Professional Documents
Culture Documents
4 6 March 2013
INDUCTION COURSE IN
AIR-CONDITIONING
1)
2)
3)
4)
5)
6)
7)
8)
9)
INTRODUCTION TO AIR-CONDITIONING
PRINCIPLES OF REFRIGERATION
PSYCHROMETRICS
COOLING LOAD ESTIMATION & SOFTWARE
REFRIGERANT ISSUE
TYPES OF AIR CONDITIONING SYSTEMS
AHRI 550/590 or MS2449 FOR CHILLERS
MS1525:2007
Green Building Index ( GBI )
Climatic conditions
Outdoor environment
Indoor environment
Activities & clothing
Comfort Requirements
Temperature
Humidity
Air movement
Fresh air
Clean air
Noise level
Lighting
Furniture and work surfaces
2. What is a Refrigerant?
A refrigerant is a fluid that absorbs heat and changes from
vapor to liquid phase at reasonable pressures and temperatures
as encountered in mechanical refrigeration.
Principles of Refrigeration
The science of refrigeration is based upon the fact that a liquid can
be vaporised at any desired temperature by changing the pressure
on it.
Liquids boiling at low temperatures (Refrigerants) are the most
desirable medium for removing heat.
The large quantities of heat is absorbed when liquid is evaporated
(Changed to vapour).
2.What is a Refrigerant
.
PRESSURE psia
F
Water
-40
HCFC-22
HFC-410A
0.00186
15.26
26
0.0185
38.73
40
0.122
100
CO2
Propane
7.43
145.77
16.1
64
21.62
305.80
38.4
82.28
132
49.70
567.50
78.6
0.950
210.70
340
138.80
188.6
130
2.225
311.60
500
213.40
273.3
212
14.696
*CP
*CP
587.20
HFC-134a
Sensible Heat
Btu is the heat energy necessary to
change one pound of water by 1 F
Btu British thermal unit
1 F
RISE
1 lb
1 Btu
Latent Heat
Total Heat = Sensible Heat + Latent Heat
212 F
212 F
Not measured on
a thermometer
Change of State
Refrigeration Cycle
The refrigeration can be obtained by use of
the refrigerants.
When the liquid refrigerants are allowed to
expose to the atmosphere, it evaporates and
refrigeration can be obtained.
To make use of the vaporised refrigerant
over and over again it is necessary to use
the devices like evaporator, compressor and
condenser.
2. Vapor
pump
108 F
274.7 psia
120 F
274.7 psia
SCT
SDT
Air in: 95 F
SST
Air out: 59.7 F db / 57.3 F wb
Evaporator
Evaporator
Compressor
Compressor
45 F
90.8 psia
55 F
90.8 psia
SET
Air in: 80 F db / 67 F wb
Condenser
Rejects the heat from the load
and system losses
Highly superheated refrigerant
condenses in the tubes as heat load is
rejected and changes back to a
liquid and is subcooled
3. Psychrometrics
Objectives
Understand the properties of air and water
vapor mixtures
Build the psychrometric chart
Use the psychrometric chart to determine
the properties of an air/water vapor mixture
Use the psychrometric chart to understand
the basic air conditioning processes
Understand how the processes can be
combined into a system using a system plot
diagram and psychrometric chart
Section 1 Introduction
Dry-Bulb Thermometer
Wet-Bulb Thermometer
Sling Psychrometer
Water
Vapor
Dry Air
Air + Vapor
Mechanical Mixture
Relative Humidity ( RH )
50%
100% (saturated)
Relative Humidity
Relative
Humidity =
wb dp
F
db F
100 gr
wb dp
F
db F
55 67
95
Condensation Occurs at
Dew Point
132 gr
45%
wb dp
F
db F
75
60 gr
Enthalpy Scale
hs = Enthalpy at saturation
hs = 27.5 Btu/lb
wb dp
F
db F
Psychrometric Chart
Enthalpy
Specific
Volume
Relative
Humidity
Specific
Humidity
wb dp
F
db F
Dry Bulb
Temperature
Sensible Heating
Sensible Cooling
Humidification
Dehumidification
Cooling and Humidification
(Evaporative Cooling)
6. Cooling and
Dehumidification
7. Heating and
Humidification
8. Heating and
Dehumidification
wb dp
F
db F
Sensible Heat
qs 1.10 cfm t
db
wb
dp
gr
Changes
Changes
Constant
Constant
68% rh
24% rh
COOLING
52 gr
HEATING
wb dp
F
90 60 = 30
t
db F
60
90
Latent Heat
q l 0.69 cfm grains
Changes
Changes
Changes
Constant
68% rh
Evaporation
Condensation
wb
dp
gr
db
wb dp
F
db F
75
24% rh
grains
89 30 = 60
89 gr
Latent
Heat
Change
30 gr
Total Heat
qt qs ql
Grains
t
Evaporation
wb dp
F
Condensation
Cooling
Heating
db F
75
95
89 gr
Latent
Heat
Change
30 gr
Latent Heat
1.7
Sensible Heat
5.0
wb dp
F
db F
55
75
Cooling Coils
Face Area = Length Height
Length
Height
Velocity
cfm / face area
Rows
Fins
Refrigerant
Temperature
- Location/altitude/ orientation
Transmission through Building Components walls, glass, ceilings, roofs, doors and floors,
partitions from non conditioned spaces.
