STRUCTURAL NOTES

GENERAL

1. THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH ALL ARCHITECTURAL AND OTHER
CONSULTANTS' DRAWINGS AND SPECIFICATIONS AND WITH SUCH OTHER WRITTEN INSTRUCTIONS
AS MAY BE ISSUED DURING THE COURSE OF THE CONTRACT. ANY DISCREPANCIES SHALL BE
REFERRED TO THE CONTRACT ADMINISTRATOR BEFORE PROCEEDING WITH THE WORK.
2. ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE RELEVANT AND
CURRENT A.S. CODES AND WITH THE BY-LAWS AND ORDINANCES OF THE RELEVANT BUILDING
AUTHORITIES EXCEPT WHERE VARIED BY THE PROJECT SPECIFICATION.
3. SETTING-OUT DIMENSIONS AND SIZES OF STRUCTURAL MEMBERS SHALL NOT BE OBTAINED
BY SCALING THE STRUCTURAL DRAWINGS. ANY SETTING-OUT DIMENSIONS SHOWN IN THE
STRUCTURAL DRAWINGS SHALL BE CHECKED BY THE CONTRACTOR BEFORE CONSTRUCTION
COMMENCES. ANY DISCREPANCIES IN THE DOCUMENTS MUST BE RESOLVED BEFORE ORDERING
OR PLACING ANY MATERIALS.
4. DURING CONSTRUCTION THE STRUCTURE SHALL BE MAINTAINED IN A SAFE AND STABLE
CONDITION AND NO PART SHALL BE OVERSTRESSED. TEMPORARY BRACING SHALL BE PROVIDED
BY THE CONTRACTOR AS REQUIRED TO KEEP THE WORKS AND EXCAVATIONS STABLE AT ALL
TIMES.
5. UNLESS NOTED OTHERWISE ALL LEVELS ARE IN METRES AND ALL DIMENSIONS ARE IN
MILLIMETRES.
WIND LOADS ARE IN ACCORDANCE WITH AS 1170.2 AS FOLLOWS:
BASIC WIND VELOCITY
Vu =70m/s
TERRAIN CATEGORY
2
REGION
C
FORMWORK
1. THE DESIGN CERTIFICATION, CONSTRUCTION AND PERFORMANCE OF THE FORMWORK AND
FALSE WORK IS THE RESPONSIBILITY OF THE CONTRACTOR.
2. DESIGN AND CONSTRUCTION AND STRIPPING TIMES TO COMPLY WITH AS 3610 AND AS 3600
UNLESS OTHERWISE APPROVED BY THE CONTRACT ADMINISTRATOR.
3. FOR FINISH TO FORMED CONCRETE SURFACES REFER TO SPECIFICATION.
FOUNDATIONS
1. THE LEVELS SHOWN ON THE DRAWINGS ARE FOR PRICING PURPOSES ONLY.
2. ACTUAL FOOTINGS SHALL BE BASED ON A MATERIAL HAVING A SAFE BEARING CAPACITY AS
LISTED IN THE TABLE BELOW UNLESS OTHERWISE NOTED, AND SHALL BE INSPECTED BY THE
CONTRACT ADMINISTRATOR BEFORE CONCRETE IS PLACED.
SAFE BEARING CAPACITIES: STRIP FOOTINGS 100 kPa PAD FOOTINGS 100 kPa

4. SUB-BASE FOR SLABS ON GROUND AND BACKFILL OVER FOOTINGS SHALL BE APPROVED
GRANULAR MATERIAL COMPACTED IN LAYERS OF 150 mm MAXIMUM TO AT LEAST 95% OF THE
MAXIMUM DRY DENSITY IN ACCORDANCE WITH AS 1289.
PROJECT CONTROL TESTING SHALL BE
CARRIED OUT IN ACCORDANCE WITH AS 3600.

4. MINIMUM CLEAR COVER TO REINFORCEMENT TO BE 70mm MIN TO TIES IN


EXPOSED
EXTERNAL FACES OF BEAMS AND COLUMNS. COVER TO SLAB
REINFORCEMENT TO BE 40mm FROM TOP OF SLAB.
5. ALL REINFORCEMENT SHALL BE FIRMLY SUPPORTED ON PLASTIC CHAIRS AT NOT
GREATER THAN 1 METRE CENTRES BOTH WAYS, BARS SHALL BE TIED AT ALTERNATE
INTERSECTIONS.
6. CONCRETE DIMENSIONS SHOWN DO NOT INCLUDE THICKNESSES OF APPLIED
FINISHES.
7.

