Professional Documents
Culture Documents
Anlisis de Cargas
MIC
FAM
RGV
20-Feb-12
GAR
EIB
RGV
11-Nov-11
GAR
EIB
RGV
27-Sep-11
REV.
FECHA
DESCRIPCIN
GAR
EIB
LFP
ELABOR
REVIS
APROB
DOCUMENTO No.
VAS-5209124-11040-ID-ELE-MC-051-1
APROB
CLIENTE
VAS-5209124-11040-ID-ELE-MC-051-1
Anlisis de Cargas
Revisin: 1
Documento No.
TABLA DE CONTENIDO
GENERALIDADES .................................................................................................................................4
LIMITES OPERATIVOS .........................................................................................................................4
MODELAMIENTO DEL SISTEMA .........................................................................................................4
SOFTWARE UTILIZADO .......................................................................................................................5
CONDICIONES DE OPERACIN .........................................................................................................5
VAS-5209124-11040-ID-ELE-MC-051-R1.doc.
1 de 7
VAS-5209124-11040-ID-ELE-MC-051-1
Anlisis de Cargas
Revisin: 1
1.0
Documento No.
OBJETIVO
Para el desarrollo del plan estratgico de evacuacin de crudos de la VIT, es necesario desarrollar la
ingeniera detallada para la construccin de nuevas facilidades de rebombeo dentro de la actual
estacin de Vasconia, ubicada en el departamento de Boyac, Magdalena medio a 17 km del
municipio de Puerto Boyac, sobre la margen derecha del rio magdalena (estacin de origen) y Casa
Bombas 8 del GRB (estacin de destino). Esta Ingeniera se hace con el fin de aumentar la capacidad
de bombeo a aproximadamente a 270 KBPD desde la estacin Vasconia hasta el complejo GRB
(Casa Bombas 8).
2.0
ALCANCE
El alcance del presente documento es realizar el anlisis de flujo de cargas del sistema elctrico
propuesto para la estacin Vasconia, como parte del proyecto Ingeniera detallada para el incremento
de capacidad a +220 KBPD en el oleoducto VAS-CIB, en las estaciones Vasconia y Casa Bombas 8
en el GRB.
3.0
CONDICIONES AMBIENTALES
Las condiciones que se presentan en las estaciones se muestran en la siguiente tabla:
Parmetro
Vasconia
139
14.24
40
29
99
78%
2078
100
Intermedia
DOCUMENTOS DE REFERENCIA
Los documentos utilizados para el desarrollo del presente anlisis son los siguientes:
1.
2.
3.
4.
5.
5.0
VAS-5209124-11040-ID-ELE-CD-001
VAS-5209124-11040-ID-ELE-PL-051
VAS-5209124-11040-ID-ELE-LI-051
VAS-5209124-11040-ID-ELE-MC-062
VAS-5209124-11040-ID-ELE-MC-063
NORMAS APLICABLES
IEEE-141
Industrial Plants (Red Book).
VAS-5209124-11040-ID-ELE-MC-051-R1.doc.
2 de 7
VAS-5209124-11040-ID-ELE-MC-051-1
Anlisis de Cargas
Revisin: 1
Documento No.
IEEE 399
Recommended Practice for Industrial and Commercial Power
Systems Analysis, IEEE brown Book.
6.0
6.2
VAS-5209124-11040-ID-ELE-MC-051-R1.doc.
3 de 7
VAS-5209124-11040-ID-ELE-MC-051-1
Anlisis de Cargas
Revisin: 1
Documento No.
(principal y respaldo) para alimentar los servicios auxiliares; El sistema actual de media tensin
de Vasconia II se alimenta de un transformador 110/6.6 kV con capacidad de 13 MVA ONAN, y
el sistema de 6.3 kV esta conformado por tres bombas principales de 2540 HP (arranque por
autotransformador), dos bombas principales de 3000 HP (arrancador suave) y dos
transformadores 6.3/0.480 kV con capacidad de 2.5 MVA (principal y respaldo), para alimentar
los servicios auxiliares; Tanto Vasconia I y Vasconia II comparten un transformador de 10 MVA
ONAN, 110/6.6 kV como respaldo.
Los diseos propuestos consideran el cambio de los tres transformadores de 10 MVA y 13 MVA
110kV que alimentan las subestaciones Vasconia I y Vasconia II por tres transformadores de
20/26 MVA 110kV, adems de incluir un nuevo Switchgear de 6.3 kV que alimentar los
transformadores de 6.3/0.48 kV existentes en las subestaciones de Vasconia I y Vasconia II.
7.0
METODOLOGA
7.1
GENERALIDADES
LIMITES OPERATIVOS
Para evaluar la cargabilidad y las tensiones del sistema, se consideran los siguientes lmites
operativos:
Carga mxima en transformadores, cables, generadores, barras: 100% de la capacidad nominal
Voltaje mnimo en buses y barras: 95% del voltaje nominal
Voltaje mximo en buses y barras: 105% del voltaje nominal
Sobreexcitacin mxima en Generadores y fuentes: 100% de Qmax.
7.3
El modelamiento del sistema elctrico de la estacin Vasconia fue elaborado de acuerdo con los
siguientes documentos:
VAS-5209124-11040-ID-ELE-PL-051 1/2/3 Diagramas Unifilares Detallados de Alta, Media y
Baja Tensin.
VOD-VOD-195-EL-PLN-010 REV B
VAS-5209124-11040-ID-ELE-PL-063
VAS-5209124-11040-ID-ELE-MC-051-R1.doc.
4 de 7
VAS-5209124-11040-ID-ELE-MC-051-1
Anlisis de Cargas
Revisin: 1
7.4
Documento No.
SOFTWARE UTILIZADO
El software utilizado en la ejecucin de los clculos es el Electrical Transient Analysis Program
(ETAP), versin 7.5.
7.5
CONDICIONES DE OPERACIN
Corto circuito
MVA
X/R
I cc (kA)
Trifsico
512
3,884
2.69
Monofsico
461
7,675
2,42
En operacin normal, las cadas de tensin permisibles en los alimentadores (en % del
voltaje nominal de los sistemas) se definieron de acuerdo con el documento de bases y
criterios de diseo documento de referencia No. 1:
o
o
o
o
o
o
o
1.5%
1.5%
3.0%
5.0%
2.0%
15.0%
20.0%
VAS-5209124-11040-ID-ELE-MC-051-R1.doc.
5 de 7
VAS-5209124-11040-ID-ELE-MC-051-1
Anlisis de Cargas
Revisin: 1
8.0
Documento No.
ESCENARIOS DE ESTUDIO
Para el anlisis de sistema elctrico propuesto se consideraron los siguientes escenarios:
Escenario 1: Subestacin Vasconia alimentada por la lnea Cocorna-Puerto Boyaca-Vasconia,
voltaje en las barras 110 kV de la subestacin Cocorna igual al 88% del valor
nominal, carga mxima en Vasconia
Escenario 2: Subestacin Vasconia alimentada por la lnea Cocorna-Teca-Vasconia, voltaje
en las barras 110 kV de la subestacin Cocorna igual al 88% del valor nominal,
carga mxima en Vasconia.
Escenario 3: Subestacin Vasconia alimentada por la lnea Cocorna-Puerto Boyaca-Vasconia,
voltaje en las barras 110 kV de la subestacin Cocorna igual al 100% del valor
nominal, carga mxima en Vasconia
Escenario 4: Subestacin Vasconia alimentada por la lnea Cocorna-Teca-Vasconia, voltaje
en las barras 110 kV de la subestacin Cocorna igual al 100% del valor nominal,
carga mxima en Vasconia.
Escenario 5: Subestacin Vasconia alimentada por la lnea Cocorna-Puerto Boyaca-Vasconia,
voltaje en las barras 110 kV de la subestacin Cocorna igual al 110% del valor
nominal, carga mnima en Vasconia
Escenario 6: Subestacin Vasconia alimentada por la lnea Cocorna-Teca-Vasconia, voltaje
en las barras 110 kV de la subestacin Cocorna igual al 110% del valor nominal,
carga mnima en Vasconia.
9.0
10.0 CONCLUSIONES
1.
Para los escenarios 1 y 2, en los cuales el voltaje en las subestacin Cocorna alcanza valores
del 88% del voltaje nominal, el voltaje en la subestacin Vasconia disminuye a valores entre cercanos
al 80 y 85%, lo cual genera que los cambiadores de tomas de los transformadores de 110/6.6 kV se
ubiquen en el punto mnimo (-18.75%) para poder mantener el voltaje en las barras de 6.3 kV
cercanos al 100% del valor nominal, valores de voltaje inferiores al 90% o mayores al 110% del voltaje
nominal no deben presentarse como lo indica la CREG en su resolucin 70-1998.
2.
Para los escenarios 5 y 6, en los cuales el voltaje en las subestacin Cocorna alcanza valores
del 110% del voltaje nominal, el voltaje en la subestacin Vasconia se incrementa a valores entre
106% y 108%, generando que los cambiadores de tomas de los transformadores de 110/6.6 kV se
ubiquen en el punto mximo (6.25%) para poder reducir el voltaje en las barras de 6.3 kV los cuales
alcanzaron valores mayores al 105% del valor nominal, generando riesgos de salida del sistema por
sobretensin.
VAS-5209124-11040-ID-ELE-MC-051-R1.doc.
6 de 7
VAS-5209124-11040-ID-ELE-MC-051-1
Anlisis de Cargas
Revisin: 1
Documento No.
3.
El uso de cambiadores de tomas en los transformadores de 110/6.6 kV, permite hacer un
adecuado control de los niveles de voltaje en las subestaciones de Vasconia I y Vasconia II,
permitiendo matener los cambiadores de tomas de los transformadores de 6.3/0.48 kV en la posicin
0%.
4.
Los resultados obtenidos en el flujo de carga para los escenarios 1, 2, 3 y 4, reflejan que los
niveles de tensin en los barrajes o nodos de 6.3 kV, y 480 V, se encuentran dentro de los lmites de
operacin permitidos (95% - 105%), pero el escenario de baja carga en la subestacin Vasconia y
mximo voltaje en la subestacin Cocorna sobrepasa los lmites de operacin permitidos (>105%).
5.
En cuanto a cargabilidad de los elementos, se puede observar que los alimentadores y los
transformadores no presentan niveles de carga superiores al 100%, a excepcin del transformador
TR-4 (6.3/0.48 1.6 MVA), el cual presenta una sobrecarga cercana al 7%, lo anterior debido a que
todas las cargas se consideraron operativas al 90% de su potencia nominal, lo que nos permite asumir
que el transformador operar cercano a su potencia nominal y sin sobrecarga permanente.
VAS-5209124-11040-ID-ELE-MC-051-R1.doc.
7 de 7
VAS-5209124-11040-ID-ELE-MC-051-1
Anlisis de Cargas
Revisin: 1
Documento No.
VAS-5209124-11040-ID-ELE-MC-051-R1.doc.
1 de 1
Cocorna - EPM
AL
Jazmn - MSB
Palagua - ECP
6%
79 ,8
110 kV
-3,4
0 de
g
23 A
86,7%
2%
79,9
110 kV
-3,3
6 de
g
4,4 A
90,0%
0,95 MVA
AL
AL
6 km
397.5-26
0,1318+j0,4842 ohms/1km
AL
TECA
0,1 %Vd
%
86,3
-0,9
95,4 A
6 de
g
88,0%
-1,5% TapP
Trafo EBSA
30/15/15 MVA
110/34,5/13,2 kV
10/10/10 %Z
149,8 A 391,5 A
90,0%
90,0%
-3 ,4
149,8 A
8 de
g
90,0%
PB-34,5
10,5 MVA
6 km
397.5-26
0,1318+j0,4842 ohms/1km
deg
0,26974+j0,54136 ohms/1km
6 km
Penguin
383,5 A
90,0%
AL
,25%
85
13,2 kV-3
,48
%
87,9
-0,0
7
Trafo Teca
15 MVA
8,5
110/13,8
%Z
kV
B-P.BOYACA 2
391,5 A
90,0%
110 kV
48,1 A
87,6%
de g
Lump1
10 MVA
PB-13,2
10,5 MVA
T - L. PTO Boyaca
110 kV
0,0 %Vd
0,1 %Vd
6,15 km
300-30
0,2092+j0,5276 ohms/1km
0,1318+j0,4842 ohms/1km
4 km
397.5-26
1,7 %Vd
0,26974+j0,54395 ohms/1km
22,1 km
Penguin
B-P.BOYACA 1
34,5 kV
5%
85,2
6,4 %Vd
Palagua
88%
47,8 A0,00
deg
88,2%
312,1 A
89,0%
AL
Jazmn
5,479 MVA
110 kV
454,9 A
88,1%
110 kV
407,2 A
88,0%
3%
79,9
T - L. Teca
Ocensa B2
107,5 A
88,4%
Ocensa B1
3%
206,4 A 79,9
91,3% -3
110 kV
-3,3
5
,35
deg
AMPLIACIN OCENSA
deg
T - L. Teca
T - L. PTO Boyaca
10 m
36-1/C 750
VAS-PALAGUA
3%
79 ,9
4,1 A
97,5%
110 kV
0,0 %Vd
VAS-TECA
3%
79,9
-3,3
5 de
g
112,4 A
90,9%
90 A
91,5%
110 kV
-3 ,3
5 de
g
SW70
0 A
SW72
0 A
10 m
36-1/C 750
VAS-JAZMIN-A
110 kV
22,5 A
88,6%
116,4 A
91,2%
3%
79 ,9
VAS-PTO BOYACA
-3 ,3
5 de
g
90 A
91,5%
10 m
36-1/C 750
10 m
36-1/C 750
90 A
91,5%
0,0 %Vd
3%
79 ,9
-3,3
5 de
g
110 kV
SW75
0 A
0,0 %Vd
3%
79 ,9
CT16
VAS-T1
110 kV
2,6 A -3 ,35
de g
-69,2%
0,0%
CT18
CT22
CT24
3%
79,9
SW80
0 A
3%
79,9
Ocensa B2
-3 ,3
107,5 A
5 de
g 88,4%
107,5 A
88,4%
110 kV
SW88
0 A
SW86
0 A
-3 ,3
5 de
g
110 kV
SW84
0 A
3%
79,9
2,6 A
-69,2%
VAS-T3
-3,3
89,1 A
5 de
g
90,4%
Cuarto Elctrico Vasconia
100 m
3-1/C 500
0,0 %Vd
SW76
0 A
Ocensa B1
3%
79,9
VAS-T2110 kV
-3,3
5 de
g
90 A
91,5%
VAS-JAZMIN-B
110 kV
0,0 %Vd
3%
79,9
110 kV
CCM 703
-3
90,9
,35 A
92,5%de g
100 m
3-1/C 500
0,0 %Vd
SW79
0 A
100 m
3-1/C 500
0,0 %Vd
SW83
0 A
T2
20 MVA
110/6,6 kV
9,5 %Z
T3
20 MVA
110/6,6 kV
9,5 %Z
NUEVO SW MT
THCMT-0202 A
6,3 kV
3150 A
31,5 kA
THCMT-0202 B
6,3 kV
3150 A
31,5 kA
04 %
100,
1206,8 A
92,8%
692 A
92,7%
514,7 A
93,0%
THCMT-0202 C
6,3 kV
3150 A
31,5 kA
,98%
-399
,35
deg
0,0%
33%
10 0,
-6,9
8 de
g
1230,6 A
94,8%
604,1 A
94,4%
-6 ,8
3 de
g
626,6 A
95,1%
20 m
18-1/C 500
0,0 %Vd
20 m
18-1/C 500
0,0 %Vd
X7
0,3 %Vd
0,05 ohms
X3
Barra-A
6,3 kV
1200 A
31,5 kA
692 A
92,7%
338,7 A
92,7%
176,7 A
92,7%
0,3 %Vd
0,05 ohms
130 m
18-1/C 500
0,1 %Vd
130 m
18-1/C 500
0,1 %Vd
Barra-B
6,3 kV
1200 A
31,5 kA
,96%
99
-6,8
7 de
g
176,7 A
92,7%
150 m
18-1/C 500
0,1 %Vd
CT14
150 m
18-1/C 500
0,1 %Vd
514,7 A
93,0%
176,7 A
92,7%
161,3 A
93,6%
-5% TapP
TR-3
1,6 MVA
5,9 %Z
6,3/0,48 kV
200,4 A
93,0%
0,2 %Vd
BPC6430
2500 HP
0,2 %Vd
BPC6420
2500 HP
0,2 %Vd
BPC6440
2500 HP
0,2 %Vd
199,2 A
96,8%
Vasconia III
4%
99,9
626,6 A
95,3%
205,3 A
93,9%
199,2 A
96,8%
CT12
Relay10
Relay3
Relay11
27,5 A
A
207,8
0,0%
92,8%
30 m
1-3/C 350
0,0 %Vd
Relay12
199,1 A
96,8%
CT9
206,5 A
92,6%
CAP2
300 kvar
27,5 A
A
207,8
0,0%
92,8%
CAP4
300 kvar
Relay9
27,5 A
A
207,8
0,0%
92,8%
CAP5
300 kvar
BPC-704
3000 HP
BPC-703
3000 HP
0,2 %Vd
G1
500 kW
0,48 kV
T7
800 kVA
5,75 %Z
6,3/0,48 kV
30 m
1-3/C 350
TGD-VA3-01
-2,5% TapP
T704
2,5 MVA
6,3/0,48
5,75 %Z kV
BPC-705
3000 HP
Relay5
Relay4
CAP7
300 kvar
0,1 %Vd
CT6
27,5 A
A
218,4
0,0%
87,5%
CAP6
300 kvar
BPC-702
3000 HP
0,2 %Vd
-7 ,5
0 de
g
Relay8CT10
23,4 A
89,2%
CT5
CT13
27,5 A
A
216,3
0,0%
89,1%
BPC-701
T703
3000 HP
2,5 MVA
6,3/0,48 kV 0,2 %Vd
5,75 %Z
TR-4
1,6 MVA
6,3/0,48 kV
5,9 %Z
0,2 %Vd
Barra_B
6,3 kV
1500 A
25 kA
30 m
3-1/C 4/0
0,0 %Vd
BPC6410
2500 HP
Barra_A
6,3 kV
1500 A 99 ,93%
25 kA-7,4 8
deg
-6 ,8
6 de
g
CT11
30 m
3-1/C 4/0
Relay13
604,1 A
94,7%
8%
99 ,9
176,7 A
92,7%
CT4
BPC6450
5000 HP
6%
98 ,8
0,48 kV
244,4 A
89,9%
0,2 %Vd
62,2 A
89,6%
Centro de Generacin
GD 701
0,48 kV
GD-702
0,48 kV
CCM-VA3-01
0,48 kV
4000 A
65 kA
GD-703
0,48 kV
1100 kW
1100 kW
1100 kW
190 m
15-1/C 750
190 m
15-1/C 750
190 m
15-1/C 750
6%
98 ,8 0,48 kV
6%
98 ,8
-8 ,3 4000 A
565
degkA
-8 ,3
5 de
g
MOV-5
4x1 HP
1,1 %Vd
4000 A
48,2 A
92,0%
BM-704
100 HP
BM-701
125 HP
0,5 %Vd
244,5 A
91,6%
BB-701
250 HP
0,5 %Vd
4%
97,7
-1 0,
12 de
g
2630,1 A
94,6%
55 kA
61,3 A
91,4%
0,9 %Vd
0,7 A
81,0%
TA-601
1 HP
244,8 A
91,6%
BB-704
250 HP
0,0 %Vd
97,4 A
91,7%
BT-701
200 HP
1,0 %Vd
244,4 A
91,6%
BB-706
250 HP
0,3 %Vd
0,9 %Vd
CCM 702
0,48 kV
31,7 A
89,3%
32 A
89,3%
AGT-717
40 HP
AGT-707
30 HP
AGT-710
30 HP
6,5 %Vd
1,7 %Vd
2,6 %Vd
97,6 A
0,0%
AGT-714 BDC-701
40 HP
83 kvar
0,0 %Vd
31,9 A
89,3%
1,8 A
83,7%
AGT-701
30 HP
AGT-704
30 HP
2,2 %Vd
0,0 %Vd
Mtr25
3 HP
Cable38
48,5 A
92,0%
BM-705
100 HP
61,9 A
91,5%
BM-702
125 HP
30 A
90,8%
CO-702
60 HP
31,9 A
89,3%
AGT-718
40 HP
AGT-713
30 HP
1,1 %Vd
1,5 %Vd
0,7 %Vd
0,0 %Vd
2,3 %Vd
CCM1
0,48 kV
146,6 A
91,8%
BA-701
300 HP
31,9 A
89,3%
249,7 A
91,3%
10,8 A
88,2%
10,8 A
88,4%
3 A
84,9%
1,9 A
82,0%
249,2 A
89,4%
488,6 A
91,7%
26,8 A
88,8%
26,8 A
88,8%
3,7 A
83,7%
19,2 A
88,2%
PG
17,5 HP
0,2 %Vd
26,7 A
90,0%
AGT-711
30 HP
AGT-715
40 HP
2,2 %Vd
0,0 %Vd
1,9 A
82,0%
5,7 A
86,7%
1,0 %Vd
CCM2
0,48 kV
1%
97,0
261 A
-0,3%
BX-702
3 HP
Cable5
0,0 %Vd
32 A
89,3%
30 m
6-1/C 4/0
AGT-705
30 HP
31,7 A
89,3%
AG-708
30 HP
26,7 A
1,0 %Vd
1,7 %Vd
31,9 A
89,3%
31,9 A
89,3%
32 A
89,3%
97,7 A
-0,4%
AGT-712
30 HP
AGT-719
40 HP
AGT-703
30 HP
AGT-706
30 HP
AGT-709
30 HP
2,2 %Vd
0,0 %Vd
2,2 %Vd
2,6 %Vd
0,0 %Vd
97,4 A
91,7%
BDC-703
83 kvar
BT-702
200 HP
-0,2 %Vd
0,3 %Vd
31,9 A
89,3%
30 m
6-1/C 4/0
AGT-702
30 HP
8,3 A
87,9%
BE-701
15 HP
13,3 A
88,8%
BU-712
25 HP
13,2 A
88,8%
BU-715
25 HP
15,8 A
89,2%
1,2 A
90,0%
30 m
6-1/C 4/0
BS-713
30 HP
26,7 A
90,0%
0,0 %Vd
PB-702
45 kVA
2,6 %Vd
1,7 %Vd
98,5 A
89,1%
DR
1,2 A
90,0%
0,0 %Vd
PB-701
45 kVA
2,2 %Vd
1,7 %Vd
0,8 %Vd
0,7 %Vd
1,2 %Vd
98,5 A
89,1%
-3% TapP
T 705
113 kVA
DR
4 %Z 0,48/0,208
220,5 A
90,0%
90,0%
0,0 %Vd
TAE 701
1 kVA
TAS-702
80 kVA
kV
97,6 A
0,0%
-3% TapP
T 706
113 kVA
4 %Z 0,48/0,208 BDC-702
kV
83 kvar
220,5 A
90,0%
242,5 A
88,7%
8,2 A
87,6%
DR
CO-703
15 HP
0,6 %Vd
Lump11
80 kVA
0,0 %Vd
-0,3 %Vd
BB-6403
250 HP
0,0 %Vd
2,2 %Vd
6441-D
20 HP
0,2 %Vd
6441-C
20 HP
0,8 %Vd
6441-B
5 HP
LUB-6441 BB-6402
1,47 HP
250 HP
0,2 %Vd
0,1 %Vd
2,0 %Vd
1,1 %Vd
Bus23
0,48 kV
1%
97,0
249,8 A
91,2%
13,3 A
88,8%
26,8 A
88,8%
249,8 A
91,2%
10,8 A
88,4%
10,8 A
88,4%
3 A
84,9%
198,1 A
91,4%
0,4 A
0,0%
0,4 A
0,0%
0,3 A
0,0%
0,3 A
0,0%
0,0%
5,7 A
86,7%
77,2 A
90,4%
0,1 %Vd
0,6 %Vd
CO-601
25 HP
2,3 %Vd
0,6 %Vd
1,1 %Vd
2,3 %Vd
0,0 %Vd
6431C
20 HP
0,8 %Vd
0,8 %Vd
6431B
5 HP
0,2 %Vd
BB-5402
200 HP
BL-6420
0,5 HP
BL-6410
0,5 HP
TFLA 15
0,46 HP
TFLB 15
0,46 HP
5,1 A -1 123,4 A
0,24
86,3%
100,0%
deg
1,2 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
123,4 A
100,0%
TDA 604
10 HP
0,7 %Vd
CCM-3
77 A
90,4%
13,3 A
88,8%
0,3 A
0,0%
0,6 A
100,0%
3 A
84,9%
15,8 A
89,2%
81,8 A
89,5%
81,8 A
89,5%
9,5 A
87,9%
1,3 A
82,7%
4,4 A -10,66
de g
85,9%
PB-6001
BD-9606
3x50 HP
BD-9603
3x50 HP
BD-VERT
7,5 HP
0,3 %Vd
0,3 %Vd
0,1 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
0,1 %Vd
185 m
12-1/C 500
0,0 %Vd
DR
30 m
3-1/C 1/0
30 m
3-1/C 1/0
0,0%
0,3 A
0,0%
3 A
84,9%
Charger1
10 kVA/7,65 kW
%
95,7
BD-9610
4x50 HP
Mtr14
9 HP
1,1 %Vd
1%
dcLump3
97 ,0
227,7 A-1
0,24
93,4%
de g
300 m
9-1/C 500
1,3 %Vd
102,8 A
90,4%
0,2 %Vd
BB-6404
250 HP
1%
97 ,0 0,48 kV
261,3 A
90,0%
CCM-DESCARGADER
0,48 kV
1,1 %Vd
BB-707
250 HP
BB-705
250 HP
BB-703
250 HP
MOV2
1 HP
T 602
T5
0,0 %Vd
0,4 %Vd
100
kVA
100
%Vd
kVA
DR kV 0,4
2,6 %Z
0,48/0,208
2,60,48/0,208
%Z
kV
ESPUMA
20 HP
PGRU
17,5 HP
INTERC
2 HP
MOV4
1 HP
0,0 %Vd
TFL 05
0,46 HP
0,0 %Vd
dcLump1
0,0 %Vd
MOV6
1 HP
-10,
24 de
g
15 m
3-1/C 2/0
1225331
5 HP
0,0 %Vd
32,2 A
84,5%
0,1 %Vd
0,1 %Vd
ECDT-0201
0,48 kV
3000 A
40 kA
4%
96 ,9
11,7 A
89,8%
9,5 A
81,0%
4,8 A
81,0%
6,3 A
81,0%
-1 0,
23 de
g
CCM 703
188,8 A
90,0%
Lump5
70 kVA
188,8 A
90,0%
100 m
3-1/C 2/0
0,2 %Vd
Lump7
70 kVA
DS
ECDT-0201
ECDT-0202
0,208 kV
225 A
10 kA
ECDT-0201
Cable42
Cable48
Cable52
T4
30 kVA
2,6 %Z
0,48/0,208 kV
26,9 A
90,0%
8%
96 ,0
26,9 A
90,0%
-1 0,
51 de
g
ECDT-0201
Lump2
10 kVA
120 m
3-1/C 500
270 m
3-1/C 500
0,1 %Vd
ECDT-0205
0,48 kV
3000 A
40 kA
120 m
3-1/C 500
0,2 %Vd
9%
96 ,8
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
-10,
25
ECDT-0203
0,48 kV
3000 A
40 kA
0,0 %Vd
7%
96 ,7
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
deg
-10,
28
ECDT-0204
0,48 kV
3000 A
40 kA
1%
96 ,9
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
deg
-10,
24
BM-706
125 HP
0,5 %Vd
deg
98,5 A
89,1%
-3% TapP
T 707
45 kVA
DR
4 %Z 0,48/0,208
82,8 A
90,0%
kV
-10,
12 de
g
61,3 A
91,4%
0,9 %Vd
37 A
89,1%
CARGA
30 kVA
2117,4 A
95,5%
998,2 A
98,1%
-10,
24 de
g
26,7 A
90,0%
230 m
6-1/C 4/0
BB-5401
100 HP
244,4 A
91,6%
4%
97 ,7
-10,
12 de
g
Charger3
10 kVA/7,65 kW
INCENDIO CAP1
250 HP
223 kvar
0,0 %Vd
4%
97,7
1,8 A
83,7%
BB-708
300 HP
0,2 %Vd
TSA-VA3-01
50 kVA
CCM 703
0,48 kV
1583,7 A
94,7%
487,9 A
97,1%
244,6 A
91,6%
BB-702
250 HP
43,7 A
90,2%
-3% TapP
TR-VA3
75 kVA
0,48/0,208
2,6 %Z
kV
139,2 A
90,0%
MX-01A
6x40 HP
CCM 701
0,48 kV
DR
TMOVS-VA3-01
244,4 A
89,9%
-3% TapP
T 709
113 kVA
4 %Z 0,48/0,208 kV
220,5 A
90,0%
CARGA1
80 kVA
BB-709
300 HP
0,0 %Vd
-8 ,3
5 de
g
VAS-5209124-11040-ID-ELE-MC-051-1
Anlisis de Cargas
Revisin: 1
Documento No.
