You are on page 1of 20

ETAP

Project:

12.6.0H

Location:
Contract:

Date:

05-25-2016

SN:

Engineer:
Filename:

Page:

Study Case: LF
Brown Book Load Flow Analysis

Revision:

Base

Config.:

Normal

Electrical Transient Analyzer Program


Load Flow Analysis
Loading Category (1):

Design

Generation Category (1):

Design

Load Diversity Factor:

Number of Buses:

Number of Branches:

None

Swing

V-Control

Load

Total

42

45

XFMR2

XFMR3

Reactor

Line/Cable

Impedance

Tie PD

Total

16

25

44

Method of Solution:

Adaptive Newton-Raphson Method

Maximum No. of Iteration:

99

Precision of Solution:

0.0001000

System Frequency:

60.00 Hz

Unit System:

English

Project Filename:

Brown Book Load Flow Analysis

Output Filename:

C:\ETAP 1260\Brown Book Load Flow Analysis\Load Flow Analysis.lfr

ETAP

Project:

12.6.0H

Location:
Contract:

Date:

05-25-2016

SN:

Engineer:
Filename:

Page:

Study Case: LF
Brown Book Load Flow Analysis

Adjustments
Apply
Tolerance

Individual

Adjustments

/Global

Transformer Impedance:

Yes

Individual

Reactor Impedance:

Yes

Individual

Overload Heater Resistance:

No

Transmission Line Length:

No

Cable Length:

No

Apply
Temperature Correction

Percent

Individual

Adjustments

/Global

Transmission Line Resistance:

Yes

Individual

Cable Resistance:

Yes

Individual

Degree C

Revision:

Base

Config.:

Normal

ETAP

Project:

12.6.0H

Location:
Contract:

Date:

05-25-2016

SN:

Engineer:
Filename:

Page:

Study Case: LF
Brown Book Load Flow Analysis

Revision:

Base

Config.:

Normal

Bus Input Data


Load
Bus
ID

Initial Voltage
kV

Sub-sys

% Mag.

Ang.

01:69-1

69.000

100.0

0.0

02:69-2

69.000

100.0

0.0

03:MILL-1

13.800

100.0

0.0

04:MILL-2

13.800

100.0

0.0

05:FDR F

13.800

100.0

0.0

06:FDR H

13.800

100.0

0.0

07:FDR 70/71

13.800

100.0

0.0

08:FDR L

13.800

100.0

0.0

09:FDR E

13.800

100.0

0.0

10:EMERG

13.800

100.0

0.0

11:T4 SEC

2.400

100.0

0.0

12:T5 PRI

13.800

100.0

0.0

13:T6 PRI

13.800

100.0

0.0

15:FDR I

13.800

100.0

0.0

16:T9 PRI

13.800

100.0

0.0

17:T5 SEC

0.480

100.0

18:T6 SEC

0.480

100.0

19:T7 SEC

2.400

20:T8 SEC

2.400

21:T9 SEC

0.480

22:T5 MCC

0.480

23:T6 MCC

0.480

24:FDR M

13.800

25:T10 PRI
26:FDR G

Constant kVA
MW

Mvar

6.361

0.000

0.353

0.200

0.0

0.830

0.521

0.0

0.831

0.521

100.0

0.0

2.650

1.502

100.0

0.0

2.120

1.202

100.0

0.0

0.421

0.283

100.0

0.0

0.084

0.057

100.0

0.0

0.084

0.057

100.0

0.0

13.800

100.0

0.0

13.800

100.0

0.0

27:T12 PRI

13.800

100.0

0.0

28:T10 SEC

0.480

100.0

0.0

0.578

0.351

29:T11 SEC

0.480

100.0

0.0

0.703

0.426

0.563

0.349

30:T12 SEC

0.480

100.0

0.0

31:FDR P

13.800

100.0

0.0

32:FDR Q

13.800

100.0

0.0

33:T10 MCC

0.480

100.0

0.0

0.168

0.113

34:T11 MCC

0.480

100.0

0.0

0.062

0.042

Constant Z
MW

Constant I

Mvar

0.000

-2.000

0.530

0.300

MW

Mvar

Generic
MW

Mvar

ETAP

Project:

12.6.0H

Location:
Contract:

Date:

05-25-2016

SN:

Engineer:
Filename:

Page:

Study Case: LF
Brown Book Load Flow Analysis

Revision:

Base

Config.:

Normal

Load
Bus
ID

Initial Voltage
% Mag.

Ang.

35:T12MCC

0.480

100.0

0.0

0.168

0.113

36:T13 SEC

2.400

100.0

0.0

1.767

1.001

37:T17 SEC

0.480

100.0

0.0

0.663

0.394

38:480 TIE

0.480

100.0

0.0

39:T3 SEC

4.160

100.0

0.0

1.237

0.701

41:LGTS

0.480

100.0

0.0

0.150

0.049

49:RECT

0.480

100.0

0.0

0.963

0.520

50:GEN1

13.800

100.0

0.0
0.478

0.307

21.234

8.708

51:AUX

kV

Sub-sys

Constant kVA

0.480

100.0

0.0

100:UTIL-69

69.000

100.0

0.0

Bus1

13.800

100.0

0.0

NODE2

13.800

100.0

0.0

Total Number of Buses: 45

Generation Bus
ID

kV

MW

Constant Z

Mvar

MW

Type

Sub-sys

Mvar

0.530

Voltage

Constant I
MW

-1.700

Generation
MW

Mvar

0.000

MW

0.000

Mvar Limits

% Mag.

