Swimming Pool Calculation

Enter Your Numbers In GreenCells Only:


Surface Area of Swimming Pool
Pool average depth
=

145
1.14

Pool Volume
=
165.3
NO. Water Inlets
=
5.8
So Get the No. Of inlets
=
6
Enter No. Of Turn Over Period
6
Get Swimming Pool Pump Capacity
=
=
No. Of pump will used
=
1
Get pump flow rate
= 0.459167
Balance tank volume

m2
m
m3
inlets
time / day
Pool Volume / ( turn over period * 60 )
0.4591667 m3/min
=
pumps
m3/min

= 40 L/m2 X Pool Surface area + 10 min X pump flow rate + 0.01 X pool surface area
= 11.84167 m3
=
11.8
m3

Balance tank volume

To calculate pipe sizing


Supply pipe maximum velocity will be 2 m/s
No. Of inlet
Pump flow rate

=
=

6
27.55

Inlet
m3/hr

Each inlet give flow rate


= 4.591667
Assuming that all inlet in sequence
Dia 1
= 28.49947
Taking it
Dia 2
= 40.30434
Taking it
Dia 3
= 49.36253
Taking it
Dia 4
= 56.99894
Taking it
Dia 5
= 63.72676
Taking it
Dia 6 = 69.80916
Taking it

m3/hr
28
40
49
57
64
70

50
50
50
50
65
65

mm.
mm.
mm.
mm.
mm.
mm.

Take just no. Of inlet for your calculation


for 4 inlet take to dia4

65
100
100
150

mm.
mm.
mm.
mm.

Take just no. Of outlet for your calculation


for 2 outlet take to dia2

50
65
75
75
100
100
100
100
150
150

mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.

Take just no. Of grille for your calculation


for 6 grille take to dia 6

Suction pipe maximum velocity will be 1.5 m/s


Pump flow rate
No. Of outlet

=
=

27.55
2

Each outlet give flow rate


Dia 1
= 63.09497
Dia 2
= 89.22976
Dia 3
= 109.2837
Dia 4
= 126.1899

m3/hr
Outlet
=

13.775 m3/hr
Taking it
63
Taking it
89
Taking it
109
Taking it
126

Over flow pipe Grille velocity will be 0.3m/s


the No. Of grille
=
5
Grilles
Pump flow rate
= 27.55
m3/hr
Assuming that all grilles in sequence
Dia 1
= 43.42577
Taking it
Dia 2
= 61.41331
Taking it
Dia 3
= 75.21564
Taking it
Dia 4
= 86.85154
Taking it
Dia 5
= 97.10297
Taking it
Dia 6
= 106.371
Taking it
Dia 7
= 114.8938
Taking it
Dia 8
= 122.8266
Taking it
Dia 9
= 130.2773
Taking it
Dia 10 = 137.3243
Taking it

43
61
75
87
97
106
115
123
130
137

Getting the filter area to be used


Pump flow rate

Filter area

= 0.787143

27.55

m3/hr
m2

at 15 gpm / ft2

Heating Calculation for swimming pools


Heater is required for heating purposes at winter seasons if required take inconsideration that
it's not particle to heat the pool without covers at coldest winter months
For calculation purposes the following conditions to be considered:The recommended Pool water temperature is around 28 C deg.
Outdoor air condition
: 46 / 30 deg C DB/WB summer condition, max 122deg F (50 C)
: 6/ 10 deg C BD/WB -winter condition
From SPATA p5, Sec3, the Average Daily heat loss (DH) in KWhr / m2 of pool surface area
correction value to

0.8

No. of hours per day available for heati


72
Heater required
13.533333

hours
Kw

cooling Calculation for swimming pools


To cool 1gpm and maintain at 28C(82.4F) will require the corresponding 51.25 Cfm of air & 59.97 Btu/min to reject the heat.
Cooling capacity
6216.575
CFM
436458.1
Btu/hr
36.37151
TR

pump head calculation for swimming pools


heater pressure drop
=
filter pressure drop
=
chlorination auto pilot unit
pipes and fittings losses
=
Static head heat pump
=
pump head
pump HP

10
50
5
7
18.93

= 109.116
= 1.449615

ft
ft
ft
ft
ft
ft
hp

Result of Calculation :Pump Capacity


Pump Head
Pump HP
Balance tank V.
Filter Area
Heater Capacity
Cooling Capacity

=
=
=
=
=
=
=

121.299
109.116
1.449615
11.8
0.787143
13.53333
36.37151

m3/hr
Ft
HP
m3
m2
Kw
TR

with

at 15 gpm / ft2
6216.575

CFM

Pumps

Swimming Pool Calculation


Enter Your Numbers In GreenCells Only:
Surface Area of Swimming Pool
Pool average depth
=

