CALCULATION FOR NEUTRAL GROUNDING TRANSFORMER

PROJECT : 11KV, 40MW CONDENSING TYPE TURBO GENERATOR


Generator MW Rating
Generator KV Rating
Generator Capacitance/Ph (U(Micro Farad)
Connected Capacitance(assumed)/Ph (Micro Farad)
Connected Capacitance(assumed)/Ph (Micro Farad)
Net Capacitance/Ph
LAPT Capacitance/Ph (Micro Farad)
Total Capacitance (Micro Farad)
3 X Capacitance
Xc
Capacitor Current/Amps
Field Forcing Allowance
(a)
NGT Vk (KV)
(b)
Insulation (KV)
(Vp)

57 **
11 **
0.286 **
0.0572 **
0.006 **
0.3492
0.3 **
0.6492
1.9476
1634.37
3.885811
5.828717
11 **
11 **

NGT KVA
Rounded off KVA

64.11588
65

(a x b)

Equ. Primary Resistance

(c)

Secondary Voltage Selected

(Vs)

1634.37
240 **

Secondary Resistance
c x ( Vs/Vp) Sq.
Trafo. Resistance (assumed)/Ohms
External Resistance/Ohms(Total Res. - Tr.Resistance) Rs

0.778014
0.05708
0.720934

Current Rating/Amps
I
Rounded Off Current Rating

90160.81
300.2679
301

NGA Rating :
NGR Rating (LR):
** values to be entered

KVA/Rs = Isq =
=

65 KVA
0.720934 +/_ 10%

For 30sec
Ohms