Angle

04:MILL-2

13.800

Voltage Control

100.0

0.0

8.000

8.000

-2.000

50:GEN1

13.800

Voltage Control

100.0

0.0

11.000

8.000

-2.000

100:UTIL-69

69.000

Swing

100.0

0.0
19.000

Mvar

Generic

0.000

% PF

Max

Min

0.000

Mvar

0.000

ETAP

Project:

12.6.0H

Location:
Contract:

Date:

05-25-2016

SN:

Engineer:
Filename:

Page:

Study Case: LF
Brown Book Load Flow Analysis

Revision:

Base

Config.:

Normal

Line/Cable Input Data


Ohms or Siemens/1000 ft per Conductor (Cable) or per Phase (Line)
Line/Cable
ID

Length
Library

T (C)

% Tol.

#/Phase

69NCUS1

250

10000.0

0.0

75

0.059134

0.087000

Cable2

69NCUS1

250

10000.0

0.0

75

0.059134

0.087000

Cable3

15NCUS1

500

2000.0

0.0

75

0.028400

0.042100

Cable4

15NCUN3

250

325.0

0.0

75

0.054799

0.036728

Cable5

15NCUN3

250

510.0

0.0

75

0.054799

0.036728

Cable6

15NCUN3

250

340.0

0.0

75

0.054799

0.036728

Cable7

15NCUN3

250

485.0

0.0

75

0.054799

0.036728

Cable8

15NCUN3

500

510.0

0.0

75

0.029100

0.033680

Cable9

15NCUN3

250

1187.0

0.0

75

0.054799

0.036728

Cable10

15NCUN3

250

619.0

0.0

75

0.054799

0.036728

Cable11

0.6MCUN3

250

20.0

0.0

75

0.055200

0.037900

Cable13

15NCUN3

250

980.0

0.0

75

0.054799

0.036728

Cable14

15NCUN3

250

471.0

0.0

75

0.054799

0.036728

Cable15

15NCUN3

250

680.0

0.0

75

0.054799

0.036728

Cable16

0.6MCUN3

250

20.0

0.0

75

0.055200

0.037900

Cable17

0.6MCUN3

350

66.0

0.0

75

0.037800

0.037300

Cable18

15NCUN3

250

650.0

0.0

75

0.054799

0.036728

Cable19

15NCUN3

250

475.0

0.0

75

0.054799

0.036728

Cable20

15NCUN3

250

200.0

0.0

75

0.054799

0.036728

Cable21

0.6MCUN3

250

20.0

0.0

75

0.055200

0.037900

Cable23

0.6MCUN3

250

20.0

0.0

75

0.055200

0.037900

Cable25

15NCUN3

250

165.0

0.0

75

0.054799

0.036728

Cable26

15NCUN3

250

1833.0

0.0

75

0.054799

0.036728

Cable29

0.6MCUN3

250

20.0

0.0

75

0.055200

0.037900

Cable30

0.6NCUN1

14

50.0

0.0

75

3.100000

0.058000

Line / Cable resistances are listed at the specified temperatures.

Size

Adj. (ft)

Cable1

ETAP

Project:

12.6.0H

Location:
Contract:

Page:

Date:

05-25-2016

SN:

Engineer:

Study Case: LF

Filename:

Brown Book Load Flow Analysis

Revision:

Base

Config.:

Normal

2-Winding Transformer Input Data

Transformer
ID

Rating
Phase

MVA

Z Variation
% Z1

% Tap Setting
Prim.

Sec.

Adjusted

Phase Shift

Prim. kV

Sec. kV

X1/R1

+ 5%

- 5%

% Tol.

%Z

Type

T-1

3-Phase

15.000

69.000

13.800

8.00

17.00

8.0000

Dyn

Angle
0.000

T-2

3-Phase

15.000

69.000

13.800

8.00

17.00

8.0000

Dyn

0.000

T-3

3-Phase

1.725

13.800

4.160

6.00

8.00

6.0000

Dyn

0.000

T-4

3-Phase

1.500

13.800

2.400

5.50

6.50

5.5000

Dyn

0.000

T-5

3-Phase

1.500

13.800

0.480

6.75

6.50

6.7500

Dyn

0.000

T-6

3-Phase

1.500

13.800

0.480

5.75

6.50

5.7500

Dyn

0.000

T-7

3-Phase

3.750

13.800

2.400

5.50

12.00

5.5000

Dyn

0.000

T-8

3-Phase

3.750

13.800

2.400

5.50

12.00

5.5000

Dyn

0.000

T-9

3-Phase

0.750

13.800

0.480

5.75

5.00

5.7500

Dd

0.000

T-10

3-Phase

1.500

13.800

0.480

5.75

6.50

5.7500

Dyn

0.000

T-11

3-Phase

1.500

13.800

0.480

5.75

6.50

5.7500

Dyn

0.000

T-12

3-Phase

1.500

13.800

0.480

5.75

6.50

5.7500

Dyn

0.000

T-13

3-Phase

2.500

13.800

2.400

5.75

10.00

5.7500

Dyn

0.000

T-14

3-Phase

1.000

13.800

0.480

5.75

5.50

5.7500

Dyn

0.000

T-17

3-Phase

1.250

13.800

0.480

4.50

6.00

4.5000

Dyn

0.000

3-Phase

1.500

13.800

0.480

5.75

5.91

5.7500

Dyn

0.000

T-18

ETAP

Project:

