Notes:
On start up for genset applications the ECM automatically determines which speed/load
signal out of range (o.o.r.) fault management to use. This is dependant on the wiring
configuration it observes
Stand alone (isochronous) operation APS & RPS inputs are both inactive.
Manual synchronised load sharing APS input is active, RPS input is inactive.
Automatic synchronised load sharing APS input is inactive, RPS input is active.
2 way protection is achieved by selecting 3 way protection and normally open (plastic
tank) for the CLS type. No connection should then be made to the CLS input.
Page 8
10
AWG
86
ECM
30 AMP
30
Rating 30A
min
18 AWG
14 AWG
14 AWG
14 AWG
18 AWG
10 AWG
85
87
87a
See note 4
See note 2
14 AWG
14 AWG
14 AWG
14 AWG
Battery
10 AWG
5 AMP
12V or 24V
Attention
1
Note: Power supply for ECM must
be taken directly from the battery,
not the starter motor terminal.
18 AWG
Battery
Diagnostic
switch
On/off switch
18 AWG
18 AWG
18 AWG
5 AMP
16 AWG
18 AWG
25
21
22
41
23
42
1
2
37 PRE Input
32 SCS Input (set coast)
34 STI Switch
24 VIGN - IPR (+) Feed
Notes
16 AWG
1) Wire sizing:
10AWG (approx. 5mm 2 ) Main feed and return to battery
14AWG (approx. 2mm 2 ) ECM pin Nos 21.22.41.23.42.1.2
16AWG (approx. 1mm 2 ) Ignition and diagnostic socket supply
18AWG (approx. 0.8mm 2 ) All other circuits
10 AMP
18
Red
AWG lamp
Amber
lamp
18 AWG
Emergency
stop device
See note 5
Main
power rly
Interface harness
(if used)
18 AWG
Terminal can be
marked 87 or G
To starter and
charging circuits
See note 6
18 AWG
Diagnostic
connector
10 AMP
CEBA
16 AWG
16 AWG
Clear wire
Black wire
18 AWG
18 AWG
16 ATA (+)
(Data link J1708)
17 ATA (-)
95
W1361/1
See note 3
Emergency 10
stop device AWG
86
30 AMP
30
Rating 30A
min
87
18 AWG
14 AWG
14 AWG
14 AWG
87a
See note 4
ECM
18 AWG
10 AWG
85
14 AWG
14 AWG
14 AWG
14 AWG
See note 2
Battery
-
10 AWG
12V
or
24V
Attention
1
Note: Power supply for ECM must
be taken directly from the battery,
not the starter motor terminal.
On/off switch
Manual speed
(demand) signal.
(working range
0.5 to 4.5 volts
into ECM pin 8).
All resistors rated
at 0.25 watts.
+
Battery
Notes
16 AWG
10 AMP
250
Ohms
23
42
1
2
See note 7
See
note 3
Diagnostic
switch
18 AWG
Red lamp
Amber lamp
18 AWG
34 STI Switch
See note 6
18 AWG
CEBA
16 AWG
Clear wire
Black wire
18 AWG
18 AWG
16 ATA (+)
(Data link J1708)
17 ATA (-)
Diagnostic
connector
10 AMP
25
21
22
41
2K
Ohms
18
AWG
18 AWG
250
Ohms
18 AWG
2) Main Power Relay
12V part no. 1688314C1
(12V alternative part nos. 2848A203)
W1362/1
1) Wire sizing:
10AWG (approx. 5mm 2 ) Main feed and return to battery
14AWG (approx. 2mm 2 ) ECM pin Nos 21.22.41.23.42.1.2
16AWG (approx. 1mm 2 ) Ignition and diagnostic socket supply
18AWG (approx. 0.8mm 2 ) All other circuits
5 AMP
16 AWG
Main
power rly
96
Terminal can be
marked 87 or G
To starter and
charging circuits
10
AWG
86
ECM
18 AWG
10 AWG
85
30 AMP
87
30
Rating 30A
min
18 AWG
14 AWG
14 AWG
14 AWG
87a
See note 4
See note 2
14 AWG
14 AWG
14 AWG
14 AWG
+
Battery
10 AWG
18 AWG
On/off switch
Attention
5 AMP
16 AWG
1
Note: Power supply for ECM must
be taken directly from the battery,
not the starter motor terminal.
18 AWG
12V or 24V
Auto speed
(demand)
signal
+
Battery
Notes
Working input
voltage into ECM
pin 30 is 0.5 to 4.5
18 AWG
16 AWG
10 AMP
Diagnostic
connector
10 AMP
18 AWG
Red
lamp
Amber
lamp
23
42
1
2
37 RPRE Input
24 VIGN - IPR (+) Feed
See note 7
Diagnostic
switch
18
AWG
25
21
22
41
1) Wire sizing:
10AWG (approx. 5mm 2 ) Main feed and return to battery
14AWG (approx. 2mm 2 ) ECM pin Nos 21.22.41.23.42.1.2
16AWG (approx. 1mm 2 ) Ignition and diagnostic socket supply
18AWG (approx. 0.8mm 2 ) All other circuits
18 AWG
Main
power rly
Emergency
stop device
Terminal can be
marked 87 or G
5 AMP
To starter and
charging circuits
34 STI Switch
See note 6
18 AWG
CEBA
16 AWG
16 AWG
Clear wire
Black wire
18 AWG
18 AWG
16 ATA (+)
(Data link J1708)
17 ATA (-)
97
W1363/1
See note 3
Emergency 10
stop device AWG
Main
power rly
86
ECM
30 AMP
Rating 30A
min
18 AWG
14 AWG
14 AWG
14 AWG
18 AWG
10 AWG
85
87
30
18 AWG
87a
14 AWG
14 AWG
14 AWG
14 AWG
+
Battery
10 AWG
5 AMP
Attention
1
Note: Power supply for ECM must
be taken directly from the battery,
not the starter motor terminal.
Notes
Battery
18 AWG
J2
See note 7
18 AWG
Diagnostic
switch
18 AWG
18 AWG
On/off switch
10 AMP
18
AWG
Red
lamp
Amber
lamp
Diagnostic
connector
10 AMP
18 AWG
18 AWG
25
21
22
41
23
42
1
2
37 PRE Input
32 SCS Input (set coast)
31 RAS Input (resume/accel)
34 STI Switch
See note 6
18 AWG
CEBA
16 AWG
16 AWG
Clear wire
Black wire
18 AWG
18 AWG
See note 3
16 ATA (+)
(Data link J1708)
17 ATA (-)
16 AWG
W1364/1
5 AMP
16 AWG
1) Wire sizing:
10AWG (approx. 5mm 2 ) Main feed and return to battery
14AWG (approx. 2mm 2 ) ECM pin Nos 21.22.41.23.42.1.2
16AWG (approx. 1mm 2 ) Ignition and diagnostic socket supply
18AWG (approx. 0.8mm 2 ) All other circuits
18 AWG
J1
12V or 24V
+
Wiring diagram - 1500/1800 rev/min Switchable stand alone isochronous (non-load sharing)
98
Terminal can be
marked 87 or G
To starter and
charging circuits
Coolant
Battery
Battery
Request to
shutdown
On/off
level
switch
10
PIN 10
See note 2
See note 1
10 AMP
Red
54
Emergency
stop
PIN 54
Additional notes
1) Maximum total current from OWL (54) output = 1 Amp (including lamp and
Snooze
Single pin
connector
11
10 AMP
86
30
85
87
87a
A
B
Two pin
connector
Radiator shutter
Radiator
shutter
control relay
See note 3
W1365