CONCRETE
1. ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH AS2870 &
AS3600 AND THE CONCRETE SPECIFICATION.
2. CONCRETE QUALITY.

SLUMP MAX SIZE AGG

CONCRETE GRADE

ALL (U.N.O)

80

20

25

BLOCK FILL
RING BEAM

200
100

10
10

17
25

FOOTINGS

80

20

25

80

10

25

INTERNAL FLOOR SLAB

DEPTHS OF BEAMS ARE GIVEN FIRST AND INCLUDE SLAB THICKNESS.

8. FOR CHAMFERS,DRIP GROOVES, FILLETS ETC REFER TO ARCHITECTS DETAILS,


MAINTAIN COVER TO REINFORCEMENT AT THESE DETAILS.
9. NO HOLES, CHASES OR EMBEDMENT OF PIPES OTHER THAN THOSE SHOWN ON
THE
STRUCTURAL DRAWINGS SHALL BE MADE IN CONCRETE MEMBERS WITHOUT
THE PRIOR
WRITTEN APPROVAL OF THE CONTRACT ADMINISTRATOR.

11. THE FINISHED CONCRETE SHALL BE A DENSE HOMOGENEOUS MASS,


COMPLETELY FILLING THE FORMWORK THOROUGHLY EMBEDDING THE
REINFORCEMENT AND FREE OF STONE POCKETS. ALL CONCRETE SHALL BE
COMPACTED WITH MECHANICAL VIBRATORS.
12. CURING OF ALL CONCRETE SHALL BE ACHIEVED BY KEEPING SURFACES
CONTINUOUSLY WET FOR A PERIOD OF 3 DAYS, AND PREVENTION OF LOSS OF
MOISTURE FOR A TOTAL OF 7 DAYS FOLLOWED BY A GRADUAL DRYING OUT.
APPROVED SPRAYED ON CURING COMPOUNDS MAY BE USED WHERE NO FLOOR
FINISHES ARE PROPOSED. POLYTHENE SHEETING OR WET HESSIAN MAY BE USED IF
PROTECTED FROM WIND AND TRAFFIC.
13. THE CONTRACT ADMINISTRATOR SHALL BE GIVEN A MINIMUM OF 24 HOURS
NOTICE FOR REINFORCEMENT INSPECTION AND CONCRETE SHALL NOT BE DELIVERED
UNTIL FINAL
APPROVAL IS OBTAINED.
14. CONDUITS, PIPES ETC, SHALL ONLY BE LOCATED IN THE MIDDLE ONE THIRD OF
SLAB DEPTH AND SPACED AT NOT LESS THAN 3 DIAMETERS.

18. WELDING OF REINFORCEMENT SHALL NOT BE PERMITTED UNLESS SHOWN ON THE


STRUCTURAL DRAWINGS OR APPROVED BY THE CONTRACT ADMINISTRATOR.
19. JOGGLES TO BARS SHALL BE 1 BAR DIAMETER OVER A LENGTH OF 12 BAR DIAMETERS UNLESS
NOTED OTHERWISE.
20.

22. A BOND BREAKING MATERIAL SHALL BE PLACED BETWEEN CONTACTING SURFACES AT


CONTRACTION JOINTS. REINFORCEMENT SHALL NOT BE CONTINUOUS THROUGH
CONTRACTION JOINTS.

23. AT PENETRATIONS IN SLABS UNLESS OTHERWISE DETAILED REINFORCEMENT SHALL


NOT BE
CUT BUT SHALL BE GATHERED EQUALLY TO EACH SIDE OF PENETRATION AND
EXTRA
REINFORCEMENT PROVIDED BETWEEN THE PENETRATIONS AS DIRECTED BY THE
CONTRACT ADMINISTRATOR.
24.

LAP LENGTHS FOR STARTER BARS IS TO BE 600mm.

REINFORCED BLOCKWORK

1.

ALL WORKMANSHIP AND MATERIALS SHALL COMPLY WITH AS 3700

2.

ALL BLOCKS SHALL BE STRENGTH GRADE 10 MPa.