12.6.0H

Location:
Contract:

Date:

05-25-2016

SN:

Engineer:
Filename:

Page:

Study Case: LF
Brown Book Load Flow Analysis

Revision:

Base

Config.:

Normal

Branch Connections
CKT/Branch

Connected Bus ID

ID

Type

From Bus

% Impedance, Pos. Seq., 100 MVA Base


To Bus

R
3.13

53.24

53.33

T-1

2W XFMR

01:69-1

03:MILL-1

T-2

2W XFMR

02:69-2

04:MILL-2

3.13

53.24

53.33

T-3

2W XFMR

05:FDR F

39:T3 SEC

43.14

345.14

347.83

T-4

2W XFMR

06:FDR H

11:T4 SEC

55.75

362.40

366.67

T-5

2W XFMR

12:T5 PRI

17:T5 SEC

68.43

444.77

450.00

T-6

2W XFMR

13:T6 PRI

18:T6 SEC

58.29

378.88

383.33

T-7

2W XFMR

06:FDR H

19:T7 SEC

12.18

146.16

146.67

T-8

2W XFMR

15:FDR I

20:T8 SEC

12.18

146.16

146.67

T-9

2W XFMR

16:T9 PRI

21:T9 SEC

150.36

751.78

766.67

T-10

2W XFMR

25:T10 PRI

28:T10 SEC

58.29

378.88

383.33

T-11

2W XFMR

26:FDR G

29:T11 SEC

58.29

378.88

383.33

T-12

2W XFMR

27:T12 PRI

30:T12 SEC

58.29

378.88

383.33

T-13

2W XFMR

31:FDR P

36:T13 SEC

22.89

228.86

230.00

T-14

2W XFMR

32:FDR Q

37:T17 SEC

102.86

565.73

575.00

T-17

2W XFMR

05:FDR F

49:RECT

59.18

355.10

360.00

T-18

2W XFMR

50:GEN1

51:AUX

63.95

377.96

383.33

Cable1

Cable

100:UTIL-69

01:69-1

1.24

1.83

2.21

Cable2

Cable

100:UTIL-69

02:69-2

1.24

1.83

2.21

Cable3

Cable

50:GEN1

03:MILL-1

1.49

2.21

2.67

Cable4

Cable

03:MILL-1

05:FDR F

0.94

0.63

1.13

Cable5

Cable

04:MILL-2

24:FDR M

1.47

0.98

1.77

Cable6

Cable

Bus1

31:FDR P

0.98

0.66

1.18

Cable7

Cable

24:FDR M

32:FDR Q

1.40

0.94

1.68

Cable8

Cable

NODE2

08:FDR L

0.78

0.90

1.19

Cable9

Cable

07:FDR 70/71

16:T9 PRI

3.42

2.29

4.11

Cable10

Cable

07:FDR 70/71

27:T12 PRI

1.78

1.19

2.14

Cable11

Cable

30:T12 SEC

35:T12MCC

47.92

32.90

58.12

Cable13

Cable

04:MILL-2

15:FDR I

2.82

1.89

3.39

Cable14

Cable

03:MILL-1

06:FDR H

1.36

0.91

1.63

Cable15

Cable

03:MILL-1

26:FDR G

1.96

1.31

2.36

Cable16

Cable

29:T11 SEC

34:T11 MCC

47.92

32.90

58.12

Cable17

Cable

29:T11 SEC

38:480 TIE

54.14

53.42

76.06

Cable18

Cable

03:MILL-1

09:FDR E

1.87

1.25

2.25

Cable19

Cable

27:T12 PRI

10:EMERG

1.37

0.92

1.65

Cable20

Cable

10:EMERG

13:T6 PRI

0.58

0.39

0.69

Cable21

Cable

18:T6 SEC

23:T6 MCC

47.92

32.90

58.12

Cable23

Cable

17:T5 SEC

22:T5 MCC

47.92

32.90

58.12

ETAP

Project:

12.6.0H

Location:
Contract:

Date:

05-25-2016

SN:

Engineer:
Filename:

Page:

Study Case: LF
Brown Book Load Flow Analysis

CKT/Branch

Connected Bus ID

ID

Type

From Bus

Cable

09:FDR E

12:T5 PRI

Cable26

Cable

09:FDR E

25:T10 PRI

Cable29

Cable

28:T10 SEC

33:T10 MCC

Cable30

Cable

28:T10 SEC

41:LGTS

CB20

Tie Breakr

24:FDR M

Bus1

CB25

Tie Breakr

04:MILL-2

NODE2

CB26

Tie Breakr

04:MILL-2

07:FDR 70/71

Base

Config.:

Normal

% Impedance, Pos. Seq., 100 MVA Base


To Bus

Cable25

Revision:

R
0.47

X
0.32

Z
0.57

5.27

3.54

6.35

47.92

32.90

58.12

6727.43

125.87

6728.61

ETAP

Project:

12.6.0H

Location:
Contract:

Date:

05-25-2016

SN:

Engineer:
Filename:

Page:

Study Case: LF
Brown Book Load Flow Analysis

Revision:

Base

Config.:

Normal

LOAD FLOW REPORT

Bus
ID
01:69-1

02:69-2

Voltage
kV

% Mag.

