sheet 1 of 6

Project: West Coast Paper

Set capacity

3000

KW

System voltage

6600

Volts

CT primary

1250

Amps

Considering 10 %, -ve tolerance, voltage

5.94

KV

MVA rating

3.75

MVA

Sub-transient reactance, xd"

=
=
=

13
0.13
0.091

Fault contribution from Generator

=
=

MVA/xd" MVA
41.21
MVA

Fault current, KA

=
=

Fault MVA/(1.732*KV)
4.01
KA

Set capacity

5300

KW

System voltage

11000

Volts

CT primary

1250

Amps

Considering 10 %, -ve tolerance, voltage

9.9

MVA rating

6.625

MVA

Sub-transient reactance, xd"

=
=
=

22
0.22
0.154

Fault contribution from Generator

=
=

MVA/xd" MVA
43.02
MVA

Fault current, KA

=
=

Fault MVA/(1.732*KV)
2.51
KA

Considering 30 %, -ve tolerance, xd"

Considering 30 %, -ve tolerance, xd"

KV

259724434.xls

Doc No: TDC/FL/WCP


sheet 2 of 6

Project: West Coast Paper

Set capacity

3800

KW

System voltage

11000

Volts

CT primary

1250

Amps

Considering 10 %, -ve tolerance, voltage

9.9

KV

MVA rating

4.75

MVA

Sub-transient reactance, xd"

=
=
=

18
0.18
0.126

Fault contribution from Generator

=
=

MVA/xd" MVA
37.70
MVA

Fault current, KA

=
=

Fault MVA/(1.732*KV)
2.20
KA

Set capacity

4000

KW

System voltage

11000

Volts

CT primary

1250

Amps

Considering 10 %, -ve tolerance, voltage

9.9

MVA rating

Sub-transient reactance, xd"

=
=
=

18
0.18
0.126

Fault contribution from Generator

=
=

MVA/xd" MVA
39.68
MVA

Fault current, KA

=
=

Fault MVA/(1.732*KV)
2.31
KA

Considering 30 %, -ve tolerance, xd"

Considering 30 %, -ve tolerance, xd"

KV
MVA
%

259724434.xls

Doc No: TDC/FL/WCP


sheet 3 of 6

Project: West Coast Paper

Set capacity

4040

KW

System voltage

11000

Volts

CT primary

1250

Amps

Considering 10 %, -ve tolerance, voltage

9.9

KV

MVA rating

5.05

MVA

Sub-transient reactance, xd"

=
=
=

18
0.18
0.126

Fault contribution from Generator

=
=

MVA/xd" MVA
40.08
MVA

Fault current, KA

=
=

Fault MVA/(1.732*KV)
2.34
KA

=
=

MVA/(impedance) MVA
20
11000
Volts

CT primary

1250

Considering 10 %, -ve tolerance, voltage


Transformer Impedance

=
=
=
=

9.9
10.11
0.1011
0.09

Fault contribution from Transformer

=
=

MVA/xd" MVA
219.80
MVA

Fault current, KA

=
=

Fault MVA/(1.732*KV)
12.82
KA

Considering 30 %, -ve tolerance, xd"

Fault contribution from grid, through transformer :


Transformer MVA rating
System voltage

Considering 10 %, -ve tolerance, impedance

Amps
KV
%

259724434.xls

Doc No: TDC/FL/WCP


sheet 4 of 6

Project: West Coast Paper

Total fault KA, 10.20+2.51+2.2+2.31+2.34+12.82

26.18

Hence selected fault level is 40 KA

259724434.xls

Base Impedance = ((KV)sqr)/Base MVA


PU impedance = Actual impedance / Base impedance
Fault level = Base MVA / PU impedance

Fault MVA rating


Voltage rating
Fault current in KA

500 MVA
11000 Volts
Fault MVA/ (1.732*KV rating)
26.24396