21.4
0.8

Pool Volume
=
17.12
NO. Water Inlets
=
0.856
So Get the No. Of inlets
=
1
Enter No. Of Turn Over Period
3
Get Swimming Pool Pump Capacity
=
=
No. Of pump will used
=
1
Get pump flow rate
= 0.095111

m
m

Swimming Pool Design sheet Rev-0


prepared by Eng.Mahmoud Selim

m3
inlets
time / day
Pool Volume / ( turn over period * 60 )
0.095111 m3/min
pumps
m3/min

To calculate pipe sizing


Supply pipe maximum velocity will be 2 m/s
No. Of inlet
=
1
Inlet
Pump flow rate
= 5.706667
m3/hr
Each inlet give flow rate
= 5.706667
Assuming that all inlet in sequence
Dia 1
= 31.77188
Taking it

m3/hr
32

50

mm.

Take just no. Of inlet for

mm.

Take just no. Of outlet f

Suction pipe maximum velocity will be 1.5 m/s


Pump flow rate
No. Of outlet

= 5.706667
m3/hr
=
1
Outlet

Each outlet give flow rate


Dia 1
= 40.61067

= 5.706667 m3/hr
Taking it
41

50

Getting the filter area to be used


Pump flow rate
Filter area

= 5.706667
= 0.163048

m3/hr
m2

at 15 gpm / ft2

Heating Calculation for swimming pools


Heater is required for heating purposes at winter seasons if required take inconsideration that
it's not particle to heat the pool without covers at coldest winter months
For calculation purposes the following conditions to be considered:The recommended Pool water temperature is around 28 C deg.
Outdoor air condition
: 46 / 30 deg C DB/WB summer condition, max 122deg F (50 C)
: 6/ 10 deg C BD/WB -winter condition
From SPATA p5, Sec3, the Average Daily heat loss (DH) in KWhr / m2 of pool surface area

correction value to
1.25
No. of hours per day available for heati
48
Heater required
4.68125

hours
Kw

cooling Calculation for swimming pools

To cool 1gpm and maintain at 28C(82.4F) will require the corresponding 51.25 Cfm of air & 59.97 Bt
Cooling capacity
1287.692
CFM
90407.3
Btu/hr
7.533942
TR

pump head calculation for swimming pools


heater pressure drop
=
filter pressure drop
=
chlorination auto pilot unit
pipes and fittings losses
=
Static head heat pump
=
pump head
pump HP

10
30
5
7
18.93

= 85.116
= 0.300271

ft
ft
ft
ft
ft
ft
hp

Result of Calculation :Pump Capacity


Pump Head
Pump HP
Balance tank V.
Filter Area
Heater Capacity
Cooling Capacity

=
=
=
=
=
=
=

25.1257
85.116
0.300271
#REF!
0.163048
4.68125
7.533942

m3/hr
Ft
HP
m3
m2
Kw
TR

with

at 15 gpm / ft2
1287.692

CFM

Pool Design sheet Rev-0 (24-11-2010)


y Eng.Mahmoud Selim

Take just no. Of inlet for your calculation

Take just no. Of outlet for your calculation

sideration that

22deg F (50 C)

rface area

5 Cfm of air & 59.97 Btu/min to reject the heat.

Pumps

Swimming Pool Calculation


Enter Your Numbers In GreenCells Only:
Surface Area of Swimming Pool
Pool average depth
=

29
0.8

Pool Volume
=
23.2
NO. Water Inlets
=
1.16
So Get the No. Of inlets
=
1
Enter No. Of Turn Over Period
1
Get Swimming Pool Pump Capacity
=
=
No. Of pump will used
=
2
Get pump flow rate
= 0.193333
Balance tank volume

m
m

Swimming Pool Design sheet Rev-0


prepared by Eng.Mahmoud Selim

m3
inlets
time / day
Pool Volume / ( turn over period * 60 )
0.386667 m3/min
pumps
m3/min

= 40 L/m2 X Pool Surface area + 10 min X pump flow rate + 0.01 X pool surface ar
= 3.383333 m3
=
3.4
m3