69.000

100.020

69.000

99.938

Generation

Ang.
0.0

-0.1

MW

Load

Mvar
0

MW
0

Load Flow
Mvar

ID
0

100:UTIL-69

* 04:MILL-2

13.800

13.800

99.749

100.000

0.9

-1.8

8.000

3.110

0.000

-2.000

06:FDR H

07:FDR 70/71

13.800

13.800

13.800

99.720

99.691

100.000

0.9

0.9

-1.8

08:FDR L

13.800

99.950

-1.8

6.361

0.000

09:FDR E

13.800

99.699

0.9

10:EMERG

13.800

99.939

-1.8

11:T4 SEC

2.400

98.751

0.2

12:T5 PRI

13.800

99.693

0.9

13:T6 PRI

15:FDR I

13.800

13.800

99.931

99.895

-1.8

-1.8

Amp

%PF

2.643

-0.685

22.8

-96.8

-2.643

0.685

22.8

-96.8

100:UTIL-69

-5.542

0.361

46.5

-99.8

5.542

-0.361

46.5

-99.8

50:GEN1

-10.501

-4.243

475.0

92.7

05:FDR F

2.217

1.341

108.7

85.6

06:FDR H

3.018

1.853

148.5

85.2

26:FDR G

0.770

0.500

38.5

83.9

09:FDR E

1.851

1.193

92.3

84.0

01:69-1

2.645

-0.645

114.2

-97.2

24:FDR M

2.448

1.532

120.8

84.8

15:FDR I

2.636

1.628

129.6

85.1

02:69-2

-5.532

0.525

232.5

-99.6

NODE2

6.364

0.004

266.3

100.0

07:FDR 70/71
05:FDR F

XFMR
Mvar

03:MILL-1

04:MILL-2
03:MILL-1

MW

2.084

1.421

105.5

82.6

03:MILL-1

-2.217

-1.341

108.7

85.6

39:T3 SEC

1.246

0.776

61.6

84.9

49:RECT

0.971

0.565

47.1

86.4

03:MILL-1

-3.016

-1.852

148.5

85.2

11:T4 SEC

0.354

0.206

17.2

86.4

19:T7 SEC

2.662

1.646

131.3

85.1

16:T9 PRI

0.425

0.304

21.9

81.4

27:T12 PRI

1.659

1.118

83.7

82.9

04:MILL-2

-2.084

-1.421

105.5

82.6

NODE2

-6.361

0.000

266.3

100.0

03:MILL-1

-1.850

-1.192

92.3

84.0

12:T5 PRI

0.923

0.634

47.0

82.4

25:T10 PRI

0.927

0.559

45.4

85.6

27:T12 PRI

-0.922

-0.625

46.6

82.8

13:T6 PRI

0.922

0.625

46.6

82.8

0.353

0.200

06:FDR H

-0.353

-0.200

98.8

87.0

09:FDR E

-0.923

-0.634

47.0

82.4

17:T5 SEC

0.923

0.634

47.0

82.4

10:EMERG

-0.922

-0.625

46.6

82.8

18:T6 SEC

0.922

0.625

46.6

82.8

04:MILL-2

-2.633

-1.626

129.6

85.1

%Tap

ETAP

Project:

12.6.0H

Location:
Contract:

Study Case: LF
Brown Book Load Flow Analysis

Bus
ID

Voltage
kV

% Mag.

Generation

Ang.