VAS-5209124-11040-ID-ELE-MC-051-R1.doc.
1 de 1
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Voltage
kV
% Mag.
Generation
Ang.
MW
Load
Mvar
MW
Load Flow
Mvar
ID
MW
XFMR
Mvar
Amp
% PF
220-MCC-20100 Barra A
0.480
87.914
-10.1
0.209
0.104
Bus84
-0.209
-0.104
319.1
89.5
220-MCC-20100 Barra B
0.480
86.368
-11.5
0.030
0.016
Bus88
-0.646
-0.324
1006.1
89.4
220-MCC-20200
0.616
0.307
958.4
89.5
Barra 220-DP-20300
0.000
0.000
0.0
0.0
220-MCC-20200
0.480
85.831
-11.8
0.613
0.303
220-MCC-20100 Barra B
-0.613
-0.303
958.4
89.7
Bus138
0.000
0.000
0.0
0.0
Bus140
0.000
0.000
0.0
0.0
Bus137
0.000
0.000
0.0
0.0
Barra 220-DP-20300
0.208
86.368
-11.5
220-MCC-20100 Barra B
Barra_A
6.300
99.934
-7.5
Bus26
Barra_B
Barra A
6.300
6.600
99.940
84.304
-7.5
-9.5
0.000
0.000
0.0
0.0
-6.237
-2.117
604.1
94.7
T703-AT
2.033
0.801
200.4
93.0
Bus4
2.102
0.547
199.2
96.8
Bus8
2.102
0.770
205.3
93.9
Bus5
-6.515
-2.061
626.6
95.3
TGD-VA3-01
0.227
0.115
23.4
89.2
Bus10
2.102
0.547
199.2
96.8
Bus25
2.085
0.852
206.5
92.6
Bus24
2.102
0.546
199.1
96.8
Bus94
-14.350
-5.740
1603.7
92.8
Bus95
0.209
0.107
24.4
89.0
Bus97
3.372
1.319
375.8
93.1
Bus102
3.372
1.319
375.8
93.1
Barra B
7.395
2.994
827.9
92.7
Barra-A
6.300
99.960
-6.9
6.997
2.833
Bus32
-6.997
-2.833
692.0
92.7
Barra B
6.600
84.304
-9.5
Bus96
0.651
0.356
77.0
87.7
Bus105
3.372
1.319
375.7
93.1
Bus106
3.372
1.319
375.7
93.1
Barra A
-7.395
-2.994
827.9
92.7
Barra-B
B-P.BOYACA 1
6.300
34.500
99.982
85.249
-6.9
-3.5
3.574
6.868
1.446
3.326
TR4-AT
1.648
0.618
161.3
93.6
Bus28
-5.223
-2.064
514.7
93.0
B-P.BOYACA 2
-6.868
-3.326
149.8
90.0
-6.868
-3.326
391.5
90.0
-0.059
-0.029
81.8
89.5
0.059
0.029
81.8
89.5
13.200
85.249
-3.5
6.868
3.326
Bus1
0.480
96.628
-10.2
CCM-3
Bus3
% Tap
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Bus2
Voltage
kV
% Mag.
110.000
79.931
Bus3
0.208
Bus4
Bus5
Generation
Ang.
-3.3
MW
Load
Mvar
0
MW
0
Load Flow
Mvar
ID
0
Bus7
XFMR
Mvar
Amp
% PF
VAS-T2
0.000
0.000
0.0
THCMT-0202 B
0.000
0.000
0.0
0.0
-10.8
0.058
0.028
Bus1
-0.058
-0.028
188.8
90.0
6.300
99.934
-7.5
2.102
0.547
Barra_A
-2.102
-0.547
199.2
96.8
6.300
100.019
-7.4
Barra_B
6.519
2.068
626.6
95.3
-6.519
-2.068
626.6
95.3
110.000
0.480
79.928
96.628
-3.3
-10.2
VAS-T1
-12.263
-5.813
89.1
90.4
THCMT-0202 A
12.263
5.813
89.1
90.4
CCM-3
-0.059
-0.029
81.8
89.5
0.059
0.029
81.8
89.5
Bus9
Bus8
6.300
99.934
-7.5
2.102
0.770
Barra_A
-2.102
-0.770
205.3
93.9
Bus9
0.208
95.203
-10.8
0.058
0.028
Bus7
-0.058
-0.028
188.8
90.0
Bus10
6.300
99.940
-7.5
2.102
0.547
Barra_B
-2.102
-0.547
199.2
96.8
Bus11
0.480
97.703
-10.1
0.020
0.009
CCM 702
-0.020
-0.009
26.7
90.0
Bus12
110.000
79.928
-3.3
VAS-T3
-12.805
-5.247
90.9
92.5
THCMT-0202 C
12.805
5.247
90.9
92.5
CCM 702
-0.020
-0.009
26.7
90.0
THCMT-0202 C
-6.243
-2.179
604.1
94.4
Bus13
0.480
97.703
-10.1
0.020
0.009
Bus14
6.300
100.323
-7.0
6.243
2.179
604.1
94.4
Bus15
0.480
97.738
-10.1
CCM 702
-0.001
0.000
1.2
90.0
Bus16
0.208
98.858
-11.3
0.071
0.034
CCM 702
-0.071
-0.034
220.5
90.0
Bus17
6.300
100.323
-7.0
THCMT-0202 C
-6.522
-2.127
626.6
95.1
6.522
2.127
626.6
95.1
Bus26
Bus5
Bus18
0.208
98.858
-11.3
0.071
0.034
CCM 702
-0.071
-0.034
220.5
90.0
Bus19
0.480
95.918
-10.6
0.098
0.000
CCM2
-0.098
0.000
123.4
100.0
Bus20
0.208
98.969
-11.2
0.027
0.013
CCM 702
-0.027
-0.013
82.8
90.0
Bus21
0.208
98.858
-11.3
0.071
0.034
CCM 702
-0.071
-0.034
220.5
90.0
Bus22
0.208
100.513
-8.9
0.045
0.022
TGD-VA3-01
-0.045
-0.022
139.2
90.0
Bus23
0.480
97.012
-10.2
CCM-DESCARGADER
CCM1
Tablero Dist. 480V
Bus24
6.300
Bus25
Bus26
0.190
0.092
261.3
90.0
-0.361
-0.157
488.6
91.7
0.172
0.065
227.7
93.4
99.940
-7.5
2.102
0.546
Barra_B
-2.102
-0.546
199.1
96.8
6.300
99.940
-7.5
2.085
0.852
Barra_B
-2.085
-0.852
206.5
92.6
6.300
100.014
-7.4
Barra_A
6.241
2.124
604.1
94.7
Bus14
-6.241
-2.124
604.1
94.7
ECDT-0201
-0.008
-0.004
11.7
89.8
Bus27
0.480
96.782
-10.2
Bus28
6.300
100.042
-6.8
% Tap
0.0
95.203
Bus17
Bus6
MW
ECDT-0202
0.008
0.004
11.7
89.8
Barra-B
5.224
2.069
514.7
93.0
-16.250
-18.750
-18.750
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Voltage
kV
% Mag.
Generation
Ang.
MW
Load
Mvar
MW
Load Flow
Mvar
ID
MW
XFMR
Mvar
Amp
% PF
THCMT-0202 A
-5.224
-2.069
514.7
93.0
Bus29
0.480
95.715
-10.3
0.059
0.013
-0.059
-0.013
75.9
97.7
Bus30
0.480
94.890
-9.9
0.029
0.013
-0.029
-0.013
40.7
91.6
Bus31
0.480
94.890
-9.9
0.029
0.013
-0.029
-0.013
40.7
91.6
Bus32
6.300
100.042
-6.8
7.000
2.841
692.0
92.7
THCMT-0202 A
-7.000
-2.841
692.0
92.7
Barra-A
Bus33
0.480
95.233
-10.2
0.049
0.013
-0.049
-0.013
64.1
96.7
Bus34
0.480
96.854
-9.9
0.001
0.013
-0.001
-0.013
16.3
11.3
Bus67
110.000
79.931
-3.3
Ocensa B2
0.000
0.000
0.0
0.0
Bus84
0.480
88.040
-10.1
220-MCC-20100 Barra A
0.209
0.104
319.1
89.5
-0.209
-0.104
319.1
89.5
Bus88
0.480
86.493
-11.5
0.647
0.324
1006.1
89.4
Bus96
-0.647
-0.324
1006.1
89.4
14.468
7.664
107.5
88.4
Bus95
220-MCC-20100 Barra B
Bus93
115.000
76.456
-3.3
Bus94
-14.468
-7.664
107.5
88.4
Bus94
6.600
84.431
-9.4
Barra A
14.366
5.762
1603.7
92.8
Bus93
-14.366
-5.762
1603.7
92.8
-0.209
-0.107
24.4
89.0
Ocensa B1
Bus95
6.600
84.300
-9.5
Barra A
Bus84
0.209
0.107
24.4
89.0
Bus96
6.600
84.301
-9.5
Barra B
-0.651
-0.356
77.0
87.7
Bus88
0.651
0.356
77.0
87.7
Bus97
6.600
84.291
-9.5
3.372
1.319
Barra A
-3.372
-1.319
375.8
93.1
Bus102
6.600
84.291
-9.5
3.372
1.319
Barra A
-3.372
-1.319
375.8
93.1
Bus105
6.600
84.300
-9.5
3.372
1.319
Barra B
-3.372
-1.319
375.7
93.1
Bus106
6.600
84.300
-9.5
3.372
1.319
Barra B
-3.372
-1.319
375.7
93.1
Bus137
0.480
85.831
-11.8
220-MCC-20200
0.000
0.000
0.0
0.0
Bus138
0.480
85.831
-11.8
220-MCC-20200
0.000
0.000
0.0
0.0
Bus140
0.480
85.831
-11.8
220-MCC-20200
0.000
0.000
0.0
0.0
CCM1
0.480
97.012
-10.2
0.429
-0.003
Bus23
0.361
0.157
488.6
91.7
CCM2
-0.790
-0.154
998.2
98.1
CCM2
0.480
97.012
-10.2
0.568
0.259
Bus19
0.100
0.001
123.4
100.0
TR4-AT
-1.632
-0.504
2117.4
95.5
CCM-3
0.173
0.090
242.5
88.7
CCM1
CCM 701
CCM 702
0.480
0.480
97.739
97.739
-10.1
-10.1
0.803
0.554
0.279
0.174
0.790
0.154
998.2
98.1
T703-AT
-2.022
-0.691
2630.1
94.6
CCM 702
1.219
0.412
1583.7
94.7
Bus13
0.020
0.009
26.7
90.0
Bus11
0.020
0.009
26.7
90.0
% Tap
-10.500
-5.000
-5.000
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Voltage
kV
% Mag.
Generation
Ang.
MW
Load
Mvar
CCM 703
0.480
97.739
-10.1
CCM-3
0.480
97.012
-10.2
MW
Load Flow
Mvar
ID
MW
XFMR
Mvar
Amp
% PF
Bus15
0.001
0.000
1.2
90.0
Bus16
0.071
0.036
98.5
89.1
-3.000
Bus18
0.071
0.036
98.5
89.1
-3.000
Bus20
0.027
0.014
37.0
89.1
-3.000
Bus21
0.071
0.036
98.5
89.1
-3.000
CCM 703
0.385
0.095
487.9
97.1
CCM 701
-1.219
-0.412
1583.7
94.7
0.385
0.095
CCM 702
-0.385
-0.095
487.9
97.1
0.033
0.018
Bus1
0.059
0.029
81.8
89.5
Bus7
0.059
0.029
81.8
89.5
ECDT-0201
0.022
0.014
32.2
84.5
CCM2
-0.173
-0.090
242.5
88.7
CCM-DESCARGADER
0.480
95.701
-10.7
0.188
0.089
Bus23
-0.188
-0.089
261.3
90.3
CCM-VA3-01
0.480
98.856
-8.4
0.181
0.088
TGD-VA3-01
-0.181
-0.088
244.4
89.9
110.000
88.000
0.0
67.172
36.133
60.108
32.364
407.2
88.0
0.480
96.944
-10.2
* Cocorna - EPM
ECDT-0201
TECA
7.064
3.769
47.8
88.2
CCM-3
-0.022
-0.014
32.2
84.5
Bus27
0.008
0.004
11.7
89.8
ECDT-0203
0.006
0.005
9.5
81.0
ECDT-0204
0.003
0.002
4.8
81.0
ECDT-0205
0.004
0.003
6.3
81.0
ECDT-0202
0.208
96.081
-10.5
0.008
0.004
Bus27
-0.008
-0.004
26.9
90.0
ECDT-0203
0.480
96.773
-10.3
0.006
0.004
ECDT-0201
-0.006
-0.004
9.5
81.0
ECDT-0204
0.480
96.906
-10.2
0.003
0.002
ECDT-0201
-0.003
-0.002
4.8
81.0
ECDT-0205
0.480
96.894
-10.2
0.004
0.003
ECDT-0201
-0.004
-0.003
6.3
81.0
Jazmn - MSB
110.000
79.856
-3.4
3.029
1.741
VAS-JAZMIN-A
-3.029
-1.741
23.0
86.7
Ocensa B1
110.000
79.931
-3.3
Bus93
14.468
7.664
107.5
88.4
Ocensa B2
-14.468
-7.664
107.5
88.4
Ocensa B2
110.000
79.931
-3.3
T - L. PTO Boyaca
-14.468
-7.664
107.5
88.4
0.000
0.000
0.0
0.0
14.468
7.664
107.5
88.4
Bus67
Ocensa B1
Palagua - ECP
110.000
79.919
-3.4
0.608
0.294
110.000
86.298
-1.0
VAS-PALAGUA
-0.608
-0.294
4.4
90.0
-59.467
-30.856
407.5
88.8
T - L. PTO Boyaca
45.666
23.405
312.1
89.0
B-P.BOYACA 1
13.802
7.451
95.4
88.0
Barra_A
-2.033
-0.800
200.4
93.1
CCM 701
2.033
0.800
200.4
93.1
Cocorna - EPM
& B-P.BOYACA 2
T703-AT
6.300
99.907
-7.5
% Tap
-1.500
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Tablero Dist. 480V
TECA
Voltage
kV
0.480
% Mag.
97.012
Generation
Ang.
-10.2
MW
Load
Mvar
0
MW
0
Load Flow
Mvar
ID
0
110.000
87.895
-0.1
Teca 13.8 kV
13.800
85.266
-3.0
7.035
3.407
TGD-VA3-01
0.480
98.856
-8.4
6.300
100.042
-6.8
XFMR
Mvar
Amp
% PF
Bus29
0.060
0.013
75.9
97.6
Bus30
0.030
0.013
40.7
91.8
Bus31
0.030
0.013
40.7
91.8
96.7
Bus33
0.050
0.013
64.1
Bus34
0.002
0.013
16.3
11.8
Bus23
-0.172
-0.065
227.7
93.4
Cocorna - EPM
-7.060
-3.882
48.1
87.6
Teca 13.8 kV
THCMT-0202 A
MW
7.060
3.882
48.1
87.6
TECA
-7.035
-3.407
383.5
90.0
Barra_B
-0.226
-0.111
306.6
89.8
Bus22
0.046
0.023
62.2
89.6
CCM-VA3-01
0.181
0.088
244.4
89.9
TMOVS-VA3-01
0.000
0.000
0.0
0.0
-12.225
-4.910
1206.8
92.8
Bus32
7.000
2.841
692.0
92.7
93.0
Bus6
Bus28
5.224
2.069
514.7
THCMT-0202 B
6.300
99.985
-3.3
Bus2
0.000
0.000
0.0
0.0
THCMT-0202 C
6.300
100.334
-7.0
Bus14
6.244
2.180
604.1
94.4
Bus17
6.522
2.128
626.6
95.1
Bus12
-12.766
-4.308
1230.6
94.8
28.707
12.787
206.4
91.3
-43.175
-20.450
313.7
90.4
14.468
7.664
107.5
88.4
0.0
T - L. PTO Boyaca
110.000
79.931
-3.3
VAS-PTO BOYACA
Puerto Boyac - EBSA
Ocensa B2
T - L. Teca
110.000
79.931
-3.3
VAS-TECA
0.000
0.000
0.0
TMOVS-VA3-01
0.480
98.856
-8.4
TGD-VA3-01
0.000
0.000
0.0
0.0
TR4-AT
6.300
99.949
-6.9
Barra-B
-1.648
-0.617
161.3
93.6
CCM2
1.648
0.617
161.3
93.6
12.534
5.531
90.0
91.5
3.030
1.588
22.5
88.6
VAS-PALAGUA
-15.565
-7.119
112.4
90.9
VAS-JAZMIN-A
-12.534
-5.531
90.0
91.5
12.534
5.531
90.0
91.5
0.608
0.137
4.1
97.5
15.565
7.119
112.4
90.9
VAS-PTO BOYACA
-16.173
-7.256
116.4
91.2
T - L. PTO Boyaca
VAS-JAZMIN-A
110.000
79.931
-3.3
VAS-JAZMIN-B
Jazmn - MSB
VAS-JAZMIN-B
110.000
79.931
-3.3
VAS-PALAGUA
110.000
79.931
-3.3
VAS-T1
Palagua - ECP
VAS-JAZMIN-A
VAS-PTO BOYACA
110.000
79.931
-3.3
-28.707
-12.787
206.4
91.3
VAS-PALAGUA
16.173
7.256
116.4
91.2
VAS-TECA
12.534
5.531
90.0
91.5
% Tap
-3.000
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
VAS-T1
Voltage
kV
% Mag.
110.000
79.931
Generation
Ang.
-3.3
MW
Load
Mvar
0
MW
0
Load Flow
Mvar
ID
0
Bus6
VAS-T2
VAS-JAZMIN-B
VAS-T2
110.000
79.931
-3.3
Bus2
VAS-T1
VAS-T3
VAS-T3
110.000
79.931
-3.3
Bus12
VAS-TECA
VAS-TECA
110.000
79.931
-3.3
Amp
% PF
12.263
5.814
89.1
90.4
0.271
-0.283
2.6
-69.2
-12.534
-5.531
90.0
91.5
0.000
0.000
0.0
0.0
-0.271
0.283
2.6
-69.2
0.271
-0.283
2.6
-69.2
12.806
5.248
90.9
92.5
-12.534
-5.531
90.0
91.5
-0.271
0.283
2.6
-69.2
VAS-T3
12.534
5.531
90.0
91.5
0.000
0.000
0.0
0.0
-12.534
-5.531
90.0
91.5
VAS-PTO BOYACA
XFMR
Mvar
VAS-T2
T - L. Teca
* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
MW
% Tap
VAS-5209124-11040-ID-ELE-MC-051-1
Anlisis de Cargas
Revisin: 1
Documento No.
VAS-5209124-11040-ID-ELE-MC-051-R1.doc.
1 de 1
Cocorna - EPM
AL
Jazmn - MSB
8%
85 ,5
110 kV
Palagua - ECP
-1,1
9 de
g
24,6 A
86,7%
5%
85,6
110 kV
Palagua
AL
6 km
397.5-26
0,1318+j0,4842 ohms/1km
152 A
90,0%
8%
87,2
110 kV
-0,5
3
47,9 A
87,6%
deg
Trafo Teca
15 MVA
8,5
110/13,8
%Z
kV
0,26974+j0,54136 ohms/1km
6 km
Penguin
382,2 A
90,0%
3%
86,5
Lump1
10 MVA
PB-13,2
10,5 MVA
6%
85,6
T - L. Teca
Ocensa B2
100,4 A
89,0%
TECA
0,7 %Vd
295,9 A
90,2%
AL
B-P.BOYACA 2
397,4 A
90,0%
T - L. PTO Boyaca
110 kV
0,0 %Vd
0,1 %Vd
397,4 A
90,0%
152 A -2 ,74
de g
90,0%
PB-34,5
10,5 MVA
6 km
397.5-26
0,1318+j0,4842 ohms/1km
AL
9%
87,5
-0,2
96,8 A
2 de
g
88,0%
-1,5% TapP
Trafo EBSA
30/15/15 MVA
110/34,5/13,2 kV
10/10/10 %Z
0,95 MVA
AL
6,15 km
300-30
0,2092+j0,5276 ohms/1km
0,1318+j0,4842 ohms/1km
4 km
397.5-26
0,4 %Vd
0,26974+j0,54395 ohms/1km
22,1 km
Penguin
B-P.BOYACA 1
3%
34,5 kV
86,5
AL
Jazmn
5,479 MVA
110 kV
88%
343,4 0,
A 00
deg
89,6%
-1,1
5 de
g
4,6 A
90,0%
439,9 A
89,3%
110 kV
96,5 A
88,1%
Ocensa B1
6%
85,6
296,3 A
90,6%
110 kV
-1,1
4 de
g
-1,1
4
AMPLIACIN OCENSA
deg
T - L. Teca
T - L. PTO Boyaca
10 m
36-1/C 750
VAS-PALAGUA
6%
85 ,6
4,2 A
97,8% ,66%
85
110 kV
-1,1
4
108 A
90,9%
0,0 %Vd
VAS-TECA
212,4 A
90,2%
deg
83,9 A
91,5%
110 kV
-1 ,1
4 de
g
SW70
0 A
SW72
0 A
10 m
36-1/C 750
VAS-JAZMIN-A
110 kV
24,1 A
88,6%
112,1 A
91,2%
6%
85 ,6
10 m
36-1/C 750
100,4 A
89,0%
0,0 %Vd
VAS-PTO BOYACA
-1 ,1
4 de
g
83,9 A
91,5%
10 m
36-1/C 750
6%
85 ,6
-1,1
4 de
g
110 kV
SW75
0 A
0,0 %Vd
6%
85 ,6
CT16
VAS-T1
110 kV
6%
85,6
VAS-T2110 kV
-1,1
4 de
g
83,9 A
91,5%
VAS-JAZMIN-B
110 kV
0,0 %Vd
CT22
6%
85,6
2,3 A
-72,5%
CT24
SW80
0 A
6%
85,6
Ocensa B2
-1 ,1
100,4 A
4 de
g 89,0%
100,4 A
89,0%
110 kV
SW88
0 A
SW86
0 A
-1 ,1
4 de
g
110 kV
SW84
0 A
6%
85,6
VAS-T3
-1,1
83,1 A
4 de
g
90,4%
Cuarto Elctrico Vasconia
100 m
3-1/C 500
0,0 %Vd
SW76
0 A
6%
85,6
Ocensa B1
2,3 A -1 ,14
de g
-72,5%
0,0%
CT18
110 kV
CCM 703
-1
84,8
,14 A
92,5%de g
100 m
3-1/C 500
0,0 %Vd
SW79
0 A
100 m
3-1/C 500
0,0 %Vd
SW83
0 A
T2
20 MVA
110/6,6 kV
9,5 %Z
-13,75% TapP
T3
20 MVA
110/6,6 kV
9,5 %Z
-11,25% TapP
-12,5% TapP
NUEVO SW MT
THCMT-0202 A
6,3 kV
3150 A
31,5 kA
THCMT-0202 B
6,3 kV
07 %
101,
3150 A
31,5 kA
1194,5 A
92,8%
685 A
92,7%
509,6 A
93,0%
THCMT-0202 C
6,3 kV
3150 A
31,5 kA
12 %
101,
-1,1
4 de
g
0,0%
1%
99 ,8
-4,8
1 de
g
1237,4 A
94,7%
607,3 A
94,4%
-4 ,5
5 de
g
630,2 A
95,0%
20 m
18-1/C 500
0,0 %Vd
20 m
18-1/C 500
0,0 %Vd
X7
0,3 %Vd
0,05 ohms
X3
Barra-A
6,3 kV
1200 A
31,5 kA
685 A
92,7%
335,2 A
92,7%
174,9 A
92,7%
0,3 %Vd
0,05 ohms
130 m
18-1/C 500
0,1 %Vd
130 m
18-1/C 500
0,1 %Vd
99 %
100,
-4,6
0 de
174,9 A
92,7%
Barra-B
6,3 kV
1200 A
31,5 kA
509,6 A
93,0%
01%
10 1,
174,9 A
92,7%
174,9 A
92,7%
159,8 A
93,8%
150 m
18-1/C 500
0,1 %Vd
CT14
150 m
18-1/C 500
0,1 %Vd
-5% TapP
TR-3
1,6 MVA
5,9 %Z
6,3/0,48 kV
0,2 %Vd
BPC6430
2500 HP
0,2 %Vd
BPC6420
2500 HP
0,2 %Vd
BPC6440
2500 HP
0,2 %Vd
200,3 A
96,7%
Vasconia III
1%
99,4
630,2 A
95,3%
206,5 A
93,9%
200,3 A
96,7%
CT12
Relay10
Relay3
Relay11
27,3 A
A
208,9
0,0%
92,8%
30 m
1-3/C 350
0,0 %Vd
Relay12
200,3 A
96,7%
CT9
207,7 A
92,5%
CAP2
300 kvar
27,3 A
A
208,9
0,0%
92,8%
CAP4
300 kvar
Relay9
27,3 A
A
208,9
0,0%
92,8%
CAP5
300 kvar
BPC-704
3000 HP
BPC-703
3000 HP
0,2 %Vd
G1
500 kW
0,48 kV
T7
800 kVA
5,75 %Z
6,3/0,48 kV
30 m
1-3/C 350
TGD-VA3-01
-2,5% TapP
T704
2,5 MVA
6,3/0,48
5,75 %Z kV
BPC-705
3000 HP
Relay5
Relay4
CAP7
300 kvar
0,1 %Vd
CT6
27,3 A
A
219,5
0,0%
87,5%
CAP6
300 kvar
BPC-702
3000 HP
0,2 %Vd
-5 ,3
3 de
g
Relay8CT10
23,4 A
89,2%
CT5
CT13
27,3 A
A
217,5
0,0%
89,1%
BPC-701
T703
3000 HP
2,5 MVA
6,3/0,48 kV 0,2 %Vd
5,75 %Z
TR-4
1,6 MVA
6,3/0,48 kV
5,9 %Z
0,2 %Vd
Barra_B
6,3 kV
1500 A
25 kA
30 m
3-1/C 4/0
0,0 %Vd
BPC6410
2500 HP
Barra_A
6,3 kV
1%
1500 A 99 ,4
25 kA-5,3 1
deg
201,3 A
93,0%
CT11
BPC6450
5000 HP
Relay13
607,3 A
94,6%
-4 ,5
9 de
g
CT4
30 m
3-1/C 4/0
3%
98 ,3
0,48 kV
245,8 A
89,9%
0,2 %Vd
Centro de Generacin
GD 701
0,48 kV
GD-702
0,48 kV
CCM-VA3-01
0,48 kV
4000 A
65 kA
GD-703
0,48 kV
1100 kW
1100 kW
1100 kW
190 m
15-1/C 750
190 m
15-1/C 750
190 m
15-1/C 750
3%
98 ,3 0,48 kV
3%
98 ,3
-6 ,1 4000 A
965
degkA
-6 ,1
9 de
g
MOV-5
4x1 HP
1,1 %Vd
4000 A
48,5 A
92,0%
BM-704
100 HP
BM-701
125 HP
0,5 %Vd
0,5 %Vd
%
97,2
-7 ,9
7
2642,4 A
94,6%
55 kA
61,6 A
91,4%
245,9 A
91,6%
BB-701
250 HP
0,9 %Vd
0,7 A
81,0%
TA-601
1 HP
246,2 A
91,5%
BB-704
250 HP
0,0 %Vd
97,9 A
91,7%
BT-701
200 HP
1,0 %Vd
245,8 A
91,6%
BB-706
250 HP
0,3 %Vd
0,9 %Vd
CCM 702
0,48 kV
246 A
91,6%
BB-702
250 HP
43,9 A
90,2%
31,9 A
89,3%
32,2 A
89,3%
AGT-717
40 HP
AGT-707
30 HP
AGT-710
30 HP
6,5 %Vd
1,7 %Vd
2,6 %Vd
97 A
0,0%
AGT-714 BDC-701
40 HP