Solar Radiations on - glass, wall, roof, etc.
residential occupancies.
The airflow rate per square foot of building floor area is basedon the design occupancy density and the required flow rate per person,
adjusted to reflect the air distribution system used.
1.)
2.)
Air Rate
Air Rate
Default Values
Occupant
Density
Combined
Outdoor
Air Rate
Category
Rp
Ra
cfm/
person
L/s
person
cfm/ft
L/s
m
Office
Space
2.5
0.06
Reception
areas
2.5
0.06
#1000 ft
or #100 m
cfm/
person
L/s
person
0.3
17
8.5
0.3
30
3.5
Office
Buildings
2.5
0.06
0.3
10
11
5.5
Barracks sleeping
areas
2.5
0.06
0.3
20
4.0
Laundry rooms,
central
2.5
0.12
0.6
10
17
8.5
2.5
0.12
0.6
10
17
8.5
7.5
3.8
0.06
0.3
30
10
4.8
2.5
0.06
0.3
120
2.8
dwelling units
Lobbies / pre-function
Multipurpose assembly
MS1525-2007
Air Conditioning and Mechanical Ventilation (ACMV) System
a)
b)
c)
d)
e)
a)
33.3C / 27.2C
( 92F/ 81F )
Type of Refrigerants
CFC
HCFC
HFC
R-11
R-12
R-13
R-500
R-502
R-503
R-22
R-123
R-401A
R-401B
R-402A
R-402B
R-408A
R-409A
R-134a
R404A
R-407C
R-410A
R-507
HFO
HFO
1234fy
Outdoor air
Condensing Unit
Floor Standing
Cassette
Ceiling Exposed
Typical Cooling
Capacity (kWr)
Remark
Wall mounted
2.64-7.03
Most common
Ceiling cassette
5.26-14.65
Most aesthetic
Floor Standing
7.03-14.65
Not so Common
here
Under Ceiling
Exposed
5.26-17.60
Can be Floor
mounted
Office
Restaurant
Shop Office
Advantages
Other Systems
Low Efficiency
No Fresh Air
Potential IAQ
issues
A fan may be
added if the
intake is far
away.
- WC Packaged
- Typ. Capacity range
from 20 100 Hp
- Floor Standing
Typical kw / ton around 1.0- 1.2 kw/ton
Advantages
Flexibilities
Better RH than
ACSUs
Space Saving
Better EE than
ACSUs
Others Systems
Moderate Energy
Efficiency
Compared to
CHWS
Potential IAQ
Problem
80F
(26.7C)
54F
(12.2C)
50F 110F
(10C)(43.3C)
97F
(36.1C)
condenser
55F
(12.8C)
44F
(6.7C)
41F 100F
(5.0C)(37.8C)
87F
(30.6C)
cooling
tower
pump
Airside Loop
(AHU & Air Duct)
Refrigeration Loop
(Water-cooled Chiller)
evaporator
Airside Loop
(AHU & Air Duct)
expansion
device
Refrigeration Loop
(Air-cooled Chiller)
air-cooled
condenser
44F
[6.7C]
54F
[12.2C]
3-way valve
Primary-Secondary Configuration
primary
pumps
Variable
secondary
pump
production
loop
distribution
loop
two-way valve
Variable-Primary-Flow Systems
Variable-flow
pumps
check
valves
control
valve
two-way
valve
optional bypass
with three-way valve
Chiller
Chiller
(Constant
Flow)
(Constant
Flow)
Decoupling Bypass
Isolation
Valves
Load
Load
(Variable
Flow)
(Variable
Flow)
Control
Valves
Primary Pumps
(Constant Speed)
80
Helical-Rotary
Screw
Centrifugal
Compressor
Air-cooled Chiller
20 100RT for Scroll
70 500 RT for Screw
Typical Efficiency
range 1.1 1.3 kw/ton
Applications :
Retail, Commercial,
Industrial & Government
Water-cooled Chiller
20 100RT for Scroll
70 400RT for Screw
100 2500 RT
Typical Efficiency
range 0.5 0.7 kw/ton
Applications :
Retail, Commercial,
Industrial & Govt.