3. ALL MORTAR SHALL CONSIST OF PORTLAND CEMENT, HYDRATED LIME AND SAND IN THE
PROPORTIONS OF 1:0.25:3 BY VOLUME RESPECTIVELY. 4. CHASES AND HOLES SHALL NOT BE
MADE IN BLOCKWORK WITHOUT THE APPROVAL OF THE CONTRACT ADMINISTRATOR.
5. JOINT THICKNESS SHALL BE MINIMUM 6 mm AND MAXIMUM 12 mm. FACE SHELLS AND
PERPENDS SHALL BE FULLY BEDDED IN MORTAR.
6. ALL CORES ARE TO BE FILLED WITH 25 MPa CONCRETE (10 mm AGGREGATE SIZE, MAXIMUM
SLUMP 200).
PROVIDE CLEAN OUT HOLES AT BOTTOM OF ALL FILLED CORES.

8. PROVIDE 65 mm COVER FROM THE OUTSIDE OF THE BLOCKWORK TO ALLOW ADEQUATE


GROUT COVER TO REINFORCEMENT.

STEEL REINFORCEMENT

REINFORCEMENT SYMBOLS:

3 D12
3 (NUMBER OF BARS IN GROUP)
D (BAR GRADE AND TYPE)
12 (NOMINAL BAR SIZE IN mm)

FABRIC SHALL BE LAPPED 2 TRANSVERSE WIRES PLUS 50mm.

21. CONCRETE BELOW GROUND IN WALLS, BEAMS, OR PEDESTALS SHALL BE PLACED INTO PROPERLY
CONSTRUCTED FORMS. IF APPROVED BY THE CONTRACT ADMINISTRATOR, CONCRETE MAY BE
PLACED AGAINST AN EARTH FACE BUT THE CONCRETE DIMENSIONS SHOWN ON THE DRAWINGS
SHALL BE INCREASED TO PROVIDE 20mm ADDITIONAL COVER TO THE REINFORCEMENT ADJACENT
THE EARTH FACE.

7.

15.

ELEMENT

NO ADMIXTURES SHALL BE USED IN CONCRETE UNLESS APPROVED IN WRITING.

10. CONSTRUCTION JOINTS WHERE NOT SHOWN SHALL BE LOCATED TO THE


APPROVAL OF THE CONTRACT ADMINISTRATOR.

6.

3.

3.

D12 @ 170
D
(BAR GRADE AND TYPE)
12
(NOMINAL BAR SIZE IN mm)
170
(SPACING IN mm)

THE FIGURE FOLLOWING THE FABRIC SYMBOL F IS THE REFERENCE NUMBER FOR FABRIC TO
AS 1304.

9. PROVIDE VERTICAL JOINTS IN BLOCKWORK AT MAX 10 METRE CENTRES UNLESS NOTED


OTHERWISE (UNO).
10.

BLOCKWORK SHALL COMPLY WITH AS 3700

STRUCTURAL TIMBER

1.
16. REINFORCEMENT IS REPRESENTED DIAGRAMMATICALLY AND NOT NECESSARILY IN TRUE
PROJECTION.
2.

ALL TIMBERS SHALL HAVE A MC OF 14% +/- 3% AND SHALL BE MSG8 TIMBER GRADE.
PRIME ALL END GRAIN 2 - 3 THICK COATS OF PRIMER BEFORE ASSEMBLY

17. SPLICES IN REINFORCEMENT SHALL BE MADE ONLY IN POSITION SHOWN OR OTHERWISE 3. ALL NAILS SHALL BE OF LENGTH 2.5 TIMES THE THICKNESS OF TIMBER BEING SECURED AND
APPROVED IN WRITING BY THE CONTRACT ADMINISTRATOR.
OF ADEQUATE GAUGE ALL VISIBLE SCREWS ARE TO BE DRILLED AND COUNTERSUNK AND BE
BRASS OR STAINLESS STEEL AS DIRECTED
IMPORTANT: Do not scale off this drawing. All dimensions should be checked on site prior to construction.

ID

AMMENDMENTS

DATE

Engineering &
Architectural Consultants
Unit 10 Tongilava Plaza, Taufa'ahau Rd., Fanga
Nuku'alofa, Tonga. Ph/Fax (676) 28807 / 28412