MW

Load

Mvar

MW

Mvar

ID

13.800

99.979

-1.8

07:FDR 70/71
21:T9 SEC

17:T5 SEC

0.480

96.303

-1.3

0.830

0.521

22:T5 MCC

0.480

97.073

-3.6

19:T7 SEC

2.400

97.023

-1.3

20:T8 SEC

2.400

97.263

-3.9

21:T9 SEC

0.480

97.096

-3.4

22:T5 MCC

0.480

96.241

-1.3

23:T6 MCC

0.480

97.013

-3.6

24:FDR M

13.800

99.949

-1.8

0.831

0.521

0.084

0.057

126.9

82.7

-0.578

1350.5

84.5

0.084

0.057

125.9

82.7

13:T6 PRI

-0.915

-0.578

1341.1

84.5

23:T6 MCC

2.621

1.486

15:FDR I

-2.621

-1.486

745.3

87.0

0.421

0.283

16:T9 PRI

-0.421

-0.283

628.4

83.0

0.084

0.057

17:T5 SEC

-0.084

-0.057

126.9

82.7

0.084

0.057

18:T6 SEC

-0.084

-0.057

125.9

82.7

04:MILL-2

-2.447

-1.531

120.8

84.8

32:FDR Q

0.670

0.430

33.3

84.1

Bus1

1.777

1.101

87.5

85.0

-0.926

-0.558

45.4

85.6

09:FDR E
28:T10 SEC

0.926

0.558

45.4

85.6

03:MILL-1

-0.770

-0.500

38.5

83.9

29:T11 SEC

0.770

0.500

38.5

83.9

-1.658

-1.117

83.7

82.9

0.923

0.625

46.6

82.8

30:T12 SEC

0.736

0.492

37.0

83.1

33:T10 MCC

0.168

0.113

251.3

83.0

41:LGTS

0.173

0.049

223.3

96.2

-0.919

-0.514

1305.6

87.3

34:T11 MCC

0.062

0.042

92.5

82.8

38:480 TIE

0.000

0.000

0.0

0.0

26:FDR G

-0.765

-0.468

1107.4

85.3

07:FDR 70/71
10:EMERG

0.578

0.351

25:T10 PRI

30:T12 SEC

31:FDR P

0.480

13.800

97.696

99.924

-3.2

-1.8

0.703

0.563

0.426

0.349

35:T12MCC

0.168

0.113

249.6

83.0

27:T12 PRI

-0.731

-0.462

1065.0

84.5

Bus1

-1.777

-1.101

87.5

85.0

1.777

1.101

87.5

85.0

-0.670

-0.430

33.3

84.1

37:T17 SEC

0.670

0.430

33.3

84.1

36:T13 SEC
32:FDR Q

13.800

99.936

-1.8

81.4

0.9

-0.7

81.4

21.9

99.727

97.413

21.9

0.304

13.800

0.480

-0.304

0.425

26:FDR G

29:T11 SEC

-0.425

87.0

-1.0

85.1

97.018

%PF

129.6

755.3

0.480

Amp

1.626

-1.502

28:T10 SEC

Mvar

2.633

-2.650

0.9

-1.8

MW

XFMR

06:FDR H

99.630

99.957

Normal

1.502

13.800

13.800

Base

Config.:

2.650

25:T10 PRI

27:T12 PRI

Revision:

-0.914

12:T5 PRI
18:T6 SEC

05-25-2016

Load Flow

20:T8 SEC
16:T9 PRI

10

Date:
SN:

Engineer:
Filename:

Page:

24:FDR M

33:T10 MCC

0.480

96.897

-1.0

0.168

0.113

28:T10 SEC

-0.168

-0.113

251.3

83.0

34:T11 MCC

0.480

97.368

-0.7

0.062

0.042

29:T11 SEC

-0.062

-0.042

92.5

82.8

35:T12MCC

0.480

97.575

-3.2

0.168

0.113

30:T12 SEC

-0.168

-0.113

249.6

83.0

36:T13 SEC

2.400

97.070

-4.0

1.767

1.001

31:FDR P

-1.767

-1.001

503.3

87.0

37:T17 SEC

0.480

96.871

-3.7

0.663

0.394

32:FDR Q

-0.663

-0.394

957.6

86.0

0
0

%Tap

ETAP

Project:

12.6.0H

Location:
Contract:

Study Case: LF
Brown Book Load Flow Analysis

Bus
ID
38:480 TIE

Voltage
kV

% Mag.

Generation

Ang.

MW

Load

Mvar

MW

Normal

Mvar

ID

MW

1.237

0.701

05:FDR F

-1.237

-0.701

204.3

87.0

0.049

28:T10 SEC

-0.150

-0.049

223.3

95.1

05:FDR F

-0.963

-0.520

1354.6

88.0

03:MILL-1

10.520

4.271

475.0

92.7

51:AUX

0.480

0.320

24.1

83.2

50:GEN1

-0.478

-0.307

693.7

84.1

01:69-1

-2.642

0.686

22.8

-96.8

02:69-2

5.546

-0.355

46.5

-99.8

31:FDR P

1.777

1.101

87.5

85.0

24:FDR M

-1.777

-1.101

87.5

85.0

08:FDR L

6.364

0.004

266.3

100.0

04:MILL-2

-6.364

-0.004

266.3

100.0

-1.5

85.006

1.1

0.150

49:RECT

0.480

97.182

-1.0

0.963

0.520

* 50:GEN1

13.800

100.000

0.9

11.000

4.591

0.480

98.498

0.0

69.000

100.000

0.0

2.904

0.331

13.800

99.949

-1.8

13.800

100.000

-1.8

* Indicates a voltage regulated bus (voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA

0.478

0.307

0.0

%PF

96.577

0.000

Amp

0.000

Mvar

29:T11 SEC

XFMR

-0.7

4.160

NODE2

Base

Config.:

97.413

0.480

Bus1

Revision:

0.480

39:T3 SEC

* 100:UTIL-69

05-25-2016

Load Flow

41:LGTS

51:AUX

11

Date:
SN:

Engineer:
Filename:

Page:

0.0

%Tap

ETAP

Project:

12.6.0H

Location:
Contract:

12

Date:

05-25-2016

SN:

Engineer:
Filename:

Page:

Study Case: LF
Brown Book Load Flow Analysis

Revision:

Base

Config.:

