LEVEL SWITCH DATA SHEET

Sheet No

1 of 1

TAG NO.
To sense level of coal dust in hopper and give a
signal on relay and give level indication

Service

NO: ELAC030003
Preliminary

Prepared by

vsc

SRH

For Inquiry

Approved by

ps

MSK

For Order

Date
Revision Index

12/1/2007 19/9/2008
0

APPLICATION DETAILS
PROCESS MEDIA

DUSTY GASES OF CEMENT / COAL ETC

SUPPLY VOLTAGE

UNIVERSAL 110 V / 230 V 50 Hz. 1 Ph.

MAKE

EIP ENVIRO LEVEL CONTROLS PVT. LTD.

MODEL

550

ELECTRICAL DETAILS

TYPE

RF / CAPACITANCE

INITIAL CAPACITANCE RANGE

ADJUSTABLE AT SITE

SWITCHING HYSTERESIS

N/A

RESPONSE TIME

0.3 SEC.

SWITCHING DELAY

0.5 SEC.

AMBIENT TEMP.

0 DEG. C. TO 60 DEG. C

INDICATION

RED LED FOR HIGH LEVEL, GREEN LED FOR NORMAL LEVEL

OUTPUT

2 SET OF CHANGEOVER CONTACT OF RELAY RATED 5 A AT 230 V AC

FAIL SAFE MODE

MAN. / MAX. SELECTABLE AT SITE

POWER CONSUMPTION

4 VA

HOUSING / MOUNTING

CAST ALUMINIUM

DIMENTION (H X D )

159x158

WEIGHT

12 Kg.

OPERATING FREQUENCY

200 khz APPROX.


CAST ALUMINIUM WEATHER PROOF HOUSING /IP 66 FIELD MOUNTED

ENCLOSURE / MOUNTING
PART INSULATED PROBE
a)PROCESS TEMP.
b) INSULATION

UP TO 160
PTFE

c) ACTIVE SHIELD & PROBE ROD

SS -304

d) INSERTION LENGTH

610 MM OVER ALL LENGTH

e) CABLE ENTRY

3/4" ET /1 NO. CABLE GLAND TO BE PROVIDED WITH UNIT

f) MOUNTING

1 1/2" BSP (M) (MATCHING SOCKET TO BE PROVIDED)

g)SPECIAL RF COAXIAL CABLE

10 MTRS

SCOPE OF SUPPLY

1 NO. LEVEL SWITCH ( PROBE + AMPLIFIER ) & 10 MTRS. CABLE. REQUIRED ACCESSORIES & OTHER
SPECS. AS PER PART CATALOGUE.

INSPECTION & TESTING REQUIREMENTS


INSPECTION

BY THERMAX,CLIENT,CONSULTANT

DOCUMENTS SUBMITTED ALONG WITH SUPPLY


06 set of O & M Manual.

GUARANTEE
18 MONTHS FROM DATE OF SUPPLY OR 12 MONTHS FROM DATE OF COMMISSIONING WHICHEVER IS EARLIER
REV NO

REVISION DETAILS

REV BY

DATE

PART NO. REVISED FOR ERP & PROCESS CONNECTION SOCKET THREADING CHANGE FROM NPT
TO BSP.

SRH

19/9/2008

NOTE :
The serial number should be mentioned on the unit and also on all inspection reports.
Thermax spcification sheet number should be mentioned on all inspection reports
Supplier to confirm specification as mentioned above devation/ discrepancy if any should be informed before suppling the material .