INFORMATIONS TO DESIGN A CONTROL VALVE

Line Size -

100 MM

Tag No.-

ITEM NO. 40

State of the Flow Medium -

STEAM

Name Of the Flow Medium -

STEAM

Pipe Schedule Service -

80
STEAM

Flow Parameters :
Min.

Nor.

Max.

Flow Rate - (TPH/ M3/HR)

0 TPH

1.2 TPH

2 TPH

Inlet Pressure (kg/cm2 / Bar g)

0 BAR

5.5 BAR

6 BAR

Outlet Pressure (kg/cm2 / Bar g)

0 BAR

5 BAR

5.5 BAR

Pressure Drop (kg/cm2 / Bar g)

0.5 BAR

0.5 BAR

250

260

270

Temperature (degree C)
Design Pressure -

6 BAR

Design Temperature -

260 DEG C

Body Material -

VENDOR TO SPECIFY

Body Rating -

VENDOR TO SPECIFY

IBR Certification -

REQUIRE

Duty - Modulating / ON-OFF

MODULATING

End Connection -

FLANGE

Actuator -

Pneumatic / Electrical

PNEUMATIC

For Pneumatic Actuator :


Actuator Action -

LINEAR

Air Fail Position -

OPEN

Positioner -

SMART

I/P Converter -

INBUILD

Position Feedback Transmitter -

4-20 mA

Hand Wheel -

REQUIRE

Limit Switches -

NOT REQUIRED

For Smart Positioner -

HART / FF / PB

Solenoid Valve -

NOT REQUIRED

HART

INFORMATIONS TO DESIGN A CONTROL VALVE


Line Size -

200 MM

Tag No.-

ITEM NO. 60

State of the Flow Medium -

STEAM

Name Of the Flow Medium -

STEAM

Pipe Schedule Service -

Flow Parameters :
Min.

Nor.

Flow Rate - (TPH/ M3/HR)

0 TPH

5.0 TPH

Inlet Pressure (kg/cm2 / Bar g)

0 BAR

5.5 BAR

Outlet Pressure (kg/cm2 / Bar g)

0 BAR

5 BAR

Pressure Drop (kg/cm2 / Bar g)

0 BAR

0.5 BAR

250

260

Temperature (degree C)
Design Pressure -

6 BAR

Design Temperature -

Body Material -

VENDOR TO SPECIFY

Body Rating -

IBR Certification -

REQUIRE

Duty - Modulating / ON-OFF

End Connection -

FLANGE

Actuator -

Pneumatic / Electrical

For Pneumatic Actuator :


Actuator Action -

LINEAR

Air Fail Position -

OPEN

Positioner -

SMART

I/P Converter -

INBUILD

Position Feedback Transmitter -

4-20 mA

Hand Wheel -

REQUIRE

PNEUMATIC

Limit Switches -

NOT REQUIRED

For Smart Positioner -

HART / FF / PB

Solenoid Valve -

NOT REQUIRED

HART

80
STEAM

Max.

6 TPH
6 BAR
5.5 BAR
0.5 BAR
270
260 DEG C
VENDOR TO SPECIFY
MODULATING

INFORMATIONS TO DESIGN A CONTROL VALVE


Line Size -

150 MM

Tag No.-

ITEM NO. 50

State of the Flow Medium -

STEAM

Name Of the Flow Medium -

STEAM

Pipe Schedule Service -

Flow Parameters :
Min.

Nor.

Flow Rate - (TPH/ M3/HR)

0 TPH

3 TPH

Inlet Pressure (kg/cm2 / Bar g)

0 BAR

5.5 BAR

Outlet Pressure (kg/cm2 / Bar g)

0 BAR

5 BAR

Pressure Drop (kg/cm2 / Bar g)

0 BAR

0.5 BAR

250

260

Temperature (degree C)
Design Pressure -

6 BAR

Design Temperature -

Body Material -

VENDOR TO SPECIFY

Body Rating -

IBR Certification -

REQUIRE

Duty - Modulating / ON-OFF

End Connection -

FLANGE

Actuator -

Pneumatic / Electrical

For Pneumatic Actuator :


Actuator Action -

LINEAR

Air Fail Position -

OPEN

Positioner -

SMART

I/P Converter -

INBUILD

Position Feedback Transmitter -

4-20 mA

Hand Wheel -

REQUIRE

PNEUMATIC

Limit Switches -

NOT REQUIRED

For Smart Positioner -

HART / FF / PB

Solenoid Valve -

NOT REQUIRED

HART

80
STEAM

Max.

3.6 TPH
6 BAR
5.5 BAR
0.5 BAR
270
260 DEG C
VENDOR TO SPECIFY
MODULATING

INFORMATIONS TO DESIGN A CONTROL VALVE


Line Size -

150 MM

Tag No.-

ITEM NO. 70

State of the Flow Medium -

OXYGEN

Name Of the Flow Medium -

OXYGEN

Pipe Schedule Service -

Flow Parameters :
Min.

Nor.

0 M3/HR

2500 M3/HR

Inlet Pressure (kg/cm2 / Bar g)

0 BAR

2.5 BAR

Outlet Pressure (kg/cm2 / Bar g)

0 BAR

2.3 BAR

Pressure Drop (kg/cm2 / Bar g)

0 BAR

0.2 BAR

25

30

Flow Rate - (TPH/ M3/HR)

Temperature (degree C)
Design Pressure -

3 BAR

Design Temperature -

Body Material -

VENDOR TO SPECIFY

Body Rating -

IBR Certification -

REQUIRE

Duty - Modulating / ON-OFF

End Connection -

FLANGE

Actuator -

Pneumatic / Electrical

For Pneumatic Actuator :


Actuator Action -

LINEAR

Air Fail Position -

OPEN

Positioner -

SMART

I/P Converter -

INBUILD

Position Feedback Transmitter -

4-20 mA

Hand Wheel -

REQUIRE

Limit Switches -

NOT REQUIRED

PNEUMATIC

For Smart Positioner -

HART / FF / PB

Solenoid Valve -

NOT REQUIRED

HART

40
OXYGEN

Max.
3200 M3/HR
3 BAR
2.8 BAR
0.2 BAR
32
30 DEG C
VENDOR TO SPECIFY
MODULATING