Normal

Bus Loading Summary Report

Directly Connected Load


Bus
ID

Constant kVA
kV

Rated Amp

MW

Constant Z

Mvar

MW

Total Bus Load

Constant I

Mvar

MW

Generic

Mvar

MW

Mvar

01:69-1

69.000

02:69-2

69.000

03:MILL-1

13.800

04:MILL-2

13.800

-2.000

05:FDR F

13.800

06:FDR H

13.800

07:FDR 70/71

13.800

08:FDR L

13.800

6.361

09:FDR E

13.800

10:EMERG

13.800

11:T4 SEC

2.400

0.353

0.200

12:T5 PRI

13.800

13:T6 PRI

13.800

15:FDR I

13.800

16:T9 PRI

13.800

17:T5 SEC

0.480

0.830

18:T6 SEC

0.480

0.831

19:T7 SEC

2.400

2.650

20:T8 SEC

2.400

21:T9 SEC
22:T5 MCC

MVA

% PF

Amp

2.730

96.8

5.554

99.8

46.5

11.582

90.7

485.8

14.465

93.6

605.2

2.591

85.6

108.7

3.539

85.2

148.5

2.523

82.6

105.5

6.361

100.0

266.3

2.201

84.0

92.3

1.114

82.8

46.6

0.406

87.0

98.8

1.119

82.4

47.0

1.114

82.8

46.6

3.095

85.1

129.6

0.522

81.4

21.9

0.521

1.081

84.5

1350.5

0.521

1.082

84.5

1341.1

1.502

3.046

87.0

755.3

2.120

1.202

0.501

0.284

3.013

87.0

745.3

0.480

0.421

0.283

0.507

83.0

628.4

0.480

0.084

0.057

0.102

82.7

126.9

23:T6 MCC

0.480

0.084

0.057

0.102

82.7

125.9

24:FDR M

13.800

2.887

84.8

120.8

25:T10 PRI

13.800

1.081

85.6

45.4

26:FDR G

13.800

0.918

83.9

38.5

27:T12 PRI

13.800

2.000

82.9

83.7

28:T10 SEC

0.480

0.578

0.351

1.053

87.3

1305.6

29:T11 SEC

0.480

0.703

0.426

0.897

85.3

1107.4

30:T12 SEC

22.8

0.480

0.563

0.349

0.865

84.5

1065.0

31:FDR P

13.800

2.091

85.0

87.5

32:FDR Q

13.800

0.796

84.1

33.3

33:T10 MCC

0.480

0.168

0.113

0.202

83.0

251.3

34:T11 MCC

0.480

0.062

0.042

0.075

82.8

92.5

35:T12MCC

0.480

0.168

0.113

0.202

83.0

249.6

36:T13 SEC

2.400

1.767

1.001

2.031

87.0

503.3

37:T17 SEC

0.480

0.663

0.394

0.771

86.0

957.6

Percent
Loading

ETAP

Project:

12.6.0H

Location:
Contract:

13

Date:

05-25-2016

SN:

Engineer:
Filename:

Page:

Study Case: LF
Brown Book Load Flow Analysis

Revision:

Base

Config.:

Normal

Directly Connected Load


Bus
ID

Constant kVA
kV

Rated Amp

MW

Constant Z

Mvar

MW

Total Bus Load

Constant I

Mvar

MW

Generic

Mvar

MW

Mvar

MVA

% PF

Amp

38:480 TIE

0.480

0.0

0.0

39:T3 SEC

4.160

1.237

0.701

1.422

87.0

204.3

41:LGTS

0.480

0.150

0.049

0.158

95.1

223.3

49:RECT

0.480

0.963

0.520

1.094

88.0

1354.6

50:GEN1

13.800

11.920

92.3

498.7

51:AUX

0.480

0.478

0.307

0.568

84.1

693.7

100:UTIL-69

69.000

5.588

99.2

46.8

Bus1

13.800

2.091

85.0

87.5

NODE2

13.800

6.364

100.0

266.3

* Indicates operating load of a bus exceeds the bus critical limit ( 100.0% of the Continuous Ampere rating).
# Indicates operating load of a bus exceeds the bus marginal limit ( 95.0% of the Continuous Ampere rating).

Percent
Loading

ETAP

Project:

12.6.0H

Location:
Contract:

14

Date:

05-25-2016

SN:

Engineer:
Filename:

Page:

Study Case: LF
Brown Book Load Flow Analysis

Revision:

Base

Config.:

Normal

Branch Loading Summary Report

Transformer
CKT / Branch
ID

Cable & Reactor


Type

Ampacity
(Amp)

Loading
Amp

Cable2

Cable

436.32

46.50

10.66

Cable3

Cable

1029.43

475.01

46.14

Cable4

Cable

277.00

108.70

39.24

Cable5

Cable

277.00

120.83

43.62

Cable6

Cable

277.00

87.53

31.60

Cable7

Cable

277.00

33.31

12.02

Cable8

Cable

400.78

266.26

66.43

Cable9

Cable

277.00

21.86

7.89

Cable10

Cable

277.00

83.69

30.21

Cable11

Cable

250.58

249.58

99.60

Cable13

Cable

277.00

129.61

46.79

Cable14

Cable

277.00

148.53

53.62

Cable15

Cable

277.00

38.52

13.91

Cable16

Cable

250.58

92.51

36.92

Cable17

Cable

626.00

0.00

0.00

Cable18

Cable

277.00

92.35

33.34

Cable19

Cable

277.00

46.65

16.84

Cable20

Cable

277.00

46.65

16.84

Cable21

Cable

250.58

125.86

50.23

Cable23

Cable

250.58

126.87

50.63

Cable25

Cable

277.00

46.97

16.96

Cable26

Cable

277.00

45.41

16.39

* Cable29

Cable

250.58

251.33

100.30

Capability
(MVA)

Loading (input)
MVA

Loading (output)

MVA

T-1

Transformer

15.000

2.730

18.2

2.722

18.1

T-2

Transformer

15.000

5.557

37.0

5.554

37.0

T-3

Transformer

1.725

1.468

85.1

1.422

82.4

T-4

Transformer

1.500

0.410

27.3

0.406

27.0

T-5

Transformer

1.500

1.119

74.6

1.081

72.1

T-6

Transformer

1.500

1.114

74.3

1.082

72.2

T-7

Transformer

3750.000

3.130

0.1

3.046

0.1

T-8

Transformer

3750.000

3.095

0.1

3.013

0.1

T-9

Transformer

0.750

0.522

69.6

0.507

67.6

T-10

Transformer

1.500

1.081

72.1

1.053

70.2

ETAP

Project:

12.6.0H

Location:
Contract:

15

Date:

05-25-2016

SN:

Engineer:
Filename:

Page:

Study Case: LF
Brown Book Load Flow Analysis

Revision:

Base

Config.:

Normal

Transformer
CKT / Branch
ID

Cable & Reactor


Type

Ampacity
(Amp)

Loading
Amp

Capability
(MVA)

Loading (input)
MVA

T-11

Transformer

1500.000

0.918

T-12

Transformer

1500.000

T-13

Transformer

2.500

T-14

Transformer

T-17

Transformer

T-18

Transformer

* Indicates a branch with operating load exceeding the branch capability.

