 11.0EER
10.3IPLV(before
Package

Allother

SplitSystemandSingle 10.8EER
10.1 IPLV(before
Package

>240,000Btu/h

Reference:ASHRAEStandard90.1Table6.8.1.A2007

1/1/2010)
11.1IEER(asof1/1/2010)

1/1/2010)
10.9IEER(asof1/1/2010)

Test
Procedure
ARI210/240

ARI340/360

ElectricallyOperatedUnitaryandAppliedHeat
PumpsMinimumEfficiencyRequirements
EquipmentType

SizeCategory

> 65,000Btu/h
and
<135,000Btu/h

HeatingSection SubCategory or
Type
RatingCondition

Minimum
Efficiencya

Electric Resistance
(orNone)

SplitSystemandSingle 10.1EER(before1/1/2010)
11.0EER(asof1/1/2010)
Package

Allother

SplitSystemandSingle 9.9EER(before1/1/2010)
10.8EER(asof1/1/2010)
Package

Test
Procedure

11.2IEER(asof1/1/2010)

11.0IEER(asof1/1/2010)

AirCooled
(CoolingMode)

>135,000Btu/h
and
<240,000Btu/h

Electric Resistance
(orNone)

SplitSystemandSingle 9.3EER(before1/1/2010)
10.6EER(asof1/1/2010)
Package

Allother

SplitSystemandSingle 9.1EER(before1/1/2010)
10.4IEER(asof1/1/2010)
Package

10.7IEER(asof1/1/2010)

10.5IEER(asof1/1/2010)

Electric Resistance
(orNone)

SplitSystemandSingle 9.0EER(before1/1/2010)
9.5EER(asof1/1/2010)
Package

Allother

SplitSystemandSingle 8.8EER(before1/1/2010)
9.3EER(asof1/1/2010)
Package

>240,000Btu/h

Reference:ASHRAEStandard90.1Table6.8.1.B2007

9.2IPLV(before1/1/2010)
9.6IEER(asof1/1/2010)

9.0IPLV(before1/1/2010)
9.4IEER(asof1/1/2010)

ARI
340/360

ElectricallyOperatedUnitaryandAppliedHeat
PumpsMinimumEfficiencyRequirements
EquipmentType

AirCooled
(HeatingMode)

Minimum
Efficiencya

SizeCategory

HeatingSection
Type

SubCategory or
RatingCondition

> 65,000Btu/h
and
<135,000Btu/h

47 Fdb/43 Fwb
OutdoorAir

3.2COP(before1/1/2010)
3.3COP(asof1/1/2010)

17 Fdb/15 Fwb
OutdoorAir

2.2COP(before1/1/2010)
2.25COP(asof1/1/2010)

47 Fdb/43 Fwb
OutdoorAir

3.1COP(before1/1/2010)
3.2COP(asof1/1/2010)

17 Fdb/15 Fwb
OutdoorAir

2.0COP(before1/1/2010)
2.05COP(asof1/1/2010)

(CoolingCapacity)

>135,000Btu/h
(CoolingCapacity)

Integratedenergyefficiencyratio(IEER):asinglenumberfigureofmerit
expressingcoolingpartloadEERefficiencyforcommercialunitaryair
conditioningandheatpumpequipmentonthebasisofweightedoperation
atvariousloadcapacitiesfortheequipment.
Reference:ASHRAEStandard90.11999,Table6.2.1.C.
Reference

Title

ARI340/360
20047

PerformanceRatingofCommercialandIndustrial
UnitaryAirConditioningandHeatPump
Equipment

Reference:ASHRAEStandard90.1Table6.8.1.B2007

Test
Procedure

ARI
340/360