Balance tank volume

To calculate pipe sizing


Supply pipe maximum velocity will be 2 m/s
No. Of inlet
=
1
Inlet
Pump flow rate
=
23.2
m3/hr
Each inlet give flow rate
= 23.2
Assuming that all inlet in sequence
Dia 1
= 64.06128
Taking it
Dia 2
= 90.59634
Taking it
Dia 3
= 110.9574
Taking it
Dia 4
= 128.1226
Taking it
Dia 5
= 143.2454
Taking it
Dia 6 = 156.9175
Taking it
Dia 7 = 169.4902
Taking it
Dia 8 = 181.1927
Taking it
Dia 9 = 192.1838
Taking it
Dia 10 = 202.5796
Taking it
Dia 11 = 212.4672
Taking it
Dia 12 = 221.9148
Taking it

m3/hr
64
91
111
128
143
157
169
181
192
203
212
222

65
100
100
150
150
150
150
150
150
150
150
150

mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.

Take just no. Of inlet for


for 4 inlet take to dia4

mm.
mm.
mm.

Take just no. Of outlet f


for 2 outlet take to dia2

Suction pipe maximum velocity will be 1.2 m/s


Pump flow rate
No. Of outlet

=
=

Each outlet give flow rate


Dia 1
= 57.89991
Dia 2
= 81.88284
Dia 3
= 100.2856

23.2
2

m3/hr
Outlet
=

11.6 m3/hr
Taking it
58
Taking it
82
Taking it
100

65
75
100

Dia 4

= 115.7998

Taking it

116

100

mm.

Over flow pipe Grille velocity will be 0.3m/s


the No. Of grille
=
7
Grilles
Pump flow rate
=
23.2
m3/hr
Assuming that all grilles in sequence
Dia 1
= 33.67958
Taking it
Dia 2
= 47.63012
Taking it
Dia 3
= 58.33475
Taking it
Dia 4
= 67.35917
Taking it
Dia 5
= 75.30984
Taking it
Dia 6
= 82.49779
Taking it
Dia 7
= 89.1078
Taking it
Dia 8
= 95.26025
Taking it
Dia 9
= 101.0387
Taking it
Dia 10 = 106.5042
Taking it

34
48
58
67
75
82
89
95
101
107

50
50
65
65
75
75
100
100
100
100

mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.

Take just no. Of grille fo


for 6 grille take to dia 6

Getting the filter area to be used


Pump flow rate
Filter area

=
23.2
= 0.662857

m3/hr
m2

at 15 gpm / ft2

Heating Calculation for swimming pools


Heater is required for heating purposes at winter seasons if required take inconsideration that
it's not particle to heat the pool without covers at coldest winter months
For calculation purposes the following conditions to be considered:The recommended Pool water temperature is around 28 C deg.
Outdoor air condition
: 46 / 30 deg C DB/WB summer condition, max 122deg F (50 C)
: 6/ 10 deg C BD/WB -winter condition
From SPATA p5, Sec3, the Average Daily heat loss (DH) in KWhr / m2 of pool surface area
correction value to
1.25
No. of hours per day available for heati
48
Heater required
6.34375

hours
Kw

cooling Calculation for swimming pools

To cool 1gpm and maintain at 28C(82.4F) will require the corresponding 51.25 Cfm of air & 59.97 Bt
Cooling capacity
5235.01
CFM
367543.7
Btu/hr
30.62864
TR

pump head calculation for swimming pools


heater pressure drop
=
filter pressure drop
=
chlorination auto pilot unit

10
30
5

ft
ft
ft

pipes and fittings losses


Static head heat pump

=
=

7
18.93

pump head
pump HP

= 85.116
= 0.610364

ft
ft
ft
hp

Result of Calculation :Pump Capacity


Pump Head
Pump HP
Balance tank V.
Filter Area
Heater Capacity
Cooling Capacity

=
=
=
=
=
=
=

51.07327
85.116
0.610364
3.4
0.662857
6.34375
30.62864

m3/hr
Ft
HP
m3
m2
Kw
TR

with

at 15 gpm / ft2
5235.01

CFM

Pool Design sheet Rev-0 (24-11-2010)


y Eng.Mahmoud Selim

e + 0.01 X pool surface area

Take just no. Of inlet for your calculation


for 4 inlet take to dia4

Take just no. Of outlet for your calculation


for 2 outlet take to dia2

Take just no. Of grille for your calculation


for 6 grille take to dia 6

sideration that

22deg F (50 C)

rface area

5 Cfm of air & 59.97 Btu/min to reject the heat.

Pumps

Swimming Pool Calculation


Enter Your Numbers In GreenCells Only:
Surface Area of Swimming Pool
Pool average depth
=