Loading (output)

MVA

0.1

0.897

0.1

0.885

0.1

0.865

0.1

2.091

83.6

2.031

81.2

1.000

0.796

79.6

0.771

77.1

1.250

1.123

89.8

1.094

87.6

1.500

0.577

38.5

0.568

37.9

ETAP

Project:

12.6.0H

Location:
Contract:

16

Date:

05-25-2016

SN:

Engineer:
Filename:

Page:

Study Case: LF
Brown Book Load Flow Analysis

Revision:

Base

Config.:

Normal

Branch Losses Summary Report

CKT / Branch
ID

From-To Bus Flow

To-From Bus Flow

MW

MW

kW

kvar

Vd
% Drop
in Vmag

From

To

-0.685

-2.642

0.686

0.9

1.4

100.0

100.0

0.02

T-1

-2.643

0.685

2.645

-0.645

2.3

39.7

100.0

99.7

0.27

Cable2

-5.542

0.361

5.546

-0.355

3.8

5.6

99.9

100.0

0.06

5.542

-0.361

-5.532

0.525

9.7

164.4

99.9

100.0

0.06

Cable3

-10.501

-4.243

10.520

4.271

19.2

28.5

99.7

100.0

0.25

Cable4

2.217

1.341

-2.217

-1.341

0.6

0.4

99.7

99.7

0.03

Cable14

3.018

1.853

-3.016

-1.852

1.7

1.1

99.7

99.7

0.06

T-2

Mvar

% Bus Voltage

2.643

Cable1

Mvar

Losses

Cable15

0.770

0.500

-0.770

-0.500

0.2

0.1

99.7

99.7

0.02

Cable18

1.851

1.193

-1.850

-1.192

0.9

0.6

99.7

99.7

0.05

Cable5

2.448

1.532

-2.447

-1.531

1.2

0.8

100.0

99.9

0.05

Cable13

2.636

1.628

-2.633

-1.626

2.7

1.8

100.0

99.9

0.11

T-3

1.246

0.776

-1.237

-0.701

9.4

74.8

99.7

96.6

3.14

T-17

0.971

0.565

-0.963

-0.520

7.5

45.0

99.7

97.2

2.54

T-4

0.354

0.206

-0.353

-0.200

0.9

6.1

99.7

98.8

0.94

T-7

2.662

1.646

-2.650

-1.502

12.0

144.1

99.7

97.0

2.67

Cable9

0.425

0.304

-0.425

-0.304

0.1

0.1

100.0

100.0

0.02

Cable10

1.659

1.118

-1.658

-1.117

0.7

0.5

100.0

100.0

0.04

Cable8

-6.361

0.000

6.364

0.004

3.2

3.7

100.0

100.0

0.05

Cable25

0.923

0.634

-0.923

-0.634

0.1

0.0

99.7

99.7

0.01

Cable26

0.927

0.559

-0.926

-0.558

0.6

0.4

99.7

99.6

0.07

Cable19

-0.922

-0.625

0.923

0.625

0.2

0.1

99.9

100.0

0.02

Cable20

0.922

0.625

-0.922

-0.625

0.1

0.0

99.9

99.9

0.01

T-5

0.923

0.634

-0.914

-0.578

8.6

56.1

99.7

96.3

3.39

T-6

0.922

0.625

-0.915

-0.578

7.2

47.1

99.9

97.1

2.86

T-8

2.633

1.626

-2.621

-1.486

11.7

140.3

99.9

97.3

2.63

T-9

0.425

0.304

-0.421

-0.283

4.1

20.5

100.0

97.1

2.88

Cable23

0.084

0.057

-0.084

-0.057

0.1

0.0

96.3

96.2

0.06

Cable21

0.084

0.057

-0.084

-0.057

0.1

0.0

97.1

97.0

0.06

Cable7

0.670

0.430

-0.670

-0.430

0.1

0.1

99.9

99.9

0.01

T-10

0.926

0.558

-0.919

-0.514

6.9

44.6

99.6

97.0

2.61

T-11

0.770

0.500

-0.765

-0.468

4.9

32.1

99.7

97.4

2.31

T-12

0.736

0.492

-0.731

-0.462

4.6

29.7

100.0

97.7

2.26

Cable29

0.168

0.113

-0.168

-0.113

0.2

0.1

97.0

96.9

0.12

Cable30

0.173

0.049

-0.150

-0.049

23.2

0.4

97.0

85.0

12.01

Cable16

0.062

0.042

-0.062

-0.042

0.0

0.0

97.4

97.4

0.04

ETAP

Project:

12.6.0H

Location:
Contract:

17

Date:

05-25-2016

SN:

Engineer:
Filename:

Page:

