55 daN
113.3 at 100-ft
3/28/2016
Date
SIZING DATA
Design Code
ASME Section VIII
Sizing Std. API 520
Sizing Basis
Control Valve Failure
Fluid State at Inlet
Steam
Relieving Case
Pressure Relief
Fluid Properties
Fluid Name
Steam
Molecular Weight, M
18.020
Compressibility, Z
1.000
Ratio of Sp. Heats, k (Cp / Cv)
1.310
Saturation Temperature
358.660 F
Sizing Coefficients
K, Steam
Kd, Steam
Kb
Kc
Kn
Ksh
Ksc
Required Capacity
Total
Unit
0.868
1.0
1
0.965
1
0.846
Unit
lb/hr
9000
Unit
psig
Pressures
MAWP
Operating
125
100
Set
CDTP
125
125
Over Pressure
12.5
10%
Constant Superimposed
0
Variable Superimposed
0
Back
Pressure
Built-Up
0
Total
0
Inlet Loss
0
0%
Atmospheric (Barometric)
12.93 psia
Relieving (Flowing)
150.43 psia
Temperatures
Unit
F
Operating
Relieving
700
700
Design Min
Design Max
695
705
A
5.25
B
5.57
C
30.13
Weight
106
Valve Dimensions
2.046
K
9000
11646.524
WT SMS KNG
Prpd. Chk. Appr.
in
Accessories
Tag Notes
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
lb
HGA
8401 New Trails Dr
Suite 100
dlands, Tx 77381, United States o
281-671-6825
A
wthatcher@HGA-LLC.com
No
Quote Number:
Page : 1
Pentair Valves & Controls and its parent, subsidiaries, and affiliates assume no liability in any way whatsoever for any direct or indirect loss or damage through the application of this software. See terms of license