Monitors two High Voltage DC

(HVDC) circuits per unit


Wireless for simple plug and play
monitoring
Local LED display
Highly secure wireless network
isolates monitoring devices from
primary data networks

The first wireless HIGH VOLTAGE DC (HVDC)


Monitoring system designed for Data centers
The Packet Power wireless HVDC monitoring system utilizes an advanced design
to provide full load, power and energy information while minimizing costs. The
system consists of:
Wireless Current Monitoring Monitor: The compact DC-CMM monitors two HVDC circuits
and installs quickly and easily using a standard 1.25 knockout hole. A bright LED display
makes information available at a glance.
Wireless HVDC Power Monitor: The DC-PMM adds voltage monitoring capabilities and
serves as the voltage reference for all DC-CMMs sharing a bus. Only one DC-PMM is needed
per bus to provide power and energy information for all circuits monitored by DC-CMM
monitors.

Scales easily from 10 to thousands


of monitoring points
SNMP or Modbus TCP/IP output
for easy integration with BMS and
DCIM systems.
Integrates fully with other Packet
Power devices
Optional EMX Energy Portal makes
information immediately available
after installation
Global certifications
Wireless technology proven in
critical facilities

Wireless Ethernet Gateway: The HVDC power monitoring system uses Packet Powers
wireless network to form a self configuring wireless network that automatically adapts as
devices are added or removed.

Packet Power Mesh Network Architechture


DC CMMs

MONITORING

GATEWAY
Monitor your system instantly using the EMX portal

THIRD PARTY INTERFACE


DC PMM

SNMP / MODBUS

V
Packet Power LLC 2014
Packet Power LLC 2014

Interface for BMS and


DCIM systems via SNMP or
ModBus

WIRELESS HVDC MONITORING

FEATURES

Packet Power wireless monitoring is secure, cost effective and easy to install.

DC-PMM
DC-CMM

DC-CMM

V, A, W, Wh
per circuit

Technical Specifications
MEASUREMENT
PMM: Voltage Channels / Sources
CMM: Current Channels
Measurements (per circuit):
Accuracy
Temperature
Current Transducer Module

Two independent 270 V DC voltage inputs


Two
Voltage, Current, Watts, Watt Hours
1.0% accuracy
Internal temperature 2C
35 A or 65 A versions with two transducers per module

COMMUNICATIONS
Operating Frequency
Wireless Network Protocol
Data output (Gateway)

Firmware Updates
Typical transmission range
Antenna
Monitoring Unit to Gateway Radio
Multi-site Support
Encryption
System Status

860 to 930MHz and 2.4 GHz; frequencies specific to region


Frequency hopping self-configuring load-balancing mesh
SNMP and Modbus TCP/IP protocols with one IP address needed per
Gateway. EMX cloud or local energy management system available
Wireless
10 to 30 meters indoors between any two devices in mesh network
Fully enclosed, fixed configuration
Up to 300 monitoring units per gateway with unlimited Gateways per site
Yes
128-bit encryption
Local LED display for measurement readings

OPERATING ENVIRONMENT AND


MECHANICAL
Operating Temperature
Operating Humidity
Power Monitor Dimensions
Input Voltage Range (measure and supply)

0 to +70 C (+32 to +104 F)


10% to 90% non-condensing
Display Bezel: 2.0 diameter x 0.75 height Stem:1.25 diameter x 0.5 height
270 VDC nominal

Packet Power, 2716 Summer St. NE, Minneapolis, MN, 55413 USA
Tel: (1) 877-560-8770 - Fax: (1) 866-324-2511
www.packetpower.com
Packet Power LLC 2014

DCW 1.0

WIRELESS HVDC MONITORING