Study Case: LF
Brown Book Load Flow Analysis

CKT / Branch
ID
Cable17

From-To Bus Flow

To-From Bus Flow

MW

MW

0.000

Mvar

Mvar

0.000

0.000

0.000

Losses
kW

Revision:

Base

Config.:

Normal

% Bus Voltage
kvar

From
97.4

To
97.4

Vd
% Drop
in Vmag
0.00

Cable11

0.168

0.113

-0.168

-0.113

0.2

0.1

97.7

97.6

0.12

Cable6

-1.777

-1.101

1.777

1.101

0.4

0.3

99.9

99.9

0.02

T-13

1.777

1.101

-1.767

-1.001

10.0

100.2

99.9

97.1

2.85

T-14

0.670

0.430

-0.663

-0.394

6.5

35.9

99.9

96.9

3.06

T-18

0.480

0.320

-0.478

-0.307

2.1

12.6

100.0

98.5

1.50

169.0

1039.5

ETAP

Project:

12.6.0H

Location:
Contract:

18

Date:

05-25-2016

SN:

Engineer:
Filename:

Page:

Study Case: LF
Brown Book Load Flow Analysis

Revision:

Base

Config.:

Normal

Alert Summary Report


% Alert Settings
Critical

Marginal

Loading
Bus

100.0

95.0

Cable

100.0

95.0

Reactor

100.0

95.0

Line

100.0

95.0

Transformer

100.0

95.0

Panel

100.0

95.0

Protective Device

100.0

95.0

Generator

100.0

95.0

Inverter/Charger

100.0

95.0

OverVoltage

105.0

102.0

UnderVoltage

95.0

98.0

OverExcited (Q Max.)

100.0

95.0

UnderExcited (Q Min.)

100.0

Bus Voltage

Generator Excitation

Critical Report
Device ID

Type

Condition

41:LGTS

Bus

Under Voltage

Cable29

Cable

Overload

Rating/Limit
0.48
250.58

Unit
kV
Amp

Operating

% Operating

Phase Type

0.41

85.0

3-Phase

251.33

100.3

3-Phase

Marginal Report
Device ID

Type

Condition

Rating/Limit

Unit

Operating

% Operating

Phase Type

17:T5 SEC

Bus

Under Voltage

0.48

kV

0.46

96.3

3-Phase

18:T6 SEC

Bus

Under Voltage

0.48

kV

0.47

97.1

3-Phase

19:T7 SEC

Bus

Under Voltage

2.40

kV

2.33

97.0

3-Phase

20:T8 SEC

Bus

Under Voltage

2.40

kV

2.33

97.3

3-Phase

21:T9 SEC

Bus

Under Voltage

0.48

kV

0.47

97.1

3-Phase

22:T5 MCC

Bus

Under Voltage

0.48

kV

0.46

96.2

3-Phase

23:T6 MCC

Bus

Under Voltage

0.48

kV

0.47

97.0

3-Phase

28:T10 SEC

Bus

Under Voltage

0.48

kV

0.47

97.0

3-Phase

29:T11 SEC

Bus

Under Voltage

0.48

kV

0.47

97.4

3-Phase

30:T12 SEC

Bus

Under Voltage

0.48

kV

0.47

97.7

3-Phase

ETAP

Project:

12.6.0H

Location:
Contract:

19

Date:

05-25-2016

SN:

Engineer:
Filename:

Page:

Study Case: LF
Brown Book Load Flow Analysis

Revision:

Base

Config.:

Normal

Marginal Report
Device ID

Type

Condition

Rating/Limit

Unit

Operating

% Operating

Phase Type

33:T10 MCC

Bus

Under Voltage

0.48

kV

0.47

96.9

3-Phase

34:T11 MCC

Bus

Under Voltage

0.48

kV

0.47

97.4

3-Phase

35:T12MCC

Bus

Under Voltage

0.48

kV

0.47

97.6

3-Phase

36:T13 SEC

Bus

Under Voltage

2.40

kV

2.33

97.1

3-Phase

37:T17 SEC

Bus

Under Voltage

0.48

kV

0.46

96.9

3-Phase

38:480 TIE

Bus

Under Voltage

0.48

kV

0.47

97.4

3-Phase

39:T3 SEC

Bus

Under Voltage

4.16

kV

4.02

96.6

3-Phase

49:RECT

Bus

Under Voltage

0.48

kV

0.47

97.2

3-Phase

Cable11

Cable

Overload

249.58

99.6

3-Phase

250.58

Amp

ETAP

Project:

12.6.0H

Location:
Contract:

20

Date:

05-25-2016

SN:

Engineer:
Filename:

Page:

Study Case: LF
Brown Book Load Flow Analysis

Revision:

Base

Config.:

Normal

SUMMARY OF TOTAL GENERATION , LOADING & DEMAND

MW

Mvar

MVA

% PF

2.904

0.331

2.923

99.36 Lagging

Source (Non-Swing Buses):

19.000

7.701

20.501

92.68 Lagging

Total Demand:

21.904

8.032

23.331

93.89 Lagging

Total Motor Load:

21.234

8.708

22.950

92.52 Lagging

Total Static Load:

0.501

-1.716

1.788

28.05 Leading

Total Constant I Load:

0.000

0.000

0.000

Total Generic Load:

0.000

0.000

0.000

Apparent Losses:

0.169

1.040

System Mismatch:

0.000

0.000

Source (Swing Buses):

Number of Iterations: 3

You might also like