PT GNI Ceragon
g
networks Indonesia

MW Split mount system installation method

Revision 1.2
May 2008

Created by:
Adam Landes,
Projects Director Ceragon Indonesia.

ANTENNA LINE
Coax Cable Grounding Kit positions

In a tower and equipment room there are 3 coax grounding points with a
optional fourth one:
1.
1

At the highpoint of installed antenna under the antenna to the


closest tower grounding bar (TGB) following a downward path

2.

At the bottom of the tower TGB before the cable turns from
vertical to horizontal.

3.

A lightning arrestor at the MGB at the entry to the shelter (entry


gland MGB)

4
4.

In case of vertical cable length of more than 30meters an


additional coax grounding point is optional to be installed above
the center tower TGB.

5.

Each radio unit will have a separate grounding cable directly to


the closest TGB under it. This can be done directly to the tower
TGB or to a sub TGB next to the antenna mounting.

TGB

1
4. optional additional point if
over 30m vertical

TGB

3. Lightning arrestors
Cable entry
glands

2
TGB

To ODU

Coax

MGB
To TGB

Sub TGB
Shelter wall

Cabling layout at Antenna / ODU


Note: For radio configurations and connections
please refer to the document:

HPinstall-1-08
Doc ID: DOC
DOC-00015514
00015514 Rev a.06

Outdoor cable ties to support


Wave Guide

Flexible waveguide

Coax and
grounding shall
follow the same
path to the
tower cable
ladder, (or Sub
TGB) cable ties
will be placed
every 50 Cm
along the path

Weatherproofing
mandatory

Sub TGB

Outdoor type Black cable ties 9x30 or larger

Outdoor type Black cable ties 9x30 or larger

Tower cable ladder

Antenna fixed strut bar method

Grounding installation method lighting arrestors


1.
2.
3
3.
4.

5.

6.

Connect yellow green cable to MGB


(main grounding bar).
Create path to determine position to
install arrestor (cutting point).
C tC
Cut
Coaxial
i l cable
bl and
d Prepare
P
NN
type connectors (in the kit) at both
ends of the cut Coax cable.
Install arrestor by connecting it to
both connectors and close
connectors with open end crescent
wrench
wrench.
Weather proof the assembly
according to weather proofing
method lightning arrestors slides
number 8 and 9.
Connect yellow green grounding
cable and secure the nut with 13mm
open wrench.

Lightning arrestor

Indoor

Step 5 Weatherproofing

outdoor
Step 4

Cable entry Glands


Step 6
Step 2

Step 3 Connector preparation

Step 1 connect
grounding cable - One
cable p
per hole ONLY !!!

I
Important
t t Note
N t
Use cable ties where
necessary to obtain
straight path and
neat installation

MGB

To Site Main Grounding ring

Connector weatherproofing
p
g method

50 % overlap

ODU (outdoor radio unit)

1
2
4
1. PVC insulating tape x 2 layers 50% overlap
2. Insulating rubber tape x 2 layers 50% overlap

3
40mm
N-type connector

3. PVC insulating tape x 2 layers 50% overlap


4. Place cable ties at the designated places

Coax cable g
grounding
g method
Grounding Kit on coaxial cable installation order

2. Connect
grounding kit to
Coax cable

1.
2.
3.
4.

Connect grounding kit to Tower Grounding Bar (TGB)


Create a path as straight as possible to the Coax and connect
grounding
di Kit tto C
Coax cable
bl
Place cable tie every 20 cm along the cable from the TGB to
the connector
Weather proof according to standard (figure 1.2)
1. 2xPvc Tape
2 2xRubber
2.
2 R bb T
Tape
3. 2xPvc Tape

40mm

3. Cable tie every 20cm

50 % overlap
40mm

1. Connect
grounding kit
to TGB
Correct

Not correct
Figure 1.2 - Correct method

Weather p
proofing
g method- lightning
g
g arrestors
Cable ties
Cable entry Gland

40mm

40mm

A
50 % overlap

Lightning arrestor

1. PVC insulating tape x 2 layers 50% overlap


2. Insulating rubber tape x 2 layers 50% overlap
3. PVC insulating tape x 2 layers 50% overlap
4. After completing steps 1-3 Connect grounding cable A"
A (supplied) to grounding bolt B
B
5. Place cable ties at the designated places

Step by step Weatherproofing lightning protection

1. Installation direction

2. 2 layers 50%
overlapping PVC tape

3. 2 layers 50% overlapping


rubber tape

4. 2 layers 50% overlapping PVC tape

5. Connect 4 cable ties (black outdoor type)


to hold tape in place
6. Connect yellow green grounding cable to complete installation.