PROJECT

'EUA COMMUNITY PACK HOUSE

LOCATION -, 'EUA
CLIENT

MORDI

TITLE
DRAWN BY
CHECKED BY
DATE
DRAWING STATUS
PROJECT NUMBER

STRUCTURAL NOTES
TT
FL
02/10/15
CONSTRUCTION DEVELOPMENT
15-057

DRAWING NUMBER

S00

10

11
LEGEND

24000
4000

800

3200

2400

1600

1600

800

2400

3200

G
ST1

C1

PF1 -EL.-1400
SC

PF1 -EL.-1400

C1

C1

CF

COLUMN FOOTING

PF1

PAD FOOTING

ST1

SLAB THICKENING

C1

360UB 50.7

SC

SC

147

PF1 -EL.-1400

C1

TB

SC

F
TB
665 MESH
40mm COVER

TB

PF1 -EL.-1400

C1

SC

S06

TB

SC
TB

TB

SC
SC

TB

3957

PF1 -EL.-1400

17288

TB

TB

17288

5857

PF1 -EL.-1400

3957

TB
PF1 -EL.-1400

SC

S06

E
1900

1900

7
S05A
5

SC

SC

SC

TB

S05A

SC

SC

SC

1900

125MM RC SLAB ON FILL


21 MPa

402

CF 2

SC

PF1 -EL.-1400

C1

TB

TB

PF1 -EL.-1400

C1

C1

CF 1 -EL.-300
SC

4
S05A

PF1 -EL.-1400

2
S04

B
TB

SC
2
S05B

PF1 -EL.-1400

SC

TB

4
S05A

C1

PF1 -EL.-1400

PF1 -EL.-1400

C1

C1

C1

S06

PF1 -EL.-1400

SLAB EDGE
4000

4000

4000

4000

4000

1
S05B

4000

24000

TB

SC

TB

3957

TB

5857

1
S04

3555

1900

125x125 SHS

SAW CUT

SC

TB

C1

SC

SC

5575

SC

TB

C1

SC

SC

ST1

ST1

5575

SC

7
S05A

TIE BEAM

S06

S06

SC

TB
4000

10

11

1 A08

FOUNDATION PLAN
SCALE 1 : 100

IMPORTANT: Do not scale off this drawing. All dimensions shhould be checked on site prior to construction.

ID

AMMENDMENTS

DATE

REMOVE STRIP FOOTING & RETAINING WALL

13.10.2015

ADD TIE BEAM ON GRID A-F & 1-11


ADD SLAB THICKENING ON GRID F-G

13.10.2015
13.10.2015

Engineering &
Architectural Consultants
Unit 10 Tongilava Plaza, Taufa'ahau Rd., Fanga
Nuku'alofa, Tonga. Ph/Fax (676) 28807 / 28412

PROJECT

'EUA COMMUNITY PACK HOUSE

LOCATION -, 'EUA
CLIENT

MORDI

TITLE
DRAWN BY
CHECKED BY
DATE
DRAWING STATUS
PROJECT NUMBER

FOUNDATION PLAN
TT
FL
04/15/15
CONSTRUCTION DEVELOPMENT
15-057

DRAWING NUMBER

S01

125X125MM
SHS COLUMN
400
250

75

D12 TRIMMER BAR

400MM LAP

40

125X125MM SHS
COLUMN

125

75
250

125MM RC SLAB
400MM LAP

275

75

400

665 MESH, 40MM


TOP COVER

4-M12X300mm
ANCHOR BOLTS

250X250X8MM BASE
PLATE WITH 4-M12X300mm
ANCHOR BOLTS

85

75

DPM ON 20MM
BLINDING SAND

70

250X250X8MM
BASE PLATE

PLAN VIEW

MEZZANINE SHS FOOTING (CF 1)

1 S01

3-D16 BAR EACHWAY


100

SCALE 1 : 10

400

100

600
1150
374

402

SETION A-A

374

250
170

40

400

40

253

40

125X125MM SHS COLUMN

125X125MM SHS COLUMN

282

40

147

250

B
170

D12 TRIMMER BAR

250X250X8MM BASE PLATE

FLOOR PLAN

400MM LAP

COLUMN FOOTING (CF 2)


SCALE 1 : 10

275

1 S01

400MM LAP

125MM RC SLAB

DPM ON 20MM
BLINDING SAND

70

665 MESH, 40MM


TOP COVER
125
85 40

120X120MM
SHS COLUMN

4-M12X300MM LONG GALV. J BOLTS

250X250X8MM BASE PLATE


WITH 4-M12X300 LONG
GALV. J BOLTS

4-D16 BAR @ 200 CRS EACHWAY


100

950

100

1150

SECTION B-B
IMPORTANT: Do not scale off this drawing. All dimensions should be checked on site prior to construction.