Buildings
Installed Cost
Energy Consumption
Type of Application
Space Requirements
Building Aesthetics
System Capacity
Centralized Maintenance
Stability of Control
Redundancy
Air-Cooled vs Water-Cooled
Air-cooled
Water-cooled
Life Span
15 - 20 years
20 - 30 years
System EE kW/ton
1.0 - 1.3
0.9 - 1.1
Maintenance
Lower
Higher
Noise Containment
Open
Enclosed
Space Requirement
Less
More
Cost
Lower
Higher
Capacity Range
3 - 500RT
50 - 2,500RT+
DHW
12%
Lighting
10%
Other
Equipment
15%
Variable Frequency
Drive (VFD)/
Variable Speed Drive
(VSD)/ Speed
Controller
-Improve comfort levels
-Reduce operating costs,
Central
Plant
39%
Illuminated enclosure
GREEN: normal
RED: fault
Static Pressure2
Static Pressure1
Air Flow2
Air Flow1
Input Power2
Input Power1
Air Flow2
Air Flow1
e.g
80% speed
Input power
= (0.8x0.8x0.8)
= 0.51 or 51%
Supply Fan
T
Supply
Fan
Sensor may be in
return air duct.
3. Air Diffuser
4. Return Grille
5. Duct Static Pressure
Sensor
6. Supply Fan VFD
7. AHU
8. Supply Duct
Section 1 Introduction
Zone 1
Zone 2
Zone 3
Zone 4
Supply Fan
Drive
Conditioned
Space
T
T
Sensor may be in
return air duct.
MS 1525:2007
Code of Practice on
Energy Efficiency and
Use of Renewable
Energy for NonResidential Buildings
(1st Revision)
Eurovent
JIS
GB
MS2449:2012
MS 2449:2012
Performance
rating of waterchilling packages
using the vapor
compression cycle
44F
[35C]
44F
97F
[6.7C
[6.7C] [36.1C]
85F
87F
[29.4C]
[30.6C]
ARI
conditions
Malaysia
Conditions
54F
54F
[12.2C]
[12.2C]
evaporator
flow rate
condenser
flow rate
2.4 gpm/ton
[0.043 L/s/kW]
3.0 gpm/ton
[0.054 L/s/kW]
evaporator
flow rate
condenser
flow rate
2.4 gpm/ton
[0.043 L/s/kW]
3.0 gpm/ton
[0.054 L/s/kW]
CHILLED
WATER
F
FCU
COOLING
TOWERS
15C
AHU
MAIN RISER
FEED 6C
15C
AHU
AHU
RETURN
AIR FAN
MAIN RISER
RETURN 9 - 12 C
15C
By Air
T
By Refrigerant
PRIMARY CHILLED
WATER PUMPS
By Air
CONDENSER
CHILLER 3
SECONDARY
CHILLED
WATER PUMPS
CHILLER 2
15C
CHILLER 1
EVAPORATOR
CONDENSER
WATER PUMPS
By Water
The
importance
of
controlling
the flow of
air and water
in HVAC
systems
=____________1____________
0.01 + 0.42 + 0.45 + 0.12
A
45%
100% Load
1%
50% Load
75% Load
42%
1-116
MS 1525:2007
Code of Practice on
Energy Efficiency and
Use of Renewable
Energy for NonResidential Buildings
(1st Revision)
Load calculations
System and equipment sizing
Separate air distribution systems
Controls
Piping insulation
Air handling duct system insulation
Duct construction
Balancing
ACMV systems
ACMV system equipment
ACMV system components
ACMV system equipment/component
heat operated (absorption), cooling mode
8.13 System testing and commissioning
8.14 Operation and maintenance (O&M) manual
and as-built drawings
8.15 Preventive maintenance
8.1.4 Ventilation
Outdoor air-ventilation rates should comply with Third
Schedule (By Law 41) Article 12(1) of Uniform
Building By Laws, 1984.
Exception:
Outdoor air quantities may exceed those shown, if
required because of special occupancy or process
requirements or source control of air contamination or
Indoor Air Quality consideration.
8.2.2 Where chillers are used and when the design load
is greater than 1,000 kWr, a minimum of either
two chillers or a single multi-compressor chiller
should be provided to meet the required load.
8.2.3 Multiple units of the same equipment type, such as
multiple chillers, with combined capacities
exceeding the design load may be specified to
operate concurrently only if controls are provided
which sequence or otherwise optimally control the
operation of each unit based on the required cooling
load.