83 kvar
0,0 %Vd
32,1 A
89,3%
1,8 A
83,7%
AGT-701
30 HP
AGT-704
30 HP
2,3 %Vd
0,0 %Vd
Mtr25
3 HP
1,8 A
83,7%
Cable38
BM-705
100 HP
62,3 A
91,5%
BM-702
125 HP
30,1 A
90,8%
CO-702
60 HP
32,1 A
89,3%
AGT-718
40 HP
AGT-713
30 HP
1,1 %Vd
1,5 %Vd
0,7 %Vd
0,0 %Vd
2,4 %Vd
147,5 A
91,8%
BA-701
300 HP
32,1 A
89,3%
10,7 A
88,2%
10,7 A
88,4%
2,9 A
84,9%
1,9 A
82,0%
246,4 A
89,4%
484 A
91,7%
26,5 A
88,8%
26,5 A
88,8%
3,7 A
83,7%
PG
17,5 HP
0,2 %Vd
26,6 A
90,0%
AGT-711
30 HP
AGT-715
40 HP
2,3 %Vd
0,0 %Vd
1,9 A
82,0%
5,6 A
86,7%
1,0 %Vd
CCM2
0,48 kV
9%
98,0
246,9 A
91,3%
19,3 A
88,2%
1,7 %Vd
32,1 A
89,3%
32,1 A
89,3%
32,2 A
89,3%
97,2 A
-0,4%
AGT-712
30 HP
AGT-719
40 HP
AGT-703
30 HP
AGT-706
30 HP
AGT-709
30 HP
2,3 %Vd
0,0 %Vd
2,3 %Vd
2,6 %Vd
0,0 %Vd
97,9 A
91,7%
BDC-703
83 kvar
BT-702
200 HP
-0,2 %Vd
0,3 %Vd
32,2 A
89,3%
30 m
6-1/C 4/0
AGT-705
30 HP
31,9 A
89,3%
AG-708
30 HP
30 m
6-1/C 4/0
AGT-702
30 HP
8,4 A
87,9%
BE-701
15 HP
13,3 A
88,8%
BU-712
25 HP
13,3 A
88,8%
BU-715
25 HP
15,9 A
89,2%
1,2 A
90,0%
30 m
6-1/C 4/0
BS-713
30 HP
26,6 A
90,0%
0,0 %Vd
PB-702
45 kVA
2,6 %Vd
1,7 %Vd
98,2 A
89,1%
DR
1,2 A
90,0%
0,0 %Vd
PB-701
45 kVA
2,3 %Vd
1,7 %Vd
0,8 %Vd
0,7 %Vd
1,2 %Vd
98,2 A
89,1%
-3% TapP
T 705
113 kVA
DR
4 %Z 0,48/0,208
219,8 A
90,0%
90,0%
0,0 %Vd
TAE 701
1 kVA
TAS-702
80 kVA
kV
97 A
0,0%
-3% TapP
T 706
113 kVA
4 %Z 0,48/0,208 BDC-702
kV
83 kvar
219,8 A
90,0%
242,9 A
88,7%
8,3 A
87,6%
DR
CO-703
15 HP
0,6 %Vd
Lump11
80 kVA
0,0 %Vd
-0,3 %Vd
BB-6403
250 HP
0,0 %Vd
2,2 %Vd
6441-D
20 HP
0,2 %Vd
6441-C
20 HP
0,8 %Vd
6441-B
5 HP
LUB-6441 BB-6402
1,47 HP
250 HP
0,2 %Vd
0,1 %Vd
2,0 %Vd
1,1 %Vd
Bus23
0,48 kV
9%
98,0
247 A
91,3%
13,2 A
88,8%
26,5 A
88,8%
247 A
91,3%
10,7 A
88,4%
10,7 A
88,4%
2,9 A
84,9%
195,9 A
91,4%
0,3 A
0,0%
0,3 A
0,0%
0,3 A
0,0%
0,3 A
0,0%
76,3 A
90,4%
0,1 %Vd
0,6 %Vd
CO-601
25 HP
2,2 %Vd
0,6 %Vd
1,1 %Vd
2,2 %Vd
0,0 %Vd
6431C
20 HP
0,8 %Vd
0,8 %Vd
6431B
5 HP
0,2 %Vd
BB-5402
200 HP
BL-6420
0,5 HP
BL-6410
0,5 HP
TFLA 15
0,46 HP
TFLB 15
0,46 HP
1,2 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
CCM-3
0,0%
5,6 A
86,7%
5,1 A -7 122,5 A
,90
86,3%
100,0%
de g
76,1 A
90,4%
13,1 A
88,8%
0,3 A
0,0%
0,6 A
100,0%
2,9 A
84,9%
15,6 A
89,2%
82,3 A
89,5%
82,3 A
89,5%
9,4 A
87,9%
1,3 A
82,7%
9%
96,7
4,3 A -8,31
deg
85,9%
PB-6001
BD-9610
4x50 HP
BD-9606
3x50 HP
BD-9603
3x50 HP
BD-VERT
7,5 HP
0,3 %Vd
0,3 %Vd
0,1 %Vd
0,0 %Vd
122,5 A
100,0%
TDA 604
10 HP
0,6 %Vd
Mtr14
9 HP
1,1 %Vd
9%
98 ,0
dcLump3
226,1 A-7
,90
93,4%
deg
300 m
9-1/C 500
1,3 %Vd
101,7 A
90,4%
0,2 %Vd
BB-6404
250 HP
9%
98 ,0 0,48 kV
258,4 A
90,0%
CCM-DESCARGADER
0,48 kV
1,1 %Vd
BB-705
250 HP
BB-703
250 HP
0,9 %Vd
%
97 ,2
0,0 %Vd
0,0 %Vd
0,1 %Vd
185 m
12-1/C 500
0,0 %Vd
DR
30 m
3-1/C 1/0
30 m
3-1/C 1/0
0,0%
0,3 A
0,0%
2,9 A
84,9%
Charger1
10 kVA/7,65 kW
MOV2
1 HP
T 602
T5
0,0 %Vd
0,4 %Vd
100
kVA
100
%Vd
kVA
DR kV 0,4
2,6 %Z
0,48/0,208
2,60,48/0,208
%Z
kV
ESPUMA
20 HP
PGRU
17,5 HP
INTERC
2 HP
MOV4
1 HP
0,0 %Vd
TFL 05
0,46 HP
0,0 %Vd
dcLump1
0,0 %Vd
MOV6
1 HP
-7,9
0 de
g
15 m
3-1/C 2/0
1225331
5 HP
0,0 %Vd
32,1 A
84,5%
0,1 %Vd
0,1 %Vd
ECDT-0201
0,48 kV
3000 A
40 kA
2%
98 ,0
11,8 A
89,8%
9,4 A
81,0%
4,7 A
81,0%
6,3 A
81,0%
-7 ,8
9 de
g
CCM 703
190 A
90,0%
Lump5
70 kVA
190 A
90,0%
100 m
3-1/C 2/0
0,2 %Vd
Lump7
70 kVA
DS
ECDT-0201
ECDT-0202
0,208 kV
225 A
10 kA
ECDT-0201
Cable42
Cable48
Cable52
T4
30 kVA
2,6 %Z
0,48/0,208 kV
27,1 A
90,0%
5%
97 ,1
27,1 A
90,0%
-8 ,1
7 de
g
ECDT-0201
Lump2
10 kVA
120 m
3-1/C 500
270 m
3-1/C 500
0,1 %Vd
ECDT-0205
0,48 kV
3000 A
40 kA
120 m
3-1/C 500
0,2 %Vd
7%
97 ,9
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
-7,9
1
ECDT-0203
0,48 kV
3000 A
40 kA
0,0 %Vd
5%
97 ,8
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
deg
-7,9
4
ECDT-0204
0,48 kV
3000 A
40 kA
8%
97 ,9
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
deg
-7,9
0
36,8 A
89,1%
82,5 A
90,0%
deg
BM-706
125 HP
0,5 %Vd
deg
98,2 A
89,1%
-3% TapP
T 707
45 kVA
DR
4 %Z 0,48/0,208
CARGA
30 kVA
230 m
6-1/C 4/0
BB-5401
100 HP
BB-707
250 HP
kV
-7,9
7 de
g
61,7 A
91,4%
-7,9
7
32,1 A
89,3%
2096,9 A
95,6%
987 A
98,3%
-7,9
0 de
g
26,6 A
90,0%
Charger3
10 kVA/7,65 kW
INCENDIO CAP1
250 HP
223 kvar
245,8 A
91,6%
490,9 A
97,0%
48,8 A
92,0%
CCM1
0,48 kV
263,9 A
-0,3%
BX-702
3 HP
Cable5
0,0 %Vd
26,6 A
1,0 %Vd
0,0 %Vd
%
97,2
1589,9 A
94,7%
BB-708
300 HP
0,2 %Vd
TSA-VA3-01
50 kVA
CCM 703
0,48 kV
deg
-3% TapP
TR-VA3
75 kVA
0,48/0,208
2,6 %Z
kV
138,8 A
90,0%
MX-01A
6x40 HP
CCM 701
0,48 kV
DR
TMOVS-VA3-01
245,8 A
89,9%
-6 ,1
9 de
g
62 A
89,6%
-3% TapP
T 709
113 kVA
4 %Z 0,48/0,208 kV
219,8 A
90,0%
CARGA1
80 kVA
BB-709
300 HP
0,0 %Vd
VAS-5209124-11040-ID-ELE-MC-051-1
Anlisis de Cargas
Revisin: 1
Documento No.
VAS-5209124-11040-ID-ELE-MC-051-R1.doc.
1 de 1
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Voltage
kV
% Mag.
Generation
Ang.
MW
Load
Mvar
MW
Load Flow
Mvar
ID
MW
XFMR
Mvar
Amp
% PF
220-MCC-20100 Barra A
0.480
95.027
-7.1
0.236
0.117
Bus84
-0.236
-0.117
334.1
89.6
220-MCC-20100 Barra B
0.480
93.387
-8.5
0.031
0.017
Bus88
-0.739
-0.369
1063.8
89.5
220-MCC-20200
0.708
0.352
1018.8
89.5
Barra 220-DP-20300
0.000
0.000
0.0
0.0
220-MCC-20200
0.480
92.817
-8.7
0.705
0.347
220-MCC-20100 Barra B
-0.705
-0.347
1018.8
89.7
Bus138
0.000
0.000
0.0
0.0
Bus140
0.000
0.000
0.0
0.0
Bus137
0.000
0.000
0.0
0.0
Barra 220-DP-20300
0.208
93.387
-8.5
220-MCC-20100 Barra B
Barra_A
6.300
99.408
-5.3
Bus26
Barra_B
Barra A
6.300
6.600
99.414
91.096
-5.3
-6.5
0.000
0.000
0.0
0.0
-6.235
-2.126
607.3
94.6
T703-AT
2.031
0.803
201.3
93.0
Bus4
2.102
0.550
200.3
96.7
Bus8
2.102
0.773
206.5
93.9
Bus5
-6.515
-2.070
630.2
95.3
TGD-VA3-01
0.227
0.115
23.4
89.2
Bus10
2.102
0.550
200.3
96.7
Bus25
2.085
0.855
207.7
92.5
Bus24
2.102
0.550
200.3
96.7
Bus94
-14.471
-5.803
1497.2
92.8
Bus95
0.237
0.121
25.6
89.1
Bus97
3.372
1.319
347.7
93.1
Bus102
3.372
1.319
347.7
93.1
Barra B
7.489
3.044
776.3
92.6
Barra-A
6.300
100.988
-4.6
6.997
2.833
Bus32
-6.997
-2.833
685.0
92.7
Barra B
6.600
91.096
-6.5
Bus96
0.745
0.406
81.4
87.8
Bus105
3.372
1.319
347.7
93.1
Bus106
3.372
1.319
347.7
93.1
Barra A
-7.489
-3.044
776.3
92.6
Barra-B
B-P.BOYACA 1
6.300
34.500
101.010
86.528
-4.6
-2.7
3.574
7.075
1.446
3.427
TR4-AT
1.651
0.612
159.8
93.8
Bus28
-5.226
-2.059
509.6
93.0
B-P.BOYACA 2
-7.075
-3.427
152.0
90.0
-7.075
-3.427
397.4
90.0
-0.060
-0.030
82.3
89.5
0.060
0.030
82.3
89.5
13.200
86.528
-2.7
7.075
3.427
Bus1
0.480
97.699
-7.9
CCM-3
Bus3
% Tap
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Bus2
Voltage
kV
% Mag.
110.000
85.664
Generation
Ang.
-1.1
MW
Load
Mvar
0
MW
0
Load Flow
Mvar
ID
0
MW
XFMR
Mvar
Amp
% PF
VAS-T2
0.000
0.000
0.0
THCMT-0202 B
0.000
0.000
0.0
0.0
0.0
Bus3
0.208
96.266
-8.5
0.059
0.029
Bus1
-0.059
-0.029
190.0
90.0
Bus4
6.300
99.408
-5.3
2.102
0.550
Barra_A
-2.102
-0.550
200.3
96.7
Bus5
6.300
99.493
-5.3
Barra_B
6.518
2.078
630.2
95.3
-6.518
-2.078
630.2
95.3
Bus17
Bus6
Bus7
110.000
0.480
85.661
97.699
-1.1
-7.9
VAS-T1
-12.265
-5.789
83.1
90.4
THCMT-0202 A
12.265
5.789
83.1
90.4
CCM-3
-0.060
-0.030
82.3
89.5
0.060
0.030
82.3
89.5
Bus9
Bus8
6.300
99.408
-5.3
2.102
0.773
Barra_A
-2.102
-0.773
206.5
93.9
Bus9
0.208
96.266
-8.5
0.059
0.029
Bus7
-0.059
-0.029
190.0
90.0
Bus10
6.300
99.414
-5.3
2.102
0.550
Barra_B
-2.102
-0.550
200.3
96.7
Bus11
0.480
97.161
-8.0
0.019
0.009
CCM 702
-0.019
-0.009
26.6
90.0
Bus12
110.000
85.661
-1.1
VAS-T3
-12.803
-5.277
84.8
92.5
THCMT-0202 C
12.803
5.277
84.8
92.5
CCM 702
-0.019
-0.009
26.6
90.0
THCMT-0202 C
-6.241
-2.188
607.3
94.4
Bus13
0.480
97.161
-8.0
0.019
0.009
Bus14
6.300
99.800
-4.8
6.241
2.188
607.3
94.4
Bus15
0.480
97.196
-8.0
CCM 702
-0.001
0.000
1.2
90.0
Bus16
0.208
98.306
-9.2
0.070
0.034
CCM 702
-0.070
-0.034
219.8
90.0
Bus17
6.300
99.800
-4.8
THCMT-0202 C
-6.521
-2.137
630.2
95.0
6.521
2.137
630.2
95.0
Bus26
Bus5
Bus18
0.208
98.306
-9.2
0.070
0.034
CCM 702
-0.070
-0.034
219.8
90.0
Bus19
0.480
96.999
-8.3
0.099
0.000
CCM2
-0.099
0.000
122.5
100.0
Bus20
0.208
98.416
-9.1
0.026
0.013
CCM 702
-0.026
-0.013
82.5
90.0
Bus21
0.208
98.306
-9.2
0.070
0.034
CCM 702
-0.070
-0.034
219.8
90.0
Bus22
0.208
99.971
-6.8
0.045
0.022
TGD-VA3-01
-0.045
-0.022
138.8
90.0
Bus23
0.480
98.086
-7.9
CCM-DESCARGADER
CCM1
Tablero Dist. 480V
0.190
0.092
258.4
90.0
-0.362
-0.157
484.0
91.7
0.172
0.066
226.1
93.4
Bus24
6.300
99.414
-5.3
2.102
0.550
Barra_B
-2.102
-0.550
200.3
96.7
Bus25
6.300
99.414
-5.3
2.085
0.855
Barra_B
-2.085
-0.855
207.7
92.5
Bus26
6.300
99.488
-5.3
Barra_A
6.238
2.133
607.3
94.6
Bus14
-6.238
-2.133
607.3
94.6
ECDT-0201
-0.009
-0.004
11.8
89.8
ECDT-0202
0.009
0.004
11.8
89.8
Barra-B
5.227
2.063
509.6
93.0
Bus27
0.480
97.854
-7.9
Bus28
6.300
101.069
-4.6
% Tap
-11.250
-13.750
-12.500
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Voltage
kV
% Mag.
Generation
Ang.
MW
Load
Mvar
MW
Load Flow
Mvar
ID
MW
XFMR
Mvar
Amp
% PF
THCMT-0202 A
-5.227
-2.063
509.6
93.0
Bus29
0.480
96.798
-8.0
0.059
0.013
-0.059
-0.013
75.4
97.7
Bus30
0.480
95.979
-7.6
0.030
0.013
-0.030
-0.013
40.4
91.6
Bus31
0.480
95.979
-7.6
0.030
0.013
-0.030
-0.013
40.4
91.6
Bus32
6.300
101.069
-4.6
7.000
2.841
685.0
92.7
THCMT-0202 A
-7.000
-2.841
685.0
92.7
Barra-A
Bus33
0.480
96.320
-7.9
0.049
0.013
-0.049
-0.013
63.6
96.7
Bus34
0.480
97.929
-7.6
0.001
0.013
-0.001
-0.013
16.1
11.3
Bus67
110.000
85.664
-1.1
Ocensa B2
0.000
0.000
0.0
0.0
Bus84
0.480
95.158
-7.1
220-MCC-20100 Barra A
0.237
0.118
334.1
89.6
-0.237
-0.118
334.1
89.6
Bus88
0.480
93.519
-8.5
0.740
0.370
1063.8
89.4
Bus96
-0.740
-0.370
1063.8
89.4
14.574
7.480
100.4
89.0
Bus95
220-MCC-20100 Barra B
Bus93
115.000
81.940
-1.1
Bus94
-14.574
-7.480
100.4
89.0
Bus94
6.600
91.215
-6.4
Barra A
14.485
5.822
1497.2
92.8
Bus93
-14.485
-5.822
1497.2
92.8
-0.237
-0.121
25.6
89.1
Ocensa B1
Bus95
6.600
91.092
-6.4
Barra A
Bus84
0.237
0.121
25.6
89.1
Bus96
6.600
91.093
-6.4
Barra B
-0.745
-0.406
81.4
87.8
Bus88
0.745
0.406
81.4
87.8
Bus97
6.600
91.085
-6.5
3.372
1.319
Barra A
-3.372
-1.319
347.7
93.1
Bus102
6.600
91.085
-6.5
3.372
1.319
Barra A
-3.372
-1.319
347.7
93.1
Bus105
6.600
91.092
-6.5
3.372
1.319
Barra B
-3.372
-1.319
347.7
93.1
Bus106
6.600
91.092
-6.5
3.372
1.319
Barra B
-3.372
-1.319
347.7
93.1
Bus137
0.480
92.817
-8.7
220-MCC-20200
0.000
0.000
0.0
0.0
Bus138
0.480
92.817
-8.7
220-MCC-20200
0.000
0.000
0.0
0.0
Bus140
0.480
92.817
-8.7
220-MCC-20200
0.000
0.000
0.0
0.0
CCM1
0.480
98.086
-7.9
0.429
-0.008
Bus23
0.362
0.157
484.0
91.7
CCM2
-0.791
-0.150
987.0
98.3
CCM2
0.480
98.086
-7.9
0.568
0.259
Bus19
0.100
0.001
122.5
100.0
TR4-AT
-1.635
-0.501
2096.9
95.6
CCM-3
0.176
0.092
242.9
88.7
CCM1
CCM 701
CCM 702
0.480
0.480
97.197
97.197
-8.0
-8.0
0.803
0.554
0.280
0.175
0.791
0.150
987.0
98.3
T703-AT
-2.020
-0.692
2642.4
94.6
CCM 702
1.217
0.412
1589.9
94.7
Bus13
0.019
0.009
26.6
90.0
Bus11
0.019
0.009
26.6
90.0
% Tap
-10.500
-5.000
-5.000
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Voltage
kV
% Mag.
Generation
Ang.
MW
Load
Mvar
CCM 703
0.480
97.197
-8.0
CCM-3
0.480
98.086
-7.9
MW
Load Flow
Mvar
ID
MW
XFMR
Mvar
Amp
% PF
Bus15
0.001
0.000
1.2
90.0
Bus16
0.071
0.036
98.2
89.1
-3.000
Bus18
0.071
0.036
98.2
89.1
-3.000
Bus20
0.027
0.014
36.8
89.1
-3.000
Bus21
0.071
0.036
98.2
89.1
-3.000
CCM 703
0.385
0.096
490.9
97.0
CCM 701
-1.217
-0.412
1589.9
94.7
0.385
0.096
CCM 702
-0.385
-0.096
490.9
97.0
0.033
0.018
Bus1
0.060
0.030
82.3
89.5
Bus7
0.060
0.030
82.3
89.5
ECDT-0201
0.022
0.014
32.1
84.5
CCM2
-0.176
-0.092
242.9
88.7
CCM-DESCARGADER
0.480
96.790
-8.3
0.188
0.089
Bus23
-0.188
-0.089
258.4
90.3
CCM-VA3-01
0.480
98.326
-6.2
0.181
0.088
TGD-VA3-01
-0.181
-0.088
245.8
89.9
110.000
88.000
0.0
65.830
33.262
14.255
7.658
96.5
88.1
TECA
51.574
25.603
343.4
89.6
0.480
98.019
-7.9
CCM-3
-0.022
-0.014
32.1
84.5
Bus27
0.009
0.004
11.8
89.8
ECDT-0203
0.006
0.005
9.4
81.0
ECDT-0204
0.003
0.002
4.7
81.0
ECDT-0205
0.004
0.003
6.3
81.0
* Cocorna - EPM
ECDT-0201
ECDT-0202
0.208
97.147
-8.2
0.009
0.004
Bus27
-0.009
-0.004
27.1
90.0
ECDT-0203
0.480
97.849
-7.9
0.006
0.004
ECDT-0201
-0.006
-0.004
9.4
81.0
ECDT-0204
0.480
97.981
-7.9
0.003
0.002
ECDT-0201
-0.003
-0.002
4.7
81.0
ECDT-0205
0.480
97.968
-7.9
0.004
0.003
ECDT-0201
-0.004
-0.003
6.3
81.0
Jazmn - MSB
110.000
85.584
-1.2
3.479
2.000
VAS-JAZMIN-A
-3.479
-2.000
24.6
86.7
Ocensa B1
110.000
85.664
-1.1
Bus93
14.574
7.480
100.4
89.0
Ocensa B2
-14.574
-7.480
100.4
89.0
Ocensa B2
110.000
85.664
-1.1
T - L. PTO Boyaca
-14.574
-7.480
100.4
89.0
0.000
0.000
0.0
0.0
14.574
7.480
100.4
89.0
Bus67
Ocensa B1
Palagua - ECP
110.000
85.652
-1.1
0.673
0.326
110.000
87.593
-0.2
-0.673
-0.326
4.6
90.0
Cocorna - EPM
VAS-PALAGUA
-14.219
-7.676
96.8
88.0
B-P.BOYACA 1
14.219
7.676
96.8
88.0
Barra_A
-2.030
-0.803
201.3
93.0
CCM 701
2.030
0.803
201.3
93.0
Bus29
0.060
0.013
75.4
97.6
& B-P.BOYACA 2
T703-AT
6.300
0.480
99.381
98.086
-5.3
-7.9
% Tap
-1.500
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
TECA
Voltage
kV
110.000
% Mag.
87.282
Generation
Ang.
-0.5
MW
Load
Mvar
MW
Load Flow
Mvar
ID
84.661
-3.5
6.961
3.371
TGD-VA3-01
0.480
98.326
-6.2
THCMT-0202 A
6.300
101.069
-4.6
Amp
% PF
0.030
0.013
40.4
91.8
Bus31
0.030
0.013
40.4
91.8
Bus33
0.050
0.013
63.6
96.7
Bus34
0.002
0.013
16.1
11.8
Bus23
-0.172
-0.066
226.1
93.4
-51.388
-25.043
343.8
89.9
44.402
21.200
295.9
90.2
Cocorna - EPM
Teca 13.8 kV
13.800
XFMR
Mvar
Bus30
T - L. Teca
Teca 13.8 kV
MW
6.986
3.843
47.9
87.6
TECA
-6.961
-3.371
382.2
90.0
Barra_B
-0.226
-0.111
307.8
89.8
Bus22
0.045
0.023
62.0
89.6
CCM-VA3-01
0.181
0.088
245.8
89.9
TMOVS-VA3-01
0.000
0.000
0.0
0.0
-12.227
-4.904
1194.5
92.8
Bus32
7.000
2.841
685.0
92.7
93.0
Bus6
Bus28
5.227
2.063
509.6
THCMT-0202 B
6.300
101.119
-1.1
Bus2
0.000
0.000
0.0
0.0
THCMT-0202 C
6.300
99.811
-4.8
Bus14
6.241
2.189
607.3
94.4
Bus17
6.522
2.138
630.2
95.0
Bus12
-12.763
-4.327
1237.4
94.7
VAS-PTO BOYACA
-14.574
-7.480
100.4
89.0
14.574
7.480
100.4
89.0
43.797
20.516
296.3
90.6
-43.797
-20.516
296.3
90.6
0.000
0.000
0.0
0.0
Barra-B
-1.651
-0.612
159.8
93.8
CCM2
1.651
0.612
159.8
93.8
12.534
5.533
83.9
91.5
3.481
1.824
24.1
88.6
VAS-PALAGUA
-16.015
-7.358
108.0
90.9
VAS-JAZMIN-A
-12.534
-5.533
83.9
91.5
12.534
5.533
83.9
91.5
0.673
0.145
4.2
97.8
16.015
7.358
108.0
90.9
-16.688
-7.503
112.1
91.2
T - L. PTO Boyaca
14.574
7.480
100.4
89.0
VAS-PALAGUA
16.688
7.503
112.1
91.2
-31.262
-14.982
212.4
90.2
12.265
5.789
83.1
90.4
T - L. PTO Boyaca
110.000
85.664
-1.1
Ocensa B2
T - L. Teca
110.000
85.664
-1.1
VAS-TECA
TMOVS-VA3-01
0.480
98.326
-6.2
TGD-VA3-01
TR4-AT
6.300
100.977
-4.6
TECA
VAS-JAZMIN-A
110.000
85.664
-1.1
VAS-JAZMIN-B
Jazmn - MSB
VAS-JAZMIN-B
110.000
85.664
-1.1
VAS-PALAGUA
110.000
85.664
-1.1
VAS-T1
Palagua - ECP
VAS-JAZMIN-A
VAS-PTO BOYACA
VAS-PTO BOYACA
110.000
85.664
-1.1
VAS-TECA
VAS-T1
110.000
85.664
-1.1
Bus6
% Tap
-3.000
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Voltage
kV
% Mag.
Generation
Ang.
MW
Load
Mvar
MW
Load Flow
Mvar
ID
VAS-T2
VAS-JAZMIN-B
VAS-T2
VAS-T3
110.000
110.000
85.664
85.664
-1.1
-1.1
Bus2
110.000
85.664
-1.1
% PF
0.269
-0.256
2.3
-72.5
-12.534
-5.533
83.9
91.5
0.000
0.000
0.0
0.0
-0.269
0.256
2.3
-72.5
0.269
-0.256
2.3
-72.5
12.803
5.278
84.8
92.5
-12.534
-5.533
83.9
91.5
Bus12
VAS-T2
-0.269
0.256
2.3
-72.5
VAS-T3
12.534
5.533
83.9
91.5
-43.797
-20.516
296.3
90.6
31.262
14.982
212.4
90.2
VAS-PTO BOYACA
Amp
VAS-T3
T - L. Teca
* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
XFMR
Mvar
VAS-T1
VAS-TECA
VAS-TECA
MW
% Tap
VAS-5209124-11040-ID-ELE-MC-051-1
Anlisis de Cargas
Revisin: 1
Documento No.
VAS-5209124-11040-ID-ELE-MC-051-R1.doc.
