Cooling Load Summery

DBT in oC

WBT in oC

33.9

29.2

Indoor Design Condition

24

18.2

Difference Between Outdoor & Indoor

9.9

Outdoor Design Condition

Sensible Heat
Roof

Walls

Glass - Conduction

Glass - Solar Gain

Partitions

Ceiling

Not separately considered, included with roof

Floor

Since no heat generation through floor, did not get in to co

People

G-a

Lights

Power

Assume no power consuming equipment other than the lam

Appliances

Assume no heat generating appliance other than the lamp

Room Sensible Heat - RSH

[ 'B' + 'C' + 'D' + 'E' + 'F' + 'G-a' + 'H' ] =

Supply duct Heat Gain % of RSH

Since there are no details on duct, it assumed no duct avai

Fan Motor Heat [from AC unit]

Since there are no details, Fan motor heat generation is no

Ventilation (qSensible = 1.23 . Q.BF.t) [assumed BF = 0.8]

I - ae

WBT in oC

Hum. Ratio in kg/kg

29.2

0.71

18.2

0.55

Cooling Load in W

3,698.92 W
1,678.32 W
9,763.21 W
21,900.15 W
1,016.38 W

h roof

did not get in to consideration


7,000.00 W
1,814.50 W

t other than the lamps

ther than the lamps


46,871.48 W

sumed no duct available

at generation is not considered.

4,870.80 W

Assignment - Heat Load Calculation - 2015


MSc/ PG Dip in Building Services Engineering

Lecturer:
Module No:
Candidate:
Student No:
Date of Submission:

signment - Heat Load Calculation - 2015

MSc/ PG Dip in Building Services Engineering

Mr. Vijitha Perera


A.S.Dharmabandu
148611 B
2015-12-04