158
1.7

m2
m

Pool Volume
=
268.6
NO. Water Inlets
=
6.32
So Get the No. Of inlets
=
6
Enter No. Of Turn Over Period
6
Get Swimming Pool Pump Capacity
=
=
1

m3
inlets
time / day
Pool Volume / ( turn over period * 60 )
0.746111 m3/min
pumps

No. Of pump will used

Get pump flow rate

= 0.74611111

Balance tank volume

= 40 L/m2 X Pool Surface area


+ 10 min X pump flow rate + 0.01 X pool surface area

m3/min

= 15.3611111 m3
Balance tank volume

15.4

m3

To calculate pipe sizing


For Main Pool :
Supply pipe maximum velocity will be 2 m/s
No. Of inlet

Pump flow rate

= 44.76667

Inlet
m3/hr

Each inlet give flow rate


= 7.46111111
Assuming that all inlet in sequence
Dia 1
= 36.329
Taking it
Dia 2
= 51.37696
Taking it
Dia 3
= 62.92367
Taking it
Dia 4
= 72.65799
Taking it
Dia 5
= 81.2341
Taking it
Dia 6 = 88.9875
Taking it
Dia 7 = 96.11749
Taking it

m3/hr
36
51
63
73
81
89
96

50
50
65
75
75
100
100

mm.
mm.
mm.
mm.
mm.
mm.
mm.

Suction pipe maximum velocity will be 1.5 m/s


Pump flow rate
No. Of outlet

= 44.76667
m3/hr
=
3
Outlet

Each outlet give flow rate


Dia 1
= 65.6698
Dia 2
= 92.87112
Dia 3
= 113.7434
Dia 4
= 131.3396

= 14.9222222 m3/hr
Taking it
66
Taking it
93
Taking it
114
Taking it
131

65
100
100
150

mm.
mm.
mm.
mm.

Getting the filter area to be used


Pump flow rate

= 44.76667

m3/hr

Filter area

= 1.279048

m2

at 15 gpm / ft2

Heating Calculation for swimming pools


Heater is required for heating purposes at winter seasons if required take inconsi
t's not particle to heat the pool without covers at coldest winter months
For calculation purposes the following conditions to be considered:The recommended Pool water temperature is around 28 C deg.
condition
: 46 / 30 deg C DB/WB summer condition, max 122deg F (50 C)
: 6/ 10 deg C BD/WB -winter condition
TA p5, Sec3, the Average Daily heat loss (DH) in KWhr / m2 of pool surface area
correction value to be
No. of hours per day available for heating
Heater required

0.8
12
88.48

hours
Kw

cooling Calculation for swimming pools


To cool 1gpm and maintain at 28C(82.4F) will require the corresponding 51.25 Cfm of air & 59.97 Btu/min to r
Cooling capacity

10101.46
709211.5
59.10096

CFM
Btu/hr
TR

pump head calculation for swimming pools


heater pressure drop
=
filter pressure drop
=
chlorination auto pilot unit
pipes and fittings losses
=
Static head heat pump
=
pump head

10
30
5
6
3

ft
ft
ft
ft
ft

64.8

ft

pump HP

= 8.06325296

hp

Result of Calculation :Pump Capacity


Pump Head
Pump HP

=
=
=

197.1017
64.8
8.063253

m3/hr
Ft
HP

Balance tank V.

15.4

m3

Filter Area
Heater Capacity
Cooling Capacity

=
=
=

1.279048
88.48
59.10096

m2
Kw
TR

with

at 15 gpm / ft2
10101.46

Swimming Pool Calculation


Enter Your Numbers In GreenCells Only:
Surface Area of Swimming Pool
158
Pool average depth
=
1.7
Pool Volume
=
268.6
NO. Water Inlets
=
6.32
So Get the No. Of inlets
=
6
Enter No. Of Turn Over Period
6
Get Swimming Pool Pump Capacity
=
=
No. Of pump will used
=
1
Get pump flow rate
= 0.746111
Balance tank volume
Balance tank volume

Swimming Pool Design sheet Rev-0


prepared by Eng.Mahmoud Selim

m2
m
m3

inlets
time / day
Pool Volume / ( turn over period * 60 )
0.746111 m3/min
pumps
m3/min

= 40 L/m2 X Pool Surface area + 10 min X pump flow rate + 0.01 X pool surface a
= 15.36111 m3
=
15.4
m3