1 de 1
Cocorna - EPM
AL
Jazmn - MSB
4%
92 ,7
110 kV
Palagua - ECP
-2,7
5 de
g
26,7 A
86,7%
1%
92,8
110 kV
-2,7
1 de
g
4,8 A
90,0%
0,95 MVA
AL
AL
6 km
397.5-26
0,1318+j0,4842 ohms/1km
170,8 A 446,5 A
90,0%
90,0%
-3 ,3
170,8 A
3 de
g
90,0%
-0,0
7
deg
Trafo Teca
15 MVA
8,5
110/13,8
%Z
kV
0,26974+j0,54136 ohms/1km
6 km
Penguin
411,1 A
90,0%
2%
97,2
9%
99,8
110 kV
51,6 A
87,8%
AL
B-P.BOYACA 2
446,5 A
90,0%
de g
Lump1
10 MVA
PB-13,2
10,5 MVA
2%
92,8
T - L. Teca
Ocensa B2
92,9 A
89,5%
TECA
0,1 %Vd
-0,8
108,8 A
1 de
g
88,0%
-1,5% TapP
Trafo EBSA
30/15/15 MVA
110/34,5/13,2 kV
10/10/10 %Z
T - L. PTO Boyaca
110 kV
0,0 %Vd
AL
1%
98,4
PB-34,5
10,5 MVA
6 km
397.5-26
0,1318+j0,4842 ohms/1km
0,1 %Vd
6,15 km
300-30
0,2092+j0,5276 ohms/1km
0,1318+j0,4842 ohms/1km
4 km
397.5-26
1,6 %Vd
0,26974+j0,54395 ohms/1km
22,1 km
Penguin
B-P.BOYACA 1
2%
34,5 kV
97,2
5,6 %Vd
Palagua
100%
51,2 A0,00
deg
88,4%
276,2 A
89,9%
AL
Jazmn
5,479 MVA
110 kV
435,8 A
88,8%
110 kV
384,6 A
88,9%
Ocensa B1
,82%
185,2 A 92
91,4% -2
110 kV
-2,7
0
,70
deg
AMPLIACIN OCENSA
deg
T - L. Teca
T - L. PTO Boyaca
10 m
36-1/C 750
VAS-PALAGUA
2%
92 ,8
4,4 A
98,0% ,82%
92
110 kV
-2,7
0
103,5 A
90,9%
0,0 %Vd
VAS-TECA
77,4 A
91,6%
110 kV
deg
-2 ,7
0 de
g
SW70
0 A
SW72
0 A
10 m
36-1/C 750
VAS-JAZMIN-A
110 kV
26,1 A
88,6%
107,7 A
91,2%
2%
92 ,8
VAS-PTO BOYACA
-2 ,7
0 de
g
77,4 A
91,6%
10 m
36-1/C 750
10 m
36-1/C 750
77,4 A
2%
91,6% 92 ,8
0,0 %Vd
-2,7
0 de
g
110 kV
SW75
0 A
0,0 %Vd
2%
92 ,8
CT16
VAS-T1
110 kV
2%
92,8
VAS-T2110 kV
-2,7
0 de
g
77,4 A
91,6%
VAS-JAZMIN-B
110 kV
0,0 %Vd
CT22
2%
92,8
2,3 A
-67,8%
CT24
SW80
0 A
2%
92,8
Ocensa B2
-2 ,7
92,9 A
0 de
g 89,5%
92,9 A
89,5%
110 kV
SW88
0 A
SW86
0 A
-2 ,7
0 de
g
110 kV
SW84
0 A
2%
92,8
VAS-T3
-2,7
76,7 A
0 de
g
90,4%
Cuarto Elctrico Vasconia
100 m
3-1/C 500
0,0 %Vd
SW76
0 A
2%
92,8
Ocensa B1
2,3 A -2 ,70
de g
-67,8%
0,0%
CT18
110 kV
CCM 703
-2
78,2
,70 A
92,6%de g
100 m
3-1/C 500
0,0 %Vd
SW79
0 A
100 m
3-1/C 500
0,0 %Vd
SW83
0 A
T2
20 MVA
110/6,6 kV
9,5 %Z
-6,25% TapP
T3
20 MVA
110/6,6 kV
9,5 %Z
-3,75% TapP
-6,25% TapP
NUEVO SW MT
THCMT-0202 A
6,3 kV
3150 A
31,5 kA
THCMT-0202 B
6,3 kV
73 %
100,
3150 A
31,5 kA
1198,6 A
92,8%
687,3 A
92,7%
511,3 A
93,0%
THCMT-0202 C
6,3 kV
3150 A
31,5 kA
03 %
101,
-2,7
0 de
g
0,0%
04%
10 1,
-6,2
9 de
g
1221,7 A
94,8%
599,8 A
94,5%
-6 ,1
4 de
g
621,9 A
95,1%
20 m
18-1/C 500
0,0 %Vd
20 m
18-1/C 500
0,0 %Vd
X7
0,3 %Vd
0,05 ohms
X3
Barra-A
6,3 kV
1200 A
31,5 kA
687,3 A
92,7%
336,3 A
92,7%
175,5 A
92,7%
0,3 %Vd
0,05 ohms
130 m
18-1/C 500
0,1 %Vd
130 m
18-1/C 500
0,1 %Vd
65 %
100,
-6,1
8 de
175,5 A
92,7%
Barra-B
6,3 kV
1200 A
31,5 kA
511,3 A
93,0%
67%
10 0,
175,5 A
92,7%
175,5 A
92,7%
160,3 A
93,7%
150 m
18-1/C 500
0,1 %Vd
CT14
150 m
18-1/C 500
0,1 %Vd
-5% TapP
TR-3
1,6 MVA
5,9 %Z
6,3/0,48 kV
0,2 %Vd
BPC6430
2500 HP
0,2 %Vd
BPC6420
2500 HP
0,2 %Vd
BPC6440
2500 HP
0,2 %Vd
197,7 A
96,8%
Vasconia III
65 %
100,
621,9 A
95,4%
203,7 A
94,0%
197,7 A
96,8%
CT12
Relay10
Relay3
Relay11
27,7 A
A
206,3
0,0%
92,8%
30 m
1-3/C 350
0,0 %Vd
Relay12
197,6 A
96,8%
CT9
204,9 A
92,6%
CAP2
300 kvar
27,7 A
A
206,3
0,0%
92,8%
CAP4
300 kvar
Relay9
27,7 A
A
206,3
0,0%
92,8%
CAP5
300 kvar
BPC-704
3000 HP
BPC-703
3000 HP
0,2 %Vd
G1
500 kW
0,48 kV
T7
800 kVA
5,75 %Z
6,3/0,48 kV
30 m
1-3/C 350
TGD-VA3-01
-2,5% TapP
T704
2,5 MVA
6,3/0,48
5,75 %Z kV
BPC-705
3000 HP
Relay5
Relay4
CAP7
300 kvar
0,1 %Vd
CT6
27,7 A
A
216,8
0,0%
87,5%
CAP6
300 kvar
BPC-702
3000 HP
0,2 %Vd
-6 ,8
0 de
g
Relay8CT10
23,3 A
89,2%
CT5
CT13
27,7 A
A
214,8
0,0%
89,1%
BPC-701
T703
3000 HP
2,5 MVA
6,3/0,48 kV 0,2 %Vd
5,75 %Z
TR-4
1,6 MVA
6,3/0,48 kV
5,9 %Z
0,2 %Vd
Barra_B
6,3 kV
1500 A
25 kA
30 m
3-1/C 4/0
0,0 %Vd
BPC6410
2500 HP
Barra_A
6,3 kV
64%
1500 A 10 0,
25 kA-6,7 8
deg
199,2 A
93,1%
CT11
BPC6450
5000 HP
Relay13
599,8 A
94,8%
-6 ,1
7 de
g
CT4
30 m
3-1/C 4/0
7%
99 ,5
0,48 kV
242,7 A
89,9%
0,2 %Vd
62,5 A
89,6%
Centro de Generacin
GD 701
0,48 kV
GD-702
0,48 kV
CCM-VA3-01
0,48 kV
4000 A
65 kA
GD-703
0,48 kV
1100 kW
1100 kW
1100 kW
190 m
15-1/C 750
190 m
15-1/C 750
190 m
15-1/C 750
7%
99 ,5 0,48 kV
7%
99 ,5
-7 ,6 4000 A
465
degkA
-7 ,6
4 de
g
MOV-5
4x1 HP
1,1 %Vd
4000 A
47,9 A
92,0%
BM-704
100 HP
BM-701
125 HP
0,5 %Vd
0,5 %Vd
7%
98,4
-9 ,3
8
2614,2 A
94,7%
55 kA
60,8 A
91,4%
242,7 A
91,6%
BB-701
250 HP
0,9 %Vd
0,7 A
81,0%
TA-601
1 HP
242,9 A
91,6%
BB-704
250 HP
0,0 %Vd
96,7 A
91,7%
BT-701
200 HP
1,0 %Vd
242,6 A
91,6%
BB-706
250 HP
0,3 %Vd
0,9 %Vd
CCM 702
0,48 kV
31,5 A
89,3%
31,8 A
89,3%
AGT-717
40 HP
AGT-707
30 HP
AGT-710
30 HP
6,4 %Vd
1,7 %Vd
2,6 %Vd
98,3 A
0,0%
AGT-714 BDC-701
40 HP
83 kvar
0,0 %Vd
31,6 A
89,3%
1,8 A
83,7%
AGT-701
30 HP
AGT-704
30 HP
2,2 %Vd
0,0 %Vd
Mtr25
3 HP
Cable38
48,2 A
92,0%
BM-705
100 HP
61,5 A
91,5%
BM-702
125 HP
29,8 A
90,8%
CO-702
60 HP
1,1 %Vd
1,5 %Vd
0,7 %Vd
CCM1
0,48 kV
31,7 A
89,3%
AGT-718
40 HP
AGT-713
30 HP
0,0 %Vd
2,3 %Vd
145,5 A
91,8%
BA-701
300 HP
31,6 A
89,3%
247,8 A
91,3%
10,7 A
88,2%
10,8 A
88,4%
2,9 A
84,9%
1,9 A
82,0%
247,3 A
89,4%
485,5 A
91,7%
26,6 A
88,8%
26,6 A
88,8%
3,7 A
83,7%
19 A
88,2%
PG
17,5 HP
0,2 %Vd
26,8 A
90,0%
AGT-711
30 HP
AGT-715
40 HP
2,2 %Vd
0,0 %Vd
1,9 A
82,0%
5,6 A
86,7%
1,0 %Vd
CCM2
0,48 kV
3%
97,7
262,9 A
-0,3%
BX-702
3 HP
Cable5
0,0 %Vd
31,8 A
89,3%
30 m
6-1/C 4/0
AGT-705
30 HP
31,5 A
89,3%
AG-708
30 HP
26,8 A
1,0 %Vd
1,7 %Vd
31,6 A
89,3%
31,6 A
89,3%
31,8 A
89,3%
98,5 A
-0,4%
AGT-712
30 HP
AGT-719
40 HP
AGT-703
30 HP
AGT-706
30 HP
AGT-709
30 HP
2,2 %Vd
0,0 %Vd
2,2 %Vd
2,6 %Vd
0,0 %Vd
96,7 A
91,7%
BDC-703
83 kvar
BT-702
200 HP
-0,2 %Vd
0,3 %Vd
30 m
6-1/C 4/0
AGT-702
30 HP
8,2 A
87,9%
BE-701
15 HP
13,2 A
88,8%
BU-712
25 HP
13,1 A
88,8%
BU-715
25 HP
15,6 A
89,2%
1,2 A
90,0%
30 m
6-1/C 4/0
BS-713
30 HP
26,8 A
90,0%
0,0 %Vd
PB-702
45 kVA
2,6 %Vd
1,7 %Vd
99 A
89,1%
DR
1,2 A
90,0%
0,0 %Vd
PB-701
45 kVA
2,2 %Vd
1,7 %Vd
0,8 %Vd
0,7 %Vd
1,2 %Vd
99 A
89,1%
-3% TapP
T 705
113 kVA
DR
4 %Z 0,48/0,208
221,5 A
90,0%
90,0%
0,0 %Vd
TAE 701
1 kVA
TAS-702
80 kVA
kV
98,3 A
0,0%
-3% TapP
T 706
113 kVA
4 %Z 0,48/0,208 BDC-702
kV
83 kvar
221,5 A
90,0%
242,8 A
88,7%
8,2 A
87,6%
DR
CO-703
15 HP
0,6 %Vd
Lump11
80 kVA
0,0 %Vd
-0,3 %Vd
BB-6403
250 HP
0,0 %Vd
2,2 %Vd
6441-D
20 HP
0,2 %Vd
6441-C
20 HP
0,8 %Vd
6441-B
5 HP
LUB-6441 BB-6402
1,47 HP
250 HP
0,2 %Vd
0,1 %Vd
2,0 %Vd
1,1 %Vd
Bus23
0,48 kV
3%
97,7
247,9 A
91,3%
13,2 A
88,8%
26,6 A
88,8%
247,9 A
91,3%
10,8 A
88,4%
10,8 A
88,4%
2,9 A
84,9%
196,6 A
91,4%
0,3 A
0,0%
0,3 A
0,0%
0,3 A
0,0%
0,3 A
0,0%
76,6 A
90,4%
0,1 %Vd
0,6 %Vd
CO-601
25 HP
2,2 %Vd
0,6 %Vd
1,1 %Vd
2,2 %Vd
0,0 %Vd
6431C
20 HP
0,8 %Vd
0,8 %Vd
6431B
5 HP
0,2 %Vd
BB-5402
200 HP
BL-6420
0,5 HP
BL-6410
0,5 HP
TFLA 15
0,46 HP
TFLB 15
0,46 HP
1,2 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
CCM-3
0,0%
5,6 A
86,7%
5,1 A -9 122,8 A
,50
86,3%
100,0%
de g
76,4 A
90,4%
13,2 A
88,8%
0,3 A
0,0%
0,6 A
100,0%
2,9 A
84,9%
15,6 A
89,2%
82,2 A
89,5%
82,2 A
89,5%
9,4 A
87,9%
1,3 A
82,7%
3%
96,4
4,3 A -9,92
deg
85,9%
PB-6001
BD-9610
4x50 HP
BD-9606
3x50 HP
BD-9603
3x50 HP
BD-VERT
7,5 HP
0,3 %Vd
0,3 %Vd
0,1 %Vd
0,0 %Vd
122,8 A
100,0%
TDA 604
10 HP
0,6 %Vd
Mtr14
9 HP
1,1 %Vd
3%
97 ,7
dcLump3
226,6 A-9
,50
93,4%
deg
300 m
9-1/C 500
1,3 %Vd
102,1 A
90,4%
0,2 %Vd
BB-6404
250 HP
3%
97 ,7 0,48 kV
259,4 A
90,0%
CCM-DESCARGADER
0,48 kV
1,1 %Vd
BB-707
250 HP
BB-705
250 HP
BB-703
250 HP
0,0 %Vd
0,0 %Vd
0,1 %Vd
185 m
12-1/C 500
0,0 %Vd
DR
30 m
3-1/C 1/0
30 m
3-1/C 1/0
0,0%
0,3 A
0,0%
2,9 A
84,9%
Charger1
10 kVA/7,65 kW
MOV2
1 HP
T 602
T5
0,0 %Vd
0,4 %Vd
100
kVA
100
%Vd
kVA
DR kV 0,4
2,6 %Z
0,48/0,208
2,60,48/0,208
%Z
kV
ESPUMA
20 HP
PGRU
17,5 HP
INTERC
2 HP
MOV4
1 HP
0,0 %Vd
TFL 05
0,46 HP
0,0 %Vd
dcLump1
0,0 %Vd
MOV6
1 HP
-9,5
0 de
g
15 m
3-1/C 2/0
1225331
5 HP
0,0 %Vd
32,1 A
84,5%
0,1 %Vd
0,1 %Vd
ECDT-0201
0,48 kV
3000 A
40 kA
7%
97 ,6
11,7 A
89,8%
9,5 A
81,0%
4,7 A
81,0%
6,3 A
81,0%
-9 ,5
0 de
g
CCM 703
189,6 A
90,0%
Lump5
70 kVA
189,6 A
90,0%
100 m
3-1/C 2/0
0,2 %Vd
Lump7
70 kVA
DS
ECDT-0201
ECDT-0202
0,208 kV
225 A
10 kA
ECDT-0201
Cable42
Cable48
Cable52
T4
30 kVA
2,6 %Z
0,48/0,208 kV
27 A
90,0%
%
96 ,8
27 A
90,0%
-9 ,7
7 de
g
ECDT-0201
Lump2
10 kVA
120 m
3-1/C 500
270 m
3-1/C 500
0,1 %Vd
ECDT-0205
0,48 kV
3000 A
40 kA
120 m
3-1/C 500
0,2 %Vd
2%
97 ,6
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
-9,5
1
ECDT-0203
0,48 kV
3000 A
40 kA
0,0 %Vd
%
97 ,5
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
deg
-9,5
4
ECDT-0204
0,48 kV
3000 A
40 kA
3%
97 ,6
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
deg
-9,5
1
83,1 A
90,0%
deg
BM-706
125 HP
7%
98 ,4
0,5 %Vd
deg
99 A
89,1%
-3% TapP
T 707
45 kVA
DR
4 %Z 0,48/0,208
kV
-9,3
8 de
g
60,9 A
91,4%
0,9 %Vd
37,1 A
89,1%
CARGA
30 kVA
230 m
6-1/C 4/0
BB-5401
100 HP
242,5 A
91,6%
-9,3
8
31,6 A
89,3%
2103,9 A
95,6%
990,8 A
98,2%
-9,5
0 de
g
26,8 A
90,0%
Charger3
10 kVA/7,65 kW
INCENDIO CAP1
250 HP
223 kvar
0,0 %Vd
7%
98,4
1,8 A
83,7%
BB-708
300 HP
0,2 %Vd
TSA-VA3-01
50 kVA
CCM 703
0,48 kV
deg
1575,9 A
94,8%
484 A
97,1%
242,8 A
91,6%
BB-702
250 HP
43,3 A
90,2%
-3% TapP
TR-VA3
75 kVA
0,48/0,208
2,6 %Z
kV
139,8 A
90,0%
MX-01A
6x40 HP
CCM 701
0,48 kV
DR
TMOVS-VA3-01
242,7 A
89,9%
-3% TapP
T 709
113 kVA
4 %Z 0,48/0,208 kV
221,5 A
90,0%
CARGA1
80 kVA
BB-709
300 HP
0,0 %Vd
-7 ,6
4 de
g
VAS-5209124-11040-ID-ELE-MC-051-1
Anlisis de Cargas
Revisin: 1
Documento No.
VAS-5209124-11040-ID-ELE-MC-051-R1.doc.
1 de 1
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
Voltage
Generation
Load
Load Flow
XFMR
kV
% Mag.
220-MCC-20100 Barra A
0.480
101.140
-7.8
0.262
0.130
Bus84
-0.262
-0.130
347.6
89.6
220-MCC-20100 Barra B
0.480
102.052
-9.2
0.032
0.017
Bus88
-0.864
-0.430
1137.3
89.5
220-MCC-20200
0.832
0.413
1095.0
89.6
Barra 220-DP-20300
0.000
0.000
0.0
0.0
ID
220-MCC-20200
0.480
101.440
Ang.
-9.5
MW
Mvar
MW
Mvar
0.829
ID
0.407
220-MCC-20100 Barra B
-0.407
1095.0
89.7
0.000
0.0
0.0
Bus140
0.000
0.000
0.0
0.0
Bus137
0.000
0.000
0.0
0.0
102.052
-9.2
220-MCC-20100 Barra B
6.300
100.640
-6.8
Bus26
Barra A
6.600
99.487
-6.8
-7.2
% PF
0.000
0.208
100.647
Amp
-0.829
Barra_A
6.300
Mvar
Bus138
Barra 220-DP-20300
Barra_B
MW
0.000
0.000
0.0
0.0
-6.241
-2.106
599.8
94.8
T703-AT
2.037
0.798
199.2
93.1
Bus4
2.102
0.542
197.7
96.8
Bus8
2.102
0.766
203.7
94.0
Bus5
-6.516
-2.048
621.9
95.4
TGD-VA3-01
0.228
0.116
23.3
89.2
Bus10
2.102
0.542
197.7
96.8
Bus25
2.085
0.848
204.9
92.6
Bus24
2.102
0.542
197.6
96.8
Bus94
-14.622
-5.882
1385.8
92.8
Bus95
0.263
0.134
25.9
89.1
Bus97
3.372
1.319
318.4
93.1
Bus102
3.372
1.319
318.4
93.1
Barra B
7.615
3.110
723.2
92.6
Barra-A
6.300
100.653
-6.2
6.997
2.833
Bus32
-6.997
-2.833
687.3
92.7
Barra B
6.600
99.487
-7.2
Bus96
0.870
0.472
87.1
87.9
Bus105
3.372
1.319
318.4
93.1
Bus106
3.372
1.319
318.4
93.1
Barra A
-7.615
-3.110
723.2
92.6
Barra-B
B-P.BOYACA 1
6.300
34.500
100.674
97.218
-6.2
-3.3
3.575
8.931
1.446
4.326
TR4-AT
1.650
0.614
160.3
93.7
Bus28
-5.225
-2.061
511.3
93.0
B-P.BOYACA 2
-8.931
-4.326
170.8
90.0
-8.931
-4.326
446.5
90.0
-0.060
-0.030
82.2
89.5
0.060
0.030
82.2
89.5
13.200
97.218
-3.3
8.931
4.326
Bus1
0.480
97.349
-9.5
CCM-3
Bus3
% Tap
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Bus2
Voltage
kV
% Mag.
110.000
92.824
Generation
Ang.
-2.7
MW
Load
Mvar
0
MW
0
Load Flow
Mvar
ID
0
MW
XFMR
Mvar
Amp
% PF
VAS-T2
0.000
0.000
0.0
THCMT-0202 B
0.000
0.000
0.0
0.0
0.0
Bus3
0.208
95.918
-10.1
0.059
0.029
Bus1
-0.059
-0.029
189.6
90.0
Bus4
6.300
100.640
-6.8
2.102
0.542
Barra_A
-2.102
-0.542
197.7
96.8
Bus5
6.300
100.725
-6.7
Barra_B
6.519
2.056
621.9
95.4
-6.519
-2.056
621.9
95.4
Bus17
Bus6
Bus7
110.000
0.480
92.821
97.349
-2.7
-9.5
VAS-T1
-12.265
-5.797
76.7
90.4
THCMT-0202 A
12.265
5.797
76.7
90.4
CCM-3
-0.060
-0.030
82.2
89.5
0.060
0.030
82.2
89.5
Bus9
Bus8
6.300
100.640
-6.8
2.102
0.766
Barra_A
-2.102
-0.766
203.7
94.0
Bus9
0.208
95.918
-10.1
0.059
0.029
Bus7
-0.059
-0.029
189.6
90.0
Bus10
6.300
100.647
-6.8
2.102
0.542
Barra_B
-2.102
-0.542
197.7
96.8
Bus11
0.480
98.429
-9.4
0.020
0.010
CCM 702
-0.020
-0.010
26.8
90.0
Bus12
110.000
92.821
-2.7
VAS-T3
-12.809
-5.208
78.2
92.6
THCMT-0202 C
12.809
5.208
78.2
92.6
CCM 702
-0.020
-0.010
26.8
90.0
THCMT-0202 C
-6.247
-2.167
599.8
94.5
Bus13
0.480
98.429
-9.4
0.020
0.010
Bus14
6.300
101.025
-6.3
6.247
2.167
599.8
94.5
Bus15
0.480
98.464
-9.4
CCM 702
-0.001
0.000
1.2
90.0
Bus16
0.208
99.599
-10.6
0.072
0.035
CCM 702
-0.072
-0.035
221.5
90.0
Bus17
6.300
101.025
-6.3
THCMT-0202 C
-6.522
-2.114
621.9
95.1
6.522
2.114
621.9
95.1
Bus26
Bus5
Bus18
0.208
99.599
-10.6
0.072
0.035
CCM 702
-0.072
-0.035
221.5
90.0
Bus19
0.480
96.645
-9.9
0.099
0.000
CCM2
-0.099
0.000
122.8
100.0
Bus20
0.208
99.710
-10.5
0.027
0.013
CCM 702
-0.027
-0.013
83.1
90.0
Bus21
0.208
99.599
-10.6
0.072
0.035
CCM 702
-0.072
-0.035
221.5
90.0
Bus22
0.208
101.240
-8.2
0.046
0.022
TGD-VA3-01
-0.046
-0.022
139.8
90.0
Bus23
0.480
97.735
-9.5
CCM-DESCARGADER
CCM1
Tablero Dist. 480V
0.190
0.092
259.4
90.0
-0.362
-0.157
485.5
91.7
0.172
0.066
226.6
93.4
Bus24
6.300
100.647
-6.8
2.102
0.542
Barra_B
-2.102
-0.542
197.6
96.8
Bus25
6.300
100.647
-6.8
2.085
0.848
Barra_B
-2.085
-0.848
204.9
92.6
Bus26
6.300
100.719
-6.7
Barra_A
6.244
2.113
599.8
94.7
Bus14
-6.244
-2.113
599.8
94.7
ECDT-0201
-0.009
-0.004
11.7
89.8
ECDT-0202
0.009
0.004
11.7
89.8
Barra-B
5.227
2.065
511.3
93.0
Bus27
0.480
97.503
-9.5
Bus28
6.300
100.734
-6.1
% Tap
-3.750
-6.250
-6.250
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Voltage
kV
% Mag.
Generation
Ang.
MW
Load
Mvar
MW
Load Flow
Mvar
ID
MW
XFMR
Mvar
Amp
% PF
THCMT-0202 A
-5.227
-2.065
511.3
93.0
Bus29
0.480
96.443
-9.6
0.059
0.013
-0.059
-0.013
75.5
97.7
Bus30
0.480
95.622
-9.2
0.029
0.013
-0.029
-0.013
40.5
91.6
Bus31
0.480
95.622
-9.2
0.029
0.013
-0.029
-0.013
40.5
91.6
Bus32
6.300
100.734
-6.1
7.000
2.841
687.3
92.7
THCMT-0202 A
-7.000
-2.841
687.3
92.7
Barra-A
Bus33
0.480
95.964
-9.5
0.049
0.013
-0.049
-0.013
63.8
96.7
Bus34
0.480
97.577
-9.2
0.001
0.013
-0.001
-0.013
16.2
11.3
Bus67
110.000
92.824
-2.7
Ocensa B2
0.000
0.000
0.0
0.0
Bus84
0.480
101.277
-7.9
220-MCC-20100 Barra A
0.262
0.130
347.6
89.6
-0.262
-0.130
347.6
89.6
Bus88
0.480
102.193
-9.2
0.865
0.431
1137.3
89.5
Bus96
-0.865
-0.431
1137.3
89.5
14.711
7.318
92.9
89.5
Bus95
220-MCC-20100 Barra B
Bus93
115.000
88.788
-2.7
Bus94
Ocensa B1
-14.711
-7.318
92.9
89.5
Bus94
6.600
99.597
-7.2
Barra A
14.634
5.898
1385.8
92.8
Bus93
-14.634
-5.898
1385.8
92.8
-0.263
-0.134
25.9
89.1
Bus95
6.600
99.483
-7.2
Barra A
Bus84
0.263
0.134
25.9
89.1
Bus96
6.600
99.483
-7.2
Barra B
-0.870
-0.472
87.1
87.9
Bus88
0.870
0.472
87.1
87.9
Bus97
6.600
99.476
-7.2
3.372
1.319
Barra A
-3.372
-1.319
318.4
93.1
Bus102
6.600
99.476
-7.2
3.372
1.319
Barra A
-3.372
-1.319
318.4
93.1
Bus105
6.600
99.483
-7.2
3.372
1.319
Barra B
-3.372
-1.319
318.4
93.1
Bus106
6.600
99.483
-7.2
3.372
1.319
Barra B
-3.372
-1.319
318.4
93.1
Bus137
0.480
101.440
-9.5
220-MCC-20200
0.000
0.000
0.0
0.0
Bus138
0.480
101.440
-9.5
220-MCC-20200
0.000
0.000
0.0
0.0
Bus140
0.480
101.440
-9.5
220-MCC-20200
0.000
0.000
0.0
0.0
CCM1
0.480
97.735
-9.5
0.429
-0.006
Bus23
0.362
0.157
485.5
91.7
CCM2
-0.791
-0.151
990.8
98.2
CCM2
0.480
97.735
-9.5
0.569
0.259
Bus19
0.100
0.001
122.8
100.0
TR4-AT
-1.634
-0.502
2103.9
95.6
CCM-3
0.175
0.091
242.8
88.7
CCM1
CCM 701
CCM 702
0.480
0.480
98.466
98.466
-9.4
-9.4
0.803
0.554
0.278
0.173
0.791
0.151
990.8
98.2
T703-AT
-2.026
-0.689
2614.2
94.7
CCM 702
1.223
0.411
1575.9
94.8
Bus13
0.020
0.010
26.8
90.0
Bus11
0.020
0.010
26.8
90.0
% Tap
-10.500
-2.500
-5.000
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Voltage
kV
% Mag.
Generation
Ang.