ID

AMMENDMENTS

DATE

Engineering &
Architectural Consultants
Unit 10 Tongilava Plaza, Taufa'ahau Rd., Fanga
Nuku'alofa, Tonga. Ph/Fax (676) 28807 / 28412

PROJECT

'EUA COMMUNITY PACK HOUSE

LOCATION -, 'EUA
CLIENT

MORDI

TITLE
DRAWN BY
CHECKED BY
DATE
DRAWING STATUS
PROJECT NUMBER

STRUCTURAL DETAILS
TT
FL
04/16/15
CONSTRUCTION DEVELOPMENT
15-057

DRAWING NUMBER

S04

1000

30mm X 4mm SAWCUT BETWEEN 12


AND 24 HOURS AFTER CASTING. FILL
JOINT TO 3mm BELOW SLAB LEVEL
WITH AN APPROVED JOINT FILLER

665 MESH

55

55

115

40

6-D20 TIES WITH


R10 @ 150MM CRS

665 MESH, COVER 40MM

125MM RC SLAB

REUSE 360UB 50.7 STEEL


COLUMN WITH BASE PLATE

70

TYP. TIE BEAM DETAIL

REUSE 360UB 50.7 STEEL


COLUMN WITH BASE PLATE

EXISTING BASE PLATE

SCALE 1 : 10

4-M24X600MM LONG
ANCHOR BOLTS

25MM CONCRETE GROUT 25MPa

TB

D20 BARS TIES WITH


R10 150MM CRS

3-D12 TOP AND BOTTOM TIES


WITH R10 @ 300MM CRS

TB

D20 BARS TIES WITH


R10 150MM CRS

500X300 RC PEDESTAL
6-D20 TIES WITH
R10 @ 150MM CRS

PF 1

D16 @ 200MM
CRS EACHWAY

500X300 RC PEDESTAL
600

PF1 (PAD FOOTING)


860

D16 @ 200MM
CRS EACHWAY

70

400

330

PF 1

2-D16 BAR @
MID-DEPTH

D16 @ 200MM
CRS EACHWAY

70

400

S05A

70

449

3-D12 TOP AND BOTTOM TIES


WITH R10 @ 300MM CRS

300

S05A

1 S01

1000

70

4-M24X600MM LONG
ANCHOR BOLTS

25MM CONCRETE GROUT 25MPa

160

125

EXISTING BASE PLATE

BASE PLATE DETAIL


SCALE 1 : 10

DPM ON 20MM
BLINDING SAND

TB

70

SCALE 1 : 10

205

TYP. PEDESTAL DETAIL

275

NOTE: VERIFY ACTUAL BASE PLATE


DIMENSION AND HOLES LOCATION

85

125

40

2-D16 BAR @ MID-DEPTH

219

DEPRESS REINFORCEMENT LOCALLY


AT SAWCUT LOCATIONS BY CUTTING
ALTERNATE WIRE.

SCALE 1 : 10

219

SAW CUT SC

115

220

1 S01

50 65

S05A

40

300

800

449

40

420

116

65 50

PF1 (PAD FOOTING)

500
40

225

1000

TYP. PAD FOOTING DETAIL

1 S05A

SCALE 1 : 20

TYP. TIE BEAM CONNECTION

SCALE 1 : 20

1 S01

TYP. SECTION DETAIL


SCALE 1 : 20

IMPORTANT: Do not scale off this drawing. All dimensions should be checked on site prior to construction.

ID

AMMENDMENTS

DATE

Engineering &
Architectural Consultants
Unit 10 Tongilava Plaza, Taufa'ahau Rd., Fanga
Nuku'alofa, Tonga. Ph/Fax (676) 28807 / 28412

PROJECT

'EUA COMMUNITY PACK HOUSE

LOCATION -, 'EUA
CLIENT

MORDI

TITLE
DRAWN BY
CHECKED BY
DATE
DRAWING STATUS
PROJECT NUMBER

STRUCTURAL DETAILS
TT
FL
04/17/15
CONSTRUCTION DEVELOPMENT
15-057

DRAWING NUMBER

S05A

300
70 160 70

TIE BEAM

D16 @ 200MM
CRS EACHWAY

PF1 (PAD FOOTING)

6-D20 TIES WITH


R10 @ 150MM CRS

3-D12 TOP AND


BOTTOMTIES WITH
R10 @ 300 CRS

300

PF1 (PAD FOOTING)