To calculate pipe sizing


Supply pipe maximum velocity will be 2 m/s
No. Of inlet
=
6
Inlet
Pump flow rate
= 44.76667 m3/hr
Each inlet give flow rate
= 7.461111
Assuming that all inlet in sequence
Dia 1
=
36.329
Taking it
Dia 2
= 51.37696
Taking it
Dia 3
= 62.92367
Taking it
Dia 4
= 72.65799
Taking it
Dia 5
= 81.2341
Taking it
Dia 6 =
88.9875
Taking it
Dia 7 = 96.11749
Taking it
Dia 8 = 102.7539
Taking it
Dia 9 =
108.987
Taking it
Dia 10 = 114.8824
Taking it
Dia 11 = 120.4896
Taking it
Dia 12 = 125.8473
Taking it

m3/hr
36
51
63
73
81
89
96
103
109
115
120
126

50
50
65
75
75
100
100
100
100
100
100
150

mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.

Take just no. Of inlet for y


for 4 inlet take to dia4

Suction pipe maximum velocity will be 1.5 m/s


Pump flow rate
= 44.76667 m3/hr
No. Of outlet
=
2 Outlet
Each outlet give flow rate
= 22.38333 m3/hr
Dia 1
= 80.42875
Taking it
80
Dia 2
= 113.7434
Taking it
114
Dia 3
= 139.3067
Taking it
139
Dia 4
= 160.8575
Taking it
161

75
100
150
150

mm.
mm.
mm.
mm.

Take just no. Of outlet for


for 2 outlet take to dia2

Over flow pipe Grille velocity will be 0.3m/s


the No. Of grille
=
7 Grilles

Pump flow rate


= 44.76667 m3/hr
Assuming that all grilles in sequence
Dia 1
= 46.78429
Taking it
Dia 2
= 66.16298
Taking it
Dia 3
= 81.03278
Taking it
Dia 4
= 93.56859
Taking it
Dia 5
= 104.6129
Taking it
Dia 6
= 114.5977
Taking it
Dia 7
= 123.7796
Taking it
Dia 8
= 132.326
Taking it
Dia 9
= 140.3529
Taking it
Dia 10 = 147.9449
Taking it
Getting the filter area to be used
Pump flow rate
= 44.76667 m3/hr
Filter area
= 1.279048 m2

47
66
81
94
105
115
124
132
140
148

50
65
75
100
100
100
100
150
150
150

mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.
mm.

Take just no. Of grille for


for 6 grille take to dia 6

at 15 gpm / ft2

Heating Calculation for swimming pools


Heater is required for heating purposes at winter seasons if required take inconsideration that
it's not particle to heat the pool without covers at coldest winter months
For calculation purposes the following conditions to be considered:The recommended Pool water temperature is around 28 C deg.
Outdoor air condition
: 46 / 30 deg C DB/WB summer condition, max 122deg F (50 C)
: 6/ 10 deg C BD/WB -winter condition
From SPATA p5, Sec3, the Average Daily heat loss (DH) in KWhr / m2 of pool surface area
correction value to be used
No. of hours per day available for heating
Heater required

0.8
24 hours
44.24 Kw

cooling Calculation for swimming pools


To cool 1gpm and maintain at 28C(82.4F) will require the corresponding 51.25 Cfm of air & 59.97 Btu/min to reject
Cooling capacity
10101.46 CFM
709211.5 Btu/hr
59.10096 TR
pump head calculation for swimming pools
heater pressure drop
=
10
filter pressure drop
=
30
chlorination auto pilot unit
5
pipes and fittings losses
=
60
Static head heat pump
=
7
pump head
pump HP
Result of Calculation :-

ft
ft
ft
ft
ft

=
134.4 ft
= 16.72378 hp

Pump Capacity
Pump Head
Pump HP
Balance tank V.
Filter Area
Heater Capacity
Cooling Capacity

=
=
=
=
=
=
=

197.1017
134.4
16.72378
15.4
1.279048
44.24
59.10096

m3/hr
Ft
HP
m3
m2
Kw
TR

with

at 15 gpm / f
10101.46 CFM

Pool Design sheet Rev-0 (24-11-2010)


y Eng.Mahmoud Selim

e + 0.01 X pool surface area

Take just no. Of inlet for your calculation


for 4 inlet take to dia4

Take just no. Of outlet for your calculation


for 2 outlet take to dia2

Take just no. Of grille for your calculation


for 6 grille take to dia 6

& 59.97 Btu/min to reject the heat.