MW
Load
Mvar
CCM 703
0.480
98.466
-9.4
CCM-3
0.480
97.735
-9.5
MW
Load Flow
Mvar
ID
MW
XFMR
Mvar
Amp
% PF
Bus15
0.001
0.000
1.2
90.0
Bus16
0.072
0.037
99.0
89.1
-3.000
Bus18
0.072
0.037
99.0
89.1
-3.000
Bus20
0.027
0.014
37.1
89.1
-3.000
Bus21
0.072
0.037
99.0
89.1
-3.000
CCM 703
0.385
0.094
484.0
97.1
CCM 701
-1.223
-0.411
1575.9
94.8
0.385
0.094
CCM 702
-0.385
-0.094
484.0
97.1
0.033
0.018
Bus1
0.060
0.030
82.2
89.5
Bus7
0.060
0.030
82.2
89.5
ECDT-0201
0.022
0.014
32.1
84.5
CCM2
-0.175
-0.091
242.8
88.7
CCM-DESCARGADER
0.480
96.433
-9.9
0.188
0.089
Bus23
-0.188
-0.089
259.4
90.3
CCM-VA3-01
0.480
99.567
-7.6
0.181
0.088
TGD-VA3-01
-0.181
-0.088
242.7
89.9
110.000
100.000
0.0
73.724
38.177
65.106
33.621
384.6
88.9
0.480
97.667
-9.5
* Cocorna - EPM
ECDT-0201
TECA
8.619
4.556
51.2
88.4
CCM-3
-0.022
-0.014
32.1
84.5
Bus27
0.009
0.004
11.7
89.8
ECDT-0203
0.006
0.005
9.5
81.0
ECDT-0204
0.003
0.002
4.7
81.0
ECDT-0205
0.004
0.003
6.3
81.0
ECDT-0202
0.208
96.798
-9.8
0.008
0.004
Bus27
-0.008
-0.004
27.0
90.0
ECDT-0203
0.480
97.496
-9.5
0.006
0.004
ECDT-0201
-0.006
-0.004
9.5
81.0
ECDT-0204
0.480
97.629
-9.5
0.003
0.002
ECDT-0201
-0.003
-0.002
4.7
81.0
ECDT-0205
0.480
97.616
-9.5
0.004
0.003
ECDT-0201
-0.004
-0.003
6.3
81.0
Jazmn - MSB
110.000
92.737
-2.8
4.085
2.348
VAS-JAZMIN-A
-4.085
-2.348
26.7
86.7
Ocensa B1
110.000
92.824
-2.7
Bus93
14.711
7.318
92.9
89.5
Ocensa B2
-14.711
-7.318
92.9
89.5
Ocensa B2
110.000
92.824
-2.7
T - L. PTO Boyaca
-14.711
-7.318
92.9
89.5
0.000
0.000
0.0
0.0
14.711
7.318
92.9
89.5
Bus67
Ocensa B1
Palagua - ECP
110.000
92.812
-2.7
0.760
0.368
110.000
98.414
-0.8
VAS-PALAGUA
-0.760
-0.368
4.8
90.0
-64.534
-32.319
384.9
89.4
T - L. PTO Boyaca
46.585
22.629
276.2
89.9
B-P.BOYACA 1
17.949
9.690
108.8
88.0
Barra_A
-2.036
-0.797
199.2
93.1
CCM 701
2.036
0.797
199.2
93.1
Cocorna - EPM
& B-P.BOYACA 2
T703-AT
6.300
100.613
-6.8
% Tap
-1.500
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Tablero Dist. 480V
TECA
Voltage
kV
0.480
% Mag.
97.735
Generation
Ang.
-9.5
MW
Load
Mvar
0
MW
0
Load Flow
Mvar
ID
0
110.000
99.888
-0.1
Teca 13.8 kV
13.800
97.077
-2.9
8.585
4.158
TGD-VA3-01
0.480
99.567
-7.6
6.300
100.734
-6.1
XFMR
Mvar
Amp
% PF
Bus29
0.060
0.013
75.5
97.6
Bus30
0.030
0.013
40.5
91.8
Bus31
0.030
0.013
40.5
91.8
96.7
Bus33
0.050
0.013
63.8
Bus34
0.002
0.013
16.2
11.8
Bus23
-0.172
-0.066
226.6
93.4
Cocorna - EPM
-8.615
-4.704
51.6
87.8
Teca 13.8 kV
THCMT-0202 A
MW
8.615
4.704
51.6
87.8
TECA
-8.585
-4.158
411.1
90.0
Barra_B
-0.227
-0.111
305.2
89.8
Bus22
0.046
0.023
62.5
89.6
CCM-VA3-01
0.181
0.088
242.7
89.9
TMOVS-VA3-01
0.000
0.000
0.0
0.0
-12.227
-4.906
1198.6
92.8
Bus32
7.000
2.841
687.3
92.7
93.0
Bus6
Bus28
5.227
2.065
511.3
THCMT-0202 B
6.300
101.033
-2.7
Bus2
0.000
0.000
0.0
0.0
THCMT-0202 C
6.300
101.036
-6.3
Bus14
6.247
2.168
599.8
94.5
Bus17
6.523
2.115
621.9
95.1
Bus12
-12.770
-4.282
1221.7
94.8
29.921
13.304
185.2
91.4
-44.632
-20.622
278.0
90.8
14.711
7.318
92.9
89.5
0.0
T - L. PTO Boyaca
110.000
92.824
-2.7
VAS-PTO BOYACA
Puerto Boyac - EBSA
Ocensa B2
T - L. Teca
110.000
92.824
-2.7
VAS-TECA
0.000
0.000
0.0
TMOVS-VA3-01
0.480
99.567
-7.6
TGD-VA3-01
0.000
0.000
0.0
0.0
TR4-AT
6.300
100.641
-6.2
Barra-B
-1.650
-0.614
160.3
93.7
CCM2
1.650
0.614
160.3
93.7
12.537
5.503
77.4
91.6
4.087
2.142
26.1
88.6
VAS-PALAGUA
-16.624
-7.645
103.5
90.9
VAS-JAZMIN-A
-12.537
-5.503
77.4
91.6
12.537
5.503
77.4
91.6
0.760
0.156
4.4
98.0
16.624
7.645
103.5
90.9
VAS-PTO BOYACA
-17.384
-7.801
107.7
91.2
T - L. PTO Boyaca
VAS-JAZMIN-A
110.000
92.824
-2.7
VAS-JAZMIN-B
Jazmn - MSB
VAS-JAZMIN-B
110.000
92.824
-2.7
VAS-PALAGUA
110.000
92.824
-2.7
VAS-T1
Palagua - ECP
VAS-JAZMIN-A
VAS-PTO BOYACA
110.000
92.824
-2.7
-29.921
-13.304
185.2
91.4
VAS-PALAGUA
17.384
7.801
107.7
91.2
VAS-TECA
12.537
5.503
77.4
91.6
% Tap
-3.000
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
VAS-T1
Voltage
kV
% Mag.
110.000
92.824
Generation
Ang.
-2.7
MW
Load
Mvar
0
MW
0
Load Flow
Mvar
ID
0
Bus6
VAS-T2
VAS-JAZMIN-B
VAS-T2
110.000
92.824
-2.7
Bus2
VAS-T1
VAS-T3
VAS-T3
110.000
92.824
-2.7
Bus12
VAS-TECA
VAS-TECA
110.000
92.824
-2.7
Amp
% PF
12.265
5.798
76.7
90.4
0.272
-0.295
2.3
-67.8
-12.537
-5.503
77.4
91.6
0.000
0.000
0.0
0.0
-0.272
0.295
2.3
-67.8
0.272
-0.295
2.3
-67.8
12.809
5.209
78.2
92.6
-12.537
-5.503
77.4
91.6
-0.272
0.295
2.3
-67.8
VAS-T3
12.537
5.503
77.4
91.6
0.000
0.000
0.0
0.0
-12.537
-5.503
77.4
91.6
VAS-PTO BOYACA
XFMR
Mvar
VAS-T2
T - L. Teca
* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
MW
% Tap
VAS-5209124-11040-ID-ELE-MC-051-1
Anlisis de Cargas
Revisin: 1
Documento No.
VAS-5209124-11040-ID-ELE-MC-051-R1.doc.
1 de 1
Cocorna - EPM
AL
Jazmn - MSB
%
97 ,8
110 kV
Palagua - ECP
-0,9
7 de
g
28,1 A
86,7%
8%
97,8
110 kV
AL
172,8 A 451,6 A
90,0%
90,0%
-2 ,7
172,8 A
4 de
g
90,0%
PB-34,5
10,5 MVA
6 km
397.5-26
0,1318+j0,4842 ohms/1km
4%
99,3
110 kV
-0,4
3
51,4 A
87,8%
deg
0,26974+j0,54136 ohms/1km
6 km
Penguin
409,8 A
90,0%
AL
3%
98,3
Lump1
10 MVA
PB-13,2
10,5 MVA
%
97,9
T - L. Teca
Ocensa B2
87,8 A
89,6%
TECA
0,7 %Vd
265,9 A
90,6%
deg
Trafo Teca
15 MVA
8,5
110/13,8
%Z
kV
B-P.BOYACA 2
451,6 A
90,0%
T - L. PTO Boyaca
110 kV
0,0 %Vd
0,1 %Vd
-0,2
2
-1,5% TapP
Trafo EBSA
30/15/15 MVA
110/34,5/13,2 kV
10/10/10 %Z
0,26974+j0,54395 ohms/1km
22,1 km
Penguin
B-P.BOYACA 1
3%
34,5 kV
98,3
Palagua
6 km
397.5-26
0,1318+j0,4842 ohms/1km
AL
4%
99,5
0,5 %Vd
0,95 MVA
AL
6,15 km
300-30
0,2092+j0,5276 ohms/1km
0,1318+j0,4842 ohms/1km
4 km
397.5-26
110 A
88,0%
AL
Jazmn
5,479 MVA
110 kV
100%
316,8 0,
A 00
deg
90,0%
-0,9
3 de
g
4,9 A
90,0%
426,4 A
89,5%
110 kV
109,7 A
88,1%
Ocensa B1
%
97,9
266,4 A
90,8%
110 kV
-0,9
2 de
g
-0,9
2
AMPLIACIN OCENSA
deg
T - L. Teca
T - L. PTO Boyaca
10 m
36-1/C 750
VAS-PALAGUA
%
97 ,9
4,5 A
98,1% ,9%
97
110 kV
-0,9
2
100,9 A
90,8%
VAS-TECA
193 A
90,5%
deg
0,0 %Vd
73,4 A
91,6%
110 kV
-0 ,9
2 de
g
SW70
0 A
SW72
0 A
10 m
36-1/C 750
VAS-JAZMIN-A
110 kV
27,5 A
88,6%
105,3 A
91,2%
%
97 ,9
10 m
36-1/C 750
87,8 A
89,6%
0,0 %Vd
VAS-PTO BOYACA
-0 ,9
2 de
g
73,4 A
91,6%
10 m
36-1/C 750
%
97 ,9
-0,9
2 de
g
110 kV
SW75
0 A
0,0 %Vd
%
97 ,9
CT16
VAS-T1
110 kV
%
97,9
VAS-T2110 kV
-0,9
2 de
g
73,4 A
91,6%
VAS-JAZMIN-B
110 kV
0,0 %Vd
CT22
%
97,9
2,2 A
-67,6%
CT24
SW80
0 A
%
97,9
Ocensa B2
-0 ,9
87,8 A
2 de
g 89,6%
87,8 A
89,6%
110 kV
SW88
0 A
SW86
0 A
-0 ,9
2 de
g
110 kV
SW84
0 A
%
97,9
VAS-T3
-0,9
72,7 A
2 de
g
90,4%
Cuarto Elctrico Vasconia
100 m
3-1/C 500
0,0 %Vd
SW76
0 A
%
97,9
Ocensa B1
2,2 A -0 ,92
de g
-67,6%
0,0%
CT18
110 kV
CCM 703
-0
74,1
,92 A
92,7%de g
100 m
3-1/C 500
0,0 %Vd
SW79
0 A
100 m
3-1/C 500
0,0 %Vd
SW83
0 A
T2
20 MVA
110/6,6 kV
9,5 %Z
-1,25% TapP
T3
20 MVA
110/6,6 kV
9,5 %Z
2,5% TapP
-1,25% TapP
NUEVO SW MT
THCMT-0202 A
6,3 kV
3150 A
31,5 kA
THCMT-0202 B
6,3 kV
87 %
100,
3150 A
31,5 kA
1196,9 A
92,8%
686,4 A
92,7%
510,5 A
93,0%
THCMT-0202 C
6,3 kV
3150 A
31,5 kA
06 %
100,
-0,9
2 de
g
0,0%
17%
10 1,
-4,5
0 de
g
1219,8 A
94,8%
598,9 A
94,5%
-4 ,3
4 de
g
621 A
95,1%
20 m
18-1/C 500
0,0 %Vd
20 m
18-1/C 500
0,0 %Vd
X7
0,3 %Vd
0,05 ohms
X3
Barra-A
6,3 kV
1200 A
31,5 kA
686,4 A
92,7%
335,9 A
92,7%
175,2 A
92,7%
0,3 %Vd
0,05 ohms
130 m
18-1/C 500
0,1 %Vd
130 m
18-1/C 500
0,1 %Vd
79 %
100,
-4,3
9 de
175,2 A
92,7%
Barra-B
6,3 kV
1200 A
31,5 kA
510,5 A
93,0%
81%
10 0,
175,3 A
92,7%
175,3 A
92,7%
150 m
18-1/C 500
0,1 %Vd
CT14
150 m
18-1/C 500
0,1 %Vd
197,4 A
96,8%
CT11
-5% TapP
TR-3
1,6 MVA
5,9 %Z
6,3/0,48 kV
BPC6450
5000 HP
0,2 %Vd
BPC6430
2500 HP
0,2 %Vd
BPC6420
2500 HP
0,2 %Vd
BPC6440
2500 HP
0,2 %Vd
Vasconia III
78 %
100,
621 A
95,4%
203,4 A
94,0%
197,4 A
96,8%
CT12
Relay10
Relay3
Relay11
27,7
206
A A
0,0%
92,8%
30 m
1-3/C 350
0,0 %Vd
Relay12
197,4 A
96,8%
CT9
204,6 A
92,6%
CAP2
300 kvar
27,7
206
A A
0,0%
92,8%
CAP4
300 kvar
Relay9
27,7
206
A A
0,0%
92,8%
CAP5
300 kvar
BPC-704
3000 HP
BPC-703
3000 HP
0,2 %Vd
G1
500 kW
0,48 kV
T7
800 kVA
5,75 %Z
6,3/0,48 kV
30 m
1-3/C 350
TGD-VA3-01
-2,5% TapP
T704
2,5 MVA
6,3/0,48
5,75 %Z kV
BPC-705
3000 HP
Relay5
Relay4
CAP7
300 kvar
0,1 %Vd
CT6
27,7 A
A
216,6
0,0%
87,5%
CAP6
300 kvar
BPC-702
3000 HP
0,2 %Vd
-5 ,0
1 de
g
Relay8CT10
23,2 A
89,2%
CT5
CT13
27,7 A
A
214,5
0,0%
89,1%
BPC-701
T703
3000 HP
2,5 MVA
6,3/0,48 kV 0,2 %Vd
5,75 %Z
TR-4
1,6 MVA
6,3/0,48 kV
5,9 %Z
0,2 %Vd
Barra_B
6,3 kV
1500 A
25 kA
30 m
3-1/C 4/0
0,0 %Vd
BPC6410
2500 HP
Barra_A
6,3 kV
78%
1500 A 10 0,
25 kA-4,9 8
deg
198,9 A
93,1%
CT4
30 m
3-1/C 4/0
Relay13
598,9 A
94,8%
-4 ,3
8 de
g
160 A
93,7%
1%
99 ,7
0,48 kV
242,3 A
89,9%
0,2 %Vd
62,5 A
89,6%
Centro de Generacin
GD 701
0,48 kV
GD-702
0,48 kV
CCM-VA3-01
0,48 kV
4000 A
65 kA
GD-703
0,48 kV
1100 kW
1100 kW
1100 kW
190 m
15-1/C 750
190 m
15-1/C 750
190 m
15-1/C 750
1%
99 ,7 0,48 kV
1%
99 ,7
-5 ,8 4000 A
565
degkA
-5 ,8
5 de
g
MOV-5
4x1 HP
1,1 %Vd
4000 A
47,8 A
92,0%
BM-704
100 HP
BM-701
125 HP
0,5 %Vd
0,5 %Vd
1%
98,6
-7 ,5
8
2610,2 A
94,7%
55 kA
60,7 A
91,4%
242,3 A
91,6%
BB-701
250 HP
0,9 %Vd
0,7 A
81,0%
TA-601
1 HP
242,6 A
91,6%
BB-704
250 HP
0,0 %Vd
96,5 A
91,7%
BT-701
200 HP
1,0 %Vd
242,3 A
91,6%
BB-706
250 HP
0,3 %Vd
0,9 %Vd
CCM 702
0,48 kV
31,4 A
89,3%
31,7 A
89,3%
AGT-717
40 HP
AGT-707
30 HP
AGT-710
30 HP
6,4 %Vd
1,7 %Vd
2,6 %Vd
98,4 A
0,0%
AGT-714 BDC-701
40 HP
83 kvar
0,0 %Vd
31,6 A
89,3%
1,8 A
83,7%
AGT-701
30 HP
AGT-704
30 HP
2,2 %Vd
0,0 %Vd
Mtr25
3 HP
Cable38
48,1 A
92,0%
BM-705
100 HP
61,4 A
91,5%
BM-702
125 HP
29,7 A
90,8%
CO-702
60 HP
1,1 %Vd
1,5 %Vd
0,7 %Vd
CCM1
0,48 kV
31,6 A
89,3%
AGT-718
40 HP
AGT-713
30 HP
0,0 %Vd
2,3 %Vd
145,3 A
91,8%
BA-701
300 HP
31,6 A
89,3%
247,4 A
91,3%
10,7 A
88,2%
10,7 A
88,4%
2,9 A
84,9%
1,9 A
82,0%
246,9 A
89,4%
484,9 A
91,7%
26,6 A
88,8%
26,6 A
88,8%
3,7 A
83,7%
19 A
88,2%
PG
17,5 HP
0,2 %Vd
26,8 A
90,0%
AGT-711
30 HP
AGT-715
40 HP
2,2 %Vd
0,0 %Vd
1,9 A
82,0%
5,6 A
86,7%
1,0 %Vd
CCM2
0,48 kV
8%
97,8
263,3 A
-0,3%
BX-702
3 HP
Cable5
0,0 %Vd
31,7 A
89,3%
30 m
6-1/C 4/0
AGT-705
30 HP
31,4 A
89,3%
AG-708
30 HP
26,8 A
1,0 %Vd
1,7 %Vd
31,6 A
89,3%
31,6 A
89,3%
31,7 A
89,3%
98,6 A
-0,4%
AGT-712
30 HP
AGT-719
40 HP
AGT-703
30 HP
AGT-706
30 HP
AGT-709
30 HP
2,2 %Vd
0,0 %Vd
2,2 %Vd
2,6 %Vd
0,0 %Vd
96,5 A
91,7%
BDC-703
83 kvar
BT-702
200 HP
-0,2 %Vd
0,3 %Vd
30 m
6-1/C 4/0
AGT-702
30 HP
8,2 A
87,9%
BE-701
15 HP
13,1 A
88,8%
BU-712
25 HP
13,1 A
88,8%
BU-715
25 HP
15,6 A
89,2%
1,2 A
90,0%
30 m
6-1/C 4/0
BS-713
30 HP
26,8 A
90,0%
0,0 %Vd
PB-702
45 kVA
2,6 %Vd
1,7 %Vd
99 A
89,1%
DR
1,2 A
90,0%
0,0 %Vd
PB-701
45 kVA
2,2 %Vd
1,7 %Vd
0,8 %Vd
0,7 %Vd
1,1 %Vd
99 A
89,1%
-3% TapP
T 705
113 kVA
DR
4 %Z 0,48/0,208
221,7 A
90,0%
90,0%
0,0 %Vd
TAE 701
1 kVA
TAS-702
80 kVA
kV
98,4 A
0,0%
-3% TapP
T 706
113 kVA
4 %Z 0,48/0,208 BDC-702
kV
83 kvar
221,7 A
90,0%
242,9 A
88,7%
8,1 A
87,6%
DR
CO-703
15 HP
0,6 %Vd
Lump11
80 kVA
0,0 %Vd
-0,3 %Vd
BB-6403
250 HP
0,0 %Vd
2,2 %Vd
6441-D
20 HP
0,2 %Vd
6441-C
20 HP
0,8 %Vd
6441-B
5 HP
LUB-6441 BB-6402
1,47 HP
250 HP
0,2 %Vd
0,1 %Vd
2,0 %Vd
1,1 %Vd
Bus23
0,48 kV
8%
97,8
247,5 A
91,3%
13,2 A
88,8%
26,6 A
88,8%
247,5 A
91,3%
10,7 A
88,4%
10,7 A
88,4%
2,9 A
84,9%
196,3 A
91,4%
0,3 A
0,0%
0,3 A
0,0%
0,3 A
0,0%
0,3 A
0,0%
76,5 A
90,4%
0,1 %Vd
0,6 %Vd
CO-601
25 HP
2,2 %Vd
0,6 %Vd
1,1 %Vd
2,2 %Vd
0,0 %Vd
6431C
20 HP
0,8 %Vd
0,8 %Vd
6431B
5 HP
0,2 %Vd
BB-5402
200 HP
BL-6420
0,5 HP
BL-6410
0,5 HP
TFLA 15
0,46 HP
TFLB 15
0,46 HP
1,2 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
CCM-3
0,0%
5,6 A
86,7%
5,1 A -7 122,7 A
,70
86,3%
100,0%
de g
76,3 A
90,4%
13,2 A
88,8%
0,3 A
0,0%
0,6 A
100,0%
2,9 A
84,9%
15,6 A
89,2%
82,2 A
89,5%
82,2 A
89,5%
9,4 A
87,9%
1,3 A
82,7%
8%
96,5
4,3 A -8,12
deg
85,9%
PB-6001
BD-9610
4x50 HP
BD-9606
3x50 HP
BD-9603
3x50 HP
BD-VERT
7,5 HP
0,3 %Vd
0,3 %Vd
0,1 %Vd
0,0 %Vd
122,7 A
100,0%
TDA 604
10 HP
0,6 %Vd
Mtr14
9 HP
1,1 %Vd
8%
97 ,8
dcLump3
226,4 A-7
,70
93,4%
deg
300 m
9-1/C 500
1,3 %Vd
101,9 A
90,4%
0,2 %Vd
BB-6404
250 HP
8%
97 ,8 0,48 kV
259 A
90,0%
CCM-DESCARGADER
0,48 kV
1,1 %Vd
BB-707
250 HP
BB-705
250 HP
BB-703
250 HP
0,0 %Vd
0,0 %Vd
0,1 %Vd
185 m
12-1/C 500
0,0 %Vd
DR
30 m
3-1/C 1/0
30 m
3-1/C 1/0
0,0%
0,3 A
0,0%
2,9 A
84,9%
Charger1
10 kVA/7,65 kW
MOV2
1 HP
T 602
T5
0,0 %Vd
0,4 %Vd
100
kVA
100
%Vd
kVA
DR kV 0,4
2,6 %Z
0,48/0,208
2,60,48/0,208
%Z
kV
ESPUMA
20 HP
PGRU
17,5 HP
INTERC
2 HP
MOV4
1 HP
0,0 %Vd
TFL 05
0,46 HP
0,0 %Vd
dcLump1
0,0 %Vd
MOV6
1 HP
-7,7
0 de
g
15 m
3-1/C 2/0
1225331
5 HP
0,0 %Vd
32,1 A
84,5%
0,1 %Vd
0,1 %Vd
ECDT-0201
0,48 kV
3000 A
40 kA
1%
97 ,8
11,7 A
89,8%
9,4 A
81,0%
4,7 A
81,0%
6,3 A
81,0%
-7 ,7
0 de
g
CCM 703
189,8 A
90,0%
Lump5
70 kVA
189,8 A
90,0%
100 m
3-1/C 2/0
0,2 %Vd
Lump7
70 kVA
DS
ECDT-0201
ECDT-0202
0,208 kV
225 A
10 kA
ECDT-0201
Cable42
Cable48
Cable52
T4
30 kVA
2,6 %Z
0,48/0,208 kV
27,1 A
90,0%
4%
96 ,9
27,1 A
90,0%
-7 ,9
7 de
g
ECDT-0201
Lump2
10 kVA
120 m
3-1/C 500
270 m
3-1/C 500
0,1 %Vd
ECDT-0205
0,48 kV
3000 A
40 kA
120 m
3-1/C 500
0,2 %Vd
6%
97 ,7
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
-7,7
1
ECDT-0203
0,48 kV
3000 A
40 kA
0,0 %Vd
4%
97 ,6
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
deg
-7,7
4
ECDT-0204
0,48 kV
3000 A
40 kA
7%
97 ,7
1,6 A
81,0%
1,6 A
81,0%
1,6 A
81,0%
deg
-7,7
1
83,2 A
90,0%
deg
BM-706
125 HP
1%
98 ,6
0,5 %Vd
deg
99 A
89,1%
-3% TapP
T 707
45 kVA
DR
4 %Z 0,48/0,208
kV
-7,5
8 de
g
60,8 A
91,4%
0,9 %Vd
37,2 A
89,1%
CARGA
30 kVA
230 m
6-1/C 4/0
BB-5401
100 HP
242,2 A
91,6%
-7,5
8
31,6 A
89,3%
2100,4 A
95,6%
989 A
98,2%
-7,7
0 de
g
26,8 A
90,0%
Charger3
10 kVA/7,65 kW
INCENDIO CAP1
250 HP
223 kvar
0,0 %Vd
1%
98,6
1,8 A
83,7%
BB-708
300 HP
0,2 %Vd
TSA-VA3-01
50 kVA
CCM 703
0,48 kV
deg
1573,9 A
94,8%
483,1 A
97,2%
242,4 A
91,6%
BB-702
250 HP
43,2 A
90,2%
-3% TapP
TR-VA3
75 kVA
0,48/0,208
2,6 %Z
kV
139,9 A
90,0%
MX-01A
6x40 HP
CCM 701
0,48 kV
DR
TMOVS-VA3-01
242,3 A
89,9%
-3% TapP
T 709
113 kVA
4 %Z 0,48/0,208 kV
221,7 A
90,0%
CARGA1
80 kVA
BB-709
300 HP
0,0 %Vd
-5 ,8
5 de
g
VAS-5209124-11040-ID-ELE-MC-051-1
Anlisis de Cargas
Revisin: 1
Documento No.
VAS-5209124-11040-ID-ELE-MC-051-R1.doc.
1 de 1
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Voltage
kV
% Mag.
Generation
Ang.
MW
Load
Mvar
MW
Load Flow
Mvar
ID
MW
XFMR
Mvar
Amp
% PF
220-MCC-20100 Barra A
0.480
99.069
-6.0
0.253
0.125
Bus84
-0.253
-0.125
343.0
89.6
220-MCC-20100 Barra B
0.480
99.889
-7.4
0.031
0.017
Bus88
-0.832
-0.414
1118.7
89.5
220-MCC-20200
0.800
0.397
1075.8
89.6
Barra 220-DP-20300
0.000
0.000
0.0
0.0
220-MCC-20200
0.480
99.287
-7.6
0.797
0.392
220-MCC-20100 Barra B
-0.797
-0.392
1075.8
89.7
Bus138
0.000
0.000
0.0
0.0
Bus140
0.000
0.000
0.0
0.0
Bus137
0.000
0.000
0.0
0.0
Barra 220-DP-20300
0.208
99.889
-7.4
220-MCC-20100 Barra B
Barra_A
6.300
100.777
-5.0
Bus26
Barra_B
Barra A
6.300
6.600
100.783
99.955
-5.0
-5.4
0.000
0.000
0.0
0.0
-6.241
-2.103
598.9
94.8
T703-AT
2.037
0.796
198.9
93.1
Bus4
2.102
0.542
197.4
96.8
Bus8
2.102
0.765
203.4
94.0
Bus5
-6.516
-2.045
621.0
95.4
TGD-VA3-01
0.228
0.116
23.2
89.2
Bus10
2.102
0.541
197.4
96.8
Bus25
2.085
0.847
204.6
92.6
Bus24
2.102
0.541
197.4
96.8
Bus94
-14.581
-5.860
1375.3
92.8
Bus95
0.254
0.129
24.9
89.1
Bus97
3.372
1.319
316.9
93.1
Bus102
3.372
1.319
316.9
93.1
Barra B
7.582
3.093
716.6
92.6
Barra-A
6.300
100.787
-4.4
6.997
2.833
Bus32
-6.997
-2.833
686.4
92.7
Barra B
6.600
99.955
-5.4
Bus96
0.838
0.455
83.4
87.9
Bus105
3.372
1.319
316.9
93.1
Bus106
3.372
1.319
316.9
93.1
Barra A
-7.582
-3.093
716.6
92.6
Barra-B
B-P.BOYACA 1
6.300
34.500
100.808
98.328
-4.4
-2.7
3.574
9.137
1.446
4.425
TR4-AT
1.650
0.613
160.0
93.7
Bus28
-5.225
-2.059
510.5
93.0
B-P.BOYACA 2
-9.137
-4.425
172.8
90.0
-9.137
-4.425
451.6
90.0
-0.060
-0.030
82.2
89.5
0.060
0.030
82.2
89.5
13.200
98.328
-2.7
9.137
4.425
Bus1
0.480
97.491
-7.7
CCM-3
Bus3
% Tap
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Bus2
Voltage
kV
% Mag.
110.000
97.895
Generation
Ang.