S05B

D16 @ 200MM
CRS EACHWAY

2-D16 BAR @
MID-DEPTH
100

S05B

TIE BEAM

2-D16 BAR @
MID-DEPTH

70 160 70

300

TIE BEAM

3-D12 TOP AND


BOTTOMTIES WITH
R10 @ 300 CRS

6-D20 TIES WITH


R10 @ 150MM CRS

1 S01

TYP. FOOTING INTERSECTION


SCALE 1 : 20

TYP. CORNER PLAN DETAIL

1 S01

SCALE 1 : 20

REUSE 360UB 50.7 STEEL


COLUMN WITH BASE PLATE

EXISTING BASE PLATE

REUSE 360UB 50.7 STEEL


COLUMN WITH BASE PLATE

EXISTING BASE PLATE


25MM CONCRETE GROUT 25MPa

665 MESH

425

D20 BARS TIES WITH


R10 150MM CRS

3-D12 TOP AND


BOTTOMTIES WITH
R10 @ 300 CRS

500X300 RC PEDESTAL

3-D12 TOP AND


BOTTOMTIES WITH
R10 @ 300 CRS

1 S05B

425

40

40

25MM CONCRETE GROUT 25MPa

TYP. SECTION DETAIL

D20 BARS TIES WITH


R10 150MM CRS

TYP. SECTION DETAIL

2 S05B

SCALE 1 : 20

500X300 RC PEDESTAL

SCALE 1 : 20

PF 1
PF 1

ID

AMMENDMENTS
CHANGE DETAILS OF SF TO TIE BEAM

DATE
13.10.2015

D16 @ 200MM
CRS EACHWAY

Engineering &
Architectural Consultants
Unit 10 Tongilava Plaza, Taufa'ahau Rd., Fanga
Nuku'alofa, Tonga. Ph/Fax (676) 28807 / 28412

D16 @ 200MM
CRS EACHWAY

IMPORTANT: Do not scale off this drawing. All dimensions should be checked on site prior to construction.
PROJECT

'EUA COMMUNITY PACK HOUSE

LOCATION -, 'EUA
CLIENT

MORDI

TITLE
DRAWN BY
CHECKED BY
DATE
DRAWING STATUS
PROJECT NUMBER

STRUCTURAL DETAILS
TT
FL
09/02/15
CONSTRUCTION DEVELOPMENT
15-057

DRAWING NUMBER

S05B

90x90MM TIMBER POST

2-M12x120MM HDG
BOLTS
665 MESH, 40MM
TOP COVER

400MM LAP

665 MESH, 40MM


TOP COVER

125MM RC SLAB

400MM LAP

125MM RC SLAB

125MM RC SLAB
100

N.G.L

N.G.L

275

400

400

85

125

40

125MM RC SLAB

PRYDA SBK 16
BRACKET WITH 2M12x120 HDG BOLTS

WELL COMPACTED
HARDFILL TO 95% MODIFIED
COMPACTION

275

3-D12 TOP AND


BOTTOM TIES WITH
R10 @ 300 CRS

3-D12 TOP AND


BOTTOM TIES WITH
R10 @ 300 CRS

WELL COMPACTED
HARDFILL TO 95% MODIFIED
COMPACTION
100

360

40
100

DPM ON 20MM
BLINDING SAND

1
1 S01

360

40

DPM ON 20MM
BLINDING SAND

TYP. SLAB THICKENING


SCALE 1 : 10

2
1 S01

100X100MM TIMBER COLUMN FIXING


SCALE 1 : 10

665 MESH, COVER 40MM

125MM RC SLAB

665 MESH, COVER 40MM

85

DPM ON 20MM
BLINDING SAND

205

275

TB

TB
70

70

DPM ON 20MM
BLINDING SAND

N.G.L

205

275

125

40

N.G.L

85

125

40

125MM RC SLAB

3-D12 TOP AND BOTTOM TIES


WITH R10 @ 300MM CRS

3
1 S01

70

160

70

150
3-D12 TOP AND BOTTOM TIES
WITH R10 @ 300MM CRS

300

SLAB OVERLAP 1

1 S01

SCALE 1 : 10

70

160

70

103

300

SLAB OVERLAP 2
SCALE 1 : 10

IMPORTANT: Do not scale off this drawing. All dimensions should be checked on site prior to construction.

ID

AMMENDMENTS

DATE

Engineering &
Architectural Consultants
Unit 10 Tongilava Plaza, Taufa'ahau Rd., Fanga
Nuku'alofa, Tonga. Ph/Fax (676) 28807 / 28412

PROJECT

'EUA COMMUNITY PACK HOUSE

LOCATION -, 'EUA
CLIENT

MORDI

TITLE
DRAWN BY
CHECKED BY
DATE
DRAWING STATUS
PROJECT NUMBER

STRUCTURAL DETAILS
TT
FL
04/17/15
CONSTRUCTION DEVELOPMENT
15-057

DRAWING NUMBER

S06