8.4 Controls
8.4.1 Temperature control
Each system should be provided with at least
one thermostat for the regulation of temperature.
Each thermostat should be capable of being set by
adjustment or selection of sensors over a
minimum range of between 22 C to 27 C.
Multi-stage thermostat should be provided for
equipment exceeding 35/65 kWr in conjunction
with 8.2.4.
8.7
Duct construction
All ductwork should be constructed and erected in
accordance with HVAC Duct Construction
Standards Metal and Flexible published by
SMACNA or any other equivalent duct construction
standards.
8.8 Balancing
The system design should provide means for
balancing the air and water system such as but not
limited to dampers, temperature and pressure test
connections and balancing valves.
Launched
July 2007
Relative humidity
(c)
Air movement
Acceptable range
23.0 26.0 C
40 70%
0.15 0.50
Chemical contaminants
(a) Carbon dioxide
(b) Carbon monoxide
(c) Formaldehyde
(d) Ozone
(e) Respirable particulates
(f) Total volatile organic compounds
(TVOC)
Biological contaminants
(a) Total bacterial counts
(b) Total fungal counts
mg/m
cfu/m
C1000
10
0.1
0.05
3
0.15
-
500
1000
AHU Room
CO2 sensor
Supply Air
AHU
Fresh Air
Fresh air damper
Damper Actuator
Energy Monitoring
Energy meter
EFC3500
DA
NF
OS
S
Flowmeter
Pt 500 RTD
FARADAYS LAW
Ui = When an electrical conductor of length L is
moved at velocity v, perpendicular to the lines of
flux through a magnetic field of strength B, the
voltage Ui is induced at the ends of the
conductor.
Ui = L x B x v
Ui = Induced voltage
L = Conductor length
B = Magnetic field strength
v = Velocity of conductor
Electromagnetic
Qualities
Obstruction free
No moving parts
Virtually no maintenance
Measuring Principle
Acoustic flow measuring procedures like
the ultrasonic-flow measurement use
sound waves above the hearing barrier,
i.e.> 20 kHz for speed and flow
measurement. The velocity and direction
of the sound rays change due to the
transport of the sound waves in the fluid.
With the transit time procedure, the time
is measured in which a sound wave takes
to get around path 1. I.e. point A, the
sender
Obstruction free
No moving parts
Wide flow range
Virtually no maintenance
Sensitive to pipe elbows and
control valves
Respond well to fast changing
flows
Full BMS Integration
Low Cost of Ownership on
larger pipe (>DN300)
Canada
LEED Canada
BREEAM Canada
Green Globe
UK
BREEAM
Italy
Protocollo
ITACA
USA
LEED
Energy Star
Green Globe
Brazil
GBTool
Korea
GBTool
Japan
China
CASBEE
Hong Kong
India
HK-BEAM
LEED-India
Malaysia Taiwan
GBI
Singapore
Green Mark
Australia
Green Star
2.
3.
4.
5.
6.
7.
8.
9.
FM Service
Provider
Owner
/User
Architect
Civil
Engineer
Commisiong
Specialist
Energy
Consultant
Working
together
to achieve
Goals
Mechanical
Engineer
Electrical
Engineer
GBIF
Contractor
Vendors
Sub-cons
Quantity
Surveyor
Landscape
Architect
BEI =
Where;
TBEC: Total Building Energy Consumption (kWh/year) for all
landlord and tenancy areas.
CPEC: Carpark Energy Consumption (kWh/year) for carpark
area (which is not air-conditioned) and typically covers
artificial lighting, lifts, mechanical ventilation fans, sump
pumps and plug loads (car washing facilities).
Installations serving the whole building (such as hydraulic
pumps and fire pumps) shall not be included.
DCEC: Data Centre Energy Consumption (kWh/year) for
operation of the Data Centre equipment and for
controlling its indoor environment (air-conditioning,
mechanical ventilation, lighting and plug loads).
GFAexcluding carpark : Gross Floor Area of buildings exclusive
of car park area (m2)
BEI =
BEI
EE5 pts Office Retail Hotel
2
150
240
200
3
140
225
190
5
130
210
175
8
120
195
160
10
110
180
150
12
100
160
135
15
90
145
120
Hospital
200
190
175
160
150
135
120
Etc
?
?
?
?
?
?
?
Electrical Sub-Metering
Separate metering provided for the following;
Landlord and/or tenant
Lift and escalator
Major water pumping system
Central air-conditioning system
THANK YOU
Ir. NG YONG KONG, P.Eng., GBIF, MASHRAE
Email: nyk@nyk.com.my
Tel: +6012 201 9319