-0.9
MW
Load
Mvar
0
MW
0
Load Flow
Mvar
ID
0
MW
XFMR
Mvar
Amp
% PF
VAS-T2
0.000
0.000
0.0
THCMT-0202 B
0.000
0.000
0.0
0.0
0.0
Bus3
0.208
96.059
-8.3
0.059
0.029
Bus1
-0.059
-0.029
189.8
90.0
Bus4
6.300
100.777
-5.0
2.102
0.542
Barra_A
-2.102
-0.542
197.4
96.8
Bus5
6.300
100.861
-5.0
Barra_B
6.519
2.053
621.0
95.4
-6.519
-2.053
621.0
95.4
Bus17
Bus6
Bus7
110.000
0.480
97.893
97.491
-0.9
-7.7
VAS-T1
-12.264
-5.793
72.7
90.4
THCMT-0202 A
12.264
5.793
72.7
90.4
CCM-3
-0.060
-0.030
82.2
89.5
0.060
0.030
82.2
89.5
Bus9
Bus8
6.300
100.777
-5.0
2.102
0.765
Barra_A
-2.102
-0.765
203.4
94.0
Bus9
0.208
96.059
-8.3
0.059
0.029
Bus7
-0.059
-0.029
189.8
90.0
Bus10
6.300
100.783
-5.0
2.102
0.541
Barra_B
-2.102
-0.541
197.4
96.8
Bus11
0.480
98.571
-7.6
0.020
0.010
CCM 702
-0.020
-0.010
26.8
90.0
Bus12
110.000
97.893
-0.9
VAS-T3
-12.809
-5.199
74.1
92.7
THCMT-0202 C
12.809
5.199
74.1
92.7
CCM 702
-0.020
-0.010
26.8
90.0
THCMT-0202 C
-6.247
-2.164
598.9
94.5
Bus13
0.480
98.571
-7.6
0.020
0.010
Bus14
6.300
101.161
-4.5
6.247
2.164
598.9
94.5
Bus15
0.480
98.606
-7.6
CCM 702
-0.001
0.000
1.2
90.0
Bus16
0.208
99.744
-8.8
0.072
0.035
CCM 702
-0.072
-0.035
221.7
90.0
Bus17
6.300
101.161
-4.5
THCMT-0202 C
-6.522
-2.111
621.0
95.1
6.522
2.111
621.0
95.1
Bus26
Bus5
Bus18
0.208
99.744
-8.8
0.072
0.035
CCM 702
-0.072
-0.035
221.7
90.0
Bus19
0.480
96.789
-8.1
0.099
0.000
CCM2
-0.099
0.000
122.7
100.0
Bus20
0.208
99.855
-8.7
0.027
0.013
CCM 702
-0.027
-0.013
83.2
90.0
Bus21
0.208
99.744
-8.8
0.072
0.035
CCM 702
-0.072
-0.035
221.7
90.0
Bus22
0.208
101.381
-6.4
0.046
0.022
TGD-VA3-01
-0.046
-0.022
139.9
90.0
Bus23
0.480
97.877
-7.7
CCM-DESCARGADER
CCM1
Tablero Dist. 480V
0.190
0.092
259.0
90.0
-0.362
-0.157
484.9
91.7
0.172
0.066
226.4
93.4
Bus24
6.300
100.783
-5.0
2.102
0.541
Barra_B
-2.102
-0.541
197.4
96.8
Bus25
6.300
100.783
-5.0
2.085
0.847
Barra_B
-2.085
-0.847
204.6
92.6
Bus26
6.300
100.856
-4.9
Barra_A
6.244
2.110
598.9
94.7
Bus14
-6.244
-2.110
598.9
94.7
ECDT-0201
-0.009
-0.004
11.7
89.8
ECDT-0202
0.009
0.004
11.7
89.8
Barra-B
5.226
2.064
510.5
93.0
Bus27
0.480
97.646
-7.7
Bus28
6.300
100.868
-4.3
% Tap
2.500
-1.250
-1.250
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Voltage
kV
% Mag.
Generation
Ang.
MW
Load
Mvar
MW
Load Flow
Mvar
ID
MW
XFMR
Mvar
Amp
% PF
THCMT-0202 A
-5.226
-2.064
510.5
93.0
Bus29
0.480
96.587
-7.8
0.059
0.013
-0.059
-0.013
75.5
97.7
Bus30
0.480
95.767
-7.4
0.030
0.013
-0.030
-0.013
40.5
91.6
Bus31
0.480
95.767
-7.4
0.030
0.013
-0.030
-0.013
40.5
91.6
Bus32
6.300
100.868
-4.3
7.000
2.841
686.4
92.7
THCMT-0202 A
-7.000
-2.841
686.4
92.7
Barra-A
Bus33
0.480
96.108
-7.7
0.049
0.013
-0.049
-0.013
63.7
96.7
Bus34
0.480
97.720
-7.4
0.001
0.013
-0.001
-0.013
16.2
11.3
Bus67
110.000
97.895
-0.9
Ocensa B2
0.000
0.000
0.0
0.0
Bus84
0.480
99.204
-6.0
220-MCC-20100 Barra A
0.253
0.126
343.0
89.6
-0.253
-0.126
343.0
89.6
Bus88
0.480
100.028
-7.4
0.832
0.415
1118.7
89.5
Bus96
-0.832
-0.415
1118.7
89.5
Bus94
14.668
7.275
87.8
89.6
Bus95
Bus93
115.000
93.639
-0.9
Bus94
6.600
100.064
-5.4
220-MCC-20100 Barra B
Ocensa B1
Bus95
6.600
99.951
-5.4
Bus96
6.600
99.952
-5.4
-14.668
-7.275
87.8
89.6
Barra A
14.593
5.876
1375.3
92.8
Bus93
-14.593
-5.876
1375.3
92.8
Barra A
-0.254
-0.129
24.9
89.1
Bus84
0.254
0.129
24.9
89.1
Barra B
-0.838
-0.455
83.4
87.9
Bus88
0.838
0.455
83.4
87.9
Bus97
6.600
99.944
-5.4
3.372
1.319
Barra A
-3.372
-1.319
316.9
93.1
Bus102
6.600
99.944
-5.4
3.372
1.319
Barra A
-3.372
-1.319
316.9
93.1
Bus105
6.600
99.951
-5.4
3.372
1.319
Barra B
-3.372
-1.319
316.9
93.1
Bus106
6.600
99.951
-5.4
3.372
1.319
Barra B
-3.372
-1.319
316.9
93.1
Bus137
0.480
99.287
-7.6
220-MCC-20200
0.000
0.000
0.0
0.0
Bus138
0.480
99.287
-7.6
220-MCC-20200
0.000
0.000
0.0
0.0
Bus140
0.480
99.287
-7.6
220-MCC-20200
0.000
0.000
0.0
0.0
CCM1
0.480
97.877
-7.7
0.429
-0.007
Bus23
0.362
0.157
484.9
91.7
CCM2
-0.791
-0.150
989.0
98.2
CCM2
0.480
97.877
-7.7
0.568
0.259
Bus19
0.100
0.001
122.7
100.0
TR4-AT
-1.634
-0.501
2100.4
95.6
CCM-3
0.175
0.091
242.9
88.7
CCM1
CCM 701
CCM 702
0.480
0.480
98.608
98.608
-7.6
-7.6
0.803
0.554
0.277
0.173
0.791
0.150
989.0
98.2
T703-AT
-2.026
-0.688
2610.2
94.7
CCM 702
1.223
0.411
1573.9
94.8
Bus13
0.020
0.010
26.8
90.0
Bus11
0.020
0.010
26.8
90.0
% Tap
-6.000
-2.500
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Voltage
kV
% Mag.
Generation
Ang.
MW
Load
Mvar
CCM 703
0.480
98.608
-7.6
CCM-3
0.480
97.877
-7.7
MW
Load Flow
Mvar
ID
MW
XFMR
Mvar
Amp
% PF
Bus15
0.001
0.000
1.2
90.0
Bus16
0.072
0.037
99.0
89.1
-3.000
Bus18
0.072
0.037
99.0
89.1
-3.000
Bus20
0.027
0.014
37.2
89.1
-3.000
Bus21
0.072
0.037
99.0
89.1
-3.000
CCM 703
0.385
0.094
483.1
97.2
CCM 701
-1.223
-0.411
1573.9
94.8
0.385
0.094
CCM 702
-0.385
-0.094
483.1
97.2
0.033
0.018
Bus1
0.060
0.030
82.2
89.5
Bus7
0.060
0.030
82.2
89.5
ECDT-0201
0.022
0.014
32.1
84.5
CCM2
-0.175
-0.091
242.9
88.7
CCM-DESCARGADER
0.480
96.578
-8.1
0.188
0.089
Bus23
-0.188
-0.089
259.0
90.3
CCM-VA3-01
0.480
99.705
-5.8
0.181
0.088
TGD-VA3-01
-0.181
-0.088
242.3
89.9
110.000
100.000
0.0
72.709
36.258
18.408
9.889
109.7
88.1
TECA
54.300
26.368
316.8
90.0
0.480
97.809
-7.7
CCM-3
-0.022
-0.014
32.1
84.5
Bus27
0.009
0.004
11.7
89.8
ECDT-0203
0.006
0.005
9.4
81.0
ECDT-0204
0.003
0.002
4.7
81.0
ECDT-0205
0.004
0.003
6.3
81.0
* Cocorna - EPM
ECDT-0201
ECDT-0202
0.208
96.940
-8.0
0.009
0.004
Bus27
-0.009
-0.004
27.1
90.0
ECDT-0203
0.480
97.639
-7.7
0.006
0.004
ECDT-0201
-0.006
-0.004
9.4
81.0
ECDT-0204
0.480
97.772
-7.7
0.003
0.002
ECDT-0201
-0.003
-0.002
4.7
81.0
ECDT-0205
0.480
97.759
-7.7
0.004
0.003
ECDT-0201
-0.004
-0.003
6.3
81.0
Jazmn - MSB
110.000
97.804
-1.0
4.544
2.612
VAS-JAZMIN-A
-4.544
-2.612
28.1
86.7
Ocensa B1
110.000
97.895
-0.9
Bus93
14.668
7.275
87.8
89.6
Ocensa B2
-14.668
-7.275
87.8
89.6
Ocensa B2
110.000
97.895
-0.9
T - L. PTO Boyaca
-14.668
-7.275
87.8
89.6
0.000
0.000
0.0
0.0
14.668
7.275
87.8
89.6
Bus67
Ocensa B1
Palagua - ECP
110.000
97.883
-0.9
0.826
0.400
110.000
99.538
-0.2
-0.826
-0.400
4.9
90.0
Cocorna - EPM
VAS-PALAGUA
-18.362
-9.912
110.0
88.0
B-P.BOYACA 1
18.362
9.912
110.0
88.0
& B-P.BOYACA 2
T703-AT
6.300
0.480
100.750
97.877
-5.0
-7.7
% Tap
Barra_A
-2.036
-0.796
198.9
93.1
CCM 701
2.036
0.796
198.9
93.1
Bus29
0.060
0.013
75.5
97.6
-1.500
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
TECA
Voltage
kV
110.000
% Mag.
99.343
Generation
Ang.
-0.4
MW
Load
Mvar
MW
Load Flow
Mvar
ID
96.540
-3.2
8.510
4.122
TGD-VA3-01
0.480
99.705
-5.8
THCMT-0202 A
6.300
100.868
-4.3
Amp
% PF
0.030
0.013
40.5
91.8
Bus31
0.030
0.013
40.5
91.8
Bus33
0.050
0.013
63.7
96.7
Bus34
0.002
0.013
16.2
11.8
Bus23
-0.172
-0.066
226.4
93.4
-54.141
-25.947
317.2
90.2
45.602
21.283
265.9
90.6
Cocorna - EPM
Teca 13.8 kV
13.800
XFMR
Mvar
Bus30
T - L. Teca
Teca 13.8 kV
MW
8.540
4.665
51.4
87.8
TECA
-8.510
-4.122
409.8
90.0
Barra_B
-0.227
-0.111
304.8
89.8
Bus22
0.046
0.023
62.5
89.6
CCM-VA3-01
0.181
0.088
242.3
89.9
TMOVS-VA3-01
0.000
0.000
0.0
0.0
-12.226
-4.904
1196.9
92.8
Bus32
7.000
2.841
686.4
92.7
93.0
Bus6
Bus28
5.226
2.064
510.5
THCMT-0202 B
6.300
100.055
-0.9
Bus2
0.000
0.000
0.0
0.0
THCMT-0202 C
6.300
101.171
-4.5
Bus14
6.247
2.164
598.9
94.5
Bus17
6.522
2.112
621.0
95.1
Bus12
-12.770
-4.276
1219.8
94.8
VAS-PTO BOYACA
-14.668
-7.275
87.8
89.6
7.275
87.8
89.6
20.814
266.4
90.8
-20.814
266.4
90.8
0.000
0.0
0.0
-1.650
-0.613
160.0
93.7
1.650
0.613
160.0
93.7
12.536
5.496
73.4
91.6
4.546
2.382
27.5
88.6
VAS-PALAGUA
-17.082
-7.879
100.9
90.8
VAS-JAZMIN-A
-12.536
-5.496
73.4
91.6
12.536
5.496
73.4
91.6
0.826
0.164
4.5
98.1
17.082
7.879
100.9
90.8
-17.909
-8.043
105.3
91.2
T - L. PTO Boyaca
14.668
7.275
87.8
89.6
VAS-PALAGUA
17.909
8.043
105.3
91.2
-32.577
-15.318
193.0
90.5
12.264
5.793
72.7
90.4
T - L. PTO Boyaca
110.000
97.895
-0.9
Ocensa B2
14.668
T - L. Teca
110.000
97.895
-0.9
VAS-TECA
45.113
-45.113
TMOVS-VA3-01
0.480
99.705
-5.8
TGD-VA3-01
0.000
TR4-AT
6.300
100.775
-4.4
Barra-B
CCM2
TECA
VAS-JAZMIN-A
110.000
97.895
-0.9
VAS-JAZMIN-B
Jazmn - MSB
VAS-JAZMIN-B
110.000
97.895
-0.9
VAS-PALAGUA
110.000
97.895
-0.9
VAS-T1
Palagua - ECP
VAS-JAZMIN-A
VAS-PTO BOYACA
VAS-PTO BOYACA
110.000
97.895
-0.9
VAS-TECA
VAS-T1
110.000
97.895
-0.9
Bus6
% Tap
-3.000
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MAXIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Voltage
kV
% Mag.
Generation
Ang.
MW
Load
Mvar
MW
Load Flow
Mvar
ID
VAS-T2
VAS-JAZMIN-B
VAS-T2
VAS-T3
110.000
110.000
97.895
97.895
-0.9
-0.9
Bus2
110.000
97.895
-0.9
* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA
XFMR
Mvar
Amp
% PF
0.272
-0.297
2.2
-67.6
-12.536
-5.496
73.4
91.6
0.000
0.000
0.0
0.0
VAS-T1
-0.272
0.297
2.2
-67.6
VAS-T3
0.272
-0.297
2.2
-67.6
12.809
5.199
74.1
92.7
-12.536
-5.496
73.4
91.6
Bus12
VAS-TECA
VAS-TECA
MW
VAS-T2
-0.272
0.297
2.2
-67.6
VAS-T3
12.536
5.496
73.4
91.6
T - L. Teca
-45.113
-20.814
266.4
90.8
VAS-PTO BOYACA
32.577
15.318
193.0
90.5
% Tap
VAS-5209124-11040-ID-ELE-MC-051-1
Anlisis de Cargas
Revisin: 1
Documento No.
VAS-5209124-11040-ID-ELE-MC-051-R1.doc.
1 de 1
Cocorna - EPM
AL
Jazmn - MSB
4%
10 6,
110 kV
Palagua - ECP
-1,3
0 de
g
30,6 A
86,7%
49 %
106,
110 kV
-1,2
6 de
g
5,2 A
90,0%
0,95 MVA
AL
AL
6 km
397.5-26
0,1318+j0,4842 ohms/1km
189,2 A 494,5 A
90,0%
90,0%
-2 ,9
189,2 A
9 de
g
90,0%
deg
0,26974+j0,54136 ohms/1km
6 km
Penguin
436,1 A
90,0%
de g
Lump1
10 MVA
PB-13,2
10,5 MVA
5%
106,
Ocensa B1
80,7 A
89,5% -1
,2
6,5%
126,1 A 10
90,6% -1
-0,0
7
Trafo Teca
15 MVA
8,5
110/13,8
%Z
kV
68%
107,
88 %
109,
110 kV
54,7 A
87,8%
AL
B-P.BOYACA 2
494,5 A
90,0%
T - L. Teca
Ocensa B2
TECA
0,1 %Vd
-0,4
120,5 A
7 de
g
88,0%
-1,5% TapP
Trafo EBSA
30/15/15 MVA
110/34,5/13,2 kV
10/10/10 %Z
T - L. PTO Boyaca
110 kV
0,0 %Vd
AL
109%
PB-34,5
10,5 MVA
6 km
397.5-26
0,1318+j0,4842 ohms/1km
0,1 %Vd
6,15 km
300-30
0,2092+j0,5276 ohms/1km
0,1318+j0,4842 ohms/1km
4 km
397.5-26
1,0 %Vd
0,26974+j0,54395 ohms/1km
22,1 km
Penguin
B-P.BOYACA 1
68 %
34,5 kV
107,
2,5 %Vd
Palagua
110%
54,3 A0,00
deg
88,5%
124,2 A
91,4%
AL
Jazmn
5,479 MVA
110 kV
298,4 A
89,4%
110 kV
244,1 A
89,6%
110 kV
AMPLIACIN OCENSA
5 de
g
,25
deg
T - L. Teca
T - L. PTO Boyaca
10 m
36-1/C 750
VAS-PALAGUA
5%
4,7 A
98,3% 6,5%
10
110 kV
-1,2
5
35,4 A
90,2%
80,7 10A6,
89,5%
0,0 %Vd
VAS-TECA
5,6 A
96,9%
110 kV
deg
-1 ,2
5 de
g
SW70
0 A
SW72
0 A
10 m
36-1/C 750
VAS-JAZMIN-A
110 kV
29,9 A
88,6%
40 A
91,5%
5%
10 6,
VAS-PTO BOYACA
-1 ,2
5 de
g
5,6 A
96,9%
10 m
36-1/C 750
86,2 A
5%
90,1% 10 6,
0,0 %Vd
10 m
36-1/C 750
-1,2
5 de
g
110 kV
SW75
0 A
0,0 %Vd
5%
10 6,
CT16
VAS-T1
110 kV
5%
106,
VAS-T2110 kV
-1,2
5 de
g
5,6 A
96,9%
VAS-JAZMIN-B
110 kV
0,0 %Vd
CT22
5%
106,
1,8 A
87,4%
CT24
SW80
0 A
5%
106,
Ocensa B2
-1 ,2
5 de
g
80,7 A
89,5%
110 kV
SW88
0 A
SW86
0 A
-1 ,2
5 de
g
110 kV
SW84
0 A
VAS-T3
-1,2
3,9 A
5 de
g
99,2%
Cuarto Elctrico Vasconia
100 m
3-1/C 500
0,0 %Vd
SW76
0 A
5%
106,
Ocensa B1
1,8 A -1 ,25
de g
87,4%
0,0%
CT18
5%
106,
110 kV
CCM 703
-1
7,3
,25 A
de
95,2% g
100 m
3-1/C 500
0,0 %Vd
100 m
3-1/C 500
0,0 %Vd
SW79
0 A
SW83
0 A
T2
20 MVA
110/6,6 kV
9,5 %Z
T3
20 MVA
110/6,6 kV
9,5 %Z
NUEVO SW MT
THCMT-0202 A
6,3 kV
3150 A
31,5 kA
THCMT-0202 B
6,3 kV
3150 A
31,5 kA
94 %
104,
68,7 A
99,2%
68,7 A
99,2%
01 %
105,
-1,2
5 de
g
0,0%
THCMT-0202 C
6,3 kV
3150 A
31,5 kA
76%
10 4,
-1,6
3 de
g
129,3 A
95,4%
107,1 A
96,4%
-1 ,4
6 de
g
22,6 A
89,2%
20 m
18-1/C 500
0,0 %Vd
20 m
18-1/C 500
0,0 %Vd
X7
0,0 %Vd
0,05 ohms
X3
Barra-A
6,3 kV
1200 A
31,5 kA
0,0 %Vd
0,05 ohms
130 m
18-1/C 500
0,0 %Vd
130 m
18-1/C 500
0,0 %Vd
94 %
104,
-1,4
6 de
0,0%
Barra-B
6,3 kV
1200 A
31,5 kA
68,7 A
99,2%
94%
10 4,
-5% TapP
TR-3
1,6 MVA
5,9 %Z
6,3/0,48 kV
BPC6430
2500 HP
BPC6420
2500 HP
BPC6440
2500 HP
Barra_B
6,3 kV
1500 A
25 kA
Vasconia III
74 %
104,
22,6 A
89,2%
22,6 A
89,2%
CT12
Relay10
Relay11
Relay12
CT9
Relay3
Relay9
CAP4
300 kvar
BPC-704
3000 HP
BPC-701
T703
3000 HP
2,5 MVA
6,3/0,48 kV
5,75 %Z
TR-4
1,6 MVA
6,3/0,48 kV
5,9 %Z
CAP5
300 kvar
CAP6
300 kvar
BPC-703
3000 HP
BPC-702
3000 HP
Relay4
CAP2
300 kvar
CT6
CT5
CT13
30 m
1-3/C 350
0,0 %Vd
-1 ,6
4 de
g
Relay8CT10
30 m
3-1/C 4/0
0,0 %Vd
BPC6410
2500 HP
Barra_A
6,3 kV
7%
1500 A 10 4,
25 kA-1,7 1
deg
CT11
BPC6450
5000 HP
Relay13
107,1 A
96,4%
CT4
30 m
3-1/C 4/0
107,1 A
96,4%
-1 ,4
7 de
g
68,7 A
99,2%
150 m
18-1/C 500
0,0 %Vd
CT14
150 m
18-1/C 500
0,0 %Vd
G1
500 kW
0,48 kV
TGD-VA3-01
-2,5% TapP
T704
2,5 MVA
6,3/0,48
5,75 %Z kV
BPC-705
3000 HP
Relay5
T7
800 kVA
5,75 %Z
6,3/0,48 kV
30 m
1-3/C 350
CAP7
300 kvar
69%
10 3,
0,48 kV
232,7 A
89,9%
64,1 A
89,6%
Centro de Generacin
GD 701
0,48 kV
GD-702
0,48 kV
CCM-VA3-01
0,48 kV
4000 A
65 kA
GD-703
0,48 kV
1100 kW
1100 kW
1100 kW
190 m
15-1/C 750
190 m
15-1/C 750
190 m
15-1/C 750
232,8 A
89,9%
69%
10 3,
-2 ,4
3 de
g
4000 A
45,4 A
92,0%
BM-704
100 HP
BM-701
125 HP
0,5 %Vd
0,5 %Vd
0,6 A
81,0%
BB-701
250 HP
0,0 %Vd
TA-601
1 HP
91,7 A
91,7%
BB-704
250 HP
0,0 %Vd
0,0 %Vd
BT-701
200 HP
40,8 A
90,2%
BB-706
250 HP
0,0 %Vd
0,3 %Vd
CCM 702
0,48 kV
30,1 A
89,3%
AGT-717
40 HP
AGT-707
30 HP
AGT-710
30 HP
6,1 %Vd
1,6 %Vd
2,4 %Vd
39,8 A
90,0%
103,6 A
0,0%
AGT-714 BDC-701
40 HP
83 kvar
3,7 %Vd
30 A
89,3%
30,1 A
89,3%
AGT-701
30 HP
AGT-704
30 HP
2,1 %Vd
2,4 %Vd
1,7 A
83,7%
Mtr25
3 HP
Cable38
BM-705
100 HP
58,2 A
91,5%
BM-702
125 HP
28,2 A
90,8%
CO-702
60 HP
1,0 %Vd
1,4 %Vd
0,7 %Vd
CCM1
0,48 kV
30 A
89,3%
AGT-718
40 HP
AGT-713
30 HP
0,0 %Vd
2,2 %Vd
137,9 A
91,8%
BA-701
300 HP
30 A
89,3%
10 A
88,2%
10,1 A
88,3%
2,8 A
84,9%
1,8 A
82,0%
460 A
91,7%
24,9 A
88,8%
24,9 A
88,8%
3,4 A
83,7%
18 A
88,2%
PG
17,5 HP
0,1 %Vd
27,7 A
90,0%
AGT-711
30 HP
AGT-715
40 HP
2,1 %Vd
0,0 %Vd
1,8 A
82,0%
5,3 A
86,7%
1,0 %Vd
CCM2
0,48 kV
23 %
104,
280,4 A
-0,3%
BX-702
3 HP
Cable5
0,0 %Vd
30,1 A
89,3%
30 m
6-1/C 4/0
AGT-705
30 HP
29,8 A
89,3%
AG-708
30 HP
27,7 A
0,0 %Vd
1,6 %Vd
38,5 A
89,9%
30,1 A
89,3%
103,8 A
-0,4%
AGT-712
30 HP
AGT-719
40 HP
AGT-703
30 HP
AGT-706
30 HP
AGT-709
30 HP
0,0 %Vd
0,4 %Vd
0,0 %Vd
2,4 %Vd
0,0 %Vd
91,7 A
91,7%
BDC-703
83 kvar
BT-702
200 HP
-0,2 %Vd
0,3 %Vd
30 m
6-1/C 4/0
AGT-702
30 HP
7,8 A
87,8%
BE-701
15 HP
12,5 A
88,8%
BU-712
25 HP
12,5 A
88,8%
BU-715
25 HP
14,8 A
89,2%
1,2 A
90,0%
30 m
6-1/C 4/0
BS-713
30 HP
27,7 A
90,0%
0,0 %Vd
PB-702
45 kVA
2,4 %Vd
1,6 %Vd
102,2 A
89,1%
DR
1,2 A
90,0%
0,0 %Vd
PB-701
45 kVA
2,1 %Vd
1,6 %Vd
0,8 %Vd
0,7 %Vd
1,1 %Vd
102,2 A
89,1%
-3% TapP
T 705
113 kVA
DR
4 %Z 0,48/0,208
228,8 A
90,0%
90,0%
0,0 %Vd
TAE 701
1 kVA
TAS-702
80 kVA
kV
103,6 A
0,0%
-3% TapP
T 706
113 kVA
4 %Z 0,48/0,208 BDC-702
kV
83 kvar
228,8 A
90,0%
DR
CO-703
15 HP
0,6 %Vd
Lump11
80 kVA
12,4 A
88,8%
24,9 A
88,8%
10,1 A
88,3%
10,1 A
88,3%
2,8 A
84,9%
0,3 A
0,0%
0,3 A
0,0%
0,3 A
0,0%
0,3 A
0,0%
0,0%
5,3 A
86,7%
4,8 A -2 118,1 A
,93
86,3%
100,0%
de g
230 m
6-1/C 4/0
0,0 %Vd
-0,3 %Vd
BB-5401
100 HP
BB-6403
250 HP
0,0 %Vd
0,0 %Vd
6441-D
20 HP
0,2 %Vd
6441-C
20 HP
0,7 %Vd
6441-B
5 HP
LUB-6441 BB-6402
1,47 HP
250 HP
0,2 %Vd
0,1 %Vd
0,0 %Vd
1,1 %Vd
Bus23
0,48 kV
95,5 A
90,4%
0,1 %Vd
0,6 %Vd
CO-601
25 HP
0,0 %Vd
0,5 %Vd
1,1 %Vd
0,0 %Vd
0,0 %Vd
6431C
20 HP
0,7 %Vd
0,7 %Vd
6431B
5 HP
0,2 %Vd
BB-5402
200 HP
BL-6420
0,5 HP
BL-6410
0,5 HP
TFLA 15
0,46 HP
TFLB 15
0,46 HP
0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
71,5 A
90,4%
12,4 A
88,7%
0,3 A
0,0%
0,6 A
100,0%
2,8 A
84,9%
14,7 A
89,2%
85,4 A
89,6%
85,4 A
89,6%
8,8 A
87,9%
1,2 A
82,7%
01 %
103,
4,1 A -3,30
deg
85,9%
PB-6001
BD-9610
4x50 HP
BD-9606
3x50 HP
BD-9603
3x50 HP
BD-VERT
7,5 HP
0,3 %Vd
0,3 %Vd
0,0 %Vd
0,0 %Vd
118,1 A
100,0%
TDA 604
10 HP
0,6 %Vd
23 %
10 4,
dcLump3
217,7 A-2
,93
93,4%
deg
300 m
9-1/C 500
1,2 %Vd
71,6 A
90,4%
0,2 %Vd
BB-6404
250 HP
CCM-3
23%
10 4, 0,48 kV
242,7 A
90,1%
CCM-DESCARGADER
0,48 kV
1,1 %Vd
BB-707
250 HP
BB-705
250 HP
BB-703
250 HP
0,0 %Vd
0,5 %Vd
0,0 %Vd
0,0 %Vd
0,1 %Vd
185 m
12-1/C 500
0,0 %Vd
DR
30 m
3-1/C 1/0
30 m
3-1/C 1/0
0,0%
0,3 A
0,0%
2,8 A
84,9%
Charger1
10 kVA/7,65 kW
MOV2
1 HP
T 602
T5
0,0 %Vd
0,4 %Vd
100
kVA
100
%Vd
kVA
DR kV 0,4
2,6 %Z
0,48/0,208
2,60,48/0,208
%Z
kV
ESPUMA
20 HP
PGRU
17,5 HP
INTERC
2 HP
MOV4
1 HP
0,0 %Vd
TFL 05
0,46 HP
0,0 %Vd
dcLump1
0,0 %Vd
MOV6
1 HP
1,0 %Vd
-2,9
3 de
g
15 m
3-1/C 2/0
1225331
5 HP
0,0 %Vd
31,4 A
84,7%
Mtr14
9 HP
0,1 %Vd
0,1 %Vd
ECDT-0201
0,48 kV
3000 A
40 kA
16%
10 4,
12,3 A
89,8%
8,9 A
81,0%
4,4 A
81,0%
5,9 A
81,0%
-2 ,9
3 de
g
CCM 703
197,1 A
90,0%
Lump5
70 kVA
197,1 A
90,0%
100 m
3-1/C 2/0
0,2 %Vd
Lump7
70 kVA
DS
ECDT-0201
ECDT-0202
0,208 kV
225 A
10 kA
ECDT-0201
Cable42
Cable48
Cable52
T4
30 kVA
2,6 %Z
0,48/0,208 kV
28,5 A
90,0%
25%
10 3,
28,5 A
90,0%
-3 ,2
0 de
g
ECDT-0201
Lump2
10 kVA
120 m
3-1/C 500
270 m
3-1/C 500
0,0 %Vd
ECDT-0205
0,48 kV
3000 A
40 kA
0,2 %Vd
12%
10 4,
1,5 A
81,0%
120 m
3-1/C 500
1,5 A
81,0%
1,5 A
81,0%
1,5 A
81,0%
-2,9
4
ECDT-0203
0,48 kV
3000 A
40 kA
0,0 %Vd
01%
10 4,
1,5 A
81,0%
1,5 A
81,0%
1,5 A
81,0%
1,5 A
81,0%
1,5 A
81,0%
1,5 A
81,0%
deg
-2,9
7
ECDT-0204
0,48 kV
3000 A
40 kA
13 %
10 4,
1,5 A
81,0%
1,5 A
81,0%
1,5 A
81,0%
deg
-2,9
4
deg
deg
102,2 A
89,1%
-3% TapP
T 707
45 kVA
DR
4 %Z 0,48/0,208
85,9 A
90,0%
BM-706
125 HP
76 %
10 3,
38,4 A
89,2%
CARGA
30 kVA
23%
104,
245,8 A
88,8%
7,7 A
87,6%
-3,1
1 de
g
57,7 A
91,4%
-3,1
1
30 A
89,3%
901,1 A
99,5%
500,6 A
-99,4%
-2,9
3 de
g
27,7 A
90,0%
Charger3
10 kVA/7,65 kW
INCENDIO CAP1
250 HP
223 kvar
0,0 %Vd
76 %
103,
1,7 A
83,7%
BB-708
300 HP
0,1 %Vd
TSA-VA3-01
50 kVA
CCM 703
0,48 kV
1041,2 A
96,5%
216,1 A
-100,0%
45,6 A
92,0%
BB-702
250 HP
29,8 A
89,3%
MOV-5
4x1 HP
1,0 %Vd
76%
103,
-3 ,1
1 de
g
1405,7 A
97,0%
55 kA
57,7 A
91,4%
-3% TapP
TR-VA3
75 kVA
0,48/0,208
2,6 %Z
kV
143,4 A
90,0%
MX-01A
6x40 HP
CCM 701
0,48 kV
DR
TMOVS-VA3-01
69%
10 3, 0,48 kV
-2 ,4 4000 A
365
degkA
kV
-3% TapP
T 709
113 kVA
4 %Z 0,48/0,208 kV
228,8 A
90,0%
CARGA1
80 kVA
BB-709
300 HP
0,0 %Vd
-2 ,4
3 de
g
VAS-5209124-11040-ID-ELE-MC-051-1
Anlisis de Cargas
Revisin: 1
Documento No.