10

3200T split mount with MUX layout and cable


method in 19
19rack
rack
Follow the general principal depicted here for all configurations.

Spiral plastic
protection on
exposed fiber optic
cable

Spiral
p
plastic
p
protection
p
on exposed
p
fiber optic
p cable
3200T cable layout and labeling
1+1 rack layout

10

11

3200T split mount with MUX layout and cable


method in 19
19rack
rack
Follow the general principal depicted here for all configurations.

Rack cable layout

MUX and
d DDF

11

12

3200T split mount with MUX layout and cable


method in 19
19rack
rack
Follow the general principal depicted here for all configurations.
Spiral plastic protection on exposed fiber optic cable

LSA (Krone 3/8) layout and labeling in DDF

MUX cable layout and labeling

12

13

3200T split mount with MUX layout and cable


method in 19
19rack
rack
Follow the general principal depicted here for all configurations.

Fiber optic cable layout in storage tray

Cable arrangement MUX to DDF

13

14

Distribution frame (DDF) cabling method


Follow the general principal depicted here for all configurations.
Spare PCM from front
= 100mm

PVC tape

Color scheme
according
di to
t cable
bl
spec

F Incoming
For
I
i Cable
C bl (from
(f
Mux)
M )

DDF Cabling method

For Outgoing Cable


Indoor Cable ties
To disconnect module

DDF Frame
To Mux
Front

Back

Spare on
DDF rear
bar
Must leave spare of 2 times the rack width = 80cm +10cm from the front of the DDF for maintenance

14

15

Distribution frame (DDF) cabling method


DDF Cabling PIM2_21 Connection Data - RX

15

16

Distribution frame (DDF) cabling method


DDF Cabling PIM2_21 Connection Data -TX

16

17

3200T split mount with MUX layout and cable


method in 19
19rack
rack
Follow the general principal depicted here for all configurations.

DDF grounding

LSA (krone block) spacing in DDF

17

18

3200T split mount with MUX layout and cable


method in 19
19rack
rack
Follow the general principal depicted here for all configurations.

N-Type
yp L connector

N-Type
N
Type connector with L adaptor

Coax cable connector options - Indoor

18

19

Typical
yp
19rack and equipment
q p
layout
y
16mm grounding cable

This is a typical layout guideline for


equipment layout in a 19 rack, this
layout may vary according to the
amount of IDU / DDF needed but the
general concept must be preserved i.e.

Rack grounding bar

DCPDB
MGB

DCPDB

IDU
Minimum 7 holes

IDUs (In Door Unit) i.e. 3200T /


1500HP (according to configuration)
Fiber optic cables storage tray (where
applicable)
Mux (Multiplexer) XDM100 (or other
depending on sys configuration)
DDFs ((Distribution frame)) 3/8 or 2/10
Krone profile system (according to
configuration)

Fiber optic cable


storage tray
MUX

DDF

Minimum 3 holes
Minimum 5 holes

Minimum 3 holes

19

20

19 Rack - unit Grounding layout


16mm grounding cable

Rack grounding bar

Inside frame

DCPDB
TGB
IDU 3200T

Fiber optic cable


storage trey
Important Note - All frame internal cabling
will be fastened with cable ties every 20cm

MUX XDM 100

DDF

20

21

Ladder transition Cable layout


y
All cable positions / path must be maintained on the cable trays / ladders as shown in this drawing:

Cable tray/ladder Indoor

Cable ties indoor type

21

22

Cable layout
y
on support
pp
trays
y
Indoor cable ties

Grounding
g

Coax
PCM
19 DCPDB to Rectifier
DC to Rectifier

Cables shall be separated on the tray/ladder according to


type.
In event of multiple instances (cables from different
installations occupying the cable tray/ladder) cables shall be
grouped
db
by ttype on ttop off each
h other
th as ffollows:
ll

22

23

Cutting
g cable ties
Cable ties MUST be cut following these samples:

Dangerous protruding edge NOT OK

Flat smooth surface - OK

Use Flush wire cutter for cutting cable ties


Tool samples:

23