VAS-5209124-11040-ID-ELE-MC-051-R1.doc.
1 de 1
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MINIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
Voltage
Generation
Load
Load Flow
XFMR
kV
% Mag.
220-MCC-20100 Barra A
0.480
100.822
-6.4
0.261
0.129
Bus84
-0.261
-0.129
346.9
89.6
220-MCC-20100 Barra B
0.480
99.104
-7.8
0.031
0.017
Bus88
-0.820
-0.409
1112.0
89.5
220-MCC-20200
0.789
0.392
1068.9
89.6
Barra 220-DP-20300
0.000
0.000
0.0
0.0
ID
220-MCC-20200
0.480
98.506
Ang.
-8.0
MW
Mvar
MW
Mvar
0.786
ID
0.386
220-MCC-20100 Barra B
MW
Mvar
Amp
% PF
-0.786
-0.386
1068.9
89.7
Bus138
0.000
0.000
0.0
0.0
Bus140
0.000
0.000
0.0
0.0
Bus137
0.000
0.000
0.0
0.0
Barra 220-DP-20300
0.208
99.104
-7.8
220-MCC-20100 Barra B
Barra_A
6.300
104.697
-1.7
Bus26
Barra_B
6.300
104.739
-1.6
Barra A
6.600
99.175
-5.8
T703-AT
Bus5
TGD-VA3-01
0.000
0.000
0.0
0.0
-1.180
-0.324
107.1
96.4
1.180
0.324
107.1
96.4
-0.231
-0.117
22.6
89.2
0.231
0.117
22.6
89.2
Bus94
-14.577
-5.858
1385.7
92.8
Bus95
0.262
0.133
25.9
89.1
Bus97
3.372
1.319
319.4
93.1
Bus102
3.372
1.319
319.4
93.1
Barra B
7.571
3.087
721.1
92.6
Barra-A
6.300
104.944
-1.5
Bus32
0.000
0.000
0.0
0.0
Barra B
6.600
99.175
-5.8
Bus96
0.826
0.449
82.9
87.9
Bus105
3.372
1.319
319.4
93.1
Bus106
3.372
1.319
319.4
93.1
Barra A
-7.571
-3.087
721.1
92.6
TR4-AT
0.780
0.099
68.7
99.2
Barra-B
6.300
104.938
-1.5
34.500
107.679
-3.0
10.957
5.307
Bus28
B-P.BOYACA 1
B-P.BOYACA 2
-0.780
-0.099
68.7
99.2
-10.957
-5.307
189.2
90.0
-10.957
-5.307
494.5
90.0
% Tap
13.200
107.679
-3.0
10.957
5.307
0.480
103.830
-2.9
Bus1
Bus2
110.000
106.502
-1.2
Bus3
0.208
102.343
-3.5
0.065
0.032
Bus5
6.300
104.742
-1.6
-0.066
-0.033
85.4
89.5
Bus3
CCM-3
0.066
0.033
85.4
89.5
VAS-T2
0.000
0.000
0.0
0.0
THCMT-0202 B
Bus1
Barra_B
Bus17
0.000
0.000
0.0
0.0
-0.065
-0.032
197.1
90.0
0.231
0.117
22.6
89.2
-0.231
-0.117
22.6
89.2
6.250
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MINIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Bus6
Voltage
kV
% Mag.
110.000
106.501
Generation
Ang.
-1.2
MW
Load
Mvar
0
MW
0
Load Flow
Mvar
ID
0
VAS-T1
THCMT-0202 A
CCM-3
MW
XFMR
Mvar
Amp
% PF
-0.780
-0.102
3.9
99.2
0.780
0.102
3.9
99.2
-0.066
-0.033
85.4
89.5
Bus7
0.480
103.830
-2.9
Bus9
0.066
0.033
85.4
89.5
Bus9
0.208
102.343
-3.5
0.065
0.032
Bus7
-0.065
-0.032
197.1
90.0
Bus11
0.480
103.726
-3.1
0.021
0.010
CCM 702
-0.021
-0.010
27.7
90.0
Bus12
110.000
106.501
-1.2
VAS-T3
-1.411
-0.453
7.3
95.2
1.411
0.453
7.3
95.2
CCM 702
-0.021
-0.010
27.7
90.0
THCMT-0202 C
-1.180
-0.326
107.1
96.4
THCMT-0202 C
Bus13
0.480
103.726
-3.1
0.021
0.010
Bus14
6.300
104.756
-1.6
1.180
0.326
107.1
96.4
Bus15
0.480
103.761
-3.1
CCM 702
-0.001
0.000
1.2
90.0
Bus16
0.208
104.998
-4.3
0.078
0.038
CCM 702
-0.078
-0.038
228.8
90.0
Bus17
6.300
104.757
-1.6
THCMT-0202 C
-0.231
-0.117
22.6
89.2
0.231
0.117
22.6
89.2
Bus18
0.208
104.998
-4.3
0.078
0.038
CCM 702
-0.078
-0.038
228.8
90.0
Bus19
0.480
103.184
-3.3
0.101
0.000
CCM2
-0.101
0.000
118.1
100.0
Bus20
0.208
105.113
-4.2
0.029
0.014
CCM 702
-0.029
-0.014
85.9
90.0
Bus21
0.208
104.998
-4.3
0.078
0.038
CCM 702
-0.078
-0.038
228.8
90.0
Bus22
0.208
105.454
-3.0
0.049
0.024
TGD-VA3-01
-0.049
-0.024
143.4
90.0
Bus23
0.480
104.231
-2.9
0.189
0.091
242.7
90.1
Bus26
Bus5
CCM-DESCARGADER
CCM1
Bus26
Bus27
Bus28
6.300
0.480
6.300
104.710
103.993
104.944
-1.7
-2.9
-1.5
-0.366
-0.159
460.0
91.7
0.176
0.067
217.7
93.4
Barra_A
1.180
0.324
107.1
96.4
Bus14
-1.180
-0.324
107.1
96.4
ECDT-0201
-0.010
-0.005
12.3
89.8
ECDT-0202
0.010
0.005
12.3
89.8
Barra-B
0.780
0.099
68.7
99.2
THCMT-0202 A
-0.780
-0.099
68.7
99.2
Bus29
0.480
102.990
-3.0
0.061
0.013
-0.061
-0.013
72.6
97.7
Bus30
0.480
102.203
-2.7
0.030
0.013
-0.030
-0.013
38.9
91.6
Bus31
0.480
102.203
-2.7
0.030
0.013
-0.030
-0.013
38.9
91.6
Bus32
6.300
104.944
-1.5
0.000
0.000
0.0
0.0
0.000
0.000
0.0
0.0
Bus33
0.480
102.530
-2.9
0.051
0.013
-0.051
-0.013
61.3
96.7
Bus34
0.480
104.080
-2.7
0.002
0.013
-0.002
-0.013
15.6
11.3
Bus67
110.000
106.502
-1.2
Ocensa B2
0.000
0.000
0.0
0.0
Bus84
0.480
100.958
-6.4
220-MCC-20100 Barra A
0.261
0.129
346.9
89.6
Barra-A
THCMT-0202 A
% Tap
6.250
6.250
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MINIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Voltage
kV
% Mag.
Generation
Ang.
MW
Load
Mvar
MW
Load Flow
Mvar
ID
Bus95
Bus88
0.480
99.242
-7.8
220-MCC-20100 Barra B
Bus96
Bus93
115.000
101.871
-1.2
Bus94
Ocensa B1
Bus94
Bus95
Bus96
6.600
6.600
6.600
99.284
99.170
99.171
-5.8
-5.8
-5.8
MW
XFMR
Mvar
Amp
% PF
-0.261
-0.129
346.9
89.6
0.821
0.410
1112.0
89.5
-0.821
-0.410
1112.0
89.5
14.665
7.294
80.7
89.5
-14.665
-7.294
80.7
89.5
Barra A
14.589
5.874
1385.7
92.8
Bus93
-14.589
-5.874
1385.7
92.8
89.1
Barra A
-0.261
-0.133
25.9
Bus84
0.261
0.133
25.9
89.1
Barra B
-0.826
-0.449
82.9
87.9
Bus88
0.826
0.449
82.9
87.9
% Tap
3.000
-2.500
-2.500
Bus97
6.600
99.164
-5.8
3.372
1.319
Barra A
-3.372
-1.319
319.4
93.1
Bus102
6.600
99.164
-5.8
3.372
1.319
Barra A
-3.372
-1.319
319.4
93.1
Bus105
6.600
99.171
-5.8
3.372
1.319
Barra B
-3.372
-1.319
319.4
93.1
Bus106
6.600
99.171
-5.8
3.372
1.319
Barra B
-3.372
-1.319
319.4
93.1
Bus137
0.480
98.506
-8.0
220-MCC-20200
0.000
0.000
0.0
0.0
Bus138
0.480
98.506
-8.0
220-MCC-20200
0.000
0.000
0.0
0.0
Bus140
0.480
98.506
-8.0
220-MCC-20200
0.000
0.000
0.0
0.0
CCM1
0.480
104.231
-2.9
0.065
-0.208
Bus23
0.366
0.159
460.0
91.7
CCM2
-0.431
0.049
500.6
-99.4
Bus19
0.102
0.001
118.1
100.0
TR4-AT
-0.777
-0.079
901.1
99.5
CCM-3
0.189
0.098
245.8
88.8
CCM1
0.431
-0.049
500.6
-99.4
T703-AT
-1.177
-0.293
1405.7
97.0
CCM 702
0.866
0.237
1041.2
96.5
Bus13
0.021
0.010
27.7
90.0
Bus11
0.021
0.010
27.7
90.0
Bus15
0.001
0.000
1.2
90.0
Bus16
0.079
0.040
102.2
89.1
-3.000
Bus18
0.079
0.040
102.2
89.1
-3.000
Bus20
0.030
0.015
38.4
89.2
-3.000
Bus21
0.079
0.040
102.2
89.1
-3.000
CCM 703
0.186
-0.003
216.1
-100.0
CCM 701
-0.866
-0.237
1041.2
96.5
CCM 702
-0.186
0.003
216.1
-100.0
Bus1
0.066
0.033
85.4
89.6
Bus7
0.066
0.033
85.4
89.6
CCM2
CCM 701
CCM 702
0.480
0.480
0.480
104.231
103.763
103.763
-2.9
-3.1
-3.1
0.055
0.310
0.371
0.029
0.056
0.084
CCM 703
0.480
103.763
-3.1
0.186
-0.003
CCM-3
0.480
104.231
-2.9
0.033
0.018
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MINIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Voltage
kV
% Mag.
Generation
Ang.
MW
Load
Mvar
MW
Load Flow
Mvar
ID
ECDT-0201
CCM-DESCARGADER
CCM-VA3-01
* Cocorna - EPM
ECDT-0201
0.480
103.014
-3.3
0.188
0.089
0.480
103.690
-2.4
0.180
0.088
110.000
110.000
0.0
55.898
28.034
0.480
104.165
-2.9
MW
XFMR
Mvar
Amp
% PF
0.023
0.014
31.4
84.7
CCM2
-0.189
-0.098
245.8
88.8
Bus23
-0.188
-0.089
242.7
90.3
TGD-VA3-01
-0.180
-0.088
232.7
89.9
45.832
22.744
244.1
89.6
TECA
10.066
5.290
54.3
88.5
CCM-3
-0.023
-0.014
31.4
84.7
89.8
Bus27
0.010
0.005
12.3
ECDT-0203
0.006
0.005
8.9
81.0
ECDT-0204
0.003
0.002
4.4
81.0
ECDT-0205
0.004
0.003
5.9
81.0
ECDT-0202
0.208
103.250
-3.2
0.010
0.005
Bus27
-0.010
-0.005
28.5
90.0
ECDT-0203
0.480
104.005
-3.0
0.006
0.004
ECDT-0201
-0.006
-0.004
8.9
81.0
ECDT-0204
0.480
104.129
-2.9
0.003
0.002
ECDT-0201
-0.003
-0.002
4.4
81.0
ECDT-0205
0.480
104.118
-2.9
0.004
0.003
ECDT-0201
-0.004
-0.003
5.9
81.0
Jazmn - MSB
110.000
106.402
-1.3
5.378
3.091
VAS-JAZMIN-A
86.7
Ocensa B1
110.000
106.502
-1.2
-5.378
-3.091
30.6
-14.665
-7.294
80.7
89.5
14.665
7.294
80.7
89.5
Ocensa B2
0.000
0.000
0.0
0.0
Bus67
0.000
0.000
0.0
0.0
Ocensa B1
0.000
0.000
0.0
0.0
-0.947
-0.458
5.2
90.0
T - L. Teca
Bus93
Ocensa B2
110.000
106.502
-1.2
Palagua - ECP
110.000
106.489
-1.3
0.947
0.458
110.000
109.004
-0.5
VAS-PALAGUA
Cocorna - EPM
-45.602
-22.332
244.5
89.8
T - L. PTO Boyaca
23.582
10.444
124.2
91.4
B-P.BOYACA 1
22.020
11.887
120.5
88.0
& B-P.BOYACA 2
T703-AT
TECA
6.300
0.480
104.683
104.231
-1.7
-2.9
110.000
109.882
-0.1
Teca 13.8 kV
13.800
106.904
-2.8
10.028
4.857
TGD-VA3-01
0.480
103.690
-2.4
Barra_A
-1.180
-0.324
107.1
96.4
CCM 701
1.180
0.324
107.1
96.4
Bus29
0.061
0.014
72.6
97.6
Bus30
0.031
0.013
38.9
91.7
Bus31
0.031
0.013
38.9
91.7
Bus33
0.051
0.014
61.3
96.7
Bus34
0.002
0.013
15.6
11.8
Bus23
-0.176
-0.067
217.7
93.4
-10.062
-5.472
54.7
87.8
Cocorna - EPM
Teca 13.8 kV
TECA
Barra_B
10.062
5.472
54.7
87.8
-10.028
-4.857
436.1
90.0
-0.230
-0.112
296.8
89.8
% Tap
-1.500
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MINIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
THCMT-0202 A
Voltage
kV
6.300
% Mag.
104.944
Generation
Ang.
-1.5
MW
Load
Mvar
MW
Load Flow
Mvar
ID
THCMT-0202 B
6.300
105.010
-1.2
THCMT-0202 C
6.300
104.758
-1.6
T - L. PTO Boyaca
110.000
106.502
-1.2
T - L. Teca
110.000
106.502
-1.2
TMOVS-VA3-01
0.480
103.690
-2.4
TR4-AT
6.300
104.925
-1.5
VAS-JAZMIN-A
VAS-JAZMIN-B
VAS-PALAGUA
110.000
110.000
110.000
106.502
106.502
106.502
-1.2
-1.2
-1.2
106.502
-1.2
0.049
0.025
64.1
89.6
0.088
232.7
89.9
TMOVS-VA3-01
0.000
0.000
0.0
0.0
99.2
Bus6
-0.780
-0.099
68.7
Bus32
0.000
0.000
0.0
0.0
Bus28
0.780
0.099
68.7
99.2
Bus2
0.000
0.000
0.0
0.0
Bus14
1.180
0.326
107.1
96.4
Bus17
0.231
0.117
22.6
89.2
Bus12
-1.411
-0.443
129.3
95.4
VAS-PTO BOYACA
23.183
10.848
126.1
90.6
-23.183
-10.848
126.1
90.6
VAS-TECA
-14.665
-7.294
80.7
89.5
Ocensa B1
14.665
7.294
80.7
89.5
0.000
0.000
0.0
0.0
TGD-VA3-01
Barra-B
-0.780
-0.099
68.7
99.2
CCM2
0.780
0.099
68.7
99.2
VAS-JAZMIN-B
1.096
0.278
5.6
96.9
Jazmn - MSB
5.380
2.820
29.9
88.6
90.2
VAS-PALAGUA
-6.476
-3.097
35.4
VAS-JAZMIN-A
-1.096
-0.278
5.6
96.9
VAS-T1
1.096
0.278
5.6
96.9
Palagua - ECP
0.947
0.179
4.7
98.3
T - L. PTO Boyaca
VAS-TECA
110.000
106.502
-1.2
VAS-T3
VAS-TECA
110.000
110.000
110.000
106.502
106.502
106.502
-1.2
-1.2
-1.2
6.476
3.097
35.4
90.2
-7.422
-3.277
40.0
91.5
-23.183
-10.848
126.1
90.6
7.422
3.277
40.0
91.5
90.1
15.761
7.572
86.2
Bus6
0.780
0.102
3.9
99.2
VAS-T2
0.316
0.175
1.8
87.4
-1.096
-0.278
5.6
96.9
VAS-JAZMIN-B
VAS-T2
% PF
0.180
VAS-PALAGUA
VAS-T1
Amp
CCM-VA3-01
VAS-PTO BOYACA
110.000
XFMR
Mvar
Bus22
VAS-JAZMIN-A
VAS-PTO BOYACA
MW
Bus2
0.000
0.000
0.0
0.0
VAS-T1
-0.316
-0.175
1.8
87.4
VAS-T3
0.316
0.175
1.8
87.4
Bus12
1.411
0.453
7.3
95.2
VAS-TECA
-1.096
-0.278
5.6
96.9
VAS-T2
-0.316
-0.175
1.8
87.4
VAS-T3
1.096
0.278
5.6
96.9
14.665
7.294
80.7
89.5
T - L. Teca
% Tap
-3.000
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MINIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Voltage
kV
% Mag.
Ang.
Generation
MW
Mvar
Load
MW
Load Flow
Mvar
ID
VAS-PTO BOYACA
* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA
MW
-15.761
XFMR
Mvar
-7.572
Amp
86.2
% PF
90.1
% Tap
VAS-5209124-11040-ID-ELE-MC-051-1
Anlisis de Cargas
Revisin: 1
Documento No.
VAS-5209124-11040-ID-ELE-MC-051-R1.doc.
1 de 1
Cocorna - EPM
AL
Jazmn - MSB
85 %
10 8,
110 kV
Palagua - ECP
-0,4
8 de
g
31,3 A
86,7%
94 %
108,
110 kV
AL
190,1 A 496,7 A
90,0%
90,0%
-2 ,7
190,1 A
4 de
g
90,0%
PB-34,5
10,5 MVA
6 km
397.5-26
0,1318+j0,4842 ohms/1km
63 %
109,
110 kV
-0,2
2
54,6 A
87,8%
deg
0,26974+j0,54136 ohms/1km
6 km
Penguin
435,4 A
90,0%
AL
16%
108,
Lump1
10 MVA
PB-13,2
10,5 MVA
95 %
108,
T - L. Teca
95 %
108,
Ocensa B2
TECA
0,4 %Vd
124,3 A
90,9%
deg
Trafo Teca
15 MVA
8,5
110/13,8
%Z
kV
B-P.BOYACA 2
496,7 A
90,0%
T - L. PTO Boyaca
110 kV
0,0 %Vd
0,1 %Vd
-0,2
2
-1,5% TapP
Trafo EBSA
30/15/15 MVA
110/34,5/13,2 kV
10/10/10 %Z
0,26974+j0,54395 ohms/1km
22,1 km
Penguin
B-P.BOYACA 1
16 %
34,5 kV
108,
Palagua
6 km
397.5-26
0,1318+j0,4842 ohms/1km
AL
49%
109,
0,5 %Vd
0,95 MVA
AL
6,15 km
300-30
0,2092+j0,5276 ohms/1km
0,1318+j0,4842 ohms/1km
4 km
397.5-26
121 A
88,0%
AL
Jazmn
5,479 MVA
110 kV
110%
178,5 0,
A 00
deg
90,0%
-0,4
4 de
g
5,3 A
90,0%
299 A
89,3%
110 kV
120,6 A
88,1%
Ocensa B1
78,9 A
89,6% -0
,4
46,1 A
92,3%
110 kV
-0,4
3 de
g
AMPLIACIN OCENSA
3 de
g
T - L. Teca
T - L. PTO Boyaca
10 m
36-1/C 750
VAS-PALAGUA
95%
10 8,
4,8 A
98,3% 8,95 %
10
110 kV
-0,4
3
36 A
90,2%
VAS-TECA
40,6 A
91,5%
deg
0,0 %Vd
5,5 A
97,2%
110 kV
-0 ,4
3 de
g
SW70
0 A
SW72
0 A
10 m
36-1/C 750
VAS-JAZMIN-A
110 kV
30,6 A
88,6%
40,6 A
91,5%
95%
10 8,
10 m
36-1/C 750
95 %
10 8,
CT16
VAS-T1
110 kV
-0,4
3 de
g
CT22
95%
108,
1,8 A
87,5%
SW80
0 A
-0 ,4
3 de
g
110 kV
SW84
0 A
SW88
0 A
SW86
0 A
95%
108,
Ocensa B2
-0 ,4
3 de
g
78,9 A
89,6%
110 kV
VAS-T3
-0,4
3,8 A
3 de
g
99,3%
Cuarto Elctrico Vasconia
100 m
3-1/C 500
0,0 %Vd
CT24
SW76
0 A
95 %
108,
Ocensa B1
1,8 A -0 ,43
de g
87,5%
0,0%
SW75
0 A
0,0 %Vd
95%
108,
VAS-T2110 kV
CT18
10 m
36-1/C 750
0,0 %Vd
110 kV
-0,4
3 de
g
5,5 A
97,2%
VAS-JAZMIN-B
110 kV
0,0 %Vd
95%
10 8,
VAS-PTO BOYACA
-0 ,4
3 de
g
5,5 A
97,2%
95 %
108,
110 kV
CCM 703
-0
7,2
,43 A
de
95,4% g
100 m
3-1/C 500
0,0 %Vd
100 m
3-1/C 500
0,0 %Vd
SW79
0 A
SW83
0 A
T2
20 MVA
110/6,6 kV
9,5 %Z
T3
20 MVA
110/6,6 kV
9,5 %Z
NUEVO SW MT
THCMT-0202 A
6,3 kV
3150 A
31,5 kA
THCMT-0202 B
6,3 kV
3150 A
31,5 kA
37 %
107,
67,7 A
99,3%
67,7 A
99,3%
43 %
107,
-0,4
3 de
g
0,0%
THCMT-0202 C
6,3 kV
3150 A
31,5 kA
18%
10 7,
-0,7
9 de
g
127,4 A
95,6%
105,6 A
96,6%
-0 ,6
3 de
g
22,3 A
89,2%
20 m
18-1/C 500
0,0 %Vd
20 m
18-1/C 500
0,0 %Vd
X7
0,0 %Vd
0,05 ohms
X3
Barra-A
6,3 kV
1200 A
31,5 kA
0,0 %Vd
0,05 ohms
130 m
18-1/C 500
0,0 %Vd
130 m
18-1/C 500
0,0 %Vd
37 %
107,
-0,6
3 de
0,0%
Barra-B
6,3 kV
1200 A
31,5 kA
67,7 A
99,3%
36%
10 7,
-5% TapP
TR-3
1,6 MVA
5,9 %Z
6,3/0,48 kV
BPC6430
2500 HP
BPC6420
2500 HP
BPC6440
2500 HP
Barra_B
6,3 kV
1500 A
25 kA
Vasconia III
16 %
107,
22,3 A
89,2%
22,3 A
89,2%
CT12
Relay10
Relay11
Relay12
CT9
Relay3
Relay9
CAP4
300 kvar
BPC-704
3000 HP
BPC-701
T703
3000 HP
2,5 MVA
6,3/0,48 kV
5,75 %Z
TR-4
1,6 MVA
6,3/0,48 kV
5,9 %Z
CAP5
300 kvar
CAP6
300 kvar
BPC-703
3000 HP
BPC-702
3000 HP
Relay4
CAP2
300 kvar
CT6
CT5
CT13
30 m
1-3/C 350
0,0 %Vd
-0 ,8
1 de
g
Relay8CT10
30 m
3-1/C 4/0
0,0 %Vd
BPC6410
2500 HP
Barra_A
6,3 kV
12%
1500 A 10 7,
25 kA-0,8 7
deg
CT11
BPC6450
5000 HP
Relay13
105,6 A
96,7%
CT4
30 m
3-1/C 4/0
105,6 A
96,7%
-0 ,6
3 de
g
67,7 A
99,3%
150 m
18-1/C 500
0,0 %Vd
CT14
150 m
18-1/C 500
0,0 %Vd
G1
500 kW
0,48 kV
TGD-VA3-01
-2,5% TapP
T704
2,5 MVA
6,3/0,48
5,75 %Z kV
BPC-705
3000 HP
Relay5
T7
800 kVA
5,75 %Z
6,3/0,48 kV
30 m
1-3/C 350
CAP7
300 kvar
13%
10 6,
0,48 kV
227,5 A
89,9%
Centro de Generacin
GD 701
0,48 kV
GD-702
0,48 kV
CCM-VA3-01
0,48 kV
4000 A
65 kA
GD-703
0,48 kV
1100 kW
1100 kW
1100 kW
190 m
15-1/C 750
190 m
15-1/C 750
190 m
15-1/C 750
227,3 A
89,9%
4000 A
44,3 A
92,0%
13%
10 6,
-1 ,5
6 de
g
BM-704
100 HP
BM-701
125 HP
0,5 %Vd
0,5 %Vd
0,6 A
81,0%
BB-701
250 HP
0,0 %Vd
TA-601
1 HP
89,6 A
91,7%
BB-704
250 HP
0,0 %Vd
0,0 %Vd
BT-701
200 HP
39,7 A
90,1%
BB-706
250 HP
0,0 %Vd
0,3 %Vd
CCM 702
0,48 kV
29,3 A
89,3%
AGT-717
40 HP
AGT-707
30 HP
AGT-710
30 HP
5,9 %Vd
1,6 %Vd
2,4 %Vd
38,8 A
90,0%
106 A
0,0%
AGT-714 BDC-701
40 HP
83 kvar
3,7 %Vd
29,2 A
89,3%
29,3 A
89,3%
AGT-701
30 HP
AGT-704
30 HP
2,1 %Vd
2,4 %Vd
1,7 A
83,7%
Mtr25
3 HP
Cable38
BM-705
100 HP
56,8 A
91,5%
BM-702
125 HP
27,6 A
90,8%
CO-702
60 HP
1,0 %Vd
1,4 %Vd
0,7 %Vd
CCM1
0,48 kV
29,3 A
89,3%
AGT-718
40 HP
AGT-713
30 HP
0,0 %Vd
2,2 %Vd
134,7 A
91,8%
BA-701
300 HP
29,2 A
89,3%
9,8 A
88,2%
9,8 A
88,3%
2,7 A
84,9%
1,7 A
82,0%
451,3 A
91,7%
24,3 A
88,8%
24,3 A
88,8%
3,4 A
83,7%
17,6 A
88,2%
PG
17,5 HP
0,1 %Vd
28,1 A
90,0%
AGT-711
30 HP
AGT-715
40 HP
2,1 %Vd
0,0 %Vd
1,7 A
82,0%
5,2 A
86,7%
1,0 %Vd
CCM2
0,48 kV
69 %
106,
287 A
-0,3%
BX-702
3 HP
Cable5
0,0 %Vd
29,3 A
89,3%
30 m
6-1/C 4/0
AGT-705
30 HP
29,1 A
89,3%
AG-708
30 HP
28,1 A
0,0 %Vd
1,5 %Vd
37,6 A
89,9%
29,3 A
89,3%
106,2 A
-0,4%
AGT-712
30 HP
AGT-719
40 HP
AGT-703
30 HP
AGT-706
30 HP
AGT-709
30 HP
0,0 %Vd
0,4 %Vd
0,0 %Vd
2,4 %Vd
0,0 %Vd
89,6 A
91,7%
BDC-703
83 kvar
BT-702
200 HP
-0,2 %Vd
0,3 %Vd
30 m
6-1/C 4/0
AGT-702
30 HP
7,6 A
87,8%
BE-701
15 HP
12,2 A
88,8%
BU-712
25 HP
12,2 A
88,8%
BU-715
25 HP
14,5 A
89,2%
1,2 A
90,0%
30 m
6-1/C 4/0
BS-713
30 HP
28,1 A
90,0%
0,0 %Vd
PB-702
45 kVA
2,4 %Vd
1,6 %Vd
103,8 A
89,1%
DR
1,2 A
90,0%
0,0 %Vd
PB-701
45 kVA
2,1 %Vd
1,6 %Vd
0,8 %Vd
0,7 %Vd
1,1 %Vd
103,8 A
89,1%
-3% TapP
T 705
113 kVA
DR
4 %Z 0,48/0,208
232,3 A
90,0%
90,0%
0,0 %Vd
TAE 701
1 kVA
TAS-702
80 kVA
kV
106 A
0,0%
-3% TapP
T 706
113 kVA
4 %Z 0,48/0,208 BDC-702
kV
83 kvar
232,3 A
90,0%
7,6 A
87,6%
DR
CO-703
15 HP
0,6 %Vd
Lump11
80 kVA
69%
106,
247,1 A
88,8%
12,1 A
88,8%
24,3 A
88,8%
9,8 A
88,3%
9,8 A
88,3%
2,7 A
84,9%
0,3 A
0,0%
0,3 A
0,0%
0,3 A
0,0%
0,3 A
0,0%
0,0%
5,2 A
86,7%
4,7 A -2 116,5 A
,05
86,3%
100,0%
de g
230 m
6-1/C 4/0
0,0 %Vd
-0,3 %Vd
BB-5401
100 HP
BB-6403
250 HP
0,0 %Vd
0,0 %Vd
6441-D
20 HP
0,2 %Vd
6441-C
20 HP
0,7 %Vd
6441-B
5 HP
LUB-6441 BB-6402
1,47 HP
250 HP
0,2 %Vd
0,1 %Vd
0,0 %Vd
1,0 %Vd
93,2 A
90,4%
300 m
9-1/C 500
1,2 %Vd
69,9 A
90,4%
0,2 %Vd
0,1 %Vd
0,6 %Vd
CO-601
25 HP
0,0 %Vd
0,5 %Vd
1,0 %Vd
0,0 %Vd
0,0 %Vd
6431C
20 HP
0,7 %Vd
0,7 %Vd
6431B
5 HP
0,2 %Vd
BB-5402
200 HP
BL-6420
0,5 HP
BL-6410
0,5 HP
TFLA 15
0,46 HP
TFLB 15
0,46 HP
0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
0,0 %Vd
69,8 A
90,4%
12,1 A
88,7%
0,3 A
0,0%
0,6 A
100,0%
2,7 A
84,9%
14,3 A
89,2%
86,6 A
89,6%
86,6 A
89,6%
8,6 A
87,9%
1,2 A
82,7%
51 %
105,
-2,4
4 A
0 de
g
85,9%
PB-6001
BD-9610
4x50 HP
BD-9606
3x50 HP
BD-9603
3x50 HP
BD-VERT
7,5 HP
0,3 %Vd
0,3 %Vd
0,0 %Vd
0,0 %Vd
116,5 A
100,0%
TDA 604
10 HP
0,6 %Vd
69 %
10 6,
dcLump3
214,7 A-2
,05
93,4%
deg
237 A
90,1%
CCM-DESCARGADER
0,48 kV
1,0 %Vd
BB-6404
250 HP
CCM-3
69%
10 6, 0,48 kV
Bus23
0,48 kV
BB-707
250 HP
BB-705
250 HP
BB-703
250 HP
0,0 %Vd
0,5 %Vd
0,0 %Vd
0,0 %Vd
0,1 %Vd
185 m
12-1/C 500
0,0 %Vd
DR
30 m
3-1/C 1/0
30 m
3-1/C 1/0
0,0%
0,3 A
0,0%
2,7 A
84,9%
Charger1
10 kVA/7,65 kW
MOV2
1 HP
T 602
T5
0,0 %Vd
0,4 %Vd
100
kVA
100
%Vd
kVA
DR kV 0,4
2,6 %Z
0,48/0,208
2,60,48/0,208
%Z
kV
ESPUMA
20 HP
PGRU
17,5 HP
INTERC
2 HP
MOV4
1 HP
0,0 %Vd
TFL 05
0,46 HP
0,0 %Vd
dcLump1
0,0 %Vd
MOV6
1 HP
1,0 %Vd
-2,0
5 de
g
15 m
3-1/C 2/0
1225331
5 HP
0,0 %Vd
31,2 A
84,8%
Mtr14
9 HP
0,1 %Vd
0,1 %Vd
ECDT-0201
0,48 kV
3000 A
40 kA
63%
10 6,
12,6 A
89,8%
8,7 A
81,0%
4,3 A
81,0%
5,8 A
81,0%
-2 ,0
5 de
g
CCM 703
200 A
90,0%
Lump5
70 kVA
200 A
90,0%
100 m
3-1/C 2/0
0,2 %Vd
Lump7
70 kVA
DS
ECDT-0201
ECDT-0202
0,208 kV
225 A
10 kA
ECDT-0201
Cable42
Cable48
Cable52
T4
30 kVA
2,6 %Z
0,48/0,208 kV
29 A
90,0%
7%
10 5,
29 A
90,0%
-2 ,3
2 de
g
ECDT-0201
Lump2
10 kVA
120 m
3-1/C 500
270 m
3-1/C 500
0,0 %Vd
ECDT-0205
0,48 kV
3000 A
40 kA
0,2 %Vd
58%
10 6,
1,4 A
81,0%
120 m
3-1/C 500
1,4 A
81,0%
1,4 A
81,0%
1,4 A
81,0%
-2,0
6
ECDT-0203
0,48 kV
3000 A
40 kA
0,0 %Vd
47%
10 6,
1,4 A
81,0%
1,4 A
81,0%
1,4 A
81,0%
1,4 A
81,0%
1,4 A
81,0%
1,4 A
81,0%
deg
-2,0
9
ECDT-0204
0,48 kV
3000 A
40 kA
59 %
10 6,
1,4 A
81,0%
1,4 A
81,0%
1,4 A
81,0%
deg
-2,0
6
deg
deg
103,8 A
89,1%
-3% TapP
T 707
45 kVA
DR
4 %Z 0,48/0,208
87,2 A
90,0%
BM-706
125 HP
22 %
10 6,
38,9 A
89,2%
CARGA
30 kVA
-2,2
2 de
g
56,4 A
91,4%
-2,2
2
29,2 A
89,3%
888,7 A
99,6%
492,5 A
-99,0%
-2,0
5 de
g
28,1 A
90,0%
Charger3
10 kVA/7,65 kW
INCENDIO CAP1
250 HP
223 kvar
0,0 %Vd
22 %
106,
1,7 A
83,7%
BB-708
300 HP
0,1 %Vd
TSA-VA3-01
50 kVA
CCM 703
0,48 kV
1030 A
96,6%
211,3 A
-99,9%
44,6 A
92,0%
BB-702
250 HP
29,1 A
89,3%
-3% TapP
TR-VA3
75 kVA
0,48/0,208
2,6 %Z
kV
145,6 A
90,0%
MOV-5
4x1 HP
1,0 %Vd
22%
106,
-2 ,2
2 de
g
1385,4 A
97,2%
55 kA
56,4 A
91,4%
DR
TMOVS-VA3-01
13%
10 6, 0,48 kV
-1 ,5 4000 A
665
degkA
MX-01A
6x40 HP
CCM 701
0,48 kV
-1 ,5
6 de
g
65 A
89,6%
kV
-3% TapP
T 709
113 kVA
4 %Z 0,48/0,208 kV
232,3 A
90,0%
CARGA1
80 kVA
BB-709
300 HP
0,0 %Vd
VAS-5209124-11040-ID-ELE-MC-051-0
Anlisis de Cargas
Revisin: 0
Documento No.
VAS-5209124-11040-ID-ELE-MC-051-R1.doc
1 de 1
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MINIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Voltage
kV
% Mag.
Generation
Ang.
MW
Load
Mvar
MW
Load Flow
Mvar
ID
MW
XFMR
Mvar
Amp
% PF
220-MCC-20100 Barra A
0.480
99.190
-5.5
0.254
0.126
Bus84
-0.254
-0.126
343.3
89.6
220-MCC-20100 Barra B
0.480
100.012
-6.9
0.031
0.017
Bus88
-0.833
-0.415
1119.8
89.5
220-MCC-20200
0.802
0.398
1076.9
89.6
Barra 220-DP-20300
0.000
0.000
0.0
0.0
220-MCC-20200
0.480
99.409
-7.1
0.799
0.393
220-MCC-20100 Barra B
-0.799
-0.393
1076.9
89.7
Bus138
0.000
0.000
0.0
0.0
Bus140
0.000
0.000
0.0
0.0
Bus137
0.000
0.000
0.0
0.0
Barra 220-DP-20300
0.208
100.012
-6.9
220-MCC-20100 Barra B
Barra_A
6.300
107.124
-0.9
Bus26
Barra_B
6.300
107.164
-0.8
Barra A
6.600
100.076
-4.9
T703-AT
Bus5
TGD-VA3-01
0.000
0.000
0.0
0.0
-1.193
-0.316
105.6
96.7
1.193
0.316
105.6
96.7
-0.233
-0.118
22.3
89.2
0.233
0.118
22.3
89.2
Bus94
-14.583
-5.862
1373.8
92.8
Bus95
0.255
0.130
25.0
89.1
Bus97
3.372
1.319
316.5
93.1
Bus102
3.372
1.319
316.5
93.1
Barra B
7.584
3.094
716.0
92.6
Barra-A
6.300
107.365
-0.6
Bus32
0.000
0.000
0.0
0.0
Barra B
6.600
100.076
-4.9
Bus96
0.840
0.456
83.5
87.9
Bus105
3.372
1.319
316.5
93.1
Bus106
3.372
1.319
316.5
93.1
Barra A
-7.584
-3.094
716.0
92.6
TR4-AT
0.788
0.090
67.7
99.3
Barra-B
6.300
107.360
-0.6
34.500
108.161
-2.7
11.055
5.354
Bus28
B-P.BOYACA 1
B-P.BOYACA 2
-0.788
-0.090
67.7
99.3
-11.055
-5.354
190.1
90.0
-11.055
-5.354
496.7
90.0
% Tap
13.200
108.161
-2.7
11.055
5.354
0.480
106.288
-2.0
Bus1
Bus2
110.000
108.952
-0.4
Bus3
0.208
104.779
-2.6
0.068
0.033
Bus5
6.300
107.167
-0.8
-0.069
-0.034
86.6
89.5
Bus3
CCM-3
0.069
0.034
86.6
89.5
VAS-T2
0.000
0.000
0.0
0.0
THCMT-0202 B
Bus1
Barra_B
Bus17
0.000
0.000
0.0
0.0
-0.068
-0.033
200.0
90.0
0.233
0.118
22.3
89.2
-0.233
-0.118
22.3
89.2
6.250
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MINIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Bus6
Voltage
kV
% Mag.
110.000
108.952
Generation
Ang.
-0.4
MW
Load
Mvar
0
MW
0
Load Flow
Mvar
ID
0
VAS-T1
THCMT-0202 A
CCM-3
MW
XFMR
Mvar
Amp
% PF
-0.788
-0.093
3.8
99.3
0.788
0.093
3.8
99.3
-0.069
-0.034
86.6
89.5
Bus7
0.480
106.288
-2.0
Bus9
0.069
0.034
86.6
89.5
Bus9
0.208
104.779
-2.6
0.068
0.033
Bus7
-0.068
-0.033
200.0
90.0
Bus11
0.480
106.186
-2.2
0.022
0.011
CCM 702
-0.022
-0.011
28.1
90.0
Bus12
110.000
108.952
-0.4
VAS-T3
-1.426
-0.446
7.2
95.4
1.426
0.446
7.2
95.4
CCM 702
-0.022
-0.011
28.1
90.0
THCMT-0202 C
-1.193
-0.318
105.6
96.6
THCMT-0202 C
Bus13
0.480
106.186
-2.2
0.022
0.011
Bus14
6.300
107.181
-0.8
1.193
0.318
105.6
96.6
Bus15
0.480
106.222
-2.2
CCM 702
-0.001
0.000
1.2
90.0
Bus16
0.208
107.505
-3.4
0.081
0.039
CCM 702
-0.081
-0.039
232.3
90.0
Bus17
6.300
107.182
-0.8
THCMT-0202 C
-0.233
-0.118
22.3
89.2
0.233
0.118
22.3
89.2
Bus18
0.208
107.505
-3.4
0.081
0.039
CCM 702
-0.081
-0.039
232.3
90.0
Bus19
0.480
105.662
-2.4
0.102
0.000
CCM2
-0.102
0.000
116.5
100.0
Bus20
0.208
107.622
-3.3
0.030
0.015
CCM 702
-0.030
-0.015
87.2
90.0
Bus21
0.208
107.505
-3.4
0.081
0.039
CCM 702
-0.081
-0.039
232.3
90.0
Bus22
0.208
107.949
-2.1
0.051
0.025
TGD-VA3-01
-0.051
-0.025
145.6
90.0
Bus23
0.480
106.695
-2.1
0.189
0.091
237.0
90.1
Bus26
Bus5
CCM-DESCARGADER
CCM1
Bus26
Bus27
Bus28
6.300
0.480
6.300
107.137
106.453
107.365
-0.9
-2.1
-0.6
-0.367
-0.159
451.3
91.7
0.178
0.068
214.7
93.4
Barra_A
1.193
0.317
105.6
96.7
Bus14
-1.193
-0.317
105.6
96.7
ECDT-0201
-0.010
-0.005
12.6
89.8
ECDT-0202
0.010
0.005
12.6
89.8
Barra-B
0.788
0.091
67.7
99.3
THCMT-0202 A
-0.788
-0.091
67.7
99.3
Bus29
0.480
105.470
-2.1
0.061
0.013
-0.061
-0.013
71.6
97.7
Bus30
0.480
104.695
-1.8
0.031
0.013
-0.031
-0.013
38.4
91.6
Bus31
0.480
104.695
-1.8
0.031
0.013
-0.031
-0.013
38.4
91.6
Bus32
6.300
107.365
-0.6
0.000
0.000
0.0
0.0
0.000
0.000
0.0
0.0
Bus33
0.480
105.017
-2.1
0.051
0.013
-0.051
-0.013
60.4
96.7
Bus34
0.480
106.545
-1.8
0.002
0.014
-0.002
-0.014
15.4
11.3
Bus67
110.000
108.952
-0.4
Ocensa B2
0.000
0.000
0.0
0.0
Bus84
0.480
99.325
-5.5
220-MCC-20100 Barra A
0.254
0.126
343.3
89.6
Barra-A
THCMT-0202 A
% Tap
6.250
6.250
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MINIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Voltage
kV
% Mag.
0.480
100.150
Generation
Ang.
MW
Load
Mvar
MW
Load Flow
Mvar
ID
Bus95
Bus88
-6.9
220-MCC-20100 Barra B
Bus96
Bus93
115.000
104.215
-0.4
Bus94
Ocensa B1
Bus94
Bus95
Bus96
6.600
6.600
6.600
100.185
100.072
100.073
-4.9
-4.9
-4.9
MW
XFMR
Mvar
Amp
% PF
-0.254
-0.126
343.3
89.6
0.834
0.416
1119.8
89.5
-0.834
-0.416
1119.8
89.5
14.670
7.273
78.9
89.6
-14.670
-7.273
78.9
89.6
Barra A
14.595
5.877
1373.8
92.8
Bus93
-14.595
-5.877
1373.8
92.8
Barra A
-0.255
-0.130
25.0
89.1
Bus84
0.255
0.130
25.0
89.1
Barra B
-0.840
-0.456
83.5
87.9
Bus88
0.840
0.456
83.5
87.9
% Tap
4.500
-2.500
Bus97
6.600
100.066
-4.9
3.372
1.319
Barra A
-3.372
-1.319
316.5
93.1
Bus102
6.600
100.066
-4.9
3.372
1.319
Barra A
-3.372
-1.319
316.5
93.1
Bus105
6.600
100.073
-4.9
3.372
1.319
Barra B
-3.372
-1.319
316.5
93.1
Bus106
6.600
100.073
-4.9
3.372
1.319
Barra B
-3.372
-1.319
316.5
93.1
Bus137
0.480
99.409
-7.1
220-MCC-20200
0.000
0.000
0.0
0.0
Bus138
0.480
99.409
-7.1
220-MCC-20200
0.000
0.000
0.0
0.0
Bus140
0.480
99.409
-7.1
220-MCC-20200
0.000
0.000
0.0
0.0
CCM1
0.480
106.695
-2.1
0.065
-0.220
Bus23
0.367
0.159
451.3
91.7
CCM2
-0.433
0.060
492.5
-99.0
Bus19
0.103
0.001
116.5
100.0
TR4-AT
-0.785
-0.070
888.7
99.6
CCM-3
0.195
0.101
247.1
88.8
CCM1
0.433
-0.060
492.5
-99.0
T703-AT
-1.190
-0.286
1385.4
97.2
CCM 702
0.879
0.235
1030.0
96.6
Bus13
0.022
0.011
28.1
90.0
Bus11
0.022
0.011
28.1
90.0
Bus15
0.001
0.000
1.2
90.0
Bus16
0.082
0.042
103.8
89.1
Bus18
0.082
0.042
103.8
89.1
-3.000
Bus20
0.031
0.016
38.9
89.2
-3.000
-3.000
CCM2
CCM 701
CCM 702
0.480
0.480
0.480
106.695
106.224
106.224
-2.1
-2.2
-2.2
0.055
0.311
0.371
0.029
0.051
0.080
CCM 703
0.480
106.224
-2.2
0.186
-0.008
CCM-3
0.480
106.695
-2.1
0.033
0.018
Bus21
0.082
0.042
103.8
89.1
CCM 703
0.186
-0.008
211.3
-99.9
CCM 701
-0.879
-0.235
1030.0
96.6
CCM 702
-0.186
0.008
211.3
-99.9
Bus1
0.069
0.034
86.6
89.6
Bus7
0.069
0.034
86.6
89.6
-3.000
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MINIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Voltage
kV
% Mag.
Generation
Ang.
MW
Load
Mvar
MW
Load Flow
Mvar
ID
ECDT-0201
CCM-DESCARGADER
CCM-VA3-01
* Cocorna - EPM
ECDT-0201
0.480
105.506
-2.4
0.188
0.089
0.480
106.130
-1.6
0.180
0.088
110.000
110.000
0.0
55.953
28.232
0.480
106.629
-2.1
MW
XFMR
Mvar
Amp
% PF
0.024
0.015
31.2
84.8
CCM2
-0.195
-0.101
247.1
88.8
Bus23
-0.188
-0.089
237.0
90.3
TGD-VA3-01
-0.180
-0.088
227.5
89.9
22.274
11.966
120.6
88.1
TECA
33.678
16.265
178.5
90.0
CCM-3
-0.023
-0.015
31.2
84.8
89.8
Bus27
0.010
0.005
12.6
ECDT-0203
0.006
0.005
8.7
81.0
ECDT-0204
0.003
0.002
4.3
81.0
ECDT-0205
0.004
0.003
5.8
81.0
ECDT-0202
0.208
105.696
-2.3
0.010
0.005
Bus27
-0.010
-0.005
29.0
90.0
ECDT-0203
0.480
106.473
-2.1
0.006
0.004
ECDT-0201
-0.006
-0.004
8.7
81.0
ECDT-0204
0.480
106.594
-2.1
0.003
0.002
ECDT-0201
-0.003
-0.002
4.3
81.0
ECDT-0205
0.480
106.583
-2.1
0.004
0.003
ECDT-0201
-0.004
-0.003
5.8
81.0
Jazmn - MSB
110.000
108.850
-0.5
5.628
3.235
VAS-JAZMIN-A
86.7
Ocensa B1
110.000
108.952
-0.4
-5.628
-3.235
31.3
-14.670
-7.273
78.9
89.6
14.670
7.273
78.9
89.6
Ocensa B2
0.000
0.000
0.0
0.0
Bus67
0.000
0.000
0.0
0.0
Ocensa B1
0.000
0.000
0.0
0.0
-0.983
-0.476
5.3
90.0
Cocorna - EPM
-22.218
-11.994
121.0
88.0
B-P.BOYACA 1
22.218
11.994
121.0
88.0
Barra_A
-1.192
-0.316
105.6
96.7
CCM 701
1.192
0.316
105.6
96.7
Bus29
0.062
0.014
71.6
97.6
Bus30
0.031
0.014
38.4
91.7
Bus31
0.031
0.014
38.4
91.7
96.7
T - L. Teca
Bus93
Ocensa B2
110.000
108.952
-0.4
Palagua - ECP
110.000
108.939
-0.4
0.983
0.476
110.000
109.492
-0.2
VAS-PALAGUA
& B-P.BOYACA 2
T703-AT
6.300
107.110
-0.9
0.480
106.695
-2.1
TECA
110.000
109.629
-0.2
Teca 13.8 kV
13.800
106.656
-2.9
9.990
4.839
TGD-VA3-01
0.480
106.130
-1.6
Bus33
0.052
0.014
60.4
Bus34
0.002
0.014
15.4
11.8
Bus23
-0.178
-0.068
214.7
93.4
-33.628
-16.278
178.9
90.0
T - L. Teca
23.605
10.827
124.3
90.9
Teca 13.8 kV
10.023
5.451
54.6
87.8
TECA
-9.990
-4.839
435.4
90.0
Barra_B
-0.232
-0.113
292.5
89.8
Cocorna - EPM
% Tap
-1.500
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MINIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
THCMT-0202 A
Voltage
kV
6.300
% Mag.
107.365
Generation
Ang.
-0.6
MW
Load
Mvar
MW
Load Flow
Mvar
ID
THCMT-0202 B
6.300
107.426
-0.4
THCMT-0202 C
6.300
107.183
-0.8
0.051
0.026
65.0
89.6
0.088
227.5
89.9
TMOVS-VA3-01
0.000
0.000
0.0
0.0
99.3
Bus6
-0.788
-0.091
67.7
Bus32
0.000
0.000
0.0
0.0
Bus28
0.788
0.091
67.7
99.3
Bus2
0.000
0.000
0.0
0.0
Bus14
1.193
0.318
105.6
96.6
Bus17
0.233
0.118
22.3
89.2
Bus12
-1.425
-0.436
127.4
95.6
0.000
0.000
0.0
0.0
-0.4
VAS-PTO BOYACA
T - L. Teca
110.000
108.952
-0.4
VAS-TECA
TECA
Ocensa B1
-1.6
TR4-AT
6.300
107.347
-0.6
VAS-JAZMIN-A
VAS-JAZMIN-B
VAS-PALAGUA
110.000
110.000
110.000
108.952
108.952
108.952
-0.4
-0.4
-0.4
TGD-VA3-01
108.952
-0.4
110.000
108.952
-0.4
VAS-T3
VAS-TECA
110.000
110.000
110.000
108.952
108.952
108.952
-0.4
-0.4
-0.4
92.3
90.6
14.670
7.273
78.9
89.6
0.000
0.000
0.0
0.0
-0.090
67.7
99.3
0.788
0.090
67.7
99.3
VAS-JAZMIN-B
1.107
0.270
5.5
97.2
Jazmn - MSB
5.631
2.951
30.6
88.6
90.2
VAS-PALAGUA
-6.738
-3.221
36.0
VAS-JAZMIN-A
-1.107
-0.270
5.5
97.2
VAS-T1
1.107
0.270
5.5
97.2
Palagua - ECP
0.983
0.184
4.8
98.3
6.738
3.221
36.0
90.2
-7.720
-3.404
40.6
91.5
T - L. PTO Boyaca
0.000
0.000
0.0
0.0
VAS-PALAGUA
7.720
3.404
40.6
91.5
91.5
-7.720
-3.404
40.6
Bus6
0.788
0.093
3.8
99.3
VAS-T2
0.319
0.176
1.8
87.5
-1.107
-0.270
5.5
97.2
VAS-JAZMIN-B
VAS-T2
46.1
124.9
-0.788
VAS-TECA
VAS-T1
3.674
-10.947
Barra-B
VAS-PTO BOYACA
110.000
8.827
-23.498
CCM2
VAS-JAZMIN-A
VAS-PTO BOYACA
% PF
0.180
108.952
106.130
Amp
CCM-VA3-01
110.000
0.480
XFMR
Mvar
Bus22
T - L. PTO Boyaca
TMOVS-VA3-01
MW
Bus2
0.000
0.000
0.0
0.0
VAS-T1
-0.319
-0.176
1.8
87.5
VAS-T3
0.319
0.176
1.8
87.5
Bus12
1.426
0.446
7.2
95.4
VAS-TECA
-1.107
-0.270
5.5
97.2
VAS-T2
-0.319
-0.176
1.8
87.5
VAS-T3
1.107
0.270
5.5
97.2
-8.827
-3.674
46.1
92.3
T - L. Teca
% Tap
-3.000
Project:
Location:
ETAP
7.5.0C
ESTACIN VASCONIA
Contract:
Engineer:
G.RODRGUEZ
Filename:
OT40 VASCONIA
Study Case: LF
Page:
Date:
05-07-2012
SN:
PROCYDISEN
Revision:
Base
Config.:
MINIMO
INGENIERA DETALLADA PARA EL INCREMENTO DE CAPACIDAD A +220 KBPD EN EL OLEODUCTO VAS-CIB EN LA ESTACIN DE VASCONIA
Bus
ID
Voltage
kV
% Mag.
Ang.
Generation
MW
Mvar
Load
MW
Load Flow
Mvar
ID
VAS-PTO BOYACA
* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA
MW
7.720
XFMR
Mvar
3.404
Amp
40.6
% PF
91.5
% Tap